This is a draft presentation for the VHA National Elevator Modernization Program Vendor Industry Day scheduled for January 14-15, 2026. The presentation outlines VA's approach to modernizing approximately 800 elevators across 102 facility locations in 17 of 18 VA networks nationwide, with significant concentrations in VISN 2 (New York/New Jersey), VISN 1 (Massachusetts/New Hampshire/Connecticut), and VISN 22 (California/Arizona). The scope includes 443 traction and 340 hydraulic freight, passenger, and service elevators in owned VA assets where the VA serves as the Authority Having Jurisdiction, eliminating permitting requirements. Elevators must be assigned a D or F rating on the most current Facility Condition Assessment to qualify for modernization. The program encompasses 511 elevators in Critical Buildings, 125 in Essential Buildings, and 148 in Ancillary Buildings, with roughly 65 elevators in banks allowing only sequential modernization.

The VA intends to employ a design-build approach without traditional architect/engineer-produced design drawings, instead issuing a scope of work and modernization specifications as the basis of design. Contractors will submit shop drawings, samples, and wiring diagrams for VA approval. Key contractor responsibilities include manufacturer standard designs, calculations/certifications, code compliance documentation, and accommodations for variables including seismic requirements, Infection Control Risk Assessments (ICRAs), phasing in active 24/7/365 hospitals, scheduling, rigging, and identifying out-of-scope issues. The VA assumes sufficient upstream power exists, appropriate machine rooms, and VA solutions for new ASME A17.1 voice/text/video requirements. Typical modernization scope includes machine and drive system replacement (traction or hydraulic), new controls, traveling cables, operating panels, corridor devices, hoistway doors, car enclosures, finishes, and fire life safety items per MSJ 1-9, with car frames and platforms reused unless replacement is necessary. The procurement strategy emphasizes non-proprietary componentry to ensure long-term maintainability by any service provider. Governing standards include IBC, ASME A17.1/A17.2, and applicable NFPA codes. Ground rules specify no detailed pricing discussions, no manufacturer commitments, and non-binding feedback, with Q&A responses shared equitably and vendor input potentially informing the final acquisition package.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VHA National Elevator Modernization Program

Vendor Industry Day January 14th-15th, 2026

DRAFT

www.ehrm.va.go v

Transforming Health Care for Veterans, Revolutionizing Health Care for All

Purpose of Meeting

• Why VA is engaging industry early

• What VA wants to validate

• What does success look like for both VA and contractors

“This is about executability, fairness, and risk reduction”

Transforming Health Care for Veterans, Revolutionizing Health Care for All

Ground Rules

No detailed pricing discussions

No manufacturer commitments

Feedback is non-binding

Q&A will be captured and shared equitably

Input from the next days may inform final acquisition package/strategy

Transforming Health Care for Veterans, Revolutionizing Health Care for All

Overview Background

Program Overview: Scale, Scope, and Assumptions

Submittal/Shop Drawing Phase

Proprietary vs. Non-Proprietary

Expectations

• Turnkey Solution

• Quality Assurance

• Submittals

• Scheduling/Phasing

• Infection Control

• Seismic

• Rigging

• Cab Interiors

Risk Allocation

Open Forum

Transforming Health Care for Veterans, Revolutionizing Health Care for All

Background

• VHA owns approximately 5700 buildings Many of these building are old and require infrastructure upgrades

• Maintaining Assets = Constraints Time, money, bureaucracy, etc.

• VA design-bid-build strategy - AE/Consulting firms

• Different approach

• Modernizations ≠ install/new construction

Transforming Health Care for Veterans, Revolutionizing Health Care for All

Facility Condition Assessment (FCA)

VA program

~ 3 to 4 year cycles

Contractor performed Elevator consultant for vertical transport

Assigns letter grades to assets/equipment/infrastructure

D’s and F’s are assigned a cost Associated costs become “deferred maintenance”

To be considered for this Modernization Program, elevators must be assigned a D or F on most current FCA

Transforming Health Care for Veterans, Revolutionizing Health Care for All

Program Scale and Complexity

≈ 800 elevators in 17 of 18 networks spread across the entire US, including

Puerto Rico

102 individual site locations

Owned assets only – meaning that VA is

AHJ, no permits required

Significant amount of need •VISN 2 (New York, New

Jersey) •VISN 1 (Massachusetts, New Hampshire, Connecticut)

•VISN 22 (California, Arizona) DRAFT

Transforming Health Care for Veterans, Revolutionizing Health Care for All

Elevator Types in Scope

Scope includes

Freight, Passenger and Service elevators only

No dumbwaiters, dock levelers, wheelchair lifts

Hydraulic and Traction only

443 Traction

340 HydraulicDRAFT

Transforming Health Care for Veterans, Revolutionizing Health Care for All

Scope Read

• Elevator Modernization Scope - final 11.6.25.docx

DRAFT

https://dvagov.sharepoint.com/:w:/r/sites/VHAOCAMESEHRM/VHAOCAMESSPEHRM/HEFPSEPElevators/Shared%20Documents/Scope/Modernization%20Scopes/Elevator%20Modernization%20Scope%20-%20final%2011.6.25.docx?d=w85f0f5f3da1a4df2850063891439ecbd&csf=1&web=1&e=CcvOCQ https://dvagov.sharepoint.com/:w:/r/sites/VHAOCAMESEHRM/VHAOCAMESSPEHRM/HEFPSEPElevators/Shared%20Documents/Scope/Modernization%20Scopes/Elevator%20Modernization%20Scope%20-%20final%2011.6.25.docx?d=w85f0f5f3da1a4df2850063891439ecbd&csf=1&web=1&e=CcvOCQ https://dvagov.sharepoint.com/:w:/r/sites/VHAOCAMESEHRM/VHAOCAMESSPEHRM/HEFPSEPElevators/Shared%20Documents/Scope/Modernization%20Scopes/Elevator%20Modernization%20Scope%20-%20final%2011.6.25.docx?d=w85f0f5f3da1a4df2850063891439ecbd&csf=1&web=1&e=CcvOCQ https://dvagov.sharepoint.com/:w:/r/sites/VHAOCAMESEHRM/VHAOCAMESSPEHRM/HEFPSEPElevators/Shared%20Documents/Scope/Modernization%20Scopes/Elevator%20Modernization%20Scope%20-%20final%2011.6.25.docx?d=w85f0f5f3da1a4df2850063891439ecbd&csf=1&web=1&e=CcvOCQ

Master Elevator List

VISN Station Number State Location (City) Building Number FCA Record # Elevator Name & Number Elevator Type Elevator use Overall Platform Size (inches) Clear Inside Platform (inches) (Occupiable, inside cab) Rated Load (lbs) Contract Speed (FPM) Total Travel (feet) Floors Served # of Openings or Landings Entrance Type and Size (center opening, telescoping, automatic, etc.) Type of Roping (configuration) Plunger Size (diameter inches) N/A for traction Building Criticality (FCD) Seismic Design Category (SDC) Hazardous Material Impact? Phasing Restrictions Notes

VISN 1 518 MA Bedford 3 14889 P1 Hydraulic Passenger 116x90 99x65 4000 100 10 2 2 Telescoping - 60" N/A for Hydraulic 6 Essential C Yes Single elevator not in a bank

VISN 1 518 MA Bedford 5 217194 P1 Traction Passenger 106x90 87X55 4000 200 32 3 3 Telescoping - 42" 5 Ropes overhead N/A Essential C Yes Single elevator not in a bank

VISN 1 518 MA Bedford 5 217195 P2 Hydraulic Passenger 117 X 72 99 X 64 4000 100 32 3 3 Telescoping - 48" N/A for Hydraulic 6 Essential C Yes Single elevator not in a bank

VISN 1 518 MA Bedford 19/21 14684 F1 Traction Service 63 x 73 57.5 x 56.5 2000 25 10 2 2 Manual Gate - 48" Basement drum 2 ropes N/A Ancillary C Yes Single elevator not in a bank

