Attachment 03 - Set 1_G Series_Part4.pdf

PDF 15 MB Posted

Attached to
Y1DA--636-502 Construct Sterile Processing Service VISN 23 Federal contract opportunity
Solicitation number
36C77625R0063
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

These are comprehensive architectural and engineering design documents for a Design/Construct Sterile Processing Service project at the Omaha VA Medical Center. The 25-sheet technical drawing set includes detailed electrical, fire alarm, fire suppression, and architectural plans for a multi-level medical facility addition, specifically focusing on levels 1-3 of the building. The documents provide extensive technical specifications for electrical systems, including power distribution schematics, lighting plans, special systems routing, telecommunications details, and fire protection requirements. Key technical elements include medium voltage electrical service, zone control valve assemblies for fire sprinkler systems, specific sprinkler protection requirements for different occupancy types, and comprehensive fire alarm system integration with existing infrastructure. The design is for the Department of Veterans Affairs and involves intricate coordination across multiple engineering disciplines to support a sterile processing service area.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--636-502 Construct Sterile Processing Service VISN 23, newest first.
File Type Posted
Attachment 1 - RFP 36C77625R0063 Tech Questions - dated 8-7-25.docx DOCX document
Attachment 2 - Attachment 22 - WD - NEW20250057 Rev 7 - 8-1-25.pdf PDF
36C77625R0063 0005.docx DOCX document
36C77625R0063 0004.docx DOCX document
Addendum 001 Division 27 - Communications - dated 7-31-25.pdf PDF
36C77625R0063 0003.docx DOCX document
Attachment 1 - RFP 36C77625R0063 Tech Questions - dated 7-31-25.docx DOCX document
Attachment 1 _ RFP 36C77625R0063 Tech Questions _ dated 7-17-25.docx DOCX document
36C77625R0063 0002.docx DOCX document
Attachment 1 - Sign-In Sheet - 636-502 Construct SPS - Omaha 7-7-25.pdf PDF
36C77625R0063 0001.docx DOCX document
Attachment 03 - Set 1_G Series_Part2.pdf PDF
Attachment 08 - Set 6_Arch4.pdf PDF
Attachment 12 - Set 10_Mech2.pdf PDF
Attachment 15 - Set 13_Fire Protect.pdf PDF
Attachment 02 - Vol 2 Combined Specs - FINAL.pdf PDF
Attachment 04 - Set 2_Civil.pdf PDF
Attachment 07 - Set 5_Arch3.pdf PDF
Attachment 09 - Set 7_Equipment.pdf PDF
Attachment 13 - Set 11_Plumbing.pdf PDF
Attachment 01 - Vol 1 Combined Specs - FINAL.pdf PDF
Attachment 03 - Set 1_G Series_Part1.pdf PDF
Attachment 05 - Set 3_Arch1.pdf PDF
Attachment 06 - Set 4_Arch2.pdf PDF
Attachment 03 - Set 1_G Series_Part3.pdf PDF
Attachment 10 - Set 8_Structure.pdf PDF
Attachment 11 - Set 9_Mech1.pdf PDF
Attachment 14 - Set 12_Electrical.pdf PDF
Attachment 16 - VHA ICRA - 6-25-25.pdf PDF
Attachment 18 - PPQ.docx DOCX document
36C77625R0063.docx DOCX document
Attachment 17 - Project Information Sheet for Contractors.docx DOCX document
Attachment 21 - Site Visit Instructions - Construct SPS - Omaha.docx DOCX document
Attachment 20 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 19 - Subcontractor Information and Consent Form.docx DOCX document
Attachment 22 - WD - NE20250057 Rev 4 - 5-16-25.pdf PDF
Show all 36

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AT CONTRACTOR OPTION GFCI BREAKERS CAN BE USED

FOR HOMERUNS THAT HAVE MORE THAN ONE GFCI

REQUIREMENT. PARALLELING GFCI BREAKERS IS NOT

ALLOWED. EACH GFCI DEVICE SHOWN MUST BE

DEDICATED DEVICE, OR ON GFCI PROTECTED HOMERUN.

GENERAL NOTE

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COM

D E S I G N I N C.

Office of Construction and Facilities Management

Project Number

Building Number

Drawing Number

Dwg.

DrawnCheckedDate

Location

Project TitleDrawing Title

Approved: Project Director

ARCHITECTCONSULTANTS:

DateRevisions:

VA FORM 08-6231

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

1 2 3 4 5 6 7 8 9

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

Department of Veterans Affairsof

16.2330.A08

11/23/2020 KABWEW

4101 Woolworth Ave #4199 Omaha, Ne 68105Omaha VA Medical Center

Design/Construct Sterile Processing Service - Omaha VA Medical Center

CONSTRUCTION DOCUMENTS

FOURFRONT

ALBERTSON ENGINEERING, INC.

315 NORTH MAIN AVENUE, SUITE 200

SIOUX FALLS, SOUTH DAKOTA 57104

PH: (605) 274-0880

FARRIS ENGINEERING

12700 WEST DODGE ROAD

OMAHA, NEBRASKA 68154

PH: (402) 330-5900

TERRASITE DESIGN

1635 DEADWOOD AVENUE

RAPID CITY, SOUTH DAKOTA 57702

PH: (605) 791-1736

COMPLIANCY REVIEW INCLUDED

PANEL SCHEDULES CONTINUED

E-002 116 143119

SCHEDULE OF EQUIPMENT DISCONNECTS

DISCONNECTCONNECTED LOAD

EQUIPMENT

PH MFR. CATALOG NO. SIZE

NOTES

POLESVOLTS

NOTES:

1. DISCONNECT ENCLOSURE TO BE NEMA 3R MIN RATED.

2. NEW HEAVY DUTY FUSED DISCONNECTS ARE TO BE PROVIDED FOR NEW CONDENSING UNITS CU-1 AND CU-2.

3. NEW MOTOR COMBINATION STARTERS ARE TO BE PROVIDED FOR NEW CHILLERS CHR-1 AND CHR-2.

4. NEW MOTOR COMBINATION STARTERS ARE TO BE PROVIDED FOR NEW COOLING TOWER PUMPS CTP-1 AND CTP-2.

5. NEW HEAVY DUTY DISCONNECTS ARE TO BE PROVIDED FOR NEW COOLING TOWERS ACCH-1 AND ACCH-2.

6. NEW MOTOR COMBINATION STARTERS ARE TO BE PROVIDED FOR NEW CHILLED WATER PUMPS CHWP-1 AND CHWP-2.

7. POWER FOR THE INDOOR EVAPORATOR EV-1 IS PROVIDED BY OUTDOOR CONDENSING UNIT. COORDINATE POWER AND WIRING CONNECTIONS WITH

MANUFACTURER'S WRITTEN INSTRUCTIONS.

TYPE

FUSE

MCAHP W FLA TYPE

CU-1, CU-2 3 208 SQUARE D 100 3HEAVY DUTY FUSED 98- - -

HWP-1 1 208 2-.75 - -

UH-1,2,3,4 1 120-1/20 - -

AHU-1 23.13- - 18.5

AHU-2 SUPPLY 11.75- - 9.4

CT-1, CT-2 (FANS) 3 480-7.5 - 14

EF-1 -7-1/2 - 11

EF-2 -1/4 - 1.1

1,5

CARTRIDGE CLASS R

3 480 SQUARE D 20A 3

3 208 SQUARE D 4A 3GENERAL DUTY FUSED

CARTRIDGE CLASS R

CARTRIDGE CLASS R

SQUARE D 25 3(2) HEAVY DUTY FUSED CARTRIDGE CLASS R

3 480

3 480

SQUARE D H361NRB 40 3HEAVY DUTY FUSED CARTRIDGE CLASS R

SQUARE D H361NRB 20 3HEAVY DUTY FUSED CARTRIDGE CLASS R

COOPER BP/SSU 1.5A 1 -FUSESTAT EDISON BASE CLASS T

VH323NRB

D321N

1 120-- 40 - COOPER BP/SSU 0.5A 1 -FUSESTAT EDISON BASE CLASS T

1 120-- 40 - COOPER BP/SSU 0.5A 1 -FUSESTAT EDISON BASE CLASS T

VAV-5,6,7,8,9,20,21,22, 23

AHU-2 RETURN 5.25- - 4.2 3 480 SQUARE D H361NRB 15 3HEAVY DUTY FUSED CARTRIDGE CLASS R

H361NRBHEAVY DUTY FUSED

VV-1E,2E,3E,4E,10E,11E,12E,13E,

14E,15E,16E,17E,18E,19E,24E,1S, 2S,3S,4S,10S,11S,12S,13S,14S,15S, 16S,17S,18S,19S,24S

CP-1 1 208 SQUARE D 16A 2GENERAL DUTY FUSED-1/2 - - CARTRIDGE CLASS RD321N

SQUARE D 25A(2) COMBO STARTER CARTRIDGE CLASS R8538CASP4

CHWP-1, CHWP-2 3 480 SQUARE D 15A 3(2) COMBO STARTER-3 - - CARTRIDGE CLASS R8538CASP3

CHR-1, CHR-2 3 480 SQUARE D 125A 384.8- - 67.8 CARTRIDGE CLASS R8538SFG13V81CFF4T

CTP-1, CTP-2 1 480 SQUARE D 35A 2(2) COMBO STARTER-7.5 - 32 CARTRIDGE CLASS R8538SDG63V02

(2) COMBO STARTER

VH361NRB

CT-1, CT-2 (PUMPS) 3 480-5 - 8 1,515 3CARTRIDGE CLASS R

CT-1, CT-2 (HEATER/CONTOLER) 3 480-- 9920 - 1,5SQUARE D 15 3(2) HEAVY DUTY FUSED CARTRIDGE CLASS RVH361NRB

CT-1, CT-2 (120V HEATER/SWITCHES) 1 120-- - 4 1,5SQUARE D 5 1(2) GEN DUTY FUSED CARTRIDGE CLASS RD221NRB

SQUARE D(2) HEAVY DUTY FUSED VH361NRB

SINGLE CHAMBER WASHER #1 (2)

CART AND UTENSIL WASH #1 (5)

SINGLE CHAMBER WASHER #2 (2)

SINGLE CHAMBER WASHER #3 (2)

MOTORIZED CONVEYORS #1 (10)

CART AND UTENSIL WASH #2 (5)

MOTORIZED CONVEYORS #2 (10)

AMSCO 600 STEAM STERIL #1 (15)

AMSCO 600 STEAM STERIL #2 (15)

AMSCO 600 STEAM STERIL #3 (15)

AMSCO 400 STEAM STERIL (14)

INNOWAVE PFC IRRIGATOR #1 (3)

INNOWAVE PFC IRRIGATOR #2 (3)

PASS-THROUGH WINDOW #1 (8)

PASS-THROUGH WINDOW #2 (8)

AMSCO 400 STEAM STERIL CNTRL (14)

