Attachment 08 - Bedford MA EHRM Specifications IFC 20250604 Part2of3.pdf
PDF 19 MB Posted
- Solicitation number
- 36C77626R0003
About this file
This document is a comprehensive specification package for the EHRM Infrastructure Upgrades Construction project at Bedford Veterans Administration Medical Center in Bedford, Massachusetts. The solicitation number is 36C77626R0003, issued by the Department of Veterans Affairs Technology Acquisition Center Austin.
The project scope encompasses extensive plumbing, fire suppression, electrical, HVAC, communications, and site work for a new Electronic Health Records Master Control Room building addition. Key specifications include domestic and facility water distribution systems with copper tubing and cast iron piping; wet-pipe sprinkler systems designed per NFPA 13 with FM-approved sprinklers; clean agent fire suppression systems for data center protection; sanitary and storm drainage systems; plumbing fixtures including wall-hung water closets, lavatories, and service sinks; domestic water heat exchangers with temperature and pressure relief controls; electrical systems with panelboards, transformers, and lighting; HVAC systems with direct digital controls and commissioning; communications infrastructure with structured cabling; and fire detection and alarm systems. The contractor must comply with seismic restraint requirements per Section 13 05 41, sustainable construction requirements including bio-based materials, and comprehensive commissioning procedures outlined in Section 01 91 00. All systems require shop drawings, equipment specifications, as-built documentation in AutoCAD format, performance testing, and training of VA personnel. Materials in potable water systems must meet NSF 61 and NSF 372 requirements with lead content not exceeding 0.25 percent by weighted average. The project includes detailed specifications for 35 divisions of work with coordination requirements across mechanical, electrical, fire protection, and plumbing trades, all subject to Massachusetts State Building Code and International Code Council standards.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
6 7
8 9
10 11
12 13 14
15 16
S P R
IN
G S R
D
P
IN
E H
IL
L R
D
TREES
COMM DUCT
COMM MANHOLE
COMM CONDUIT
SCAN PATH
UNKN MANHOLE
UNKN MISC
ELEC MANHOLE
DATE
DRAWING NO. REV. 0
PROJECT MANAGER:
PREPARED FOR:
LOCATION:
GPRS UTILITY MAP
200 SPRINGS RD
TRIPLE C- THE AE GROUP
VA NEW ENGLAND HEALTHCARE SYSTEM
MATTHEW.CAERULIUS@GPRSINC.COM
MATTHEW CAERULIUS
617.655.4971
BEDFORD, MA 01730
8/30/2024
DISCLAIMER
LEGEND
FOR INFORMATION ONLY
C
U S
E R
S \A
D R
I A
N .K
O E
H N
\O N
E D
R I V
E
G P
R S
\P
R O
J E
C T
S \6
\C
A D
\6 E
X .D
G N
PURPOSES EXCEPT AS EXPRESSLY STATED HEREIN.
ANY FOR USED OR ON RELIED BE NOT MAY AND SURVEY LAND A NOT IS PDF
THIS SURVEYOR. LAND LICENSED A NOT IS GPRS SERVICES. ENGINEERING
OR SURVEYING, LAND GEOLOGICAL, GEOPHYSICAL, PROVIDE NOT DOES GPRS
5.
2.
1.
6.
FIELD WORK.
OF COMPLETION FOLLOWING EMAIL VIA SENT LETTER SUBMITTAL THE IN
INCLUDED SUBMITTALS OTHER AS WELL AS REPORT" SUMMARY "JOB THE SEE
USED, EQUIPMENT AND FINDINGS REGARDING INFORMATION ADDITIONAL FOR
DATE OF FIELD WORK.
THE ON LLC) (GPRS, SYSTEMS RADAR PENETRATING GROUND BY COLLECTED
COMMENTS AND MARKINGS DOCUMENT TO INTENDED IS IT FIELD.
THE IN COLLECTED DATA FROM DIRECTLY CREATED OUTPUT IS DRAWING THIS
EXCAVATION ACTIVITIES.
ALL AND ANY TO PRIOR CALLED BE TO 811 REQUIRES LAW STATE SERVICES.
CALL/811 ONE FOR REPLACEMENT A NEVER IS LOCATING UTILITY PRIVATE
https://gp-radar.com/terms-conditions
TERMS AND CONDITIONS THAT CAN BE VIEWED WITH THE LINK:
THE TO SUBJECT ARE FINDINGS ALL SITE. ON FEATURES SUBSURFACE OTHER
OR UTILITIES ALL LOCATE TO ABLE BE WILL IT GUARANTEE CANNOT GPRS 3.
IMAGERY PLACEMENT SHOULD BE CONSIDERED APPROXIMATE.
THE HOWEVER, ORDERED, IS CAD WHEN IMAGE THE ALIGN BETTER TO MADE
IS EFFORT AN FIELD. THE IN COLLECTED AS REMAIN DATA POINT AND LINE THE
WHILE INACCURATE OR OUTDATED, SHIFTED, SOMETIMES IS IMAGERY AERIAL 4.
SAN LIFTSTATION
SAN VAULT
P.I. VALVE
ELEC BOX
ELEC CABINET
ELEC MISC
ELEC PANEL
TRANSFORMER
COMM MISC
COMM POLE
SANITARY
WATER
UNKNOWN
STORM
FIRE WATER
SITE LIGHT
ELEC DUCT
ELECTRICAL
GAS
SITELIGHT
UTILITYPOLE
D= DEPTH
LINE CONTINUES
END OF INFO
SAN MANHOLE
CATCH BASIN
STRM MANHOLE
VALVE
HYDRANT
GAS METER
GAS VALVE
SCAN AREA
OBSTRUCTION
COMM
FENCE
STEAM
WTR STRUCT
UNK STRUCT
UNK DUCT
LANDSCAPE LIGHT
TRENCHDRAIN
STEAM MANHOLE
TRAF SIGN
SIGN
SEE NOTE #6 ABOVE.
THE SERVICE IS USED ON EVERY PROJECT IN ADDITION TO OUR OWN.
GPRS IS NOT AFFILIATED WITH 811 BUT DOES RECOMMEND THAT
0 500'250'
Know what'sbelow.
before you dig.Call
R
MISC POINT
U
U
U
U
U
S P R
IN
G S R
D
SCAN PATH
D=2'-3'
ELECTRICAL
COMM DUCT
COMM MANHOLE
COMM CONDUIT
SCAN PATH
UNKN MANHOLE
UNKN MISC
ELEC MANHOLE
DATE
DRAWING NO. REV. 0
PROJECT MANAGER:
PREPARED FOR:
LOCATION:
GPRS UTILITY MAP
200 SPRINGS RD
TRIPLE C- THE AE GROUP
VA NEW ENGLAND HEALTHCARE SYSTEM
MATTHEW.CAERULIUS@GPRSINC.COM
MATTHEW CAERULIUS
617.655.4971
BEDFORD, MA 01730
8/30/2024
DISCLAIMER
LEGEND
FOR INFORMATION ONLY
C
U S
E R
S \A
D R
I A
N .K
O E
H N
\O N
E D
R I V
E
G P
R S
\P
R O
J E
C T
S \6
\C
A D
\6 E
X .D
G N
PURPOSES EXCEPT AS EXPRESSLY STATED HEREIN.
ANY FOR USED OR ON RELIED BE NOT MAY AND SURVEY LAND A NOT IS PDF
THIS SURVEYOR. LAND LICENSED A NOT IS GPRS SERVICES. ENGINEERING
OR SURVEYING, LAND GEOLOGICAL, GEOPHYSICAL, PROVIDE NOT DOES GPRS
5.
2.
1.
6.
FIELD WORK.
OF COMPLETION FOLLOWING EMAIL VIA SENT LETTER SUBMITTAL THE IN
COMMENTS AND MARKINGS DOCUMENT TO INTENDED IS IT FIELD.
THE IN COLLECTED DATA FROM DIRECTLY CREATED OUTPUT IS DRAWING THIS
EXCAVATION ACTIVITIES.
ALL AND ANY TO PRIOR CALLED BE TO 811 REQUIRES LAW STATE SERVICES.
CALL/811 ONE FOR REPLACEMENT A NEVER IS LOCATING UTILITY PRIVATE
https://gp-radar.com/terms-conditions
TERMS AND CONDITIONS THAT CAN BE VIEWED WITH THE LINK:
THE TO SUBJECT ARE FINDINGS ALL SITE. ON FEATURES SUBSURFACE OTHER
OR UTILITIES ALL LOCATE TO ABLE BE WILL IT GUARANTEE CANNOT GPRS 3.
IMAGERY PLACEMENT SHOULD BE CONSIDERED APPROXIMATE.
THE HOWEVER, ORDERED, IS CAD WHEN IMAGE THE ALIGN BETTER TO MADE
IS EFFORT AN FIELD. THE IN COLLECTED AS REMAIN DATA POINT AND LINE THE
WHILE INACCURATE OR OUTDATED, SHIFTED, SOMETIMES IS IMAGERY AERIAL 4.
SAN LIFTSTATION
SAN VAULT
P.I. VALVE
ELEC BOX
ELEC CABINET
ELEC MISC
ELEC PANEL
TRANSFORMER
COMM MISC
COMM POLE
SANITARY
WATER
UNKNOWN
STORM
FIRE WATER
SITE LIGHT
ELEC DUCT
ELECTRICAL
GAS
SITELIGHT
UTILITYPOLE
D= DEPTH
LINE CONTINUES
END OF INFO
SAN MANHOLE
CATCH BASIN
STRM MANHOLE
VALVE
HYDRANT
GAS METER
GAS VALVE
SCAN AREA
OBSTRUCTION
COMM
FENCE
STEAM
WTR STRUCT
UNK STRUCT
UNK DUCT
LANDSCAPE LIGHT
TRENCHDRAIN
STEAM MANHOLE
TRAF SIGN
SIGN
SEE NOTE #6 ABOVE.
THE SERVICE IS USED ON EVERY PROJECT IN ADDITION TO OUR OWN.
GPRS IS NOT AFFILIATED WITH 811 BUT DOES RECOMMEND THAT
0 40'20'
Know what'sbelow.
before you dig.Call
R
MISC POINT
P R
IN
G S R
D
SCAN PATH
D=2'-3'
D=2'-3'
D=2'-3'
PHONE
D=1'-2'
D=1'-2'
D=1'-2'
COMM DUCT
COMM MANHOLE
COMM CONDUIT
SCAN PATH
UNKN MANHOLE
UNKN MISC
ELEC MANHOLE
DATE
DRAWING NO. REV. 0
PROJECT MANAGER:
PREPARED FOR:
LOCATION:
GPRS UTILITY MAP
200 SPRINGS RD
TRIPLE C- THE AE GROUP
VA NEW ENGLAND HEALTHCARE SYSTEM
MATTHEW.CAERULIUS@GPRSINC.COM
MATTHEW CAERULIUS
617.655.4971
BEDFORD, MA 01730
8/30/2024
DISCLAIMER
LEGEND
FOR INFORMATION ONLY
C
U S
E R
S \A
D R
I A
N .K
O E
H N
\O N
E D
R I V
E
G P
R S
\P
R O
J E
C T
S \6
\C
A D
\6 E
X .D
G N
PURPOSES EXCEPT AS EXPRESSLY STATED HEREIN.
