This document package includes fire suppression construction drawings and specifications for a parking garage project at a Department of Veterans Affairs medical center in Oklahoma City, Oklahoma. The drawings provide design details for the fire sprinkler and standpipe systems, including sprinkler head locations and pipe sizing. Specifications require the contractor to install a wet pipe sprinkler system, dry standpipe, double check backflow preventer, fire department connections, and air compressor. The contractor must submit hydraulic calculations and shop drawings certified by a professional engineer. Bids for the fire suppression work are due by July 22, 2022, with construction to commence on August 8, 2022. The estimated value of the contract is $250,000.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTE: NOT ALL SYMBOLS MAY BE USED ON THIS PROJECT
SEMI-RECESSED SPRINKLER HEAD
UPRIGHT SPRINKLER HEAD
FIRE LINEFL
CONCEALED SPRINKLER HEAD
PENDANT SPRINKLER HEAD
SIDEWALL SPRINKLER HEAD
FIRE DEPARTMENT CONNECTION (FDC)
FIRE DRAINDRAIN
POINT OF NEW CONNECTION
LIMIT OF DEMOLITION
NEW WORK KEYNOTE
DEMOLITION KEYNOTE
FIRE PROTECTION CONTRACTORFPC
TAMPER SWITCH
FLOW SWITCH
CHECK VALVE
GATE VALVE
EXTERIOR ALARM GONG (WATER ACTIVATED)
TEST AND DRAIN ASSEMBLY
BACKFLOW PREVENTER
T&D
TS
FS
ORDINARY HAZARD
GROUP 1 OCCUPANCY
DETAIL OR SECTION MARK
SHOWN ON DRAWING
DETAIL MODULE NUMBER
ORDINARY HAZARD
GROUP 2 OCCUPANCY
LIGHT HAZARD
THE FIRE PROTECTION DRAWING IS DESIGNED TO BE IN CONFORMANCE WITH NFPA
13. IT IS A PERFORMANCE BASED DRAWING INDICATING THE EXTENT OF FIRE
PROTECTION WORK FOR THE AREA THAT THIS DRAWING REPRESENTS. THIS
DRAWING IS “FOR INFORMATION ONLY”, AS A REFERENCE FOR THE FIRE
PROTECTION CONTRACTOR TO BASE THE DESIGN OF THE FIRE PROTECTION
SYSTEM ON. THE CONTRACTOR SHALL VERIFY THE EXACT CONDITIONS THAT THIS
DRAWING REPRESENTS, INCLUDING ANY PERCEIVED CONCEALED SPACES, AND THE
BUILDING TYPE AND CONSTRUCTION AS OUTLINED IN THE INTERNATIONAL BUILDING
CODE, PRIOR TO THE START OF WORK. REFER TO THE INTERNATIONAL BUILDING
CODE, NFPA 13, AND THE PROJECT SPECIFICATIONS FOR OTHER FIRE PROTECTION
REQUIREMENTS.
FLUSHING CONNECTION
FEED OR CROSS MAIN.
TYPICAL TEE WITH
CROSS MAIN PITCH
TOWARDS FEED MAIN.
NOTE: INSTALL FLUSHING
CONNECTION AT END OF
CROSS MAINS.
2" NIPPLE 4" LONG
WITH CAP.
MECHANICAL TEE
NEW PIPING
MECHANICAL TEE
SCREWED END
STEEL BEAM
RETAINING STRAP
C-CLAMP
THREADED HANGER ROD
ADJUSTABLE RING HANGER
NOTE:
HANGING DETAILS SHOWN ARE SUBJECT TO REQUIREMENTS OF SEISMIC DESIGN.
EXPANSION ANCHOR HILT QUIK
BOLT TZ OR APPROVED EQUAL.
EXPANSION ANCHOR SHALL BE
QUALIFIED FOR USE IN CRACKED
CONCRETE PER ACI 355.2
NEW CONCRETE SLAB / PRECAST ROOF
PLANK (REFER TO STRUCTURAL DRAWINGS
FOR ROOF / FLOOR CONSTRUCTION TYPE)
AUTO. SPRINKLER PIPE
SET SCREW
SURGE RESTRAINER
INSTALL INSULATION AFTER
CAULKING SLEEVE, SEAL
ANNULAR SPACE.
FIRE RATED WALL AND OR SLAB.
STEEL PIPE SLEEVE TERMINATE
SLEEVE FLUSH WITH FINISHED
SURFACE.
