This federal contract opportunity solicitation seeks proposals for construction services for the Construct Mental Health Phase 2 project at the Providence VA Medical Center in Providence, Rhode Island. The Department of Veterans Affairs, Veterans Health Administration, Program Contracting Activity Central aims to award a single firm-fixed-price contract to furnish all labor, tools, materials, equipment, and supervision for general construction, alterations, civil site work, finishes, HVAC, electrical work, plumbing, fire alarm and suppression, security, and other work contained in the construction documents. The solicitation number is 36C77623R0039 and proposals are due in response to the Design-Bid-Build procurement for the new mental health building phase two minor construction project at the specified location.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TELECOMMUNICATIONS ABBREVIATIONS
TELEPHONE BACKBOARD (WALL MOUNTED)
SEE VA BARRIER FREE DESIGN GUIDE PG-18-13.
NURSE CALL TERMINAL CABINET.
NURSE'S CALL MASTER STATION MTD ON NURSE'S COUNTER TOP
UNLESS OTHERWISE NOTED.
OUTLET; LETTER INDICATES AS FOLLOWS:
A = AUDIO I = INTERCOM
OUTLET DATA ONLY - (1) CAT6A CABLE PER OUTLET.
# = NUMBER OF OUTLETS, CH = COUNTER HEIGHT
OUTLET (VOIP) TELEPHONE; (1) CAT6A CABLE. LETTER INDICATES AS FOLLOWS:
J = JACK TYPE 18" AFF W = WALL TYPE 48" AFF
TELECOMMUNICATIONS OUTLET (TCO), COMBINATION TELEPHONE/DATA
COMMUNICATION OUTLET - 4 DATA PORT FACE PLATE WITH 4 DATA PORTS AND
CAT6A CABLES.
NCS
NCT
TTB
A
J
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
ALT ALTERNATE
AMB OR A AMBIENT
ARCH ARCHITECT
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BC BARE COPPER
BD BOARD
BDA BI-DIRCTIONAL ANTENNA
BFF BELOW FINISH FLOOR
BLDG BUILDING
BPIP BOILER PLANT INSTRUMENTATION PANEL
BYP BY PASS
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
CUR CURRENT
OC ON CENTER
OD OUTSIDE DIAMETER
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
REC RECESSED
RECPT RECEPTACLE
RGS RIGID GALVANIZED STEEL
RM ROOM
REQD REQUIRED
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SURF SURFACE
SW SWITCH
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
TCO WORK AREA OUTLET
WP WEATHERPROOF
COMMUNICATION SYMBOLS
SYMBOL DESCRIPTION
DAS DISTRIBUTED ANTEANNA SYSTEM
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISTR DISTRIBUTION
DN DOWN
DRSW DOOR SWITCH
DWG DRAWING
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ESMT EASEMENT
EXIST EXISTING
FLEX FLEXIBLE METALLIC CONDUIT
FOUTT TELEPHONE FLOOR OUTLET
FP FIRE PROTECTION
FT FEET OR FOOT
FU SW FUSED SWITCH
G OR GND GROUND OR GENERATOR
GEN GENERATOR
GTB GROUND TERMINAL BOX
HOA HAND-OFF-AUTOMATIC
HT HEIGHT
HZ HERTZ
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
J-BOX JUNCTION BOX
LF LINEAR FEET (FOOT)
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MECH MECHANICAL
MH MANHOLE
MIN MINIMUM
MT MOUNT
MTD MOUNTED
MTG MOUNTING
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEUT OR N NEUTRAL
NIC NOT IN CONTRACT
NS NO SCALE
NTS NOT TO SCALE
CH = COUNTER HEIGHT
CH
GENERAL NOTES
1. PRODUCTS SHALL BE OF MATERIALS THAT ARE SUITABLE FOR THE ENVIRONMENT IN WHICH THEY ARE TO BE INSTALLED.
2. WORKING CLEARANCES AROUND ELECTRICAL EQUIPMENT SHALL BE MAINTAINED IN COMPLIANCE WITH THE NATIONAL ELECTRICAL CODE ARTICLE 110, COORDINATE EQUIPMENT INSTALLATION TO MAINTAIN REQUIRED CLEARANCES.
3. IF AN OUTLET BOX IS REQUIRED TO BE LOCATED IN AN ASSEMBLY OR PARTITION RATED AS "FIRE/SMOKE" OR "SMOKE" OR IDENTIFIED AS EITHER "FIRE/SMOKE" OR "SMOKE", THEN ALL OF THE FOLLOWING CONDITIONS SHALL BE MET:
THE OUTLET BOX OPENINGS SHALL OCCUR ONLY ON ONE SIDE OF THE FRAMING SPACE.
THE OUTLET BOX SHALL BE METALLIC.
THE OUTLET BOX OPENINGS SHALL NOT EXCEED 16 SQUARE INCHES.
ALL CLEARANCES BETWEEN THE OUTLET BOX AND THE WALL BOARD MATERIAL SHALL BE COMPLETELY SEALED WITH APPROVED MATERIALS IN ACCORDANCE WITH THE APPLICABLE CODES AND STANDARDS FOR THE PROJECT.
PROVIDE A SUPPLEMENTAL BARRIER AROUND OUTLETS LARGER THAN 16 INCHES SO THAT THE ORIGINAL RATING OF
THE PENETRATION IS MAINTAINED.
THE TOTAL AGGREGATE SURFACE AREA OF THE OUTLET BOX SHALL NOT EXCEED 100 SQUARE INCHES PER 100
SQUARE FEET.
THE OUTLET BOX SHALL BE SEPARATED FROM OPENINGS ON THE OPPOSITE SIDE OF THE RATED PARTITION BY
A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES.
THE OUTLET BOX SHALL BE SECURELY FASTENED TO A PARTITION FRAMING MEMBER BY MEANS OF AN APPROVED
ATTACHMENT METHOD.
OPENINGS CUT INTO THE WALL BOARD MATERIAL SHALL NOT EXCEED 1/8 INCH BETWEEN THE EDGES OF THE OUTLET
BOX AND THE EDGES OF THE OPENING.
A.
B.
C.
D.
E.
F.
G.
H.
I.
LOCATIONS OF EQUIPMENT SHOWN ON THE DRAWINGS ARE APPROXIMATE, COORDINATE EXACT EQUIPMENT LOCATION AND
CONNECTION REQUIREMENTS WITH THE APPROPRIATE TRADE PRIOR TO INSTALLATION.
FOR EXACT LOCATION OF CEILING MOUNTED EQUIPMENT REFER TO THE ARCHITECTURAL REFLECTED CEILING PLAN. LOCATIONS OF EQUIPMENT NOT INCLUDED ON THE REFLECTED CEILING PLAN SHALL BE COORDINATED WITH THOSE ITEMS SHOWN. COORDINATION OF CEILING MOUNTED EQUIPMENT SHALL BE PRIOR TO ANY ROUGH-IN. NOTIFY ARCHITECT OF ANY DISCREPANCY.
PROVIDE FINAL CONNECTIONS TO OWNER PROVIDED EQUIPMENT WHERE INDICATED ON THE PLAN DRAWINGS.
PRIOR TO ROUGH-IN AND INSTALLATION OF ANY FLOOR MOUNTED DEVICE, VERIFY LOCATION WITH THE ARCHITECT.
VERIFY AND COORDINATE THE LOCATION OF REQUIRED DIVISION 27 OUTLETS WITH OTHER TRADE DRAWINGS AND OWNER
PROVIDED EQUIPMENT.
ALL RACEWAY SYSTEMS SHOWN TO SUPPORT THE INSTALLATION OF THE DIVISION 27 EQUIPMENT SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR. PROVIDE COORDINATION FOR THE INSTALLATION OF THIS RACEWAY SYSTEM WITH THE ELECTRICAL
CONTRACTOR.
4.
5.
6.
7.
8.
9.
10. EACH VOICE/DATA OUTLET LOCATION SHOWN, SHALL HAVE A DOUBLE GANG OUTLET BOX WITH A SINGLE GANG PLASTER RING AND (1) 1-1/2" CONDUIT STUBBED UP TO AN ACCESSIBLE LOCATION ABOVE THE FINISHED CEILING OR TO AN ACCESSIBLE CABLE TRAY WHERE
PROVIDED. WORK BY ELECTRICAL CONTRACTOR PER SPECS.
11.
12.
ALL BONDING AND GROUNDING ELEMENTS UTILIZED FOR STRUCTURED CABLING SYSTEM SHALL BE IN COMPLIANCE WITH SPECIFICATION
SECTION 262000.
13.
PROVIDE ALL SLEEVES AS REQUIRED FOR ALL LOW VOLTAGE CABLE PATHWAYS. RESTORE THE FIRE RATING OF THE SURFACE.
14.
CABLE UNDER SLAB USE INDOOR/OUTDOOR JACKET.
15.
TELECOMMUNICATIONS ROOM SHALL BE BONDED AND GROUNDED IN ACCORDANCE WITH TIA-607B.
PULL SCHEDULE REQUIREMENTS
CONTRACTOR SHALL PROVIDE PULL SCHEDULE WITH TELECOM SHOP DRAWINGS. TELECOM SHOP DRAWINGS WILL NOT BE REVIEWED
UNLESS THEY INCLUDE PULL SCHEDULES.
CAT 6a COPPER CABLE COLOR CODING
WHITE
YELLOW
GREEN
BLUE
- TELEPHONE
- PC/PRINTER
- MULTIPLE MAC
- LAPTOP
ALL TELECOMMUNICATIONS CONDUITS SHALL BE PROVIDED WITH BUSHINGS AT EACH END FOR PROTECTION OF STRUCTURED
CABLE.