ANY FOR USED OR ON RELIED BE NOT MAY AND SURVEY LAND A NOT IS PDF
THIS SURVEYOR. LAND LICENSED A NOT IS GPRS SERVICES. ENGINEERING
OR SURVEYING, LAND GEOLOGICAL, GEOPHYSICAL, PROVIDE NOT DOES GPRS
5.
2.
1.
6.
FIELD WORK.
OF COMPLETION FOLLOWING EMAIL VIA SENT LETTER SUBMITTAL THE IN
COMMENTS AND MARKINGS DOCUMENT TO INTENDED IS IT FIELD.
THE IN COLLECTED DATA FROM DIRECTLY CREATED OUTPUT IS DRAWING THIS
EXCAVATION ACTIVITIES.
ALL AND ANY TO PRIOR CALLED BE TO 811 REQUIRES LAW STATE SERVICES.
CALL/811 ONE FOR REPLACEMENT A NEVER IS LOCATING UTILITY PRIVATE
https://gp-radar.com/terms-conditions
TERMS AND CONDITIONS THAT CAN BE VIEWED WITH THE LINK:
THE TO SUBJECT ARE FINDINGS ALL SITE. ON FEATURES SUBSURFACE OTHER
OR UTILITIES ALL LOCATE TO ABLE BE WILL IT GUARANTEE CANNOT GPRS 3.
IMAGERY PLACEMENT SHOULD BE CONSIDERED APPROXIMATE.
THE HOWEVER, ORDERED, IS CAD WHEN IMAGE THE ALIGN BETTER TO MADE
IS EFFORT AN FIELD. THE IN COLLECTED AS REMAIN DATA POINT AND LINE THE
WHILE INACCURATE OR OUTDATED, SHIFTED, SOMETIMES IS IMAGERY AERIAL 4.
SAN LIFTSTATION
SAN VAULT
P.I. VALVE
ELEC BOX
ELEC CABINET
ELEC MISC
ELEC PANEL
TRANSFORMER
COMM MISC
COMM POLE
SANITARY
WATER
UNKNOWN
STORM
FIRE WATER
SITE LIGHT
ELEC DUCT
ELECTRICAL
GAS
SITELIGHT
UTILITYPOLE
D= DEPTH
LINE CONTINUES
END OF INFO
SAN MANHOLE
CATCH BASIN
STRM MANHOLE
VALVE
HYDRANT
GAS METER
GAS VALVE
SCAN AREA
OBSTRUCTION
COMM
FENCE
STEAM
WTR STRUCT
UNK STRUCT
UNK DUCT
LANDSCAPE LIGHT
TRENCHDRAIN
STEAM MANHOLE
TRAF SIGN
SIGN
SEE NOTE #6 ABOVE.
THE SERVICE IS USED ON EVERY PROJECT IN ADDITION TO OUR OWN.
GPRS IS NOT AFFILIATED WITH 811 BUT DOES RECOMMEND THAT
0 40'20'
Know what'sbelow.
before you dig.Call
R
MISC POINT
P R
IN
G S R
D
SCAN PATH
SCAN PATH
D=2'-3'
D=2'-3'
D=1'-2'
D=1'-2'
D=2'-3'
D=2'-3'
MH12
D=3'-4'
D=1'-2'
D=1'-2'
D=3'-4'
COMM DUCT
COMM MANHOLE
COMM CONDUIT
SCAN PATH
UNKN MANHOLE
UNKN MISC
ELEC MANHOLE
DATE
DRAWING NO. REV. 0
PROJECT MANAGER:
PREPARED FOR:
LOCATION:
GPRS UTILITY MAP
200 SPRINGS RD
TRIPLE C- THE AE GROUP
VA NEW ENGLAND HEALTHCARE SYSTEM
MATTHEW.CAERULIUS@GPRSINC.COM
MATTHEW CAERULIUS
617.655.4971
BEDFORD, MA 01730
8/30/2024
DISCLAIMER
LEGEND
FOR INFORMATION ONLY
C
U S
E R
S \A
D R
I A
N .K
O E
H N
\O N
E D
R I V
E
G P
R S
\P
R O
J E
C T
S \6
\C
A D
\6 E
X .D
G N
PURPOSES EXCEPT AS EXPRESSLY STATED HEREIN.
ANY FOR USED OR ON RELIED BE NOT MAY AND SURVEY LAND A NOT IS PDF
THIS SURVEYOR. LAND LICENSED A NOT IS GPRS SERVICES. ENGINEERING
OR SURVEYING, LAND GEOLOGICAL, GEOPHYSICAL, PROVIDE NOT DOES GPRS
5.
2.
1.
6.
FIELD WORK.
OF COMPLETION FOLLOWING EMAIL VIA SENT LETTER SUBMITTAL THE IN
COMMENTS AND MARKINGS DOCUMENT TO INTENDED IS IT FIELD.
THE IN COLLECTED DATA FROM DIRECTLY CREATED OUTPUT IS DRAWING THIS
EXCAVATION ACTIVITIES.
ALL AND ANY TO PRIOR CALLED BE TO 811 REQUIRES LAW STATE SERVICES.
CALL/811 ONE FOR REPLACEMENT A NEVER IS LOCATING UTILITY PRIVATE
https://gp-radar.com/terms-conditions
TERMS AND CONDITIONS THAT CAN BE VIEWED WITH THE LINK:
THE TO SUBJECT ARE FINDINGS ALL SITE. ON FEATURES SUBSURFACE OTHER
OR UTILITIES ALL LOCATE TO ABLE BE WILL IT GUARANTEE CANNOT GPRS 3.
IMAGERY PLACEMENT SHOULD BE CONSIDERED APPROXIMATE.
THE HOWEVER, ORDERED, IS CAD WHEN IMAGE THE ALIGN BETTER TO MADE
IS EFFORT AN FIELD. THE IN COLLECTED AS REMAIN DATA POINT AND LINE THE
WHILE INACCURATE OR OUTDATED, SHIFTED, SOMETIMES IS IMAGERY AERIAL 4.
SAN LIFTSTATION
SAN VAULT
P.I. VALVE
ELEC BOX
ELEC CABINET
ELEC MISC
ELEC PANEL
TRANSFORMER
COMM MISC
COMM POLE
SANITARY
WATER
UNKNOWN
STORM
FIRE WATER
SITE LIGHT
ELEC DUCT
ELECTRICAL
GAS
SITELIGHT
UTILITYPOLE
D= DEPTH
LINE CONTINUES
END OF INFO
SAN MANHOLE
CATCH BASIN
STRM MANHOLE
VALVE
HYDRANT
GAS METER
GAS VALVE
SCAN AREA
OBSTRUCTION
COMM
FENCE
STEAM
WTR STRUCT
UNK STRUCT
UNK DUCT
LANDSCAPE LIGHT
TRENCHDRAIN
STEAM MANHOLE
TRAF SIGN
SIGN
SEE NOTE #6 ABOVE.
THE SERVICE IS USED ON EVERY PROJECT IN ADDITION TO OUR OWN.
GPRS IS NOT AFFILIATED WITH 811 BUT DOES RECOMMEND THAT
0 40'20'
Know what'sbelow.
before you dig.Call
R
MISC POINT
P R
IN
G S R
D
SCAN PATH
D=1'-2'
D=1'-2'
D=7'-8'
D=3'-4'
D=3'-4'
COMM DUCT
COMM MANHOLE
COMM CONDUIT
SCAN PATH
UNKN MANHOLE
UNKN MISC
ELEC MANHOLE
DATE
DRAWING NO. REV. 0
PROJECT MANAGER:
PREPARED FOR:
LOCATION:
GPRS UTILITY MAP
200 SPRINGS RD
TRIPLE C- THE AE GROUP
VA NEW ENGLAND HEALTHCARE SYSTEM
MATTHEW.CAERULIUS@GPRSINC.COM
MATTHEW CAERULIUS
617.655.4971
BEDFORD, MA 01730
8/30/2024
DISCLAIMER
LEGEND
FOR INFORMATION ONLY
C
U S
E R
S \A
D R
I A
N .K
O E
H N
\O N
E D
R I V
E
G P
R S
\P
R O
J E
C T
S \6
\C
A D
\6 E
X .D
G N
PURPOSES EXCEPT AS EXPRESSLY STATED HEREIN.
ANY FOR USED OR ON RELIED BE NOT MAY AND SURVEY LAND A NOT IS PDF
THIS SURVEYOR. LAND LICENSED A NOT IS GPRS SERVICES. ENGINEERING
OR SURVEYING, LAND GEOLOGICAL, GEOPHYSICAL, PROVIDE NOT DOES GPRS
5.
2.
1.
6.
FIELD WORK.
OF COMPLETION FOLLOWING EMAIL VIA SENT LETTER SUBMITTAL THE IN
COMMENTS AND MARKINGS DOCUMENT TO INTENDED IS IT FIELD.
THE IN COLLECTED DATA FROM DIRECTLY CREATED OUTPUT IS DRAWING THIS
EXCAVATION ACTIVITIES.
ALL AND ANY TO PRIOR CALLED BE TO 811 REQUIRES LAW STATE SERVICES.
CALL/811 ONE FOR REPLACEMENT A NEVER IS LOCATING UTILITY PRIVATE
https://gp-radar.com/terms-conditions
TERMS AND CONDITIONS THAT CAN BE VIEWED WITH THE LINK:
THE TO SUBJECT ARE FINDINGS ALL SITE. ON FEATURES SUBSURFACE OTHER
OR UTILITIES ALL LOCATE TO ABLE BE WILL IT GUARANTEE CANNOT GPRS 3.
IMAGERY PLACEMENT SHOULD BE CONSIDERED APPROXIMATE.
THE HOWEVER, ORDERED, IS CAD WHEN IMAGE THE ALIGN BETTER TO MADE
IS EFFORT AN FIELD. THE IN COLLECTED AS REMAIN DATA POINT AND LINE THE
WHILE INACCURATE OR OUTDATED, SHIFTED, SOMETIMES IS IMAGERY AERIAL 4.
SAN LIFTSTATION
SAN VAULT
P.I. VALVE
ELEC BOX
ELEC CABINET
ELEC MISC
ELEC PANEL
TRANSFORMER
COMM MISC
COMM POLE
SANITARY
WATER
UNKNOWN
STORM
FIRE WATER
SITE LIGHT
ELEC DUCT
ELECTRICAL
GAS
SITELIGHT
UTILITYPOLE
D= DEPTH
LINE CONTINUES
END OF INFO
SAN MANHOLE
CATCH BASIN
STRM MANHOLE
VALVE
HYDRANT
GAS METER
GAS VALVE
SCAN AREA
OBSTRUCTION
COMM
FENCE
STEAM
WTR STRUCT
UNK STRUCT
UNK DUCT
LANDSCAPE LIGHT
TRENCHDRAIN
STEAM MANHOLE
TRAF SIGN
SIGN
SEE NOTE #6 ABOVE.
THE SERVICE IS USED ON EVERY PROJECT IN ADDITION TO OUR OWN.
GPRS IS NOT AFFILIATED WITH 811 BUT DOES RECOMMEND THAT
0 40'20'
Know what'sbelow.
before you dig.Call
R
MISC POINT
SCAN AREA
SCAN AREA
SCAN PATH
SCAN PATH
D=2'-3'
D=6'-7'
D=5'-6'
DEBRIS
DUMPSTER &
D=6'-7'
D=2'-3'
D=2'-3'
D=0-1'
D=2'-3' D=2'-3'
D=4'-5'
D=4'-5'
D=2'-3'
MH23
D=4'-5'
D=4'-5'
D=4'-5'
D=7'-8'
D=2'-3'
D=2'-3'
D=2'-3'
D=2'-3'
D=2'-3'
D=2'-3'
MH22
D=1'-2'
D=1'-2'
D=1'-2'
D=5'-6'
STORM
D=8'-9'
SANITARY
SCAN AREA
COMM DUCT
COMM MANHOLE
COMM CONDUIT
SCAN PATH
UNKN MANHOLE
UNKN MISC
ELEC MANHOLE
DATE
DRAWING NO. REV. 0
PROJECT MANAGER:
PREPARED FOR:
LOCATION:
GPRS UTILITY MAP
200 SPRINGS RD
TRIPLE C- THE AE GROUP
VA NEW ENGLAND HEALTHCARE SYSTEM
MATTHEW.CAERULIUS@GPRSINC.COM
MATTHEW CAERULIUS
617.655.4971
BEDFORD, MA 01730
8/30/2024
DISCLAIMER
LEGEND
FOR INFORMATION ONLY
C
U S
E R
S \A
D R
I A
N .K
O E
H N
\O N
E D
R I V
E
G P
R S
\P
R O
J E
C T
S \6
\C
A D
\6 E
X .D
G N
PURPOSES EXCEPT AS EXPRESSLY STATED HEREIN.
ANY FOR USED OR ON RELIED BE NOT MAY AND SURVEY LAND A NOT IS PDF
THIS SURVEYOR. LAND LICENSED A NOT IS GPRS SERVICES. ENGINEERING
OR SURVEYING, LAND GEOLOGICAL, GEOPHYSICAL, PROVIDE NOT DOES GPRS
5.
2.
1.
6.
FIELD WORK.
OF COMPLETION FOLLOWING EMAIL VIA SENT LETTER SUBMITTAL THE IN
COMMENTS AND MARKINGS DOCUMENT TO INTENDED IS IT FIELD.
THE IN COLLECTED DATA FROM DIRECTLY CREATED OUTPUT IS DRAWING THIS
EXCAVATION ACTIVITIES.
ALL AND ANY TO PRIOR CALLED BE TO 811 REQUIRES LAW STATE SERVICES.
CALL/811 ONE FOR REPLACEMENT A NEVER IS LOCATING UTILITY PRIVATE
https://gp-radar.com/terms-conditions
TERMS AND CONDITIONS THAT CAN BE VIEWED WITH THE LINK:
THE TO SUBJECT ARE FINDINGS ALL SITE. ON FEATURES SUBSURFACE OTHER
OR UTILITIES ALL LOCATE TO ABLE BE WILL IT GUARANTEE CANNOT GPRS 3.
IMAGERY PLACEMENT SHOULD BE CONSIDERED APPROXIMATE.
THE HOWEVER, ORDERED, IS CAD WHEN IMAGE THE ALIGN BETTER TO MADE
IS EFFORT AN FIELD. THE IN COLLECTED AS REMAIN DATA POINT AND LINE THE
WHILE INACCURATE OR OUTDATED, SHIFTED, SOMETIMES IS IMAGERY AERIAL 4.
SAN LIFTSTATION
SAN VAULT
P.I. VALVE
ELEC BOX
ELEC CABINET
ELEC MISC
ELEC PANEL
TRANSFORMER
COMM MISC
COMM POLE
SANITARY
WATER
UNKNOWN
STORM
FIRE WATER
SITE LIGHT
ELEC DUCT
ELECTRICAL
GAS
SITELIGHT
UTILITYPOLE
D= DEPTH
LINE CONTINUES
END OF INFO
SAN MANHOLE
CATCH BASIN
STRM MANHOLE
VALVE
HYDRANT
GAS METER
GAS VALVE
SCAN AREA
OBSTRUCTION
COMM
FENCE
STEAM
WTR STRUCT
UNK STRUCT
UNK DUCT
LANDSCAPE LIGHT
TRENCHDRAIN
STEAM MANHOLE
TRAF SIGN
SIGN
SEE NOTE #6 ABOVE.
THE SERVICE IS USED ON EVERY PROJECT IN ADDITION TO OUR OWN.
GPRS IS NOT AFFILIATED WITH 811 BUT DOES RECOMMEND THAT
0 40'20'
Know what'sbelow.
before you dig.Call
R
MISC POINT
P R
IN
G S R
D
SCAN PATH
SCAN PATH
SCAN PATH
SCAN PATH
SCAN PATH
SCAN PATH
NO ACCESS
NO ACCESS
MH11
D=3'-4'
D=3'-4'
D=1'-2'
D=9'-10'
D=9'-10'
D=7'-8'
D=6'-7'
D=5'-6'
D=4'-5'
D=4'-5'
D=4'-5'
D=5'-6'
D=5'-6'
D=5'-6'
D=1'-2'
D=1'-2'
D=2'-3'
D=2'-3'
D=2'-3'
D=2'-3'
D=1'-2'
D=1'-2'
D=1'-2'
D=1'-2'
D=1'-2'
D=1'-2'
D=1'-2'
NO ACCESS
MH10
D=1'-2'
D=1'-2'
D=1'-2'
COMM & ELEC
D=2'-3'
D=5'-6'
D=3'-4'
D=2'-3'
D=4'-5'
D=1'-2'
D=1'-2'
D=2'-3'
D=2'-3'
D=2'-3'
D=4'-5'
D
D=2'-3'
D=2'-3'
D=2'-3'
D=2'-3'
D=2'-3'
D
D
COMM DUCT
COMM MANHOLE
COMM CONDUIT
SCAN PATH
UNKN MANHOLE
UNKN MISC
ELEC MANHOLE
DATE
DRAWING NO. REV. 0
PROJECT MANAGER:
PREPARED FOR:
LOCATION:
GPRS UTILITY MAP
200 SPRINGS RD
TRIPLE C- THE AE GROUP
VA NEW ENGLAND HEALTHCARE SYSTEM
MATTHEW.CAERULIUS@GPRSINC.COM
MATTHEW CAERULIUS
617.655.4971
BEDFORD, MA 01730
8/30/2024
DISCLAIMER
LEGEND
FOR INFORMATION ONLY
C
U S
E R
S \A
D R
I A
N .K
O E
H N
\O N
E D
R I V
E
G P
R S
\P
R O
J E
C T
S \6
\C
A D
\6 E
X .D
G N
PURPOSES EXCEPT AS EXPRESSLY STATED HEREIN.
ANY FOR USED OR ON RELIED BE NOT MAY AND SURVEY LAND A NOT IS PDF
THIS SURVEYOR. LAND LICENSED A NOT IS GPRS SERVICES. ENGINEERING
OR SURVEYING, LAND GEOLOGICAL, GEOPHYSICAL, PROVIDE NOT DOES GPRS
5.
2.
1.
6.
FIELD WORK.
OF COMPLETION FOLLOWING EMAIL VIA SENT LETTER SUBMITTAL THE IN
COMMENTS AND MARKINGS DOCUMENT TO INTENDED IS IT FIELD.
THE IN COLLECTED DATA FROM DIRECTLY CREATED OUTPUT IS DRAWING THIS
EXCAVATION ACTIVITIES.
ALL AND ANY TO PRIOR CALLED BE TO 811 REQUIRES LAW STATE SERVICES.
CALL/811 ONE FOR REPLACEMENT A NEVER IS LOCATING UTILITY PRIVATE
https://gp-radar.com/terms-conditions
TERMS AND CONDITIONS THAT CAN BE VIEWED WITH THE LINK:
THE TO SUBJECT ARE FINDINGS ALL SITE. ON FEATURES SUBSURFACE OTHER
OR UTILITIES ALL LOCATE TO ABLE BE WILL IT GUARANTEE CANNOT GPRS 3.
IMAGERY PLACEMENT SHOULD BE CONSIDERED APPROXIMATE.
THE HOWEVER, ORDERED, IS CAD WHEN IMAGE THE ALIGN BETTER TO MADE
IS EFFORT AN FIELD. THE IN COLLECTED AS REMAIN DATA POINT AND LINE THE
WHILE INACCURATE OR OUTDATED, SHIFTED, SOMETIMES IS IMAGERY AERIAL 4.
SAN LIFTSTATION
SAN VAULT
P.I. VALVE
ELEC BOX
ELEC CABINET
ELEC MISC
ELEC PANEL
TRANSFORMER
COMM MISC
COMM POLE
SANITARY
WATER
UNKNOWN
STORM
FIRE WATER
SITE LIGHT
ELEC DUCT
ELECTRICAL
GAS
SITELIGHT
UTILITYPOLE
D= DEPTH
LINE CONTINUES
END OF INFO
SAN MANHOLE
CATCH BASIN
STRM MANHOLE
VALVE
HYDRANT
GAS METER
GAS VALVE
SCAN AREA
OBSTRUCTION
COMM
FENCE
STEAM
WTR STRUCT
UNK STRUCT
UNK DUCT
LANDSCAPE LIGHT
TRENCHDRAIN
STEAM MANHOLE
TRAF SIGN
SIGN
SEE NOTE #6 ABOVE.
THE SERVICE IS USED ON EVERY PROJECT IN ADDITION TO OUR OWN.
GPRS IS NOT AFFILIATED WITH 811 BUT DOES RECOMMEND THAT
0 40'20'
Know what'sbelow.
before you dig.Call
R
MISC POINT
SCAN PATH
SCAN PATH
SOLAR CALL BOX
D=2'-3'
D=2'-3'
D=2'-3'
MH21
D=1'-2'
D=1'-2'
D=0-1'
D=7'-8'
D=7'-8'
D=7'-8'
D=7'-8'
D=6'-7' D=5'-6'
D=7'-8'
D=9'-10'
D=1'-2'
D=3'-4'
D=1'-2'
D=3'-4' D=3'-4'
D=1'-2'
D=1'-2'
D=1'-2'
D=1'-2'
D=2'-3'
COMM & ELEC
D=2'-3'
COMM & ELEC
D=2'-3'
D=2'-3'
D=4'-5'
D=1'-2'
D=1'-2'
SCAN AREA
SCAN AREA
COMM DUCT
COMM MANHOLE
COMM CONDUIT
SCAN PATH
UNKN MANHOLE
UNKN MISC
ELEC MANHOLE
DATE
DRAWING NO. REV. 0
PROJECT MANAGER:
PREPARED FOR:
LOCATION:
GPRS UTILITY MAP
200 SPRINGS RD
TRIPLE C- THE AE GROUP
VA NEW ENGLAND HEALTHCARE SYSTEM
MATTHEW.CAERULIUS@GPRSINC.COM
MATTHEW CAERULIUS
617.655.4971
BEDFORD, MA 01730
8/30/2024
DISCLAIMER
LEGEND
FOR INFORMATION ONLY
C
U S
E R
S \A
D R
I A
N .K
O E
H N
\O N
E D
R I V
E
G P
R S
\P
R O
J E
C T
S \6
\C
A D
\6 E
X .D
G N
PURPOSES EXCEPT AS EXPRESSLY STATED HEREIN.
