Attachment 03 - Set 1_G Series_Part2.pdf
PDF 25 MB Posted
- Attached to
- Y1DA--636-502 Construct Sterile Processing Service VISN 23 Federal contract opportunity
- Solicitation number
- 36C77625R0063
About this file
This file is a comprehensive set of architectural and engineering drawings for the Design/Construct Sterile Processing Service project at the Omaha VA Medical Center. The project involves renovating and expanding facilities on the second and third levels of an existing building, with a focus on creating a new sterile processing service area. The drawings include detailed plans for spaces such as scope processing rooms, decontamination areas, cart wash zones, sterilization rooms, locker rooms, and support spaces totaling approximately 15,000 square feet.
Key technical details include constructing new walls using metal studs with specific fire ratings, installing resinous flooring and porcelain tile in specialized areas, implementing sophisticated mechanical and electrical systems, and integrating specialized medical equipment zones. The project involves complex demolition and renovation work within an active medical facility, with specific attention to maintaining infection control standards, managing traffic flow, and ensuring precise technical specifications for medical processing environments. The design emphasizes functional workflow, clean/sterile separation, and compliance with VA medical facility standards.
View the file
Other files for this federal contract opportunity
Show all 36
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PARKING LOT #1
EI
SE
N H
O W
ER
D
R
N
EM
IT
Z
D R
BUILDING #7
S
CO CO
SS
SS
SS
SS
SS
O
O O
O
O O
O
O O
O
O
O O
O O
SS
CO
P P
P
C C
C C
C C
C C
C C
C C
C C
C
C C
C C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C C
C
C C C C
C
C C
C
C
CC
C
C
C
C C
C C
C C
CC
CC
CC
CC
C C
C C
C C
C C
C C
C C
C C
C C
C C
C C
C C
C C
C C
C C
C C
C C
C C
C C
BUILDING #8
FFE = 1117.00'
THICKENED PAVEMENT EDGE, TYP. - SEE F4/C-501
STANDARD CURB AND GUTTER - SEE A1/C-500
CURB TAPER - SEE F1/C-500
CURB ISOLATION JOINT - SEE A4/C-500
SEE A8/C-500 FOR ASPHALT ABUTMENT DETAIL
EQUALLY SPACED CONTRACTION JOINTS THIS AREA (6' PREFERRED); 4'
MIN., 6' MAX. FOR NEW SIDEWALK
EQUALLY SPACED CONTRACTION JOINTS THIS AREA (7' PREFERRED);
5' MIN., 8' MAX. FOR NEW SIDEWALK
DOWELED CONSTRUCTION JOINT
CURB CONSTRUCTION JOINT
DOWELED CONSTRUCTION OR CONTRACTION JOINT
ISOLATION JOINT
CONTRACTION JOINT FOR SIDEWALK
JOINTED PLAIN CONCRETE PAVEMENT - SEE A7/C-500
STANDARD CONCRETE SIDEWALK - SEE E1/C-500
ASPHALT PAVEMENT - SEE E4/C-500
C C C C C
NOTES:
1. EXISTING JOINTS WERE NOT LOCATED IN THE FIELD AND ARE APPROXIMATE.
2. THE LOCATION OF JOINTS AS SHOWN/OR DESIGNATED ON THIS SHEET ARE ONLY
APPROXIMATE LOCATIONS TO BE USED AS A GUIDE IN THE FINAL LOCATION OF THE
JOINTS AND TO AFFORD BIDDERS A BASIS FOR ESTIMATING THE CONSTRUCTION
COSTS OF THE JOINTS. JOINTS IN NEW PAVEMENT SHALL ALIGN WITH EXISTING
JOINTS, WHEREVER POSSIBLE. THE FINAL LOCATION OF THE JOINTS IS TO BE
CONFIRMED BY THE COR DURING CONSTRUCTION.
3. SEE F4/C-501 FOR JOINT TYPE CONSTRUCTION DETAILS.
4. MAXIMUM CONCRETE PAVEMENT JOINT SPACING IS 15' UNLESS OTHERWISE NOTED.
5. PROVIDE EXPANSION JOINTS AT A MAXIMUM 100' FT SPACING FOR SIDEWALKS.
6. SEE F4/C-501 FOR SIDEWALK CONTRACTION AND ISOLATION JOINTS.
7. IF EXISTING CONCRETE PAVEMENT IS LESS THAN 7" THICK, CONTACT THE COR FOR
DIRECTION.
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
on e ei gh th in ch o ne fo ot on e qu ar te r i nc h on e fo ot th re e ei gh th s in ch o ne fo ot on e ha lf in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e ha lf in ch es o ne fo ot th re e in ch es o ne fo ot
6"
6"
6"
6"
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
16.2330.A08
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
TERRASITE DESIGN
1635 DEADWOOD AVENUE
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 791-1736
6/10/2025REVISED ELECTRICAL DUCT BANK LOCATION
8/ 5/
1:
:2
AM
CONSTRUCTION DOCUMENTS
11/23/2020
Design/Construct Sterile Processing Service- Omaha VA Medical Center
JMSM
4101 Woolworth Ave #4199 Omaha, Ne 68105Omaha VA Medical Center
16.2330.A08 138
11/23/2020
JOINTING PLAN
CP100
00 20' 40'
JOINTING PLAN
1"=20'CP100
S
CO CO
SS
SS
O
O
O
O
O
O
CO
S
CO CO
SS
SS
O
O
O
O
O
O
O
O
O O
O O
CO
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
on e ei gh th in ch o ne fo ot on e qu ar te r i nc h on e fo ot th re e ei gh th s in ch o ne fo ot on e ha lf in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e ha lf in ch es o ne fo ot th re e in ch es o ne fo ot
6"
6"
6"
6"
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
16.2330.A08
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
TERRASITE DESIGN
1635 DEADWOOD AVENUE
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 791-1736
6/10/2025REVISED ELECTRICAL DUCT BANK LOCATION
8/ 5/
1:
:2
AM
CONSTRUCTION DOCUMENTS
11/23/2020
Design/Construct Sterile Processing Service- Omaha VA Medical Center
JMSM
4101 Woolworth Ave #4199 Omaha, Ne 68105Omaha VA Medical Center
16.2330.A08 138
11/23/2020
TRAFFIC CONTROL PLAN
CT100
BUILDING #8
PARKING #1
ACCESS TO
PARKING
LOT #1
OVERALL TRAFFIC PLAN
1"=50'
SANITARY SEWER INSTALLATION TRAFFIC PLAN
1"=40'
CHANNELIZING DEVICES
TRAFFIC SIGNAL
TRAFFIC SIGNAL
CHANNELIZING DEVICES
EXISTING STOP BAR
4W
4Y
24W
LEGEND
24" WHITE TEMPORARY
PAVEMENT MARKING
4" YELLOW TEMPORARY
PAVEMENT MARKING
42" CHANNELIZING DEVICE
OR BARREL
PORTABLE TRAFFIC LIGHT
SYSTEM - SEE NOTE 5
ONE-WAY ROUTE
TEMPORARY CONSTRUCTION
FENCE
4Y
24W
R10-6 W3-3 W20-4 W20-1 W1-4L W1-4R
R11-2B-18
CHANNELIZING
DEVICES
TYPE III BARRICADES
PARKING LOT
ENTRANCE
CLOSED
PROTECT
LIGHT POLE
CT100
CT100
ACCESS TO
PARKING
LOT #1
PARKING LOT
ENTRANCE
CLOSED
TEMPORARY
GRAVEL
ACCESS ROAD
CHANNELIZING DEVICES
CHANNELIZING DEVICES
PROTECT
LIGHT POLE
12.5' MAX
PARKING #1
TRAFFIC CONTROL NOTES
1. CONSTRUCTION SIGNING AND TRAFFIC CONTROL SHALL CONFORM TO THE MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES (MUTCD), AND AS DIRECTED BY THE CONTRACTING OFFICER'S REPRESENTATIVE (COR) ON OMAHA VA PROPERTY.
2. ALL TEMPORARY FIXED LOCATION SIGNS AND APPLICABLE TRAFFIC CONTROL DEVICES SHALL BE INSTALLED PRIOR TO THE START OF WORK IN THE APPLICABLE PHASE. ALL TEMPORARY TRAFFIC CONTROL SIGNAGE SHALL BE ATTACHED TO TUBULAR STEEL OR APPROVED EQUIVALENT PAINTED BLACK AND BURIED A MINIMUM OF 3' IN THE GROUND OR ANCHORED WITH ADEQUATE SANDBAGS TO PREVENT BLOWING OVER. ALL TEMPORARY SIGNAGE SHALL BE REMOVED AFTER THEY WILL
BE NO LONGER UTILIZED.
3. THE CONTRACTOR OR DESIGNATED TRAFFIC CONTROL SUBCONTRACTOR SHALL MAKE AFTER DARK INSPECTIONS EVERY WEEK TO INSURE THE ADEQUACY, LEGIBILITY, AND REFLECTIVITY OF EACH SIGN AND DEVICE. A WRITTEN SUMMARY OF EACH INSPECTION SHALL BE GIVEN TO THE PROJECT MANAGER WITHIN 24 HOURS AFTER COMPLETION OF THE INSPECTION.
4. CONSTRUCTION SIGNS THAT ARE TO BE INSTALLED SHALL NOT BLOCK THE VIEW OF EXISTING APPLICABLE TRAFFIC SIGNS. NON-APPLICABLE SIGNING WILL BE COVERED OR REMOVED DURING PERIODS OF INACTIVITY.
