Attachment 08 Plumb 100_ 19-292.pdf
PDF 1 MB Posted
- Solicitation number
- 36C77623B0046
About this file
This package includes construction documents for a plumbing system upgrade at a Department of Veterans Affairs parking garage in Oklahoma City, Oklahoma. The project involves installing new drainage, vent and water piping throughout two levels of the garage, with work including a new sump pump, backflow preventer, roof drains and overflow drains. Plumbing plans show fixture locations and pipe routing, while details provide specifications for hangers, wall penetrations, trench drains and other components. Bidding contractors will use these documents to understand the full scope of work and prepare their responses to the related federal contract opportunity for minor construction issued by the VA Technology Acquisition Center in Austin, Texas. The solicitation number is 36C77623B0046 and responses are due on an unspecified date.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DCWR
DHW
PIPING SYSTEM
NG NATURAL GAS
ST STORM
PD PUMP DISCHARGE
OFD OVERFLOW STORM DRAIN
GW GREASE WASTE
OW OIL WASTE
SAN SANITARY WASTE
CD CONDENSATE DRAIN
CA COMPRESSED AIR
AW ACID WASTE
N2 NITROGEN
N2O NITROUS OXIDE
MA MEDICAL AIR
O2 OXYGEN
WAGD WASTE ANESTHETIC GAS DISPOSAL
VAC VACUUM
V SANITARY VENT
OV OIL VENT
AV ACID VENT
NPCW NONPOTABLE COLD WATER
DI DE-IONIZED WATER
SCW SOFTENED COLD WATER
DCW DOMESTIC COLD WATER
RO REVERSE OSMOSIS WATER
DOMESTIC CW RECIRCULATION
DOMESTIC HOT WATER
CO2 CARBON DIOXIDE
DHW 140 DOMESTIC HOT WATER (OTHER TEMP)
PG PROPANE GAS
PLUMBING SYMBOLS
DHWR DOMESTIC HW RECIRCULATION
NG
ST
PD
OFD
GW
OW
SAN
CD
CA
AW
N2
N2O
MA
O2
WAGD
VAC
CO2
PG
V
OV
AV
HW 140
SCW
NPCW
DI
RO
ANNOTATION SYMBOLS
EXISTING
NEW WORK KEYNOTE
DEMOLITION KEYNOTE
NEW BOLD TEXT INDICATES NEW ITEM
ITALICIZED TEXT INDICATES EXISTING ITEM
NEW PLUMBING EQUIPMENT MARK
DETAIL OR SECTION MARK
SHOWN ON DRAWING
DETAIL MODULE NUMBER
CONNECT TO EXISTING
LIMIT OF DEMOLITION
P-###
EXISTING PLUMBING EQUIPMENT MARKP-###
PLUMBING SYMBOLS & ABBREVIATIONS
3-WAY CONTROL VALVE
ANGLE GATE VALVE
ANGLE GLOBE VALVE
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
CONTROL VALVE
GATE VALVE
GLOBE VALVE
SAFETY RELIEF VALVE
TWO POSITION CONTROL VALVE
BACKFLOW PREVENTER
ECCENTRIC REDUCER
CONCENTRIC REDUCER
FLOW ARROW
HOSE BIBB / SILLCOCK
PLUG VALVE
PLUMBING SYMBOLS
PRESSURE REDUCING VALVE (WATER)
PRESSURE REGULATOR (GAS)
PIPE ANCHOR
PIPE GUIDES
WALL CLEANOUT
SUSPENDED CLEANOUT
WCO
WYE STRAINER
WYE STRAINER W/DRAIN VALVE
FLOOR DRAIN - ROUND OR SQUARE
FLOOR CLEANOUT - ROUND OR SQUARE
PIPE CAP
PIPE TURNING DOWN
PIPE TURNING UP
TEE UP
TEE DOWN
DROP AND RUN
DROP AND TURN
TEE OFF TOP
TEE OFF BOTTOM
CROSS AND RISER
PLAN 90° ELBOW
PIPE TEE
PIPE UNION
FLEXIBLE PIPE CONNECTOR
WATER METER
PUMP
AUTOMATIC AIR VENT
PRESSURE SWITCH
PRESSURE GAUGE
THERMOMETER
FLOW SWITCH
TEMPERATURE SWITCH
OR
OR
CO
PIPE SLOPE ARROW
AV
F
P
T
M
CIRCUIT SETTER
ANNOTATION ABBREVIATIONS
F FAHRENHEIT
FA FROM ABOVE
FB FROM BELOW
FBO FURNISHED BY OTHERS
FCO FLOOR CLEANOUT
FCW FILTERED COLD WATER
FD FLOOR DRAIN
FDC FIRE DEPARTMENT (HOSE)
CONNECTION
FM FLOW METER
FOP FUEL OIL PUMP
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOV FUEL OIL VENT
FS FLOOR SINK
FU FIXTURE UNITS
G GALLON
GC GENERAL CONTRACTOR
GCO GRADE CLEANOUTS
GD GARBAGE DISPOSAL
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GRS GAS REGULATOR STATION
GT GREASE TRAP
GVTR GAS VENT THROUGH ROOF
GWH GAS FIRED WATER HEATER
H&CW HOT AND COLD WATER
HB HOSE BIBB (INTERIOR)
HD HUB DRAIN
HEX HEAT EXCHANGER
HP HORSEPOWER
HS HAND SINK
HST HOT WATER STORAGE TANK
(DOMESTIC)
HWB HOT WATER BOILER
HWCP HOT WATER CIRCULATING PUMP
HWP HOT WATER PUMP
HYD HYDRANT
ICW INDUSTRIAL COLD WATER
INV INVERT
IPC INTERNATIONAL PLUMBING CODE
IRW IRRIGATION WATER
IW INDIRECT WASTE
IWH INSTANTANEOUS WATER HEATER
IWR INDUSTRIAL WATER RETURN
IWS INDUSTRIAL WATER SUPPLY
KW KILOWATT
KWHR KILOWATT-HOUR
L/S LITER PER SECOND
LA LABORATORY AIR
LAV LAVATORY
LBS/HR POUNDS PER HOUR
LCW LABORATORY COLD WATER
LHW LABORATORY HOT WATER
LNG LIQUID NATURAL GAS
LOX LIQUID OXYGEN
LV LABORATORY VACUUM
LW LOW WATER
M METER
MA MEDICAL AIR
MAV MANUAL AIR VENT
MBH THOUSANDS OF BTU PER HOUR
MC MECHANICAL CONTRACTOR
MED MEDICAL
MER MECHANICAL EQUIPMENT ROOM
MH MANHOLE
MOU MEMORANDUM OF UNDERSTANDING
MSB MOP SINK BASIN
MV MEDICAL VACUUM
N2 NITROGEN
N2O NITROUS OXIDE
NC NORMALLY CLOSED
NG NATURAL GAS
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NOM NOMINAL
NPW NON POTABLE WATER
NTS NOT TO SCALE
O2 OXYGEN
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OR OPERATING ROOM
OVFL OVERFLOW
PA PASCAL
PC PLUMBING CONTRACTOR
PD PRESSURE DROP
PDI PLUMBING AND DRAINAGE INSTITUTE
PG PRESSURE GAUGE
PP PLUMBING PUMP
PPM PARTS PER MILLION
PRS PRESSURE REDUCING STATION
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH
ATMOSPHERE
PSIG POUNDS PER SQUARE INCH GAUGE
PTRV PRESSURE TEMPERATURE RELIEF
VALVE
PW POTABLE WATER
RD ROOF DRAIN
RDL ROOF DRAIN LEADER
RL ROOF LEADER
RO REVERSE OSMOSIS
RWL RAIN WATER LEADER
SAN SANITARY SEWER
SCFM STANDARD CUBIC FOOT/MIN
SCW SOFTENED COLD WATER
SDMH STORM DRAIN MANHOLE
SP SUMP PUMP
SPR SPRINKLER LINE
SQFT SQUARE FOOT
SS STAINLESS STEEL
ST STORAGE TANK
SW STORM WATER
TCV TEMPERATURE CONTROL VALVE
TD TRENCH DRAIN
TDH TOTAL DYNAMIC HEAD
TDL TEMPERATURE DIFFERENTIAL
TEMP TEMPERATURE
TMV THERMOSTATIC MIXING VALVE
TP TRAP PRIMER
TSTAT THERMOSTAT
TWR TEMPERED WATER RETURN
TWS TEMPERED WATER SUPPLY
TYP TYPICAL
UPC UNIFORM PLUMBING CODE
V SANITARY VENT
VAC VACUUM
VB VACUUM BREAKER
VCO VACUUM CLEANER OUTLET
VP VACUUM PUMP
VS VENT STACK
VTR VENT THROUGH ROOF
W WASTE
WC WATER CLOSET
WCO WALL CLEANOUT
WG WATER GAUGE
WH WATER HEATER
WHA WATER HAMMER ARRESTOR
WHD WALL HYDRANT
WL WATER LINE
WM WATER METER
WPD WATER PRESSURE DROP
WS WASTE STACK
YCO YARD CLEANOUT
YH YARD HYDRANT
A/E ARCHITECT/ENGINEER
AC ABOVE CEILING
AD AREA DRAIN
AFF ABOVE FINISHED FLOOR
AG AIR GAP
AP ACCESS PANEL
AS AUTOMATIC SPRINKLER
AFG ABOVE FINISHED GRADE
ASD ADJUSTABLE SPEED DRIVE
ASHRAE AMERICAN SOCIETY HEATING,
REFRIGERATING, AIR CONDITIONING
ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
ASPE AMERICAN SOCIETY PLUMBING
ENGINEERS
ASR AUTOMATIC SPRINKLER RISER
AV ACID VENT
AW ACID WASTE
BAS BUILDING AUTOMATION SYSTEM
BF BELOW FLOOR
BFP BACKFLOW PREVENTER
BG BELOW GRADE
BH BOOSTER HEATER
BHP BREAK HORSEPOWER
BJ BETWEEN JOISTS
BOP BOTTOM OF PIPE
BSP BLACK STEEL PIPE
BT BATHTUB
BTUH BRITISH THERMAL UNITS PER HOUR
C CELSIUS
CF COMBINATION FIXTURE
CGA COMPRESSED GAS ASSOCIATION
CI CAST IRON
CO CLEANOUT
COND CONDENSATE
CP CONDENSATE PUMP
CS CLINICAL SINK
CV CONTROL VALVE
DA DENTAL COMPRESSED AIR
DCW DOMESTIC COLD WATER
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DHWS DOMESTIC HOT WATER SUPPLY
DF DRINKING FOUNTAIN
DI DEIONIZED WATER
DN DOWN
DOE DEPARTMENT OF ENERGY
DS DOWNSPOUT
DV DENTAL VACUUM
DW DISHWASHER
DWG DRAWING
DWH DOMESTIC WATER HEATER
DWR DRINKING WATER RETURN
DWS DRINKING WATER SUPPLY
DWV DRAIN WASTE VENT
EC ELECTRICAL CONTRACTOR
EL ELEVATION
EMCS ENERGY MONOSERRAT AND CENTRAL
SYSTEM
EPA ENVIRONMENTAL PROTECTION
AGENCY
EPACT ENERGY POLICY ACT
ESC ESCUTCHEON
ESH EMERGENCY SHOWER
ET EXPANSION TANK
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EWS EYEWASH STATION
EX EXISTING
1. WORK SHALL CONFORM TO APPLICABLE LOCAL, STATE, AND NATIONAL CODES AND APPLICABLE VA STANDARDS.
2. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS.
3. OBTAIN AND PAY FOR PERMITS, FEES, AND INSPECTIONS REQUIRED FOR THIS WORK.
4. PROVIDE NEW MATERIALS, EQUIPMENT AND PRODUCTS INCORPORATED IN THE WORK, OF A SUITABLE GRADE FOR THE
PURPOSES INTENDED.
5. EQUIPMENT OR MATERIAL DEVIATIONS FROM INDICATED CONTRACT REQUIREMENTS ARE SUBJECT TO THE APPROVAL OF THE COR. SUBMIT PROPOSED EQUIPMENT DEVIATIONS THAT ARE SIMILAR BOTH IN QUALITY AND CAPACITY TO THAT
EQUIPMENT SPECIFIED, AS SOLELY DETERMINED BY THE COR.
6. INSTALL EQUIPMENT AS INDICATED, ALLOWING FOR SUFFICIENT ACCESS AND CLEARANCE SPACE FOR EQUIPMENT
MAINTENANCE, REPAIRS, AND REPLACEMENT.
7. AT EACH PLUMBING FIXTURE, PROVIDE A PISTON TYPE WATER HAMMER ARRESTOR SIZED ACCORDING TO
MANUFACTURER'S RECOMMENDATIONS.
8. SANITARY DRAINAGE PIPING INDICATED IS LOCATED BELOW FLOOR SLAB OR WITHIN WALLS UNLESS NOTED OTHERWISE.
SANITARY VENT PIPING INDICATED IS ABOVE THE CEILING OR WITHIN WALLS UNLESS NOTED OTHERWISE.
9. SUPPORT PIPING SYSTEM AS REQUIRED BY APPLICABLE LOCAL, STATE, AND NATIONAL CODES ALONG WITH
SPECIFICATIONS, VA STANDARDS AND MANUFACTURER'S RECOMMENDATIONS.
10. FIRESTOP AND SEAL PIPING PENETRATIONS THROUGH WALLS AND FLOORS EQUAL TO THE RATING OF WALLS AND FLOORS.
11. TEST PLUMBING SYSTEM IN ACCORDANCE WITH APPLICABLE LOCAL, STATE AND NATIONAL CODES AND APPLICABLE VA
STANDARDS.
12. COORDINATE PLUMBING PIPING WITH WORK OF OTHER DISCIPLINES.
13. DISINFECT DOMESTIC WATER SYSTEM IN ACCORDANCE WITH APPLICABLE LOCAL, STATE, AND NATIONAL CODES AND
APPLICABLE VA STANDARDS.
14. PROVIDE SHUT OFF VALVES AT BRANCH PIPING TO FIXTURES.
15. COORDINATE PLUMBING WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION. COORDINATE ROUTING OF PIPING WITH
EXISTING CONDITIONS.
16. PROVIDE ALL NECESSARY OFFSETS, TEES, ELBOWS, ETC. FOR A COMPLETE AND COORDINATED WORKING PLUMBING SYSTEM. DRAWING PLANS, SCHEMATICS, AND DIAGRAMS INDICATE GENERAL LOCATION AND ARRANGEMENT OF PIPING
SYSTEMS.
17. CONTRACTOR SHALL COORDINATE ANY PLUMBING SYSTEM REQUIRED SHUTDOWN WITH THE COR/VA 1 WEEK IN ADVANCE.
18. PATCH, PAINT AND CLEAN SURFACES SUSTAINING DAMAGE ASSOCIATED WITH PLUMBING WORK OF THIS CONTRACT, UNLESS NOTED OTHERWISE.
19. INSTALL ESCUTCHEONS IN ALL PLACES WHERE PIPING PENETRATES A WALL IN AN EXPOSED LOCATION.
20. DO NOT INSTALL PIPES ABOVE TELECOM OR ELECTRICAL EQUIPMENT.
ALTERNATE DEDUCT #2:
• OMIT INSTALLATION OF DOMESTIC WATER BACKFLOW PREVENTER, HOSE BIBBS AND
ASSOCIATED DOMESTIC WATER PIPING FROM PARKING GARAGE.
FOR ORDER OF DEDUCTIVE BID ALTERNATE REFER TO SHEET G-002.
# ALTERNATE NOTES
OVERFLOW
DRAIN (OFD)ROOF
DRAIN (RD)
DOME STRAINER
ROOF MEMBRANE
1 1/2" RIGID INSULATION
SUMP RECEIVER
DRAIN BODY
STORM CONDUCTOR
DOME STAINER ROOF DRAIN 1 1/2" RIGID INSULATION
ROOF MEMBRANE
SUMP RECEIVER STORM CONDUCTOR
2" WATER DAM COLLAR
DOME STRAINER
OVERFLOW ROOF DRAIN
SUMP PAN
15' 27' 15'
1'-6" 3'-0" 1'-6"
2"
GRAVEL
UNDER DECK CLAMPUNDER DECK CLAMP
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/5
/2
:5
:0
P M
C U s e rs
\t b u d a i\ D o c u m e n ts \M
P
-2
-O
K C
P a rk in g G a ra g e tb u d a i.
rv t
P-001
PLUMBING GENERAL INFORMATION
1 5SMR
PARKING GARAGE 2
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
JULY 8, 2022
100% CONSTRUCTION DOCUMENTS
635-41419-292
N/A
PLH
PLUMBING GENERAL NOTES
PLUMBING SUMP PUMP SCHEDULE
MARK LOCATION
PERFORMANCE ELECTRICAL SPEED
CONTROL REMARKSFLUID FLOW HEAD FT TEMPERATURE HP PHASE VOLTAGE
SP-1 ELEV E1 WATER 150.0 GPM 20.0 60 °F 2 1 208 NONE 1, 2, 3
REMARKS:
1. WITH OIL/WATER DISCRIMINATING FEATURE. HIGH OIL AND HIGH WATER LIMIT ALARM. INTEGRATE ALARM WITH BUILDING AUTOMATION SYSTEM.
2. NON AUTOMATIC SUBMERSIBLE SUMP PUMP. WITH CONTROL PANEL.
3. CONTROL PANEL: 1 PHASE SIMPLEX PUMP CONTROL PANEL. 208 V, MOTOR CONTACTOR, NEMA 4X ENCLOSURE, ALARM LIGHT/HORN, PUMP RUN INDICATOR LIGHT, HOA SWITCH, DRY AUXILIARY CONTACT (ALARM STATUS), INTEGRATE DRY AUXILIARY CONTACT WITH BUILDING AUTOMATION SYSTEM.
PLUMBING BACKFLOW PREVENTER SCHEDULE
MARK LOCATION AREA AND/OR ROOM SERVED SYSTEM TYPE FLOW
INLET
PRESSURE SIZE REMARKS
BFP-1 MECH 101 PARKING GARAGE DCW REDUCED PRESSURE
PRINCIPLE
10.0 GPM 60.00 psi 2" 1, 2
PLUMBING FIXTURE SCHEDULE
MARK DESCRIPTION QUANTITY WASTE PIPE VENT PIPE
COLD
WATER HOT WATER REMARKS
FD-E FLOOR DRAIN, ROUND, 4" OUTLET 1 4" - - - FLOOR DRAIN, ROUND, 4" OUTLET
FD-Y FLOOR DRAIN, ROUND, 4'' OUTLET 24 - - - - GALVANIZED BODY, EXTRA HEAVY DUTY POLISHED BRONZE GRATE, SUITABLE FOR
PARKING DECKS
OFD-1 OVERFLOW ROOF DRAIN 4 - - - - OVERFLOW ROOF DRAIN
P-804 HOSE BIBB 5 - - 3/4" - HOSE BIBB
RD-1 PRIMARY ROOF DRAIN 4 - - - - PRIMARY ROOF DRAIN
NOTE: REFER TO FLOOR PLANS FOR WASTE PIPE SIZE CONNECTIONS FOR FD-Y, OFD-1, RD-1.
REMARKS:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. BACKFLOW PREVENTER IS SIZED FOR FUTURE GARAGE EXPANSION.
Scale: No Scale
ROOF DRAIN / OVERFLOW DRAIN DETAIL
DocuSign Envelope ID: DE6B1966-C688-4097-B859-109EA506307E
7/6/2022
DN
UP
RAMP DOWN
SLOPE = 1:20
RAMP DOWN
SLOPE = 1:20
RAMP UP
VEHICLE
SEC
ELEC
IT
S2
STAIR
ELEV EQUIP
MECH
E2
ELEV
E3
FUTURE
ELEV
E1
ELEV
FD-Y
FD-Y
FD-Y
FD-Y
FD-E
SP-1
FD-Y
BFP-1
P-804
P-804
S1
STAIR
987654321
8" SD4" SD 8" SD
5" SD
5" SD3" SD
8" SD
5" SD
5" SD
10" SD
10" SD
10" SD 10" SD
5" SD
5" SD
5" SD
5" SD
5" SD
3" SD
3" SD
2" SD
5" SD
8" SD
8" SD
2" SD
3" SAN
4" SAN
7 4" SAN
P-804
14 14
14 14
15(TYP.)
15 (TYP.)
15 (TYP.)
5" SD
4'' FCO
5" SD
4'' FCO
4'' FCO 4'' FCO
4'' FCO
4'' FCO
4'' FCO
4'' FCO
4'' FCO
4'' FCO
3'' FCO
5" SD
5" SD 4'' FCO
5" SD
10" SD
3" SD
INV. 1238.43
12" SD
3" SD
5" SD
INV. 1239.24
2" DCW
A
B
C
D
E
F
G
5.2
4" SD
6" SD
4" SD
FD-Y
6" SD
FD-Y
6" SD
6" SD
4" SD
4" SD
FD-Y
FD-Y
6" OSD
3.91.6
B.6
8.8
FD-Y 15 (TYP.)
3" SD
5.5
4" SAN
164" SAN
4" SD
4" SAN
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/6
/2
:0
:5
A M
C U s e rs
\t b u d a i\ D o c u m e n ts \M
P
-2
-O
K C
P a rk in g G a ra g e tb u d a i.
rv t
PP101
LEVEL 1 PLUMBING PLAN
2 5SMR
PARKING GARAGE 2
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
JULY 8, 2022
100% CONSTRUCTION DOCUMENTS
635-41419-292
N/A
PLH
Scale: 3/32" = 1'-0"
LEVEL 1 PLUMBING PLAN
N O
R T
H0 84 16
1 PROVIDE SUMP PUMP. INSTALL PER DETAIL
5/P-501.
2 2'' DCW UP TO CEILING SPACE AND 3/4'' DOWN
TO HOSE BIBB. PROVIDE WITH DRAIN VALVE TO
FACILIATE SYSTEM WINTERIZATION.
3 OVERFLOW STORM DRAIN UP. TERMINATE WITH
DOWNSPOUT NOZZLE AND PROVIDE SPLASH
BLOCK PER DETAIL 8/P-501.
4 2'' DCW UP TO SECOND FLOOR AND 3/4'' DN TO
HOSE BIBB.
5 REFER TO CIVIL DRAWINGS FOR CONNECTION
POINT TO SITE STORM DRAIN.
6 UP TO AIR GAP FITTING. REFER TO DETAIL
6/P-501.
7 REFER TO CIVIL DRAWINGS FOR CONNECTION
POINT TO SITE SANITARY.
8 2'' DCW UP TO HOSE BIBB.
9 CONNECT 2'' DCW TO INCOMING 6'' WATER LINE
UNDER SLAB. COORDINATE WITH FIRE
PROTECTION AND CIVIL DISCIPLINE.
10 PROVIDE REDUCED PRESSURE BACKFLOW
PREVENTER PER 11/P-501.
12 CONNECT SUMP PUMP DISCHARGE TO 4 IN
SANITARY LINE BY AN AIR GAP.
13 5'' STORM DRAIN CONDUCTOR UP. PROTECT
WITH PIPE GUARD.
14 PROVIDE 4'' CLEANOUT AT THE BASE OF THE
RISER. COORDINATE WITH PIPE GUARD.
15 PROVIDE FLOOR DRAIN.
16 2'' VENT UP THRU ROOF.
N
SCOPE OF WORK
KEY PLAN
SCALE: NO SCALE
AREA OF WORK
A. SANITARY AND STORM PIPING IS LOCATED
BELOW FIRST FLOOR. SHOWN ON THIS PLAN TO
CLARIFY ROUTING.