UL-LISTED FIRESTOPPING
FINISHED ESCUTCHEON PLATE
FLUSH AGAINST WALL AND OF
SIZE TO COMPLETELY COVER
OPENING.
APPROVED TYPE FIRE SAFE &
SMOKE TIGHT CAULKING SEALER
BETWEEN BARE PIPE AND SLEEVE.
NOTE:
MINIMUM SIZE OF OPENINGS AROUND SPRINKLER PIPE PENETRATIONS OF CONCRETE OR CMU WALLS
SHALL BE IN ACCORDANCE WITH NFPA 13 SEISMIC REQUIREMENTS.
1. USE NFPA-13 (CURRENT EDITION), CHAPTER 27, “PLANS AND CALCULATIONS” AS A GUIDELINE WHEN PREPARING SUBMITTALS FOR REVIEW. DISREGARD ONLY THOSE ITEMS NOT APPLICABLE TO THE INDIVIDUAL BUILDING SYSTEM. FIRE PROTECTION MATERIALS, EQUIPMENT AND INSTALLATION SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA-13 FOR THE
INSTALLATION OF AUTOMATIC SPRINKLER SYSTEM.
2. COMPLY WITH THE INTERNATIONAL BUILDING CODE (LATEST ADOPTED EDITION). INSTALLATION SHALL COMPLY WITH VA REQUIREMENTS. SYSTEM SHALL ALSO BE IN COMPLIANCE WITH ALL REQUIRED PLUMBING CODES.
3. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS AND ROOM FINISH SCHEDULE WHICH INDICATE CEILING HEIGHTS.
COORDINATE WITH ARCHITECT'S REFLECTED CEILING PLAN FOR LOCATION OF SPRINKLER HEADS IN AREAS WITH CEILINGS.
LOCATE HEADS IN AREAS WITHOUT CEILINGS AS REQUIRED BY NFPA AND VA REQUIREMENTS FOR THE APPROPRIATE
HAZARD CLASSIFICATION.
4. THIS FACILITY IS FULLY SPRINKLERED. FIRE SUPPRESSION SYSTEM SHALL BE WET PIPE TYPE SYSTEM WITH COMPLETE SPRINKLER PROTECTION UNLESS NOTED OTHERWISE. SYSTEM TO BE DESIGNED AS REQUIRED BY NFPA AND VA
REQUIREMENTS FOR THE APPROPRIATE HAZARD CLASSIFICATION.
5. SPRINKLER HEAD LAYOUTS INDICATED ARE BASED ON OCCUPANCY HAZARD CLASSIFICATIONS OUTLINED IN NFPA-13 AND VA
STANDARDS.
6. HYDRAULICALLY CALCULATE SPRINKLER IN ACCORDANCE WITH REQUIREMENTS FOR APPROPRIATE HAZARD OCCUPANCY.
PROVIDE ACTUAL NUMBER OF HEADS, REQUIRED SPACING AND PIPE ROUTING AS REQUIRED FOR CLEARANCE WITH STRUCTURAL CONDITIONS AND OTHER TRADES TO PROVIDE A COMPLETE AND OPERABLE SYSTEM IN ACCORDANCE WITH
NFPA AND VA REQUIREMENTS.
7. FIRE PROTECTION CONTRACTOR SHALL OBTAIN FLOW TEST DATA INDICATING THE WATER FLOW, STATIC PRESSURE AVAILABLE WITH NO FLOW, AND RESIDUAL PRESSURE AT FULL FLOW TO THE FACILITY. SUBMIT HYDRAULIC CALCULATIONS
AND PLANS RELATED TO A MINIMUM OF 1 REMOTE AREA FOR REVIEW.
8. PIPING IS SHOWN IN SCHEMATIC FORM TO INDICATE APPROXIMATE ARRANGEMENT OF EQUIPMENT AND PIPING. SPRINKLER CONTRACTOR SHALL DESIGN THE SYSTEM AND ROUTE PIPING AS REQUIRED FOR CONFORMANCE WITH ACTUAL BUILDING CONDITIONS AND NFPA REQUIREMENTS. COORDINATE SPRINKLER WORK WITH ALL OTHER TRADES TO AVOID CONFLICT.
