BID DOCUMENTS
FULLY SPRINKLERED
BID DOCUMENTS SUBMISSION
26-M1.0 1/4" = 1'-0"1
MECHANICAL FLOOR PLAN -
COTTAGE BUILDING #26
26-M1.0.dwg
1.
BUILDING
N.I.C.
N.I.C.
N.I.C.
BUILDING
2.
3.
4.
5.
6.
7.
8.
COORDINATE ALL EQUIPMENT AND DUCTWORK WITH ARCHITECTURAL, STRUCTURAL,
PLUMBING, FIRE PROTECTION, AND ELECTRICAL.
CONTRACTOR SHALL FIELD MEASURE ALL CLEARANCES REQUIRED FOR DUCTWORK
INSTALLATION PRIOR TO FABRICATION.
ALL SUPPLY, RETURN, AND OUTSIDE INTAKE DUCTWORK SHALL BE WRAPPED. REFER
TO SPECIFICATION SECTION 23 07 00.
LOW PRESSURE FLEXIBLE SUPPLY DUCTS TO BE MAXIMUM 3'-0" IN LENGTH. DO NOT
CONNECT FLEXIBLE DUCT DIRECTLY TO DIFFUSER NECK. REFER TO DETAIL 1/26-M5.0.
ALL VAV BOXES SHALL HAVE MINIMUM 18 INCHES STRAIGHT RIGID DUCT INSTALLED AT
PRIMARY AIR INLET. DUCT SIZE SHALL BE PRIMARY INLET SIZE. REFER TO DETAIL
6/26-M5.0.
ALL PRIMARY SUPPLY DUCT UPSTREAM OF VAV BOXES SHALL BE HELICAL WOUND
SPIRAL. ALL SPIRAL DUCT TAPS AND FITTINGS SHALL BE HIGH EFFICIENCY TYPE.
FLAT OVAL DUCT DIMENSIONS ARE INDICATED AS XX/XX.
ALL SPACE TEMPERATURE SENSORS SHALL BE MOUNTED ON WALL BOX AT 48 INCHES
AFF. WALL BOX AND CONDUIT PATHWAYS TO BE PROVIDED AND INSTALLED BY
DIVISION 26.
INSTALL CONCEALED DAMPER OPERATOR IN GYP BOARD CEILING. REFER TO DETAIL
2/26-M5.0.
INSTALL BOTTOM OF SUPPLY GRILLE AT 9'-6" AFF.
MOUNT VARIABLE FREQUENCY DRIVE SERVING AHU 26-1 SUPPLY FAN ARRAY ON WALL.
VAV BOX TO BE INSTALLED EXPOSED WITHIN MECHANICAL ROOM. COORDINATE EXACT
ROUTING OF ALL MECHANICAL AND PLUMBING PIPING TO MAINTAIN SERVICE
CLEARANCE.
INSTALL BOTTOM OF OUTSIDE AIR LOUVER AT 7'-0" AFF. CONNECT FULL SIZE DUCT TO
LOUVER AND ROUTE DOWN INSIDE MECHANCIAL ROOM FOR CONNECTION TO AIR
HANDLING UNIT. REFER TO SECTION 1/26-M4.0. TERMINATE DUCT TO UNIT USING
FLEXIBLE CONNECTION.
TRANSITION RETURN DUCT AS REQUIRED AND TERMINATE TO AIR HANDLING UNIT
USING FLEXIBLE CONNECTION. DIVISION 28 TO PROVIDE AND INSTALL SMOKE
DETECTOR IN RETURN DUCT AT 24 INCHES ABOVE UNIT.
EXTEND 30x36 RELIEF AIR DUCT DOWN THRU ROOF AND CONNECT TO RETURN DUCT.
INSTALL MOTORIZED RELIEF AIR DAMPER BELOW ROOF. REFER TO SECTION 1/26-M4.0.
MOUNT AIR HANDLING UNIT ON 4 INCH CONCRETE HOUSEKEEPING PAD. SECURE UNIT
TO PAD USING HILTI KWIK BOLT II ANCHORS. PAD SHALL EXTEND 6 INCHES BEYOND
EACH EDGE OF UNIT.
TRANSITION FROM AIR HANDLING UNIT OPENING TO 22/35 PRIMARY SUPPLY DUCT AND
ROUTE VERTICALLY AS SHOWN. TERMINATE DUCTWORK TO UNIT USING FLEXIBLE
CONNECTION. REFER TO SECTION 1/26-M4.0.
CONNECT 6 INCH ROUND EXHAUST DUCT TO RESIDENTIAL KITCHEN HOOD AND ROUTE
UP WITHIN STAINLESS STEEL ENCLOSURE TO ABOVE CEILING. EXTEND DUCT UP THRU
ROOF AS SHOWN. TERMINATE DUCTWORK WITH RAINCAP AT 18 INCHES ABOVE
FINISHED ROOF. MAKE ROOF PENETRATION THRU DEKTITE PREMIUM FLASHING.
EXTEND 12x10 EXHAUST DUCT UP THRU ROOF AND TERMINATE TO FAN USING
FLEXIBLE CONNECTION. TRANSITION AS REQUIRED. CONNECT 2 CONDUCTOR, 18 AWG
CONTROL WIRING TO 24V RELAY AND PULL TO VAV 26-8 CONTROLLER. RELAY
PROVIDED AND INSTALLED BY DIVISION 26.
EXTEND 4 INCH ROUND DRYER DUCT UP IN WALL AND TERMINATE THRU ROOF WITH
GOOSENECK AT 12 INCHES ABOVE FINISHED ROOF ASSEMBLY. MAKE ROOF
PENETRATION THRU CHEMCURB AND COMPLETELY FILL WITH CHEMLINK COMPOUND.
ROUTE SUPPLY AND RETURN DUCTS WITHIN ARCHITECTURAL FURRING ACROSS
OPENING AREA.
INSTALL BOTTOM OF SUPPLY GRILLE AT 9'-6" AFF. INSTALL SMOKE DAMPER DIRECTLY
BEHIND GRILLE IN WALL.
INSTALL CONCEALED DAMPER OPERATOR IN SUPPLY DUCT. PROVIDE DAMPER WITH
CABLE AND INSTALL DAMPER OPERTOR IN ADJACENT GYP BOARD CEILING.
EXTEND 12x8 EXHAUST DUCT UP THRU ROOF AND TERMINATE TO FAN USING FLEXIBLE
CONNECTION. TRANSITION AS REQUIRED. CONNECT 2 CONDUCTOR, 18 AWG CONTROL
WIRING TO 24V RELAY AND PULL TO VAV 26-8 CONTROLLER. RELAY PROVIDED AND
INSTALLED BY DIVISION 26.
INSTALL 12x12 POTTORFF MODEL XSV-845 FEMA RATED GRILLE IN CONCRETE SLAB
ABOVE CEILING. FREE AREA OF ASSEMBLY SHALL BE MINIMUM 0.4 FT2. DIRECTLY
ABOVE FEMA GRILLE, INSTALL "OUT OF PARTITION" TYPE COMBINATION FIRE/SMOKE
DAMPER TO PROTECT PENETRATION. DAMPER SLEEVE SHALL BE SECURED TO TOP OF
CONCRETE LID AND FIRE CAULKED. TRANSITION FROM DAMPERS TO DUCTWORK
ABOVE LID AND GRILLE BELOW.
INSTALL CONCEALED DAMPER OPERATOR IN EXHAUST DUCT. PROVIDE DAMPER WITH
CABLE AND INSTALL DAMPER OPERTOR IN ADJACENT GYP BOARD CEILING.
INSTALL SMOKE DAMPER IN SUPPLY DUCT AT WALL PENETRATION. INSTALL DUCT
ACCESS DOOR ABOVE GYP BOARD CEILING OUTSIDE OF GUEST TOILET 37. PROVIDE
AND INSTALL ACCESS DOOR IN CEILING TO ALLOW INSPECTION/MAINTENANCE FOR
COMBINATION FIRE/SMOKE DAMPER.
INSTALL SMOKE DAMPER IN PRIMARY SUPPLY DUCT AT WALL PENETRATION. INSTALL
DUCT ACCESS DOOR ABOVE LAY-IN CEILING IN STAFF OFFICE 9.
INSTALL SMOKE DAMPER IN RETURN DUCT AT WALL PENETRATION. INSTALL DUCT
ACCESS DOOR ABOVE LAY-IN CEILING IN STAFF OFFICE 9.
SUSPEND FAN/HEATER ASSEMBLY FROM STRUCTURE USING ALL-THREAD ROD AND
NEOPRENE ISOLATORS. CONNECT 6 INCH ROUND EXHAUST DUCT TO UNIT AND ROUTE
UP THRU ROOF. TERMINATE DUCT AT 12 INCHES ABOVE FINISHED ROOF ASSEMBLY
WITH RAIN CAP. MAKE ROOF PENETRATION THRU PREMIUM DEKTITE FLASHING.
SCALE: 1/4" = 1'-0"
COTTAGE BLDG. 26 -
MECHANICAL FLOOR PLAN
NO SCALE
KEYPLAN
D
B
G
H E A
C
F
AHU 26-1
L 26-1
M x2
36x20 30x20 x2 x1 x1 x1 x1
12x8
RH 26-1
x8
12x8
CEF 26-10
x8 x1
26x16 x1
CEF 26-4
x8 x8 x8
10x10/R-1
10x10/R-1 10x10/R-1
10x10/R-1
10x10/R-1
10x10/R-1
10x10/R-1
22x10/R-3
22x10/R-3
10x10/R-1 10x10/R-1
10x10/R-1
10x10/R-1
22x10/R-3
22X22/R-1
SD
Ø
22Ø
SD
14/12 10Ø 8Ø 6Ø
6Ø6Ø6Ø
/12
/12
14/12 12Ø 8Ø 6Ø
6Ø
6Ø6Ø
Ø
Ø
Ø
Ø
10"Ø/S-3
300 CFM
10"Ø/S-3
300 CFM 10"Ø/S-3
300 CFM
10"Ø/S-3
300 CFM
CEF 26-7
CEF 26-8
CEF 26-9
22 22
VAV 26-12 VAV 26-13 VAV 26-14 VAV 26-15
x1 x8 x8
8Ø
6Ø 6Ø
8Ø
8Ø
VAV 26-3 VAV 26-4 VAV 26-5 VAV 26-6
Ø
Ø
Ø
Ø
10"Ø/S-3
300 CFM
10"Ø/S-3
300 CFM
10"Ø/S-3
300 CFM
10"Ø/S-3
300 CFM
22 22
CEF 26-3CEF 26-2
CEF 26-1
8"Ø/S-4
250 CFM
6Ø
Ø
8Ø 6Ø x8
8Ø
6Ø
6Ø
6Ø
10"Ø/S-3
300 CFM
10"Ø/S-3
300 CFM
10Ø
10Ø
VAV 26-8
VAV 26-9
VAV 26-10
VAV 26-11
CEF 26-5
CEF 26-6
8"Ø/S-4
250 CFM
6"Ø/S-1
50 CFM
8"Ø/S-1
200 CFM
6"Ø/S-1
75 CFM
FSD17
FSD
x1 x8
FSD
x8
10x10/E-1
125 CFM
10x10/E-1
250 CFM
EF 26-2
EF 26-1
10x10/E-1
125 CFM
6"Ø/S-1
75 CFM
6"Ø/S-1
50 CFM
/16
32x10 x1
Ø
Ø
SD
SD
SD
SD
18x10/S-2
300 CFM
18x10/S-2
300 CFM
18x10/S-2
300 CFM
VAV 26-7
6"Ø/S-1
50 CFM
18x10/S-2
300 CFM
S
S x8 x6 x6
10x10/E-1
250 CFM
8"Ø/S-3
200 CFM
FSD
10x10/E-1
100 CFM
x1 x1
6Ø
24x10 24x10/S-2
600 CFM
Ø
6"Ø/S-1
50 CFM
S
VAV 26-1
24x10/S-2
400 CFM
6Ø
VAV 26-2
9Ø x1
8Ø
8Ø 10Ø (2)-8"Ø/S-1
150 CFM EACH
x2
10"Ø/S-4
400 CFM
x1
12Ø
6Ø x1 x1
12x8
26-M4.0
S
S S
S
S
S
S
S
SS
S
S
Ø
WALL LEGEND
LINE TYPE DESCRIPTION
1-HR PARTITION
2-HR PARTITION
SMOKE SEPERATION
Ø
LAUNDRY/
SAFE
ROOM
DATA
SUPPLIES/
EQUIP.
STOR. 18
ELEC.
S
TO
R A
G E
A
STORAGE
19B
MECHANICAL
S
TO
R A
G E
A
PANTRY
CORR.
RECEIVING/STORAGE
KITCHEN
DINING
ROOM
LIVING
ROOM
FOYER
STAFF
OFFICE 9
TOIL.
RESIDENT
ROOM
RESIDENT
ROOM
5 RESIDENT
ROOM
RESIDENT
ROOM
TOIL.
TOIL.
TOIL.
SOILED
C
LE
A N
CORR.
GUEST
TOIL. 37
M E
D S
S
P A
/B A
TH
S A
FE
R
O O
M
TOIL.
RESIDENT
ROOM
RESIDENT
ROOM
RESIDENT
ROOM
RESIDENT
ROOM
TOIL.
TOIL.
S O
IL
E
D
C
LE
A N
CORR.
TOIL.
RESIDENT
ROOM
SOILED
UTIL. 35
RESIDENT
ROOM
CORR.
TOIL.
CORR.
H.A.C.
S
TO
R A
G E
TOIL.
BID DOCUMENTS SUBMISSION
26-M2.0 1/4" = 1'-0"1
MECHANICAL PIPING FLOOR PLAN
- COTTAGE BUILDING #26
26-M2.0.dwg
BUILDING
N.I.C.
N.I.C.
N.I.C.
BUILDING
1.
2.
3.
4.
5.
6.
7.
8.
9.
COORDINATE ALL EQUIPMENT AND PIPING WITH ARCHITECTURAL, STRUCTURAL,
PLUMBING, FIRE PROTECTION, AND ELECTRICAL.
ROUTE ALL PIPING AS HIGH AS POSSIBLE.
HEATING WATER RUNOUTS TO TERMINAL UNITS ARE 3/4 INCH, UNLESS SPECIFICALLY
NOTED OTHERWISE.
DROP OUT OF BOTTOM OF MAINS FOR RUNOUTS TO PREVENT AIR ENTRAPMENT IN
PIPING SYSTEM.
REFER TO DETAIL 8/26-M5.0 FOR VAV BOX HEATING WATER PIPING CONNECTIONS.
ALL REFRIGERANT PIPING SHALL BE TYPE ACR HARD DRAWN COPPER. ALL FITTINGS
SHALL BE LONG RADIUS TYPE.
ALL REFRIGERANT SUCTION PIPING SHALL BE INSULATED USING CLOSED CELL
ARMAFLEX INSULATION. REFER TO SPECIFICATION SECTION 23 07 00.
SUSPEND ALL REFRIGERANT PIPING FROM STRUCTURE USING TRAPEZE SUPPORTS
AND CUSH-A-CLAMPS.
REFER TO MECHANICAL SCHEDULES FOR REFRIGERANT PIPING SIZES.
CONTRACTOR SHALL PROVIDE A SEPARATE LINE ITEM FOR DELETION OF PURCHASE
AND INSTALLATION OF CU 26-2 AND ALL ASSOCIATED REFRIGERANT PIPING AS PART
OF DEDUCTIVE ALTERNATE #5.
MOUNT BOILER ON 4 INCH CONCRETE HOUSEKEEPING PAD. PAD SHALL EXTEND 6
INCHES BEYOND OUTER EDGES OF BOTH BOILERS.
CONNECT 2 INCH HWS AND HWR PIPING TO BOILER. INSTALL BOILER PUMP IN VERTICAL
HWR PIPING. REFER TO HEATING WATER SYSTEM PIPING DIAGRAM 14/26-M5.0 FOR ALL
PIPING CONNECTIONS.
MOUNT HEATING WATER SYSTEM BYPASS FILTER/FEEDER ON 4 INCH CONCRETE
HOUSEKEEPING PAD. REFER TO HEATING WATER SYSTEM PIPING DIAGRAM 14/26-M5.0
FOR ALL PIPING CONNECTIONS.
MOUNT HEATING WATER SYSTEM EXPANSION TANK ON 4 INCH CONCRETE
HOUSEKEEPING PAD. REFER TO HEATING WATER SYSTEM PIPING DIAGRAM 14/26-M5.0
FOR ALL PIPING CONNECTIONS.
INLINE TANGENTIAL AIR SEPARATOR MOUNTED IN PIPING. REFER TO HEATING WATER
SYSTEM PIPING DIAGRAM 14/26-M5.0.
RACK HEATING WATER PUMPSON WALL IN STACKED CONFIGURATION. HWP 26-1 SHALL
BE 5'-0" AFF AND HWP 26-2 SHALL BE 3'-0" AFF. REFER TO HEATING WATER SYSTEM
PIPING DIAGRAM 14/26-M5.0.
CONNECT 3/4 INCH HWS AND HWR PIPING TO UNIT HEATER. REFER TO DETAIL
9/26-M5.0 FOR PIPING CONNECTIONS.
CONNECT 1-1/2 INCH HWS AND HWR PIPING TO AIR HANDLING UNIT COIL. REFER TO
DETAIL 10/26-M5.0 FOR PIPING CONNECTIONS.
EXTEND REFERIGERANT CIRCUIT #1 AND CIRCUIT #2 FOR TERMINATION TO PRIMARY
DX COOLING COIL IN AHU 26-1. PROVIDE OIL TRAP IN LIQUID LINE RISERS AND
TERMINATION TO EACH CIRCUIT.
INSTALL MANUAL AIR VENTS FROM TOP OF PIPING. REFER TO DETAIL 7/26-M5.0.
EXTEND REFERIGERANT CIRCUIT #1 AND CIRCUIT #2 FOR TERMINATION TO
SECONDARY DX COOLING COIL IN AHU 26-1. PROVIDE OIL TRAP IN LIQUID LINE RISERS
AND TERMINATION TO EACH CIRCUIT.
ROUTE ALL REFRIGERANT AND HEATING WATER PIPING WITHIN ARCHITECTURAL
FURRING ACROSS FOYER 10.
EXTEND REFRIGERANT CIRCUIT #1 AND CIRCUIT #2 PIPING DOWN THRU ROOF FROM
CU 26-2. INSTALL OIL TRAP IN BOTTOM OF VERTICAL RISER OF EACH LIQUID LINE.
REFER TO 26-M3.0 FOR CONTINUATION.
EXTEND REFRIGERANT CIRCUIT #1 AND CIRCUIT #2 PIPING DOWN THRU ROOF FROM
CU 26-1. INSTALL OIL TRAP IN BOTTOM OF VERTICAL RISER OF EACH LIQUID LINE.
REFER TO 26-M3.0 FOR CONTINUATION.
EXTEND 3/4 INCH HWS AND HWR PIPING FOR TERMINATION TO HEATING WATER
REHEAT COIL ON VAV 26-3 AND VAV 26-4.
MOUNT FAN COIL UNIT ABOVE DOORWAY.
EXTEND REFRIGERANT LIQUID AND SUCTION PIPING DOWN THRU ROOF AND
ROUTE AS SHOWN FOR CONNECTION TO FAN COIL UNIT. TERMINATE PIPING TO
FAN COIL UNIT USING RECTORSEAL NO-KINK FLEXIBLE CONNECTORS.
10.
SCALE: 1/4" = 1'-0"
COTTAGE BLDG. 26 -
MECHANICAL PIPING FLOOR
PLAN
NO SCALE
KEYPLAN
D
B
G
H E A
C
F
AHU 26-1
HWP 26-1
HWP 26-2
BOILER 26-2
BOILER 26-1
VAV 26-12
VAV 26-13
VAV 26-14 VAV 26-15
VAV 26-3 VAV 26-4 VAV 26-5 VAV 26-6
VAV 26-8
VAV 26-9
VAV 26-10
VAV 26-11
VAV 26-7
VAV 26-1
VAV 26-2
HW
R
HW
R
HW
S
HW
S
10 11
UH-26-1
HWS
HWR
HW
S
HW
R
RL
/R
S-
RL
/R
S-
RL
/R
S-
RL
/R
S-
HWS
HWR
RL/RS-1
RL/RS-2
RL/RS-1
RL/RS-2
HWS
HWR
RL/RS-1
RL/RS-2
RL/RS-1
RL/RS-2
13 14
HW
S
HW
R
RL
/R
S-
RL
/R
S-
RL
/R
S-
RL
/R
S-
HWR
HWS
HWR
HW
S
HW
R
HWS
HWR
2"
3/4"2"
1-1/2"
3/4" 1-1/2"
1-1/2"
1-1/4"
3/4"
1"
3/4"3/4" 3/4"3/4"
1"
3/4"
3/4"
3/4"3/4"
1"
HW
S
HW
R
3/4"
3/4"
3/4"
3/4"
2"1-1/2"
1-1/2"3/4"
T
FC 26-A
3/4"
TOIL.
DATA
SUPPLIES/EQUIP.
STOR.
ELEC.
STORAGE
18A
MECHANICAL
S
TO
R A
G E
A
PANTRY
CORR.
RECEIVING/STORAGE
KITCHEN
DINING
ROOM
LIVING
ROOM
FOYER
STAFF
OFFICE
TOIL.
RESIDENT
ROOM
RESIDENT
ROOM
RESIDENT
ROOM
RESIDENT
ROOM
TOIL.
TOIL.
TOIL.
S O
IL
E
D
C
LE
A N
CORR.
GUEST
TOIL.
MEDS
SPA/BATH/SAFE
ROOM
TOIL.
RESIDENT
ROOM
RESIDENT
ROOM
RESIDENT
ROOM
RESIDENT
ROOM
TOIL.
TOIL.
S O
IL
E
D
C
LE
A N
CORR.
TOIL.
RESIDENT
ROOM
SOILED
UTIL.
RESIDENT
ROOM
CORR.
TOIL.
CORR.
H.A.C.
33 STORAGE
STORAGE
19B
LAUNDRY/
SAFE
ROOM
BID DOCUMENTS SUBMISSION
26-M3.0 1/4" = 1'-0"1
MECHANICAL ROOF PLAN -
COTTAGE BUILDING #26
26-M3.0.dwg
1.
BUILDING
N.I.C.
N.I.C.
N.I.C.
BUILDING
2.
3.
4.
COORDINATE ALL EQUIPMENT AND PIPING WITH ARCHITECTURAL, STRUCTURAL,
PLUMBING, FIRE PROTECTION, AND ELECTRICAL.
ALL REFRIGERANT PIPING SHALL BE TYPE ACR HARD DRAWN COPPER. ALL FITTINGS
SHALL BE LONG RADIUS TYPE.
ALL REFRIGERANT SUCTION PIPING SHALL BE INSULATED USING CLOSED CELL
ARMAFLEX INSULATION. COVER INSULATION ON ROOF WITH RIGID ALUMINUM
JACKETING AND PREFORMED FITTING COVERS. REFER TO SPECIFICATION SECTION
23 07 00.
REFER TO MECHANICAL SCHEDULES FOR REFRIGERANT PIPING SIZES.
CONTRACTOR SHALL PROVIDE A SEPARATE LINE ITEM FOR DELETION OF PURCHASE
AND INSTALLATION OF CU 26-2 AND ALL ASSOCIATED REFRIGERANT PIPING AS PART
OF DEDUCTIVE ALTERNATE #5.
ROUTE REFRIGERANT PIPING DOWN THRU ROOF. MAKE ROOF PENETRATIONS THRU
SINGLE CHEMCURB AND COMPLETELY FILL WITH CHEMLINK COMPOUND. REFER TO
26-M2.0 FOR CONTINUATION.
MOUNT CONDENSING UNIT IN THYBAR MODEL TC-3 (OR APPROVED EQUAL) ROOF CURB
WITH CAP. SECURE UNIT TO CURB.
MOUNT CONDENSING UNIT ON (2) 72(W)x18(H) THYBAR MODEL TEMS-3 (OR APPROVED
EQUAL) SUPPORTS. REFER TO DETAIL 4/26-M5.0.
5.