ANY FOR USED OR ON RELIED BE NOT MAY AND SURVEY LAND A NOT IS PDF
THIS SURVEYOR. LAND LICENSED A NOT IS GPRS SERVICES. ENGINEERING
OR SURVEYING, LAND GEOLOGICAL, GEOPHYSICAL, PROVIDE NOT DOES GPRS
5.
2.
1.
6.
FIELD WORK.
OF COMPLETION FOLLOWING EMAIL VIA SENT LETTER SUBMITTAL THE IN
COMMENTS AND MARKINGS DOCUMENT TO INTENDED IS IT FIELD.
THE IN COLLECTED DATA FROM DIRECTLY CREATED OUTPUT IS DRAWING THIS
EXCAVATION ACTIVITIES.
ALL AND ANY TO PRIOR CALLED BE TO 811 REQUIRES LAW STATE SERVICES.
CALL/811 ONE FOR REPLACEMENT A NEVER IS LOCATING UTILITY PRIVATE
https://gp-radar.com/terms-conditions
TERMS AND CONDITIONS THAT CAN BE VIEWED WITH THE LINK:
THE TO SUBJECT ARE FINDINGS ALL SITE. ON FEATURES SUBSURFACE OTHER
OR UTILITIES ALL LOCATE TO ABLE BE WILL IT GUARANTEE CANNOT GPRS 3.
IMAGERY PLACEMENT SHOULD BE CONSIDERED APPROXIMATE.
THE HOWEVER, ORDERED, IS CAD WHEN IMAGE THE ALIGN BETTER TO MADE
IS EFFORT AN FIELD. THE IN COLLECTED AS REMAIN DATA POINT AND LINE THE
WHILE INACCURATE OR OUTDATED, SHIFTED, SOMETIMES IS IMAGERY AERIAL 4.
SAN LIFTSTATION
SAN VAULT
P.I. VALVE
ELEC BOX
ELEC CABINET
ELEC MISC
ELEC PANEL
TRANSFORMER
COMM MISC
COMM POLE
SANITARY
WATER
UNKNOWN
STORM
FIRE WATER
SITE LIGHT
ELEC DUCT
ELECTRICAL
GAS
SITELIGHT
UTILITYPOLE
D= DEPTH
LINE CONTINUES
END OF INFO
SAN MANHOLE
CATCH BASIN
STRM MANHOLE
VALVE
HYDRANT
GAS METER
GAS VALVE
SCAN AREA
OBSTRUCTION
COMM
FENCE
STEAM
WTR STRUCT
UNK STRUCT
UNK DUCT
LANDSCAPE LIGHT
TRENCHDRAIN
STEAM MANHOLE
TRAF SIGN
SIGN
SEE NOTE #6 ABOVE.
THE SERVICE IS USED ON EVERY PROJECT IN ADDITION TO OUR OWN.
GPRS IS NOT AFFILIATED WITH 811 BUT DOES RECOMMEND THAT
0 40'20'
Know what'sbelow.
before you dig.Call
R
MISC POINT
U
P R
IN
G S R
D
SCAN PATH
SCAN PATH
SCAN PATH
SCAN PATH
NO OUTLET
N O O
U T
L E
T N
O O
U T
L E
T
NO OUTLET
STEAM CONTROL
STEAM CONTROL
F
IR
E B
O X
D=1'-2'
D=1'-2'
D=1'-2'
D=2'-3'
D=2'-3'
D=2'-3'
D=2'-3'
D=1'-2'
D=5'-6'
D=2'-3'
D=2'-3'
D=2'-3'
D=2'-3'
D=2'-3'
D=1'-2'
D=5'-6'
D=4'-5'
D=4'-5'
D
D=2'-3'
D=2'-3'
D=2'-3'
D=4'-5'
D=6'-7'
D
D
D
D
D
D=2'-3'
D=4'-5'
COMM DUCT
COMM MANHOLE
COMM CONDUIT
SCAN PATH
UNKN MANHOLE
UNKN MISC
ELEC MANHOLE
DATE
DRAWING NO. REV. 0
PROJECT MANAGER:
PREPARED FOR:
LOCATION:
GPRS UTILITY MAP
200 SPRINGS RD
TRIPLE C- THE AE GROUP
VA NEW ENGLAND HEALTHCARE SYSTEM
MATTHEW.CAERULIUS@GPRSINC.COM
MATTHEW CAERULIUS
617.655.4971
BEDFORD, MA 01730
8/30/2024
DISCLAIMER
LEGEND
FOR INFORMATION ONLY
C
U S
E R
S \A
D R
I A
N .K
O E
H N
\O N
E D
R I V
E
G P
R S
\P
R O
J E
C T
S \6
\C
A D
\6 E
X .D
G N
PURPOSES EXCEPT AS EXPRESSLY STATED HEREIN.
ANY FOR USED OR ON RELIED BE NOT MAY AND SURVEY LAND A NOT IS PDF
THIS SURVEYOR. LAND LICENSED A NOT IS GPRS SERVICES. ENGINEERING
OR SURVEYING, LAND GEOLOGICAL, GEOPHYSICAL, PROVIDE NOT DOES GPRS
5.
2.
1.
6.
FIELD WORK.
OF COMPLETION FOLLOWING EMAIL VIA SENT LETTER SUBMITTAL THE IN
COMMENTS AND MARKINGS DOCUMENT TO INTENDED IS IT FIELD.
THE IN COLLECTED DATA FROM DIRECTLY CREATED OUTPUT IS DRAWING THIS
EXCAVATION ACTIVITIES.
ALL AND ANY TO PRIOR CALLED BE TO 811 REQUIRES LAW STATE SERVICES.
CALL/811 ONE FOR REPLACEMENT A NEVER IS LOCATING UTILITY PRIVATE
https://gp-radar.com/terms-conditions
TERMS AND CONDITIONS THAT CAN BE VIEWED WITH THE LINK:
THE TO SUBJECT ARE FINDINGS ALL SITE. ON FEATURES SUBSURFACE OTHER
OR UTILITIES ALL LOCATE TO ABLE BE WILL IT GUARANTEE CANNOT GPRS 3.
IMAGERY PLACEMENT SHOULD BE CONSIDERED APPROXIMATE.
THE HOWEVER, ORDERED, IS CAD WHEN IMAGE THE ALIGN BETTER TO MADE
IS EFFORT AN FIELD. THE IN COLLECTED AS REMAIN DATA POINT AND LINE THE
WHILE INACCURATE OR OUTDATED, SHIFTED, SOMETIMES IS IMAGERY AERIAL 4.
SAN LIFTSTATION
SAN VAULT
P.I. VALVE
ELEC BOX
ELEC CABINET
ELEC MISC
ELEC PANEL
TRANSFORMER
COMM MISC
COMM POLE
SANITARY
WATER
UNKNOWN
STORM
FIRE WATER
SITE LIGHT
ELEC DUCT
ELECTRICAL
GAS
SITELIGHT
UTILITYPOLE
D= DEPTH
LINE CONTINUES
END OF INFO
SAN MANHOLE
CATCH BASIN
STRM MANHOLE
VALVE
HYDRANT
GAS METER
GAS VALVE
SCAN AREA
OBSTRUCTION
COMM
FENCE
STEAM
WTR STRUCT
UNK STRUCT
UNK DUCT
LANDSCAPE LIGHT
TRENCHDRAIN
STEAM MANHOLE
TRAF SIGN
SIGN
SEE NOTE #6 ABOVE.
THE SERVICE IS USED ON EVERY PROJECT IN ADDITION TO OUR OWN.
GPRS IS NOT AFFILIATED WITH 811 BUT DOES RECOMMEND THAT
0 40'20'
Know what'sbelow.
before you dig.Call
R
MISC POINT
SCAN PATH
D=2'-3'
D=2'-3'
MH20
MH19
D=7'-8'
D=5'-6'
D=1'-2'
D
D=1'-2'
D=1'-2'
D=1'-2'
D=7'-8'
D=7'-8'
D=4'-5'
D=4'-5'
D=4'-5' D=4'-5'
D=1'-2'
D=2'-3'
NO ACCESS
MH18
D=2'-3'
D=2'-3'
D=1'-2' D=1'-2'
D=1'-2'
POST
BUTTON
D=1'-2'
D=1'-2'
COMM DUCT
COMM MANHOLE
COMM CONDUIT
SCAN PATH
UNKN MANHOLE
UNKN MISC
ELEC MANHOLE
DATE
DRAWING NO. REV. 0
PROJECT MANAGER:
PREPARED FOR:
LOCATION:
GPRS UTILITY MAP
200 SPRINGS RD
TRIPLE C- THE AE GROUP
VA NEW ENGLAND HEALTHCARE SYSTEM
MATTHEW.CAERULIUS@GPRSINC.COM
MATTHEW CAERULIUS
617.655.4971
BEDFORD, MA 01730
8/30/2024
DISCLAIMER
LEGEND
FOR INFORMATION ONLY
C
U S
E R
S \A
D R
I A
N .K
O E
H N
\O N
E D
R I V
E
G P
R S
\P
R O
J E
C T
S \6
\C
A D
\6 E
X .D
G N
PURPOSES EXCEPT AS EXPRESSLY STATED HEREIN.
ANY FOR USED OR ON RELIED BE NOT MAY AND SURVEY LAND A NOT IS PDF
THIS SURVEYOR. LAND LICENSED A NOT IS GPRS SERVICES. ENGINEERING
OR SURVEYING, LAND GEOLOGICAL, GEOPHYSICAL, PROVIDE NOT DOES GPRS
5.
2.
1.
6.
FIELD WORK.
OF COMPLETION FOLLOWING EMAIL VIA SENT LETTER SUBMITTAL THE IN
COMMENTS AND MARKINGS DOCUMENT TO INTENDED IS IT FIELD.
THE IN COLLECTED DATA FROM DIRECTLY CREATED OUTPUT IS DRAWING THIS
EXCAVATION ACTIVITIES.
ALL AND ANY TO PRIOR CALLED BE TO 811 REQUIRES LAW STATE SERVICES.