E3
FUTURE
ELEV
S2
STAIR
RD-1
OFD-1
FD-Y
FD-Y
FD-Y
FD-Y
FD-Y
FD-Y
FD-Y
FD-Y
FD-YFD-Y
FD-Y
FD-Y
P-804
E2
ELEV
E1
ELEV
S1
STAIR
1(TYP.)
FD-Y
ELEV
LOBBY
987654321
5" SD
3" SD
5" SD
5" SD
4" SD
3" SD
5" SD5" SD
3" SD
5" SD
5" SD
5" SD
5" SD
5" SD
5" SD
2" SD
3" SD
3" SD
4" SD
5" SD
P-804
3/4"
2'' CO
3'' CO
4" SD
4'' CO
5" SD 5" SD
5" SD
5" SD
3" SD
3" SD
3" SD
3" SD
3" SD
5" SD
5" SD
3" SD
5" SD
A
B
C
D
E
F
G
5.2
FD-Y
3" SD
4" OSD
6" OSD
4" OSD
3" SD
3.91.6
B.6
8.85.5
3" SD
2" SD
1 (TYP.)
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/5
/2
:5
:0
P M
C U s e rs
\t b u d a i\ D o c u m e n ts \M
P
-2
-O
K C
P a rk in g G a ra g e tb u d a i.
rv t
PP102
LEVEL 2 PLUMBING PLAN
3 5SMR
PARKING GARAGE 2
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
JULY 8, 2022
100% CONSTRUCTION DOCUMENTS
635-41419-292
N/A
PLH
Scale: 3/32" = 1'-0"
LEVEL 2 PLUMBING PLAN
N O
R T
H0 84 16
1 PROVIDE FLOOR DRAIN.
2 PROVIDE ROOF DRAIN AND OVERFLOW DRAIN.
3 2'' DCW DOWN TO CEILING SPACE BELOW AND
VALVED AND CAPPED 2'' DCW UP FOR FUTURE
CONNECTION.
4 3'' STORM DRAIN UP. REFER TO 1/P-501 FOR
CONTINUATION.
5 4'' OVERFLOW DRAIN UP AND DOWN. REFER TO
1/P-501 FOR CONTINUATION.
6 5'' STORM DRAIN CONDUCTOR DOWN. PROTECT
WITH PIPE GUARD.
7 2'' STORM DRAIN UP. REFER TO 2/P-501 FOR
CONTINUATION.
8 3'' OVERFLOW STORM DRAIN UP. REFER TO
2/P-501 FOR CONTINUATION.
9 6'' OVERFLOW STORM DRAIN DOWN.
10 2" VENT THRU ROOF.
11 3'' SD AND 4'' OSD THRU ROOF. SEE 1 / P-501
FOR CONTINUATION.
N
SCOPE OF WORK
KEY PLAN
SCALE: NO SCALE
AREA OF WORK
A. SANITARY AND STORM PIPING IS LOCATED
OVERHEAD ON FIRST FLOOR. SHOWN ON THIS
PLAN TO CLARIFY ROUTING.
NOM. SIZE (IN.)
PIPE (FT.)
TUBING (FT.)
5 FT
THRU 3/4
1 1 1/4
1 1/2
HANGER ROD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR
LOW TEMPERATURE
PIPE)
PROVIDE HIGH
COMPRESSIVE
STRENGTH
INSULATION (9 PSF
MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION SHIELD AT
HANGER
WELD
SADDLE
ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE
SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE
SPECIFICATIONS
1/2" DIA. HANGER RODS WITH 36"
MAX. SPACING ON EACH CHANNEL
BAND
1-5/8" 12 GAUGE CHANNEL
OR 2" x 2" x 1/4" ANGLE
NOTES:
SEE SPECIFICATIONS FOR
DETAILED HANGER
REQUIREMENTS. SIDE VIEW TRAPEZE HANGER
FOR UP TO 1000 LB. UNIFORM
LOAD
1" MAX.
PROVIDE INSULATION SHIELD &
INSERT FOR ALL PIPING (8" MIN.)
2 2 1/2 3 4 5 6 8 10 12
11 12 14 16 17 19 22 23
9 10 12 13 14 16 - -
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE
MAXIMUM PIPE/TUBING SUPPORT SPACING
3" PIPE EXPOSED ON WALL IN ELEVATOR
HOISTWAY. COORDINATE WITH ELEVATOR
INSTALLER PRIOR TO ROUGH IN.