STRUCTURED CABLING SYSTEM (SCS):
THE SCS CONTRACTOR (SCSC) SHALL PROVIDE ALL BACKBONE AND HORIZONTAL CABLING,
COMPONENTS AND TERMINATIONS AS REQUIRED FOR A COMPLETE AND OPERATIONAL CABLING
SYSTEM PER INDUSTRY BEST PRACTICES AS PRESCRIBED BY BICSI AND NEC.
THE SCSC SHALL BE RESPONSIBLE FOR COORDINATION WITH THE ELECTRICAL CONTRACTOR (EC) FOR SPECIFIC LOCATIONS OF ALL TELECOMMUNICATIONS SYSTEM DEVICES, INCLUDING ANCILLARY
SYSTEM COMPONENTS AND ASSOCIATED CONDUITS PROVIDED BY THE EC.
THE ELECTRICAL CONTRACTOR (EC) SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL
ROUGH-IN COMPONENTS ASSOCIATED WITH THE TELECOMMUNICATIONS SYSTEM COMPONENTS
AS NOTED ON THE DRAWINGS AND SPECIFICATIONS, INCLUDING BUT NOT LIMITED TO, CONDUIT AND BACK-BOXES. THE EC SHALL COORDINATE ALL REQUIREMENTS WITH THE SCS CONTRACTOR.
TELECOM ROOM (TR) EQUIPMENT RACKS:
THE SCS CONTRACTOR (SCS) SHALL FURNISH AND INSTALL ALL EQUIPMENT RACKS. THE SCS
CONTRACTOR SHALL FURNISH AND INSTALL ALL CABLING PATCH PANELS (COPPER AND FIBER)
WITH RACK, AND SHALL BE RESPONSIBLE FOR ALL CABLE TERMINATIONS AT THE PATCH PANELS.
THE VA SHALL BE RESPONSIBLE FOR FURNISHING AND INSTALLING ALL ACTIVE EQUIPMENT,
CONTROLLERS, SWITCHES, ETC. THAT RESIDE WITHIN THESE RACKS.
GROUNDING AND BONDING:
THE EC SHALL BE RESPONSIBLE FOR INSTALLING THE GROUNDING BUSBAR(S) AS ILLUSTRATED ON THE DRAWINGS AND SPECIFICATIONS, AND CONNECTING IT TO THE BUILDING MAIN ELECTRICAL
SERVICE GROUND. THE EC SHALL BE RESPONSIBLE FOR GROUNDING ALL BACKBONE CONDUIT
AND CABLE TRAY.
THE SCSC SHALL BE RESPONSIBLE FOR GROUNDING ALL RACKS, CABINETS, ENCLOSURES,
PROTECTOR BLOCKS AND CABLE LADDER-RACK INSIDE TELECOMMUNICATIONS ROOMS.
FIRESTOPPING:
THE EC SHALL BE RESPONSIBLE FOR FIRE-STOPPING SLEEVE ASSEMBLIES TO OBTAIN A UL RATING.
THE SCSC SHALL BE RESPONSIBLE FOR FIRE-STOPPING INSIDE THE SLEEVES AFTER CABLE
INSTALLATION IS COMPLETE.
CASEWORK / ,MILLWORK:
THE SCSC SHALL BE RESPONSIBLE FOR INSTALLING TELECOMMUNICATIONS OUTLETS IN CASEWORK, AS REQUIRED. CABLES SHALL BE CONCEALED IN CASEWORK.
THE EC SHALL BE RESPONSIBLE FOR INSTALLING ASSOCIATED CONDUIT AND BACK-BOXES AND
SHALL STUB CONDUIT TO THE ABOVE ACCESSIBLE CEILING SPACE.
CONDUIT:
THE EC SHALL BE RESPONSIBLE TO PROVIDE AND INSTALL ALL BACKBONE AND HORIZONTAL CABLING
PATHWAYS. THIS SHALL INCLUDE ALL INTERIOR CONDUITS, PATHWAY COMPONENTS SUCH AS
JUNCTION BOXES, PULL BOXES, WALL/CEILING PENETRATIONS AND CONDUIT SLEEVES, WHETHER SHOWN ON THE DRAWINGS OR AS REQUIRED TO PENETRATE FULL-HEIGHT PARTITIONS AS SHOWN ON THE DRAWINGS. THE EC SHALL PROVIDE AND INSTALL ALL BUSHINGS ON TELECOMMUNICATIONS
CONDUITS PRIOR TO INSTALLATION OF CABLING.
THE SCSC SHALL BE RESPONSIBLE FOR ALL WIRE RACEWAYS, CABLE RUNWAY (LADDER RACK) AND
OTHER REQUIREMENTS FOR ROUTING AND SECURING CABLE INSIDE THE MAIN
TELECOMMUNICATIONS ROOM (MTR) AND ALL TR'S.
TELECOMMUNICATIONS COMMUNICATIONS OUTLETS (C.O.'S) AND DEVICES:
THE EC SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL CONDUIT AND BACK-BOXES
ASSOCIATED WITH THE TELECOMMUNICATIONS C.O.'S AND DEVICES.
THE SCSC SHALL BE RESPONSIBLE FOR INSTALLATION OF ALL STRUCTURED CABLING, JACKS,
FACEPLATES AND JUMPER/PATCH CORDS.
BACKBOARDS:
THE EC SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL BACKBOARDS AS ILLUSTRATED
ON THE DRAWINGS AND AS REQUIRED FOR A COMPLETE SYSTEM AS ILLUSTRATED IN THE
SPECIFICATIONS. THE EX SHALL BE RESPONSIBLE FOR ROUGH-IN OF ALL CONDUIT AND BACK-BOXES.
POWER CONDUITS SHALL BE CONCEALED BEHIND ALL BACKBOARDS. BACKBONE CONDUIT SHALL BE
EXPOSED AS ILLUSTRATED ON THE DRAWINGS (TR WALL ELEVATIONS).
COORDINATION NOTES:
CEILING MOUNTED DAS ANTENNA. BI-DIRECTIONAL ANTENNA (BDA) SYSTEM
FLOOR RECEPTACLE, COMBINATION POWER/DATA OUTLET - 4 DATA PORTS AND
(1) CAT6A CABLE PER OUTLET.
CEILING MOUNTED PUBLIC ADDRESS SYSTEM SPEAKERPA
N
D NURSE CALL DOME LIGHT, CEILING MOUNTED.
D = CORRIDOR DOME LIGHT WITH SOUNDER.
NURSE CALL STATION.N
E
D = DUTY STATION. MTD 5'-0" [1524mm] AFF UNLESS NOTED
OTHERWISE.
E = (2) LOCATIONS VERTICALLY MTD 48'-0" AFF & 1'-6" AFF FOR TOILET LOCATION.
V = VIDEO - PROVIDE RECESSED AUDIO/VIDEO CONNECTION BOX FOR NETWORK
AND ELECTRICAL CONNECTION.
16. WIRELESS ACCESS POINTS (WAP), HORIZONTAL CABLING AND ASSOCIATED RACK MOUNTED EQUIPMENT (SWITCHES, PATCH
PANES, AND HORIZONTAL CABLE MANAGEMENT) PROVIDED AND INSTALLED BY OTHERS.
BASKET STLE CABLE TRAY. SIZE AND MOUNTING HEIGHT AS
INDICATED ON PLANS.
LADDER STLE CABLE TRAY. SIZE AND MOUNTING HEIGHT AS
INDICATED ON PLANS.
CEILING MOUNTED (1) PORT DATA OUTLET - (1) CAT6A CABLE PER OUTLET.
J CEILING MOUNTED, RECESSED 4" SQUARE JUNCTION BOX.
J WALL MOUNTED, RECESSED 4" SQUARE JUNCTION BOX.
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
ENGINEER ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title
Approved:
Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH
www.abovegroupinc.com
COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
/3
/2
:2
:2
P
M B
IM
/0
V A
P ro v id e n c e M e n ta l H e a lt h
B u ild in g
P H
/0
V A
P ro v id e n c e
M H
C P
H
R
D iv
.r v t
T-001
650-347
PROVIDENCE VAMC MENTAL
HEALTH PHASE 2
PROVIDENCE, RI
JFR CVMFEB 04 2022
CONSTRUCTION
DOCUMENTS
TELECOM LEGEND AND
ABBREVIATIONS
FULLY SPRINKLERED
Christopher H. Van Meter RCDD Reg. No. 285002
TELECOM DRAWING INDEX
SHEET DESCRIPTION
T-001 TELECOM LEGEND AND ABBREVIATIONS
T-101 LEVEL B PLAN - FIBER ROUTING
T-102 LEVEL 1 PLAN - OVERALL
TA101 LEVEL B PLAN - AV/PA/NURSE CALL
TA102 LEVEL 1 PLAN - AV/PA/NURSE CALL
TA103 LEVEL 2 PLAN - AV/PA/NURSE CALL
TN101 LEVEL B PLAN - DATA/BDA
TN102 LEVEL 1 PLAN - DATA/BDA
TN103 LEVEL 2 PLAN - DATA/BDA
TN104 ROOF LEVEL PLAN - DATA/BDA
T-401 TELECOM ENLARGED PLANS
T-501 TELECOM DETAILS
T-601 TELECOM RISERS AND DIAGRAMS
Revisions: Revision Description Date:
R E
F
REF.
