Atch 8 Nashville VA Steam Components Name and Location Key.xlsx
XLSX spreadsheet 84 KB Posted
- Attached to
- Z1DA--626-24-204 - Update / Upgrade Steam System Components Federal contract opportunity
- Solicitation number
- 36C24924B0011
About this file
This document is a Statement of Work (SOW) for a federal contract opportunity to update and upgrade steam system components at the Tennessee Valley Healthcare System (TVHS) Nashville campus. The key objectives include replacing failing condensate return skid pumps and components, adding venting, and correcting piping and condensate return issues throughout the facility. The solicitation will result in one award, and the contractor is responsible for all work required to provide an acceptable final product. The contract period of performance is 120 calendar days from notice to proceed. The SOW provides details on the scope of work, guidelines and standards, work constraints, submittals, and requirements for work completion and contractor warranties.
View the file
Other files for this federal contract opportunity
Show all 32
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Facility Information
| Name | Location | Address |
| VA Tennessee Valley Medical Center | Nashville, TN 37212 | 1310 24th Ave S |
| Site Contacts | Phone Number | |
| George Yousef - Energy Engineer | george.yousef@va.gov | 502-422-2957 |
| Clint - Energy Plant Manager | ||
| Robert - Pipe Fitter |
| Facility Information | |
| 4WI-200-600-200 CB-LE Clever Brooks Firetube Boiler | 90 PSIG |
| 4WI-200-600-200 CB-LE Clever Brooks Firetube Boiler | 90 PSIG |
| 4WI-200-600-200 CB-LE Clever Brooks Firetube Boiler | 90 PSIG |
| BFS ZER-O-PAC Spray DA | 8 PSIG |
| Hours of Operation | Facility Steam Pressures |
| 8600 | 90 PSIG |
| 8600 | 60 PSIG |
| 8600 | 40 PSIG |
| 3600 | 35 PSIG |
| 3600 | 30 PSIG |
| 3600 | 25 PSIG |
| 3600 | 20 PSIG |
| 3600 | 15 PSIG |
| 3600 | 10 PSIG |
| 3600 | 5 PSIG |
| Cost of Fuel | |
| Cost per therm | $ 0.87 |
| Cost per MMBTU | $ 8.65 |
mailto:george.yousef@va.gov Routes
| Route # | Location |
| 1 | Boiler Room |
| 2 | Chiller Plant |
| 3 | Fan Room 4 |
| 4 | Fan Room 11 |
| 5 | Fan Room 5 |
| 6 | Fan Room 7 |
| 7 | Fan Room 17 |
| 8 | Fan Room 2 |
| 9 | Fan Room 1 |
| 10 | Fan Room 8 |
| 11 | Fan Room 14 |
| 12 | 2nd Floor Roof AHU's 35 & 42 |
| 13 | Fan Room 15 |
| 14 | Fan Room 6 |
| 15 | Fan Room 3 |
| 16 | Fan Room 16 |
| 17 | Level 5 Rooftop Cooling Tower |
| 18 | Acres Fan Room 8A |
| 19 | Acres Fan Room 9 |
| 20 | Acres Fan Room 10 |
| 21 | Hospital Sub-Basement |
Master List
| Trap # | Route | Location | Elevation | Application | Usage | Make | Model | Type | PMO | Connection Size | Condensate Lift | Pressure In | Pressure Out | Check Valve | Isolation In | Isolation Out | Constant/Modulating | Status | Comments | Recommendations |
| 1 | 1 | Above BLR1 | 15' | Drip | HPS Supply | Watson McDaniel | 1031 | IVBT | 125 | 0.75 | 4' | 90 | 0-10 | X | X | X | Constant | Ok | Condensate outlet ties into LP return main. | Remove piping from LP retrun and return directly to the DA. |
| 2 | 1 | Above BLR1 | 17' | Equipment | MAU Coil | Spirax-Sarco | FTI30 | F&T | 30 | 0.75 | 0' | 10 | 0 | X | X | X | Modulating | Flooded | Back pressure from trap 001 has caused this trap to fail. | Remove trap #001 return from the LP return system. |
| 3 | 1 | Water Heater Mezzanine | 1' | Drip | DA PRV Station - HP | Armstrong | TVS811-125 | IVBT | 125 | 0.75 | 0' | 90 | 0-10 | X | X | X | Constant | Blow Thru | Trap has failed. Condensate outlet ties into LP return main. | Repair/Replace, remove piping from LP retrun and return directly to the DA. |
| 4 | 1 | Water Heater Mezzanine | 1' | Drip | DA PRV Station - LP | Armstrong | TVS811-15 | IVBT | 15 | 0.75 | 0' | 10 | 0 | X | X | X | Constant | Blow Thru | Back pressure from trap 003 has caused this trap to fail. | Remove trap #003 return from the LP return system. |
| 5 | 1 | Water Heater Mezzanine | 1' | Drip | Main PRV Station - HP | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 90 | 0-10 | X | X | X | Constant | Ok | None | None |
| 6 | 1 | Water Heater Mezzanine | 7' | Drip | WH PRV - LP | Armstrong | 15B3 | F&T | 15 | 0.75 | 0' | 10 | 0 | O | X | X | Constant | Blow Thru | Bad application for a modulating pressure application steam trap. | Replace with a constant pressure application steam trap. |
| 7 | 1 | Water Heater Mezzanine | 7' | Drip | WH PRV - HP | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 90 | 0-10 | X | X | X | Constant | Ok | None | None |
| 8 | 1 | Water Heater Mezzanine | GL | Drip | PRV4 | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 9 | 1 | Water Heater Mezzanine | 7' | Drip | PRV1 | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 40 | 0-5 | X | X | X | Constant | OK | None | None |
| 10 | 1 | Water Heater Mezzanine | GL | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 20 | 0 | X | X | X | Constant | Ok | None | None |
| 11 | 1 | Above Stairs | 9' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 20 | 0 | X | X | X | Constant | Ok | None | None |
| 12 | 1 | Water Heaters | 1' | Drip | MPS Supply | Armstrong | 800-80 | IVBT | 80 | 0.75 | 2' | 40 | 0-5 | X | X | X | Constant | Ok | None | None |
| 13 | 1 | Water Heaters | 1' | Drip | MPS Supply | Armstrong | 800-80 | IVBT | 80 | 0.75 | 2' | 40 | 0-5 | X | X | X | Constant | Ok | None | None |
| 14 | 1 | Water Heaters | 1' | Drip | MPS Supply | Armstrong | 800-80 | IVBT | 80 | 0.75 | 2' | 40 | 0-5 | X | X | X | Constant | Ok | None | None |
| 15 | 1 | Water Heaters | 1' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 2' | 40 | 0-5 | X | X | X | Constant | OK | None | None |
| 16 | 1 | Water Heaters | 1' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 40 | 0-5 | X | X | X | Constant | OK | None | None |
| 17 | 1 | Water Heaters | 1' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 40 | 0-5 | X | X | X | Constant | OK | None | None |
| 18 | 1 | Water Heaters | 1' | Drip | MPS Supply | Hoffman | B1125A | IVBT | 125 | 0.75 | 0' | 40 | 0-5 | X | X | X | Constant | OK | None | None |
| 19 | 1 | In front of BLR1 | 10' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 10' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 20 | 1 | Near exit | 8' | Equipment | Unit Heater | Armstrong | 30A3 | F&T | 30 | 0.75 | 10' | 20 | 0 | X | X | X | Constant | Ok | None | None |
| 21 | 1 | In front of BLR2 | 8' | Equipment | Unit Heater | Armstrong | 2011 | IVBT | 125 | 0.75 | 10' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 22 | 1 | In front of BLR3 | 8' | Equipment | Unit Heater | Armstrong | 30A3 | F&T | 30 | 0.75 | 10' | 20 | 0 | X | X | X | Constant | Ok | None | None |
| 23 | 1 | In front of BLR3 | 9' | Drip | LPS Supply | Armstrong | TVS811 | IVBT | 125 | 0.75 | 0' | 20 | 0 | X | X | X | Constant | Ok | None | None |
| 24 | 1 | Near gauge station | 7' | Drip | HPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 90 | 0-10 | X | X | X | Constant | OK | None | None |