FINISHED GROUND FLOOR
ELEVATOR PIT
FLOOR
SUMP PUMP PIT (SEE ARCHITECTURAL/STRUCTURAL DRAWINGS
FOR PIT SIZE, SEE ELECTRICAL DRAWINGS FOR ELECTRICAL
REQUIREMENTS)
SUBMERSIBLE SUMP PUMP WITH
PIGGYBACK FLOAT SWITCH
UNION
CHECK VALVE
PUMP DISCHARGE TO SANITARY
LINE. CONNECT TO SANITARY BY
AN AIR GAP. REFER TO FLOOR
PLANS FOR PIPE ROUTING.
ELECTRICAL OUTLET REFER TO
ELECTRICAL PLANS
FRAME AND GRATE BY GC
ARRANGE PIPING TO AVOID ELEVATOR
UNION
POINT NAME
PUMP ALARM STATUS
TOTALS
HARDWARE POINTS
AI AO BI BO
SOFTWARE POINTS
AV BV LOOP SCHED TREND ALARM SHOW ON GRAPHIC
X
X
10 0 0 0 0 0 0 0 1
TOTAL HARDWARE (1) TOTAL SOFTWARE (1)
SUMP PUMP CONTROL SEQUENCE:
ON WATER RISE, THE PUMP WILL ACTIVATE WHEN THE FLOAT RISES ABOVE THE "HIGH LIMIT" LEVEL . PUMP WILL REMAIN ON UNTIL THE WATER LEVEL IS BELOW THE "LOW LIMIT". WHEN THE "OFF" FLOAT NO LONGER SENSES WATER IT TURNS
THE PUMP OFF.
NOTE: REFER TO SUMP PUMP SCHEDULE.
RD-1
OFD-1
RD-1
OFD-1
4'' OSD DN
3'' SD DN
2" SD
A
B
C
4" OSD
3" SD
DN THRU ROOF
TO FIRST FLR
CLG SPACE
1.6
B.6
OFD-1
RD-1
2" SD
3" OSD
F
G
8.8
LEVEL 1 SW STAIR
0"
LOWER LEVEL
-4' - 0"
E
LEVEL 01 NE STAIR
-1' - 2"
LEVEL 1
0"
1" D
1" D
1" D
OU-102
OU-103
IU-104
OU-104
2" SD 2" SD
2" SD
2" SD
3" SD
STANDPIPE WITH AIR
GAP FITTING (TYP.)
THIS DETAIL APPLIES TO IT 102 (SHOWN), ELEC 103 (SHOWN), SECURITY 104 (SHOWN).
ROUTE CONDENSATE PIPING IN ELEV EQUIP 100 SIMILAR TO DETAIL SHOWN.
IT
ELEC
SECURITY
IU-102
3" SD
E
3" SD
GRADE
SPLASH BLOCK
HEIGHT LOCATION
FROM FINISHED
GRADE
DOUNSPOUT NOZZLE
LEVEL 1
0' - 0"
1/4" X 1-1/4" IRON
PIPE STRAP.
1/4" X 1-1/4" IRON
PIPE CLAMP
FLANGED
CONNECTION
PIPE
5/8" ~ ROD
MECHANICAL SLEEVE SEAL
WATER STOP AND ANCHOR
COLLAR
LINK SEAL TYPE WALL
SLEEVE OR PIPE SLEEVE
PIPE CLAMP AND
STRAP PROVIDED
ONLY FOR PRECAST
OR POURED WALL
CONSTRUCTION.
EXTERIOR WALL. REFER TO
ARCHITECTURAL PLANS FOR
EXACT CONSTRUCTION TYPE
NOTE: APPLICABLE TO ABOVE
AND BELOW GRADE
APPLICATIONS.
THREADED HANGER ROD
ADJUSTABLE RING HANGER
NOTE: 1
1. HANGING DETAILS SHOWN ARE SUBJECT TO REQUIREMENTS OF SEISMIC DESIGN.
2. INSTALL IN ACCORDANCE WITH NFPA 13.
EXPANSION ANCHOR HILTI QUIK
BOLT TZ OR APPROVED EQUAL.
EXPANSION ANCHOR SHALL BE
QUALIFIED FOR USE IN CRACKED
CONCRETE PER ACI 355.2
NEW CONCRETE SLAB
PIPE
SURGE RESTRAINER
INSULATION
BOLT
FLOOR SLAB
RISER CLAMP. BOTTOM
CLAMP REQUIRED AT
ANCHOR POINTS ONLY
PIPE SLEEVE WHERE
SPECIFIED
RISER CLAMP
FIRE-STOPPING
MATERIAL
BOLT
RISER CLAMP
PIPE SLEEVE WHERE
SPECIFIED
PIPE
RISER
SECTION
TOP
NOTE:
EXTEND SLEEVE ABOVE
FLOOR WHERE SPECIFIED.
REDUCED PRESSURE
BACKFLOW PREVENTER.
PROVIDE IN AN ACCESIBLE
LOCATION. COMPLY WITH
LOCAL REQUIREMENTS
ISOLATION VALVE
(TYP.)
FLOOR
DRAIN PIPE TO BE 2X
LINE SIZE. ROUTE TO
EXTERIOR.
COORDINATE MAIN
DRAIN ROUTING WITH
FIRE PROTECTION
DRAWINGS.
TEST COCK
(TYP.)
PROVIDE PROPER
SUPPORT FOR RPZ
ASSEMBLY
AIR GAP
TO PARKING GARAGEFROM CITY SUPPLY
DRAIN VALVE TO
ALLOW FOR
WINTERIZATION.
TO PARKING GARAGE
WATER CUT-
OFF MASTIC
THERMOPLASTIC
PRE-MOLDED PIPE
FLASHING
HOT AIR-WELD, 1-1/2"
BEYOND FASTENING
PLATES
CUT EDGE SEALANT
STAINLESS STEEL
CLAMPING RING
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/5
/2
:5
:0
P M
C U s e rs
\t b u d a i\ D o c u m e n ts \M
P
-2
-O
K C
P a rk in g G a ra g e tb u d a i.
rv t
P-501
ROOF PLUMBING PLANS AND
PLUMBING DETAILS
4 5SMR
PARKING GARAGE 2
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
JULY 8, 2022
100% CONSTRUCTION DOCUMENTS
635-41419-292
N/A
PLH
Scale: No Scale
PIPE HANGER DETAIL
Scale: No Scale
SUMP PUMP DETAIL
N O
R T
H0 84 16
N O
R T
H0 84 16
Scale: 3/32" = 1'-0"
ROOF PLUMBING PLAN
Scale: 3/32" = 1'-0"
ROOF PLUMBING PLAN
Scale: No Scale
CONDENSATE DRAIN DETAIL
Scale: No Scale
DOWNSPOUT NOZZLE DETAIL
Scale: No Scale
EXTERIOR WALL PIPE PENETRATION DETAIL
Scale: No Scale
CONCRETE PIPE HANGER DETAIL
Scale: No Scale
SUPPORT/ANCHOR FOR PIPE RISER DETAIL
Scale: No Scale
RPZ INSTALLATION DETAIL
Scale: 3" = 1'-0"
ROOF PIPE PENETRATION DETAIL
2" SD
3" OSD
2" SD
2" DCW
FD-Y
FD-Y
4" SD
3" SD
2" SD
5" SD
10" SD
10" SD
4" SD
8" SD
8" SD
5" SD
FD-Y
FD-Y
5" SD
3" SD
8" SD
4" SD
FD-Y
FD-Y
FD-Y
5" SD
FD-Y
FD-Y
5" SD
FD-Y
8" SD
8" SD
5" SD
4" SD
FD-Y
4" SD
2" SD
4" SD
2" DCW
4" SAN
3" SAN
3" SAN
3" SD
OFD-1
RD-1
OFD-1
RD-1OFD-1
RD-1
4" OSD
3"
4"
10"
5"
3"
5" SD
FD-Y
FD-Y
FD-Y
5" SD
P-804
P-804
2" SD
3" SD
3"
FD-Y
SP-1
FD-Y
RD-1
OFD-1
3'' CO
4''FCO
4'' FCO
P-804
P-804
P-804
FD-E
BFP-1
4'' FCO
2" DCW
4'' FCO
4'' FCO
4'' CO
4'' CO
4'' FCO
4'' FCO
4'' CO
4'' CO
4'' FCO
4'' FCO
4'' CO
FD-Y
2'' CO
4'' FCO
4'' CO
4'' FCO
4'' CO
4'' CO
4'' FCO
3" SD 5" SD
3" SD
5" SD
5" SD
3" SD
3" SD
3" SD
12" SD
10" SD
12" SD
4'' FCO
3" SD
2"
FD-Y
FD-Y
FD-Y
FD-Y
FD-Y
6" SD
6" SD
4" SD
4" SD
6" SD 6" SD
FD-Y
12" SD
4" SD
4" OSD
3" SD
6" OSD
4" SAN
4" SAN
4" SAN
2" V
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/5
/2
:5
:1
P M
C U s e rs
\t b u d a i\ D o c u m e n ts \M
P
-2
-O
K C
P a rk in g G a ra g e tb u d a i.
rv t
P-901
PLUMBING RISERS
5 5SMR
PARKING GARAGE 2
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
JULY 8, 2022
100% CONSTRUCTION DOCUMENTS
635-41419-292
N/A
PLH
Scale: No Scale
PLUMBING RISERS
| Sheets |
| P-001 - PLUMBING GENERAL INFORMATION |
| PP101 - LEVEL 1 PLUMBING PLAN |
| PP102 - LEVEL 2 PLUMBING PLAN |
| P-501 - ROOF PLUMBING PLANS AND PLUMBING DETAILS |
| P-901 - PLUMBING RISERS |
| 2022-07-13T10:02:30-0700 | |
| Digitally verifiable PDF exported from www.docusign.com |