3 480

3 480

16.5

13.5

3 480-- - 16.5

3 480-- - 16.5

1 208-- 1440 -

3 480-- 865 13.5

1 208-- 1440 -

3 480-- - 7

3 480-- - 7

3 480-- - 7

3 480-- - 3

3 208-- - 24

3 208-- - 24

3 208-- - 1

3 208-- - 1

1 120-- - 2

HEAVY DUTY FUSED

HEAVY DUTY FUSED

HEAVY DUTY FUSED

HEAVY DUTY FUSED

HEAVY DUTY FUSED

HEAVY DUTY FUSED

HEAVY DUTY FUSED

HEAVY DUTY FUSED

GENERAL DUTY FUSED

GENERAL DUTY FUSED

GENERAL DUTY FUSED

GENERAL DUTY FUSED

GENERAL DUTY FUSED

GENERAL DUTY FUSED

HEAVY DUTY FUSED

GENERAL DUTY FUSED

SQUARE D

SQUARE D VH361NRB

CARTRIDGE CLASS R

CARTRIDGE CLASS R

SQUARE D CARTRIDGE CLASS R

SQUARE D CARTRIDGE CLASS R

SQUARE D D321NRB CARTRIDGE CLASS R

SQUARE D VH361NRB CARTRIDGE CLASS R

SQUARE D D321NRB CARTRIDGE CLASS R

SQUARE D CARTRIDGE CLASS R

SQUARE D CARTRIDGE CLASS R

SQUARE D CARTRIDGE CLASS R

SQUARE D CARTRIDGE CLASS R

SQUARE D D321NRB CARTRIDGE CLASS R

SQUARE D D321NRB CARTRIDGE CLASS R

SQUARE D D321NRB CARTRIDGE CLASS R

SQUARE D D321NRB CARTRIDGE CLASS R

VH361NRB

VH361NRB

VH361NRB

VH361NRB

VH361NRB

VH361NRB

VH361NRB

SQUARE D CARTRIDGE CLASS RD321NRB

30A 3

20A 3

30A 3

30A 3

15A 3

20A 3

15A 3

20A 3

20A 3

20A 3

4A 3

30A 3

30A 3

15A 3

15A 3

15A 1

MOTORIZED CONVEYORS #3 (10) 1 208-- 1440 - GENERAL DUTY FUSED SQUARE D D321NRB CARTRIDGE CLASS R 15A 3 1

MOTORIZED CONVEYORS #1 (4A) 1 208-- 1440 - GENERAL DUTY FUSED SQUARE D D321NRB CARTRIDGE CLASS R 15A 3 1

CU-3/EV-1 25- - - 1,71 208 SQUARE D 35A 2CARTRIDGE CLASS RH361NRBHEAVY DUTY FUSED

SWITCH

SYMBOL

NOTES:

LIGHTING CONTROL SCHEDULE

AON = AUTO ON AOF = AUTO OFF MON = MANUAL ON MOF = MANUAL OFF MOWO = MANUAL OFF WHILE OCCUPIED TDO = TIME DELAY OFF DLD = DAY LIGHT DETECTION 3W = THREE WAY 4W = 4 WAY E = ENABLED D = DISABLED

DESCRIPTION MANUFACTURER MODEL

AON AOF MON MOF MOWO TDO DLD 3W 4W

NOTES

CONTROL OPTIONS

WALL SWITCH HUBBELL CS120 - - E E - - - - -

WALL OCCUPANCY SENSOR SWITCH LUTRON MS-OPS6M2U-DV D E E E D 30m D - -

CEILING OCCUPANCY SENSOR SWITCH HUBBELL OMNI-DT-500 E E - - - 30m - - - 1OS

0-10V DIM

TRIAC DIM

1. SENSOR IS RATED FOR 24VDC INSTEAD OF LINE VOLTAGE. CONTRACTOR TO PROVIDE NECESSARY RELAYS AND WIRING COMPONENTS FOR A COMPLETE INSTALLATION.

PROVIDE SWITCHES WITH LOW VOLTAGE POWER PACKS AS REQUIRED.

LIGHTING

AMP

RATING

FAN AMP

RATING

LIGTHING +

FAN AMP

RATING

.033

.033

.033

HYPERLINK

SPEC

SPEC

SPEC

OS

SPDT OVERRIDE SWITCH W/ CENTER OFF HUBBELL 4922 SPECOV - - E E - - - - - - -202020

A. ON BOARD OCCUPANCY SENSING.

B. ON BOARD PHOTO CONTROL.

C. 0-10 V DIMMING.

D. TRIAC DIMMING.

E. EMERGENCY BACKUP BATTERY ON FIXTURES WITH ADDITIONAL E TAG.

RECESSED

LOCATION

NOTES

MANUFACTURER CATALOG NO. TYPE

LAMP

TYPE NO.

FIXTURE

LIGHTING FIXTURE SCHEDULE

SYMBOL

DESCRIPTION

LUMINAIRE NOTES:

HEIGHT WATTS

CONTROL NOTES:

LUMEN

HYPERLINK

LEDNEW STAR LIGHTING SCR24/HA/OA-L2351C-E-UN-EL1 16000CEILING -2X4 RECESSED CLEANROOM TROFFER 50-A -

-NEW STAR LIGHTING VIC4N-L2351C-RW-UN-WH -B LED1X4 STRIP LIGHT CEILING - 1540050SURFACE

-NEW STAR LIGHTING AACG24-HC20-IC20/CA12-L2351C-RW -C LED2X4 TROFFER CEILING - 1595050SURFACE

1. PROVIDE ALL NECESSARY HARDWARE OR KITS FOR MOUNTING LUMINAIRE AS NOTED BY LOCATION AND TYPE.

2. CONNECT TO NEAREST UNSWITCHED CIRCUIT.

3. REFER TO PLANS FOR DIRECTIONAL ARROWS, SINGLE OR DOUBLE SIDED, AND MOUNTING TYPE WILL BE WALL

MOUNTED UNLESS OTHERWISE NOTED ON PLANS.

SPEC

SPEC

SPEC

LETTER

DESIG.

SCR24/HA/IA-L2351C-E-UN-EL1

-NEW STAR LIGHTING AACG24-HC20-IC20/CA12-CL351C-RW -D LED2X4 TROFFER CEILING - 1400038SURFACE SPEC

-NEW STAR LIGHTING VIC4N-L3351C-RW-UN-WH -G LED1X4 STRIP LIGHT CEILING - 1720075SURFACE SPEC

X DUAL-LITE EXIT SIGN CEILING -LED 1,2,33.3 - 4.57' 6"LE-__-__-G-__-C-E-I - ESURFACE SPEC

-NEW STAR LIGHTING MUS2-HC-L135-A-UN -H LEDUNDERCABINET LIGHT UNDERCABINET - 1121512SURFACE SPEC

-NEW STAR LIGHTING DLM6-D-L135-__/__-__-3-UN -J LED6" DOWNLIGHT CEILING - 187611SURFACE SPEC

GENERAL LUMINAIRE NOTES.

1. MANUFACTURERS LISTED ARE CONSIDERED BASIS OF DESIGN PURPOSES. CONTRACTOR TO REFER TO SPECIFICATION, AND SALIENT FEATURES LISTED BOTH ON PLANS AND SPECIFICATIONS WHEN OFFERING EQUAL PRODUCTS.

8'COMPASS LIGHTING CUSO BK-H A,BK LEDOUTDOOR LED WALLPACK WITH HEATER WALL - 116007SURFACE SPEC

LOCATION NOTESMANUFACTURER MODEL NO.

SECURITY CAMERA SCHEDULE

SYMBOL

NOTES:

HYPERLINK

AXIS COMMUNICATIONS -CORRIDORCORNER

AXIS COMMUNICATIONS M3067-P360 CORRIDOR 1

AXIS COMMUNICATIONS P5655-E -

CAMERA HAS NO VANDAL RESISTANCE RATING BUT HAS A BUILT IN VANDAL ALARM.

SPEC

SPEC

SPEC

TYPE

C

C

C

PAN TILT

ZOOM

Q9216-SLV

ACCESS

DOORS

FUSED DISCONNECT

SWITCH

30A 480V 3Ø

FUSE AT 25

AMPS

L1 L2 L3

DOOR

DISCONNECT

CIRCUIT

BREAKER

CONTROLLING

CONTACTORS

ELECTRIC

BASIN

IMMERSION

HEATER

FACTORY

480V TO 24V

TRANSFORMER

R B Y

Y

W

CT

N

240/24 C

NO

NC

SH

T1

T2

G1

G2

SENSOR PROBE/CORD

ASSEMBLY

SPRAY PUMP

AUX CONTACT ON PUMP VFD

(PROVIDED AND WIRED BY

CONTRACTOR)

COMBINATION TEMPERATURE

LIQUID LEVEL CONTROLLERCONTROL PANEL

SHIELDED CABLE

ELEMENTS SHOWN AS DASHED ARE

TO BE PROVIDED/FIELD WIRED BY

ELECTRICAL CONTRACTOR.

ELEMENTS SHOWN IN SOLID LINES

ARE TO BE FACTORY

PROVIDED/WIRED.

FUSES

HEATER

POWER

HOT

HEATER

POWER

NEUTRAL

INTERPOSING RELAY

(BY ELECTRICAL CONTRACTOR)

HEATER

POWER

HOT

HEATER

POWER

NEUTRAL

MOTOR SPACE HEATER

BY FACTORY

MOTOR STARTER/VFD N.C.

AUXILIARY CONTACTS

(BY ELECTRICAL CONTRACTOR)

ELEMENTS SHOWN AS DASHED ARE

TO BE PROVIDED/FIELD WIRED BY

ELECTRICAL CONTRACTOR.

ELEMENTS SHOWN IN SOLID LINES

ARE TO BE FACTORY

PROVIDED/WIRED.

BROWN

RED

YELLOW

WHITE

BLACK

BLUE

ORANGE

VIOLET

GREEN

N.O.

N.C.

COMMON

N.O.

N.C.

COMMON

SOLENOID

COIL

CASE

GROUND

120V AC REMOTE

RESET AND TIME

DELAY COIL

TO FAN

VFD

CONTACTS

TO BAS

ALARM

MECHANICAL VIBRATION CUT-OUT SWITCH

WIRING DIAGRAM

SWITCH #2

SWITCH #1

ELEMENTS SHOWN AS DASHED ARE

TO BE PROVIDED/FIELD WIRED BY

ELECTRICAL CONTRACTOR.

ELEMENTS SHOWN IN SOLID LINES

ARE TO BE FACTORY

PROVIDED/WIRED.

SCHEDULE OF VARIABLE FREQUENCY DRIVES AND EQUIPMENT CONTROLLERS

STARTERMOTOR

UNIT

PHLOAD MFR. CATALOG NO. SIZE

DEVICES

PILOT

NOTES

POLESVOLTS SWT

14 FLA ABB ACS880-01 1 3 * HOA G 1,2,3

8 FLA 3 480 ABB ACS880-01 0 3 * HOA G 1,2,3

NOTES:

1. PROVIDE NEMA 3R MINIMUM RATED ENCLOSURE FOR VFDs.

2. VFD IS REQUIRED TO HAVE FULL MECHANICAL BYPASS. ELECTRONIC BYPASS WILL NOT BE ACCEPTABLE FOR THIS PROJECT.

3. VFDs FOR COOLING TOWER EQUIPMENT ARE INCLUDED AS PART OF THE BASE BID. BID ALTERNATE #3 REMOVES THE CT-1

AND CT-2 FROM THE PROJECT ALONG WITH THE ASSOCIATED VFDs.

* HEATERS BY VFD MANUFACTURER.

3 480

O.L.

HTRS

CT-1, CT-2 (FANS)

CT-1, CT-2 (PUMPS)

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COM

D E S I G N I N C.

Office of Construction and Facilities Management

Project Number

Building Number

Drawing Number

Dwg.

DrawnCheckedDate

Location

Project TitleDrawing Title

Approved: Project Director

ARCHITECTCONSULTANTS:

DateRevisions:

VA FORM 08-6231

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

1 2 3 4 5 6 7 8 9

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

Department of Veterans Affairsof

16.2330.A08

11/23/2020 KABWEW

4101 Woolworth Ave #4199 Omaha, Ne 68105Omaha VA Medical Center

Design/Construct Sterile Processing Service - Omaha VA Medical Center

CONSTRUCTION DOCUMENTS

FOURFRONT

ALBERTSON ENGINEERING, INC.

315 NORTH MAIN AVENUE, SUITE 200

SIOUX FALLS, SOUTH DAKOTA 57104

PH: (605) 274-0880

FARRIS ENGINEERING

12700 WEST DODGE ROAD

OMAHA, NEBRASKA 68154

PH: (402) 330-5900

TERRASITE DESIGN

1635 DEADWOOD AVENUE

RAPID CITY, SOUTH DAKOTA 57702

PH: (605) 791-1736

COMPLIANCY REVIEW INCLUDED

ELECTRICAL SCHEDULES

E-003

FAN MOTOR SPACE HEATER WIRING SCHEMATIC

SCALE: NTS

ELECTRIC IMMERSION HEATER WIRING DETAIL

SCALE: NTS

MECHANICAL VIBRATION CUT-OUT WIRING DETAIL

SCALE: NTS

143120 https://hubbellcdn.com/specsheet/WIRING_CS120_spec.pdf http://www.lutron.com/TechnicalDocumentLibrary/369741_ENG.pdf https://hubbellcdn.com/specsheet/1301A_OMNIDT_Cutsheet.pdf https://hubbellcdn.com/catalogpage/Bryant_Catalog_E3_CatPage.pdf http://newstarlighting.com/wp-content/uploads/2018/07/AAC_AuraMedClassic_NewStarLighting.pdf http://newstarlighting.com/wp-content/uploads/2018/03/VICN_VictoryNarrow_NewStarLighting.pdf http://newstarlighting.com/wp-content/uploads/2018/03/SCR_StarCleanRecessed_NewStarLighting.pdf http://newstarlighting.com/wp-content/uploads/2018/07/AAC_AuraMedClassic_NewStarLighting.pdf http://newstarlighting.com/wp-content/uploads/2018/03/VICN_VictoryNarrow_NewStarLighting.pdf https://hubbellcdn.com/specsheet/DL_LE_OHW.pdf https://newstarlighting.com/wp-content/uploads/2018/07/MUS_Undercabinet_NewStarLighting.pdf http://newstarlighting.com/wp-content/uploads/2018/07/DLM_Downlight_NewStarLighting.pdf https://hubbellcdn.com/specsheet/COM_CUSO_SPEC.pdf https://www.axis.com/files/datasheet/ds_p5655e_t10132168_en_2006.pdf https://www.axis.com/files/datasheet/ds_m3067p_t10140543_en_2005.pdf https://www.axis.com/files/datasheet/ds_q9216slv_t10144021_en_2005.pdf

3/8" MAX

FLOOR

SLAB, TYP.

FIRESTOP SEALANT

CONDUIT, TYP MINERAL WOOL

(FIRMLY PACKED)

INTEGRAL GALVANIZED

LIPPED STEEL MOUNTING

CHANNEL, TYP.

STEEL EXPANSION

ANCHOR, TYP

JUNCTION BOX

(SIZE AS REQUIRED)

CONDUIT FITTING

SPRING

NUT, TYP

LENGTH AS REQUIRED1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING

CHANNEL LONGER THAN 36" SHALL BE INSTALLED

WITH A CENTER SUPPORT ROD.

2. FASTEN THREADED ROD TO STRUCTURE BY

APPROVED METHOD PER SPECIFICATION 26 05 33,

RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS.

FIELD VERIFY EXACT CONDITIONS.

GENERAL NOTES

WASHER &

LOCKNUT

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

LOCKING SQUARE

WASHER & LOCKNUT

3/8" MIN GALVANIZED

THREADED ROD, TYP.

CONDUIT CLAMP.

SIZE AS REQUIRED

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

INSTALL IN ACCORDANCE WITH MANUFACTURER'S

MOUNTING INSTRUCTIONS AND USING THE

RECOMMENDED MOUNTING HARDWARE.GYPSUM BOARD

CEILING CROSS BEAM

LUMINAIRE.

REFER TO

SCHEDULE

DRYWALL BORDER

LUMINAIRE.

REFER TO

SCHEDULE

FIXTURE WHIP

FROM JUNCTION

BOX 6' LONG MAX.

LUMINAIRE MANUFACTURER'S

MOUNTING HARDWARE

LUMINAIRE

SUSPENSION

WIRES

3 TWIST MINIMUM (TYP)

GYPSUM BOARD (TYP)

CEILING CROSS BEAM

CEILING MAIN BEAM

INSTALL IN ACCORDANCE WITH MANUFACTURER'S

MOUNTING INSTRUCTIONS AND USING THE

RECOMMENDED MOUNTING HARDWARE.

LUMINAIRE.

REFER TO

SCHEDULE

LUMINAIRE.

REFER TO

SCHEDULE

FIXTURE WHIP

FROM JUNCTION

BOX 6' LONG MAX.

LUMINAIRE MANUFACTURER'S

MOUNTING HARDWARE

LUMINAIRE

SUSPENSION

WIRES

3 TWIST MINIMUM (TYP)

ACOUSTICAL

CEILING TILE (TYP)

ARCHITECTURAL

CEILING GRID

INSTALL IN ACCORDANCE WITH MANUFACTURER'S

MOUNTING INSTRUCTIONS AND USING THE

RECOMMENDED MOUNTING HARDWARE.

DRYWALL CEILING

CROSS TEE, TYP.

GYPSUM

BOARD

CEILING

MAIN BEAM.

WIRE TIE THROUGH

MOUNTING CHANNEL

& CROSS BEAM, TYP.

INTEGRAL GALVANIZED LIPPED

STEEL MOUNTING CHANNEL

HANGER WIRE AND

MOUNTING CHANNEL

ATTACHED TO STRUCTURE

FIXTURE WHIP FROM

JUNCTION BOX 6' LONG MAX

DRYWALL CEILING

CROSS TEE, TYP.

CEILING HANGER WIRE

LOCKING SQUARE

WASHER & NUT

JUNCTION BOX

1/4" SCREW

INSTALL IN ACCORDANCE WITH MANUFACTURER'S

MOUNTING INSTRUCTIONS AND USING THE

RECOMMENDED MOUNTING HARDWARE.

CEILING HANGER

WIRE, TYP.

WIRE TIE OR SCREW

BAR HANGER TO

CROSS BEAM TYP.

CEILING

CROSS BEAM

CEILING MAIN BEAM

FIXTURE WHIP FROM

JUNCTION BOX 6'

LONG MAX

RECESSED CAN

LUMINAIRE

CEILING BEAM

GYPSUM

BOARD (TYP)

LUMINAIRE

BAR HANGERS

LUMINAIRE SUSPENSION WIRES

RECESSED CAN

LUMINAIRE

REFER TO

SCHEDULE.

INSTALL IN ACCORDANCE WITH MANUFACTURER'S

MOUNTING INSTRUCTIONS AND USING THE

RECOMMENDED MOUNTING HARDWARE.

LOCKING SQUARE

WASHER & NUT

JUNCTION BOX

1/4" SCREW

INTEGRAL GALVANIZED LIPPED

STEEL MOUNTING CHANNEL

HANGER WIRE AND

MOUNTING CHANNEL

ATTACHED TO STRUCTURE

FIXTURE WHIP FROM

JUNCTION BOX 6' LONG MAX

CEILING HANGER WIRE

WIRE TIE THROUGH

MOUNTING CHANNEL

& CROSS BEAM, TYP.

ARCHITECTURAL

CEILING GRID

ARCHITECTURAL

CEILING GRID

ACOUSTICAL

CEILING TILE

(TYP)

ARCHITECTURAL

CEILING GRID

DETAIL IS APPLICABLE

ONLY FOR CONDUIT

SMALLER THAN 3"

3' MAX

PROVIDE 127mm (5") OF SLACK AT MIDPOINT

BETWEEN TWO END OF FLEXIBLE GALVANIZED

STEEL CONDUIT. PROVIDE GREEN INSULATED

COPPER EQUIPMENT GROUNDING

CONDUCTOR WITH FLEXIBLE CONDUIT. SEISMIC OR EXPANSION

JOINT. FIELD VERIFY ACTUAL

CONDITIONS & LOCATIONS.

FLOOR OR ROOF

STRUCTURE. FIELD VERIFY

ACTUAL CONDITIONS, TYP.

CONDUIT TRAPEZE

PER DETAIL _/E___

TYP.

CONDUIT, TYP.

STRUCTURAL MEMBER

(BEAM, JOIST, ETC.), TYP.

STEEL

EXPANSION

ANCHOR

SPRING NUT

PROVIDE EXTRA CABLE TO

MAKE COMPLETE LOOP

AROUND BOX PERIMETER

CONDUIT FITTING

JUNCTION BOX

(SIZE AS REQUIRED)

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL

JUNCTION BOX, TYP

(SIZE AS REQUIRED)

BEAM

CLAMP,

TYP.

3' MAX

DETAIL IS REQUIRED

FOR CONDUIT 3" OR

LARGER BUT MAY

ALSO BE USED FOR

CONDUIT LESS THAN 3"

CONDUIT TRAPEZE

PER DETAIL _/E___

TYP.

CONDUIT, TYP.

SEISMIC OR EXPANSION

JOINT. FIELD VERIFY ACTUAL

CONDITIONS & LOCATIONS.

STRUCTURAL MEMBER

(BEAM, JOIST, ETC.), TYP.

STEEL

EXPANSION

ANCHOR

SPRING NUT

PROVIDE EXTRA CABLE TO

MAKE COMPLETE LOOP

AROUND BOX PERIMETER

CONDUIT FITTING

JUNCTION BOX

(SIZE AS REQUIRED)

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL

JUNCTION BOX, TYP

(SIZE AS REQUIRED)

BEAM

CLAMP,

TYP.

HEAD

FLOOR OR ROOF STRUCTURE. FIELD

VERIFY ACTUAL CONDITIONS, TYP.

EXPANSION FITTING

WITH BONDING JUMPER

INSULATING

BUSHING

ON

OFF

AUTO

OS OS OS OS OS

LOAD

OS

LINE

NEUTRAL

OV

OV

SINGLE POLE DOUBLE THROW

LOCAL OVERRIDE SWITCH.

CEILING OCCUPANCY

SENSORS. REFER TO PLANS

FOR NUMBER AND LOCATION.

NOTE: MINIMUM 2" STAND-OFF FROM WALL TO BACK SIDE OF PLATE

WALL MOUNTED

GROUNDING

BUSBAR

INSULATOR

LUG

SUPPORT BRACKET

COPPER

PLATE

1/0 CU TO PANEL

25.2.LLMDP

#8 CU TO MEDIUM

VOLTAGE LOAD

INTERRUPTER

SWITCHGEAR

1/0 CU TO PANEL

25.2.LHMDP

#2 CU TO LIGHTING

PROTECTION ON

ROOF

NOTE: BACK FACE

(NOT SHOWN) TO

MATCH FRONT FACE

SHOWN

TELECOMMUNICATIONS

RECEPTACLE

2 DUPLEX

RECEPTACLES

TWO POWER POST FOR POWER AND

COMMUNICATIONS MOUNTED BACK.

BASIS OF DESIGN TO BE LEGRAND

30TP-2V. CONTRACTOR TO REFER TO

SPECIFICATION, AND SALIENT

FEATURES LISTED BOTH ON PLANS

AND SPECIFICATIONS WHEN

OFFERING EQUAL PRODUCTS.

SMALL COMPARTMENT IN

POST FOR ROUTING 120V

POWER TO RECEPTACLES

LARGE COMPARTMENT

IN POST FOR ROUTING

OF CAT 6 CABLES TO

TELECOMMUNICATIONS

RECEPTACLE

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COM

D E S I G N I N C.

Office of Construction and Facilities Management

Project Number

Building Number

Drawing Number

Dwg.

DrawnCheckedDate

Location

Project TitleDrawing Title

Approved: Project Director

ARCHITECTCONSULTANTS:

DateRevisions:

VA FORM 08-6231

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

1 2 3 4 5 6 7 8 9

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

Department of Veterans Affairsof

16.2330.A08

11/23/2020 KABWEW

4101 Woolworth Ave #4199 Omaha, Ne 68105Omaha VA Medical Center

Design/Construct Sterile Processing Service - Omaha VA Medical Center

CONSTRUCTION DOCUMENTS

FOURFRONT

ALBERTSON ENGINEERING, INC.

315 NORTH MAIN AVENUE, SUITE 200

SIOUX FALLS, SOUTH DAKOTA 57104

PH: (605) 274-0880

FARRIS ENGINEERING

12700 WEST DODGE ROAD

OMAHA, NEBRASKA 68154

PH: (402) 330-5900

TERRASITE DESIGN

1635 DEADWOOD AVENUE

RAPID CITY, SOUTH DAKOTA 57702

PH: (605) 791-1736

COMPLIANCY REVIEW INCLUDED

ELECTRICAL DETAILS

E-004

CONDUIT TRAPEZE MOUNTING DETAIL

SCALE: NTS

FLOOR SLAB PENETRATION DETAIL

SCALE: NTS

DOWNLIGHT MOUNTING - GYPBOARD CEILING

SCALE: NTS

EXIT SIGN MOUNTING - GYPBOARD CEILING

SCALE: NTS

LUMINAIRE MOUNTING - GYPBOARD CEILING

SCALE: NTS

LUMINAIRE MOUNTING - LAY-IN CEILING

SCALE: NTS

EXIT SIGN MOUNTING - LAY-IN CEILING

SCALE: NTS

CONDUIT EXPANSION JOINT CROSSING DETAIL - FLEXIBLE CONDUIT

SCALE: NTS

CONDUIT EXPANSION JOINT CROSSING DETAIL - EXPANSION FITTING

SCALE: NTS

OCCUPANCY SENSOR OVERRIDE SWITCH LIGHTING CONTROL DETAIL

SCALE: NTS

ELECTRICAL GROUND BUS BAR DETAIL

SCALE: NTS

POWER POST DETAIL

SCALE: NTS

143121

CATV & DATA OUTLET

(BEHIND TV)

GENERAL NOTE:

G1.

G2.

G3.

G4.

COORDINATE EXACT CONFIGURATION AND OUTLETS

IN FACE PLATE WITH OWNER.

COORDINATE EXACT LOCATION AND MOUNTING

HEIGHT WITH ARCHITECTURAL WALL ELEVATIONS.

ROUTE CABLES FROM ''AV'' AT +18'' AFF TO ''AV''

ABOVE THROUGH CONDUIT. FURNISH AND INSTALL

PATCH CABLES TO BE USED FROM ''AV'' ABOVE TO

ADJACENT TELEVISION SET FOR CONNECTIVITY.

G5. RANDL INDUSTRIES, INC., 5 SQUARE BOX, MODEL #

T-55017, WITH 2 GANG EXTENTION RING BY RANDL;

RISE/DEPTH TO BE DETERMINED BY DRYWALL

THICKNESS. A/V VENDOR IS TO COORDINATE EXACT

FACEPLATE CONFIGURATION WITH OWNER PRIOR TO

INSTALLATION.

POWER OUTLET (BY

DIVISION 26, BEHIND TV)

AV BACKBOX ABOVE AT +72''

AFF. OR PER ARCHITECURAL

WALL ELEVATION, BEHIND TV

(BY DIVISION 26)

AV BACKBOX AT

+18'' AFF, OR PER

ARCHITECTURAL

ELEVATIONS

2 - 1 1/4'' CONDUITS

(BY DIVISION 26)

CONDUIT AND BACKBOX PROVIDED BY

DIVISION 26 CONTRACTOR.

DATA

RG-6

D D

DB-15

HDMI

DVI

DATA

RG-6

RCA JACKS

D D

DB-15

HDMI

DVI

RCA JACKS

AV

M

AV

CABLE TO SECURITY PANEL

BY DIVISION 28 CONTRACTOR;

POWER BY DIVISION 26 TO BE

AT SECURITY PANEL.

COORDINATE POWER REQUIREMENTS

WITH DIVISION 28 CONTRACTOR

JUNCTION BOX

BY DIVISION 26 CONTRACTOR

ABOVE ACCESSIBLE CEILING

CONDUIT BY DIVISON 26 CONTRACTOR.

CABLING BY DIVISON 28 CONTRACTOR.

1'' CONDUIT

DIVISION 26;

CABLING BY

DIVISION 28

CARD READER OR KEYPAD

PROVIDED BY DIVISION 28;

IF REQUIRED, 1 - 4'' x 4''

BACKBOX WITH SINGLE

GANG PLASTER RING, BY

DIVISION 26

ELECTRIC DOOR

STRIKE/LOCK

RETRACTOR, BY

DOOR HARDWARE

VENDOR.

DC

ES

DOOR

W

S

NOTE:

1. IN THE EVENT OF A LOSS OF POWER OR

A FIRE ALARM SIGNAL DOOR LOCKING

MECHANISM TO DISABLE ALLOWING

FREE ACCESS THROUGH DOOR.

2. THIS DOOR DOES NOT RECIEVE ANY

EQUIPMENT FOR AUTOMATIC OPENING.

ELECTRIC POWER DOOR

OPENER BY DOOR

HARDWARE VENDOR.

ADO

CABLE TO SECURITY PANEL

BY DIVISION 28 CONTRACTOR;

POWER BY DIVISION 26 TO BE

AT SECURITY PANEL.

COORDINATE POWER REQUIREMENTS

WITH DIVISION 28 CONTRACTOR

JUNCTION BOX

BY DIVISION 26 CONTRACTOR

ABOVE ACCESSIBLE CEILING

CONDUIT BY DIVISON 26 CONTRACTOR.

CABLING BY DIVISON 28 CONTRACTOR.

ELECTRIC DOOR

STRIKE/LOCK

RETRACTOR, BY

DOOR HARDWARE

VENDOR.

DOOR RELEASE BUTTON

AND CABLING IN ANY

LOCATION BY DIVISION 28

CONTRACTOR.

CONDUIT AND BACK

BOX, BY DIVISON 26

CONTRACTOR

DC

ES

DOOR

EPO

EH

ELECTRIC POWER HINGE BY

DOOR HARDWARE VENDOR

NOTE: IN THE EVENT OF A

LOSS OF POWER OR A FIRE

ALARM SIGNAL DOOR

LOCKING MECHANISM TO

DISABLE ALLOWING FREE

ACCESS THROUGH DOOR

CABLE TO SECURITY PANEL BY DIVISION 28

CONTRACTOR; POWER BY DIVISION 26 TO

BE AT SECURITY PANEL. COORDINATE

POWER REQUIREMENTS

WITH DIVISION 28 CONTRACTOR. JUNCTION BOX

CONDUIT BY DIVISION

26 AND CABLING BY

DIVISION 28.

ABOVE ACCESSIBLE CEILING

1'' CONDUIT BY

DIVISION 26;

CABLING BY

DIVISION 28

CARD READER

OR KEYPAD

BY

DIVISION 28;

IF REQUIRED,

1 - 4'' x 4''

BACKBOX WITH

SINGLE GANG

PLASTER RING,

BY DIVISION 26

ELECTRIC POWER HINGE BY

DOOR HARDWARE VENDOR

DOOR CONTACT BY

DOOR HARDWARE

VENDOR, CABLING BY

DIVISION 28.

PANIC BAR PANIC BAR

MAG LOCK BY DOOR

HARDWARE VENDOR

CABLING BY

DIVISION 28.

ELECTRIC POWER

DOOR OPENER

BY DOOR HARDWARE VENDOR.

EPO DC DC

MAG MAG

EH

EPO

EH

BY DIVISION 26 CONTRACTOR

W

S

NOTE: IN THE

EVENT OF A LOSS

OF POWER OR A

FIRE ALARM SIGNAL

DOOR LOCKING

MECHANISM TO

DISABLE ALLOWING

FREE ACCESS

THROUGH DOOR

18'' MAX.

O.C.

18'' AFF. O.C.,

ABOVE COUNTER, AS NOTED, OR

MATCH HEIGHT OF POWER RECEPTACLE

FINISHED FLOOR

VOICE/DATA OUTLETS TO BE MOUNTED ADJACENT TO POWER OUTLETS WHERE

APPLICABLE. COORDINATE ALL MOUNTING HEIGHTS WITH ARCHITECTURAL

WALL ELEVATIONS, ELECTRICAL DRAWINGS, AND EQUIPMENT VENDOR DRAWINGS.

G1.

GENERAL NOTE:

CABLE TO SECURITY PANEL BY DIVISION 28

CONTRACTOR; POWER BY DIVISION 26 TO

BE AT SECURITY PANEL. COORDINATE

POWER REQUIREMENTS

WITH DIVISION 28 CONTRACTOR. JUNCTION BOX

CONDUIT BY DIVISION

26 AND CABLING BY

DIVISION 28.

ABOVE ACCESSIBLE CEILING

ELECTRIC POWER HINGE BY

DOOR HARDWARE VENDOR

DOOR CONTACT BY

DOOR HARDWARE

VENDOR, CABLING BY

DIVISION 28.

CONDUIT BY

DIVISION 26

DOOR RELEASE BUTTON AND

CABLING IN ANY LOCATION

BY DIVISION 28 CONTRACTOR.

MAG LOCK BY DOOR

HARDWARE VENDOR

CABLING BY

DIVISION 28.

EPO DC DC

MAG MAG

EH

ADO

EPO

EH

BY DIVISION 26 CONTRACTOR

ELECTRIC POWER

DOOR OPENER

BY DOOR HARDWARE VENDOR.

NOTE: IN THE EVENT OF A

LOSS OF POWER OR A FIRE

ALARM SIGNAL DOOR

LOCKING MECHANISM TO

DISABLE ALLOWING FREE

ACCESS THROUGH DOOR

SEAL PENETRATIONS SO AS TO

MAINTAIN WALL RATING PER

NATIONAL/LOCAL CODES AND

MANUFACTURER'S SPECIFICATIONS

RATED WALL

EZ-PATH FIRE RATED

MANUFACTURED SLEEVE

LOOSE CABLES

SEAL PENETRATIONS SO AS TO

MAINTAIN WALL RATING PER

NATIONAL & LOCAL CODES

RATED WALL

1'' MIN. CONDUIT; ADD OR

UP-SIZE AS REQUIRED

BUSHING TERMINATION

1'' MIN. SLEEVE; ADD OR

UP-SIZE AS REQUIRED

BUSHING TERMINATION

SEAL AT THIS END SO AS TO

MAINTAIN WALL RATING

FLOOR SLAB ABOVE

FIRE CAULK PENETRATION

ABOVE ACCESSIBLE CEILING

FLOOR SLAB

ABOVE ACCESSIBLE CEILING BELOW

GENERAL NOTES:

G1.

G2.

CEILING BELOW

ABOVE ACCESSIBLE CEILING

ALL CONDUITS AND BACKBOXES TO BE INSTALLED BY DIVISION 26 CONTRACTOR.

ALL CONDUITS IN PATIENT CARE AREAS ARE TO TERMINATE IN CORRIDOR WITH BUSHING TERMINATION.

COORDINATE EXACT LOCATION AND INSTALLATION

REQUIREMENTS OF FLOOR MOUNTED OUTLET WITH

STRUCTURAL ENGINEER, OWNER, DIVISION 27 CONTRACTOR,

AND MILLWORK VENDOR

1 - 2'' SYSTEMS CONDUIT

WITH BUSHING TERMINATIONS

(QUANTITY OF CONDUITS

TO BE DETERMINED BY

QUANTITY OF CABLES;

ADD AS NEEDED)FREE STANDING MILLWORK,

DESK OR CONFERENCE TABLE

FIRE CAULKED PENETRATION,

ABOVE AND BELOW (TYPICAL

ALL SLAB PENETRATIONS)

E005

FLOOR

CEILING

SPECIAL SYSTEMS

RECEPTACLE

REFER TO SHEET

T001 FOR

CONDUIT SIZES

EMT CONDUIT IN

CEILING WITH

ELBOW & BUSHING

12" MAX

CABLE TRAY

CONDUIT TO CABLE TRAY

SUPPORT BRACKET

INSULATOR

LUG

1/4"

WALL MOUNTED

GROUNDING

BUSBAR

TELECOMMUNICATIONS

BONDING BACKBONE

#6 AWG MIN.

TELECOMMUNICATIONS

BONDING CONDUCTOR

TO EQUIPMENT RACK13.5"

(MIN)

2"(MIN)

PLATE

GENERAL NOTE:

G1. MINIMUM 2" STAND-OFF FROM WALL TO BACK SIDE OF PLATE

ALL JACKS SHALL BE 568B PIN CONFIGURATION.

QTY DESCRIPTION

C

OUTLET TO TELECOM ROOM FOR TERMINATION.

1 UL LISTED CATEGORY 6, 4PR CABLE, PULLED FROM EACH

CAT 6 OUTLET

1 DATA SURFACE MOUNT HOUSING

INITIAL CAPACITY: 1 CONNECTION

FACE PLATE, BACK BOX, & CONDUIT REQUIREMENTS

INITIAL CAPACITY: 1 CATV CONNECTION;

QTY DESCRIPTION

1 RG6 COAX OUTLET

* COORDINATE ALL DEVICE MOUNTING HEIGHTS WITH ARCHITECTURAL WALL ELEVATIONS

AND POWER MOUNTING HEIGHTS ON ELECTRICAL DRAWINGS. REFER TO ''MOUNTING HEIGHT

TO CENTER LINE" DETAIL, SHEET 1-T-102.

FACE PLATE, BACK BOX, & CONDUIT REQUIREMENTSFACE PLATE, BACK BOX, & CONDUIT REQUIREMENTS

INITIAL CAPACITY: 4 CONNECTIONS

MAXIMUM CAPACITY: 4 CONNECTIONS

QTY DESCRIPTION

CAT 6 OUTLET

6 PORT COVER PLATE

1 UL LISTED CATEGORY 6, 4PR CABLE, PULLED FROM EACH

OUTLET TO TELECOM ROOM FOR TERMINATION.

TOP JACK TO BE RJ 45/11 FOR VOICE.

* COORDINATE ALL VOICE/DATA LOCATIONS, SPECIAL MOUNTING HEIGHT (SMH) DEVICES

WITH ARCHITECTURAL WALL ELEVATIONS AND/OR MOUNTING HEIGHTS OF POWER DEVICES

ON ELECTRICAL DRAWINGS. REFER TO ''MOUNTING HEIGHT TO CENTER LINE'', SHEET 1-T-102.

1 2 PORT COVER PLATE (PROVIDED BY CATV VENDOR)

1 UL LISTED COAX CABLE PULLED TO EACH COAX OUTLET FROM

TELECOM ROOM FOR CATV TERMINATION. TO BE INSTALLED BY

CATV CONTRACTOR.

PULL CABLE IN 1" EMT WITHIN 12" OF CABLE TRAY.

PULL CABLE IN 1" EMT WITHIN 12" OF CABLE TRAY.PULL CABLE IN 1" EMT WITHIN 12" OF CABLE TRAY.

GENERAL NOTES:

G1. CONDUIT AND BACKBOX PROVIDED BY DIVISION 26 CONTRACTOR.

G2. COORDINATE EXACT CONFIGURATION AND OUTLETS IN FACE PLATE WITH A/V VENDOR.

G3. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT WITH ARCHITECTURAL WALL ELEVATIONS.

DATA

RG-6

RCA JACKS

D D

DB-15

HDMI

DVI

AUDIO/VISUAL FACEPLATE DETAILS

AV

M

CABLE JACKET COLOR LEGEND

VOICE - WHITE

DATA - YELLOW

DATA - GREEN

DATA - GREY

WIRELESS - ORANGE

VIDEO SURVEILLANCE - VIOLET

NURSE CALL - BLUE

FIRE ALARM - RED

BAS & DAS - BLACK

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COM

D E S I G N I N C.

Office of Construction and Facilities Management

Project Number

Building Number

Drawing Number

Dwg.

DrawnCheckedDate

Location

Project TitleDrawing Title

Approved: Project Director

ARCHITECTCONSULTANTS:

DateRevisions:

VA FORM 08-6231

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

1 2 3 4 5 6 7 8 9

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

Department of Veterans Affairsof

16.2330.A08

11/23/2020 KABWEW

4101 Woolworth Ave #4199 Omaha, Ne 68105Omaha VA Medical Center

Design/Construct Sterile Processing Service - Omaha VA Medical Center

CONSTRUCTION DOCUMENTS

FOURFRONT

ALBERTSON ENGINEERING, INC.

315 NORTH MAIN AVENUE, SUITE 200

SIOUX FALLS, SOUTH DAKOTA 57104

PH: (605) 274-0880

FARRIS ENGINEERING

12700 WEST DODGE ROAD

OMAHA, NEBRASKA 68154

PH: (402) 330-5900

TERRASITE DESIGN

1635 DEADWOOD AVENUE

RAPID CITY, SOUTH DAKOTA 57702

PH: (605) 791-1736

COMPLIANCY REVIEW INCLUDED

AUDIO/VISUAL FACE PLATE CONFIGURATION DETAIL

SCALE: NTS

DOOR ACCESS CONTROL DETAIL - SINGLE DOOR

SCALE: NTS

DOOR ACCESS CONTROL DETAIL - DOUBLE DOOR

SCALE: NTS

AUTOMATIC DOOR OPENER DETAIL - SINGLE DOOR

SCALE: NTS

AUTOMATIC DOOR DETAIL - DOUBLE DOOR

SCALE: NTS

POWER OUTLET COORDINTATION REQUIREMENTS

SCALE: NTS

RATED WALL CONDUIT AND SLEEVE PENETRATIONS

SCALE: NTS

MANUFACTURED SLEEVE WALL PENETRATION

SCALE: NTS

CONDUIT TO CABLE TRAY

SCALE: NTS

TELECOMMUNICATIONS GROUNDING BUS BAR (TGB)

SCALE: NTS

UNDER SLAB TO FLUSH MOUNTED FLOOR BOX

SCALE: NTS

TELECOMMUNICATIONS DETAILS

E-005 119 143122

INSTALL COPPER STATIC

DISSIPATION GRID PER

MANUFACTURERS

INSTRUCTIONS

STATIC DISSIPATION

BONDING GRID

RUBBER

BASE TRIM

GROUNDING

BUS BAR

ROUTE 24" COPPER RIBBON

FROM BELOW GRADE STATIC

DISSIPATION GRID TO #6

BONDING WIRE EXPOSED ON

WALL

BOND COPPER

RIBBON TO STATIC

DISSIPATION GRID

TELECOMMUNCIATION ROOM

ROUTE #6 THHN GREEN COPPER GROUNDING

WIRE EXPOSED ON WALL FROM GROUNDING

BUS BAR TO OPPOSING ENDS OF THE STATIC

DISSIPATION GRID. BOND TO 24" COPPER

RIBBON FOR BELOW GRADE CONNECTION

ADO

CABLE TO SECURITY PANEL

BY DIVISION 28 CONTRACTOR;

POWER BY DIVISION 26 TO BE

AT SECURITY PANEL.

COORDINATE POWER REQUIREMENTS

WITH DIVISION 28 CONTRACTOR

JUNCTION BOX

BY DIVISION 26 CONTRACTOR

ABOVE ACCESSIBLE CEILING

CONDUIT BY DIVISON 26 CONTRACTOR.

CABLING BY DIVISON 28 CONTRACTOR.

DOOR RELEASE BUTTON

AND CABLING IN ANY

LOCATION BY DIVISION 28

CONTRACTOR.

CONDUIT AND BACK

BOX, BY DIVISON 26

CONTRACTOR

DC

DOOR

NOTE: IN THE EVENT OF A LOSS OF POWER OR A FIRE ALARM

SIGNAL DOOR LOCKING MECHANISM TO DISABLE ALLOWING

FREE ACCESS THROUGH DOOR.

CONTRACTOR TO PROVIDE AND INSTALL ALL NEW

EQUIPMENT, DEVICES, CONDUIT, AND CABLING WITH THE

USE OF A LENEL CERTIFIED TECHNICIAN. VA SECURITY

DEPARTMENT TO MAKE FINAL CONNECTIONS AND PROGRAM

FOR INTEGRATION TO EXISTING ACCESS CONTROL SYSTEM.