A
A1
A1
B
B
AL AL AL
AL AL AL AL
ALA
A
A A
G-2
G-2G-2
A
A
A
A
AS
A1
A
A1
A
A
G-2
G-3
A
B1
B1
G-1
G-1
R E
F
1 TYPICAL
2-A
2-C
2-E
2-12-2.1 2-22-3
2-4
2-5
2-6
2-7
2-8
2-F
STORAGE
CONSULT ROOM
CONSULT ROOM
OFFICE (TRIPLE)
OFFICE (TRIPLE)
TEAM RM
CORRIDOR
OFFICE (TRIPLE)
STAIR 3
OFFICE (TRIPLE)
OFFICE (DOUBLE)
050 OFFICE (DOUBLE)
CONSULT ROOM
OFFICE
054 OFFICE
CHIEF OFFICE
CONSULT ROOM
037 WAITING AREA
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
ENGINEER ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title
Approved:
Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH
www.abovegroupinc.com
COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
/3
/2
:2
:2
P
M B
IM
/0
V A
P ro v id e n c e M e n ta l H e a lt h
B u ild in g
P H
/0
V A
P ro v id e n c e
M H
C P
H
R
D iv
.r v t
T-101
650-347PROVIDENCE VAMC MENTAL
HEALTH PHASE 2
PROVIDENCE, RI
JFR CVMFEB 04 2022
CONSTRUCTION
DOCUMENTS
LEVEL B PLAN - FIBER ROUTING
FULLY SPRINKLERED
Christopher H. Van Meter RCDD Reg. No. 285002
1/8" = 1'-0"F1
LEVEL B PLAN - FIBER ROUTING
ROUTE (1) OM4 FIBER OPTIC CABLE AND (1) OS2 FIBER OPTIC CABLE ABOVE CEILING FROM PHASE 1 TELE/DATA ROOM 019 TO NEW PHASE 2 TELE/DATA ROOM 138. PROVIDE 2", FLEXIBLE, NON-METALIC CONDUIT WITH 2" - 4 CELL FABRIC INNERDUCT AND PULL BOXES AS REQUIRED. ROUTING SHOWN IS DIAGRAMMATIC. EXACT ROUTING TO BE COORDINATED IN FIELD. INNER DUCT BASIS OF DESIGN IS
MAXCELL MXE52224.
PROVIDE CONDUIT SLEEVES THROUGH FLOOR UP INTO NEW TELE/DATA ROOM 138. REFER TO SHEET
T-401 FOR ADDITIONAL INFORMATION.
COORDINATE EXACT LOCATION OF FIBER OPTIC CABLE TERMINATION IN PHASE 1 ROOM 019 WITH VA IT PERSONNEL PRIOR TO CONSTRUCTION. PROVIDE 20' FIBER OPTIC CABLE SERVICE LOOP IN EACH
IT ROOM.
(1) 2" SLEEVE THROUGH WALL WITH BUSHINGS ON EACH END. PROVIDE HILTI FIRESTOP ASSEMBLY OR SYSTEM AS REQUIRED TO MAINTAIN FIRE RATING OF PARTITION. BASIS OF DESIGN IS HILTI SPEED
SLEEVE FAMILY OF PRODUCTS
1. CONDUIT ROUTING INDICATED ON THIS PLAN IS DIAGRAMMATIC. CONTRACTOR TO COORDINATE EXACT CONDUIT ROUTING IN FIELD WITH ALL OTHER TRADES AND STRUCTURE PRIOR TO CONSTRUCTION.
CODED NOTES:
DRAWING NOTES:
0 4' 8' 16' 24'
1/8" = 1'-0"
P1P2
KEY PLAN
AL
AL
ALAL
AL
AL
AL
AL
ALALALA
B B
BA
AL
A
A1
A1
A A
A
E3 E3 E3 A
G-1
G-2
G-2
G-2A
A1
A1
DIR-W2G-3
G-1
G-1
A1
DL3
A1
2-B E.5
2-D
2-A
2-C
2-E
2-12-2.12-22-3
2-4
2-5
2-6
2-7
2-8
2-F
EXISTING
FACP
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
ENGINEER ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title
Approved:
Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH
www.abovegroupinc.com
COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
/3
/2
:2
:3
P
M B
IM
/0
V A
P ro v id e n c e M e n ta l H e a lt h
B u ild in g
P H
/0
V A
P ro v id e n c e
M H
C P
H
R
D iv
.r v t
T-102
650-347PROVIDENCE VAMC MENTAL
HEALTH PHASE 2
PROVIDENCE, RI
JFR CVMFEB 04 2022
CONSTRUCTION
DOCUMENTS
LEVEL 1 PLAN - OVERALL
FULLY SPRINKLERED
Christopher H. Van Meter RCDD Reg. No. 285002
1/8" = 1'-0" F1
LEVEL 1 PLAN - OVERALL
0 4' 8' 16' 24'
1/8" = 1'-0"
BDA ANNUNCIATOR. LOCATE ADJACENT TO EXISTING FIRE ALARM CONTROL PANEL. COORDINATE EXACT LOCATION IN FIELD PRIOR TO CONSTRUCTION. REFER TO SHEET T-601 FOR ADDITIONAL
INFORMATION.
1. EXISTING EQUIPMENT LOCATION IS APPROXIMATE. CONTRACTOR TO FIELD VERIFY EXACT LOCATION
PRIOR TO CONSTRUCTION.
CODED NOTES:
DRAWING NOTES:
P1P2
KEY PLAN
F
PA
PA
PA
PA
PA
PA
PA
PA
PA
N
D
N
V
N
2-A
2-C
2-E
2-12-2.12-22-3
2-4
2-5
2-6
2-7
2-8
2-F
E
1 TYPICAL
D
CONSULT ROOM
PRINTER
034B
STORAGE
CONSULT ROOM
CONSULT ROOM
OFFICE (TRIPLE)
OFFICE (TRIPLE)
TEAM RM
STAFF TOILET
CORRIDOR
034A
HAC
STAIR 3
CORRIDOR
OFFICE (TRIPLE)
OFFICE (TRIPLE)
ELEC. CL.
OFFICE (DOUBLE)
VETERAN W.S.
OFFICE (DOUBLE)
CONSULT ROOM
OFFICE
OFFICE
CHIEF OFFICE
PUBLIC TOILET
MSA
WAITING AREA
+78"
0 2' 4' 8' 12'
1/4" = 1'-0"
CEILING MOUNTED PUBLIC ADDRESS SPEAKER. REFER TO SHEET T-601 FOR ADDITIONAL
INFORMATION.
COORDINATE EXACT LOCATION OF ALL NURSE CALL EQUIPMENT WITH ARCHITECTURAL AND
INTERIORS PLANS PRIOR TO CONSTRUCTION. REFER TO SHEET T-601 FOR ADDITIONAL
INFORMATION.
COORDINATE LOCATION OF OUTLET BOX WITH TV MOUNT, DATA OUTLETS AND POWER RECEPTACLE.
ALL CONNECTIONS TO BE CONTAINED WITHIN RECESSED VIDEO OUTLET BOX. REFER TO ELECTRICAL
DRAWINGS FOR MODEL NUMBER AND ADDITIONAL INFORMATION. PROVIDE RG6 COAXIAL CABLE
FROM VIDEO OUTLET BOX TO COAXIAL TERMINATION POINT IN PHASE 1 IT ROOM 019. COORDINATE
EXACT TERMINATION POINT IN PHASE 1 WITH VA IT PRIOR TO CONSTRUCTION.
1. COORDINATE EXACT LOCATION OF CEILING MOUNTED DEVICES WITH ARCHITECTURAL REFLECTED
CEILING PLAN PRIOR TO CONSTRUCTION.
CODED NOTES:
DRAWING NOTES:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
ENGINEER ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title
Approved:
Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH
www.abovegroupinc.com
COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
/3
/2
:3
:1
P
M B
IM
/0
V A
P ro v id e n c e M e n ta l H e a lt h
B u ild in g
P H
/0
V A
P ro v id e n c e
M H
C P
H
R
D iv
.r v t
TA101
650-347PROVIDENCE VAMC MENTAL
HEALTH PHASE 2
PROVIDENCE, RI
JFR CVMFEB 04 2022
CONSTRUCTION
DOCUMENTS
LEVEL B PLAN - AV/PA/NURSE
CALL
FULLY SPRINKLERED
Christopher H. Van Meter RCDD Reg. No. 285002
1/4" = 1'-0" F1
LEVEL B PLAN - AV/PA/NURSE CALL
P1P2
KEY PLAN
V
V
PA
PA
PA
PA
PA
PA PA
PA
PA
N
D
J
J
PA
N
V
J
J
N
T-401 C7
2-A
2-C
2-E
2-12-2.12-22-3
2-4
2-5
2-6
2-7
2-8
2-F +66"
+60"
E
NCS
D
2 TYPICAL
WAITING AREA
MSA
PUBLIC TOILET
CORRIDOR
GROUP THERAPY
GROUP THERAPY
OFFICE
OFFICE
OFFICE
COUPLE'S THERAPY
COUPLE'S THERAPY
OFFICE
OFFICE
PRINTER
131A
TELEDATA
OFFICE
ELEC. CL.
OFFICE
OFFICE
SECTION CHIEF
STAFF TOILET
STAIR 3
LOUNGE, STAFF
COUPLE'S THERAPY
+78"
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
ENGINEER ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title
Approved:
Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH
www.abovegroupinc.com
COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
/3
/2
:3
:2
P
M B
IM
/0
V A
P ro v id e n c e M e n ta l H e a lt h
B u ild in g
P H
/0
V A
P ro v id e n c e
M H
C P
H
R
D iv
.r v t
TA102
650-347PROVIDENCE VAMC MENTAL
HEALTH PHASE 2
PROVIDENCE, RI
JFR CVMFEB 04 2022
CONSTRUCTION
DOCUMENTS
LEVEL 1 PLAN - AV/PA/NURSE
CALL
FULLY SPRINKLERED
Christopher H. Van Meter RCDD Reg. No. 285002
1/4" = 1'-0" F1
LEVEL 1 PLAN - AV/PA/NURSE CALL
0 2' 4' 8' 12'
1/4" = 1'-0"
PROVIDE 1-1/2" CONDUIT WITH PULL STRING FROM VIDEO OUTLET BOX TO RECESSED JUNCTION BOX FOR VIDEO CONNECTION TO LOCAL EQUIPMENT. COORDINATE LOCATION OF OUTLET BOX WITH TV
MOUNT, DATA OUTLETS AND POWER RECEPTACLE. ALL CONNECTIONS TO BE CONTAINED WITHIN
RECESSED VIDEO OUTLET BOX.