| 25 | 2 | Near condenser water strainer | 2' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 26 | 2 | Near condenser water strainer | 6' | Drip | HPS Supply | Armstrong | TVS811 | IVBT | 125 | 0.75 | 0' | 90 | 0-10 | X | X | X | Constant | Ok | None | None |
| 27 | 2 | Above Heating Water Pumps | 6' | Drip | HPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 90 | 0-10 | X | X | X | Constant | OK | None | None |
| 28 | 2 | Above Heating Water Pumps | 6' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 30 | 0-5 | X | X | X | Constant | OK | None | None |
| 29 | 2 | Above York VSD | 6' | Equipment | Heat Exchanger | Armstrong | ICS | F&T | 125 | 0.75 | 0' | 20 | 0 | X | X | X | Modulating | OK | None | None |
| 30 | 2 | Above York VSD | 6' | Equipment | Heat Exchanger | Hoffman | FT075X8 | F&T | 75 | 2 | 0' | 20 | 0 | X | X | X | Modulating | Ok | None | None |
| 31 | 3 | AC22 Steam Supply | 9' | Drip | MPS Supply | Armstrong | 811 | IVBT | 70 | 0.75 | 0' | 30 | 0-5 | X | X | X | Constant | Offline | Humidifier not in used due to no drain pan installed. | Install a drain pan, turn steam back on and test. |
| 32 | 3 | AC22 Steam Supply | 9' | Equipment | Steam Coil | Armstrong | 30A3 | F&T | 30 | 0.75 | 0' | 30 | 0-5 | X | X | X | Modulating | Offline | Humidifier not in used due to no drain pan installed. | Install a drain pan, turn steam back on and test. |
| 33 | 3 | AC22 Steam Supply | 9' | Equipment | Steam Coil | Armstrong | 30A3 | F&T | 30 | 0.75 | 0' | 30 | 0-5 | X | X | X | Modulating | Offline | Humidifier not in used due to no drain pan installed. | Install a drain pan, turn steam back on and test. |
| 34 | 3 | AHU-21 | GL | Drip | LPS Supply | Spirax-Sarco | UTD52L | Disk | 600 | 0.5 | 1' | 30 | 0-5 | X | X | X | Constant | Ok | None | None |
| 35 | 3 | AHU-21 | GL | Pump Trap | AHU-21 | Spirax-Sarco | PPC | F&T | 150 | 2 | 12' | 30 | 0-5 | X | X | X | Constant | Ok | None | None |
| 36 | 3 | AHU-21 | 1' | Equipment | Steam Coil | Spirax-Sarco | FTI125 | F&T | 125 | 1.5 | 0' | 30 | 0-5 | X | X | X | Modulating | Ok | None | None |
| 37 | 3 | AHU-21 | 1' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 30 | 0-5 | X | X | X | Constant | Ok | None | None |
| 38 | 3 | AHU-21 | 1' | Equipment | Steam Coil | Mepco | 44-275A | F&T | 75 | 0.75 | 0' | 30 | 0-5 | X | X | X | Modulating | Ok | None | None |
| 39 | 3 | AHU-18 | 2' | Drip | LPS Supply | Mepco | 1B11 | IVBT | 15 | 0.75 | 0' | 5 | 0 | X | X | X | Constant | Blow Thru | Trap has failed. | Repair/Replace |
| 40 | 3 | AHU-18 | 1' | Equipment | Humidifier | Mepco | 44-215A | F&T | 15 | 0.75 | 0' | 5 | 0 | X | X | X | Modulating | Ok | None | None |
| 41 | 3 | AHU-18 | GL | Pump Trap | Humidifier | Johnson | LMHT-500 | F&T | 200 | 1 | 12' | 30 | 0-5 | X | X | X | Constant | Flooded | Pump mechanism has failed and needs rebuilt. | Rebuild the pump trap mechanism. |
| 42 | 3 | AHU-18 | 7' | Drip | MPS Supply | Armstrong | TVS811 | IVBT | 125 | 0.75 | 0' | 30 | 0-5 | X | X | X | Constant | Ok | None | None |
| 43 | 3 | AHU-18 | 1 | Equipment | Steam Coil | Mepco | IB14 | IVBT | 30 | 1.5 | 10' | 30 | 0-5 | X | X | X | Modulating | Offline | Control valve does not open when called for. | Check controls. |
| 44 | 3 | AHU-17 VSD | 7' | Drip | MPS Supply | Armstrong | TVS811 | IVBT | 125 | 0.75 | 0' | 30 | 0-5 | X | X | X | Constant | Ok | None | None |
| 45 | 3 | AHU-17 | 1' | Equipment | Steam Coil | Spirax-Sarco | UFT-32 | F&T | 450 | 0.75 | 0' | 30 | 0-5 | X | X | X | Modulating | Offline | Control valve does not open when called for. | Check controls. |
| 46 | 3 | AHU-17 | 1' | Drip | MPS Supply | Armstrong | TVS811 | IVBT | 125 | 0.75 | 0' | 30 | 0-5 | X | X | X | Constant | Offline | Control valve does not open when called for. | Check controls. |
| 47 | 3 | AHU-17 | 1' | Equipment | Steam Coil | Armstrong | TVS811 | IVBT | 125 | 0.75 | 0' | 30 | 0-5 | X | X | X | Modulating | Offline | Control valve does not open when called for. | Check controls. |
| 48 | 3 | AHU-17 | 1' | Equipment | Steam Coil | Armstrong | TVS811 | IVBT | 125 | 0.75 | 0' | 30 | 0-5 | X | X | X | Modulating | Offline | Control valve does not open when called for. | Check controls. |
| 49 | 3 | Clean Steam Generator | 9' | Drip | MPS Supply | Armstrong | TVS811 | IVBT | 125 | 0.75 | 0' | 30 | 0-5 | X | X | X | Constant | Ok | None | None |
| 50 | 3 | Clean Steam Generator | 3' | Equipment | Steam Coil | Hoffman | FT030H3 | F&T | 30 | 0.75 | 0' | 30 | 0-5 | O | O | O | Modulating | Offline | Generator is currently shut down due to maintenance. | Check when generator has been repaired. |
| 51 | 3 | Clean Steam Generator | 4' | Drip | MPS Supply | Hoffman | FT030H3 | F&T | 30 | 0.75 | 0' | 30 | 0-5 | O | O | O | Constant | Offline | Generator is currently shut down due to maintenance. | Check when generator has been repaired. |
| 52 | 3 | Heat Exchanger | 2' | Drip | MPS Supply | Spirax-Sarco | TD52 | Disk | 600 | 0.75 | 2' | 30 | 0-5 | O | X | O | Constant | Ok | None | None |
| 53 | 3 | Heat Exchanger | GL | Pump Trap | Heat Exchanger | Spirax-Sarco | PPC | F&T | 150 | 2 | 8' | 30 | 0-5 | X | X | X | Constant | Ok | None | None |
| 54 | 4 | Unit Heater Discharge | 10' | Equipment | Unit Heater | Spirax-Sarco | FT15 | F&T | 15 | 0.75 | 0' | 20 | 0 | X | O | X | Constant | Ok | None | None |
| 55 | 4 | Corner of the room | 6' | Drip | LPS Supply | Mepco | 40-215A | F&T | 15 | 0.75 | 0' | 20 | 0 | O | X | X | Constant | Ok | Condensate outlet dumps to drain. | Return the condensate to the pump skid. |
| 56 | 4 | AC-20 | 1' | Equipment | Steam Coil | Mepco | 40-215A | F&T | 15 | 0.75 | 0' | 20 | 0 | X | X | X | Modulating | OK | None | None |
| 57 | 4 | AC-20 | 1' | Equipment | Steam Coil | Mepco | 40-215A | F&T | 15 | 0.75 | 0' | 20 | 0 | X | X | X | Modulating | OK | None | None |
| 58 | 4 | AC-20 | 1' | Equipment | Steam Coil | Armstrong | ICS | F&T | 125 | 2 | 0' | 20 | 0 | X | X | X | Modulating | OK | None | None |
| 59 | 4 | AC-20 | GL | Pump Trap | AC-20 | Armstrong | PT-104 | F&T | 100 | 1 | 12' | 20 | 0 | X | X | X | Constant | Ok | None | None |
| 60 | 5 | PRV Station | GL | Drip | HPS Supply | Armstrong | TVS811–125 | IVBT | 125 | 0.75 | 5' | 90 | 0-10 | X | X | X | Constant | Blow Thru | Trap has failed. | Repair/Replace |
| 61 | 5 | PRV Station | 2' | Drip | MPS Supply | Armstrong | TVS811–125 | IVBT | 125 | 0.75 | 5' | 30 | 0-5 | X | X | X | Constant | Ok | None | None |
| 62 | 5 | Heat Exchanger | 4' | Equipment | Heat Exchanger | Armstrong | 30B8 | F&T | 30 | 2 | 0' | 30 | 0-5 | X | X | X | Modulating | Ok | None | None |
| 63 | 5 | Heat Exchanger | 4' | Equipment | Heat Exchanger | Armstrong | 30B8 | F&T | 30 | 2 | 0' | 30 | 0-5 | X | X | X | Modulating | Ok | None | None |
| 64 | 5 | Heat Exchanger | GL | Pump Trap | Heat Exchanger | Spirax-Sarco | PTC | F&T | 200 | 2 | 15' | 90 | 0-10 | X | X | X | Constant | Ok | None | None |
| 65 | 5 | AHU-16 | 3' | Equipment | Steam Coil | Spirax-Sarco | SIB30 | IVBT | 435 | 0.75 | 0' | 30 | 0-5 | X | X | X | Modulating | OK | None | None |
