Att. 5-Drawings 3-Erie, PA.pdf

PDF 40 MB Posted

Attached to
Y1DA--VHA Minor Construction Project 562-184 Consolidate Primary Care - Erie VAMC
Solicitation number
36C77624R0007_1
Issued by

About this file

This document appears to be Attachment 5 - Drawings related to a federal contract opportunity for a Minor Construction Project (Solicitation Number 36C77624R0007_1) to consolidate and expand the primary care clinic at the Erie VAMC. The project involves constructing a new first-floor addition to the existing main building, including renovating existing clinical space to create an integrated, expanded primary care clinic. The project also includes constructing a partial basement to house mechanical equipment and utility closets, as well as reconfiguring the surrounding outdoor areas impacted by the building expansion. The contracting agency is the Department of Veterans Affairs Technology Acquisition Center in Austin.

View the file

Other files

File Type Posted
S06 - Amend 0007 - 36C77624R0007 0007.pdf PDF
S06 - Amend 0007 - Clause Changes.docx DOCX document
Amendment 0006 - 36C77624R0007 0006.docx DOCX document
Amendment 0006 - Addenda No 3 AHU 20240620.pdf PDF
Amendment 0006 - Att. 6 - VA.ERI - SSK-1.pdf PDF
Amendment 0006 - AE VA Responses Rev 6.21.2024.xlsx XLSX spreadsheet
Amendment 0005 - 36C77624R0007 0005.docx DOCX document
Amendment 0005 - AE VA Responses Rev 6.19.2024.xlsx XLSX spreadsheet
Amendment 0005 - dg_infrastruc_std_telecom_spaces.pdf PDF
Amendment 0005 - Att 11 - VA ERI - E-011A and E-211A Rev 6.18.11.pdf PDF
Amendment 0004 - Replace Legacy EPSS - Dwgs EP103 and EP104.pdf PDF
Amendment 0004 - AE VA Responses Rev 6.12.2024.xlsx XLSX spreadsheet
Amendment 0004 - 36C77624R0007 0004.docx DOCX document
Amendment 0004 - Drawing NC111c.2.pdf PDF
Amendment 0004 - Drawing NC111b.2.pdf PDF
Amendment 0004 - Nurse Call Riser.pdf PDF
Amendment 0003 - Drawings.zip ZIP file
Amendment 0003 - EXISTING ELEC_COMMS CLOSET PICS.zip ZIP file
Amendment 0003 - AE VA Responses 5.31.24.xlsx XLSX spreadsheet
Amendment 0003 - Pics Questions 86 and 89.zip ZIP file
Amendment 0003 - Specs.zip ZIP file
Amendment 0003 - RM WB-39 EXISTING MAIN TELECOM.zip ZIP file
Amendment 0003 - SQ. D SWITCHBOARD.zip ZIP file
Amendment 0003 - Pics Questions 123 and 124.zip ZIP file
Amendment 0003 - Supporting Attachments.zip ZIP file
Amendment 0003 - EATON LV SWITCHGEAR PICS.zip ZIP file
Amendment 0003 - 36C77624R0007 0003.docx DOCX document
Amendment 0003 - RM NB-59 LOC.zip ZIP file
Amendment 0002 - 36C77624R0007 0002 v2.docx DOCX document
Amendment 0002 - 36C77624R0007 0002.docx DOCX document
014530 Statement_of_Special_Inspections.pdf PDF
014535 SI Schedule.pdf PDF
Site Visit Sign-In Sheet 4-16-2024.pdf PDF
Revised E_S Sheets GK101 and GK102 3.18.2024.pdf PDF
Updated Geotech Report 40.1938r 06.22.2020.pdf PDF
Amendment 0001 36C77624R00007 0001.pdf PDF
Att. 4-Drawings 2-Erie, PA.pdf PDF
Att. 7-Brand Name Justifications_Redacted.pdf PDF
Att. 1-Specifications Volume 1-Erie, PA.pdf PDF
S02 - 36C77624R0007_1.docx DOCX document
Att. 2-Specifications Volume 2-Erie, PA.pdf PDF
Att. 6 - Wage Determination - Pulled 3.26.24.pdf PDF
Att. 3-Drawings 1-Erie, PA.pdf PDF
Show all 43

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

For the best experience, open this PDF portfolio in

Acrobat X or Adobe Reader X, or later.

Get Adobe Reader Now!

http://www.adobe.com/go/reader

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/2

-1

MEP ENGINEER:

BOWMAN FOSTER

6353 Center Drive Norfolk, VA 23502 757-466-7400

HEALTHCARE PLANNER:

EYP

811 West Hargett St.

Raleigh, NC 27603 713-852-3610

ARCHITECT:

CB DESIGN GROUP

421 King Street

SUITE 301

ALEXANDRIA, VA 22314

703-772-4213

PROFESSIONAL SEAL:

Erie VA Medical Center 135 East 38th Street, Erie, PA 16504

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

STRUCTURAL ENGINEER:

HUITT-ZOLLARS

500 W. 7th St., Ste. 300

Fort Worth, TX 76102

817-335-3000

FP/LS ENGINEER:

STANTON ENGINEERING

10280 Old Columbia Rd.

Ste. 275 Columbia, MD 21046 410-290-9304

CIVIL ENGINEER:

Integrity Federal Services 148 S. Queen Street Suite 201 Martinsburg, WV 25401 304-725-8456

03/07/2023

VA 562-184

CADRW

ERIE VAMC - CONSOLIDATED

PRIMARY CARE

CDF SUBMISSION

DETAILS

E-522

V

-5

.p d f

ROOM STATUS LIGHT POWER SUPPLY DETAILROOM STATUS LIGHT AND SWITCH DETAIL.

RECESSED LED SLOT LIGHT C G J P ROOM STATUS LIGHT FIXTURE & SWITCH IN ROOM

NO SCALE

CONTROL MODULE FOR ROOM STATUS LIGHTS

ROOF CONDUIT SUPPORT DETAILCONDUIT TRAPEZE MOUNTING DETAIL ROOF PENETRATION DETAIL POWER MANHOLE DETAILS

DUCT BANK DETAILS MANHOLE GROUNDING DETAILS RECEPTACLE ROOF MOUNTING DETAIL LUMINAIRE MOUNTING - LAY-IN CEILING

DOWNLIGHT MOUNTING - GYPBOARD CEILING DOWNLIGHT MOUNTING - LAY-IN CEILING EXIT SIGN MOUNTING - GYPBOARD CEILING EXIT SIGN MOUNTING - LAY-IN CEILING

LENGTH AS

REQUIRED

R

IE

S

5'-0"

[1930mm] 6'-4"

8" [1524mm] [203mm]

[2 m m

[1 m

[3 m

M

IN

m

[1524mm] 5'-0" m

"[2 m

[965mm][965mm] 3'-2"

[1930mm] 6'-4"

3'-2" m m m

3" [76mm] m m m m

[9 m

[915mm] 3'-0"

[7 m m

(T Y P m m m

[76mm][76mm] m m m

[152mm]

6"(NOTE

#4)

X

[3

[4

NO SCALENO SCALE NO SCALE NO SCALE

TOP VIEW

SECTION "A-A"

POWER

SECTION "B-B"

LO

P

SLO

PE

SLOPE

NO SCALE NO SCALE NO SCALE

SECTION "A-A"

ELEVATION

NO SCALE NO SCALE NO SCALE NO SCALE

CONDUIT CLAMP.

SIZE AS REQUIRED

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL

REFER TO PLANS

FOR QUANTITY &

SIZE OF CONDUITS

LOCKING

SQUARE WASHER

& LOCKNUT

3/8" MIN GALVANIZED

THREADED ROD, TYP.

UV-INHIBITED POLYCARBONATE

OR HIGH-DENSITY

POLYPROPYLENE PLASTIC

BLOCK, LENGTH AS REQUIRED

CONDUIT CLAMP.

SIZE AS REQUIRED

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

REFER TO PLANS FOR

QUANTITY & SIZE OF

CONDUITS

NOTES

1. METAL CHANNEL STRUT SUPPORT LONGER THAN THAN

36" SHALL BE INSTALLED WITH A CENTER SUPPORT ROD.

2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED

METHOD PER SPECIFICATION 26 0533, RACEWAYS AND

BOXES FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT

CONDITIONS.

3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER

TO SPECIFICATION SECTION 10 05 41, SEISMIC RESTRAINT

REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.

LOCKING SQUARE

WASHER & LOCKNUT

3/8" MIN GALVANIZED

THREADED ROD, TYP.

WASHER &

LOCKNUT

INTEGRAL

LIPPED STEEL

MOUNTING

GENERAL NOTES:

1. MAINTAIN A MINIMUM CLEARANCE OF 12" [308mm] ON ALL SIDES OF ROOF

PENETRATION FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE

PROPER FLASHING.

2. FLANGES OF ADJACENT FLASHINGS SHALL NOT BE CUT OR OVERLAPPED.

3. VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT.

4. COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR TO ENSURE

PROPER METHODS & MATERIALS ARE USED TO MAINTAIN ROOF WARRANTY.

PREFABRICATED RUBBER

BOOT CAP WITH GRADUATED

STEPS & WEATHER-PROOF

PRESSURE SEAL TO COLLAR

SEALANT AT PENETRATION

TO MEMBRANE JUNCTURE

BY ROOFING CONTRACTOR

MULTIPLE MEMBRANE STRIPPING

PLIES FEATHERED AT FIELD OF

ROOF BY ROOFING CONTRACTOR.

PRIME FLANGE BEFORE STRIPPING.

PREFABRICATED FORMED 0.06"

THICK ALUMINUM FLASHING

ROUND COLLAR WITH MIN. 3"

WIDE FLANGE. ATTACH TO ROOF

PER MANUFACTURER'S

INSTRUCTIONS

CONDUIT CLAMP. SIZE AS

REQUIRED

BATT INSULATION

ROOF MEMBRANE

WATER CUT-OFF

MASTIC COMPATIBLE

WITH ROOF MEMBRANE

STAINLESS CLAMP, TYP.

3/8" MIN

THREADED ROD,

TYP.

SEAL-OFF

FITTING,

ROOF

STEEL

EXPANSION

ANCHOR

INTEGRAL GALVANIZED

LIPPED STEEL

CONDUIT,

CONDUIT

CLAMP. SIZE

AS REQUIRED

LOCKING

SQUARE

WASHER &

LOCKNUT 12"x12" SUMP

[305x305mm]

FINISHED

GRADE

GROUND ROD

PER SECTION

26 05 26.

PULLING

IRON

CONC.

ENVELOPE

GROUND

ROD

SLEEVE

PULLING

IRON

CABLE STANCHION PER

SECTION 26 05 41.

12" [305mm] SUMP

SUMP FRAME &

COVER

GRADE RINGS AS REQ'D TO MATCH

CIVIL FINISHED GRADE ELEVATION.

CABLE STANCHION

1 CUBIC YARD

3/4" GRAVEL

SUMP.

GENERAL NOTES:

1. INCLUDE ALUMINUM LADDER

(NOT SHOWN FOR CLARITY)

PLASTIC

SPACER

INNERDUCT,

SEE NOTE 5

DUCT [SIZE

AS INDICATED

ON DWGS.]

6-WAY DUCT LINE 4-WAY DUCT LINE

2-WAY DUCT LINE

DUCT BANK NOTES:

1.

2.

3.

4.

5.

CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS, OR AS SPECIFIED.

PROVIDE REINFORCING RODS ON TOP AND BOTTOM OF DUCTS

WHEN CROSSING OR PLACED IN ROADWAYS.

MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 24" [610mm].

PROVIDE MINIMUM 6" [152mm] SPACE BETWEEN POWER AND

TELECOMMUNICATION DUCTS. INCREASE SIZE AS REQUIRED.

INNERDUCT QUANTITY AND SIZE AS INDICATED ON PLANS.

TIE WIRE

EQUIPMENT GROUND CONDUCTOR

MANHOLE COVER FRAME

GROUND CONNECTION

#6 STRANDED BARE CU

CABLE (TYP)

DUCT BANK

CABLE PULLING

IRONS

#3/0 STRANDED

BARE CU

COMPLETE RING.

EXOTHERMIC WELD

CONNECTION

GROUND ROD PER

SECTION 26 05 26

SUMP

FRAME

BRAIDED SHIELD

DRAIN WIRES (TYP)

EMBED CHANNEL

OR CABLE RACK

(TYP)

EXOTHERMIC

WELD

CABLE CLIP

DRILL AND

TAP GROUND

CABLE SPLICES CAST METAL

"WHILE-IN-USE"

WP COVER(S) &

RECEPTACLE(S).

CAST METAL, 2-GANG,

NEMA 3R JUNCTION BOX

WITH THREADED HUBS.

RIGID STEEL CONDUIT

FOR WIRING

FOR SUPPORT PER

N.E.C. ART. 314

ROOF PENETRATION

AND CONDUIT SUPPORT

PER SD260533-04

LUMINAIRE

SUSPENSION WIRES

(#10 MIN) ATTACHED

TO STRUCTURE

(TYP EA. CORNER)

3 TWIST MINIMUM

FIXTURE WHIP FROM

JUNCTION BOX

(6FT. LONG MAX.)

LUMINAIRE.

REFER TO

SCHEDULE

LUMINAIRE MANUFACTURER'S

EARTHQUAKE CLIP, (4) PER

FIXTURE AT CORNERS. ATTACH

WITH SHEET METAL SCREW

ACOUSTICAL CEILING

TILE (TYP)

ARCHITECTURAL

CEILING GRID

LUMINAIRE.

REFER TO

SCHEDULE

CEILING HANGER

WIRE, TYP.

RECESSED CAN

CEILING MAIN

BEAM

GYPSUM

BOARD (TYP)

WIRE TIE OR SCREW

BAR HANGER TO

CROSS BEAM TYP.

BAR HANGERS

12GA. HANGER WIRE AT DIAGONAL

CORNER ATTACHED TO STRUCTURE

CEILING

CROSS BEAM

CEILING BEAM

CEILING HANGER

WIRE, TYP.

WIRE TIE OR SCREW

BAR HANGER TO

CEILING GRID TYP.

BAR HANGERS

12GA. HANGER WIRE AT DIAGONAL

CORNER ATTACHED TO STRUCTURE

ACOUSTICAL

CEILING TILE (TYP)

ARCHITECUTRAL

CEILING HANGER WIRE

DRYWALL CEILING

CROSS TEE, TYP.

CEILING MAIN

BEAM.

DRYWALL CEILING

CROSS TEE, TYP.

GYPSUM

BOARD

WIRE TIE THROUGH

& CROSS BEAM, TYP.

#12 GA. HANGER WIRE THROUGH INTEGRAL

GALVANIZED LIPPED STEEL MOUNTING

CHANNEL & ATTACHED TO STRUCTURE

INTEGRAL GALVANIZED LIPPED

STEEL MOUNTING CHANNEL

WASHER & NUT

1/4" SCREW

CEILING HANGER WIRE

ACOUSTICAL

CEILING

TILE (TYP)

#12 GA. HANGER WIRE THROUGH INTEGRAL

GALVANIZED LIPPED STEEL MOUNTING

CHANNEL & ATTACHED TO STRUCTURE

INTEGRAL GALVANIZED LIPPED

STEEL MOUNTING CHANNEL

WASHER & NUT

1/4" SCREW

WIRE TIE THROUGH

& CROSS BEAM, TYP.

SUITE 301

Ste. 275

E-523

BOLLARD BASE DETAIL BOLLARD BASE DETAIL CONDUIT AND OUTLET SUPPORT IN METAL STUD WALL TYPICAL PANELBOARD SURFACE MOUNTED DETAIL SURFACE MOUNTED PANEL (TYP)

CONDUIT SUPPORT DETAIL FOR

VANDAL RESISTANT LIGHT

BOLLARD PER LIGHT FIXTURE

SCHEDULE.

PVC CONDUIT ADAPTER

COUPLING

PVC CONDUIT

FINISHED PAVING

GALVANIZED ANCHOR BOLTS &

HEX NUTS. PROVIDE LEVELING

SHIMS OR HEX NUTS.

[6

UNDISTURBED SOIL OR

SELECT BACKFILL

COMPACTED, SEE

NOTE BELOW.

CONCRETE BASE &

REINFORCING STEEL,

SEE NOTE BELOW.

NOTE:

BACKFILL, CONCRETE, REINFORCING STEEL, AND ANCHOR BOLTS ARE SHOWN FOR

REFERENCE ONLY. STRUCTURAL DESIGN IS SHOWN ON STRUCTURAL DRAWINGS.

(PAVED AREAS)

VANDAL RESISTANT LIGHT

BOLLARD PER LIGHT FIXTURE

SCHEDULE.

PVC CONDUIT ADAPTER

COUPLING

PVC CONDUIT

FINISHED GRADE

GALVANIZED ANCHOR BOLTS &

HEX NUTS. PROVIDE LEVELING

SHIMS OR HEX NUTS.

[6

UNDISTURBED SOIL OR

SELECT BACKFILL

COMPACTED, SEE

NOTE BELOW.

CONCRETE BASE &

REINFORCING STEEL,

SEE NOTE BELOW.

BACKFILL, CONCRETE, REINFORCING STEEL, AND ANCHOR BOLTS ARE SHOWN FOR

REFERENCE ONLY. STRUCTURAL DESIGN IS SHOWN ON STRUCTURAL DRAWINGS.

(TURF AREAS)

GALVINZED CONDUIT

SUPPORT

METAL STUD

SECURE TO CEILING

SLAB OR JOISTS

8-1/4" STEEL ANGLE

CONNECTORS

1-1/2" SQ, 12 GA

ELECTRO GALV STL

SECURE TO FLOOR

ELECTRIC CLOSET

FOR DRYWALL INSTALLATION FOR MASONRY WALL INSTALLATION

ELECTRIC CLOSET

PANEL

WIRE CLOSET WALL

SECURE TO FULL

WIDTH OF MASONRY

WALL

1-1/2" SQ, 12 GA

ELECTRO GALV STL

SINGLE CONDUIT

WITH SINGLE BOLT

PIPE STRAPS

36" MAX

SURFACE MOUNTED

36" MAX

1-1/2"x3/4" - 14 GA

NO SCALE NO SCALE NO SCALE NO SCALE NO SCALE

N

GROUNDING ELECTRODE

CONDUCTOR TO BLDG STEEL

EQUIPMENT GROUNDING

#1/0 AWG GND FOR TELECOMMUNICATION SYSTEM

WATER PIPE

#4/0 TO COLD

EGC

GROUND ROD / BUILDING

#4/0 BARE COPPER AWG TO

STEEL.

GROUND BUS

NEUTRAL BUS

TYPICAL

PANELBOARD

CONDUCTOR

PANELBOARD

MAIN BONDING

JUMPER

SECONDARY

PAD MOUNT XFMR

MAIN SWITCHBOARD DRY TYPE TRANSFORMER

TYPICAL STEP DOWN

GROUND BUS

GROUNDING DIAGRAM

SUITE 301

Ste. 275

E-524

A:

TOTAL

TOTAL CONNECTED AMPS B: C:

EXISTING PANELBOARD "PP12" SCHEDULE SEC. 1

CBA

WIRE

SIZE

CKT

NO

BRKR

TRIP

PHASE CKT

LOAD SERVED

1 2

3 4

5 6

7 8

9 10

11 12

13 14

15 16

17 18

19 20

21 22

23 24

25 26

27 28

29 30

31 32

33 34

35 36

37 38

39 40

* 41 42

20 *

LOAD (AMP)

B CA

B C

LIGHTING RMS 207-214

LIGHTING RMS 217-219

LIGHTING WAITING AREA 134

LTNG NEW BROOMS CHECK-IN

RECEPTACLES EXAM ROOM 12

ATRIUM RECEPTACLES

RECEPTACLES EXAM ROOM 16

RECEPTACLES EXAM ROOM 15

REC MED & PHARM RMS

RECEPTACLES EXAM ROOM 20

RECEPTACLES EXAM RM 25

RECEPTACLES EXAM RM

RECEPTACLE WATER FOUNTAIN

RECEPTACLES NEW RESTROOM

FLOOR REC ATRIUM WAITING

RECEPTACLES ATRIUM WAITING

ROOF TOP RECEPTACLES

RECEPTACLES ATRIUM WAITING

SPARE

EXTERIOR LIGHTING BOLLARDS

SENSOR SINKS/TOILET RMS E1-99

225A, MLO, 208Y/120V, 3 PHASE, 4 WIRE, 22 KAIC MIN, SURFACE MOUNT

CORRIDOR 206 & S LIGHTING

LIGHTING EXAM RMS 220-225

WAITING AREA 134 LIGHTING

EXT LIGHTING NEW ADDITION

EXAM ROOM 11 RECEPTACLES

LIGHTING CONTROL RELAY PANEL

CORRIDOR RECEPTACLES

COR. TELE, ELEC. HSEKPNG REC

EXAM ROOM 23 RECEPTACLES

EXAM ROOM 18 RECEPTACLES

EXAM ROOM RECEPTACLES

MINI FRIG MED RM RECEPTACLES

HALLWAY N1-189 RECEPTACLES

EXAM & STORAGE RM RECPT.

ATRIUM WAITING RECEPTACLES

ROOF TOP RECEPTACLES

SENOR SINKS RMS 190 & 191 REC

LIGHTING - PENDANTS IN ATRIUM

43 44

45 46

47 48

49 50

51 52

53 54

55 56

57 58

59 60

61 62

63 64

65 66

67 68

69 70

71 72

73 74

75 76

77 78

79 80

81 82

* 83 84

TRIP A

REC/COPIER/WAITING RM N1-

SENSOR SINKS/ TOILET RM N1-

MOTORIZED SHADES

REC WAITING RM N1-142

RECEPTACLES EXAM RM 14

PACS CONTROLLERS

LIGHTING WAITING RM N1-14

SENSOR SINKS/TOILET RM E1-

REC WAITING RM NA-142

RECEPTACLES EXAM RM 13

RECEPTACLES EXAM RM 22

RECEPTACLES EXAM RM 21

WAITING RM 1-142 DESK REC

RECEPTACLES CGW

PARTITION REC RM N1-142

CAMERA POWER SUPPLY

PARTITION REC RM N1-142

EXISTING PANELBOARD "PPM" SCHEDULE

39 40

* * 41 42

PUMP P-2

CABINET UNIT HEATER

POWER ROOF VENTILATOR PRV-1

ICI PANEL

RTU ENTRANCE VEST

ROOF TOP UNIT RTU-1

AIR FLOW MEASURING DEVICE

HEAT TRACE

SPACE

ERU-1 LIGHTS AND OUTLETS

225A, MLO, 208/120V, 3 PHASE, 4 WIRE, 22 KAIC MIN, SURFACE MOUNT

PUMP P-1

SSAHU-1

CABINET UNIT HEATER

VARIABLE VOLUME BOXES

POWER ROOF VENTILATOR PRV-1

ENERGY RECOVERY UNIT ERU-1

RTU-1 LIGHTS AND OUTLETS

CIRC PUMP AIR FLOW MEAS DEV

REST ROOM IN 103

20 20

EXISTING PANELBOARD "PP12" SCHEDULE SEC. 2

225A, MLO, 208Y/120V, 3 PHASE, 4 WIRE, 22 KAIC MIN, SURFACE MOUNT

RECEPTACLES EXAM RM 17

RECEPTACLES EXAM RM 19

RECEPTACLES EXAM RM 24

NURSE CALL POWER SUPPLY

NOTES: 1.

MANUFACTURER: GENERAL ELECTRIC (GE) A-SERIES II PANELBOARD CAT. AQF3422SB2.

MANUFACTURER: GENERAL ELECTRIC (GE) A-SERIES II PANELBOARD CAT. AQF3422SB2.

MANUFACTURER: GENERAL ELECTRIC (GE) A-SERIES II PANELBOARD CAT. AQF3422MB

( * ) INDICATES EXISTING LOAD OR CONDITION.

PANELBOARD "EMH1" SCHEDULE

301.3

PANEL "EMH2"225

4/0

P-3

P-4

16.4

322.6 287.3

800A, 800A M.C.B., 480Y/277V, 3 PHASE, 4 WIRE, 65 KAIC MIN, SURFACE MOUNT

31.2193.5

20.4169

-52.9

-27

3.41.6

3.44.8

-4.8

23.2278.1 38284.6 27.2260.1

PANEL "EML1" VIA 150KVA XFMR

AHU-1 (SUPPLY)

AHU-1 (RETURN)

EF-2

P-2

P-1

SPD/TVSS

NOTES: 1. PROVIDE ARC FLASH WARNING LABEL ON ALL PANELBOARDS.

40 - -

42 - -

PANELBOARD "EMH2" SCHEDULE

16.4

LIGHTS EXAM ROOM & WORK AREA20

LIGHTS RECEPTION AND WAITING

LIGHTS EXAM ROOM AND WORK AREA

6.7

31.2 22.2

100A, M.L.O., 480Y/277V, 3 PHASE, 4 WIRE, 35 KAIC MIN, SURFACE MOUNT

5.61.2

4.93

1.72.2

12.94.8

5.21.75

4.8-

6.7-

7.3-

13.23.2 25.26 17.44.75

ELEC, FCC, ELEVATOR RM LIGHTING

EXTERIOR POLE LIGHTING

320 12BASEMENT CORRIDOR LIGHTING

520 12MECHANICAL ROOM LIGHTING

LIGHTS EXAM ROOM AND WORK AREASPACE

SPACESPACE

LIGHTS MAIN LOBBYEXTERIOR BOLLARD LIGHTING

LIGHTS WAITING AREAFACADE LIGHTING

LIGHTS CORRIDORSSPACE

LIGHTS EXAM ROOM & WORK AREA

LIGHTS OFFICES AND CORRIDOR

SUITE 301

Ste. 275

SCHEDULES

E-620

-6

/1

PANELBOARD "EML1" SCHEDULE

426.7

WORK AREA20 12

EXAM RM. RECPTS.

PANEL "EML2"

PANEL "TPP1"

3/0

362 325.6

600A, 600A M.C.B., 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MIN, SURFACE MOUNT

7.5

154.5

165.5

156.6

142.6

23.6

370.756 38656 355.650

WORK AREA

320 12

520 12

20 1210

20 12

20 1210COPIER

FCC RECPT.

COPIER

PANEL "EML4"

3/0

PANELBOARD "EML2" SCHEDULE

20 12 41

161.2

COPIER20

PANEL "EML3"

171.6 137.2

200A, MAIN LUGS ONLY, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MIN, SURFACE MOUNT

-10

77.27.5

86.66

70.26

93.767.5 105.666 81.256

EXAM RECPTS.

320 12

VAV-1,2,3,4,20,21

VAV-5,6,9,17,18,19

EF-4

VAV-7,10,11,13,14,16

.46

PANELBOARD "TPP1" SCHEDULE

23.6

RACK RECPTS.20

100A, 80A M.C.B., 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MIN, SURFACE MOUNT

-1.6

1013.6 1010 1010

RECPTS.

IT ROOM LTG

320 12RACK RECPTS.

520 12RACK RECPTS.

SPARESPARE

RACK RECPTS.

RACK RECPTS.

CCTV CAMERA

PANELBOARD "EML4" SCHEDULE

RECPTS. RM. 1N2104

154.5

RECPTS. CORRIDOR20 12

RECPTS. BREAKROOM

RECPT. PROJECTOR SCREEN

RECPT. PROJECTOR

GFI RECPT. REFRIGERATOR

KIOSK RECPT.

RECPTION RECPTS.

PANEL "EML5"

4.5

159.5 161

200 M.L.O., 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MIN, SURFACE MOUNT

1.5

7.5-

7.56

1.56

83.56

857.5

11737.5 120.539 117.543.5

ELEC. RM. RECPT.

RECPTS. RM. 1N316

RECPTS. TEAM WORK AREA

RECPTS. CORRIDOR

320 -SPARE

20 12 12

RECPTS. RM. 1N314

RECPTS. RM. 1N312

RECPTS. RM. 1N310

RECPTS. RM. 1N308

RECPTS. RM. 1N306

RECPTS. RM. 1N304

RECPTS. RM. 1N302

RECPTS. RM. 1N300

RECPTS. RM. 1N215

RECPTS. RM. 1N213

RECPTS. RM. 1N211

RECPTS. RM. 1N209

RECPTS. RM. 1N207

RECPTS. RM. 1N205

RECPTS. RM. 1N201

RECPTS. RM. 1N203 & 1N201A

RECPTS. RM. 1N208

RECPTS. RM. 1N206

RECPTS. RM. 1N204

GFI RECPT. REFRIGERATOR

GFI RECPT.

GFI RECPT. MICROWAVE

GFI RECPT. COFFEE MAKER

GFI RECPT. COFFEE MAKER

PANELBOARD "EML5" SCHEDULE

20 12 41

83.5

RECPTS. RM. 1N40220

TELEVISION RECPT.

RECPTS.

THERMAL SCANNER

RECEPTION RECPTS.

RECPTS. VESTIBULE

RECPT. LOBBY

84 85

100A, MAIN LUGS ONLY, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MIN, SURFACE MOUNT

7.512

37.5

4.57.5

4.512

4.54.5

4.56

4.57.5

64.5

1.57.5

67.5

-7.5

37.5

4.59

3746.5 25.558.5 35.549.5

RECPT. WAITING

RECPT. WAITING

RECPTS. RM. 1N506 - 1N506A

RECPTS. RM. 1N508 - 1N508A

RECPTS. RM. 1N502 - 1N502A

RECPTS. RM. 1N504 - 1N504A

RECPTS. RM. 1N414

RECPTS. RM. 1N500, 1N500A, 1N007

WHEEL CHAIR SCALE - HEIGHT & WEIGHT STATION12 20

OFFICE RECPTS.

12 20

RECPTS. RM. 1N412

RECPTS. RM. 1N410

RECPTS. RM. 1N408

RECPTS. RM. 1N406

RECPTS. RM. 1N404

RECPTS. RM. 1N400, 1N005

RECPTS. RM. 1N602

RECPTS. RM. 1N313

RECPTS. RM. 1N311

RECPTS. RM. 1N309

RECPTS. RM. 1N307

RECPTS. RM. 1N305

RECPTS. RM. 1N303, 1N301A

RECPTS. RM. 1N301

TELEVISION RECPT.

PANELBOARD "EML3" SCHEDULE

TRIP A

100A, MAIN LUGS ONLY, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MIN, SURFACE MOUNT

17.1

17.1

MED. REFRIGERATOR

MSO-1

DOOR POWER

20 12EXAM RECPTS.

20 12EXAM RECPTS.

SLIDING DOORS

B.D PYXIS MED

B.D PYXIS MED

MSO-2

HOISTWAY LIGHTS, RECPT.

VAV-22

SHREDDER

7.2

BASEMENT CORRIDOR RECPT.

MECHANICAL ROOM RECPT.

EF-1

ELEV. ROOM RECPT.

ELEV. PIT RECPT. & LIGHTS

9.8

4.6

54.1 49 43.1 23.1 37.6 27.1

77.2 86.6 70.2

SP-1

EF-3

SCP-1

WHEEL CHAIR SCALE - HEIGHT & WEIGHT STATION

VAV-8,12,15

SUITE 301

Ste. 275

SCHEDULES

E-621

G EE

POWER RISER DIAGRAM

PENNELEC (LOCAL UTILITY)

12470V GREENWOOD SIDE

PENNELEC (LOCAL UTILITY)

12470V OLD FRENCH SIDE

(CURRENTLY SERVING VAMC)

POWER POLE AT

CORNER OF WEST

38TH STREET

MAIN B

GLENWOOD

FEED

(OPEN)

NOT

UTILIZED

XFMR T1A

FEEDER

2500 KVA XFMR

12470 - 480Y/277V, 3∅

IMP 5.76

3000A/3P

MCB

SQ. D SWITCHBOARD 2, 3000A,

3000A M.C.B., 480Y/277V, 3∅, 4W

400A/3P

800A/3P

ATS

400A/3P 2500A/3P

PANEL DPG-1

400A, 480Y/277V, 3∅, 4W

WESTSIDE OF SWITCHBOARD IN RM 200

MAIN ELEC. RM. OF HOSPITAL SERVING

AMBULATORY SIDE OF HOSPITAL

PARKING

GARAGE &

CLC BRKR

X-RAY

BREAKER

LAUNDRY

TIE

TIE BUS

TRANSITION

IN THE

REAR

AUXILLIARY

IN FRONT

XFMR T1B

FEEDER

MAIN A BRKR

OLD FRENCH

RD FEEDER

(CLOSED) BEING

USED TO

SERVE VAMC

METALCLAD SWITCHGEAR SERIES 5

RATED MAX VOLTAGE 15KV

IMPULSE WITHSTAND (BIL) 95KV, FREQUENCY 60HZ

CONT. CURRENT 1200A

MAX SHORT CKT. CURRENT 25 KA SYM.

NOTE; BOTH 12,470V SERVICES TERMINATE TO THE

EXISTING SQ. D SWITCHGEAR. ONLY THE OLD

FRENCH UTILITY IS CURRENTLY BEING USED

TO ENERGIZE BOTH SWBD1 & SWBD2

2500 KVA XFMR

12470 - 480Y/277V, 3∅

IMP 5.76

MCB

SQ. D SWITCHBOARD 1, 3000A,

3000A M.C.B., 480Y/277V, 3∅, 4W

PANEL DPG-2

450A, 480Y/277V, 3∅, 4W, 65 KAIC

300A/3P

100A/3P

60A/3P

125A/3P

PANEL MP1

125A/3P

ATS-ES-

SWGR

1200A/3P

(OPEN)

1200A/3P 1200A/3P 1200A/3P 80A/3P

100A/3P 2000A/3P

SPACE SPACE SPACE SPACE SPACE SPACE

XFMR-1LOAD BANK

/TEMP

GENERATOR

CAM LOK

(CABINET

OUTSIDE IN

BACK)

GENERATOR

WATER BLDG. PANEL "H1"

GENERATOR

EATON LV SWITCHGEAR

4000A, 480Y/277V, 3∅, 4W, 65 KAIC

AUTOMATIC TRANSFER SWITCH

ATS-ES-SWGR

PANEL P-ES-1 125A, 480Y/277V, 3∅,

4W

ATS-ES-

SWGR

1200A/3P 1200A/3P 1200A/3P 80A/3P

100A/3P 2000A/3P

PANEL "LH-1"

800A, 800A M.C.B., 480Y/277V, 3∅, 4W

PANEL "EMH1", ROOM BN110

800A, 800A M.C.B., 480Y/277V, 3∅, 4W

225A/3P

150 KVA XFMR

480 - 208Y/120V, 3∅

600A/3P MCB

PANEL "EML1", ROOM BN110

600A, 600A M.C.B., 208Y/120V, 3∅, 4W

200A/3P

PANEL "EML2", ROOM BN110

200A, MAIN LUGS ONLY, 208Y/120V, 3∅, 4W

ATS

800A AUTOMATIC TRANSFER SWITCH

ROOM BN110

200A/3P

PANEL "EML4", ROOM BN110

200A, MAIN LUGS ONLY, 208Y/120V, 3∅, 4W

CONNECT TO EXISTING

800A/3P CIRCUIT

PROVIDE A 800A/3P CIRCUIT

BREAKER TO SERVE THE NEW

800A ATS

PANEL "EML3", ROOM BN110

100A, MAIN LUGS ONLY, 208Y/120V, 3∅, 4W

PANEL "EMH2", ROOM BN110

100A, MAIN LUGS ONLY, 480Y/277V, 3∅, 4W

80A/3P

PANEL "TPP1", ROOM BN106

100A, 80A M.C.B., 208Y/120V, 3∅, 4W

PANEL "EML5", ROOM BN110

100A, MAIN LUGS ONLY, 208Y/120V, 3∅, 4W

NEW ELECTRICAL MANHOLE

PANEL "H1"

PANEL "H1"

M.C.B.

80A/3P MCB

NEW ELECTRICAL MANHOLE

SUITE 301

Ste. 275

POWER RISER DIAGRAM

E-622

1 1

1 1 1 1 1 1 1 1

SUITE 301

Ste. 275

TELECOMMUNICATIONS PLAN -

DEMOLITION

TD101

T

3/16" = 1' - 0" 0 5' 10' 20'

NORTH

NOTE: IF THIS DRAWING IS A REDUCTION

GRAPHIC SCALE MUST BE USED.

KEY PLAN

PLAN

TRUE

NOT TO SCALE

NIC

GENERAL NOTES

1. LIGHT LINEWEIGHT SYMBOLS INDICATE EXISTING DEVICES,

EQUIPMENT, CONDUIT, ETC. TO REMAIN. HEAVY LINEWEIGHT

SYMBOLS INDICATES NEW DEVICES, EQUIPMENT TO BE

SUPPLIED AND OR INSTALLED. HEAVY AND DASHED

LINEWEIGHT SYMBOLS INDICATE DEVICES, EQUIPMENT,

CONDUIT, ETC. TO BE REMOVED.

2. SEAL AND FIREPROOF ALL PENETRATIONS CREATED BY THE

REMOVAL OR INSTALLATION OF CONDUITS.

DEMOLITION NOTES

1. REMOVE EXISTING TELEPHONE AND DATA OUTLETS AND ALL

ASSOCIATED CONDUIT AND WIRING COMPLETE BACK TO

EXISTING TELECOMMUNICATIONS ROOM COMPLETE.

2. EXISTING ELECTRICAL ROOM. THE CONTRACTOR SHALL

COORDINATE THE REMOVAL OF THE LENEL SECURITY

EQUIPMENT IN THE EXISTING ELECTRICAL ROOM WITH THE

VAMC/GOVERNMENT AND TURN OVER ANY EQUIPMENT

REQUESTED BY THE VAMC. THE BOSCH INTRUSION PANEL

LOCATED IN THE EXISTING TELECOMMUNICATION ROOM

MUST REMAIN ACTIVE AS LONG AS THE ROOM IS

SUPPORTING THE NETWORK. THIS PANEL SERVES DOOR

THAT ARE BEING DEMOLISHED IN THE SCOPE OF WORK AND

ALSO DOORS OUTSIDE OF OUR AREA OF WORK.

3. EXISTING TELECOMMUNICATION ROOM. THE CONTRACTOR

SHALL COORDINATE THE REMOVAL OF ALL

TELECOMMUNICATIONS EQUIPMENT WITH THE

VAMC/GOVERNMENT AND TURN OVER ANY EQUIPMENT

REQUESTED BY THE VAMC.

4. EXISTING CCTV CAMERA TO REMAIN. CONTRACTOR MUST

MAINTAIN THE CONNECTIVITY OF THE CAMERA DURING THE

CONSTRUCTION PHASE OF THE PROJECT.

5. DISCONNECT EXISTING CCTV CAMERA AT LOCATION

INDICATED AND CLEAN AND STORE FOR REUSE. REMOVE

WIRING AND CONDUIT COMPLETE BACK TO SOURCE.

6. THE DOORS THAT ARE SERVED BY THE EXISTING BOSCH

PANEL ARE AS FOLLOWS: RED CLINIC 1W190 ENTRANCE,

WOMEN'S CLINIC 1W110, REP CLINIC REAR ENTRANCE,

WOMEN'S CLINIC REAR ENTRANCE, OIF EAST ENTRANCE,

RED CLINIC MED ROOM, WOMEN'S CLINIC MED ROOM,

PRIMARY CARE ADMIN 1N169-1. THE DOORS CONNECTIONS

WILL NEED TO BE TRANSFERED TO THE EQUIPMENT

MOUNTED IN THE ENGIEERING CLOSET BY THE ELEVATOR

LOBBY. TO PREVENT DISRUPTION TO THE HOSPITAL DURING

REGULAR HOURS, AFTER HOUR WORK WILL NEED TO BE

DONE. THIS INCLUDES OPENING CEILING TILES AND PULLING

THE WIRES TO THE DOORS OR WHERE POSSIBLE REUSING

THE EXISTING WIRING. ONCE THE WIRE IS TERMINATED AT

THE HEAD END EQUIPMENT, THE DOOR WILL NEED TO BE

CONVERTED TO THE NEW WIRE. THE CONTRACTOR MUST

COORDINATE THIS WORK WITH THE VAMC AND THEIR

SECURITY PROVIDER.

7. DISCONNECT AND REMOVE ALL ASSOCIATED CARD READER,

DOOR CONTACTS, AND SIREN CONNECTION WHEN THE DOOR

IS DEMOLISHED.

8. EXISTING DOUBLE DOORS TO REMAIN. REUSE EXISTING

CARD READER AND REWIRE FOR NEW SYSTEM.

3/16" = 1'-0"

TELECOMMUNICATIONS PLAN - DEMOLITION

0' 3/32"=1'-0"

40'20'10' 30'

CONSTRUCTION NOTES#

5.

6.

7.

LOCATION OF EXISTING TELEPHONE/VOICE TERMINAL CABINETS

FOR INCOMMING COPPER BACKBONE CABLING IN MECHANICAL

ROOM.

LOCATION OF EXISTING MAIN TELEPHONE ROOM FOR THE MAIN

HOSPITAL SERVICE ENTRANCE.

LOCATION OF EXISTING FIBER ROOM FOR THE MAIN HOSPITAL

SERVICE ENTRANCE.

400 PAIR COPPER BACKBONE IN A 4" CONDUIT FOR

CONNECTIVITY OF THE NEW IT ROOM BN106 VOICE TO THE MAIN

TELEPHONE ROOM WB-39 AND ONE SPARE 4" CONDUIT.

12 PAIR SINGLE MODE FIBER AND 12 PAIR MULTIMODE FIBER

FOR CONNECTIVITY OF THE NEW IT ROOM BN106 DATA TO THE

MAIN FIBER ROOM B13A.

THREE (3) 4" CONDUIT ROUTED THRU THE CRAWL SPACE

BETWEEN COLUMNS 5 & 6 FROM THE NEW IT ROOM BN106 AND

THE EXISTING LEVEL 00 OF THE MAIN HOSPITAL.

LIGHT LINEWEIGHT SYMBOLS INDICATE EXISTING DEVICES,

SYMBOLS INDICATES NEW DEVICES, EQUIPMENT TO BE

SUPPLIED AND OR INSTALLED. HEAVY AND DASHED

SEAL AND FIREPROOF ALL PENETRATIONS CREATED BY THE

ROUTE CONDUIT AS SHOWN ABOVE FINISHED CEILING TO THE

LOCATION INDICATED. THE CONTRACTOR MUST COORDINATE

THE CONDUIT ROUTING WITH ALL EXISTING UTILITIES ABOVE

THE FINISHED CEILING.

REFER TO DRAWINGS GC300, GC301 AND GC401 FOR PHASING WORK.

1 PAIR MULTIMODE FIBER IN 3/4"C FOR CONNECTION OF

"LENEL" ACCESS CONTROL ON NON-VA NETWORK.

F.E.C

WB-39

B13A

BN045

3/32" = 1'-0"

BASEMENT TELECOMMUNICATIONS PLAN - NEW WORK

EXISTING LEVEL

00 OF MAIN

HOSPITAL

NB-59

SUITE 301

Ste. 275

BASEMENT TELECOMMUNICATIONS

PLAN - NEW WORK

T-011A

-0

2 2

R R

R

9 (TYP)

K

K R

BMS

SUITE 301

Ste. 275

BASEMENT TELECOMMUNICATIONS

PLAN - NEW WORK

T-011B

-0

BASEMENT TELECOMMUNICATIONS ROOM PLAN - NEW WORK

CONSTRUCTION NOTES

1. PROVIDE A 24" WIDE X 6" DEEP CABLE RUNWAY/LADDER

TRAY AS INDICATED.

2. PROVIDE A 12" WIDE X 6" DEEP CABLE RUNWAY/LADDER

TRAY AS INDICATED.

3. TELEPHONE TERMINATION AREA FOR OUTSIDE PLANT

INCOMING CABLING.

4. SECURITY EQUIPMENT TERMINATION AREA.

5. 6" VERTICAL CABLE MANAGEMENT FOR 19" FLOOR MOUNTED

RACK.

6. 19" FLOOR MOUNTED (4) POST EQUIPMENT RACKS FOR

PATCH PANELS. COORDINATE WITH THE VAMC AS TO HOW

MANY WILL BE REQUIRED AS A MINIMUM.

7. PROVIDE A TGBB 4" X 12" X 1/4" COPPER GROUND BUS BAR

WITH #6 AWG INSULATED COPPER GROUND WIRE TO THE

BUILDING SERVICE. COORDINATE LOCATION OF GROUND BUS

BAR WITH LOCATION OF COMMUNICATIONS CABINET/RACKS.

8. PROVIDE 3/4" FIRE RETARDANT PLYWOOD ON ALL WALLS OF

SMALL IT (BN1D6) AND FCC (BN108). BOTTOM OF PLYWOOD

AT 6" AFF.

9. CCTV CAMERA.

10. NURSE CALL SYSTEM TERMINATION AREA.

11. THREE 4" CONDUIT STUBS INTO FCC ROOM ROUTED FROM

THE FIRST FLOOR CABLE TRAY SYSTEM THROUGH THE

CHASE.

12. PROVIDE SIX (6) 4" CONDUITS SLEEVES. GROUND EACH

SLEEVE TO THE TMGB USING #6 GREEN COPPER

CONDUCTORS.

13. PROVIDE THREE (3) 4" CONDUITS AND ROUTE THRU CRAWL

SPACE INTO EXISTING BASEMENT LEVEL OF MAIN HOSPITAL

TO THE LOCATION OF THE EXISTING TELEPHONE AND FIBER

ROOMS. SEE SHEET T-011A.

14. CARD READER.

15. PROVIDE ONE (1) 3/4" CONDUIT AND ROUTE THRU CRAWL

SPACE INTO EXISTING BASEMENT LEVEL OF MAIN HOSPITAL

TO THE LOCATION OF ROOM BN045 FOR THE "LENEL" SYSTEM

CONNECTION.

16. MOUNT BALANCE MAGNETIC SWITCH CONTACT AT FLOOR

LEVEL OF ROLL-UP DOOR. CONTACT WILL BE CONNECTED

TO THE BOSCH KEYPAD ON DOOR (BN114) TO THE

MECHANICAL ROOM.

SUPPLIED AND OR INSTALLED. HEAVY AND DASHED

3. REFER TO DRAWINGS GC300, GC301 AND GC401 FOR PHASING

OF WORK.

J J

J J J J J J J J

N N N N

NNNNN NN N

4 5

6 6

TEAMWORK ZONE

1N2.1

CONSULT/ EXAM

1N215

1N213

1N211

1N209

1N207

CONSULT

1N205

CONSULT

1N203

PATIENT TOILET

1N201A

PROCEDURE

1N201

PATIENT CORRIDOR

1N2

1N200

WHEEL CHAIRS

1N001C

1N204

1N206

1N208

1N210

1N1.1

CORRIDOR

1N1

STAFF TOILET

1N102

PC ASST. MANAGER

1N104A

BREAKROOM

1N106

8 (TYP.)

(1) 1"C

(1) 1.5"C

(1) 1.25"C

(1) 1"C

(2) 1.25"C

(1) 1.25"C(1) 1.5"C

11 11

8 (TYP)

8 (TYP)

PC MED. DIRECTOR

1N104C

PC MANAGER

1N104B

ADMIN. OFFICE

1N104

STAFF TOILET

1N102

SUITE 301

Ste. 275

TELECOMMUNICATIONS PLAN AREA

'A' - NEW WORK

T-111A

TELECOMMUNICATIONS PLAN AREA 'A' - NEW WORK

SUPPLIED AND OR INSTALLED. HEAVY AND DASHED

3. ALL DROPS WILL BE A MINIMUM OF 1" CONDUIT ROUTED BACK

TO THE LOCATION OF THE CABLE TRAY AND BONDED TO THE

CABLE TRAY.

4. ALL TELECOMMUNICATION CABLING MUST BE CAT6A F/UTP.

5. REFER TO DRAWINGS GC300, GC301 AND GC401 FOR PHASING

1. FLUSH FLOOR JUNCTION BOX FOR TELECOMMUNICATION

CABLING TO GREETER STATION. COORDINATE LOCATION

WITH GREETER STATION.

2. MOUNT TELECOMMUNICATION OUTLET DEVICES UNDER

COUNTERTOP OF GREETER STATION

3. LOCATION OF SELF CHECK-IN STATION. COORDINATE

MOUNTING HEIGHT OF TELECOMMUNICATION OUTLET WITH

CHECK-IN STATION REQUIREMENTS.

4. FLUSH FLOOR BOX FOR CONNECTION OF TWO TEAMWORK

STATION TELECOMMUNICATION SERVICES. COORDINATE

FLOOR BOX LOCATION WITH TEAMWORK STATION

5. FLUSH FLOOR BOX FOR CONNECTION OF FOUR TEAMWORK

FLOOR BOX LOCATION WITH TEAMWORK STATION.

6. FLUSH FLOOR BOX FOR CONNECTION OF THREE TEAMWORK

7. MOUNT COAXIAL OUTLET ROUGH-IN AT 60" AFF. COORDINATE

LOCATION WITH TELEVISION AND VAMC.

8. CCTV CAMERA..

9. COORDINATE MOUNTING OF DATA OUTLET WITH MOUNTING

HEIGHT OF TELEVISION. ROUTE CONDUIT DROP TO THE

LOCATION OF THE NEAREST CABLE TRAY.

10. MOUNT TELEPHONE OUTLET 48" AFF.

11. ROUTE CONDUIT DROP TO LOCATION OF COLUMN ABOVE

FINISHED CEILING AND DOWN COLUMN TO UNDER FLOOR.

12. PROVIDE A 24"W X 4"D BASKET TYPE CABLE TRAY.

13. PROVIDE A 6"W X 2"D BASKET TYPE CABLE TRAY.

14. PROVIDE A 18"W X 4"D BASKET TYPE CABLE TRAY.

15. EXISTING CCTV CAMERA TO REMAIN.

16. EMPTY 3/4" CONDUIT W/ PULLSTRING TO LOCATION OF NEW

CCTV CAMERA LOCATION FOR CONNECTIVITY TO EXISTING

CCTV HEADEND EQUIPMENT. FOR CONTINUATION, SEE

SHEET T-111B.

17. MOUNT TELE/DATA OUTLET 48" AFF FOR WALLDOC UNIT.

COORDINATE LOCATION WITH RECEPTACLE FOR POWER.

J J J J J J J J

N N N N N N N N N

NNNNNNN

N N N N N N N N

NJ

1 1 1

CORRIDOR

1N6

1N508A

CONSULT/ EXAM (W)

1N508

1N506

WOMEN'S HEALTH CORRIDOR

1N5

1N6.1

1N3.1

1N506A

1N504A

1N504

1N502

1N500A

1N500

TEMPORARY STORAGE

1N007

TOILET

1N005

1N400

1N402

1N404

1N406

1N408

1N410

1N412

1N414

1N309

1N311

1N307

1N305

1N313

MEDICATION ROOM

1N602

CONSULT/ EXAM (NEG)

1N303

PROCEDURE (NEG)

1N301

CONCOURSE

1N002

1N316

1N314 CONSULT/ EXAM

1N312

1N310

1N308

1N306

1N304

1N302

1N300

CLEAN ROOM

1N601

(1) 1.5"C (1) 1.5"C

(2) 1.5"C

(2) 1.5"C (2) 1.25"C

7 7 7 7

5 (TYP)

R BMS

1N6.3

SOILED ROOM

1N603

3 3

SUITE 301

Ste. 275

TELECOMMUNICATIONS PLAN AREA

'B' - NEW WORK

T-111B

/3

TELECOMMUNICATIONS PLAN AREA 'B' - NEW WORK

1. FLUSH FLOOR BOX FOR CONNECTION OF FOUR TEAMWORK

2. LOCATION OF COPIER MACHINE.

3. MOUNT TELE/DATA OUTLET 48" AFF. FOR WALL DOC UNIT.

COORDINATE LOCATION WITH RECEPTACLE FOR POWER.

4. PROVIDE SIX 4" CONDUITS THROUGH WALL INTO CHASE AND

ROUTE CONDUITS TO THE LOCATION OF THE

TELECOMMUNICATIONS ROOM AT THE BASEMENT LEVEL.

FIREPROOF CONDUIT PENETRATIONS TO MAINTAIN FIRE

RATING OF WALL.

5. CCTV CAMERA..

6. COORDINATE MOUNTING OF DATA AND CATV OUTLET WITH

MOUNTING HEIGHT OF TELEVISION.

7. ROUTE CONDUIT DROP TO LOCATION OF COLUMN ABOVE

FINISHED CEILING AND DOWN COLUMN TO UNDERFLOOR.

8. PROVIDE A 24"W X 4"D BASKET TYPE CABLE TRAY.

9. PROVIDE A 12"W X 4"D BASKET TYPE CABLE TRAY.

10. PROVIDE A 8"W X 2"D BASKET TYPE CABLE TRAY.

11. MOUNT CCTV CAMERA REMOVED DURING DEMOLITION

PHASE OF PROJECT AS LOCATION INDICATED. MOUNT AT

12'-0" AFG TO BOTTOM OF FIXTURE.

12. PROVIDE A 4" SQUARE JUNCTION BOX AND A 3/4" EMPTY

CONDUIT WITH PULLSTRING BACK TO LOCATION OF EXISTING

CCTV HEADEND EQUIPMENT. THE CONTRACTOR MUST

COORDINATE THE CONNECTIVITY OF THE CAMERA WITH THE

VAMC SECURITY PROVIDE FOR THEIR EXISTING EQUIPMENT.

SEE SHEET T-111A FOR CONTNUATION.

SUPPLIED AND OR INSTALLED. HEAVY AND DASHED

3. ALL DROPS WILL BE A MINIMUM OF 1" CONDUIT ROUTED BACK

TO THE LOCATION OF THE CABLE TRAY AND BONDED TO THE

CABLE TRAY.

4. ALL TELECOMMUNICATION CABLING MUST BE CAT6A F/UTP.

5. REFER TO DRAWINGS GC300, GC301 AND GC401 FOR PHASING

FOUR (4) CATEGORY 6A

8P8C OUTLETS ACTIVE

FOR TELEPHONY DATA

THROUGH-PENETRATION FIRESTOP DETAILS

FIRESTOPPING

WITH APPROVED

SEAL OPENING

CONDUIT

WALL

SLEEVE

SEALANT

FIRESTOPPING

WITH APPROVED

SEAL SPACE BETWEEN

SEALANT

SLEEVE AND CONDUIT

TELECOMMUNICATIONS GROUNDING BUSBAR DETAIL

BRACKETS AND ALL MOUNTING HARDWARE SHALL BE STAINLESS STEEL.

2" (8

PLACES)

.75"

NOTES:

.437" D

IA (36 PLACES)

COPPER BUSBAR

.25"

24"

.75"

4"

4" H

IGH IN

SULATOR

BRACKET

1"

DETAIL AND TRAPEZE SUPPORT

TYPICAL TELECOM/DATA OUTLET CONDUIT

FOR INSTALLATION WHERE ELECTRIC STRIKE IS REQUIRED, 1/2

INCH CONDUIT IS NEEDED.

ON DOORS THAT

REQUIRE IT)

FOR ELECTRIC

STRIKE ( )

MAGNETIC DOOR

SWITCH (BMS)

6"x6" JUNCTION BOX

ABOVE LAY-IN CEILING

FINISHED FLOOR

HINGE SIDE

GROUNDING BUSHING

WITH #6 AWG TO

CABLE BASKET

SUPPORT

FRAMING

TWO (2) 1" CONDUITS FROM THE 2-GANG

OUTLET BOX OUT TO CORRIDOR CABLE TRAY.

PROVIDE SINGLE 1" EMT OUT TO CABLE

TRAY FROM VOICE ONLY OUTLETS

DOOR SECURITY ROUGH-IN DETAIL

OUTLET DETAIL

RACK POWER STRIP DETAIL

INSULATORS SHALL BE FIBERGLASS-REINFORCED THERMOSET.

OUTLET

(TYP.)

CONTROL TRANSFORMER

110/120V POWER

REQUEST TO EXIT

MOTION (REX)

(LOCATED ON OPPOSITE

SIDE OF DOOR)

SECURITY/ACCESS

KEYPAD OR EXIT

READER

BOSCH INTRUSION

KEYPAD (ONLY

21A-07A-21B

WHITE

PHONE 2

DATA 2

RED

GRAY BLUE

PHONE 1

DATA 1

21C-07A-21D

SUITE 301

Ste. 275

T-520

N N N N N N N N N N N N N N N N N N N N N

N N N N N N N N N N N N N N N N N N N N

N N N N N N N N N N N N N N N N N N N N N

N N N N N N N N N N N N N N N N N N N N

REMARKSDESCRIPTION

NEW

CABLE

IDENTIFICATION

CAT6A CABLING BACK TO TELECOM CABINET/NETWORK EQUIPMENT VIA CABLE TRAY

400 PR COPPER BACKBONE CABLING ROUTED IN 4" CONDUIT TO ROOM NB-59 TO TERMINATE TO EXISTING TELECOM INFRASTRUCTURE WHICH TIES BACK TO ROOM WB-39 MAIN TELEPHONE ROOM

12 PR. SM FIBER CABLE AND 12 PR. MM FIBER CABLE

TELECOMMUNICATIONS RISER DIAGRAM CABLE SCHEDULE

CABLING ROUTED IN 4" CONDUIT TO ROOM B13A FIBER ROOM

CABLING FOR VOICE ROUTED TO NETWORK EQUIPMENT IN IT ROOM BN106

CABLING FOR DATA ROUTED TO NETWORK EQUIPMENT IN IT ROOM BN106

CAT6A

CAT6A

TELECOMMUNICATIONS RISER DIAGRAM

DATA TELE

BASEMENT FLOOR TELECOMM RM

NETWORK

EQUIPMENT

ROOM STATUS LIGHT DIAGRAM

1ST FLOOR

CABLE TRAY

1N104

AREA "B" (T-111B)

AREA "A" (T-111A)

BASEMENT

1N104A

1N104B

1N104C

1N1.1

1N210

1N204

1N106

1N001C

1N001

1N2.1

1N314

1N311 1N309

1N301 1N3.1

1N6.1 1N414

1N002

1N007

1N6.3

1N210 1N208 1N206 1N204 1N215 1N213 1N211 1N209 1N207 1N205 1N203 1N201 1N316 1N314 1N312 1N310 1N308 1N306 1N304 1N302 1N300

1N313 1N311 1N309 1N307 1N305 1N303 1N301 1N414 1N412 1N410 1N408 1N406 1N404 1N402 1N400 1N508 1N506 1N504 1N502 1N500

SWITCHES SHALL BE INSTALLED WITHIN EXAM

ROOM. EACH SWITCH SHALL CONTROL ONE

OF THE THREE LAMPS IN THE DOME LIGHT

OUTSIDE THE EXAM ROOM

NOTES:

1. ALL WIRING SHOWN SHALL BE AS PER MANUFACTURERS RECOMMENDATIONS. FOR BIDDING PURPOSES, ASSUME EACH CABLE SHOWN SHALL BE 2 #16 IN 3/4"C.

EXAM

ROOM

THREE LAMP DOME LIGHT

OUTSIDE EXAM ROOM

12 OR 24 VDC

POWER SOURCE

MTD IN IT RM.

BN106

SWITCHES SHALL BE INSTALLED WITHIN EXAM

ROOM. EACH SWITCH SHALL CONTROL ONE

OF THE THREE LAMPS IN THE DOME LIGHT

OUTSIDE THE EXAM ROOM

12 OR 24 VDC

POWER SOURCE

MTD IN IT RM.

CONTROL

MODULE

CONTROL

MODULE

NURSE CALL BUTTON (TYP.)

THREE LAMP DOME LIGHT

OUTSIDE EXAM ROOM

NURSE CALL BUTTON (TYP.)

SUITE 301

Ste. 275

DIAGRAMS

T-601

R R R R

R R

R K

R K

BMSBMS

BMSBMS BMS BMS

BMS BMS

NETWORK

EQUIPMENT

SECURITY DIAGRAM

SECURITY

AREA "B" (T-111B)

AREA "A" (T-111A)

BASEMENT

CABLING FOR

SECURITY DEVICES

CABLING FOR

SECURITY DEVICES

1 DURESS/PANIC ACTIVATION WILL BE VIA COMPUTER IN EACH EXAM ROOM.

DOOR

1N1 1N210

E-1N601A 1N204

1N2A

1N2

1N001

E-1N601B

1N314

1N21

1N3

1N301

1N309

1N311

1N3A

E-1N601C

1N414

1N3.1

1N4

1N4A

1N5A

1N51N002A1N002A

1N002A

EBN116A

EBN116

S-2A

BN114

BN108

BN114

SUITE 301

Ste. 275

DIAGRAM

T-602

ELECTRICAL

E-522 - DETAILS

E-523 - DETAILS

E-524 - DETAILS

E-620 - SCHEDULES

E-621 - SCHEDULES

E-622 - POWER RISER DIAGRAM

TELECOMMUNICATIONS

TD101 - TELECOMMUNICATIONS PLAN - DEMOLITION

T-011A - BASEMENT TELECOMMUNICATIONS PLAN - NEW WORK

T-011B - BASEMENT TELECOMMUNICATIONS PLAN - NEW WORK

T-111A - TELECOMMUNICATIONS PLAN AREA 'A' - NEW WORK

T-111B - TELECOMMUNICATIONS PLAN AREA 'B' - NEW WORK

T-520 - DETAILS

T-601 - DIAGRAMS

T-602 - DIAGRAM

E-18E-18

E-17E-17

E-16

E-J.2

E-OO

G G

N N

12'-6"

L

(E) W27X84

W

X26

X

27'-7 3/4"

27'-7 3/4"

W12X26

AA

W14 CANTILEVER OVER HSS12X12

W12 CANTILEVER OVER HSS10X10

W8X10

W8X18

W8X18

12'-6" 1'-9 7/16" 4'-0" 2'-4" 10'-4 5/16" 1'-8 15/16" 13'-3 9/16" 4'-0 1/16"

2'-0"

10' - 3 5/16" 11 1/4"4' - 4 3/16" 4' - 4 3/16" 4' - 2 7/8" 4' - 2 7/8" 4' - 2 7/8" 5' - 0 3/16" 5' - 0 3/16" 4' - 5"

7 1/8"

1' - 8 5/8"

X6X 1/

S

8X

6X 5/

10X

10X 1/4

HSS10X10X1/4

H16 S562

E-4

E16 S561

A5

A16

H7

H4

3' - 0 7/8"

W14X30

IG

O

O

LO

/S

L=

'-7

T/STL=27'-0"

T/STL=28'-0 3/4"

E4

C12

T/STL=28'-0 3/4"

C8

C5

A12

A8

A4

8X

4X

JOIST BRIDGING

"H H

E-3.8

E-3.1

E-2.5

E-2.1

RADIUS = 87'-0"

RADIUS = 91'-9 1/4"

H9 S563

I I

LL

MM

T/STL-27'-7 3/4"

C10

C7

C4

PHASE 1A CONSTRUCTION

A10

1. SEE S001 FOR GENERAL NOTES.

2. SEE S002 FOR SPECIAL INSPECTION REQUIREMENTS.

3. SEE S003 FOR COMPONENTS AND CLADDING WIND LOADS.

4. FINISH FLOOR ELEVATION 0'-0" EQUALS TRUE ELEVATION 846.61 FT. T/STL IS 28'-0 3/4" UNO, WITH ADJUSTMENTS MADE FOR JOISTS BEARING ON BEAMS AS SHOWN ON PLAN.

5. JOIST SEATS ARE 5" DEEP.

6. GRIDS LOCATED AT CENTERLINE OF COLUMN, UNO.

7. SEE S602 FOR STEEL BEAM CONNECTION SCHEDULES.

8. SEE GENERAL NOTES FOR SLAB ON DECK INFORMATION.

9. SEE GENERAL NOTES FOR ROOF DECK INFORMATION.

10. ALL HANGERS, FASTENERS, AND METAL CONNECTORS IN CONTACT WITH TREATED

LUMBER, CONCRETE, OR EXPOSED TO WEATHER SHALL HAVE AT A MINIMUM G185 ZINC

COATING (E.G. SIMPSON ZMAX COATING) AND BE PAINTED WITH LATEX PAINT.

11. GC RESPONSIBLE TO FIELD VERIFY ALL EXISTING DIMENSIONS, ELEVATIONS AND SITE

CONDITIONS.

12. COORDINATE WALL AND SLAB OPENINGS WITH ARCHITECTURAL, MECHANICAL,

ELECTRICAL, AND PLUMBING DRAWINGS.

13. SEE H12/S561 FOR TYPICAL OPENING IN ROOF FRAMING DETAIL.

PLAN NOTES

NOTE DESCRIPTION

SUITE 301

Ste. 275

BTEWAW

HIGH ROOF FRAMING PLAN - PHASE

1B

S104-1B

HIGH ROOF FRAMING PLAN - PHASE 1B (T/STL = 28'-0 3/4" UNO)

3/7/23

W10X12

HSS6X3X1/4 HSS6X3X1/4 W10X12

7' - 4 1/8"4' - 6 3/8"1' - 11 5/8"5' - 1"2' - 3 1/8"

S502

S201

G7

D7

HSS6X4X1/4

5.5 5.6 5.7 6.5 6.6

7' - 4 1/8"4' - 6 3/8"1' - 11 5/8"5' - 1"2' - 3 1/8"

X

4 H

3X

HSS6X3X1/4

0" 8' - 11 3/4"

G4

8' - 11 3/4"

HSS6X3X1/4

4 H

8' - 11 3/4" 0"

8' - 11 3/4"

F D CEG

HSS6X6X1/4

HSS6X6X1/4 HSS6X4X1/4

20' - 8 3/16" 31' - 10" 11' - 7" 19' - 5" 7' - 8"

HSS COLUMN, SEE PLAN

HSS BRACE, SEE ELEVATION

WORKPOINT

3/8" GUSSET PLATE

TYP

3/16

ROOF BEAM, SEE PLAN

TYP SHEAR CONNECTION

HSS BEAM, SEE ELEVATION

HSS BRACE, SEE ELEVATION

STAIR LANDING BEAM,

SEE PLAN

TYP SHEAR CONNECTION

3/8" KNIFE PLATE THROUGH

CONTINUOUS BRACE

6"

EACH FACE

SUITE 301

Ste. 275

ELEVATIONS

1/4" = 1'-0"

STAIR ELEVATION

F16

F12

F9

TRUSS ELEVATION

1" = 1'-0"

DETAIL

D7

3/4" = 1'-0"

4 6 85 75.5 5.6 5.7 6.5 6.6 99.1

8' - 0" 1' - 4 3/4"

4' - 3" 4' - 4"

2' - 3 1/8"

6' - 4" 3' - 3 3/8" 3' - 4"

S202

OPENING IN CONCRETE WALL

2-#5 x 4'-0" @ EACH CORNER

2-#5 @ EACH SIDE OF OPENING

1 1/2" CLR

#3 STIRRUPS @ 8" OC

4-#5 BARS

1' - 0"

IE

SUITE 301

Ste. 275

ELEVATIONS

BASEMENT WALL ELEVATION

G16

3/4" = 1'-0"

TYP OPENING IN CONCRETE WALL DETAIL

G6

3" = 1'-0"

SECTION

2 3

F F

D D

C C

E E

E-20E-20

BB

18'-10" 20'-10" 20'-7" 20'-10" 19'-6" 12'-6" 12'-6" 1'-9 7/16" 6'-4"

5'-7 3/8"

24' - 0"

9' - 4 3/4" 9' - 5 5/8"

9' - 0 3/8" 11' - 5 3/4"

1' - 0" 1' - 6"

3' - 4" 8' - 2 1/8"

1' - 11 15/16"

6" 6"14' - 8" 3' - 4"

1' - 6"

1. S400 SHEETS ARE FOR SLAB DIMENSIONS ONLY.

2. DIMENSIONS SHOWN FOR ROOF DECK ARE TO EDGE OF ANGLE OR PLATE.

3. VERIFY OPENINGS WITH MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS.

SUITE 301

Ste. 275

AuthorChecker

BASEMENT SLAB PLAN

S401-1A

1/8" = 1'-0"

BASEMENT FOUNDATION / SLAB PLAN

1 2 3 4 6 85

E-19

E-X1 E-X6E-X5 E-LL E-MM E-NN E-OO

E-2.5E-2.1

1'-2 3/8" 18'-10" 20'-10" 20'-7" 20'-10" 19'-6" 12'-6" 12'-6" 1'-11 15/16"

18'-10" 20'-10" 20'-7" 20'-10" 19'-6" 12'-6" 12'-6"

1'-0" 4'-7 3/8"

BP1

9' - 4 3/4" 9' - 5 5/8"

BP2

SIDEWALK, REFER TO CIVIL

0'-5 1/2" 2'-5 1/2" 9'-1 5/8"

3' - 4" 8' - 1 1/2"

1' - 2 3/8"

1' - 11 3/4"

8"

1' - 5 15/16" 6" 8"

SUITE 301

Ste. 275

1ST FLOOR SLAB PLAN - PHASE 1A

S402-1A

1ST FLOOR FOUNDATION / SLAB AND FLOOR FRAMING PLAN - PHASE 1A

C1

C2

C3

C5

C6

CA CB CC CD CF CG

J J

CH CJ

C7

C8

E-5

E-5

H H

K K

119 9.1

1'-0 7/8" 2'-0" 7'-6 3/4" 2'-11 1/4"

1'-9 7/16"

0'-6 9/16"

3'-5 7/16" 2'-4"

2'-5 1/16"

2'-7 1/2" 3'-5" 1'-10 3/4"

1'-8 15/16" 0'-10"

5'-5" 6'-3 7/16" 0'-9 1/8" 4'-0 1/16" 2'-3 5/8" 2'-7 3/8" 3'-9 7/8"

.4

.8

.2

.6

.1

.0

.0

.5

7 1/2"

41'-11 7/8"

11 3/16"

1' - 5 3/8"

SUITE 301

Ste. 275

1ST FLOOR SLAB PLAN - PHASE 1B

S402-1B

1ST FLOOR FOUNDATION / SLAB AND FLOOR FRAMING PLAN - PHASE 1B Copy 1

1 2 3 4 6 85

E-X1 E-X6E-X5 E-LL E-MM E-NN E-OO

18'-10" 20'-10" 20'-7" 20'-10" 10'-2 1/4" 2'-3 1/8" 5'-1" 1'-11 5/8"

4'-6 3/8"

7'-4 1/8"

0'-7 1/2"

7"

3' - 4" 8' - 1 1/2"

6 3/4"

ROOF DRAIN OPENINGS

SUITE 301

Ste. 275

2ND FLOOR SLAB PLAN - PHASE 1A

S403-1A

ROOF/FUTURE SECOND FLOOR FRAMING PLAN (T/STL=13'-2 3/4" UNO)

4 6 85

5.5 5.6 5.7 6.5 6.6 9

20'-10" 10'-2 1/4" 2'-3 1/8" 5'-1"

1'-11 5/8"

4'-6 3/8" 7'-4 1/8"

0'-7 1/2"

1'-9 7/16"

EDGE OF ROOF DECK AT CENTLINE OF BEAMS

1' - 4 3/4"

4' - 0"

4' - 0"

SUITE 301

Ste. 275

HIGH ROOF DECK PLAN-PHASE 1A

S404-1A

HIGH ROOF FRAMING PLAN (T/STL=28'-0 3/4" UNO)

E-18E-18

E-17E-17

E-16

E-J.2

N N

H H

I I

12'-6" 1'-9 7/16" 4'-0" 2'-4" 10'-4 5/16" 1'-8 15/16" 13'-3 9/16" 4'-0 1/16"

11 1/4" 1' - 8 5/8"

3' - 0 7/8"

1' - 8 5/8"

5' - 0 1/4"

1' - 0 3/4"

2' - 1"

11"

1' - 11 3/4"

5' - 0 1/4"

Dr

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .