This document appears to be Attachment 3 - Drawings for a Department of Veterans Affairs (VA) Minor Construction project to consolidate the Primary Care Clinic at the Erie VA Medical Center (VAMC).
The project involves constructing a new addition to the first floor of the existing Main Building at the Erie VAMC and renovating a portion of the existing building. The new addition will extend the building towards E 38th Street and the west to the current entry vestibule, providing expanded and integrated Primary Care Clinic space. The project also includes construction of a partial basement to house mechanical equipment and utility closets, as well as reconfiguration of the impacted outdoor areas such as the parking lot, vehicular circulation, and landscaping.
The solicitation number is 36C77624R0007_1, and the project is titled "Y1DA--VHA Minor Construction Project 562-184 Consolidate Primary Care - Erie VAMC". The contracting agency is the VA Technology Acquisition Center Austin.
View the file
Other files
Show all 43
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
E-18
E-17
E-16
E-19
E-X3E-X1
E-12.1
E-X4
E-14
E-15
E-X6E-X5 E-LL E-MM E-NN E-2.1 E-2.5
CONSULT/ EXAM
1N210
RT-02/03
RB-01 P
-0
P
P-01
1N208
1N206
1N204
WHEEL CHAIRS
1N001C
PT-01
PATIENT CORRIDOR
1N2
1N213
1N211
1N209
CONSULT
1N203
TEAMWORK ZONE
1N2.1
CPT-03/RT-01
RB-02 P
BREAKROOM
1N106
P-07
HAC
1N100
RT-01
1N215
CORRIDOR
1N1
PROCEDURE
1N201
PHONE BOOTH
1N001E
RB-01
T S
COFFEE
1N001F
RB-01
G
PC ASST. MANAGER
1N104A
CPT-03
STAFF TOILET
1N102
TRS-01 P
1N205
1N207
ADMIN. OFFICE
1N104
P-04
PATIENT TOILET
1N201A
PT-02
1N200
1N1.1
E-13.8
P-07
LA
R
E
V
IN
Y L
A
H
IC
PC MED. DIRECTOR
1N104C
PC MANAGER
1N104B
HR-01 HR-01 HR-01 HR-01 HR-01 HR-01HR-01 HR-01
HR-01HR-01HR-01HR-01HR-01HR-01
PT-04
HEIGHT/WEIGHT STN.
1N2A
RT-03
J
I
K
7.5
9 10
9.1
E-X2 E-X3.6 E-X5.8
4' - 5"
/1
CG-01 CG-01
CG-01 CG-01CG-01CG-01
CG-01CG-01
CG-01
Floor Finish
Base Finish
Room No.
S Wall FinishW W a ll
F in is h
Room Name
N Wall Finish
INDICATES FINISH ON HORIZONTAL SURFACE
INDICATES FINISH ON VERTICAL SURFACE
CODE
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Submission:
ARCHITECT OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/2
-1
MEP ENGINEER:
BOWMAN FOSTER
6353 Center Drive Norfolk, VA 23502 757-466-7400
HEALTHCARE PLANNER:
EYP
811 West Hargett St.
Raleigh, NC 27603 713-852-3610
ARCHITECT:
CB DESIGN GROUP
421 King Street
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
Erie VA Medical Center 135 East 38th Street, Erie, PA 16504
2345678910111213141516
B
C
D
12345678910111213141516
STRUCTURAL ENGINEER:
HUITT-ZOLLARS
500 W. 7th St., Ste. 300 Fort Worth, TX 76102 817-335-3000
FP/LS ENGINEER:
STANTON ENGINEERING
10280 Old Columbia Rd.
Ste. 275 Columbia, MD 21046 410-290-9304
CIVIL ENGINEER:
INTEGRITY FEDERAL
SERVICES
148 S. Queen St. Ste. 201 Martinsburg, WV 25401 304-725-8456
03/07/2023
VA 562-184
MMKJ
ERIE VAMC - CONSOLIDATED
PRIMARY CARE
CDF SUBMISSION
PARTIAL FINISH FLOOR PLAN - LEVEL
1 AREA B
IF111B
IF
.p d f
1/4" = 1'-0"A16
FINISH PLAN - LEVEL 01 - AREA B
KEY PLAN
PLAN
NORTH
TRUE
NOT TO SCALE
NIC
GENERAL FINISH NOTES
G1 PROVIDE PAINTABLE SEALANT AT ALL DISSIMILAR MATERIALS UNLESS NOTED OTHERWISE.
G2 TERMINATE DIFFERING FLOOR FINISHES BELOW CENTERLINE OF SWING DOORS AND FACE OF
PARTITION AT SLIDING DOORS, UNLESS NOTED OTHERWISE.
G3 SEE FINISH SCHEDULE FOR INDIVIDUAL FINISH INFORMATION. SEE PROJECT
MANUAL/SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
G4 ALL INTERIOR FINISHES SHALL MEET NFPA LIFE SAFETY CODES SPECIFIC TO INTERIOR
FINISHES.
GENERAL FINISH NOTES - PAINT
P1 PAINT NEW AND EXISTING METAL DOORS P-04. REFER TO OPENING SCHEDULE FOR
EXCEPTIONS.
P2 PAINT NEW AND EXISTING METAL DOOR FRAMES P-04. REFER TO OPENING SCHEDULE FOR
P3 PAINT METAL STAIRS AND HANDRAILS P-04.
P4 PAINT GRILLES AND REGISTERS THAT ARE PRIMER FINISHED TO MATCH ADJACENT
SURFACES. REFER TO 'A' SERIES SHEETS FOR EXCEPTIONS.
P5 PAINT METAL WALL-MOUNTED ACCESS DOORS, GRILLES, COVER PLATES, FAN COIL UNITS,
FIRE EQUIPMENT CABINETS, AND ELECTRICAL CABINETS TO MATCH ADJACENT SURFACE.
P6 PAINT ALL WALLS P-01 UNLESS NOTED OTHERWISE.
P7 PAINT GYPSUM BOARD CEILINGS, FURR DOWNS, AND SOFFITS P-02 UNLESS NOTED
OTHERWISE.
P8 PROVIDE A HARD STRAIGHT EDGE LINE WHERE AN ACCENT COLOR MEETS AND ADJACENT
WALL COLOR OR MATERIAL.
P9 BULKHEADS INDICATED TO RECEIVE ACCENT PAINT SHALL HAVE ACCENT PAINT ON BOTTOM
AND ALL SIDES UNLESS OTHERWISE NOTED.
GENERAL FINISH NOTES - TILE
T1 INSTALL ALL TILE FLOORING CENTERED IN ROOMS UNLESS SHOWN OTHERWISE ON
DRAWINGS.
T2 INSTALL TILE FLOORING WITH GRAIN RUNNING IN THE SAME DIRECTION.
T3 ALL TILE ON WALLS TO RUN VERTICALLY UNLESS NOTED OTHERWISE.
T4 CENTER WALL TILE ON WALLS (TYPICAL FOR ALL TILED WALLS).
FINISH CODES
FINISH
CODE DESCRIPTION
PLAM-01 PLASTIC LAMINATE
PLAM-02 PLASTIC LAMINATE
PT-01 PORCELAIN TILE
PT-02 PORCELAIN TILE
PT-03 PORCELAIN TILE
PT-04 PORCELAIN TILE
RB-01 RUBBER BASE
RB-02 RUBBER BASE
RP-01 RESIN PANEL 72"W X 36" H X 3/8"
THICKNESS
RT-01 RESILIENT TILE FLOORING
RT-02 RESILIENT TILE FLOORING
RT-03 RESILIENT TILE FLOORING
SHD-01 WINDOW SHADE
SS-01 SOLID SURFACE
SS-02 SOLID SURFACE
TRS-01 TRANSITION STRIP
TS-01 TACKABLE SURFACE
FINISH CODES
AT-01 ACOUSTIC TILE CEILING
AT-02 ACOUSTIC TILE CEILING
C-01 SEALED CONCRETE
CG-01 CORNER GUARD
CPT-01 CARPET
CPT-02 CARPET
CPT-03 CARPET
EF-01 ENTRANCE FLOORING
FRP-01 FIBER REINFORCED PANEL
GRT-01 GROUT
GT-01 GLASS TILE
GT-02 GLASS TILE
HR-01 HAND RAIL
P-01 TYPICAL WALL PAINT
P-02 TYPICAL CEILING PAINT
P-03 ACCENT PAINT
P-04 ACCENT PAINT
P-05 ACCENT PAINT
P-06 TYPICAL DOOR FRAME PAINT
P-07 ACCENT PAINT
P-08 ACCENT PAINT
SYMBOL LEGEND
F F
2 3 4 6
E E
E-20
E-X1
E-20.1
E-X6E-X5 E-LL E-MM E-NN
MEDICATION ROOM
1N602
1N313
1N311
1N307
1N305
CONSULT/ EXAM (NEG)
1N303
PROCEDURE (NEG)
1N301
1N3.1
CPT-03/RT-01
CLEAN ROOM
1N601
CONCOURSE
1N002
1N309
1N6.1
1N301A
CORRIDOR
1N6
ISOLATION PATIENT CORRIDOR
1N3
WAITING
1N002A
CPT-01
1N316
1N314
1N312
1N310
1N308
1N306
1N304
1N302
1N300
HR-01 HR-01 HR-01 HR-01 HR-01 HR-01 HR-01 HR-01
HR-01HR-01HR-01HR-01HR-01HR-01HR-01
1N3A
ALCOVE
1N6A
1 7
7.5 9
4' - 0" 6' - 0 1/8"
CG-01CG-01 CG-01CG-01
CG-01 CG-01CG-01CG-01
SUITE 301
Ste. 275
148 S. Queen St. Ste. 201
1 AREA C
IF111C
/0
1/4" = 1'-0"D16
FINISH PLAN - LEVEL 01 - AREA C
RP-01 RESIN PANEL 72"W
X 36" H X 3/8"
RT-01 RESILIENT TILE
FLOORING
RT-02 RESILIENT TILE
RT-03 RESILIENT TILE
TS-01 TACKABLE
SURFACE
AT-01 ACOUSTIC TILE
CEILING
AT-02 ACOUSTIC TILE
EF-01 ENTRANCE
FRP-01 FIBER REINFORCED
PANEL
P-01 TYPICAL WALL
PAINT
P-02 TYPICAL CEILING
P-06 TYPICAL DOOR
FRAME PAINT
FINISH CODESGENERAL FINISH NOTES
UPUP
DN
D D
C C
AA
1N414
1N412
1N410
1N408
1N406
1N404
1N402
1N400
TOILET
1N005
PATIENT CORRIDOR
1N4
CONSULT/ EXAM (W)
1N502
1N500
WOMEN'S HEALTH CORRIDOR
1N5
RT-02
STAIRS
1N003
C-01
CONCOURSE
COPIES
1N6.2
1N6.3
1N508A
1N508
1N506
1N504A
1N504
1N500A
TEMPORARY STORAGE
1N007
1N506A
1N502A
SOILED ROOM
1N603
HR-01 HR-01 HR-01 HR-01
HR-01HR-01HR-01HR-01HR-01HR-01HR-01HR-01
HR-01
HR-01HR-01HR-01HR-01HR-01
1N4A
BB
5.5 5.6 5.7 6.5 6.61 7
7 7.5
CG-01CG-01CG-01 CG-01CG-01
SUITE 301
Ste. 275
148 S. Queen St. Ste. 201
1 AREA D
IF111D
1/4" = 1'-0"D16
FINISH PLAN - LEVEL 01 - AREA D
RP-01 RESIN PANEL 72"W
X 36" H X 3/8"
RT-01 RESILIENT TILE
RT-02 RESILIENT TILE
RT-03 RESILIENT TILE
TS-01 TACKABLE
AT-01 ACOUSTIC TILE
AT-02 ACOUSTIC TILE
EF-01 ENTRANCE
FRP-01 FIBER REINFORCED
PANEL
P-01 TYPICAL WALL
P-02 TYPICAL CEILING
P-06 TYPICAL DOOR
FRAME PAINT
FINISH CODESGENERAL FINISH NOTES
E-17E-17
E-16E-16
E-12.1 E-12.1
E-14 E-14
E-15 E-15
E-2.1
E-2.5
E-3.1
E-3.8
E-3.8
E-J.2 E-J.2
E-13.8E-13.8
E-11 E-11
PT-01 PT-01
PT-01 PT-03
PT-03
4' - 4 1/16" 29' - 0"
ALIGN
24' - 0"
19' - 0 1/16"
15' - 0"
12' - 0"
9' - 0"
7' - 0"
3' - 8 1/16"
LI
N
NA
FULL TILE 1' - 6"
CPT-02
EQ 1 FULL TILE EQ
CPT-023 FULL TILES
1'
IL
ID
Q
U
3' - 9"
EF-01
ALIGN ALIGN
I D
WHCHRS
1N000
VEST.
BRKRM.
P. CORR.
TEAMLET
1N001
LOBBY
1N001A
CORR.
PROC. 1N001E
PHONE
COFF.
P. TLT.
1N001B
VOL. DESK
JJ
II
K K
L L
M M
N N
GENERAL NOTES
A. REFER TO SHEET IF100 FOR FINISH SCHEDULE.
B. REFER TO SHEET AE301 FOR FLOOR TRANSITIONS.
C. WHERE TYPE OF FLOOR FINISH, PATTERN OR COLOR ARE DIFFERENT ON OPOSITE SIDES OF
REGULAR DOOR, TERMINATE FLOORING UNDER CENTERLINE OF DOOR. IF IT IS A SLIDING DOOR, TERMINATE FLOORING ON THE OUTSIDE EDGE OF THE WALL.
D. FLOOR PATTERN TO CONTINUE UNDER ALL OPEN WOODWORK/ WORKSURFACES
E. CURTAINWALL/STOREFRONT SYSTEMS SHALL NOT RECEIVE APPLIED WALL BASE
SYMBOLS LEGEND
INDICATES FLOOR FINISHCODE
INDICATES FLOOR FINISH INSTALLATION DIRECTION
SUITE 301
Ste. 275
148 S. Queen St. Ste. 201
PARTIAL FLOOR PATTERN PLAN -
LEVEL 1 AREA A
IP112A
IP
E-18E-18
E-17E-17
E-16E-16
E-X3E-X1
E-12.1 E-12.1
E-X4
E-14 E-14
E-15 E-15
E-13.8E-13.8
GG
EXISTING FLOORING
RT-01 PT-01
4' - 1" 1' - 7"
RT-02 RT-02 RT-02 RT-02
RT-01 RT-01 RT-01 RT-01
RT-03 RT-03 RT-03 RT-03
RT-03RT-03 RT-03 RT-03 RT-03 RT-03RT-03 RT-03
RT-01 RT-02
RT-03 RT-03
RT-02 RT-02 RT-02 RT-02 RT-02 RT-02 RT-02
4' - 5"
RT-02 RT-02 RT-02 RT-02 RT-02 RT-02 RT-02 RT-02 RT-02
EXAM
1N211
EXAM 1N306
EXAM (NEG)
1N206
WAIT.
PROC. 1N001E
PHONE
COFF.
OFFICE
S. TLT
ADMIN
HT/WT
EF-01
JJ
H H
II
K K
L L
M M
N N
E-X2 E-X3.6 E-X5.8
SUITE 301
Ste. 275
148 S. Queen St. Ste. 201
LEVEL 1 AREA B
IP112B
F F
2 3 4 6 85
E-20E-20
E-19E-19
E-X1
E-20.1 E-20.1
GG
ALIGN ALIGN ALIGN
RT-03 RT-03 RT-03 RT-03 RT-03 RT-03
RT-02 RT-02 RT-02 RT-02 RT-02 RT-02
RT-02 RT-02
4' - 0"
EQ FULL TILE EQ
I D
2 FULL TILES
MED. RM.
EXAM1N311
PROC. (NEG)
TLT
CL. RM.
COPY
1N301A
1N3
ISO. P. CORR.
SOIL RM.
1N6A
ALC.
1 7
SUITE 301
Ste. 275
148 S. Queen St. Ste. 201
LEVEL 1 AREA C
IP112C
D D
AA
RT-03 RT-03 RT-03 RT-03 RT-03 RT-03 RT-03 RT-03
RT-03 RT-03 RT-03 RT-03 RT-03
PT-01 CPT-01
RT-01RT-02
RT-02RT-02RT-02
RT-02 RT-02 RT-02 RT-02 RT-02 RT-02 RT-02 RT-02
N A
ALIGN ALIGN ALIGN ALIGN ALIGN
W. EXAM
STRS
TEMP. STOR.
WMN CORR.
BN116
AREAWELL
CONC.
P. TLT. 1N506
BB
5.5 5.6 5.7 6.5 6.61 7
7 7.5
SUITE 301
Ste. 275
148 S. Queen St. Ste. 201
LEVEL 1 AREA D
IP112D
UPUP
QH502
A16
QH501
F16
QH503
E7
E16
QH506
QH504
F16
EXAM 1N211
MED. RM.
1N311
PROC. (NEG)
1N000
VEST.
CL. RM.
STRS
TEMP. STOR.
BRKRM.1N206
WMN CORR.
CONC.
WAIT.1N301A
PROC.
S. TLT
1N001A
A11
A10
A13
ADMIN
QH505
A15
F11
M1840
M4045
M0512
F2000
M4040
M4705
M0515
SUITE 301
Ste. 275
148 S. Queen St. Ste. 201
EQUIPMENT AND SPECIALTIES PLAN
QH101
EQUIPMENT SCHEDULE
JSN DESCRIPTION A
IR
LL
M
MODEL
F0415 CABINET, FILING, LATERAL, FULL
HEIGHT
V V
F0635 FIXED HEIGHT DESK TABLE V V Herman Miller, Inc. DK111.1848N
F0685 24" x 48" ADJUSTABLE HEIGHT
WORKSTATION
F0795 TABLE, DINING V V
F2000 WASTEPAPER BASKET V V
F2010 WASTE PAPER BASKET, STEP-ON V V
F2015 BASKET, WASTEPAPER, METAL/
PLASTIC, 2 SWINGING DOORS
F2310 RACK, PAMPHLET, WALL MOUNTED V V
F2550 SHRED BOX V V
F3010 BOARD, BULLETIN, 48 x 48 V V
F3025 BOARD, BULLETIN, WOOD FRAMED,
36"X24"
F3065 WHITE BOARD/ BULLETIN BOARD,
COMBINATION
F3200 CLOCK, 12" DIAMETER V V
FEC FIRE EXTINGUISHER CABINET C C
K1552 BREWER, COFFEE, AUTO, ELECT, 3
BURNER, FRONT/ BACK
K4665 MICROWAVE, COMMERCIAL V V AMANA
M0506 FLAT SCREEN TELEVISION, 32" V V SAMSUNG UN40J5200
M0508 WALL-MOUNTED TELEMEDICINE
STATION.
V V GlobalMed
M0510 TELEVISION, HD, 40" V V
M0512 TELEVISION, HDTV, LARGE SCREEN, 60" V V
M0515 TELEVISION, HDTV, LARGE SCREEN, 70" V V SAMSUNG UN60J6200
M1801 COMPUTER, MICROPROCESSING, W/
FLAT PANEL MONITOR
M1805 ADJUSTABLE STANDING DESK V V Kimball Office 45W2960WSSAH
M1840 PRINTER/ COPIER/ FAX COMBINATION V V
M2055 WIRE SHELVING, ADJUSTABLE V V
M3073 INFECTIOUS WASTE BASKET, STEP-ON V V
M3150 AUTOMATIC MEDICATION DISTRIBUTION
SYSTEM (BD PYXIS)
V V BECTON, DICKINSON PYXIS
MEDSTATION ES
TOWER
M3155 AUTOMATIC MEDICATION DISTRIBUTION
SYSTEM (BD PYXIS)
M4040 TILT AND ROLL HANDRAIL SCALE W/
BMI, 1000 LB CAPACITY
V V BEFOUR
M4045 SCALE, WHEELCHAIR, 550 LB CAPACITY V V
M4116 MONITOR, VITAL SIGNS, MOBILE V V WELCH ALLYN CONNEX 6000
SERIES ON
ACCESSORY
CABLE
MANAGEMENT
STAND
M4705 PATIENT TRANSPORT CHAIR V V STRYKER PRIME TC
M7401 LIGHT, EXAM V V WELCH ALLYN 44400 GREEN
SERIES 300
M9025 EXAM TABLE V V MIDMARK 626 BARRIER-
FREE EXAM.
CHAIR
R7250 BOTTOM FREEZER REFRIGERATOR, 22
CUBIC FEET
V V WHIRLPOOL WRB322DMB
R7250M FULL SIZE MEDICAL REFRIGERATOR (BD
PYXIS)
EQUIPMENT SCHEDULE
JSN DESCRIPTION A
IR
LL
MODEL
A1010 OUTLET, COMMUNICATION, TYP. C C
A1012 TELEPHONE, WALL MOUNTED, 1 LINE V V
A1015 TELEPHONE, DESK, MULTIPLE LINE V V
A1067 MIRROR, ADA ACCESSIBLE C C
A5075 SOAP DISPENSER V C
A5077 DISPENSER, HAND SANITIZER V C
A5080 PAPER TOWEL DISPENSER V C
A5090 SANITARY NAPKIN DISPENSER V C
A5107 SURGICAL GLOVE DISPENSER, WALL
MOUNTED
A5108 SHARPS WASTE DISPOSAL UNIT, WALL
A5109 GRAB BAR, 1-1/4" DIA., SS, 2 WALL, W/C
ACCESSIBLE
A5145 DOUBLE GARMENT HOOK C C
A5180 CUBICLE, TRACK WITH CURTAIN C C Construction Specialties ON THE RIGHT
TRACK SYSTEM
A5200 TOILET TISSUE DISPENSER V C
A5210 BRACKET, TELEVISION, WALL
MOUNTED, W/ ADJUST ARM
A5220 BRACKET, TELEVISION, WALL BACKING C C
A5225 COMPUTER WITH DOUBLE FLAT PANEL
MONITORS
C02C0 CABINET, U/C/B, 1 SHELF, 1 DRAWER, 1
DO, 36x24x22 - Not Lockable
C02D0 CABINET, U/C/B, 4 DRAWER, 36x24x22 C C
C02Q0 CABINET, SINK, U/C/B, 1 DOOR, 36x18x22 C C
C02Q01 CABINET, ADA, SINK SUPPORT
(MIDMARK)
C C Herman Miller, Inc. BA00
C04P0 CABINET, SINK, U/C/B, 2 DOOR, 36x36x22 C C
C06M0 CABINET THREE DRAWERS - NOT
LOCKABLE
CB020 CABINET, W/H, GLOVE/CUP/TOWEL
DISPENSER
C C MIDMARK OD23
CD020 CABINET, WALL C C MIDMARK OA23
CD040 CABINET, W/H, 2 SHELF, 2 DO, SLOPING
TOP, 38.36.13
COA23 CABINET, WALL (MIDMARK) C C MIDMARK OA23
COA24 CABINET, WALL (MIDMARK) C C MIDMARK OA24
COD23 CABINET, W/H, GLOVE/CUP/TOWEL
DISPENSER (MIDMARK)
C C MIDMARK OD23
CT020 COUNTERTOP, SOLID SURFACE C C
E0123 WORKSTATION V V
E0903 LOCKER, SUPPLY, W/ SHELVES, WALL
MTD., 23"W x 20"D
E0906 LOCKER, SUPPLY, GENERAL, WALL
MTD, 23"W x 20"D
E0912 LOCKER, SUPPLY, MED SURG., WALL
MTD.
E0945 WORKSTATION - MOBILE V V
E0948 UNDER COUNTER STORAGE CART,
MOBILE (MIDMARK)
V V MIDMARK BM42
E1500 RAIL, MOD, W/ MNTD, HX144XD V V
F0206 SIDE CHAIR W/ ARMS, BARIATRIC V V
F0210 CHAIR, SIDE V V
F0225 CHAIR, DINING ROOM V V
F0240 EXECUTIVE SWIVEL CHAIR V V
F0275 CHAIR, SWIVEL, HIGH BACK V V
F0340 SELF ADJUSTING STOOL V V MIDMARK RITTER 277 AIR
LIFT STOOL
F0410 CABINET, FILING, HALF HEIGHT V V Herman Miller, Inc. LQ11D.24BBF
1" = 10'-0"A15
EQUIPMENT PLAN - LEVEL 01
SCOPE
OF WORK
RENOVATION
ADDITION
MIDMARK
QH501 H16
H13
H7
H10
A5108
SHARPS WASTE
DISPOSAL UNIT, WALL
M3073
INFECTIOUS WASTE
BASKET, STEP-ON
E0948
UNDER COUNTER
STORAGE CART, MOBILE
A5075
SOAP DISPENSER
A5080
PAPER TOWEL
F2010
WASTE PAPER BASKET,
STEP-ON
M7401
LIGHT, EXAM F0210
CHAIR, SIDE
M4116
MONITOR, VITAL SIGNS,
MOBILE
E0945
WORKSTATION - MOBILE
F0340
SELF ADJUSTING STOOL
A1012
TELEPHONE, WALL
MOUNTED, 1 LINE
M1801
COMPUTER,
MICROPROCESSING, W/
A5180
CUBICLE, TRACK WITH
CURTAIN
M0506
C02Q01
COD23
COA23
CT020
F0210
F3025
M9025
3' - 3"
F3200
A5145
E13
E10
M0508
WALL-MOUNTED
TELEMEDICINE STATION.
EXAM TABLE
COUNTERTOP, SOLID
LIGHT, EXAMM4116
MOBILEM1801
FLAT SCREEN
TELEVISION, 32"
CABINET, W/H,
GLOVE/CUP/TOWEL
A5210
BRACKET, TELEVISION,
WALL MOUNTED, W/
ADJUST ARM
A5145 M0508
SUITE 301
Ste. 275
148 S. Queen St. Ste. 201
ENLARGED EQUIPMENT PLANS -
EXAM ROOMS
1/2" = 1'-0"F16
ENLARGED EQUIPMENT PLAN - CONSULT/EXAM ROOM
EQUIPMENT LIST - TYP. EXAM ROOM
JSN DESCRIPTION
CUBICLE, TRACK WITH CURTAIN
A1012 TELEPHONE, WALL MOUNTED, 1 LINE
A5075 SOAP DISPENSER
A5080 PAPER TOWEL DISPENSER
A5107 SURGICAL GLOVE DISPENSER, WALL MOUNTED
A5108 SHARPS WASTE DISPOSAL UNIT, WALL MOUNTED
A5145 DOUBLE GARMENT HOOK
A5180 CUBICLE, TRACK WITH CURTAIN
A5210 BRACKET, TELEVISION, WALL MOUNTED, W/ ADJUST ARM
C02Q01 CABINET, ADA, SINK SUPPORT (MIDMARK)
COA23 CABINET, WALL (MIDMARK)
COD23 CABINET, W/H, GLOVE/CUP/TOWEL DISPENSER (MIDMARK)
CT020 COUNTERTOP, SOLID SURFACE
E0945 WORKSTATION - MOBILE
E0948 UNDER COUNTER STORAGE CART, MOBILE (MIDMARK)
F0210 CHAIR, SIDE
F0340 SELF ADJUSTING STOOL
F2010 WASTE PAPER BASKET, STEP-ON
F3025 BOARD, BULLETIN, WOOD FRAMED, 36"X24"
F3200 CLOCK, 12" DIAMETER
M0506 FLAT SCREEN TELEVISION, 32"
M0508 WALL-MOUNTED TELEMEDICINE STATION.
M1801 COMPUTER, MICROPROCESSING, W/ FLAT PANEL MONITOR
M3073 INFECTIOUS WASTE BASKET, STEP-ON
M4116 MONITOR, VITAL SIGNS, MOBILE
M7401 LIGHT, EXAM
M9025 EXAM TABLE
1/2" = 1'-0"H13
IN408 EXAM NORTH INT. ELEVATION
1/2" = 1'-0"H16
IN408 EXAM EAST INT. ELEVATION
1/2" = 1'-0"H10
IN408 EXAM WEST INT. ELEVATION
1/2" = 1'-0"H7
IN408 EXAM SOUTH INT. ELEVATION
1/2" = 1'-0"F11
ENLARGED EQUIPMENT PLAN - EXAM ROOM WITH GLOBALMED WALLDOC UNIT
1/2" = 1'-0"E16
1N213 EXAM EAST INT. ELEVATION (WALL DOC)
1/2" = 1'-0"E13
1N213 EXAM NORTH INT. ELEVATION (WALL DOC)
1/2" = 1'-0"E10
1N213 EXAM WEST INT. ELEVATION (WALL DOC)
1/2" = 1'-0"E7
1N213 EXAM SOUTH INT. ELEVATION (WALL DOC)
EXAM ROOMS WITH GLOBALMED WALLDOC UNIT
1N207 1N314 1N308 1N311 1N305 1N300 1N412 1N406 1N400
NOTES
SEE EQUIPMENT SCHEDULE ON SHEET QH101 FOR FULL DESCRIPTION OF ITEMS
SHOWN ON EQUIPMENT LISTS.
AE512
H7
H16
H13
AE510
A8
A13
AE510
D8
D16
D13
D10
E11
E9
D3
E6
H6
A3
H14
H11
H9
LIGHT, EXAM
F2310
RACK, PAMPHLET, WALL
WALL-MOUNTED
TELEMEDICINE STATION.
7"
RACK, PAMPHLET, WALL
F2010 F0210 F0340
E0945F0340M4116
E0945F0340
F2010 F0340 E0945
M4116F0340M1801 E0945
SUITE 301
Ste. 275
148 S. Queen St. Ste. 201
WOMEN'S EXAM ROOMS
1/2" = 1'-0"A16
ENLARGED EQUIPMENT PLAN - WOMEN'S HEALTH EXAM ROOMS
1/2" = 1'-0"E6
1N504 - WEST INT. ELEVATION
1/2" = 1'-0"E11
1N504 - NORTH INT. ELEVATION
1/2" = 1'-0"E9
1N504 - EAST INT. ELEVATION
1/2" = 1'-0"D3
1N504 - SOUTH INT. ELEVATION
1/2" = 1'-0"H6
1N502 - NORTH INT. ELEVATION
1N502 - EAST INT. ELEVATION
1/2" = 1'-0"E13
1N502 - SOUTH INT. ELEVATION
1/2" = 1'-0"A3
1N502 - WEST INT. ELEVATION
1N500 - NORTH INT. ELEVATION
1/2" = 1'-0"H14
1N500 - EAST INT. ELEVATION
1/2" = 1'-0"H11
1N500 - SOUTH INT. ELEVATION
1/2" = 1'-0"H9
1N500 - WEST INT. ELEVATION
EQUIPMENT LIST - WOMEN'S EXAM ROOM
E0945 WORKSTATION - MOBILE
F2310 RACK, PAMPHLET, WALL MOUNTED
F3025 BOARD, BULLETIN, WOOD FRAMED, 36"X24"
M0506 FLAT SCREEN TELEVISION, 32"
M0508 WALL-MOUNTED TELEMEDICINE STATION.
EQUIPMENT LIST - WOMEN'S EXAM ROOM,...
A5109 GRAB BAR, 1-1/4" DIA., SS, 2 WALL, W/C ACCESSIBLE
ADMIN. OFFICE
PC ASST. MANAGER
STAFF TOILET
A5109
GRAB BAR, 1-1/4" DIA.,
SS, 2 WALL, W/C
A5090
SANITARY NAPKIN
A1067
MIRROR, ADA
A5200
TOILET TISSUE
DOUBLE GARMENT HOOK
WASTEPAPER BASKET
PC MANAGER
PC MED. DIRECTOR
F0415
CABINET, FILING,
LATERAL, FULL HEIGHT
PRINTER/ COPIER/ FAX
COMBINATION
AE512E16
E10
CD040
CABINET, W/H, 2 SHELF, 2
DO, SLOPING TOP,
38.36.13
CD020
CABINET, WALL
A1015
TELEPHONE, DESK,
MULTIPLE LINE
F0635
FIXED HEIGHT DESK
TABLE
F0240
EXECUTIVE SWIVEL
F0410
CABINET, FILING, HALF
F0685
24" x 48" ADJUSTABLE
HEIGHT WORKSTATION
CD020
A1010
OUTLET,
COMMUNICATION, TYP.
F0275
CHAIR, SWIVEL, HIGH
BACK
C06M0
CABINET THREE
DRAWERS - NOT
C06M0
CABINET THREE
DRAWERS - NOT
F2550
SHRED BOX
AE510H6
H12
H8
M1805
ADJUSTABLE STANDING
DESK
WHEEL CHAIRS
AE511
A12
A9
A6
M4705
PATIENT TRANSPORT
PHONE BOOTH
1N001E
COFFEE
K1552
BREWER, COFFEE, AUTO,
ELECT, 3 BURNER,
FRONT/ BACK
AE510F12
SUITE 301
Ste. 275
148 S. Queen St. Ste. 201
OFFICE SUITE AND LOBBY
ENLARGED EQUIPMENT PLAN - OFFICE SUITE & TOILET
1/2" = 1'-0"E7
ENLARGED EQUIPMENT PLAN - V. DESK
EQUIPMENT LIST - VOL DESK
A1010 OUTLET, COMMUNICATION, TYP.
A1015 TELEPHONE, DESK, MULTIPLE LINE
C06M0 CABINET THREE DRAWERS - NOT LOCKABLE
F0275 CHAIR, SWIVEL, HIGH BACK
F2000 WASTEPAPER BASKET
F2550 SHRED BOX
M1805 ADJUSTABLE STANDING DESK
EQUIPMENT LIST - OFFICE SUITE
CD040 CABINET, W/H, 2 SHELF, 2 DO, SLOPING TOP, 38.36.13
F0240 EXECUTIVE SWIVEL CHAIR
F0410 CABINET, FILING, HALF HEIGHT
F0415 CABINET, FILING, LATERAL, FULL HEIGHT
F0635 FIXED HEIGHT DESK TABLE
F0685 24" x 48" ADJUSTABLE HEIGHT WORKSTATION
M1840 PRINTER/ COPIER/ FAX COMBINATION
EQUIPMENT LIST - STAFF TOILET
A1067 MIRROR, ADA ACCESSIBLE
A5090 SANITARY NAPKIN DISPENSER
A5200 TOILET TISSUE DISPENSER
1/2" = 1'-0"A11
ENLARGED EQUIPMENT PLAN - PATIENT TOILET
ENLARGED EQUIPMENT PHONE BOOTH & COFFEE STATION
EQUIPMENT LIST - PHONE & COFFEE BOOTH
CABINET, ADA, SINK SUPPORT (MIDMARK)
C02Q0 CABINET, SINK, U/C/B, 1 DOOR, 36x18x22
K1552 BREWER, COFFEE, AUTO, ELECT, 3 BURNER, FRONT/ BACK
A7
V. DESK AXONOMETRICS
B14
PHONE & COFFEE BOOTH AXONOMETRICS
EQUIPMENT LIST - PATIENT TOILET
F0206
M0510
TELEVISION, HD, 40"
A5145A5145
A5220
BRACKET, TELEVISION,
WALL BACKING
CLEAN ROOM
MEDICATION ROOM
M2055
M2055M2055M2055
E0912
E0906
E0903
E1500
R7250M
M3150
M3155
F2550
TEMPORARY
STORAGE
M0510
A5220
M2055M2055
M3155
M3150
R7250M
SUITE 301
Ste. 275
148 S. Queen St. Ste. 201
STAFF SUPPORT SPACES
1/2" = 1'-0"A13
ENLARGED EQUIPMENT PLAN - CONSULT
1/2" = 1'-0"F16
ENLARGED EQUIPMENT PLAN - MED. ROOM/CLEAN ROOM
ENLARGED EQUIPMENT PLAN - COPIES AND SOILED ROOM
EQUIPMENT LIST - MED. ROOM
M3150 AUTOMATIC MEDICATION DISTRIBUTION SYSTEM (BD PYXIS)
M3155 AUTOMATIC MEDICATION DISTRIBUTION SYSTEM (BD PYXIS)
R7250M FULL SIZE MEDICAL REFRIGERATOR (BD PYXIS)
EQUIPMENT LIST - CLEAN ROOM
E0903 LOCKER, SUPPLY, W/ SHELVES, WALL MTD., 23"W x 20"D
E0906 LOCKER, SUPPLY, GENERAL, WALL MTD, 23"W x 20"D
E0912 LOCKER, SUPPLY, MED SURG., WALL MTD.
E1500 RAIL, MOD, W/ MNTD, HX144XD
M2055 WIRE SHELVING, ADJUSTABLE
EQUIPMENT LIST - CONSULT
A5210 BRACKET, TELEVISION, WALL MOUNTED, W/ ADJUST ARM
A5220 BRACKET, TELEVISION, WALL BACKING
F0206 SIDE CHAIR W/ ARMS, BARIATRIC
M0510 TELEVISION, HD, 40"
EQUIPMENT LIST - COPY ALCOVE
F2550 SHRED BOX
M1840 PRINTER/ COPIER/ FAX COMBINATION
EQUIPMENT LIST - SOILED
1/2" = 1'-0"A10
ENLARGED EQUIPMENT PLAN - TEMP. STORAGE
EQUIPMENT LIST - TEMP. STORAGE
CONSULT ROOM AXONOMETRICS
E8
MED. ROOM/CLEAN ROOM AXONOMETRICS
K4665
F2015
A1012A1010
F3065
C04P0
R7250
F0225
F0795
QH505 H7
C02D0
F0795
F0225
CB020
C04P0
C02C0
SS-02
PLAM-02SCHEDULED BASE
2' - 0" 1' - 6" 3' - 0" 1' - 6"
2' - 0" 1' - 6" 3' - 0" 1' - 6"
BACKSPLASH - CT-04
SCHEDULED BASE
SUITE 301
Ste. 275
148 S. Queen St. Ste. 201
STAFF AREAS
QH505
1/2" = 1'-0"A15
ENLARGED EQUIPMENT PLAN - BREAK ROOM
EQUIPMENT LIST - BREAKROOM
C02C0 CABINET, U/C/B, 1 SHELF, 1 DRAWER, 1 DO, 36x24x22 - Not Lockable
C02D0 CABINET, U/C/B, 4 DRAWER, 36x24x22
C04P0 CABINET, SINK, U/C/B, 2 DOOR, 36x36x22
F0225 CHAIR, DINING ROOM
F0795 TABLE, DINING
F2015 BASKET, WASTEPAPER, METAL/ PLASTIC, 2 SWINGING DOORS
F3065 WHITE BOARD/ BULLETIN BOARD, COMBINATION
K1552 BREWER, COFFEE, AUTO, ELECT, 3 BURNER, FRONT/ BACK
K4665 MICROWAVE, COMMERCIAL
R7250 BOTTOM FREEZER REFRIGERATOR, 22 CUBIC FEET
BREAK ROOM AXONOMETRICS
1/2" = 1'-0"H7
EQUIPMENT ELEVATION - BREAKROOM 1N106 EAST
1/2" = 1'-0"H12
EQUIPMENT ELEVATION - BREAKROOM 1N106 NORTH
EQUIPMENT ELEVATION - BREAKROOM 1N106 WEST
PROCEDURE
SIDE CHAIR W/ ARMS,
BARIATRIC
TOILET TISSUE
AE511
H6
H9 H16
A5225
COMPUTER WITH
DOUBLE FLAT PANEL
MONITORS
QH506 E16QH506
QH506E12
TILT AND ROLL HANDRAIL
SCALE W/ BMI, 1000 LB
CAPACITY
CABINET, W/H,
GLOVE/CUP/TOWEL
D3
F3010
SUITE 301
Ste. 275
148 S. Queen St. Ste. 201
AuthorChecker
PROCEDURE ROOMS
ENLARGED EQUIPMENT PLAN - PROCEDURE ROOM
EQUIPMENT LIST - PROCEDURE ROOM
A5225 COMPUTER WITH DOUBLE FLAT PANEL MONITORS
F0206 SIDE CHAIR W/ ARMS, BARIATRIC
F3010 BOARD, BULLETIN, 48 x 48
EQUIPMENT LIST - PROCEDURE ROOM, TOILET
PROCEDURE ROOM AXONOMETRICS
IN201 PROCEDURE EAST INT. ELEVATION
IN201 PROCEDURE NORTH INT. ELEVATION
1/2" = 1'-0"H12
IN201 PROCEDURE SOUTH INT. ELEVATION
1/2" = 1'-0"E12
IN201 PROCEDURE WEST INT. ELEVATION
DESIGN CRITERIA
1. 2018 INTERNATIONAL BUILDING CODE WITH CITY OF ERIE AMMENDMENTS
2. LIVE LOAD PARAMETERS - IBC 2018 DESIGN LIVE LOADS - ASCE 7-16
GROUND SNOW---------------------------------------------------------------- 40 PSF
3. RAIN LOAD PARAMETERS - ASCE 7-16
15-MINUTE PRECIPITATION INTENSITY ----------------------------- 5.37 IN/HR
60-MINUTE PRECIPITATION INTENSITY ----------------------------- 2.59 IN/HR
4. WIND LOAD PARAMETERS - ASCE 7-16
ULTIMATE DESIGN WIND SPEED -------------------------------------- 117 MPH
RISK CATEGORY ------------------------------------------------------------- III
EXPOSURE CATEGORY --------------------------------------------------- B
5. SEISMIC DESIGN PARAMETERS - VA HANDBOOK H-18-8, ASCE 7-16
SEISMIC SPECTRAL ACCELERATIONS
Ss -------------------------------------------------------------------------- 0.107g S1 -------------------------------------------------------------------------- 0.039g
RISK CATEGORY ------------------------------------------------------------- III
Ie -------------------------------------------------------------------------- 1.25
SITE CLASS -------------------------------------------------------------------- D
DESIGN SPECTRAL ACCELERATIONS
SDS ------------------------------------------------------------------------ 0.114g SD1 ----------------------------------------------------------------------- 0.063g TL ------------------------------------------------------------------------- 12 sec
SEISMIC DESIGN CATEGORY ------------------------------------------ A
6. THE STRUCTURE SHOULD NOT BE CONSIDERED TO BE STABLE DURING CONSTRUCTION
UNTIL ALL ELEMENTS ARE IN PLACE AND CONNECTED. THE CONTRACTOR IS RESPONSIBLE
FOR ALL TEMPORARY CONSTRUCTION BRACING REQUIRED.
NOTE DESCRIPTION
1. REFER TO GEOTECHNICAL ENGINEERING STUDY BY ECS MID-ATLANTIC, LLC. PROJECT
NUMBER NO. 40:1938 DATED MAY 26, 2020 FOR DETAILED DESCRIPTION OF SUB-SURFACE
SOIL CONDITIONS.
2. THE CONTRACTOR SHALL PROVIDE A LICENSED GEOTECHNICAL ENGINEER TO VERIFY THAT
THE BUILDING SUBGRADE PREPARATION IS SUITABLE AND THAT APPROPRIATE BEARING
MATERIAL IS ACHIEVED PRIOR TO SLAB AND FOUNDATION POURS.
3. SPREAD FOOTINGS SHALL BEAR ON COMPETENT NATURAL SOILS OR NEW STRUCTURAL
FILL. IF EXISTING UNCONTROLLED FILL MATERIAL IS ENCOUNTERED BENEATH THE FOOTING,
EXISTING FILL SHALL BE UNDERCUT TO NATURAL SOILS AND THE RESULTING OVER-
EXCAVATION BE BACKFILLED WITH LEAN CONCRETE OR COMPACTED STRUCTURAL FILL TO
THE PLANNED BEARING LOCATION OF THE FOOTING.
4. ALLOWABLE BEARING CAPACITY OF SPREAD FOOTINGS ON NATURAL SOILS OR
STRUCTURAL FILL IS 3,000 PSF.
5. STRUCTURAL FILL SHALL CONSIST OF AN APPROVED MATERIAL FREE OF ORGANIC MATTER,
DEBRIS, COBBLES, AND ROCK FRAGMENTS GREATER THAN 6 INCHES. IT SHALL HAVE A
LIQUID LIMIT LESS THAN OR EQUAL TO 40 AND A PLASTICITY INDEX LESS THAN OR EQUAL TO
20. UNACCEPTABLE FILL MATERIALS INCLUDE TOPSOIL AND ORGANIC MATERIALS (OH, OL),
AND HIGH PLASTICITY SILT (MH) OR CLAY (CH).
6. ON-SITE MATERIALS MAY BE REUSED AS STRUCTURAL FILL IF THEY CONFORM TO THE
CRITERIA OUTLINED ABOVE.
7. FILL MATERIALS SHALL BE PLACED IN LIFTS NOT EXCEEDING 8 INCHES AND MOISTURE
CONDITIONED TO WITHIN ± 2% OF THE OPTIMUM MOISTURE CONTENT. THE SOILS SHALL BE
COMPACTED TO A MINIMUM OF 95% OF THE MAXIMUM DRY DENSITY IN ACCORDANCE WITH
ASTM D698, STANDARD PROCTOR METHOD. AREAS TO RECEIVE NEW FILL IN EXCESS OF 8
FEET SHOULD BE COMPACTED TO 98% OF THE MAXIMUM DRY DENSITY.
8. FOUNDATION CONCRETE SHALL BE PLACED THE SAME DAY THAT EXCAVATION ARE MADE.
9. EXISTING PAVEMENTS, SITE FEATURES, UNUSED UTILITIES AND UNSUITABLE BACKFILL
MATERIALS SHALL BE DEMOLISHED AND REMOVED PRIOR TO SUBGRADE PREPARATIONS.
10. SUBGRADE PREPARATION SHALL CONSIST OF STRIPPING EXISTING VEGETATION, ROOTMAT, TOPSOIL, DEMOLITION DEBRIS, PAVEMENTS, AND ANY OTHER SOFT OR UNSUITABLE
MATERIAL FROM THE PROPOSED BUILDING AREA. THE STRIPPING SHALL EXTEND A MINIMUM
OF 10 FEET BEYOND THE PLANNED LIMITS OF STRUCTURES AND PAVEMENTS.
11. THE EXPOSED SUBGRADE SHALL BE THOROUGHLY PROOFROLLED WITH CONSTRUCTION
EQUIPMENT HAVING A MINIMUM AXLE LOAD OF 10 TONS IN TWO PERPENDICULAR
DIRECTIONS AND OBSERVED BY THE GEOTECHNICAL ENGINEER. ANY AREA IDENTIFIED
WITH UNSTABLE SUBGRADE BY THE PROOFROLLING SHALL BE MARKED FOR REPAIR PRIOR
TO PLACING SELECT FILL OR CONSTRUCTION MATERIALS. METHODS OF REPAIR FOR
UNSTABLE SUBGRADE SHALL BE DETERMINED WITH THE GEOTECHNICAL ENGINEER.
12. SLABS-ON-GROUND SHALL BE PLACED ON A MINIMUM OF 6 INCHES OF GRANULAR MATERIAL
WITH A MAXIMUM AGGREGATE SIZE OF 1.5 INCHES AND NO MORE THAN 2% FINES. A 15 MIL
VAPOR BARRIER SHALL BE PLACED BETWEEN THE GRANULAR MATERIAL AND THE
CONCRETE SLAB.
SUBGRADE AND FOUNDATION PREP NOTES
1. UNLESS NOTED OTHERWISE, ALL DETAILING, FABRICATION, AND PLACING OF REINFORCING
STEEL SHALL CONFORM TO "DETAILS AND DETAILING OF CONCRETE REINFORCEMENT" (ACI
315) AND "MANUAL OF ENGINEERING AND PLACING DRAWINGS FOR REINFORCED CONCRETE
STRUCTURES" (ACI 315R).
2. UNLESS NOTED OTHERWISE, ALL CONCRETE SHALL DEVELOP A MINIMUM COMPRESSIVE
STRENGTH OF 4000 PSI IN 28 DAYS.
3. UNLESS NOTED OTHERWISE, ALL REINFORCING STEEL SHALL BE DEFORMED BARS
CONFORMING TO ASTM A615 GRADE 60, INCLUDING SUPPLEMENTARY REQUIREMENTS.
4. UNLESS NOTED OTHERWISE, ALL SPLICES OF REINFORCING STEEL SHALL BE CLASS B
TENSION LAP SPLICES (12" MIN).
5. UNLESS NOTED OTHERWISE, ALL REINFORCING STEEL HOOKS SHALL BE ACI STANDARD 90°
HOOKS.
6. ALL OPENINGS IN CONCRETE WHERE GREATEST DIMENSION EXCEEDS 1'-0" SHALL HAVE 2- #
5 BARS ON EACH SIDE AND AT EACH CORNER. BARS SHALL EXTEND THE FULL EMBEDMENT
LENGTH (2'-0" MIN.) BEYOND EDGE OF OPENING.
7. UNLESS NOTED OTHERWISE, PROVIDE A 3/4"x3/4" CHAMFER AT ALL EXPOSED EXTERNAL
CORNERS.
8. ALL SLOTS, SLEEVES, AND OTHER EMBEDDED ITEMS SHALL BE SET PRIOR TO CONCRETE
PLACEMENT. SEE ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND VENDOR DRAWINGS
FOR SIZES AND LOCATIONS.
9. UNLESS NOTED OTHERWISE, CONCRETE COVER OVER STEEL REINFORCEMENT SHALL
CONFORM TO THE MINIMUM REQUIREMENTS OF ACI 318.
10. SIZE AND PLACEMENT OF ALL CONCRETE REINFORCEMENT AND EMBEDS SHALL BE
INSPECTED AND APPROVED PRIOR TO PLACING CONCRETE.
CONCRETE NOTES
1. ALL DETAILING, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL CONFORM TO
THE REQUIREMENTS OF THE AISC SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS,
AND WITH ALL LOCAL LAWS AND ORDINANCES. WHERE CONFLICTING REQUIREMENTS
OCCUR, THE MORE STRINGENT REQUIREMENT SHALL APPLY.
2. ALL W SHAPES SHALL CONFORM TO THE REQUIREMENTS OF ASTM A992 GRADE 50. ALL C
SHAPES SHALL CONFORM TO THE REQUIREMENTS OF ASTM A36.
3. ALL ANGLES AND PLATES SHALL CONFORM TO THE REQUIREMENTS OF ASTM A36 UNLESS
NOTED OTHERWISE.
4. ALL HOLLOW STRUCTURAL STEEL (HSS) SHALL CONFORM TO THE REQUIREMENTS OF ASTM
A500 GRADE B, Fy=46 KSI OR ASTM 1085.
5. ALL STEEL PIPE SHALL CONFORM TO ASTM A53 GRADE B
6. ALL WELDS SHALL CONFORM TO THE AMERICAN WELDING SOCIETY'S D1.1 "STRUCTURAL
WELDING CODE - STEEL"
7. ALL HIGH STRENGTH BOLTS SHALL CONFORM TO ASTM A325. UNLESS NOTED OTHERWISE,
BOLTS SHALL BE 3/4" DIA. AND HOLES SHALL BE 1/16" LARGER THAN BOLT SIZE. BOLTED
CONNECTIONS ARE DESIGNED AS BEARING TYPE WITH THREADS IN SHEAR PLANE,
WASHERS SHALL BE INSTALLED UNDER NUTS OF FASTENERS WHEN REQUIRED BY THE
SPECIFICATION FOR STRUCTURAL JOINTS. ALL HIGH STRENGTH BOLTS SHALL BE
TIGHTENED TO THE SNUG TIGHT CONDITION.
8. UNLESS NOTED OTHERWISE, ALL SHOP CONNECTIONS SHALL BE MADE WITH WELDS OR
HIGH STRENGTH BOLTS.
9. UNLESS NOTED OTHERWISE, ALL FIELD CONNECTIONS SHALL BE MADE WITH HIGH
STRENGTH BOLTS.
10. NO OPENINGS MAY BE CUT IN STRUCTURAL MEMBERS UNLESS SHOWN ON THE DRAWINGS.
11. GUSSET PLATES SHALL BE 3/8" MINIMUM THICKNESS.
12. ALL ELEVATIONS IN THE BUILDING(S) ARE BASED ON A DATUM ELEVATION OF 100'-0" AT
FINISHED FLOOR.
13. ALL EXPOSED STRUCTURAL STEEL ON THE EXTERIOR OF THE BUILDING SHALL BE HOT DIP
GALVANIZED G-90 UNO.
14. STEEL FRAME IS NOT SELF SUPPORTING. ROOF DECK, FLOOR SLAB, AND SHEAR WALLS
ARE REQUIRED FOR LATERAL STABILITY OF THE FRAME AGAINST WIND AND SEISMIC
FORCES. CONTRACTOR SHALL PROVIDE ALL TEMPORARY BRACING REQUIRED TO MAINTAIN
THE STABILITY OF THE STRUCTURAL SYSTEM(S) UNTIL ALL ELEMENTS REQUIRED FOR
STRUCTURAL STABILITY ARE IN PLACE.
15. COLUMN ANCHOR BOLTS ARE DESIGNED FOR A COMPLETE CONDITION, ONLY.
CONTRACTOR SHALL PROVIDE ALL TEMPORARY BRACING REQUIRED TO MAINTAIN
STABILITY UNTIL ALL ELEMENTS REQUIRED FOR STRUCTURAL STABILITY ARE IN PLACE.
STRUCTURAL STEEL
STRUCTURAL ABBREVIATIONS
(ALL ABBREVIATIONS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS)
AB ANCHOR BOLT
ADDL ADDITIONAL
ADJ ADJACENT
AFF ABOVE FINISH FLOOR
APPROX APPROXIMATE(LY)
ARCH ARCHITECTURAL
ASTM AMERICAN SOCIETY
OF TEST MATERIALS
BB BACK TO BACK
BC BOTTOM CHORD
BF BRACED FRAME
BL BASE LINE
BLDG BUILDING
BM BEAM
BOD BOTTOM OF DECK
BOTT BOTTOM
BP BASE PLATE
BRG BEARING
BF BRACE FRAME
BRKT BRACKET
BS BOTH SIDES
BSMT BASEMENT
BVL BEVEL
BW BOTH WAYS
C COMPRESSION
CJ CONSTRUCTION JOINT
CL CENTERLINE
CLR CLEAR OR CLEARANCE
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS
CONT'D CONTINUED
CONN CONNECTION
CP COMPLETE PENETRATION
CTRJ CONTROL JOINT
CY CUBIC YARD
D DEPTH
DBL DOUBLE
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DL DEAD LOAD
DN DOWN
DP DAMP PROOFING
DWG DRAWING(S)
DWL DOWEL
E EAST
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
ELEC ELECTRICAL
EL, ELEV ELEVATION
EOD EDGE OF DECK
EOS EDGE OF SLAB
EQ EQUAL
EQUIP EQUIPMENT
EW EACH WAY
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FAB FABRICATION
FD FLOOR DRAIN
FDN FOUNDATION
FF FINISH FLOOR
FF FAR FACE
FF EL FINISH FLOOR ELEVATION
FIN FINISH(ED)
FS FAR SIDE
FT FOOT
FTG FOOTING
GA GAGE
GALV GALVANIZED
GB GRADE BEAM
HORIZ HORIZONTAL
HP HIGH POINT
HT HEIGHT
HS HEADED STUD
HSS HOLLOW STEEL SECTION
O
ID INSIDE DIAMETER
IF INSIDE FACE
IN INCH
INT INTERIOR
JT JOINT
JST JOIST
K KIPS (1000 LBS)
KO KNOCKOUT
KSI KIPS PER SQARE INCH
LB,# POUND
LD DEVELOPMENT LENGTH
LDG LANDING
LH LEFT HAND
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG LONGITUDINAL
LP LOW POINT
LW LONG WAY
LWC LIGHTWEIGHT CONCRETE
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL
PLUMBING
MEZZ MEZZANINE
MF MOMENT FRAME
MFR MANUFACTURE(R)
MID MIDDLE
MIN MINIMUM
MISC MISCELLANEOUS
MS MIDDLE STRIP
MT STRUCTURAL TEE CUT FROM
MISCELLANEOUS STEEL
MF MOMENT FRAME
MO MASONRY OPENING
N/A NOT APPLICABLE
NF NEAR FACE
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OPNG OPENING
OPP OPPOSITE
OH OPPOSITE HAND
OPT OPTIONAL
PC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PERP PERPENDICULAR
PG PRESTRESSED GIRDER
PL PLATE
PLG PLUMBING
PMJ PRE-MOLDED JOINT FILLER
PREL PRELIMINARY
PRM PREMOLDED
PROJ PROJECTION
PSF POUNDS PER SQUARE FOOT
PT POINT
PVC POLYVINYL CHLORIDE
PVT PAVEMENT
R RISER
RAD RADIUS
RD ROOF DRAIN
RE REFER
REINF REINFORCING (ED, MENT)
REM REMINDER
REQD REQUIRED
REV REVISION
RH RIGHT HAND
RJ RUSTICATION JOINT
RND ROUND
RO ROUND OPENING
RW RETAINING WALL
K
S SOUTH
SC SHEAR CONNECTORS
SCH SCHEDULE(D)
SECT SECTION
SHT SHEET
SIM SIMILAR
SJ SAW JOINT
SL SLOPE
SPA SPACE
SPEC SPECIFICATION(S)
SPL SPECIAL
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STIFF STIFFENER
STIR STIRRUP
STL STEEL
STR STRUCTURAL
STRUCT STRUCTURAL
SW SHEAR WALL
SYM SYMMETRICAL
T TREAD(S)
T/ TOP OF
T/CONC TOP OF CONCRETE
T/FD TOP OF FLOOR DRAIN
T/FTG TOP OF FOOTING
T/SLAB TOP OF SLAB
T&B TOP AND BOTTOM
TEMP TEMPERATURE
THK THICKNESS
THRD THREADED
TN TENSION
TOS TOP OF STEEL
TRANS TRANSVERSE
TS STRUCTURAL TUBING
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
USGS UNITED STATES
GEOLOGICAL SOCIETY
VERT VERTICAL
W WEST, WIDTH
WF WIDE FLANGE
WF WALL FOOTING
W/ WITH
W/O WITHOUT
WP WORK POINT
WT WEIGHT
WT STRUCTURAL TEE CUT FROM
WIDE FLANGE BEAM
WWF WELDED WIRE FABRIC
YD YARD
1. ALL STEEL DECKING SHALL COMPLY WITH THE SPECIFICATIONS OF THE STEEL DECK
INSTITUTE (SDI) FOR DESIGN AND ERECTION.
2. STEEL DECK FOR THE SECOND AND THIRD FLOOR SHALL BE 1 1/2" DEEP, 20 GAGE, TYPE VL, WITH 4" TOTAL SLAB DEPTH (t = 2 1/2") AND REINFORCED WITH 6x6-W1.4xW1.4 UNLESS
NOTED OTHERWISE. PROVIDE ADDITIONAL #4 BARS @ 12" OC OVER THE STEEL GIRDERS
PER H8/S551.
3. DECK SHALL BE FASTENED TO FRAMING WITH POWDER ACTUATED FASTENERS OR 5/8"
PUDDLE WELDS WITH A 36/4 LAYOUT AND 4 SIDELAP CONNECTIONS PER SPAN.
4. DECK SPECIFIED HAS BEEN DETERMINED ON THE BASIS OF A 3 SPAN CONDITION. DECK
SUPPLIER SHALL USE HEAVIER GAGE IF REQUIRED FOR ONE OR TWO SPAN CONDITION.
STEEL FLOOR DECK NOTES
1. DRAWINGS AND GENERAL PROVISIONS OF CONTRACT, INCLUDING GENERAL AND
SUPPLEMENTARY CONDITIONS AND DIVISION 1 SPECIFICATIONS SECTIONS, APPLY TO THIS
SECTION.
2. COLD FORMED STEEL SHALL COMPLY WITH THE STEEL STUD MANUFACTURER'S
ASSOCIATION AND SECTION 2210 OF THE IBC.
3. TYPES OF COLD-FORMED METAL FRAMING UNITS INCLUDE THE FOLLOWING:
a. C-SHAPED STEEL JOIST.
b. STEEL TRACK.
c. C-SHAPED STEEL STUD WITH OR WITHOUT STIFFENERS.
4. SYSTEM COMPONENTS: MANUFACTURER'S STANDARD LOAD-BEARING STEEL JOISTS OF
TYPE, SIZE, SHAPE, AND GAUGE AS INDICATED. WITH EACH TYPE OF METAL FRAMING
REQUIRED, PROVIDE MANUFACTURER'S STANDARD, STEEL RUNNERS (TRACKS), BLOCKING,
LINTELS, CLIP ANGLES, SHOES, REINFORCEMENTS, FASTENERS, AND ACCESSORIES FOR
APPLICATIONS INDICATED, AS NEEDED TO PROVIDE A COMPLETE METAL FRAMING SYSTEM.
5. MATERIALS AND FINISHES:
a. FOR 16-GAUGE AND HEAVIER UNITS, FABRICATE METAL FRAMING
COMPONENTS OF STRUCTURAL QUALITY STEEL SHEET WITH A MINIMUM
YIELD POINT OF 50,000 PSI;ASTM A1003, ASTM A1011, ASTM A1008, OR ASTM
A653.
b. FOR 18-GAUGE AND LIGHTER UNITS, FABRICATE METAL FRAMING
COMPONENTS OF COMMERCIAL QUALITY STEEL SHEET WITH A MINIMUM
YIELD POINT OF 33,000 PSI; ASTM A1003, ASTM A1011, ASTM A1008, OR ASTM
A653.
c. PROVIDE GALVANIZED FINISH TO METAL FRAMING COMPONENTS
COMPLYING WITH ASTM A653 FOR MINIMUM G60 COATING.
d. PROVIDE PRIME-COATED FINISHED WITH ONE COAT OF SHOP-APPLIED RED-
OXIDE, ZINC-CHROMATE, OR OTHER SIMILAR RUST INHIBITIVE PRIMER.
6. FINISH OF INSTALLATION ACCESSORIES TO MATCH THAT OF MAIN FRAMING COMPONENTS,
UNLESS OTHERWISE INDICATED.
a. FASTENERS: PROVIDE NUTS, BOLTS, WASHERS, SCREWS AND OTHER
FASTENERS WITH CORROSION-RESISTANT PLATED FINISH.
b. ELECTRODES FOR WELDING: COMPLY WITH AWS CODE AND AS
RECOMMENDED BY STUD MANUFACTURER.
c. GALVANIZING REPAIR: WHERE GALVANIZED SURFACES ARE DAMAGED, PREPARE SURFACES AND REPAIR IN ACCORDANCE WITH PROCEDURES
SPECIFIED IN ASTM A780.
7. FRAMING COMPONENTS MAY BE PREFABRICATED INTO ASSEMBLIES BEFORE ERECTION.
FABRICATE PANELS PLUMB, SQUARE, TRUE TO LINE, AND BRACED AGAINST RACKING WITH
JOINTS WELDED. PERFORM LIFTING OF PREFABRICATED UNITS TO PREVENT DAMAGE OR
DISTORTION.
8. FABRICATE UNITS IN JIG TEMPLATES TO HOLD MEMBERS IN PROPER ALIGNMENT AND
POSITION AND TO ASSURE CONSISTENT COMPONENT PLACEMENT.
9. ATTACH SIMILAR COMPONENTS BY WELDING. ATTACH DISSIMILAR COMPONENTS BY
WELDING, BOLTING, OR SCREW FASTENERS, AS STANDARD PER MANUFACTURER.
10. WIRE TYING OF FRAMING COMPONENTS IS NOT PERMITTED.
11. FABRICATION TOLERANCES: FABRICATE UNITS TO A MAXIMUM ALLOWABLE TOLERANCE
VARIATION FROM PLUMB, LEVEL, AND TRUE TO LINE OF 1/8 INCH IN 10 FEET.
12. INSTALL METAL FRAMING SYSTEMS IN ACCORDANCE WITH MANUFACTURER'S PRINTED OR
WRITTEN INSTRUCTIONS AND RECOMMENDATIONS.
13. INSTALL CONTINUOUS TRACKS SIZED TO MATCH STUDS. ALIGN TRACKS ACCURATELY TO
LAYOUT AT BASE AND TOPS OF STUDS. SECURE TRACKS AS RECOMMENDED BY STUD
MANUFACTURER FOR TYPE OF CONSTRUCTION INVOLVED, EXCEPT DO NOT EXCEED 16
INCHES O.C. SPACING FOR NAIL OR POWDER-DRIVEN FASTENERS AND FOR OTHER TYPES
OF ATTACHMENT. PROVIDE FASTENERS AT CORNERS AND ENDS OF TRACKS. ATTACH
TRACKS TO FOUNDATION WALL WITH MINIMUM 1/2"Øx10" LONG ANCHOR BOLTS AT 32" O.C.
MAX SPACING. THERE SHALL BE A MINIMUM OF TWO BOLTS PER PIECE WITH ONE BOLT
LOCATED WITHIN 2" OF EACH END OF EACH PIECE.
14. INSTALLATION OF WALL STUDS: SECURE STUDS TO TRACKS BY EITHER WELDING OR
SCREW FASTENING AT BOTH INSIDE AND OUTSIDE FLANGES.
15. PROVIDE DEFLECTION ALLOWANCE BELOW SUPPORTED HORIZONTAL BUILDING FRAMING IN
CEILING OR HEAD TRACK FOR NON LOAD-BEARING FRAMING.
16. WHERE JOIST SYSTEM ABUTS STRUCTURAL COLUMNS OR WALLS, INCLUDING MASONRY
WALLS, ANCHOR ENDS OF STIFFENERS TO SUPPORTING STRUCTURE.
17. INSTALL SUPPLEMENTARY FRAMING, BLOCKING, AND BRACING IN METAL FRAMING SYSTEM
WHERE EVER WALL OR PARTITIONS ARE INDICATED TO SUPPORT FIXTURES, EQUIPMENT,
SERVICES, CASEWORK, HEAVY TRIM AND FURNISHINGS, AND SIMILAR WORK REQUIRING
ATTACHMENT TO THE WALL OR PARTITION. WHERE TYPE OF SUPPLEMENTARY SUPPORT IS
NOT OTHERWISE INDICATED, COMPLY WITH STUD MANUFACTURER'S RECOMMENDATIONS
AND INDUSTRY STANDARDS IN EACH CASE, CONSIDERING WEIGHT OR LOADING RESULTING
FROM ITEM SUPPORTED.
COLD FORMED STEEL FRAMING NOTES
1. ALL STEEL DECKING SHALL COMPLY WITH THE SPECIFICATIONS OF THE STEEL DECK
INSTITUTE (SDI) FOR DESIGN AND ERECTION.
2. ROOF DECK SHALL BE 1 1/2" DEEP, 20 GA. (0.0312"), TYPE B, GALV G-60, WITH A MINIMUM SECTION MODULUS OF 0.234 IN3, A MINIMUM MOMENT OF INERTIA OF 0.212 IN4, A MINIMUM
YIELD STRENGTH OF 33 KSI, AND SHALL HAVE NESTED TYPE SIDE JOINTS.
3. STEEL ROOF DECK SPECIFIED HAS BEEN DETERMINED ON THE BASIS OF A 3 SPAN
CONDITION. DECK SUPPLIER SHALL USE HEAVIER GAGE IF REQUIRED FOR ONE OR TWO
SPAN CONDITIONS.
4. STEEL ROOF DECK SHALL BE FASTENED TO FRAMING WITH MECHANICAL DECK FASTENERS
OR 5/8" PUDDLE WELDS AT A 36/7 PATTERN. PROVIDE 4 SIDELAP FASTENERS PER SPAN.
5. DECK DETAILS AND FASTENING PATTERNS DIFFERING FROM THOSE CALLED OUT SHALL BE
SUBMITTED TO THE ENGINEER FOR APPROVAL, PRIOR TO PROCEEDING WITH FABRICATION
AND INSTALLATION.
6. REQUIRED SUPPORTING CALCULATIONS AND DATA SHALL BE BASED UPON THE STEEL DECK
INSTITUTE'S DIAPHRAGM DESIGN MANUAL. SIDELAP WELDING IS NOT RECOMMENDED FOR
22 GA. (0.0269") THICK DECKS.
STEEL ROOF DECK NOTES
1. ALL CMU WALLS SHALL BE DETAILED ACCORDING TO THE REQUIREMENTS OF ACI 530-11 AND
THE PROJECT DOCUMENTS. WHERE CONFLICTS ARISE, THE MORE STRINGENT CRITERIA
SHALL APPLY.
2. CONCRETE MASONRY UNITS (CMU) MUST HAVE A MINIMUM COMPRESSIVE STRENGTH (f'm) OF
1900 PSI AT 28 DAYS.
3. REINFORCEMENT SHALL MEET THE REQUIREMENTS OF ASTM A615.
4. HORIZONTAL WALL REINFORCEMENT SHALL BE FULLY GROUTED BOND BEAMS W/ 2- #5 BARS
@ 48" OC VERT, TYP.
5. MORTAR SHALL BE PORTLAND CEMENT-LIME AND SHALL COMPLY WITH ASTM C270, TYPE S.
6. GROUT SHALL COMPLY WITH ASTM C476, 2000 PSI.
7. THE BOTTOM CMU COURSE SHALL BE A FULLY GROUTED BOND BEAM W/ 2- #5 BARS.
8. VERTICAL WALL REINFORCEMENT SHALL BE #5 BARS @ 32" O.C. IN A FULLY GROUTED CELL.
VERTICAL REINFORCEMENT SHALL BE HOOKED INTO THE BOND BEAM AT THE TOP OF ALL
WALLS.
9. PROVIDE DOWELS AT THE SAME SIZE AND SPACING AS THE WALL REINFORCING, 4'-0" LONG
WITH 25" EMBEDED DEPTH INTO SUPPORTING CONCRETE. PROVIDE TWO DOWELS IN CELLS
ADJACENT TO WALL OPENINGS AND AT ENDS OF WALLS.
10. PROVIDE 2- #4 VERTICAL BARS IN GROUTED CELLS ADJACENT TO WALL OPENINGS.
MASONRY NOTES
DESCRIPTIONNOTE
POST INSTALLED ANCHOR SYSTEM NOTES
1. POST-INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED ON THE
CONSTRUCTION DOCUMENTS. THE CONTRACTOR SHALL OBTAIN APPROVAL FROM THE
ENGINEER–OF-RECORD PRIOR TO INSTALLING POST-INSTALLED ANCHORS IN PLACE OF
MISSING OR MISPLACED CAST-IN-PLACE ANCHORS. CARE SHALL BE TAKEN IN PLACING
POST-INSTALLED ANCHORS TO AVOID CONFLICTS WITH EXISTING REBAR. HOLES SHALL
BE DRILLED AND CLEANED IN ACCORDANCE WITH THE MANUFACTURER’S WRITTEN
INSTRUCTIONS. SUBSTITUTION REQUESTS FOR PRODUCTS OTHER THAN THOSE
SPECIFIED BELOW SHALL BE SUBMITTED BY THE CONTRACTOR TO THE ENGINEER-OF-
RECORD ALONG WITH CALCULATIONS THAT ARE PREPARED & SEALED BY A
REGISTERED PROFESSIONAL ENGINEER. THE CALCULATIONS SHALL DEMONSTRATE
THAT THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING THE PERTINENT
EQUIVALENT PERFORMANCE VALUES (MINIMUM) OF THE SPECIFIED PRODUCT USING
THE APPROPRIATE DESIGN PROCEDURE AND/OR STANDARD(S) AS REQUIRED BY THE
BUILDING CODE. PROVIDE CONTINUOUS OR PERIODIC SPECIAL INSPECTION FOR ALL
ADHESIVE AND MECHANICAL ANCHORS PER THE PRODUCT’S APPLICABLE ICC-ES
EVALUATION REPORT (ICC-ES ESR). CONTACT MANUFACTURER’S REPRESENTATIVE
FOR THE INITIAL TRAINING AND INSTALLATION OF ANCHORS AND FOR PRODUCT
RELATED QUESTIONS AND AVAILABILITY. CALL SIMPSON STRONG-TIE AT (800) 999-5099.
CALL HILTI AT (866) 445-8827. CALL DEWALT AT (800) 524-3244.
2. CONCRETE ANCHORS:
ADHESIVE ANCHORS SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN
ACCORDANCE WITH ACI 355.4 AND ICC-ES AC308 FOR CRACKED AND UNCRACKED
CONCRETE RECOGNITION. POST INSTALLED EXPANSION ANCHORS, UNDERCUT
ANCHORS, AND SCREW ANCHORS SHALL MEET THE ASSESSMENT CRITERIA OF ACI
355.2. INSTALLATION SHALL BE IN ACCORDANCE WITH THE ANCHOR MANUFACTURER'S
PRINTED INSTALLATION INSTRUCTIONS. HORIZONTAL AND/OR UPWARD INCLINED
INSTALLATION ORIENTATION SHALL BE PERFORMED BY A CERTIFIED ADHESIVE ANCHOR
INSTALLER. CONCRETE SHALL MEET THE FOLLOWING CONDITIONS FOR INSTALLATION
AND PERFORMANCE OF ADHESIVE ANCHORS:
MINIMUM AGE OF CONCRETE AT TIME OF INSTALLATION: 21 DAYS
MAXIMUM SERVICE TEMPERATURE: 110° F
SERVICE MOISTURE CONDITION OF CONCRETE: DRY
CONCRETE WEIGHT: NORMAL WEIGHT
SPECIAL INSTALLATION AND LOADING CONDITIONS: OVER