5. THE WEST SIDE OF BUILDING 8 IS THE ONLY ACCESS TO THE EMERGENCY ROOM ENTRANCE. ACCESS TO THIS ENTRANCE MUST BE MAINTAINED AT ALL TIMES. TWO LANES OF TRAFFIC SHALL REMAIN OPEN ON ALL ROADS THROUGHOUT THE ENTIRE PROJECT WITH THE FOLLOWING EXCEPTIONS. FOR SHORT DURATIONS (8 HOURS OR LESS), CONTRACTOR SHALL PROVIDE APPROPRIATE SIGNAGE AND FLAGGERS AT BOTH ENDS OF ONE LANE TRAFFIC WITH RADIO COMMUNICATIONS. FOR WORK ON THE SANITARY SEWER MAIN/SERVICE AND ASSOCIATED RESTORATION OF PAVEMENT, PORTABLE TRAFFIC LIGHT SYSTEMS WITH EMERGENCY VEHICLE PRE-EMPTION OPTION (BASED ON EMERGENCY VEHICLE STROBE LIGHT PATTERNS) SHALL BE UTILIZED AT BOTH ENDS FOR ONE LANE TRAFFIC. THE PORTABLE TRAFFIC LIGHT SYSTEMS SHALL BE IN SERVICE 24 HOURS A DAY UNTIL THE COMPLETION OF THE SANITARY SEWER MAIN/SERVICE WORK AND ASSOCIATED RESTORATION OF PAVEMENT. POSSIBLE TRAFFIC LIGHT SYSTEM BASIS OF DESIGN SHALL BE: STREET SMART SQ3TS OR TOWER SIGN AND
SIGNALS SX7500.
6. ALL TRAFFIC SIGNAGE SHOWN IN 1/CT100 SHALL BE THE MINIMUM SIGNAGE REQUIRED THROUGHOUT THE ENTIRE PROJECT. ALL TRAFFIC SIGNAGE SHOWN IN 2/CT100 SHALL BE UTILIZED IN ADDITION TO 1/CT100 ONLY DURING WORK ON THE SANITARY SEWER MAIN/SERVICE AND ASSOCIATED RESTORATION OF PAVEMENT. ADDITIONAL TRAFFIC CONTROL MAY BE
NECESSARY, COORDINATE WITH OWNER.
7. THE TRAFFIC CONTROL PLANS WERE DEVELOPED TO SHOW GENERAL INTENT AND FOR THE CONTRACTOR'S USE AS A BASIS OF BIDDING. THESE PLANS PROVIDE DETAIL NECESSARY TO MINIMIZE THE DISRUPTION TO USERS. IT IS THE INTENT OF THE ENGINEER THAT THE CONTRACTOR WILL SUPPLEMENT THIS PLAN WITH THEIR RECOMMENDATIONS TO THE COR AND
RECEIVE NECESSARY APPROVAL PRIOR TO THE START OF CONSTRUCTION.
8. THE TRAFFIC CONTROL PLANS INCLUDED WERE PREPARED TO ENABLE THE CONSTRUCTION OF THE IMPROVEMENTS DESCRIBED IN THESE DOCUMENTS IN A SEQUENTIAL ORDER WITH MINIMAL IMPACT ON THE OMAHA VA AND ITS USERS. THE CONTRACTOR SHALL INCORPORATE THE TRAFFIC CONTROL PLANS INTO THEIR SEQUENCE OF OPERATIONS.
9. ANY MODIFICATIONS TO THE TRAFFIC CONTROL DESCRIBED IN THESE DOCUMENTS SHALL BE APPROVED, IN WRITING, BY THE COR. REQUESTS FOR VARIATIONS TO THE TRAFFIC CONTROL SHALL BE SUBMITTED TO THE COR FOR REVIEW A MINIMUM OF TWO (2) WEEKS PRIOR TO IMPLEMENTATION. THE REQUEST SHALL INCLUDE A DETAILED DESCRIPTION OF THE CHANGE REQUESTED. ALTERNATE SEQUENCE OF OPERATIONS, OR TRAFFIC CONTROL WILL ONLY BE ALLOWED WHEN THE PROPOSED CHANGES MEET WITH THE OWNER'S INTENT FOR TRAFFIC CONTROL AND MAINTENANCE OF SERVICE.
10. PROTECTION OF PEDESTRIAN TRAFFIC FROM OPEN EXCAVATIONS AND OTHER HAZARDS IN AND AROUND THE CONSTRUCTION SITE SHALL BE IN COMPLIANCE WITH OSHA, THE AMERICANS WITH DISABILITIES ACT, AND AS DIRECTED BY
THE COR.
11. ORANGE SAFETY CONES OR CONCRETE BARRIERS SHALL BE USED TO DELINEATE TAPERS AND LANE SHIFTS AND TO
SEPARATE TRAFFIC FROM WORK AREAS.
12. PEDESTRIAN SIDEWALK MAY BE SHUT DOWN FOR SHORT DURATIONS (4 DAYS OR LESS). CONTRACTOR TO
COORDINATE WITH COR. TEMPORARY SURFACING SHALL BE GRAVEL.
13. PROPOSED ELECTRICAL DUCT BANK AND SANITARY SEWER SERVICE / MAIN CANNOT BE CONSTRUCTED AT SAME TIME AS THE ELECTRICAL DUCT BANK WOULD CONFLICT WITH TRAFFIC CONTROL PLAN. TRAFFIC CONTROL FOR INSTALLATION OF DUCT BANK IS NOT SPECIFICALLY SHOWN. CONTRACTOR SHALL INCLUDE A SEPARATE TRAFFIC CONTROL PLAN FOR THIS PORTION OF WORK UTILIZING EITHER FLAGGERS OR PORTABLE DEVICE TRAFFIC LIGHT SYSTEM DISCUSSED IN NOTE 5.
14. EMERGENCY EXITING ROUTES SHALL BE MAINTAINED THROUGHOUT CONSTRUCTION. COORDINATE WITH OWNER.
O
TEMPORARY
CONSTRUCTION
FENCE
EMERGENCY ENTRANCE
/ DROPOFF
EMERGENCY ENTRANCE
/ DROPOFF
00 50' 100' 00 40' 80'
SCARIFY AND RECOMPACT SUBGRADE TO 12"
COMPACTED PER SPECIFICATIONS
4 " AGGREGATE BASE COURSE
COMPACTION PER SPECIFICATIONS
A7
C-500
JOINTED PLAIN TYPICAL CONCRETE PAVEMENT SECTION
N.T.S.
CONCRETE MATCH EXISTING DEPTH, 8" MIN.
15"
9"
9" 5"
3"
NEW CURB & GUTTER
BACK OF CURB
#5 SMOOTH EPOXY COATED
DOWEL, ONE SIDE LUBRICATED
EXISTING CURB &
GUTTER
TOP OF NEW
CURB & GUTTER
#5 SMOOTH EPOXY COATED
DOWEL, ONE SIDE LUBRICATED
GUTTER LIP
3/8" EXPANSION
FILLER
BOTTOM OF NEW
CURB & GUTTER
3/8" EXPANSION FILLER
AND JOINT SEALANT
A4 N.T.S.
CURB AND GUTTER ISOLATION JOINT
PROFILE
3"
3/8" EXPANSION FILLER
AND JOINT SEALANT
BOTTOM OF EXISTING
CURB & GUTTER
C-500
3"
5"
9"
COMPACTED
SUBBASE
C-500 A1
N.T.S.
CURB TYPICAL SECTIONS
CONCRETE CURB
MATCH EXISTING
DIMENSIONS
DOWELS
WHEN REQ'D
(SEE A4/C-500)
3" ASPHALT SURFACE COURSE
NDOT SPR FINE, PG 58H-34
COMPACTED PER SPECIFICATIONS
3" LIFT OF ASPHALT BASE
COURSE NDOT SPR, PG 58H-34
COMPACTED PER SPECIFICATIONS
TACK COAT CSS-1H
@ 0.05 GAL/S.Y.
BETWEEN LIFTS
SCARIFY AND RECOMPACT SUBGRADE 12"
COMPACTED PER SPECIFICATIONS
6" AGGREGATE BASE COURSE
COMPACT AS PER SPECIFICATIONS
C-500 E4
N.T.S.
ASPHALT PAVEMENT DETAIL
PLAN VIEW
NOTES:
ALL REINFORCEMENT STEEL SHALL
BE EPOXY COATED, DEFORMED BAR.
SEE PLANS FOR FLOW LINE CONFIGURATION.
NOTES:
ALL REINFORCING BARS SHALL BE TIED AND
CHAIRED, HAVE 2.0" CLEAR AND CONFORM TO
ASTM A615 GRADE 60 EPOXY COATED STEEL.
THE CONCRETE CURB SHALL BE MONOLITHIC WITH
THE CONCRETE FILLET.
SEE PLANS FOR FLOW LINE CONFIGURATION.
KEYWAY OR TIE BAR JOINT
ON SEPARATE POURS.
TIE BAR JOINT ON
CONTINUOUS POURS.
CONCRETE CURB
AND GUTTER
#5 SMOOTH EPOXY
COATED DOWELS
CURB & GUTTER ENDS &
FILLET BEGINS (TYP.)
KEYWAY JOINT P.C.