SCALE: 1/4" = 1'-0"
COTTAGE BLDG. 26 -
MECHANICAL ROOF PLAN
NO SCALE
KEYPLAN
EF 26-2
EF 26-1
CU 26-1
CU 26-2
RL
/R
S-
RL
/R
S-
RL
/R
S-
RL
/R
S-
CU 26-A
RH 26-1
BID DOCUMENTS SUBMISSION
26-M4.0 26-M4.0.dwg
COTTAGE BLDG. 26 -
MECHANICAL DETAILS AND
SCHEDULES
4" CONCRETE
HOUSEKEEPING
PAD
FLEXIBLE
CONNECTION
/35
22"Ø SPIRAL
SUPPLY DUCT
BEYOND 24x36 x5
M
FLEXIBLE
CONNECTION
MOTORIZED RETURN
AIR DAMPER
36x24 RETURN
DUCT BEYOND
OUTSIDE AIR
INTAKE LOUVER
L 26-1
MOTORIZED
OUTSIDE AIR
DAMPER
7'-0"
MOTORIZED RELIED
AIR DAMPER
RELIEF AIR
HOOD RH 26-1
AIR HANDLING UNIT - SECTION
SCALE: 1/2" = 1'-0"
SD
RETURN DUCT
SMOKE DETECTOR
BY DIVISION 28
SA
DISCHARGE AIR
TEMP
HW VALVE
HWR
HWS
PRIMARY AIR
INLET
INLET AIRFLOW
SENSOR
(BY MFG.)
M
VAV BOX
DAMPER
S
SPACE TEMP
SENSOR
TYPICAL SINGLE DUCT VAV BOX WITH HW REHEAT CONTROL SCHEMATIC
NO SCALE
HE
AT
IN
G
CO
IL
BOILER 26-1 BOILER 26-2
HWS
HWS
T
HWR
BOILER LOOP
OUTDOOR
TEMPERATURE
SENSOR
MAIN EMS CONTROLLER
MOUNTED IN MECHANICAL
PENTHOUSE
2C/18AWG
1. TEMPERATURE CONTROLS CONTRACTOR SHALL PROVIDE AND INSTALL ALL CONTROL WIRING AND CONDUIT. ALL CONTROL WIRING SHALL BE ROUTED IN 1/2
INCH EMT CONDUIT WITH COMPRESSION FITTINGS INSIDE THE MECHANICAL PENTHOUSE.
SECURE ALL CONDUIT TO INSIDE OF WALL/CEILING OF MECHANICAL PENTHOUSE UNIT. ROUTE ALL CONDUIT PARALLEL AND PERPENDICULAR TO UNIT LINES.
ALL CONTROL WIRING RUNS BETWEEN TERMINATION POINTS SHALL BE IN ONE PIECE WITHOUT SPLICES.
MOUNT ALL DEVICES AND TERMINATE ALL WIRING AT EACH DEVICE.
REFER TO SPECIFICATION SECTION 15940 FOR HEATING WATER SYSTEM OPERATION.
MOUNT LOCHINVAR OUTDOOR AIR TEMPERATURE SENSOR ON NORTH FACE OF MECHANICAL PENTHOUSE UNIT. SENSOR SHALL BE MOUNTED BENEATH FIELD FABRICATED GALVANIZED STEEL SHROUD TO SHIELD FROM DIRECT SUNLIGHT. PAINT SHROUD TO MATCH MECHANICAL PENTHOUSE.
PULL 2 CONDUCTOR, 18 AWG CONTROL WIRING FROM OUTDOOR TEMPERATURE SENSOR TO LEAD BOILER TERMINAL STRIP.
PULL 2 CONDUCTOR, 18 AWG CONTROL WIRING FROM BUILDING EMS CONTROL PANEL, MOUNTED IN MECHANICAL PENTHOUSE, TO BOILER ALARM CONTACTS
ON LEAD BOILER TERMINAL STRIP.
PULL 2 CONDUCTOR, 18 AWG CONTROL WIRING FROM BUILDING EMS CONTROL PANEL, MOUNTED IN MECHANICAL PENTHOUSE, TO BOILER ENABLE/DISABLE
CONTACTS ON LEAD BOILER TERMINAL STRIP.
INSTALL LOCHINVAR PROVIDED TEMPERATURE SENSOR IN WELL AND PULL 2 CONDUCTOR, 18 AWG CONTROL WIRING FROM SENSOR AND TERMINATE TO LEAD
BOILER.
INSTALL EMS TEMPERATURE SENSOR IN WELL AND PULL 2 CONDUCTOR, 18AWG CONTROL WIRING TO MAIN EMS CONTROL PANEL.
PULL 18 AWG SHIELDED TWISTED PAIR WIRING FROM LEAD BOILER AND TERMINATE AT EACH BOILER IN DAISY CHAIN CONFIGURATION.
PULL 2 CONDUCTOR, 18 AWG CONTROL WIRING, IN DAISY CHAIN CONFIGURATION, FROM OUTDOOR TEMPERATURE SENSOR TERMINALS IN BOILER 26-1 AND
TERMINATE TO BOILER 26-2.
PULL 2 CONDUCTOR, 18 AWG CONTROL WIRING, IN DAISY CHAIN CONFIGURATION, FROM ENABLE/DISABLE TERMINALS IN BOILER 26-1 AND TERMINATE TO
BOILER 26-2.
HEATING WATER SYSTEM CONTROL WIRING SCHEMATIC
NO SCALE
2.
3.
4.
5.
T
T
MECHANICAL DESIGN CONDITIONS
SUMMER OUTSIDE DESIGN - DEG F (DB) 105
SUMMER OUTSIDE DESIGN - DEG F (WB) 70
SUMMER INSIDE DESIGN - DEG F (DB) 72
SUMMER INSIDE DESIGN - % RH 40
WINTER OUTSIDE DESIGN - DEG F (DB) 10
WINTER INSIDE DESIGN - -DEG F (DB) 68
MAIN AIR UNIT COOLING DEMAND - TONS 25
MIN FRESH AIR REQUIRED - CFM 2,000
CONNECTED HEATING DEMAND - BTU/HR 458.0
DOMESTIC COLD WATER DEMAND - GPM 90
SANITARY DRAINAGE - DFU 98
AIR DISTRIBUTION SCDHEULE
MARK TYPE LOCATION FINISH FRAME EXAMPLE: PRICE INDUSTRIES
S-1 SUPPLY CEILING WHITE LAY-IN SMD, 12x12, AMF FRAME
S-2 SUPPLY SIDEWALL WHITE SURFACE 32S
S-3 SUPPLY CEILING WHITE LAY-IN SMD, 24x24, AMF FRAME
S-4 SUPPLY CEILING WHITE LAY-IN SMD, 24x24
R-1 RETURN CEILING WHITE LAY-IN 80, AMF FRAME
R-2 RETURN CEILING WHITE LAY-IN 80, 24x24
R-3 RETURN CEILING WHITE LAY-IN 80, 24x12
E-1 EXHAUST CEILING WHITE LAY-IN 80, AMF FRAME
NOTES: 1. COORDINATE FRAME STYLE WITH CEILING LAYOUT.
BOILER SCHEDULE
MARK INPUT (MBH) OUTPUT (MBH) FUEL TURNDOWN RATIO EFFICIENCY TYPE ELECTRICAL EXAMPLE: LOCHINVAR
BOILER 26-1 500.0 470.0 NATURAL GAS 5:1 94% CONDENSING 120/1/60 KBN501
BOILER 26-2 500.0 470.0 NATURAL GAS 5:1 94% CONDENSING 120/1/60 KBN501
NOTES: 1. BOILERS SHALL BE RATED FOR USE AT ELEVATION OF 2450 FEET.
2. PROVIDE BOILERS WITH CONDENSATE NEUTRALIZATION KIT, CONCENTRIC VENT KIT, AND BMS GATEWAY.
CONDENSING UNIT SCHEDULE
MARK SERVES
CAPACITY
(MBH)
CIRCUITS
(QTY) AMBIENT EER
REFRIGERANT PIPING SIZES ELECTRICAL DATA
EXAMPLE: AAON
LIQUID SUCTION SERVICE MCA MOCP
CU 26-1 AHU 26-1 266.8 2 105 10.1 (2) 5/8 (2) 1-3/8 208/3/60 130.0 175 CFA-025
CU 26-2 AHU 26-1 266.8 2 105 10.1 (2) 3/4 (2) 1-3/8 208/3/60 130.0 175 CFA-025
NOTES: 1. UNITS SELECTED AT ELEVATION OF 2450 FEET.
2. PROVIDE UNITS WITH FACTORY MOUNTED DISCONNECT AND POWERED GFCI RECEPTACLE.
3. LEAD COMPRESSOR SHALL BE VARIABLE CAPACITY SCROLL TYPE.
AIR HANDLING UNIT SCHEDULE
MARK
SUPPLY FAN DATA COOLING COIL DATA REHEAT COIL DATA
ELECTRICAL EXAMPLE:
MAX CFM MIN CFM MIN OUTSIDE AIR MATRIX TSP (ON. WG) HP CFM TOTAL (MBH) SENSIBLE (MBH) EAT (DB/WB) CIRCUITS ROWS/FPI CFM EAT LAT EWT GPM MAX WPD (FT) ROWS/FPI
AHU 26-1 6,800 4,500 2,000 1x2 4.0 (2) 4 6,800 266.8 199.7 81.7/65.4 2 6/10 6,800 50 81.6 160 15.0 3.8 1/8 208/3/60 TEMTROL
NOTES: 1. UNIT SELECTED AT ELEVATION OF 2450 FEET.
2. PROVIDE UNIT WITH VAPOR PROOF LIGHT FIXTURES IN EACH ACCESSIBLE SECTION OF UNIT, FACTORY WIRED TO EXTERIOR SWITCH. LIGHTING CIRCUIT SHALL BE 120/1/60.
3. REFER TO DETAILS 12/26-M5.0 AND 13/26-M5.0 FOR UNIT CONFIGURATIONS.
SINGLE DUCT TERMINAL UNIT SCHEDULE
MARK MODEL
PRICE
INLET
DIAMETER
CFM HEATING WATER COIL DATA
MAX MIN CFM MBH EAT LAT GPM EWT ROWS
VAV 26-1 SDV5 12" 1050 350 600 34.6 55.0 111.8 2.5 160 2
VAV 26-2 SDV5 9" 700 250 250 11.0 55.0 98.1 1.5 160 1
VAV 26-3 SDV5 6" 300 150 200 11.1 55.0 109.1 1.0 160 2
VAV 26-4 SDV5 6" 300 150 200 11.1 55.0 109.1 1.0 160 2
VAV 26-5 SDV5 6" 300 150 200 11.1 55.0 109.1 1.0 160 2
VAV 26-6 SDV5 6" 300 150 200 11.1 55.0 109.1 1.0 160 2
VAV 26-7 SDV5 12" 1250 400 600 34.6 55.0 111.8 2.5 160 2
VAV 26-8 SDV5 10" 850 600 600 28.6 55.0 101.9 2.5 160 2
VAV 26-9 SDV5 6" 300 150 200 11.1 55.0 109.1 1.0 160 2
VAV 26-10 SDV5 6" 300 150 200 11.1 55.0 109.1 1.0 160 2
VAV 26-11 SDV5 6" 300 150 150 8.1 55.0 107.6 0.5 160 2
VAV 26-12 SDV5 6" 300 150 200 11.1 55.0 109.1 1.0 160 2
VAV 26-13 SDV5 6" 300 150 200 11.1 55.0 109.1 1.0 160 2
VAV 26-14 SDV5 6" 300 150 200 11.1 55.0 109.1 1.0 160 2
VAV 26-15 SDV5 6" 300 150 200 11.1 55.0 109.1 1.0 160 2
NOTES: 1. UNITS SELECTED AT ELEVATION OF 2450 FEET.
2. UNITS SHALL HAVE THIRD PARTY DDC CONTROLS FIELD INSTALLED.
3. PROVIDE UNITS WITH PROTECTIVE SHROUD TO HOUSE DDC COMPONENTS.
4. REFER TO PIPING DIAGRAM 8/26-M5.0 FOR HW COIL CONNECTIONS.
FAN SCHEDULE
MARK CFM SP HP RPM TYPE DRIVE ELECTRICAL MAX. SONES EXAMPLE: COOK
EF 26-1 350 0.5 1/4 1452 PRV DIRECT 115/1/60 7.2 ACED-ED 100C17DEC
EF 26-2 500 0.5 1/4 1451 PRV DIRECT 115/1/60 7.9 ACED-ED 101C17DEC
NOTES: 1. FANS SELECTED AT ELEVATION OF 2450 FEET.