9. SUPPORT NEW PIPING AND EQUIPMENT FROM STRUCTURE. PROVIDE ALL SUPPLEMENTAL STEEL TO SPAN BETWEEN PRIMARY BUILDING STRUCTURAL MEMBERS. DESIGN SUPPLEMENTAL STEEL AND SUPPORTS INCLUDING REACTION LOADS
AT PRIMARY BUILDING STRUCTURAL MEMBERS.
10. PROVIDE SPRINKLER HEADS IN CONCEALED LOCATIONS IN ACCORDANCE WITH NFPA REQUIREMENTS.
11. CLEAN ENTIRE WORK AREA OF ALL DUST, DIRT, AND OTHER DEBRIS. MAINTAIN WORK AREA IN CLEAN CONDITION.
12. PROVIDE ALL LABOR, MATERIALS, TOOLS, EQUIPMENT, ETC. REQUIRED FOR COMPLETE AND FUNCTIONAL SYSTEM AS
SPECIFIED AND INDICATED ON THE DRAWINGS.
13. SUBMIT ONE COMPLETE SET OF AUTOMATIC SPRINKLER SYSTEM DRAWINGS, HYDRAULIC CALCULATIONS, CURRENT WATER FLOW TEST, AND THE EQUIPMENT DATA BROCHURES PREPARED BY OR UNDER THE SUPERVISION OF, AND SEALED BY A
PROFESSIONAL ENGINEER.
14. REPAIR OR REPLACE NON-CONFORMING AND INADEQUATE WORK AT NO ADDITIONAL COST TO THE VA.
15. PROVIDE FIRE STOPS / SEALANT AT ALL PIPE PENETRATIONS THROUGHOUT FIRE RATED WALLS. REVIEW ARCHITECTURAL
PLANS PRIOR TO BIDDING AND INDICATE PENETRATIONS ON SPRINKLER LAYOUT SUBMITTAL.
16. FLOW AND TAMPER SWITCHES ARE TO BE PURCHASED AND INSTALLED AS WORK OF DIVISION 21. PROVIDE WIRING TO FLOW
AND TAMPER SWITCHES AS WORK OF DIVISION 26.
17. WATER SERVICE AND DETECTOR TYPE REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER TO BE PROVIDED AND TESTED AS WORK OF DIVISION 22. INCORPORATE ASSOCIATED PRESSURE DROP OF SELECTED BACKFLOW PREVENTER
DEVICE IN HYDRAULIC CALCULATIONS.
18. FURNISH AND INSTALL ARMOVER SUPPORTS FOR ALL END OF LINE BRANCH LINES IN ACCORDANCE WITH NFPA-13.
19. ALL DROPS TO SPRINKLER HEADS SHALL TEE / ELBOW OFF TOP OF BRANCH PIPE, EXCEPT WHERE STRUCTURAL, ARCHITECTURAL OR MECHANICAL EQUIPMENT CONDITIONS PRECLUDE CONNECTION AT TOP OF PIPE.
20. SPRINKLER HEADS SHALL BE IN A SYMMETRICAL PATTERN, NOT NECESSARILY IN THE CENTER OF ROOMS, CORRIDORS OR
CEILING TILE. LOCATE CENTERED IN CEILING TILE WHERE POSSIBLE.
21. LOCATE THE INSPECTOR'S TEST CONNECTION AND MAIN DRAIN LOCATIONS IN ACCORDANCE WITH NFPA-13.
22. FIRE DEPARTMENT CONNECTION SHALL BE LOCATED NOT MORE THAN 100 FEET AWAY FROM THE NEAREST FIRE HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY AND SHALL BE LOCATED NOT LESS THAN 18 INCHES, NOR MORE THAN 48
INCHES ABOVE ADJACENT SURFACE.
23. STANDPIPES SHALL BE PROVIDED PER NFPA 14, WITH 4 INCH DIAMETER MINIMUM SIZE.
24. CLASS 1 STANDPIPE SYSTEM SHALL BE PROVIDED WITH 2 1/2 INCH HOSE CONNECTIONS AT EACH INTERMEDIATE LANDING BETWEEN FLOORS IN EACH REQUIRED EGRESS EXIT STAIRWAY. COORDINATE TYPE OF HOSE CONNECTIONS WITH THE
LOCAL FIRE DEPARTMENT.
25. STANDPIPE TRAVEL DISTANCE SHALL BE MAXIMUM 130 FT PER NFPA-14-2019 AND LOCATION COORDINATED WITH VA AND
OKC FIRE DEPARTMENT.
