Attachment 03 142410 Hydraulic Elevator Modernization.pdf
PDF 205 KB Posted
- Solicitation number
- 36C77626Q0039
About this file
This is a detailed technical specification for a hydraulic elevator modernization project for a VA (Veterans Affairs) Medical Center. The specification covers comprehensive requirements for upgrading passenger, service, and freight elevators, including precise technical specifications for equipment components such as controllers, door operators, car enclosures, platforms, guide rails, electrical systems, and communication devices. Key technical requirements include microprocessor control systems, power door operators, emergency communication features, audio voice systems, and compliance with multiple safety and accessibility standards including ASME A17.1, NFPA, and ADA requirements.
The specification mandates extensive testing protocols, maintenance services, and a one-year warranty period with full maintenance coverage. Contractors must use certified elevator mechanics, provide detailed documentation, perform rigorous pre-acceptance testing, and maintain a logbook of all maintenance activities. The project requires 24-hour emergency call-back service, bi-weekly equipment examinations, and a written Maintenance Control Program to ensure ongoing compliance with safety standards. The comprehensive document outlines precise technical, operational, and maintenance expectations for a complete elevator system modernization.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
04-01-24
14 24 10-1
SECTION 14 24 10
HYDRAULIC ELEVATOR – MODERNIZATION
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies the engineering, furnishing and installation of the complete hydraulic elevator system as described herein and as indicated in the scope of work.
B. Items listed in the singular apply to each elevator in this specification except where noted.
C. Passenger Elevators must be oil hydraulic, microprocessor control system and power-operated car and hoistway doors. Elevator must be
Class “A” loading rated as a minimum.
D. Service/Passenger Elevators must be oil hydraulic, microprocessor control system and power operated car and hoistway doors. Elevator must be Class “C3” loading rated as a minimum.
E. Freight Elevators must be oil hydraulic, microprocessor control system and power operated vertical bi parting hoistway doors and vertical sliding car gate. Elevator must be Class “C1” loading rated as a minimum.
ELEVATOR SCHEDULE
Elevator Number
Overall Platform Size
Clear Inside Platform
Rated Load – kg (lb)
Contract Speed - m/s (fpm)
Total Travel – m (ft)
Floors Served
Number of Openings
Entrance Type & Size
Plunger Size
1.2 RELATED WORK
A. Section 01 33 23 SPECIFICATIONS AND DRAWINGS FOR CONSTRUCTION (FAR
52.236-21) and, SPECIAL NOTES (VAAR 852.236-91), in GENERAL CONDITIONS.
14 24 10-2
B. Section 07 84 00, FIRESTOPPING: Sealing around penetrations to maintain the integrity of fire-rated construction.
C. SECTION 09 06 00, SCHEDULE FOR FINISHES: As a master format for construction projects, to identify interior and exterior material finishes for type, texture, patterns, color and placement.
D. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL
COMPONENTS: Requirements for seismic restraint of non-structural components.
1.3 QUALIFICATIONS
A. Approval by the Contracting Officer is required for products and services of proposed manufacturers, suppliers, installers and must be contingent upon submission of certificates by the Contractor stating the following:
1. Elevator contractor is currently and regularly engaged in the installation of elevator equipment as one of his principal products.
2. Elevator contractor must have five (5) years of successful experience, trained supervisory personnel and facilities to install elevator equipment specified herein.
3. Elevator Mechanic (Installer) must have passed a Mechanic
Examination approved by the U.S. Department of Labor and have technical qualifications of at least five years of experience in the elevator industry or 10,000 hours of field experience working in the elevator industry with technical update training. Apprentices must be actively pursuing Certified Elevator Mechanic status.
Certification must be submitted for all workers employed in this capacity.
B. Welding at the project site must be performed by certified welders who have previously qualified by test as prescribed in American Welding
Society Publications AWS Dl.1 to perform the type of work required.
Certificates must be submitted for all workers employed in this capacity. A welding or hot work permit is required for each day and must be obtained from the VAMC safety department. Request permit one day in advance.
C. Electrical work must be performed by a Licensed Master Electrician and
Licensed Journeymen Electricians as requirements by NEC. Certificates must be submitted for all workers employed in this capacity.
D. Approval will not be given to elevator contractors and manufacturers who have established on prior projects, either government, municipal, 14 24 10-3 or commercial, a record of unsatisfactory elevator installations, have failed to complete awarded contracts within the contract period and do not have the requisite record of satisfactorily performing elevator installations of similar type and magnitude.
E. Approval of Elevator Contractor’s equipment will be contingent upon their providing factory training, engineering and technical support, including all manuals, wiring diagrams and tools necessary for adjusting, maintenance, repair and testing of equipment to the VA for use by the VA’s designated Elevator Maintenance Service Provider.
F. Identifying an elevator maintenance service provider that must render services within one hour of receipt of notification, together with certification that the quantity and quality of replacement parts stock is enough to warranty continued operation of the elevator installation.
G. Equipment within a group of hydraulic elevators must be the product of the same manufacturer.
H. The Contractor must provide and install safety devices that have been subjected to tests witnessed and certified by an independent professional testing laboratory that is not a subsidiary of the firm that manufactures supplies or installs the equipment.
1.4 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification.
Elevator installation must meet the requirements of the latest editions published and adopted by the United States Department of Veterans
Affairs on the date this contract is signed.