CALL/811 ONE FOR REPLACEMENT A NEVER IS LOCATING UTILITY PRIVATE
https://gp-radar.com/terms-conditions
TERMS AND CONDITIONS THAT CAN BE VIEWED WITH THE LINK:
THE TO SUBJECT ARE FINDINGS ALL SITE. ON FEATURES SUBSURFACE OTHER
OR UTILITIES ALL LOCATE TO ABLE BE WILL IT GUARANTEE CANNOT GPRS 3.
IMAGERY PLACEMENT SHOULD BE CONSIDERED APPROXIMATE.
THE HOWEVER, ORDERED, IS CAD WHEN IMAGE THE ALIGN BETTER TO MADE
IS EFFORT AN FIELD. THE IN COLLECTED AS REMAIN DATA POINT AND LINE THE
WHILE INACCURATE OR OUTDATED, SHIFTED, SOMETIMES IS IMAGERY AERIAL 4.
SAN LIFTSTATION
SAN VAULT
P.I. VALVE
ELEC BOX
ELEC CABINET
ELEC MISC
ELEC PANEL
TRANSFORMER
COMM MISC
COMM POLE
SANITARY
WATER
UNKNOWN
STORM
FIRE WATER
SITE LIGHT
ELEC DUCT
ELECTRICAL
GAS
SITELIGHT
UTILITYPOLE
D= DEPTH
LINE CONTINUES
END OF INFO
SAN MANHOLE
CATCH BASIN
STRM MANHOLE
VALVE
HYDRANT
GAS METER
GAS VALVE
SCAN AREA
OBSTRUCTION
COMM
FENCE
STEAM
WTR STRUCT
UNK STRUCT
UNK DUCT
LANDSCAPE LIGHT
TRENCHDRAIN
STEAM MANHOLE
TRAF SIGN
SIGN
SEE NOTE #6 ABOVE.
THE SERVICE IS USED ON EVERY PROJECT IN ADDITION TO OUR OWN.
GPRS IS NOT AFFILIATED WITH 811 BUT DOES RECOMMEND THAT
0 40'20'
Know what'sbelow.
before you dig.Call
R
MISC POINT
R
IN
G S R
D
E D
IT
H
N R
O G
E R
S W
A Y
SCAN PATH
SCAN PATH
SCAN PATH
SCAN PATH
RISER
SOLAR
POTENTIAL WATER TRENCH
D=2'-3'
D=2'-3' D=2'-3'
D=4'-5'
D=3'-4'
D-2'-3'
D=4'-5'
D=1'-2'
D=4'-5'
D=4'-5'
D=4'-5'
D=4'-5'
D=9'-10'
D=9'-10'
D=1'-2'
D=1'-2'
D=0-1'
D=1'-2' D=2'-3'
D
D=1'-2'
D=2'-3'
D=5'-6'
D=5'-6'
D=5'-6'
NO ACCESS
MH17
NO ACCESS
MH16
D=2'-3'
D=2'-3'
D=2'-3'
D=2'-3'
D=2'-3'
D=3'-4'
D=1'-2'
D=1'-2'
COMM & ELEC
D=1'-2'
D=2'-3'
D=2'-3'
D=1'-2' D=1'-2'
D
D=2'-3'
D=2'-3'
D=2'-3'
D=1'-2'
D=1'-2'
NO ACCESS
MH14
D=1'-2'
D=1'-2'
D=1'-2'
D=1'-2'
D=1'-2'
COMM & ELEC
COMM DUCT
COMM MANHOLE
COMM CONDUIT
SCAN PATH
UNKN MANHOLE
UNKN MISC
ELEC MANHOLE
DATE
DRAWING NO. REV. 0
PROJECT MANAGER:
PREPARED FOR:
LOCATION:
GPRS UTILITY MAP
200 SPRINGS RD
TRIPLE C- THE AE GROUP
VA NEW ENGLAND HEALTHCARE SYSTEM
MATTHEW.CAERULIUS@GPRSINC.COM
MATTHEW CAERULIUS
617.655.4971
BEDFORD, MA 01730
8/30/2024
DISCLAIMER
LEGEND
FOR INFORMATION ONLY
C
U S
E R
S \A
D R
I A
N .K
O E
H N
\O N
E D
R I V
E
G P
R S
\P
R O
J E
C T
S \6
\C
A D
\6 E
X .D
G N
PURPOSES EXCEPT AS EXPRESSLY STATED HEREIN.
ANY FOR USED OR ON RELIED BE NOT MAY AND SURVEY LAND A NOT IS PDF
THIS SURVEYOR. LAND LICENSED A NOT IS GPRS SERVICES. ENGINEERING
OR SURVEYING, LAND GEOLOGICAL, GEOPHYSICAL, PROVIDE NOT DOES GPRS
5.
2.
1.
6.
FIELD WORK.
OF COMPLETION FOLLOWING EMAIL VIA SENT LETTER SUBMITTAL THE IN
COMMENTS AND MARKINGS DOCUMENT TO INTENDED IS IT FIELD.
THE IN COLLECTED DATA FROM DIRECTLY CREATED OUTPUT IS DRAWING THIS
EXCAVATION ACTIVITIES.
ALL AND ANY TO PRIOR CALLED BE TO 811 REQUIRES LAW STATE SERVICES.
CALL/811 ONE FOR REPLACEMENT A NEVER IS LOCATING UTILITY PRIVATE
https://gp-radar.com/terms-conditions
TERMS AND CONDITIONS THAT CAN BE VIEWED WITH THE LINK:
THE TO SUBJECT ARE FINDINGS ALL SITE. ON FEATURES SUBSURFACE OTHER
OR UTILITIES ALL LOCATE TO ABLE BE WILL IT GUARANTEE CANNOT GPRS 3.
IMAGERY PLACEMENT SHOULD BE CONSIDERED APPROXIMATE.
THE HOWEVER, ORDERED, IS CAD WHEN IMAGE THE ALIGN BETTER TO MADE
IS EFFORT AN FIELD. THE IN COLLECTED AS REMAIN DATA POINT AND LINE THE
WHILE INACCURATE OR OUTDATED, SHIFTED, SOMETIMES IS IMAGERY AERIAL 4.
SAN LIFTSTATION
SAN VAULT
P.I. VALVE
ELEC BOX
ELEC CABINET
ELEC MISC
ELEC PANEL
TRANSFORMER
COMM MISC
COMM POLE
SANITARY
WATER
UNKNOWN
STORM
FIRE WATER
SITE LIGHT
ELEC DUCT
ELECTRICAL
GAS
SITELIGHT
UTILITYPOLE
D= DEPTH
LINE CONTINUES
END OF INFO
SAN MANHOLE
CATCH BASIN
STRM MANHOLE
VALVE
HYDRANT
GAS METER
GAS VALVE
SCAN AREA
OBSTRUCTION
COMM
FENCE
STEAM
WTR STRUCT
UNK STRUCT
UNK DUCT
LANDSCAPE LIGHT
TRENCHDRAIN
STEAM MANHOLE
TRAF SIGN
SIGN
SEE NOTE #6 ABOVE.
THE SERVICE IS USED ON EVERY PROJECT IN ADDITION TO OUR OWN.
GPRS IS NOT AFFILIATED WITH 811 BUT DOES RECOMMEND THAT
0 40'20'
Know what'sbelow.
before you dig.Call
R
MISC POINT
D=1'-2'
D=1'-2'
D=1'-2'
D=2'-3'
D=1'-2'
D=1'-2'
D=1'-2'
NO ACCESS
MH15
D=1'-2'
D=1'-2'
D=4'-5'
D=3'-4'
D=3'-4'
D=3'-4'
D=3'-4'
D=3'-4'
D=5'-6'
D=5'-6'
COMM DUCT
COMM MANHOLE
COMM CONDUIT
SCAN PATH
UNKN MANHOLE
UNKN MISC
ELEC MANHOLE
DATE
DRAWING NO. REV. 0
PROJECT MANAGER:
PREPARED FOR:
LOCATION:
GPRS UTILITY MAP
200 SPRINGS RD
TRIPLE C- THE AE GROUP
VA NEW ENGLAND HEALTHCARE SYSTEM
MATTHEW.CAERULIUS@GPRSINC.COM
MATTHEW CAERULIUS
617.655.4971
BEDFORD, MA 01730
8/30/2024
DISCLAIMER
LEGEND
FOR INFORMATION ONLY
C
U S
E R
S \A
D R
I A
N .K
O E
H N
\O N
E D
R I V
E
G P
R S
\P
R O
J E
C T
S \6
\C
A D
\6 E
X .D
G N
PURPOSES EXCEPT AS EXPRESSLY STATED HEREIN.
ANY FOR USED OR ON RELIED BE NOT MAY AND SURVEY LAND A NOT IS PDF
THIS SURVEYOR. LAND LICENSED A NOT IS GPRS SERVICES. ENGINEERING
OR SURVEYING, LAND GEOLOGICAL, GEOPHYSICAL, PROVIDE NOT DOES GPRS
5.
2.
1.
6.
FIELD WORK.
OF COMPLETION FOLLOWING EMAIL VIA SENT LETTER SUBMITTAL THE IN
COMMENTS AND MARKINGS DOCUMENT TO INTENDED IS IT FIELD.
THE IN COLLECTED DATA FROM DIRECTLY CREATED OUTPUT IS DRAWING THIS
EXCAVATION ACTIVITIES.
ALL AND ANY TO PRIOR CALLED BE TO 811 REQUIRES LAW STATE SERVICES.
CALL/811 ONE FOR REPLACEMENT A NEVER IS LOCATING UTILITY PRIVATE
https://gp-radar.com/terms-conditions
TERMS AND CONDITIONS THAT CAN BE VIEWED WITH THE LINK:
THE TO SUBJECT ARE FINDINGS ALL SITE. ON FEATURES SUBSURFACE OTHER
OR UTILITIES ALL LOCATE TO ABLE BE WILL IT GUARANTEE CANNOT GPRS 3.
IMAGERY PLACEMENT SHOULD BE CONSIDERED APPROXIMATE.
THE HOWEVER, ORDERED, IS CAD WHEN IMAGE THE ALIGN BETTER TO MADE
IS EFFORT AN FIELD. THE IN COLLECTED AS REMAIN DATA POINT AND LINE THE
WHILE INACCURATE OR OUTDATED, SHIFTED, SOMETIMES IS IMAGERY AERIAL 4.
SAN LIFTSTATION
SAN VAULT
P.I. VALVE
ELEC BOX
ELEC CABINET
ELEC MISC
ELEC PANEL
TRANSFORMER
COMM MISC
COMM POLE
SANITARY
WATER
UNKNOWN
STORM
FIRE WATER
SITE LIGHT
ELEC DUCT
ELECTRICAL
GAS
SITELIGHT
UTILITYPOLE
D= DEPTH
LINE CONTINUES
END OF INFO
SAN MANHOLE
CATCH BASIN
STRM MANHOLE
VALVE
HYDRANT
GAS METER
GAS VALVE
SCAN AREA
OBSTRUCTION
COMM
FENCE
STEAM
WTR STRUCT
UNK STRUCT
UNK DUCT
LANDSCAPE LIGHT
TRENCHDRAIN
STEAM MANHOLE
TRAF SIGN
SIGN
SEE NOTE #6 ABOVE.
