STRUCTURAL NOTES
MEANS OR METHOD OR SEQUENCE OF CONSTRUCTION.
REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE THE
THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS
CONSTRUCTION INDUSTRY.
ADMINISTRATION (OSHA) SAFETY AND HEALTH STANDARDS FOR THE
THE REGULATIONS OF THE OCCUPATIONAL SAFETY AND HEALTH
PROGRAMS IN CONNECTION WITH THE WORK THAT CONFORMS WITH
THE CONTRACTOR IS RESPONSIBLE FOR SAFETY PRECAUTIONS AND
SQUARE FOOT.
STRUCTURE SO AS NOT TO EXCEED THE DESIGN LIVE LOAD PER
CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON THE
ADDENDUM.
MATERIALS, SUCH STANDARDS SHALL BE THE LATEST EDITION AND/OR
WHERE REFERENCE IS MADE TO VARIOUS TEST STANDARDS FOR
THROUGH THE ARCHITECT.
WITHOUT PRIOR WRITTEN APPROVAL OF THE STRUCTURAL ENGINEER
ELEMENTS (BEAMS, COLUMNS, WALLS, STEEL DECK, SLABS, ETC.)
APPROVED BY THE ENGINEER. DO NOT PENETRATE ANY STRUCTURAL
COMPONENTS. ALL OPENINGS SHALL BE PROPERLY REINFORCED AS
THE MANUFACTURER OF ANY PRE-ENGINEERED FRAMING OR
SUSPENDED FROM THE STRUCTURE SHALL BE COORDINATED WITH
EQUIPMENT SUPPLIERS. EQUIPMENT BEING SUPPORTED BY OR
RESPONSIBILITY TO COORDINATE WITH THE SUBCONTRACTORS AND
APPROPRIATE TRADE. IT IS THE GENERAL CONTRACTORS
ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING WITH
ESTABLISH AND VERIFY ALL OPENINGS, INSERTS, OR EQUIPMENT FOR
NOT USE SCALED DIMENSIONS.
ARCHITECT PRIOR TO CONSTRUCTION AND PRIOR TO PROCEEDING. DO
DISCREPANCIES AND OMISSIONS SHALL BE RESOLVED WITH THE
CONDITIONS WITH THE DRAWINGS PRIOR TO CONSTRUCTION. ANY
CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND COORDINATE SITE
REQUIREMENTS SHALL GOVERN.
STRUCTURAL NOTES AND SPECIFICATIONS, THE GREATER
WHERE ANY DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS,
SHALL APPLY UNLESS NOTED OTHERWISE.
DETAILS MAY OR MAY NOT BE CUT AT ALL SPECIFIC LOCATIONS, BUT
TYPICAL DETAILS MAY OR MAY NOT BE CUT ON THE DRAWINGS, AND
WORK.
OF ALL DETAILS AS REQUIRED TO INCORPORATE THE OPTION INTO THE
FOR ALL CHANGES AND COSTS NECESSARY AND FOR COORDINATION
AN OPTION IS CHOSEN, THE CONTRACTOR SHALL BE RESPONSIBLE
CONVENIENCE AND ARE SUBJECT TO APPROVAL BY THE ARCHITECT. IF
APPROVED EQUAL OPTIONS ARE FOR THE CONTRACTOR'S
PROJECT IS LOCATED.
STRUCTURAL ENGINEER REGISTERED IN THE STATE WHICH THE
REVIEW SHALL BEAR THE SEAL OF A PROFESSIONAL CIVIL OR
ANY ENGINEERING DESIGN PROVIDED BY OTHERS AND SUBMITTED FOR
GENERAL:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
INTERNATIONAL BUILDING CODE.
ALL CONSTRUCTION SHALL CONFORM TO THE 2015 EDITION OF THE
ROOF:
WIND:
SEISMIC:
1.
2.
3.
4.
RISK CATEGORY - II
EXPOSURE - "C"
ULTIMATE WIND SPEED - 115 MPH (3 SEC GUST.)
R - 2.0
SD1 - 0.048
SDS - 0.090
SPECTRAL RESPONSE COEFFICIENTS:
IMPORTANCE FACTOR - "1.0"
RISK CATEGORY - II
DESIGN LOADS:
GEOTECHNICAL CONSULTANT: TERRACON1.
REPORT NUMBER: A41250532.
REPORT DATE: JULY 12, 20123.
FOUNDATION DETAILS AND/OR PLANS.
BOTTOM OR TOP OF FOOTING ELEVATIONS, COORDINATE WITH
GEOTECHNICAL REPORT AND TYPICAL EARTHWORK DETAIL. FOR
UNDISTURBED SOIL AND/OR ENGINEERED FILL PER THE
LOWEST ADJACENT FINISHED GRADE. FOOTINGS SHALL BEAR ON FIRM
DESIGN SOIL BEARING PRESSURE = 2500 PSF AT 2'-0" BELOW 4.
5.
6.
BY THE SOILS ENGINEER.
REMOVED AS COORDINATED WITH THE ARCHITECT AND AS DIRECTED
INTERFERE WITH NEW CONSTRUCTION SHALL BE REROUTED OR
ABANDONED FOOTINGS, NEW OR EXISTING UTILITIES, ETC., THAT
7.
1.
MATERIAL RATIO BE EXCEEDED.
ON SITE. IN NO CASE SHALL THE DESIGN WATER TO CEMENTITIOUS
THE MAXIMUM AMOUNT OF WATER THAT CAN BE ADDED TO THE BATCH
SUCH CASE THE MIX DESIGN AND TRUCK TICKET MUST CLEARLY STATE
SPECIFICALLY WITHHELD WATER FROM THE BATCH AT THE PLANT. IN
SLUMP WILL NOT BE PERMITTED, UNLESS THE SUPPLIER HAS
ADDITION OF WATER TO THE BATCH FOR MATERIAL WITH INSUFFICIENT 2.
ASTM C94.
CONCRETE SHALL BE READY MIXED CONCRETE IN ACCORDANCE WITH 3.
BY THE STRUCTURAL ENGINEER PRIOR TO CONSTRUCTION.
PRODUCTION FACILITY IN ACCORDANCE WITH ACI 301 AND APPROVED
PLACEMENT. MIX DESIGNS SHALL BE DESIGNED BY THE CONCRETE
SUPERPLASTICIZING ADMIXTURE SHALL HAVE 8" MAXIMUM SLUMP AT
SLUMP FOR ALL CONCRETE. CONCRETE CONTAINING
ASTM C33. LIGHTWEIGHT AGGREGATE PER ASTM C330. MAXIMUM 5"
CEMENT SHALL CONFORM TO ASTM C150, TYPE II. AGGREGATE PER 4.
TESTING SHALL BE DONE BY A QUALIFIED TESTING LABORATORY.
ENGINEER. TEST ONE CYLINDER AT 7 DAYS AND TWO AT 28 DAYS.
EACH DAY'S CONCRETE PLACEMENT OR AS DIRECTED BY THE
PER ASTM C31, C39 AND C143. PROVIDE 3 CYLINDERS PER TEST FOR
CONCRETE COMPRESSIVE STRENGTH AND SLUMP SHALL BE TESTED
SPECIFIED BY THE MANUFACTURER.
THEREOF. IF CURING COMPOUND IS USED, APPLY AT A RATE
CURING, MOISTURE-RETAINING COVER CURING, OR COMBINATIONS
CRACKING. CURE WITH CURING AND SEALING COMPOUND, MOIST
ACCORDANCE WITH ACI 301 PROCEDURES IN ORDER TO PREVENT
CURE EXPOSED CONCRETE FOR A MINIMUM OF 7 DAYS IN
OCCURRED IS NOT PERMITTED.
BE USED. RETEMPERING OF CONCRETE AFTER INITIAL SET HAS
CONCRETE WHICH HAS CONTAINED WATER FOR MORE THAN 90
REPLACE MORE THAN 20% OF CEMENT BY WEIGHT.
SHALL CONFORM TO ASTM C618, CLASS F. FLY ASH SHALL NOT
CONCRETE SHALL BE FREE OF CHLORIDE. WHEN USED, FLY ASH
VERTICALLY WITHOUT USE OF TREMIES.
CONCRETE SHALL NOT BE DROPPED MORE THAN FIVE FEET
5.
MAINTAINED.
AND THE REQUIRED CONCRETE COVERAGE FOR REINFORCING IS
EXCAVATIONS PROVIDED THAT FOOTING DIMENSION ARE ADHERED TO,
CONCRETE FOOTINGS AND PADS MAY BE POURED AGAINST NEAT
6.
PLACING CONCRETE. DO NOT CUT ANY CONFLICTING REINFORCING.
PROVIDE SLEEVES FOR UTILITY OPENINGS IN CONCRETE BEFORE
7.
8.
COLUMNS, WALLS, ETC., U.N.O.
PROVIDE 3/4" CHAMFER ON ALL EXPOSED EDGES OF BEAMS,
AREA, AND ADJACENT TO PENETRATIONS.
ONLY AT AREA OF REINFORCEMENT, EMBEDDED ITEMS, THICKENED
ON GRADE, 4" INCHES OR LESS IN THICKNESS, NEED BE VIBRATED
MECHANICALLY VIBRATE ALL CONCRETE WHEN PLACED, EXCEPT SLABS
10.
IS APPLIED.
CAST CLOSURE POUR AROUND COLUMNS AFTER COLUMN DEAD LOAD 12.
13.
CAST-IN-PLACE CONCRETE:
ACI 305; AND ACI 306 FOR COLD WEATHER CONCRETING.
ALL HOT WEATHER CONCRETING SHALL MEET THE REQUIREMENTS OF
14.
ALL OTHERS PER LATEST EDITION OF ACI 318
BEAMS (TO STIRRUPS) . . . . . 1 1/2"
COLUMNS (TO TIES) . . . . . . . 1 1/2"
#5 AND SMALLER . . . . . . 1 1/2"
#6 AND LARGER . . . . . . . . 2"
EXPOSED TO EARTH OR WEATHER:
ALL REINFORCING . . . . . . 3"
CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH:
PROVIDE THE FOLLOWING MINIMUM CLEAR CONCRETE COVERAGE:
GALVANIZED METAL OR PLASTIC CHAIRS, SPACERS OR HANGERS.
ON GRADE, SHALL BE ACCURATELY PLACED AND SUPPORTED BY
ALL REINFORCING STEEL, INCLUDING WELDED WIRE FABRIC IN SLAB
AND WALLS.
HORIZONTAL BARS AT CORNERS AND INTERSECTIONS OF FOOTINGS
OR PROVIDE BENT CORNER BARS TO MATCH AND LAP WITH
REINFORCING CONTINUOUS AROUND CORNERS AND INTERSECTIONS
INDICATED ON THE DRAWINGS. EXTEND ALL HORIZONTAL
LOCATIONS SUBJECT TO APPROVAL AND SHALL BE MADE ONLY WHERE
THAN THE CROSS WIRE SPACING PLUS 2 INCHES. ALL SPLICE
BETWEEN OUTERMOST CROSS WIRES OF EACH SHEET IS NOT LESS
ONE LAP LENGTH. LAP WELDED WIRE FABRIC SO THAT THE OVERLAP
EDITION OF ACI 318. STAGGER ALTERNATE SPLICES A MINIMUM OF
CLASS "B" TENSION LAP SPLICES (2'-0" MINIMUM) PER THE LATEST
UNLESS NOTED OTHERWISE, LAP SPLICES IN CONCRETE SHALL BE
EMBEDMENT LENGTH PER THE LATEST EDITION OF ACI 318.
EMBEDMENT SHALL BE A STANDARD COMPRESSION DOWEL
POSITION BEFORE PLACING CONCRETE. CONCRETE COLUMN DOWEL
REQUIRED FOR CONCRETE COVER. SECURELY TIE ALL BARS IN
DOWEL ALL VERTICAL REINFORCING TO FOUNDATION. SKEW HOOKS AS
REINFORCING BAR SPACING GIVEN ARE MAXIMUM ON CENTERS.
BY THE ENGINEER.
CONTINUOUS AND SPLICED ONLY AS SHOWN, OR WHERE APPROVED
"CONTINUOUS" OR WITH LENGTH NOT SHOWN SHALL BE FULLY
UNLESS NOTED OTHERWISE. REINFORCING BARS NOTED
SPLICED BARS SHALL BE PLACED AT THE SAME EFFECTIVE DEPTH
NOTED OTHERWISE.
REINFORCING BAR HOOKS SHALL BE STANDARD ACI HOOKS UNLESS 8.
7.
6.
5.
REINFORCING BAR BENDS SHALL BE MADE COLD.
CONSTRUCTION", AND AS MODIFIED BY THE DRAWINGS. ALL
"MANUAL OF STANDARD PRACTICE FOR REINFORCED CONCRETE
CONFORMANCE WITH THE LATEST EDITIONS OF ACI 318 AND THE CRSI
ALL REINFORCING STEEL SHALL BE DETAILED AND PLACED IN
4.
2.
1.
REINFORCING STEEL:
REPORT #ESR-3013.
HILTI "HIT-HY I5O MAX-SD" ADHESIVE INSTALLED PER ICC B.
#ESR-2508.
SIMPSON "SET-XP" EPOXY INSTALLED PER ICC REPORT A.
EPOXY USED IN CONCRETE SHALL BE ONE OF THE FOLLOWING:
REPORT WHEN APPROVED IN WRITING BY THE ENGINEER.
EQUAL VALUE IN THE SPECIFIED MATERIAL WITH A CURRENT ICC
CONTRACTOR MAY SUBSTITUTE EXPANSION BOLTS OR EPOXY OF
MECHANICAL ANCHORS":
COMPONENTS "EPOXY AND
POST INSTALLED ANCHORING
1.
3.
6.
IN WRITING BY THE ENGINEER.
ONLY WHERE SPECIFICALLY DETAILED OR NOTED, OR WHEN DIRECTED
USE OF EXPANSION ANCHORS OR EPOXY TYPE ADHESIVE SHALL BE
5.
REPORT #ESR-1771.
STRONG-BOLT WEDGE ANCHOR BY SIMPSON INSTALLED PER ICC B.
KWIK BOLT TZ BY HILTI INSTALLED PER ICC REPORT #ESR-1917.A.
FOLLOWING:
EXPANSION ANCHORS USED IN CONCRETE SHALL BE ONE OF THE
#ESR-1967.
HILTI "HIT-HY I5O MAX" ADHESIVE INSTALLED PER ICC REPORT B.
SIMPSON "SET" EPOXY INSTALLED PER ICC REPORT #ESR-1772.A.
EPOXY USED IN MASONRY SHALL BE ONE OF THE FOLLOWING:2.
4.
#ESR-1396.
WEDGE-ALL ANCHOR BY SIMPSON INSTALLED PER ICC REPORT B.
KWIK BOLT 3 BY HILTI INSTALLED PER ICC REPORT #ESR-1385.A.
FOLLOWING:
EXPANSION ANCHORS USED IN MASONRY SHALL BE ONE OF THE
SS1
11.
ARCHITECT/ENGINEER.
TRIMMED FOR ANY REASON WITHOUT THE WRITTEN APPROVAL OF THE
COLUMNS, BEAMS, JOISTS, OR TRUSSES SHALL NOT BE FIELD CUT OR
12.
BUILDING SLABS.
VEHICLES ARE NOT TO BE DRIVEN ACROSS GRADE BEAMS OR
CRANES, CONCRETE TRUCKS AND ALL OTHER HEAVILY LOADED
6'-6" FEET FROM EACH CORNER
CORNER ZONE ______________ 35 PSF
INTERIOR ZONE ______________ 30 PSF
WALL COMPONENTS AND CLADDING (EFFECTIVE WIND AREA 50 PSF)
6'-6" FEET FROM EACH CORNER
CORNER ZONE ______________ 60 PSF
EXTERIOR ZONE ______________ 40 PSF
INTERIOR ZONE ______________ 30 PSF
ROOF NET UPLIFT (EFFECTIVE WIND AREA 50 PSF) 3.
ASTM A706, GRADE 60 (Fy = 60 KSI) LOW ALLOY DEFORMED BARS.
AND SMALLER. REINFORCING TO BE WELDED SHALL CONFORM TO
A615, GRADE 40 (Fy = 40 KSI) DEFORMED BARS FOR ALL BARS #3
= 60 KSI) DEFORMED BARS FOR ALL BARS #5 AND LARGER. ASTM
REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60 (Fy
OR 8". PROVIDE FLAT SHEETS, NO ROLLS.
EMBEDMENT TO BE GREATER OF ONE CROSS WIRE SPACING PLUS 2"
WELDING OF REINFORCING BARS ALLOWED. MINIMUM LAP AND
OF REINFORCING SHALL BE ACCORDING TO AWS D1.4. NO TACK
WELDED WIRE FABRIC PER ASTM A185, WIRE PER ASTM A82. WELDING
9.
GRADE 40.
ASTM A-615, GRADE 60, EXCEPT #3 STIRRUP BARS WHICH MAY BE
RUST OR OIL, AND SHALL MEET OR EXCEED THE REQUIREMENTS OF
ALL REINFORCING STEEL SHALL BE CLEAN, NEW AND FREE OF DIRT,
10.
REQUIRED.
SECTION NOTES AND GENERAL NOTES FOR ACTUAL REINFORCING
SCHEMATIC INDICATION THAT REINFORCING EXISTS. SEE SCHEDULES,
REINFORCING STEEL SHOWN IN SECTIONS AND DETAILS ARE A
11.
BUSH-HAMMERED, PROVIDE ACCESSORIES OF STAINLESS STEEL.
RUSTPROOF LEGS. WHERE CONCRETE IS SAND-BLASTED OR
EXPOSED IN FINISHED BUILDING, PROVIDE ACCESSORIES WITH
WITH ACI MANUAL OF STANDARD PRACTICE. WHERE CONCRETE IS
REINFORCING BAR PLACING ACCESSORIES SHALL BE IN ACCORDANCE
7. INSTALL ANCHORS PER MANUFACTURER'S RECOMMENDATIONS.
FOUNDATIONS:
LIGHT FRAMED WALLS WITH SHEET STEEL SHEAR PANELS.
BASIC SEISMIC FORCE RESISTANCE SYSTEM:
SEISMIC DESIGN CATEGORY - "A"
SITE CLASS - "D"
PROCEDURE - EQUIVALENT LATERAL FORCE PROCEDURE
DESIGN BASE SHEAR - 0.032W (WORKING STRESS) ANALYSIS
15.
SHALL BE PROVIDED ON ALL CONCRETE.
CONSTRUCTION TO PROCEED. A HARD STEEL TROWEL FINISH
SUFFICIENT TIME ALLOWED BEFORE PERMITTING TRAFFIC OR
ALL CONCRETE SURFACES SHALL BE PROPERLY CURED AND
16.
CONFORM TO ASTM D-3405.
SEALANT FOR PORTLAND CEMENT CONCRETE PAVEMENTS SHALL
MINIMUM UNLESS SHOWN OTHERWISE ON DRAWINGS. JOINT
D-1751 OR D-1752. JOINT FILLER SHALL BE 1/2 INCH THICK
JOINT FILLER STRIPS FOR JOINTS SHALL CONFORM TO ASTM
17.
18.
19.
20.
23.
THE RESPONSIBILITY OF THE CONTRACTOR.
THE DESIGN, CONSTRUCTION, AND SAFETY OF ALL FORMWORK IS
AT CORNERS.
2'-0" PAST OPENINGS. PROVIDE 2-#5 x 4'-0" DIAGONAL BARS
OR GREATER (TYPICAL UNLESS NOTED): 2 - #5, EXTEND REINF
MINIMUM REINFORCING AROUND CONCRETE WALL OPENINGS 2'-0"
FLOOR FINISH REQUIREMENTS TO ENSURE COMPATIBILITY.
CONTRACTOR SHALL COORDINATE ALL CURING COMPOUNDS WITH
5. ROOF SNOW LOADS
6.
BUILDINGS.
BUILDING TO ENSURE NO PONDING OF WATER OCCURS AROUND
ALL EXTERIOR FINISHED GRADES SHALL SLOPE AWAY FROM THE
8.
9.
STEEL.
EXCAVATIONS TO A HARD SURFACE BEFORE PLACING REINFORCING
CONTRACTOR SHALL HAND TAMP BOTTOM OF GRADE BEAM
COLUMN ANCHOR RODS SHALL BE SET WITH A TEMPLATE.
POSITION PRIOR TO CONCRETE PLACEMENT. STRUCTURAL STEEL
PROJECTION AND THAT ANCHOR RODS ARE HELD SECURELY IN
FOUNDATION CONTRACTOR TO ENSURE PROPER ANCHOR ROD
10.
SHALL BE PROVIDED ON ALL CONCRETE.
CONSTRUCTION TO PROCEED. A HARD STEEL TROWEL FINISH
SUFFICIENT TIME ALLOWED BEFORE PERMITTING TRAFFIC OR
ALL CONCRETE SURFACES SHALL BE PROPERLY CURED AND
11.
12.
13.
14.
OF THE BUILDING FOUNDATION.
SHALL BE PROVIDED IN ALL UTILITY TRENCHES AT THE FACE
BACKFILL. DO NOT USE SAND BACKFILL. A BENTONITE PLUG
THE BUILDING SHALL BE BACKFILLED WITH SELECT FILL
BUILDING PAD AND EXTENDING OUT 5'-0" MINIMUM BEYOND
ALL BACKFILL FOR BURIED PIPES AND CONDUIT WITHIN THE
15.
REQUIREMENTS.