| 66 | 5 | AHU-16 | 3' | Equipment | Steam Coil | Spirax-Sarco | SIB30 | IVBT | 435 | 0.75 | 0' | 30 | 0-5 | X | X | X | Modulating | OK | None | None |
| 67 | 5 | AHU-16 Behind Column | 3' | Drip | MPS Supply | Mepco | 1031 | IVBT | 125 | 0.75 | 0' | 30 | 0-5 | X | X | X | Constant | Ok | None | None |
| 68 | 5 | Clean Steam Generator | 3' | Equipment | Steam Coil | Hoffman | FT030H3 | F&T | 30 | 0.75 | 0' | 30 | 0-5 | O | O | O | Modulating | OK | None | None |
| 69 | 5 | Clean Steam Generator | 4' | Drip | MPS Supply | Hoffman | FT030H3 | F&T | 30 | 0.75 | 0' | 30 | 0-5 | O | O | O | Constant | OK | Bad application for a modulating pressure steam trap. Outlet tied into the heat exchanger outlet. | None |
| 70 | 6 | PRV Station | 4' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 30 | 0-5 | X | X | X | Constant | OK | None | None |
| 71 | 6 | AHU7 | 6' | Equipment | Humidifier | Armstrong | 30B3 | F&T | 30 | 0.75 | 0' | 30 | 0-5 | O | O | X | Modulating | Offline | Humidifier is valved with 2 control valves. This should always be hot or the safety valve needs to be open prior to the modulating valve. | Test when the humidifier is hot. |
| 72 | 6 | AHU7 | 6' | Drip | Humidifier | Armstrong | 811 | IVBT | 70 | 0.75 | 0' | 30 | 0-5 | X | O | X | Constant | Offline | Humidifier is valved with 2 control valves. This should always be hot or the safety valve needs to be open prior to the modulating valve. | Test when the humidifier is hot. |
| 73 | 6 | AHU3 | 7' | Drip | Humidifier | Armstrong | 800 | IVBT | 70 | 0.75 | 0' | 30 | 0-5 | X | O | X | Constant | Offline | Humidifier is valved with 2 control valves. This should always be hot or the safety valve needs to be open prior to the modulating valve. | Test when the humidifier is hot. |
| 74 | 6 | AHU7 | 6' | Drip | MPS Supply | Armstrong | 800 | IVBT | 70 | 0.75 | 0' | 30 | 0-5 | X | X | X | Constant | Ok | None | None |
| 75 | 6 | AHU7 | GL | Equipment | Steam Coil | Armstrong | 30B3 | F&T | 30 | 0.75 | 0' | 30 | 0-5 | X | X | X | Modulating | Ok | None | None |
| 76 | 6 | AHU7 | GL | Equipment | Steam Coil | Armstrong | 30B3 | F&T | 30 | 0.75 | 0' | 30 | 0-5 | X | X | X | Modulating | Ok | None | None |
| 77 | 6 | AHU3 | GL | Equipment | Steam Coil | Armstrong | 30B3 | F&T | 30 | 0.75 | 0' | 30 | 0-5 | X | X | X | Modulating | OK | None | None |
| 78 | 6 | AHU3 | GL | Equipment | Steam Coil | Armstrong | 30B3 | F&T | 30 | 0.75 | 0' | 30 | 0-5 | X | X | X | Modulating | OK | None | None |
| 79 | 6 | Near Exit | 8' | Equipment | Unit Heater | Armstrong | TVS811–125 | IVBT | 125 | 0.75 | 5' | 30 | 0-5 | X | X | X | Constant | Ok | None | None |
| 80 | 7 | Above 1ECCE Panel | 8' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 30 | 0-5 | X | X | X | Constant | OK | None | None |
| 81 | 7 | AHU54 | 6' | Drip | Steam Coil | Armstrong | TVS811–125 | IVBT | 125 | 0.75 | 0' | 30 | 0-5 | O | X | X | Constant | Ok | None | None |
| 82 | 7 | AHU54 | GL | Equipment | Steam Coil | Armstrong | 30B5 | F&T | 30 | 1.25 | 0' | 30 | 0-5 | X | X | X | Modulating | Ok | None | None |
| 83 | 7 | AHU54 | GL | Equipment | Steam Coil | Armstrong | 30B5 | F&T | 30 | 1.25 | 0' | 30 | 0-5 | X | X | X | Modulating | Ok | None | None |
| 84 | 7 | AHU54 | GL | Equipment | Steam Coil | Armstrong | 30B5 | F&T | 30 | 1.25 | 0' | 30 | 0-5 | X | X | X | Modulating | Ok | None | None |
| 85 | 7 | AHU55 | 7' | Drip | Steam Coil | Armstrong | 811–125 | IVBT | 125 | 0.75 | 0' | 30 | 0-5 | O | X | X | Constant | Ok | None | None |
| 86 | 7 | AHU56 | 3' | Equipment | Steam Coil | Armstrong | 15B3 | F&T | 15 | 0.75 | 0' | 30 | 0-5 | X | X | X | Modulating | Ok | None | None |
| 87 | 7 | AHU57 | 2' | Equipment | Steam Coil | Armstrong | 15B3 | F&T | 15 | 0.75 | 0' | 30 | 0-5 | X | X | X | Modulating | Ok | None | None |
| 88 | 8 | AHU-3AR | GL | Equipment | Steam Coil | Armstrong | 15B3 | F&T | 15 | 0.75 | 0' | 20 | 0 | X | X | X | Modulating | OK | None | None |
| 89 | 8 | AHU-50 | 8' | Drip | LPS Supply | Armstrong | TVS811–125 | IVBT | 125 | 0.75 | 0' | 20 | 0 | X | X | X | Constant | Ok | None | None |
| 90 | 8 | AHU-50 | GL | Drip | LPS Supply | Armstrong | TVS811–125 | IVBT | 125 | 0.75 | 0' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 91 | 8 | AHU-50 | GL | Equipment | Steam Coil | Armstrong | ICS | F&T | 125 | 0.75 | 0' | 20 | 0 | X | X | X | Modulating | OK | None | None |
| 92 | 8 | AHU-3AR | 1' | Drip | Humidifier | Armstrong | TVS811-15 | IVBT | 15 | 0.75 | 0' | 10 | 0 | X | X | X | Constant | Ok | None | None |
| 93 | 8 | AHU-3AR | 1' | Equipment | Humidifier | Colton Ind | FTX30 | F&T | 30 | 0.75 | 0' | 10 | 0 | X | X | X | Modulating | Ok | None | None |
| 94 | 8 | Above AHU-50 Ductwork | 12' | Equipment | Unit Heater | Spirax-Sarco | FT30 | F&T | 30 | 0.75 | 0' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 95 | 8 | Along Wall Above Ductwork | 12' | Drip | LPS Supply | Armstrong | TVS811–125 | IVBT | 125 | 0.75 | 0' | 20 | 0 | X | X | X | Constant | Ok | None | None |
| 96 | 8 | Above Door Ductwork | 12' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 20 | 0 | X | X | X | Constant | Ok | None | None |
| 97 | 9 | PRV Station | 1' | Drip | HPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 10' | 90 | 0-10 | X | X | X | Constant | OK | None | None |
| 98 | 9 | PRV Station | 1' | Drip | LPS Supply | Armstrong | TVS811-15 | IVBT | 15 | 0.75 | 10' | 15 | 10 | X | X | X | Constant | Flooded | Backpressure from trap 97 is causing this trap to fail. | Remove outlet from the high pressure return system. |
| 99 | 9 | PRV Station | 7' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 10' | 60 | 0-5 | X | X | X | Constant | OK | None | None |
| 100 | 9 | Heat Exchanger | 2' | Equipment | Heat Exchanger | Armstrong | 30B8 | F&T | 30 | 2 | 0' | 15 | 0 | O | X | X | Modulating | Ok | None | None |
| 101 | 9 | Heat Exchanger | 2' | Equipment | Heat Exchanger | Armstrong | 30B8 | F&T | 30 | 2 | 0' | 15 | 0 | O | X | X | Modulating | Ok | None | None |
| 102 | 9 | Heat Exchanger | 2' | Equipment | Heat Exchanger | Armstrong | 30B8 | F&T | 30 | 2 | 0' | 15 | 0 | O | X | X | Modulating | Ok | None | None |
| 103 | 9 | Heat Exchanger | 2' | Equipment | Heat Exchanger | Armstrong | 30B8 | F&T | 30 | 2 | 0' | 15 | 0 | O | X | X | Modulating | Ok | None | None |
| 104 | 9 | Above Heating Water Pumps | 7' | Drip | LPS Supply | Armstrong | TVS811-15 | IVBT | 15 | 0.75 | 0' | 15 | 0 | X | X | X | Constant | Ok | None | None |
| 105 | 9 | AHU-6 | 7' | Drip | LPS Supply | Armstrong | TVS811-15 | IVBT | 15 | 0.75 | 0' | 15 | 0 | X | X | X | Constant | Blow Thru | Trap has failed. | Repair/Replace |
| 106 | 9 | AHU-6 | 5' | Drip | Steam Coil | Armstrong | 15B3 | F&T | 15 | 0.75 | 0' | 15 | 0 | X | X | X | Constant | Flooded | Trap is installed upside down. Bad application for a modulating style steam trap. | Replace with a constant pressure application steam trap. |
| 107 | 9 | AHU-6 | GL | Equipment | Steam Coil | Spirax-Sarco | FT15 | F&T | 15 | 1.5 | 0' | 15 | 0 | X | X | X | Modulating | Ok | None | None |
| 108 | 9 | AHU-6 | 8' | Drip | LPS Supply | Armstrong | 811 | IVBT | 15 | 0.75 | 0' | 15 | 0 | X | X | X | Constant | Ok | None | None |
| 109 | 9 | AHU-11 | 2' | Drip | LPS Supply | Armstrong | 15B3 | F&T | 15 | 0.75 | 0' | 15 | 0 | X | X | X | Modulating | OK | None | None |
| 110 | 9 | AHU-11 | 2' | Drip | LPS Supply | Armstrong | 15B4 | F&T | 15 | 1 | 0' | 15 | 0 | X | X | X | Modulating | OK | None | None |
| 111 | 9 | AHU-11 | GL | Equipment | Steam Coil | Armstrong | 30B8 | F&T | 30 | 2 | 0' | 15 | 0 | O | X | X | Modulating | Ok | None | None |
| 112 | 9 | AHU-5 | GL | Equipment | Steam Coil | Armstrong | 30B8 | F&T | 30 | 2 | 0' | 15 | 0 | O | X | X | Modulating | Ok | None | None |
| 113 | 9 | AHU-5 | GL | Equipment | Steam Coil | Armstrong | 30B8 | F&T | 30 | 2 | 0' | 15 | 0 | O | X | X | Modulating | Ok | None | None |
| 114 | 9 | AHU-5 | GL | Equipment | Steam Coil | Armstrong | 30B8 | F&T | 30 | 2 | 0' | 15 | 0 | O | X | X | Modulating | Ok | None | None |
| 115 | 9 | On top of AHU-11 | 8 | Drip | LPS Supply | Spirax-Sarco | FT15 | F&T | 30 | 0.75 | 0' | 15 | 0 | X | X | X | Constant | Ok | Bad application for a modulating pressure application steam trap. | None |
| 116 | 9 | AHU-5 | GL | Drip | LPS Supply | Armstrong | TVS811-15 | IVBT | 15 | 0.75 | 0' | 15 | 0 | X | X | X | Constant | Ok | None | None |
| 117 | 9 | AHU-5 | GL | Drip | LPS Supply | Nortec | 159 9601 | F&T | 125 | 0.75 | 0' | 15 | 0 | X | X | X | Constant | Ok | None | None |
| 118 | 10 | LPS Supply | 7' | Drip | LPS Supply | Armstrong | TVS811-15 | IVBT | 15 | 0.75 | 0' | 15 | 0 | X | X | X | Constant | Ok | None | None |
| 119 | 10 | LPS Supply | 3' | Drip | LPS Supply | Armstrong | TVS811-15 | IVBT | 15 | 0.75 | 0' | 15 | 0 | X | X | X | Constant | Blow Thru | Trap has failed. | Repair/Replace |
| 120 | 10 | Unit Heater | 7' | Equipment | Unit Heater | Armstrong | 15B3 | F&T | 15 | 0.5 | 0' | 15 | 0 | X | X | X | Constant | Offline | Unit heater is not used. Valved off, not controlled by BAS. | Remove from service or force to operation and check status. |
| 121 | 10 | AHU-2 | 6' | Equipment | Steam Coil | Armstrong | 25JD8 | F&T | 25 | 2 | 0' | 15 | 0 | O | X | X | Modulating | Ok | None | None |
| 122 | 10 | AHU-2 | 3' | Drip | LPS Supply | Armstrong | TVS811-30 | IVBT | 30 | 0.75 | 0' | 15 | 0 | X | X | X | Constant | Ok | None | None |
| 123 | 10 | AHU-2 | GL | Equipment | Steam Coil | Armstrong | 25JD8 | F&T | 25 | 2 | 0' | 15 | 0 | O | X | X | Modulating | Ok | None | None |
| 124 | 10 | AHU-2 | 2' | Equipment | Steam Coil | TLV | SS3N-10/B | F&T | 345 | 0.75 | 0' | 15 | 0 | O | X | X | Modulating | Ok | None | None |
| 125 | 10 | AHU-2 | 3' | Drip | LPS Supply | Armstrong | TVS811-30 | IVBT | 30 | 0.75 | 0' | 15 | 0 | X | X | X | Constant | Ok | None | None |
| 126 | 10 | AHU-2 PRV Station | 2' | Drip | HPS Supply | Armstrong | TVS811-125 | IVBT | 125 | 0.75 | 0' | 90 | 0-10 | X | X | X | Constant | Ok | The condensate outlet is tied to low pressure return. | Separate return line from LPR. |
| 127 | 10 | AHU-2 PRV Station | 2' | Drip | LPS Supply | Armstrong | TVS811-125 | IVBT | 125 | 0.75 | 0' | 15 | 0 | X | X | X | Constant | Ok | None | None |
| 128 | 11 | Behind AHU-37/38 | 2' | Drip | MPS Supply | Spirax-Sarco | TD52 | Disk | 600 | 0.75 | 0' | 15 | 0 | O | X | X | Constant | Ok | None | None |
| 129 | 11 | Behind AHU-37/38 | 4' | Equipment | Steam Coil | Spirax-Sarco | TD52 | Disk | 600 | 0.75 | 0' | 15 | 0 | O | X | X | Modulating | OK | None | None |
| 130 | 11 | Behind AHU-37/38 | 1' | Equipment | Steam Coil | Spirax-Sarco | TD52 | Disk | 600 | 0.75 | 0' | 15 | 0 | O | X | X | Modulating | OK | None | None |
| 131 | 11 | Beside AHU-37/38 | GL | Equipment | Steam Coil | Armstrong | 30B6 | F&T | 30 | 1.25 | 0' | 15 | 0 | O | X | X | Modulating | Flooded | Trap position is rotated down. | Repair/Replace |
| 132 | 11 | Beside AHU-37/38 | 3' | Equipment | Steam Coil | Hoffman | 550 | F&T | 30 | 1.25 | 0' | 15 | 0 | O | X | X | Modulating | Ok | None | None |
| 133 | 11 | Beside AHU-37/38 | 4' | Drip | Steam Coil | Armstrong | TVS811-15 | IVBT | 15 | 0.75 | 0' | 15 | 0 | O | X | X | Modulating | Offline | High limit duct humid-a-stat prevents valve override. | Test when operational. |
| 134 | 11 | Beside AHU-37/38 | 4' | Equipment | Steam Coil | Mepco | 40-215A | F&T | 15 | 0.75 | 0' | 15 | 0 | O | X | X | Modulating | Offline | High limit duct humid-a-stat prevents valve override. | Test when operational. |
| 135 | 11 | Beside AHU-37/38 | 4' | Drip | Steam Coil | Armstrong | TVS811-15 | IVBT | 15 | 0.75 | 0' | 15 | 0 | O | X | X | Modulating | Offline | High limit duct humid-a-stat prevents valve override. | Test when operational. |
| 136 | 11 | Beside AHU-37/38 | 4' | Equipment | Steam Coil | Mepco | 40-215A | F&T | 15 | 0.75 | 0' | 15 | 0 | O | X | X | Modulating | Offline | High limit duct humid-a-stat prevents valve override. | Test when operational. |
| 137 | 12 | AHU56 | 3' | Equipment | Steam Coil | Armstrong | 30A3 | F&T | 30 | 1.75 | 0' | 15 | 0 | O | X | X | Modulating | OK | None | None |
| 138 | 12 | AHU56 | 3' | Equipment | Steam Coil | Armstrong | TVS811-15 | IVBT | 15 | 0.75 | 0' | 15 | 0 | O | X | X | Modulating | OK | Bad application for a constant pressure application steam trap. | None |
| 139 | 12 | AHU56 | 1' | Drip | LPS Supply | Armstrong | 811 | IVBT | 30 | 0.75 | 0' | 15 | 0 | O | X | X | Modulating | Flooded | Trap has failed. Bad application for a constant pressure steam trap. | Replace with a modulating pressure steam trap. |
| 140 | 12 | AHU56 | 6' | Drip | LPS Supply | Armstrong | 811 | IVBT | 30 | 0.75 | 0' | 15 | 0 | O | X | X | Constant | Ok | None | None |
| 141 | 13 | PRV Station | 2' | Drip | HPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 60 | 0-5 | X | X | X | Constant | OK | None | None |
| 142 | 13 | PRV Station | 2' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | OK | None | None |
| 143 | 13 | Flash Tank | 3' | Drip | MPS Supply | Watson McDaniel | 1031 | IVBT | 150 | 1.75 | 0' | 25 | 0 | O | X | X | Constant | Ok | None | None |
| 144 | 13 | Flash Tank | GL | Pump Trap | Fan Room 15 | Spirax-Sarco | PTC | F&T | 200 | 2 | 15' | 90 | 0-10 | X | X | X | Constant | Leaking | Pump mechanism has failed and needs rebuilt. | Rebuild the pump trap mechanism. |
| 145 | 13 | Unit Heater | 9' | Equipment | Unit Heater | Armstrong | TVS811-70 | IVBT | 70 | 0.75 | 0' | 25 | 0 | O | X | X | Constant | Ok | None | None |
| 146 | 13 | Above Flash Tank | 12' | Drip | LPS Supply | Armstrong | TVS811-70 | IVBT | 70 | 0.75 | 0' | 15 | 0 | O | X | X | Constant | Ok | None | None |
| 147 | 13 | Above Flash Tank | 12' | Equipment | Heat Exchanger | Armstrong | 15B3 | F&T | 15 | 0.75 | 0' | 15 | 0 | X | X | X | Modulating | OK | None | None |
| 148 | 13 | Above Flash Tank | 12' | Equipment | Heat Exchanger | Armstrong | 15B3 | F&T | 15 | 0.75 | 0' | 15 | 0 | X | X | X | Modulating | OK | None | None |