THE SERVICE IS USED ON EVERY PROJECT IN ADDITION TO OUR OWN.
GPRS IS NOT AFFILIATED WITH 811 BUT DOES RECOMMEND THAT
0 40'20'
Know what'sbelow.
before you dig.Call
R
MISC POINT
SCAN PATH
SCAN PATH
NO ACCESS
NO ACCESS
NO ACCESS
D=1'-2'
D=2'-3'
D=2'-3'
D=2'-3'
D=2'-3'
D=2'-3'
D=5'-6'
D=3'-4'
D=3'-4'
D=1'-2'
D=1'-2'
D=2'-3'
D=2'-3'
D=2'-3'
D=2'-3'
D=2'-3'
D=2'-3'
D=5'-6'
D=5'-6'
D=6'-7'
D
D=1'-2'
D=1'-2'
D=4'-5'
D=4'-5'
D=4'-5'
D=1'-2'
D=1'-2'
D=2'-3'
D=1'-2'
D=1'-2'
D=1'-2'
D=1'-2'
D=1'-2'
D=2'-3'
D=1'-2'
D=1'-2'
D=1'-2'
D=1'-2'
D=1'-2'
D=4'-5'
D=4'-5'
D=3'-4'
D=3'-4'
D=1'-2'
D=1'-2'
D=1'-2'
D=1'-2'
D=1'-2'
D=1'-2'
NO ACCESS
MH14
D=4'-5'
D=5'-6'
D=1'-2'
COMM DUCT
COMM MANHOLE
COMM CONDUIT
SCAN PATH
UNKN MANHOLE
UNKN MISC
ELEC MANHOLE
DATE
DRAWING NO. REV. 0
PROJECT MANAGER:
PREPARED FOR:
LOCATION:
GPRS UTILITY MAP
200 SPRINGS RD
TRIPLE C- THE AE GROUP
VA NEW ENGLAND HEALTHCARE SYSTEM
MATTHEW.CAERULIUS@GPRSINC.COM
MATTHEW CAERULIUS
617.655.4971
BEDFORD, MA 01730
8/30/2024
DISCLAIMER
LEGEND
FOR INFORMATION ONLY
C
U S
E R
S \A
D R
I A
N .K
O E
H N
\O N
E D
R I V
E
G P
R S
\P
R O
J E
C T
S \6
\C
A D
\6 E
X .D
G N
PURPOSES EXCEPT AS EXPRESSLY STATED HEREIN.
ANY FOR USED OR ON RELIED BE NOT MAY AND SURVEY LAND A NOT IS PDF
THIS SURVEYOR. LAND LICENSED A NOT IS GPRS SERVICES. ENGINEERING
OR SURVEYING, LAND GEOLOGICAL, GEOPHYSICAL, PROVIDE NOT DOES GPRS
5.
2.
1.
6.
FIELD WORK.
OF COMPLETION FOLLOWING EMAIL VIA SENT LETTER SUBMITTAL THE IN
COMMENTS AND MARKINGS DOCUMENT TO INTENDED IS IT FIELD.
THE IN COLLECTED DATA FROM DIRECTLY CREATED OUTPUT IS DRAWING THIS
EXCAVATION ACTIVITIES.
ALL AND ANY TO PRIOR CALLED BE TO 811 REQUIRES LAW STATE SERVICES.
CALL/811 ONE FOR REPLACEMENT A NEVER IS LOCATING UTILITY PRIVATE
https://gp-radar.com/terms-conditions
TERMS AND CONDITIONS THAT CAN BE VIEWED WITH THE LINK:
THE TO SUBJECT ARE FINDINGS ALL SITE. ON FEATURES SUBSURFACE OTHER
OR UTILITIES ALL LOCATE TO ABLE BE WILL IT GUARANTEE CANNOT GPRS 3.
IMAGERY PLACEMENT SHOULD BE CONSIDERED APPROXIMATE.
THE HOWEVER, ORDERED, IS CAD WHEN IMAGE THE ALIGN BETTER TO MADE
IS EFFORT AN FIELD. THE IN COLLECTED AS REMAIN DATA POINT AND LINE THE
WHILE INACCURATE OR OUTDATED, SHIFTED, SOMETIMES IS IMAGERY AERIAL 4.
SAN LIFTSTATION
SAN VAULT
P.I. VALVE
ELEC BOX
ELEC CABINET
ELEC MISC
ELEC PANEL
TRANSFORMER
COMM MISC
COMM POLE
SANITARY
WATER
UNKNOWN
STORM
FIRE WATER
SITE LIGHT
ELEC DUCT
ELECTRICAL
GAS
SITELIGHT
UTILITYPOLE
D= DEPTH
LINE CONTINUES
END OF INFO
SAN MANHOLE
CATCH BASIN
STRM MANHOLE
VALVE
HYDRANT
GAS METER
GAS VALVE
SCAN AREA
OBSTRUCTION
COMM
FENCE
STEAM
WTR STRUCT
UNK STRUCT
UNK DUCT
LANDSCAPE LIGHT
TRENCHDRAIN
STEAM MANHOLE
TRAF SIGN
SIGN
SEE NOTE #6 ABOVE.
THE SERVICE IS USED ON EVERY PROJECT IN ADDITION TO OUR OWN.
GPRS IS NOT AFFILIATED WITH 811 BUT DOES RECOMMEND THAT
0 40'20'
Know what'sbelow.
before you dig.Call
R
MISC POINT
U
R
IN
G S R
D
SCAN PATH
D=1'-2'
D=2'-3'
D=1'-2'
D=1'-2'
NO ACCESS
MH8
NO ACCESS
MH9
D=3'-4'
COMM DUCT
COMM MANHOLE
COMM CONDUIT
SCAN PATH
UNKN MANHOLE
UNKN MISC
ELEC MANHOLE
DATE
DRAWING NO. REV. 0
PROJECT MANAGER:
PREPARED FOR:
LOCATION:
GPRS UTILITY MAP
200 SPRINGS RD
TRIPLE C- THE AE GROUP
VA NEW ENGLAND HEALTHCARE SYSTEM
MATTHEW.CAERULIUS@GPRSINC.COM
MATTHEW CAERULIUS
617.655.4971
BEDFORD, MA 01730
8/30/2024
DISCLAIMER
LEGEND
FOR INFORMATION ONLY
C
U S
E R
S \A
D R
I A
N .K
O E
H N
\O N
E D
R I V
E
G P
R S
\P
R O
J E
C T
S \6
\C
A D
\6 E
X .D
G N
PURPOSES EXCEPT AS EXPRESSLY STATED HEREIN.
ANY FOR USED OR ON RELIED BE NOT MAY AND SURVEY LAND A NOT IS PDF
THIS SURVEYOR. LAND LICENSED A NOT IS GPRS SERVICES. ENGINEERING
OR SURVEYING, LAND GEOLOGICAL, GEOPHYSICAL, PROVIDE NOT DOES GPRS
5.
2.
1.
6.
FIELD WORK.
OF COMPLETION FOLLOWING EMAIL VIA SENT LETTER SUBMITTAL THE IN
COMMENTS AND MARKINGS DOCUMENT TO INTENDED IS IT FIELD.
THE IN COLLECTED DATA FROM DIRECTLY CREATED OUTPUT IS DRAWING THIS
EXCAVATION ACTIVITIES.
ALL AND ANY TO PRIOR CALLED BE TO 811 REQUIRES LAW STATE SERVICES.
CALL/811 ONE FOR REPLACEMENT A NEVER IS LOCATING UTILITY PRIVATE
https://gp-radar.com/terms-conditions
TERMS AND CONDITIONS THAT CAN BE VIEWED WITH THE LINK:
THE TO SUBJECT ARE FINDINGS ALL SITE. ON FEATURES SUBSURFACE OTHER
OR UTILITIES ALL LOCATE TO ABLE BE WILL IT GUARANTEE CANNOT GPRS 3.
IMAGERY PLACEMENT SHOULD BE CONSIDERED APPROXIMATE.
THE HOWEVER, ORDERED, IS CAD WHEN IMAGE THE ALIGN BETTER TO MADE
IS EFFORT AN FIELD. THE IN COLLECTED AS REMAIN DATA POINT AND LINE THE
WHILE INACCURATE OR OUTDATED, SHIFTED, SOMETIMES IS IMAGERY AERIAL 4.
SAN LIFTSTATION
SAN VAULT
P.I. VALVE
ELEC BOX
ELEC CABINET
ELEC MISC
ELEC PANEL
TRANSFORMER
COMM MISC
COMM POLE
SANITARY
WATER
UNKNOWN
STORM
FIRE WATER
SITE LIGHT
ELEC DUCT
ELECTRICAL
GAS
SITELIGHT
UTILITYPOLE
D= DEPTH
LINE CONTINUES
END OF INFO
SAN MANHOLE
CATCH BASIN
STRM MANHOLE
VALVE
HYDRANT
GAS METER
GAS VALVE
SCAN AREA
OBSTRUCTION
COMM
FENCE
STEAM
WTR STRUCT
UNK STRUCT
UNK DUCT
LANDSCAPE LIGHT
TRENCHDRAIN
STEAM MANHOLE
TRAF SIGN
SIGN
SEE NOTE #6 ABOVE.
THE SERVICE IS USED ON EVERY PROJECT IN ADDITION TO OUR OWN.
GPRS IS NOT AFFILIATED WITH 811 BUT DOES RECOMMEND THAT
0 40'20'
Know what'sbelow.
before you dig.Call
R
MISC POINT
NO ACCESS
D=9'-10'
D=6'-7'
D=9'-10'
D=1'-2'
ELEC LINE
COMM DUCT
COMM MANHOLE
COMM CONDUIT
SCAN PATH
UNKN MANHOLE
UNKN MISC
ELEC MANHOLE
DATE
DRAWING NO. REV. 0
PROJECT MANAGER:
PREPARED FOR:
LOCATION:
GPRS UTILITY MAP
200 SPRINGS RD
TRIPLE C- THE AE GROUP
VA NEW ENGLAND HEALTHCARE SYSTEM
MATTHEW.CAERULIUS@GPRSINC.COM
MATTHEW CAERULIUS
617.655.4971
BEDFORD, MA 01730
8/30/2024
DISCLAIMER
LEGEND
FOR INFORMATION ONLY
C
U S
E R
S \A
D R
I A
N .K
O E
H N
\O N
E D
R I V
E
G P
R S
\P
R O
J E
C T
S \6
\C
A D
\6 E
X .D
G N
PURPOSES EXCEPT AS EXPRESSLY STATED HEREIN.
ANY FOR USED OR ON RELIED BE NOT MAY AND SURVEY LAND A NOT IS PDF
THIS SURVEYOR. LAND LICENSED A NOT IS GPRS SERVICES. ENGINEERING
OR SURVEYING, LAND GEOLOGICAL, GEOPHYSICAL, PROVIDE NOT DOES GPRS
5.