WITH THE MANUFACTURER'S RECOMMENDATIONS AND
VAPOR BARRIER SHALL BE SEALED IN STRICT ACCORDANCE
BENEATH THE VAPOR BARRIER. ALL PENETRATIONS IN THE
CONDUITS SHALL BE PLACED IN THE SELECT FILL MATERIAL
CONDUITS SHALL NOT BE PLACED IN THE CONCRETE SLAB.
16.
17.
GROUND SUPPORTED SLAB AT GRADE CONSTRUCTION.
CONSTRUCTION, PERFORMANCE AND RISKS INVOLVED IN
ENGINEER IF THERE ARE ANY QUESTIONS CONCERNING
OWNER SHOULD CONSULT WITH THE GEOTECHNICAL
OCCUPANCY OF THE BUILDING. THE CONTRACTOR AND THE
OVER WHICH THE OWNER HAS CONTROL OF AFTER
AND IS DEPENDENT ON MANY ENVIRONMENTAL CONDITIONS
THE PERFORMANCE OF THE SLAB INVOLVES SOME RISKS
REPORT. THE ARCHITECT SHALL ADVISE THE OWNER THAT
SITE PREPARATION INSTRUCTIONS IN THE GEOTECHNICAL
DEPENDENT ON HOW WELL THE CONTRACTOR FOLLOWS THE
INTENDED BY THE GEOTECHNICAL ENGINEER IS HIGHLY
THAT THE PERFORMANCE OF THE SLAB AS DESIGNED AND
GROUND UNDER THE SLAB. THE CONTRACTOR SHOULD NOTE
INTENDED TO BE ENTIRELY SUPPORTED BY THE PREPARED
ANY EXTERNAL UPWARD OR DOWNWARD LOADS. IT IS
STRUCTURAL SLAB AND AS SUCH IT IS NOT DESIGNED FOR
RECOMMENDED IN THE GEOTECHNICAL REPORT. IT IS NOT A
SUPPORTED SLAB AT GRADE AS PER THE DESIGN
NOTE THAT THE GROUND FLOOR SLAB IS A GROUND
AT CHANGES IN WALL THICKNESS.
IN WALLS SHALL ALSO BE LOCATED 15'-0" FROM CORNERS AND
SHALL BE SPACED AT 25'-0" MAX FOR WALLS. CONTROL JOINTS
NO GREATER THAN 60'-0". INTERMEDIATE CONTROL JOINTS
AND WALLS THAT DO NOT CHANGE DIRECTION SHALL BE SPACED
CONSTRUCTION JOINTS IN GRADE BEAMS, CONTINUOUS FOOTINGS,
FOR APPROVAL. REFER TO TYP DETAIL 401/SS12.
POSSIBLE. CONTRACTOR SHALL SUBMIT JOINT LAYOUT TO ARCHITECT
JOINTS SHALL BE LOCATED AT COLUMN CENTERLINES WHERE
SHALL NOT EXCEED THE SHORTER DIMENSIONS BY MORE THAN 20%.
EXCEED 225 SQUARE FEET. THE LONGER DIMENSION OF EACH PANEL
GRADE SHALL BE SPACED TO DIVIDE THE SLAB INTO PANELS NOT TO
SAW CUT JOINTS OR KEYED CONSTRUCTION JOINTS IN SLABS ON
BUILDING.
THE FLOOR SLAB AND EXTENDING 5'-0" MINIMUM BEYOND THE
ON A MINIMUM OF 2 FEET OF SELECT FILL MATERIAL BENEATH
FOUNDATION DETAILING SHOWN ON THE DRAWINGS IS BASED
PHYSICAL SECURITY DESIGN LOADING
THERMAL FACTOR (Ct) ________________ 1.1
SNOW LOAD IMPORTANCE FACTOR (Is) ______ 1.0
SNOW EXPOSURE FACTOR (Ce) ___________ 1.0
FLAT ROOF SNOW LOAD (Pf) _____________ 5 PSF
GROUND SNOW LOAD (Pg) ______________ 5 PSF
BUILDINGS AND CHAPTER 7 OF PSDM.
REQUIRED PER ASCE 59-11 BLAST PROTECTION OF
AND USE. PER PSDM CHAPTER 7, BALANCE DESIGN
CONSTRUCTION PER IBC 2015 BASED ON OCCUPANCY
BUILDING COULD BE CLASSIFIED AS TYPE V
PER PHYSICAL SECURITY DESIGN MANUAL (PSDM) CH 7,
RECOMMENDATIONS AND REQUIREMENTS.
SEALED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S
REQUIREMENTS OF ASTM E 1643. PENETRATIONS SHALL BE
INSTALLED AND LAPPED IN ACCORDANCE WITH THE
WITH ASTM E96. THE WATER VAPOR BARRIER SHALL BE
PERMEANCE OF 0.01 PERMS WHEN TESTED IN ACCORDANCE
1745, CLASS C OR BETTER AND SHALL A MAXIMUM WATER
VAPOR BARRIER MEETING THE REQUIREMENTS OF ASTM E
GRADE BEAMS SHALL BE COVERED WITH A 15 MIL WATER
PREPARED GRADE AREA UNDER ALL BUILDING SLABS AND
ROOF DEAD LOAD = 20 PSF
OR 300 lb CONCENTRATED LOAD
ROOF LIVE LOAD = 20 PSF (REDUCIBLE)
STRUCTURAL GENERAL NOTES
SCALE: NTS
SS1-STRUCTURAL NOTES.dgn
DRILLED SHAFTS 3,000PSI
FOUNDATIONS 3,000 PSI (DESIGNED FOR 2,500 PSI)
SLABS ON GRADE 3,000 PSI (DESIGNED FOR 2,500 PSI)
WALLS 3,000 PSI
ELEVATED SLABS 3,000 PSI
MIN. 28 DAY COMPRESSIVE STRENGTH CONCRETE USES:
10.
11.
21.
22.
FINAL FACE OF SHOTCRETE WALL.
REQUIRED REINFORCEMENT AND SET MAT 2" MIN TO 4" MAX FROM
FOR FINAL SHOTCRETE FACE AS NECESSARY TO MAINTAIN MINIMUM
CONTRACTOR SHALL ADJUST AND ADD TO EXISTING REINFORCING MAT
EXCAVATIONS SHALL BE REMOVED FROM THE BUILDING PAD.
BEARING SURFACE. ALL SPOILS FROM THE FOOTING
COMPLETION OF EXCAVATION AND CLEANING OF FOOTING
FOOTINGS SHALL BE POURED AS SOON AS POSSIBLE UPON
GREATER REQUIREMENTS SHALL GOVERN.
STRUCTURAL NOTES, SPECIFICATIONS AND GEOTECH REPORT, THE
WHERE ANY DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS,
RESPONSIBLE FOR ANY GEOTECHNICAL ASPECTS OF THIS PROJECT.
THE GEOTECHNICAL REPORT. THE STRUCTURAL ENGINEER IS NOT
ALL CONSTRUCTION SHALL COMPLY WITH THE RECOMMENDATIONS OF
SERVICES.
SPECIFICATION SECTION 01 45 29 TESTING LABORATORY
ARCHITECT/ENGINEER/GEOTECHNICAL ENGINEER. SEE
REQUIREMENTS, COORDINATE ADJUSTMENTS WITH
ACTUAL SITE CONDITIONS DO NOT SATISFY THESE
ENSURE DESIGN ALLOWABLE BEARING VALUES ARE MET. IF
GEOTECHNICAL ENGINEER PRIOR TO INSTALLING FOOTINGS TO
SOIL BEARING TESTS SHALL BE PERFORMED BY A
CONCRETE".
AND ACI 318, "BUILDING CODE REQUIREMENTS FOR REINFORCED
301, "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS",
CONCRETE WORK SHALL CONFORM TO ALL REQUIREMENTS OF ACI
o n e q u a r t e r in c h o n e f o o t o n e e ig h t h in n e f o o t t h r e e q u a r t e r s in n e f o o t t h r e e e ig h t h s in n e f o o t o n e h a lf in n e f o o t o n e in n e f o o t o n e a n d o n e h a lf in n e f o o t t h r e e in c h e s n e f o o t 6
H2B, INC.
713.864.2900
HOUSTON, TX 77008
1225 N Loop W, Suite 800
Texas Firm Registration No. 8856
S
P r o j e c t s
S p u r
D s ig n
B ig
S p r in g
C L
P
II
D G
N
S S S
T R
U C
T U
R A
N O
T E
S .d g n
:5
:3
M
SBBL PROJECT NO:
V.A. PROJECT NO:
ARCHITECT OF RECORD:
CAD FILE #
Approved: VA Area Proj. Mgr.
15032
519-369
Revision
DATE:
Date
DRAWN BY: ZAF
Revision
DATE:
Date Revision
DATE:
Date Revision
DATE:
Date
Approved: Med. Ctr. Director
Approved: Associate Director
Approved: Chief of Engineering
Approved: Projects Supervisor
C O
N S
T R
U C
T N
E W C
L C P
H A
S E
C A
R E S
Y S
T E
M
B
IG
S
P R
IN
G T E
X A
S
W E
S T T
E X
A S V
A H
E A
L T
H
12-23-2020
Management and Facilities
Construction
Office of
SHEET OF
BID DOCUMENTS
FULLY SPRINKLERED
CONSULTANTS:
CHECKED BY: CCM
BID DOCUMENTS SUBMISSION
12/23/2020
ERECTION OF STRUCTURAL STEEL FOR BUILDINGS.
LATEST AISC SPECIFICATION FOR THE DESIGN, FABRICATION, AND
STRUCTURAL STEEL CONSTRUCTION SHALL CONFORM WITH THE 1.
STRUCTURAL PROPERTIES:2.
6.
WIDE FLANGE SHAPES -
AND ANGLES -
CHANNELS, PLATES,
SHAPES -
STRUCTURAL TUBE
STEEL PIPE -
BOLTS IN WOOD -
BOLTS STEEL/STEEL -
BOLTS) -
ANCHOR RODS (ANCHOR
ASTM A992 (Fy = 50 KSI)
ASTM A36 (Fy = 36 KSI)
ASTM A500, GRADE B (Fy = 46 KSI)
TYPES E OR S, GRADE B (Fy = 35 KSI).
ASTM A501 (Fy = 36 KSI) OR ASTM A53, ASTM A307
NOTED OTHERWISE
CONDITION AS DEFINED BY AISC UNLESS
SHALL BE TIGHTENED TO THE SNUG-TIGHT
ASTM A325N. ALL HIGH-STRENGTH BOLTS
TYPICAL DETAIL)
ASTM F1554 GR 36 (EMBEDMENT PER THE
STRUCTURAL STEEL:
DRAWINGS.
SHALL BE INSTALLED IN LIEU OF BRIDGING WHERE NOTED ON THE
LINES, AND ELSEWHERE AS NOTED ON DRAWINGS. SOLID BLOCKING
ADDITION, BRIDGING SHALL BE PROVIDED AT ROOF LINES, FLOOR
PROVIDE BRIDGING EQUALLY SPACED AT 4'-0" O.C. MAXIMUM. IN
RECOMMENDATIONS WITH THE FOLLOWING MINIMUM REQUIREMENTS:
BRIDGING SHALL BE INSTALLED PER MANUFACTURER'S
DEAD LOADS.
