Attachment 06 - Electrical Drawings - Pt 1.pdf

PDF 12 MB Posted

Attached to
36C77623R0039 - Y1DZ - New Mental Health Building Phase 2 Minor Construction - Providence, RI
Solicitation number
36C77623R0039
Issued by

About this file

This solicitation is seeking proposals for a firm-fixed-price construction contract to complete phase two of a new mental health building project at the Providence VA Medical Center in Rhode Island. The Department of Veterans Affairs intends to award a single contract to furnish all labor, materials, equipment and supervision for general construction, site work, alterations, finishes, HVAC, electrical, plumbing, fire alarm and suppression systems, security and other work contained in the construction documents. The contractor will perform all work consistent with the provided drawings and specifications. The solicitation number is 36C77623R0039 and proposals are due by the date specified in the solicitation. The construction project involves completing phase two of a new mental health building to serve veterans at the Providence VA Medical Center.

View the file

Other files

File Type Posted
36C77623R0039 0002.pdf PDF
Attachment 18 - Addendum 01.pdf PDF
Attachment 24 - Sheet P-001.pdf PDF
Attachment 23 - MDP Panel Info.pdf PDF
Attachment 20 - Updated Wage Rates.pdf PDF
Attachment 21 - CR211 Panel Info.pdf PDF
Attachment 19 - Technical Questions and Answers.xlsx XLSX spreadsheet
Attachment 22 - Fire Alarm As-Builts.pdf PDF
S02 - Solicitation - 36C77623R0039_R1.pdf PDF
Attachment 17 - Site Visit Sign in Sheet.pdf PDF
36C77623R0039 0001.pdf PDF
Attachment 08 - Fire Protection Drawings.pdf PDF
Attachment 03 - Architectural Drawings - Pt 1.pdf PDF
Attachment 12 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 04 - Architectural Drawings - Pt 2.pdf PDF
Attachment 02 - Specifications - Pt 2.pdf PDF
Attachment 15 - Providence County - Wage Rates.pdf PDF
Attachment 11 - Structural Drawings.pdf PDF
Attachment 14 - VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 12-14-2021.docx DOCX document
Attachment 16 - SOW - Mental Health Phase 2.pdf PDF
Attachment 05 - Civil Drawings.pdf PDF
S02 - Solicitation - 36C77623R0039.pdf PDF
Attachment 01 - Specifications - Pt 1.pdf PDF
Attachment 07 - Electrical Drawings - Pt 2.pdf PDF
Attachment 10 - Plumbing Drawings.pdf PDF
Attachment 13 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 09 - Mechanical Drawings.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1PH SINGLE-PHASE

3PH THREE-PHASE

4W FOUR-WIRE

A/E ARCHITECT/ENGINEER

AF AMPERE FRAME OR AMP FUSE

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMP AMPERE

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BLDG BUILDING

C CONDUIT

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CKT CIRCUIT

CLG CEILING

COAX COAX CABLE

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUE

COORD COORDINATE

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CU COPPER

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DISC DISCONNECT

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DS DISCONNECT SWITCH

DWG DRAWING

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

ESMT EASEMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

ETR EXISTING TO REMAIN

ELECTRICAL ABBREVIATIONS

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FLA FULL LOAD AMPS

FP FIRE PROTECTION

FT FEET OR FOOT

GND GROUND

G or GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HZ HERTZ

IESNA ILLUMINATION ENGINEERING SOCIETY OF NORTH AMERICA

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

kV KILOVOLT kVA KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWH KILOWATT HOUR

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LRA LOCKED ROTOR AMPS

LTG LIGHTING

LV LOW VOLTAGE

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT MICROWAVE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NEUT OR N NEUTRAL

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

P POLE

PA PUBLIC ADDRESS

PCB POLYCHLORINATED BIPHENYL

PH PHASE

PNL PANEL

POD POWER OPERATED DAMPER

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

RCP REFLECTED CEILING PLAN

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

REQD REQUIRED

SCC SHORT CIRCUIT CAPACITY

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

W WATT

WH WATER HEATER

WP WEATHERPROOF

XFER TRANSFER

XFMR TRANSFORMER

ABBR. DESCRIPTION ABBR. DESCRIPTION ABBR. DESCRIPTION

AWG AMERICAN WIRE GAUGE

KCMIL ONE-THOUSAND CIRCULAR MILS

NA NOT APPLICABLE

HD HEAT DETECTOR

TEE SPLICE

FOUR-WAY SPLICE

NEW (HEAVY, SOLID LINE)

EXISTING TO REMAIN (LIGHT, SOLID LINE)

ABC

PANELBOARD MAIN CIRCUIT BREAKER TYPE, ONE-LINE

### - INDICATES BREAKER RATING

ABC - INDICATES PANEL DESIGNATION

ABC

PANELBOARD MAIN LUG TYPE, ONE-LINE

### - INDICATES BUS RATING

ABC - INDICATES PANEL DESIGNATION

DN

DN

THRU-ROOF CONDUCTOR

DOWN CONDUCTOR

GROUND TERMINAL

AIR TERMINAL; PROVIDE PARAPET TYPE BASE WHERE MOUNTED ON PARAPET;

PROVIDE FLAT BASE FOR MECHANICAL EQUIPMENT OR ROOF PERIMETER WITH NO

PARAPET; PROVIDE BLUNT TIP WHERE MOUNTED ON INTERIOR OF ROOF, UNLESS

OTHERWISE NOTED ON LIGHTNING PROTECTION PLANS

BONDING PLATE

LIGHTNING PROTECTION SYSTEM

DISCONNECT SWITCH, FUSED

DISCONNECT SWITCH, UNFUSED

JUNCTION BOX

EARTH GROUND

RECEPTACLE, DUPLEX

RECEPTACLE, DOUBLE DUPLEX (QUADRAPLEX)

ELECTRICAL SYMBOLS - POWER/LIGHTING PLANS

SWITCH (# SUBSCRIPT AS INDICATED BELOW) - SEE PLANS AND SPECIFICATIONS FOR DETAILS

BLANK = SINGLE POLE 2 = DOUBLE POLE

4 = FOUR-WAY

K = KEY OPERATED

P = WITH PILOT LIGHT

RC= REMOTE CONTROL

WP= WEATHER PROOF

OS= DUAL TECHNOLOGY OCCUPANCY SENSOR

a= SUBSCRIPT DEFINES FIXTURES THAT ARE CONTROLLED BY SWITCH

X= EXPLOSION PROOF

HOA= HAND/OFF/AUTOMATIC

3 = THREE-WAY

D = DIMMER

F = FAN SWITCH

LV= LOW VOLTAGE - SEE BELOW FOR DETAILS

T = TIMER OPERATED

M = MANUAL MOTOR STARTING

MP= MOTOR SNAP WITH PILOT LIGHT

(THERMAL TYPE)

E= SWITCH ON EMERGENCY CIRCUIT

(RED DEVICE)

LIGHTING, EXTERIOR BUILDING

J

SYMBOL DESCRIPTION DESCRIPTION

ALARM, FIRE, PANEL; LETTERS INDICATE AS FOLLOWS:

NAC = BOOSTER PANEL FACP = CONTROL PANEL

FAAP = ANNUNCIATOR PANEL

FACP

DESCRIPTION

SUBSCRIPTS (TYPICAL FOR ALL RECEPTACLES):

G = GFCI TYPE

CH = MOUNTED AT COUNTER HEIGHT WITH BOTTOM OF DEVICE AT 6" ABOVE BACKSPLASH

TV = RECEPTACLE MOUNTED ADJACENT TO TV OUTLET

USB = DUPLEX RECEPTACLE WITH (1) USB TYPE 'A' AND (1) USB TYPE 'C'

WP = DEVICE PROVIDED WITH WEATHERPROOF IN-USE METAL COVER

EWC = DENOTES DEVICE FOR ELECTRIC WATER COOLER - COORDINATE WITH EWC INSTALLER FOR

MOUNTING HEIGHT

E = WIRED TO CRITICAL BRANCH CIRCUIT; PROVIDE RED DEVICE AND COVER PLATE

TRANSFORMER, PLAN

BRANCH CIRCUIT HOMERUN. "ABCD" INDICATES PANEL NAME, "##" INDICATE POLE POSITIONS IN PANEL. ONE

SEPARATE GREEN GROUNDING CONDUCTOR SHALL BE PROVIDED FOR EACH HOMERUN

T

ABCD-## TRANSFORMER, ONE-LINE

FUSIBLE DISCONNECT SWITCH, ONE-LINE

###AF - INDICATES FUSE RATING

###AS - INDICATED SWITCH RATING

###AF

BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS, SURFACE MOUNTED

BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS, FLUSH MOUNTED

BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS, SURFACE MOUNTED

BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS, FLUSH MOUNTED

SWITCHBOARD/ SWITCHGEAR/ DISTRIBUTION PANEL, UNDER 250 VOLTS

SWITCHBOARD/ SWITCHGEAR/ DISTRIBUTION PANEL - OVER 250 VOLTS

LOW VOLTAGE SWITCH - SEE PLANS, SPECIFICATIONS AND WIRING DIAGRAMS FOR DETAILS

LV2Da

S

S

'D' INDICATES 0-10V DIMMING

'2' INDICATES NUMBER OF ZONES CONTROLLED

VFD VARIABLE FREQUENCY DRIVE

A

EXIT LIGHT, LED, WALL MOUNTED

EXIT LIGHT, LED, CEILING OR PENDANT MOUNTED; DIRECTIONAL ARROWS AS INDICATED; SHADED QUADRANT

INDICATES FACE(S) OF LUMINAIRE

LED, RECESSED, PENDANT OR SURFACE CEILING LUMINAIRE

LED, RECESSED, PENDANT OR SURFACE CEILING LIGHTING FIXTURE

SHADING INDICATES FIXTURE CONNECTED TO EMERGENCY CIRCUIT

OR PROVIDED WITH INTEGRAL EMERGENCY BATTERY PACK; "E"

AFTER FIXTURE TYPE TAG INDICATES INTEGRAL BATTERY PACK

UNLESS OTHERWISE NOTED ON LIGHT FIXTURE SCHEDULE

(TYPICAL FOR ALL LIGHT FIXTURE SYMBOLS)