CEILING MOUNTED PUBLIC ADDRESS SPEAKER. REFER TO SHEET T-601 FOR ADDITIONAL
INFORMATION.
COORDINATE EXACT LOCATION OF ALL NURSE CALL EQUIPMENT WITH ARCHITECTURAL AND
INTERIORS PLANS PRIOR TO CONSTRUCTION. REFER TO SHEET T-601 FOR ADDITIONAL
INFORMATION.
COORDINATE LOCATION OF OUTLET BOX WITH TV MOUNT, DATA OUTLETS AND POWER RECEPTACLE.
ALL CONNECTIONS TO BE CONTAINED WITHIN RECESSED VIDEO OUTLET BOX. REFER TO ELECTRICAL
DRAWINGS FOR MODEL NUMBER AND ADDITIONAL INFORMATION. PROVIDE RG6 COAXIAL CABLE
FROM VIDEO OUTLET BOX TO COAXIAL TERMINATION POINT IN PHASE 1 IT ROOM 019. COORDINATE
EXACT TERMINATION POINT IN PHASE 1 WITH VA IT PRIOR TO CONSTRUCTION.
PUBLIC ADDRESS HANDSET. COORDINATE EXACT LOCATION WITH MILLWORK AND VA PRIOR TO
CONSTRUCTION. REFER TO SHEET T-601 FOR ADDITIONAL INFORMATION.
PROVIDE 1-1/2" CONDUIT WITH PULL STRING FROM CEILING MOUNTED PROJECTOR OUTLET BOX TO RECESSED JUNCTION BOX FOR VIDEO CONNECTION TO LOCAL EQUIPMENT. COORDINATE LOCATION
OF OUTLET BOX WITH PROJECTOR MOUNT, DATA OUTLETS AND POWER RECEPTACLE.
CODED NOTES:
DRAWING NOTES:
1. COORDINATE EXACT LOCATION OF CEILING MOUNTED DEVICES WITH ARCHITECTURAL REFLECTED
CEILING PLAN PRIOR TO CONSTRUCTION.
P1P2
KEY PLAN
PA
PA
PA
PA
PA
PA
PA
PA
PA
PA
N
D
V
N
2-A
2-C
2-E
2-12-2.12-22-3
2-4
2-5
2-6
2-7
2-8
2-F
E
1 TYPICAL
WAITING AREA
PUBLIC TOILET
STAFF TOILET
N.P. OFFICE
N.P. OFFICE
N.P. OFFICE
CORRIDOR
CHIEF OFFICE
OFFICE
OFFICE
OFFICE/CONSULT
OFFICE
OFFICE/CONSULT
CORRIDOR
ELEC. RM.
HAC
N.P. OFFICE
N.P. OFFICE
N.P. OFFICE
MECH. RM.
STAIR 3
PRINTER
204A +78"
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
ENGINEER ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title
Approved:
Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH
www.abovegroupinc.com
COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
/3
/2
:3
:2
P
M B
IM
/0
V A
P ro v id e n c e M e n ta l H e a lt h
B u ild in g
P H
/0
V A
P ro v id e n c e
M H
C P
H
R
D iv
.r v t
TA103
650-347PROVIDENCE VAMC MENTAL
HEALTH PHASE 2
PROVIDENCE, RI
JFR CVMFEB 04 2022
CONSTRUCTION
DOCUMENTS
LEVEL 2 PLAN - AV/PA/NURSE
CALL
FULLY SPRINKLERED
Christopher H. Van Meter RCDD Reg. No. 285002
1/4" = 1'-0"F1
LEVEL 2 PLAN - AV/PA/NURSE CALL
0 2' 4' 8' 12'
1/4" = 1'-0"
CEILING MOUNTED PUBLIC ADDRESS SPEAKER. REFER TO SHEET T-601 FOR ADDITIONAL
INFORMATION.
COORDINATE EXACT LOCATION OF ALL NURSE CALL EQUIPMENT WITH ARCHITECTURAL AND
INTERIORS PLANS PRIOR TO CONSTRUCTION. REFER TO SHEET T-601 FOR ADDITIONAL
INFORMATION.
COORDINATE LOCATION OF OUTLET BOX WITH TV MOUNT, DATA OUTLETS AND POWER RECEPTACLE.
ALL CONNECTIONS TO BE CONTAINED WITHIN RECESSED VIDEO OUTLET BOX. REFER TO ELECTRICAL
DRAWINGS FOR MODEL NUMBER AND ADDITIONAL INFORMATION. PROVIDE RG6 COAXIAL CABLE
FROM VIDEO OUTLET BOX TO COAXIAL TERMINATION POINT IN PHASE 1 IT ROOM 019. COORDINATE
EXACT TERMINATION POINT IN PHASE 1 WITH VA IT PRIOR TO CONSTRUCTION.
1. COORDINATE EXACT LOCATION OF CEILING MOUNTED DEVICES WITH ARCHITECTURAL REFLECTED
CEILING PLAN PRIOR TO CONSTRUCTION.
CODED NOTES:
DRAWING NOTES:
P1P2
KEY PLAN
F
2-A
2-C
2-E
2-12-2.12-22-3
2-4
2-5
2-6
2-7
2-8
2-F
3 TYPICAL
4 TYPICAL
7 TYPICAL
CONSULT ROOM
PRINTER
034B
STORAGE
CONSULT ROOM
CONSULT ROOM
OFFICE (TRIPLE)
OFFICE (TRIPLE)
042TEAM RM
STAFF TOILET
CORRIDOR
034A
HAC
STAIR 3
CORRIDOR
034OFFICE (TRIPLE)
OFFICE (TRIPLE)
ELEC. CL.
OFFICE (DOUBLE)
VETERAN W.S.
OFFICE (DOUBLE)
CONSULT ROOM
OFFICE
OFFICE
CHIEF OFFICE
PUBLIC TOILET
MSA
WAITING AREA
+48"
+78"
(2) 4" SLEEVES THROUGH WALL WITH BUSHINGS ON EACH END. PROVIDE HILTI FIRESTOP ASSEMBLY OR SYSTEM AS REQUIRED TO MAINTAIN FIRE RATING OF PARTITION. BASIS OF DESIGN IS HILTI SPEED
SLEEVE FAMILY OF PRODUCTS.
(4) 4" SLEEVES WITH BUSHINGS ON EACH END. PROVIDE HILTI FIRESTOP ASSEMBLY OR SYSTEM AS
REQUIRED TO MAINTAIN FIRE RATING OF PARTITION.
CONDUIT FOR FIBER OPTIC CABLE ROUTED ADJACENT TO CABLE TRAY. REFER TO SHEETS T-101 AND T-601 FOR ADDITIONAL INFORMATION. PROVIDE HILTI FIRESTOP ASSEMBLY OR SYSTEM AS REQUIRED TO MAINTAIN FIRE RATING OF PARTITION. BASIS OF DESIGN IS HILTI SPEED SLEEVE FAMILY OF
PRODUCTS.
12" X 4" BASKET STYLE CABLE TRAY INSTALLED AT MINIMUM OF 4" ABOVE ACCESSIBLE CEILING TO
BOTTOM OF TRAY. MAINTAIN 12" CLEAR ABOVE CABLE TRAY FOR ANY ELEMENTS THAT RUN
PARALLEL TO THE CABLE TRAY AND MINIMUM OF 4" CLEAR FOR ANY ELEMENTS THAT CROSS
PERPENDICULAR TO CABLE TRAY. COORDINATE ROUTING OF CABLE TRAY WITH ALL OTHER
UTILITIES.
PUBLIC SAFETY RADIO BI-DIRECTIONAL ANTENNA MASTER BDA AMPLIFIER. REFER TO IN-BUILDING PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM ON SHEET T-601 FOR ADDITIONAL INFORMATION.
BATTERY CABINET MOUNTED BELOW BDA AMPLIFIER. REFER TO SHEET T-601 FOR ADDITIONAL
INFORMATION.
COORDINATE EXACT LOCATION OF DAS ANTENNA WITH SYSTEM SUBMITTAL DOCUMENTS PRIOR TO CONSTRUCTION. REFER TO IN-BUILDING PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM DIAGRAM ON
SHEET T-601 FOR ADDITIONAL INFORMATION.
SLEEVE THROUGH WALL. REFER TO SHEET T-101 FOR ADDITIONAL INFORMATION.
COORDINATE LOCATION OF OUTLET BOX WITH TV MOUNT, DATA OUTLETS AND POWER RECEPTACLE.
ALL CONNECTIONS TO BE CONTAINED WITHIN RECESSED VIDEO OUTLET BOX. REFER TO ELECTRICAL
DRAWINGS FOR MODEL NUMBER AND ADDITIONAL INFORMATION.
COORDINATE EXACT LOCATION AND MOUNTING HEIGHT OF TELEPHONE OUTLET WITH VA PRIOR TO
CONSTRUCTION.
1. COORDINATE EXACT LOCATION OF ALL OUTLETS AT MONITORS WITH ARCHITECTURAL PLANS AND ALL
OTHER MONITOR CONNECTIONS IN FIELD PRIOR TO CONSTRUCTION.
2. PROVIDE 10' SERVICE LOOP ABOVE CEILING AT ALL CAT6A TERMINATION LOCATIONS FOR EACH CAT6A
CABLE.
CODED NOTES:
DRAWING NOTES:
0 2' 4' 8' 12'
1/4" = 1'-0"
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
ENGINEER ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title
Approved:
Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH
www.abovegroupinc.com
COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
/3
/2
:3
:3
P
M B
IM
/0
V A
P ro v id e n c e M e n ta l H e a lt h
B u ild in g
P H
/0
V A
P ro v id e n c e
M H
C P
H
R
D iv
.r v t
TN101
650-347PROVIDENCE VAMC MENTAL
HEALTH PHASE 2
PROVIDENCE, RI
JFR CVMFEB 04 2022
CONSTRUCTION
DOCUMENTS
LEVEL B PLAN - DATA/BDA
FULLY SPRINKLERED
Christopher H. Van Meter RCDD Reg. No. 285002
1/4" = 1'-0"F1
LEVEL B PLAN - DATA/BDA
P1P2
KEY PLAN
T-401 C7
2-A
2-C
2-E
2-12-2.12-22-3
2-4
2-5
2-6
2-7
2-8
2-F
1 TYPICAL, UON
W
+66"
+66"
3 TYPICAL
4TYPICAL
WAITING AREA
MSA
PUBLIC TOILET
CORRIDOR
GROUP THERAPY
GROUP THERAPY
OFFICE
OFFICE
OFFICE
COUPLE'S THERAPY
COUPLE'S THERAPY
OFFICE
OFFICE
PRINTER
131A
TELEDATA
OFFICE
ELEC. CL.
OFFICE
OFFICE
SECTION CHIEF
STAFF TOILET
STAIR 3
LOUNGE, STAFF
COUPLE'S THERAPY
6 6
+48"
+78"
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
ENGINEER ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title
Approved:
Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH
www.abovegroupinc.com
COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
/3
/2
:3
:3
P
M B
IM
/0
V A
P ro v id e n c e M e n ta l H e a lt h
B u ild in g
P H
/0
V A
P ro v id e n c e
M H
C P
H
R
D iv
.r v t
TN102
650-347PROVIDENCE VAMC MENTAL
HEALTH PHASE 2
PROVIDENCE, RI
JFR CVMFEB 04 2022
CONSTRUCTION
DOCUMENTS
LEVEL 1 PLAN - DATA/BDA
FULLY SPRINKLERED
Christopher H. Van Meter RCDD Reg. No. 285002
1/4" = 1'-0" F1
LEVEL 1 PLAN - DATA/BDA
0 2' 4' 8' 12'
1/4" = 1'-0"
(2) 4" SLEEVES THROUGH WALL WITH BUSHINGS ON EACH END. PROVIDE HILTI FIRESTOP ASSEMBLY OR SYSTEM AS REQUIRED TO MAINTAIN FIRE RATING OF PARTITION. BASIS OF DESIGN IS HILTI SPEED
SLEEVE FAMILY OF PRODUCTS.
(4) 4" SLEEVES THROUGH WALL WITH BUSHINGS ON EACH END. PROVIDE HILTI FIRESTOP ASSEMBLY OR SYSTEM AS REQUIRED TO MAINTAIN FIRE RATING OF PARTITION. BASIS OF DESIGN IS HILTI SPEED
SLEEVE FAMILY OF PRODUCTS.
12" X 4" BASKET STYLE CABLE TRAY INSTALLED AT MINIMUM OF 4" ABOVE ACCESSIBLE CEILING TO
BOTTOM OF TRAY. MAINTAIN 12" CLEAR ABOVE CABLE TRAY FOR ANY ELEMENTS THAT RUN
PARALLEL TO THE CABLE TRAY AND MINIMUM OF 4" CLEAR FOR ANY ELEMENTS THAT CROSS
PERPENDICULAR TO CABLE TRAY. COORDINATE ROUTING OF CABLE TRAY WITH ALL OTHER
UTILITIES.
COORDINATE EXACT LOCATION OF DAS ANTENNA WITH SYSTEM SUBMITTAL DOCUMENTS PRIOR TO CONSTRUCTION. REFER TO IN-BUILDING PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM DIAGRAM ON
SHEET T-601 FOR ADDITIONAL INFORMATION.
COORDINATE LOCATION OF OUTLET BOX WITH TV MOUNT, DATA OUTLETS AND POWER RECEPTACLE.
ALL CONNECTIONS TO BE CONTAINED WITHIN RECESSED VIDEO OUTLET BOX. REFER TO ELECTRICAL
DRAWINGS FOR MODEL NUMBER AND ADDITIONAL INFORMATION.
CONDUIT ROUTED IN ABOVE CEILING SPACE OF LEVEL BELOW. ROUTE CONDUIT TO NEAREST WALL
AND UP TO ABOVE CEILING SPACE OF LEVEL 1.
COORDINATE EXACT LOCATION OF CEILING MOUNTED OUTLET WITH PROJECTOR POWER LOCATION
PRIOR TO CONSTRUCTION.
COORDINATE EXACT LOCATION AND MOUNTING HEIGHT OF TELEPHONE OUTLET WITH VA PRIOR TO
CONSTRUCTION.
CODED NOTES:
DRAWING NOTES:
1. COORDINATE EXACT LOCATION OF ALL OUTLETS AT MONITORS WITH ARCHITECTURAL PLANS AND ALL
OTHER MONITOR CONNECTIONS IN FIELD PRIOR TO CONSTRUCTION.
2. PROVIDE 10' SERVICE LOOP ABOVE CEILING AT ALL CAT6A TERMINATION LOCATIONS FOR EACH CAT6A
CABLE.
P1P2
KEY PLAN
2-A
2-C
2-E
2-12-2.12-22-3
2-4
2-5
2-6
2-7
2-8
2-F
TYPICAL, UON
3 TYPICAL, UON
TYPICAL4
WAITING AREA
PUBLIC TOILET
STAFF TOILET
N.P. OFFICE
N.P. OFFICE
N.P. OFFICE
CORRIDOR
CHIEF OFFICE
OFFICE
OFFICE
OFFICE/CONSULT
OFFICE
OFFICE/CONSULT
CORRIDOR
ELEC. RM.
HAC
N.P. OFFICE
N.P. OFFICE
N.P. OFFICE
MECH. RM.
STAIR 3
PRINTER
204A
+48"
+78"
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
ENGINEER ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title
Approved:
Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH
www.abovegroupinc.com
COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
/3
/2
:3
:3
P
M B
IM
/0
V A
P ro v id e n c e M e n ta l H e a lt h
B u ild in g
P H
/0
V A
P ro v id e n c e
M H
C P
H
R
D iv
.r v t
TN103
650-347PROVIDENCE VAMC MENTAL
HEALTH PHASE 2
PROVIDENCE, RI
JFR CVMFEB 04 2022
CONSTRUCTION
DOCUMENTS
LEVEL 2 PLAN - DATA/BDA
FULLY SPRINKLERED
Christopher H. Van Meter RCDD Reg. No. 285002
1/4" = 1'-0" F1
LEVEL 2 PLAN - DATA/BDA
0 2' 4' 8' 12'
1/4" = 1'-0"
(2) 4" SLEEVES THROUGH WALL WITH BUSHINGS ON EACH END. PROVIDE HILTI FIRESTOP ASSEMBLY OR SYSTEM AS REQUIRED TO MAINTAIN FIRE RATING OF PARTITION. BASIS OF DESIGN IS HILTI SPEED
SLEEVE FAMILY OF PRODUCTS.
(4) 4" SLEEVES THROUGH WALL WITH BUSHINGS ON EACH END. PROVIDE HILTI FIRESTOP ASSEMBLY OR SYSTEM AS REQUIRED TO MAINTAIN FIRE RATING OF PARTITION. BASIS OF DESIGN IS HILTI SPEED
SLEEVE FAMILY OF PRODUCTS.
12" X 4" BASKET STYLE CABLE TRAY INSTALLED AT MINIMUM OF 4" ABOVE ACCESSIBLE CEILING TO
BOTTOM OF TRAY. MAINTAIN 12" CLEAR ABOVE CABLE TRAY FOR ANY ELEMENTS THAT RUN
PARALLEL TO THE CABLE TRAY AND MINIMUM OF 4" CLEAR FOR ANY ELEMENTS THAT CROSS
PERPENDICULAR TO CABLE TRAY. COORDINATE ROUTING OF CABLE TRAY WITH ALL OTHER
UTILITIES.
COORDINATE EXACT LOCATION OF DAS ANTENNA WITH SYSTEM SUBMITTAL DOCUMENTS PRIOR TO CONSTRUCTION. REFER TO IN-BUILDING PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM DIAGRAM ON
SHEET T-601 FOR ADDITIONAL INFORMATION.
COORDINATE LOCATION OF OUTLET BOX WITH TV MOUNT, DATA OUTLETS AND POWER RECEPTACLE.
ALL CONNECTIONS TO BE CONTAINED WITHIN RECESSED VIDEO OUTLET BOX. REFER TO ELECTRICAL
DRAWINGS FOR MODEL NUMBER AND ADDITIONAL INFORMATION.
COORDINATE EXACT LOCATION AND MOUNTING HEIGHT OF TELEPHONE OUTLET WITH VA PRIOR TO
CONSTRUCTION.
1. COORDINATE EXACT LOCATION OF ALL OUTLETS AT MONITORS WITH ARCHITECTURAL PLANS AND ALL
OTHER MONITOR CONNECTIONS IN FIELD PRIOR TO CONSTRUCTION.