CONCRETE PAVING
ONLY
#4 REBAR
18" 10"
LONGITUDINAL CONSTRUCTION
JOINT WITHOUT TIE BARS
EXPANSION JOINT
#5 SMOOTH EPOXY
COATED DOWELS
CONCRETE FILLET
RADIUS (VARIES)
#4 REBAR SPACED 24" O.C.
FLOW
LINE*
E6
C-500
REINFORCED PORTLAND CEMENT CONCRETE FILLET & PAN
N.T.S.
MILL THE 12"
OUTSIDE PERIMETER AT
2" DEPTH
TACK COAT
EXISTING
ASPHALT
SEE DETAIL E2/C-504 FOR
TYPICAL PAVEMENT SECTION.
ASPHALT ABUTMENT DETAIL
N.T.S.
A8
C-500
6"
3"
3"
5' TYP. 2' MINIMUM
TOOLED JOINT
GUTTER LINE
CURB TAPER DETAIL
N.T.S.
F1
C-500
E1 N.T.S.C-500
SCARIFY AND RECOMPACT 6" OF SUBGRADE
COMPACTED PER SPECIFICATIONS
4" MIN. COMPACTED
AGGREGATE
BASE COURSE
COMPACTED PER
SPECIFICATIONS
6" CONCRETE
SECTION
PLAN
2% CROSS SLOPE, MAX.
6" REINFORCED SIDEWALK DETAIL
TOOLED JOINT
SPACED TO MATCH
SIDEWALK WIDTH
TRANSVERSE
TOOLED JOINT
EXPANSION JOINT
#4 REBAR
EXPANSION JOINT
48" (TYP.) 24"
" M
A X
48" (TYP.)
6" THICK
CONCRETE
SIDEWALK
SEE
PLANS
8"
60' MAX.
#4 REBAR, SEE PLAN VIEW
NOTE:
IF ADJACENT EXISTING PAVEMENT HAS BASE COURSE, THEN PROVIDE BASE
COURSE FOR NEW PAVEMENT TO MATCH EXISTING BASE COURSE
THICKNESS. IF ADJACENT EXISTING PAVEMENT DOES NOT HAVE BASE
COURSE, DO NOT USE BASE COURSE FOR NEW PAVEMENT.
NOTE:
1. IF EXISTING EDGE DRAIN IS PRESENT, CONTRACTOR SHALL PROVIDE
EDGE DRAIN IN CONFORMANCE WITH TYPE 1 OR TYPE 2 OF CITY OF
OMAHA STANDARD PLATE 305-01. ALL MATERIALS SHALL BE IN
ACCORDANCE WITH CURRENT VERSION OF THE CITY OF OMAHA
STANDARD SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION 3RD
EDITION. CONNECT TO EXISTING EDGE DRAIN. CONTRACTOR SHALL
PROVIDE POSITIVE DRAINAGE.
EDGE DRAIN -
SEE NOTE 1
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
on e ei gh th in ch o ne fo ot on e qu ar te r i nc h on e fo ot th re e ei gh th s in ch o ne fo ot on e ha lf in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e ha lf in ch es o ne fo ot th re e in ch es o ne fo ot
6"
6"
6"
6"
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
16.2330.A08
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
TERRASITE DESIGN
1635 DEADWOOD AVENUE
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 791-1736
8/ 5/
1:
:2
A
M
CONSTRUCTION DOCUMENTS
11/23/2020
Design/Construct Sterile Processing Service- Omaha VA Medical Center
JMSM
4101 Woolworth Ave #4199 Omaha, Ne 68105Omaha VA Medical Center
16.2330.A08 138
11/23/20
CIVIL DETAILS #1
C-500 19 193
COMPLIANCY REVIEW INCLUDED 2/23/2024
T/
T/
T
15" 15"
SMOOTH EPOXY COATED DOWEL,
ONE SIDE LUBRICATED, 30" LONG,
SPACED 12" O.C.
DOWELED CONTRACTION JOINT
N.T.S.
T/
T/
T
15" 15"
DOWELED CONSTRUCTION JOINT
N.T.S.
ISOLATION JOINT - SEE
DETAIL THIS SHEET
ISOLATION JOINT
N.T.S.
T
4" TO 12" ISOLATION JOINT FILLER
T
NOTES:
1. SLOPE GRADE AS REQUIRED FOR DRAINAGE.
2. JOINTS IN PAVEMENT TO EXTEND THROUGH CURB.
3. SEE CURB DESIGN FOR REINFORCING DETAILS.
DISCONTINUE REINFORCING AT JOINTS.
4. CURB MAY BE PLACED MONOLITHICALLY WITH THE
ADJACENT PAVEMENT AND A CONTRACTION JOINT
SAWED IN LOCATION OF CONSTRUCTION JOINT.
CURB CONSTRUCTION JOINT
N.T.S.
T/
T
LOW MODULUS
SILICONE SEALANT
LINE OF
FRACTURE
NOTE:
THE FIRST SAW CUT TO CONTROL CRACKING SHALL BE A MINIMUM OF 1/4 THE
DEPTH OF THE PAVEMENT. ADDITIONAL SAWING FOR WIDENING THE SAW CUT TO
PROVIDE THE WIDTH FOR THE INSTALLATION OF THE LOW MODULUS SILICONE
JOINT SEALANT WILL BE NECESSARY. JOINT SEALING SHALL BE A TWO PART
PROCESS. FOLLOWING SAWCUTTING AND CLEANING THE JOINTS WITH
COMPRESSED AIR, A PENETRATING CONCRETE SEALER (SILANE, SILICATE, OR
SILICONATE BASED) SHOULD BE SPRAY APPLIED TO THE JOINT EXTENDING
OUTWARDS A MINIMUM OF 8 INCHES EITHER SIDE OF THE SAWCUT. THIS
PENETRATING SEALER WILL HELP TO LIMIT MOISTURE INFILTRATION ALONG THE
SAWCUT FACE, HELPING TO MITIGATE PREMATURE JOINT DAMAGE FROM
FREEZE-THAW CYCLES. FOLLOWING THE SPRAY APPLIED SEALER, SILICONE
SEALANT SHALL BE APPLIED. USE OF BACKER RODS IS PROHIBITED. WIDTH AND
DEPTH OF SECOND SAWCUT SHALL BE AS PER SEALANT MANUFACTURERS
RECOMMENDATION FOR USE WITHOUT BACKER ROD.
SAWED JOINT WITH
SEALANT - SEE
DETAIL THIS SHEET
SAWED JOINT WITH
SEALANT - SEE
DETAIL THIS SHEET
SAWED JOINT WITH
SEALANT - SEE
DETAIL THIS SHEET
SMOOTH EPOXY COATED
DOWEL, ONE SIDE
LUBRICATED, 30" LONG,
SPACED 12" O.C.
CONCRETE CURB
MATCH EXISTING
DIMENSIONS
SIDEWALK OR PAVEMENT ISOLATION JOINT DETAILS
N.T.S.
SIDEWALK OR PAVEMENT ISOLATION
JOINT WITH SILICONE SEALANTS
SIDEWALK
SILICONE
JOINT
SEALANT
PREFORMED
NON-EXTRUDING
JOINT FILLER
D E
P
TH
BUILDING ISOLATION JOINT
SILICONE JOINT SEALANT
PREFORMED
NON-EXTRUDING
JOINT FILLER
R1/8" R1/8"
1/2"
R1/8"
1/2"
1/4" 1/8"
1/4"
GENERAL NOTES:
1. ALL WORK SHALL BE DONE IN
ACCORDANCE WITH ACI 330R-08.
2. DOWEL BAR ASSEMBLY IS
RECOMMENDED TO KEEP DOWELS IN
PROPER ALIGNMENT.
3. DOWELS SHALL NOT BE PLACED
CLOSER THAN 12" TO A JOINT
INTERSECTION.
PAVEMENT
THICKNESS
(IN.)
DOWEL
DIAMETER
(IN.)
7 1
>8 1 1/4
4' MIN.
T/
O R
2" M
IN
IM
U M
3" O
R T
/2 W
H
IC
H E
V E
R
IS
LE
S
S
PAVEMENT OR SIDEWALK
PAVEMENT CONTRACTION JOINT DETAILS
N.T.S.
F4 C-501
JOINT DETAILS
N.T.S.
STRUCTURE, EXISTING
PAVEMENT, NEW PAVEMENT
OR SIDEWALK
T/
T/
T
15" 15"
SMOOTH EPOXY COATED
DOWEL, ONE SIDE
LUBRICATED, 30" LONG,
SPACED 12" O.C.
SAWED JOINT WITH
SEALANT - SEE
DETAIL THIS SHEET
NEW CONSTRUCTION ADJACENT TO EXISTING PCC
DRILLED
HOLE
18" LONG EPOXY COATED SMOOTH DOWEL
@12" C.C. GREASE ONE END,
ANCHOR OTHER END IN HOLE W/ EPOXY RESIN
ADHESIVE - SEE TABLE FOR DOWEL DIAMETER
NOTE: IF EXISTING PCC IS < 6", USE
ISOLATION JOINT DETAIL
6 3/4"
BUILDING WALL
SIDEWALK CONTRACTION JOINT DETAILS
N.T.S.
TOOLEDSAWEDSAWED
1" MIN.
1/8" MIN.
5/8" 1/8"
1" MIN.
1/8"
1" MIN.