B. Federal Specifications (Fed. Spec.):
J-C-30B - Cable and Wire, Electrical (Power, Fixed Installation)
J-C-580 – Cord, Flexible and Wire, Fixture
W-S-610 – Splice Connectors
W-C-596F - Connector, Plug, Electrical; Connector, Receptacle, Electrical
W-F-406E - Fittings for Cable, Power, Electrical and Conduit, Metal, Flexible
HH-I-558C - Insulation, Blankets, Thermal (Mineral Fiber, Industrial
Type)
W-F-408E - Fittings for Conduit, Metal, Rigid (Thick- Wall and Thin-wall (EMT) Type)
RR-W-410 - Wire Rope and Strand
TT-E-489J - Enamel, Alkyd, Gloss, Low VOC Content
14 24 10-4
QQ-S-766 - Steel, Stainless and Heat Resisting, Alloys, Plate, Sheet and Strip
C. American Society of Mechanical Engineers (ASME):
A17.1 - Safety Code for Elevators and Escalators
A17.2 - Inspectors Manual for Electric Elevators and Escalators
D. National Fire Protection Association:
NFPA 13 - Standard for the Installation of Sprinkler Systems
NFPA 70 - National Electrical Code (NEC)
NFPA 72 - National Fire Alarm and Signaling Code
NFPA 101 - Life Safety Code
NFPA 252 - Fire Test of Door Assemblies
E. International Building Code (IBC)
F. American Society for Testing and Materials (ASTM):
A1008/A1008M-09 - Steel, Sheet, Cold Rolled, Carbon, Structural, High-
Strength Low-Alloy and High Strength Low-Alloy with
Improved Formability
E1042-02 - Acoustically Absorptive Materials Applied by Trowel or Spray
G. Manufacturer's Standardization Society of the Valve and Fittings
Industry (MSS):
SP-58 - Pipe Hangers and Supports
H. Society of Automotive Engineers, Inc. (SAE)
J517-91 - Hydraulic Hose, Standard
I. Gages:
For Sheet and Plate: U.S. Standard (USS)
For Wires: American Wire Gauge (AWG)
J. American Welding Society (AWS):
D1.1 - Structured Welding Code – Steel
K. National Electrical Manufacturers Association (NEMA):
LD-3 - High-Pressure Decorative Laminates
L. Underwriter's Laboratories (UL):
486A - Safety Wire Connectors for Copper Conductors
797 - Safety Electrical Metallic Tubing
M. Institute of Electrical and Electronic Engineers (IEEE)
N. Regulatory Standards:
Uniform Federal Accessibility Standards
Americans with Disabilities Act
VA Barrier Free Design Handbook H-18-13
O. National Elevator Industry, Inc.
14 24 10-5
NEII-1 Building Transportation Standards and Guidelines
1.5 SUBMITTALS
A. Submit in accordance with Specification Section 01 33 23, SHOP
DRAWINGS, PRODUCT DATA and SAMPLES.
B. Before execution of work, furnish information to evidence full compliance with contract requirements for proposed items. Such information must include, as required: Manufacturer's Name, Trade
Names, Model or Catalog Number, Nameplate Data (size, capacity and rating) and corresponding specification reference (Federal or project specification number and paragraph). All submitted drawings and related elevator material must be forwarded to the Contracting Officer.
C. Shop Drawings:
1. Complete scaled and dimensioned layout in plan and section view showing the arrangement of equipment and all details of each elevator unit specified including:
a. Complete layout showing location of storage tank/pump assembly, controller, piping layout, outside diameter of cylinder/plunger assembly, size of car platform, car frame members and support assembly.
b. Car, guide rails, brackets, buffers and other components located in hoistway.
c. Rail bracket spacing and maximum vertical forces on guide rails in accordance with H-18-8 for Seismic Risk Zone 2 or greater.
d. Reaction at points of support and buffer impact loads.
e. Weight of principal parts.
f. Top and bottom clearances and over travel of the car.
g. Location of main line switch/shunt trip circuit breaker, switchboard panel, light switch and feeder extension points in the machine room.
2. Drawings of hoistway entrances and doors showing details of construction and method of fastening to the structural members of the building.
a. If drywall construction is used to enclose hoistway, submit details of interface fastenings between entrance frames and drywall.
b. Sill details including sill support.
D. Samples:
1. One each of stainless steel, 75 mm x 125 mm (3 in. x 5 in.).
14 24 10-6
2. One each of baked enamel, 75 mm x 125 mm (3 in. x 5 in.).
3. One each of color floor covering.
4. One each of protection pads, 75 mm x 125 mm (3 in. x 5 in.) if used.
5. One each car and hoistway Braille plate sample.
6. One each car and hall button sample.
7. One each car and hall lantern/position indicator sample.
8. One each wall and ceiling material finish sample.
9. One each car lighting sample.
E. Name of manufacturer, type or style designation and applicable data of the following equipment must be shown on the elevator layouts:
1. Storage tank/pump assembly.
2. Pump and motor, HP and RPM rating, Voltage, Starting and Full Load
Ampere, Number of phases and Gallons per minute.
3. Controller.
4. Starters and Overload Current Protection Devices.
5. Car Safety Device; Rupture Valve and Manual Shut Off Valves.
6. Electric Door Operator; HP, RPM, Voltage and Ampere rating of motor.
7. Hoistway Door Interlocks.
8. Car Buffers; maximum and minimum rated load, maximum rated striking speed and stroke.
9. Cab Ventilation Unit; HP rating and CFM rating.
F. Complete construction drawings of elevator car enclosure, showing dimensioned details of construction, fastenings to platform, car lighting, ventilation, ceiling framing, top exits and location of car equipment.
G. Complete dimensioned detail of vibration isolating foundations for storage tank/pump assembly.
H. Dimensioned drawings showing details of:
1. All signal and operating fixtures.
2. Car slide guides/roller guides.
3. Hoistway door tracks, hangers and sills.
4. Door operator, infrared curtain units.
I. Cut sheets or drawings showing details of controllers and supervisory panels.
J. Furnish certificates as required under: Paragraph "QUALIFICATIONS".
1.6 WIRING DIAGRAMS
A. Provide three complete sets of paper and one electronic set of field wiring and straight-line wiring diagrams showing all electrical
14 24 10-7 circuits in the hoistway, machine room and fixtures. Install one set coated with an approved plastic sealer and mounted in the elevator machine room as directed by the Resident Engineer/Contracting Officer or authorized representative.
B. In the event field modifications are necessary during installation, diagrams must be revised to include all corrections made prior to and during the final inspection. Corrected diagrams must be delivered to the Resident Engineer/Contracting Officer within 30 days of final acceptance.
C. Provide the following information relating to the specific type of microprocessor controls installed:
1. Owner's information manual, containing job specific data on major components, maintenance and adjustment.
2. System logic description.
3. Complete wiring diagrams needed for field troubleshooting, adjustment, repair and replacement of components. Diagrams must be base diagrams, containing all changes and additions made to the equipment during the design and construction period.
4. Changes made during the warranty period must be noted on the drawings in adequate time to have the finalized drawings reproduced for mounting in the machine room no later than six months prior to the expiration of the warranty period.
1.7 PERFORMANCE STANDARDS
A. The elevators must meet the highest standards of the industry and specifically the following:
1. Contract speed is high speed in either direction of travel with rated capacity load in the elevator. Speed variation under all load conditions, regardless of direction of travel, must not vary more than five (5) percent.
2. The controlled rate of change of acceleration and retardation of the car must not exceed 0.1G per ft/s/s and the maximum acceleration and retardation must not exceed 0.2G per ft/s/s.
3. Starting, stopping and leveling must be smooth and comfortable without appreciable steps of acceleration and deceleration.
B. The door operator must open the car door and hoistway door simultaneously at 2.5-feet per second and close at 1-foot per second.
C. Pressure: Fluid system components must be designed and factory tested for 500 psi operating pressure.
14 24 10-8
D. Floor level stopping accuracy must be within 3 mm (.125 in.) above or below the floor, regardless of load condition.
E. Noise and Vibration Isolation: All elevator equipment including their supports and fastenings to the building, must be mechanically and electrically isolated from the building structure to minimize objectionable noise and vibration transmission to car, building structure, or adjacent occupied areas of building.
F. Sound Isolation: Noise level relating to elevator equipment operation in machine room must not exceed 80 decibels. All db readings must be taken three (3) feet off the floor and three (3) feet from equipment.
G. Airborne Noise: Measured noise level of elevator equipment during operation must not exceed 50 decibels in elevator lobbies and 60 decibels inside car under any condition including door operation and car ventilation exhaust blower on its highest speed.
1.8 WARRANTY
A. Submit all labor and materials furnished regarding elevator system and installation to terms of "Warranty of Construction" articles of FAR clause 52.246-21. The One-Year Warranty and Guarantee Period of Service must commence and run concurrent after final inspection, completion of performance test and upon acceptance of each elevator.
B. During warranty period if a device is not functioning properly in accordance with specification requirements, more maintenance than the contract requires keeping device operational, device must be removed and a new device meeting all requirements must be installed as part of work until satisfactory operation of installation is obtained. Period of warranty must start anew for such parts from date of completion of each new installation performed, in accordance with foregoing requirements.
1.9 POWER SUPPLY
A. For power supply in each machine room, see Specification 26 05 19, Electrical specifications and Electrical drawings.
B. Main Line Fused Disconnect Switch/Shunt Trip Circuit Breaker for each controller must be located inside the machine room at the strike side of the machine room door and lockable in the “Off” position.
C. Provide Surge Suppressors to protect the elevator equipment.
1.10 EMERGENCY POWER SUPPLY
A. Emergency power supply, its starting means, transfer switch for transfer of elevator supply from normal to emergency power, two pair of
14 24 10-9 conductors in a conduit from an auxiliary contact on the transfer switch (open or close contacts as required by Elevator Controller
Manufacturer) to terminals in the group elevator controller and other related work must be provided by the Electrical Contractor.
B. Upon loss of normal power supply there must be a delay before transferring to emergency power of 10 seconds minimum to 45 seconds maximum, the delay must be accomplished through an adjustable timing device.
C. Prior to the return of normal power an adjustable timed circuit must be activated that will cause all cars to remain at a floor if already there or stop and remain at the next floor if in flight. Actual transfer of power from emergency power to normal building power must take place after all cars are stopped at a floor with their doors open.
D. Car lighting circuits must be connected to the emergency power panel.
1.11 ELEVATOR MACHINE ROOM
A. Reuse existing machine room and meet the requirements of ASME A17.1, NFPA 70, NFPA 101 and IBC. The elevator drive machine and elevator controller must be in the same code approved machine room.
B. Locate the shunt trip breakers and machine room light switch to the lock side of the door inside the room.
C. Locate sprinkler pipes to provide seven (7) feet head clearance. Do not locate sprinkler heads, heat detectors and smoke detectors directly over elevator equipment.
1.12 HOISTWAY LIGHTING
A. Provide lighting with 3-way switches at the top and bottom of the hoistway accessible from elevator hoistway entrance prior to entering the pit or stepping onto the car top.
B. Lighting must illuminate top of elevator cab when it is at the top floor and the pit when at the bottom floor.
1.13 TOOL CABINET
A. Provide a metal parts/tool cabinet, having two shelves and hinged doors. Cabinet must be 1219 mm (48 in.) high, 762 mm (30 in.) wide and
457 mm (18 in.) deep.
1.14 WORK SCHEDULE
A. Before starting work submit a detailed work schedule for approval and arrange with COR sequence of procedure, means of access to premises, space for storage, use of approaches, corridors, stairways, elevators, location of temporary partitions, disposal of trash and recyclable
14 24 10-10 materials. The COR must be notified twenty (20) calendar days, in writing, in advance of starting work on elevators. No work may begin on any elevator until all materials for that elevator have been delivered to the site and verified by the Contracting Officer and/or Contracting
Officer’s Representative. The phasing of work on the elevators must be coordinated with the Contracting Officer and/or the Contracting
Officer’s Representative.
1.15 SAFETY PRECAUTIONS
A. Buildings will be occupied during execution of work. Work must be conducted in a manner to afford maximum protection of patients, public, employees, building and facilities to prevent unreasonable delay or interference with normal functioning of hospital activities.
B. Where an adjacent elevator is in operation, isolate the elevators from each other with suitable barriers between them, extending from the pit floor to bottom of secondary slab at top of hoistway, while work is in progress. Remove partition when work is completed.
C. Provide fire extinguishers that are readily available always.
D. It must be the obligation of the contractor to maintain a free and clear passageway in each elevator lobby. Parts and tools must be kept within the confines of entrance partitions. Trash and debris must be removed daily.
E. Provide fire rated partition during the modernization of elevators.
Barrier must extend to the full height of the elevator entrance and must be dust and vapor proof with dust absorbing mats at access points.
1.16 REMOVAL OF MATERIALS AND EQUIPMENT
A. Material and equipment that are not specified to be reused or retained under contract must be removed daily from the site at the expense of the contractor. The contractor must receive title to all material and equipment not specified to be reused as of date of withdrawal from service. The government does not warranty condition of the material to which contractor must obtain title, nor must the government be liable for damage before or after title passes to contractor.
PART 2 - PRODUCTS
2.1 MATERIALS
A. Where stainless steel is specified, it must be corrosion resisting steel complying with Fed. Spec. QQ-S-766, Class 302 or 304, Condition A with Number 4 finish on exposed surfaces. Stainless steel must have the grain of belting in the direction of the longest dimension and surfaces
14 24 10-11 must be smooth and without waves. During installation stainless steel surfaces must be protected with a suitable material.
B. Where cold rolled steel is specified, it must be low-carbon steel rolled to stretcher level standard flatness, complying with ASTM A109.
2.2 MANUFACTURED PRODUCTS
A. Materials, devices and equipment furnished must be of current production by manufacturers regularly engaged in the manufacture of such items. The elevator equipment, including controllers, door operators and supervisory system must be the product of manufacturers of established reputation, provided such items are capably engineered and produced under coordinated specifications to ensure compatibility with the total operating system.
B. Manufacturers of equipment assemblies which include components made by others must assume complete responsibility for the final assembled unit. Components must be compatible with each other and with the total assembly for the intended service.
C. Mixing of manufactures related to a single system or group of components must be identified in the submittals.
D. Key operated switches provide for this elevator modernization, must be provide four (4) keys for each individual switch or lock. Provide different key tumblers for different switch and lock functions. Each key must have a tag bearing a stamped or etched legend identifying its purpose.
2.3 CONDUIT AND WIREWAY
A. Remove existing and provide new conduit and wireway. Install electrical conductors, except traveling cable connected to the elevator, in rigid zinc-coated steel or aluminum conduit, electrical metallic tubing or metal wireways. Rigid conduit smaller than .75 inch or electrical metallic tubing smaller than .50-inch electrical trade size must not be used. All raceways completely embedded in concrete slabs, walls, or floor fill must be rigid steel conduit. Wireway (duct) must be installed in the hoistway and to the controller and between similar apparatus in the elevator machine room. Fully protect self-supporting connections, where approved, from abrasion or other mechanical injury.
Flexible metal conduit not less than .375-inch electrical trade size may be used, not exceeding 18 inches in length unsupported, for short connections between risers and limit switches, interlocks and for other applications permitted by NEC.
14 24 10-12
B. All conduits terminating in steel cabinets, junction boxes, wireways, switch boxes, outlet boxes and similar locations must have approved insulation bushings. Install a steel lock nut under the bushings if they are constructed completely of insulating materials. Protect the conductors at ends of conduits not terminating in steel cabinets or boxes by terminal fittings having an insulated opening for the conductors.
C. Rigid conduit and EMT fittings using set screws or indentations as a means of attachment must not be used.
D. Connect motors or other items subject to movement, vibration or removal to the conduit or EMT systems with flexible, steel conduits.
2.4 CONDUCTORS
A. Remove existing and provide new. Conductors must be stranded or solid coated annealed copper in accordance with Federal Specification J-C-30B for Type RHW or THW. Where 16 and 18 AWG are permitted by NEC, single conductors or multiple conductor cables in accordance with Federal
Specification J-C-580 for Type TF may be used provided the insulation of single conductor cable and outer jacket of multiple conductor cable is flame retardant and moisture resistant. Multiple conductor cable must have color or number coding for each conductor. Conductors for control boards must be in accordance with NEC. Joints or splices are not permitted in wiring except at outlets. Tap connectors may be used in wireways provided they meet all UL requirements.
