These are comprehensive architectural and engineering design documents for a Design/Construct Sterile Processing Service project at the Omaha VA Medical Center. The 25-sheet technical drawing set includes detailed electrical, fire alarm, fire suppression, and architectural plans for a multi-level medical facility addition, specifically focusing on levels 1-3 of the building. The documents provide extensive technical specifications for electrical systems, including power distribution schematics, lighting plans, special systems routing, telecommunications details, and fire protection requirements. Key technical elements include medium voltage electrical service, zone control valve assemblies for fire sprinkler systems, specific sprinkler protection requirements for different occupancy types, and comprehensive fire alarm system integration with existing infrastructure. The design is for the Department of Veterans Affairs and involves intricate coordination across multiple engineering disciplines to support a sterile processing service area.
View the file
Other files for this federal contract opportunity
Show all 36
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AT CONTRACTOR OPTION GFCI BREAKERS CAN BE USED
FOR HOMERUNS THAT HAVE MORE THAN ONE GFCI
REQUIREMENT. PARALLELING GFCI BREAKERS IS NOT
ALLOWED. EACH GFCI DEVICE SHOWN MUST BE
DEDICATED DEVICE, OR ON GFCI PROTECTED HOMERUN.
GENERAL NOTE
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
16.2330.A08
11/23/2020 KABWEW
4101 Woolworth Ave #4199 Omaha, Ne 68105Omaha VA Medical Center
Design/Construct Sterile Processing Service - Omaha VA Medical Center
CONSTRUCTION DOCUMENTS
FOURFRONT
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
TERRASITE DESIGN
1635 DEADWOOD AVENUE
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 791-1736
COMPLIANCY REVIEW INCLUDED
PANEL SCHEDULES CONTINUED
E-002 116 143119
SCHEDULE OF EQUIPMENT DISCONNECTS
DISCONNECTCONNECTED LOAD
EQUIPMENT
PH MFR. CATALOG NO. SIZE
NOTES
POLESVOLTS
NOTES:
1. DISCONNECT ENCLOSURE TO BE NEMA 3R MIN RATED.
2. NEW HEAVY DUTY FUSED DISCONNECTS ARE TO BE PROVIDED FOR NEW CONDENSING UNITS CU-1 AND CU-2.
3. NEW MOTOR COMBINATION STARTERS ARE TO BE PROVIDED FOR NEW CHILLERS CHR-1 AND CHR-2.
4. NEW MOTOR COMBINATION STARTERS ARE TO BE PROVIDED FOR NEW COOLING TOWER PUMPS CTP-1 AND CTP-2.
5. NEW HEAVY DUTY DISCONNECTS ARE TO BE PROVIDED FOR NEW COOLING TOWERS ACCH-1 AND ACCH-2.
6. NEW MOTOR COMBINATION STARTERS ARE TO BE PROVIDED FOR NEW CHILLED WATER PUMPS CHWP-1 AND CHWP-2.
7. POWER FOR THE INDOOR EVAPORATOR EV-1 IS PROVIDED BY OUTDOOR CONDENSING UNIT. COORDINATE POWER AND WIRING CONNECTIONS WITH
MANUFACTURER'S WRITTEN INSTRUCTIONS.
TYPE
FUSE
MCAHP W FLA TYPE
CU-1, CU-2 3 208 SQUARE D 100 3HEAVY DUTY FUSED 98- - -
HWP-1 1 208 2-.75 - -
UH-1,2,3,4 1 120-1/20 - -
AHU-1 23.13- - 18.5
AHU-2 SUPPLY 11.75- - 9.4
CT-1, CT-2 (FANS) 3 480-7.5 - 14
EF-1 -7-1/2 - 11
EF-2 -1/4 - 1.1
1,5
CARTRIDGE CLASS R
3 480 SQUARE D 20A 3
3 208 SQUARE D 4A 3GENERAL DUTY FUSED
CARTRIDGE CLASS R
CARTRIDGE CLASS R
SQUARE D 25 3(2) HEAVY DUTY FUSED CARTRIDGE CLASS R
3 480
3 480
SQUARE D H361NRB 40 3HEAVY DUTY FUSED CARTRIDGE CLASS R
SQUARE D H361NRB 20 3HEAVY DUTY FUSED CARTRIDGE CLASS R
COOPER BP/SSU 1.5A 1 -FUSESTAT EDISON BASE CLASS T
VH323NRB
D321N
1 120-- 40 - COOPER BP/SSU 0.5A 1 -FUSESTAT EDISON BASE CLASS T
1 120-- 40 - COOPER BP/SSU 0.5A 1 -FUSESTAT EDISON BASE CLASS T
VAV-5,6,7,8,9,20,21,22, 23
AHU-2 RETURN 5.25- - 4.2 3 480 SQUARE D H361NRB 15 3HEAVY DUTY FUSED CARTRIDGE CLASS R
H361NRBHEAVY DUTY FUSED
VV-1E,2E,3E,4E,10E,11E,12E,13E,
14E,15E,16E,17E,18E,19E,24E,1S, 2S,3S,4S,10S,11S,12S,13S,14S,15S, 16S,17S,18S,19S,24S
CP-1 1 208 SQUARE D 16A 2GENERAL DUTY FUSED-1/2 - - CARTRIDGE CLASS RD321N
SQUARE D 25A(2) COMBO STARTER CARTRIDGE CLASS R8538CASP4
CHWP-1, CHWP-2 3 480 SQUARE D 15A 3(2) COMBO STARTER-3 - - CARTRIDGE CLASS R8538CASP3
CHR-1, CHR-2 3 480 SQUARE D 125A 384.8- - 67.8 CARTRIDGE CLASS R8538SFG13V81CFF4T
CTP-1, CTP-2 1 480 SQUARE D 35A 2(2) COMBO STARTER-7.5 - 32 CARTRIDGE CLASS R8538SDG63V02
(2) COMBO STARTER
VH361NRB
CT-1, CT-2 (PUMPS) 3 480-5 - 8 1,515 3CARTRIDGE CLASS R
CT-1, CT-2 (HEATER/CONTOLER) 3 480-- 9920 - 1,5SQUARE D 15 3(2) HEAVY DUTY FUSED CARTRIDGE CLASS RVH361NRB
CT-1, CT-2 (120V HEATER/SWITCHES) 1 120-- - 4 1,5SQUARE D 5 1(2) GEN DUTY FUSED CARTRIDGE CLASS RD221NRB
SQUARE D(2) HEAVY DUTY FUSED VH361NRB
SINGLE CHAMBER WASHER #1 (2)
CART AND UTENSIL WASH #1 (5)
SINGLE CHAMBER WASHER #2 (2)
SINGLE CHAMBER WASHER #3 (2)
MOTORIZED CONVEYORS #1 (10)
CART AND UTENSIL WASH #2 (5)
MOTORIZED CONVEYORS #2 (10)
AMSCO 600 STEAM STERIL #1 (15)
AMSCO 600 STEAM STERIL #2 (15)
AMSCO 600 STEAM STERIL #3 (15)
AMSCO 400 STEAM STERIL (14)
INNOWAVE PFC IRRIGATOR #1 (3)
INNOWAVE PFC IRRIGATOR #2 (3)
PASS-THROUGH WINDOW #1 (8)
PASS-THROUGH WINDOW #2 (8)
AMSCO 400 STEAM STERIL CNTRL (14)
3 480
3 480
16.5
13.5
3 480-- - 16.5
3 480-- - 16.5
1 208-- 1440 -
3 480-- 865 13.5
1 208-- 1440 -
3 480-- - 7
3 480-- - 7
3 480-- - 7
3 480-- - 3
3 208-- - 24
3 208-- - 24
3 208-- - 1
3 208-- - 1
1 120-- - 2
HEAVY DUTY FUSED
HEAVY DUTY FUSED
HEAVY DUTY FUSED
HEAVY DUTY FUSED
HEAVY DUTY FUSED
HEAVY DUTY FUSED
HEAVY DUTY FUSED
HEAVY DUTY FUSED
GENERAL DUTY FUSED
GENERAL DUTY FUSED
GENERAL DUTY FUSED
GENERAL DUTY FUSED
GENERAL DUTY FUSED
GENERAL DUTY FUSED
HEAVY DUTY FUSED
GENERAL DUTY FUSED
SQUARE D
SQUARE D VH361NRB
CARTRIDGE CLASS R
CARTRIDGE CLASS R
SQUARE D CARTRIDGE CLASS R
SQUARE D CARTRIDGE CLASS R
SQUARE D D321NRB CARTRIDGE CLASS R
SQUARE D VH361NRB CARTRIDGE CLASS R
SQUARE D D321NRB CARTRIDGE CLASS R
SQUARE D CARTRIDGE CLASS R
SQUARE D CARTRIDGE CLASS R
SQUARE D CARTRIDGE CLASS R
SQUARE D CARTRIDGE CLASS R
SQUARE D D321NRB CARTRIDGE CLASS R
SQUARE D D321NRB CARTRIDGE CLASS R
SQUARE D D321NRB CARTRIDGE CLASS R
SQUARE D D321NRB CARTRIDGE CLASS R
VH361NRB
VH361NRB
VH361NRB
VH361NRB
VH361NRB
VH361NRB
VH361NRB
SQUARE D CARTRIDGE CLASS RD321NRB
30A 3
20A 3
30A 3
30A 3
15A 3
20A 3
15A 3
20A 3
20A 3
20A 3
4A 3
30A 3
30A 3
15A 3
15A 3
15A 1
MOTORIZED CONVEYORS #3 (10) 1 208-- 1440 - GENERAL DUTY FUSED SQUARE D D321NRB CARTRIDGE CLASS R 15A 3 1
MOTORIZED CONVEYORS #1 (4A) 1 208-- 1440 - GENERAL DUTY FUSED SQUARE D D321NRB CARTRIDGE CLASS R 15A 3 1
CU-3/EV-1 25- - - 1,71 208 SQUARE D 35A 2CARTRIDGE CLASS RH361NRBHEAVY DUTY FUSED
SWITCH
SYMBOL
NOTES:
LIGHTING CONTROL SCHEDULE
AON = AUTO ON AOF = AUTO OFF MON = MANUAL ON MOF = MANUAL OFF MOWO = MANUAL OFF WHILE OCCUPIED TDO = TIME DELAY OFF DLD = DAY LIGHT DETECTION 3W = THREE WAY 4W = 4 WAY E = ENABLED D = DISABLED
DESCRIPTION MANUFACTURER MODEL
AON AOF MON MOF MOWO TDO DLD 3W 4W
NOTES
CONTROL OPTIONS
WALL SWITCH HUBBELL CS120 - - E E - - - - -
WALL OCCUPANCY SENSOR SWITCH LUTRON MS-OPS6M2U-DV D E E E D 30m D - -
CEILING OCCUPANCY SENSOR SWITCH HUBBELL OMNI-DT-500 E E - - - 30m - - - 1OS
0-10V DIM
TRIAC DIM
1. SENSOR IS RATED FOR 24VDC INSTEAD OF LINE VOLTAGE. CONTRACTOR TO PROVIDE NECESSARY RELAYS AND WIRING COMPONENTS FOR A COMPLETE INSTALLATION.
PROVIDE SWITCHES WITH LOW VOLTAGE POWER PACKS AS REQUIRED.
LIGHTING
AMP
RATING
FAN AMP
RATING
LIGTHING +
FAN AMP
RATING
.033
.033
.033
HYPERLINK
SPEC
SPEC
SPEC
OS
SPDT OVERRIDE SWITCH W/ CENTER OFF HUBBELL 4922 SPECOV - - E E - - - - - - -202020
A. ON BOARD OCCUPANCY SENSING.
B. ON BOARD PHOTO CONTROL.
C. 0-10 V DIMMING.
D. TRIAC DIMMING.
E. EMERGENCY BACKUP BATTERY ON FIXTURES WITH ADDITIONAL E TAG.
RECESSED
LOCATION
NOTES
MANUFACTURER CATALOG NO. TYPE
LAMP
TYPE NO.
FIXTURE
LIGHTING FIXTURE SCHEDULE
SYMBOL
DESCRIPTION
LUMINAIRE NOTES:
HEIGHT WATTS
CONTROL NOTES:
LUMEN
HYPERLINK
LEDNEW STAR LIGHTING SCR24/HA/OA-L2351C-E-UN-EL1 16000CEILING -2X4 RECESSED CLEANROOM TROFFER 50-A -
-NEW STAR LIGHTING VIC4N-L2351C-RW-UN-WH -B LED1X4 STRIP LIGHT CEILING - 1540050SURFACE
-NEW STAR LIGHTING AACG24-HC20-IC20/CA12-L2351C-RW -C LED2X4 TROFFER CEILING - 1595050SURFACE
1. PROVIDE ALL NECESSARY HARDWARE OR KITS FOR MOUNTING LUMINAIRE AS NOTED BY LOCATION AND TYPE.
2. CONNECT TO NEAREST UNSWITCHED CIRCUIT.
3. REFER TO PLANS FOR DIRECTIONAL ARROWS, SINGLE OR DOUBLE SIDED, AND MOUNTING TYPE WILL BE WALL
MOUNTED UNLESS OTHERWISE NOTED ON PLANS.
SPEC
SPEC
SPEC
LETTER
DESIG.
SCR24/HA/IA-L2351C-E-UN-EL1
-NEW STAR LIGHTING AACG24-HC20-IC20/CA12-CL351C-RW -D LED2X4 TROFFER CEILING - 1400038SURFACE SPEC
-NEW STAR LIGHTING VIC4N-L3351C-RW-UN-WH -G LED1X4 STRIP LIGHT CEILING - 1720075SURFACE SPEC
X DUAL-LITE EXIT SIGN CEILING -LED 1,2,33.3 - 4.57' 6"LE-__-__-G-__-C-E-I - ESURFACE SPEC
-NEW STAR LIGHTING MUS2-HC-L135-A-UN -H LEDUNDERCABINET LIGHT UNDERCABINET - 1121512SURFACE SPEC
-NEW STAR LIGHTING DLM6-D-L135-__/__-__-3-UN -J LED6" DOWNLIGHT CEILING - 187611SURFACE SPEC
GENERAL LUMINAIRE NOTES.
1. MANUFACTURERS LISTED ARE CONSIDERED BASIS OF DESIGN PURPOSES. CONTRACTOR TO REFER TO SPECIFICATION, AND SALIENT FEATURES LISTED BOTH ON PLANS AND SPECIFICATIONS WHEN OFFERING EQUAL PRODUCTS.
8'COMPASS LIGHTING CUSO BK-H A,BK LEDOUTDOOR LED WALLPACK WITH HEATER WALL - 116007SURFACE SPEC
LOCATION NOTESMANUFACTURER MODEL NO.
SECURITY CAMERA SCHEDULE
SYMBOL
NOTES:
HYPERLINK
AXIS COMMUNICATIONS -CORRIDORCORNER
AXIS COMMUNICATIONS M3067-P360 CORRIDOR 1
AXIS COMMUNICATIONS P5655-E -
CAMERA HAS NO VANDAL RESISTANCE RATING BUT HAS A BUILT IN VANDAL ALARM.
SPEC
SPEC
SPEC
TYPE
C
C
C
PAN TILT
ZOOM
Q9216-SLV
ACCESS
DOORS
FUSED DISCONNECT
SWITCH
30A 480V 3Ø
FUSE AT 25
AMPS
L1 L2 L3
DOOR
DISCONNECT
CIRCUIT
BREAKER
CONTROLLING
CONTACTORS
ELECTRIC
BASIN
IMMERSION
HEATER
FACTORY
480V TO 24V
TRANSFORMER
R B Y
Y
W
CT
N
240/24 C
NO
NC
SH
T1
T2
G1
G2
SENSOR PROBE/CORD
ASSEMBLY
SPRAY PUMP
AUX CONTACT ON PUMP VFD
(PROVIDED AND WIRED BY
CONTRACTOR)
COMBINATION TEMPERATURE
LIQUID LEVEL CONTROLLERCONTROL PANEL
SHIELDED CABLE
ELEMENTS SHOWN AS DASHED ARE
TO BE PROVIDED/FIELD WIRED BY
ELECTRICAL CONTRACTOR.
ELEMENTS SHOWN IN SOLID LINES
ARE TO BE FACTORY
PROVIDED/WIRED.
FUSES
HEATER
POWER
HOT
HEATER
POWER
NEUTRAL
INTERPOSING RELAY
(BY ELECTRICAL CONTRACTOR)
HEATER
POWER
HOT
HEATER
POWER
NEUTRAL
MOTOR SPACE HEATER
BY FACTORY
MOTOR STARTER/VFD N.C.
AUXILIARY CONTACTS
(BY ELECTRICAL CONTRACTOR)
ELEMENTS SHOWN AS DASHED ARE
TO BE PROVIDED/FIELD WIRED BY
ELECTRICAL CONTRACTOR.
ELEMENTS SHOWN IN SOLID LINES
ARE TO BE FACTORY
PROVIDED/WIRED.
BROWN
RED
YELLOW
WHITE
BLACK
BLUE
ORANGE
VIOLET
GREEN
N.O.
N.C.
COMMON
N.O.
N.C.
COMMON
SOLENOID
COIL
CASE
GROUND
120V AC REMOTE
RESET AND TIME
DELAY COIL
TO FAN
VFD
CONTACTS
TO BAS
ALARM
MECHANICAL VIBRATION CUT-OUT SWITCH
WIRING DIAGRAM
SWITCH #2
SWITCH #1
ELEMENTS SHOWN AS DASHED ARE
TO BE PROVIDED/FIELD WIRED BY
ELECTRICAL CONTRACTOR.
ELEMENTS SHOWN IN SOLID LINES
ARE TO BE FACTORY
PROVIDED/WIRED.
SCHEDULE OF VARIABLE FREQUENCY DRIVES AND EQUIPMENT CONTROLLERS
STARTERMOTOR
UNIT
PHLOAD MFR. CATALOG NO. SIZE
DEVICES
PILOT
NOTES
POLESVOLTS SWT
14 FLA ABB ACS880-01 1 3 * HOA G 1,2,3
8 FLA 3 480 ABB ACS880-01 0 3 * HOA G 1,2,3
NOTES:
1. PROVIDE NEMA 3R MINIMUM RATED ENCLOSURE FOR VFDs.
2. VFD IS REQUIRED TO HAVE FULL MECHANICAL BYPASS. ELECTRONIC BYPASS WILL NOT BE ACCEPTABLE FOR THIS PROJECT.
3. VFDs FOR COOLING TOWER EQUIPMENT ARE INCLUDED AS PART OF THE BASE BID. BID ALTERNATE #3 REMOVES THE CT-1
AND CT-2 FROM THE PROJECT ALONG WITH THE ASSOCIATED VFDs.
* HEATERS BY VFD MANUFACTURER.
3 480
O.L.
HTRS
CT-1, CT-2 (FANS)
CT-1, CT-2 (PUMPS)
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
16.2330.A08
11/23/2020 KABWEW
4101 Woolworth Ave #4199 Omaha, Ne 68105Omaha VA Medical Center
Design/Construct Sterile Processing Service - Omaha VA Medical Center
CONSTRUCTION DOCUMENTS
FOURFRONT
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
TERRASITE DESIGN
1635 DEADWOOD AVENUE
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 791-1736
COMPLIANCY REVIEW INCLUDED
ELECTRICAL SCHEDULES
E-003
FAN MOTOR SPACE HEATER WIRING SCHEMATIC
SCALE: NTS
ELECTRIC IMMERSION HEATER WIRING DETAIL
SCALE: NTS
MECHANICAL VIBRATION CUT-OUT WIRING DETAIL
SCALE: NTS
143120 https://hubbellcdn.com/specsheet/WIRING_CS120_spec.pdf http://www.lutron.com/TechnicalDocumentLibrary/369741_ENG.pdf https://hubbellcdn.com/specsheet/1301A_OMNIDT_Cutsheet.pdf https://hubbellcdn.com/catalogpage/Bryant_Catalog_E3_CatPage.pdf http://newstarlighting.com/wp-content/uploads/2018/07/AAC_AuraMedClassic_NewStarLighting.pdf http://newstarlighting.com/wp-content/uploads/2018/03/VICN_VictoryNarrow_NewStarLighting.pdf http://newstarlighting.com/wp-content/uploads/2018/03/SCR_StarCleanRecessed_NewStarLighting.pdf http://newstarlighting.com/wp-content/uploads/2018/07/AAC_AuraMedClassic_NewStarLighting.pdf http://newstarlighting.com/wp-content/uploads/2018/03/VICN_VictoryNarrow_NewStarLighting.pdf https://hubbellcdn.com/specsheet/DL_LE_OHW.pdf https://newstarlighting.com/wp-content/uploads/2018/07/MUS_Undercabinet_NewStarLighting.pdf http://newstarlighting.com/wp-content/uploads/2018/07/DLM_Downlight_NewStarLighting.pdf https://hubbellcdn.com/specsheet/COM_CUSO_SPEC.pdf https://www.axis.com/files/datasheet/ds_p5655e_t10132168_en_2006.pdf https://www.axis.com/files/datasheet/ds_m3067p_t10140543_en_2005.pdf https://www.axis.com/files/datasheet/ds_q9216slv_t10144021_en_2005.pdf
3/8" MAX
FLOOR
SLAB, TYP.