LED FIXTURE, RECESSED, PENDANT OR SURFACE CEILING

LED STRIP LUMINAIRE

FIXTURE TYPE

LOWER CASE LETTER INDICATES CONTROLLING SWITCH

a

CIRCUIT NUMBER

LED, WALL MOUNTED LUMINAIRE

DN

UP

CONDUIT CONTINUED

CONDUIT STUBBED OUT OR UP

CONDUIT TURNING DOWN

CONDUIT TURNING UP

MULTI-SERVICE FLOOR BOX WITH DUPLEX RECEPTACLE, VOICE/DATA/AV DEVICES (REFER TO TECHNOLOGY

DRAWINGS OR OWNER'S VENDOR DRAWINGS FOR LOW VOLTAGE REQUIREMENTS)

CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSORGROUND BUS BAR, COPPER

SPD SURGE PROTECTIVE DEVICE

SYMBOL SYMBOL

WALL MOUNTED JUNCTION BOXJ

LPP LIGHTING POWER PACK RELAY

LPD LIGHTING POWER PACK RELAY WITH 0-10V DIMMING

###AS

ELECTRICAL ONE-LINE

###A

BRANCH CIRCUIT BREAKER

### - INDICATES BREAKER RATING

OS

a

LOWER CASE LETTER INDICATES FIXTURES CONTROLLED

LOWER CASE LETTER INDICATES FIXTURES / RELAY CONTROLLED

'LV' INDICATES LOW VOLTAGE SWITCH

ELECTRICAL DRAWING INDEX

SHEET DESCRIPTION

E-001 ELECTRICAL LEGENDS

E-002 ELECTRICAL GENERAL NOTES

E-100 ELECTRICAL SITE PLAN

EL201 LEVEL B PLAN - LIGHTING

EL202 LEVEL 1 PLAN - LIGHTING

EL203 LEVEL 2 PLAN - LIGHTING

EP201 LEVEL B PLAN - POWER

EP202 LEVEL 1 PLAN - POWER

EP203 LEVEL 2 PLAN - POWER

EP213 LEVEL 2 PHASE 1 - POWER

EP214 ROOF PLAN - LIGHTNING PROTECTION

E-501 ELECTRICAL DETAILS

E-601 ELECTRICAL ONE-LINE DIAGRAM

E-801 ELECTRICAL SCHEDULES

E-802 ELECTRICAL PANEL SCHEDULES

E-803 ELECTRICAL PANEL SCHEDULES

EC101 ELECTRICAL CALCULATIONS - LEVEL B

EC102 ELECTRICAL CALCULATIONS - LEVEL 1

EC103 ELECTRICAL CALCULATIONS - LEVEL 2

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

ENGINEER ARCHITECT/ENGINEER OF RECORD

WBRC

A R C H I T E C T S • E N G I N E E R S

WWW.WBRCAE.COM

BANGOR, MAINE 207-947-4511

PORTLAND, MAINE 207-828-4511

SARASOTA, FLORIDA 941-556-0757

STAMP

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

Project TitleDrawing Title

Approved:

Phase

Location

Issue Date

Project Number

Building Number

Drawing Number

Checked Drawn

TRUE NORTH

PROJECT NORTH

www.abovegroupinc.com

COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

/1

/2

:5

:2

A

M B

IM

/0

V A

P ro v id e n c e M e n ta l H e a lt h

B u ild in g

P H

/0

V A

P ro v id e n c e

M H

C P

H

R

D iv

.r v t

E-001

650-347

PROVIDENCE VAMC MENTAL

HEALTH PHASE 2

PROVIDENCE, RI

JFR SDLFEB 04 2022

CONSTRUCTION

DOCUMENTS

ELECTRICAL LEGENDS

FULLY SPRINKLERED

JOHN F. RAINE, P.E.

MD License #41408Revisions: Revision Description Date:

ELECTRICAL GENERAL NOTES ELECTRICAL DEMOLITION NOTES

WHERE THERE IS A DISCREPANCY BETWEEN ABOVE GENERAL NOTES AND SPECIFICATIONS, WHERE APPLICABLE, SPECIFICATIONS SHALL BE FOLLOWED

APPLICABLE CODES

1. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), INCLUDING (BUT NOT LIMITED TO):

a. NATIONAL ELECTRICAL CODE (NEC), NFPA 70 - 2020

b. NATIONAL FIRE ALARM CODE, NFPA 72 - 2019

c. LIFE SAFETY CODE, NFPA 101 – 2021

d. STANDARD FOR THE INSTALLATION OF LIGHTNING PROTECTION SYSTEMS, NFPA 780

e. HEALTH CARE FACILITIES CODE, NFPA 99 - 2021

2. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI), INCLUDING (BUT NOT LIMITED TO):

a. NATIONAL ELECTRICAL SAFETY CODE, ANSI C2

3. OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA)

4. FEDERAL COMMUNICATION COMMISSION (FCC)

5. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

6. INSULATED CABLE ENGINEERS ASSOCIATION (ICEA)

7. INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

8. NATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)

9. AMERICAN SOCIETY OF TESTING AND MATERIALS (ASTM)

10. ILLUMINATION ENGINEERING SOCIETY (IES)

11. ANTI-FRICTION BEARING MANUFACTURERS ASSOCIATION (AFBMA)

12. BUILDING OFFICIALS AND CODE ADMINISTRATORS INTERNATIONAL, INC. (BOCA)

13. INTERNATIONAL CODE COUNCIL (ICC):

a. INTERNATIONAL BUILDING CODE (IBC)

14. UNIFORM BUILDING CODE (UBC)

15. NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION INSTALLATION STANDARDS (NECA)

16. AMERICANS WITH DISABILITIES ACT (ADA)

17. APPLICABLE STATE AND LOCAL CODES, AMENDMENTS, REGULATIONS, AND PRACTICES.

18. APPLICABLE REGULATORY REQUIREMENTS AND ADVISORY PRACTICES OF APPROPRIATE

a. AUTHORITIES HAVING JURISDICTION (AHJs).

19. APPLICABLE STANDARDS, REGULATIONS, AND PRACTICES OF THE OWNER.

20. VA ELECTRICAL DESIGN MANUAL - 2019

21. VA LIGHTING DESIGN MANUAL - 2015

General:

1. THE DRAWINGS AND APPLICABLE SPECIFICATIONS SHALL BE CONSIDERED SUPPLEMENTARY,

ONE TO THE OTHER AND ARE CONSIDERED THE "CONTRACT DOCUMENTS". ALL WORKMANSHIP,

METHODS AND/OR MATERIALS DESCRIBED OR IMPLIED BY ONE AND NOT DESCRIBED OR

IMPLIED BY THE OTHER SHALL BE PROVIDED, FURNISHED OR PERFORMED AS IF IT HAD

APPEARED IN BOTH SECTIONS. THE TERM "CONTRACT DOCUMENTS" DESCRIBED HEREIN IS

NOT LIMITED SOLELY TO THE ELECTRICAL PORTION OF THE DRAWINGS AND SPECIFICATIONS,

BUT ENCOMPASSES THE DRAWINGS AND SPECIFICATIONS OF ALL DIVISIONS AS A WHOLE.

2. PROVIDE AN OPERATING AND MAINTENANCE MANUAL TO OWNER PRIOR TO THE FINAL

ACCEPTANCE. THE MANUAL SHALL INCLUDE, AS A MINIMUM, (1) SUBMITTAL DATA STATING

EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING

MAINTENANCE. ALSO PROVIDE TWO OPERATIONS AND MAINTENANCE MANUALS FOR EACH

PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS

AND METHOD OF OPERATION FOR EQUIPMENT SHALL BE CLEARLY IDENTIFIED, AND THE NAME,

PHONE NUMBER AND ADDRESS OF AT LEAST ONE QUALIFIED SERVICE AGENCY.

3. INCLUDE ALL COSTS FOR EXCAVATION, SAW CUTTING, DIRECTIONAL BORING, CORE DRILLING, BACKFILLING, SURFACE RESTORATION, REPAIR OF FINISHES, ETC. THAT IS REQUIRED IN ORDER

TO MEET THE PROJECT REQUIREMENTS.

4. INCLUDE IN BID ALL COSTS ASSOCIATED WITH TEMPORARY ELECTRICAL SERVICE AS REQUIRED

FOR USE BY ALL TRADES DURING CONSTRUCTION. REMOVE TEMPORARY POWER AT THE

COMPLETION OF THE PROJECT. OBTAIN AND PAY FOR ALL REQUIRED PERMITS FOR

TEMPORARY POWER. ENGINEER OF RECORD SHALL BE PROVIDED WITH ADDITIONAL

COMPENSATION FROM THE CONTRACTOR WHERE SIGNED & SEALED DRAWINGS ARE

REQUESTED BY THE CONTRACTOR TO THE ENGINEER OF RECORD IF REQUIRED BY THE AHJ

FOR THE TEMPORARY POWER.

5. PROVIDE A COMPLETE UL LISTED LIGHTNING PROTECTION SYSTEM WITH A MASTER LABEL FOR

THE ENTIRE FACILITY PER THE REQUIREMENTS OF NFPA 780, AND THE DIVISION 26

SPECIFICATIONS, UNLESS NOTED OTHERWISE. LIGHTNING PROTECTION SYSTEM SHALL

INCLUDE BURIED COUNTERPOISE, UNLESS NOTED OTHERWISE.

6. INCLUDE IN BID THE TRANSPORT AND DISPOSAL OR RECYLING OF ALL WASTE MATERIALS

GENERATED BY THIS PROJECT IN ACCORDANCE WITH ALL LOCAL, STATE AND FEDERAL RULES,

REGULATIONS AND GUIDELINES APPLICABLE. COMPLY FULLY WITH FLORIDA STATUTES

REGARDING MERCURY-CONTAINING DEVICES, AND WITH ALL DEP AND EPA APPLICABLE

GUIDELINES AT THE TIME OF DISPOSAL. PROVIDE OWNER WITH WRITTEN CERTIFICATION OF

ACCEPTED DISPOSAL.

7. ALL POWER CIRCUITS HAVE BEEN DESIGNED IN COMPLIANCE WITH SECTION C405.7.3 OF THE

ENERGY CONSERVATION CODE, REQUIRING 2% OR LESS VOLTAGE DROP FOR FEEDERS, AND

3% OR LESS VOLTAGE DROP FOR BRANCH CIRCUITS.

ELECTRICAL SYSTEM HAS BEEN DESIGNED IN ACCORDANCE WITH THE 2020 NATIONAL

ELECTRICAL CODE (NFPA 70).

8. ALL BRANCH CIRCUITS SHALL BE FURNISHED WITH A DEDICATED NEUTRAL. SHARED NEUTRALS

ARE NOT ALLOWED UNLESS SPECIFICALLY NOTED ON THE DRAWINGS.

