Att. 5-Drawings 3-Erie, PA.pdf
PDF 40 MB Posted
- Solicitation number
- 36C77624R0007_1
About this file
This document appears to be Attachment 5 - Drawings related to a federal contract opportunity for a Minor Construction Project (Solicitation Number 36C77624R0007_1) to consolidate and expand the primary care clinic at the Erie VAMC. The project involves constructing a new first-floor addition to the existing main building, including renovating existing clinical space to create an integrated, expanded primary care clinic. The project also includes constructing a partial basement to house mechanical equipment and utility closets, as well as reconfiguring the surrounding outdoor areas impacted by the building expansion. The contracting agency is the Department of Veterans Affairs Technology Acquisition Center in Austin.
View the file
Other files
Show all 43
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/2
-1
MEP ENGINEER:
BOWMAN FOSTER
6353 Center Drive Norfolk, VA 23502 757-466-7400
HEALTHCARE PLANNER:
EYP
811 West Hargett St.
Raleigh, NC 27603 713-852-3610
ARCHITECT:
CB DESIGN GROUP
421 King Street
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
Erie VA Medical Center 135 East 38th Street, Erie, PA 16504
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
STRUCTURAL ENGINEER:
HUITT-ZOLLARS
500 W. 7th St., Ste. 300
Fort Worth, TX 76102
817-335-3000
FP/LS ENGINEER:
STANTON ENGINEERING
10280 Old Columbia Rd.
Ste. 275 Columbia, MD 21046 410-290-9304
CIVIL ENGINEER:
Integrity Federal Services 148 S. Queen Street Suite 201 Martinsburg, WV 25401 304-725-8456
03/07/2023
VA 562-184
CADRW
ERIE VAMC - CONSOLIDATED
PRIMARY CARE
CDF SUBMISSION
DETAILS
E-522
V
-5
.p d f
ROOM STATUS LIGHT POWER SUPPLY DETAILROOM STATUS LIGHT AND SWITCH DETAIL.
RECESSED LED SLOT LIGHT C G J P ROOM STATUS LIGHT FIXTURE & SWITCH IN ROOM
NO SCALE
CONTROL MODULE FOR ROOM STATUS LIGHTS
ROOF CONDUIT SUPPORT DETAILCONDUIT TRAPEZE MOUNTING DETAIL ROOF PENETRATION DETAIL POWER MANHOLE DETAILS
DUCT BANK DETAILS MANHOLE GROUNDING DETAILS RECEPTACLE ROOF MOUNTING DETAIL LUMINAIRE MOUNTING - LAY-IN CEILING
DOWNLIGHT MOUNTING - GYPBOARD CEILING DOWNLIGHT MOUNTING - LAY-IN CEILING EXIT SIGN MOUNTING - GYPBOARD CEILING EXIT SIGN MOUNTING - LAY-IN CEILING
LENGTH AS
REQUIRED
R
IE
S
5'-0"
[1930mm] 6'-4"
8" [1524mm] [203mm]
[2 m m
[1 m
[3 m
M
IN
m
[1524mm] 5'-0" m
"[2 m
[965mm][965mm] 3'-2"
[1930mm] 6'-4"
3'-2" m m m
3" [76mm] m m m m
[9 m
[915mm] 3'-0"
[7 m m
(T Y P m m m
[76mm][76mm] m m m
[152mm]
6"(NOTE
#4)
X
[3
[4
NO SCALENO SCALE NO SCALE NO SCALE
TOP VIEW
SECTION "A-A"
POWER
SECTION "B-B"
LO
P
SLO
PE
SLOPE
NO SCALE NO SCALE NO SCALE
SECTION "A-A"
ELEVATION
NO SCALE NO SCALE NO SCALE NO SCALE
CONDUIT CLAMP.
SIZE AS REQUIRED
INTEGRAL GALVANIZED
LIPPED STEEL
MOUNTING CHANNEL
REFER TO PLANS
FOR QUANTITY &
SIZE OF CONDUITS
LOCKING
SQUARE WASHER
& LOCKNUT
3/8" MIN GALVANIZED
THREADED ROD, TYP.
UV-INHIBITED POLYCARBONATE
OR HIGH-DENSITY
POLYPROPYLENE PLASTIC
BLOCK, LENGTH AS REQUIRED
CONDUIT CLAMP.
SIZE AS REQUIRED
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
REFER TO PLANS FOR
QUANTITY & SIZE OF
CONDUITS
NOTES
1. METAL CHANNEL STRUT SUPPORT LONGER THAN THAN
36" SHALL BE INSTALLED WITH A CENTER SUPPORT ROD.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED
METHOD PER SPECIFICATION 26 0533, RACEWAYS AND
BOXES FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT
CONDITIONS.
3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER
TO SPECIFICATION SECTION 10 05 41, SEISMIC RESTRAINT
REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.
LOCKING SQUARE
WASHER & LOCKNUT
3/8" MIN GALVANIZED
THREADED ROD, TYP.
WASHER &
LOCKNUT
INTEGRAL
LIPPED STEEL
MOUNTING
GENERAL NOTES:
1. MAINTAIN A MINIMUM CLEARANCE OF 12" [308mm] ON ALL SIDES OF ROOF
PENETRATION FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE
PROPER FLASHING.
2. FLANGES OF ADJACENT FLASHINGS SHALL NOT BE CUT OR OVERLAPPED.
3. VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT.
4. COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR TO ENSURE
PROPER METHODS & MATERIALS ARE USED TO MAINTAIN ROOF WARRANTY.
PREFABRICATED RUBBER
BOOT CAP WITH GRADUATED
STEPS & WEATHER-PROOF
PRESSURE SEAL TO COLLAR
SEALANT AT PENETRATION
TO MEMBRANE JUNCTURE
BY ROOFING CONTRACTOR
MULTIPLE MEMBRANE STRIPPING
PLIES FEATHERED AT FIELD OF
ROOF BY ROOFING CONTRACTOR.
PRIME FLANGE BEFORE STRIPPING.
PREFABRICATED FORMED 0.06"
THICK ALUMINUM FLASHING
ROUND COLLAR WITH MIN. 3"
WIDE FLANGE. ATTACH TO ROOF
PER MANUFACTURER'S
INSTRUCTIONS
CONDUIT CLAMP. SIZE AS
REQUIRED
BATT INSULATION
ROOF MEMBRANE
WATER CUT-OFF
MASTIC COMPATIBLE
WITH ROOF MEMBRANE
STAINLESS CLAMP, TYP.
3/8" MIN
THREADED ROD,
TYP.
SEAL-OFF
FITTING,
ROOF
STEEL
EXPANSION
ANCHOR
INTEGRAL GALVANIZED
LIPPED STEEL
CONDUIT,
CONDUIT
CLAMP. SIZE
AS REQUIRED
LOCKING
SQUARE
WASHER &
LOCKNUT 12"x12" SUMP
[305x305mm]
FINISHED
GRADE
GROUND ROD
PER SECTION
26 05 26.
PULLING
IRON
CONC.
ENVELOPE
GROUND
ROD
SLEEVE
PULLING
IRON
CABLE STANCHION PER
SECTION 26 05 41.
12" [305mm] SUMP
SUMP FRAME &
COVER
GRADE RINGS AS REQ'D TO MATCH
CIVIL FINISHED GRADE ELEVATION.
CABLE STANCHION
1 CUBIC YARD
3/4" GRAVEL
SUMP.
GENERAL NOTES:
1. INCLUDE ALUMINUM LADDER
(NOT SHOWN FOR CLARITY)
PLASTIC
SPACER
INNERDUCT,
SEE NOTE 5
DUCT [SIZE
AS INDICATED
ON DWGS.]
6-WAY DUCT LINE 4-WAY DUCT LINE
2-WAY DUCT LINE
DUCT BANK NOTES:
1.
2.
3.
4.
5.
CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS, OR AS SPECIFIED.
PROVIDE REINFORCING RODS ON TOP AND BOTTOM OF DUCTS
WHEN CROSSING OR PLACED IN ROADWAYS.
MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 24" [610mm].
PROVIDE MINIMUM 6" [152mm] SPACE BETWEEN POWER AND
TELECOMMUNICATION DUCTS. INCREASE SIZE AS REQUIRED.
INNERDUCT QUANTITY AND SIZE AS INDICATED ON PLANS.
TIE WIRE
EQUIPMENT GROUND CONDUCTOR
MANHOLE COVER FRAME
GROUND CONNECTION
#6 STRANDED BARE CU
CABLE (TYP)
DUCT BANK
CABLE PULLING
IRONS
#3/0 STRANDED
BARE CU
COMPLETE RING.