FIRESTOP SEALANT
CONDUIT, TYP MINERAL WOOL
(FIRMLY PACKED)
INTEGRAL GALVANIZED
LIPPED STEEL MOUNTING
CHANNEL, TYP.
STEEL EXPANSION
ANCHOR, TYP
JUNCTION BOX
(SIZE AS REQUIRED)
CONDUIT FITTING
SPRING
NUT, TYP
LENGTH AS REQUIRED1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING
CHANNEL LONGER THAN 36" SHALL BE INSTALLED
WITH A CENTER SUPPORT ROD.
2. FASTEN THREADED ROD TO STRUCTURE BY
APPROVED METHOD PER SPECIFICATION 26 05 33,
RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS.
FIELD VERIFY EXACT CONDITIONS.
GENERAL NOTES
WASHER &
LOCKNUT
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
LOCKING SQUARE
WASHER & LOCKNUT
3/8" MIN GALVANIZED
THREADED ROD, TYP.
CONDUIT CLAMP.
SIZE AS REQUIRED
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
INSTALL IN ACCORDANCE WITH MANUFACTURER'S
MOUNTING INSTRUCTIONS AND USING THE
RECOMMENDED MOUNTING HARDWARE.GYPSUM BOARD
CEILING CROSS BEAM
LUMINAIRE.
REFER TO
SCHEDULE
DRYWALL BORDER
LUMINAIRE.
REFER TO
SCHEDULE
FIXTURE WHIP
FROM JUNCTION
BOX 6' LONG MAX.
LUMINAIRE MANUFACTURER'S
MOUNTING HARDWARE
LUMINAIRE
SUSPENSION
WIRES
3 TWIST MINIMUM (TYP)
GYPSUM BOARD (TYP)
CEILING CROSS BEAM
CEILING MAIN BEAM
INSTALL IN ACCORDANCE WITH MANUFACTURER'S
MOUNTING INSTRUCTIONS AND USING THE
RECOMMENDED MOUNTING HARDWARE.
LUMINAIRE.
REFER TO
SCHEDULE
LUMINAIRE.
REFER TO
SCHEDULE
FIXTURE WHIP
FROM JUNCTION
BOX 6' LONG MAX.
LUMINAIRE MANUFACTURER'S
MOUNTING HARDWARE
LUMINAIRE
SUSPENSION
WIRES
3 TWIST MINIMUM (TYP)
ACOUSTICAL
CEILING TILE (TYP)
ARCHITECTURAL
CEILING GRID
INSTALL IN ACCORDANCE WITH MANUFACTURER'S
MOUNTING INSTRUCTIONS AND USING THE
RECOMMENDED MOUNTING HARDWARE.
DRYWALL CEILING
CROSS TEE, TYP.
GYPSUM
BOARD
CEILING
MAIN BEAM.
WIRE TIE THROUGH
MOUNTING CHANNEL
& CROSS BEAM, TYP.
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
HANGER WIRE AND
MOUNTING CHANNEL
ATTACHED TO STRUCTURE
FIXTURE WHIP FROM
JUNCTION BOX 6' LONG MAX
DRYWALL CEILING
CROSS TEE, TYP.
CEILING HANGER WIRE
LOCKING SQUARE
WASHER & NUT
JUNCTION BOX
1/4" SCREW
INSTALL IN ACCORDANCE WITH MANUFACTURER'S
MOUNTING INSTRUCTIONS AND USING THE
RECOMMENDED MOUNTING HARDWARE.
CEILING HANGER
WIRE, TYP.
WIRE TIE OR SCREW
BAR HANGER TO
CROSS BEAM TYP.
CEILING
CROSS BEAM
CEILING MAIN BEAM
FIXTURE WHIP FROM
JUNCTION BOX 6'
LONG MAX
RECESSED CAN
LUMINAIRE
CEILING BEAM
GYPSUM
BOARD (TYP)
LUMINAIRE
BAR HANGERS
LUMINAIRE SUSPENSION WIRES
RECESSED CAN
LUMINAIRE
REFER TO
SCHEDULE.
INSTALL IN ACCORDANCE WITH MANUFACTURER'S
MOUNTING INSTRUCTIONS AND USING THE
RECOMMENDED MOUNTING HARDWARE.
LOCKING SQUARE
WASHER & NUT
JUNCTION BOX
1/4" SCREW
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
HANGER WIRE AND
MOUNTING CHANNEL
ATTACHED TO STRUCTURE
FIXTURE WHIP FROM
JUNCTION BOX 6' LONG MAX
CEILING HANGER WIRE
WIRE TIE THROUGH
MOUNTING CHANNEL
& CROSS BEAM, TYP.
ARCHITECTURAL
CEILING GRID
ARCHITECTURAL
CEILING GRID
ACOUSTICAL
CEILING TILE
(TYP)
ARCHITECTURAL
CEILING GRID
DETAIL IS APPLICABLE
ONLY FOR CONDUIT
SMALLER THAN 3"
3' MAX
PROVIDE 127mm (5") OF SLACK AT MIDPOINT
BETWEEN TWO END OF FLEXIBLE GALVANIZED
STEEL CONDUIT. PROVIDE GREEN INSULATED
COPPER EQUIPMENT GROUNDING
CONDUCTOR WITH FLEXIBLE CONDUIT. SEISMIC OR EXPANSION
JOINT. FIELD VERIFY ACTUAL
CONDITIONS & LOCATIONS.
FLOOR OR ROOF
STRUCTURE. FIELD VERIFY
ACTUAL CONDITIONS, TYP.
CONDUIT TRAPEZE
PER DETAIL _/E___
TYP.
CONDUIT, TYP.
STRUCTURAL MEMBER
(BEAM, JOIST, ETC.), TYP.
STEEL
EXPANSION
ANCHOR
SPRING NUT
PROVIDE EXTRA CABLE TO
MAKE COMPLETE LOOP
AROUND BOX PERIMETER
CONDUIT FITTING
JUNCTION BOX
(SIZE AS REQUIRED)
INTEGRAL GALVANIZED
LIPPED STEEL
MOUNTING CHANNEL
JUNCTION BOX, TYP
(SIZE AS REQUIRED)
BEAM
CLAMP,
TYP.
3' MAX
DETAIL IS REQUIRED
FOR CONDUIT 3" OR
LARGER BUT MAY
ALSO BE USED FOR
CONDUIT LESS THAN 3"
CONDUIT TRAPEZE
PER DETAIL _/E___
TYP.
CONDUIT, TYP.
SEISMIC OR EXPANSION
JOINT. FIELD VERIFY ACTUAL
CONDITIONS & LOCATIONS.
STRUCTURAL MEMBER
(BEAM, JOIST, ETC.), TYP.
STEEL
EXPANSION
ANCHOR
SPRING NUT
PROVIDE EXTRA CABLE TO
MAKE COMPLETE LOOP
AROUND BOX PERIMETER
CONDUIT FITTING
JUNCTION BOX
(SIZE AS REQUIRED)
INTEGRAL GALVANIZED
LIPPED STEEL
MOUNTING CHANNEL
JUNCTION BOX, TYP
(SIZE AS REQUIRED)
BEAM
CLAMP,
TYP.
HEAD
FLOOR OR ROOF STRUCTURE. FIELD
VERIFY ACTUAL CONDITIONS, TYP.
EXPANSION FITTING
WITH BONDING JUMPER
INSULATING
BUSHING
ON
OFF
AUTO
OS OS OS OS OS
LOAD
OS
LINE
NEUTRAL
OV
OV
SINGLE POLE DOUBLE THROW
LOCAL OVERRIDE SWITCH.
CEILING OCCUPANCY
SENSORS. REFER TO PLANS
FOR NUMBER AND LOCATION.
NOTE: MINIMUM 2" STAND-OFF FROM WALL TO BACK SIDE OF PLATE
WALL MOUNTED
GROUNDING
BUSBAR
INSULATOR
LUG
SUPPORT BRACKET
COPPER
PLATE
1/0 CU TO PANEL
25.2.LLMDP
#8 CU TO MEDIUM
VOLTAGE LOAD
INTERRUPTER
SWITCHGEAR
1/0 CU TO PANEL
25.2.LHMDP
#2 CU TO LIGHTING
PROTECTION ON
ROOF
NOTE: BACK FACE
(NOT SHOWN) TO
MATCH FRONT FACE
SHOWN
TELECOMMUNICATIONS
RECEPTACLE
2 DUPLEX
RECEPTACLES
TWO POWER POST FOR POWER AND
COMMUNICATIONS MOUNTED BACK.
BASIS OF DESIGN TO BE LEGRAND
30TP-2V. CONTRACTOR TO REFER TO
SPECIFICATION, AND SALIENT
FEATURES LISTED BOTH ON PLANS
AND SPECIFICATIONS WHEN
OFFERING EQUAL PRODUCTS.
SMALL COMPARTMENT IN
POST FOR ROUTING 120V
POWER TO RECEPTACLES
LARGE COMPARTMENT
IN POST FOR ROUTING
OF CAT 6 CABLES TO
TELECOMMUNICATIONS
RECEPTACLE
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
16.2330.A08
11/23/2020 KABWEW
4101 Woolworth Ave #4199 Omaha, Ne 68105Omaha VA Medical Center
Design/Construct Sterile Processing Service - Omaha VA Medical Center
CONSTRUCTION DOCUMENTS
FOURFRONT
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
TERRASITE DESIGN
1635 DEADWOOD AVENUE
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 791-1736
COMPLIANCY REVIEW INCLUDED
ELECTRICAL DETAILS
E-004
CONDUIT TRAPEZE MOUNTING DETAIL
SCALE: NTS
FLOOR SLAB PENETRATION DETAIL
SCALE: NTS
DOWNLIGHT MOUNTING - GYPBOARD CEILING
SCALE: NTS
EXIT SIGN MOUNTING - GYPBOARD CEILING
SCALE: NTS
LUMINAIRE MOUNTING - GYPBOARD CEILING
SCALE: NTS
LUMINAIRE MOUNTING - LAY-IN CEILING
SCALE: NTS
EXIT SIGN MOUNTING - LAY-IN CEILING
SCALE: NTS
CONDUIT EXPANSION JOINT CROSSING DETAIL - FLEXIBLE CONDUIT
SCALE: NTS
CONDUIT EXPANSION JOINT CROSSING DETAIL - EXPANSION FITTING
SCALE: NTS
OCCUPANCY SENSOR OVERRIDE SWITCH LIGHTING CONTROL DETAIL
SCALE: NTS
ELECTRICAL GROUND BUS BAR DETAIL
SCALE: NTS
POWER POST DETAIL
SCALE: NTS
143121
CATV & DATA OUTLET
(BEHIND TV)
GENERAL NOTE:
G1.
G2.
G3.
G4.
COORDINATE EXACT CONFIGURATION AND OUTLETS
IN FACE PLATE WITH OWNER.
COORDINATE EXACT LOCATION AND MOUNTING
HEIGHT WITH ARCHITECTURAL WALL ELEVATIONS.
ROUTE CABLES FROM ''AV'' AT +18'' AFF TO ''AV''
ABOVE THROUGH CONDUIT. FURNISH AND INSTALL
PATCH CABLES TO BE USED FROM ''AV'' ABOVE TO
ADJACENT TELEVISION SET FOR CONNECTIVITY.
G5. RANDL INDUSTRIES, INC., 5 SQUARE BOX, MODEL #
T-55017, WITH 2 GANG EXTENTION RING BY RANDL;
RISE/DEPTH TO BE DETERMINED BY DRYWALL
THICKNESS. A/V VENDOR IS TO COORDINATE EXACT
FACEPLATE CONFIGURATION WITH OWNER PRIOR TO
INSTALLATION.
POWER OUTLET (BY
DIVISION 26, BEHIND TV)
AV BACKBOX ABOVE AT +72''
AFF. OR PER ARCHITECURAL
WALL ELEVATION, BEHIND TV
(BY DIVISION 26)
AV BACKBOX AT
+18'' AFF, OR PER
ARCHITECTURAL
ELEVATIONS
2 - 1 1/4'' CONDUITS
(BY DIVISION 26)
CONDUIT AND BACKBOX PROVIDED BY
DIVISION 26 CONTRACTOR.
DATA
RG-6
D D
DB-15
HDMI
DVI
DATA
RG-6
RCA JACKS
D D
DB-15
HDMI
DVI
RCA JACKS
AV
M
AV
CABLE TO SECURITY PANEL
BY DIVISION 28 CONTRACTOR;
POWER BY DIVISION 26 TO BE
AT SECURITY PANEL.
COORDINATE POWER REQUIREMENTS
WITH DIVISION 28 CONTRACTOR
JUNCTION BOX
BY DIVISION 26 CONTRACTOR
ABOVE ACCESSIBLE CEILING
CONDUIT BY DIVISON 26 CONTRACTOR.
CABLING BY DIVISON 28 CONTRACTOR.
1'' CONDUIT
DIVISION 26;
CABLING BY
DIVISION 28
CARD READER OR KEYPAD
PROVIDED BY DIVISION 28;
IF REQUIRED, 1 - 4'' x 4''
BACKBOX WITH SINGLE
GANG PLASTER RING, BY
DIVISION 26
ELECTRIC DOOR
STRIKE/LOCK
RETRACTOR, BY
DOOR HARDWARE
VENDOR.
DC
ES
DOOR
W
S
NOTE:
1. IN THE EVENT OF A LOSS OF POWER OR
A FIRE ALARM SIGNAL DOOR LOCKING
MECHANISM TO DISABLE ALLOWING
FREE ACCESS THROUGH DOOR.
2. THIS DOOR DOES NOT RECIEVE ANY
EQUIPMENT FOR AUTOMATIC OPENING.
ELECTRIC POWER DOOR
OPENER BY DOOR
HARDWARE VENDOR.
ADO
CABLE TO SECURITY PANEL
BY DIVISION 28 CONTRACTOR;
POWER BY DIVISION 26 TO BE
AT SECURITY PANEL.
COORDINATE POWER REQUIREMENTS
WITH DIVISION 28 CONTRACTOR
JUNCTION BOX
BY DIVISION 26 CONTRACTOR
ABOVE ACCESSIBLE CEILING
CONDUIT BY DIVISON 26 CONTRACTOR.
CABLING BY DIVISON 28 CONTRACTOR.
ELECTRIC DOOR
STRIKE/LOCK
RETRACTOR, BY
DOOR HARDWARE
VENDOR.
DOOR RELEASE BUTTON
AND CABLING IN ANY
LOCATION BY DIVISION 28
CONTRACTOR.
CONDUIT AND BACK
BOX, BY DIVISON 26
CONTRACTOR
DC
ES
DOOR
EPO
EH
ELECTRIC POWER HINGE BY
DOOR HARDWARE VENDOR
NOTE: IN THE EVENT OF A
LOSS OF POWER OR A FIRE
ALARM SIGNAL DOOR
LOCKING MECHANISM TO
DISABLE ALLOWING FREE
ACCESS THROUGH DOOR
CABLE TO SECURITY PANEL BY DIVISION 28
CONTRACTOR; POWER BY DIVISION 26 TO
BE AT SECURITY PANEL. COORDINATE
POWER REQUIREMENTS
WITH DIVISION 28 CONTRACTOR. JUNCTION BOX
CONDUIT BY DIVISION
26 AND CABLING BY
DIVISION 28.
ABOVE ACCESSIBLE CEILING
1'' CONDUIT BY
DIVISION 26;
CABLING BY
DIVISION 28
CARD READER
OR KEYPAD
BY
DIVISION 28;
IF REQUIRED,
1 - 4'' x 4''
BACKBOX WITH
SINGLE GANG
PLASTER RING,
BY DIVISION 26
ELECTRIC POWER HINGE BY
DOOR HARDWARE VENDOR
DOOR CONTACT BY
DOOR HARDWARE
VENDOR, CABLING BY
DIVISION 28.
PANIC BAR PANIC BAR
MAG LOCK BY DOOR
HARDWARE VENDOR
CABLING BY
DIVISION 28.
ELECTRIC POWER
DOOR OPENER
BY DOOR HARDWARE VENDOR.
EPO DC DC
MAG MAG
EH
EPO
EH
BY DIVISION 26 CONTRACTOR
W
S
NOTE: IN THE
EVENT OF A LOSS
OF POWER OR A
FIRE ALARM SIGNAL
DOOR LOCKING
MECHANISM TO
DISABLE ALLOWING
FREE ACCESS
THROUGH DOOR
18'' MAX.
O.C.
18'' AFF. O.C.,
ABOVE COUNTER, AS NOTED, OR
MATCH HEIGHT OF POWER RECEPTACLE
FINISHED FLOOR
VOICE/DATA OUTLETS TO BE MOUNTED ADJACENT TO POWER OUTLETS WHERE
APPLICABLE. COORDINATE ALL MOUNTING HEIGHTS WITH ARCHITECTURAL
WALL ELEVATIONS, ELECTRICAL DRAWINGS, AND EQUIPMENT VENDOR DRAWINGS.
G1.
GENERAL NOTE:
CABLE TO SECURITY PANEL BY DIVISION 28
CONTRACTOR; POWER BY DIVISION 26 TO
BE AT SECURITY PANEL. COORDINATE
POWER REQUIREMENTS
WITH DIVISION 28 CONTRACTOR. JUNCTION BOX
CONDUIT BY DIVISION
26 AND CABLING BY
DIVISION 28.
ABOVE ACCESSIBLE CEILING
ELECTRIC POWER HINGE BY
DOOR HARDWARE VENDOR
DOOR CONTACT BY
DOOR HARDWARE
VENDOR, CABLING BY
DIVISION 28.
CONDUIT BY
DIVISION 26
DOOR RELEASE BUTTON AND
CABLING IN ANY LOCATION
BY DIVISION 28 CONTRACTOR.
MAG LOCK BY DOOR
HARDWARE VENDOR
CABLING BY
DIVISION 28.
EPO DC DC
MAG MAG
EH
ADO
EPO
EH
BY DIVISION 26 CONTRACTOR
ELECTRIC POWER
DOOR OPENER
BY DOOR HARDWARE VENDOR.
NOTE: IN THE EVENT OF A
LOSS OF POWER OR A FIRE
ALARM SIGNAL DOOR
LOCKING MECHANISM TO
DISABLE ALLOWING FREE
ACCESS THROUGH DOOR
SEAL PENETRATIONS SO AS TO
MAINTAIN WALL RATING PER
NATIONAL/LOCAL CODES AND
MANUFACTURER'S SPECIFICATIONS
RATED WALL
EZ-PATH FIRE RATED
MANUFACTURED SLEEVE
LOOSE CABLES
SEAL PENETRATIONS SO AS TO
MAINTAIN WALL RATING PER
NATIONAL & LOCAL CODES
RATED WALL
1'' MIN. CONDUIT; ADD OR
UP-SIZE AS REQUIRED
BUSHING TERMINATION
1'' MIN. SLEEVE; ADD OR
UP-SIZE AS REQUIRED
BUSHING TERMINATION
SEAL AT THIS END SO AS TO
MAINTAIN WALL RATING
FLOOR SLAB ABOVE
FIRE CAULK PENETRATION
ABOVE ACCESSIBLE CEILING
FLOOR SLAB
ABOVE ACCESSIBLE CEILING BELOW
GENERAL NOTES:
G1.
G2.
CEILING BELOW
ABOVE ACCESSIBLE CEILING
ALL CONDUITS AND BACKBOXES TO BE INSTALLED BY DIVISION 26 CONTRACTOR.
ALL CONDUITS IN PATIENT CARE AREAS ARE TO TERMINATE IN CORRIDOR WITH BUSHING TERMINATION.
COORDINATE EXACT LOCATION AND INSTALLATION
REQUIREMENTS OF FLOOR MOUNTED OUTLET WITH
STRUCTURAL ENGINEER, OWNER, DIVISION 27 CONTRACTOR,
AND MILLWORK VENDOR
1 - 2'' SYSTEMS CONDUIT
WITH BUSHING TERMINATIONS
(QUANTITY OF CONDUITS
TO BE DETERMINED BY
QUANTITY OF CABLES;
ADD AS NEEDED)FREE STANDING MILLWORK,
DESK OR CONFERENCE TABLE
FIRE CAULKED PENETRATION,
ABOVE AND BELOW (TYPICAL
ALL SLAB PENETRATIONS)
E005
FLOOR
CEILING
SPECIAL SYSTEMS
RECEPTACLE
REFER TO SHEET
T001 FOR
CONDUIT SIZES
EMT CONDUIT IN
CEILING WITH
ELBOW & BUSHING
12" MAX
CABLE TRAY
CONDUIT TO CABLE TRAY
SUPPORT BRACKET
INSULATOR
LUG
1/4"
WALL MOUNTED
GROUNDING
BUSBAR
TELECOMMUNICATIONS
BONDING BACKBONE
#6 AWG MIN.
TELECOMMUNICATIONS
BONDING CONDUCTOR
TO EQUIPMENT RACK13.5"
(MIN)
2"(MIN)
PLATE
GENERAL NOTE:
G1. MINIMUM 2" STAND-OFF FROM WALL TO BACK SIDE OF PLATE
ALL JACKS SHALL BE 568B PIN CONFIGURATION.
QTY DESCRIPTION
C
OUTLET TO TELECOM ROOM FOR TERMINATION.
1 UL LISTED CATEGORY 6, 4PR CABLE, PULLED FROM EACH
CAT 6 OUTLET
1 DATA SURFACE MOUNT HOUSING
INITIAL CAPACITY: 1 CONNECTION
FACE PLATE, BACK BOX, & CONDUIT REQUIREMENTS
INITIAL CAPACITY: 1 CATV CONNECTION;
QTY DESCRIPTION
1 RG6 COAX OUTLET
* COORDINATE ALL DEVICE MOUNTING HEIGHTS WITH ARCHITECTURAL WALL ELEVATIONS
AND POWER MOUNTING HEIGHTS ON ELECTRICAL DRAWINGS. REFER TO ''MOUNTING HEIGHT
TO CENTER LINE" DETAIL, SHEET 1-T-102.
FACE PLATE, BACK BOX, & CONDUIT REQUIREMENTSFACE PLATE, BACK BOX, & CONDUIT REQUIREMENTS
INITIAL CAPACITY: 4 CONNECTIONS
MAXIMUM CAPACITY: 4 CONNECTIONS
QTY DESCRIPTION
CAT 6 OUTLET
6 PORT COVER PLATE
1 UL LISTED CATEGORY 6, 4PR CABLE, PULLED FROM EACH
OUTLET TO TELECOM ROOM FOR TERMINATION.
TOP JACK TO BE RJ 45/11 FOR VOICE.
* COORDINATE ALL VOICE/DATA LOCATIONS, SPECIAL MOUNTING HEIGHT (SMH) DEVICES
WITH ARCHITECTURAL WALL ELEVATIONS AND/OR MOUNTING HEIGHTS OF POWER DEVICES
ON ELECTRICAL DRAWINGS. REFER TO ''MOUNTING HEIGHT TO CENTER LINE'', SHEET 1-T-102.
1 2 PORT COVER PLATE (PROVIDED BY CATV VENDOR)
1 UL LISTED COAX CABLE PULLED TO EACH COAX OUTLET FROM
TELECOM ROOM FOR CATV TERMINATION. TO BE INSTALLED BY
CATV CONTRACTOR.
PULL CABLE IN 1" EMT WITHIN 12" OF CABLE TRAY.
PULL CABLE IN 1" EMT WITHIN 12" OF CABLE TRAY.PULL CABLE IN 1" EMT WITHIN 12" OF CABLE TRAY.
GENERAL NOTES:
G1. CONDUIT AND BACKBOX PROVIDED BY DIVISION 26 CONTRACTOR.
G2. COORDINATE EXACT CONFIGURATION AND OUTLETS IN FACE PLATE WITH A/V VENDOR.
G3. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT WITH ARCHITECTURAL WALL ELEVATIONS.
DATA
RG-6
RCA JACKS
D D
DB-15
HDMI
DVI
AUDIO/VISUAL FACEPLATE DETAILS
AV
M
CABLE JACKET COLOR LEGEND
VOICE - WHITE
DATA - YELLOW
DATA - GREEN
DATA - GREY
WIRELESS - ORANGE
VIDEO SURVEILLANCE - VIOLET
NURSE CALL - BLUE
FIRE ALARM - RED
BAS & DAS - BLACK
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
16.2330.A08
11/23/2020 KABWEW
4101 Woolworth Ave #4199 Omaha, Ne 68105Omaha VA Medical Center
Design/Construct Sterile Processing Service - Omaha VA Medical Center
CONSTRUCTION DOCUMENTS
FOURFRONT
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
TERRASITE DESIGN
1635 DEADWOOD AVENUE
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 791-1736
COMPLIANCY REVIEW INCLUDED
AUDIO/VISUAL FACE PLATE CONFIGURATION DETAIL
SCALE: NTS
DOOR ACCESS CONTROL DETAIL - SINGLE DOOR
SCALE: NTS
DOOR ACCESS CONTROL DETAIL - DOUBLE DOOR
SCALE: NTS
AUTOMATIC DOOR OPENER DETAIL - SINGLE DOOR
SCALE: NTS
AUTOMATIC DOOR DETAIL - DOUBLE DOOR
SCALE: NTS
POWER OUTLET COORDINTATION REQUIREMENTS
SCALE: NTS
RATED WALL CONDUIT AND SLEEVE PENETRATIONS
SCALE: NTS
MANUFACTURED SLEEVE WALL PENETRATION
SCALE: NTS
CONDUIT TO CABLE TRAY
SCALE: NTS
TELECOMMUNICATIONS GROUNDING BUS BAR (TGB)
SCALE: NTS
UNDER SLAB TO FLUSH MOUNTED FLOOR BOX
SCALE: NTS
TELECOMMUNICATIONS DETAILS
E-005 119 143122
INSTALL COPPER STATIC
DISSIPATION GRID PER
MANUFACTURERS
INSTRUCTIONS
STATIC DISSIPATION
BONDING GRID
RUBBER
BASE TRIM
GROUNDING
BUS BAR
ROUTE 24" COPPER RIBBON
FROM BELOW GRADE STATIC
DISSIPATION GRID TO #6
BONDING WIRE EXPOSED ON
WALL
BOND COPPER
RIBBON TO STATIC
DISSIPATION GRID
TELECOMMUNCIATION ROOM
ROUTE #6 THHN GREEN COPPER GROUNDING
WIRE EXPOSED ON WALL FROM GROUNDING
BUS BAR TO OPPOSING ENDS OF THE STATIC
DISSIPATION GRID. BOND TO 24" COPPER
RIBBON FOR BELOW GRADE CONNECTION
ADO
CABLE TO SECURITY PANEL
BY DIVISION 28 CONTRACTOR;
POWER BY DIVISION 26 TO BE
AT SECURITY PANEL.
COORDINATE POWER REQUIREMENTS
WITH DIVISION 28 CONTRACTOR
JUNCTION BOX
BY DIVISION 26 CONTRACTOR
ABOVE ACCESSIBLE CEILING
CONDUIT BY DIVISON 26 CONTRACTOR.
CABLING BY DIVISON 28 CONTRACTOR.
DOOR RELEASE BUTTON
AND CABLING IN ANY
LOCATION BY DIVISION 28
CONTRACTOR.
CONDUIT AND BACK
BOX, BY DIVISON 26
CONTRACTOR
DC
DOOR
NOTE: IN THE EVENT OF A LOSS OF POWER OR A FIRE ALARM
SIGNAL DOOR LOCKING MECHANISM TO DISABLE ALLOWING
FREE ACCESS THROUGH DOOR.
CONTRACTOR TO PROVIDE AND INSTALL ALL NEW
EQUIPMENT, DEVICES, CONDUIT, AND CABLING WITH THE
USE OF A LENEL CERTIFIED TECHNICIAN. VA SECURITY
DEPARTMENT TO MAKE FINAL CONNECTIONS AND PROGRAM
FOR INTEGRATION TO EXISTING ACCESS CONTROL SYSTEM.
1'' CONDUIT
DIVISION 26;
CABLING BY
DIVISION 28
IDENTIV 8216ABP00DK CARD READER
WITH KEYPAD PROVIDED BY DIVISION
28; IF REQUIRED, 1 - 4'' x 4'' BACKBOX
WITH SINGLE GANG PLASTER RING,
BY DIVISION 26
W P,K
MAG LOCK BY DOOR
HARDWARE VENDOR
CABLING BY
DIVISION 28.
MAG
RTES
RECOMMENDED CABLE TRAY:
· CABLOFIL
· 4 IN. DEEP X 12 IN. WIDE MINIMUM (SIZE COMMENSURATE WITH
DISTRIBUBTION REQUIREMENT)
· WHITE POWERCOAT
· TRAY INSERT
· PART NUMBER: CF105 300 (4 IN. DEPTH, 12 IN. WIDTH)
·· MODIFIED PN FOR VARIOUS DEPTHS AND WIDTHS
3.94 IN.
(100 MM)
6.53 IN.
(156 MM)
118.2 IN.
(3000 MM)1.97 IN.
(50 MM)
RECOMMENDED UTP MEDIA: ATLAS-X1 COPPER TRUNKS
· PN: CTA-U6AP06LxxxF-CYNXA24N-CYNXA24N-CB01E (xxx IS LENGTH IN FEET)
· CAT 6A UTP CMP CABLE ASSEMBLY; BUNDLE OF 6 BLUE CABLES
· BERK-TEK - LANMARK-10G2 (UTP) BRANDED CABLE USED, TIA/EIA WIRING T568B
· TESTED TO ANSI/TIA 568.2-D
· CUSTOM LABELING, NO PULLING EYE
· FIRST END TERMINATION: ATLAS-X1 E2XHD CONNECTOR WITH BLUE JACK 24 IN.
BREAKOUT LENGTH
· SECOND END TERMINATION: ATLAS-X1 E2XHD CONNECTOR WITH YELLOW JACK
24 IN. BREAKOUT LENGTH
B-SIDE JACK COLOR: YELLOW A-SIDE JACK COLOR: BLUE B-SIDE JACK COLOR: YELLOW
RECOMMENDED UTP MEDIA: ATLAS-X1 COPPER TRUNKS
· PN: CTA-U6AP06LxxxF-CLNXA24N-CYNXA24N-CB01E (xxx IS LENGTH IN FEET)
· CAT 6A UTP CMP CABLE ASSEMBLY; BUNDLE OF 6 BLUE CABLES
· BERK-TEK - LANMARK-10G2 (UTP) BRANDED CABLE USED, TIA/EIA WIRING T568B
· TESTED TO ANSI/TIA 568.2-D
· CUSTOM LABELING, NO PULLING EYE
· FIRST END TERMINATION: ATLAS-X1 E2XHD CONNECTOR WITH BLUE JACK 24 IN.
BREAKOUT LENGTH
· SECOND END TERMINATION: ATLAS-X1 E2XHD CONNECTOR WITH YELLOW JACK
24 IN. BREAKOUT LENGTH
A-SIDE JACK COLOR: BLUE
RECOMMENDED UTP MEDIA: ATLAS-X1 COPPER TRUNKS
· PN: CTA-U6AP06LxxxF-CLNXA24N-CLNXA24N-CB01E (xxx IS LENGTH IN FEET)
· CAT 6A UTP CMP CABLE ASSEMBLY; BUNDLE OF 6 BLUE CABLES
· BERK-TEK - LANMARK-10G2 (UTP) BRANDED CABLE USED, TIA/EIA WIRING T568B
· TESTED TO ANSI/TIA 568.2-D
· CUSTOM LABELING, NO PULLING EYE
· FIRST END TERMINATION: ATLAS-X1 E2XHD CONNECTOR WITH BLUE JACK 24 IN.
BREAKOUT LENGTH
· SECOND END TERMINATION: ATLAS-X1 E2XHD CONNECTOR WITH YELLOW JACK
24 IN. BREAKOUT LENGTH
19 IN.
1RU - FRONT VIEW
ANGLED PANEL COVER
REAR CABLE MANAGER
RECOMMENDED UTP PATCH PANEL
· LEVITON E2XHD-BLK HIGH-DENSITY ANGLED
· 48 POSITION
· ONE RU PER PANEL
· WITH REAR CABLE MANAGER
· ANGLED PANEL COVERS
RECOMMENDED MP0-8 STANDARD DENSITY FIBER CASSETTE: LEVITON HDX2 UNITY MTP
· PART NUMBER: 42NM2-S5C
· HDX UNITY MTP CASSETTE
· (0.75 dB) 24-FIBER 0M4
· 3X8-FIBER MTP (MALE) TO 1X24-FIBER MTP (MALE)
· 120G TO 40G; BLACK LATCH; UNIVERSAL POLARITY CASSETTES
RECOMMENDED MP0-24 TRUNK CABLE: OPT-X UNITY ULTRA LOW LOSS MTP TRUNK CABLES
· PART NUMBER: FTU-FW4024JJxxxF36C36CY-NNBS (xxx INDICATES LENGTH IN FEET)
· FIBER TRUNK UNITY
· 24 FIBERS; MULTIMODE 0M4; 24F SUB-UNITS OPT-X SJP
· FIRST END WITH PULLING EYE, CUSTOM LABEL; POLARITY MTP METHOD B
· FIRST END CONNECTOR: 24F LLMTP 0.35dB FEMALE CONNECTOR, BREAKOUT LENGTH
OF 36 IN. INTO 3.6 MM JACKETED FIBER, NO STAGGER
· SECOND END CONNECTOR: 24F LLMTP 0.35 dB FEMALE CONNECTOR, BREAKOUT
LENGTH OF 36 IN. INTO 3.6 MM JACKETED FIBER, NO STAGGER
RECOMMENDED LC FIBER SPLICE CASSETTE: LEVITON HDX
PART NUMBER: SPLCH-12AQ (0M4)/SPLCH-12GN (0S2)
· HDX 0M4 LC CASSETTE, (0.15 dB) 12-FIBER 0M4 TO 12X1-FIBER LC(UPC)
· HDX 0S2 LC CASSETTE, (0.24 dB) 12-FIBER 0S2 TO 12X1-FIBER LC(APC)
RECOMMENDED MP0-8 TO MP0-8 PATCH CORDS:
· LEVITON OPT-X UNITY ULTRA LOW LOSS ARRAY CORDS
· PART NUMBER: UL548MM-BxxxF (xxx INDICATED LENGTH IN FEET)
· OPT0X UNITY 40-100G MTP ARRAY CORD (3 MM ROUND CABLE),
MULTIMODE (0M4), 8 FIBERS, ULMTP 8 FIBER FEMALE TO ULMTP 8
FIBER FEMALE, METHOD B POLARITY)
RECOMMENDED LC TO LC PATCH CORDS:
· LEVITON PREMIUM PLUS FIBER PATCH CORDS
· 0M4: PART NUMBER: PCF-M4PD1RR-xxxxF (xxxx INDICATED LENGTH IN
FEET TO 0.5 FT. [I.E. 5 FT. = 0050])
·· PREMIUM PLUS FIBER PATCH CORD, 0M4 AQUA, PLENUM, DUP-ZIP
1.6 MM, LC, LC, ULTRA POLISHED CONNECTORS (UPC)
· OS2: PART NUMBER: PCF-S2PD1FF-xxxxFAB (xxxx INDICATES LENGTH
IN FEET TO 0.5 FT.)
·· PREMIUM PLUS FIBER PATCH CORD, 0S2 YELLOW, PLENUM,
DUP-ZIP 1.6 MM, LC/APC, LC/APC, A-B POLARITY (PART NUMBER
PCF-S2PD1FF-xxxxFAA FOR A-A POLARITY)
· RECOMMENDED LC FIBER CASSETTE: LEVITON HDX2 UNITY MTP
· PART NUMBER: 41LSM4-UNN
· HDX UNITY MTP CASSETTE, (0.35 dB), 12-FIBER 0M4, LC SHUTTERED (AQUA) TO
1X12-FIBER MTP, UNIVERSAL POLARITY, BLACK LATCH UNIVERSAL POLARITY
CASSETTES
RECOMMENDED MP0-12 TRUNK CABLE: OPT-X UNITY ULTRA LOW LOSS MTP TRUNK CABLES
· PART NUMBER: FTU-FW2012LLxxxF36B36BY-NNBC (xxx INDICATES LENGHT IN FEET)
· FIBER TRUNK UNITY; 12 FIBER, MULTIMODE 0M4; 12F SUB-UNITS OPT-X SJP; OVERALL
CABLE LENGTH OF 100 FT; FIRST END WITH PULLING EYE, CUSTOM LABEL; POLARITY
MTP METHOD B;L FIRST END CONNECTOR: 12F ULMTP 0.20 dB FEMALE CONNECTOR, BREAKOUT LENGHT OF 36 IN. INTO 2 MM JACKETED FIBER, NO STAGGER; SECOND END
CONNECTOR: 12F ULMTP 0.20 dB FEMALE CONNECTOR, BREAKOUT LENGTH OF 36 IN.
INTO 2 MM JACKETED FIBER, NO STAGGER
RECOMMENDED LC FIBER CASSETTE: LEVITON HDX2 UNITY MTP
· PART NUMBER: 42LSM2-21C
· HDX2 UNITY MTP CASSETTE, (0.50 dB), 24-FIBER 0M4, LC SHUTTERED TO 1X24-FIBER MTP
(MALE), 120G TO 10G, BLACK LATCH UNIVERSAL POLARITY CASSETTES
RECOMMENDED MP0-24 TRUNK CABLE: OPT-X UNITY ULTRA LOW LOSS MTP TRUNK CABLES
· PART NUMBER: FTU-FW4024JJxxxF36C36CY-NNBS (xxx INDICATES LENGHT IN FEET)
· FIBER TRUNK UNITY; 24 FIBER, MULTIMODE 0M4; 24F SUB-UNITS OPT-X SJP; FIRST END
WITH PULLING EYE, CUSTOM LABEL; POLARITY MTP METHOD B;L FIRST END
CONNECTOR: 24F LLMTP 0.35 dB FEMALE CONNECTOR, BREAKOUT LENGHT OF 36 IN.
INTO 3.6 MM JACKETED FIBER, NO STAGGER; SECOND END CONNECTOR: 24F LLMTP 0.35
dB FEMALE CONNECTOR, BREAKOUT LENGTH OF 36 IN. INTO 3.6 MM JACKETED FIBER, NO STAGGER
RECOMMENDED FIBER DISTRIBUTION PANEL:
· LEVITON ANGLED OPT-X UHDX
· 144 FIBER
· ONE RU
P/N: OR-MM20VMD706 (OR EQUIVALENT)
MM20 VERTICAL CABLE MANAGEMENT
"CAGE", WITH DOOR, 6.45 IN. X 10.26 IN. X
76.94 IN., WHITE
CAPACITY: 350 CATEGORY 6A PATCH CORDS
OR 245 CATEGORY 6A PATCH CORDS
LARGER VCM AUTHORIZED IN ACCORDANCE
WITH CABLING REQUIREMENT
76.94 IN.
10.26 IN. 6.45 IN.
NOTE: TELECOMMUNICATION CHANNEL RACKS
ARE REQUIRED IN ALL TELECOMUNICATION ROOMS.
TELECOMMUNICATION CHANNEL RACKS OR
TELECOMMUNICATION CABINETS MAY BE USED IN
THE HORIONTAL AND MAIN DISTRIBUTION AREAS.
16.00 IN.
23.75 IN.
30.00 IN.
40.00 IN.
84.00 IN.
86.00 IN.
P/N: OR-MM2073038-W (OR EQUIVALENT)
MIGHTY MO 20 CABLE MANAGEMENT RACK
30 IN. CHANNEL DEPTH, 7 FT HIGH, WHITE
FINISH OR EQUIVALENT
DIMENSIONS:
USABLE HEIGHT: 45 RU
DEPTH (US): 30 IN.