2. COORDINATE LOCATION OF OUTLET BOX WITH TV MOUNT, DATA OUTLETS AND POWER RECEPTACLE.
ALL CONNECTIONS TO BE CONTAINED WITHIN RECESSED VIDEO OUTLET BOX.
CODED NOTES:
DRAWING NOTES:
P1P2
KEY PLAN
2-B
E.5
2-D
2-A
2-C
2-E
2-12-2.12-22-3
2-4
2-5
2-6
2-7
2-8
2-F
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
ENGINEER ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title
Approved:
Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH
www.abovegroupinc.com
COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
/3
/2
:3
:4
P
M B
IM
/0
V A
P ro v id e n c e M e n ta l H e a lt h
B u ild in g
P H
/0
V A
P ro v id e n c e
M H
C P
H
R
D iv
.r v t
TN104
650-347PROVIDENCE VAMC MENTAL
HEALTH PHASE 2
PROVIDENCE, RI
JFR CVMFEB 04 2022
CONSTRUCTION
DOCUMENTS
ROOF LEVEL PLAN - DATA/BDA
FULLY SPRINKLERED
Christopher H. Van Meter RCDD Reg. No. 285002
1/4" = 1'-0" F1
ROOF LEVEL PLAN - DATA/BDA 0 2' 4' 8' 12'
1/4" = 1'-0"
PUBLIC SAFETY RADIO DONOR ANTENNA. REFER TO SHEET T-601 FOR ADDITIONAL INFORMATION.
COORDINATE EXACT LOCATION AND ORIENTATION WITH OWNER AND EQUIPMENT SUBMITTAL
DRAWINGS PRIOR TO CONSTRUCTION. INSTALL IN ACCORDANCE WITH MANUFACTURERS
INSTALLATION INSTRUCTIONS. PROVIDE ALL REQUIRED MOUNTING HARDWARE.
COORDINATE EXACT LOCATION OF ROOF PENETRATIONS WITH ARCHITECTURAL/STRUCTURAL
DRAWINGS AND DETAILS. ROUTE CABLE DOWN TO BASEMENT LEVEL PUBLIC SAFETY RADIO BI-
DIRECTIONAL ANTENNA MASTER BDA AMPLIFIER. REFER TO SHEETS TN101 AND T-601 FOR
ADDITIONAL INFORMATION.
CODED NOTES:
P1P2
KEY PLAN
RACK 3
RACK 2
RACK 1
F6
T-401
2-A
2-C
2-6
FUTURE RACK
1 TYPICAL
2 TYPICAL
4 TYPICAL
5TYPICAL
C5
T-401
2-A
2-C
NCT
LEVEL 2
99' - 8"
LEVEL 1
86' - 4"
T-401 F2
T-401 F4
T-401 F5
RACK 1 RACK 2 RACK 3 FUTURE RACK
1 TYPICAL
2 TYPICAL
4 TYPICAL
5 TYPICAL
C5
T-401
LEVEL 2
99' - 8"
LEVEL 1
86' - 4"
SWITCH COUNTS:
POE+ Switches:-------------------------------
Total POE+ Switch ports:-------------------
Patch Panels:---------------------------------- Patch Panel Ports:---------------------------- Horiz Cable Management:------------------
TERMINATED PATCH PORT COUNTS:
Data/VOIP Ports:------------------------------ Total TCO/Phone ports required:----------
AVAILABLE SPARE PATCH PORTS:
TCO/Phone Ports Required:-------------- Total Available Patch Ports:----------------- Available Spare Patch Ports:----------------
VA DATA/VOIP SWITCH AND PATCH COUNTS
3x48 0x24
16x48
LEVEL 2
99' - 8"
ROOF
113' - 8"
LEVEL 1
86' - 4"
2-6
4 RACKS
CABLE TRAY. REFER TO SHEET TN103
FOR ADDITIONAL INFORMATION.
CABLE TRAY. REFER TO SHEET TN101
FOR ADDITIONAL INFORMATION.
CEILING, REFER TO ARCHITECTURAL
DRAWINGS FOR ADDITIONAL
INFORMATION.
CEILING, REFER TO ARCHITECTURAL
DRAWINGS FOR ADDITIONAL
INFORMATION.
LEVEL B
73' - 0"
LEVEL 2
99' - 8"
LEVEL 1
86' - 4"
ROOF
113' - 8"
BASEMENT LEVEL
73' - 0"
PROVIDE TIA APPROVED, FIRE RATED, AC GRADE PLYWOOD BACKBOARD 4'x8'x1/2", OR
APPROVED FIRE PLYWOOD. PAINT ON ALL SIDES AND WITHIN CUTOUT AREAS WITH AT
LEAST (2) COATS OF FIRE RETARDANT, LIGHT COLORED PAINT. LOCATE BACKBOARD 12" AFF, INSTALL SO 'A' SIDE OF PLYWOOD IS EXPOSED.
PROVIDE 19" X 30" 45RU 4-POST EQUIPMENT RACK, COLOR - WHITE, MINIMUM OF 30" DEPTH.
BASIS OF DESIGN IS CHATSWORTH ADJUSTABLE QUADRARACK 1521 SERIES.
GROUND BUSBAR. ALL VERTICAL AND HORIZONTAL RACKS AND CABLE TRAYS SHALL BE
BONDED TO BUSBAR. REFER TO GROUND BUS BAR DETAIL ON SHEET T-501 FOR MORE
INFORMATION.
PROVIDE 18"W X 6"H LADDER TYPE CABLE TRAY. MOUNT CABLE TRAY AT 8' AFF TO BOTTOM
OF TRAY.
6" VERTICAL WIRE MANAGERS. (TYPICAL)
(4) 4" SLEEVES THROUGH WALL WITH BUSHINGS ON BOTH SIDES.
(4) 4" CONDUITS THROUGH FLOOR TO LEVEL BELOW WITH BUSHINGS ON ALL ENDS.
PROVIDE HILTI FIRESTOP ASSEMBLY OR SYSTEM AS REQUIRED TO MAINTAIN FIRE RATING
OF PARTITION.
(4) 4" CONDUITS UP TO CABLE TRAY AT LEVEL ABOVE WITH BUSHINGS ON ALL ENDS.
PROVIDE HILTI FIRESTOP ASSEMBLY OR SYSTEM AS REQUIRED TO MAINTAIN FIRE RATING
OF PARTITION. BASIS OF DESIGN IS HILTI SPEED SLEEVE FAMILY OF PRODUCTS.
2" CONDUIT FROM FLOOR BELOW FOR FIBER BACKBONE CONNECTION. REFER TO SHEETS
T-101, T-401 AND T-601 FOR ADDITIONAL INFORMATION. PROVIDE HILTI FIRESTOP ASSEMBLY
OR SYSTEM AS REQUIRED TO MAINTAIN FIRE RATING OF PARTITION.
PROVIDE 16"W X 4"H LADDER TYPE CABLE TRAY. ROUTED VERTICALLY UP WALL. BEGINNING
AT 4" AFF, ENDING AT 8'-4" AFF. COORDINATE EXACT LOCATION OF CABLE TRAY WITH 4"
CONDUITS UP FROM LEVEL BELOW.
PROVIDE 16"W X 4"H LADDER TYPE CABLE TRAY. ROUTED VERTICALLY UP WALL.
COORDINATE EXACT LOCATION AND HEIGHTS WITH HORIZONTAL CABLE TRAY AND (4) 4"
CONDUITS THROUGH WALL.
1U FIBER OPTIC SHELF WITH (2) 12 FIBER SC CONNECTOR CASSETTES FOR TERMINATION
OF INCOMING OM4 FIBER OPTIC CABLES FROM BUILDING 38 ROOM 019. AND (1) 6 FIBER SC
CONNECTOR CASSETTES FOR TERMINATION OF OS2 CCTV CABLES FROM BUILDING 38
ROOM 019. REFER TO SHEET T-601 FOR ADDITIONAL INFORMATION.
1U, (48) PORT POE+ (DATA) SWITCH FOR DATA/VOIP NETWORK. SWITCH PROVIDED AND
INSTALLED BY VA. BASIS OF DESIGN IS CISCO 9300.
PUBLIC ADDRESS SYSTEM EQUIPMENT. REFER TO SHEET T-601 FOR ADDITIONAL
INFORMATION.
WIRELESS NETWORK EQUIPMENT. PROVIDED AND INSTALLED BY OTHERS.
2U HORIZONTAL CABLE MANAGEMENT.
2U, (48) PORT, ANGLED PATCH PANEL. PATCH PANELS TO BE COLOR CODED TO MATCH TCO
PORT COLORS. FOR A TOTAL OF (4) WHITE, (4) YELLOW, (4) BLUE, AND (4) GREEN PATCH
PANELS. REFER TO SHEETS T-001 AND T-601 FOR ADDITIONAL INFORMATION.
PROVIDE (2) RACK MOUNTED VERTICAL PDUS FOR CONNECTION OF RACK MOUNTED
EQUIPMENT. PDUS SHALL HAVE A MINIMUM OF (30) C13, (5) C19 OUTLETS AND BE RATED FOR 5KW MINIMUM. PDU BASIS OF DESIGN IS APC AP7564 (A-SIDE PDU SHALL BE BLACK IN COLOR
ON LEFT SIDE OF RACK, B-SIDE PDU SHALL BE RED IN COLOR ON RIGHT SIDE OF RACK).
CONNECT A-SIDE PDU TO ELECTRICAL CONNECTION LOCATED ABOVE RACK AND B-SIDE
PDU TO UPS OUTPUT. REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.