3/16" R1/8"
SEE NOTES BELOW FOR WIDTH
AND PREPARATION
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
on e ei gh th in ch o ne fo ot on e qu ar te r i nc h on e fo ot th re e ei gh th s in ch o ne fo ot on e ha lf in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e ha lf in ch es o ne fo ot th re e in ch es o ne fo ot
6"
6"
6"
6"
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
16.2330.A08
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
TERRASITE DESIGN
1635 DEADWOOD AVENUE
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 791-1736
8/ 5/
1:
:2
A
M
CONSTRUCTION DOCUMENTS
11/23/2020
Design/Construct Sterile Processing Service- Omaha VA Medical Center
JMSM
4101 Woolworth Ave #4199 Omaha, Ne 68105Omaha VA Medical Center
16.2330.A08 138
11/23/20
CIVIL DETAILS #2
C-501 20 193
WATER STOP GASKET,
"CONCRETE MANHOLE
ADAPTER" BY FERNCO OR
PREAPPROVED EQUAL
6" MINIMUM OVERLAP
FULL CIRCUMFERENCE
6" MINIMUM OVERLAP
FULL CIRCUMFERENCE
NON-SHRINK GROUT PER
STANDARD SPECIFICATIONS
"D
BREAKOUT 3" MINIMUM &
6" MAXIMUM FULL
CIRCUMFERENCE
BREAKOUT 3" MINIMUM & 6"
MAXIMUM FULL CIRCUMFERENCE
"D"
NEW SEWER
MAIN
GROUT SHALL EXTEND A
MINIMUM OF "D" BEYOND
THE MANHOLE SIDEWALL
NOTE:
AS AN ALTERNATIVE, THE CONTRACTOR MAY CORE THE EXISTING
MANHOLE AND INSTALL A BOOT-TYPE FLEXIBLE CONNECTOR
CONSISTING OF A RUBBER GASKET OR BOOT, METAL EXPANSION
RING AND DOUBLE METAL TAKE-UP CLAMPS, AS MANUFACTURED
BY PRESS SEAL GASKET CORPORATION, OR PREAPPROVED
EQUAL. A STAINLESS STEEL “POWER SLEEVE” SHALL BE SUPPLIED
FOR CONNECTING THE BOOT TO THE MANHOLE. THE BOOTS
SHALL BE TYPE PSX AS MANUFACTURED BY PRESS SEAL GASKET
CORPORATION OR APPROVED EQUAL. RUBBER BOOTS AND
GASKET MATERIAL SHALL MEET OR EXCEED ASTM C-923.
BENTONITE WATERSTOP PLACED AGAINST
MANHOLE AROUND ENTIRE CIRCUMFERENCE
OF HOLE, EMBEDDED IN GROUT. WATER
STOP - RX BY AMERICAN COLLOID OR
PREAPPROVED EQUAL.
C-502 A5
N.T.S.
PIPE CONNECTION TO SANITARY MANHOLE
M A
N H
O
LE
D E
P
TH
* STANDARD MANHOLE SHALL BE
USED FOR INSTALLATIONS WITH
MANHOLE DEPTHS 5.5' OR GREATER.
12.00" TYP.
4" MINIMUM TYPE 1
GRANULAR VALUE
SURFACE
CHIMNEY SEAL
RING AND COVER NEENAH
R-1733 OR APPROVED EQUAL
CENTER OPENING
OVER OUTLET PIPE
ADJUSTING RINGS
AS SPECIFIED
CONE SECTION
NEOPRENE
O-RING TYPE
GASKET AND
BUTYL JOIN
SEALANT
U-SHAPED CHANNEL
EQUAL TO PIPE I.D.
1:10 VERTICAL, TYP
SET CHIMNEY
ADJUSTING RINGS
IN FULL MORTAR
RE-BAR
C-502 A1
N.T.S.
SANITARY SEWER MANHOLE
STEPS - SEE
SPECIFICATIONS
MIN. 24"
OPENING
R
RADIUS (R) SHALL BE
AS LARGE AS POSSIBLE
AND PC'S & PT'S SHALL
BE AT THE MANHOLE
SIDEWALLS
NOTES:
1. PC'S & PT'S ARE TO BE WITHIN THE MANHOLE.
2. ALL INVERTS TO BE U-SHAPED CHANNEL EQUAL TO PIPE I.D.
AND SHALL BE CONSTRUCTED WITH SWEEPS.
3. A MINIMUM RADIUS (R) OF 2.5 TIMES THE I.D. OF THE BRANCH
MAIN IS REQUIRED FOR ALL SWEEPS. IF THE 2.5 TIMES THE
I.D. OF THE BRANCH CAN'T BE MET, A LARGER DIAMETER
MANHOLE SHALL BE REQUIRED. SEE DETAIL SHEET 9-3.
4. MANHOLE PIPE CONNECTOR SHALL BE A RESILIENT WATER
TIGHT SEAL.
I.D.
INVERT ELEVATION SHALL BE A MINIMUM
0.05' BELOW BRANCH INVERT IN OR NOT
LESS THAN THE PIPE SLOPE OF THE
BRANCH IN
BRANCH MAIN
PC
PT
FOUNDATION
MATERIAL, (UNSTABLE
TRENCH BOTTOM ONLY)
SLO
PE
BENCH
SPECIFICATIONS
LOCATOR
WIRE FOR
NON-METALLIC PIPE
BEDDING
MATERIAL3"
M
IN
3"
TRENCH
WIDTH PER
9" SELECT BEDDING
MATERIAL (INCIDENTAL)
(C O
M P
A C
TE
D
P E
R S
P E
C
IF
IC
A
TI
O
N S
P
IP
E D
IA
N O
R M
A L
B A
C K
FI
LL
V A
R
IE
S
WARNING TAPE 12"
BELOW SLABS AND
PAVEMENT, AND 6" IN
TURF AND
LANDSCAPE AREAS
TRENCH
SIDEWALL
VERTICAL TO
THIS POINT
A8 C-502
STANDARD PIPE TRENCH DETAIL
N.T.S.
C-502 E1
N.T.S.
SANITARY SERVICE DOUBLE CLEANOUT DETAIL
NOTES:
1. ALL FITTINGS SHALL BE GASKETED.
2. CLEANOUTS TO BE SAME DIAMETER (D) AS SERVICE LINE.
D
CLEANOUT RISER
45° ELBOW
SERVICE LINE
45° WYE DxDxD
FINISH GRADE
D
2" AGGREGATE BASE COURSE
D
PVC CLEANOUT
WITH THREADED
CAP
CLEANOUT FRAME & SOLID LID
NEENAH R-1974-A OR APPROVED EQUAL
2" CONCRETE BLOCKS
±1'
6" OF FLOWABLE FILL ON ALL
SIDES OF SANITARY SEWER
SANITARY SEWER
C-502 F8
N.T.S.
ENCASEMENT DETAIL
INSIDE DROP CONNECTION
EXTEND INSIDE
DROP OUTLET TO
EDGE OF CHANNEL
INSIDE DROP BOWL - BASIS FOR
DESIGN IS FROM RELINER OR
PRE-APPROVED EQAUL. INSTALL
INSIDE DROP CONNECTION AS PER
MANUFACTURER INSTRUCTIONS, TO
BOTTOM OF MANHOLE
FINISH GRADE
2" AGGREGATE
BASE COURSE
CLEANOUT FRAME
& SOLID LID
NEENAH R-1974-A
OR APPROVED
EQUAL
2" CONCRETE
BLOCKS
FLOWFLOW
45° STREET ELBOW
45° WYE
SANITARY SERVICE CLEANOUT DETAIL
N.T.S.
PVC CLEANOUT WITH
THREADED CAP
C7 C-502
NOTES:
1. ALL FITTINGS SHALL BE GASKETED.
2. CLEANOUTS TO BE SAME DIAMETER AS SERVICE LINE.
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
on e ei gh th in ch o ne fo ot on e qu ar te r i nc h on e fo ot th re e ei gh th s in ch o ne fo ot on e ha lf in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e ha lf in ch es o ne fo ot th re e in ch es o ne fo ot
6"
6"
6"
6"
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
16.2330.A08
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
TERRASITE DESIGN
1635 DEADWOOD AVENUE
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 791-1736
8/ 5/
1:
:2
A
M
CONSTRUCTION DOCUMENTS
11/23/2020
Design/Construct Sterile Processing Service- Omaha VA Medical Center
JMSM
4101 Woolworth Ave #4199 Omaha, Ne 68105Omaha VA Medical Center
16.2330.A08 138
11/23/20
CIVIL DETAILS #3
C-502 21 193
1. SHEET SIZE FOR PROPER SCALE IS 30X42.
CONTRACTOR SHALL NOT SCALE DRAWINGS BUT
SHALL REQUEST THE DESIRED DIMENSIONS FROM
THE ARCHITECT.
2. SEE SHEET G-002 FOR GENERAL NOTES
3. APPLY 1 1/2" THICK FIREPROOFING AT ALL EXPOSED
STEEL WITHIN INTERSTITIAL SPACE AND AT
EXPOSED STEEL STRUCTURE ABOVE 3RD FLOOR
CEILING, TYP.
WORK PERIMETER
AREA OF WORK NOT IN THE SCOPE.
EXISTING TO REMAIN.
ITEMS TO BE DEMOLISHED. SEE
KEYNOTES.
CEILING TO BE REMOVED AND
REINSTALLED
DEMOLITION LEGEND:
A
B
C
D
F
H
K
13455'7 68910
G
TELECOM
E1510
ELECTRIC
E1511FAMILY TLT
E1512
DRAW
E1514
DRAW
E1515
DRAW
E1516
DRAW
E1517
DRAW
E1519
DRAW
E1520
WAITING
E1557
CORRIDOR
EC250
CORRIDOR
EC250
CHECK IN
E1700
STAIR
E1701
#30
E1702
#31
E1704
INTAKE
E1705
SOILED
E1707
#32
E1708
#34
E1709
STORAGE
E1710
OFFICES
E1711
#33
E1712
#34
E1713
TLT
E1711A
CLOSET
E1711B
#26
E1731
#27
E1733
#23
E1734
#28
E1735
STORAGE
E1736
#29
E1737
#24
E1738
TLT
E1738A
#15
E1755
#9
E1756
#16
E1757
#10
E1758
#17
E1759
#11
E1760
#18
E1761
#12
E1762
MEDS
E1763
CORRIDOR
EC255
CORRIDOR
EC255
CORRIDOR
EC250
CORRIDOR
EC255
STAIR
E1777
#4
E1779
#5
E1781
#6
E1783
JAN
E1785
#7
E1787
#3
E1788
CORRIDOR
E1789
CORRIDOR
STORAGE
E1786A
MRI VESTIBULE
EM101
02-50
02-51
02-50
02-51
02-50
02-51
02-50
02-51
02-50
02-51
2.7
#22
E1732
EXAM #13
E1431
EXAM #14
E1429
EXAM #15
E1427
EXAM #16
E1425
EXAM #17
E1423
EXAM #18
E1421
CORRIDOR
EC245
AGENT CASHIER
E1501
OFFICE
E1502
OFFICE
E1503
OFFICE
E1504
OFFICE
E1505A
CHECK IN
E1505 PUBLIC TLT
E1508
LAB
E1507
STAFF TLT
E1509STOR
E1506
CORRIDOR
E1513
02-51
02-50 02-51
02-50
#2
E1786 #1
E1784
UTILITY
E1782
OFFICE
E1625
WAITING
E1801
OFFICE
E1778
OFFICE
E1778A
02-50
02-51
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of
Veterans Affairsof
16.2330.A08
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
TERRASITE DESIGN
1635 DEADWOOD AVENUE
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 791-1736
2/23/2024COMPLIANCY REVIEW COMPLETED
/1
/2
:3
:3
P
M
CONSTRUCTION DOCUMENTS
11/23/2020
DEMOLITION CEILING PLAN - FIRST
LEVEL
AD-100
Design/Construct Sterile Processing Service- Omaha VA Medical Center
JGCJL
4101 Woolworth Ave #4199 Omaha, Ne 68105Omaha VA Medical Center
22 138
GENERAL NOTES:
KEYNOTES:
02-50 REMOVE AND REINSTALL (AS REQUIRED) EXISTING
ACOUSTICAL CEILING TILE, GRID, CEILING MOUNTED
EQUIPMENT, AND ANY ASSOCIATED MECHANICAL/
ELECTRICAL/ PLUMBING/ FIRE PROTECTION
FIXTURES. SEE MECHANICAL/ PLUMBING/
ELECTRICAL/ FIRE PROTECTION FOR ADDITIONAL
INFORMATION.
02-51 REMOVE AND REINSTALL (AS REQUIRED) EXISTING
CEILING LIGHTS. SEE ELECTRICAL FOR ADDITIONAL
INFORMATION.
SHEET SPECIFIC NOTES:
1. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE PROJECT AND VERIFY EXISTING
CONDITIONS/DIMENSIONS AND PROPOSED CONDITIONS.
2. THE DEMOLITION PLAN INDICATES GENERAL INFORMATION AND INTENT. THE CONTRACTOR SHALL COORDINATE
DEMOLITION WITH NEW CONSTRUCTION TO ENSURE QUALITY OF FINAL PRODUCT.
3. DASHED BOLD LINES INDICATE EXTENT OF DEMOLITION INCLUDING THE FOLLOWING: INTERIOR PARTITIONS (REMOVE TO STRUCTURE); CEILINGS, INCLUDING CEILING SUSPENSION SYSTEM, MISC. STEEL SUPPORTS FOR SUSPENDED EQUIPMENT, SUSPENDED EQUIPMENT, LIGHT FIXTURES, DIFFUSERS AND GRILLES ETC.; FLOOR FINISHES (TO CONCRETE) INCLUDING CARPET, RESILIENT TILE, SHEET VINYL, CERAMIC TILE ETC; DOORS AND FRAMES UNLESS NOTED OTHERWISE;
CMU BLOCK/BRICK AND BACKUP WALL SYSTEM; CABINET WORK, SHELVING, BASES; TOILET PARTITIONS AND
ACCESSORIES; EQUIPMENT ITEMS; PLUMBING FIXTURES.
4. GENERAL CONTRACTOR SHALL COORDINATE DEMOLITION BETWEEN ALL TRADES. NOTIFY A/E IMMEDIATELY OF ANY
CONFLICTS OR DISCREPANCIES.
5. REFER TO PHASING SHEET FOR PROJECT PHASING AND SEQUENCE OF WORK. ALL DEMOLITION AND REMODEL WORK
MUST BE CLOSELY COORDINATED WITH THE COR.
6. THE GENERAL CONTRACTOR SHALL INSPECT AND FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING WORK, INCLUDING ELEMENTS SUBJECT TO DAMAGE OR MOVEMENT DURING DEMOLITION, CUTTING OR PATCHING.
7. MATERIAL PRODUCT FROM DEMOLITION SHALL BECOME THE PROPERTY AND RESPONSIBILITY OF THE CONTRACTOR WITH THE EXCEPTION OF SPECIFIED ITEMS DESIGNATED EITHER IN THE PLANS OR VERBALLY REQUESTED BY THE (COR)
TO BE RETAINED BY THE VA.
8. OFFSITE DISPOSAL OF THE DEMOLISHED ITEMS IS THE RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE DISPOSED
OF LAWFULLY.
9. DEMOLITION MATERIALS SHALL BE REMOVED FROM SITE ON A DAILY BASIS. COORDINATE WITH THE COR THE
IDENTIFICATION AND TRANSFER OF ANY ITEMS THAT NEED TO BE SALVAGED.
10. VERIFY LOCATION OF EXISTING UTILITY LINES PRIOR TO STARTING DEMOLITION. MAY NOT BE LIMITED TO UTILITIES SHOWN ON ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL PLANS. REFER TO THE THESE DRAWINGS FOR
ADDITIONAL INFORMATION.
11. UPON ENCOUNTERING UNFORESEEN CONDITIONS DURING REMODEL WORK, THE CONTRACTOR SHALL NOTIFY THE (COR)
BEFORE PROCEEDING.
12. COORDINATE DEMOLITION SHOWN ON THIS SHEET WITH DEMOLITION SHOWN ON MECHANICAL, PLUMBING, AND ELECTRICAL DEMOLITION DRAWINGS. CREATE PENETRATIONS AS REQUIRED FOR NEW CONSTRUCTION ON MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS.
13. THE CONTRACTOR SHALL PROTECT EXISTING CONSTRUCTION TO REMAIN. DAMAGE TO EXISTING CONSTRUCTION SHALL
BE REPAIRED TO EXISTING OR BETTER CONDITION.
14. ERECT AND MAINTAIN TEMPORARY PARTITIONS AND ENCLOSURES FOR EXTERIOR OPENINGS TO PREVENT THE
TRANSMISSION OF DUST, ODOR, AND NOISE AND MAINTAIN WEATHER TIGHT CONDITIONS.
15. PROVIDE TEMPORARY MECHANICAL EXHAUST SYSTEMS TO MAINTAIN A NEGATIVE PRESSURE WITHIN DEMOLITION
ZONES.
16. AT INTERSECTIONS OF REMOVED WALLS WITH WALL TO REMAIN, REPAIR REMAINING WALLS TO MATCH ADJACENT
FINISHED WALLS OR BETTER.
17. REFER TO HAZARDOUS ABATEMENT MANUAL FOR REMOVAL OF HAZARDOUS MATERIALS.
18. CONTRACTOR SHALL PROVIDE TEMPORARY SEAL AT ALL DOOR AND WALL OPENINGS AT PERIMETER WALLS DURING
DEMOLITION WORK TO PROTECT ADJACENT AREAS FROM DUST INTRUSION.
19. SOLID SHADED (GRAY) REGIONS DEPICT EXISTING CONSTRUCTION TO REMAIN.
20. SEE MECHANICAL, ELECTRICAL AND FIRE PROTECTION DRAWINGS FOR OTHER DEMOLITION WORK.
21. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING ALL FURNISHINGS AND NON PERMANENTLY ATTACHED EQUIPMENT
PRIOR TO COMMENCEMENT OF DEMOLITION. CONTRACTOR SHALL COORDINATE WITH COR ON LOCATION OF STORED
FURNISHINGS.
22. CAP/ABANDON ALL UTILITIES NOT REMOVED TO MAKE ROOM FOR NEW CONSTRUCTION AS REQUIRED. COORDINATE
WITH PROPOSED NEW CONSTRUCTION CONDITIONS.
23. SEE DEMOLITION CEILING PLAN FOR CEILING DEMOLITION.
24. CONTRACTOR SHALL PROTECT ADJACENT ROOMS FROM DAMAGE DURING CONSTRUCTION. RESTORE ALL DAMAGE TO
ORIGINAL CONDITION.