HEIGHT (US) 7 FT
WIDTH (US): 23.75 IN.
STATIC LOAD CAPACITY: 2000 lb
SQUARE HOLD P/N: OR-MM20724PDHD-W
23.31 IN.
77.00 IN.
MM20 DOOR MOUNT KIT
UPPER & LOWER BRACKETS
(SOLD SEPERATELY)
MM20 RACK 7FT
(SOLD SEPARATELY)
CAN BE FRONT OR
REAR MOUNTED
P/N: OR-MM2024DMFHD-W
KIT INCLUDES:
(1) TOP DOOR SUPPORT
(1) LOWER DOOR SUPPORT
WITH 2 FAN OPENINGS
82.36 IN. 7FT RACK
94.09 IN. 8 FT RACK
12.55 IN.23.63 IN.
MM20, PERFORATED
DOOR, 7 FT OR 8 FT,
24 IN. WIDE (SOLD
SEPERATELY)
MM20, PERFORATED
DOOR, 7 FT OR 8 FT,
24 IN. WIDE (SOLD
SEPERATELY)
P/N: OR-MM2024DMRHD-W P/N: OR-MM20PDUMB1D2W-W
20A 120/ 208V
Y
CHATSWORTH ECONNECT PDUJ OR EQUIVALENT;
VERTICAL; MONITORED; L21-20 PLUG; THREE-PHASE;
120/208 V INPUT; 20 A; (30) C13 (6) C19 OUTLETS; 208 V
OUTPUT; 3 x 2P 20 A; LCD; ETHERNET, USB, AND
ENVIRONMENTAL SENSOR PORTS; IP AND SERIAL
MONITORING; IP CONSOLIDATION (PDU LINKING);
TOOL-LESS MOUNTING; 70.5 IN. H (1791 MM) X 2.2 IN. W
(56 MM) X 2.2 IN. D (56 MM)
REQUIRES ONE L21-20R
RACK MOUNT UPS
CAPACITY: 5 kW (EXTERNAL BATTERY MODULES AVAILABLE)
INPUT VOLTAGE: 208 V
INPUT CONNECTION: L21-20P, THREE-PHASE, FOUR-WIRE + GROUND
OUTPUT CONNECTION: L21-20R
SIZE: 6 RU, 19 IN. RACK-MOUNTABLE
RUNTIME: 16.5 MINUTES AT 50% LOAD
(EATON BLADEUPS ZC0517700110000 OR EQUIVALENT
20A 120/ 208V
Y
MODULAR UPS OPTIONS FOR COMPUTER ROOMS
A
B
GROUP A B A BGROUP GROUP GROUP
LEG 1 LEG 2 LEG 1 LEG 2
OZ OY OX OZ
GRP A LEG 2
GRP B LEG 1
GRP A LEG 2
GRP B LEG 1
GRP A LEG 2
GRP B LEG 1
PHASE Z PHASE Y PHASE X
30 A THREE-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH FOUR L21-20R AND SIX
NEMA 5-20 OUTLETS AND TWO 10 FT POWER CORDS TERMINATING IN L21-30P ZONIT
ZPDS-208V30A-L21-4L21-20R-CR OR EQUIVALENT
ZONE PDU INPUTS
REQUIRE TWO L21-30Rs
NOTE: THE CORRECT SPECIFICATION FOR THE ZONE PDU IS TO ENERGIZE IT FROM
TWO INDEPENDENT POWER SOURCES. EACH INPUT WILL USE IDENTICAL SPECS: WYE
(5-WIRE), 208 V, 30 A, THREE-PHASE, TERMINATING IN A NEMA L21-30R LOCKING
RECEPTACLE. THE NEUTRAL CONDUCTOR SHOULD BE UPSIZED ON GAUGE TO MATCH
THE UPSIZED NETUTRAL CONDUCTOS IN THE ZONE PDU UNITS. THE NEUTRAL
"UPSIZING" SHOULD IDEALLY BE CONTINUED IN THE POWER DISTRIBUTION SYSTEM
BACK TO THE UPS OR TRANSFORMER WINDING POLE. THIS INCREASES THE EFFICIENCY
OF THE POWER DISTRIBUTION SYSTEM AND SUPPRESSES HARMONICS IN THE SYSTEM.
OYOX OXOZ OZOY OYOX
BLADE UPS
LEVITON
LEVITON
LEVITON
LEVITON
LEVITON
LEVITON
LEVITON
LEVITON
LEVITON
LEVITON
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6
O U
T
IN
O
BCN STS ENV
CISCO NEXUS N9K-C9108TC-FX
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54
BCN STS ENV
CISCO NEXUS N9K-C9108TC-FX
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54
BCN STS ENV
CISCO NEXUS N9K-C9108TC-FX
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54
BCN STS ENV
CISCO NEXUS N9K-C9108TC-FX
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54
BCN STS ENV
CISCO NEXUS N9K-C9108TC-FX
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54
MAIN
POWER
POWER
ON
GROUP A
ON
OFF
MAIN
POWER
POWER
ON
GROUP B
ON
OFF
GROUP A GROUP B
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
A B C A B C A B C A B C
PATCHING
(UP TO A MAXIMUM 480 PASSIVE WAOs
FOR BOTH OIT & FMS SYSTEMS)
SWITCHING
(UP TO A MAXIMUM 240 ACTIVE WASs
FOR OIT SYSTEMS)
POWER & FMS ACTIVE EQUIPMENT
IF ISP: 24-STRAND 0M4 PER SIDE, 12-STRAND
SM PER SIDE
IF OSP: 24-STRAND SM PER SIDE (NOT SHOWN)
24-STRAND 0M4 (B-SIDE)
12-STRAND SM (B-SIDE)
24-STRAND 0M4 (A-SIDE)
24-STRAND 0M4 (A-SIDE)
ANGLED FIBER PATCH PANEL FOR
BACKBONE CONNECTION TO MCR
CAT 5E PATCH PANEL FOR ANALOG
TELEPHONY & OTHER TWO-WIRE
APPLICATIONS
PRIMARY PROTECTOR (*OSP
APPLICATIONS ONLY)
48-PORT CAT 6A ANGLED PATCH
PANELS TO WAOs (TYPICAL)
1 RU HORIZONTAL CABLE MANAGER
(TYPICAL)
2 RU HORIZONTAL CABLE MANAGER
(TYPICAL)
NETWORK ACCESS SWITCH
(TYPICAL)
BLANKING PANELS (TYPICAL)
ZONE PDU (zPDU)
5 kW UPS (L21-20 INPUT/L21-20
OUTPUT)
BLADE UPS BLADE UPS
LEVITON
LEVITON
LEVITON
LEVITON
LEVITON
LEVITON
LEVITON
LEVITON
LEVITON
LEVITON
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6
O
BCN STS ENV
CISCO NEXUS N9K-C9108TC-FX
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54
BCN STS ENV
CISCO NEXUS N9K-C9108TC-FX
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54
BCN STS ENV
CISCO NEXUS N9K-C9108TC-FX
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54
BCN STS ENV
CISCO NEXUS N9K-C9108TC-FX
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54
BCN STS ENV
CISCO NEXUS N9K-C9108TC-FX
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54
MAIN
POWER
POWER
ON
GROUP A
ON
OFF
MAIN
POWER
POWER
ON
GROUP B
ON
OFF
GROUP A GROUP B
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
A B C A B C A B C A B C
BAYSTACK
INSTANT INTERNET
PWR 1 2 3 4 5 6 7 8
1000BASE-SX
TX RX 450 1SX MDA
ACTIVITY
PHY
LNK
1 3 5 7 9 11 13 15 17 19 21 23
2 4 6 8 10 12 14 16 18 20 22 24
BAYSTACK 410-24T SWITCH
1 3 5 7 9 11 13 15 17 19 21 23
2 4 6 8 10 12 14 16 18 20 22 24
RESET
USB A
MANAGEMENT
SPEED LINK/ACT
CONSOLE
CF
POWER SUPPLY SWITCH FABRIC AUXILIARY
MODULES
CONTROL
PROCESSOR
9080CP
ONLINE
MASTER
SYSTEM
TEMP
AUX1 2 1 2
B
BA
A
FRONT REAR
1 1
GE 0/4SFPGE 0/3GE 0/1
GE 0/2
1 2
3 4
SR4134
1 3 5 7
SLOT 2
IN USE 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
LINK/ACT LINK/ACT OPT41
PWR
STATUS
RPS
FAN
1 3 5 7
SLOT 1
IN USE 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
LINK/ACT LINK/ACT OPT41
VSP 8284XSQ
CONSOLE
USB
STATUS FAN
PWR RPS
VSP 8404
COUNTERACT
COUNTERACT
1 2 3 4 5 6
25 26 27 28 29 30 31 32 33 34 35 36
7 8 9 10 11 12
37 38 39 40 41 42
13 14 15 16 17 18
43 44 45 46 47 48
19 20 21 22 23 24
1 2 3 4 5 6
25 26 27 28 29 30 31 32 33 34 35 36
7 8 9 10 11 12
37 38 39 40 41 42
13 14 15 16 17 18
43 44 45 46 47 48
19 20 21 22 23 24
PATCHING (UP TO A MAXIMUM 480
PASSIVE WAOs FOR BOTH OIT & FMS
SYSTEMS)
SWITCHING (UP TO A MAXIMUM 240
ACTIVE WAOs FOR OIT SYSTEMS)
POWER & FMS ACTIVE EQUIPMENT
PDU
A
PDU
B
RACK/ENCLOSURE
RACKED EQUIP
PS1 PS2
PDU
A
PDU
B
RACK/ENCLOSURE
RACKED EQUIP
PS1 PS2
LEG1 LEG2
ZONE PDU
BUS A BUS B
RACK-MOUNT
UPS
RACK-MOUNT
UPS
C B1