(1) 6KW RACK MOUNTED UPS FOR B-SIDE (CRITICAL) PDU POWER. BASIS OF DESIGN IS APC
SRT6KRMXLT-5KTF WITH (1) ADDITIONAL BATTERY PACK SRT192RMBP.
(2) PAIR OF OM4 FIBER OPTIC CABLES FROM FIBER PATCH PANEL TO FIRST DATA SWITCH.
(1) PAIR OF OS2 FIBER OPTIC CABLES FROM FIBER PATCH PANEL TO DIV. 28 CCTV SWITCH.
REFER TO FIBER BACKBONE RISER DIAGRAM ON SHEET T-601 FOR ADDITIONAL
INFORMATION.
NURSE CALL TERMINAL CABINET.
1U, (24) PORT POE+ (CCTV) SWITCH FOR CCTV NETWORK. PROVIDED BY DIV. 28
CONTRACTOR. BASIS OF DESIGN IS CISCO 3850 WITH (2) PWR-C1-1100WAC POWER
SUPPLIES.
2U HORIZONTAL CABLE MANAGEMENT. PROVIDED BY DIV. 28 CONTRACTOR.
1U, (24) PORT, ANGLED PATCH PANEL. PROVIDED BY DIV. 28 CONTRACTOR.
RACK MOUNTED CCTV EQUIPMENT 120V, 2700W UPS. PROVIDED BY DIV. 28 CONTRACTOR.
1. LABELING STANDARDS SHALL BE FOLLOWED FOR TR NUMBER, RACK NUMBER, PATCH
PANEL (A-Z), AND PORT NUMBER. EXAMPLE: TR1-1A-01.
2. WAP'S SHALL BE TERMINATED ON DATA TYPE PATCH PANELS, BUT TERMINATED ON
THEIR OWN PANELS SEPARATE FROM DATA, VOIP AND ACCESS CONTROL
TERMINATIONS. DATA, VOIP AND ACCESS CONTROL SHALL BE TERMINATED ON DATA
TYPE PATCH PANELS SEPARATE FROM WAP'S. WAP CABLING AND ASSOCIATED
EQUIPMENT PROVIDED AND INSTALLED BY OTHERS.
3. 8P8C CONNECTION PORTS IN TCO WALL PLATES SHALL BE COLOR CODED BASED ON
TYPE. REFER TO SHEET T-001 FOR CABLE COLOR CHART. TCO WALL PLATE PORT AND
CABLE COLOR SHALL MATCH ASSOCIATED PATCH PANEL COLOR.
4. LABEL ALL CABLES AND PORTS ON BOTH ENDS WITH COMPUTER GENERATED, SELF-
LAMINATING, ADHESIVE, WRAPAROUND LABELS WITH THE TCO PORT LEVEL (B, 01, 02)
ROOM NUMBER (101, 102...), AND PORT SEQUENCE NUMBER (001, 002...).
B-138-001
5. CONTRACTOR SHALL PROVIDE CABLE PULL SCHEDULE FOR EACH SWITCH IN ALL RACKS
AS PART OF SHOP DRAWING SUBMITTAL.
6. PROVIDE SERVICE LOOP, (1) FULL LOOP IN CABLE TRAY AROUND PERIMETER OF DATA
ROOM, FOR ALL STRUCTURED CABLING PRIOR TO TERMINATION ON PATCH PANEL.
7. PATCH PANELS ARE TO BE COLOR CODED WITH THE DATA OUTLET PORT THAT IT IS
ASSOCIATED WITH. YELLOW, BLUE, GREEN, AND WHITE. REFER TO WALL MOUNTED
OUTLET DETAIL ON SHEET T-501 FOR ADDITIONAL INFORMATION.
PORT SEQUENCE
ROOM NUMBER
LEVEL
CODED NOTES:
DRAWING NOTES:
0 1' 2' 3'
1" = 1'-0"
0 1' 2' 4' 6'
1/2" = 1'-0"
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
ENGINEER ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title
Approved:
Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH
www.abovegroupinc.com
COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
/3
/2
:3
:1
P
M B
IM
/0
V A
P ro v id e n c e M e n ta l H e a lt h
B u ild in g
P H
/0
V A
P ro v id e n c e
M H
C P
H
R
D iv
.r v t
T-401
650-347PROVIDENCE VAMC MENTAL
HEALTH PHASE 2
PROVIDENCE, RI
JFR CVMFEB 04 2022
CONSTRUCTION
DOCUMENTS
TELECOM ENLARGED PLANS
FULLY SPRINKLERED
Christopher H. Van Meter RCDD Reg. No. 285002
1/2" = 1'-0" C7
ENLARGED TELEDATA RM 138
1/2" = 1'-0" F6
TELEDATA RM 138 ELEVATION
1" = 1'-0"
F5
RACK 3 ELEVATION
1" = 1'-0" F4
RACK 2 ELEVATION
1" = 1'-0"
F2
RACK 1 ELEVATION
N.T.S.
TELE DATA RM T-138 3D
C1 1/4" = 1'-0"C5
CONDUIT ROUTING SECTION
0 2' 4' 8' 12'
1/4" = 1'-0"
OUTLET DESIGNATOR LABELS
BLANK FACEPLATE FOR FUTURE CONNECTIONS
SINGLE GANG FACEPLATE
FRAME WITH 4 PORTS
UTP 4 PAIR CAT6A CABLES TO TR. CABLE SHALL BE PLENUM OR NON-
PLENUM RATED PER DIVISION 27 SPECIFICATIONS.
1-1/2" CONDUIT STUB UP ABOVE CEILING
NOTES:
1. CABLE LABELING STANDARDS SHALL BE AS INDICATED ON SHEET T-401.
2. 8P8C CONNECTIONS IN WALL PLATES SHALL BE COLOR CODED TO MATCH PATCH PANEL
COLORS AND CABLE COLORS INDICATED ON THIS SHEET AND SHEET T-001.
TCO #
TCO PORT#
2-001 2-002
3. WALL BOX SHALL BE DOUBLE-GANG TELECOMMUNICATIONS-RATED WORK BOX WITH RIGID
CONDUIT EXTENDING TO THE HORIZONTAL PATHWAY.
(4) 8P8C CAT6A DATA MODULES
107-2
TCO ROOM NUMBER
TCO NUMBERING EXAMPLE:
RM 17, SECOND TCO IN ROOM
YELLOW BLUE
GREEN WHITE
TCO IN ROOM
2-003 2-004
TIA/EIA T568A
JACK POSITIONS
PAIR4PAIR1PAIR3
PAIR2
BRW-BROW-BLBLW-OGW-G
MODULAR JACK WIRING (FRONT VIEW)
2 3 4 5 6 7 8
FLOOR SLAB
1" CONDUIT TO ABOVE CEILING
ACCESSIBLE CEILING
(ROUTE CABLE IN CONDUIT ABOVE HARD
CEILINGS.)
J-HOOKS
1" CONCEALED CONDUIT EMT
WALL
FACEPLATE
DEEP 4 SQUARE BOX WITH
SINGLE GANG STEEL PLASTER RING.
3'-5' MAX
CAT6A DATA CABLE
0.312Ø (54)
0.437Ø (8) CHATSWORTH "UL"
GROUND BAR LABEL
UL
1' 1/8" TYPICAL
PART NO. 40153-020
1"
1 1/2"
PROVIDE GROUNDING CONDUCTOR TO BUILDINGS STEEL PER TIA-607-B.
PROVIDE GROUNDING CONDUCTOR TO MAIN
SERVICE GROUND POINT PER TIA-607-B.
INSULATOR MOUNTING
BRACKET (TYP.) CPI 10622-000
INSULATOR (TYP)
GENERAL NOTES:
ALL HARDWARE (BOLTS, NUTS, WASHERS,ETC.) SHALL BE SOLID
COPPER OR BRONZE. COPPER PLATING SHALL NOT BE
ACCEPTABLE.
BUSBAR SHALL BE 1/4" THICK (MINIMUM).
1.
INCREASE LENGTH OF BUSBAR, FOR NUMBER OF
CONNECTIONS, AS REQUIRED TO MAINTAIN CORRECT
SPACING BETWEEN LUGS.
2.
3.
CPI 10622-012 OR EQUALPROVIDE # 6 COPPER CABLE 2-HOLE LUG
CLAMP FOR CABLE CONNECTION. (TYP)
2-HOLE LUG (TYP)
TGB-XXX
PROVIDE WHITE CORE BAKELITE NAMEPLATE FASTENED TO A
WALL/SURFACE BELOW BUSBAR AT EACH FLOOR, WITH
DESIGNATION ENGRAVED THEREON IN 1/2" HIGH LETTERS.
INSTALLATION NOTES:
SELECT BOLT LENGTH TO PROVIDE A MINIMUM OF TWO EXPOSED THREADS.A.
BURNISH MOUNTING SURFACE TO REMOVE PAINT IN THE AREA OF LUG CONTACT.B.
APPLY ANTI-OXIDANT COMPOUND TO MATING SURFACE OF LUG AND WIPE CLEAN EXCESS COMPOUND.C.
USE SOLID COPPER WIRE AND MECHANICAL 2-HOLE LUG FOR ALL EXTERIOR GROUNDING.D.
#6 OR #2 GRN TO GROUND BAR OF FLAT SURFACE.
#6 IS USED PRIMARILY AS CABINET TO BUS LINK.
#6 GRN OR #2 GRN 2 HOLE LUG
1/4-20 HEX BOLT
1/4" FLAT WASHER
1/4-20 HEX NUT
1/4" EXT. TOOTH LOCKWASHER
PRIMARY GROUND BAR/
METAL ENCLOSURE
NOTES:
#6 AWG COPPER GROUNDING CONDUCTOR.
BOND RACKS TO BUSBAR.
BOND METAL CONDUIT TO BUSBAR.
REFER TO DETAIL 6 OF FOR TGB CONNECTIVITY.
BOND CABLE TRAY & RUNWAY TO BUSBAR.
EQUIPMENT RACK
TGB
NOTES:
1. #3/0 TO PRIMARY PROTECTOR.
2. #3/0 TO ELECTRICAL PANEL.
3. #3/0 TO EQUIPMENT RACKS/CABLE TRAY.
4. TWO-HOLE LUG, IRRIVERSABLE.
TMGB: TELECOMMUNICATIONS MAIN GROUND BUSBAR
TGB: TELECOMMUNICATIONS GROUND BUSBAR
MSB: MAIN SWITCH BOARD
TBB: TELECOMMUNICATIONS BONDING BACKBONE
GENERAL NOTES:
1. BONDING CONDUCTOR SHALL BE NO SMALLER THAN #2 CU.
2. ALL WORK SHALL COMPLY WITH NEC ARTICLE 250, UL 467, ANSI/TIA TIA-607-C, NECA/BICSI 607-2011.
3. PREPARE BUSBAR SURFACE AS DESCRIBED BELOW:
a. USE AN ABRASIVE PAD, REMOVE ANY DIRT, GREASE, OIL OR OXIDATION THAT IS PRESENT AT
THE SURFACE.
b. APPLY THIN COAT OF AN ANTIOXIDANT TO THE CONNECTION POINT ON THE BUSBAR.
c. USE STAINLESS STEEL OR SILICON BRONZE HARDWARE, TIGHTEN AND TORQUE TO THE
REQUIREMENTS OF THE HARDWARE MATERIAL, SIZE AND GRADE.
4. CONDUCTORS SHALL BE COPPER.
5. LUGS SHALL BE 2-HOLE TYPE WITH INSPECTION WINDOW, LONG BARREL, IRREVERSIBLE
(COMPRESSION OR EXOTHERMIC WELDING) AND MECHANICAL.
6. REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL GROUNDING INFORMATION.
TBB LENGTH (FT)
TBB CONDUCTOR TABLE
<13
14-20
21-26
TBB SIZE (AWG)
27-33
34-41
42-52
1/0
53-66
67-84
85-105
2/0
3/0
4/0
106-125
126-150
151-175
250 KCMIL
300 KCMIL
350 KCMIL
176-250
251-300
>301
500 KCMIL
600 KCMIL
750 KCMIL
X
DATA RM 019
MGB
TBB CONDUCTOR PER TABLE
DATA RM 138
TGB3
PROVIDE NUMBER OF SLEEVE AS REQUIRED TO MATCH CABLE TRAY CROSS SECTIONAL AREA. UL W-L 3112
PROVIDE SUPPORTS
WITHIN 12" OF WALL
ON BOTH SIDES
RATED WALL PENETRATION. 1
HOUR FIRE/SMOKE OR GREATER
PACK WITH FIRE SAFING AFTER
CABLE INSTALLATION
CABLE TRAY, REFER
TO DRAWINGS FOR
EXACT SIZE AND TYPE
4" STRAP TO TRAY
PROVIDE APPROPRIATE UL LISTED FIRE
SAFING AT SLEEVE PENETRATIONS OF RATED
WALLS TO RESTORE FIRE RATING OF WALL
4" EMT CONNECTOR
WITH GROUNDING
BOND BUSHING
GROUND WIRE.
MINIMUM #6 COPPER
TO CABLE TRAY
4" SLEEVE (TYPICAL
FOR ALL SLEEVES) QUANTITIES SHOWN ON
FLOOR PLANS.
WALL
LENGTH
WIDTH
B
A
NOTES:
"A"
"B" MEASURED FROM MIDDLE OF CROSS SLATS.
MEASURED FROM END OF STRINGER TO MIDDLE OF CROSS SLAT.
UNIVERSAL TUBULAR RUNWAY SYSTEM
CABLE RUNWAY RADIUS DROP
#6 COPPER TO NEXT
SECTION
N.T.S.B7
WALL MOUNTED OUTLET - (TCO) VOICE/DATA
N.T.S.D7
MODULAR JACK WIRING DETAIL
N.T.S.
F7
TYPICAL FLUSH OUTLET MOUNTING
N.T.S.B4
GROUND BUS BAR (TYP FOR ALL TR'S)
N.T.S.D4
GROUND BAR 2-HOLE LUG TERMINATION
N.T.S.
F4
GROUNDING DETAIL (TYP. TELECOM ROOM)
N.T.S.B1
TELECOM GROUNDING RISER DIAGRAM
N.T.S.D1
TYPICAL CABLE TRAY WALL PENETRATION
N.T.S.
F1
TUBULAR RUNWAY/LADDER RACK IN TR'S
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
ENGINEER ARCHITECT/ENGINEER OF RECORD
WBRC
A R C H I T E C T S • E N G I N E E R S
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title
Approved:
Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH
www.abovegroupinc.com
COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
/3
/2
:3
:1
P
M B
IM
/0
V A
P ro v id e n c e M e n ta l H e a lt h
B u ild in g
P H
/0
V A
P ro v id e n c e
M H
C P
H
R
D iv
.r v t
T-501
650-347
PROVIDENCE VAMC MENTAL
HEALTH PHASE 2
PROVIDENCE, RI
JFR CVMFEB 04 2022
CONSTRUCTION
DOCUMENTS
TELECOM DETAILS
FULLY SPRINKLERED
Christopher H. Van Meter RCDD Reg. No. 285002Revisions: Revision Description Date:
REFER TO RACK ELEVATIONS ON SHEET
T-401 FOR ADDITIONAL INFORMATION.
TELE DATA RM 138
LEVEL 2 ABOVE
ROUTE NEW FIBER OPTIC CABLE TO NEW
FIBER PATCH PANEL. REFER TO SHEETS
T-101 AND T-401 FOR MORE
INFORMATION.
RACK 2RACK 1
RACK 3
FIBER PATH
PANEL
SWITCH 1 RACK 1
(2) PAIR OM4 FIBER
OPTIC CABLE
LEVEL 1
FINISHED FLOOR
CCTV SWITCH 1 BY DIV 28
(1) PAIR OS2 FIBER
OPTIC CABLE FOR
CCTV NETWORK
ROOF
THIRD FLOOR
COMM RM 311
PA EQUIPMENT
REFER TO SHEET T-401
FOR RACK ELEVATION
S
CABLE PER MANUFACTURERS
INSTALLATION INSTRUCTIONS
CEILING PA SPEAKER
TYPICAL, UON.
12V FROM FIRE ALARM RELAY FOR FIRE
ALARM SHUTDOWN OF PA SYSTEM
PA HANDSET AT MSA RM 135
RECEPTION DESK
INTERCOMM INPUT FROM
EXISTING VA PA SYSTEM IN BLDG
38 PHASE 1
RACK 3
NEW PA COMPONENTS TO BE COMPATIBLE WITH
EXISTING BOGEN C35 PA SYSTEM ALREADY IN USE IN
BLDG 38 PHASE 1. CONTRACTOR TO VERIFY
COMPATIBILITY OF SYSTEMS PRIOR TO CONSTRUCTION.
CAT6A CABLE, TYPICAL, UNLESS
OTHERWISE NOTED
EOL
RESISTOR
CONTRACTOR TO PROVIDE A FULLY FUNCTIONAL PUBLIC ADDRESS
COMPONENTS THAT ARE CONNECTED TO EXISTING BOGEN C35 PUBLIC
ADDRESS SYSTEM FOR ZONED PAGING CAPABILITIES. PA SYSTEM TO
BE CUT OUT UPON ACTIVATION OF FIRE ALARM SYSTEM FOR FIRE
ALARM VOICE EVAC COMMUNICATIONS OVER FIRE ALARM SPEAKERS.
TELE/DATA ROOM 138
CAT6A CABLE TYPICAL, UON
EXISTING RAULAND
RESPONDER 5000
NURSE CALL
SYSTEM
N N E
D P
NCSNEW NURSE CALL
TERMINAL CABINET
TYPICAL CONNECTIONS
TYPICAL CONNECTIONS
CABLE PER MANUFACTURER
SPECIFICATIONS
TELE/DATA ROOM 019
DEDICATED 120V BRANCH CIRCUIT
24V
BATTERY
PUBLIC SAFETY RADIO
BI-DIRECTIONAL
ANTENNA MASTER
BDA AMPLIFIER
BDA
ANNUNCIATOR
PUBLIC SAFETY RADIO
DONOR ANTENNA
ANTENNA MAST - BOND
TO BUILDING STEEL
LIGHTNING ARRESTOR - PROVIDE GROUND, LOCATE
OUTSIDE BEFORE CABLE BUILDING ENTRY
CONNECT TO EXISTING PHASE 1 FIRE ALARM
CONTROL PANEL.
(5) SUPERVISORY INPUT MODULES REQUIRED:
BDA ANTENNA FAILURE
BDA TROUBLE
BDA POWER LOSS
BDA CHARGER TROUBLE
BDA LOW BATTERY
1/2 INCH COAX CABLE
OUTDOOR 2 HOUR RATED
(2) 120V, 20A
EMERGENCY CIRCUITS
DAS ANTENNA'S (SEE FLOOR
PLANS FOR QUANTITIES AND
LOCATIONS) (TYPICAL)
LOCATE AT PHASE 1
FIRE ALARM
ANNUNCIATOR PANEL
BASEMENT
1ST FLOOR
2ND FLOOR
ROOF
2-CONDUCTOR 18GA
CABLE & (2) RS-485
1/2 INCH COAX CABLE
2 HOUR RATED
RF TAPPER - LOW PIM
(-161dBc…