EXOTHERMIC WELD
CONNECTION
GROUND ROD PER
SECTION 26 05 26
SUMP
FRAME
BRAIDED SHIELD
DRAIN WIRES (TYP)
EMBED CHANNEL
OR CABLE RACK
(TYP)
EXOTHERMIC
WELD
CABLE CLIP
DRILL AND
TAP GROUND
CABLE SPLICES CAST METAL
"WHILE-IN-USE"
WP COVER(S) &
RECEPTACLE(S).
CAST METAL, 2-GANG,
NEMA 3R JUNCTION BOX
WITH THREADED HUBS.
RIGID STEEL CONDUIT
FOR WIRING
FOR SUPPORT PER
N.E.C. ART. 314
ROOF PENETRATION
AND CONDUIT SUPPORT
PER SD260533-04
LUMINAIRE
SUSPENSION WIRES
(#10 MIN) ATTACHED
TO STRUCTURE
(TYP EA. CORNER)
3 TWIST MINIMUM
FIXTURE WHIP FROM
JUNCTION BOX
(6FT. LONG MAX.)
LUMINAIRE.
REFER TO
SCHEDULE
LUMINAIRE MANUFACTURER'S
EARTHQUAKE CLIP, (4) PER
FIXTURE AT CORNERS. ATTACH
WITH SHEET METAL SCREW
ACOUSTICAL CEILING
TILE (TYP)
ARCHITECTURAL
CEILING GRID
LUMINAIRE.
REFER TO
SCHEDULE
CEILING HANGER
WIRE, TYP.
RECESSED CAN
CEILING MAIN
BEAM
GYPSUM
BOARD (TYP)
WIRE TIE OR SCREW
BAR HANGER TO
CROSS BEAM TYP.
BAR HANGERS
12GA. HANGER WIRE AT DIAGONAL
CORNER ATTACHED TO STRUCTURE
CEILING
CROSS BEAM
CEILING BEAM
CEILING HANGER
WIRE, TYP.
WIRE TIE OR SCREW
BAR HANGER TO
CEILING GRID TYP.
BAR HANGERS
12GA. HANGER WIRE AT DIAGONAL
CORNER ATTACHED TO STRUCTURE
ACOUSTICAL
CEILING TILE (TYP)
ARCHITECUTRAL
CEILING HANGER WIRE
DRYWALL CEILING
CROSS TEE, TYP.
CEILING MAIN
BEAM.
DRYWALL CEILING
CROSS TEE, TYP.
GYPSUM
BOARD
WIRE TIE THROUGH
& CROSS BEAM, TYP.
#12 GA. HANGER WIRE THROUGH INTEGRAL
GALVANIZED LIPPED STEEL MOUNTING
CHANNEL & ATTACHED TO STRUCTURE
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
WASHER & NUT
1/4" SCREW
CEILING HANGER WIRE
ACOUSTICAL
CEILING
TILE (TYP)
#12 GA. HANGER WIRE THROUGH INTEGRAL
GALVANIZED LIPPED STEEL MOUNTING
CHANNEL & ATTACHED TO STRUCTURE
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
WASHER & NUT
1/4" SCREW
WIRE TIE THROUGH
& CROSS BEAM, TYP.
SUITE 301
Ste. 275
E-523
BOLLARD BASE DETAIL BOLLARD BASE DETAIL CONDUIT AND OUTLET SUPPORT IN METAL STUD WALL TYPICAL PANELBOARD SURFACE MOUNTED DETAIL SURFACE MOUNTED PANEL (TYP)
CONDUIT SUPPORT DETAIL FOR
VANDAL RESISTANT LIGHT
BOLLARD PER LIGHT FIXTURE
SCHEDULE.
PVC CONDUIT ADAPTER
COUPLING
PVC CONDUIT
FINISHED PAVING
GALVANIZED ANCHOR BOLTS &
HEX NUTS. PROVIDE LEVELING
SHIMS OR HEX NUTS.
[6
UNDISTURBED SOIL OR
SELECT BACKFILL
COMPACTED, SEE
NOTE BELOW.
CONCRETE BASE &
REINFORCING STEEL,
SEE NOTE BELOW.
NOTE:
BACKFILL, CONCRETE, REINFORCING STEEL, AND ANCHOR BOLTS ARE SHOWN FOR
REFERENCE ONLY. STRUCTURAL DESIGN IS SHOWN ON STRUCTURAL DRAWINGS.
(PAVED AREAS)
VANDAL RESISTANT LIGHT
BOLLARD PER LIGHT FIXTURE
SCHEDULE.
PVC CONDUIT ADAPTER
COUPLING
PVC CONDUIT
FINISHED GRADE
GALVANIZED ANCHOR BOLTS &
HEX NUTS. PROVIDE LEVELING
SHIMS OR HEX NUTS.
[6
UNDISTURBED SOIL OR
SELECT BACKFILL
COMPACTED, SEE
NOTE BELOW.
CONCRETE BASE &
REINFORCING STEEL,
SEE NOTE BELOW.
BACKFILL, CONCRETE, REINFORCING STEEL, AND ANCHOR BOLTS ARE SHOWN FOR
REFERENCE ONLY. STRUCTURAL DESIGN IS SHOWN ON STRUCTURAL DRAWINGS.
(TURF AREAS)
GALVINZED CONDUIT
SUPPORT
METAL STUD
SECURE TO CEILING
SLAB OR JOISTS
8-1/4" STEEL ANGLE
CONNECTORS
1-1/2" SQ, 12 GA
ELECTRO GALV STL
SECURE TO FLOOR
ELECTRIC CLOSET
FOR DRYWALL INSTALLATION FOR MASONRY WALL INSTALLATION
ELECTRIC CLOSET
PANEL
WIRE CLOSET WALL
SECURE TO FULL
WIDTH OF MASONRY
WALL
1-1/2" SQ, 12 GA
ELECTRO GALV STL
SINGLE CONDUIT
WITH SINGLE BOLT
PIPE STRAPS
36" MAX
SURFACE MOUNTED
36" MAX
1-1/2"x3/4" - 14 GA
NO SCALE NO SCALE NO SCALE NO SCALE NO SCALE
N
GROUNDING ELECTRODE
CONDUCTOR TO BLDG STEEL
EQUIPMENT GROUNDING
#1/0 AWG GND FOR TELECOMMUNICATION SYSTEM
WATER PIPE
#4/0 TO COLD
EGC
GROUND ROD / BUILDING
#4/0 BARE COPPER AWG TO
STEEL.
GROUND BUS
NEUTRAL BUS
TYPICAL
PANELBOARD
CONDUCTOR
PANELBOARD
MAIN BONDING
JUMPER
SECONDARY
PAD MOUNT XFMR
MAIN SWITCHBOARD DRY TYPE TRANSFORMER
TYPICAL STEP DOWN
GROUND BUS
GROUNDING DIAGRAM
SUITE 301
Ste. 275
E-524
A:
TOTAL
TOTAL CONNECTED AMPS B: C:
EXISTING PANELBOARD "PP12" SCHEDULE SEC. 1
CBA
WIRE
SIZE
CKT
NO
BRKR
TRIP
PHASE CKT
LOAD SERVED
1 2
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
25 26
27 28
29 30
31 32
33 34
35 36
37 38
39 40
* 41 42
20 *
LOAD (AMP)
B CA
B C
LIGHTING RMS 207-214
LIGHTING RMS 217-219
LIGHTING WAITING AREA 134
LTNG NEW BROOMS CHECK-IN
RECEPTACLES EXAM ROOM 12
ATRIUM RECEPTACLES
RECEPTACLES EXAM ROOM 16
RECEPTACLES EXAM ROOM 15
REC MED & PHARM RMS
RECEPTACLES EXAM ROOM 20
RECEPTACLES EXAM RM 25
RECEPTACLES EXAM RM
RECEPTACLE WATER FOUNTAIN
RECEPTACLES NEW RESTROOM
FLOOR REC ATRIUM WAITING
RECEPTACLES ATRIUM WAITING
ROOF TOP RECEPTACLES
RECEPTACLES ATRIUM WAITING
SPARE
EXTERIOR LIGHTING BOLLARDS
SENSOR SINKS/TOILET RMS E1-99
225A, MLO, 208Y/120V, 3 PHASE, 4 WIRE, 22 KAIC MIN, SURFACE MOUNT
CORRIDOR 206 & S LIGHTING
LIGHTING EXAM RMS 220-225
WAITING AREA 134 LIGHTING
EXT LIGHTING NEW ADDITION
EXAM ROOM 11 RECEPTACLES
LIGHTING CONTROL RELAY PANEL
CORRIDOR RECEPTACLES
COR. TELE, ELEC. HSEKPNG REC
EXAM ROOM 23 RECEPTACLES
EXAM ROOM 18 RECEPTACLES
EXAM ROOM RECEPTACLES
MINI FRIG MED RM RECEPTACLES
HALLWAY N1-189 RECEPTACLES
EXAM & STORAGE RM RECPT.