9. VERIFY AND COORDINATE LOCATIONS OF ANY MISCELLANEOUS EQUIPMENT REQUIRING

ELECTRICAL CONNECTIONS (I.E., COPIERS, FAX MACHINES, PRINTERS, KITCHEN APPLIANCES, LAUNDRY APPLIANCES, PROJECTION SCREENS, SHOP TOOLS, MACHINE, ELEVATORS, ETC.)

WITH APPROVED SHOP DRAWINGS, OWNER-PROVIDED CUT SHEETS, MANUFACTURER'S

INSTRUCTIONS, AND EQUIPMENT NAMEPLATE INFORMATION, PRIOR TO ROUGH IN, AND

PROVIDE ALL NECESSARY ELECTRICAL REQUIRED.

10. VERIFY AND COORDINATE LOCATIONS AND EXACT ELECTRICAL REQUIREMENTS FOR ALL

MECHANICAL, PLUMBING AND FIRE PROTECTION EQUIPMENT PRIOR TO SUBMITTAL OF SHOP

DRAWINGS OF ELECTRICAL EQUIPMENT. PROVIDE ALL NECESSARY RACEWAYS, CONDUCTORS,

BOXES, EQUIPMENT, ACCESSORIES, ASSOCIATED DISCONNECT SWITCHES, CIRCUIT BREAKERS,

CONTROL TRANSFORMERS, FIRE ALARM SHUTDOWN, ETC. REQUIRED FOR A COMPLETE AND

OPERATIONAL SYSTEM. COORDINATE WITH APPROPRIATE TRADE'S APPROVED SHOP

DRAWINGS, MANUFACTURER'S INSTRUCTIONS, AND EQUIPMENT NAMEPLATE INFORMATION,

PRIOR TO ROUGH IN, AND PROVIDE ALL NECESSARY ELECTRICAL REQUIRED, UNLESS

OTHERWISE NOTED.

11. ALL WORK ON THE ELECTRICAL SYSTEM REQUIRED BY THE CONTRACT DOCUMENTS SHALL BE

COORDINATED WITH THE WORK OF ALL OTHER DIVISIONS/TRADES PRIOR TO COMMENCEMENT

OF WORK. AVOID INTERFERENCES WITH THE PROGRESS OF OTHER DIVISIONS/TRADES.

12. WHERE STRUCTURAL WALLS ARE OF TILT-UP CONSTRUCTION, PROVIDE COORDINATION FOR

EXACT DIMENSIONS AND OPENINGS REQUIRED FOR ALL ELECTRICAL COMPONENTS INSTALLED

WITHIN TILT-UP WALLS DURING THE SHOP DRAWING REVIEW PROCESS OF THE TILT-UP WALLS, PRIOR TO MANUFACTURE OF THE TILT-UP WALLS.

13. LOCATIONS OF VFD'S, DISCONNECTS, MOTOR STARTERS, ETC. FOR HVAC EQUIPMENT ARE

DIAGRAMMATIC ON THE PLAN DRAWINGS. EXACT LOCATIONS ARE TO BE COORDINATED WITH

CONTRACTOR'S COORDINATION DRAWINGS PRIOR TO ROUGHING IN TO ENSURE PROPER NEC

CLEARANCES AND APPROPRIATE MOUNTING SURFACE.

14. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS.

PROVIDE COMPONENTS INDICATED ON RISER DIAGRAMS WHETHER OR NOT INDICATED ON

PLANS AND VICE VERSA.

15. ROUTING OF CONDUIT IS DIAGRAMMATIC AND NOT INTENDED TO SHOW REQUIRED OFFSETS

AND DETAILS. COORDINATE EXACT ROUTING WITH FIELD CONDITIONS AND OTHER TRADES.

16. COORDINATE RECEPTACLE LOCATIONS WITH TECHNOLOGY DRAWINGS OR OWNER'S VENDOR

DRAWINGS SO THAT A 120V 20A 5-20R RECEPTACLE IS LOCATED ADJACENT TO EACH

VOICE/DATA OUTLET AND TV OUTLET INDICATED ON PLANS. RECEPTACLE IS TO BE CONNECTED

TO NEAREST 120V RECEPTACLE CIRCUIT, UNLESS OTHERWISE NOTED ON PLANS.

17. REFER TO ARCHITECTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION, CIVIL, LANDSCAPE, INTERIOR DESIGN, TECHNOLOGY, STRUCTURAL, AND KITCHEN EQUIPMENT DRAWINGS FOR

RELATED INFORMATION AND ADDITIONAL INSTALLATION REQUIREMENTS TO BE PERFORMED AS

PART OF THE WORK. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT MOUNTING HEIGHT

AND LOCATIONS.

18. WHERE A DISCREPANCY OR CONFLICT IS FOUND BETWEEN ONE DRAWING AND ANOTHER, OR

BETWEEN A DRAWING AND APPLICABLE SPECIFICATIONS, NOTIFY THE ARCHITECT/ENGINEER

IMMEDIATELY IN WRITTEN FORM. IN GENERAL, THE MOST STRINGENT REQUIREMENT SHALL

GOVERN UNLESS THE DISCREPANCY CONFLICTS WITH APPLICABLE CODES OR OWNER'S

DESIGN STANDARDS, WHEREIN THE CODE OR OWNER'S DESIGN STANDARDS SHALL GOVERN.

19. COORDINATE ALL PROJECT SCHEDULING AND PHASING REQUIREMENTS WITH

ARCHITECT/ENGINEER AND OWNER PRIOR TO SUBMITTING BID PRICE. THIS PROJECT MAY

REQUIRE PHASING SEQUENCES AND POTENTIAL PREMIUM TIME WORK AND ALL COSTS FOR

SUCH SHALL BE INCLUDED IN THE BID PRICE. PROVIDE ADEQUATE WORK FORCE AND

EQUIPMENT, AND INCLUDE PREMIUM TIME AS MAY BE REQUIRED IN ORDER TO ADHERE TO THE

PROJECT SCHEDULE. ADDITIONALLY, ENSURE THAT LONG LEAD ITEMS DO NOT IMPACT THE

PROJECT'S SCHEDULE OR PHASING.

20. ANY TEMPORARY INTERRUPTION ON POWER REQUIRED FOR THE SYSTEM TIE-IN OR

SWITCHOVER FOR ANY PORTION OF THE ELECTRICAL SYSTEM SHALL BE PRE-APPROVED IN

WRITING BY THE OWNER AND SCHEDULED IN ADVANCE.

21. COORDINATE EXACT REQUIREMENTS WITH THE LOCAL UTILITY COMPANIES AND PROVIDERS

(ELECTRIC, TELEPHONE, CABLE TV, ETC.) AND INCLUDE ALL COSTS FOR PROVIDING

TEMPORARY AND PERMANENT SERVICES REQUIRED FOR THIS PROJECT IN THE BID PRICE. BID

PRICE SHALL INCLUDE, BUT NOT BE LIMITED TO, EXCAVATION, RACEWAYS, BACKFILL,

EQUIPMENT, EQUIPMENT PADS, BACKBOARDS, METERS, GROUNDING, UTILITY ENGINEERING

AND IMPACT FEES.

22. CONDUCT WORK OPERATIONS AND DEBRIS REMOVAL IN A MANNER THAT ENSURES MINIMUM

INTERFERENCE WITH NORMAL BUSINESS OPERATIONS, TRAFFIC, PARKING, ETC. ONGOING IN

ADJACENT OCCUPIED SPACES OR FACILITIES. PROVIDE ALL THAT IS REQUIRED TO

EFFECTIVELY PROTECT SURROUNDING OCCUPANTS, EQUIPMENT, FINISHES, FURNITURE, ETC.

FROM DAMAGE OR EXCESSIVE NOISE THROUGHOUT THE DURATION OF THIS PROJECT.

CONTRACTOR IS RESPONSIBLE FOR ANY LOSSES OR DAMAGE. ANY DAMAGE RESULTING FROM

THE FAILURE TO ADHERE TO THIS REQUIREMENT. RESTORE DAMAGED ELEMENTS TO ORIGINAL

CONDITION BY THE CONTRACTOR TO THE SATISFACTION OF THE ARCHITECT/ENGINEER AND

OWNER, AT NO ADDITIONAL COSTS. REPORT OF ANY SUCH OCCURRENCE TO THE

ARCHITECT/ENGINEER AND OWNER IMMEDIATELY AND AWAIT WRITTEN DIRECTION PRIOR TO

PROCEEDING WITH REPAIRS.

23. COORDINATE THE LOCATION OF ALL LIGHT FIXTURES, DEVICES AND BOXES WITH WINDOWS, MIRRORS, MILLWORK, CABINETS, GLASS CURTAIN WALLS, AND GLASS WALLS PRIOR TO

INSTALLATION OF CONDUITS OR BOXES. REVIEW ALL CONTRACT DRAWINGS TO ASCERTAIN

ANY CONFLICTS PRIOR TO BIDDING. OBTAIN CLARIFICATION FROM A/E PRIOR TO BID.

CONTRACTOR SHALL NOT BE ENTITLED TO ADDITIONAL COMPENSATION FOR WORK REQUIRED

TO RELOCATE OUTLET BOXES OR RACEWAYS FOR COORDINATION WITH OTHER TRADE'S

WORK.

24. THE EXCLUSIVELY DEDICATED SPACE EXTENDING FROM FLOOR TO 6' ABOVE EQUIPMENT OR

STRUCTURAL CEILING, WHICHEVER DISTANCE IS LOWER, WITH A WIDTH AND DEPTH OF THE

PANELBOARD OR SWITCHBOARD MUST BE CLEAR OF ALL PIPING, DUCTS, EQUIPMENT FOREIGN

TO THE ELECTRICAL EQUIPMENT OR ARCHITECTURAL APPURTENANCES IN ACCORDANCE WITH

NEC.

25. PROVIDE ALL TEMPORARY NORMAL LIGHTING, EMERGENCY LIGHTING AND EXIT SIGNAGE

REQUIRED DURING THE PROJECT CONSTRUCTION PHASE.

