Atch 4 Drawing Armstrong AFH 4100 J Condensate Pump 15GAL Duplex.pdf
PDF 262 KB Posted
- Attached to
- Z1DA--626-24-204 - Update / Upgrade Steam System Components Federal contract opportunity
- Solicitation number
- 36C24924B0011
About this file
This document appears to be a Solicitation for a project to upgrade the steam system components at the Department of Veterans Affairs Tennessee Valley Healthcare System (TVHS) Nashville Campus. The key details are:
The project will replace failing condensate return skid pumps, piping, and associated components, as well as add venting as shown in the attached drawings. The work includes replacing the condensate return systems in several areas of the facility, including the Boiler Room Mezzanine, Chiller Plant, Fan Rooms, Clinical Sub-Basement, SPS, and ACRE Building. The contractor must comply with all applicable federal, state, and local regulations, as well as VA policies. The period of performance is 120 calendar days from the notice to proceed. Award will be made to a single contractor. Submittals are required within 10 days of contract award, and a schedule must be provided within 10 days of the notice to proceed. The work will require coordination with ongoing medical center operations, including conducting some work during off-hours.
View the file
Other files for this federal contract opportunity
Show all 32
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
3.13
6.31 16.31
17.00
LIFTING EYES
(OPTIONAL)
8.50
7.50
28.91
1-1/2" NPT
PUMP DISCHARGE
PRESSURE GAUGE, CHECK VALVE
GATE VALV AND BALL VALVE
(OPTIONAL)
1-1/2" NPT VENT
3.00 7.50
.25
FOOT PAD
12.25
15.00 3.97 3.34
29.78 44.24
1-1/2 NPT
OVERFLOW
2" NPT
PROCESS RETURN
7.50
8.76
14.25
35.44
NEMA 12
CONTROL PANEL
(OPTIONAL)
FLOAT SWITCH OR
ALTERNATOR
THERMOMETER
(OPTIONAL)
GAUGE GLASS
(OPTIONAL)
ISOLATION VALVE
(OPTIONAL) 1/2" NPT DRAIN
NOTES:
• TANK MATERIAL: STEEL
• ALL DIMENSIONS ARE ±0.25"
• DRAWING NOT FOR CONSTRUCTION
• CONSULT FACTORY AT TIME OF ORDER FOR CURRENT PRINT
• INLET BASKET STRAINER OR Y-STRAINER ALSO AVAILABLE
CONTROL PANEL OPTIONS ALSO AVAILABLE (NOT SHOWN):
• NEMA 4 OR NEMA 4X OR NEMA 3R CONSTRUCTION
• ELECTRIC ALTERNATOR
• POWER ON LIGHT
• PUMP TEST BUTTON
• PUMP RUN TIME METER
• EXTRA DRY CONTACTS
• UL/CUL LABELED PANEL
• HIGH LEVEL ALARM HORN & LIGHT W/SILENCE SWITCH
• LEAD-AUTO-LAG SELECTOR SWITCH
D
C
B
A A
B
D
12345678
8 7 6 5 4 3 2 1
5/3/2021INITIAL DESIGN
SIZE
B
THIRD ANGLE PROJECTION
SCALE: 1:10SHEET: 1 OF 1 A684.41015.00J
3/16/2018
NAME DATE
ENG APPR.
CHECKED
DRAWN
15 GALLON DUPLEX
PART NO:
GJM
684.41015.00J
TITLE
DWG NO. REV
4100 SERIES
"J" CONDENSATE PUMP
DRAWING MAY NOT BE PRINTED TO SCALE.
DATENAME
GJMA
REV DESCRIPTION ECN
WEIGHT
1359.01
FABRICATION TOLERANCES
UNLESS OTHERWISE SPECIFIED:
DIMENSIONS ARE IN INCHES
TOLERANCES:
ANGULAR DIMENSIONS 1
FRACTIONS 1/16
TWO PLACE DECIMAL 0.06
THREE PLACE DECIMAL 0.030
PRODUCT CATEGORY
HTSP Boiler and Condensate
PRODUCT FAMILY
C armstronginternational.com
| Sheet1 |
| Drawing View11 |
| Drawing View12 |
| Drawing View13 |
| Drawing View14 |
| Drawing View15 |
File details come from the government source that posted it. Updated .