PERMANENT SHEATHING PRIOR TO APPLICATION OF FLOOR OR ROOF
BEARING STEEL STUD WALLS SHALL BE BRACED WITH TEMPORARY OR
INTERRUPT ONE OR MORE MEMBERS UNLESS NOTED OTHERWISE.
PARTITIONS AND AROUND ALL FLOOR AND ROOF OPENINGS WHICH
BEAM BEARINGS AND JOIST BEARINGS. DOUBLE UP JOISTS BELOW
PROVIDE DOUBLE STUDS AT ALL JAMBS, CORNERS, INTERSECTIONS
UNLESS NOTED OTHERWISE, AT STEEL STUD BEARING SYSTEMS
DEFLECTING UNDER SUPERIMPOSED LOADS.
STRUCTURE IN ANY WAY THAT WOULD PREVENT THE FRAMING FROM
ATTACH THE STUDS TO THE NOTSHOWN ON THE SHOP DRAWINGS. DO
SYSTEMS SHALL HAVE VERTICAL SLIP CONNECTIONS AS DETAILED AND
STEEL STUD CONSTRUCTION FOR NON-BEARING CURTAIN WALL
OF STRUCTURAL ENGINEER.
STUDS OR JOISTS SHALL NOT BE SPLICED WITHOUT PRIOR APPROVAL
DRAWINGS.
AT LOCATIONS EXPOSED TO WEATHER AND WHEREVER NOTED ON THE
OF TT-P-636C. STEEL SHALL BE GALVANIZED PER ASTM A525, G60
RUST-INHIBITIVE PAINT MEETING THE PERFORMANCE REQUIREMENTS
STUDS, JOISTS AND ACCESSORIES SHALL BE PRIMED WITH
PSI.
ASTM A446, GRADE A, WITH A MINIMUM YIELD STRENGTH OF 33,000
GALVANIZED TRACK, BRIDGING AND ACCESSORIES SHALL CONFORM TO
GALVANIZED 18 AND 20 GAGE STUDS AND JOISTS AND ALL
OF 50,000 PSI.
CONFORM TO ASTM A446, GRADE D, WITH A MINIMUM YIELD STRENGTH
GALVANIZED 12, 14 AND 16 GAGE STUDS AND JOISTS SHALL
PSI.
ASTM A611, GRADE C, WITH A MINIMUM YIELD STRENGTH OF 33,000
PAINTED TRACK, BRIDGING AND ACCESSORIES SHALL CONFORM TO
PAINTED 18 AND 20 GAGE STUDS, TRACK AND JOISTS, AND ALL
MINIMUM YIELD STRENGTH OF 50,000 PSI.
TENSION STRAPS SHALL CONFORM TO ASTM A570, GRADE 50, WITH A
PAINTED 12, 14 AND 16 GAGE STUDS AND JOISTS, AND DIAGONAL
5.
11.
10.
9.
8.
7.
12.
4.
3.
2.
DRAWINGS. TYPICAL CALLOUTS ARE AS FOLLOWS:
STEEL STUD AND/OR JOIST SIZES ARE AS INDICATED ON THE 6.
68 IS 14 GAUGE MATERIAL
54 IS 16 GAUGE MATERIAL
43 IS 18 GAUGE MATERIAL
33 IS 20 GAUGE MATERIAL
33 INDICATES MINIMUM MATERIAL THICKNESS IN 1/1000 INCHES
162 INDICATES FLANGE WIDTH IN 1/100 INCHES
S INDICATES STYLE S = STUD, T = TRACK
600 INDICATES MEMBER DEPTH IN 1/100 INCHES
EXAMPLE: 600 S162 - 33 (AS REFERENCED IN SSMA)
OF 2 ANCHORS.
INTERSECTIONS AND WALL ENDS. ALL TRACKS SHALL HAVE A MINIMUM
ANCHORS SHALL BE PLACED WITHIN 8" OF ALL JAMBS, CORNERS,
THE DETAILS. TRACK ANCHORS SHALL BE PER PLANS AND DETAILS.
MINIMUM WITH 1 1/2" FLANGES MINIMUM AND SHALL BE SIZED PER
STEEL STUD WALL TRACKS AND BLOCKING SHALL BE 16 GAGE
13.
12.
PRIMER AND TOUCHED-UP WITH PAINT.
SHALL BE DE-SLAGGED, CLEANED AND PRIMED WITH A ZINC-RICH
(MINIMUM) SERIES LOW HYDROGEN RODS. ALL EXPOSED WELDS
LIGHT GAGE STEEL DECK WORK. ALL WELDING DONE BY E60
ALL WELDING SHALL BE PERFORMED BY WELDERS EXPERIENCED IN
APPLICABLE) SHALL BE FULL PANEL WIDTH SHEETS.
COLLECTOR, OR DRAG MEMBERS (ON ONE OR BOTH SIDES AS
WALLS, PERIMETER MEMBERS, OR MEMBERS IDENTIFIED AS CHORD,
THE FIRST SHEET OF STEEL DECK ADJACENT AND PARALLEL TO
MINIMUM.
MEMBER WITH 3/16" FILLET WELD, 2" LONG AT 6" O.C., TYPICAL
ALL CONDITIONS WHERE DECK DOES NOT SIT FLAT ONTO SUPPORT
PROVIDE CONTINUOUS BENT PLATES (1/4" MINIMUM THICKNESS) AT
SHALL HAVE A CURRENT ICC APPROVAL.
DECK AND ASTM A653 GRADE A FOR GALVANIZED DECK. STEEL DECK
STEEL DECK SHALL CONFORM TO ASTM A1008 GRADE C FOR PAINTED
5.
4.
1.
ROOF DECK PROPERTIES:2.
FINISH --------- PAINTED/GALVANIZED
MIN. DIAPH. SHEAR CAPACITY - 577 PLF
SPAN MIN. ------ 3 SPAN
I MIN. --------- 0.289 INCHES^4 PER FOOT OF WIDTH
S+ min --------- 0.318 INCHES^3 PER FOOT OF WIDTH
Fy min --------- 38,000 PSI
GAGE --------- 18
WIDTH --------- 36"
DEPTH --------- 1 1/2"
3.
ATTACHMENT: PER TYPICAL DETAIL
STEEL ROOF DECK:
CONTRACTOR.
CORRECTNESS AND COMPLETENESS SHALL REST WITH THE
OBTAINING CORRECT SHOP DRAWINGS. RESPONSIBILITY FOR
REVIEWING IS INTENDED ONLY AS AN AID TO THE CONTRACTOR IN
REPRODUCIBLES WILL BE REVIEWED FOR ANY INDIVIDUAL SUBMITTAL.
NO MORE THAN TWO SETS OF BLUELINE PRINTS AND ONE SET OF
ERRORS ARE FOUND DURING REVIEW.
SHOP DRAWINGS WILL BE RETURNED FOR RESUBMITTAL IF MAJOR
IN THE STATE IN WHICH THE PROJECT IS LOCATED.
SHALL BE SEALED BY A CIVIL OR STRUCTURAL ENGINEER REGISTERED
ALL ENGINEERING DESIGNS AND LAYOUTS PERFORMED BY OTHERS
DRAWINGS.
CONSTRUCTED IN ACCORDANCE WITH THE ORIGINAL CONTRACT
ENSURE THAT ITEMS OMITTED OR SHOWN INCORRECTLY ARE
CONTRACT DRAWINGS. IT IS THE CONTRACTOR'S RESPONSIBILITY TO
ARCHITECT ARE NOT TO BE CONSIDERED CHANGES TO THE ORIGINAL
NOT NOTED AS ALLOWED BY THE STRUCTURAL ENGINEER OR
DRAWINGS. ITEMS OMITTED OR SHOWN INCORRECTLY AND WHICH ARE
THE SHOP DRAWINGS DO NOT REPLACE THE ORIGINAL CONTRACT
TIME BEFORE OR AFTER SHOP DRAWING REVIEW.
ALLOW ANY CHANGES TO THE ORIGINAL CONTRACT DRAWINGS AT ANY
THE STRUCTURAL ENGINEER RESERVES THE RIGHT TO ALLOW OR NOT
NOTED ACCORDINGLY BY THE STRUCTURAL ENGINEER.
BE CONSIDERED ALLOWED AFTER THE ENGINEER'S REVIEW, UNLESS
ARE NOT CLOUDED OR FLAGGED BY SUBMITTING PARTIES, SHALL NOT
FABRICATOR. ANY CHANGES, SUBSTITUTIONS, OR DEVIATIONS WHICH
CONTRACT DRAWINGS SHALL BE CLOUDED BY THE MANUFACTURER OR
ANY CHANGES, SUBSTITUTIONS, OR DEVIATIONS FROM THE ORIGINAL
ARCHITECT.
WITH THE CONTRACT DOCUMENTS. VERIFY ALL DIMENSIONS WITH
CONTRACTOR SHALL CLOUD OR FLAG ALL ITEMS NOT IN ACCORDANCE
GENERAL CONTRACTOR WILL BE RETURNED WITHOUT REVIEW. THE
DRAWINGS OR PRODUCT DATA NOT REVIEWED AND STAMPED BY THE
CONSTRUCTION DOCUMENTS PRIOR TO SUBMITTAL. ANY SHOP
DRAWINGS AND PRODUCT DATA FOR CONFORMANCE WITH THE
THE GENERAL CONTRACTOR SHALL REVIEW AND STAMP ALL SHOP
10.
9.
8.
7.
6.
5.
4.
3.
1.
DEFERRED SUBMITTALS:
SHOP DRAWINGS, SUBMITTALS AND
2.
SS2
6.
7.
ARE SHOWN ON DRAWINGS.
SAFE INSTALLATION OF THE TRUSS SYSTEM. TRUSS CONFIGURATIONS
ANCHORS, AND ALL OTHER ITEMS REQUIRED FOR A COMPLETE AND
PERMANENT BRACING AND BRIDGING, CONNECTIONS, HOLDOWN
FRAMING FOR OPENINGS NOT SHOWN ON DRAWINGS, TEMPORARY AND
PROCEDURES FOR ALL TRUSSES, BLOCKING, INCIDENTAL FRAMING,
FOR THE COMPLETE DESIGN, FABRICATION AND ERECTION
REQUIREMENTS. THE TRUSS MANUFACTURER SHALL BE RESPONSIBLE
SEE "DESIGN LOADS", PLANS AND DETAILS FOR TRUSS LOADING
BEARING OR CONNECTION DETAILS AND ERECTION DRAWINGS.