B. Provide all conduit and wiring between machine room, hoistway and fixtures.
C. All wiring must test free from short circuits or ground faults.
Insulation resistance between individual external conductors and between conductors and ground must be a minimum of one megohm.
D. Where size of conductors is not given, voltage and amperes must not exceed limits set by NEC.
E. Provide equipment grounding. Ground the conduits, supports, controller enclosure, motor, platform and car frame and all other non-current conducting metal enclosures for electrical equipment in accordance with
NEC. The ground wires must be copper, green insulated and sized as required by NEC. Bond the grounding wires to all junction boxes, cabinets and wire raceways.
F. Terminal connections for all conductors used for external wiring between various items of elevator equipment must be solderless pressure
14 24 10-13 wire connectors in accordance with Federal Specification W-S-610. The
Elevator Contractor may, at his option, make these terminal connections on #10 gauge or smaller conductors with approved terminal eyelets set on the conductor with a special setting tool, or with an approved pressure type terminal block. Terminal blocks using pierce-through serrated washers are not acceptable.
2.5 TRAVELING CABLES
A. Remove existing and provide new flexible traveling cables conforming to the requirements of NEC. Traveling cables must run from the junction box on the car directly to the controller. Junction boxes on the car must be equipped with terminal blocks. Terminal blocks having pressure wire connectors of the clamp type that meet UL 486A requirements for stranded wire may be used in lieu of terminal eyelet connections.
Terminal blocks must have permanent indelible identifying numbers for each connection. Cables must be securely anchored to avoid strain on individual terminal connections. Flame and moisture resistant outer covering must remain intact between junction boxes. Abrupt bending, twisting and distortion of the cables must not be permitted.
B. Provide spare conductors equal to 10 percent of the total number of conductors furnished, but not less than 5 spare conductors in each traveling cable.
C. Provide shielded wires for the auto dial telephone system within the traveling cable, five (5) pair shielded wires for card reader, one (1)
RG-6 Ethernet cable for Wi-FI, two (2) pair 14-gauge wires for 110 Volt power supply and wire for video display monitor if specified.
D. If traveling cables contact the hoistway or elevator due to sway or change in position, provide shields or pads to the elevator and hoistway to prevent damage to the traveling cables.
E. Hardware cloth may be installed from the hoistway suspension point to the elevator pit to prevent traveling cables from rubbing or chafing and securely fastened and tensioned to prevent buckling. Hardware cloth is not required when traveling cable is hung against a flat wall.
2.6 CONTROLLER AND SUPERVISORY PANEL
A. Remove existing and provide new UL/CSA Labeled Controller. Mount all assemblies, power supplies, chassis switches and relays on a steel frame in a NEMA Type 1 General Purpose Enclosure. Cabinet must be securely attached to the building structure.
14 24 10-14
B. Properly identify each device on all panels by name, letter, or standard symbol which must be neatly stencil painted or decaled in an indelible and legible manner. Identification markings must be coordinated with identical markings used on wiring diagrams. The ampere rating must be marked adjacent to all fuse holders. All spare conductors to controller and supervisory panel must be neatly formed, laced and identified.
C. Controller must be provided with wiring and components for additional future travel if required.
2.7 MICROPROCESSOR CONTROL SYSTEM
A. Provide a microprocessor control system with absolute position/speed feedback to control dispatching, signal functions, door operation and pump motor control. Complete details of the components and printed circuit boards, together with a complete operational description, must be submitted for approval. Provide closed transition SCR soft start.
B. Controller manufacturer must provide factory training, engineering and technical support, including all manuals, wiring diagrams and tools necessary for adjusting, maintenance, repair and testing of equipment to the VA for use by the VA’s designated Elevator Maintenance Service
Provider.
C. Microprocessor dispatching system must evaluate building traffic demand including number of elevators in service, hall calls, car calls, elevator position, direction of travel, load in elevator, door status and select an elevator to answer hall calls for least possible passenger wait times.
D. Provide a low oil control feature that must shut off the motor and pump and return the elevator to the lowest landing. Upon reaching the lowest landing, doors will open automatically allowing passengers to leave the elevator and then doors must close. All control buttons, except the door open button, alarm bell button and the call for help button must be made ineffective.
2.8 MACHINE ROOM MONITOR
A. Provide a monitor in each machine room, separate monitors for each passenger elevator group and each service elevator group. Provide a separate keyboard for each monitor.
B. The monitor must contain indicators to provide the following information:
1. The floor where each elevator is currently located.
14 24 10-15
2. The direction that each elevator is currently traveling or is scheduled to travel.
3. The location and direction of currently registered hall calls.
4. Elevators that are currently out of service.
5. Elevators that are currently bypassing hall calls.
6. Elevators that are currently engaged in passenger transfers.
7. Operations program under which entire group is currently operating.
8. Zone divisions of the entire group.
9. Door positions.
10. Status indication for elevators on independent service, car top inspection, fire service, earthquake protection and activated stop switch and alarm bell.
C. The maintenance terminal must be suitable for all troubleshooting procedures related to the specific type of microprocessor installed on this project.
2.9 EMERGENCY POWER OPERATION
A. The control system for Elevator(s) must provide for the operation of at least one car per elevator group on emergency power upon failure of the normal power supply.
B. Auxiliary equipment on elevator controllers, wiring between associated elevator controllers and wiring between elevator controllers and remote selector panel as required to permit the elevators to operate as detailed, must be provided by the Elevator Contractor.