VISN 1 518 MA Bedford 61 15052 P1 Traction Passenger 114 x 84 87 x 52 3200 100 32 3 3 Telescoping - 56" 4 ropes 5/8 overhead N/A Essential C Yes Single elevator not in a bank

VISN 1 518 MA Bedford 70 15123 P1 Traction Passenger 112 X 90 103 X 55 4000 100 32 3 3 Telescoping - 56" 6 ropes overhead N/A Essential C Yes Single elevator not in a bank

VISN 1 523A4 MA West Roxbury 1 14119 P01 Traction Passenger Unknown 91 7/8" x 61 3/4" 3500 300 Unknown 6 6 Telescoping 2:1 Single Wrap N/A Critical D Yes 1 elevator under modernization at a time Controller: EC 18416

VISN 1 523A4 MA West Roxbury 1 14119 P02 Traction Passenger Unknown 92" x 61 1/8" 3500 300 Unknown 6 6 Telescoping 2:1 Single Wrap N/A Critical D Yes 1 elevator under modernization at a time Controller: EC 18417

VISN 1 523A4 MA West Roxbury 1 15961 P03 Traction Freight Unknown 90" x 91 3/4" 6000 300 Unknown 4 4 Telescoping 2:1 Single Wrap N/A Critical D Yes Single elevator not in a bank Controller: EC 18415

VISN 1 523A4 MA West Roxbury 1 17242 S04 Traction Service Unknown 92 1/2" x 80" 5000 300 unknown 5 5 Center Opening 2:1 Single Wrap N/A Critical D Yes 1 elevator under modernization at a time Controller: EC 18414

VISN 1 523A4 MA West Roxbury 1 17242 S05 Traction Service Unknown 92 1/2" x 80" 5000 300 Unknown 5 5 Center Opening 2:1 Single Wrap N/A Critical D Yes 1 elevator under modernization at a time Controller: EC 18413

VISN 1 523A4 MA West Roxbury 2 17263 P01 Traction Passenger Unknown 106" x 77" 6000 350 Unknown 5 5 Telescoping 2:1 Single Wrap N/A Critical D Unknown 1 elevator under modernization at a time 2021 FCA Report Deficiency C. Current maintenance report shows elevator requires replacement due to age and part availability Controller: MCE 3219035

VISN 1 523A4 MA West Roxbury 2 17263 P02 Traction Passenger Unknown 106 1/4" x 77" 6000 350 Unknown 5 5 Telescoping 2:1 Single Wrap N/A Critical D Unknown 1 elevator under modernization at a time 2021 FCA Report Deficiency C. Current maintenance report shows elevator requires replacement due to age and part availability Controller: MCE 3219038

VISN 1 523A4 MA West Roxbury 2 17263 P03 Traction Passenger Unknown 105 3/4" x 76 3/4" 6000 350 Unknown 5 5 Telescoping 2:1 Single Wrap N/A Critical D Unknown 1 elevator under modernization at a time 2021 FCA Report Deficiency C. Current maintenance report shows elevator requires replacement due to age and part availability Controller: MCE 3219101

VISN 1 523A4 MA West Roxbury 2 17264 F4 Hydraulic Freight Unknown 108" x 91 3/4" 5000 80 Unknown 2 2 Telescoping - Vertical N/A for Hydraulic Unknown Critical D Unknown Single elevator not in a bank 2021 FCA Report Deficiency C. Current maintenance report shows elevator requires replacement due to age and part availability Controller: MCE 3221806

VISN 1 523A4 MA West Roxbury 3 17359 S4 Hydraulic Service Unknown 98 1/2" x 75 1/4" 5000 125 Unknown 3 3 Telescoping N/A for Hydraulic Unknown Critical D No Single elevator not in a bank 2021 FCA Report Deficiency C. Current maintenance report shows elevator requires replacement due to age and part availability Controller: GAL 334907-12/1

VISN 1 523A4 MA West Roxbury 96 297573 P01 Hydraulic Passenger Unknown Unknown 3000 80 Unknown 2 2 Single Slide N/A for Hydraulic Unknown Ancillary D No Single elevator not in a bank 2021 FCA Report Deficiency C. Current maintenance report shows elevator requires replacement due to age and part availability Controller: TKE EAE767

VISN 1 523A5 MA Brockton 1 17531 P19 Hydraulic Passenger Unknown 53 7/8" x 68" 2000 110 Unknown 3 3 Single Slide N/A for Hydraulic Unknown Essential D Yes Single elevator not in a bank Controller: Elevator Systems Hydro

VISN 1 523A5 MA Brockton 5 14882 P10 Traction Passenger Unknown 95 1/4" x 63 1/2" 4000 150 Unknown 3 3 Telescoping Unknown N/A Critical D Unknown Single elevator not in a bank Controller: Elevator Controls O.H. Geared Traction

VISN 1 523A5 MA Brockton 20 17622 P15 Traction Passenger Unknown 60 1/2" x 62" 2250 50 Unknown 2 2 Telescoping Unknown N/A Critical D No Single elevator not in a bank Controller: Motion Control M4000 Basement Traction

VISN 1 523A5 MA Brockton 20 17623 S14 Traction Service Unknown 93 5/8" x 81" 5000 100 Unknown 2 2 Telescoping Unknown N/A Critical D Unknown Single elevator not in a bank 2021 FCA Report Deficiency C. Current maintenance report shows elevator requires replacement due to age and part availability Controller: Motion Control M4000 Geared Traction

VISN 1 608 NH Manchester 1 52392 P1 Traction Passenger Unknown 92" x 64" 4000 350 80 approx. 7 7 telescoping Unknown from existing documentation N/A Critical C No 1 elevator under modernization at a time Bldg #1 Passenger Elevator #1- Graded C at last FCA and is more like a D now

VISN 1 608 NH Manchester 1 52392 P2 Traction Passenger TBD 92" x 64" 4000 350 80 approx 7 7 telescoping unknown N/A Critical C No 1 elevator under modernization at a time Building #1 Passenger Elevator #2

VISN 1 608 NH Manchester 15 52426 P1 Hydraulic Passenger Unknown 96" x 64" 4000 100 12' approx. 2 2 telescoping N/A for Hydraulic unknown Essential C No 1 elevator under modernization at a time Bldg #15 Seacoast entrance Passenger elevator #1 servicing CLC visitors

VISN 1 608 NH Manchester 15 52426 P2 Hydraulic Passenger unknown 96" x 64" 4000 100 12 approx 2 2 telescoping N/A for Hydraulic unknown Essential C No 1 elevator under modernization at a time Building #15 CLC/ Seacoast Entrance Passenger elevator #2 for CLC visitors and staff

VISN 1 608 NH Manchester 1 52393 S3 Traction Service unknown 80" x 92" 5000 350 80' approx 7 7 telescoping unknown N/A Critical C No 1 elevator under modernization at a time Building #1 Eagle Entrance Service Elevator

VISN 1 631 MA Leeds MA 16 219553 F1 Hydraulic Freight Not Accessible 84x99.5 6000 Not Available 12 Basement and 1st Floors 2 Manual Freight N/A for Hydraulic 6.5 Critical A Yes Single elevator not in a bank

VISN 1 631 MA Leeds MA 26 63455 P26 Hydraulic Passenger Not accessible 86.5x61 3500 100 23'9" Basement, 1st and 2nd 3 Automatic Telescoping, 2sp, s/s N/A for Hydraulic 6.5 Essential A Yes Single elevator not in a bank

VISN 1 631 MA Leeds MA 7 63664 P7 Hydraulic Passenger 100x68 91x64 4000 100 11'9" 1st and 2nd 2 Automatic Telescoping, 2sp, s/s N/A for Hydraulic 6.5 Essential A Yes Single elevator not in a bank

VISN 1 631 MA Leeds MA 6 63557 P6 Hydraulic Passenger 96x72 94x70 4500 Not available 12 1st and 2nd 2 Automatic Telescoping, 2sp, s/s N/A for Hydraulic 6.5 Critical A Yes Single elevator not in a bank

VISN 1 689 CT West Haven 1 221701 P1 Traction Passenger 100 x 68 96 x 62 4000 500 150 11 11 Telescoping - 48inches 2:1 Double Wrap NA Critical C Yes 1 elevator under modernization at a time 1 elevator per building down at a time; however, facility can allow 1 elevator in multiple buildings to be down at a time.