2.
1.
6.
FIELD WORK.
OF COMPLETION FOLLOWING EMAIL VIA SENT LETTER SUBMITTAL THE IN
COMMENTS AND MARKINGS DOCUMENT TO INTENDED IS IT FIELD.
THE IN COLLECTED DATA FROM DIRECTLY CREATED OUTPUT IS DRAWING THIS
EXCAVATION ACTIVITIES.
ALL AND ANY TO PRIOR CALLED BE TO 811 REQUIRES LAW STATE SERVICES.
CALL/811 ONE FOR REPLACEMENT A NEVER IS LOCATING UTILITY PRIVATE
https://gp-radar.com/terms-conditions
TERMS AND CONDITIONS THAT CAN BE VIEWED WITH THE LINK:
THE TO SUBJECT ARE FINDINGS ALL SITE. ON FEATURES SUBSURFACE OTHER
OR UTILITIES ALL LOCATE TO ABLE BE WILL IT GUARANTEE CANNOT GPRS 3.
IMAGERY PLACEMENT SHOULD BE CONSIDERED APPROXIMATE.
THE HOWEVER, ORDERED, IS CAD WHEN IMAGE THE ALIGN BETTER TO MADE
IS EFFORT AN FIELD. THE IN COLLECTED AS REMAIN DATA POINT AND LINE THE
WHILE INACCURATE OR OUTDATED, SHIFTED, SOMETIMES IS IMAGERY AERIAL 4.
SAN LIFTSTATION
SAN VAULT
P.I. VALVE
ELEC BOX
ELEC CABINET
ELEC MISC
ELEC PANEL
TRANSFORMER
COMM MISC
COMM POLE
SANITARY
WATER
UNKNOWN
STORM
FIRE WATER
SITE LIGHT
ELEC DUCT
ELECTRICAL
GAS
SITELIGHT
UTILITYPOLE
D= DEPTH
LINE CONTINUES
END OF INFO
SAN MANHOLE
CATCH BASIN
STRM MANHOLE
VALVE
HYDRANT
GAS METER
GAS VALVE
SCAN AREA
OBSTRUCTION
COMM
FENCE
STEAM
WTR STRUCT
UNK STRUCT
UNK DUCT
LANDSCAPE LIGHT
TRENCHDRAIN
STEAM MANHOLE
TRAF SIGN
SIGN
SEE NOTE #6 ABOVE.
THE SERVICE IS USED ON EVERY PROJECT IN ADDITION TO OUR OWN.
GPRS IS NOT AFFILIATED WITH 811 BUT DOES RECOMMEND THAT
0 40'20'
Know what'sbelow.
before you dig.Call
R
MISC POINT
U
P R
IN
G S R
D
SCAN PATH
SCAN PATH
SCAN PATH
N O A
C C
E S
S
D=1'-2'
NO ACCESS
MH7
D=3'-4'
D=3'-4'
D=3'-4'
D=3'-4'
D=3'-4'
BLDG 30
D=2'-3'
D=2'-3'
D=2'-3'
D=0-1'
D=4'-5'
D=4'-5'
D
D=3'-4'
D=2'-3'
SERVICE
D
S E
R V
IC
E
NO ACCESS
MH5
NO ACCESS
MH6
D=3'-4'
TREES
TREES
D
D '-7
COMM DUCT
COMM MANHOLE
COMM CONDUIT
SCAN PATH
UNKN MANHOLE
UNKN MISC
ELEC MANHOLE
DATE
DRAWING NO. REV. 0
PROJECT MANAGER:
PREPARED FOR:
LOCATION:
GPRS UTILITY MAP
200 SPRINGS RD
TRIPLE C- THE AE GROUP
VA NEW ENGLAND HEALTHCARE SYSTEM
MATTHEW.CAERULIUS@GPRSINC.COM
MATTHEW CAERULIUS
617.655.4971
BEDFORD, MA 01730
8/30/2024
DISCLAIMER
LEGEND
FOR INFORMATION ONLY
C
U S
E R
S \A
D R
I A
N .K
O E
H N
\O N
E D
R I V
E
G P
R S
\P
R O
J E
C T
S \6
\C
A D
\6 E
X .D
G N
PURPOSES EXCEPT AS EXPRESSLY STATED HEREIN.
ANY FOR USED OR ON RELIED BE NOT MAY AND SURVEY LAND A NOT IS PDF
THIS SURVEYOR. LAND LICENSED A NOT IS GPRS SERVICES. ENGINEERING
OR SURVEYING, LAND GEOLOGICAL, GEOPHYSICAL, PROVIDE NOT DOES GPRS
5.
2.
1.
6.
FIELD WORK.
OF COMPLETION FOLLOWING EMAIL VIA SENT LETTER SUBMITTAL THE IN
COMMENTS AND MARKINGS DOCUMENT TO INTENDED IS IT FIELD.
THE IN COLLECTED DATA FROM DIRECTLY CREATED OUTPUT IS DRAWING THIS
EXCAVATION ACTIVITIES.
ALL AND ANY TO PRIOR CALLED BE TO 811 REQUIRES LAW STATE SERVICES.
CALL/811 ONE FOR REPLACEMENT A NEVER IS LOCATING UTILITY PRIVATE
https://gp-radar.com/terms-conditions
TERMS AND CONDITIONS THAT CAN BE VIEWED WITH THE LINK:
THE TO SUBJECT ARE FINDINGS ALL SITE. ON FEATURES SUBSURFACE OTHER
OR UTILITIES ALL LOCATE TO ABLE BE WILL IT GUARANTEE CANNOT GPRS 3.
IMAGERY PLACEMENT SHOULD BE CONSIDERED APPROXIMATE.
THE HOWEVER, ORDERED, IS CAD WHEN IMAGE THE ALIGN BETTER TO MADE
IS EFFORT AN FIELD. THE IN COLLECTED AS REMAIN DATA POINT AND LINE THE
WHILE INACCURATE OR OUTDATED, SHIFTED, SOMETIMES IS IMAGERY AERIAL 4.
SAN LIFTSTATION
SAN VAULT
P.I. VALVE
ELEC BOX
ELEC CABINET
ELEC MISC
ELEC PANEL
TRANSFORMER
COMM MISC
COMM POLE
SANITARY
WATER
UNKNOWN
STORM
FIRE WATER
SITE LIGHT
ELEC DUCT
ELECTRICAL
GAS
SITELIGHT
UTILITYPOLE
D= DEPTH
LINE CONTINUES
END OF INFO
SAN MANHOLE
CATCH BASIN
STRM MANHOLE
VALVE
HYDRANT
GAS METER
GAS VALVE
SCAN AREA
OBSTRUCTION
COMM
FENCE
STEAM
WTR STRUCT
UNK STRUCT
UNK DUCT
LANDSCAPE LIGHT
TRENCHDRAIN
STEAM MANHOLE
TRAF SIGN
SIGN
SEE NOTE #6 ABOVE.
THE SERVICE IS USED ON EVERY PROJECT IN ADDITION TO OUR OWN.
GPRS IS NOT AFFILIATED WITH 811 BUT DOES RECOMMEND THAT
0 40'20'
Know what'sbelow.
before you dig.Call
R
MISC POINT
U
P R
IN
G S R
D
SCAN PATH
SCAN PATH
D=3'-4' D=2'-3'
D=4'-5'
D=4'-5'
D=6'-7'
D=4'-5'
D=6'-7'
D=6'-7'
D=4'-5'
D=6'-7'
D=6'-7'
D=4'-5'
D=4'-5'
D=4'-5'
D=3'-4'
D=3'-4'
D=3'-4'
D=1'-2'
D=1'-2'
D=1'-2'
D=1'-2'
D=1'-2'
D=1'-2'
D=1'-2'
D=4'-5'
D=4'-5'
D=2'-3'
D=2'-3'
D=2'-3'
SERVICE
NO ACCESS
MH2
ACCESS
NO MH1
NO ACCESS
MH4
MH3
D=2'-3'
D=3'-4'
D=3'-4'
TREES
D=6'-7'
D=6'-7'
COMM DUCT
COMM MANHOLE
COMM CONDUIT
SCAN PATH
UNKN MANHOLE
UNKN MISC
ELEC MANHOLE
DATE
DRAWING NO. REV. 0
PROJECT MANAGER:
PREPARED FOR:
LOCATION:
GPRS UTILITY MAP
200 SPRINGS RD
TRIPLE C- THE AE GROUP
VA NEW ENGLAND HEALTHCARE SYSTEM
MATTHEW.CAERULIUS@GPRSINC.COM
MATTHEW CAERULIUS
617.655.4971
BEDFORD, MA 01730
8/30/2024
DISCLAIMER
LEGEND
FOR INFORMATION ONLY
C
U S
E R
S \A
D R
I A
N .K
O E
H N
\O N
E D
R I V
E
G P
R S
\P
R O
J E
C T
S \6
\C
A D
\6 E
X .D
G N
PURPOSES EXCEPT AS EXPRESSLY STATED HEREIN.
ANY FOR USED OR ON RELIED BE NOT MAY AND SURVEY LAND A NOT IS PDF
THIS SURVEYOR. LAND LICENSED A NOT IS GPRS SERVICES. ENGINEERING
OR SURVEYING, LAND GEOLOGICAL, GEOPHYSICAL, PROVIDE NOT DOES GPRS
5.
2.
1.
6.
FIELD WORK.
OF COMPLETION FOLLOWING EMAIL VIA SENT LETTER SUBMITTAL THE IN
COMMENTS AND MARKINGS DOCUMENT TO INTENDED IS IT FIELD.
THE IN COLLECTED DATA FROM DIRECTLY CREATED OUTPUT IS DRAWING THIS
EXCAVATION ACTIVITIES.
ALL AND ANY TO PRIOR CALLED BE TO 811 REQUIRES LAW STATE SERVICES.
CALL/811 ONE FOR REPLACEMENT A NEVER IS LOCATING UTILITY PRIVATE
https://gp-radar.com/terms-conditions
TERMS AND CONDITIONS THAT CAN BE VIEWED WITH THE LINK:
THE TO SUBJECT ARE FINDINGS ALL SITE. ON FEATURES SUBSURFACE OTHER
OR UTILITIES ALL LOCATE TO ABLE BE WILL IT GUARANTEE CANNOT GPRS 3.
IMAGERY PLACEMENT SHOULD BE CONSIDERED APPROXIMATE.
THE HOWEVER, ORDERED, IS CAD WHEN IMAGE THE ALIGN BETTER TO MADE
IS EFFORT AN FIELD. THE IN COLLECTED AS REMAIN DATA POINT AND LINE THE
WHILE INACCURATE OR OUTDATED, SHIFTED, SOMETIMES IS IMAGERY AERIAL 4.
SAN LIFTSTATION
SAN VAULT
P.I. VALVE
ELEC BOX
ELEC CABINET
ELEC MISC
ELEC PANEL
TRANSFORMER
COMM MISC
COMM POLE
SANITARY
WATER
UNKNOWN
STORM
FIRE WATER
SITE LIGHT
ELEC DUCT
ELECTRICAL
GAS
SITELIGHT
UTILITYPOLE
D= DEPTH
LINE CONTINUES
END OF INFO
SAN MANHOLE
CATCH BASIN
STRM MANHOLE
VALVE
HYDRANT
GAS METER
GAS VALVE
SCAN AREA
OBSTRUCTION
COMM
FENCE
STEAM
WTR STRUCT
UNK STRUCT
UNK DUCT
LANDSCAPE LIGHT
TRENCHDRAIN
STEAM MANHOLE
TRAF SIGN
SIGN
SEE NOTE #6 ABOVE.
THE SERVICE IS USED ON EVERY PROJECT IN ADDITION TO OUR OWN.
GPRS IS NOT AFFILIATED WITH 811 BUT DOES RECOMMEND THAT
0 40'20'
Know what'sbelow.
before you dig.Call
R
MISC POINT
This page intentionally left blank.
Proposal Cover Page Report Cover Page
VAMC EHRM Bedford, MA
Geotechnical Engineering Report
Bedford, Massachusetts
February 10, 2025 | Terracon Project No. J4245018
Prepared for:
Triple C – The A & E Group, LLC 410 East Grand Avenue, Suite 201C Laramie, WY 82070-3701
80 Tower Office Park Woburn, MA 01801 P (603) 647-9700
Terracon.com
Facilities | Environmental | Geotechnical | Materials
Report Cover Letter to Sign
February 10, 2025
Triple C – The A & E Group, LLC 410 East Grand Avenue, Suite 201C Laramie, WY 82070-3701
Attn: Mat Perkins, AIA – Vice President P: (307) 460-2054 E: Mat.perkins@triplecaeg.com
Re: Geotechnical Engineering Report VAMC EHRM Bedford, MA 200 Spring Road Bedford, Massachusetts Terracon Project No. J4245018
Dear Mr. Perkins:
We have completed the scope of Geotechnical Engineering services for the above referenced project in general accordance with Terracon Proposal No. PJ4245018 dated August 26, 2024. This report presents the findings of the subsurface exploration and provides geotechnical recommendations concerning earthwork and the design and construction of foundations and floor slabs for the proposed project.
We appreciate the opportunity to be of service to you on this project. If you have any questions concerning this report or if we may be of further service, please contact us.
Sincerely, Terracon
Ian D. Gates, EIT(NH) Scott M. Carter, P.E.
Project Engineer Geotechnical Department Manager
Geotechnical Engineering Report VAMC EHRM Bedford, MA | Bedford, Massachusetts February 10, 2025 | Terracon Project No. J4245018
Facilities | Environmental | Geotechnical | Materials i
Table of Contents
Introduction Project Description Site Conditions Geotechnical Characterization Seismic Site Class Geotechnical Overview Earthwork
Site Preparation Existing Fill Excavation Soil Subgrade Preparation Bedrock Subgrade Preparation Fill Material Types Fill Placement and Compaction Requirements Utility Trench Backfill Grading and Drainage Earthwork Construction Considerations Construction Observation and Testing
Shallow Foundations Design Parameters – Compressive Loads Design Parameters – Overturning and Uplift Loads Construction Adjacent to Existing Building Foundation Construction Considerations Floor Slab Design Parameters Floor Slab Construction Considerations
Frost Considerations General Comments
February 10, 2025 | Terracon Project No. J4245018
Facilities | Environmental | Geotechnical | Materials ii
Figures GeoModel
Attachments
Exploration and Testing Procedures Photography Log Site Location and Exploration Plans Exploration and Laboratory Results Supporting Information
Note: This report was originally delivered in a web-based format. Blue Bold text in the report indicates a referenced section heading. The PDF version also includes hyperlinks which direct the reader to that section. For more interactive features, please view your project online at client.terracon.com.
Refer to each individual Attachment for a listing of contents.
http://client.terracon.com/ http://client.terracon.com/
February 10, 2025 | Terracon Project No. J4245018
Facilities | Environmental | Geotechnical | Materials 1
Introduction
This report presents the results of our subsurface exploration and Geotechnical Engineering services performed for the proposed Electronic Health Records (EHRM) Master Control Room (MCR) Building to be located on the VA Medical Center (VAMC) campus at 200 Spring Road in Bedford, Massachusetts. The purpose of these services was to provide information and geotechnical engineering recommendations relative to:
■ Subsurface soil conditions
■ Groundwater conditions
■ Seismic site classification per IBC 2024 (ASCE 7-22)
■ Site preparation and earthwork
■ Foundation design and construction
■ Floor slab design and construction
■ Frost considerations
The geotechnical engineering Scope of Services for this project included the advancement of test borings, laboratory testing, engineering analysis, and preparation of this report.
Plans showing the site and boring locations are shown on the Site Location and Exploration Plan attachments, respectively. The boring logs and laboratory results are shown in the Exploration Results attachment. We also collected photographs at the time of our field exploration program. Representative photos are provided in our Photography Log attachment.
Project Description
Our initial understanding of the project was provided in our proposal and was discussed during project planning. Our final understanding of the project conditions is provided in the following table. Terracon should be notified if any of the following information is inconsistent with the planned construction, especially the grading limits, as modifications to our recommendations may be necessary.
Item Description
Information Provided
Triple C – The A & E Group, LLC (Triple C) provided the following document:
■ Recommended Boring Location Plan
February 10, 2025 | Terracon Project No. J4245018
Facilities | Environmental | Geotechnical | Materials 2
Item Description
Project Description
The project is anticipated to include the construction of a new, single-story, EHRM MCR addition to the existing VAMC Medical Facility in Bedford, Massachusetts.
Proposed Structure
Unknown at this time but anticipated to be steel framed with masonry walls and slab-on-grade construction.
Finish Floor Elevation
Planned at elevation (El) 181.0 feet
Maximum Loads
Structural loads are not available at this time; however, based on our experience with similar sized structures, we anticipate the following structural loads:
■ Columns: 30 to 60 kips
■ Walls: 1 to 3 kips per linear foot (klf)
■ Slabs: 150 to 200 pounds per square foot (psf)
Grading/Slopes Minimal changes to existing site grades are anticipated.
Below-Grade Structures
Below grade space (i.e., basement) is not planned
Building Code Massachusetts State Building Code, 10th Edition
Site Conditions
The following description of site conditions was derived from our site visit in association with the field exploration and our review of publicly available topographic maps.
Item Description
Parcel Information
The project is located on the campus of the Veterans Affairs Medical Center (VAMC) at 200 Spring Road in Bedford, Massachusetts. The project area is located north of Building 6 at approximate coordinates 43.5060°N, 71.2758°W. See Site Location.
Existing Improvements
The hospital campus is an urban development and consists of asphalt pavement access drives/parking lots, concrete sidewalks, grass medians. The property is abutted by forestry along the entire campus perimeter.
Current Ground Cover
Grassy and/or bare soil from the removal of previous office trailers. Adjacent to the site are asphalt access drives and concrete sidewalks.
February 10, 2025 | Terracon Project No. J4245018
Facilities | Environmental | Geotechnical | Materials 3
Item Description
Existing Topography
(USGS Topographic Map)
The project area is relatively level at an approximately El 180 feet.
Geotechnical Characterization
We have developed a general characterization of the subsurface conditions based upon our review of the subsurface exploration, laboratory data, geologic setting, and our understanding of the project. This characterization, termed GeoModel, forms the basis of our geotechnical calculations and evaluation of the site. Conditions observed at each exploration point are indicated on the individual logs. The individual logs can be found in the Exploration Results attachment and the GeoModel can be found in the Figures attachment of this report.
As part of our analyses, we identified the following model layers within the subsurface profile. For a more detailed view of the model layer depths at each boring location, refer to the GeoModel.
Model Layer
Layer Name General Description
1 Topsoil 3 to 6 inches of topsoil, dark brown
2 Fill Silty sand with gravel, brown
3 Glacial Outwash Silty sand, trace gravel, brown, dense to very dense
1. Auger refusal, presumably on bedrock, was encountered at depths ranging from approximately 4 to 8.5 feet below existing grade.
Groundwater was not observed at the time of our exploration program. Groundwater conditions may change because of seasonal variations in rainfall, runoff, and other conditions not apparent at the time of drilling. Long-term groundwater monitoring was outside the scope of services for this project.
Seismic Site Class
A seismic survey was performed by Terracon for the new EHRM MCR Building area to measure the in-situ shear wave velocities of the subsurface, for use in determining the seismic site class in accordance with IBC 2024 (ASCE 7-22). The seismic site class
February 10, 2025 | Terracon Project No. J4245018
Facilities | Environmental | Geotechnical | Materials 4 definitions based on the weighted average of shear wave velocity in the upper 100 feet of the soil profile are presented in the IBC and are summarized below:
Site Class
Soil Profile Name Weighted Average Shear Wave
Velocity, 𝑣𝑠 (ft/s)
A Hard rock 𝑣𝑠> 5,000 ft/s
B Medium hard rock 3,000 < 𝑣𝑠 ≤ 5,000 ft/s
BC Soft rock 2,100 < 𝑣𝑠 ≤ 3,000 ft/s
C Very dense sand or hard clay 1,450 < 𝑣𝑠 ≤ 2,100 ft/s
CD Dense sand or very stiff clay 1,000 < 𝑣𝑠 ≤ 1,450 ft/s
D Medium dense sand or stiff clay 700 ≤ 𝑣𝑠 ≤ 1,000 ft/s
DE
Loose sand or medium stiff clay 500 < 𝑣𝑠 ≤ 700 ft/s
E Very loose sand or soft clay 𝑣𝑠< 500 ft/s
The results and approximate location of the seismic shear wave survey are provided in Exploration and Laboratory Results and are presented below.
Seismic Array No.
Weighted Average Shear Wave Velocity, 𝑣𝑠 (ft/s)
Site Class
Line 1 2,450 BC
Geotechnical Overview
The site appears suitable for the proposed construction based upon geotechnical conditions encountered in the test borings, provided that the recommendations presented in this report are implemented in the design and construction phases of this project. We have identified existing undocumented fill and relatively shallow bedrock as geotechnical conditions that may impact the proposed construction and will require particular attention in project planning, design and during construction and are discussed in greater detail in the following sections.
Existing, Undocumented Fill: Existing undocumented fill was encountered to depths ranging between approximately 4 and 7 feet below existing grades during the
February 10, 2025 | Terracon Project No. J4245018
Facilities | Environmental | Geotechnical | Materials 5 exploration program. Fill may be deeper in other areas of the site, particularly in the vicinity of existing buildings. We do not possess any information regarding whether the fill was placed under the observation of a geotechnical engineer and/or testing agency.
Undocumented fill can present a greater than normal risk of post-construction movement of foundations supported on or above these materials due to the potential for unsuitable materials to be present within or buried by the fill.