BID DOCUMENTS
FULLY SPRINKLERED
BID DOCUMENTS SUBMISSION
1. COORDINATE ALL PIPING WITH ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL,
PLUMBING, AND ELECTRICAL.
ROUTE ALL FIRE PROTECTION PIPING AS HIGH AS POSSIBLE AND COORDINATE WITH
ALL TRADES PRIOR TO FABRICATION OR INSTALLATION.
ALL SPRINKLER HEADS IN FINISHED CEILINGS SHALL BE CONCEALED TYPE.
ALL SPRINKLER HEADS IN EXPOSED AREAS SHALL BE UPRIGHT TYPE.
AREAS SHOWN SHADED SHALL BE DESIGNED FOR LIGHT HAZARD OCCUPANCY IN
ACCORDANCE WITH NFPA 13.
COVERED OUTDOOR AREAS SHOWN HATCHED SHALL BE PROTECTED USING
FREEZE PROTECTED GLYCOL FIRE SPRINKLER PIPING. AREAS SHALL BE DESIGNED
FOR GROUP 1 ORDINARY HAZARD OCCUPANCY IN ACCORDANCE WITH NFPA 13.
REFER TO CIVIL DRAWINGS FOR CONTINUATION.
24V ALARM BELL.
FIRE DEPARTMENT CONNECTION.
FIRE RISER. REFER TO DETAIL 1/26-FP2.0.
ROUTE GLYCOL PIPING WITHIN ENCLOSED ROOF ASSEMBLY.
INSTALL ANTI-FREEZE LOOP IN WALL. INSTALL 18X18 ACCESS DOOR AT 36 INCHES
AFF IN WALL. REFER TO DETAIL 5/26-FP2.0.
INSPECTOR'S TEST DISCHARGE VALVE ABOVE GYP BOARD CEILING. PROVIDE 18X18
ACCESS DOOR IN CEILING TO ALLOW SERVICE TO VALVE.
INSPECTOR'S TEST DISCHARGE.
BUILDING
N.I.C.
N.I.C.
N.I.C.
BUILDING
26-FP1.0
COTTAGE BLDG. 26 - FIRE
PROTECTION FLOOR PLAN
2.
3.
4.
5.
6.
1/4" = 1'-0"1
FIRE PROTECTION FLOOR PLAN-
COTTAGE BUILDING #26
26-FP1.0.dwg
SCALE: 1/4" = 1'-0"
NO SCALE
KEYPLAN
D
B
G
H E A
C
F
GF
GF
F
F 6"
GF
GF
GF
GF
GF
DATA
SUPPLIES/EQUIP.
STOR.
ELEC.
STORAGE
18A
MECHANICAL
STORAGE
11A
PANTRY
CORR.
RECEIVING/STORAGE
KITCHEN
DINING
ROOM
LIVING
ROOM
FOYER
STAFF
OFFICE
TOIL.
RESIDENT
ROOM
RESIDENT
ROOM
RESIDENT
ROOM
RESIDENT
ROOM
TOIL.
TOIL.
TOIL.
S O
IL
E
D
C
LE
A N
CORR.
GUEST
TOIL.
MEDS
SPA/BATH/SAFE
ROOM
TOIL.
RESIDENT
ROOM
RESIDENT
ROOM
RESIDENT
ROOM
RESIDENT
ROOM
TOIL.
TOIL.
S O
IL
E
D
C
LE
A N
CORR.
TOIL.
RESIDENT
ROOM
SOILED
UTIL.
RESIDENT
ROOM
CORR.
TOIL.
CORR.
H.A.C.
33 STORAGE
LA
U
N D
R Y
S
A
FE
R O
O M
STORAGE
19B
TOIL.