C B2
C B3
O
FF
N
I
O
O
FF
O
O
FF
O N I
O
C H
AT
SW
O R
TH
PR
O D
U C
T
CB1
CB1
CB2
CB2
R
ES
ET
O K
W
AR
N
IN
G C
R
IT
IC
AL
TE
M
P/ H
U M
ID
IT
Y O
U T
IN
IO
IO
IO
/1
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
C B1
C B2
C B3
O
FF
O
O
FF
O
O
FF
O N I
O
C H
AT
SW
O R
TH
PR
O D
U C
T
CB1
CB1
CB2
CB2
R
ES
ET
O K
W
AR
N
IN
G C
R
IT
IC
AL
TE
M
P/ H
U M
ID
IT
Y O
U T
IN
IO
IO
IO
/1
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
C B1
C B2
C B3
O
FF
O
O
FF
O
O
FF
O N I
O
C H
AT
SW
O R
TH
PR
O D
U C
T
CB1
CB1
CB2
CB2
R
ES
ET
O K
W
AR
N
IN
G C
R
IT
IC
AL
TE
M
P/ H
U M
ID
IT
Y O
U T
IN
IO
IO
IO
/1
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
C B1
C B2
C B3
O
FF
O
O
FF
O
O
FF
O N I
O
C H
AT
SW
O R
TH
PR
O D
U C
T
CB1
CB1
CB2
CB2
R
ES
ET
O K
W
AR
N
IN
G C
R
IT
IC
AL
TE
M
P/ H
U M
ID
IT
Y O
U T
IN
IO
IO
IO
/1
CB3
CB3
CB1
CB1
CB2
CB2
CB3
CB3
L21-30P SIDE B
REQUIRES A 208 V, 30 A, THREE-PHASE
CIRCUIT, TERMINATING IN A NEMA
L21-30R LOCKING RECEPTACLE
L21-30P SIDE A
REQUIRES A 208 V, 30 A, THREE-PHASE
CIRCUIT, TERMINATING IN A NEMA
L21-30R LOCKING RECEPTACLE
ZONE PDU
30 A THREE-PHASE ZONE PDU BASE
UNIT - REQUIRES TWO 30 A
THREE-PHASE (WYE) CIRCUITS WITH
L21-30R RECEPTACLES; OPTIONALLY,
UPSs AND B-SIDE RPDUs MAY BE
POWERED DIRECTLY WITH L21-20
RACK-MOUNTED 5kW, 208 V
UPS WITH NEMA 20A
L21-20P INPUT AND L21-20R
OUTPUT
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
16.2330.A08
11/23/2020 KABWEW
4101 Woolworth Ave #4199 Omaha, Ne 68105Omaha VA Medical Center
Design/Construct Sterile Processing Service - Omaha VA Medical Center
CONSTRUCTION DOCUMENTS
FOURFRONT
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
TERRASITE DESIGN
1635 DEADWOOD AVENUE
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 791-1736
COMPLIANCY REVIEW INCLUDED
SCALE: NTS
TELECOMMUNICATIONS DETAILS
E-006
STATIC DISSAPATIVE FLOORING SCHEMATIC
SCALE: NTS
2 ACCESS CONTROL SCHEMATIC
SCALE: NTS
3 CABLE TRAY BASIS OF DESIGN
SCALE: NTS
4 B-SIDE UTP TRUNK CABLES
SCALE: NTS
5 A-SIDE TO B-SIDE CROSS CONNECT UTP TRUNK CABLES
SCALE: NTS
6 A-SIDE UTP TRUNK CABLES
SCALE: NTS
7 PATCH PANEL BASIS OF DESIGN
SCALE: NTS
8 FIBER DISTRIBUTION EQUIPMENT BASIS OF DESIGN
SCALE: NTS
9 TELECOMMUNICATIONS RACK BASIS OF DESIGN
SCALE: NTS
10 TELECOMMUNICATIONS RACK POWER DISTRIBUTION EQUIPMENT BASIS OF DESIGN
SCALE: NTS
11 TELECOMMUNICATIONS EQUIPMENT LAYOUT IN RACK
SCALE: NTS
12 TELECOMMUNICATIONS RACK POWER DISTRIBUTION EQUIPMENT SCHEMATIC
143123
FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
25.2.LLB
25.2.LLMDP
13,800V TO 208V
TRANSFORMER
25.2.LHB
25.2.LHMDP
25.2.LLA
25.2.LLC
13,800V TO 480V
TRANSFORMER
200A
200A
100A 600A
800A
1000A
NEW MEDIUM
VOLTAGE LOAD
INTERRUPTER
SWITCHGEAR
60A
NOTE: FROM INFORMATION
PROVIDED TO ENGINEER BY
VA CIRCUIT 95 CURRENTLY
HAS A CAPACITY OF 225 AMPS
TO BUILDING 25 AND IS USING
A PEAK DEMAND OF 80 AMPS.
NOTE: FROM INFORMATION
PROVIDED TO ENGINEER BY
VA CIRCUIT 90 HAS A
CAPACITY OF 225 AMPS TO
BUILDING 25 AND IS USING A
PEAK DEMAND OF 30 AMPS.
NOTE: FROM INFORMATION
PROVIDED TO THE ENGINEER
BY VA CIRCUIT 95 IS 100%
BACKED UP BY ONSITE
GENERATOR REMOVING THE
NEED FOR AN ADDITIONAL
GENERATOR TO BE
INSTALLED ON THIS PROJECT.
BUILDING 25 INTERIOR
MAIN
MAIN
IN BASEMENT CEILING
SET SWITCH FOR
PRIMARY POWER
FROM CIRCUIT 95 AND
SECONDARY POWER
FROM CIRCUIT 90
4" EMT WITH (4) #2 MV-90
CABLE + #8 CU GRND
(3) 3" EMT CONDUITS
EACH WITH (8) 2/0
THHN + 1/0 CU GRND
(24) 250 KCMIL THHN
+ (1) 2/0 CU GRND IN
(3) 4" EMT CONDUITS
2-1/2" EMT CONDUIT WITH
(4) 4/0 THHN + #2 CU GRND
2-1/2" EMT CONDUIT WITH
(4) 4/0 THHN + #2 CU GRND
1-1/2" EMT CONDUIT
WITH (4) #2 THHN +
#6 CU GRND
(16) 4/0 THHN
+ 2/0 CU GRND IN
(2) 3" EMT CONDUITS
NEW UNDERGROUND DUCT
BANK. REFER TO SHEET E-008.
CAP 6" SPARE CONDUITS AT
ENTRANCE TO BASEMENT
MECHANICAL ROOM.
CONTRACTOR TO
PROVIDE 1000 AMP
MAIN BREAKER WITH
GFI PROTECTION
BASEMENT
13,800V
SECTIONALIZING
CABINET
13,800V
SECTIONALIZING
CABINET
CIRCUIT #90. CONTINUES TO
MEDIUM VOLTAGE SWITCHGEAR
SECTION 2, FEEDER #4.
CONNECT TO MEDIUM VOLTAGE CIRCUIT
#90 IN MANHOLE #8 USING LOAD BREAK
STYLE CONNECTORS. COORDINATE
WITH EXISTING CONDITIONS.
CONNECT TO MEDIUM VOLTAGE CIRCUIT
#95 IN MANHOLE #9 USING LOAD BREAK
STYLE CONNECTORS. COORDINATE
WITH EXISTING CONDITIONS.
NEW UNDERGROUND
DUCT BANK. REFER
TO SHEET E-008.
NEW 6" CONDUIT TO BE INSTALLED
IN NEW DUCT BANK FOR FUTURE
USE. CAP WITHIN MANHOLE. NEW 6" CONDUIT TO BE INSTALLED
IN NEW DUCT BANK FOR FUTURE
USE. CAP WITHIN MANHOLE.
CORE DRILL, SLEEVE, AND SEAL
BUILDING WALL PENETRATIONS. (TYP)
FIRST FLOOR ROOF
BUILDING 25 EXTERIOR
PANEL DPA2
60A
400A MAIN
PANEL DPB2
60A
400A MAIN
CIRCUIT #95. CONTINUES TO
MEDIUM VOLTAGE SWITCHGEAR
SECTION 1, FEEDER #2.
MANHOLE #8 MANHOLE #9
4" EMT WITH (4) #2 MV-90
CABLE + #8 CU GRND
TR.B1.3.2
1-1/4" EMT
CONDUIT WITH
(4) #4 THHN + #8
CU GRND
1-1/4" EMT CONDUIT WITH
(4) #4 THHN + #8 CU GRND
CONTINUES TO EXISTING
TRANSFORMER TA2.
CONTINUES TO EXISTING
TRANSFORMER TB2.
TR.A1.3.2
CONTRACTOR TO INSTALL
NEW SQUARE D NQ430L1C 100
AMP ELECTRICAL PANEL.
CORE DRILL, SLEEVE, AND SEAL
MANHOLE WALL PENETRATIONS.
(TYP)
CORE DRILL, SLEEVE, AND SEAL
SLAB PENETRATIONS. (TYP)
EXISTING CIRCUIT #95 PROVIDING POWER TO SITE IS 100%
BACKED UP FROM EMERGENCY GENERATOR POWER.
ELECTRICAL SERVICE NOTE
SECOND FLOOR
THIRD FLOOR
SF
ROOF
VAV-6
CB
SF
VV-1E
CB
SF
VV-1S
CB
VV-2E
CB
SF
VV-2S
CB
VV-3E
CB
SF
VV-3S
CB
VV-4E
CB
SF
VV-4S
CB
VV-24E
CB
SF
VV-24S
CB
SF SF SF SF SF SF
VAV-5
CB
VV-10E
CB
VV-12E
CB
VV-11E
CB
VV-12S
CB
VV-10S
CB
VV-11S
CB
SF
VV-13E
CB
SF
VV-13S
CB
SF
VV-17S
CB
SF
VV-15E
CB
SF
VV-17E
CB
SF
VV-16S
CB
SF
VV-14E
CB
SF
VV-15S
CB
SF
VV-14S
CB
SF
VV-16E
CB
SF SF SF SF
VV-19E
CB
VV-18E
CB
VV-19S
CB
VV-18S
CB
SF
VAV-7
CB
SF
VAV-8
CB
SF
VAV-9
CB
SF SF SF
VAV-20
CB
VAV-21
CB
VAV-22
CB
25.2.LLB-225.2.LLC-1
25.2.LLB-125.2.LLA-1
T T T T T T T T T T T T T T T T T T T T T T T T T T T
T T T T T T
T T T T T
FUSESTAT LOCATED IN
ACCESSIBLE CEILING
SPACE (TYP)
VAV CONTROL
BOX (TYP)
VV CONTROL
BOX (TYP)
120V TO 24V 40 VA
TRANSFORMER FOR VAV OR
VV CONTROL POWER (TYP)