2. PROVIDE FANS WITH 14 INCH FACTORY ROOF CURB, WIRED DISCONNECT SWITCH, AND BACKDRAFT DAMPER.
3. PROVIDE FAN WITH FACTORY MOUNTED SPEED CONTROLLER.
HOT WATER UNIT HEATER SCHEDULE
MARK CFM HP CAPACITY (MBH) MAX WPD (FT) EWT EAT LAT GPM ELECTRICAL EXAMPLE: MODINE
UH 26-1 730 1/12 19.2 0.1 160 60 83 1.25 115/1/60 HSB47
NOTES: 1. UNIT SELECTED AT ELEVATION OF 2450.
2. PROVIDE UNIT WITH FINGER-PROOF FAN GUARD.
PUMP SCHEDULE
MARK SERVES GPM HEAD (FT) HP RPM TYPE ELECTRICAL EXAMPLE: GRUNDFOS
BP 26-1 BOILER-1 32 15 1/2 1750 INLINE CENTRIFUGAL 115/1/60 UPS32-80
BP 26-2 BOILER-2 32 15 1/2 1750 INLINE CENTRIFUGAL 115/1/60 UPS32-80
HWP 26-1 HEATING WATER SYSTEM 36 30 3/4 1750 INLINE CENTRIFUGAL 115/1/60 UPS32-160
HWP 26-1 HEATING WATER SYSTEM 36 30 3/4 1750 INLINE CENTRIFUGAL 115/1/60 UPS32-160
4" CONCRETE
HOUSEKEEPING
PAD
FLEXIBLE
CONNECTION
/35
22"Ø SPIRAL
SUPPLY DUCT
BEYOND 24x36 x5
M
FLEXIBLE
CONNECTION
MOTORIZED RETURN
AIR DAMPER
36x24 RETURN
DUCT BEYOND
OUTSIDE AIR
INTAKE LOUVER
L 26-1
MOTORIZED
OUTSIDE AIR
DAMPER
7'-0"
MOTORIZED RELIED
AIR DAMPER
RELIEF AIR
HOOD RH 26-1
AIR HANDLING UNIT - SECTION
SCALE: 1/2" = 1'-0"
CEILING EXHAUST FAN SCHEDULE
MARK CFM HEATER INPUT
ELECTRICAL
EXAMPLE: BROAN
SERVICE MCA MOCP
CEF 26-1 100 1.5 KW 120/1/60 13.5 20 QTX110HFLT
CEF 26-2 100 1.5 KW 120/1/60 13.5 20 QTX110HFLT
CEF 26-3 100 1.5 KW 120/1/60 13.5 20 QTX110HFLT
CEF 26-4 100 1.5 KW 120/1/60 13.5 20 QTX110HFLT
CEF 26-5 100 1.5 KW 120/1/60 13.5 20 QTX110HFLT
CEF 26-6 100 1.5 KW 120/1/60 13.5 20 QTX110HFLT
CEF 26-7 100 1.5 KW 120/1/60 13.5 20 QTX110HFLT
CEF 26-8 100 1.5 KW 120/1/60 13.5 20 QTX110HFLT
CEF 26-9 100 1.5 KW 120/1/60 13.5 20 QTX110HFLT
CF 26-10 100 1.5 KW 120/1/60 13.5 20 QTX110HFLT
NOTES: 1. PROVIDE FANS WITH MODEL 77DW 3 WAY CONTROL SWITCH.
NO SCALE 4
AHU 26-1 CONTROL SCHEMATIC
M
M
M
HIGH
STATIC
DISCHARGE
AIR TEMP
DUCT STATIC
PRESSURE
RETURN AIR
TEMP
RETURN AIR
% RH
OUTSIDE AIR
TEMP
OUTSIDE AIR
% RH
MIXED
AIR TEMP
HWR
HWS
HE
AT
IN
G
W
AT
ER
C
OI
L
PR
IM
AR
Y
DX
C
OO
LIN
G
CO
IL
SE
CO
ND
AR
Y
DX
C
OO
LIN
G
CO
IL
FAN
S/S
FAN
SPEED
VFD
SM
OK
E
DE
TE
CT
OR
LOUVER SCHEDULE
MARK TYPE SIZE (WxHxD) FIRE AREA (FT²) FINISH EXAMPLE: POTTORFF
L 26-1 OUTSIDE AIR 54x48x6 10.4 ANODIZED EFD-637
NOTES: 1. PROVIDE WITH EXTERIOR FLANGE FRAME AND INSECT SCREEN.
2. ARCHITECT TO SELECT COLOR.
DUCTLESS SPLIT SYSTEM SCHEDULE
MARK LOCATION
NOMINAL COOLING
CAPACITY (MBH)
REFRIGERANT PIPING SIZES ELECTRICAL DATA EXAMPLE: DAIKIN
LIQUID SUCTION INDOOR UNIT OUTDOOR UNIT INDOOR UNIT OUTDOOR UNIT
FC 26-A/CU 26-A DATA 16 12.0 1/4 3/8 208/1/60 208/1/60 FTX12NMVJU RX12NMVJU
NOTES: 1. PROVIDE INDOOR UNIT WITH HARDWIRED THERMOSTAT AND MODEL DACA-CP1-1 INTERNAL CONDENSATE PUMP.
SD
RETURN DUCT
SMOKE DETECTOR
BY DIVISION 28
FILTER
STATUS
OUTSIDE
AIR
RELIEF AIR
RETURN
AIR
SUPPLY
AIR
BID DOCUMENTS SUBMISSION
26-M5.0 26-M5.0.dwg
COTTAGE BLDG. 26 -
MECHANICAL DETAILS
CEILING DIFFUSER CONNECTION DETAIL
NO SCALE 1
NOTE: SUPPLY GRILLES SHALL HAVE RIGID
ELBOWS. FLEXIBLE DUCT CONNECTED DIRECTLY
TO DIFFUSER IS PROHIBITED.
FLEXMASTER STOD
SIDE TAKE-OFF WITH
DAMPER
1-1/2" STAND-OFF
BRACKET ASSEMBLY
MANUAL LOCKING
QUADRANT W/DEGREE
GRADUATIONS
MOLDED NYLON
SLEEVE-TYPE
INTERMEDIATE BEARING
MOLDED NYLON SLEEVE-
TYPE END BEARINGS
TYPICAL CEILING MOUNTED
SUPPLY DIFFUSER
FLEXIBLE DUCT
(MAXIMUM 3')
S.A. DUCT
RIGID ELBOW
CEILING
3/8" SQUARE
SHAFT
DUCT
7/8" CHANNEL IRON METAL
LOCK NUT
COVER
2x4 WOOD BLOCKING.
3/8" SQUARE SHAFT
SPRING WASHER
MITER GEARS
ALLEN SCREWS
PINS
BUTTERFLY DAMPER
CONCEALED DAMPER ACTUATOR DETAIL
NO SCALE
GYP BOARD
CEILING
EXHAUST FAN
EXHAUST DUCT
VARIES
ROOF
BACKDRAFT DAMPER
CANT STRIP
FLASHING
EXHAUST FAN MOUNTING DETAIL
NO SCALE
COUNTER FLASHING
BY ROOFING
SUBCONTRACTOR
FACTORY
FABRICATED CURB
LOOP UP 8 INCHES ABOVE MAIN
1/2" BALL VALVE
INSULATION
HEATING WATER PIPE
MANUAL AIR VENT
NO SCALE
NEGATIVE PRESSURE CONDENSATE DRAIN DETAIL
NO SCALE
H = FAN MAXIMUM NEGATIVE STATIC
PRESSURE (IN. w.c.) +1"
DRAIN PAN
UNION TEE WITH PLUG FOR
CLEANOUT.
H
H/2
SLOPE TO DRAIN
TEE FITTING FOR
CONDENSATE VENT.
NOTE: CONDENSATE DRAIN SHALL BE NO SMALLER
THAN UNIT CONNECTION.
AHU 26-1 DETAIL - ELEVATION
NO SCALE
AHU 26-1 DETAIL - PLAN VIEW
NO SCALE
COIL
NO SCALE 10
AIR HANDLING UNIT HEATING WATER COIL PIPING DIAGRAM
RE
TU
RN
AT
C
MANUAL AIR VENT
AUTOFLOW MODEL
UP UNION/PT PORT
ASSEMBLY
AUTOFLOW MODEL UP
DRAIN/PT PORT ASSEMBLY
CONNECTION TO COILGAS COK
P/T PORT
P/T PORT
SU
PP
LY
SHUT OFF VALVE SHUT OFF VALVE
P/T PORTS P/T PORTS
THREE-WAY ELECTRIC
TEMPERATURE CONTROL
VALVE BY TEMPERATURE
CONTROLS CONTRACTOR
AUTOFLOW MODEL AC
AUTOMATIC FLOW CONTROL
VALVE ASSEBLY
AUTOFLOW MODEL YC
STRAINER ASSEMBLY
HOSE END
DRAIN VALVE
BOILER 26-1 BOILER 26-2
HW
R
HW
S
HW
R
HW
S
GG
HWR
HWS
HWS
HWR
HWP 26-1
HWP 26-2
BP 26-1 BP 26-2
HWSHWS
HW
S
HW
S
HEATING WATER SYSTEM PUMPS
AND ASSOCIATED MANIFOLD
PIPING TO BE RACKED ON WALL
OF MECHANICAL ROOM
4" CONCRETE HOUSE
KEEPING PAD
P/T PORT
UNION
DIRT LEG
GAS COCK
PIPE RELIEF VALVE
TO FLOW DRAIN
BUTTERFLY VALVE
STRAINER
2"2" 2"2"
2"
2"
CHECK VALVE
HEATING WATER
RETURN FROM
BUILDING
SENSOR WELL FOR
BOILER TEMPERATURE
SUPPLY SENSOR
BIG MODEL RL-20
TANGENTIAL AIR
SEPARATOR
BIG MODEL D-100V
EXPANSION TANK
4" SCHEDULE 40 PVC
COMBUSTION AIR INTAKE
AND FLUE VENT PIPING TO
CONCENTRIC VENT KIT
TEMPERATURE WELL
FOR EMS SENSOR
AUTOMATIC
AIR VENT
GLOBE VALVE WATTS MODEL LF909
REDUCED PRESSURE
BACKFLOW PRESSURE
1" 1-1/2"
1-1/2"
1-1/2" QUICK FILL
BALL VALVE
2"
PVR
1"
1"
1"
1"
2"
2"
2"
2"
HEATING WATER
SUPPLY TO BUILDING
SINGLE PRESSURE
GAUGE WITH COCK
STAINLESS STEAL BYPASS
FILTER/SHOT FEEDER
NO SCALE 14
HEATING WATER SYSTEM PIPING DIAGRAM
16 GA. FORMED CHANNEL CURB ALL SIDES
3/4" PLYWOOD DECKING
22 GA. GALV. SHEET METAL
CANT STRIP
18 GA. "Z" CHANNEL SUPPORT 24" O.C.
FLASHING
CONDENSING UNIT ROOF SUPPORT
NO SCALE
WALL
CAULKING MATERIAL DAMPER FRAME
MOUNTING ANGLE
6" TO 16" MAX.
HR STEEL SLEEVE
SIZE AS PER SMACNA
S-JOINT, SLEEVE
TO DUCT
120 VAC NORMALLY CLOSED
OPERATOR/ACTUATOR
VERTICAL SMOKE DAMPER DETAIL
NO SCALE
DISCHARGE
AIR
FLEXIBLE DUCT
MAXIMUM 36 INCHES
HOT WATER COIL IN UNIT
DISCHARGE
SUPPORT FROM STRUCTURE
ON STRAP HANGERS
CONNECT PRIMARY AIR WITH 18
INCHES STRAIGHT RIGID DUCT
CONNECTED TO INLET FITTING.
VAV BOX HANGING DETAIL
NO SCALE
COIL
SUPPLY
ATC
P/T PORTS
SHUT-OFF VALVE
RETURN
UNION
MANUAL
AIR VENT
P/T PLUG
HOSE END
DRAIN VALVE
AUTOFLOW MODEL AC AUTOMATIC
FLOW CONTROL VALVE ASSEMBLY
12"-STAINLESS STEEL BRAIDED HOSE
12"-STAINLESS STEEL
BRAIDED HOSE
P/T PORTSP/T PORT
DRAIN COCK
AUTOFLOW MODEL UP
UNION/PT PLUG ASSEMBLY
CONNECTED TO COIL
THREE-WAY ELECTRIC TEMPERATURE
CONTROL VALVE BY TEMPERATURE
CONTROLS CONTRACTOR
AUTOFLOW MODEL YC
STRAINER ASSEMBLY
VAV HEATING WATER COIL PIPING DIAGRAM
AUTOFLOW MODEL UP UNION/PT
PLUG/DRAIN ASSEMBLY
CONNECTED TO COIL
8NO SCALE
SHUT-OFF VALVE
P/T PORT
SUPPLY
RETURN
UNION
P/T PORTS
AUTOFLOW MODEL AC0075
AUTOMATIC FLOW CONTROL
VALVE ASSEMBLY
AUTOFLOW MODEL YC0075
STRAINER ASSEMBLY
12"-STAINLESS STEEL
BRAIDED HOSE
12"-STAINLESS STEEL
BRAIDED HOSE
UNIT HEATER
NO SCALE 9
UNIT HEATER PIPING DIAGRAM
HOSE END DRAIN
VALVE WITH CAP
SERVICE ACCESS
DOOR (TYP.)
SUPPLY FAN ARRAY OVER
CURRENT ENCLOSURECONDENSATE DRAIN
CONNECTION
16x54 SUPPLY AIR
OPENING ON TOP UNIT
INTERNALLY ISOLATED
2x1 PLENUM FAN ARRAY
SECONDARY DX
COOLING COIL
PRIMARY DX
COOLING COIL
HOT WATER
PREHEAT COIL
4" 60% PLEATED
FILTERS
16x54 SUPPLY AIR
OPENING ON TOP UNIT
WITH FACTORY OPPOSED
BLADE DAMPER ASSEMBLY
MAGNEHELIC
PRESSURE GAUGE
2" 30% PLEATED
PRE-FILTERS
54x24 OUTSIDE AIR OPENING IN
REAR OF UNIT WITH FACTORY
OPPOSED BLADE DAMPER
ASSEMBLY INSIDE UNIT CABINET
16x54 SUPPLY AIR
OPENING ON TOP UNIT
16x54 SUPPLY
AIR OPENINGINTERNALLY ISOLATED
SUPPLY FAN ARRAY
16x54 OPPOSED BLADE
RETURN AIR DAMPER
24x54 OPPOSED BLADE
RETURN AIR DAMPER
STAINLESS STEEL
SLOPED DRAIN PIPE
BID DOCUMENTS SUBMISSION
27-M1.0 1/4" = 1'-0"1
MECHANICAL FLOOR PLAN -
COTTAGE BUILDING #27
27-M1.0.dwg
BUILDING
N.I.C.
N.I.C.
N.I.C.
BUILDING
1.
2.
3.
4.
5.
6.
7.
8.
COORDINATE ALL EQUIPMENT AND DUCTWORK WITH ARCHITECTURAL, STRUCTURAL,
PLUMBING, FIRE PROTECTION, AND ELECTRICAL.
CONTRACTOR SHALL FIELD MEASURE ALL CLEARANCES REQUIRED FOR DUCTWORK
INSTALLATION PRIOR TO FABRICATION.
ALL SUPPLY, RETURN, AND OUTSIDE INTAKE DUCTWORK SHALL BE WRAPPED. REFER
TO SPECIFICATION SECTION 23 07 00.
LOW PRESSURE FLEXIBLE SUPPLY DUCTS TO BE MAXIMUM 3'-0" IN LENGTH. DO NOT
CONNECT FLEXIBLE DUCT DIRECTLY TO DIFFUSER NECK. REFER TO DETAIL 1/27-M5.0.
ALL VAV BOXES SHALL HAVE MINIMUM 18 INCHES STRAIGHT RIGID DUCT INSTALLED AT
PRIMARY AIR INLET. DUCT SIZE SHALL BE PRIMARY INLET SIZE. REFER TO DETAIL
6/27-M5.0.
ALL PRIMARY SUPPLY DUCT UPSTREAM OF VAV BOXES SHALL BE HELICAL WOUND
SPIRAL. ALL SPIRAL DUCT TAPS AND FITTINGS SHALL BE HIGH EFFICIENCY TYPE.
FLAT OVAL DUCT DIMENSIONS ARE INDICATED AS XX/XX.
ALL SPACE TEMPERATURE SENSORS SHALL BE MOUNTED ON WALL BOX AT 48 INCHES
AFF. WALL BOX AND CONDUIT PATHWAYS TO BE PROVIDED AND INSTALLED BY
DIVISION 26.
INSTALL CONCEALED DAMPER OPERATOR IN GYP BOARD CEILING. REFER TO DETAIL
2/27-M5.0.
INSTALL BOTTOM OF SUPPLY GRILLE AT 9'-6" AFF.
MOUNT VARIABLE FREQUENCY DRIVE SERVING AHU 27-1 SUPPLY FAN ARRAY ON WALL.
VAV BOX TO BE INSTALLED EXPOSED WITHIN MECHANICAL ROOM. COORDINATE EXACT
ROUTING OF ALL MECHANICAL AND PLUMBING PIPING TO MAINTAIN SERVICE
CLEARANCE.
INSTALL BOTTOM OF OUTSIDE AIR LOUVER AT 7'-0" AFF. CONNECT FULL SIZE DUCT TO
LOUVER AND ROUTE DOWN INSIDE MECHANICAL ROOM FOR CONNECTION TO AIR
HANDLING UNIT. REFER TO SECTION 1/27-M4.0. TERMINATE DUCT TO UNIT USING
FLEXIBLE CONNECTION.
TRANSITION RETURN DUCT AS REQUIRED AND TERMINATE TO AIR HANDLING UNIT
USING FLEXIBLE CONNECTION. DIVISION 28 TO PROVIDE AND INSTALL SMOKE
DETECTOR IN RETURN DUCT AT 24 INCHES ABOVE UNIT.
EXTEND 30x36 RELIEF AIR DUCT DOWN THRU ROOF AND CONNECT TO RETURN DUCT.
INSTALL MOTORIZED RELIEF AIR DAMPER BELOW ROOF. REFER TO SECTION 1/27-M4.0.
MOUNT AIR HANDLING UNIT ON 4 INCH CONCRETE HOUSEKEEPING PAD. SECURE UNIT
TO PAD USING HILTI KWIK BOLT II ANCHORS. PAD SHALL EXTEND 6 INCHES BEYOND
EACH EDGE OF UNIT.
TRANSITION FROM AIR HANDLING UNIT OPENING TO 22/35 PRIMARY SUPPLY DUCT AND
ROUTE VERTICALLY AS SHOWN. TERMINATE DUCTWORK TO UNIT USING FLEXIBLE
CONNECTION. REFER TO SECTION 1/27-M4.0.
CONNECT 6 INCH ROUND EXHAUST DUCT TO RESIDENTIAL KITCHEN HOOD AND ROUTE
UP WITHIN STAINLESS STEEL ENCLOSURE TO ABOVE CEILING. EXTEND DUCT UP THRU
ROOF AS SHOWN. TERMINATE DUCTWORK WITH RAINCAP AT 18 INCHES ABOVE
FINISHED ROOF. MAKE ROOF PENETRATION THRU DEKTITE PREMIUM FLASHING.
EXTEND 12x10 EXHAUST DUCT UP THRU ROOF AND TERMINATE TO FAN USING
FLEXIBLE CONNECTION. TRANSITION AS REQUIRED. CONNECT 2 CONDUCTOR, 18 AWG
CONTROL WIRING TO 24V RELAY AND PULL TO VAV 27-8 CONTROLLER. RELAY
PROVIDED AND INSTALLED BY DIVISION 26.
EXTEND 4 INCH ROUND DRYER DUCT UP IN WALL AND TERMINATE THRU ROOF WITH
GOOSENECK AT 12 INCHES ABOVE FINISHED ROOF ASSEMBLY. MAKE ROOF
PENETRATION THRU CHEMCURB AND COMPLETELY FILL WITH CHEMLINK COMPOUND.
ROUTE SUPPLY AND RETURN DUCTS WITHIN ARCHITECTURAL FURRING ACROSS
OPENING AREA.
INSTALL BOTTOM OF SUPPLY GRILLE AT 9'-6" AFF. INSTALL SMOKE DAMPER DIRECTLY
BEHIND GRILLE IN WALL.
INSTALL CONCEALED DAMPER OPERATOR IN SUPPLY DUCT. PROVIDE DAMPER WITH
CABLE AND INSTALL DAMPER OPERTOR IN ADJACENT GYP BOARD CEILING.
EXTEND 12x8 EXHAUST DUCT UP THRU ROOF AND TERMINATE TO FAN USING FLEXIBLE
CONNECTION. TRANSITION AS REQUIRED. CONNECT 2 CONDUCTOR, 18 AWG CONTROL
WIRING TO 24V RELAY AND PULL TO VAV 27-8 CONTROLLER. RELAY PROVIDED AND
INSTALLED BY DIVISION 26.
INSTALL 12x12 POTTORFF MODEL XSV-845 FEMA RATED GRILLE IN CONCRETE SLAB
ABOVE CEILING. FREE AREA OF ASSEMBLY SHALL BE MINIMUM 0.4 FT2. DIRECTLY
ABOVE FEMA GRILLE, INSTALL "OUT OF PARTITION" TYPE COMBINATION FIRE/SMOKE
DAMPER TO PROTECT PENETRATION. DAMPER SLEEVE SHALL BE SECURED TO TOP OF
CONCRETE LID AND FIRE CAULKED. TRANSITION FROM DAMPERS TO DUCTWORK
ABOVE LID AND GRILLE BELOW.
INSTALL CONCEALED DAMPER OPERATOR IN EXHAUST DUCT. PROVIDE DAMPER WITH
CABLE AND INSTALL DAMPER OPERATOR IN ADJACENT GYP BOARD CEILING.
INSTALL SMOKE DAMPER IN SUPPLY DUCT AT WALL PENETRATION. INSTALL DUCT
ACCESS DOOR ABOVE GYP BOARD CEILING OUTSIDE OF GUEST TOILET 37. PROVIDE
AND INSTALL ACCESS DOOR IN CEILING TO ALLOW INSPECTION/MAINTENANCE FOR
COMBINATION FIRE/SMOKE DAMPER.
INSTALL SMOKE DAMPER IN PRIMARY SUPPLY DUCT AT WALL PENETRATION. INSTALL
DUCT ACCESS DOOR ABOVE LAY-IN CEILING IN STAFF OFFICE 9.
INSTALL SMOKE DAMPER IN RETURN DUCT AT WALL PENETRATION. INSTALL DUCT
ACCESS DOOR ABOVE LAY-IN CEILING IN STAFF OFFICE 9.
SUSPEND FAN/HEATER ASSEMBLY FROM STRUCTURE USING ALL-THREAD ROD AND
NEOPRENE ISOLATORS. CONNECT 6 INCH ROUND EXHAUST DUCT TO UNIT AND ROUTE
UP THRU ROOF. TERMINATE DUCT AT 12 INCHES ABOVE FINISHED ROOF ASSEMBLY
WITH RAIN CAP. MAKE ROOF PENETRATION THRU PREMIUM DEKTITE FLASHING.
SCALE: 1/4" = 1'-0"
COTTAGE BLDG. 27 -
MECHANICAL FLOOR PLAN
NO SCALE
KEYPLAN
D
B
G
HEA
C
F
AHU 27-1
L 27-1
M x2
36x2030x20 x2 x1 x1 x1 x1
12x8
RH 27-1
x8
12x8
CEF 27-7
CEF 27-1
x8 x8
10x10/R-1
10x10/R-110x10/R-1
10x10/R-1
10x10/R-1
10x10/R-1
10x10/R-1
22x10/R-3
22x10/R-3
10x10/R-1 10x10/R-1
10x10/R-1
10x10/R-1
22x10/R-3
22X22/R-1
SD
Ø
22Ø
SD
14/12 10Ø8Ø6Ø
6Ø 6Ø 6Ø
/12
/12
14/1212Ø 8Ø6Ø
6Ø
6Ø 6Ø
Ø
Ø
Ø
Ø
Ø
10"Ø/S-3
300 CFM
10"Ø/S-3
300 CFM10"Ø/S-3
300 CFM
10"Ø/S-3
300 CFM
CEF 27-10
CEF 27-9CEF 27-8
VAV 27-13VAV 27-12VAV 27-11VAV 27-10
x1 x8 x8
8Ø
6Ø 6Ø
8Ø
8Ø
VAV 27-4VAV 27-3VAV 27-2VAV 27-1
Ø
Ø
Ø
Ø
10"Ø/S-3
300 CFM
10"Ø/S-3
300 CFM
10"Ø/S-3
300 CFM
10"Ø/S-3
300 CFM
CEF 27-2 CEF 27-3
CEF 27-4
8"Ø/S-4
250 CFM
6Ø
Ø
8Ø 6Ø x8
8Ø
6Ø
6Ø
6Ø
10"Ø/S-3
300 CFM
10"Ø/S-3
300 CFM
10Ø
10Ø
VAV 27-8
VAV 27-5
VAV 27-6
VAV 27-7
CEF 27-5
CEF 27-6
8"Ø/S-4
250 CFM
6"Ø/S-1
50 CFM
8"Ø/S-1
200 CFM
6"Ø/S-1
75 CFM
FSD 17
FSD
x1
FSD
10x10/E-1
125 CFM
10x10/E-1
250 CFM
EF 27-1
EF 27-2
10x10/E-1
125 CFM
6"Ø/S-1
75 CFM
6"Ø/S-1
50 CFM
/16
32x10 x1
Ø
Ø
SD
SD
SD
SD
18x10/S-2
300 CFM
18x10/S-2
300 CFM
18x10/S-2
300 CFM
VAV 27-9
6"Ø/S-1
50 CFM
18x10/S-2
300 CFM
S
S x8 x6
10x10/E-1
250 CFM
8"Ø/S-3
200 CFM
FSD
10x10/E-1
100 CFM
x1 x1
6Ø
24x10 24x10/S-2
600 CFM
Ø
6"Ø/S-1
50 CFM
S
VAV 27-14
24x10/S-2
400 CFM
6Ø
VAV 27-15
9Ø x1
8Ø
8Ø10Ø (2)-8"Ø/S-1
150 CFM EACH
x2
10"Ø/S-4
400 CFM
x1
12Ø
6Ø x1 x1
12x8 x8 x1
26x16 x1 x8 x6 x8 x8
27-M4.0
S
SS
S
S
S
S
S
S S
S
S
WALL LEGEND
LINE TYPE DESCRIPTION
1-HR PARTITION
2-HR PARTITION
SMOKE SEPERATION
Ø
DATA
SUPPLIES/
EQUIP.
STOR. 18
ELEC.
S
TO
R A
G E
A
MECHANICAL
S
TO
R A
G E
A
PANTRY
CORR.
RECEIVING/STORAGE
KITCHEN
DINING
ROOM
LIVING
ROOM
FOYER
STAFF
OFFICE
TOIL.
RESIDENT
ROOM
7RESIDENT
ROOM
RESIDENT
ROOM
RESIDENT
ROOM
TOIL.
TOIL.
TOIL.
SOILED
43C
LE
A
N
CORR.
GUEST
TOIL. 37
M E
D S
S
P A
/B A
TH
S A
FE
R
O O
M
TOIL.
RESIDENT
ROOM
RESIDENT
ROOM
RESIDENT
ROOM
RESIDENT
ROOM
TOIL.
TOIL.
S O
IL
E
D
C
LE
A N
CORR.
TOIL.
RESIDENT
ROOM
SOILED
UTIL. 35
RESIDENT
ROOM
CORR.
TOIL.
CORR.
H.A.C.
S
TO
R A
G E
LAUNDRY/
SAFE
ROOM
TOIL.
STORAGE
19B
BID DOCUMENTS SUBMISSION
27-M2.0 1/4" = 1'-0"1
MECHANICAL PIPING FLOOR PLAN
- COTTAGE BUILDING #27
27-M2.0.dwg
BUILDING
N.I.C.
N.I.C.
N.I.C.
BUILDING
1. COORDINATE ALL EQUIPMENT AND PIPING WITH ARCHITECTURAL, STRUCTURAL,
PLUMBING, FIRE PROTECTION, AND ELECTRICAL.
ROUTE ALL PIPING AS HIGH AS POSSIBLE.
HEATING WATER RUNOUTS TO TERMINAL UNITS ARE 3/4 INCH, UNLESS SPECIFICALLY
NOTED OTHERWISE.
DROP OUT OF BOTTOM OF MAINS FOR RUNOUTS TO PREVENT AIR ENTRAPMENT IN
PIPING SYSTEM.
REFER TO DETAIL 8/27-M5.0 FOR VAV BOX HEATING WATER PIPING CONNECTIONS.
ALL REFRIGERANT PIPING SHALL BE TYPE ACR HARD DRAWN COPPER. ALL FITTINGS
SHALL BE LONG RADIUS TYPE.
ALL REFRIGERANT SUCTION PIPING SHALL BE INSULATED USING CLOSED CELL
ARMAFLEX INSULATION. REFER TO SPECIFICATION SECTION 23 07 00.
SUSPEND ALL REFRIGERANT PIPING FROM STRUCTURE USING TRAPEZE SUPPORTS
AND CUSH-A-CLAMPS.
2.
3.
4.
5.
6.
7.
8.
9.
15 EXTEND 3/4 INCH HWS AND HWR PIPING FOR TERMINATION TO HEATING WATER
REHEAT COIL ON VAV 27-3 AND VAV 27-4.
MOUNT FAN COIL UNIT ABOVE DOORWAY.
EXTEND REFRIGERANT LIQUID AND SUCTION PIPING DOWN THRU ROOF AND
ROUTE AS SHOWN FOR CONNECTION TO FAN COIL UNIT. TERMINATE PIPING TO
FAN COIL UNIT USING RECTORSEAL NO-KINK FLEXIBLE CONNECTORS.
EXTEND REFRIGERANT CIRCUIT #1 AND CIRCUIT #2 PIPING DOWN THRU ROOF FROM
CU 27-1. INSTALL OIL TRAP IN BOTTOM OF VERTICAL RISER OF EACH LIQUID LINE.
REFER TO 27-M3.0 FOR CONTINUATION.
EXTEND REFRIGERANT CIRCUIT #1 AND CIRCUIT #2 PIPING DOWN THRU ROOF FROM
CU 27-2. INSTALL OIL TRAP IN BOTTOM OF VERTICAL RISER OF EACH LIQUID LINE.
REFER TO 27-M3.0 FOR CONTINUATION.
ROUTE ALL REFRIGERANT AND HEATING WATER PIPING WITHIN ARCHITECTURAL
FURRING ACROSS FOYER 10.
EXTEND REFERIGERANT CIRCUIT #1 AND CIRCUIT #2 FOR TERMINATION TO
SECONDARY DX COOLING COIL IN AHU 27-1. PROVIDE OIL TRAP IN LIQUID LINE RISERS
AND TERMINATION TO EACH CIRCUIT.
EXTEND REFERIGERANT CIRCUIT #1 AND CIRCUIT #2 FOR TERMINATION TO PRIMARY
DX COOLING COIL IN AHU 27-1. PROVIDE OIL TRAP IN LIQUID LINE RISERS AND
TERMINATION TO EACH CIRCUIT.
INSTALL MANUAL AIR VENTS FROM TOP OF PIPING. REFER TO DETAIL 7/27-M5.0.
CONNECT 1-1/2 INCH HWS AND HWR PIPING TO AIR HANDLING UNIT COIL. REFER TO
DETAIL 10/27-M5.0 FOR PIPING CONNECTIONS.
CONNECT 3/4 INCH HWS AND HWR PIPING TO UNIT HEATER. REFER TO DETAIL
9/27-M5.0 FOR PIPING CONNECTIONS.
RACK HEATING WATER PUMPSON WALL IN STACKED CONFIGURATION. HWP 27-1 SHALL
BE 5'-0" AFF AND HWP 27-2 SHALL BE 3'-0" AFF. REFER TO HEATING WATER SYSTEM
PIPING DIAGRAM 14/27-M5.0.
INLINE TANGENTIAL AIR SEPARATOR MOUNTED IN PIPING. REFER TO HEATING WATER
SYSTEM PIPING DIAGRAM 14/27-M5.0.
MOUNT HEATING WATER SYSTEM EXPANSION TANK ON 4 INCH CONCRETE
HOUSEKEEPING PAD. REFER TO HEATING WATER SYSTEM PIPING DIAGRAM 14/27-M5.0
FOR ALL PIPING CONNECTIONS.
MOUNT HEATING WATER SYSTEM BYPASS FILTER/FEEDER ON 4 INCH CONCRETE
HOUSEKEEPING PAD. REFER TO HEATING WATER SYSTEM PIPING DIAGRAM 14/27-M5.0
FOR ALL PIPING CONNECTIONS.
CONNECT 2 INCH HWS AND HWR PIPING TO BOILER. INSTALL BOILER PUMP IN VERTICAL
HWR PIPING. REFER TO HEATING WATER SYSTEM PIPING DIAGRAM 14/27-M5.0 FOR ALL
PIPING CONNECTIONS.
MOUNT BOILER ON 4 INCH CONCRETE HOUSEKEEPING PAD. PAD SHALL EXTEND 6
INCHES BEYOND OUTER EDGES OF BOTH BOILERS.
REFER TO MECHANICAL SCHEDULES FOR REFRIGERANT PIPING SIZES.
CONTRACTOR SHALL PROVIDE A SEPARATE LINE ITEM FOR DELETION
OF PURCHASE AND INSTALLATION OF CU 27-2 AND ALL ASSOCIATED
REFRIGERANT PIPING AS PART OF DEDUCTIVE ALTERNATE #5.
SCALE: 1/4" = 1'-0"
COTTAGE BLDG. 27 -
MECHANICAL PIPING
FLOOR PLAN
NO SCALE
KEYPLAN
D
B
G
HEA
C
F
AHU 27-1
HWP 27-1
HWP 27-2
BOILER 27-2
BOILER 27-1
HW
R
HW
R
HW
S
HW
S
UH 27-1
HWS
HWR
HW
S
HW
R
RL
/R
S-
RL
/R
S-
RL
/R
S-
RL
/R
S-
HWS
HWR
RL/RS-1
RL/RS-2
RL/RS-1
RL/RS-2
HWS
HWR
RL/RS-1
RL/RS-2
RL/RS-1
RL/RS-2
HW
S
HW
R
RL
/R
S-
RL
/R
S-
RL
/R
S-
RL
/R
S-
HWR
HWS
HWR
HW
S
HW
R
HWS
HWR
2"
3/4" 2"
1-1/2"
3/4"
1-1/2"
1-1/2"
1-1/4"
3/4"
1"
3/4" 3/4"3/4" 3/4"
1"
3/4"
3/4"
3/4" 3/4"
1"
HW
S
HW
R
3/4"
3/4"
3/4"
3/4"
2" 1-1/2"
1-1/2" 3/4"
VAV 27-13
VAV 27-12
VAV 27-11VAV 27-10
VAV 27-4VAV 27-3VAV 27-2VAV 27-1
VAV 27-8
VAV 27-5
VAV 27-6
VAV 27-7
VAV 27-9
VAV 27-14
VAV 27-15
T
FC 27-A
3/4"
DATA
SUPPLIES/EQUIP.
STOR. 18
ELEC.
STORAGE
18A
MECHANICAL
S
TO
R A
G E
A
PANTRY
CORR.
RECEIVING/STORAGE
KITCHEN
DINING
ROOM
LIVING
ROOM
FOYER
STAFF
OFFICE
TOIL.
RESIDENT
ROOM
7RESIDENT
ROOM
RESIDENT
ROOM
RESIDENT
ROOM
TOIL.
TOIL.
4 TOIL.
S O
IL
E
D
C
LE
A N
CORR.
GUEST
TOIL. 37
MEDS
SPA/BATH/
SAFE ROOM
TOIL.
RESIDENT
ROOM
RESIDENT
ROOM
RESIDENT
ROOM
25RESIDENT
ROOM
TOIL.
TOIL.
S O
IL
E
D
C
LE
A N
CORR.
TOIL.
28RESIDENT
ROOM
SOILED
UTIL. 35
RESIDENT
ROOM
CORR.
TOIL.
CORR.
H.A.C.
33STORAGE
LAUNDRY/
SAFE
ROOM
TOIL.
STORAGE
19B
BID DOCUMENTS SUBMISSION
27-M3.0 1/4" = 1'-0"1
MECHANICAL ROOF PLAN -
COTTAGE BUILDING #27
27-M3.0.dwg
BUILDING
N.I.C.
N.I.C.
N.I.C.
BUILDING
1.
2.
3.
4.
COORDINATE ALL EQUIPMENT AND PIPING WITH ARCHITECTURAL, STRUCTURAL,
PLUMBING, FIRE PROTECTION, AND ELECTRICAL.
ALL REFRIGERANT PIPING SHALL BE TYPE ACR HARD DRAWN COPPER. ALL FITTINGS
SHALL BE LONG RADIUS TYPE.
ALL REFRIGERANT SUCTION PIPING SHALL BE INSULATED USING CLOSED CELL
ARMAFLEX INSULATION. COVER INSULATION ON ROOF WITH RIGID ALUMINUM
JACKETING AND PREFORMED FITTING COVERS. REFER TO SPECIFICATION SECTION
23 07 00.
REFER TO MECHANICAL SCHEDULES FOR REFRIGERANT PIPING SIZES.
CONTRACTOR SHALL PROVIDE A SEPARATE LINE ITEM FOR DELETION OF PURCHASE
AND INSTALLATION OF CU 27-2 AND ALL ASSOCIATED REFRIGERANT PIPING AS PART
OF DEDUCTIVE ALTERNATE #5.
ROUTE REFRIGERANT PIPING DOWN THRU ROOF. MAKE ROOF PENETRATIONS THRU
SINGLE CHEMCURB AND COMPLETELY FILL WITH CHEMLINK COMPOUND. REFER TO
27-M2.0 FOR CONTINUATION.
MOUNT CONDENSING UNIT IN THYBAR MODEL TC-3 (OR APPROVED EQUAL) ROOF CURB
WITH CAP. SECURE UNIT TO CURB.
MOUNT CONDENSING UNIT ON (2) 72(W)x18(H) THYBAR MODEL TEMS-3 (OR APPROVED
EQUAL) SUPPORTS. REFER TO DETAIL 4/27-M5.0.
5.
SCALE: 1/4" = 1'-0"
COTTAGE BLDG. 27 -
MECHANICAL ROOF PLAN
NO SCALE
KEYPLAN
EF 27-1
EF 27-2
CU 27-1
CU 27-2
RL
/R
S-
RL
/R
S-
RL
/R
S-
RL
/R
S-
CU 27-A
RH 27-1
BID DOCUMENTS SUBMISSION
27-M4.0 27-M4.0.dwg
SCALE: 1/4" = 1'-0"
COTTAGE BLDG. 27 -
MECHANICAL DETAILS AND
SCHEDULES
AIR HANDLING UNIT - SECTION
SCALE: 1/2" = 1'-0"
4" CONCRETE
HOUSEKEEPING
PAD
FLEXIBLE
CONNECTION
/35
22"Ø SPIRAL
SUPPLY DUCT
BEYOND24x36 x5
M
FLEXIBLE
CONNECTION
MOTORIZED RETURN
AIR DAMPER
36x24 RETURN
DUCT BEYOND
OUTSIDE AIR
INTAKE LOUVER
L 27-1
MOTORIZED
OUTSIDE AIR
DAMPER
7'-0"
MOTORIZED RELIED
AIR DAMPER
RELIEF AIR
HOOD RH 27-1
RETURN DUCT
SMOKE DETECTOR
BY DIVISION 28
SD
SA
DISCHARGE AIR
TEMP
HW VALVE
HWR
HWS
PRIMARY AIR
INLET
INLET AIRFLOW
SENSOR
(BY MFG.)
M
VAV BOX
DAMPER
S
SPACE TEMP
SENSOR
TYPICAL SINGLE DUCT VAV BOX WITH HW REHEAT CONTROL SCHEMATIC
NO SCALE
HE
AT
IN
G
CO
IL
BOILER 27-1 BOILER 27-2
HWS
HWS
T
HWR
BOILER LOOP
OUTDOOR
TEMPERATURE
SENSOR
MAIN EMS CONTROLLER
MOUNTED IN MECHANICAL
PENTHOUSE
2C/18AWG
1. TEMPERATURE CONTROLS CONTRACTOR SHALL PROVIDE AND INSTALL ALL CONTROL WIRING AND CONDUIT. ALL CONTROL WIRING SHALL BE ROUTED IN 1/2
INCH EMT CONDUIT WITH COMPRESSION FITTINGS INSIDE THE MECHANICAL PENTHOUSE.
SECURE ALL CONDUIT TO INSIDE OF WALL/CEILING OF MECHANICAL PENTHOUSE UNIT. ROUTE ALL CONDUIT PARALLEL AND PERPENDICULAR TO UNIT LINES.
ALL CONTROL WIRING RUNS BETWEEN TERMINATION POINTS SHALL BE IN ONE PIECE WITHOUT SPLICES.
MOUNT ALL DEVICES AND TERMINATE ALL WIRING AT EACH DEVICE.
REFER TO SPECIFICATION SECTION 15940 FOR HEATING WATER SYSTEM OPERATION.
MOUNT LOCHINVAR OUTDOOR AIR TEMPERATURE SENSOR ON NORTH FACE OF MECHANICAL PENTHOUSE UNIT. SENSOR SHALL BE MOUNTED BENEATH FIELD FABRICATED GALVANIZED STEEL SHROUD TO SHIELD FROM DIRECT SUNLIGHT. PAINT SHROUD TO MATCH MECHANICAL PENTHOUSE.
PULL 2 CONDUCTOR, 18 AWG CONTROL WIRING FROM OUTDOOR TEMPERATURE SENSOR TO LEAD BOILER TERMINAL STRIP.
PULL 2 CONDUCTOR, 18 AWG CONTROL WIRING FROM BUILDING EMS CONTROL PANEL, MOUNTED IN MECHANICAL PENTHOUSE, TO BOILER ALARM CONTACTS
ON LEAD BOILER TERMINAL STRIP.
PULL 2 CONDUCTOR, 18 AWG CONTROL WIRING FROM BUILDING EMS CONTROL PANEL, MOUNTED IN MECHANICAL PENTHOUSE, TO BOILER ENABLE/DISABLE
CONTACTS ON LEAD BOILER TERMINAL STRIP.
INSTALL LOCHINVAR PROVIDED TEMPERATURE SENSOR IN WELL AND PULL 2 CONDUCTOR, 18 AWG CONTROL WIRING FROM SENSOR AND TERMINATE TO LEAD
BOILER.
INSTALL EMS TEMPERATURE SENSOR IN WELL AND PULL 2 CONDUCTOR, 18AWG CONTROL WIRING TO MAIN EMS CONTROL PANEL.
PULL 18 AWG SHIELDED TWISTED PAIR WIRING FROM LEAD BOILER AND TERMINATE AT EACH BOILER IN DAISY CHAIN CONFIGURATION.
PULL 2 CONDUCTOR, 18 AWG CONTROL WIRING, IN DAISY CHAIN CONFIGURATION, FROM OUTDOOR TEMPERATURE SENSOR TERMINALS IN BOILER 27-1 AND
TERMINATE TO BOILER 27-2.
PULL 2 CONDUCTOR, 18 AWG CONTROL WIRING, IN DAISY CHAIN CONFIGURATION, FROM ENABLE/DISABLE TERMINALS IN BOILER 27-1 AND TERMINATE TO
BOILER 27-2.
HEATING WATER SYSTEM CONTROL WIRING SCHEMATIC
NO SCALE
2.
3.
4.
5.
T
T
AIR HANDLING UNIT - SECTION
SCALE: 1/2" = 1'-0"
NO SCALE 4
AHU 27-1 CONTROL SCHEMATIC
M
M
M
HIGH
STATIC
DISCHARGE
AIR TEMP
DUCT STATIC
PRESSURE
RETURN AIR
TEMP
RETURN AIR
% RH
OUTSIDE AIR
TEMP
OUTSIDE AIR
% RH
MIXED
AIR TEMP
HWR
HWS
HE
AT
IN
G
W
AT
ER
C
OI
L
PR
IM
AR
Y
DX
C
OO
LIN
G
CO
IL
SE
CO
ND
AR
Y
DX
C
OO
LIN
G
CO
IL
FAN
S/S
FAN
SPEED
VFD
SM
OK
E
DE
TE
CT
OR
MECHANICAL DESIGN CONDITIONS
SUMMER OUTSIDE DESIGN - DEG F (DB) 105
SUMMER OUTSIDE DESIGN - DEG F (WB) 70
SUMMER INSIDE DESIGN - DEG F (DB) 72
SUMMER INSIDE DESIGN - % RH 40
WINTER OUTSIDE DESIGN - DEG F (DB) 10
WINTER INSIDE DESIGN - -DEG F (DB) 68
MAIN AIR UNIT COOLING DEMAND - TONS 30
MIN FRESH AIR REQUIRED - CFM 2,000
CONNECTED HEATING DEMAND - BTU/HR 500
DOMESTIC COLD WATER DEMAND - GPM 90
SANITARY DRAINAGE - DFU 98
AIR DISTRIBUTION SCDHEULE
MARK TYPE LOCATION FINISH FRAME EXAMPLE: PRICE INDUSTRIES
S-1 SUPPLY CEILING WHITE LAY-IN SMD, 12x12, AMF FRAME
S-2 SUPPLY SIDEWALL WHITE SURFACE 325
S-3 SUPPLY CEILING WHITE LAY-IN SMD, 24x24, AMF FRAME
S-4 SUPPLY CEILING WHITE LAY-IN SMD, 24x24
R-1 RETURN CEILING WHITE LAY-IN 80, AMF FRAME
R-2 RETURN CEILING WHITE LAY-IN 80, 24x24
R-3 RETURN CEILING WHITE LAY-IN 80, 24x12
E-1 EXHAUST CEILING WHITE LAY-IN 80, AMF FRAME
NOTES: 1. COORDINATE FRAME STYLE WITH CEILING LAYOUT.
BOILER SCHEDULE
MARK INPUT (MBH) OUTPUT (MBH) FUEL TURNDOWN RATIO EFFICIENCY TYPE ELECTRICAL EXAMPLE: LOCHINVAR
BOILER 27-1 500.0 470.0 NATURAL GAS 5:1 94% CONDENSING 120/1/60 KBN501
BOILER 27-2 500.0 470.0 NATURAL GAS 5:1 94% CONDENSING 120/1/60 KBN501
NOTES: 1. BOILERS SHALL BE RATED FOR USE AT ELEVATION OF 2450 FEET.
2. PROVIDE BOILERS WITH CONDENSATE NEUTRALIZATION KIT, CONCENTRIC VENT KIT, AND BMS GATEWAY.
CONDENSING UNIT SCHEDULE
MARK SERVES
CAPACITY
(MBH)
CIRCUITS
(QTY) AMBIENT EER
REFRIGERANT PIPING SIZES ELECTRICAL DATA
EXAMPLE: AAON
LIQUID SUCTION SERVICE MCA MOCP
CU 27-1 AHU 27-1 266.8 2 105 10.1 (2) 5/8 (2) 1-3/8 208/3/60 130.0 175 CFA-025
CU 27-2 AHU 27-1 266.8 2 105 10.1 (2) 3/4 (2) 1-3/8 208/3/60 130.0 175 CFA-025
NOTES: 1. UNITS SELECTED AT ELEVATION OF 2450 FEET.
2. PROVIDE UNITS WITH FACTORY MOUNTED DISCONNECT AND POWERED GFCI RECEPTACLE.
3. LEAD COMPRESSOR SHALL BE VARIABLE CAPACITY SCROLL TYPE.
AIR HANDLING UNIT SCHEDULE
MARK
SUPPLY FAN DATA COOLING COIL DATA REHEAT COIL DATA
ELECTRICAL EXAMPLE:
MAX CFM MIN CFM MIN OUTSIDE AIR MATRIX TSP (ON. WG) HP CFM TOTAL (MBH) SENSIBLE (MBH) EAT (DB/WB) CIRCUITS ROWS/FPI CFM EAT LAT EWT GPM MAX WPD (FT) ROWS/FPI
AHU 27-1 6,800 4,500 2,000 1x2 4.0 (2) 4 6,800 266.8 199.7 81.7/65.4 2 6/10 6,800 50 81.6 160 15.0 3.8 1/8 208/3/60 TEMTROL
NOTES: 1. UNIT SELECTED AT ELEVATION OF 2450 FEET.
2. PROVIDE UNIT WITH VAPOR PROOF LIGHT FIXTURES IN EACH ACCESSIBLE SECTION OF UNIT, FACTORY WIRED TO EXTERIOR SWITCH. LIGHTING CIRCUIT SHALL BE 120/1/60.
3. REFER TO DETAILS 12/27-M5.0 AND 13/27-M5.0 FOR UNIT CONFIGURATIONS.
HOT WATER UNIT HEATER SCHEDULE
MARK CFM HP CAPACITY (MBH) MAX WPD (FT) EWT EAT LAT GPM ELECTRICAL EXAMPLE: MODINE
UH 27-1 730 1/12 19.2 0.1 160 60 83 1.25 115/1/60 HSB47
NOTES: 1. UNIT SELECTED AT ELEVATION OF 2450.
2. PROVIDE UNIT WITH FINGER-PROOF FAN GUARD.
PUMP SCHEDULE
MARK SERVES GPM HEAD (FT) HP RPM TYPE ELECTRICAL EXAMPLE: GRUNDFOS
BP 27-1 BOILER-1 32 15 1/2 1750 INLINE CENTRIFUGAL 115/1/60 UPS32-80
BP 27-2 BOILER-2 32 15 1/2 1750 INLINE CENTRIFUGAL 115/1/60 UPS32-80
HWP 27-1 HEATING WATER SYSTEM 36 30 3/4 1750 INLINE CENTRIFUGAL 115/1/60 UPS32-160
HWP 27-1 HEATING WATER SYSTEM 36 30 3/4 1750 INLINE CENTRIFUGAL 115/1/60 UPS32-160
CEILING EXHAUST FAN SCHEDULE
MARK CFM HEATER INPUT
ELECTRICAL
EXAMPLE: BROAN
SERVICE MCA MOCP
CEF 27-1 100 1.5 KW 120/1/60 13.5 20 QTX110HFLT
CEF 27-2 100 1.5 KW 120/1/60 13.5 20 QTX110HFLT
CEF 27-3 100 1.5 KW 120/1/60 13.5 20 QTX110HFLT
CEF 27-4 100 1.5 KW 120/1/60 13.5 20 QTX110HFLT
CEF 27-5 100 1.5 KW 120/1/60 13.5 20 QTX110HFLT
CEF 27-6 100 1.5 KW 120/1/60 13.5 20 QTX110HFLT
CEF 27-7 100 1.5 KW 120/1/60 13.5 20 QTX110HFLT
CEF 27-8 100 1.5 KW 120/1/60 13.5 20 QTX110HFLT
CEF 27-9 100 1.5 KW 120/1/60 13.5 20 QTX110HFLT
CEF 27-10 100 1.5 KW 120/1/60 13.5 20 QTX110HFLT
NOTES: 1. PROVIDE FANS WITH MODEL 77DW 3 WAY CONTROL SWITCH.
SINGLE DUCT TERMINAL UNIT SCHEDULE
MARK MODEL
PRICE
INLET
DIAMETER
CFM HEATING WATER COIL DATA
MAX MIN CFM MBH EAT LAT GPM EWT ROWS
VAV 27-1 SDV5 6" 300 150 200 11.1 55.0 109.1 1.0 160 2
VAV 27-2 SDV5 6" 300 150 200 11.1 55.0 109.1 1.0 160 2
VAV 27-3 SDV5 6" 300 150 200 11.1 55.0 109.1 1.0 160 2
VAV 27-4 SDV5 6" 300 150 200 11.1 55.0 109.1 1.0 160 2
VAV 27-5 SDV5 6" 300 150 200 11.1 55.0 109.1 1.0 160 2
VAV 26-6 SDV5 6" 300 150 200 11.1 55.0 109.1 1.0 160 2
VAV 26-7 SDV5 6" 300 150 150 8.1 55.0 107.6 0.5 160 2
VAV 27-8 SDV5 10" 850 400 600 28.6 55.0 101.9 2.5 160 2
VAV 27-9 SDV5 12" 1250 400 600 34.6 55.0 111.8 2.5 160 2
VAV 27-10 SDV5 6" 300 150 200 11.1 55.0 109.1 1.0 160 2
VAV 27-11 SDV5 6" 300 150 200 11.1 55.0 109.1 1.0 160 2
VAV 27-12 SDV5 6" 300 150 200 11.1 55.0 109.1 1.0 160 2
VAV 27-13 SDV5 6" 300 150 200 11.1 55.0 109.1 1.0 160 2
VAV 27-14 SDV5 12" 1050 350 600 34.6 55.0 111.8 2.5 160 2
VAV 27-15 SDV5 9" 700 250 250 11.0 55.0 98.1 1.5 160 1
NOTES: 1. UNITS SELECTED AT ELEVATION OF 2450 FEET.
2. UNITS SHALL HAVE THIRD PARTY DDC CONTROLS FIELD INSTALLED.
3. PROVIDE UNITS WITH PROTECTIVE SHROUD TO HOUSE DDC COMPONENTS.
4. REFER TO PIPING DIAGRAM 8/27-M5.0 FOR HW COIL CONNECTIONS.
FAN SCHEDULE
MARK CFM SP HP RPM TYPE DRIVE ELECTRICAL MAX. SONES EXAMPLE: COOK
EF 27-1 500 0.5 1/4 1451 PRV DIRECT 115/1/60 7.9 ACED-ED 101C17DEC
EF 27-2 350 0.5 1/4 1452 PRV DIRECT 115/1/60 7.2 ACED-ED 100C17DEC
NOTES: 1. FANS SELECTED AT ELEVATION OF 2450 FEET.
2. PROVIDE FANS WITH 14 INCH FACTORY ROOF CURB, WIRED DISCONNECT SWITCH, AND BACKDRAFT DAMPER.
3. PROVIDE FAN WITH FACTORY MOUNTED SPEED CONTROLLER.
LOUVER SCHEDULE
MARK TYPE SIZE (WxHxD) FIRE AREA (FT²) FINISH EXAMPLE: POTTORFF
L 27-1 OUTSIDE AIR 54x48x6 10.4 ANODIZED EFD-637
NOTES: 1. PROVIDE WITH EXTERIOR FLANGE FRAME AND INSECT SCREEN.
2. ARCHITECT TO SELECT COLOR.
4" CONCRETE
HOUSEKEEPING
PAD
FLEXIBLE
CONNECTION
/35
22"Ø SPIRAL
SUPPLY DUCT
BEYOND24x36 x5
M
FLEXIBLE
CONNECTION
MOTORIZED RETURN
AIR DAMPER
36x24 RETURN
DUCT BEYOND
OUTSIDE AIR
INTAKE LOUVER
L 27-1
MOTORIZED
OUTSIDE AIR
DAMPER
7'-0"
MOTORIZED RELIED
AIR DAMPER
RELIEF AIR
HOOD RH 27-1
DUCTLESS SPLIT SYSTEM SCHEDULE
MARK LOCATION
NOMINAL COOLING
CAPACITY (MBH)
REFRIGERANT PIPING SIZES ELECTRICAL DATA EXAMPLE: DAIKIN
LIQUID SUCTION INDOOR UNIT OUTDOOR UNIT INDOOR UNIT OUTDOOR UNIT
FC 27-A/CU 27-A DATA 16 12.0 1/4 3/8 208/1/60 208/1/60 FTX12NMVJU RX12NMVJU
NOTES: 1. PROVIDE INDOOR UNIT WITH HARDWIRED THERMOSTAT AND MODEL DACA-CP1-1 INTERNAL CONDENSATE PUMP.
RETURN DUCT
SMOKE DETECTOR
BY DIVISION 28
SD
OUTSIDE
AIR
RELIEF AIR
RETURN
AIR
SUPPLY
AIR
FILTER
STATUS
BID DOCUMENTS SUBMISSION
27-M5.0 27-M5.0.dwg
SCALE: 1/4" = 1'-0"
COTTAGE BLDG. 26 -
MECHANICAL DETAILS
AHU 27-1 DETAIL - PLAN VIEW
NO SCALE
SERVICE ACCESS
DOOR (TYP.)
SUPPLY FAN ARRAY OVER
CURRENT ENCLOSURE CONDENSATE DRAIN
CONNECTION
16x54 SUPPLY AIR
OPENING ON TOP UNIT
INTERNALLY ISOLATED
2x1 PLENUM FAN ARRAY
SECONDARY DX
COOLING COIL
PRIMARY DX
COOLING COIL
HOT WATER
PREHEAT COIL
4" 60% PLEATED
FILTERS
16x54 SUPPLY AIR
OPENING ON TOP UNIT
WITH FACTORY OPPOSED
BLADE DAMPER ASSEMBLY
MAGNEHELIC
PRESSURE GAUGE
2" 30% PLEATED
PRE-FILTERS
54x24 OUTSIDE AIR OPENING IN
REAR OF UNIT WITH FACTORY
OPPOSED BLADE DAMPER
ASSEMBLY INSIDE UNIT CABINET
16x54 SUPPLY AIR
OPENING ON TOP UNIT
AHU 27-1 DETAIL - ELEVATION
NO SCALE
COIL
NO SCALE 10
AIR HANDLING UNIT HEATING WATER COIL PIPING DIAGRAM
RE
TU
RN
AT
C
MANUAL AIR VENT
AUTOFLOW MODEL
UP UNION/PT PORT
ASSEMBLY
AUTOFLOW MODEL UP
DRAIN/PT PORT ASSEMBLY
CONNECTION TO COILGAS COK
P/T PORT
P/T PORT
SU
PP
LY
SHUT OFF VALVE SHUT OFF VALVE
P/T PORTS P/T PORTS
THREE-WAY ELECTRIC
TEMPERATURE CONTROL
VALVE BY TEMPERATURE
CONTROLS CONTRACTOR
AUTOFLOW MODEL AC
AUTOMATIC FLOW CONTROL
VALVE ASSEBLY
AUTOFLOW MODEL YC
STRAINER ASSEMBLY
HOSE END
DRAIN VALVE
CEILING DIFFUSER CONNECTION DETAIL
NO SCALE 1
NOTE: SUPPLY GRILLES SHALL HAVE RIGID
ELBOWS. FLEXIBLE DUCT CONNECTED DIRECTLY
TO DIFFUSER IS PROHIBITED.
FLEXMASTER STOD
SIDE TAKE-OFF WITH
DAMPER
1-1/2" STAND-OFF
BRACKET ASSEMBLY
MANUAL LOCKING
QUADRANT W/DEGREE
GRADUATIONS
MOLDED NYLON
SLEEVE-TYPE
INTERMEDIATE BEARING
MOLDED NYLON SLEEVE-
TYPE END BEARINGS
TYPICAL CEILING MOUNTED
SUPPLY DIFFUSER
FLEXIBLE DUCT
(MAXIMUM 3')
S.A. DUCT
RIGID ELBOW
CEILING
3/8" SQUARE
SHAFT
DUCT
7/8" CHANNEL IRON METAL
LOCK NUT
COVER
2x4 WOOD BLOCKING.
3/8" SQUARE SHAFT
SPRING WASHER
MITER GEARS
ALLEN SCREWS
PINS
BUTTERFLY DAMPER
CONCEALED DAMPER ACTUATOR DETAIL
NO SCALE
GYP BOARD
CEILING
EXHAUST FAN
EXHAUST DUCT
VARIES
ROOF
BACKDRAFT DAMPER
CANT STRIP
FLASHING
EXHAUST FAN MOUNTING DETAIL
NO SCALE
COUNTER FLASHING
BY ROOFING
SUBCONTRACTOR
FACTORY
FABRICATED CURB
16 GA. FORMED CHANNEL CURB ALL SIDES
3/4" PLYWOOD DECKING
22 GA. GALV. SHEET METAL
CANT STRIP
18 GA. "Z" CHANNEL SUPPORT…