1'' CONDUIT

DIVISION 26;

CABLING BY

DIVISION 28

IDENTIV 8216ABP00DK CARD READER

WITH KEYPAD PROVIDED BY DIVISION

28; IF REQUIRED, 1 - 4'' x 4'' BACKBOX

WITH SINGLE GANG PLASTER RING,

BY DIVISION 26

W P,K

MAG LOCK BY DOOR

HARDWARE VENDOR

CABLING BY

DIVISION 28.

MAG

RTES

RECOMMENDED CABLE TRAY:

· CABLOFIL

· 4 IN. DEEP X 12 IN. WIDE MINIMUM (SIZE COMMENSURATE WITH

DISTRIBUBTION REQUIREMENT)

· WHITE POWERCOAT

· TRAY INSERT

· PART NUMBER: CF105 300 (4 IN. DEPTH, 12 IN. WIDTH)

·· MODIFIED PN FOR VARIOUS DEPTHS AND WIDTHS

3.94 IN.

(100 MM)

6.53 IN.

(156 MM)

118.2 IN.

(3000 MM)1.97 IN.

(50 MM)

RECOMMENDED UTP MEDIA: ATLAS-X1 COPPER TRUNKS

· PN: CTA-U6AP06LxxxF-CYNXA24N-CYNXA24N-CB01E (xxx IS LENGTH IN FEET)

· CAT 6A UTP CMP CABLE ASSEMBLY; BUNDLE OF 6 BLUE CABLES

· BERK-TEK - LANMARK-10G2 (UTP) BRANDED CABLE USED, TIA/EIA WIRING T568B

· TESTED TO ANSI/TIA 568.2-D

· CUSTOM LABELING, NO PULLING EYE

· FIRST END TERMINATION: ATLAS-X1 E2XHD CONNECTOR WITH BLUE JACK 24 IN.

BREAKOUT LENGTH

· SECOND END TERMINATION: ATLAS-X1 E2XHD CONNECTOR WITH YELLOW JACK

24 IN. BREAKOUT LENGTH

B-SIDE JACK COLOR: YELLOW A-SIDE JACK COLOR: BLUE B-SIDE JACK COLOR: YELLOW

RECOMMENDED UTP MEDIA: ATLAS-X1 COPPER TRUNKS

· PN: CTA-U6AP06LxxxF-CLNXA24N-CYNXA24N-CB01E (xxx IS LENGTH IN FEET)

· CAT 6A UTP CMP CABLE ASSEMBLY; BUNDLE OF 6 BLUE CABLES

· BERK-TEK - LANMARK-10G2 (UTP) BRANDED CABLE USED, TIA/EIA WIRING T568B

· TESTED TO ANSI/TIA 568.2-D

· CUSTOM LABELING, NO PULLING EYE

· FIRST END TERMINATION: ATLAS-X1 E2XHD CONNECTOR WITH BLUE JACK 24 IN.

BREAKOUT LENGTH

· SECOND END TERMINATION: ATLAS-X1 E2XHD CONNECTOR WITH YELLOW JACK

24 IN. BREAKOUT LENGTH

A-SIDE JACK COLOR: BLUE

RECOMMENDED UTP MEDIA: ATLAS-X1 COPPER TRUNKS

· PN: CTA-U6AP06LxxxF-CLNXA24N-CLNXA24N-CB01E (xxx IS LENGTH IN FEET)

· CAT 6A UTP CMP CABLE ASSEMBLY; BUNDLE OF 6 BLUE CABLES

· BERK-TEK - LANMARK-10G2 (UTP) BRANDED CABLE USED, TIA/EIA WIRING T568B

· TESTED TO ANSI/TIA 568.2-D

· CUSTOM LABELING, NO PULLING EYE

· FIRST END TERMINATION: ATLAS-X1 E2XHD CONNECTOR WITH BLUE JACK 24 IN.

BREAKOUT LENGTH

· SECOND END TERMINATION: ATLAS-X1 E2XHD CONNECTOR WITH YELLOW JACK

24 IN. BREAKOUT LENGTH

19 IN.

1RU - FRONT VIEW

ANGLED PANEL COVER

REAR CABLE MANAGER

RECOMMENDED UTP PATCH PANEL

· LEVITON E2XHD-BLK HIGH-DENSITY ANGLED

· 48 POSITION

· ONE RU PER PANEL

· WITH REAR CABLE MANAGER

· ANGLED PANEL COVERS

RECOMMENDED MP0-8 STANDARD DENSITY FIBER CASSETTE: LEVITON HDX2 UNITY MTP

· PART NUMBER: 42NM2-S5C

· HDX UNITY MTP CASSETTE

· (0.75 dB) 24-FIBER 0M4

· 3X8-FIBER MTP (MALE) TO 1X24-FIBER MTP (MALE)

· 120G TO 40G; BLACK LATCH; UNIVERSAL POLARITY CASSETTES

RECOMMENDED MP0-24 TRUNK CABLE: OPT-X UNITY ULTRA LOW LOSS MTP TRUNK CABLES

· PART NUMBER: FTU-FW4024JJxxxF36C36CY-NNBS (xxx INDICATES LENGTH IN FEET)

· FIBER TRUNK UNITY

· 24 FIBERS; MULTIMODE 0M4; 24F SUB-UNITS OPT-X SJP

· FIRST END WITH PULLING EYE, CUSTOM LABEL; POLARITY MTP METHOD B

· FIRST END CONNECTOR: 24F LLMTP 0.35dB FEMALE CONNECTOR, BREAKOUT LENGTH

OF 36 IN. INTO 3.6 MM JACKETED FIBER, NO STAGGER

· SECOND END CONNECTOR: 24F LLMTP 0.35 dB FEMALE CONNECTOR, BREAKOUT

LENGTH OF 36 IN. INTO 3.6 MM JACKETED FIBER, NO STAGGER

RECOMMENDED LC FIBER SPLICE CASSETTE: LEVITON HDX

PART NUMBER: SPLCH-12AQ (0M4)/SPLCH-12GN (0S2)

· HDX 0M4 LC CASSETTE, (0.15 dB) 12-FIBER 0M4 TO 12X1-FIBER LC(UPC)

· HDX 0S2 LC CASSETTE, (0.24 dB) 12-FIBER 0S2 TO 12X1-FIBER LC(APC)

RECOMMENDED MP0-8 TO MP0-8 PATCH CORDS:

· LEVITON OPT-X UNITY ULTRA LOW LOSS ARRAY CORDS

· PART NUMBER: UL548MM-BxxxF (xxx INDICATED LENGTH IN FEET)

· OPT0X UNITY 40-100G MTP ARRAY CORD (3 MM ROUND CABLE),

MULTIMODE (0M4), 8 FIBERS, ULMTP 8 FIBER FEMALE TO ULMTP 8

FIBER FEMALE, METHOD B POLARITY)

RECOMMENDED LC TO LC PATCH CORDS:

· LEVITON PREMIUM PLUS FIBER PATCH CORDS

· 0M4: PART NUMBER: PCF-M4PD1RR-xxxxF (xxxx INDICATED LENGTH IN

FEET TO 0.5 FT. [I.E. 5 FT. = 0050])

·· PREMIUM PLUS FIBER PATCH CORD, 0M4 AQUA, PLENUM, DUP-ZIP

1.6 MM, LC, LC, ULTRA POLISHED CONNECTORS (UPC)

· OS2: PART NUMBER: PCF-S2PD1FF-xxxxFAB (xxxx INDICATES LENGTH

IN FEET TO 0.5 FT.)

·· PREMIUM PLUS FIBER PATCH CORD, 0S2 YELLOW, PLENUM,

DUP-ZIP 1.6 MM, LC/APC, LC/APC, A-B POLARITY (PART NUMBER

PCF-S2PD1FF-xxxxFAA FOR A-A POLARITY)

· RECOMMENDED LC FIBER CASSETTE: LEVITON HDX2 UNITY MTP

· PART NUMBER: 41LSM4-UNN

· HDX UNITY MTP CASSETTE, (0.35 dB), 12-FIBER 0M4, LC SHUTTERED (AQUA) TO

1X12-FIBER MTP, UNIVERSAL POLARITY, BLACK LATCH UNIVERSAL POLARITY

CASSETTES

RECOMMENDED MP0-12 TRUNK CABLE: OPT-X UNITY ULTRA LOW LOSS MTP TRUNK CABLES

· PART NUMBER: FTU-FW2012LLxxxF36B36BY-NNBC (xxx INDICATES LENGHT IN FEET)

· FIBER TRUNK UNITY; 12 FIBER, MULTIMODE 0M4; 12F SUB-UNITS OPT-X SJP; OVERALL

CABLE LENGTH OF 100 FT; FIRST END WITH PULLING EYE, CUSTOM LABEL; POLARITY

MTP METHOD B;L FIRST END CONNECTOR: 12F ULMTP 0.20 dB FEMALE CONNECTOR, BREAKOUT LENGHT OF 36 IN. INTO 2 MM JACKETED FIBER, NO STAGGER; SECOND END

CONNECTOR: 12F ULMTP 0.20 dB FEMALE CONNECTOR, BREAKOUT LENGTH OF 36 IN.

INTO 2 MM JACKETED FIBER, NO STAGGER

RECOMMENDED LC FIBER CASSETTE: LEVITON HDX2 UNITY MTP

· PART NUMBER: 42LSM2-21C

· HDX2 UNITY MTP CASSETTE, (0.50 dB), 24-FIBER 0M4, LC SHUTTERED TO 1X24-FIBER MTP

(MALE), 120G TO 10G, BLACK LATCH UNIVERSAL POLARITY CASSETTES

RECOMMENDED MP0-24 TRUNK CABLE: OPT-X UNITY ULTRA LOW LOSS MTP TRUNK CABLES

· PART NUMBER: FTU-FW4024JJxxxF36C36CY-NNBS (xxx INDICATES LENGHT IN FEET)

· FIBER TRUNK UNITY; 24 FIBER, MULTIMODE 0M4; 24F SUB-UNITS OPT-X SJP; FIRST END

WITH PULLING EYE, CUSTOM LABEL; POLARITY MTP METHOD B;L FIRST END

CONNECTOR: 24F LLMTP 0.35 dB FEMALE CONNECTOR, BREAKOUT LENGHT OF 36 IN.

INTO 3.6 MM JACKETED FIBER, NO STAGGER; SECOND END CONNECTOR: 24F LLMTP 0.35

dB FEMALE CONNECTOR, BREAKOUT LENGTH OF 36 IN. INTO 3.6 MM JACKETED FIBER, NO STAGGER

RECOMMENDED FIBER DISTRIBUTION PANEL:

· LEVITON ANGLED OPT-X UHDX

· 144 FIBER

· ONE RU

P/N: OR-MM20VMD706 (OR EQUIVALENT)

MM20 VERTICAL CABLE MANAGEMENT

"CAGE", WITH DOOR, 6.45 IN. X 10.26 IN. X

76.94 IN., WHITE

CAPACITY: 350 CATEGORY 6A PATCH CORDS

OR 245 CATEGORY 6A PATCH CORDS

LARGER VCM AUTHORIZED IN ACCORDANCE

WITH CABLING REQUIREMENT

76.94 IN.

10.26 IN. 6.45 IN.

NOTE: TELECOMMUNICATION CHANNEL RACKS

ARE REQUIRED IN ALL TELECOMUNICATION ROOMS.

TELECOMMUNICATION CHANNEL RACKS OR

TELECOMMUNICATION CABINETS MAY BE USED IN

THE HORIONTAL AND MAIN DISTRIBUTION AREAS.

16.00 IN.

23.75 IN.

30.00 IN.

40.00 IN.

84.00 IN.

86.00 IN.

P/N: OR-MM2073038-W (OR EQUIVALENT)

MIGHTY MO 20 CABLE MANAGEMENT RACK

30 IN. CHANNEL DEPTH, 7 FT HIGH, WHITE

FINISH OR EQUIVALENT

DIMENSIONS:

USABLE HEIGHT: 45 RU

DEPTH (US): 30 IN.

HEIGHT (US) 7 FT

WIDTH (US): 23.75 IN.

STATIC LOAD CAPACITY: 2000 lb

SQUARE HOLD P/N: OR-MM20724PDHD-W

23.31 IN.

77.00 IN.

MM20 DOOR MOUNT KIT

UPPER & LOWER BRACKETS

(SOLD SEPERATELY)

MM20 RACK 7FT

(SOLD SEPARATELY)

CAN BE FRONT OR

REAR MOUNTED

P/N: OR-MM2024DMFHD-W

KIT INCLUDES:

(1) TOP DOOR SUPPORT

(1) LOWER DOOR SUPPORT

WITH 2 FAN OPENINGS

82.36 IN. 7FT RACK

94.09 IN. 8 FT RACK

12.55 IN.23.63 IN.

MM20, PERFORATED

DOOR, 7 FT OR 8 FT,

24 IN. WIDE (SOLD

SEPERATELY)

MM20, PERFORATED

DOOR, 7 FT OR 8 FT,

24 IN. WIDE (SOLD

SEPERATELY)

P/N: OR-MM2024DMRHD-W P/N: OR-MM20PDUMB1D2W-W

20A 120/ 208V

Y

CHATSWORTH ECONNECT PDUJ OR EQUIVALENT;

VERTICAL; MONITORED; L21-20 PLUG; THREE-PHASE;

120/208 V INPUT; 20 A; (30) C13 (6) C19 OUTLETS; 208 V

OUTPUT; 3 x 2P 20 A; LCD; ETHERNET, USB, AND

ENVIRONMENTAL SENSOR PORTS; IP AND SERIAL

MONITORING; IP CONSOLIDATION (PDU LINKING);

TOOL-LESS MOUNTING; 70.5 IN. H (1791 MM) X 2.2 IN. W

(56 MM) X 2.2 IN. D (56 MM)

REQUIRES ONE L21-20R

RACK MOUNT UPS

CAPACITY: 5 kW (EXTERNAL BATTERY MODULES AVAILABLE)

INPUT VOLTAGE: 208 V

INPUT CONNECTION: L21-20P, THREE-PHASE, FOUR-WIRE + GROUND

OUTPUT CONNECTION: L21-20R

SIZE: 6 RU, 19 IN. RACK-MOUNTABLE

RUNTIME: 16.5 MINUTES AT 50% LOAD

(EATON BLADEUPS ZC0517700110000 OR EQUIVALENT

20A 120/ 208V

Y

MODULAR UPS OPTIONS FOR COMPUTER ROOMS

A

B

GROUP A B A BGROUP GROUP GROUP

LEG 1 LEG 2 LEG 1 LEG 2

OZ OY OX OZ

GRP A LEG 2

GRP B LEG 1

GRP A LEG 2

GRP B LEG 1

GRP A LEG 2

GRP B LEG 1

PHASE Z PHASE Y PHASE X

30 A THREE-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH FOUR L21-20R AND SIX

NEMA 5-20 OUTLETS AND TWO 10 FT POWER CORDS TERMINATING IN L21-30P ZONIT

ZPDS-208V30A-L21-4L21-20R-CR OR EQUIVALENT

ZONE PDU INPUTS

REQUIRE TWO L21-30Rs

NOTE: THE CORRECT SPECIFICATION FOR THE ZONE PDU IS TO ENERGIZE IT FROM

TWO INDEPENDENT POWER SOURCES. EACH INPUT WILL USE IDENTICAL SPECS: WYE

(5-WIRE), 208 V, 30 A, THREE-PHASE, TERMINATING IN A NEMA L21-30R LOCKING

RECEPTACLE. THE NEUTRAL CONDUCTOR SHOULD BE UPSIZED ON GAUGE TO MATCH

THE UPSIZED NETUTRAL CONDUCTOS IN THE ZONE PDU UNITS. THE NEUTRAL

"UPSIZING" SHOULD IDEALLY BE CONTINUED IN THE POWER DISTRIBUTION SYSTEM

BACK TO THE UPS OR TRANSFORMER WINDING POLE. THIS INCREASES THE EFFICIENCY

OF THE POWER DISTRIBUTION SYSTEM AND SUPPRESSES HARMONICS IN THE SYSTEM.

OYOX OXOZ OZOY OYOX

BLADE UPS

LEVITON

LEVITON

LEVITON

LEVITON

LEVITON

LEVITON

LEVITON

LEVITON

LEVITON

LEVITON

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6

O U

T

IN

O

BCN STS ENV

CISCO NEXUS N9K-C9108TC-FX

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54

BCN STS ENV

CISCO NEXUS N9K-C9108TC-FX

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54

BCN STS ENV

CISCO NEXUS N9K-C9108TC-FX

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54

BCN STS ENV

CISCO NEXUS N9K-C9108TC-FX

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54

BCN STS ENV

CISCO NEXUS N9K-C9108TC-FX

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54

MAIN

POWER

POWER

ON

GROUP A

ON

OFF

MAIN

POWER

POWER

ON

GROUP B

ON

OFF

GROUP A GROUP B

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

A B C A B C A B C A B C

PATCHING

(UP TO A MAXIMUM 480 PASSIVE WAOs

FOR BOTH OIT & FMS SYSTEMS)

SWITCHING

(UP TO A MAXIMUM 240 ACTIVE WASs

FOR OIT SYSTEMS)

POWER & FMS ACTIVE EQUIPMENT

IF ISP: 24-STRAND 0M4 PER SIDE, 12-STRAND

SM PER SIDE

IF OSP: 24-STRAND SM PER SIDE (NOT SHOWN)

24-STRAND 0M4 (B-SIDE)

12-STRAND SM (B-SIDE)

24-STRAND 0M4 (A-SIDE)

24-STRAND 0M4 (A-SIDE)

ANGLED FIBER PATCH PANEL FOR

BACKBONE CONNECTION TO MCR

CAT 5E PATCH PANEL FOR ANALOG

TELEPHONY & OTHER TWO-WIRE

APPLICATIONS

PRIMARY PROTECTOR (*OSP

APPLICATIONS ONLY)

48-PORT CAT 6A ANGLED PATCH

PANELS TO WAOs (TYPICAL)

1 RU HORIZONTAL CABLE MANAGER

(TYPICAL)

2 RU HORIZONTAL CABLE MANAGER

(TYPICAL)

NETWORK ACCESS SWITCH

(TYPICAL)

BLANKING PANELS (TYPICAL)

ZONE PDU (zPDU)

5 kW UPS (L21-20 INPUT/L21-20

OUTPUT)

BLADE UPS BLADE UPS

LEVITON

LEVITON

LEVITON

LEVITON

LEVITON

LEVITON

LEVITON

LEVITON

LEVITON

LEVITON

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6 CAT6

O

BCN STS ENV

CISCO NEXUS N9K-C9108TC-FX

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54

BCN STS ENV

CISCO NEXUS N9K-C9108TC-FX

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54

BCN STS ENV

CISCO NEXUS N9K-C9108TC-FX

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54

BCN STS ENV

CISCO NEXUS N9K-C9108TC-FX

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54

BCN STS ENV

CISCO NEXUS N9K-C9108TC-FX

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54

MAIN

POWER

POWER

ON

GROUP A

ON

OFF

MAIN

POWER

POWER

ON

GROUP B

ON

OFF

GROUP A GROUP B

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

A B C A B C A B C A B C

BAYSTACK

INSTANT INTERNET

PWR 1 2 3 4 5 6 7 8

1000BASE-SX

TX RX 450 1SX MDA

ACTIVITY

PHY

LNK

1 3 5 7 9 11 13 15 17 19 21 23

2 4 6 8 10 12 14 16 18 20 22 24

BAYSTACK 410-24T SWITCH

1 3 5 7 9 11 13 15 17 19 21 23

2 4 6 8 10 12 14 16 18 20 22 24

RESET

USB A

MANAGEMENT

SPEED LINK/ACT

CONSOLE

CF

POWER SUPPLY SWITCH FABRIC AUXILIARY

MODULES

CONTROL

PROCESSOR

9080CP

ONLINE

MASTER

SYSTEM

TEMP

AUX1 2 1 2

B

BA

A

FRONT REAR

1 1

GE 0/4SFPGE 0/3GE 0/1

GE 0/2

1 2

3 4

SR4134

1 3 5 7

SLOT 2

IN USE 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

LINK/ACT LINK/ACT OPT41

PWR

STATUS

RPS

FAN

1 3 5 7

SLOT 1

IN USE 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

LINK/ACT LINK/ACT OPT41

VSP 8284XSQ

CONSOLE

USB

STATUS FAN

PWR RPS

VSP 8404

COUNTERACT

COUNTERACT

1 2 3 4 5 6

25 26 27 28 29 30 31 32 33 34 35 36

7 8 9 10 11 12

37 38 39 40 41 42

13 14 15 16 17 18

43 44 45 46 47 48

19 20 21 22 23 24

1 2 3 4 5 6

25 26 27 28 29 30 31 32 33 34 35 36

7 8 9 10 11 12

37 38 39 40 41 42

13 14 15 16 17 18

43 44 45 46 47 48

19 20 21 22 23 24

PATCHING (UP TO A MAXIMUM 480

PASSIVE WAOs FOR BOTH OIT & FMS

SYSTEMS)

SWITCHING (UP TO A MAXIMUM 240

ACTIVE WAOs FOR OIT SYSTEMS)

POWER & FMS ACTIVE EQUIPMENT

PDU

A

PDU

B

RACK/ENCLOSURE

RACKED EQUIP

PS1 PS2

PDU

A

PDU

B

RACK/ENCLOSURE

RACKED EQUIP

PS1 PS2

LEG1 LEG2

ZONE PDU

BUS A BUS B

RACK-MOUNT

UPS

RACK-MOUNT

UPS

C B1

C B2

C B3

O

FF

N

I

O

O

FF

O

O

FF

O N I

O

C H

AT

SW

O R

TH

PR

O D

U C

T

CB1

CB1

CB2

CB2

R

ES

ET

O K

W

AR

N

IN

G C

R

IT

IC

AL

TE

M

P/ H

U M

ID

IT

Y O

U T

IN

IO

IO

IO

/1

CB3

CB3

CB1

CB1

CB2

CB2

CB3

CB3

C B1

C B2

C B3

O

FF

O

O

FF

O

O

FF

O N I

O

C H

AT

SW

O R

TH

PR

O D

U C

T

CB1

CB1

CB2

CB2

R

ES

ET

O K

W

AR

N

IN

G C

R

IT

IC

AL

TE

M

P/ H

U M

ID

IT

Y O

U T

IN

IO

IO

IO

/1

CB3

CB3

CB1

CB1

CB2

CB2

CB3

CB3

C B1

C B2

C B3

O

FF

O

O

FF

O

O

FF

O N I

O

C H

AT

SW

O R

TH

PR

O D

U C

T

CB1

CB1

CB2

CB2

R

ES

ET

O K

W

AR

N

IN

G C

R

IT

IC

AL

TE

M

P/ H

U M

ID

IT

Y O

U T

IN

IO

IO

IO

/1

CB3

CB3

CB1

CB1

CB2

CB2

CB3

CB3

C B1

C B2

C B3

O

FF

O

O

FF

O

O

FF

O N I

O

C H

AT

SW

O R

TH

PR

O D

U C

T

CB1

CB1

CB2

CB2

R

ES

ET

O K

W

AR

N

IN

G C

R

IT

IC

AL

TE

M

P/ H

U M

ID

IT

Y O

U T

IN

IO

IO

IO

/1

CB3

CB3

CB1

CB1

CB2

CB2

CB3

CB3

L21-30P SIDE B

REQUIRES A 208 V, 30 A, THREE-PHASE

CIRCUIT, TERMINATING IN A NEMA

L21-30R LOCKING RECEPTACLE

L21-30P SIDE A

REQUIRES A 208 V, 30 A, THREE-PHASE

CIRCUIT, TERMINATING IN A NEMA

L21-30R LOCKING RECEPTACLE

ZONE PDU

30 A THREE-PHASE ZONE PDU BASE

UNIT - REQUIRES TWO 30 A

THREE-PHASE (WYE) CIRCUITS WITH

L21-30R RECEPTACLES; OPTIONALLY,

UPSs AND B-SIDE RPDUs MAY BE

POWERED DIRECTLY WITH L21-20

RACK-MOUNTED 5kW, 208 V

UPS WITH NEMA 20A

L21-20P INPUT AND L21-20R

OUTPUT

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COM

D E S I G N I N C.

Office of Construction and Facilities Management

Project Number

Building Number

Drawing Number

Dwg.

DrawnCheckedDate

Location

Project TitleDrawing Title

Approved: Project Director

ARCHITECTCONSULTANTS:

DateRevisions:

VA FORM 08-6231

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

1 2 3 4 5 6 7 8 9

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9

Department of Veterans Affairsof

16.2330.A08

11/23/2020 KABWEW

4101 Woolworth Ave #4199 Omaha, Ne 68105Omaha VA Medical Center

Design/Construct Sterile Processing Service - Omaha VA Medical Center

CONSTRUCTION DOCUMENTS

FOURFRONT

ALBERTSON ENGINEERING, INC.

315 NORTH MAIN AVENUE, SUITE 200

SIOUX FALLS, SOUTH DAKOTA 57104

PH: (605) 274-0880

FARRIS ENGINEERING

12700 WEST DODGE ROAD

OMAHA, NEBRASKA 68154

PH: (402) 330-5900

TERRASITE DESIGN

1635 DEADWOOD AVENUE

RAPID CITY, SOUTH DAKOTA 57702

PH: (605) 791-1736

COMPLIANCY REVIEW INCLUDED

SCALE: NTS

TELECOMMUNICATIONS DETAILS

E-006

STATIC DISSAPATIVE FLOORING SCHEMATIC

SCALE: NTS

2 ACCESS CONTROL SCHEMATIC

SCALE: NTS

3 CABLE TRAY BASIS OF DESIGN

SCALE: NTS

4 B-SIDE UTP TRUNK CABLES

SCALE: NTS

5 A-SIDE TO B-SIDE CROSS CONNECT UTP TRUNK CABLES

SCALE: NTS

6 A-SIDE UTP TRUNK CABLES

SCALE: NTS

7 PATCH PANEL BASIS OF DESIGN

SCALE: NTS

8 FIBER DISTRIBUTION EQUIPMENT BASIS OF DESIGN

SCALE: NTS

9 TELECOMMUNICATIONS RACK BASIS OF DESIGN

SCALE: NTS

10 TELECOMMUNICATIONS RACK POWER DISTRIBUTION EQUIPMENT BASIS OF DESIGN

SCALE: NTS

11 TELECOMMUNICATIONS EQUIPMENT LAYOUT IN RACK

SCALE: NTS

12 TELECOMMUNICATIONS RACK POWER DISTRIBUTION EQUIPMENT SCHEMATIC

143123

FIRST FLOOR

SECOND FLOOR

THIRD FLOOR

25.2.LLB

25.2.LLMDP

13,800V TO 208V

TRANSFORMER

25.2.LHB

25.2.LHMDP

25.2.LLA

25.2.LLC

13,800V TO 480V

TRANSFORMER

200A

200A

100A 600A

800A

1000A

NEW MEDIUM

VOLTAGE LOAD

INTERRUPTER

SWITCHGEAR

60A

NOTE: FROM INFORMATION

PROVIDED TO ENGINEER BY

VA CIRCUIT 95 CURRENTLY

HAS A CAPACITY OF 225 AMPS

TO BUILDING 25 AND IS USING

A PEAK DEMAND OF 80 AMPS.

NOTE: FROM INFORMATION

PROVIDED TO ENGINEER BY

VA CIRCUIT 90 HAS A

CAPACITY OF 225 AMPS TO

BUILDING 25 AND IS USING A

PEAK DEMAND OF 30 AMPS.

NOTE: FROM INFORMATION

PROVIDED TO THE ENGINEER

BY VA CIRCUIT 95 IS 100%

BACKED UP BY ONSITE

GENERATOR REMOVING THE

NEED FOR AN ADDITIONAL

GENERATOR TO BE

INSTALLED ON THIS PROJECT.

BUILDING 25 INTERIOR

MAIN

MAIN

IN BASEMENT CEILING

SET SWITCH FOR

PRIMARY POWER

FROM CIRCUIT 95 AND

SECONDARY POWER

FROM CIRCUIT 90

4" EMT WITH (4) #2 MV-90

CABLE + #8 CU GRND

(3) 3" EMT CONDUITS

EACH WITH (8) 2/0

THHN + 1/0 CU GRND

(24) 250 KCMIL THHN

+ (1) 2/0 CU GRND IN

(3) 4" EMT CONDUITS

2-1/2" EMT CONDUIT WITH

(4) 4/0 THHN + #2 CU GRND

2-1/2" EMT CONDUIT WITH

(4) 4/0 THHN + #2 CU GRND

1-1/2" EMT CONDUIT

WITH (4) #2 THHN +

#6 CU GRND

(16) 4/0 THHN

+ 2/0 CU GRND IN

(2) 3" EMT CONDUITS

NEW UNDERGROUND DUCT

BANK. REFER TO SHEET E-008.

CAP 6" SPARE CONDUITS AT

ENTRANCE TO BASEMENT

MECHANICAL ROOM.

CONTRACTOR TO

PROVIDE 1000 AMP

MAIN BREAKER WITH

GFI PROTECTION

BASEMENT

13,800V

SECTIONALIZING

CABINET

13,800V

SECTIONALIZING

CABINET

CIRCUIT #90. CONTINUES TO

MEDIUM VOLTAGE SWITCHGEAR

SECTION 2, FEEDER #4.

CONNECT TO MEDIUM VOLTAGE CIRCUIT

#90 IN MANHOLE #8 USING LOAD BREAK

STYLE CONNECTORS. COORDINATE

WITH EXISTING CONDITIONS.

CONNECT TO MEDIUM VOLTAGE CIRCUIT

#95 IN MANHOLE #9 USING LOAD BREAK

STYLE CONNECTORS. COORDINATE

WITH EXISTING CONDITIONS.

NEW UNDERGROUND

DUCT BANK. REFER

TO SHEET E-008.

NEW 6" CONDUIT TO BE INSTALLED

IN NEW DUCT BANK FOR FUTURE

USE. CAP WITHIN MANHOLE. NEW 6" CONDUIT TO BE INSTALLED

IN NEW DUCT BANK FOR FUTURE

USE. CAP WITHIN MANHOLE.

CORE DRILL, SLEEVE, AND SEAL

BUILDING WALL PENETRATIONS. (TYP)

FIRST FLOOR ROOF

BUILDING 25 EXTERIOR

PANEL DPA2

60A

400A MAIN

PANEL DPB2

60A

400A MAIN

CIRCUIT #95. CONTINUES TO

MEDIUM VOLTAGE SWITCHGEAR

SECTION 1, FEEDER #2.

MANHOLE #8 MANHOLE #9

4" EMT WITH (4) #2 MV-90

CABLE + #8 CU GRND

TR.B1.3.2

1-1/4" EMT

CONDUIT WITH

(4) #4 THHN + #8

CU GRND

1-1/4" EMT CONDUIT WITH

(4) #4 THHN + #8 CU GRND

CONTINUES TO EXISTING

TRANSFORMER TA2.

CONTINUES TO EXISTING

TRANSFORMER TB2.

TR.A1.3.2

CONTRACTOR TO INSTALL

NEW SQUARE D NQ430L1C 100

AMP ELECTRICAL PANEL.

CORE DRILL, SLEEVE, AND SEAL

MANHOLE WALL PENETRATIONS.

(TYP)

CORE DRILL, SLEEVE, AND SEAL

SLAB PENETRATIONS. (TYP)

EXISTING CIRCUIT #95 PROVIDING POWER TO SITE IS 100%

BACKED UP FROM EMERGENCY GENERATOR POWER.

ELECTRICAL SERVICE NOTE

SECOND FLOOR

THIRD FLOOR

SF

ROOF

VAV-6

CB

SF

VV-1E

CB

SF

VV-1S

CB

VV-2E

CB

SF

VV-2S

CB

VV-3E

CB

SF

VV-3S

CB

VV-4E

CB

SF

VV-4S

CB

VV-24E

CB

SF

VV-24S

CB

SF SF SF SF SF SF

VAV-5

CB

VV-10E

CB

VV-12E

CB

VV-11E

CB

VV-12S

CB

VV-10S

CB

VV-11S

CB

SF

VV-13E

CB

SF

VV-13S

CB

SF

VV-17S

CB

SF

VV-15E

CB

SF

VV-17E

CB

SF

VV-16S

CB

SF

VV-14E

CB

SF

VV-15S

CB

SF

VV-14S

CB

SF

VV-16E

CB

SF SF SF SF

VV-19E

CB

VV-18E

CB

VV-19S

CB

VV-18S

CB

SF

VAV-7

CB

SF

VAV-8

CB

SF

VAV-9

CB

SF SF SF

VAV-20

CB

VAV-21

CB

VAV-22

CB

25.2.LLB-225.2.LLC-1

25.2.LLB-125.2.LLA-1

T T T T T T T T T T T T T T T T T T T T T T T T T T T

T T T T T T

T T T T T

FUSESTAT LOCATED IN

ACCESSIBLE CEILING

SPACE (TYP)

VAV CONTROL

BOX (TYP)

VV CONTROL

BOX (TYP)

120V TO 24V 40 VA

TRANSFORMER FOR VAV OR

VV CONTROL POWER (TYP)

FOURFRONT DESIGN, INC.

517 7TH…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .