Atch 8 Nashville VA Steam Components Name and Location Key.xlsx

XLSX spreadsheet 84 KB Posted

Attached to
Z1DA--626-24-204 - Update / Upgrade Steam System Components Federal contract opportunity
Solicitation number
36C24924B0011
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9

About this file

This document is a Statement of Work (SOW) for a federal contract opportunity to update and upgrade steam system components at the Tennessee Valley Healthcare System (TVHS) Nashville campus. The key objectives include replacing failing condensate return skid pumps and components, adding venting, and correcting piping and condensate return issues throughout the facility. The solicitation will result in one award, and the contractor is responsible for all work required to provide an acceptable final product. The contract period of performance is 120 calendar days from notice to proceed. The SOW provides details on the scope of work, guidelines and standards, work constraints, submittals, and requirements for work completion and contractor warranties.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--626-24-204 - Update / Upgrade Steam System Components, newest first.
File Type Posted
Atch 17 VAAR Clause 852.219-75 VA Notice of Limitations on Subcontracting CC.pdf PDF
36C24924B0011 0009.docx DOCX document
Atch 14 VAAR Clause 852.219-75 VA Notice of Limitations on Subcontracting.docx DOCX document
36C24924B0011 0008.docx DOCX document
Atch 2 Specifications 626-24-204 Final R1.pdf PDF
36C24924B0011 0007.docx DOCX document
36C24924B0011 0006.docx DOCX document
36C24924B0011 0005.docx DOCX document
36C24924B0011 0004.docx DOCX document
Atch 6 Drawing Combined Steam-CAD Version.pdf PDF
36C24924B0011 0003.docx DOCX document
Atch 16 VA Form 6112 Equipment Record.pdf PDF
36C24924B0011 0002.docx DOCX document
SPEC Section 01 45 00.pdf PDF
Atch 15 Construction Safety Guidebook.pdf PDF
SPEC Section 01 32 16.15.pdf PDF
Atch 14 VA TVHS Confined Space Policy.docx DOCX document
Atch 1 WD Davidson County Building TN20240178 dated 07262024.pdf PDF
36C24924B0011 0001.docx DOCX document
Atch 10 General Conditions Breakout.xlsx XLSX spreadsheet
Atch 5 Drawing Armstrong AFH 4100 J Condensate Pump 30GAL Duplex.pdf PDF
Atch 4 Drawing Armstrong AFH 4100 J Condensate Pump 15GAL Duplex.pdf PDF
Atch 2 Specifications 626-24-204 Final.pdf PDF
Atch 7 Drawing Typical Flash Tank Connections.pdf PDF
Atch 6 Drawing Combined Steam.pdf PDF
Atch 3 Condensate Pump Selections Basis of Design.pdf PDF
Atch 1 WD Davidson County Building TN20240178 dated 06212024.pdf PDF
36C24924B0011_1.docx DOCX document
Atch 13 Contractor EMR Certification Form.docx DOCX document
Atch 12 TAX ID UEI Document.docx DOCX document
Atch 11 Calculation of Contractor Self Performed Work.xlsx XLSX spreadsheet
Atch 9 Price Breakout Schedule Construction.xlsx XLSX spreadsheet
Show all 32

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Facility Information

NameLocationAddress
VA Tennessee Valley Medical CenterNashville, TN 372121310 24th Ave S
Site ContactsEmailPhone Number
George Yousef - Energy Engineergeorge.yousef@va.gov502-422-2957
Clint - Energy Plant Manager
Robert - Pipe Fitter
Facility Information
4WI-200-600-200 CB-LE Clever Brooks Firetube Boiler90 PSIG
4WI-200-600-200 CB-LE Clever Brooks Firetube Boiler90 PSIG
4WI-200-600-200 CB-LE Clever Brooks Firetube Boiler90 PSIG
BFS ZER-O-PAC Spray DA8 PSIG
Hours of OperationFacility Steam Pressures
860090 PSIG
860060 PSIG
860040 PSIG
360035 PSIG
360030 PSIG
360025 PSIG
360020 PSIG
360015 PSIG
360010 PSIG
36005 PSIG
Cost of Fuel
Cost per therm$ 0.87
Cost per MMBTU$ 8.65

mailto:george.yousef@va.gov Routes

Route #Location
1Boiler Room
2Chiller Plant
3Fan Room 4
4Fan Room 11
5Fan Room 5
6Fan Room 7
7Fan Room 17
8Fan Room 2
9Fan Room 1
10Fan Room 8
11Fan Room 14
122nd Floor Roof AHU's 35 & 42
13Fan Room 15
14Fan Room 6
15Fan Room 3
16Fan Room 16
17Level 5 Rooftop Cooling Tower
18Acres Fan Room 8A
19Acres Fan Room 9
20Acres Fan Room 10
21Hospital Sub-Basement

Master List

Trap #RouteLocationElevationApplicationUsageMakeModelTypePMOConnection SizeCondensate LiftPressure InPressure OutCheck ValveIsolation InIsolation OutConstant/ModulatingStatusCommentsRecommendations
11Above BLR115'DripHPS SupplyWatson McDaniel1031IVBT1250.754'900-10XXXConstantOkCondensate outlet ties into LP return main.Remove piping from LP retrun and return directly to the DA.
21Above BLR117'EquipmentMAU CoilSpirax-SarcoFTI30F&T300.750'100XXXModulatingFloodedBack pressure from trap 001 has caused this trap to fail.Remove trap #001 return from the LP return system.
31Water Heater Mezzanine1'DripDA PRV Station - HPArmstrongTVS811-125IVBT1250.750'900-10XXXConstantBlow ThruTrap has failed. Condensate outlet ties into LP return main.Repair/Replace, remove piping from LP retrun and return directly to the DA.
41Water Heater Mezzanine1'DripDA PRV Station - LPArmstrongTVS811-15IVBT150.750'100XXXConstantBlow ThruBack pressure from trap 003 has caused this trap to fail.Remove trap #003 return from the LP return system.
51Water Heater Mezzanine1'DripMain PRV Station - HPArmstrong2011IVBT1250.750'900-10XXXConstantOkNoneNone
61Water Heater Mezzanine7'DripWH PRV - LPArmstrong15B3F&T150.750'100OXXConstantBlow ThruBad application for a modulating pressure application steam trap.Replace with a constant pressure application steam trap.
71Water Heater Mezzanine7'DripWH PRV - HPArmstrong2011IVBT1250.750'900-10XXXConstantOkNoneNone
81Water Heater MezzanineGLDripPRV4Armstrong2011IVBT1250.750'200XXXConstantOKNoneNone
91Water Heater Mezzanine7'DripPRV1Armstrong2011IVBT1250.750'400-5XXXConstantOKNoneNone
101Water Heater MezzanineGLDripLPS SupplyArmstrong2011IVBT1250.750'200XXXConstantOkNoneNone
111Above Stairs9'DripLPS SupplyArmstrong2011IVBT1250.750'200XXXConstantOkNoneNone
121Water Heaters1'DripMPS SupplyArmstrong800-80IVBT800.752'400-5XXXConstantOkNoneNone
131Water Heaters1'DripMPS SupplyArmstrong800-80IVBT800.752'400-5XXXConstantOkNoneNone
141Water Heaters1'DripMPS SupplyArmstrong800-80IVBT800.752'400-5XXXConstantOkNoneNone
151Water Heaters1'DripMPS SupplyArmstrong2011IVBT1250.752'400-5XXXConstantOKNoneNone
161Water Heaters1'DripMPS SupplyArmstrong2011IVBT1250.750'400-5XXXConstantOKNoneNone
171Water Heaters1'DripMPS SupplyArmstrong2011IVBT1250.750'400-5XXXConstantOKNoneNone
181Water Heaters1'DripMPS SupplyHoffmanB1125AIVBT1250.750'400-5XXXConstantOKNoneNone
191In front of BLR110'DripLPS SupplyArmstrong2011IVBT1250.7510'200XXXConstantOKNoneNone
201Near exit8'EquipmentUnit HeaterArmstrong30A3F&T300.7510'200XXXConstantOkNoneNone
211In front of BLR28'EquipmentUnit HeaterArmstrong2011IVBT1250.7510'200XXXConstantOKNoneNone
221In front of BLR38'EquipmentUnit HeaterArmstrong30A3F&T300.7510'200XXXConstantOkNoneNone
231In front of BLR39'DripLPS SupplyArmstrongTVS811IVBT1250.750'200XXXConstantOkNoneNone
241Near gauge station7'DripHPS SupplyArmstrong2011IVBT1250.750'900-10XXXConstantOKNoneNone
252Near condenser water strainer2'DripLPS SupplyArmstrong2011IVBT1250.750'200XXXConstantOKNoneNone
262Near condenser water strainer6'DripHPS SupplyArmstrongTVS811IVBT1250.750'900-10XXXConstantOkNoneNone
272Above Heating Water Pumps6'DripHPS SupplyArmstrong2011IVBT1250.750'900-10XXXConstantOKNoneNone
282Above Heating Water Pumps6'DripMPS SupplyArmstrong2011IVBT1250.750'300-5XXXConstantOKNoneNone
292Above York VSD6'EquipmentHeat ExchangerArmstrongICSF&T1250.750'200XXXModulatingOKNoneNone
302Above York VSD6'EquipmentHeat ExchangerHoffmanFT075X8F&T7520'200XXXModulatingOkNoneNone
313AC22 Steam Supply9'DripMPS SupplyArmstrong811IVBT700.750'300-5XXXConstantOfflineHumidifier not in used due to no drain pan installed.Install a drain pan, turn steam back on and test.
323AC22 Steam Supply9'EquipmentSteam CoilArmstrong30A3F&T300.750'300-5XXXModulatingOfflineHumidifier not in used due to no drain pan installed.Install a drain pan, turn steam back on and test.
333AC22 Steam Supply9'EquipmentSteam CoilArmstrong30A3F&T300.750'300-5XXXModulatingOfflineHumidifier not in used due to no drain pan installed.Install a drain pan, turn steam back on and test.
343AHU-21GLDripLPS SupplySpirax-SarcoUTD52LDisk6000.51'300-5XXXConstantOkNoneNone
353AHU-21GLPump TrapAHU-21Spirax-SarcoPPCF&T150212'300-5XXXConstantOkNoneNone
363AHU-211'EquipmentSteam CoilSpirax-SarcoFTI125F&T1251.50'300-5XXXModulatingOkNoneNone
373AHU-211'DripMPS SupplyArmstrong2011IVBT1250.750'300-5XXXConstantOkNoneNone
383AHU-211'EquipmentSteam CoilMepco44-275AF&T750.750'300-5XXXModulatingOkNoneNone
393AHU-182'DripLPS SupplyMepco1B11IVBT150.750'50XXXConstantBlow ThruTrap has failed.Repair/Replace
403AHU-181'EquipmentHumidifierMepco44-215AF&T150.750'50XXXModulatingOkNoneNone
413AHU-18GLPump TrapHumidifierJohnsonLMHT-500F&T200112'300-5XXXConstantFloodedPump mechanism has failed and needs rebuilt.Rebuild the pump trap mechanism.
423AHU-187'DripMPS SupplyArmstrongTVS811IVBT1250.750'300-5XXXConstantOkNoneNone
433AHU-181EquipmentSteam CoilMepcoIB14IVBT301.510'300-5XXXModulatingOfflineControl valve does not open when called for.Check controls.
443AHU-17 VSD7'DripMPS SupplyArmstrongTVS811IVBT1250.750'300-5XXXConstantOkNoneNone
453AHU-171'EquipmentSteam CoilSpirax-SarcoUFT-32F&T4500.750'300-5XXXModulatingOfflineControl valve does not open when called for.Check controls.
463AHU-171'DripMPS SupplyArmstrongTVS811IVBT1250.750'300-5XXXConstantOfflineControl valve does not open when called for.Check controls.
473AHU-171'EquipmentSteam CoilArmstrongTVS811IVBT1250.750'300-5XXXModulatingOfflineControl valve does not open when called for.Check controls.
483AHU-171'EquipmentSteam CoilArmstrongTVS811IVBT1250.750'300-5XXXModulatingOfflineControl valve does not open when called for.Check controls.
493Clean Steam Generator9'DripMPS SupplyArmstrongTVS811IVBT1250.750'300-5XXXConstantOkNoneNone
503Clean Steam Generator3'EquipmentSteam CoilHoffmanFT030H3F&T300.750'300-5OOOModulatingOfflineGenerator is currently shut down due to maintenance.Check when generator has been repaired.
513Clean Steam Generator4'DripMPS SupplyHoffmanFT030H3F&T300.750'300-5OOOConstantOfflineGenerator is currently shut down due to maintenance.Check when generator has been repaired.
523Heat Exchanger2'DripMPS SupplySpirax-SarcoTD52Disk6000.752'300-5OXOConstantOkNoneNone
533Heat ExchangerGLPump TrapHeat ExchangerSpirax-SarcoPPCF&T15028'300-5XXXConstantOkNoneNone
544Unit Heater Discharge10'EquipmentUnit HeaterSpirax-SarcoFT15F&T150.750'200XOXConstantOkNoneNone
554Corner of the room6'DripLPS SupplyMepco40-215AF&T150.750'200OXXConstantOkCondensate outlet dumps to drain.Return the condensate to the pump skid.
564AC-201'EquipmentSteam CoilMepco40-215AF&T150.750'200XXXModulatingOKNoneNone
574AC-201'EquipmentSteam CoilMepco40-215AF&T150.750'200XXXModulatingOKNoneNone
584AC-201'EquipmentSteam CoilArmstrongICSF&T12520'200XXXModulatingOKNoneNone
594AC-20GLPump TrapAC-20ArmstrongPT-104F&T100112'200XXXConstantOkNoneNone
605PRV StationGLDripHPS SupplyArmstrongTVS811–125IVBT1250.755'900-10XXXConstantBlow ThruTrap has failed.Repair/Replace
615PRV Station2'DripMPS SupplyArmstrongTVS811–125IVBT1250.755'300-5XXXConstantOkNoneNone
625Heat Exchanger4'EquipmentHeat ExchangerArmstrong30B8F&T3020'300-5XXXModulatingOkNoneNone
635Heat Exchanger4'EquipmentHeat ExchangerArmstrong30B8F&T3020'300-5XXXModulatingOkNoneNone
645Heat ExchangerGLPump TrapHeat ExchangerSpirax-SarcoPTCF&T200215'900-10XXXConstantOkNoneNone
655AHU-163'EquipmentSteam CoilSpirax-SarcoSIB30IVBT4350.750'300-5XXXModulatingOKNoneNone
665AHU-163'EquipmentSteam CoilSpirax-SarcoSIB30IVBT4350.750'300-5XXXModulatingOKNoneNone
675AHU-16 Behind Column3'DripMPS SupplyMepco1031IVBT1250.750'300-5XXXConstantOkNoneNone
685Clean Steam Generator3'EquipmentSteam CoilHoffmanFT030H3F&T300.750'300-5OOOModulatingOKNoneNone
695Clean Steam Generator4'DripMPS SupplyHoffmanFT030H3F&T300.750'300-5OOOConstantOKBad application for a modulating pressure steam trap. Outlet tied into the heat exchanger outlet.None
706PRV Station4'DripMPS SupplyArmstrong2011IVBT1250.750'300-5XXXConstantOKNoneNone
716AHU76'EquipmentHumidifierArmstrong30B3F&T300.750'300-5OOXModulatingOfflineHumidifier is valved with 2 control valves. This should always be hot or the safety valve needs to be open prior to the modulating valve.Test when the humidifier is hot.
726AHU76'DripHumidifierArmstrong811IVBT700.750'300-5XOXConstantOfflineHumidifier is valved with 2 control valves. This should always be hot or the safety valve needs to be open prior to the modulating valve.Test when the humidifier is hot.
736AHU37'DripHumidifierArmstrong800IVBT700.750'300-5XOXConstantOfflineHumidifier is valved with 2 control valves. This should always be hot or the safety valve needs to be open prior to the modulating valve.Test when the humidifier is hot.
746AHU76'DripMPS SupplyArmstrong800IVBT700.750'300-5XXXConstantOkNoneNone
756AHU7GLEquipmentSteam CoilArmstrong30B3F&T300.750'300-5XXXModulatingOkNoneNone
766AHU7GLEquipmentSteam CoilArmstrong30B3F&T300.750'300-5XXXModulatingOkNoneNone
776AHU3GLEquipmentSteam CoilArmstrong30B3F&T300.750'300-5XXXModulatingOKNoneNone
786AHU3GLEquipmentSteam CoilArmstrong30B3F&T300.750'300-5XXXModulatingOKNoneNone
796Near Exit8'EquipmentUnit HeaterArmstrongTVS811–125IVBT1250.755'300-5XXXConstantOkNoneNone
807Above 1ECCE Panel8'DripMPS SupplyArmstrong2011IVBT1250.750'300-5XXXConstantOKNoneNone
817AHU546'DripSteam CoilArmstrongTVS811–125IVBT1250.750'300-5OXXConstantOkNoneNone
827AHU54GLEquipmentSteam CoilArmstrong30B5F&T301.250'300-5XXXModulatingOkNoneNone
837AHU54GLEquipmentSteam CoilArmstrong30B5F&T301.250'300-5XXXModulatingOkNoneNone
847AHU54GLEquipmentSteam CoilArmstrong30B5F&T301.250'300-5XXXModulatingOkNoneNone
857AHU557'DripSteam CoilArmstrong811–125IVBT1250.750'300-5OXXConstantOkNoneNone
867AHU563'EquipmentSteam CoilArmstrong15B3F&T150.750'300-5XXXModulatingOkNoneNone
877AHU572'EquipmentSteam CoilArmstrong15B3F&T150.750'300-5XXXModulatingOkNoneNone
888AHU-3ARGLEquipmentSteam CoilArmstrong15B3F&T150.750'200XXXModulatingOKNoneNone
898AHU-508'DripLPS SupplyArmstrongTVS811–125IVBT1250.750'200XXXConstantOkNoneNone
908AHU-50GLDripLPS SupplyArmstrongTVS811–125IVBT1250.750'200XXXConstantOKNoneNone
918AHU-50GLEquipmentSteam CoilArmstrongICSF&T1250.750'200XXXModulatingOKNoneNone
928AHU-3AR1'DripHumidifierArmstrongTVS811-15IVBT150.750'100XXXConstantOkNoneNone
938AHU-3AR1'EquipmentHumidifierColton IndFTX30F&T300.750'100XXXModulatingOkNoneNone
948Above AHU-50 Ductwork12'EquipmentUnit HeaterSpirax-SarcoFT30F&T300.750'200XXXConstantOKNoneNone
958Along Wall Above Ductwork12'DripLPS SupplyArmstrongTVS811–125IVBT1250.750'200XXXConstantOkNoneNone
968Above Door Ductwork12'DripLPS SupplyArmstrong2011IVBT1250.750'200XXXConstantOkNoneNone
979PRV Station1'DripHPS SupplyArmstrong2011IVBT1250.7510'900-10XXXConstantOKNoneNone
989PRV Station1'DripLPS SupplyArmstrongTVS811-15IVBT150.7510'1510XXXConstantFloodedBackpressure from trap 97 is causing this trap to fail.Remove outlet from the high pressure return system.
999PRV Station7'DripMPS SupplyArmstrong2011IVBT1250.7510'600-5XXXConstantOKNoneNone
1009Heat Exchanger2'EquipmentHeat ExchangerArmstrong30B8F&T3020'150OXXModulatingOkNoneNone
1019Heat Exchanger2'EquipmentHeat ExchangerArmstrong30B8F&T3020'150OXXModulatingOkNoneNone
1029Heat Exchanger2'EquipmentHeat ExchangerArmstrong30B8F&T3020'150OXXModulatingOkNoneNone
1039Heat Exchanger2'EquipmentHeat ExchangerArmstrong30B8F&T3020'150OXXModulatingOkNoneNone
1049Above Heating Water Pumps7'DripLPS SupplyArmstrongTVS811-15IVBT150.750'150XXXConstantOkNoneNone
1059AHU-67'DripLPS SupplyArmstrongTVS811-15IVBT150.750'150XXXConstantBlow ThruTrap has failed.Repair/Replace
1069AHU-65'DripSteam CoilArmstrong15B3F&T150.750'150XXXConstantFloodedTrap is installed upside down. Bad application for a modulating style steam trap.Replace with a constant pressure application steam trap.
1079AHU-6GLEquipmentSteam CoilSpirax-SarcoFT15F&T151.50'150XXXModulatingOkNoneNone
1089AHU-68'DripLPS SupplyArmstrong811IVBT150.750'150XXXConstantOkNoneNone
1099AHU-112'DripLPS SupplyArmstrong15B3F&T150.750'150XXXModulatingOKNoneNone
1109AHU-112'DripLPS SupplyArmstrong15B4F&T1510'150XXXModulatingOKNoneNone
1119AHU-11GLEquipmentSteam CoilArmstrong30B8F&T3020'150OXXModulatingOkNoneNone
1129AHU-5GLEquipmentSteam CoilArmstrong30B8F&T3020'150OXXModulatingOkNoneNone
1139AHU-5GLEquipmentSteam CoilArmstrong30B8F&T3020'150OXXModulatingOkNoneNone
1149AHU-5GLEquipmentSteam CoilArmstrong30B8F&T3020'150OXXModulatingOkNoneNone
1159On top of AHU-118DripLPS SupplySpirax-SarcoFT15F&T300.750'150XXXConstantOkBad application for a modulating pressure application steam trap.None
1169AHU-5GLDripLPS SupplyArmstrongTVS811-15IVBT150.750'150XXXConstantOkNoneNone
1179AHU-5GLDripLPS SupplyNortec159 9601F&T1250.750'150XXXConstantOkNoneNone
11810LPS Supply7'DripLPS SupplyArmstrongTVS811-15IVBT150.750'150XXXConstantOkNoneNone
11910LPS Supply3'DripLPS SupplyArmstrongTVS811-15IVBT150.750'150XXXConstantBlow ThruTrap has failed.Repair/Replace
12010Unit Heater7'EquipmentUnit HeaterArmstrong15B3F&T150.50'150XXXConstantOfflineUnit heater is not used. Valved off, not controlled by BAS.Remove from service or force to operation and check status.
12110AHU-26'EquipmentSteam CoilArmstrong25JD8F&T2520'150OXXModulatingOkNoneNone
12210AHU-23'DripLPS SupplyArmstrongTVS811-30IVBT300.750'150XXXConstantOkNoneNone
12310AHU-2GLEquipmentSteam CoilArmstrong25JD8F&T2520'150OXXModulatingOkNoneNone
12410AHU-22'EquipmentSteam CoilTLVSS3N-10/BF&T3450.750'150OXXModulatingOkNoneNone
12510AHU-23'DripLPS SupplyArmstrongTVS811-30IVBT300.750'150XXXConstantOkNoneNone
12610AHU-2 PRV Station2'DripHPS SupplyArmstrongTVS811-125IVBT1250.750'900-10XXXConstantOkThe condensate outlet is tied to low pressure return.Separate return line from LPR.
12710AHU-2 PRV Station2'DripLPS SupplyArmstrongTVS811-125IVBT1250.750'150XXXConstantOkNoneNone
12811Behind AHU-37/382'DripMPS SupplySpirax-SarcoTD52Disk6000.750'150OXXConstantOkNoneNone
12911Behind AHU-37/384'EquipmentSteam CoilSpirax-SarcoTD52Disk6000.750'150OXXModulatingOKNoneNone
13011Behind AHU-37/381'EquipmentSteam CoilSpirax-SarcoTD52Disk6000.750'150OXXModulatingOKNoneNone
13111Beside AHU-37/38GLEquipmentSteam CoilArmstrong30B6F&T301.250'150OXXModulatingFloodedTrap position is rotated down.Repair/Replace
13211Beside AHU-37/383'EquipmentSteam CoilHoffman550F&T301.250'150OXXModulatingOkNoneNone
13311Beside AHU-37/384'DripSteam CoilArmstrongTVS811-15IVBT150.750'150OXXModulatingOfflineHigh limit duct humid-a-stat prevents valve override.Test when operational.
13411Beside AHU-37/384'EquipmentSteam CoilMepco40-215AF&T150.750'150OXXModulatingOfflineHigh limit duct humid-a-stat prevents valve override.Test when operational.
13511Beside AHU-37/384'DripSteam CoilArmstrongTVS811-15IVBT150.750'150OXXModulatingOfflineHigh limit duct humid-a-stat prevents valve override.Test when operational.
13611Beside AHU-37/384'EquipmentSteam CoilMepco40-215AF&T150.750'150OXXModulatingOfflineHigh limit duct humid-a-stat prevents valve override.Test when operational.
13712AHU563'EquipmentSteam CoilArmstrong30A3F&T301.750'150OXXModulatingOKNoneNone
13812AHU563'EquipmentSteam CoilArmstrongTVS811-15IVBT150.750'150OXXModulatingOKBad application for a constant pressure application steam trap.None
13912AHU561'DripLPS SupplyArmstrong811IVBT300.750'150OXXModulatingFloodedTrap has failed. Bad application for a constant pressure steam trap.Replace with a modulating pressure steam trap.
14012AHU566'DripLPS SupplyArmstrong811IVBT300.750'150OXXConstantOkNoneNone
14113PRV Station2'DripHPS SupplyArmstrong2011IVBT1250.750'600-5XXXConstantOKNoneNone
14213PRV Station2'DripMPS SupplyArmstrong2011IVBT1250.750'250XXXConstantOKNoneNone
14313Flash Tank3'DripMPS SupplyWatson McDaniel1031IVBT1501.750'250OXXConstantOkNoneNone
14413Flash TankGLPump TrapFan Room 15Spirax-SarcoPTCF&T200215'900-10XXXConstantLeakingPump mechanism has failed and needs rebuilt.Rebuild the pump trap mechanism.
14513Unit Heater9'EquipmentUnit HeaterArmstrongTVS811-70IVBT700.750'250OXXConstantOkNoneNone
14613Above Flash Tank12'DripLPS SupplyArmstrongTVS811-70IVBT700.750'150OXXConstantOkNoneNone
14713Above Flash Tank12'EquipmentHeat ExchangerArmstrong15B3F&T150.750'150XXXModulatingOKNoneNone
14813Above Flash Tank12'EquipmentHeat ExchangerArmstrong15B3F&T150.750'150XXXModulatingOKNoneNone
14913Above Flash Tank12'EquipmentHeat ExchangerArmstrong15B3F&T150.750'150XXXModulatingOKNoneNone
15013Above Flash Tank12'EquipmentHeat ExchangerArmstrong15B3F&T150.750'150XXXModulatingOKNoneNone
15113Between AHU39 & 4010'DripMPS SupplyArmstrong2011IVBT1250.750'250XXXConstantOKNoneNone
15213AHU-39 Humidifier1'DripMPS SupplyArmstrong800IVBT300.750'250XXXConstantOfflineHumidifier is isolated off with manual valve. Outlet trap is abandoned.Test when valve can be opened.
15313Above PitGLEquipmentHumidifierArmstrong812IVBT300.750'250XXXConstantAbandonedTrap inlet is cut and capped.Fix piping, test trap.
15413Above PitGLEquipmentSteam CoilUnknownUnknownF&TUNK20'250XXXModulatingOkNoneNone
15513In Pit2'DripMPS SupplyWatson McDaniel1032IVBT1500.750'250XXXConstantOkNoneNone
15613In PitGLPump TrapAHU-39Spirax-SarcoPPECF&T125115'600-5XXXConstantLeakingPump mechanism has failed and needs rebuilt.Rebuild the pump trap mechanism.
15713AHU-40 Unit Heater10'EquipmentUnit HeaterHoffmanFT015H4F&T1510'250OOXConstantOKNoneNone
15813AHU-401'DripHumidifierArmstrong800IVBT800.750'250XOXConstantOfflineHumidifier is isolated off with manual valve.Test when valve can be opened.
15913AHU-40GLEquipmentHumidifierArmstrong811IVBT700.750'250XOXConstantOfflineHumidifier is isolated off with manual valve.Test when valve can be opened.
16013AHU-411'EquipmentHumidifierArmstrongICSF&T12510'250XXXModulatingOKNoneNone
16113AHU-411'DripHumidifierArmstrong2011IVBT1250.50'250XXXConstantOKNoneNone
16213AHU-411'DripHumidifierArmstrong2011IVBT1250.750'250XXXConstantOKNoneNone
16313AHU-4112'DripMPS SupplySpirax-SarcoFT-30F&T300.750'250XXXModulatingOkNoneNone
16413AHU-413'DripSteam CoilHoffmanFT015H4F&T1510'250XXXModulatingOKNoneNone
16513AHU-413'DripSteam CoilHoffmanFT015H4F&T1510'250XXXModulatingOKNoneNone
16613AHU-410'EquipmentSteam CoilHoffmanFT015H5F&T151.251'250XXXModulatingOKNoneNone
16713AHU-410'EquipmentSteam CoilHoffmanFT015H5F&T151.251'250XXXModulatingBlow ThruTrap has failed.Repair/Replace
16813AHU-4015'Dripend of mainArmstrong2011IVBT1250.750'250XXXConstantOKNoneNone
16913AHU-401'EquipmentSteam CoilHoffmanFT030C8F&T3020'250OOXModulatingOkNoneNone
17013AHU-40 Pit2'DripMPS SupplyArmstrongTVS811-70IVBT700.750'250OXXConstantOkNoneNone
17113AHU-40 Pit2'Pump TrapAHU-40 & 41Spirax-SarcoPPECF&T125120'2510XXXConstantBlow ThruPump mechanism has failed and needs rebuilt.Rebuild the pump trap mechanism.
17213AHU-40 Pit2'DripMPS SupplyArmstrongTVS811-70IVBT700.750'250OXXConstantOkNoneNone
17313AHU-40 Pit2'Pump TrapAHU-40 & 41Spirax-SarcoPPECF&T125120'2510XXXConstantOkNoneNone
17414AHU-2412'DripHumidifierArmstrong811IVBT700.750'300-5XXXModulatingOfflineHumidifier is isolated off with manual valve. System has a tarp and a hose to drain a leak.Test when valve can be opened.
17514AHU-2412'DripHumidifierArmstrong30B3F&T300.750'300-5XXXModulatingOfflineHumidifier is isolated off with manual valve. System has a tarp and a hose to drain a leak.Test when valve can be opened.
17614AHU-2312'DripHumidifierArmstrong811IVBT700.750'300-5XXXModulatingOfflineHumidifier is isolated off with manual valve.Test when valve can be opened.
17714AHU-2312'DripHumidifierArmstrong30B3F&T300.750'300-5XXXModulatingOfflineHumidifier is isolated off with manual valve.Test when valve can be opened.
178NO TAG
17914Water Heater1'DripMPS SupplyArmstrong75A3F&T750.750'300-5XXXConstantOfflineMedium pressure steam supply is offline in this area.Test when system is online.
18014Water Heater1'EquipmentWater HeaterArmstrong216IVBTUNK1.50'300-5XOXModulatingOfflineMedium pressure steam supply is offline in this area.Test when system is online.
18115Main PRV Station4'DripMPS SupplyArmstrong2011IVBT1250.757'600-5XXXConstantOKNoneNone
18215Main PRV Station4'DripMPS SupplyArmstrong2011IVBT1250.757'250XXXConstantOKNoneNone
18315Above Honeywell Control Panels12'EquipmentUnit HeaterSpirax-SarcoFT30F&T300.750'250OXXConstantOfflineUnit heater is not used. Valved off, not controlled by BAS.Remove from service or force to operation and check status.
18415Above AHU-1012'DripMPS SupplyArmstrongTVS811-70IVBT700.750'250OXXConstantOkNoneNone
18515AHU-9 Disconnect6'DripSteam CoilArmstrong2011IVBT1250.750'250XXXConstantOkNoneNone
18615On Top of AHU-910'DripMPS SupplyArmstrongTVS811-70IVBT700.750'250XXXConstantOkNoneNone
18715AHU-92'EquipmentSteam CoilArmstrongICSF&T1251.50'250XXXModulatingOKNoneNone
18815AHU-912'DripMPS SupplyArmstrongTVS811-70IVBT700.750'250OXXConstantOkNoneNone
18915AHU-95'DripSteam CoilArmstrongTVS811-70IVBT700.750'250XXXConstantOkNoneNone
19015AHU-91'EquipmentSteam CoilArmstrongICSF&T1251.50'250XXXModulatingOKNoneNone
19115Rooftop Exit15'DripMPS SupplyArmstrongTVS811-70IVBT700.750'250OXXConstantOkCondensate inlet piping is leaking.Repair the piping.
19215Rooftop Exit15'EquipmentSteam CoilSpirax-SarcoFT30F&T300.750'250OXXModulatingAbandonedSteam supply to coil has been removed and capped.Repair coil or remove abandoned equipment.
19316Main PRV StationGLDripHPS SupplyArmstrong2011IVBT1250.751'900-10XXXConstantOKNoneNone
19416Main PRV StationGLDripMPS SupplyArmstrong2011IVBT1250.751'2510XXXConstantOKNoneNone
19516Main PRV Station15'EquipmentUnit HeaterArmstrong2011IVBT1250.750'250XXXConstantOKNoneNone
19616Pump Trap Station1'DripMPS SupplyArmstrongTVS811-70IVBT700.750'400-5OXXConstantOkNoneNone
19716Pump Trap StationGLPump Trapfan Room 16ArmstrongPT-206KF&T1251.515'400-5XXXConstantOkThis pumping trap needs flash tank.Install a flash tank with proper fill head prior to the pump.
19816AHU-562'DripLPS SupplyArmstrong2011IVBT1250.750'150XXXConstantOKNoneNone
19916AHU-561'EquipmentSteam CoilArmstrong15B3F&T150.750'150XXXModulatingOKNoneNone
20016AHU-561'EquipmentSteam CoilArmstrong15B3F&T150.750'150XXXModulatingOKNoneNone
20116AHU-56 Unit Heater12'EquipmentUnit HeaterWatson McDaniel1032IVBT300.750'250OOXConstantOkNoneNone
20216Heat Exchanger Skid7'DripMPS SupplyArmstrong2011IVBT1250.750'250XXXConstantOKNoneNone
20316Heat Exchanger 12'EquipmentHeat ExchangerWatson McDanielFTT-65F&T650.750'250XXXModulatingOkNoneNone
20416Heat Exchanger 12'EquipmentHeat ExchangerWatson McDanielFTT-65F&T650.750'250XXXModulatingOkNoneNone
20516Heat Exchanger 22'EquipmentHeat ExchangerWatson McDanielFTT-65F&T650.750'250XXXModulatingOkNoneNone
20616Heat Exchanger 22'EquipmentHeat ExchangerWatson McDanielFTT-65F&T650.750'250XXXModulatingOkNoneNone
20716AHU-528'DripMPS SupplyArmstrong811IVBT300.750'250XXXConstantOkNoneNone
20816AHU-521'EquipmentSteam CoilArmstrong15B3F&T150.750'250XXXModulatingOkNoneNone
20916AHU-52GLEquipmentSteam CoilWatson McDanielFT30F&T3020'250OXXModulatingOkNoneNone
21016AHU-52GLEquipmentSteam CoilWatson McDanielFT30F&T3020'250OXXModulatingOkNoneNone
21116AHU-529'DripHPS SupplyArmstrong2011IVBT1250.750'250XXXConstantOKNoneNone
21216AHU-518'DripMPS SupplyArmstrong811IVBT300.750'250XXXConstantOkNoneNone
21316AHU-511'EquipmentSteam CoilArmstrong15B3F&T150.750'250XXXModulatingOKNoneNone
21416AHU-51GLEquipmentSteam CoilWatson McDanielFT30F&T3020'250OXXModulatingOkNoneNone
21516AHU-51GLEquipmentSteam CoilWatson McDanielFT30F&T3020'250OXXModulatingOkNoneNone
21617Cooling Tower Emergency Heat8'DripMPS SupplySpirax-SarcoFT30F&T300.750'250OXXConstantOKNoneNone
21717Cooling Tower Emergency Heat8'EquipmentSteam CoilArmstrongTVS811-30IVBT300.750'250OXXConstantOKNoneNone
21817Cooling Tower Emergency Heat8'EquipmentSteam CoilArmstrongTVS811-30IVBT300.750'250OXXConstantOKNoneNone
No Tag17Water Room7'EquipmentUnit HeaterSpirax-SarcoFT31F&T303/43'200OXXConstantOKNoneNone
21918Steam Entrance - Down StairsGLDripHPS SupplyArmstrong2011IVBT1250.750'600-5XXXConstantOKNoneNone
22018Steam Entrance - Above Stairs6'DripMPS SupplyArmstrong2011IVBT1250.750'250XXXConstantOKNoneNone
22118Steam Entrance - Above Stairs6'DripHPS SupplyArmstrong2011IVBT1250.750'600-5XXXConstantOKNoneNone
22218Above Chemical Treatment Station7'EquipmentUnit HeaterSpirax-SarcoFT30F&T300.750'250OXXConstantOfflineUnit heater is not used. Valved off, not controlled by BAS.Remove from service or force to operation and check status.
22318AHU-287'DripMPS SupplySpirax-SarcoB-1HIVBT300.750'250OXXConstantOKNoneNone
22418AHU-28GLDripMPS SupplyArmstrong2011IVBT1250.750'250XXXConstantOKNoneNone
22518AHU-28GLEquipmentSteam CoilArmstrongICSF&T1250.750'250XXXModulatingOKNoneNone
22618AHU-28GLEquipmentSteam CoilArmstrongICSF&T1250.750'250XXXModulatingOKNoneNone
22718AHU-28GLEquipmentSteam CoilArmstrongICSF&T1250.750'250XXXModulatingOKNoneNone
22818AHU-28GLEquipmentSteam CoilArmstrongICSF&T1250.750'250XXXModulatingOKNoneNone
22918AHU-29GLEquipmentSteam CoilHoffmanFT015H3F&T150.750'250OXXModulatingFloodedBack pressure and bad check valves are probably the issue.Repair/Replace
23018AHU-29GLEquipmentSteam CoilArmstrong15B3F&T150.750'250OXXModulatingFloodedBack pressure and bad check valves are probably the issue.Repair/Replace
23118AHU-29GLDripMPS SupplyArmstrong2011IVBT1250.750'250XXXConstantOKNoneNone
23218AHU-29GLEquipmentSteam CoilArmstrong15B3F&T150.750'250OXXModulatingFloodedBack pressure and bad check valves are probably the issue.Repair/Replace
23318AHU-29GLEquipmentSteam CoilArmstrong15B3F&T150.750'250OXXModulatingFloodedBack pressure and bad check valves are probably the issue.Repair/Replace
23418AHU-316'DripMPS SupplyArmstrong2011IVBT1250.750'250XXXConstantOKNoneNone
23518AHU-31GLEquipmentSteam CoilArmstrongICSF&T1250.750'250XXXModulatingOKNoneNone
23618AHU-311'DripMPS SupplyArmstrongTVS811-15IVBT150.750'250OXXConstantOkNoneNone
23718AHU-31GLEquipmentSteam CoilArmstrongICSF&T1250.750'250XXXModulatingOKNoneNone
23818Heat Exchanger6'DripMPS SupplyArmstrong2011IVBT1250.750'250XXOConstantOkNoneNone
23918Heat Exchanger2'EquipmentHeat ExchangerArmstrong30B8F&T3020'250OXXModulatingOkNoneNone
24018Heat Exchanger2'EquipmentHeat ExchangerArmstrong30B8F&T3020'250OXXModulatingOkNoneNone
No Tag18Gravel PRV Station1'DripMPS SupplyArmstrong2011IVBT1253/43'400XXXConstantOKNoneNone
No Tag18Crawl Space1'DripMPS SupplyArmstrong2011IVBT1253/43'400XXXConstantOKNoneNone
24119AHU-307'DripMPS SupplyArmstrong2011IVBT1250.750'250XXXConstantOKNoneNone
24219AHU-30GLEquipmentSteam CoilWatson McDanielFT7F&T151.50'250XXXModulatingOkNoneNone
24319AHU-309'EquipmentUnit HeaterSpirax-SarcoFT30F&T300.750'250OXXConstantOfflineUnit heater is not used. Valved off, not controlled by BAS.Remove from service or force to operation and check status.
24419AHU-301'EquipmentHumidifierArmstrong2011IVBT1250.750'250XXXConstantOkNoneNone
24519AHU-30GLDripHumidifierArmstrong2011IVBT1250.750'250XXXConstantOkNoneNone
24619AHU-321'EquipmentHumidifierArmstrongTVS811-15IVBT150.750'250OXXConstantOkNoneNone
24719AHU-32GLDripHumidifierArmstrong2011IVBT1250.750'250XXXConstantOkNoneNone
24819AHU-327'DripMPS SupplyArmstrongTVS811-15IVBT150.750'250OXXConstantOkNoneNone
24919On top of AHU-328'EquipmentUnit HeaterSpirax-SarcoFT30F&T300.750'250OXXConstantOfflineUnit heater is not used. Valved off, not controlled by BAS.Remove from service or force to operation and check status.
25019AHU-32GLEquipmentSteam CoilBestobellFT1256F&T651.50'250XXXModulatingOKNoneNone
25120On top of AHU-338'EquipmentUnit HeaterSpirax-SarcoFT30F&T300.750'250OXXConstantOfflineUnit heater is not used. Valved off, not controlled by BAS.Remove from service or force to operation and check status.
25220AHU-33GLEquipmentSteam CoilArmstrong75A5F&T751.250'250XXXModulatingOkNoneNone
25320AHU-336'DripMPS SupplyArmstrong2011IVBT1250.750'250XXXConstantOkNoneNone
25420AHU-332'EquipmentHumidifierArmstrong2011IVBT1250.750'250XXXConstantOkNoneNone
25520AHU-332'EquipmentHumidifierArmstrong2011IVBT1250.750'250XXXConstantOKNoneNone
25621Column GA212'DripMPS SupplyArmstrong2011IVBT1250.754'250XXXConstantOkNoneNone
25721Column GA212'DripMPS SupplyArmstrongTVS811-70IVBT700.754'250XXXConstantOkNoneNone
25821Column H212'DripLPS SupplyArmstrong2011IVBT12514'200XXXConstantOKNoneNone
25921Column J223'DripLPS SupplySpirax-SarcoFT30F&T300.754'200XXXConstantOfflineTest when online.Test when online.
26021Column M273'DripLPS SupplySpirax-SarcoFT30F&T300.754'200XXXConstantAbandonedRemove from service.Remove from service.
26121Column M232'DripLPS SupplyArmstrongTVS811-70IVBT700.754'200XXXConstantOkNoneNone
26221Column M222'DripLPS SupplyArmstrongTVS811-70IVBT700.754'200XXXConstantOkNoneNone
26321Column M222'DripLPS SupplyHoffmanUnknownIVBTUNK0.754'200XXXConstantOkNoneNone
26421Column P213'DripLPS SupplyArmstrong2011IVBT1250.754'200XXXConstantOKNoneNone
26521Column N213'DripLPS SupplyArmstrong2011IVBT1250.754'200XXXConstantOkNoneNone
26621Column M203'DripLPS SupplyArmstrong2011IVBT1250.754'200XXXConstantOKNoneNone
26721Column L213'DripMPS SupplyArmstrongTVS811-70IVBT700.754'300-5XXXConstantOkNoneNone
26821Column K213'DripMPS SupplyArmstrong2011IVBT1250.754'300-5XXXConstantOKNoneNone
26921Column M20GLDripHPS SupplyArmstrong2011IVBT1250.756'900-10XXXConstantOKNoneNone
27021Column L193'DripLPS SupplySpirax-SarcoFT30F&T300.754'200OXXConstantOfflineTest when online.Test when online.
27121Column L182'DripMPS SupplyArmstrong2011IVBT1251.253'300-5XXXConstantOKNoneNone
27221Column L182'DripMPS SupplyArmstrong2011IVBT1251.253'300-5XXXConstantOKNoneNone
27321Column K171'DripLPS SupplyArmstrong2011IVBT1250.754'200XXXConstantOKNoneNone
27421Column M172'DripMPS SupplyArmstrong811IVBT700.753'600-5XXXConstantOkNoneNone
27521Column M172'DripMPS SupplyArmstrong811IVBT700.753'600-5XXXConstantOkNoneNone
27621Column M172'DripMPS SupplyArmstrong811IVBT700.753'600-5XXXConstantOkNoneNone
27721Column M17GLDripMPS SupplyArmstrong2011IVBT1250.753'600-5XXXConstantOKNoneNone
27821Column L171'DripMPS SupplyArmstrongTVS811-125IVBT1250.752'600-5XXXConstantOkNoneNone
27921Column L171'DripLPS SupplyArmstrong2011IVBT1250.754'200XXXConstantOKNoneNone
28021Column KB1'DripHPS SupplyArmstrong2011IVBT1250.752'900-10XXXConstantOKNoneNone
28121Column KB2'Liquid DrainerFlash TankArmstrongTVS811-125IVBT1250.752'600-5XXXConstantOkNoneNone
28221Column KB1'DripMPS SupplyArmstrongTVS812-125IVBT1250.753'600-5XXXConstantOkNoneNone
28321Column KB3'DripMPS SupplyArmstrong811IVBT700.753'600-5XXXConstantOkNoneNone
28421Column KBGLDripMPS SupplyArmstrong2011IVBT1250.753'600-5XXXConstantOKNoneNone
28521Column KB3'DripMPS SupplyArmstrong811IVBT700.753'600-5XXXConstantOkNoneNone
28621Column KA3'DripLPS SupplySpirax-SarcoFT30F&T300.753'200XXXConstantOfflineTest when online.Test when online.
28721#7 Stairs3'DripLPS SupplySpirax-SarcoFT30F&T300.753'200XXXConstantOfflineTest when online.Test when online.
28821Column H162'DripLPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
28921Column H173'DripLPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
29021Column G172'DripLPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
29121Column F173'DripLPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
29221Column F163'DripMPS SupplyArmstrong2011IVBT1250.753'600-5XXXConstantOKNoneNone
29321Column D163'DripMPS SupplyArmstrongTVS811-70IVBT700.753'600-5XXXConstantOfflineTest when online.Test when online.
29421Column J133'DripLPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
29521Column J133'DripLPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOkNoneNone
29621Column M133'DripLPS SupplyArmstrong2011IVBT12513'200XXXConstantOKNoneNone
29721Column M113'DripLPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
29821Column K113'DripLPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
29921Column K93'DripLPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
30021Column K113'DripLPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
30121Column F114'DripMPS SupplyArmstrongTVS811-70IVBT700.753'600-5OXXConstantOkPipe is broken on the inlet.Repair the piping.
30221Column M93'DripLPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
30321Column N73'DripLPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
30421Column N73'DripLPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
30521Column P73'DripLPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
30621Column N73'DripLPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
30721Column N73'DripLPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
30821Column M33'DripLPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
30921Column M23'DripMPS SupplyArmstrongTVS811-70IVBT700.753'600-5OXXConstantOkNoneNone
31021Column M23'DripLPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
31121Column M23'DripMPS SupplyArmstrong2011IVBT1250.753'350-5XXXConstantOKNoneNone
31221Column L23'DripMPS SupplyArmstrongTVS811-70IVBT700.753'600-5OXXConstantOkNoneNone
31321Column L23'DripMPS SupplyArmstrong2011IVBT1250.753'350-5XXXConstantOKNoneNone
31421Column L33'DripLPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
31521Column L43'DripMPS SupplyArmstrongTVS811-70IVBT700.753'350-5OXXConstantOkNoneNone
31621Column L43'DripMPS SupplyArmstrong2011IVBT1250.753'600-5XXXConstantOKNoneNone
31721Column K83'DripMPS SupplyArmstrong2011IVBT1250.753'550-5XXXConstantOKNoneNone
31821Column H53'DripMPS SupplyArmstrong2011IVBT1250.753'550-5XXXConstantOKNoneNone
31921Column J63'DripMPS SupplyArmstrong2011IVBT1250.753'550-5XXXConstantOKNoneNone
32021Column H82'DripLPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
32121Column F63'DripMPS SupplyArmstrong2011IVBT1250.753'550-5XXXConstantOKNoneNone
32221Column D74'DripMPS SupplyArmstrong2011IVBT1250.753'600-5XXXConstantOKNoneNone
32321Column D74'DripMPS SupplyArmstrong2011IVBT1250.753'600-5XXXConstantOKNoneNone
32421Column D74'DripMPS SupplyArmstrong2011IVBT1250.753'600-5XXXConstantOKNoneNone
32521Column C83'DripMPS SupplyArmstrong2011IVBT1250.753'550-5XXXConstantOKNoneNone
32621Column C83'DripMPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
32721Column B73'DripMPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
32821Column B93'DripMPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
32921Column E123'DripMPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
33021Column C133'DripMPS SupplyArmstrong2011IVBT1250.753'600-5XXXConstantOKNoneNone
33121Column C133'DripMPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
33221Column C143'DripMPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
33321Column C193'DripMPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
33421Column C193'DripMPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone
33521Column C203'DripMPS SupplyArmstrong2011IVBT1250.753'200XXXConstantOKNoneNone