VISN 1 689 CT West Haven 1 221701 P2 Traction Passenger 100 x 68 96 x 62 4000 500 150 11 11 Telescoping - 48 inches 2:1 Double Wrap NA Critical C Yes 1 elevator under modernization at a time 1 elevator per building down at a time; however, facility can allow 1 elevator in multiple buildings to be down at a time.

VISN 1 689 CT West Haven 1 221701 P3 Traction Passenger 100 x 68 96 x 62 4000 500 150 11 11 Telescoping - 48 inches 2:1 Double Wrap NA Critical C Yes 1 elevator under modernization at a time 1 elevator per building down at a time; however, facility can allow 1 elevator in multiple buildings to be down at a time.

VISN 1 689 CT West Haven 1 221701 P4 Traction Passenger 100 x 68 96 x 62 4000 500 150 11 11 Telescoping - 48 inches 2:1 Double Wrap NA Critical C Yes 1 elevator under modernization at a time 1 elevator per building down at a time; however, facility can allow 1 elevator in multiple buildings to be down at a time.

VISN 1 689 CT West Haven 1 221702 P5 Traction Passenger 114 x 86 108 x 80 4000 500 126 9 9 Telescoping - 48 inches 2:1 Double Wrap NA Critical C Yes 1 elevator under modernization at a time 1 elevator per building down at a time; however, facility can allow 1 elevator in multiple buildings to be down at a time.

VISN 1 689 CT West Haven 1 221703 S1 Traction Service 114 x 90 108 x 84 4500 500 150 11 11 Telescoping - 54 inches 2:1 Double Wrap NA Critical C Yes 1 elevator under modernization at a time 1 elevator per building down at a time; however, facility can allow 1 elevator in multiple buildings to be down at a time.

VISN 1 689 CT West Haven 1 221705 S2 Traction Service 114 x 90 108 x 84 5000 500 165 12 12 Center Opening - 48 inches 2:1 Double Wrap NA Critical C Yes 1 elevator under modernization at a time 1 elevator per building down at a time; however, facility can allow 1 elevator in multiple buildings to be down at a time.

VISN 1 689 CT West Haven 1 108234 F1 Traction Freight 89 x 54 84 x 48 2000 25 26 2 2 Manual - 48 inches Drum below elevator NA Critical C Yes Single elevator not in a bank

VISN 1 689 CT West Haven 2 89962 P6 Traction Passenger 100 x 68 96 x 62 4000 400 117 9 9 Center opening - 48 inches 2:1 Double Wrap NA Critical C Yes 1 elevator under modernization at a time 1 elevator per building down at a time; however, facility can allow 1 elevator in multiple buildings to be down at a time.

VISN 1 689 CT West Haven 2 89962 P7 Traction Passenger 100 x 68 96 x 62 4000 400 117 9 9 Center opening - 48 inches 2:1 Double Wrap NA Critical C Yes 1 elevator under modernization at a time 1 elevator per building down at a time; however, facility can allow 1 elevator in multiple buildings to be down at a time.

VISN 1 689 CT West Haven 2 89962 P8 Traction Passenger 100 x 68 96 x 62 4000 400 117 9 9 Center opening - 48 inches 2:1 Double Wrap NA Critical C Yes 1 elevator under modernization at a time 1 elevator per building down at a time; however, facility can allow 1 elevator in multiple buildings to be down at a time.

VISN 1 689 CT West Haven 2 221720 P9 Hydraulic Passenger 100 x 68 96 x 68 5000 120 39 3 4 Center opening - 48 inches N/A for Hydraulic 6.5 Critical C No 1 elevator under modernization at a time 1 elevator per building down at a time; however, facility can allow 1 elevator in multiple buildings to be down at a time.

VISN 1 689 CT West Haven 2 221720 P10 Hydraulic Passenger 100 x 68 96 x 68 5000 150 39 3 4 Center opening - 48 inches N/A for Hydraulic 6.5 Critical C No 1 elevator under modernization at a time 1 elevator per building down at a time; however, facility can allow 1 elevator in multiple buildings to be down at a time.

VISN 1 689 CT West Haven 2 221717 S3 Traction Service 114 x 90 108 x 84 5000 400 117 9 9 Center opening - 48 inches 2:1 Double Wrap NA Critical C Yes 1 elevator under modernization at a time 1 elevator per building down at a time; however, facility can allow 1 elevator in multiple buildings to be down at a time.

VISN 1 689 CT West Haven 2 221724 S4 Hydraulic Service 112 x 66 108 x 60 5000 100 26 2 2 Center opening - 62 inches N/A for Hydraulic 6 Critical C Yes 1 elevator under modernization at a time 1 elevator per building down at a time; however, facility can allow 1 elevator in multiple buildings to be down at a time.

VISN 1 689 CT West Haven 5 94643 P11 Hydraulic Passenger 100 x 78 96 x 72 4000 125 52 4 4 Telescoping - 67 inches N/A for Hydraulic 5.5 Critical C Yes Single elevator not in a bank

VISN 1 689 CT West Haven 15 94220 P12 Traction Passenger 76 x 76 72 x 72 2000 50 16 2 2 Telescoping - 48 inches Bottom drum NA Ancillary B Yes Single elevator not in a bank

VISN 1 689 CT West Haven 24 89963 S5 Hydraulic Service 52 x 52 48 x 48 1000 unknown 30 2 2 Manual - 48 inches N/A for Hydraulic 4.38 Ancillary B Yes Single elevator not in a bank

VISN 1 689A4 CT Newington 1 94947 P4 Traction Passenger 90 x 58 83 x 52 2500 300 75 5 5 Telescoping - 40 inches 2:1 Double Wrap NA Ancillary B Yes 1 elevator under modernization at a time

VISN 1 689A4 CT Newington 1 94947 P5 Traction Passenger 90 x 58 83 x 52 2500 300 75 5 5 Telescoping - 40 inches 2:1 Double Wrap NA Ancillary B Yes 1 elevator under modernization at a time

VISN 1 689A4 CT Newington 2C 95010 P6 Traction Passenger 62 x 82 55 x 76 3000 100 45 3 3 Center opening - 42 inches 2:1 Double Wrap NA Ancillary B Yes 1 elevator under modernization at a time

VISN 1 689A4 CT Newington 2C 222287 P7 Traction Passenger 99 x 77 93 x 72 5000 100 45 3 3 Center opening - 48 inches 2:1 Double Wrap NA Ancillary B Yes 1 elevator under modernization at a time

VISN 1 689A4 CT Newington 2E 95042 P1 Traction Passenger 99 x 77 93 x 72 5000 350 90 6 6 Center opening - 48 inches 2:1 Double Wrap NA Essential B Yes 1 elevator under modernization at a time

VISN 1 689A4 CT Newington 2E 95042 P2 Traction Passenger 99 x 77 93 x 72 5000 350 90 6 6 Center opening - 48 inches 2:1 Double Wrap NA Essential B Yes 1 elevator under modernization at a time

VISN 1 689A4 CT Newington 2E 95042 P3 Traction Passenger 99 x 77 93 x 72 5000 350 90 6 6 Center opening - 48 inches 2:1 Double Wrap NA Essential B Yes 1 elevator under modernization at a time

VISN 1 689A4 CT Newington 2E 222289 S1 Traction Service 99 x 77 93 x 72 5000 350 90 6 6 Center opening - 48 inches 2:1 Double Wrap NA Essential B Yes 1 elevator under modernization at a time

VISN 1 689A4 CT Newington 2E 222289 S2 Traction Service 99 x 77 93 x 72 5000 350 105 7 7 Center opening - 48 inches 2:1 Double Wrap NA Essential B Yes 1 elevator under modernization at a time

VISN 1 689A4 CT Newington 3 95123 S3 Hydraulic Service 58 x 63 52 x 49 2500 150 45 3 4 Telescoping - 41 inches N/A for Hydraulic 5.5 Essential B Yes Single elevator not in a bank

VISN 1 689A4 CT Newington 4 222292 P8 Hydraulic Passenger 70 x 63 66 x 50 2000 125 45 3 3 Telescoping - 36 inches N/A for Hydraulic 5.5 Ancillary B Yes Single elevator not in a bank

VISN 1 689A4 CT Newington 32 92112 P10 Hydraulic Passenger 96 x 62 85 x 59 3500 35 25 2 2 Telescoping - 46 inches N/A for Hydraulic 5.5 Ancillary B Yes Single elevator not in a bank

VISN 10 506 MI Ann Arbor 3 8219 P1 Hydraulic Passenger 4608 4080 2000 125 18.5' 3 3 2 Speed Side Opening - Front Only 4" ancillary B N Single elevator not in a bank

VISN 10 506 MI Ann Arbor 30 8247 WE1 Hydraulic Passenger 7128 6132 3500 125 44' 5 5 2 Speed Side Opening - Front Only 6" essential B N 1 elevator under modernization at a time

VISN 10 506 MI Ann Arbor 30 8247 WE2 Hydraulic Passenger 7128 6132 3500 125 44' 5 5 2 Speed Side Opening - Front Only 6" essential B N 1 elevator under modernization at a time

VISN 10 506 MI Ann Arbor 31 8285 S1 Hydraulic Service 12321 11449 3500 125 36' 5 5 Front and Rear Opening 5.5" critical B N 1 elevator under modernization at a time

VISN 10 506 MI Ann Arbor 31 8285 S2 Hydraulic Service 12321 11449 3500 125 36' 4 4 Front and Rear Opening 5.5" critical B N 1 elevator under modernization at a time

VISN 10 506 MI Ann Arbor 31 219203 P1 Hydraulic Service 4608 4080 2000 125 106" 2 2 Front Only - 2 Speed Side Opening 3.75" critical B N Single elevator not in a bank

VISN 10 515 MI Battle Creek 5 9309 Hydraulic Freight 2000 50 20 2 2 Manual Bi-Parting Freight Door essential B Y Single elevator not in a bank

VISN 10 515 MI Battle Creek 200 143282 Hydraulic Passenger 72"x115" 68"x94" 4500 125 23' 3 3 2 Speed Left Side Slide 48" 5.44" ancillary B N 1 elevator under modernization at a time

VISN 10 538 OH Chillicothe 31 24504 P4 Hydraulic Passenger 4000 150 3

VISN 10 541 OH Cleveland 1 26282 PE3 Traction Passenger 68"Wx 104"D 102"D x 63"W 4000 250 105 Basement,First, Second, Third, Fourth, Fifth, and Sixth Floors 7 Telescoping 1:1 Single Wrap critical B Y 2 elevators per bank down simultaneously

VISN 10 541 OH Cleveland 1 26282 PE4 Traction Passenger 68"Wx 104"D 102"D x 63"W 4000 250 105 B, 1, 2, 3, 4, 5, 6 7 Telescoping 1:1 Single Wrap critical B Y 2 elevators per bank down simultaneously

VISN 10 541 OH Cleveland 1 26282 PE5 Traction Passenger 68"Wx 104"D 102"D x 63"W 4000 250 105 B, 1, 2, 3, 4, 5, 6 7 Telescoping 1:1 Single Wrap critical B Y 2 elevators per bank down simultaneously

VISN 10 541 OH Cleveland 1 26282 PE6 Traction Passenger 68"Wx 109 1/2"D 102"D x 63"W 4000 250 105 B, 1, 2, 3, 4, 5, 6 7 Telescoping 1:1 Single Wrap critical B Y 2 elevators per bank down simultaneously

VISN 10 541 OH Cleveland 1 26282 PE7 Traction Passenger 68"Wx 104"D 102"D x 63"W 4000 250 105 B, 1, 2, 3, 4, 5, 6 7 Telescoping 1:1 Single Wrap critical B Y 2 elevators per bank down simultaneously

VISN 10 541 OH Cleveland 1 26282 PE8 Traction Passenger 68"Wx 104"D 102"D x 63"W 4000 250 105 B, 1, 2, 3, 4, 5, 6 7 Telescoping 1:1 Single Wrap critical B Y 2 elevators per bank down simultaneously

VISN 10 541 OH Cleveland 1 26287 SE1 Traction Service 84"Wx 104"D 102"D x 81"W 5000 250 116 B, 1, 2, 3, 4, 5, 6, P 8 Telescoping 1:1 Single Wrap critical B Y 2 elevators per bank down simultaneously

VISN 10 541 OH Cleveland 1 26287 SE2 Traction Service 84"Wx 104"D 102"D x 81"W 5000 250 105 B, 1, 2, 3, 4, 5, 6 7 Telescoping 1:1 Single Wrap critical B Y 2 elevators per bank down simultaneously

VISN 10 583 IN Indianapolis 1 224752 P8 Traction Passenger 8'7" x 8' 11" 8' 2" x 8' 5" 4000 350 100' 8 8 Front Opening Only 2:1 Single Wrap NA critical D Y 1 elevator under modernization at a time

VISN 10 583 IN Indianapolis 1 224752 P9 Traction Passenger 8'7" x 8' 11" 8' 2" x 8' 5" 4000 350 100' 8 8 Front Opening Only 2:1 Single Wrap NA critical D Y 1 elevator under modernization at a time

VISN 10 583 IN Indianapolis 1 224752 P10 Traction Passenger 8'7" x 8' 11" 8' 2" x 8' 5" 4000 350 100' 8 8 Front Opening Only 1:1 Single Wrap NA critical D Y 1 elevator under modernization at a time

VISN 10 610 IN Marion 16 53107 S11 Hydraulic Service 5000 150 4 4 Center Opening ancillary A N 1 elevator under modernization at a time

VISN 10 610 IN Marion 16 53107 S12 Hydraulic Service 5000 150 4 4 Center Opening ancillary A N 1 elevator under modernization at a time

VISN 10 610 IN Marion 51 53402 F1 Hydraulic Freight 4000 40 2 2 Manual Bi-Parting Freight Door ancillary A N Single elevator not in a bank

VISN 15 589 MO Kansas City 1 40313 E6 Traction Service 90x120 50 in x80 in 2000 lbs 50 FPM 15 Basement and 1st 2 Manual not known N/A Critical C Yes Single elevator not in a bank

VISN 15 589 MO Kansas City 55 320057 HA-1 Hydraulic Passenger 110x120 70x80 3500 Lbs 75 fpm 15 1st & 2nd 2 auto Other unknown ancillary C Single elevator not in a bank

VISN 15 589 MO Kansas City 55 320058 HA-2 Hydraulic Service 110x136 70x96 4500 lbs 75 fpm 15 1st &2nd 2 auto Other unknown ancillary C Single elevator not in a bank

VISN 15 589A4 MO Columbia 1 44877 P-1 Traction Passenger 110"x85" 94"x74" 4000 350 81 7 7 center 1:1 Single Wrap NA critical C N

VISN 15 589A4 MO Columbia 1 44877 P-2 Traction Passenger 110"x85" 94"x74" 4000 350 81 7 7 Center 1:1 Single Wrap NA critical C N

VISN 15 589A4 MO Columbia 1 44877 P-3 Traction Passenger 110"x85" 94"x74" 4000 350 81 7 7 Center 1:1 Single Wrap NA critical C N

VISN 15 589A4 MO Columbia 1 164171 S-4 Traction Service 105"X111" 80"x108" 5000 350 81 7 8 Center, Front and Back 1:1 Single Wrap NA critical C N

VISN 15 589A4 MO Columbia 1 164171 S-5 Traction Service 105"X111" 80"x108" 5000 350 81 7 8 Center, Front and Back 1:1 Single Wrap NA critical C N

VISN 15 589A4 MO Columbia 1 164172 P-6 Hydraulic Passenger 100"x64" 80"X60" 2500 125 40 4 4 Center Other 6" critical C N

VISN 15 589A5 KS Topeka 1 45210 S3 Traction Service ?? 79x93 5000 350 100 7 7 Side Slide 1:1 Single Wrap N/A critical A Y 2 elevators per bank down simultaneously Lead paint on doors, asbestos in door

VISN 15 589A5 KS Topeka 1 254195 S4 Traction Service ?? 76x97 5000 350 100 7 7 Side Slide 1:1 Single Wrap N/A critical A Y 2 elevators per bank down simultaneously Lead paint on doors, asbestos in door

VISN 15 589A5 KS Topeka 1 392632 P1 Traction Passenger ?? 63x96 4000 350 100 7 7 Side Slide 1:1 Single Wrap N/A critical A Y 2 elevators per bank down simultaneously Lead paint on doors, asbestos in door

VISN 15 589A5 KS Topeka 1 392632 P2 Traction Passenger ?? 63x96 4000 350 100 7 7 Side Slide 1:1 Single Wrap N/A critical A Y 2 elevators per bank down simultaneously Lead paint on doors, asbestos in door

VISN 15 589A5 KS Topeka 2 45225 P4 Traction Passenger ?? 63x96 4000 350 61 4 4 Side Slide 1:1 Single Wrap N/A critical A Y 2 elevators per bank down simultaneously Lead paint on doors, asbestos in door

VISN 15 589A5 KS Topeka 2 45225 P5 Traction Passenger ?? 63x96 4000 350 61 4 4 Side Slide 1:1 Single Wrap N/A critical A Y 2 elevators per bank down simultaneously Lead paint on doors, asbestos in door

VISN 15 589A5 KS Topeka 2 45224 S6 Traction Service ?? 77x92 5000 350 61 4 4 Side Slide 1:1 Single Wrap N/A critical A Y 2 elevators per bank down simultaneously Lead paint on doors, asbestos in door

VISN 15 589A5 KS Topeka 3 45374 P7 Traction Passenger ?? 61x89 4000 250 45 3 3 Side Slide 1:1 Single Wrap N/A essential A Y 1 elevator under modernization at a time Lead paint on doors, asbestos in door

VISN 15 589A5 KS Topeka 3 45374 S8 Traction Service ?? 77x90 5000 250 45 3 3 Side Slide 1:1 Single Wrap N/A essential A Y 1 elevator under modernization at a time Lead paint on doors, asbestos in door

VISN 15 589A5 KS Topeka 4 45409 P9 Traction Passenger ?? 63x92 4000 150 46 3 3 Side Slide 1:1 Single Wrap N/A critical A Y 1 elevator under modernization at a time Lead paint on doors, asbestos in door

VISN 15 589A5 KS Topeka 5 45691 P10 Traction Passenger ?? 64x93 4000 150 52 3 3 Side Slide 1:1 Single Wrap N/A essential A Y 1 elevator under modernization at a time Lead paint on doors, asbestos in door

VISN 15 589A5 KS Topeka 9 44625 P11 Traction Passenger ?? 64x97 5000 200 58 3 3 Side Slide 1:1 Single Wrap N/A ancillary A Y 1 elevator under modernization at a time Lead paint on doors, asbestos in door

VISN 15 589A6 KS Leavenworth 88 46564 Vertitron/#1 Traction Passenger 95 x 68 84 x 65 3500 200 50 5 5 Telescoping Single Wrap N/A Critical B No Single elevator not in a bank

VISN 15 589A6 KS Leavenworth 89 46572 Pharmacy/#2 Esco - 1993 Hydraulic Freight 66 x 54 64 x 48 3000 100 20 2 2 Telescoping N/A Unknow, buit maybe a 4" to 4.5" Critical B No Single elevator not in a bank

VISN 15 589A6 KS Leavenworth 163 46273 K1 Hydraulic Passenger 98 x 80 96 x 76 5000 100 30 3 3 Telescoping N/A Unknow, buit maybe a 4" to 4.5" Anciliary B No Single elevator not in a bank

VISN 15 589A6 KS Leavenworth 160 46204 D3 Hydraulic Passenger 112 x 78 90 x 76 5000 100 20 2 2 Telescoping N/A Unknow, buit maybe a 4" to 4.5" Critical B No Single elevator not in a bank

VISN 15 589A6 KS Leavenworth 160 46205 D1 Hydraulic Passenger 112 x 78 90 x 76 5000 100 20 2 2 Telescoping N/A Unknow, buit maybe a 4" to 4.5" Critical B No 1 elevator under modernization at a time

VISN 15 589A6 KS Leavenworth 160 46205 D2 Hydraulic Passenger 112 x 78 90 x 76 5000 100 20 2 2 Telescoping N/A Unknow, buit maybe a 4" to 4.5" Critical B No 1 elevator under modernization at a time

VISN 15 589A6 KS Leavenworth 41 46383 Logistics/Freight - Montgomery - 1972 Hydraulic Freight 104 x 86 96 x 76 4000 70 30 3 3 Telescoping N/A Unknow, buit maybe a 4" to 4.5" Essential B No Single elevator not in a bank

VISN 15 589A7 KS Wichita 1 163616 #1-3 HYDRAULIC Passenger 76.5 104 4500 80 2 2 Telescoping 48 N/A Unk Critical D N Single elevator not in a bank Elevator 3, #4500 capacity simplex unit serving Two landings adjacent to emergency room area. Installation in 2005. Front and rear opening, with a short landing. Two speed side opening doors with Kone Linear door operators Kone KCM 831 controller with submersible ITI Hydraulik power unit. COnventional inground hydraulic jack.

VISN 15 589A7 KS Wichita 2 46999 #2-1 HYDRAULIC Freight 67 60 2500 70 12 2 2 Top open 58 N/A Unk Critical D N Single elevator not in a bank Elevator 2, Freight door operation, Courion doors and gate, power operated. 1987 install with Montgomery Miprom controls. Bad machine room valve, conventional hydraulic jack and conventional tank over power unit. #2500 capacity and 80 FPM rated car spped. Hoistway freight doors in good condition and suitable for reuse

VISN 15 589A7 KS Wichita 5 47390 #5-1 HYDRAULIC Passenger 71 92 4000 100 24 3 3 Telescoping 48 N/A Unk Ancillary D N Single elevator not in a bank FCA Description mislabeled the elevator name. FCA 47390 is for #5- Elevator 14, Three stop hydraulic elevator with a conventional inground jack and original conventional tank over power unit with original control valve. 1988 installation with MOntgomery Miprom controls. Dual car operating stations. Two speed side opening doors, front only. Sump pump in pit. #4000 capacity with 125 FPM rated car speed.

VISN 15 589A7 KS Wichita 19 46934 #19-1 CABLE Passenger 61 89 3500 150 24 3 3 Telescopeing 42 1:1 Single Wrap N/A Critical D N Single elevator not in a bank The most troublesome elevator on station. Simplex operation, Three stop geared traction unit with Montgomery 208E machine and Montgomery relay logic controls installed in 1977. #3500 capacity and 150 FPM rated car speed. Dual car operating stations. Two speed side opening doors. MAC door operator. Motor generator driven with all machine room equipment located in attic area in an enclosed cage with no conditioned space, a lot of adjacent lumber reinforcement surrounding machine. Poor ride quality due to deteriorating machine condition. Sump pump in pit is inoperable.

VISN 15 589A7 KS Wichita 34 47301 #34-1 HYDRAULIC Passenger 86 97 5000 125 24 3 3 Telescoping 48 N/A Unk Critical D N 2 elevators per bank down simultaneously FCA Description mislabeled the elevator name. FCA 47301 is for #34-1 and 34-2. Elevators 10 and 11, duplex operation installed in 1982. Montgomery Miprom controllers with printed card operation. Three total landings served, front opening only. Conventional tank over power unit with maxton control valves. Keyed access to basement level and machine room, adjacent to hoistway. Sump in pit, not covered. #5000 capacity and 125 FPM rated car speed.Non compliant pit shut off valve.

VISN 15 589A7 KS Wichita 34 47301 #34-2 HYDRAULIC Passenger 86 97 5000 125 24 3 3 Telescoping 48 N/A Unk Critical D N 2 elevators per bank down simultaneously FCA Description mislabeled the elevator name. FCA 47301 is for #34-1 and 34-2. Elevators 10 and 11, duplex operation installed in 1982. Montgomery Miprom controllers with printed card operation. Three total landings served, front opening only. Conventional tank over power unit with maxton control valves. Keyed access to basement level and machine room, adjacent to hoistway. Sump in pit, not covered. #5000 capacity and 125 FPM rated car speed.Non compliant pit shut off valve.

VISN 15 589A7 KS Wichita 34 47300 #34-3 HYDRAULIC Freight 75 99 5000 125 36 4 4 Telescoping 50 1:1 Single Wrap Unk Critical D N Single elevator not in a bank SPS Dirty Elevator. Simplex operation serving four total landings. Montgomery Miprom controls installed in 1982. Conventional tank over power unit with maxton control valve, Minnesota Elevator power unit. Conventional in ground hydraulic jack and sump pump in pit. Unit is currently in keyed access operation only. front and rear opening with MAC door operators. Machine room is remote by approximately 15' at basement level.

VISN 15 589A7 KS Wichita 61 47481 #61-1 HYDRAULIC Passenger 71 97 4000 125 12 2 2 Telescoping 48 N/A Unk Ancillary D N Single elevator not in a bank FCA Description mislabeled the elevator name. FCA 47481 is for #61-1; Elevator 8; simplex operation serving two landings. Montgomery Miprom controls installed in 1990. Conventional tank over power unit with Montgomery control valve. Front opening only, two speed side opening doors with MAC door operator. Non compliant shut off valves. Dual car operating stations.

VISN 15 589A7 KS Wichita 61 47482 #61-2 HYDRAULIC Passenger 71 97 4000 125 12 2 2 Telescoping 48 N/A Unk Ancillary D N Single elevator not in a bank FCA Description mislabeled the elevator name. FCA 47482 is for #61-2; Elevator 7; simplex operation serving two landings. Montgomery Miprom controls installed in 1990. Conventional tank over power unit with Montgomery control valve. Front opening only, two speed side opening doors with MAC door operator. Non compliant shut off valves. Dual car operating stations. Keyed access on floor 2.

VISN 15 657A0 MO St. Louis, MO (Jefferson Barracks) 1 77984 P1E Hydraulic Passenger 72x105 60.5x90.5 4000 150 24 4 4 Side Telescoping 42x84 NA 6 Critical D Y 1 elevator under modernization at a time

VISN 15 657A0 MO St. Louis, MO (Jefferson Barracks) 1 252524 P1W Hydraulic Passenger 72x105 60.5x90.5 4000 150 24 4 4 Side Telescoping 42x84 NA 6 Critical D Y 1 elevator under modernization at a time

VISN 15 657A0 MO St. Louis, MO (Jefferson Barracks) 3 78199 P21 Hydraulic Passenger 83x86 65x72 2000 100 19.5 3 4 Side Telescoping 42x84 NA 4.5 Essential D Y Single elevator not in a bank

VISN 15 657A0 MO St. Louis, MO (Jefferson Barracks) 2 78104 P20 Hydraulic Passenger 68x74 61x68 2000 100 30 4 5 Side Telescoping 42x84 NA 4.5 Ancillary D Y Single elevator not in a bank

VISN 15 657A0 MO St. Louis, MO (Jefferson Barracks) 18 78045 P19 Hydraulic Passenger 70x105 63x96 4000 150 32.6 4 4 Side Telescoping 48x84 NA 6 Ancillary D Y Single elevator not in a bank

VISN 15657A0MOSt. Louis, MO (Jefferson Barracks)2378131F6HydraulicFreight74x9567x8835001501222Center Rollup/Rolldown
60x84NAunkn, est 6EssentialDYSingle elevator not in a bank

VISN 15 657A0 MO St. Louis, MO (Jefferson Barracks) 25 71776 P8 Hydraulic Passenger 67x110 54x100 3500 150 32 4 4 Side Telescoping 48x84 NA 6 Ancillary D Y Single elevator not in a bank

VISN 15 657A0 MO St. Louis, MO (Jefferson Barracks) 51 78370 P13 Hydraulic Passenger 85x105 77x92 5000 100 11.5 2 2 Side Telescoping 54x84 NA 5 Critical D N 1 elevator under modernization at a time

VISN 15 657A0 MO St. Louis, MO (Jefferson Barracks) 51 252532 P22 Hydraulic Passenger 68x105 62x97 4000 100 11.5 2 2 Side Telescoping 48x84 NA 6.5 Critical D N 1 elevator under modernization at a time

VISN 15 657A0 MO St. Louis, MO (Jefferson Barracks) 52 78402 S14 Hydraulic Service 86x105 77x92 5000 100 24.25 3 3 Center Opening, 48x84 NA 6 Critical D Y 1 elevator under modernization at a time

VISN 15 657A0 MO St. Louis, MO (Jefferson Barracks) 52 252538 P15 Hydraulic Passenger 86x105 62x97 4000 100 24.25 3 3 Side Telescoping 48x84 NA 6 Critical D Y 1 elevator under modernization at a time

VISN 15 657A0 MO St. Louis, MO (Jefferson Barracks) 52 252540 P16 Hydraulic Passenger 80x109 76x104 5000 100 24.25 3 3 Center Opening, 48x84 NA 6.5 Critical D Y 1 elevator under modernization at a time

VISN 15 657A4 MO Poplar Bluff 1 78978 4 Traction Passenger 67.5" x 100" 62.5" x 94" 4000 150 32.5833 4 4 2 speed right-hand automatic (46" wide) 1:1 Single Wrap NA critical D Y 1 elevator under modernization at a time FCA 78973 - FCA completed in 2020 shown as C. Updated FCA for 2025 is listed as D.

VISN 15 657A4 MO Poplar Bluff 1 78973 5 Traction Passenger 68" x 100" 60" x 94" 4000 100 11 2 2 2 speed right-hand automatic (46" wide) 1:1 Single Wrap NA critical D Y 1 elevator under modernization at a time FCA 78978 - 2020 FCA is listed as a B and incorrectly labeled as Material Handling. 2025 FCA update has it listed as a D however it is still incorrectly lavbeled as Material Handling. Currrenly utilized for wheel chair patient tranport from Urgent Care to Primary Care.

VISN 15 657A5 IL Marion 42 76345 9 Hydraulic Passenger 112.5x72 102x69 5000 100 12 Basement & Ground 2 Telescoping 48x84 Other 6.59" essential D N Single elevator not in a bank Two landings served, car speed 100

VISN 15 657A5 IL Marion 1 252449 10 Hydraulic Passenger ??x?? 94x69 4500 125 G,1,2,3,4 5 Telescoping 48x84 Other ????? essential D N Single elevator not in a bank

VISN 16 502 LA Alexandria 7 6934 7.1 Traction Passenger Unknown 8'4" x 5'4" 4000 600 60 5 5 Telescoping 1:1 Single Wrap N/A Essential A Unknown 1 elevator under modernization at a time The rating is a C not a D. OTIS modernization in 2023. They all need new doors and cab modernization.

VISN 16 502 LA Alexandria 7 6934 7.2 Traction Passenger Unknown 8'4" x 5'4" 4000 600 60 5 5 Telescoping 1:1 Single Wrap N/A Essential A Unknown 1 elevator under modernization at a time The rating is a C not a D. OTIS modernization in 2023. They all need new doors and cab modernization.

VISN 16 502 LA Alexandria 7 6934 7.3 Traction Service Unknown 8'4" x 6'9" 5000 600 60 5 5 Telescoping 2:1 Single Wrap N/A Essential A Unknown 1 elevator under modernization at a time The rating is a C not a D. OTIS modernization in 2023. They all need new doors and cab modernization.

VISN 16 502 LA Alexandria 7 6935 7.4 Traction Passenger Unknown 8'6" x 6'3" 5000 600 60 5 7 Center Opening 1:1 Single Wrap N/A Critical A Unknown 1 elevator under modernization at a time The rating is a C not a D. OTIS modernization in 2023. They both need new doors and cab modernization.

VISN 16 502 LA Alexandria 7 6935 7.5 Traction Passenger Unknown 8'6" x 6'3" 5000 600 60 5 7 Center Opening 1:1 Single Wrap N/A Critical A Unknown 1 elevator under modernization at a time The rating is a C not a D. OTIS modernization in 2023. They both need new doors and cab modernization.

VISN 16 502 LA Alexandria 7 6933 7.6 Hydraulic Passenger Unknown 6'4" x 4'2" 2500 Unknown 24 2 2 Telescoping N/A for Hydraulic Unknown Essential A Unknown 1 elevator under modernization at a time The rating is a F not a D.

VISN 16 580 TX Houston 100 43085 S6 Traction Service 6’-8” W, 8”-8” D 8’-0” D, 6’-6” W 5000 lbs 500 115’-8” 7 7 Center Opening 2:1 Single Wrap N/A Critical A No 1 elevator under modernization at a time

VISN 16 580 TX Houston 100 43085 S7 Traction Service 6’-8” W, 8”-8” D 8’-0” D, 6’-6” W 5000 500 115’-8” 7 7 Center Opening 2:1 Single Wrap N/A Critical A No 1 elevator under modernization at a time

VISN 16 580 TX Houston 100 43085 S8 Traction Service 6’-8” W, 8”-8” D 8’-0” D, 6’-6” W 5000 500 115’-8” 7 7 Center Opening 2:1 Single Wrap N/A Critical A No 1 elevator under modernization at a time

VISN 16 580 TX Houston 100 43085 S9 Traction Service 6’-8” W, 8”-8” D 8’-0” D, 6’-6” W 5000 500 115’-8” 7 7 Center Opening 2:1 Single Wrap N/A Critical A No 1 elevator under modernization at a time

VISN 16 580 TX Houston 100 43085 S10 Traction Service 6’-8” W, 8”-8” D 8’-0” D, 6’-6” W 5000 500 115’-8” 7 7 Center Opening 2:1 Single Wrap N/A Critical A No 1 elevator under modernization at a time

VISN 16 580 TX Houston 100 43086 S12 Hydraulic Service 4’-8” W x 8’-2”D 4’-6”W X 8’-0”D 3500 200 59'-2" Basement, 3rd 2 Telescoping N/A for Hydraulic 6 1/2" Critical A No Single elevator not in a bank

VISN 16 580 TX Houston 100 43083 P11 Hydraulic Passenger 6’-8” W X 8’-8” D 6’-6” W X 8’-0” D 5000 125 18’-10” 1st and 2nd 2 Telescoping N/A for Hydraulic 6" Critical A No 2 elevators per bank down simultaneously

VISN 16 580 TX Houston 100 43083 P12 Hydraulic Passenger 6’-8” W X 8’-8” D 6’-6” W X 8’-0” D 5000 125 18’-10” 1st and 2nd 2 Telescoping N/A for Hydraulic 6" Critical A No 2 elevators per bank down simultaneously

VISN 16 598 AR Little Rock, AR 3 406768 Parking Garage Elevators (1 & 2) Traction Passenger unknown 5460 3500 unknown unknown 4 4 telescoping 42" x 84" 1:1 Double Wrap N/A Critical C No 2 elevators per bank down simultaneously

VISN 16 598 AR Little Rock, AR 3 406783 Pedestrian Bridge Elevator Traction Passenger unknown 7228 4500 150 unknown 2 2 telescoping 48" x 84" 1:1 Double Wrap N/A Critical C No Single elevator not in a bank

VISN 16 598A0 AR North Little Rock, AR 58 50516 Main Elevator (1) Traction Passenger Uknown 4576 3500 200 unknown 4 4 telescoping 42" x 84" 1:1 Single Wrap N/A Ancillary C Unknown Single elevator not in a bank

VISN 16 598A0 AR North Little Rock, AR 65 404519 Exterior Entrance Elevator (1) Hydraulic Passenger Unknown 4032 4000 150 unknown 3 3 telescoping 48" x 84" N/A for Hydraulic 5.5 Ancillary C Unknown Single elevator not in a bank

VISN 16 598A0 AR North Little Rock, AR 65 404522 Main Corridor Elevator (2) Traction Passenger Unknown 4100 3500 200 unknown 3 3 telescoping 42" x 84" 1:1 Single Wrap N/A Ancillary C Unknown Single elevator not in a bank

VISN 16 598A0 AR North Little Rock, AR 66 47259 Patient Elevators (1 &2) Traction Passenger unknown 5760 3500 200 unknown 3 3 telescoping 42" x 84" 1:1 Single Wrap N/A Ancillary C Unknown Single elevator not in a bank

VISN 16 598A0 AR North Little Rock, AR 103 206955 Lobby Elevator Hydraulic Passenger unknown 4080 2500 125 unknown 3 3 sliding single door 42" x 84" N/A for Hydraulic 3.5 Ancillary C Unknown Single elevator not in a bank

VISN 16 598A0 AR North Little Rock, AR 170 292000 Service Elevators (S7 & S11) Traction Passenger unknown 7104 5000 350 unknown 4 4 center opening 48" x 84" 1:1 Single Wrap N/A Critical C Unknown 2 elevators per bank down simultaneously

VISN 16 598A0 AR North Little Rock, AR 182 50355 Freight Elevator Hydraulic Freight unknown 13824 10000 50 unknown 2 4 automatic lift 12' x 8' N/A for Hydraulic 8.5 Ancillary C Unknown Single elevator not in a bank

VISN 16 598A0 AR North Little Rock, AR 193 404126 Main Elevator Hydraulic Passenger unknown 4080 3000 100 unknown 2 2 telescoping 42" x 84" N/A for Hydraulic 2.75 Ancillary C No Single elevator not in a bank

VISN 16 598A0 AR North Little Rock, AR 170 50328 P1 Traction Passenger unknown 5460 3500 350 unknown 4 4 center opening 48" x 84" 1:1 Single Wrap N/A Critical C Unknown 2 elevators per bank down simultaneously

VISN 16 598A0 AR North Little Rock, AR 170 50328 P2 Traction Passenger unknown 5460 3500 350 unknown 4 4 center opening 48" x 84" 1:1 Single Wrap N/A Critical C Unknown 2 elevators per bank down simultaneously

VISN 16 598A0 AR North Little Rock, AR 170 50328 P3 Traction Passenger unknown 5460 3500 350 unknown 4 4 center opening 48" x 84" 1:1 Single Wrap N/A Critical C Unknown 2 elevators per bank down simultaneously

VISN 16 598A0 AR North Little Rock, AR 170 50328 P4 Traction Passenger unknown 5460 3500 350 unknown 4 4 center opening 48" x 84" 1:1 Single Wrap N/A Critical C Unknown 2 elevators per bank down simultaneously Christopher.Richards3@va.gov Christopher Richards

VISN 16 598A0 AR North Little Rock, AR 170 50328 P5 Traction Passenger 5888 4000 350 unknown 4 4 center opening 48" x 84" 1:1 Single Wrap N/A Critical 2 elevators per bank down simultaneously Modernized in 2010, but extensive downtime experienced. Minor repair only leads to minimal runtime before another breakage. Condition B as of 2021 but requesting consideration. Christopher.Richards3@va.gov Christopher Richards

VISN 16 598A0 AR North Little Rock, AR 170 50328 P6 Traction Passenger 5888 4000 350 unknown 4 4 center opening 48" x 84" 1:1 Single Wrap N/A Critical 2 elevators per bank down simultaneously Modernized in 2010, but extensive downtime experienced. Minor repair only leads to minimal runtime before another breakage. Condition B as of 2021 but requesting consideration. Christopher.Richards3@va.gov Christopher Richards

VISN 16 598A0 AR North Little Rock, AR 170 50328 S9 Traction Service 6900 5000 350 unknown 4 4 center opening 48" x 84" 1:1 Single Wrap N/A Critical Single Elevator not in a bank Not as significant downtime as above. Included because they are reported in the same FCA item Christopher.Richards3@va.gov Christopher Richards

VISN 16 598A0 AR North Little Rock, AR 170 50328 S12 Traction Service unknown 5460 3500 350 unknown 4 4 center opening 48" x 84" 1:1 Single Wrap N/A Critical C Unknown 2 elevators per bank down simultaneously

VISN 16 667 LA Shreveport 1 85252 Elevator 5 – Service Freight Traction Freight 7,410 sq in 7,410 sq in 5000 500 110 11 11 automatic bi-parting front 2:1 Single Wrap n/a Critical D No 1 elevator under modernization at a time

VISN 16 667 LA Shreveport 1 85252 Elevator 6 – Service Freight Type, Serves Sub-Basement to 10th Floor, front and rear doors Traction Service 7,410 sq in 7,410 sq in 500 500 100 10 10 automatic 2:1 Single Wrap n/a Critical D No 1 elevator under modernization at a time

VISN 16 667 LA Shreveport 1 85255 Elevator 1 Traction Passenger 5,612 sq in 5,612 sq in 4000 500 100 10 10 auto 2:1 Single Wrap n/a Critical D No 2 elevators per bank down simultaneously

VISN 16 667 LA Shreveport 1 85255 Elevator 2 Hydraulic Passenger 5,612 sq in 5,612 sq in 4000 500 100 10 10 auto 2:1 Single Wrap n/a Critical D No 2 elevators per bank down simultaneously

VISN 16 667 LA Shreveport 1 85255 Elevator #3 Hydraulic Passenger 5,612 sq in 5,612 sq in 4000 500 100 10 10 auto 2:1 Single Wrap n/a Critical D No 2 elevators per bank down simultaneously

VISN 16 667 LA Shreveport 1 85255 Elevator 8 Hydraulic Passenger 7,350 sq in 7,350 sq in 5000 500 100 10 10 auto 2:1 Single Wrap n/a Critical D No 2 elevators per bank down simultaneously

VISN 16 667 LA Shreveport 1 85255 Elevator 9 Hydraulic Passenger 7,350 sq in 7,350 sq in 5000 500 100 10 10 auto 2:1 Single Wrap n/a Critical D No 2 elevators per bank down simultaneously

VISN 16 667 LA Shreveport 1 85255 Elevator 10 Traction Passenger 7,350 sq in 7,350 sq in 5000 500 100 10 10 auto 2:1 Single Wrap n/a Critical D No 2 elevators per bank down simultaneously

VISN 17 504 TX Amarillo 28 383813 S2 Hydraulic Service Unk Unk 6000 350 Unk 4 4 center opening N/A for Hydraulic Unk Essential A No Single elevator not in a bank

VISN 17 519 TX Big Spring 1 15467 P-5 Hydraulic Passenger 48X72 48X72 5000 300 40 45660 1 telescoping N/A for Hydraulic Unknown Critical D No Single elevator not in a bank

VISN 17 549 TX Dallas 6 25592 P1 Hydraulic Passenger 104" deep 69" wide 100" deep 65 ' Wide 4000 100 40ft 4 2 Front and Rear N/A for Hydraulic 17" Ancillary C Unknown 2 elevators per bank down simultaneously Dover Manufacturer Model Type WCR Serial No E94776

VISN 17 549 TX Dallas 7 30283 P1 Hydraulic Passenger 104" deep X 69 " wide 100" deep X 65" w 4000 100 40 3 2 front and rear N/A for Hydraulic 17 Ancillary C Unknown 1 elevator under modernization at a time Dover Manufacturer Model Type WCR Serial No E94999

VISN 17 549 TX Dallas 1 118194 P13 Traction Passenger 95" Deep X 66 " Wide 91" Deep X 62" wide 3500 250 90 6 1 center 1:1 Single Wrap N/A Critical C Yes 1 elevator under modernization at a time Manufacturer Montgomery Model Type Miprom AI Serial No CTS-96079

VISN 17 549 TX Dallas 1 118194 P12 Traction Passenger 95" Deep X 66" Wide 91" Deep X 62 " Wide 3500 250 90 6 1 Center 1:1 Single Wrap N/A Critical C Yes 1 elevator under modernization at a time Manufacturer Montgomery Model Type Miprom AI Serial No CTS-96078

VISN 17 549 TX Dallas 2 25782 P10 Traction Passenger 104" deep X 81.5" Wide 100" Deep X 72.5" Wide 5000 200 70 5 1 Front Center Opening 1:1 Single Wrap N/A Critical C Yes 1 elevator under modernization at a time Montgomery Model Miprom21 CTS-145546

VISN 17 549 TX Dallas 2 25782 P11 Traction Passenger 104" deep X 81.5" wide 100" deep X 77 1/2" wide 5000 200 70 5 1 Front Center 1:1 Single Wrap N/A Critical C Yes 1 elevator under modernization at a time Montgomery Model Miprom 21 CTS-145547

VISN 17 549 TX Dallas 1 118194 S14 Traction Service 97.5" Deep X 85.5" wide 93.5" deep X 81.5 " wide 5000 200 90 3 1 front center opening 1:1 Single Wrap N/A Critical C Yes 1 elevator under modernization at a time Manufacture Montgomery model Type Miprom AI Serial CTS-96080

VISN 17 549 TX Dallas 74 27633 P1 Hydraulic Passenger 117.5" Deep X 83" wide 113.5" deep X 79" wide 6500 100 35 2 1 1 opening 2 landings N/A for Hydraulic 24" Critical C Unknown Single elevator not in a bank Dover Manufacturer Model Type WCR Serial No EE5285

VISN 17 549A4 TX Bonham 3 30768 P5 Hydraulic Passenger Unknown Unknown 3000 80 2 1 Front 2:1 Single Wrap Critical D Unknown Single elevator not in a bank MANUFACTURER: ESCO; MFG. NO.: FC9212169

VISN 17 549A4 TX Bonham 4 30832 P7 Hydraulic Passenger Unknown Unknown 4000 80 2 1 Front 2:1 Single Wrap Critical D Unknown Single elevator not in a bank MANUFACTURER: ESCO: MFG. NO.: FC83460

VISN 17 549A4 TX Bonham 12 30685 P6 Hydraulic Passenger 4000 80 2 1 Front 2:1 Single Wrap Critical D Unknown Single elevator not in a bank MANUFACTURER: ESCO; MFG. NO.: FC83649

VISN 17 549A4 TX Bonham 24 30727 P1 Hydraulic Passenger Unknown Unknown 4000 80 2 1 Front 2:1 Single Wrap Critical D Unknown 1 elevator under modernization at a time MANUFACTURER: ESCO; MFG. NO.: FC9212170

VISN 17 549A4 TX Bonham 24 30727 P2 Hydraulic Passenger Unknown Unknown 4000 80 2 1 Front 2:1 Single Wrap Critical D Unknown 1 elevator under modernization at a time MANUFACTURER: ESCO; MFG. NO.: FC9212168

VISN 17 549A4 TX Bonham 24 30727 P3 Hydraulic Passenger Unknown Unknown 4000 80 2 1 Front 2:1 Single Wrap Critical D Unknown 1 elevator under modernization at a time MANUFACTURER: ESCO; MFG. NO.: FC9212169

VISN 17 671 TX San Antonio G1 381357 P1-GAR Traction Passenger 92 88 4000 200 30 4 4 center opening belt drive N/A Essential A No Single elevator not in a bank

VISN 17 671 TX Kerrville 11 260447 KD-11 P4 Hydraulic Service 92 89 4000 150 24 3 3 center opening N/A for Hydraulic 8 Essential A No Single elevator not in a bank

VISN 17 671 TX San Antonio 1 251224 P16 Hydraulic Passenger 92" 81 1/2 3000 125 52 4 4 center opening N/A for Hydraulic 12" Essential A No Single elevator not in a bank

VISN 17 671 TX San Antonio 1 381356 Hydraulic Passenger 92 88 4000 125 32 3 3 center opening N/A for Hydraulic 12 Essential A No 1 elevator…

This is the start of the file's text. The full file is on GovTribe.