| 149 | 13 | Above Flash Tank | 12' | Equipment | Heat Exchanger | Armstrong | 15B3 | F&T | 15 | 0.75 | 0' | 15 | 0 | X | X | X | Modulating | OK | None | None |
| 150 | 13 | Above Flash Tank | 12' | Equipment | Heat Exchanger | Armstrong | 15B3 | F&T | 15 | 0.75 | 0' | 15 | 0 | X | X | X | Modulating | OK | None | None |
| 151 | 13 | Between AHU39 & 40 | 10' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | OK | None | None |
| 152 | 13 | AHU-39 Humidifier | 1' | Drip | MPS Supply | Armstrong | 800 | IVBT | 30 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | Offline | Humidifier is isolated off with manual valve. Outlet trap is abandoned. | Test when valve can be opened. |
| 153 | 13 | Above Pit | GL | Equipment | Humidifier | Armstrong | 812 | IVBT | 30 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | Abandoned | Trap inlet is cut and capped. | Fix piping, test trap. |
| 154 | 13 | Above Pit | GL | Equipment | Steam Coil | Unknown | Unknown | F&T | UNK | 2 | 0' | 25 | 0 | X | X | X | Modulating | Ok | None | None |
| 155 | 13 | In Pit | 2' | Drip | MPS Supply | Watson McDaniel | 1032 | IVBT | 150 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | Ok | None | None |
| 156 | 13 | In Pit | GL | Pump Trap | AHU-39 | Spirax-Sarco | PPEC | F&T | 125 | 1 | 15' | 60 | 0-5 | X | X | X | Constant | Leaking | Pump mechanism has failed and needs rebuilt. | Rebuild the pump trap mechanism. |
| 157 | 13 | AHU-40 Unit Heater | 10' | Equipment | Unit Heater | Hoffman | FT015H4 | F&T | 15 | 1 | 0' | 25 | 0 | O | O | X | Constant | OK | None | None |
| 158 | 13 | AHU-40 | 1' | Drip | Humidifier | Armstrong | 800 | IVBT | 80 | 0.75 | 0' | 25 | 0 | X | O | X | Constant | Offline | Humidifier is isolated off with manual valve. | Test when valve can be opened. |
| 159 | 13 | AHU-40 | GL | Equipment | Humidifier | Armstrong | 811 | IVBT | 70 | 0.75 | 0' | 25 | 0 | X | O | X | Constant | Offline | Humidifier is isolated off with manual valve. | Test when valve can be opened. |
| 160 | 13 | AHU-41 | 1' | Equipment | Humidifier | Armstrong | ICS | F&T | 125 | 1 | 0' | 25 | 0 | X | X | X | Modulating | OK | None | None |
| 161 | 13 | AHU-41 | 1' | Drip | Humidifier | Armstrong | 2011 | IVBT | 125 | 0.5 | 0' | 25 | 0 | X | X | X | Constant | OK | None | None |
| 162 | 13 | AHU-41 | 1' | Drip | Humidifier | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | OK | None | None |
| 163 | 13 | AHU-41 | 12' | Drip | MPS Supply | Spirax-Sarco | FT-30 | F&T | 30 | 0.75 | 0' | 25 | 0 | X | X | X | Modulating | Ok | None | None |
| 164 | 13 | AHU-41 | 3' | Drip | Steam Coil | Hoffman | FT015H4 | F&T | 15 | 1 | 0' | 25 | 0 | X | X | X | Modulating | OK | None | None |
| 165 | 13 | AHU-41 | 3' | Drip | Steam Coil | Hoffman | FT015H4 | F&T | 15 | 1 | 0' | 25 | 0 | X | X | X | Modulating | OK | None | None |
| 166 | 13 | AHU-41 | 0' | Equipment | Steam Coil | Hoffman | FT015H5 | F&T | 15 | 1.25 | 1' | 25 | 0 | X | X | X | Modulating | OK | None | None |
| 167 | 13 | AHU-41 | 0' | Equipment | Steam Coil | Hoffman | FT015H5 | F&T | 15 | 1.25 | 1' | 25 | 0 | X | X | X | Modulating | Blow Thru | Trap has failed. | Repair/Replace |
| 168 | 13 | AHU-40 | 15' | Drip | end of main | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | OK | None | None |
| 169 | 13 | AHU-40 | 1' | Equipment | Steam Coil | Hoffman | FT030C8 | F&T | 30 | 2 | 0' | 25 | 0 | O | O | X | Modulating | Ok | None | None |
| 170 | 13 | AHU-40 Pit | 2' | Drip | MPS Supply | Armstrong | TVS811-70 | IVBT | 70 | 0.75 | 0' | 25 | 0 | O | X | X | Constant | Ok | None | None |
| 171 | 13 | AHU-40 Pit | 2' | Pump Trap | AHU-40 & 41 | Spirax-Sarco | PPEC | F&T | 125 | 1 | 20' | 25 | 10 | X | X | X | Constant | Blow Thru | Pump mechanism has failed and needs rebuilt. | Rebuild the pump trap mechanism. |
| 172 | 13 | AHU-40 Pit | 2' | Drip | MPS Supply | Armstrong | TVS811-70 | IVBT | 70 | 0.75 | 0' | 25 | 0 | O | X | X | Constant | Ok | None | None |
| 173 | 13 | AHU-40 Pit | 2' | Pump Trap | AHU-40 & 41 | Spirax-Sarco | PPEC | F&T | 125 | 1 | 20' | 25 | 10 | X | X | X | Constant | Ok | None | None |
| 174 | 14 | AHU-24 | 12' | Drip | Humidifier | Armstrong | 811 | IVBT | 70 | 0.75 | 0' | 30 | 0-5 | X | X | X | Modulating | Offline | Humidifier is isolated off with manual valve. System has a tarp and a hose to drain a leak. | Test when valve can be opened. |
| 175 | 14 | AHU-24 | 12' | Drip | Humidifier | Armstrong | 30B3 | F&T | 30 | 0.75 | 0' | 30 | 0-5 | X | X | X | Modulating | Offline | Humidifier is isolated off with manual valve. System has a tarp and a hose to drain a leak. | Test when valve can be opened. |
| 176 | 14 | AHU-23 | 12' | Drip | Humidifier | Armstrong | 811 | IVBT | 70 | 0.75 | 0' | 30 | 0-5 | X | X | X | Modulating | Offline | Humidifier is isolated off with manual valve. | Test when valve can be opened. |
| 177 | 14 | AHU-23 | 12' | Drip | Humidifier | Armstrong | 30B3 | F&T | 30 | 0.75 | 0' | 30 | 0-5 | X | X | X | Modulating | Offline | Humidifier is isolated off with manual valve. | Test when valve can be opened. |
| 178 | NO TAG | |||||||||||||||||||
| 179 | 14 | Water Heater | 1' | Drip | MPS Supply | Armstrong | 75A3 | F&T | 75 | 0.75 | 0' | 30 | 0-5 | X | X | X | Constant | Offline | Medium pressure steam supply is offline in this area. | Test when system is online. |
| 180 | 14 | Water Heater | 1' | Equipment | Water Heater | Armstrong | 216 | IVBT | UNK | 1.5 | 0' | 30 | 0-5 | X | O | X | Modulating | Offline | Medium pressure steam supply is offline in this area. | Test when system is online. |
| 181 | 15 | Main PRV Station | 4' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 7' | 60 | 0-5 | X | X | X | Constant | OK | None | None |
| 182 | 15 | Main PRV Station | 4' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 7' | 25 | 0 | X | X | X | Constant | OK | None | None |
| 183 | 15 | Above Honeywell Control Panels | 12' | Equipment | Unit Heater | Spirax-Sarco | FT30 | F&T | 30 | 0.75 | 0' | 25 | 0 | O | X | X | Constant | Offline | Unit heater is not used. Valved off, not controlled by BAS. | Remove from service or force to operation and check status. |
| 184 | 15 | Above AHU-10 | 12' | Drip | MPS Supply | Armstrong | TVS811-70 | IVBT | 70 | 0.75 | 0' | 25 | 0 | O | X | X | Constant | Ok | None | None |
| 185 | 15 | AHU-9 Disconnect | 6' | Drip | Steam Coil | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | Ok | None | None |
| 186 | 15 | On Top of AHU-9 | 10' | Drip | MPS Supply | Armstrong | TVS811-70 | IVBT | 70 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | Ok | None | None |
| 187 | 15 | AHU-9 | 2' | Equipment | Steam Coil | Armstrong | ICS | F&T | 125 | 1.5 | 0' | 25 | 0 | X | X | X | Modulating | OK | None | None |
| 188 | 15 | AHU-9 | 12' | Drip | MPS Supply | Armstrong | TVS811-70 | IVBT | 70 | 0.75 | 0' | 25 | 0 | O | X | X | Constant | Ok | None | None |
| 189 | 15 | AHU-9 | 5' | Drip | Steam Coil | Armstrong | TVS811-70 | IVBT | 70 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | Ok | None | None |
| 190 | 15 | AHU-9 | 1' | Equipment | Steam Coil | Armstrong | ICS | F&T | 125 | 1.5 | 0' | 25 | 0 | X | X | X | Modulating | OK | None | None |
| 191 | 15 | Rooftop Exit | 15' | Drip | MPS Supply | Armstrong | TVS811-70 | IVBT | 70 | 0.75 | 0' | 25 | 0 | O | X | X | Constant | Ok | Condensate inlet piping is leaking. | Repair the piping. |
| 192 | 15 | Rooftop Exit | 15' | Equipment | Steam Coil | Spirax-Sarco | FT30 | F&T | 30 | 0.75 | 0' | 25 | 0 | O | X | X | Modulating | Abandoned | Steam supply to coil has been removed and capped. | Repair coil or remove abandoned equipment. |
| 193 | 16 | Main PRV Station | GL | Drip | HPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 1' | 90 | 0-10 | X | X | X | Constant | OK | None | None |
| 194 | 16 | Main PRV Station | GL | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 1' | 25 | 10 | X | X | X | Constant | OK | None | None |
| 195 | 16 | Main PRV Station | 15' | Equipment | Unit Heater | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | OK | None | None |
| 196 | 16 | Pump Trap Station | 1' | Drip | MPS Supply | Armstrong | TVS811-70 | IVBT | 70 | 0.75 | 0' | 40 | 0-5 | O | X | X | Constant | Ok | None | None |
| 197 | 16 | Pump Trap Station | GL | Pump Trap | fan Room 16 | Armstrong | PT-206K | F&T | 125 | 1.5 | 15' | 40 | 0-5 | X | X | X | Constant | Ok | This pumping trap needs flash tank. | Install a flash tank with proper fill head prior to the pump. |
| 198 | 16 | AHU-56 | 2' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 15 | 0 | X | X | X | Constant | OK | None | None |
| 199 | 16 | AHU-56 | 1' | Equipment | Steam Coil | Armstrong | 15B3 | F&T | 15 | 0.75 | 0' | 15 | 0 | X | X | X | Modulating | OK | None | None |
| 200 | 16 | AHU-56 | 1' | Equipment | Steam Coil | Armstrong | 15B3 | F&T | 15 | 0.75 | 0' | 15 | 0 | X | X | X | Modulating | OK | None | None |
| 201 | 16 | AHU-56 Unit Heater | 12' | Equipment | Unit Heater | Watson McDaniel | 1032 | IVBT | 30 | 0.75 | 0' | 25 | 0 | O | O | X | Constant | Ok | None | None |
| 202 | 16 | Heat Exchanger Skid | 7' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | OK | None | None |
| 203 | 16 | Heat Exchanger 1 | 2' | Equipment | Heat Exchanger | Watson McDaniel | FTT-65 | F&T | 65 | 0.75 | 0' | 25 | 0 | X | X | X | Modulating | Ok | None | None |
| 204 | 16 | Heat Exchanger 1 | 2' | Equipment | Heat Exchanger | Watson McDaniel | FTT-65 | F&T | 65 | 0.75 | 0' | 25 | 0 | X | X | X | Modulating | Ok | None | None |
| 205 | 16 | Heat Exchanger 2 | 2' | Equipment | Heat Exchanger | Watson McDaniel | FTT-65 | F&T | 65 | 0.75 | 0' | 25 | 0 | X | X | X | Modulating | Ok | None | None |
| 206 | 16 | Heat Exchanger 2 | 2' | Equipment | Heat Exchanger | Watson McDaniel | FTT-65 | F&T | 65 | 0.75 | 0' | 25 | 0 | X | X | X | Modulating | Ok | None | None |
| 207 | 16 | AHU-52 | 8' | Drip | MPS Supply | Armstrong | 811 | IVBT | 30 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | Ok | None | None |
| 208 | 16 | AHU-52 | 1' | Equipment | Steam Coil | Armstrong | 15B3 | F&T | 15 | 0.75 | 0' | 25 | 0 | X | X | X | Modulating | Ok | None | None |
| 209 | 16 | AHU-52 | GL | Equipment | Steam Coil | Watson McDaniel | FT30 | F&T | 30 | 2 | 0' | 25 | 0 | O | X | X | Modulating | Ok | None | None |
| 210 | 16 | AHU-52 | GL | Equipment | Steam Coil | Watson McDaniel | FT30 | F&T | 30 | 2 | 0' | 25 | 0 | O | X | X | Modulating | Ok | None | None |
| 211 | 16 | AHU-52 | 9' | Drip | HPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | OK | None | None |
| 212 | 16 | AHU-51 | 8' | Drip | MPS Supply | Armstrong | 811 | IVBT | 30 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | Ok | None | None |
| 213 | 16 | AHU-51 | 1' | Equipment | Steam Coil | Armstrong | 15B3 | F&T | 15 | 0.75 | 0' | 25 | 0 | X | X | X | Modulating | OK | None | None |
| 214 | 16 | AHU-51 | GL | Equipment | Steam Coil | Watson McDaniel | FT30 | F&T | 30 | 2 | 0' | 25 | 0 | O | X | X | Modulating | Ok | None | None |
| 215 | 16 | AHU-51 | GL | Equipment | Steam Coil | Watson McDaniel | FT30 | F&T | 30 | 2 | 0' | 25 | 0 | O | X | X | Modulating | Ok | None | None |
| 216 | 17 | Cooling Tower Emergency Heat | 8' | Drip | MPS Supply | Spirax-Sarco | FT30 | F&T | 30 | 0.75 | 0' | 25 | 0 | O | X | X | Constant | OK | None | None |
| 217 | 17 | Cooling Tower Emergency Heat | 8' | Equipment | Steam Coil | Armstrong | TVS811-30 | IVBT | 30 | 0.75 | 0' | 25 | 0 | O | X | X | Constant | OK | None | None |
| 218 | 17 | Cooling Tower Emergency Heat | 8' | Equipment | Steam Coil | Armstrong | TVS811-30 | IVBT | 30 | 0.75 | 0' | 25 | 0 | O | X | X | Constant | OK | None | None |
| No Tag | 17 | Water Room | 7' | Equipment | Unit Heater | Spirax-Sarco | FT31 | F&T | 30 | 3/4 | 3' | 20 | 0 | O | X | X | Constant | OK | None | None |
| 219 | 18 | Steam Entrance - Down Stairs | GL | Drip | HPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 60 | 0-5 | X | X | X | Constant | OK | None | None |
| 220 | 18 | Steam Entrance - Above Stairs | 6' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | OK | None | None |
| 221 | 18 | Steam Entrance - Above Stairs | 6' | Drip | HPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 60 | 0-5 | X | X | X | Constant | OK | None | None |
| 222 | 18 | Above Chemical Treatment Station | 7' | Equipment | Unit Heater | Spirax-Sarco | FT30 | F&T | 30 | 0.75 | 0' | 25 | 0 | O | X | X | Constant | Offline | Unit heater is not used. Valved off, not controlled by BAS. | Remove from service or force to operation and check status. |
| 223 | 18 | AHU-28 | 7' | Drip | MPS Supply | Spirax-Sarco | B-1H | IVBT | 30 | 0.75 | 0' | 25 | 0 | O | X | X | Constant | OK | None | None |
| 224 | 18 | AHU-28 | GL | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | OK | None | None |
| 225 | 18 | AHU-28 | GL | Equipment | Steam Coil | Armstrong | ICS | F&T | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Modulating | OK | None | None |
| 226 | 18 | AHU-28 | GL | Equipment | Steam Coil | Armstrong | ICS | F&T | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Modulating | OK | None | None |
| 227 | 18 | AHU-28 | GL | Equipment | Steam Coil | Armstrong | ICS | F&T | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Modulating | OK | None | None |
| 228 | 18 | AHU-28 | GL | Equipment | Steam Coil | Armstrong | ICS | F&T | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Modulating | OK | None | None |
| 229 | 18 | AHU-29 | GL | Equipment | Steam Coil | Hoffman | FT015H3 | F&T | 15 | 0.75 | 0' | 25 | 0 | O | X | X | Modulating | Flooded | Back pressure and bad check valves are probably the issue. | Repair/Replace |
| 230 | 18 | AHU-29 | GL | Equipment | Steam Coil | Armstrong | 15B3 | F&T | 15 | 0.75 | 0' | 25 | 0 | O | X | X | Modulating | Flooded | Back pressure and bad check valves are probably the issue. | Repair/Replace |
| 231 | 18 | AHU-29 | GL | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | OK | None | None |