BID DOCUMENTS SUBMISSION
26-FP2.0
26-FP2.0.dwg
SCALE: 1/4" = 1'-0"
COTTAGE BLDG. 26 - FIRE
PROTECTION DETAILS AND
SCHEDULES
FIRE SPRINKLER LEGEND
SYMBOL DESCRIPTION
FIRE WATER LINE
GLYCOL SYSTEM PIPING
SIAMESE CONNECTION
ELBOW TURNED DOWN
ELBOW TURNED UP
PIPE CONTINUATION
ALARM BELL
F
GF
FIRE RISER ENTRANCE DETAIL
NO SCALE
SLEEVE
FROM MAIN
GRADE
EXTERIOR WALL
RODS
RODS
BUILDING FLOOR
SLEEVE
CAULK WITH MASTIC
WATERPROOF
CAST IRON ON
WELL AND
SPIGOT PIPE
CAST IRON FLANGE
AND SPIGOT PIECE
FIRE RISER UP IN
EQUIPMENT ROOM
BEARING AREA
POURED CONCRETE BLOCKS
BEARING AREA
THRUST BLOCK DETAIL
NO SCALE
UNDISTURBED
EARTH
BEARING AREA OF BLOCK IN SQ. FT. (2000 P.S.F. SOIL)
FITTING SIZES TEE & END 90° BEND 45° BEND
4" 2.0 2.0 2.0 6" 4.0 5.0 3.0 8" 6.0 8.0 5.0
10" 9.0 13.0 7.0
FINISH FLOOR
CEILING
1" 45 DEGREE ELBOW
BUILDING WALL
SYSTEM TEST CONNECTION DETAIL
NO SCALE
INSPECTOR'S SPRINKLER
BUSHING WITH 1/2"
SMOOTH BORE CORROSION
RESISTANT OUTLET
1" GLOBE VALVE
ABOVE CEILING
TO SPRINKLER SYSTEM
ALARM CHECK VALVE
MAIN (FLOW TEST LINE)
MAIN DRAIN VALVE
RISER FROM MAIN WATER SUPPLY
DRAW TO FLOOR DRAIN
TEE CONNECTION
FIRE DEPARTMENT CONNECTION
DESCRIPTION
ITEM
DOUBLE CHECK VALVE ASSEMBLY9
SPRINKLER RISER DETAIL
NO SCALE
WATER FLOW INDICATOR3
DR
OP
FT
. M
IN
WATER SUPPLY
BUTTERBALL INDICATING
VALVE ABOVE CEILING
FILLING
CUP
ACCESS DOOR
IN WALL
CHECK VALVE
DRAIN
VALVE
EXTEND DRAIN THROUGH
EXTERIOR WALL.
WATER
NO
N-
FR
EZ
ZI
NG
S
OL
UT
IO
N
ANTI-FREEZE LOOP DETAIL
NO SCALE 5
TO COVERED
OUTDOOR AREAS
8 7
BID DOCUMENTS SUBMISSION
1. COORDINATE ALL PIPING WITH ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL,
PLUMBING, AND ELECTRICAL.
ROUTE ALL FIRE PROTECTION PIPING AS HIGH AS POSSIBLE AND COORDINATE WITH
ALL TRADES PRIOR TO FABRICATION OR INSTALLATION.
ALL SPRINKLER HEADS IN FINISHED CEILINGS SHALL BE CONCEALED TYPE.
ALL SPRINKLER HEADS IN EXPOSED AREAS SHALL BE UPRIGHT TYPE.
AREAS SHOWN SHADED SHALL BE DESIGNED FOR LIGHT HAZARD OCCUPANCY IN
ACCORDANCE WITH NFPA 13.
COVERED OUTDOOR AREAS SHOWN HATCHED SHALL BE PROTECTED USING
FREEZE PROTECTED GLYCOL FIRE SPRINKLER PIPING. AREAS SHALL BE DESIGNED
FOR GROUP 1 ORDINARY HAZARD OCCUPANCY IN ACCORDANCE WITH NFPA 13.
REFER TO CIVIL DRAWINGS FOR CONTINUATION.
24V ALARM BELL.
FIRE DEPARTMENT CONNECTION.
FIRE RISER. REFER TO DETAIL 1/27-FP2.0.
ROUTE GLYCOL PIPING WITHIN ENCLOSED ROOF ASSEMBLY.
INSTALL ANTI-FREEZE LOOP IN WALL. INSTALL 18X18 ACCESS DOOR AT 36 INCHES
AFF IN WALL. REFER TO DETAIL 5/27-FP2.0.
INSPECTOR'S TEST DISCHARGE VALVE ABOVE GYP BOARD CEILING. PROVIDE 18X18
ACCESS DOOR IN CEILING TO ALLOW SERVICE TO VALVE.
INSPECTOR'S TEST DISCHARGE.
BUILDING
N.I.C.
N.I.C.
N.I.C.
BUILDING
27-FP1.0
2.
3.
4.
5.
6.
1/4" = 1'-0"1
FIRE PROTECTION FLOOR PLAN-
COTTAGE BUILDING #27
27-FP1.0.dwg
SCALE: 1/4" = 1'-0"
COTTAGE BLDG. 27 -
FIRE PROTECTION
FLOOR PLAN
NO SCALE
KEYPLAN
DB G HEA C F
GF
GF
F
F 6"
GF
GF
GF
GF
GF
4 1
DATA
SUPPLIES/EQUIP.
STOR. 18
ELEC.
STORAGE
18A
MECHANICAL
S
TO
R A
G E
A
PANTRY
CORR.
RECEIVING/STORAGE
KITCHEN
DINING
ROOM
LIVING
ROOM
FOYER
STAFF
OFFICE
TOIL.
RESIDENT
ROOM
7RESIDENT
ROOM
RESIDENT
ROOM
RESIDENT
ROOM
TOIL.
TOIL.
4 TOIL.
SOILED
43C
LE
A
N
CORR.
GUEST
TOIL. 37
M E
D S
S
P A
/B A
TH
S A
FE
R
O O
M
TOIL.
RESIDENT
ROOM
RESIDENT
ROOM
RESIDENT
ROOM
RESIDENT
ROOM
TOIL.
TOIL.
S O
IL
E
D
C
LE
A N
CORR.
TOIL.
RESIDENT
ROOM
SOILED
UTIL. 35
RESIDENT
ROOM
CORR.
TOIL.
CORR.
H.A.C.
STORAGE
LAUNDRY/
SAFE
ROOM
TOIL.
26 6
STORAGE
19B
BID DOCUMENTS SUBMISSION
27-FP2.0
27-FP2.0.dwg
SCALE: 1/4" = 1'-0"
COTTAGE BLDG. 26 - FIRE
PROTECTION DETAILS AND
SCHEDULES
FIRE SPRINKLER LEGEND
SYMBOL DESCRIPTION
FIRE WATER LINE
GLYCOL SYSTEM PIPING
SIAMESE CONNECTION
ELBOW TURNED DOWN
ELBOW TURNED UP
PIPE CONTINUATION
ALARM BELL
F
GF
FIRE RISER ENTRANCE DETAIL
NO SCALE
SLEEVE
FROM MAIN
GRADE
EXTERIOR WALL
RODS
RODS
BUILDING FLOOR
SLEEVE
CAULK WITH MASTIC
WATERPROOF
CAST IRON ON
WELL AND
SPIGOT PIPE
CAST IRON FLANGE
AND SPIGOT PIECE
FIRE RISER UP IN
EQUIPMENT ROOM
BEARING AREA
POURED CONCRETE BLOCKS
BEARING AREA
THRUST BLOCK DETAIL
NO SCALE
UNDISTURBED
EARTH
BEARING AREA OF BLOCK IN SQ. FT. (2000 P.S.F. SOIL)
FITTING SIZES TEE & END 90° BEND 45° BEND
4" 2.0 2.0 2.0 6" 4.0 5.0 3.0 8" 6.0 8.0 5.0
10" 9.0 13.0 7.0
FINISH FLOOR
CEILING
1" 45 DEGREE ELBOW
BUILDING WALL
SYSTEM TEST CONNECTION DETAIL
NO SCALE
INSPECTOR'S SPRINKLER
BUSHING WITH 1/2"
SMOOTH BORE CORROSION
RESISTANT OUTLET
1" GLOBE VALVE
ABOVE CEILING
TO SPRINKLER SYSTEM
ALARM CHECK VALVE
MAIN (FLOW TEST LINE)
MAIN DRAIN VALVE
RISER FROM MAIN WATER SUPPLY
DRAW TO FLOOR DRAIN
TEE CONNECTION
FIRE DEPARTMENT CONNECTION
DESCRIPTION
ITEM
DOUBLE CHECK VALVE ASSEMBLY9
SPRINKLER RISER DETAIL
NO SCALE
WATER FLOW INDICATOR3
DR
OP
FT
. M
IN
WATER SUPPLY
BUTTERBALL INDICATING
VALVE ABOVE CEILING
FILLING
CUP
ACCESS DOOR
IN WALL
CHECK VALVE
DRAIN
VALVE
EXTEND DRAIN THROUGH
EXTERIOR WALL.
WATER
NO
N-
FR
EZ
ZI
NG
S
OL
UT
IO
N
ANTI-FREEZE LOOP DETAIL
NO SCALE 5
TO COVERED
OUTDOOR AREAS
8 7
| 26-FP1.0 - FIRE PROTECTION FLOOR PLAN |
| Sheets and Views |
| 26-FP1.0 - FIRE PROTECTION FLOOR PLAN |
| 26-FP2.0 - FIRE PROTECTION DETAILS AND SCHEDULES |
| Sheets and Views |
| 26-FP2.0 - FIRE PROTECTION DETAILS AND SCHEDULES |
| 27-FP1.0 - FIRE PROTECTION FLOOR PLAN |
| Sheets and Views |
| 27-FP1.0 - FIRE PROTECTION FLOOR PLAN |
| 27-FP2.0 - FIRE PROTECTION DETAILS AND SCHEDULES |
| Sheets and Views |
| 27-FP2.0 - FIRE PROTECTION DETAILS AND SCHEDULES |
File details come from the government source that posted it. Updated .