C. Upon loss of normal power supply there must be a delay before transferring to emergency power of 10 seconds minimum to 45 seconds maximum, the delay must be accomplished through an adjustable timing device. After adjusting delay, the associated elevators must function the same as on normal power or as follows:
1. Selector switch, Automatic position (NOT REQUIRED WHEN E-POWER CAN
OPERATE ALL ELEVATORS IN THE GROUP AT SAME TIME):
a. Not more than one elevator at a time in each group must be automatically selected and returned to the main floor, at contract speed, cycle its car and hoistway doors and shut down, with "Door Open" button remaining operable.
b. As each elevator reaches the designated floor and shuts down, another elevator must start and return to the designated floor.
c. Elevators that have been manually removed from automatic service and are on independent service, fire service or medical emergency
14 24 10-16 must receive an automatic return signal. Elevators on inspection service or out of service must not receive a signal.
d. When an elevator is given a signal to return and it is unable to start its movement to the designated floor within 30 seconds it must be by-passed. When an elevator is by-passed, another elevator must start and return.
e. This process must continue until all elevators have returned to the designated floor and shut down.
f. Any elevator or elevators by-passed on initial return signal must be signaled again.
g. When all cars in group have returned to designated floor, one elevator in each group must be designated for automatic operation. Individual cars in each group must restart at 5 second intervals.
h. Elevator(s) are keyed on to medical emergency service in the car prior to transfer to auxiliary power operation, medical emergency service must be retained. This elevator must be the first automatically selected elevator to operate on emergency power operation and complete its selected call demand. The elevator will return to the designated floor after the key switch is reset to normal position.
2. Selector switch, Manual operation:
a. Selector switch must be mechanically and electrically interlocked to prevent the selection of more than one elevator from operating on auxiliary power.
b. The selector switch must have positions marked with the number of each elevator controlled. It must also have a position marked
"Automatic". When the selector switch is set to the automatic position, the medical emergency service car must operate on emergency power operation, or if none, the last car arriving at the designated floor must operate on emergency power operation.
c. Change in selection of elevators must be by means of the selection switch and must occur only when the previous selected elevator is stopped at the designated floor.
d. The selector switch must be locked out of operation when the system is in the normal mode of operation.
e. Locate the selector switch above the hall push button at the designated level. The key switch must be a tumbler type lock
14 24 10-17 furnished with four keys. The enclosure faceplate must be identified "Emergency Power Control" with 13 mm (.50 in.)
engraved letters filled with black paint.
D. Prior to the return of normal power an adjustable timer circuit must activate that will cause all cars to remain at a floor if already there or stop and remain at the next floor if in flight. Actual transfer of power from auxiliary power to normal building power must take place after all cars are stopped at a floor with their doors open.
C. Emergency Rescue Operation (ONLY APPLICABLE IF E-POWER IS NOT
PROVIDED):
Provide a power source to send the elevator to the lowest landing.
After the elevator has leveled at the lowest landing, provide power to open the car and hoistway doors automatically. After a predetermined time, the doors must close. Power must stay applied to the door open button to reopen the doors from the inside of the elevator. The elevator must remain shut down at the bottom landing until normal power is restored. Install a sign on the controller indicating that power is applied to emergency rescue operator and door operator during loss of normal power.
2.10 FIREFIGHTER’S SERVICE
A. Provide Firefighter’s Service. All key switches must be barrel-key
FEOK1.
1. Main Floor:
2. Alternate Floor:
3. Verify main and alternate floors with RE/CO or authorized representative.
2.11 INDEPENDENT SERVICE
A. Provide an INDEPENDENT SERVICE key switch on the face of the main car operating panel or a toggle switch in the service operating panel that must have its positions marked "ON" and "OFF". When the switch is in the "ON" position, the car must respond only to calls registered on its car dispatch buttons and must bypass all calls registered on landing push buttons. The car must start when a car call is registered, car call button or door close button is pressed, car and hoistway doors are closed and interlock circuits are made. When switch is returned to
"OFF" position, normal service must be resumed.
14 24 10-18
2.12 MEDICAL EMERGENCY SERVICE – PATIENT CARE FACLITIES ONLY
A. Provisions must be made for calling elevator(s) to floors served by the elevator on an emergency basis, operating independently from the dispatch signals and landing call signals.
B. Install key switches in the floor landing push button fixture above the push buttons.
C. Provide a call registered light indicator adjacent to key switch. The key switch at the landings and in the car, must only be operable by authorized personnel with a key.
D. When key switch is activated at any floor, the call register light indicator must illuminate at the call floor and inside the elevator only. The elevator control system must instantly select an elevator to respond to the medical emergency call. Immediately upon selection, all car calls must be cancelled. If car is traveling away from the medical emergency call, it must slow down and stop at the nearest floor, maintain closed doors, reverse direction and proceed nonstop to the medical emergency call floor. If the car is traveling toward the medical emergency call floor, it must proceed to that floor nonstop. If at the time of selection, it is slowing down for a stop, the car must stop, maintain doors closed and start immediately toward the medical emergency floor.
E. Arriving at the medical emergency floor, the car must remain with doors open for 60 seconds. After this interval has expired and the car has not been placed on medical emergency operation inside the car, the car must automatically return to normal service.
F. Provide an LED illuminated indicator light next to the Medical
Emergency key switch the same size as the Fire Service indicator.
1. Locate a “Medical Emergency” key switch above call buttons in the main car operating panel for selecting medical emergency service.
Activation of the key switch will allow the car to accept a car call for any floor, close doors and proceed nonstop to the floor desired.
2. After medical emergency call has been completed the elevator must return to normal operation after the key is removed.