| 232 | 18 | AHU-29 | GL | Equipment | Steam Coil | Armstrong | 15B3 | F&T | 15 | 0.75 | 0' | 25 | 0 | O | X | X | Modulating | Flooded | Back pressure and bad check valves are probably the issue. | Repair/Replace |
| 233 | 18 | AHU-29 | GL | Equipment | Steam Coil | Armstrong | 15B3 | F&T | 15 | 0.75 | 0' | 25 | 0 | O | X | X | Modulating | Flooded | Back pressure and bad check valves are probably the issue. | Repair/Replace |
| 234 | 18 | AHU-31 | 6' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | OK | None | None |
| 235 | 18 | AHU-31 | GL | Equipment | Steam Coil | Armstrong | ICS | F&T | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Modulating | OK | None | None |
| 236 | 18 | AHU-31 | 1' | Drip | MPS Supply | Armstrong | TVS811-15 | IVBT | 15 | 0.75 | 0' | 25 | 0 | O | X | X | Constant | Ok | None | None |
| 237 | 18 | AHU-31 | GL | Equipment | Steam Coil | Armstrong | ICS | F&T | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Modulating | OK | None | None |
| 238 | 18 | Heat Exchanger | 6' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 25 | 0 | X | X | O | Constant | Ok | None | None |
| 239 | 18 | Heat Exchanger | 2' | Equipment | Heat Exchanger | Armstrong | 30B8 | F&T | 30 | 2 | 0' | 25 | 0 | O | X | X | Modulating | Ok | None | None |
| 240 | 18 | Heat Exchanger | 2' | Equipment | Heat Exchanger | Armstrong | 30B8 | F&T | 30 | 2 | 0' | 25 | 0 | O | X | X | Modulating | Ok | None | None |
| No Tag | 18 | Gravel PRV Station | 1' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 3/4 | 3' | 40 | 0 | X | X | X | Constant | OK | None | None |
| No Tag | 18 | Crawl Space | 1' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 3/4 | 3' | 40 | 0 | X | X | X | Constant | OK | None | None |
| 241 | 19 | AHU-30 | 7' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | OK | None | None |
| 242 | 19 | AHU-30 | GL | Equipment | Steam Coil | Watson McDaniel | FT7 | F&T | 15 | 1.5 | 0' | 25 | 0 | X | X | X | Modulating | Ok | None | None |
| 243 | 19 | AHU-30 | 9' | Equipment | Unit Heater | Spirax-Sarco | FT30 | F&T | 30 | 0.75 | 0' | 25 | 0 | O | X | X | Constant | Offline | Unit heater is not used. Valved off, not controlled by BAS. | Remove from service or force to operation and check status. |
| 244 | 19 | AHU-30 | 1' | Equipment | Humidifier | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | Ok | None | None |
| 245 | 19 | AHU-30 | GL | Drip | Humidifier | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | Ok | None | None |
| 246 | 19 | AHU-32 | 1' | Equipment | Humidifier | Armstrong | TVS811-15 | IVBT | 15 | 0.75 | 0' | 25 | 0 | O | X | X | Constant | Ok | None | None |
| 247 | 19 | AHU-32 | GL | Drip | Humidifier | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | Ok | None | None |
| 248 | 19 | AHU-32 | 7' | Drip | MPS Supply | Armstrong | TVS811-15 | IVBT | 15 | 0.75 | 0' | 25 | 0 | O | X | X | Constant | Ok | None | None |
| 249 | 19 | On top of AHU-32 | 8' | Equipment | Unit Heater | Spirax-Sarco | FT30 | F&T | 30 | 0.75 | 0' | 25 | 0 | O | X | X | Constant | Offline | Unit heater is not used. Valved off, not controlled by BAS. | Remove from service or force to operation and check status. |
| 250 | 19 | AHU-32 | GL | Equipment | Steam Coil | Bestobell | FT1256 | F&T | 65 | 1.5 | 0' | 25 | 0 | X | X | X | Modulating | OK | None | None |
| 251 | 20 | On top of AHU-33 | 8' | Equipment | Unit Heater | Spirax-Sarco | FT30 | F&T | 30 | 0.75 | 0' | 25 | 0 | O | X | X | Constant | Offline | Unit heater is not used. Valved off, not controlled by BAS. | Remove from service or force to operation and check status. |
| 252 | 20 | AHU-33 | GL | Equipment | Steam Coil | Armstrong | 75A5 | F&T | 75 | 1.25 | 0' | 25 | 0 | X | X | X | Modulating | Ok | None | None |
| 253 | 20 | AHU-33 | 6' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | Ok | None | None |
| 254 | 20 | AHU-33 | 2' | Equipment | Humidifier | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | Ok | None | None |
| 255 | 20 | AHU-33 | 2' | Equipment | Humidifier | Armstrong | 2011 | IVBT | 125 | 0.75 | 0' | 25 | 0 | X | X | X | Constant | OK | None | None |
| 256 | 21 | Column GA21 | 2' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 4' | 25 | 0 | X | X | X | Constant | Ok | None | None |
| 257 | 21 | Column GA21 | 2' | Drip | MPS Supply | Armstrong | TVS811-70 | IVBT | 70 | 0.75 | 4' | 25 | 0 | X | X | X | Constant | Ok | None | None |
| 258 | 21 | Column H21 | 2' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 1 | 4' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 259 | 21 | Column J22 | 3' | Drip | LPS Supply | Spirax-Sarco | FT30 | F&T | 30 | 0.75 | 4' | 20 | 0 | X | X | X | Constant | Offline | Test when online. | Test when online. |
| 260 | 21 | Column M27 | 3' | Drip | LPS Supply | Spirax-Sarco | FT30 | F&T | 30 | 0.75 | 4' | 20 | 0 | X | X | X | Constant | Abandoned | Remove from service. | Remove from service. |
| 261 | 21 | Column M23 | 2' | Drip | LPS Supply | Armstrong | TVS811-70 | IVBT | 70 | 0.75 | 4' | 20 | 0 | X | X | X | Constant | Ok | None | None |
| 262 | 21 | Column M22 | 2' | Drip | LPS Supply | Armstrong | TVS811-70 | IVBT | 70 | 0.75 | 4' | 20 | 0 | X | X | X | Constant | Ok | None | None |
| 263 | 21 | Column M22 | 2' | Drip | LPS Supply | Hoffman | Unknown | IVBT | UNK | 0.75 | 4' | 20 | 0 | X | X | X | Constant | Ok | None | None |
| 264 | 21 | Column P21 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 4' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 265 | 21 | Column N21 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 4' | 20 | 0 | X | X | X | Constant | Ok | None | None |
| 266 | 21 | Column M20 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 4' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 267 | 21 | Column L21 | 3' | Drip | MPS Supply | Armstrong | TVS811-70 | IVBT | 70 | 0.75 | 4' | 30 | 0-5 | X | X | X | Constant | Ok | None | None |
| 268 | 21 | Column K21 | 3' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 4' | 30 | 0-5 | X | X | X | Constant | OK | None | None |
| 269 | 21 | Column M20 | GL | Drip | HPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 6' | 90 | 0-10 | X | X | X | Constant | OK | None | None |
| 270 | 21 | Column L19 | 3' | Drip | LPS Supply | Spirax-Sarco | FT30 | F&T | 30 | 0.75 | 4' | 20 | 0 | O | X | X | Constant | Offline | Test when online. | Test when online. |
| 271 | 21 | Column L18 | 2' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 1.25 | 3' | 30 | 0-5 | X | X | X | Constant | OK | None | None |
| 272 | 21 | Column L18 | 2' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 1.25 | 3' | 30 | 0-5 | X | X | X | Constant | OK | None | None |
| 273 | 21 | Column K17 | 1' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 4' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 274 | 21 | Column M17 | 2' | Drip | MPS Supply | Armstrong | 811 | IVBT | 70 | 0.75 | 3' | 60 | 0-5 | X | X | X | Constant | Ok | None | None |