26. THE INFRASTRUCTURE FOR THE ACCESS CONTROL/ CCTV OR SECURITY ELECTRONICS SYSTEM (CONDUITS, ELECTRICAL BOXES) SHALL BE INSTALLED BY DIVISION 26. THE ACCESS CONTROL/

CCTV OR SECURITY ELECTRONICS SYSTEM CONTRACTOR SHALL PROVIDE AND INSTALL THE

WIRE AND CABLE FOR THE SYSTEM AND ALL REQUIRED EQUIPMENT. INSTALLATION OF THE

CONDUITS AND ELECTRICAL BOXES SHALL BE UNDER THE DIRECT SUPERVISION OF THE

ACCESS CONTROL/ CCTV SYSTEM CONTRACTOR. COORDINATE EXACT LOCATIONS OF DEVICES,

RACEWAY LOCATIONS, SIZES AND QUANTITY, CONDUIT STUB-UPS PRIOR TO ROUGH IN.

27. THE INFRASTRUCTURE FOR THE VOICE/DATA TELECOMMUNICATIONS SYSTEM (CONDUITS,

ELECTRICAL BOXES) SHALL BE INSTALLED BY DIVISION 26. THE TELECOMMUNICATIONS

CONTRACTOR SHALL PROVIDE AND INSTALL THE WIRE AND CABLE FOR THE SYSTEM AND ALL

REQUIRED EQUIPMENT AND COMPONENTS. INSTALLATION OF THE CONDUITS AND ELECTRICAL

BOXES SHALL BE UNDER THE DIRECT SUPERVISION OF THE TELECOMMUNICATIONS

CONTRACTOR. COORDINATE EXACT LOCATIONS OF DEVICES, RACEWAY LOCATIONS, SIZES AND

QUANTITY, CONDUIT STUB-UPS PRIOR TO ROUGH IN.

28. PROVIDE 120V 20A 5-20R RECEPTACLE AT ALL FAN COIL UNITS FOR CONDENSATE PUMP POWER

AND HOT WATER RECIRCULATING PUMPS, WHETHER SHOWN ON PLANS OR NOT. RECEPTACLE

IS TO BE CONNECTED TO NEAREST 120V RECEPTACLE CIRCUIT.

29. PROVIDE 120V CONNECTION TO ALL MOTORORIZED DAMPERS INDICATED ON MECHANICAL

PLANS, WHETHER SHOWN ON DIVISION 26 DRAWINGS OR NOT. FIRE/SMOKE DAMPER CIRCUITS

ARE TO BE PROVIDED FROM EMERGENCY BRANCH PANEL (LEGALLY REQUIRED BRANCH IF

AVAILABLE). MOTORIZED DAMPERS WITHIN THE SAME AREA CAN BE CIRCUITED TO THE SAME

CIRCUIT (I.E., DEDICATED CIRCUIT IS NOT REQUIRED).

30. PROVIDE PHONE/DATA OUTLET WITH 1" RACEWAY, AND 120V RECEPTACLE ON DEDICATED

CIRCUIT ADJACENT TO EACH AIR HANDLING UNIT FOR CONTROL POWER.

31. PROVIDE 120V DEDICATED CIRCUIT TO EACH AIR HANDLING UNIT WITH SEPARATE

CONNECTIONS TO UNIT UV LIGHT, UNIT LIGHTS, UNIT RECEPTACLE, AND BI-POLAR IONIZATION

FILTER WHERE PROVIDED. COORDINATE WITH DIVISION 23 SHOP DRAWINGS.

32. UNLESS NOTED AS EXISTING, ALL ELECTRICAL INDICATED ON THE CONTRACT DOCUMENTS

SHALL BE NEW, SHALL BE U.L. LISTED, AND SHALL BEAR A U.L. LABEL. WHERE NO U.L. LABEL OR

LISTING IS AVAILABLE, THE MATERIAL SHALL BE LISTED WITH AN APPROVED, NATIONALLY

RECOGNIZED ELECTRICAL TESTING AGENCY.

33. PROVIDE EXPERIENCED, QUALIFIED AND RESPONSIBLE SUPERVISION FOR ALL WORK

REQUIRED BY THE CONTRACT DOCUMENTS. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED

IN A NEAT AND WORKMANLIKE MANNER, TO THE SATISFACTION OF THE ARCHITECT/ENGINEER

AND OWNER.

34. THE ELECTRICAL PORTION OF THE CONTRACT DOCUMENTS ARE COORDINATED WITH THE

DESIGN BASIS EQUIPMENT SPECIFIED BY DIVISION 26 AND OTHER DIVISIONS. WHERE THE

CONTRACTOR ELECTS TO SUBSTITUTE A PRODUCT IN LIEU OF PROVIDING THE DESIGN BASIS,

AND SAID SUBSTITUTION IS ACCEPTED BY THE A/E AND OWNER, THE CONTRACTOR SHALL MAKE

ALL CORRECTIONS TO THE ELECTRICAL SYSTEM NECESSARY IN ORDER TO ENSURE A

COMPLETE AND OPERATIONAL INSTALLATION OF THE EQUIPMENT AT NO ADDITIONAL COSTS.

WHERE THE CONTRACTOR'S DESIGN SUBSTITUTION RESULTS IN THE NEED FOR THE ENGINEER

TO REVISE THE CONTRACT DOCUMENTS, THE ENGINEER RESERVES THE RIGHT TO REQUEST

COMPENSATION FROM THE CONTRACTOR FOR SAID SERVICES.

35. MAINTAIN A CURRENT AND ACCURATE SET OF PROJECT RECORD DOCUMENTS (AS-BUILTS) AT

THE SITE THROUGHOUT THE DURATION OF THE PROJECT. RECORD DRAWINGS SHALL BE

UPDATED EACH DAY TO REFLECT THE ACTUAL LOCATIONS, SIZES, ROUTING, ETC. OF EACH

PORTION OF THE ELECTRICAL SYSTEM AFFECTED BY THIS WORK. A FINAL SET OF RECORD

DOCUMENTS SHALL BE ISSUED TO THE A/E FOR REVIEW AND THEN SUBMITTED TO THE OWNER

WITHIN 30 DAYS AFTER THE DATE OF FINAL ACCEPTANCE. PROVIDE RECORD DRAWINGS OF

THE ACTUAL INSTALLATION INCLUDING SINGLE LINE DIAGRAM, POWER RISER DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM, SITE PLANS AND ALL ELECTRICAL FLOOR PLANS, DETAILS, PANEL SCHEDULES, ETC.

36. OWNER FURNISHED EQUIPMENT: VERIFY AND COORDINATE ELECTRICAL ROUGH IN

REQUIREMENTS FOR OWNER FURNISHED EQUIPMENT PRIOR TO ROUGH IN.

37. WHERE SUBMITTED EQUIPMENT REQUIRES REVISION TO OVERCURRENT PROTECTION,

CONDUIT OR WIRING, MAKE CHANGES IN ACCORDANCE WITH APPLICABLE CODES.

D1. THE FACILITY WILL REMAIN OCCUPIED DURING RENOVATIONS.

D2. DEVICES, LIGHT FIXTURES AND EQUIPMENT SHOWN IN DASHED LINE TYPE ARE EXISTING TO BE

DEMOLISHED; DEVICES, LIGHT FIXTURES AND EQUIPMENT SHOWN IN LIGHT SOLID LINE TYPE

ARE EXISTING TO REMAIN, UNLESS OTHERWISE NOTED.

D3. EXISTING EQUIPMENT, LIGHT FIXTURES, DEVICES SHOWN ARE BASED ON FIELD SURVEYS AND

RECORD DRAWINGS PROVIDED BY THE OWNER, AND IS NOT NECESSARILY ALL INCLUSIVE IN

EVERY AREA AS FAR AS EXISTING ELECTRICAL EQUIPMENT, LIGHT FIXTURES AND DEVICES.

EXISTING CIRCUITING SHOWN IS BASED ON RECORD DRAWINGS AND THE SURVEYED PANEL

DIRECTORIES, WHERE THEY WERE AVAILABLE. THE ACTUAL CONDITIONS MAY VARY. ALL

EXISTING CONDITIONS MUST BE VERIFIED PRIOR TO BID. THE CONDITIONS SHOWN ARE

INTENDED TO SHOW THE LOCATIONS OF EXISTING DEVICES, LIGHT FIXTURES AND EQUIPMENT, WHERE SHOWN ON THE PLAN DRAWINGS, AND IN NO WAY RELIEVES THE CONTRACTOR FROM

PROVIDING ANY AND ALL COORDINATION NECESSARY TO COMPLETE THE NEW WORK. FIELD

CONDITIONS SHALL GOVERN.

D4. WHERE EXISTING DEVICES ARE INDICATED TO REMAIN OR RELOCATED, LOCATED WITHIN THE

SCOPE OF THIS PROJECT AND EXISTING CIRCUITING INFORMATION IS UNAVAILABLE,

CONTRACTOR IS TO PROVIDE CIRCUIT TRACING TO IDENTIFY PANEL AND CIRCUIT DEVICES ARE

CONNECTED TO AND PROVIDE THAT INFORMATION TO A/E PRIOR TO ROUTING CONDUITS AND

WIRING FOR NEW DEVICES AND EQUIPMENT WITHIN THE SCOPE OF THIS PROJECT.

D5. PRIOR TO DEMOLITION, FIELD VERIFY CONDUIT AND WIRING WHICH SERVES AREAS OUTSIDE

THE SCOPE OF WORK AND PASSES THROUGH THE AREA OF WORK. MAINTAIN CONTINUITY OF

SYSTEMS.

D6. WHERE EXISTING DEVICES ARE TO REMAIN, CONTRACTOR MUST EXTEND EXISTING CIRCUITING

WHERE NECESSARY TO MAINTAIN CONTINUITY OF CIRCUIT.

D7. COORDINATE WITH THE OWNER FOR DISPOSITION OF ELECTRICAL ITEMS TO BE DEMOLISHED.

OWNER SHALL HAVE THE OPTION TO RETAIN REUSABLE ITEMS SUCH AS COVERPLATES,

RECEPTACLES, LIGHT FIXTURES, PANELBOARDS, TRANSFORMERS, ETC. NOT BEING USED IN

THE FINISHED WORK. COORDINATE WITH THE OWNER PRIOR TO START OF DEMOLITION.

PROPERLY AND LEGALLY DISPOSE OF ALL EQUIPMENT AND MATERIALS BEING REMOVED.

D8. COORDINATE EXACT AREAS, WALLS, CEILINGS, ETC. TO BE DEMOLISHED WITH ARCHITECTURAL, STRUCTURAL, PLUMBING AND MECHANICAL DEMOLITION PLANS.