STRESS DIAGRAMS, TRUSS TO TRUSS CONNECTIONS, SPECIAL
BUT NOT BE LIMITED TO DESIGN LOADS, ALLOWABLE STRESSES,
MANUFACTURE. CALCULATIONS AND SHOP DRAWINGS SHALL INCLUDE
REGISTERED IN THE STATE OF TEXAS FOR REVIEW PRIOR TO
AND SHOP DRAWINGS SEALED BY A CIVIL OR STRUCTURAL ENGINEER
THE DRAWINGS. CONTRACTOR SHALL SUBMIT DESIGN CALCULATIONS
SUPERIMPOSED DEAD, LIVE, UPLIFT AND LATERAL LOADS SHOWN ON
INCLUDING ALL ADDENDUMS, TO SUPPORT THEIR OWN WEIGHT PLUS
FABRICATED IN ACCORDANCE WITH AISI SG-671 AND RG-9518
PREFABRICATED STEEL TRUSSES SHALL BE DESIGNED AND
CAMBERED FOR 1.0 TIMES THE DESIGN DEAD LOAD.
SPAN/240 AT CANTILEVER MEMBERS. ALL TRUSSES SHALL BE
SHALL BE LIMITED TO SPAN/240 AT SIMPLE SPAN MEMBERS AND 2X
SPAN/360 AT CANTILEVER MEMBERS. TOTAL LOAD DEFLECTIONS
SHALL BE LIMITED TO SPAN/360 AT SIMPLE SPAN MEMBERS AND 2X
MINIMUM G60 COATING, AND ASTM 500. LIVE LOAD DEFLECTIONS
THE MEMBERS OF THE TRUSS SHALL CONFORM TO ASTM 653,
TRUSSES AND WIND UPLIFT CONDITIONS.
SPECIAL BRACING MAY BE REQUIRED FOR MULTIPLE OR CANTILEVER
FOR CONSTRUCTION BRACING OF COLD-FORMED STEEL TRUSSES).
STEEL ENGINEERS ASSOCIATION) AND LGSEA 551d (DESIGN GUIDE
INSTALLATION GUIDE FOR COLD-FORM STEEL TRUSSES; LIGHT GAUGE
MANUFACTURER IN ACCORDANCE WITH AISI LGSEA (FIELD
BRACING AND BRIDGING SIZES AND SPACING BY TRUSS
TO SUPPORT MECHANICAL EQUIPMENT, PIPING, DUCTS, ETC.
ADDITIONAL TRUSSES SHALL BE DESIGNED AND SUPPLIED AS REQUIRED
BE PERMITTED.
TWICE THE CALCULATED LOAD. NO OFFSETS FOR CONNECTIONS WILL
CURRENT ICC APPROVAL AND SHALL BE DESIGNED AND SIZED FOR
ALL CONNECTORS SPECIFIED BY THE MANUFACTURER SHALL HAVE
IN THE STATE AND SUBMITTED FOR REVIEW PRIOR TO CONSTRUCTION.
SHALL BE SEALED BY A CIVIL OR STRUCTURAL ENGINEER REGISTERED
MANUFACTURER. CALCULATIONS AND DETAILS FOR CONNECTIONS
CONNECTIONS ARE THE DESIGN RESPONSIBILITY OF THE TRUSS
TO GIRDER TRUSS; HIP GIRDER AND GIRDER TO COLUMNS/BEAMS
ALL TRUSS TO TRUSS; TRUSS TO HIP TRUSS; TRUSS AND HIP TRUSS
STEEL TRUSSES:
PREFABRICATED COLD-FORMED
ACCORDANCE WITH HIS CALCULATIONS.
PERSONALLY INSPECTED THE TRUSSES AND THAT THEY WERE BUILT IN
SHALL CERTIFY IN WRITING, PRIOR TO ERECTION, THAT HE HAS
THE ENGINEER WHO DESIGNED THE PREFABRICATED STEEL TRUSSES 8.
7.
5.
2.
1.
6.
4.
3.
7.
15.
8.
9.
10.
12.
13.
14.
GALVANIZE COATING.
LIGHT GAGE STEEL FRAMING WORK. TOUCH UP ALL WELDS WITH
ALL WELDING SHALL BE PERFORMED BY WELDERS EXPERIENCED IN
D1.1.
STUD WELDING INSPECTION AND TESTING SHALL CONFORM TO AWS
1015 OR 1020 WITH A MINIMUM TENSILE STRENGTH OF 60,000 PSI.
LOW CARBON STEEL, AND SHALL CONFORM TO ASTM A108, GRADES
ANCHOR STUDS OR APPROVED EQUAL MADE FROM COLD FINISHED
HEADED STUDS SHALL BE NELSON GRANULAR FLUX-FILLED HEADED
D1.1.
STUD WELDING INSPECTION AND TESTING SHALL CONFORM TO AWS
ROLLED STEEL WITH A MINIMUM TENSILE STRENGTH OF 70,000 PSI.
FLUX-FILLED REBAR STUDS OR APPROVED EQUAL LOW CARBON
DEFORMED BAR ANCHOR STUDS SHALL BE NELSON D2L GRANULAR
28 DAY COMPRESSIVE STRENGTH OF 5,000 PSI.
EQUAL NONMETALLIC SHRINKAGE-RESISTANT GROUT WITH MINIMUM
DRYPACK FOR BEARING PLATES SHALL BE FIVE STAR GROUT OR AN
CONCRETE, OR TO RECIEVE SPRAY-APPLIED FIREPROOFING.
PAINT FOR ALL STEEL SURFACES EXCEPT SURFACES ENCASED IN
PROVIDE FABRICATOR'S STANDARD RUST-INHIBITING PRIMER SHOP
SECTION 4.4.1.B.
PRACTICES FOR STEEL BUILDINGS AND BRIDGES", EXCLUDING
BUILDINGS AND BRIDGES", AND THE "CODE OF STANDARD
EDITION A.I.S.C. "SPECIFICATIONS FOR STRUCTURAL STEEL
STRUCTURAL STEEL SHALL BE NEW AND MEET THE 14TH
SPECIAL INSPECTIONS AS DEFINED IN THE CODE.
THIS PROJECT OR PROVIDE A QUALITY ASSURANCE PLAN AND
QUALITY CERTIFIED COMPANY FOR THE CATEGORY OF WORK IN
THE STRUCTURAL STEEL FABRICATOR SHALL BE AN AISC
APPROPRIATE.
ERECTION DRAWINGS SHALL SHOW A FIELD WELDS, AS
TURN-OF-THE-NUT METHOD UNLESS NOTED OTHERWISE.
AND WASHERS AS REQUIRED. BOLTS TO BE INSTALLED WITH
STANDARD AISC FRAMING CONNECTIONS WITH A325-N BOLTS
ALL STRUCTURAL STEEL FIELD CONNECTIONS SHALL HAVE
STAINLESS STEEL
C. AWS D1.6 - STRUCTURAL WELDING CODE -
STEEL
B. AWS D1.3 - STRUCTURAL WELDING CODE - SHEET
A. AWS D1.1 - STRUCTURAL WELDING CODE - STEEL
WELDER:
AWS STANDARDS AND BE COMPLETED BY AN AWS CERTIFIED
WELDING SHALL CONFORM TO THE CURRENT AND APPLICABLE
SURFACE.
EFFECTIVE THROAT WIDTH IF GAPS EXIST AT THE FAYING
WELD SIZES SHALL BE INCREASED TO MEET THE REQUIRED
16.
15.
18.
17.
14.
SCREWS @ 12" O.C. MAX, UNO.
WHERE BACK-TO-BACK STUD COLUMNS ARE USED, ATTACH WITH #10
OF 3/4".
EDGE DISTANCES OF 1/2" AND MINIMUM SPACING BETWEEN SCREWS
SCREWS IN LIGHT GAUGE FRAMING SHALL BE INSTALLED WITH MINIMUM
FABRICATED HOLES.
FOR ELECTRICAL OR MECHANICAL EQUIPMENT: USE EXISTING
DO NOT NOTCH, DRILL OR CUT ANY HOLES IN LOAD BEARING STUDS
PERMITTED.
NOTCHES OR SPLICES IN ANY STRUCTURAL STUDS WILL NOT BE
HELD POSITIVELY IN PLACE UNTIL PROPERLY FASTENED.
ATTACHMENTS TO PERPENDICULAR MEMBER. MEMBERS SHALL BE
ALL FRAMING COMPONENTS SHALL BE CUT SQUARELY FOR
MANUFACTURER REQUIREMENTS AND SPECIFICATIONS.
DECK INSTITUTE (SDI). ALL METAL DECK TO BE ERECTED PER
STEEL DECK MANUFACTURER SHALL BE A MEMBER OF THE STEEL
WITH THE STEEL DECK INSTITUTE.
DECK PROPERTIES AND ATTACHMENTS SHALL BE IN ACCORDANCE
CONTRACTOR TO SUBMIT ALTERNATIVES FOR APPROVAL.
OR FURNISH THICKER GAGE DECK TO SUPPORT ALL APPLICABLE LOADS.
TWO SPAN CONDITIONS CONTRACTOR SHALL PROVIDE SHORING AS REQUIRED
MINIMUM AND SHALL BEAR 2” MINIMUM ON STEEL SUPPORTS. FOR ONE OR
ALL METAL DECK HAS BEEN DESIGNED TO BE CONTINUOUS OVER 3 SPANS
DO NOT SHORE DECK, UNLESS NOTED OTHERWISE ON DRAWINGS.
COLUMNS AS REQUIRED TO SUPPORT METAL DECK.
STRUCTURAL DRAWINGS. PROVIDE BEARING ANGLES WELDED TO
PROPERLY FINISHED JOB, EVEN IF NOT SPECIFICALLY SHOWN ON THE
STRIPS, SUMP PANS, AND OTHER ACCESSORIES AS REQUIRED FOR A
PROVIDE REINFORCING CHANNELS, STANDARD CLOSURES, CANT
LARGER THAN 12” (ROUND OR SQUARE) REQUIRE A STEEL FRAME.
ONE HOLE PER DECK SHEET REQUIRES REINFORCING PER SDI. HOLES
PERMISSIBLE. HOLES LARGER THAN 6” IN DIAMETER OR MORE THAN
ONE OPENING PER DECK SHEET, 6” OR LESS IN DIAMETER, IS
AND FIELD WELD. TYPICAL UNLESS NOTED OTHERWISE.
EXTEND ANGLES TO STRUCTURAL SUPPORTS, BLOCK VERTICAL LEGS
OPENINGS IN ROOF DECK TO BE FRAMED WITH L4x4x1/4” ANGLE.
BY THE METAL ROOF DECK.
FIXTURES AND DUCTS OR OTHER UTILITIES SHALL NOT BE SUPPORTED
COLD-FORMED METAL FRAMING, SUSPENDED CEILINGS, LIGHT
INSTALLED WITH STEEL WASHERS AND TIGHTENED NUTS.
BOLTS, ANCHOR BOLTS, EXPANSION BOLTS, ETC., SHALL BE
REVIEW PRIOR TO FABRICATION.