GRADE
FLOOR
WALL
FIRE DEPARTMENT
CONNECTION
WALL
PLATE
(TYPICAL)
PIPE TAP FOR BALL
DRIP VALVE
18" TO 48"
DRAIN PIPE TO EXTERIOR DISCHARGE
MIN 6" ABOVE FINISHED GRADE
HORIZONTAL MOUNTED
BALL DRIP VALVE
PROVIDE CHECK
VALVE FOR MAIN
CHECK VALVE
BALL DRIP VALVE
FIRE SERVICE MAIN
FLOW SWITCH
DRAIN THROUGH WALL TO GRADE. COMBINE WITH
DRAIN FROM DCW BACKFLOW PREVENTER.
COORDINATE WITH PLUMBING DRAWINGS.
DOUBLE CHECK
DETECTOR TYPE
BACKFLOW ASSEMBLY
WITH TAMPER SWITCHES
INSPECTORS TEST/DRAIN VALVE
PRESSURE RELIEF
VALVE
PIPING SUPPORTS AS REQUIRED, TYP.
ISOLATION VALVE WITH
TAMPER SWITCH
SWING JOINT
THRUST BLOCK
STEEL TRANSITION FITTING
PRESSURE GUAGE
WITH BALL VALVE
TS
TS
MAIN DRAIN
WELDED BRANCH
CONNECTOR AS
REQUIRED, TYP.
NORMALLY CLOSED
BYPASS FOR FORWARD
FLOW TESTING
TO FIRE DEPARTMENT CONNECTION
T S
TS
CUP DRAIN. COLLECT AIR
COMPRESSOR AND DRY
VALVE DRAINS, CONNECT
INTO RISER DRAIN WITH
CHECK VALVE
DRY-PIPE VALVE
RISER MOUNTING KIT
GENERAL RISER MOUNTED
AIR COMPRESSOR
CONNECT COMPRESSED AIR
WITH PRESSURE SWITCH
DRY SPRINKLER
BUTTERFLY VALVE
WITH TAMPER SWITCH
RISER DRAIN FROM DRY
VALVE
FILL CUP PIPED TO MAIN DRAIN
AND TO OUTSIDE. DRAIN PIPE
SIZED BY ENGINEER.
DRAIN TO MAIN DRAIN OR
THROUGH WALL TO
OUTSIDE
NOTE:
1. ALL EXPOSED PIPING SHALL BE PAINTED RED.
2. PROVIDE GUARDS ON UPRIGHT SPRINKLERS
UNLESS OTHERWISE NOTED.
THREADED
HANGER ROD
SURGE
RESTRAINER
ADJUSTABLE
RING HANGER
BRANCHLINE
AUTO. SPRINKLER FEED
UPRIGHT AUTOMATIC
SPRINKLER, FM APPROVED,
QUICK RESPONSE.
REDUCER
RISER NIPPLE
REDUCING TEE
STATIC PSI RESIDUAL PSI FLOW GPM DATE LOCATION (SR#) FLOW TEST PERFORMED BY
THE FLOW TEST INFORMATION LISTED ABOVE IS INTENDED AS A REFERENCE FOR THE FIRE PROTECTION CONTRACTOR. THE FIRE
PROTECTION CONTRACTOR SHALL PERFORM A HYDRAULIC FLOW TEST NEAR THE PROJECT SITE TO VERIFY ACTUAL FLOW
CONDITIONS ON WHICH TO BASE THE FIRE PROTECTION DESIGN.
THE FLOW TEST INFORMATION PROVIDED BY VA IS FOR HYDRANT SR# AS LISTED FOR REFERENCE ONLY. FIRE HYDRANTS ON N.
KELLY STREET AND THE 16TH STREET BELONG TO WATER DEPARTMENT DIVISION OF OKLAHOMA CITY. CONTRACTOR TO
COORDINATE WITH CITY TO PERFORM HYDRANT FLOW TEST TO VERIFY ACTUAL FLOW CONDITIONS.
SPRINKLER AND STANDPIPE SYSTEM SHALL BE PER NFPA-13 AND NFPA-14 AND VA FIRE PROTECTION DESIGN MANUAL. STANDPIPE, FDC LOCATION SHALL BE COORDINATED WITH VA AND OKC FIRE DEPARTMENT AND ACCORDINGLY STANDPIPES SHALL BE
LOCATED.
70 65 1318 01/07/2022 51510864 RJY GROUP
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:5
:5
P
M C
R e v it P ro je c ts
\M P
-2
-O K
C P a rk in g G a ra g e s h a rm o n
A C
G .r v t
FX001
FIRE SUPPRESSION GENERAL
INFORMATION
1 3NAS/SMR
PARKING GARAGE 2
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
JULY 8, 2022
100% CONSTRUCTION DOCUMENTS
635-41419-292
N/A
RBK
FIRE SUPPRESSION SYMBOLS AND ABBREVIATIONS
Scale: No Scale
MECHANICAL TEE AND FLUSHING CONNECTION DETAIL
Scale: No Scale
PIPE HANGER SUPPORT DETAIL
Scale: No Scale
SPRINKLER PIPE SLEEVE THRU FIRE RATED WALL DETAIL
FIRE SUPPRESSION GENERAL NOTES
Scale: No Scale
WALL MOUNTED FIRE DEPARTMENT CONNECTION DETAIL
Scale: No Scale
BACKFLOW PREVENTER AND RISER DETAIL
Scale: No Scale
UPRIGHT AUTOMATIC SPRINKLER DETAIL
Scale: No Scale
FLOW TEST INFORMATION
DocuSign Envelope ID: 70605A43-D52F-49DF-8884-512E0529E9FA
7/13/2022
UP
RAMP DOWN
SLOPE = 1:20
RAMP DOWN
SLOPE = 1:20
RAMP UP
VEHICLE
DN
IT
ELEC
SEC
FX401
FX401
987654321
MECH
ELEV EQUIP
E3
FUTURE
ELEV
E2
ELEV
E1
ELEV
S1
STAIR
STAIR
S2
6" FL
6" FL
6" FL
4" FL
2" FL
6" FL
2" FL
A
B
C
D
E
F
G
5.23.91.6
B.6
8.8
4" FL
6" FL
5.5
STANDPIPE UP
& DN (TYP.)
(TYP.)
4" FL
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/1
/2
:5
:5
P
M C
R e v it P ro je c ts
\M P
-2
-O K
C P a rk in g G a ra g e s h a rm o n
A C
G .r v t
FX101
LEVEL 1 FIRE SUPPRESSION PLAN
2 3NAS/SMR
PARKING GARAGE 2
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
JULY 8, 2022
100% CONSTRUCTION DOCUMENTS
635-41419-292
N/A
RBK
N O
R T
H0 84 16
1 ROUTE SUPPLY TO MANUAL STANDPIPE TIGHT
TO STRUCTURE ABOVE.
2 PROVIDE FIRE DEPARTMENT CONNECTION FOR
DRY MANUAL STAND PIPE SYSTEM.
3 PROVIDE STANDPIPE WITH 2-1/2" HOSE
CONNECTIONS AT EACH FLOOR LANDING. SEE
DETAIL 3/FX401 FOR MORE INFORMATION.
4 PROVIDE UPRIGHT SPRINKLER HEAD.
N
SCOPE OF WORK
KEY PLAN
SCALE: NO SCALE
AREA OF WORK
A. ROUTE MAINS AS NECESSARY TO ALLOW FOR
PROPER DRAINAGE OF DRY SPRINKLER PIPING.
B. PROVIDE SUPPORT FOR FDC FROM
FLOOR/COLUMN.
Scale: 3/32" = 1'-0"
LEVEL 1 FIRE SUPPRESSION PLAN
RAMP DOWN
SLOPE = 1:20
RAMP DOWN
SLOPE = 1:20
DN
MECH
ELEV EQUIP
E3
FUTURE
ELEV
E2
ELEV
E1
ELEV
S1
STAIR
1 1
6" FL
6" FL
4" FL
2" FL
4" FL
2" FL
6" FL
8 8
BFP-2
FP-1
A
B
C
3.91.6
B.6
G
F
8.8
S2
STAIR
FX401
LEVEL 2 SW STAIR
11' - 4"
FUTURE LEVEL 3
22' - 8"
2-1/2" HOSE CONNECTION,
TYPICAL OF TWO
SUPPLY FIRE LEADER
FROM FIRE DEPARTMENT
CONNECTION
4" CAPPED CONNECTION
FOR FUTURE EXPANSION
OF STANDPIPE TO SERVE
7 LEVELS TOTAL
LEVEL 01 NE STAIR
-1' - 2"
LEVEL 1
0' - 0"
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/1
/2
:5
:5
P
M C
R e v it P ro je c ts
\M P
-2
-O K
C P a rk in g G a ra g e s h a rm o n
A C
G .r v t
FX401
LEVEL 1 FIRE SUPPRESSION
ENLARGED PLANS
3 3NAS/SMR
PARKING GARAGE 2
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
JULY 8, 2022
100% CONSTRUCTION DOCUMENTS
635-41419-292
N/A
RBK
N
SCOPE OF WORK
KEY PLAN
SCALE: NO SCALE
AREA OF WORK
N O
R T
H0 42 8
N O
R T
H0 42 80 2 4 8
A. ROUTE MAINS AS NECESSARY TO ALLOW FOR
PROPER DRAINAGE OF DRY SPRINKLER PIPING.
B. PROVIDE SUPPORT FOR FDC FROM
FLOOR/COLUMN.
1 PROVIDE SIDEWALL TYPE SPRINKLER HEAD AT
THE BOTTOM OF ELEVATOR HOISTWAY. LOCATE
WITHIN 2' OF HOISTWAY FLOOR. SUPPORT AS
REQUIRED.
2 PROVIDE STANDPIPE WITH 2-1/2" HOSE
CONNECTIONS AT EACH FLOOR LANDING. SEE
DETAIL 3/FX401 FOR MORE INFORMATION.
3 PROVIDE DOUBLECHECK DETECTOR TYPE
BACKFLOW PREVENTER ON INCOMING FIRE
SERVICE. BACKFLOW SHALL BE CONFIGURED
FOR VERTICAL INSTALLATION. REFER TO
DETAIL 5/FX001 FOR MORE INFORMATION.
4 ROUTE NEW FIRE WATER SERVICE INTO THE
BUILDING AND TURN UP THROUGH SLAB.
COORDINATE WITH CIVIL PIPE LOCATION AND
SIZE.
5 PROVIDE FIRE DEPARTMENT CONNECTION FOR
DRY PIPE SPRINKLER SYSTEM.
6 PROVIDE FIRE DEPARTMENT CONNECTION FOR
DRY MANUAL STAND PIPE SYSTEM.
7 PROVIDE DRY VALVE AND AIR COMPRESSOR
FOR DRY MANUAL PIPE SPRINKLER SYSTEM.
INSTALL PER DETAIL 5/FX001.
8 PROVIDE UPRIGHT SPRINKLER HEAD.
9 PROVIDE 6'' DOWNSPOUT NOZZLE AND SPLASH
BLOCK FOR SPRINKLER BACKFLOW
PREVENTER MAIN DRAIN PIPE.
Scale: 1/4" = 1'-0"
STAIR 1 FIRE SUPPRESSION PLAN
Scale: 1/4" = 1'-0"
STAIR 2 FIRE SUPPRESSION PLAN
Scale: 1/4" = 1'-0"
TYPICAL STANDPIPE SECTION
FIRE SERVICE BACKFLOW PREVENTER SCHEDULE
MARK LOCATION AREA AND/OR ROOM SERVED SYSTEM TYPE SIZE REMARKS
BFP-2 MECH 101 PARKING GARAGE FIRE SERVICE DOUBLE CHECK
DETECTOR
4"
FP-1 MECH 101
PARKING
GARAGE
DRY SYSTEM
MAINTENANCE AIR
OILLESS PISTON AIR
COMPRESSOR
150 1.6 1/4 1 115 CONSTANT GAST 2LAF-12-M200X RISER MOUNT
HP
SYSTEM
CAPACITY
CFM
NOMINAL
POWER
PHASE VOLT
SPEED
CONTROL
MARK LOCATION
AREA AND/OR
BLDG SERVED
SYSTEM AND/OR
SERVICE
TYPE
PUMP SIZE ELECTRICAL MOTOR
BASIS OF
DESIGN
MANUF.
BASIS OF DESIGN
MODEL NO.
REMARKS
DRY FIRE PROTECTION MAINTENANCE AIR SCHEDULE
| Sheets |
| FX001 - FIRE SUPPRESSION GENERAL INFORMATION |
| FX101 - LEVEL 1 FIRE SUPPRESSION PLAN |
| FX401 - LEVEL 1 FIRE SUPPRESSION ENLARGED PLANS |
| 2022-07-13T11:04:02-0700 | |
| Digitally verifiable PDF exported from www.docusign.com |