D9. WHERE EXISTING DEVICES, LIGHT FIXTURES AND EQUIPMENT ARE INDICATED TO BE

DEMOLISHED, REMOVE ASSOCIATED CONDUIT AND WIRING BACK TO SOURCE PANEL OR TO

NEAREST JUNCTION BOX TO MAINTAIN CIRCUIT CONTINUITY OF DEVICES TO REMAIN AND

EQUIPMENT TO REMAIN. WHERE PANELS ARE TO BE REMAIN, TURN BREAKER TO "OFF"

POSITION AND LABEL THE CIRCUIT AS "SPARE" ON THE PANEL DIRECTORY.

D10. ALL AREAS OUTSIDE THE SCOPE OF CONSTRUCTION ARE TO REMAIN ENERGIZED. COORDINATE

PHASING WITH CONSTRUCTION MANAGER AND OWNER PRIOR TO DEMOLITION WHICH MAY

RESULT IN INTERRUPTION OF POWER.

D11. REFER TO ARCHITECTURAL DEMOLITION DRAWINGS FOR EXTENT OF AREA REQUIRING

DEMOLITION AND ADDITIONAL INFORMATION ON ELECTRICAL DEMOLITION WITHIN THAT AREA.

DISCONNECT ELECTRICAL SERVICE TO ALL EQUIPMENT BEING REMOVED. DEMOLITION SHALL

BE PHASED AS REQUIRED BY DIVISION 1, OR DIRECTED BY THE OWNER.

D12. REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND CEILINGS IN REMODELED

OR RENOVATED AREA. CAP BOTH ENDS OF REMAINING CONDUIT IN WALL OR FLOOR WHERE

CUT. REMOVE ALL ASSOCIATED SUPPORTS. REMOVE WIRING BACK TO SOURCE OF VOLTAGE.

D13. ELECTRICAL DEVICES WITHIN THE AREA OF WORK., AND NOT NOTED ON THE DEMOLITION

DRAWINGS, WHETHER DUE TO CONCEALEMENT BY STORAGE SHELVING, CASEWORK,

FURNITURE OR FOR OTHER REASONS, ARE TO BE REMOVED AS REQUIRED, UNLESS SHOWN AS

EXISTING TO REMAIN.

D14. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING ALL OPENINGS IN EXISTING

CONSTRUCTION AFTER REMOVAL OF EQUIPMENT AND ELECTRICAL DEVICES, UNLESS

OTHERWISE NOTED ON ARCHITECTURAL PLANS. REPAIRS ARE TO BE DONE TO LOGICAL EDGES

OF SURFACES AFFECTED AND SHALL MATCH IMMEDIATE ADJACENT AREAS IN CONSTRUCTION,

MATERIAL, FIRE RATING, FINISH AND COLOR.

D15. PROVIDE BLANK COVERPLATES WHERE DEVICES ARE BEING REMOVED FROM EXISTING WALLS

TO REMAIN. MATCH COLOR OF NEW ADJACENT DEVICE COVERPLATES.

D16. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR TO COMMENCEMENT OF

WORK AND OBTAIN CLARIFICATIONS FROM ARCHITECT/ENGINEER IF NECESSARY.

D17. COORDINATE SERVICE INTERRUPTION WITH CONSTRUCTION MANAGER, OWNER, LANDLORD,

AND UTILITY COMPANY, WHERE APPLICABLE, AND DO NOT INTERRUPT POWER WITHOUT

WRITTEN PERMISSION. PROVIDE A MINIMUM OF ONE WEEK'S WRITTEN NOTIFICATION WHEN

POWER IS DESIRED TO BE INTERRUPTED.

D18. EXERCISE EXTREME CAUTION WHEN REMOVING/ RELOCATING WIRING AND EQUIPMENT. IT IS

THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT OTHER WIRING DEVICES, EQUIPMENT

AND LIGHT FIXTURES THAT MAY BE CONNECTED TO THE SAME CIRCUIT REMAIN OPERATIONAL

AND ACTIVE.

D19. INFORMATION INDICATED IN THE DEMOLITION PORTION OF THE CONTRACT DRAWINGS IS

DIAGRAMMATIC IN NATURE. FIELD VERIFY ELECTRICAL CIRCUIT HOMERUNS TO ALL ELECTRICAL

ITEMS SCHEDULED TO BE DEMOLISHED AND PERFORM THE WORK AS INTENDED AND DEPICTED

ON THE DRAWINGS.

D20. UPDATE ALL EXISTING ELECTRICAL EQUIPMENT NAMEPLATES AND DIRECTORIES AS

NECESSARY TO REFLECT FINAL AS-BUILT CONDITIONS AT THE END OF CONSTRUCTION.

D21. STORE ITEMS INDICATED TO BE RETURNED TO THE OWNER IN A DRY, CLEAN AND PROTECTED

AREA. NOTIFY OWNER WHEN ITEMS ARE READY TO BE REMOVED.

D22. COORDINATE ANY ALTERATION AND CHANGES TO THE ELECTRICAL SERVICE WITH THE LOCAL

UTILITY COMPANY AND THE OWNER PRIOR TO COMMENCEMENT OF WORK.

D23. SCHEDULE ALL POWER INTERRUPTION WITH OWNER FOR EXACT DATE, TIME AND DURATION.

PROVIDE A MINIMUM OF 72 HOURS NOTICE PRIOR TO DISCONNECTING ANY POWER TO ANY

PORTION OF THE BUILDING, AND MAKE ARRANGEMENTS TO MAINTAIN POWER TO ALL CRITICAL

EQUIPMENT AS NEEDED AND REQUESTED BY THE OWNER PRIOR TO COMMENCEMENT OF

WORK.

D24. PROVIDE ANY NECESSARY REPROGRAMMING OF EXISTING BUILDING FIRE ALARM SYSTEMS TO

DISABLE FIRE ALARM DEVICES THAT ARE BEING DISCONNECTED AND REMOVED, AND FOR ANY

NEW DEVICES THAT ARE ADDED, AS PART OF BID PRICE.

D25. THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL ELECTRICAL DEVICES WITHIN THE PROJECT

AREA. IT IS INTENDED TO PROVIDE A GENERAL KNOWLEDGE OF THE EXISTING CONDITIONS

WITHIN THE PROJECT AREA. ANY DISCREPANCIES OR CONDITIONS NOT SHOWN ON THE PLAN

SHALL BE BROUGHT TO THE ATTENTION OF THE A/E. THE CONTRACTOR IS RESPONSIBLE FOR

ALL REQUIRED ELECTRICAL DEMOLITION WHETHER INDICATED ON THE PLANS OR NOT.

D26. ALL CONDUITS SERVING OTHER SPACES THAT RUN THROUGH THE PROJECT AREA SHALL

REMAIN ACTIVE DURING CONSTRUCTION SO AS NOT TO CAUSE DISRUPTION TO THESE OTHER

SPACES. ENSURE THAT ALL CONDUITS, NEW OR EXISTING WITHIN THE PROJECT AREA ARE

PROPERLY SUPPORTED IN ACCORDANCE WITH THE NEC. ANY EXISTING CONDUIT IS INSTALLED

BELOW THE HEIGHT OF THE NEW CEILING SHALL BE RELOCATED TO ABOVE THE NEW CEILING

HEIGHT.

D27. REMOVE ALL ABANDONED WIRING AND CONDUIT THAT IS WITHIN THE PROJECT AREA PRIOR TO

THE END OF CONSTRUCTION.

D28. UPDATE PANELBOARD DIRECTORIES WHICH ARE MODIFIED BY THIS PROJECT.

D29. REPAIR DISTURBED AREAS TO MATCH EXISTING CONDITIONS

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

ENGINEER ARCHITECT/ENGINEER OF RECORD

WBRC

A R C H I T E C T S • E N G I N E E R S

WWW.WBRCAE.COM

BANGOR, MAINE 207-947-4511

PORTLAND, MAINE 207-828-4511

SARASOTA, FLORIDA 941-556-0757

STAMP

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

Project TitleDrawing Title

Approved:

Phase

Location

Issue Date

Project Number

Building Number

Drawing Number

Checked Drawn

TRUE NORTH

PROJECT NORTH

www.abovegroupinc.com

COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

/1

/2

:5

:2

A

M B

IM

/0

V A

P ro v id e n c e M e n ta l H e a lt h

B u ild in g

P H

/0

V A

P ro v id e n c e

M H

C P

H

R

D iv

.r v t

E-002

650-347

PROVIDENCE VAMC MENTAL

HEALTH PHASE 2

PROVIDENCE, RI

JFR SDLFEB 04 2022

CONSTRUCTION

DOCUMENTS

ELECTRICAL GENERAL NOTES

FULLY SPRINKLERED

JOHN F. RAINE, P.E.

MD License #41408Revisions: Revision Description Date:

R E

F

REF.

A

A1

A1

B

B

AL AL AL

AL AL AL AL

ALA

A

A A

G-2

G-2G-2

A

A

A

A

AS

A1

A

A1

A

A

G-2

G-3

A

B1

B1

G-1

G-1

R E

F

2-B E.5

2-D

2-2.12-2

CH-39-0-03

TYPICAL

TYPICAL

RM 018A

CR211

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

ENGINEER ARCHITECT/ENGINEER OF RECORD

WBRC

A R C H I T E C T S • E N G I N E E R S

WWW.WBRCAE.COM

BANGOR, MAINE 207-947-4511

PORTLAND, MAINE 207-828-4511

SARASOTA, FLORIDA 941-556-0757

STAMP

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

Project TitleDrawing Title

Approved:

Phase

Location

Issue Date

Project Number

Building Number

Drawing Number

Checked Drawn

TRUE NORTH

PROJECT NORTH

www.abovegroupinc.com

COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

/1

/2

:5

:2

A

M B

IM

/0

V A

P ro v id e n c e M e n ta l H e a lt h

B u ild in g

P H

/0

V A

P ro v id e n c e

M H

C P

H

R

D iv

.r v t

E-100

650-347

PROVIDENCE VAMC MENTAL

HEALTH PHASE 2

PROVIDENCE, RI

JFR SDLFEB 04 2022

CONSTRUCTION

DOCUMENTS

ELECTRICAL SITE PLAN

FULLY SPRINKLERED

JOHN F. RAINE, P.E.

MD License #41408

1/8" = 1'-0" F1

ELECTRICAL SITE PLAN

DRAWING NOTES:

1. SEE SHEET E-801 FOR ELECTRICAL EQUIPMENT CONNECTION SCHEDULE.

0 4' 8' 16' 24'

1/8" = 1'-0"

CODED NOTES:

BOND GROUND LOOP TO BUILDING STEEL WITH EXOTHERMIC WELD. REFER TO GROUNDING RISER

DIAGRAM ON SHEET E-501 FOR ADDITIONAL INFORMATION.