LOCATIONS, AND WELDING PROCEDURES ON SHOP DRAWINGS FOR
BE FULL PENETRATION WELDED AND TESTED. INDICATE ALL SPLICE
SUBJECT TO REVIEW TO THE STRUCTURAL ENGINEER. SPLICES SHALL
IF IT IS NECESSARY TO SPLICE ANY MEMBER, SPLICE LOCATIONS ARE
10.
WELD 3/16".
WELDED CONNECTIONS: E70XX ELECTRODES, MINIMUM SIZE FILLET
11.
PLATES AND STIFFENER PLATES SHALL BE WELDED ALL AROUND.
EACH SIDE, UNLESS OTHERWISE NOTED. COLUMN BASE PLATES, CAP
3/16 INCH FILLET STITCH WELDS AT 12 INCHES O.C. STAGGERED
CONTINUOUS MEMBER SHALL BE A MINIMUM OF 2 INCHES OF
SIZE FILLET ALL AROUND IN ACCORDANCE WITH AISC. WELDING OF
ALL MISCELLANEOUS WELDS (FIELD OR SHOP) SHALL BE MINIMUM
29.
30.
33.
21.
BEARING CONNECTIONS FOR ALL BOLTED CONNECTIONS.
DIAMETER. OTHER BOLTS SHALL BE 3/4" DIAMETER. USE SNUG TIGHT
A490 BOLTS". BOLTS THROUGH 4" WIDE BEAM FLANGES SHALL BE 5/8"
AISC "SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR
BOLTED CONNECTIONS: BEARING TYPE A325-N IN ACCORDANCE WITH17.
18.
UNLESS SPECIFIED, TO BE IN ACCORDANCE WITH AISC.
INDICATION THAT BOLTS MAY BE USED. ACTUAL NUMBER,
BOLTS SHOWN IN SECTIONS AND DETAILS ARE A SCHEMATIC
19.
REGISTERED IN THE STATE WHERE THE PROJECT IS LOCATED.
DIRECT SUPERVISION OF A PROFESSIONAL ENGINEER
CONTRACTOR'S CONNECTION DESIGN SHALL BE UNDER THE
BY THE CONTRACTOR TO RESIST FORCES INDICATED. THE
DETAILED ON THE STRUCTURAL DRAWINGS SHALL BE DESIGNED
ALL STRUCTURAL STEEL CONNECTIONS NOT SPECIFICALLY
20.
UNCHECKED AS AN INCOMPLETE SUBMITTAL.
CALCULATIONS HAVE NOT BEEN RECEIVED WILL BE RETURNED
SHOP DRAWINGS CONTAINING CONNECTIONS FOR WHICH
REGISTERED IN THE STATE WHERE THE PROJECT IS LOCATED.
SHALL BEAR THE SEAL OF A PROFESSIONAL ENGINEER
THE ARCHITECT AND STRUCTURAL ENGINEER. CALCULATIONS
THE CONTRACTOR SHALL BE SUBMITTED FOR THE FILES OF
DESIGN CALCULATIONS FOR THE CONNECTIONS DESIGNED BY
C. CONNECTION CAPACITY.
B. CALCULATION PAGE NUMBER.
A. DESIGN REACTION.
CONNECTION ON THE SUBMITTAL DRAWINGS AS FOLLOWS:
CONNECTION INFORMATION SHALL BE SHOWN AT EACH DETAILED
22.
AISC CAPACITY INCREASED BY 35%.
CONNECTIONS FOR COMPOSITE BEAMS SHALL HAVE THE STANDARD
FACTOR OF 1.2 FOR GIVEN SHAPE, SPAN, AND GRADE OF STEEL.
THE MAXIMUM TOTAL UNIFORM LOAD TABLE MULTIPLIED BY A
EQUAL TO ONE-HALF THE TOTAL UNIFORM LOAD CAPACITY FROM
THE CONNECTIONS SHALL BE DESIGNED TO SUPPORT A REACTION
DESIGN FORCES ARE NOT SHOWN ON THE STRUCTURAL DRAWINGS,
UNLESS NOTED OTHERWISE. WHERE BEAM REACTIONS AND/OR
ALL BEAM CONNECTIONS SHALL BE "SIMPLE SHEAR CONNECTIONS",
23.
24.
25.
26.
27.
28.
MEMBERS FRAMING INTO THE BEAM.
BEAM END AND THE VERTICAL COMPONENTS OF FORCES IN BRACE
OF MEMBERS SUPPORTED BY THE BEAM WITHIN THREE FEET OF
TO THE REACTION LISTED ABOVE, ADD ANY LOADS OR REACTIONS
THE CONNECTION.
SHALL BE TAKEN INTO ACCOUNT WHEN DESIGNING AND DETAILING
CONNECTIONS ARE SUBJECT TO ECCENTRICITY, SUCH ECCENTRICITY
CONNECTIONS SHALL DEVELOP THE REACTIONS SHOWN. WHERE
WHERE BEAM REACTIONS ARE SHOWN ON THE DRAWINGS, THE
COLUMNS.
COLUMN WEB, FLANGES OR CENTER LINE OF TUBES AND PIPE
EQUAL TO BEAM FLANGE THICKNESS, LOCATED IN ALIGNMENT WITH
WEB STIFFENER PLATES EACH SIDE OF BEAM WEB, OF THICKNESS
WHERE STEEL BEAMS ARE CONTINUOUS OVER COLUMNS, PROVIDE
SAGGING.
FABRICATE BRACING MEMBERS WITH SUFFICIENT DRAW TO PREVENT
STEEL BEAMS SHALL BE FABRICATED WITH MILL CAMBER UP
COORDINATE STEEL COATINGS ACCORDINGLY.
SEE ARCHITECTURAL PLANS FOR FIREPROOFING REQUIREMENTS AND
INDICATED IN DETAILS.
GRADE 36 OR GRADE 55 ANCHOR AND HEAVY HEX NUT, AS
SYSTEM SHALL BE USED. 10. HEADED ANCHOR RODS: ASTM F1554
A COLUMN BASE PLATE IS LESS THAN ¼", A PRESSURE INJECTION
HAVE TWO 1" DIAMETER GROUT HOLES. IF THE SPACE UNDER
ALL BASE PLATE WITH A DIMENSION GREATER THAN 24"SHALL
100 PERCENT OF VOID UNDER ALL BASE PLATE IS TO BE GROUTED.
STRENGTH OF 6000 PSI AT 28 DAYS CONFORMING TO ASTM C 1107.
NON-METALLIC NON-SHRINK WITH A MINIMUM COMPRESSIVE
GROUT WHERE INDICATED ON PLANS AT BASE PLATES SHALL BE
BEAM SPAN.
CONCRETE SHOULD BE PLACED IN EQUAL DEPTH OVER THE ENTIRE
CAMBERED TO ACCOUNT FOR WET CONCRETE DEFLECTIONS.
CONTRACTOR IS HEREBY ALERTED THAT THE BEAMS HAVE BEEN
DEFLECT FROM THE WEIGHT OF THE WET CONCRETE. THE
SHORING DURING CONSTRUCTION. HOWEVER, THE STEEL BEAMS WILL
ACCORDANCE WITH AISC PROVISIONS NOT TO REQUIRE TEMPORARY
ALL STEEL FLOOR CONSTRUCTION HAS BEEN DESIGNED IN
FOR STEEL ERECTION.
COMPLY TO OSHA 29 CFR 1926 SUBPART R, SAFETY STANDARDS
THE GENERAL CONTRACTOR AND HIS SUBCONTRACTORS SHALL
AND THE "STEEL STUD MANUFACTURERS ASSOCIATION".
STRUCTURAL MEMBERS" BY THE AMERICAN IRON AND STEEL INSTITUTE
"SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL
ERECTED IN ACCORDANCE WITH THE LATEST EDITION OF THE
ALL COLD-FORMED STEEL FRAMING SHALL BE FABRICATED AND
FRAMING:STUD
COLD-FORMED STEEL
1.
3.
4.
15.
31.
ZINC RICH PAINT.
FIELD WELDS SHALL BE GROUND SMOOTH AND TOUCHED UP WITH
CLASS OF G60 AND SHALL BE APPLIED AFTER FABRICATION. ALL
THE REQUIREMENTS OF ASTM 123-73 WITH A MINIMUM COATING
SHALL BE HOT-DIPPED GALVANIZED. ZINC COATING SHALL MEET
ALL STRUCTURAL STEEL WHICH IS OUTSIDE THE BUILDING ENVELOPE
32.
CRACKING WHEN THE SHORES ARE REMOVED.
DURING CONSTRUCTION CAN RESULT IN HORIZONTAL BED JOINT
SUPPORT ANGLE DURING CONSTRUCTION. SHORING THE BRICK
IS INSTALLED. BRICK SHALL BE INSTALLED WITHOUT SHORING THE
THE BRICK VENEER WITH SOME NORMAL DEFLECTION AS THE BRICK
ALL BRICK SUPPORT ANGLES ARE DESIGNED TO FULLY SUPPORT
11.
12.
13.
14.
5.
8.
9.
16.
BE CUT TO INSURE A MINIMUM OF THREE SPANS PER DECK WIDTH.
FLUTES PERPENDICULAR TO STEEL FRAMING MEMBERS. DECK SHALL
STEEL DECK SHALL ALWAYS BE INSTALLED WITH DIRECTION OF
STRUCTURAL GENERAL NOTES
SCALE: NTS
SS2-STRUCTURAL NOTES.dgn
(UNO).
MIN. AND SIDELAP CONNECTIONS SHALL BE #10 TEK SCREWS MIN
DECK SHALL BE CONNECTED AT SUPPORTS WITH #12 TEK SCREWS
SEGMENTED RETAINING WALL
PREFABRICATED COLD-FORMED STEEL TRUSSES
DEFERRED SUBMITTALS SHALL INCLUDE THE FOLLOWING:
DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING OFFICIAL.
ITEMS SHALL NOT BE INSTALLED UNTIL THEIR DESIGN AND SUBMITTAL
CONFORMANCE WITH THE BUILDING DESIGN. DEFERRED SUBMITTAL
ENGINEER OF RECORD AND DETERMINED TO BE IN GENERAL
OF RECORD. DEFERRED SUBMITTALS SHALL BE REVIEWED BY THE
DRAWINGS BY A REGISTERED ENGINEER OTHER THAN THE ENGINEER
SPECIFICATIONS WHICH CONTAIN SEALED DESIGN CALCULATIONS AND
CONSTRUCTION AND REQUIRED BY THE STRUCTURAL NOTES OR
DEFERRED SUBMITTALS - SUBMITTALS THAT ARE SUBMITTED DURING
LABORATORY SERVICES.
LABRATORY. SEE SPECIFICATION SECTION 01 45 29 TESTING
SHALL BE TESTED AND CERTIFIED BY AN INDEPENDENT TESTING
SHALL BE SHOWN ON SHOP DRAWINGS. FULL PENTRATION WELDS
FIELD WELD AT THEIR DISCRETION. SHOP WELDS OR FIELD WELDS
ARE SHOWN AS SHOP WELDS. CONTRACTOR MAY SHOP WELD OR
AMERICAN WELDING SOCIETY STANDARDS. ALL WELDS ON DRAWINGS
WELDS SHOWN ON THE DRAWINGS OR NOTES. ALL WELDING PER
TESTING AGENCY AND HAVING CURRENT EXPERIENCE IN TYPE OF
BY WELDERS HOLDING VALID CERTIFICATES ISSUED BY AND ACCEPTED
FOR ASTM A706 REINFORCING BARS. ALL WELDING SHALL BE DONE
AWS D1.1, GRADE E70XX. E80 SERIES ELECTRODES SHALL BE USED
E80 SERIES ELECTRODES SHALL ELECTRODES SHALL CONFORM TO
WELDING ELECTRODES SHALL CONFORM TO AWS D1.1, GRADE E70XX.
AND PRODUCT DATA)
9) COLD-FORMED METAL TRUSSES (DRAWINGS, CALCULATIONS
DATA)
8) COLD-FORMED METAL FRAMING (DRAWINGS AND PRODUCT
ENGINEER.
APPROVED MIX DESIGNS WITHOUT APPROVAL FROM THE STRUCTURAL
AS SHOP DRAWINGS. THE CONTRACTOR SHALL NOT VARY FROM THE
CONSTRUCTION DOCUMENTS SHALL NOT BE REPRODUCED FOR USE
7) STRUCTURAL STEEL (DRAWINGS AND PRODUCT DATA)
6) MASONRY REINFORCING (DRAWINGS AND PRODUCT DATA)
5) MASONRY PRODUCT DATA AND MATERIAL TEST REPORTS
4) GROUT AND MORTAR MIX DESIGN
3) FOUNDATION REINFORCING (DRAWINGS AND PRODUCT DATA)
2) CONCRETE PRODUCT DATA AND MATERIAL TEST REPORTS
1) CONCRETE MIX DESIGN
(LISTED BELOW).
REQUIRED BY THE SPECIFICATIONS AND DEFERRED SUBMITTALS
FOLLOWING STRUCTURAL ITEMS IN ADDITION TO ANY SUBMITTALS
SUBMITTALS AND SHOP DRAWINGS SHALL BE SUBMITTED FOR THE
o n e q u a r t e r in n e f o o t o n e e ig h t h in n e f o o t t h r e e q u a r t e r s in n e f o o t t h r e e e ig h t h s in n e f o o t o n e h a lf in n e f o o t o n e in n e f o o t o n e a n d o n e h a lf in n e f o o t t h r e e in c h n e f o o t 6
H2B, INC.
713.864.2900
HOUSTON, TX 77008
1225 N Loop W, Suite 800
Texas Firm Registration No. 8856
S
P r o j e c t s
S p s ig n r
II
D G
N
S S S
T R
U C
T U
R
T E
S .d g n
:5
:2
SBBL PROJECT NO:
V.A. PROJECT NO:
ARCHITECT OF RECORD:
CAD FILE #
Approved: VA Area Proj. Mgr.
15032
519-369
Revision
DATE:
Date
DRAWN BY: ZAF
Revision
DATE:
Date Revision
DATE:
Date Revision
DATE:
Date
Approved: Med. Ctr. Director
Approved: Associate Director
Approved: Chief of Engineering
Approved: Projects Supervisor
C O
N S
T R
U C
T N
E W C
L C P
H A
S E
C A
R E S
Y S
T E
M
B
IG
S
P R
IN
G T E
X A
S
W E
S T T
E X
A S V
A H
E A
L and Facilities
Construction
Office of
SHEET OF
BID DOCUMENTS
FULLY SPRINKLERED
CONSULTANTS:
CHECKED BY: CCM
SYMBOLS
MARKED "TYPICAL" MAY OR MAY NOT BE CUT ON PLANS.
TYPICAL DETAIL - SEE S100 SERIES SHEETS DETAILS
FRAMING DETAIL CUT SHOWN ON PLAN
PLAN NOTE
OPENING IN FLOOR OR ROOF
SHEAR WALL HOLDOWN
TOF
TOB
BOB
TOP
TOW
WF 1-6
C 4-4
W1
J1
B1
L1
ML1
SW1
PLAN ABBREVIATIONS
REFERENCED FROM F.F.E. = 100'-0"TOP OF FOOTING
TOP OF BEAM
BOTTOM OF BEAM
TOP OF PARAPET
TOP OF WALL
WALL FOOTING DESIGNATION
COLUMN DESIGNATION
WALL REINFORCING DESIGNATION
SHEAR WALL DESIGNATION
JOIST DESIGNATION
BEAM DESIGNATION
LEDGER DESIGNATION
MASONRY LINTEL DESIGNATION
MATERIAL
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
8" MASONRY WALL U.N.O.
8" CAST-IN-PLACE CONCRETE WALL U.N.O.
6" STEEL STUD WALL U.N.O.
6" STEEL STUD SHEAR WALL U.N.O.
F 3-3 FOOTING DESIGNATION
FOUNDATION DETAIL CUT SHOWN ON PLAN
REFERENCED FROM F.F.E. = 100'-0"
REFERENCED FROM F.F.E. = 100'-0"
REFERENCED FROM F.F.E. = 100'-0"
REFERENCED FROM F.F.E. = 100'-0"
TOL TOP OF LEDGER REFERENCED FROM F.F.E. = 100'-0"
SS3
TO SUPPORT MECHANICAL EQUIPMENT, PIPING, DUCTS, ETC.
ADDITIONAL TRUSSES SHALL BE DESIGNED AND SUPPLIED AS REQUIRED
WORKMANSHIP PROVISIONS OF THE CODE.
WITH THE APPROVED PLANS AND SPECIFICATIONS, AND THE APPLICABLE
BEST OF THE INSPECTOR'S KNOWLEDGE, THE WORK IS IN CONFORMANCE
SHALL COMPLETE AND SIGN A FINAL REPORT CERTIFYING THAT TO THE
UPON COMPLETION OF THE ASSIGNED WORK, THE SPECIAL INSPECTOR
OR ARCHITECT OF RECORD AND THE BUILDING OFFICIAL.
CONTRACTOR FOR CORRECTION, THEN, IF UNCORRECTED, TO THE ENGINEER
DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE
BUILDING OFFICIAL AND TO THE ENGINEER OR ARCHITECT OF RECORD. ALL
THE SPECIAL INSPECTOR SHALL FURNISH INSPECTION REPORTS TO THE
CONFORMANCE WITH THE APPROVED DESIGN DRAWINGS AND SPECIFICATIONS.
THE SPECIAL INSPECTOR SHALL OBSERVE THE WORK ASSIGNED FOR
DUTIES AND RESPONSIBILITIES OF THE SPECIAL INSPECTOR:
B.
C.
4.
A.
PLACING OF UNITS SHALL BE PERFORMED ON A PERIODIC BASIS.
PLACEMENT OF ALL GROUT (CONTINUOUS). SPECIAL INSPECTION FOR
IMMEDIATELY PRIOR TO CLOSING OF CLEANOUTS (PERIODIC) AND DURING
ASSOCIATED FOOTINGS (PERIODIC), INSPECTION OF GROUT SPACE
STRUCTURAL MASONRY: PLACEMENT OF REINFORCING STEEL IN WALLS AND
OPERATIONS PER IBC CHAPTER 17:
SPECIAL INSPECTION IS REQUIRED DURING THE FOLLOWING
ANY WORK FOR WHICH SPECIAL INSPECTION OR TESTING IS REQUIRED.
NOTICE TO THE SPECIAL INSPECTOR AND THE TESTING LABORATORY PRIOR TO BEGINNING
THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A MINIMUM OF 24 HOURS
1.
3.
2.
D.
IN THE SHOP OF A BUILDING OFFICIAL/APPROVED FABRICATOR - PERIODIC.
(INCLUDING WELDING OF REINFORCING STEEL), EXCEPT WELDING PERFORMED
WELDING: DURING ALL STRUCTURAL FIELD WELDING AND SHOP WELDING
GEOTECHNICAL REPORT SHALL PROVIDE THESE INSPECTIONS.
FILL. NOTE: THE GEOTECHNICAL ENGINEER WHO PERFORMED THE
REQUIREMENTS OF IBC CHAPTER 18, INCLUDING PLACEMENT OF ENGINEERED
EARTHWORK EXCAVATIONS, GRADING AND FILLING AS REQUIRED TO SATISFY
BY GEOTECHNICAL ENGINEER - GRADING, EXCAVATION AND FILLING: DURING A.
C.
SPECIAL INSPECTIONS:
EMBEDMENT REQUIREMENTS HAVE BEEN MET - CONTINUOUS.
BARS OR ALL THREAD RODS TO ENSURE THAT INSTALLATION AND
EPOXY INSTALLATIONS: DURING INSTALLATION OF ALL REINFORCING
INSTALLATION AND EMBEDMENT REQUIREMENTS HAVE BEEN MET - CONTINUOUS.
MECHANICAL ANCHORS: REVIEW INSTALLATION OF ANCHORS TO ENSURE THAT
E.
F.
DURING BOLT INSTALLATIONS AND TIGHTENING OPERATIONS - PERIODIC.
PLIES OF THE CONNECTED ELEMENTS HAVE BEEN BROUGHT INTO SNUG CONTACT AND
HIGH STRENGTH BOLTING: REVIEW OF ALL BOLT INSTALLATIONS TO ENSURE THAT THE B.
SHEAR WALLS; DRAG STRUTS; BRACES; AND HOLD DOWNS - PERIODIC.
WITHIN THE LATERAL FORCE RESISTING SYSTEM, INCLUDING DIAPHRAGMS;
ATTACHMENTS; BOLTING; ANCHORING AND OTHER FASTENING COMPONENTS
LATERAL FORCE RESISTING SYSTEM: REVIEW EDGE AND BOUNDARY G.
END HOOK DIMENSIONS
#3
#4
#5
#6
#7
#8
#9
#10
#11
#14
#18
FINISHED
BEND
DIAMETER D,
(INCHES)
180 ° HOOKS
A OR G'
(INCHES)
A OR G'
(INCHES)J, (INCHES)
2 ¼
4 ½
5 ¼
9 ½
18 ¼
13 ¼
28 ½
90° HOOK
D= INSIDE DIAMETER OF BEND
MINIMUM
STIRRUP AND TIE HOOK
#3
#4
#5
BAR
SIZE
1½
2½
D= INSIDE DIAMETER OF BEND
D
(INCHES)
90° HOOK
A OR G
(INCHES)
135° HOOK
A OR G
(INCHES)
DEVELOPMENT AND LAP SPLICE SCHEDULE
F'c = 3000 psi F'c = 4000 psi
EMBEDMENT LAP SPLICE EMBEDMENT LAP SPLICE
HOOKCOMPRCOMPRHOOKCOMPRCOMPR
(LCE)BAR TOP OTHER (LCS) TOP OTHER (LDH) (LCE) TOP OTHER (LCS) TOP OTHER (LDH)
11342
31 24
78 60
100131
16218
11 28
16 43
22 71
28 90
10031#11
#10
#9
#8
#7
#6
#5
#4
#3
NOTES (PERTAINING TO TABLE):
1. TOP BARS ARE HORIZONTAL BARS THAT HAVE MORE THAN 12" OF
FRESH CONCRETE CAST BELOW THEM.
2. ALL BARS THAT ARE NOT "TOP BARS" ARE "OTHER" BARS
3. ABBREVIATIONS:
- LCE - COMPRESSION EMBEDMENT LENGTH
- LTE - TENSION EMBEDMENT LENGTH
- LCS - COMPRESSION LAP SPLICE LENGTH
- LTS - TENSION LAP SPLICE LENGTH
- LDH - HOOKED BAR TENSION EMBEDMENT LENGTH
1.3 -- IF EPOXY COATED REBAR USED
1.3 -- IF CONC CONTAINS LIGHT WEIGHT AGGREGATES
MULTIPLE MULTIPLIERS IF APPLICABLE.
INCREASED AS REQD BY THE MULTIPLIERS BELOW. APPLY
MULTIPLIERS:
ALL EMBEDMENT AND LAP SPLICE LENGTHS SHALL BE
VERTICAL.
4. ALL SPLICES SHALL BE WIRED IN CONTACT STACKED
SPLICED
3. BARS GREATER THAN #11 SHALL BE MECHANICALLY
2. ALL DIMENSIONS INDICATED IN TABLE ARE IN INCHES
1. STAGGER ALL SPLICES 12 db MIN, BUT NOT LESS THAN 12"
NOTES (GENERAL):
TYPICAL SPLICE & DEVELOPMENT SCHEDULE
TYPICAL DETAIL
SIZE
BAR
90° HOOK 180° HOOK
GROSS TIE
CORNER CONDITIONS-STIRRUP OR TIE
4½
5½
4½
TYPICAL SPLICE & DEVELOPMENT SCHEDULE2
TYPICAL END HOOK DETAILS
90° HOOK
90° HOOK
BEYOND 90° HOOK
BEYOND
135° HOOK 135° HOOK
135° HOOK
90° HOOK
135° HOOK
90° HOOK
135° HOOK
DETAILING DIMENSION
d b
HOOKDETAILING
4 db OR1 d b
R
G
J d b
" 2
A OR GDIMENSION
6db FOR #3, #4, #5 12db FOR #6, #7, #8
D
D db
A OR G
D E
T A
IL
IN
IM
E N
S
IO
N
A N
D
S
M A L L E R d b
F O R
B
A R S
H O
K db
D
D E
T A
IL
E N
S
IO
HOUSEKEEPING PAD DETAIL
NOTES
PROVIDE ADDITIONAL LAYER OF REINFORCING FOR PAD THICKNESS GREATER THAN 18".3.
ON STRUCTURAL DRAWING OR NOT.
WITH EQUIPMENT MANUFACTURERS AND PROVIDE WHERE REQUIRED WHETHER SHOWN
CONTRACTOR SHALL COORDINATE DIMENSIONS AND OTHER SPECIAL REQUIREMENTS 2.
PLAN DIMENSIONS AND THICKNESS (4" MINIMUM THICKNESS).
REFER TO ARCHITECTURAL, STRUCTURAL, OR MEP DRAWING FOR HOUSEKEEPING PAD
1.
12" < T < = 16"
8" < T < = 12"
6" < T < = 8"
4"< T< = 6"
T-4" WWR 4x4-W2.9xW2.9 OR #3@12" EACH WAY
REINFORCEMENT
TOP
PAD THICKNESS
BOTTOM
REINFORCEMENT
NONE
NONE
NONE
#4@18" EACH WAY
#4@12" EACH WAY #4@12" EACH WAY
#4@18" EACH WAY
WWR 4x4-W6xW6 OR #4@12" EACH WAY
WWR 4x4-W4xW4 OR #4@18" EACH WAY
HOUSEKEEPING PAD REINFORCEMENT SCHEDULE
CORNERS
RE-ENTRANT
CORNERS
EXTERIOR
" 2'-0" 4
" CHAMFER, TYPICAL4
BOTTOM REINFORCEMENT,
WHERE SCHEDULED
REFER TO SCHEDULE
TOP REINFORCEMENT,
RE-ENTRANT CORNERS
AND (1) - #4X4'-0" DIAGONAL AT
AT EXTERIOR CORNERS
PERIMETER WITH (1) - #4X4'-0"
(1) - #4 CONTINUOUS AT
REFERENCE NOTE 1
TENSION(LTE) TENSION(LTS) TENSION(LTE) TENSION(LTS)
STRUCTURAL GENERAL NOTES
SCALE: NTS
SS3-STRUCTURAL NOTES.dgn
45 29 TESTING LABORATORY SERVICES.
AS APPROVED BY THE COTR AND STRUCTURAL ENGINEER. SEE SPECIFICATION SECTION 01
SPECIAL INSPECTIONS SHALL BE PERFORMED BY H2B, INC. OR A QUALIFIED INSPECTOR
o n e q u a r t e r in n e f o o t o n e e ig h t h in n e f o o t t h r e e q u a r t e r s in n e f o o t t h r e e e ig h t h s in n e f o o t o n e h a lf in n e f o o t o n e in n e f o o t o n e a n d o n e h a lf in n e f o o t t h r e e in c h n e f o o t 6
H2B, INC.
713.864.2900
HOUSTON, TX 77008
1225 N Loop W, Suite 800
Texas Firm Registration No. 8856
S
P r o j e c t s
S p s ig n r
II
D G
N
S S S
T R
U C
T U
R
T E
S .d g n
:5
:3
SBBL PROJECT NO:
V.A. PROJECT NO:
ARCHITECT OF RECORD:
CAD FILE #
Approved: VA Area Proj. Mgr.
15032
519-369
Revision
DATE:
Date
DRAWN BY: ZAF
Revision
DATE:
Date Revision
DATE:
Date Revision
DATE:
Date
Approved: Med. Ctr. Director
Approved: Associate Director
Approved: Chief of Engineering
Approved: Projects Supervisor
C O
N S
T R
U C
T N
E W C
L C P
H A
S E
C A
R E S
Y S
T E
M
B
IG
S
P R
IN
G T E
X A
S
W E
S T T
E X
A S V
A H
E A
L and Facilities
Construction
Office of
SHEET OF
BID DOCUMENTS
FULLY SPRINKLERED
CONSULTANTS:
CHECKED BY: CCM
REQUIRED. SEE TYPICAL STEPPED FOOTING DETAIL.
SHALL BE 30 DEGREES. STEP FOOTINGS AS
MAXIMUM SLOPE BETWEEN BOTTOMS OF FOOTINGS
NOTE:
FOOTING
CONCRETE
FOOTING
CONCRETE
TYPICAL DETAIL
MAXIMUM SLOPE
BETWEEN ADJACENT FOOTINGS
APPLICABLE CODES
EXCAVATIONS IN ACCORDANCE WITH ALL
PROVIDE FOR THE SAFETY OF ALL
SHORING AND BRACING NECESSARY TO
CONTRACTOR IS RESPONSIBLE FOR ALL
NOTE:
OR FOUNDATION.
BOTTOM OF FOOTING
TRENCH CLOSER THAN
DO NOT EXCAVATE A
NOTE:
FOOTING
CONCRETE
TRENCH
BOTTOM OF
TYPICAL DETAIL
TRENCH PARALLEL TO FOUNDATION
SECTION
X
X
FOOTING
CONCRETE WALL
ALL AROUND
SLEEVE BY 1/2"
PIPE TO CLEAR
SLEEVE
500 PSI)
(MINIMUM f'c =
CONCRETE FILL
COLUMN FOOTINGS.
PASS BELOW
NO PIPES SHALL
NOTE:
8"
M
IN
M
IN
8"
MIN
TYPICAL DETAIL
PIPE PASSING BELOW WALL FOOTING
ALL AROUND
SLEEVE BY 1/2"
PIPE TO CLEAR
#3 AT 12" O.C.
SLEEVE
SLEEVE NOT REQUIRED AT SLAB CONDITION.3.
DIMENSION "B" TO BE 6" MINIMUM.2.
DIMENSION "A" TO BE 2 1/2" MINIMUM.1.
NOTES:
MIN
6"
COMPACTED BASE
SOIL OR
FIRM UNDISTURBED
MIN
6"
A
B
TYPICAL DETAIL
MIN
1 1/2"
SLEEVE FOR PIPE
AT SLAB OR WALL FOOTING
WHERE NECESSARY
BEND AROUND CORNERS
CENTERED AT TRENCH -
FOOTING REINFORCING
(2) #5 X 8'-0" ADDITIONAL
DETAIL
TYPICAL TRENCH
SHORING - SEE
STEM WALL
FOOTING
CONCRETE WALL
STRUCTURAL NOTES
- SEE GENERAL
RECOMPACT TRENCH
BACKFILL AND
FOOTING
PLACEMENT OF
WRITING PRIOR TO
ENGINEER IN
NOTIFY STRUCTURAL
EXCEEDS 1'-6"
WHERE TRENCH
1'-6" MAXIMUM -
BOTTOM OF TRENCH
UTILITY
DUCT, OR OTHER
PIPE, CONDUIT,
C L
R3
STRENGTH TO RESIST EARTH PRESSURE.
CONTRACTOR SHALL VERIFY THAT BURIED UTILITIES HAVE ADEQUATE 2.
CONTINUOUS FOOTINGS OR THROUGH OR UNDER COLUMN FOOTINGS.
THROUGH/UNDER FOUNDATION DETAIL. NO UTILITY SHALL PASS THROUGH
FOR TRENCH DEPTH OF 3'-0" OR LESS, SEE TYPICAL UTILITY 1.
NOTES:
R E
TYPICAL DETAIL
UTILITY PASSING BELOW
WALL FOOTING IN TRENCH
TOP OF WALL FOOTING
"D" = 24" MAXIMUM
LAP PER STRUCTURAL NOTES
2"D" 2"D"
D
D
D
TYPICAL DETAIL
TYPICAL CONCRETE STEPPED FOOTING
INTERSECTIONCORNER
24"
SPACING AS HORIZONTAL REINFORCING X
CORNER BARS EACH SIDE SAME SIZE AND
TYPICAL DETAIL
CORNER REINFORCING IN
CONCRETE FOOTING AND STEM WALL
SLAB
CORNER IN CONCRETE
OR DEPRESSED SLAB
RE-ENTRANT CORNER
FROM TOP OF SLAB
LOCATED 1 1/2" CLEAR
#4 X 4'-0" LONG
EQUAL
E Q
U A
L
TYPICAL DETAIL
SLAB REINFORCING AT RE-ENTRANT
CORNERS AND DEPRESSED SLAB…