ATRIUM WAITING RECEPTACLES
ROOF TOP RECEPTACLES
SENOR SINKS RMS 190 & 191 REC
LIGHTING - PENDANTS IN ATRIUM
43 44
45 46
47 48
49 50
51 52
53 54
55 56
57 58
59 60
61 62
63 64
65 66
67 68
69 70
71 72
73 74
75 76
77 78
79 80
81 82
* 83 84
TRIP A
REC/COPIER/WAITING RM N1-
SENSOR SINKS/ TOILET RM N1-
MOTORIZED SHADES
REC WAITING RM N1-142
RECEPTACLES EXAM RM 14
PACS CONTROLLERS
LIGHTING WAITING RM N1-14
SENSOR SINKS/TOILET RM E1-
REC WAITING RM NA-142
RECEPTACLES EXAM RM 13
RECEPTACLES EXAM RM 22
RECEPTACLES EXAM RM 21
WAITING RM 1-142 DESK REC
RECEPTACLES CGW
PARTITION REC RM N1-142
CAMERA POWER SUPPLY
PARTITION REC RM N1-142
EXISTING PANELBOARD "PPM" SCHEDULE
39 40
* * 41 42
PUMP P-2
CABINET UNIT HEATER
POWER ROOF VENTILATOR PRV-1
ICI PANEL
RTU ENTRANCE VEST
ROOF TOP UNIT RTU-1
AIR FLOW MEASURING DEVICE
HEAT TRACE
SPACE
ERU-1 LIGHTS AND OUTLETS
225A, MLO, 208/120V, 3 PHASE, 4 WIRE, 22 KAIC MIN, SURFACE MOUNT
PUMP P-1
SSAHU-1
CABINET UNIT HEATER
VARIABLE VOLUME BOXES
POWER ROOF VENTILATOR PRV-1
ENERGY RECOVERY UNIT ERU-1
RTU-1 LIGHTS AND OUTLETS
CIRC PUMP AIR FLOW MEAS DEV
REST ROOM IN 103
20 20
EXISTING PANELBOARD "PP12" SCHEDULE SEC. 2
225A, MLO, 208Y/120V, 3 PHASE, 4 WIRE, 22 KAIC MIN, SURFACE MOUNT
RECEPTACLES EXAM RM 17
RECEPTACLES EXAM RM 19
RECEPTACLES EXAM RM 24
NURSE CALL POWER SUPPLY
NOTES: 1.
MANUFACTURER: GENERAL ELECTRIC (GE) A-SERIES II PANELBOARD CAT. AQF3422SB2.
MANUFACTURER: GENERAL ELECTRIC (GE) A-SERIES II PANELBOARD CAT. AQF3422SB2.
MANUFACTURER: GENERAL ELECTRIC (GE) A-SERIES II PANELBOARD CAT. AQF3422MB
( * ) INDICATES EXISTING LOAD OR CONDITION.
PANELBOARD "EMH1" SCHEDULE
301.3
PANEL "EMH2"225
4/0
P-3
P-4
16.4
322.6 287.3
800A, 800A M.C.B., 480Y/277V, 3 PHASE, 4 WIRE, 65 KAIC MIN, SURFACE MOUNT
31.2193.5
20.4169
-52.9
-27
3.41.6
3.44.8
-4.8
23.2278.1 38284.6 27.2260.1
PANEL "EML1" VIA 150KVA XFMR
AHU-1 (SUPPLY)
AHU-1 (RETURN)
EF-2
P-2
P-1
SPD/TVSS
NOTES: 1. PROVIDE ARC FLASH WARNING LABEL ON ALL PANELBOARDS.
40 - -
42 - -
PANELBOARD "EMH2" SCHEDULE
16.4
LIGHTS EXAM ROOM & WORK AREA20
LIGHTS RECEPTION AND WAITING
LIGHTS EXAM ROOM AND WORK AREA
6.7
31.2 22.2
100A, M.L.O., 480Y/277V, 3 PHASE, 4 WIRE, 35 KAIC MIN, SURFACE MOUNT
5.61.2
4.93
1.72.2
12.94.8
5.21.75
4.8-
6.7-
7.3-
13.23.2 25.26 17.44.75
ELEC, FCC, ELEVATOR RM LIGHTING
EXTERIOR POLE LIGHTING
320 12BASEMENT CORRIDOR LIGHTING
520 12MECHANICAL ROOM LIGHTING
LIGHTS EXAM ROOM AND WORK AREASPACE
SPACESPACE
LIGHTS MAIN LOBBYEXTERIOR BOLLARD LIGHTING
LIGHTS WAITING AREAFACADE LIGHTING
LIGHTS CORRIDORSSPACE
LIGHTS EXAM ROOM & WORK AREA
LIGHTS OFFICES AND CORRIDOR
SUITE 301
Ste. 275
SCHEDULES
E-620
-6
/1
PANELBOARD "EML1" SCHEDULE
426.7
WORK AREA20 12
EXAM RM. RECPTS.
PANEL "EML2"
PANEL "TPP1"
3/0
362 325.6
600A, 600A M.C.B., 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MIN, SURFACE MOUNT
7.5
154.5
165.5
156.6
142.6
23.6
370.756 38656 355.650
WORK AREA
320 12
520 12
20 1210
20 12
20 1210COPIER
FCC RECPT.
COPIER
PANEL "EML4"
3/0
PANELBOARD "EML2" SCHEDULE
20 12 41
161.2
COPIER20
PANEL "EML3"
171.6 137.2
200A, MAIN LUGS ONLY, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MIN, SURFACE MOUNT
-10
77.27.5
86.66
70.26
93.767.5 105.666 81.256
EXAM RECPTS.
320 12
VAV-1,2,3,4,20,21
VAV-5,6,9,17,18,19
EF-4
VAV-7,10,11,13,14,16
.46
PANELBOARD "TPP1" SCHEDULE
23.6
RACK RECPTS.20
100A, 80A M.C.B., 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MIN, SURFACE MOUNT
-1.6
1013.6 1010 1010
RECPTS.
IT ROOM LTG
320 12RACK RECPTS.
520 12RACK RECPTS.
SPARESPARE
RACK RECPTS.
RACK RECPTS.
CCTV CAMERA
PANELBOARD "EML4" SCHEDULE
RECPTS. RM. 1N2104
154.5
RECPTS. CORRIDOR20 12
RECPTS. BREAKROOM
RECPT. PROJECTOR SCREEN
RECPT. PROJECTOR
GFI RECPT. REFRIGERATOR
KIOSK RECPT.
RECPTION RECPTS.
PANEL "EML5"
4.5
159.5 161
200 M.L.O., 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MIN, SURFACE MOUNT
1.5
7.5-
7.56
1.56
83.56
857.5
11737.5 120.539 117.543.5
ELEC. RM. RECPT.
RECPTS. RM. 1N316
RECPTS. TEAM WORK AREA
RECPTS. CORRIDOR
320 -SPARE
20 12 12
RECPTS. RM. 1N314
RECPTS. RM. 1N312
RECPTS. RM. 1N310
RECPTS. RM. 1N308
RECPTS. RM. 1N306
RECPTS. RM. 1N304
RECPTS. RM. 1N302
RECPTS. RM. 1N300
RECPTS. RM. 1N215
RECPTS. RM. 1N213
RECPTS. RM. 1N211
RECPTS. RM. 1N209
RECPTS. RM. 1N207
RECPTS. RM. 1N205
RECPTS. RM. 1N201
RECPTS. RM. 1N203 & 1N201A
RECPTS. RM. 1N208
RECPTS. RM. 1N206
RECPTS. RM. 1N204
GFI RECPT. REFRIGERATOR
GFI RECPT.
GFI RECPT. MICROWAVE
GFI RECPT. COFFEE MAKER
GFI RECPT. COFFEE MAKER
PANELBOARD "EML5" SCHEDULE
20 12 41
83.5
RECPTS. RM. 1N40220
TELEVISION RECPT.
RECPTS.
THERMAL SCANNER
RECEPTION RECPTS.
RECPTS. VESTIBULE
RECPT. LOBBY
84 85
100A, MAIN LUGS ONLY, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MIN, SURFACE MOUNT
7.512
37.5
4.57.5
4.512
4.54.5
4.56
4.57.5
64.5
1.57.5
67.5
-7.5
37.5
4.59
3746.5 25.558.5 35.549.5
RECPT. WAITING
RECPT. WAITING
RECPTS. RM. 1N506 - 1N506A
RECPTS. RM. 1N508 - 1N508A
RECPTS. RM. 1N502 - 1N502A
RECPTS. RM. 1N504 - 1N504A
RECPTS. RM. 1N414
RECPTS. RM. 1N500, 1N500A, 1N007
WHEEL CHAIR SCALE - HEIGHT & WEIGHT STATION12 20
OFFICE RECPTS.
12 20
RECPTS. RM. 1N412
RECPTS. RM. 1N410
RECPTS. RM. 1N408
RECPTS. RM. 1N406
RECPTS. RM. 1N404
RECPTS. RM. 1N400, 1N005
RECPTS. RM. 1N602
RECPTS. RM. 1N313
RECPTS. RM. 1N311
RECPTS. RM. 1N309
RECPTS. RM. 1N307
RECPTS. RM. 1N305
RECPTS. RM. 1N303, 1N301A
RECPTS. RM. 1N301
TELEVISION RECPT.
PANELBOARD "EML3" SCHEDULE
TRIP A
100A, MAIN LUGS ONLY, 208Y/120V, 3 PHASE, 4 WIRE, 10 KAIC MIN, SURFACE MOUNT
17.1
17.1
MED. REFRIGERATOR
MSO-1
DOOR POWER
20 12EXAM RECPTS.
20 12EXAM RECPTS.
SLIDING DOORS
B.D PYXIS MED
B.D PYXIS MED
MSO-2
HOISTWAY LIGHTS, RECPT.
VAV-22
SHREDDER
7.2
BASEMENT CORRIDOR RECPT.
MECHANICAL ROOM RECPT.
EF-1
ELEV. ROOM RECPT.
ELEV. PIT RECPT. & LIGHTS
9.8
4.6
54.1 49 43.1 23.1 37.6 27.1
77.2 86.6 70.2
SP-1
EF-3
SCP-1
WHEEL CHAIR SCALE - HEIGHT & WEIGHT STATION
VAV-8,12,15
SUITE 301
Ste. 275
SCHEDULES
E-621
G EE
POWER RISER DIAGRAM
PENNELEC (LOCAL UTILITY)
12470V GREENWOOD SIDE
PENNELEC (LOCAL UTILITY)
12470V OLD FRENCH SIDE
(CURRENTLY SERVING VAMC)
POWER POLE AT
CORNER OF WEST
38TH STREET
MAIN B
GLENWOOD
FEED
(OPEN)
NOT
UTILIZED
XFMR T1A
FEEDER
2500 KVA XFMR
12470 - 480Y/277V, 3∅
IMP 5.76
3000A/3P
MCB
SQ. D SWITCHBOARD 2, 3000A,
3000A M.C.B., 480Y/277V, 3∅, 4W
400A/3P
800A/3P
ATS
400A/3P 2500A/3P
PANEL DPG-1
400A, 480Y/277V, 3∅, 4W
WESTSIDE OF SWITCHBOARD IN RM 200
MAIN ELEC. RM. OF HOSPITAL SERVING
AMBULATORY SIDE OF HOSPITAL
PARKING
GARAGE &
CLC BRKR
X-RAY
BREAKER
LAUNDRY
TIE
TIE BUS
TRANSITION
IN THE
REAR
AUXILLIARY
IN FRONT
XFMR T1B
FEEDER
MAIN A BRKR
OLD FRENCH
RD FEEDER
(CLOSED) BEING
USED TO
SERVE VAMC
METALCLAD SWITCHGEAR SERIES 5
RATED MAX VOLTAGE 15KV
IMPULSE WITHSTAND (BIL) 95KV, FREQUENCY 60HZ
CONT. CURRENT 1200A
MAX SHORT CKT. CURRENT 25 KA SYM.
NOTE; BOTH 12,470V SERVICES TERMINATE TO THE
EXISTING SQ. D SWITCHGEAR. ONLY THE OLD
FRENCH UTILITY IS CURRENTLY BEING USED
TO ENERGIZE BOTH SWBD1 & SWBD2
2500 KVA XFMR
12470 - 480Y/277V, 3∅
IMP 5.76
MCB
SQ. D SWITCHBOARD 1, 3000A,
3000A M.C.B., 480Y/277V, 3∅, 4W
PANEL DPG-2
450A, 480Y/277V, 3∅, 4W, 65 KAIC
300A/3P
100A/3P
60A/3P
125A/3P
PANEL MP1
125A/3P
ATS-ES-
SWGR
1200A/3P
(OPEN)
1200A/3P 1200A/3P 1200A/3P 80A/3P
100A/3P 2000A/3P
SPACE SPACE SPACE SPACE SPACE SPACE
XFMR-1LOAD BANK
/TEMP
GENERATOR
CAM LOK
(CABINET
OUTSIDE IN
BACK)
GENERATOR
WATER BLDG. PANEL "H1"
GENERATOR
EATON LV SWITCHGEAR
4000A, 480Y/277V, 3∅, 4W, 65 KAIC
AUTOMATIC TRANSFER SWITCH
ATS-ES-SWGR
PANEL P-ES-1 125A, 480Y/277V, 3∅,
4W
ATS-ES-
SWGR
1200A/3P 1200A/3P 1200A/3P 80A/3P
100A/3P 2000A/3P
PANEL "LH-1"
800A, 800A M.C.B., 480Y/277V, 3∅, 4W
PANEL "EMH1", ROOM BN110
800A, 800A M.C.B., 480Y/277V, 3∅, 4W
225A/3P
150 KVA XFMR
480 - 208Y/120V, 3∅
600A/3P MCB
PANEL "EML1", ROOM BN110
600A, 600A M.C.B., 208Y/120V, 3∅, 4W
200A/3P
PANEL "EML2", ROOM BN110
200A, MAIN LUGS ONLY, 208Y/120V, 3∅, 4W
ATS
800A AUTOMATIC TRANSFER SWITCH
ROOM BN110
200A/3P
PANEL "EML4", ROOM BN110
200A, MAIN LUGS ONLY, 208Y/120V, 3∅, 4W
CONNECT TO EXISTING
800A/3P CIRCUIT
PROVIDE A 800A/3P CIRCUIT
BREAKER TO SERVE THE NEW
800A ATS
PANEL "EML3", ROOM BN110
100A, MAIN LUGS ONLY, 208Y/120V, 3∅, 4W
PANEL "EMH2", ROOM BN110
100A, MAIN LUGS ONLY, 480Y/277V, 3∅, 4W
80A/3P
PANEL "TPP1", ROOM BN106
100A, 80A M.C.B., 208Y/120V, 3∅, 4W
PANEL "EML5", ROOM BN110
100A, MAIN LUGS ONLY, 208Y/120V, 3∅, 4W
NEW ELECTRICAL MANHOLE
PANEL "H1"
PANEL "H1"
M.C.B.
80A/3P MCB
NEW ELECTRICAL MANHOLE
SUITE 301
Ste. 275
POWER RISER DIAGRAM
E-622
1 1
1 1 1 1 1 1 1 1
SUITE 301
Ste. 275
TELECOMMUNICATIONS PLAN -
DEMOLITION
TD101
T
3/16" = 1' - 0" 0 5' 10' 20'
NORTH
NOTE: IF THIS DRAWING IS A REDUCTION
GRAPHIC SCALE MUST BE USED.
KEY PLAN
PLAN
TRUE
NOT TO SCALE
NIC
GENERAL NOTES
1. LIGHT LINEWEIGHT SYMBOLS INDICATE EXISTING DEVICES,
EQUIPMENT, CONDUIT, ETC. TO REMAIN. HEAVY LINEWEIGHT
SYMBOLS INDICATES NEW DEVICES, EQUIPMENT TO BE
SUPPLIED AND OR INSTALLED. HEAVY AND DASHED
LINEWEIGHT SYMBOLS INDICATE DEVICES, EQUIPMENT,
CONDUIT, ETC. TO BE REMOVED.
2. SEAL AND FIREPROOF ALL PENETRATIONS CREATED BY THE
REMOVAL OR INSTALLATION OF CONDUITS.
DEMOLITION NOTES
1. REMOVE EXISTING TELEPHONE AND DATA OUTLETS AND ALL
ASSOCIATED CONDUIT AND WIRING COMPLETE BACK TO
EXISTING TELECOMMUNICATIONS ROOM COMPLETE.
2. EXISTING ELECTRICAL ROOM. THE CONTRACTOR SHALL
COORDINATE THE REMOVAL OF THE LENEL SECURITY
EQUIPMENT IN THE EXISTING ELECTRICAL ROOM WITH THE
VAMC/GOVERNMENT AND TURN OVER ANY EQUIPMENT
REQUESTED BY THE VAMC. THE BOSCH INTRUSION PANEL
LOCATED IN THE EXISTING TELECOMMUNICATION ROOM
MUST REMAIN ACTIVE AS LONG AS THE ROOM IS
SUPPORTING THE NETWORK. THIS PANEL SERVES DOOR
THAT ARE BEING DEMOLISHED IN THE SCOPE OF WORK AND
ALSO DOORS OUTSIDE OF OUR AREA OF WORK.
3. EXISTING TELECOMMUNICATION ROOM. THE CONTRACTOR
SHALL COORDINATE THE REMOVAL OF ALL
TELECOMMUNICATIONS EQUIPMENT WITH THE
VAMC/GOVERNMENT AND TURN OVER ANY EQUIPMENT
REQUESTED BY THE VAMC.
4. EXISTING CCTV CAMERA TO REMAIN. CONTRACTOR MUST
MAINTAIN THE CONNECTIVITY OF THE CAMERA DURING THE
CONSTRUCTION PHASE OF THE PROJECT.
5. DISCONNECT EXISTING CCTV CAMERA AT LOCATION
INDICATED AND CLEAN AND STORE FOR REUSE. REMOVE
WIRING AND CONDUIT COMPLETE BACK TO SOURCE.
6. THE DOORS THAT ARE SERVED BY THE EXISTING BOSCH
PANEL ARE AS FOLLOWS: RED CLINIC 1W190 ENTRANCE,
WOMEN'S CLINIC 1W110, REP CLINIC REAR ENTRANCE,
WOMEN'S CLINIC REAR ENTRANCE, OIF EAST ENTRANCE,
RED CLINIC MED ROOM, WOMEN'S CLINIC MED ROOM,
PRIMARY CARE ADMIN 1N169-1. THE DOORS CONNECTIONS
WILL NEED TO BE TRANSFERED TO THE EQUIPMENT
MOUNTED IN THE ENGIEERING CLOSET BY THE ELEVATOR
LOBBY. TO PREVENT DISRUPTION TO THE HOSPITAL DURING
REGULAR HOURS, AFTER HOUR WORK WILL NEED TO BE
DONE. THIS INCLUDES OPENING CEILING TILES AND PULLING
THE WIRES TO THE DOORS OR WHERE POSSIBLE REUSING
THE EXISTING WIRING. ONCE THE WIRE IS TERMINATED AT
THE HEAD END EQUIPMENT, THE DOOR WILL NEED TO BE
CONVERTED TO THE NEW WIRE. THE CONTRACTOR MUST
COORDINATE THIS WORK WITH THE VAMC AND THEIR
SECURITY PROVIDER.
7. DISCONNECT AND REMOVE ALL ASSOCIATED CARD READER,
DOOR CONTACTS, AND SIREN CONNECTION WHEN THE DOOR
IS DEMOLISHED.
8. EXISTING DOUBLE DOORS TO REMAIN. REUSE EXISTING
CARD READER AND REWIRE FOR NEW SYSTEM.
3/16" = 1'-0"
TELECOMMUNICATIONS PLAN - DEMOLITION
0' 3/32"=1'-0"
40'20'10' 30'
CONSTRUCTION NOTES#
5.
6.
7.
LOCATION OF EXISTING TELEPHONE/VOICE TERMINAL CABINETS
FOR INCOMMING COPPER BACKBONE CABLING IN MECHANICAL
ROOM.
LOCATION OF EXISTING MAIN TELEPHONE ROOM FOR THE MAIN
HOSPITAL SERVICE ENTRANCE.
LOCATION OF EXISTING FIBER ROOM FOR THE MAIN HOSPITAL
SERVICE ENTRANCE.
400 PAIR COPPER BACKBONE IN A 4" CONDUIT FOR
CONNECTIVITY OF THE NEW IT ROOM BN106 VOICE TO THE MAIN
TELEPHONE ROOM WB-39 AND ONE SPARE 4" CONDUIT.
12 PAIR SINGLE MODE FIBER AND 12 PAIR MULTIMODE FIBER
FOR CONNECTIVITY OF THE NEW IT ROOM BN106 DATA TO THE
MAIN FIBER ROOM B13A.
THREE (3) 4" CONDUIT ROUTED THRU THE CRAWL SPACE
BETWEEN COLUMNS 5 & 6 FROM THE NEW IT ROOM BN106 AND
THE EXISTING LEVEL 00 OF THE MAIN HOSPITAL.
LIGHT LINEWEIGHT SYMBOLS INDICATE EXISTING DEVICES,
SYMBOLS INDICATES NEW DEVICES, EQUIPMENT TO BE
SUPPLIED AND OR INSTALLED. HEAVY AND DASHED
SEAL AND FIREPROOF ALL PENETRATIONS CREATED BY THE
ROUTE CONDUIT AS SHOWN ABOVE FINISHED CEILING TO THE
LOCATION INDICATED. THE CONTRACTOR MUST COORDINATE
THE CONDUIT ROUTING WITH ALL EXISTING UTILITIES ABOVE
THE FINISHED CEILING.
REFER TO DRAWINGS GC300, GC301 AND GC401 FOR PHASING WORK.
1 PAIR MULTIMODE FIBER IN 3/4"C FOR CONNECTION OF
"LENEL" ACCESS CONTROL ON NON-VA NETWORK.
F.E.C
WB-39
B13A
BN045
3/32" = 1'-0"
BASEMENT TELECOMMUNICATIONS PLAN - NEW WORK
EXISTING LEVEL
00 OF MAIN
HOSPITAL
NB-59
SUITE 301
Ste. 275
BASEMENT TELECOMMUNICATIONS
PLAN - NEW WORK
T-011A
-0
2 2
R R
R
9 (TYP)
K
K R
BMS
SUITE 301
Ste. 275
BASEMENT TELECOMMUNICATIONS
PLAN - NEW WORK
T-011B
-0
BASEMENT TELECOMMUNICATIONS ROOM PLAN - NEW WORK
CONSTRUCTION NOTES
1. PROVIDE A 24" WIDE X 6" DEEP CABLE RUNWAY/LADDER
TRAY AS INDICATED.
2. PROVIDE A 12" WIDE X 6" DEEP CABLE RUNWAY/LADDER
TRAY AS INDICATED.
3. TELEPHONE TERMINATION AREA FOR OUTSIDE PLANT
INCOMING CABLING.
4. SECURITY EQUIPMENT TERMINATION AREA.
5. 6" VERTICAL CABLE MANAGEMENT FOR 19" FLOOR MOUNTED
RACK.
6. 19" FLOOR MOUNTED (4) POST EQUIPMENT RACKS FOR
PATCH PANELS. COORDINATE WITH THE VAMC AS TO HOW
MANY WILL BE REQUIRED AS A MINIMUM.
7. PROVIDE A TGBB 4" X 12" X 1/4" COPPER GROUND BUS BAR
WITH #6 AWG INSULATED COPPER GROUND WIRE TO THE
BUILDING SERVICE. COORDINATE LOCATION OF GROUND BUS
BAR WITH LOCATION OF COMMUNICATIONS CABINET/RACKS.
8. PROVIDE 3/4" FIRE RETARDANT PLYWOOD ON ALL WALLS OF
SMALL IT (BN1D6) AND FCC (BN108). BOTTOM OF PLYWOOD
AT 6" AFF.
9. CCTV CAMERA.
10. NURSE CALL SYSTEM TERMINATION AREA.
11. THREE 4" CONDUIT STUBS INTO FCC ROOM ROUTED FROM
THE FIRST FLOOR CABLE TRAY SYSTEM THROUGH THE
CHASE.
12. PROVIDE SIX (6) 4" CONDUITS SLEEVES. GROUND EACH
SLEEVE TO THE TMGB USING #6 GREEN COPPER
CONDUCTORS.
13. PROVIDE THREE (3) 4" CONDUITS AND ROUTE THRU CRAWL
SPACE INTO EXISTING BASEMENT LEVEL OF MAIN HOSPITAL
TO THE LOCATION OF THE EXISTING TELEPHONE AND FIBER
ROOMS. SEE SHEET T-011A.
14. CARD READER.
15. PROVIDE ONE (1) 3/4" CONDUIT AND ROUTE THRU CRAWL
SPACE INTO EXISTING BASEMENT LEVEL OF MAIN HOSPITAL
TO THE LOCATION OF ROOM BN045 FOR THE "LENEL" SYSTEM
CONNECTION.
16. MOUNT BALANCE MAGNETIC SWITCH CONTACT AT FLOOR
LEVEL OF ROLL-UP DOOR. CONTACT WILL BE CONNECTED
TO THE BOSCH KEYPAD ON DOOR (BN114) TO THE
MECHANICAL ROOM.
SUPPLIED AND OR INSTALLED. HEAVY AND DASHED
3. REFER TO DRAWINGS GC300, GC301 AND GC401 FOR PHASING
OF WORK.
J J
J J J J J J J J
N N N N
NNNNN NN N
4 5
6 6
TEAMWORK ZONE
1N2.1
CONSULT/ EXAM
1N215
1N213
1N211
1N209
1N207
CONSULT
1N205
CONSULT
1N203
PATIENT TOILET
1N201A
PROCEDURE
1N201
PATIENT CORRIDOR
1N2
1N200
WHEEL CHAIRS
1N001C
1N204
1N206
1N208
1N210
1N1.1
CORRIDOR
1N1
STAFF TOILET
1N102
PC ASST. MANAGER
1N104A
BREAKROOM
1N106
8 (TYP.)
(1) 1"C
(1) 1.5"C
(1) 1.25"C
(1) 1"C
(2) 1.25"C
(1) 1.25"C(1) 1.5"C
11 11
8 (TYP)
8 (TYP)
PC MED. DIRECTOR
1N104C
PC MANAGER
1N104B
ADMIN. OFFICE
1N104
STAFF TOILET
1N102
SUITE 301
Ste. 275
TELECOMMUNICATIONS PLAN AREA
'A' - NEW WORK
T-111A
TELECOMMUNICATIONS PLAN AREA 'A' - NEW WORK
SUPPLIED AND OR INSTALLED. HEAVY AND DASHED
3. ALL DROPS WILL BE A MINIMUM OF 1" CONDUIT ROUTED BACK
TO THE LOCATION OF THE CABLE TRAY AND BONDED TO THE
CABLE TRAY.
4. ALL TELECOMMUNICATION CABLING MUST BE CAT6A F/UTP.
5. REFER TO DRAWINGS GC300, GC301 AND GC401 FOR PHASING
1. FLUSH FLOOR JUNCTION BOX FOR TELECOMMUNICATION
CABLING TO GREETER STATION. COORDINATE LOCATION
WITH GREETER STATION.
2. MOUNT TELECOMMUNICATION OUTLET DEVICES UNDER
COUNTERTOP OF GREETER STATION
3. LOCATION OF SELF CHECK-IN STATION. COORDINATE
MOUNTING HEIGHT OF TELECOMMUNICATION OUTLET WITH
CHECK-IN STATION REQUIREMENTS.
4. FLUSH FLOOR BOX FOR CONNECTION OF TWO TEAMWORK
STATION TELECOMMUNICATION SERVICES. COORDINATE
FLOOR BOX LOCATION WITH TEAMWORK STATION
5. FLUSH FLOOR BOX FOR CONNECTION OF FOUR TEAMWORK
FLOOR BOX LOCATION WITH TEAMWORK STATION.
6. FLUSH FLOOR BOX FOR CONNECTION OF THREE TEAMWORK
7. MOUNT COAXIAL OUTLET ROUGH-IN AT 60" AFF. COORDINATE
LOCATION WITH TELEVISION AND VAMC.
8. CCTV CAMERA..
9. COORDINATE MOUNTING OF DATA OUTLET WITH MOUNTING
HEIGHT OF TELEVISION. ROUTE CONDUIT DROP TO THE
LOCATION OF THE NEAREST CABLE TRAY.
10. MOUNT TELEPHONE OUTLET 48" AFF.
11. ROUTE CONDUIT DROP TO LOCATION OF COLUMN ABOVE
FINISHED CEILING AND DOWN COLUMN TO UNDER FLOOR.
12. PROVIDE A 24"W X 4"D BASKET TYPE CABLE TRAY.
13. PROVIDE A 6"W X 2"D BASKET TYPE CABLE TRAY.
14. PROVIDE A 18"W X 4"D BASKET TYPE CABLE TRAY.
15. EXISTING CCTV CAMERA TO REMAIN.
16. EMPTY 3/4" CONDUIT W/ PULLSTRING TO LOCATION OF NEW
CCTV CAMERA LOCATION FOR CONNECTIVITY TO EXISTING
CCTV HEADEND EQUIPMENT. FOR CONTINUATION, SEE
SHEET T-111B.
17. MOUNT TELE/DATA OUTLET 48" AFF FOR WALLDOC UNIT.
COORDINATE LOCATION WITH RECEPTACLE FOR POWER.
J J J J J J J J
N N N N N N N N N
NNNNNNN
N N N N N N N N
NJ
1 1 1
CORRIDOR
1N6
1N508A
CONSULT/ EXAM (W)
1N508
1N506
WOMEN'S HEALTH CORRIDOR
1N5
1N6.1
1N3.1
1N506A
1N504A
1N504
1N502
1N500A
1N500
TEMPORARY STORAGE
1N007
TOILET
1N005
1N400
1N402
1N404
1N406
1N408
1N410
1N412
1N414
1N309
1N311
1N307
1N305
1N313
MEDICATION ROOM
1N602
CONSULT/ EXAM (NEG)
1N303
PROCEDURE (NEG)
1N301
CONCOURSE
1N002
1N316
1N314 CONSULT/ EXAM
1N312
1N310
1N308
1N306
1N304
1N302
1N300
CLEAN ROOM
1N601
(1) 1.5"C (1) 1.5"C
(2) 1.5"C
(2) 1.5"C (2) 1.25"C
7 7 7 7
5 (TYP)
R BMS
1N6.3
SOILED ROOM
1N603
3 3
SUITE 301
Ste. 275
TELECOMMUNICATIONS PLAN AREA
'B' - NEW WORK
T-111B
/3
TELECOMMUNICATIONS PLAN AREA 'B' - NEW WORK
1. FLUSH FLOOR BOX FOR CONNECTION OF FOUR TEAMWORK
2. LOCATION OF COPIER MACHINE.
3. MOUNT TELE/DATA OUTLET 48" AFF. FOR WALL DOC UNIT.
COORDINATE LOCATION WITH RECEPTACLE FOR POWER.
4. PROVIDE SIX 4" CONDUITS THROUGH WALL INTO CHASE AND
ROUTE CONDUITS TO THE LOCATION OF THE
TELECOMMUNICATIONS ROOM AT THE BASEMENT LEVEL.
FIREPROOF CONDUIT PENETRATIONS TO MAINTAIN FIRE
RATING OF WALL.
5. CCTV CAMERA..
6. COORDINATE MOUNTING OF DATA AND CATV OUTLET WITH
MOUNTING HEIGHT OF TELEVISION.
7. ROUTE CONDUIT DROP TO LOCATION OF COLUMN ABOVE
FINISHED CEILING AND DOWN COLUMN TO UNDERFLOOR.
8. PROVIDE A 24"W X 4"D BASKET TYPE CABLE TRAY.
9. PROVIDE A 12"W X 4"D BASKET TYPE CABLE TRAY.
10. PROVIDE A 8"W X 2"D BASKET TYPE CABLE TRAY.
11. MOUNT CCTV CAMERA REMOVED DURING DEMOLITION
PHASE OF PROJECT AS LOCATION INDICATED. MOUNT AT
12'-0" AFG TO BOTTOM OF FIXTURE.
12. PROVIDE A 4" SQUARE JUNCTION BOX AND A 3/4" EMPTY
CONDUIT WITH PULLSTRING BACK TO LOCATION OF EXISTING
CCTV HEADEND EQUIPMENT. THE CONTRACTOR MUST
COORDINATE THE CONNECTIVITY OF THE CAMERA WITH THE
VAMC SECURITY PROVIDE FOR THEIR EXISTING EQUIPMENT.
SEE SHEET T-111A FOR CONTNUATION.
SUPPLIED AND OR INSTALLED. HEAVY AND DASHED
3. ALL DROPS WILL BE A MINIMUM OF 1" CONDUIT ROUTED BACK
TO THE LOCATION OF THE CABLE TRAY AND BONDED TO THE
CABLE TRAY.
4. ALL TELECOMMUNICATION CABLING MUST BE CAT6A F/UTP.
5. REFER TO DRAWINGS GC300, GC301 AND GC401 FOR PHASING
FOUR (4) CATEGORY 6A
8P8C OUTLETS ACTIVE
FOR TELEPHONY DATA
THROUGH-PENETRATION FIRESTOP DETAILS
FIRESTOPPING
WITH APPROVED
SEAL OPENING
CONDUIT
WALL
SLEEVE
SEALANT
FIRESTOPPING
WITH APPROVED
SEAL SPACE BETWEEN
SEALANT
SLEEVE AND CONDUIT
TELECOMMUNICATIONS GROUNDING BUSBAR DETAIL
BRACKETS AND ALL MOUNTING HARDWARE SHALL BE STAINLESS STEEL.
2" (8
PLACES)
.75"
NOTES:
.437" D
IA (36 PLACES)
COPPER BUSBAR
.25"
24"
.75"
4"
4" H
IGH IN
SULATOR
BRACKET
1"
DETAIL AND TRAPEZE SUPPORT
TYPICAL TELECOM/DATA OUTLET CONDUIT
FOR INSTALLATION WHERE ELECTRIC STRIKE IS REQUIRED, 1/2
INCH CONDUIT IS NEEDED.
ON DOORS THAT
REQUIRE IT)
FOR ELECTRIC
STRIKE ( )
MAGNETIC DOOR
SWITCH (BMS)
6"x6" JUNCTION BOX
ABOVE LAY-IN CEILING
FINISHED FLOOR
HINGE SIDE
GROUNDING BUSHING
WITH #6 AWG TO
CABLE BASKET
SUPPORT
FRAMING
TWO (2) 1" CONDUITS FROM THE 2-GANG
OUTLET BOX OUT TO CORRIDOR CABLE TRAY.
PROVIDE SINGLE 1" EMT OUT TO CABLE
TRAY FROM VOICE ONLY OUTLETS
DOOR SECURITY ROUGH-IN DETAIL
OUTLET DETAIL
RACK POWER STRIP DETAIL
INSULATORS SHALL BE FIBERGLASS-REINFORCED THERMOSET.
OUTLET
(TYP.)
CONTROL TRANSFORMER
110/120V POWER
REQUEST TO EXIT
MOTION (REX)
(LOCATED ON OPPOSITE
SIDE OF DOOR)
SECURITY/ACCESS
KEYPAD OR EXIT
READER
BOSCH INTRUSION
KEYPAD (ONLY
21A-07A-21B
WHITE
PHONE 2
DATA 2
RED
GRAY BLUE
PHONE 1
DATA 1
21C-07A-21D
SUITE 301
Ste. 275
T-520
N N N N N N N N N N N N N N N N N N N N N
N N N N N N N N N N N N N N N N N N N N
N N N N N N N N N N N N N N N N N N N N N
N N N N N N N N N N N N N N N N N N N N
REMARKSDESCRIPTION
NEW
CABLE
IDENTIFICATION
CAT6A CABLING BACK TO TELECOM CABINET/NETWORK EQUIPMENT VIA CABLE TRAY
400 PR COPPER BACKBONE CABLING ROUTED IN 4" CONDUIT TO ROOM NB-59 TO TERMINATE TO EXISTING TELECOM INFRASTRUCTURE WHICH TIES BACK TO ROOM WB-39 MAIN TELEPHONE ROOM
12 PR. SM FIBER CABLE AND 12 PR. MM FIBER CABLE
TELECOMMUNICATIONS RISER DIAGRAM CABLE SCHEDULE
CABLING ROUTED IN 4" CONDUIT TO ROOM B13A FIBER ROOM
CABLING FOR VOICE ROUTED TO NETWORK EQUIPMENT IN IT ROOM BN106
CABLING FOR DATA ROUTED TO NETWORK EQUIPMENT IN IT ROOM BN106
CAT6A
CAT6A
TELECOMMUNICATIONS RISER DIAGRAM
DATA TELE
BASEMENT FLOOR TELECOMM RM
NETWORK
EQUIPMENT
ROOM STATUS LIGHT DIAGRAM
1ST FLOOR
CABLE TRAY
1N104
AREA "B" (T-111B)
AREA "A" (T-111A)
BASEMENT
1N104A
1N104B
1N104C
1N1.1
1N210
1N204
1N106
1N001C
1N001
1N2.1
1N314
1N311 1N309
1N301 1N3.1
1N6.1 1N414
1N002
1N007
1N6.3
1N210 1N208 1N206 1N204 1N215 1N213 1N211 1N209 1N207 1N205 1N203 1N201 1N316 1N314 1N312 1N310 1N308 1N306 1N304 1N302 1N300
1N313 1N311 1N309 1N307 1N305 1N303 1N301 1N414 1N412 1N410 1N408 1N406 1N404 1N402 1N400 1N508 1N506 1N504 1N502 1N500
SWITCHES SHALL BE INSTALLED WITHIN EXAM
ROOM. EACH SWITCH SHALL CONTROL ONE
OF THE THREE LAMPS IN THE DOME LIGHT
OUTSIDE THE EXAM ROOM
NOTES:
1. ALL WIRING SHOWN SHALL BE AS PER MANUFACTURERS RECOMMENDATIONS. FOR BIDDING PURPOSES, ASSUME EACH CABLE SHOWN SHALL BE 2 #16 IN 3/4"C.
EXAM
ROOM
THREE LAMP DOME LIGHT
OUTSIDE EXAM ROOM
12 OR 24 VDC
POWER SOURCE
MTD IN IT RM.
BN106
SWITCHES SHALL BE INSTALLED WITHIN EXAM
ROOM. EACH SWITCH SHALL CONTROL ONE
OF THE THREE LAMPS IN THE DOME LIGHT
OUTSIDE THE EXAM ROOM
12 OR 24 VDC
POWER SOURCE
MTD IN IT RM.
CONTROL
MODULE
CONTROL
MODULE
NURSE CALL BUTTON (TYP.)
THREE LAMP DOME LIGHT
OUTSIDE EXAM ROOM
NURSE CALL BUTTON (TYP.)
SUITE 301
Ste. 275
DIAGRAMS
T-601
R R R R
R R
R K
R K
BMSBMS
BMSBMS BMS BMS
BMS BMS
NETWORK
EQUIPMENT
SECURITY DIAGRAM
SECURITY
AREA "B" (T-111B)
AREA "A" (T-111A)
BASEMENT
CABLING FOR
SECURITY DEVICES
CABLING FOR
SECURITY DEVICES
1 DURESS/PANIC ACTIVATION WILL BE VIA COMPUTER IN EACH EXAM ROOM.
DOOR
1N1 1N210
E-1N601A 1N204
1N2A
1N2
1N001
E-1N601B
1N314
1N21
1N3
1N301
1N309
1N311
1N3A
E-1N601C
1N414
1N3.1
1N4
1N4A
1N5A
1N51N002A1N002A
1N002A
EBN116A
EBN116
S-2A
BN114
BN108
BN114
SUITE 301
Ste. 275
DIAGRAM
T-602
ELECTRICAL
E-522 - DETAILS
E-523 - DETAILS
E-524 - DETAILS
E-620 - SCHEDULES
E-621 - SCHEDULES
E-622 - POWER RISER DIAGRAM
TELECOMMUNICATIONS
TD101 - TELECOMMUNICATIONS PLAN - DEMOLITION
T-011A - BASEMENT TELECOMMUNICATIONS PLAN - NEW WORK
T-011B - BASEMENT TELECOMMUNICATIONS PLAN - NEW WORK
T-111A - TELECOMMUNICATIONS PLAN AREA 'A' - NEW WORK
T-111B - TELECOMMUNICATIONS PLAN AREA 'B' - NEW WORK
T-520 - DETAILS
T-601 - DIAGRAMS
T-602 - DIAGRAM
E-18E-18
E-17E-17
E-16
E-J.2
E-OO
G G
N N
12'-6"
L
(E) W27X84
W
X26
X
27'-7 3/4"
27'-7 3/4"
W12X26
AA
W14 CANTILEVER OVER HSS12X12
W12 CANTILEVER OVER HSS10X10
W8X10
W8X18
W8X18
12'-6" 1'-9 7/16" 4'-0" 2'-4" 10'-4 5/16" 1'-8 15/16" 13'-3 9/16" 4'-0 1/16"
2'-0"
10' - 3 5/16" 11 1/4"4' - 4 3/16" 4' - 4 3/16" 4' - 2 7/8" 4' - 2 7/8" 4' - 2 7/8" 5' - 0 3/16" 5' - 0 3/16" 4' - 5"
7 1/8"
1' - 8 5/8"
X6X 1/
S
8X
6X 5/
10X
10X 1/4
HSS10X10X1/4
H16 S562
E-4
E16 S561
A5
A16
H7
H4
3' - 0 7/8"
W14X30
IG
O
O
LO
/S
L=
'-7
T/STL=27'-0"
T/STL=28'-0 3/4"
E4
C12
T/STL=28'-0 3/4"
C8
C5
A12
A8
A4
8X
4X
JOIST BRIDGING
"H H
E-3.8
E-3.1
E-2.5
E-2.1
RADIUS = 87'-0"
RADIUS = 91'-9 1/4"
H9 S563
I I
LL
MM
T/STL-27'-7 3/4"
C10
C7
C4
PHASE 1A CONSTRUCTION
A10
1. SEE S001 FOR GENERAL NOTES.
2. SEE S002 FOR SPECIAL INSPECTION REQUIREMENTS.
3. SEE S003 FOR COMPONENTS AND CLADDING WIND LOADS.
4. FINISH FLOOR ELEVATION 0'-0" EQUALS TRUE ELEVATION 846.61 FT. T/STL IS 28'-0 3/4" UNO, WITH ADJUSTMENTS MADE FOR JOISTS BEARING ON BEAMS AS SHOWN ON PLAN.
5. JOIST SEATS ARE 5" DEEP.
6. GRIDS LOCATED AT CENTERLINE OF COLUMN, UNO.
7. SEE S602 FOR STEEL BEAM CONNECTION SCHEDULES.
8. SEE GENERAL NOTES FOR SLAB ON DECK INFORMATION.
9. SEE GENERAL NOTES FOR ROOF DECK INFORMATION.
10. ALL HANGERS, FASTENERS, AND METAL CONNECTORS IN CONTACT WITH TREATED
LUMBER, CONCRETE, OR EXPOSED TO WEATHER SHALL HAVE AT A MINIMUM G185 ZINC
COATING (E.G. SIMPSON ZMAX COATING) AND BE PAINTED WITH LATEX PAINT.
11. GC RESPONSIBLE TO FIELD VERIFY ALL EXISTING DIMENSIONS, ELEVATIONS AND SITE
CONDITIONS.
12. COORDINATE WALL AND SLAB OPENINGS WITH ARCHITECTURAL, MECHANICAL,
ELECTRICAL, AND PLUMBING DRAWINGS.
13. SEE H12/S561 FOR TYPICAL OPENING IN ROOF FRAMING DETAIL.
PLAN NOTES
NOTE DESCRIPTION
SUITE 301
Ste. 275
BTEWAW
HIGH ROOF FRAMING PLAN - PHASE
1B
S104-1B
HIGH ROOF FRAMING PLAN - PHASE 1B (T/STL = 28'-0 3/4" UNO)
3/7/23
W10X12
HSS6X3X1/4 HSS6X3X1/4 W10X12
7' - 4 1/8"4' - 6 3/8"1' - 11 5/8"5' - 1"2' - 3 1/8"
S502
S201
G7
D7
HSS6X4X1/4
5.5 5.6 5.7 6.5 6.6
7' - 4 1/8"4' - 6 3/8"1' - 11 5/8"5' - 1"2' - 3 1/8"
X
4 H
3X
HSS6X3X1/4
0" 8' - 11 3/4"
G4
8' - 11 3/4"
HSS6X3X1/4
4 H
8' - 11 3/4" 0"
8' - 11 3/4"
F D CEG
HSS6X6X1/4
HSS6X6X1/4 HSS6X4X1/4
20' - 8 3/16" 31' - 10" 11' - 7" 19' - 5" 7' - 8"
HSS COLUMN, SEE PLAN
HSS BRACE, SEE ELEVATION
WORKPOINT
3/8" GUSSET PLATE
TYP
3/16
ROOF BEAM, SEE PLAN
TYP SHEAR CONNECTION
HSS BEAM, SEE ELEVATION
HSS BRACE, SEE ELEVATION
STAIR LANDING BEAM,
SEE PLAN
TYP SHEAR CONNECTION
3/8" KNIFE PLATE THROUGH
CONTINUOUS BRACE
6"
EACH FACE
SUITE 301
Ste. 275
ELEVATIONS
1/4" = 1'-0"
STAIR ELEVATION
F16
F12
F9
TRUSS ELEVATION
1" = 1'-0"
DETAIL
D7
3/4" = 1'-0"
4 6 85 75.5 5.6 5.7 6.5 6.6 99.1
8' - 0" 1' - 4 3/4"
4' - 3" 4' - 4"
2' - 3 1/8"
6' - 4" 3' - 3 3/8" 3' - 4"
S202
OPENING IN CONCRETE WALL
2-#5 x 4'-0" @ EACH CORNER
2-#5 @ EACH SIDE OF OPENING
1 1/2" CLR
#3 STIRRUPS @ 8" OC
4-#5 BARS
1' - 0"
IE
SUITE 301
Ste. 275
ELEVATIONS
BASEMENT WALL ELEVATION
G16
3/4" = 1'-0"
TYP OPENING IN CONCRETE WALL DETAIL
G6
3" = 1'-0"
SECTION
2 3
F F
D D
C C
E E
E-20E-20
BB
18'-10" 20'-10" 20'-7" 20'-10" 19'-6" 12'-6" 12'-6" 1'-9 7/16" 6'-4"
5'-7 3/8"
24' - 0"
9' - 4 3/4" 9' - 5 5/8"
9' - 0 3/8" 11' - 5 3/4"
1' - 0" 1' - 6"
3' - 4" 8' - 2 1/8"
1' - 11 15/16"
6" 6"14' - 8" 3' - 4"
1' - 6"
1. S400 SHEETS ARE FOR SLAB DIMENSIONS ONLY.
2. DIMENSIONS SHOWN FOR ROOF DECK ARE TO EDGE OF ANGLE OR PLATE.
3. VERIFY OPENINGS WITH MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS.
SUITE 301
Ste. 275
AuthorChecker
BASEMENT SLAB PLAN
S401-1A
1/8" = 1'-0"
BASEMENT FOUNDATION / SLAB PLAN
1 2 3 4 6 85
E-19
E-X1 E-X6E-X5 E-LL E-MM E-NN E-OO
E-2.5E-2.1
1'-2 3/8" 18'-10" 20'-10" 20'-7" 20'-10" 19'-6" 12'-6" 12'-6" 1'-11 15/16"
18'-10" 20'-10" 20'-7" 20'-10" 19'-6" 12'-6" 12'-6"
1'-0" 4'-7 3/8"
BP1
9' - 4 3/4" 9' - 5 5/8"
BP2
SIDEWALK, REFER TO CIVIL
0'-5 1/2" 2'-5 1/2" 9'-1 5/8"
3' - 4" 8' - 1 1/2"
1' - 2 3/8"
1' - 11 3/4"
8"
1' - 5 15/16" 6" 8"
SUITE 301
Ste. 275
1ST FLOOR SLAB PLAN - PHASE 1A
S402-1A
1ST FLOOR FOUNDATION / SLAB AND FLOOR FRAMING PLAN - PHASE 1A
C1
C2
C3
C5
C6
CA CB CC CD CF CG
J J
CH CJ
C7
C8
E-5
E-5
H H
K K
119 9.1
1'-0 7/8" 2'-0" 7'-6 3/4" 2'-11 1/4"
1'-9 7/16"
0'-6 9/16"
3'-5 7/16" 2'-4"
2'-5 1/16"
2'-7 1/2" 3'-5" 1'-10 3/4"
1'-8 15/16" 0'-10"
5'-5" 6'-3 7/16" 0'-9 1/8" 4'-0 1/16" 2'-3 5/8" 2'-7 3/8" 3'-9 7/8"
.4
.8
.2
.6
.1
.0
.0
.5
7 1/2"
41'-11 7/8"
11 3/16"
1' - 5 3/8"
SUITE 301
Ste. 275
1ST FLOOR SLAB PLAN - PHASE 1B
S402-1B
1ST FLOOR FOUNDATION / SLAB AND FLOOR FRAMING PLAN - PHASE 1B Copy 1
1 2 3 4 6 85
E-X1 E-X6E-X5 E-LL E-MM E-NN E-OO
18'-10" 20'-10" 20'-7" 20'-10" 10'-2 1/4" 2'-3 1/8" 5'-1" 1'-11 5/8"
4'-6 3/8"
7'-4 1/8"
0'-7 1/2"
7"
3' - 4" 8' - 1 1/2"
6 3/4"
ROOF DRAIN OPENINGS
SUITE 301
Ste. 275
2ND FLOOR SLAB PLAN - PHASE 1A
S403-1A
ROOF/FUTURE SECOND FLOOR FRAMING PLAN (T/STL=13'-2 3/4" UNO)
4 6 85
5.5 5.6 5.7 6.5 6.6 9
20'-10" 10'-2 1/4" 2'-3 1/8" 5'-1"
1'-11 5/8"
4'-6 3/8" 7'-4 1/8"
0'-7 1/2"
1'-9 7/16"
EDGE OF ROOF DECK AT CENTLINE OF BEAMS
1' - 4 3/4"
4' - 0"
4' - 0"
SUITE 301
Ste. 275
HIGH ROOF DECK PLAN-PHASE 1A
S404-1A
HIGH ROOF FRAMING PLAN (T/STL=28'-0 3/4" UNO)
E-18E-18
E-17E-17
E-16
E-J.2
N N
H H
I I
12'-6" 1'-9 7/16" 4'-0" 2'-4" 10'-4 5/16" 1'-8 15/16" 13'-3 9/16" 4'-0 1/16"
11 1/4" 1' - 8 5/8"
3' - 0 7/8"
1' - 8 5/8"
5' - 0 1/4"
1' - 0 3/4"
2' - 1"
11"
1' - 11 3/4"
5' - 0 1/4"
Dr