10' GROUND ROD WITH TEST WELL.

EXISTING RECEPTACLE LOCATED WITHIN 25' OF NEW CHILLER TO REMAIN. MAINTAIN AND PROTECT

DURING CONSTRUCTION.

CONNECT GROUND LOOP TO EXISTING PHASE 1 GROUND LOOP. COORDINATE EXACT CONNECTION

POINT IN FIELD WITH EXISTING GROUND LOOP CONDUCTOR EXACT ROUTING.

EXISTING MDP LOCATED IN RM 110 IN THIS APPROXIMATE LOCATION ON LEVEL 1. REFER TO

ELECTRICAL ONE-LINE DIAGRAM ON SHEET E-601 FOR ADDITIONAL INFORMATION.

Revisions: Revision Description Date:

F

LV1D

LV1D

LV1D

LV1D

LV1D

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

L V a

O S

OS

OS

LV1b

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

L V b

L V a

OS

OS

OS

OS

OS

OS

OS

OS

2-A

2-C

2-E

2-12-2.12-22-3

2-4

2-5

2-6

2-7

2-8

2-F

A1E

A1

A1

A1E

A1

A1

A1E

A1

A1

A1E

L1

A1

A1 L1

L1

L1E

L1E

L1

L1

L1

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

S1E

S1E

V1

V1

B1

D1

D1

D1

X

X

B1E

LPP

LPP

LPD

LV1D

LV1D

LV1D

LPD

LPD

WG

WG

WG

WG

WG

WG

WG

WG

WG

WG

WG

WG

LV2Dab

LV2Dab

LV2Dab

LV2Dab

LV2Dab

LV2Dab

LPD

LPD

LPD

LPD

LPD

LPD

LPD

LPD

LPD

LPD

LPD

LPD

b b a a a a a a a a a a a a a a a a a a a a a a a a b b b b b b b b b b b b b b b

LPD

LPD

LPD

LPD

LPD

CR217H-3

CR217H-3

CR217H-1

CR217H-1

NP048H-1

NP048H-1

CR217H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

b

NP048H-1

NP048H-1

NP048H-2

NP048H-2

NP048H-2

NP048H-2

NP048H-2

NP048H-2

NP048H-2

NP048H-2 NP048H-2

NP048H-2

NP048H-2

NP048H-4

NP048H-2

NP048H-2

NP048H-2

NP048H-2

NP048H-2

NP048H-2

NP048H-2

NP048H-2

NP048H-2

NP048H-2

NP048H-3

NP048H-3

NP048H-3 NP048H-3

CR217H-1NP048H-3

NP048H-3

NP048H-3

CR217H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-4

NP048H-4

CR217H-1

NP048H-4

NP048H-4

CR217H-1

NP048H-4

NP048H-4

CR217H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

a a a aa a a a a a b b b b b b b b b b b b b b b b b

NP048H

CONSULT ROOM

PRINTER

034B

STORAGE

CONSULT ROOM

CONSULT ROOM

OFFICE (TRIPLE)

OFFICE (TRIPLE)

042TEAM RM

STAFF TOILET

CORRIDOR

034A

HAC

STAIR 3

CORRIDOR

OFFICE (TRIPLE)

OFFICE (TRIPLE)

ELEC. CL.

OFFICE (DOUBLE)

VETERAN W.S.

OFFICE (DOUBLE)

CONSULT ROOM

OFFICE

OFFICE

CHIEF OFFICE

PUBLIC TOILET

MSA

WAITING AREA

a b

LPP

b

NP048H-4

CR217H-1

LPP

a

NP048H-3

CR217H-1

NP048H-1

NP048H-2

NP048H-4

CR217H-1

NP048H-3

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-1

NP048H-2

NP048H-2

NP048H-2

NP048H-2

NP048H-2

NP048H-2

NP048H-2

NP048H-2

XC

CR217H-1

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

ENGINEER ARCHITECT/ENGINEER OF RECORD

WBRC

A R C H I T E C T S • E N G I N E E R S

WWW.WBRCAE.COM

BANGOR, MAINE 207-947-4511

PORTLAND, MAINE 207-828-4511

SARASOTA, FLORIDA 941-556-0757

STAMP

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

Project TitleDrawing Title

Approved:

Phase

Location

Issue Date

Project Number

Building Number

Drawing Number

Checked Drawn

TRUE NORTH

PROJECT NORTH

www.abovegroupinc.com

COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

/1

/2

:5

:4

A

M B

IM

/0

V A

P ro v id e n c e M e n ta l H e a lt h

B u ild in g

P H

/0

V A

P ro v id e n c e

M H

C P

H

R

D iv

.r v t

EL201

650-347PROVIDENCE VAMC MENTAL

HEALTH PHASE 2

PROVIDENCE, RI

JFR SDLFEB 04 2022

CONSTRUCTION

DOCUMENTS

LEVEL B PLAN - LIGHTING

FULLY SPRINKLERED

JOHN F. RAINE, P.E.

MD License #41408

1/4" = 1'-0"F1

LEVEL B PLAN - LIGHTING

0 2' 4' 8' 12'

1/4" = 1'-0"

DRAWING NOTES:

1. LIFE SAFETY LIGHTING SHALL BE ADDRESSED THROUGH INTEGRAL BATTERY BACKUP. ALL LIGHTING

FIXTURES SHALL BE CONTROLLED BY LOCAL LIGHTING CONTROLS.

2. STAIRWELLS SHALL BE CONTROLLED BY INTEGRAL OCCUPANCY SENSING LIGHTING FIXTURES.

3. ALL EMERGENCY LIFE SAFETY LIGHTING FIXTURES AND EXIT SIGNS SHALL BE PROVIDED WITH A

SEPARATE UNSWITCHED PHASE CONDUCTOR FOR POWER OUTAGE SENSING.

P1P2

KEY PLAN

CODED NOTES:

COORDINATE EXACT LOCATION OF DEVICES ON THIS WALL WITH ARCHITECTURAL WALL PANELING

PRIOR TO CONSTRUCTION.

LV1D

LV1D

LV1D

LV1D

OS

LV1

LV1D

LV1D

LV1D

LV1D

O S

OS

LV1Da

LV1Da

L V a

LV1b

L V a

L V b

LV1D

LV1D

LV1D

LV1D

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

2-A

2-C

2-E

2-12-2.1 2-22-3

2-4

2-5

2-6

2-7

2-8

2-F

A1E

A1

A1

A1E

A1

A1

A1E

A1

A1

A1E

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2E

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2E

A2

A2

A2

A2

A2

A2

A2

A2E

A2

A2

A2

A2

A2

A2

A2 A2

A2

A2

A2

A2

A2

A2

A2

L1

L1

L1

L1EL1

L1

L1

L1E

D1

D1

B1

B1

B1

B1E

D1

X

X

X

V1

V1

S1E

S1E

SL1E

SL1

SL1

SL1

SL1

SL1

SL1

SL1

SL1

X

B1E

LPP

LPP

LPD

LPD

LPP

LPD

LPD

LPD

LPD

LPD

LPD

LPD

LPD

LPD

LPD

LPD

LPD

CR217H-3

CR217H-3

CR217H-3

NP146H-1

NP146H-1

NP146H-1

NP146H-1

CR217H-5

CR217H-5

CR217H-5

NP146H-2

NP146H-2

NP146H-2

NP146H-2

NP146H-2

CR217H-5

NP146H-2

NP146H-2

NP146H-2

NP146H-2

NP146H-2

NP146H-2

NP146H-4

NP146H-2

NP146H-2

NP146H-2

NP146H-2

NP146H-2

NP146H-2

NP146H-2

NP146H-2

NP146H-2

CR217H-5

NP146H-2

NP146H-2

NP146H-2

NP146H-2

CR217H-5

CR217H-5

NP146H-5

NP146H-5

NP146H-5 NP146H-5

NP146H-5 CR217H-5

CR217H-5

NP146H-5

NP146H-5

CR217H-5

NP146H-1

NP146H-1

NP146H-1

NP146H-4

NP146H-1

NP146H-1

CR217H-5

CR217H-5

NP146H-1

NP146H-1

NP146H-1

NP146H-4

NP146H-4

NP146H-1

NP146H-1

NP146H-1

NP146H-1

CR217H-5

NP146H-4

NP146H-1

NP146H-1

NP146H-1

NP146H-1

NP146H-1

NP146H-1

NP146H-1

NP146H-1

NP146H-4

SL1

NP146H

a a a a a a a a a b b b b b b b b b b b

LPD

NP146H-3

NP146H-3

NP146H-3

NP146H-3

NP146H-3

NP146H-3

NP146H-3

NP146H-3

NP146H-3

NP146H-3

WAITING AREA

MSA

PUBLIC TOILET

CORRIDOR

GROUP THERAPY

GROUP THERAPY

OFFICE

OFFICE

OFFICE

COUPLE'S THERAPY

COUPLE'S THERAPY

OFFICE

OFFICE

PRINTER

131A

TELEDATA

OFFICE

ELEC. CL.

OFFICE

OFFICE

SECTION CHIEF

STAFF TOILET

STAIR 3

LOUNGE, STAFF

COUPLE'S THERAPY

a a a a a a a a a a a a a a b

LPP

b

NP146H-9

CR217H-5

NP146H-4

NP146H-2

CR217H-5

NP146H-5

NP146H-1

LPP

a

NP146H-5

CR217H-5

NP146H-1

CR217H-5

LPD

aNP146H-1

NP146H-7

LPD

CR217H-5

NP146H-7

NP146H-7

NP146H-7

NP146H-7

NP146H-7

NP146H-7

NP146H-7

NP146H-7

NP146H-1

NP146H-1

NP146H-1

NP146H-1

NP146H-1

a a b b b b b

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

ENGINEER ARCHITECT/ENGINEER OF RECORD

WBRC

A R C H I T E C T S • E N G I N E E R S

WWW.WBRCAE.COM

BANGOR, MAINE 207-947-4511

PORTLAND, MAINE 207-828-4511

SARASOTA, FLORIDA 941-556-0757

STAMP

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

Project TitleDrawing Title

Approved:

Phase

Location

Issue Date

Project Number

Building Number

Drawing Number

Checked Drawn

TRUE NORTH

PROJECT NORTH

www.abovegroupinc.com

COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

/3

/2

:4

:0

A M

B

IM

/0

V A

P ro v id e n c e M e n ta l H e a lt h

B u ild in g

P H

/0

V A

P ro v id e n c e

M H

C P

H

R

D iv

.r v t

EL202

650-347PROVIDENCE VAMC MENTAL

HEALTH PHASE 2

PROVIDENCE, RI

JFR SDLFEB 04 2022

CONSTRUCTION

DOCUMENTS

LEVEL 1 PLAN - LIGHTING

FULLY SPRINKLERED

JOHN F. RAINE, P.E.

MD License #41408

1/4" = 1'-0" F1

LEVEL 1 PLAN - LIGHTING

DRAWING NOTES:

1. LIFE SAFETY LIGHTING SHALL BE ADDRESSED THROUGH INTEGRAL BATTERY BACKUP. ALL LIGHTING

FIXTURES SHALL BE CONTROLLED BY LOCAL LIGHTING CONTROLS.

2. STAIRWELLS SHALL BE CONTROLLED BY INTEGRAL OCCUPANCY SENSING LIGHTING FIXTURES.

3. ALL EMERGENCY LIFE SAFETY LIGHTING FIXTURES AND EXIT SIGNS SHALL BE PROVIDED WITH A

SEPARATE UNSWITCHED PHASE CONDUCTOR FOR POWER OUTAGE SENSING.

0 2' 4' 8' 12'

1/4" = 1'-0"

CODED NOTES:

DAYLIGHT RESPONSIVE ZONE PER THE 2015 IECC. LIGHT FIXTURES WITHIN DAYLIGHT-RESPONSIVE

ZONE SHALL BE CONTROLLED BY PHOTO SENSOR(S). DAYLIGHT-RESPONSIVE ZONE LIGHTING

CONTROL SHALL COMPLY WITH SECTION C405.2.3 OF THE 2015 IECC.

PROVIDE DUAL TECHNOLOGY OCCUPANCY SENSOR WITH AUTOMATIC DAYLIGHT / DIMMING CONTROL

OPTION.

EXTERIOR LIGHTING FIXTURES SHALL BE CONTROLLED BY COMBINATION TIME-CLOCK AND

PHOTOCELL. THE TIME-CLOCK SHALL BE AN ASTRONOMICAL TIMECLOCK CAPABLE OF 7-DAY

SCHEDULES AND PRE-SET HOURS. BASIS OF DESIGN IS NSI #DGLC100A-NC.

P1P2

KEY PLAN

LV1D

LV1D

LV1D

O S

OS

LV1D

OS

OS

OS

OS

OS

OS

OS

LV1D

LV1D

LV1D

LV1D

OS

LV1c

LV1b

L V a

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

L V a

L V b

L V c

LV1D

LV1D

2-A

2-C

2-E

2-12-2.12-22-3

2-4

2-5

2-6

2-7

2-8

2-F

A1E

A1

A1

A1E

A1

A1

A1E

L1

A1E

A1

A1

A1

A1E

L1E

L1 L1

L1

L1EL1

L1

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

D1

D1 D1

B1

B1

B1

B1E

B1E

B1

S1E

S1E

B1

V1

V1

X

X

X

X

LPP

LPP

LPP

B1E

B1E

B1

B1

B1E

LPD

LPD

LPD

LPD

LPD

LPD

LPD

LPD

LPD

LPD

LPD

LPD

CR217H-3

CR217H-3

NP146H-8

NP146H-8

NP146H-8

NP146H-8

NP146H-8

NP146H-8

NP146H-8

NP146H-8

NP146H-8

CR217H-7 CR217H-7

NP146H-6

NP146H-6

NP146H-8

CR217H-7

NP146H-10

NP146H-10

NP146H-6

CR217H-7

NP146H-8

NP146H-8

CR217H-7

NP146H-8

NP146H-8

NP146H-8

NP146H-8

NP146H-6

NP146H-8

NP146H-8

NP146H-8

NP146H-8

NP146H-6

CR217H-7

NP146H-10

NP146H-10

NP146H-10

NP146H-10

NP146H-10

NP146H-10

NP146H-10

NP146H-10

NP146H-10

CR217H-7

CR217H-7

NP146H-7

NP146H-7

NP146H-7 NP146H-7

NP146H-7 CR217H-7

CR217H-7

NP146H-7

NP146H-7

NP146H-8

NP146H-8

NP146H-6

NP146H-8

NP146H-8

NP146H-8

NP146H-6

b c c c c c c c b b b b b b b b b b a a a a a a a a aa

WAITING AREA

PUBLIC TOILET

STAFF TOILET

N.P. OFFICE

N.P. OFFICE

N.P. OFFICE

CORRIDOR

CHIEF OFFICE

OFFICE

OFFICE

OFFICE/CONSULT

OFFICE

OFFICE/CONSULT

CORRIDOR

ELEC. RM.

HAC

N.P. OFFICE

N.P. OFFICE

N.P. OFFICE

MECH. RM.

STAIR 3

PRINTER

204A a b c

CR217H

CR217H-7

LPP

aNP146H-7

NP146H-7

CR217H-7

NP146H-6

NP146H-8

LPP

b

NP146H-6

CR217H-7

NP146H-8

NP146H-8

NP146H-8

NP146H-8

NP146H-8

NP146H-8

NP146H-10

NP146H-10

NP146H-10

NP146H-10

NP146H-10

NP146H-10

NP146H-10

NP146H-6

LPP

cCR217H-7

SL1

SL1

SL1

SL1

SL1

SL1

NP146H-3

NP146H-3

NP146H-3

NP146H-3

NP146H-3

NP146H-3

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

ENGINEER ARCHITECT/ENGINEER OF RECORD

WBRC

A R C H I T E C T S • E N G I N E E R S

WWW.WBRCAE.COM

BANGOR, MAINE 207-947-4511

PORTLAND, MAINE 207-828-4511

SARASOTA, FLORIDA 941-556-0757

STAMP

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

Project TitleDrawing Title

Approved:

Phase

Location

Issue Date

Project Number

Building Number

Drawing Number

Checked Drawn

TRUE NORTH

PROJECT NORTH

www.abovegroupinc.com

COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

/3

/2

:4

:1

A M

B

IM

/0

V A

P ro v id e n c e M e n ta l H e a lt h

B u ild in g

P H

/0

V A

P ro v id e n c e

M H

C P

H

R

D iv

.r v t

EL203

650-347PROVIDENCE VAMC MENTAL

HEALTH PHASE 2

PROVIDENCE, RI

JFR SDLFEB 04 2022

CONSTRUCTION

DOCUMENTS

LEVEL 2 PLAN - LIGHTING

FULLY SPRINKLERED

JOHN F. RAINE, P.E.

MD License #41408

1/4" = 1'-0" F1

LEVEL 2 PLAN - LIGHTING

0 2' 4' 8' 12'

1/4" = 1'-0"

DRAWING NOTES:

1. LIFE SAFETY LIGHTING SHALL BE ADDRESSED THROUGH INTEGRAL BATTERY BACKUP. ALL LIGHTING

FIXTURES SHALL BE CONTROLLED BY LOCAL LIGHTING CONTROLS.

2. STAIRWELLS SHALL BE CONTROLLED BY INTEGRAL OCCUPANCY SENSING LIGHTING FIXTURES.

3. ALL EMERGENCY LIFE SAFETY LIGHTING FIXTURES AND EXIT SIGNS SHALL BE PROVIDED WITH A

SEPARATE UNSWITCHED PHASE CONDUCTOR FOR POWER OUTAGE SENSING.

P1P2

KEY PLAN

CODED NOTES:

COORDINATE THE EXACT LOCATION OF LIGHTING FIXTURES IN THIS ARE WITH DUCTWORK.1

F

MP

J

J

J J

J

NP048H

NP048L

TNP048L (SUPSENDED FROM ABOVE)

2-B

E.5

2-D

2-A

2-C

2-E

2-12-2.12-22-3

2-4

2-5

2-6

2-7

2-8

2-F

G,48"

G

G,48"

NP048L-1

NP048L-1

NP048L-1

NP048L-1

NP048L-3

NP048L-3

NP048L-3

NP048L-5

NP048L-5

NP048L-5

NP048L-7

NP048L-7

NP048L-7

NP048L-9

NP048L-9

NP048L-9

NP048L-11

NP048L-11

NP048L-11

NP048L-11

NP048L-11

NP048L-11

NP048L-13

NP048L-13

NP048L-15

NP048L-15

NP048L-15

NP048L-15

NP048L-15

NP048L-15

NP048L-33

NP048L-33

NP048L-17

NP048L-17

NP048L-17

NP048L-17

NP048L-21

NP048L-21

NP048L-21

NP048L-21

NP048L-22

NP048L-22

NP048L-22

NP048L-22

NP048L-19

NP048L-19

NP048L-19

NP048L-19

NP048L-24

NP048L-24

NP048L-24

NP048L-24

NP048L-25

NP048L-23

NP048L-26

NP048L-26

NP048L-26

NP048L-26NP048L-27

NP048L-27

NP048L-27

NP048L-27NP048L-28

NP048L-28

NP048L-28

NP048L-28

NP048L-32

NP048L-32

NP048L-29

NP048L-29

NP048L-29

NP048L-29

NP048L-30

NP048L-31

NP048L-31

NP048L-31

NP048L-31

NP048L-2

NP048L-2

NP048L-2

NP048L-2

NP048L-4

NP048L-6

NP048L-6

NP048L-6

NP048L-2

NP048L-4

AC-39-0-01

EWH-1

UWH-38-0-01

RP-1

UWH-38-0-02

CONSULT ROOM

PRINTER

034B

STORAGE

CONSULT ROOM

CONSULT ROOM

OFFICE (TRIPLE)

OFFICE (TRIPLE)

TEAM RM

STAFF TOILET

CORRIDOR

034A

HAC

STAIR 3

CORRIDOR

OFFICE (TRIPLE)

OFFICE (TRIPLE)

ELEC. CL.

OFFICE (DOUBLE)

VETERAN W.S.

OFFICE (DOUBLE)

CONSULT ROOM

OFFICE

OFFICE

CHIEF OFFICE

PUBLIC TOILET

MSA

036 WAITING AREA

DS-EWH-1

DS-CP-01

DS-AC-39-0-01

NP048L-34

+78"

CR217L-20

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

ENGINEER ARCHITECT/ENGINEER OF RECORD

WBRC

A R C H I T E C T S • E N G I N E E R S

WWW.WBRCAE.COM

BANGOR, MAINE 207-947-4511

PORTLAND, MAINE 207-828-4511

SARASOTA, FLORIDA 941-556-0757

STAMP

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

Project TitleDrawing Title

Approved:

Phase

Location

Issue Date

Project Number

Building Number

Drawing Number

Checked Drawn

TRUE NORTH

PROJECT NORTH

www.abovegroupinc.com

COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

/8

/2

:4

:2

P M

B

IM

/0

V A

P ro v id e n c e M e n ta l H e a lt h

B u ild in g

P H

/0

V A

P ro v id e n c e

M H

C P

H

R

D iv

.r v t

EP201

650-347PROVIDENCE VAMC MENTAL

HEALTH PHASE 2

PROVIDENCE, RI

JFR SDLFEB 04 2022

CONSTRUCTION

DOCUMENTS

LEVEL B PLAN - POWER

FULLY SPRINKLERED

JOHN F. RAINE, P.E.

MD License #41408

1/4" = 1'-0" F1

LEVEL B PLAN - POWER

0 2' 4' 8' 12'

1/4" = 1'-0"

DRAWING NOTES:

1. ALL RECEPTACLES IN PUBLIC AREAS AND CONSULT ROOMS SHALL BE TAMPER RESISTANT.

2. REFER TO ELECTRICAL EQUIPMENT CONNECTION SCHEDULE AND DISCONNECT SCHEDULE ON SHEET

E-801 FOR ADDITIONAL CONNECTION AND SIZING INFORMATION.

CODED NOTES:

FUSIBLE DISCONNECT DS-TNP048L. SEE ONE-LINE DIAGRAM FOR FURTHER DETAILS.

PROVIDE 120V JUNCTION BOX ABOVE ACCESSIBLE CEILING ON SECURE SIDE OF DOOR FOR ACCESS

CONTROL HARDWARE. PROVIDE LABEL STATING "ACCESS CONTROL 120V" AND CONNECT TO

BRANCH CIRCUIT BREAKER INDICATED WITH LOCK-ON ACCESSORY.

COORDINATE ELECTRICAL CONNECTION WITH BDA EQUIPMENT. REFER TO TELECOM DRAWING T-601

FOR ADDITIONAL INFORMATION.

COORDINATE EXACT TV RECEPTACLE LOCATION WITH TV DATA OUTLET AND TV WALL MOUNTING

BRACKET PRIOR TO ROUGH-IN.

COORDINATE EXACT LOCATION OF DEVICES ON THIS WALL WITH ARCHITECTURAL WALL PANELING

PRIOR TO CONSTRUCTION.

PROVIDE 120V JUNCTION BOX FOR WINDOW FIRE CURTAIN. COORDINATE EXACT LOCATION AND

REQUIREMENTS WITH FIRE CURTAIN VENDOR PRIOR TO ROUGH-IN.

EXISTING PHASE 1. NO WORK IN THIS AREA, UNLESS OTHERWISE NOTED.

P1P2

KEY PLAN

Revisions: Revision Description Date:

1 FIRE CURTAINS TBD

G-2A1 G-3

J

J

J

J

J

J

J J

J

J

J

NP146H

NP146L

TNP146L(SUSPENDED FROM ABOVE)

2-B

E.5

2-D

2-A

2-C

2-E

2-12-2.12-22-3

2-4

2-5

2-6

2-7

2-8

2-F

+60"

+66" G,48"

G,48"

EP202

C7

G

G

NP146L-1

NP146L-1

NP146L-1

NP146L-3

NP146L-3

NP146L-3

NP146L-5

NP146L-5

NP146L-5

NP146L-7

NP146L-7

NP146L-7

NP146L-9

NP146L-9

NP146L-9

NP146L-11

NP146L-11

NP146L-11

NP146L-13

NP146L-13

NP146L-13

NP146L-15

NP146L-15

NP146L-15

NP146L-17

NP146L-17

NP146L-17

CH

CH

NP146L-21

NP146L-21

NP146L-50

NP146L-21

NP146L-23

NP146L-23

NP146L-23

NP146L-25

NP146L-25

NP146L-25

NP146L-27

NP146L-27

NP146L-27

NP146L-29

NP146L-29

NP146L-29

NP146L-31

NP146L-31

NP146L-31

NP146L-31

NP146L-31

NP146L-37

NP146L-35

NP146L-35

NP146L-35

NP146L-37

NP146L-35

NP146L-35 NP146L-33

NP146L-37

NP146L-35

NP146L-39

NP146L-4

NP146L-2

NP146L-41

NP146L-39

NP146L-39

NP146L-39

NP146L-39

NP146L-39

NP146L-41

NP146L-41

NP146L-4

NP146L-4

NP146L-41

NP146L-41

NP146L-17

NP146L-31

NP146L-15

NP146L-13

NP146L-11

NP146L-9

NP146L-6NP146L-7NP146L-5

NP146L-3

NP146L-1

NP146L-19

NP146L-21 NP146L-23

NP146L-25

NP146L-27

NP146L-29

NP146L-8

NP146L-8

NP146L-10

NP146L-10

NP146L-10

AC-39-1-03

UWH-39-1-02 AC-39-1-04

AC-39-1-05

UWH-39-1-01

WAITING AREA

MSA

PUBLIC TOILET

CORRIDOR

GROUP THERAPY

GROUP THERAPY

OFFICE

OFFICE

OFFICE

COUPLE'S THERAPY

COUPLE'S THERAPY

OFFICE

OFFICE

PRINTER

131A

TELEDATA

OFFICE

ELEC. CL.

OFFICE

OFFICE

SECTION CHIEF

STAFF TOILET

STAIR 3

LOUNGE, STAFF

COUPLE'S THERAPY

DS-AC-39-1-03

DS-AC-39-1-04

DS-AC-39-1-05

G

G

CH

NP146L-50

NP146L-33

NP146L-2

NP146L-52

+78"

CH

+60"

NP146L-54

NP146L-53

G

CR217L-20

2-A

2-C

2-6

5 (TYPICAL)

4 (TYPICAL)

DS-UPS-3

DS-UPS-1

DS-UPS-2

DS-UPS-4

(TYPICAL) 6

SEE ENLARGED TELEDATA ROOM 138 PLAN ON

SHEET T-401 AND COORDINATION NOTES ON T-001

FOR BUSBAR AND GROUNDING REQUIREMENTS

NP146L-12,14,16

NP146L-18,20,22

NP146L-24,26,28

NP146L-30,32,34

NP146L-40

CR217L-9

NP146L-40

CR217L-9

NP146L-40

CR217L-10

NP146L-38

CR217L-10

NP146L-38 CR217L-10

NP146L-38

CR217L-11

NP146L-36

CR217L-11

NP146L-36

CR217L-11

NP146L-36

CR217L-9

CR217L-18

E

E

E

E

E

E

E

E

E

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

ENGINEER ARCHITECT/ENGINEER OF RECORD

WBRC

A R C H I T E C T S • E N G I N E E R S

WWW.WBRCAE.COM

BANGOR, MAINE 207-947-4511

PORTLAND, MAINE 207-828-4511

SARASOTA, FLORIDA 941-556-0757

STAMP

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

Project TitleDrawing Title

Approved:

Phase

Location

Issue Date

Project Number

Building Number

Drawing Number

Checked Drawn

TRUE NORTH

PROJECT NORTH

www.abovegroupinc.com

COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

/8

/2

:4

:2

P M

B

IM

/0

V A

P ro v id e n c e M e n ta l H e a lt h

B u ild in g

P H

/0

V A

P ro v id e n c e

M H

C P

H

R

D iv

.r v t

EP202

650-347PROVIDENCE VAMC MENTAL

HEALTH PHASE 2

PROVIDENCE, RI

JFR SDLFEB 04 2022

CONSTRUCTION

DOCUMENTS

LEVEL 1 PLAN - POWER

FULLY SPRINKLERED

JOHN F. RAINE, P.E.

MD License #41408

1/4" = 1'-0" F1

LEVEL 1 PLAN - POWER

0 2' 4' 8' 12'

1/4" = 1'-0"

DRAWING NOTES:

1. ALL RECEPTACLES IN PUBLIC AREAS AND CONSULT ROOMS SHALL BE TAMPER RESISTANT.

2. REFER TO ELECTRICAL EQUIPMENT CONNECTION SCHEDULE AND DISCONNECT SCHEDULE ON SHEET

E-801 FOR ADDITIONAL CONNECTION AND SIZING INFORMATION.

CODED NOTES:

FUSIBLE DISCONNECT DS-TNP146L. SEE ONE-LINE DIAGRAM ON SHEET E-601 FOR DETAILS.

6" POKE THROUGH FLOOR BOX FOR IN FLOOR POWER/DATA OUTLETS. COORDINATE INSTALLATION WITH TELELCOM AND ARCHITECTURAL DRAWINGS PRIOR TO INSTALLATION. BASIS OF DESIGN IS LEGRAND 6" FLUSH MOUNTED POKE THROUGH EVOLUTION SERIES. FINISH TO BE AS DIRECTED BY ARCHITECT. PROVIDE ALL PARTS, ACCESSORIES, PLATES AND COVERS FOR A COMPLETE SYSTEM.

COORDINATE EXACT TV RECEPTACLE LOCATION WITH TV DATA OUTLET AND TV WALL MOUNTING

BRACKET PRIOR TO ROUGH-IN.

NORMAL POWER RECEPTACLE (L21-20) FOR DATA RACK NORMAL SIDE POWER DISTRIBUTION UNIT.

MOUNT RECEPTACLE TO BOTTOM OF CABLE TRAY IN THIS ROOM. COORDINATE EXACT LOCATION

WITH TELECOM DRAWINGS PRIOR TO CONSTRUCTION.

POWER CONNECTION FOR DATA RACK MOUNTED UPS. MOUNT JUNCTION BOX TO BOTTOM OF CABLE

TRAY IN THIS ROOM. COORDINATE EXACT LOCATION WITH TELECOM DRAWINGS PRIOR TO

CONSTRUCTION. JUNCTION BOX CONNECTED TO ASSOCIATED DISCONNECT.

RACK MOUNTED UPS LOCAL DISCONNECT. (2) DISCONNECTS STACKED VERTICALLY. CONNECT

DISCONNECT LOAD SIDE TO JUNCTION BOX ABOVE ASSOCIATED RACK. REFER TO SCHEDULES ON

SHEET E-801 FOR ADDITIONAL…