25. ALL INFILL AND PATCHWORK SHALL MATCH ADJACENT SURFACES, IE. WALL, CEILINGS, FLOORS, ETC. COORDINATE WITH
NEW FINISHES WHERE REQUIRED; SEE FINISH SCHEDULE FOR DISTURBED/DAMAGED BY DEMOLITION AND NEW
CONSTRUCTION.
26. DEMOLITION PLANS SHOW EXISTING ROOM NAMES AND NUMBERS. ALL OTHER DRAWINGS SHOW NEW ROOM NAMES AND
NUMBERS.
N
N
PLAN
NORTH
TRUE
NORTH
1/8" = 1'-0"
Demolition Ceiling Plan - 1st Level
A
B
C
D
F
H
K
13455'7 68910111213
02-25
02-25
02-25
02-25
02-25
02-25
02-12
02-0702-07
02-0602-06
02-99
02-9902-99
02-99
AD-1041
02-77
02-11
02-17
AD-104
AD-104
AD-104
AD-104
AD-104
G
02-22
02-9702-9602-96
02-97
02-97
02-97
02-9602-96
02-61
02-6102-61 02-6102-61
02-6102-61
02-25
AD-104
AD-104
2.7
1. SHEET SIZE FOR PROPER SCALE IS 30X42.
CONTRACTOR SHALL NOT SCALE DRAWINGS BUT
SHALL REQUEST THE DESIRED DIMENSIONS FROM
THE ARCHITECT.
2. SEE SHEET G-002 FOR GENERAL NOTES
3. APPLY 1 1/2" THICK FIREPROOFING AT ALL EXPOSED
STEEL WITHIN INTERSTITIAL SPACE AND AT
EXPOSED STEEL STRUCTURE ABOVE 3RD FLOOR
CEILING, TYP.
LIMITS OF PROJECT/CONSTRUCTION
UNDER THIS CONTRACT.
AREA OF WORK NOT IN THE SCOPE.
EXISTING TO REMAIN.
ITEMS TO BE DEMOLISHED. SEE
KEYNOTES.
FLOOR TO BE REMOVED
DEMOLITION LEGEND:
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of
Veterans Affairsof
16.2330.A08
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
TERRASITE DESIGN
1635 DEADWOOD AVENUE
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 791-1736
2/23/2024COMPLIANCY REVIEW COMPLETED
/1
/2
:3
:3
P
M
CONSTRUCTION DOCUMENTS
11/23/2020
DEMOLITION PLAN - 2ND LEVEL
AD-101
Design/Construct Sterile Processing Service- Omaha VA Medical Center
JGCJL
4101 Woolworth Ave #4199 Omaha, Ne 68105Omaha VA Medical Center
23 138
GENERAL NOTES:
KEYNOTES:
02-06 REMOVE EXISTING TAPERED ROOF INSULATION,
ROOF MEMBRANE, AND RIGID INSULATION TO
ACCOMMODATE NEW FLOOR PLAN. SEE
STRUCTURAL.
02-07 REMOVE PORTION OF EXISTING CONCRETE
STRUCTURAL FLOOR TO ACCOMMODATE NEW
INTERIOR STAIRS; SEE STRUCTURAL.
02-11 REMOVE EAST PORTION OF EXISTING MASONRY
WALL TO ACCOMODATE NEW MASSONRY WALL. SEE
STRUCTURAL.
02-12 REMOVE PORTION OF EXISTING PARAPET WALL TO
ACCOMMODATE NEW MASONRY WALL. SEE
STRUCTURAL.
02-17 DEMO EXISTING EXTERIOR WALL AS REQUIRED TO
ACCOMMODATE NEW FLOOR PLAN. SEE
STRUCTURAL.
02-22 DEMO EXISTING ALUMINUM WINDOW. PREP ROUGH
OPENING FOR INFILL AS SHOWN ON A-100.
02-25 REMOVE EXISTING MECHANICAL PENTHOUSE
STRUCTURE. SEE MECHANICAL DRAWINGS FOR
SCOPE OF WORK ASSOCIATED WITH THE ENCLOSED
AHU.
02-61 EXISTING MECHANICAL EQUIPMENT TO REMAIN, SEE
MECHANICAL.
02-77 REMOVE EXISTING METAL STAIRS COMPLETELY.
02-96 RELOCATE EXISTING ROOF DRAIN AS SHOWN ON
NEW ROOF PLAN, SEE MECHANICAL DRAWINGS.
02-97 EXISTING ROOF DRAINS TO REMAIN.
02-99 CARRY EXISTING ROOF DRAINS VERTICALLY TO NEW
ROOF AREA.
1/8" = 1'-0"
Demolition Plan - 2nd Level
SHEET SPECIFIC NOTES:
1. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE PROJECT AND VERIFY EXISTING
CONDITIONS/DIMENSIONS AND PROPOSED CONDITIONS.
2. THE DEMOLITION PLAN INDICATES GENERAL INFORMATION AND INTENT. THE CONTRACTOR SHALL COORDINATE
DEMOLITION WITH NEW CONSTRUCTION TO ENSURE QUALITY OF FINAL PRODUCT.
3. DASHED BOLD LINES INDICATE EXTENT OF DEMOLITION INCLUDING THE FOLLOWING: INTERIOR PARTITIONS (REMOVE TO STRUCTURE); CEILINGS, INCLUDING CEILING SUSPENSION SYSTEM, MISC. STEEL SUPPORTS FOR SUSPENDED EQUIPMENT, SUSPENDED EQUIPMENT, LIGHT FIXTURES, DIFFUSERS AND GRILLES ETC.; FLOOR FINISHES (TO CONCRETE) INCLUDING CARPET, RESILIENT TILE, SHEET VINYL, CERAMIC TILE ETC; DOORS AND FRAMES UNLESS NOTED OTHERWISE;
CMU BLOCK/BRICK AND BACKUP WALL SYSTEM; CABINET WORK, SHELVING, BASES; TOILET PARTITIONS AND
ACCESSORIES; EQUIPMENT ITEMS; PLUMBING FIXTURES.
4. GENERAL CONTRACTOR SHALL COORDINATE DEMOLITION BETWEEN ALL TRADES. NOTIFY A/E IMMEDIATELY OF ANY
CONFLICTS OR DISCREPANCIES.
5. REFER TO PHASING SHEET FOR PROJECT PHASING AND SEQUENCE OF WORK. ALL DEMOLITION AND REMODEL WORK
MUST BE CLOSELY COORDINATED WITH THE COR.
6. THE GENERAL CONTRACTOR SHALL INSPECT AND FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING WORK, INCLUDING ELEMENTS SUBJECT TO DAMAGE OR MOVEMENT DURING DEMOLITION, CUTTING OR PATCHING.
7. MATERIAL PRODUCT FROM DEMOLITION SHALL BECOME THE PROPERTY AND RESPONSIBILITY OF THE CONTRACTOR WITH THE EXCEPTION OF SPECIFIED ITEMS DESIGNATED EITHER IN THE PLANS OR VERBALLY REQUESTED BY THE (COR)
TO BE RETAINED BY THE VA.
8. OFFSITE DISPOSAL OF THE DEMOLISHED ITEMS IS THE RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE DISPOSED
OF LAWFULLY.
9. DEMOLITION MATERIALS SHALL BE REMOVED FROM SITE ON A DAILY BASIS. COORDINATE WITH THE COR THE
IDENTIFICATION AND TRANSFER OF ANY ITEMS THAT NEED TO BE SALVAGED.
10. VERIFY LOCATION OF EXISTING UTILITY LINES PRIOR TO STARTING DEMOLITION. MAY NOT BE LIMITED TO UTILITIES SHOWN ON ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL PLANS. REFER TO THE THESE DRAWINGS FOR
ADDITIONAL INFORMATION.
11. UPON ENCOUNTERING UNFORESEEN CONDITIONS DURING REMODEL WORK, THE CONTRACTOR SHALL NOTIFY THE (COR)
BEFORE PROCEEDING.
12. COORDINATE DEMOLITION SHOWN ON THIS SHEET WITH DEMOLITION SHOWN ON MECHANICAL, PLUMBING, AND ELECTRICAL DEMOLITION DRAWINGS. CREATE PENETRATIONS AS REQUIRED FOR NEW CONSTRUCTION ON MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS.
13. THE CONTRACTOR SHALL PROTECT EXISTING CONSTRUCTION TO REMAIN. DAMAGE TO EXISTING CONSTRUCTION SHALL
BE REPAIRED TO EXISTING OR BETTER CONDITION.
14. ERECT AND MAINTAIN TEMPORARY PARTITIONS AND ENCLOSURES FOR EXTERIOR OPENINGS TO PREVENT THE
TRANSMISSION OF DUST, ODOR, AND NOISE AND MAINTAIN WEATHER TIGHT CONDITIONS.
15. PROVIDE TEMPORARY MECHANICAL EXHAUST SYSTEMS TO MAINTAIN A NEGATIVE PRESSURE WITHIN DEMOLITION
ZONES.
16. AT INTERSECTIONS OF REMOVED WALLS WITH WALL TO REMAIN, REPAIR REMAINING WALLS TO MATCH ADJACENT
FINISHED WALLS OR BETTER.
17. REFER TO HAZARDOUS ABATEMENT MANUAL FOR REMOVAL OF HAZARDOUS MATERIALS.
18. CONTRACTOR SHALL PROVIDE TEMPORARY SEAL AT ALL DOOR AND WALL OPENINGS AT PERIMETER WALLS DURING
DEMOLITION WORK TO PROTECT ADJACENT AREAS FROM DUST INTRUSION.
19. SOLID SHADED (GRAY) REGIONS DEPICT EXISTING CONSTRUCTION TO REMAIN.
20. SEE MECHANICAL, ELECTRICAL AND FIRE PROTECTION DRAWINGS FOR OTHER DEMOLITION WORK.
21. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING ALL FURNISHINGS AND NON PERMANENTLY ATTACHED EQUIPMENT
PRIOR TO COMMENCEMENT OF DEMOLITION. CONTRACTOR SHALL COORDINATE WITH COR ON LOCATION OF STORED
FURNISHINGS.
22. CAP/ABANDON ALL UTILITIES NOT REMOVED TO MAKE ROOM FOR NEW CONSTRUCTION AS REQUIRED. COORDINATE
WITH PROPOSED NEW CONSTRUCTION CONDITIONS.
23. SEE DEMOLITION CEILING PLAN FOR CEILING DEMOLITION.
24. CONTRACTOR SHALL PROTECT ADJACENT ROOMS FROM DAMAGE DURING CONSTRUCTION. RESTORE ALL DAMAGE TO
ORIGINAL CONDITION.
25. ALL INFILL AND PATCHWORK SHALL MATCH ADJACENT SURFACES, IE. WALL, CEILINGS, FLOORS, ETC. COORDINATE WITH
NEW FINISHES WHERE REQUIRED; SEE FINISH SCHEDULE FOR DISTURBED/DAMAGED BY DEMOLITION AND NEW
CONSTRUCTION.
26. DEMOLITION PLANS SHOW EXISTING ROOM NAMES AND NUMBERS. ALL OTHER DRAWINGS SHOW NEW ROOM NAMES AND
NUMBERS.
N
N
PLAN
NORTH
TRUE
NORTH
C
D
F
H
789101112
STORAGE
E2417
TLT
E2416A
CHECK IN
E2442SPACE
E2443
LOCKERS
E2423
TLT
E2422
WAITING
E2419
STAIR
E1415
SPACE
E2543B
SPACE
E2543C
DEXA
E2419E
SLEEP RM
E2420
TLT
E2420A
TLT
E2421A
SLEEP RM
E2421
CORRIDOR
E2418
02-5002-50
02-5002-50
02-5002-50
02-51
02-51
G
02-14
1. SHEET SIZE FOR PROPER SCALE IS 30X42.
CONTRACTOR SHALL NOT SCALE DRAWINGS BUT
SHALL REQUEST THE DESIRED DIMENSIONS FROM
THE ARCHITECT.
2. SEE SHEET G-002 FOR GENERAL NOTES
3. APPLY 1 1/2" THICK FIREPROOFING AT ALL EXPOSED
STEEL WITHIN INTERSTITIAL SPACE AND AT
EXPOSED STEEL STRUCTURE ABOVE 3RD FLOOR
CEILING, TYP.
WORK PERIMETER
AREA OF WORK NOT IN THE SCOPE.
EXISTING TO REMAIN.
ITEMS TO BE DEMOLISHED. SEE
KEYNOTES.
CEILING TO BE REMOVED AND
REINSTALLED
DEMOLITION LEGEND:
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of
Veterans Affairsof
16.2330.A08
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
TERRASITE DESIGN
1635 DEADWOOD AVENUE
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 791-1736
2/23/2024COMPLIANCY REVIEW COMPLETED
/1
/2
:3
:3
P
M
CONSTRUCTION DOCUMENTS
11/23/2020
DEMOLITION CEILING PLAN - 2ND
LEVEL
AD-102
Design/Construct Sterile Processing Service- Omaha VA Medical Center
JGCJL
4101 Woolworth Ave #4199 Omaha, Ne 68105Omaha VA Medical Center
24 138
1/8" = 1'-0"
Demolition Ceiling Plan - 2nd Level
GENERAL NOTES:
KEYNOTES:
02-14 REMOVE EXISTING WINDOW, INFILL/FINISH TO MATCH
EXISTING, AS SHOWN ON FLOOR PLAN.
02-50 REMOVE AND REINSTALL (AS REQUIRED) EXISTING
ACOUSTICAL CEILING TILE, GRID, CEILING MOUNTED
EQUIPMENT, AND ANY ASSOCIATED MECHANICAL/
ELECTRICAL/ PLUMBING/ FIRE PROTECTION
FIXTURES. SEE MECHANICAL/ PLUMBING/
ELECTRICAL/ FIRE PROTECTION FOR ADDITIONAL
INFORMATION.
02-51 REMOVE AND REINSTALL (AS REQUIRED) EXISTING
CEILING LIGHTS. SEE ELECTRICAL FOR ADDITIONAL
INFORMATION.
SHEET SPECIFIC NOTES:
1. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE PROJECT AND VERIFY EXISTING
CONDITIONS/DIMENSIONS AND PROPOSED CONDITIONS.
2. THE DEMOLITION PLAN INDICATES GENERAL INFORMATION AND INTENT. THE CONTRACTOR SHALL COORDINATE
DEMOLITION WITH NEW CONSTRUCTION TO ENSURE QUALITY OF FINAL PRODUCT.
3. DASHED BOLD LINES INDICATE EXTENT OF DEMOLITION INCLUDING THE FOLLOWING: INTERIOR PARTITIONS (REMOVE TO STRUCTURE); CEILINGS, INCLUDING CEILING SUSPENSION SYSTEM, MISC. STEEL SUPPORTS FOR SUSPENDED EQUIPMENT, SUSPENDED EQUIPMENT, LIGHT FIXTURES, DIFFUSERS AND GRILLES ETC.; FLOOR FINISHES (TO CONCRETE) INCLUDING CARPET, RESILIENT TILE, SHEET VINYL, CERAMIC TILE ETC; DOORS AND FRAMES UNLESS NOTED OTHERWISE;
CMU BLOCK/BRICK AND BACKUP WALL SYSTEM; CABINET WORK, SHELVING, BASES; TOILET PARTITIONS AND
ACCESSORIES; EQUIPMENT ITEMS; PLUMBING FIXTURES.
4. GENERAL CONTRACTOR SHALL COORDINATE DEMOLITION BETWEEN ALL TRADES. NOTIFY A/E IMMEDIATELY OF ANY
CONFLICTS OR DISCREPANCIES.
5. REFER TO PHASING SHEET FOR PROJECT PHASING AND SEQUENCE OF WORK. ALL DEMOLITION AND REMODEL WORK
MUST BE CLOSELY COORDINATED WITH THE COR.
6. THE GENERAL CONTRACTOR SHALL INSPECT AND FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING WORK, INCLUDING ELEMENTS SUBJECT TO DAMAGE OR MOVEMENT DURING DEMOLITION, CUTTING OR PATCHING.
7. MATERIAL PRODUCT FROM DEMOLITION SHALL BECOME THE PROPERTY AND RESPONSIBILITY OF THE CONTRACTOR WITH THE EXCEPTION OF SPECIFIED ITEMS DESIGNATED EITHER IN THE PLANS OR VERBALLY REQUESTED BY THE (COR)
TO BE RETAINED BY THE VA.
8. OFFSITE DISPOSAL OF THE DEMOLISHED ITEMS IS THE RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE DISPOSED
OF LAWFULLY.
9. DEMOLITION MATERIALS SHALL BE REMOVED FROM SITE ON A DAILY BASIS. COORDINATE WITH THE COR THE
IDENTIFICATION AND TRANSFER OF ANY ITEMS THAT NEED TO BE SALVAGED.
10. VERIFY LOCATION OF EXISTING UTILITY LINES PRIOR TO STARTING DEMOLITION. MAY NOT BE LIMITED TO UTILITIES SHOWN ON ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL PLANS. REFER TO THE THESE DRAWINGS FOR
ADDITIONAL INFORMATION.
11. UPON ENCOUNTERING UNFORESEEN CONDITIONS DURING REMODEL WORK, THE CONTRACTOR SHALL NOTIFY THE (COR)
BEFORE PROCEEDING.
12. COORDINATE DEMOLITION SHOWN ON THIS SHEET WITH DEMOLITION SHOWN ON MECHANICAL, PLUMBING, AND ELECTRICAL DEMOLITION DRAWINGS. CREATE PENETRATIONS AS REQUIRED FOR NEW CONSTRUCTION ON MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS.
13. THE CONTRACTOR SHALL PROTECT EXISTING CONSTRUCTION TO REMAIN. DAMAGE TO EXISTING CONSTRUCTION SHALL
BE REPAIRED TO EXISTING OR BETTER CONDITION.
14. ERECT AND MAINTAIN TEMPORARY PARTITIONS AND ENCLOSURES FOR EXTERIOR OPENINGS TO PREVENT THE
TRANSMISSION OF DUST, ODOR, AND NOISE AND MAINTAIN WEATHER TIGHT CONDITIONS.
15. PROVIDE TEMPORARY MECHANICAL EXHAUST SYSTEMS TO MAINTAIN A NEGATIVE PRESSURE WITHIN DEMOLITION
ZONES.
16. AT INTERSECTIONS OF REMOVED WALLS WITH WALL TO REMAIN, REPAIR REMAINING WALLS TO MATCH ADJACENT
FINISHED WALLS OR BETTER.
17. REFER TO HAZARDOUS ABATEMENT MANUAL FOR REMOVAL OF HAZARDOUS MATERIALS.
18. CONTRACTOR SHALL PROVIDE TEMPORARY SEAL AT ALL DOOR AND WALL OPENINGS AT PERIMETER WALLS DURING
DEMOLITION WORK TO PROTECT ADJACENT AREAS FROM DUST INTRUSION.
19. SOLID SHADED (GRAY) REGIONS DEPICT EXISTING CONSTRUCTION TO REMAIN.
20. SEE MECHANICAL, ELECTRICAL AND FIRE PROTECTION DRAWINGS FOR OTHER DEMOLITION WORK.
21. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING ALL FURNISHINGS AND NON PERMANENTLY ATTACHED EQUIPMENT
PRIOR TO COMMENCEMENT OF DEMOLITION. CONTRACTOR SHALL COORDINATE WITH COR ON LOCATION OF STORED
FURNISHINGS.
22. CAP/ABANDON ALL UTILITIES NOT REMOVED TO MAKE ROOM FOR NEW CONSTRUCTION AS REQUIRED. COORDINATE
WITH PROPOSED NEW CONSTRUCTION CONDITIONS.
23. SEE DEMOLITION CEILING PLAN FOR CEILING DEMOLITION.
24. CONTRACTOR SHALL PROTECT ADJACENT ROOMS FROM DAMAGE DURING CONSTRUCTION. RESTORE ALL DAMAGE TO
ORIGINAL CONDITION.
25. ALL INFILL AND PATCHWORK SHALL MATCH ADJACENT SURFACES, IE. WALL, CEILINGS, FLOORS, ETC. COORDINATE WITH
NEW FINISHES WHERE REQUIRED; SEE FINISH SCHEDULE FOR DISTURBED/DAMAGED BY DEMOLITION AND NEW
CONSTRUCTION.
26. DEMOLITION PLANS SHOW EXISTING ROOM NAMES AND NUMBERS. ALL OTHER DRAWINGS SHOW NEW ROOM NAMES AND
NUMBERS.
N
N
PLAN
NORTH
TRUE
A
B
C
D
F
H
K
13455'7 68910111213
AD-1041
02-13
02-13
02-13
02-13
02-0802-08
02-08
02-08
02-08
02-08
02-77
02-11
02-13
02-0902-09
02-98
G
02-98
2.7
1. SHEET SIZE FOR PROPER SCALE IS 30X42.
CONTRACTOR SHALL NOT SCALE DRAWINGS BUT
SHALL REQUEST THE DESIRED DIMENSIONS FROM
THE ARCHITECT.
2. SEE SHEET G-002 FOR GENERAL NOTES
3. APPLY 1 1/2" THICK FIREPROOFING AT ALL EXPOSED
STEEL WITHIN INTERSTITIAL SPACE AND AT
EXPOSED STEEL STRUCTURE ABOVE 3RD FLOOR
CEILING, TYP.
LIMITS OF PROJECT/CONSTRUCTION
UNDER THIS CONTRACT.
AREA OF WORK NOT IN THE SCOPE.
EXISTING TO REMAIN.
ITEMS TO BE DEMOLISHED. SEE
KEYNOTES.
FLOOR TO BE REMOVED
DEMOLITION LEGEND:
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of
Veterans Affairsof
16.2330.A08
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FARRIS ENGINEERING
12700 WEST DODGE ROAD
OMAHA, NEBRASKA 68154
PH: (402) 330-5900
TERRASITE DESIGN
1635 DEADWOOD AVENUE
RAPID CITY, SOUTH DAKOTA 57702
PH: (605) 791-1736
2/23/2024COMPLIANCY REVIEW COMPLETED
/1
/2
:3
:4
P
M
CONSTRUCTION DOCUMENTS
11/23/2020
DEMOLITION PLAN - 3RD LEVEL
AD-103
Design/Construct Sterile Processing Service- Omaha VA Medical Center
JGCJL
4101 Woolworth Ave #4199 Omaha, Ne 68105Omaha VA Medical Center
25 138
1/8" = 1'-0"
Demolition Plan 3rd Level
GENERAL NOTES:
KEYNOTES:
02-08 REMOVE PORTION OF EXISTING TAPERED ROOF
INSULATION, ROOF MEMBRANE, RIGID INSULATION,
AND CONCRETE ROOF TO ACCOMMODATE NEW
FLOOR PLAN. SEE STRUCTURAL.
02-09 REMOVE PART OF EXISTING TAPERED ROOF
INSULATION, ROOF MEMBRANE, AND RIGID
INSULATION TO ACCOMMODATE NEW MECHANICAL
EQUIPMENT.
02-11 REMOVE EAST PORTION OF EXISTING MASONRY
WALL TO ACCOMODATE NEW MASSONRY WALL. SEE
STRUCTURAL.
02-13 REMOVE PORTION OF EXISTING PARAPET WALL TO
ACCOMMODATE NEW FLOOR PLAN. SEE
STRUCTURAL.
02-77 REMOVE EXISTING METAL STAIRS COMPLETELY.
02-98 ACCOMMODATE EXISTING DRAIN FOR NEW
MECHANICAL EQUIPMENT.
SHEET SPECIFIC NOTES:
1. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE PROJECT AND VERIFY EXISTING
CONDITIONS/DIMENSIONS AND PROPOSED CONDITIONS.
2. THE DEMOLITION PLAN INDICATES GENERAL INFORMATION AND INTENT. THE CONTRACTOR SHALL COORDINATE
DEMOLITION WITH NEW CONSTRUCTION TO ENSURE QUALITY OF FINAL PRODUCT.
3. DASHED BOLD LINES INDICATE EXTENT OF DEMOLITION INCLUDING THE FOLLOWING: INTERIOR PARTITIONS (REMOVE TO STRUCTURE); CEILINGS, INCLUDING CEILING SUSPENSION SYSTEM, MISC. STEEL SUPPORTS FOR SUSPENDED EQUIPMENT, SUSPENDED EQUIPMENT, LIGHT FIXTURES, DIFFUSERS AND GRILLES ETC.; FLOOR FINISHES (TO CONCRETE) INCLUDING CARPET, RESILIENT TILE, SHEET VINYL, CERAMIC TILE ETC; DOORS AND FRAMES UNLESS NOTED OTHERWISE;
CMU BLOCK/BRICK AND BACKUP WALL SYSTEM; CABINET WORK, SHELVING, BASES; TOILET PARTITIONS AND
ACCESSORIES; EQUIPMENT ITEMS; PLUMBING FIXTURES.
4. GENERAL CONTRACTOR SHALL COORDINATE DEMOLITION BETWEEN ALL TRADES. NOTIFY A/E IMMEDIATELY OF ANY
CONFLICTS OR DISCREPANCIES.
5. REFER TO PHASING SHEET FOR PROJECT PHASING AND SEQUENCE OF WORK. ALL DEMOLITION AND REMODEL WORK
MUST BE CLOSELY COORDINATED WITH THE COR.
6. THE GENERAL CONTRACTOR SHALL INSPECT AND FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING WORK, INCLUDING ELEMENTS SUBJECT TO DAMAGE OR MOVEMENT DURING DEMOLITION, CUTTING OR PATCHING.
7. MATERIAL PRODUCT FROM DEMOLITION SHALL BECOME THE PROPERTY AND RESPONSIBILITY OF THE CONTRACTOR WITH THE EXCEPTION OF SPECIFIED ITEMS DESIGNATED EITHER IN THE PLANS OR VERBALLY REQUESTED BY THE (COR)
TO BE RETAINED BY THE VA.
8. OFFSITE DISPOSAL OF THE DEMOLISHED ITEMS IS THE RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE DISPOSED
OF LAWFULLY.
9. DEMOLITION MATERIALS SHALL BE REMOVED FROM SITE ON A DAILY BASIS. COORDINATE WITH THE COR THE
IDENTIFICATION AND TRANSFER OF ANY ITEMS THAT NEED TO BE SALVAGED.
10. VERIFY LOCATION OF EXISTING UTILITY LINES PRIOR TO STARTING DEMOLITION. MAY NOT BE LIMITED TO UTILITIES SHOWN ON ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL PLANS. REFER TO THE THESE DRAWINGS FOR
ADDITIONAL INFORMATION.
11. UPON ENCOUNTERING UNFORESEEN CONDITIONS DURING REMODEL WORK, THE CONTRACTOR SHALL NOTIFY THE (COR)
BEFORE PROCEEDING.
12. COORDINATE DEMOLITION SHOWN ON THIS SHEET WITH DEMOLITION SHOWN ON MECHANICAL, PLUMBING, AND ELECTRICAL DEMOLITION DRAWINGS. CREATE PENETRATIONS AS REQUIRED FOR NEW CONSTRUCTION ON MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS.
13. THE CONTRACTOR SHALL PROTECT EXISTING CONSTRUCTION TO REMAIN. DAMAGE TO EXISTING CONSTRUCTION SHALL
BE REPAIRED TO EXISTING OR BETTER CONDITION.
14. ERECT AND MAINTAIN TEMPORARY PARTITIONS AND ENCLOSURES FOR EXTERIOR OPENINGS TO PREVENT THE
TRANSMISSION OF DUST, ODOR, AND NOISE AND MAINTAIN WEATHER TIGHT CONDITIONS.
15. PROVIDE TEMPORARY MECHANICAL EXHAUST SYSTEMS TO MAINTAIN A NEGATIVE PRESSURE WITHIN DEMOLITION
ZONES.
16. AT INTERSECTIONS OF REMOVED WALLS WITH WALL TO REMAIN, REPAIR REMAINING…