| 275 | 21 | Column M17 | 2' | Drip | MPS Supply | Armstrong | 811 | IVBT | 70 | 0.75 | 3' | 60 | 0-5 | X | X | X | Constant | Ok | None | None |
| 276 | 21 | Column M17 | 2' | Drip | MPS Supply | Armstrong | 811 | IVBT | 70 | 0.75 | 3' | 60 | 0-5 | X | X | X | Constant | Ok | None | None |
| 277 | 21 | Column M17 | GL | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 60 | 0-5 | X | X | X | Constant | OK | None | None |
| 278 | 21 | Column L17 | 1' | Drip | MPS Supply | Armstrong | TVS811-125 | IVBT | 125 | 0.75 | 2' | 60 | 0-5 | X | X | X | Constant | Ok | None | None |
| 279 | 21 | Column L17 | 1' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 4' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 280 | 21 | Column KB | 1' | Drip | HPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 2' | 90 | 0-10 | X | X | X | Constant | OK | None | None |
| 281 | 21 | Column KB | 2' | Liquid Drainer | Flash Tank | Armstrong | TVS811-125 | IVBT | 125 | 0.75 | 2' | 60 | 0-5 | X | X | X | Constant | Ok | None | None |
| 282 | 21 | Column KB | 1' | Drip | MPS Supply | Armstrong | TVS812-125 | IVBT | 125 | 0.75 | 3' | 60 | 0-5 | X | X | X | Constant | Ok | None | None |
| 283 | 21 | Column KB | 3' | Drip | MPS Supply | Armstrong | 811 | IVBT | 70 | 0.75 | 3' | 60 | 0-5 | X | X | X | Constant | Ok | None | None |
| 284 | 21 | Column KB | GL | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 60 | 0-5 | X | X | X | Constant | OK | None | None |
| 285 | 21 | Column KB | 3' | Drip | MPS Supply | Armstrong | 811 | IVBT | 70 | 0.75 | 3' | 60 | 0-5 | X | X | X | Constant | Ok | None | None |
| 286 | 21 | Column KA | 3' | Drip | LPS Supply | Spirax-Sarco | FT30 | F&T | 30 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | Offline | Test when online. | Test when online. |
| 287 | 21 | #7 Stairs | 3' | Drip | LPS Supply | Spirax-Sarco | FT30 | F&T | 30 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | Offline | Test when online. | Test when online. |
| 288 | 21 | Column H16 | 2' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 289 | 21 | Column H17 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 290 | 21 | Column G17 | 2' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 291 | 21 | Column F17 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 292 | 21 | Column F16 | 3' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 60 | 0-5 | X | X | X | Constant | OK | None | None |
| 293 | 21 | Column D16 | 3' | Drip | MPS Supply | Armstrong | TVS811-70 | IVBT | 70 | 0.75 | 3' | 60 | 0-5 | X | X | X | Constant | Offline | Test when online. | Test when online. |
| 294 | 21 | Column J13 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 295 | 21 | Column J13 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | Ok | None | None |
| 296 | 21 | Column M13 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 1 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 297 | 21 | Column M11 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 298 | 21 | Column K11 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 299 | 21 | Column K9 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 300 | 21 | Column K11 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 301 | 21 | Column F11 | 4' | Drip | MPS Supply | Armstrong | TVS811-70 | IVBT | 70 | 0.75 | 3' | 60 | 0-5 | O | X | X | Constant | Ok | Pipe is broken on the inlet. | Repair the piping. |
| 302 | 21 | Column M9 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 303 | 21 | Column N7 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 304 | 21 | Column N7 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 305 | 21 | Column P7 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 306 | 21 | Column N7 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 307 | 21 | Column N7 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 308 | 21 | Column M3 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 309 | 21 | Column M2 | 3' | Drip | MPS Supply | Armstrong | TVS811-70 | IVBT | 70 | 0.75 | 3' | 60 | 0-5 | O | X | X | Constant | Ok | None | None |
| 310 | 21 | Column M2 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 311 | 21 | Column M2 | 3' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 35 | 0-5 | X | X | X | Constant | OK | None | None |
| 312 | 21 | Column L2 | 3' | Drip | MPS Supply | Armstrong | TVS811-70 | IVBT | 70 | 0.75 | 3' | 60 | 0-5 | O | X | X | Constant | Ok | None | None |
| 313 | 21 | Column L2 | 3' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 35 | 0-5 | X | X | X | Constant | OK | None | None |
| 314 | 21 | Column L3 | 3' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 315 | 21 | Column L4 | 3' | Drip | MPS Supply | Armstrong | TVS811-70 | IVBT | 70 | 0.75 | 3' | 35 | 0-5 | O | X | X | Constant | Ok | None | None |
| 316 | 21 | Column L4 | 3' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 60 | 0-5 | X | X | X | Constant | OK | None | None |
| 317 | 21 | Column K8 | 3' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 55 | 0-5 | X | X | X | Constant | OK | None | None |
| 318 | 21 | Column H5 | 3' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 55 | 0-5 | X | X | X | Constant | OK | None | None |
| 319 | 21 | Column J6 | 3' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 55 | 0-5 | X | X | X | Constant | OK | None | None |
| 320 | 21 | Column H8 | 2' | Drip | LPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 321 | 21 | Column F6 | 3' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 55 | 0-5 | X | X | X | Constant | OK | None | None |
| 322 | 21 | Column D7 | 4' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 60 | 0-5 | X | X | X | Constant | OK | None | None |
| 323 | 21 | Column D7 | 4' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 60 | 0-5 | X | X | X | Constant | OK | None | None |
| 324 | 21 | Column D7 | 4' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 60 | 0-5 | X | X | X | Constant | OK | None | None |
| 325 | 21 | Column C8 | 3' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 55 | 0-5 | X | X | X | Constant | OK | None | None |
| 326 | 21 | Column C8 | 3' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 327 | 21 | Column B7 | 3' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 328 | 21 | Column B9 | 3' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 329 | 21 | Column E12 | 3' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 330 | 21 | Column C13 | 3' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 60 | 0-5 | X | X | X | Constant | OK | None | None |
| 331 | 21 | Column C13 | 3' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 332 | 21 | Column C14 | 3' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 333 | 21 | Column C19 | 3' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 334 | 21 | Column C19 | 3' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |
| 335 | 21 | Column C20 | 3' | Drip | MPS Supply | Armstrong | 2011 | IVBT | 125 | 0.75 | 3' | 20 | 0 | X | X | X | Constant | OK | None | None |