G. In the center of the rear cab panel provide a back lighted "MEDICAL
EMERGENCY" LED illuminated display that must flash on and off continuously when the car is assigned to this operation and until it is restored to normal service. "MEDICAL EMERGENCY" indicator must be a photographic negative type 1828 mm (72 in.) to center above the floor, 14 24 10-19
152 mm (6 in.) wide X 76 mm (3 in.) high, with 12.5 mm (.50 in.) high letters legible only when illuminated.
H. If the car being operated on “Independent Service”, the medical emergency service indicator lights in the car operating panel and rear wall must be illuminated, buzzer must sound and the “Audio Voice” system must direct the attendant to return the car to automatic operation.
I. If the car is out of service and unable to answer medical emergency calls, the call register light must not illuminate.
J. Each key switch must have its identity legible and indelible engraved in faceplates. All lettering must be 6 mm (.25 in.) high, filled with black paint.
K. When Phase I fire recall is activated, it must over-ride elevators on medical emergency service and return them to the main or alternate fire service recall floor. When the fire emergency floor has been identified the attendants may complete their medical emergency run on Phase II firefighter’s operation if life safety is not affected.
2.13 SEISMIC REQUIREMENTS
A. Meet the requirements VA Seismic Design Manual H-18-8.
2.14 PUMP, MOTOR AND VALVE ASSEMBLY
A. Provide new pump assembly for the control of the elevator self-contained in a unit fabricated of structural steel. The unit must consist of a hydraulic fluid pump, AC motor, oil control valves with down speed regulator, muffler, piping and fittings.
B. Submersible pump with the motor and oil control valve mounted above the tank are preferred to eliminate heat from the motor being transferred to the oil. Submersible motor and pump power units are acceptable but are best suited for lower traffic areas. Enclose V-belt power unit on four open sides with not less than 16-gauge steel removable panel sections. Provide a 50 mm (2 in.) minimum, 100mm (4 in.) maximum air space between the top of the panels and bottom of tank. Line panels on the interior side with one-inch rigid acoustical insulation board.
Install metal belt guard that can be removed with hand tools for servicing and inspection.
14 24 10-20
C. Control valves must be electronically controlled. Hydraulic fluid flow must be controlled to insure speed variation of not more than five (5) percent under all load conditions in either direction of travel. Locate the manual lowering valve, easily accessible, properly identified and not concealed within the storage tank. Mark the operating handle in red.
D. Pump must be designed for hydraulic elevator service, having a steady discharge without pulsation to give smooth and quiet operation. Pump output must be capable of lifting elevator car with rated capacity, with a speed variation of no more than five (5) percent between no load and full load. Hydraulic fluid by-pass must discharge directly into storage tank.
E. Provide motor specifically designed for elevator service, synchronous speed of 1800 RPM, not to exceed nameplate full load current by more than 10% and rated 120 starts per hour without exceeding a rise of 40 degrees C.
F. Provide isolation pads to prevent transmission of pump and motor vibration to the building.
G. Install blowout-proof, non-hammering, oil-hydraulic muffler in the hydraulic fluid supply pressure line near power unit in machine room.
Design muffler to reduce to a minimum any pulsation or noises that may be transmitted through the hydraulic fluid into the hoistway.
2.15 HYDRAULIC SYSTEM
A. Construct the storage tank of sheet steel, welded construction and a steel cover with means for filling, a minimum one-inch protected vent opening and a valve drain connection. Tank must be sized to pass through machine room door as shown on drawings. Provide marked gauge to monitor hydraulic fluid level. Tank must be sized to hold volume of hydraulic fluid required to lift elevator to stop ring, plus a reserve of not less than ten gallons. Provide a baffle in the bottom of the tank to prevent entry of any sediment or foreign particles into hydraulic system. Baffle must also minimize aeration of hydraulic fluid. Permissible minimum hydraulic fluid level must be clearly indicated. Hydraulic fluid must be of good grade to assure free flow when cool and have minimum flash point of 380-400 degrees F. Provide initial supply of hydraulic fluid for operation of elevator.
14 24 10-21
1. Provide a means to maintain the fluid viscosity in the reservoir, pump and control valve at the manufacturer’s recommended operating temperature.
2. Provide a data plate on the tank frame indicating the characteristics of the hydraulic fluid used.
B. Provide and install connections between the storage tank, pump, muffler, operating valves and cylinder complete with necessary valves, pipe supports and fittings. Pipe must be minimum schedule 40 steel with threaded, flanged, or welded mechanical couplings. Size of pipe and couplings between cylinder and pumping unit must be such that fluid pressure loss is limited to 10 percent.
C. Hydraulic system working pressure must not exceed 500 psi under any load condition. Do not subject valves, piping and fittings to working pressure greater than those recommended by the manufacturer.
D. Support all horizontal piping. Place hangers or supports within 300 mm
(12 in.) on each side of every change of direction of pipeline and space supports not over 304.8 cm (10 ft) apart. Secure vertical runs properly with iron clamps at sufficiently close intervals to carry weight of pipe and contents. Provide supports under pipe to floor.
1. Provide all piping from machine room to hoistway, including necessary supports or hangers. If remote piping is underground or in damp inaccessible areas, install hydraulic piping thru PVC sleeve.
E. Install pipe sleeves where pipes pass through walls or floors. After installation of piping, equip the sleeves with snug fitting inner liner of fire rated insulation.
F. Provide an automatic shut-off valve in the oil supply line at the cylinder inlet. Activate the automatic shut-off valve when there is more than a ten percent increase in high speed in the down direction.
When activated, this device must immediately stop the descent of the elevator and hold the elevator. The exposed adjustments of the automatic shut-off valve must have their means of adjustment sealed after being set to their correct position.
G. Provide external tank shut-off valve to isolate hydraulic fluid during maintenance operations.
H. Provide shut-off valves in the pit near the cylinder and in the machine room capable of withstanding 150 percent of design operating pressure.
Each manual valve must have an attached handle.
14 24 10-22
I. Provide oil-tight drip pan for assembled pumping unit, including storage tank. Pan must be not less than 16-gauge sheet steel, with one-inch sides.
J. Components of the hydraulic system must be factory certified to withstand pressure equal to twice the calculated working pressure.
2.16 HYDRAULIC PLUNGER ASSEMBLY
A. Provide new cylinder and plunger sized to lift gross load the height specified. Factory test the plunger assembly at a pressure equal to twice the calculated working pressure, for strength and to insure freedom from leakage. Provide bottom of cylinder head with internal guide bearing and top of cylinder head with removable packing gland.
Victaulic type packing gland head must not be permitted.
1. Provide a bleeder valve located below the cylinder flange to release air or other gases from the system.
2. Equip cylinder with drip ring below the packing gland to collect leakage of hydraulic fluid.
3. Bolt the cylinder mounting brackets to footing channels that support the buffers.
B. Install a flexible tubing scavenger line with an electrically operated pump between the piston drip ring and oil storage tank. Scavenger line, pump and strainers must operate independently of hydraulic fluid pressure. Equip scavenger pump with a water float designed to prevent operation of the pump should the pit flood and designed to be manually reset. Secure pump and reservoir to the pit channels.
C. Plunger must be heavy seamless steel tubing, turned smooth and true to within plus or minus .38 mm (0.015 in.) tolerance and no diameter change greater than .07 mm (0.003 in.) per-inch of length. Where plunger is multi-piece construction, machine the joints to assure perfectly matching surfaces.
1. Secure plunger to underside of platform supporting beams with fastenings capable of supporting four times the weight of the plunger. The platen plate must incorporate piston to car vibration isolation.
2. Provide a stop ring welded or screwed to the bottom of plunger that must prevent the plunger from leaving its cylinder.
3. Isolate plunger head from the platen plate to prevent corrosion or electrolysis.
4. Protect plunger, repair or replace if gouged, nicked or scored.
14 24 10-23
2.17 HYDRAULIC CYLINDER CASING AND PVC LINER
A. Clean casing and remove waste oil, sand and other waste materials from site.
B. Provide PVC casing liner to fit inside steel casing or fabricate liner with watertight bottom and a top flange gasket to seal plunger flange and form a complete, watertight, electrically non-conductive encasement of the entire unit.
2.18 CAR BUFFERS
A. Provide two new spring buffers for the elevator. Securely fasten buffers and supports to the pit channels and in the alignment with striker plates on elevator. Buffers must have a permanently attached metal plate indicating its stroke and load rating. Buffer anchorage must not puncture pit waterproofing. Reuse existing if possible.
B. Provide pipe stanchions and struts as required to properly support the buffer.
2.19 GUIDE RAILS, SUPPORTS AND FASTENINGS
A. Reuse existing. Clean, replace missing bolts and tighten as needed.
2.20 NORMAL AND FINAL TERMINAL STOPPING DEVICES
A. Mount new terminal slowdown switches and direction limit switches on the elevator or in hoistway to reduce speed and bring car to an automatic stop at the terminal landings.
1. Switches must function with any load up to and including 100 percent of rated elevator capacity at any speed obtained in normal operation.
2. Switches, when opened, must permit operation of elevator in reverse direction of travel.
B. Mount final terminal stopping switches in the hoistway.
1. Switches must be positively opened should the car travel beyond the terminal direction limit switches.
2. Switches must be independent of other stopping devices.
3. Switches, when opened, must remove power from pump motor and control valves preventing operation of car in either direction.
2.21 CROSSHEAD DATA PLATE AND CODE DATA PLATE
A. Permanently attach a non-corrosive metal Data Plate to car crosshead.
B. Permanently attach a Code Data Plate, in plain view, to the controller.
2.22 WORKMAN’S LIGHTS AND OUTLETS
A. Provide duplex GFCI protected type receptacles and lamp, with guards on top of elevator car and beneath platform.
14 24 10-24
B. The receptacles must be in accordance with Fed. Spec. W-C-596 for Type
D7, 2-pole, 3-wire grounded type rated for 15 amperes and 125 volts.
2.23 CARTOP OPERATING DEVICE
A. Provide a new cartop operating device.
B. The device must be activated by a toggle switch mounted in the device.
The switch must be clearly marked "INSPECTION" and "NORMAL" on the faceplate, with 6 mm (.25 in.) letters.
C. Movement of the elevator must be accomplished by the continuous pressure on a direction button and a safety button.
D. Provide an emergency stop switch, push to stop/pull to run.
E. Provide permanent identification for the operation of all components in the device.
F. The device must be permanently attached to the elevator crosshead on the side of the elevator nearest to the hoistway doors used for accessing the top of the car.
2.24 LEVELING DEVICE
A. Car must be equipped with a new two-way leveling device to automatically bring the car to within 3 mm (.125 in.) of exact level with the landing for which a stop is initiated regardless of load in car or direction of travel.
B. If the car stops short or travels beyond the floor, the leveling device, within its zone must automatically correct this condition and maintain the car within 3 mm (.125 in.) of level with the floor landing regardless of the load carried.
2.25 EMERGENCY STOP SWITCHES
A. Provide an emergency stop switch, push to stop/pull to run,…