Appendix D- Service Call Historical Workload Data 2023 - Non-Real Property.xlsx

XLSX spreadsheet 57 KB Posted

Attached to
Army Field Support Battalion (AFSBn-CHS) Facility Preventive Maintenance, Inspection & Repair Services
Solicitation number
FA441824Q0001
Issued by

About this file

This document provides historical work order data for preventive maintenance, inspection and repair services at an Army Field Support Battalion facility. The data spans from June 2022 through May 2023 and includes over 100 individual work orders related to services such as battery charger PMs, air compressor checks, door and hinge repairs, electrical work and facility issue resolution. The work orders include details on the work requested, status, dates, equipment references and time spent on tasks. Services were provided by an on-site contractor and appear focused on preventative maintenance and quick response to facility maintenance needs.

View the file

Other files

File Type Posted
PWS AFSBn - CHS (Revision 11 Jan 2024).pdf PDF
Site Visit Attendees.pdf PDF
Q and A_FA441824Q0001.pdf PDF
AFSBn-CHS V2 Map.pdf PDF
Wage Determination_CBA-2023-746.pdf PDF
Appendix A - Equipment Inventory_Real Property_19 Dec 23.xlsx XLSX spreadsheet
Joint Base Charleston Base Access Worksheet - Form 111 (Aug 22).pdf PDF
COMBO_AFSBn_FA441824Q0001.pdf PDF
Appendix H - Wash Rack Service Matrix_2023.xlsx XLSX spreadsheet
Appendix A - Equipment Inventory_Real Property_26 Oct 2018.xlsx XLSX spreadsheet
Appendix M - Engineering Technical Advisory_Legionellos Mitigation Actions.pdf PDF
AFSBn Facility Maintenance and Repair Services Bid Schedule.xlsx XLSX spreadsheet
Appendix E - Building Inventory.xlsx XLSX spreadsheet
Provisions and Clauses.pdf PDF
Appendix F - Boilers (2022).xlsx XLSX spreadsheet
Appendix G - Wash Rack Parts List 2023.xlsx XLSX spreadsheet
Appendix I - Points of Demarcation.pdf PDF
Appendix L - LAMS Maintenance Requirements.pdf PDF
Appendix J - Contractor Base Security and Access.pdf PDF
PWS AFSBn-CHS (Revision 23 August 2023).pdf PDF
Appendix C- Service Call Historical Workload Data 2023 - Real Property.xlsx XLSX spreadsheet
Wage Determination 2015-4427 Rev 24 dated 10 July 2023.pdf PDF
Appendix B - Equipment Inventory NON Real Property (New) Oct 2023.xlsx XLSX spreadsheet
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

WO IDWO BarcodeDescriptionAsset IDAsset DescriptionCurrent Asset Service StatusWork TypeRequested ByCreated ByDate CreatedCost CenterExpense ClassStatusStateRequest DateActual
Start DateActual
Finish DateActual DurationRuntimeClosed DateNotesCommentsAsset ClassAsset TypeAttachment CountInstr. CountInstr. Step CountFrom Work Request?Start ResponseFinish ResponseNo Of WorkersEst Craft HoursActual Hours MaintenanceHours Variance
2022-1948*2022-1948*PM BATTERY CHARGER819-BCBattery ChargerIn ServicePM,system6/8/2022 12:23:40 PMSpecial-EquipNON RPIECompletedClosed6/8/2022 8:23:40 AM6/15/2022 12:00 AM6/15/2022 12:00 AM0d 0h 0m0.006/16/2022 7:13:47 AM
Semi-annualJun 16 2022 7:13AM by SJONES: PM complete.
EQBATTCHGR017No6d 15h 36m6d 15h 36m101.501.5
2022-1959*2022-1959*PM BATTERY CHARGER864-BC-1Battery ChargerIn ServicePM,system6/8/2022 12:23:40 PMSpecial-EquipNON RPIECompletedClosed6/8/2022 8:23:40 AM6/15/2022 12:00 AM6/15/2022 12:00 AM0d 0h 0m0.006/16/2022 7:16:26 AM
Semi-annualJun 16 2022 7:16AM by SJONES: PM complete.
EQBATTCHGR017No6d 15h 36m6d 15h 36m100.500.5
2022-1985*2022-1985*Monthly Checks of Ingersol Rand Compressors1659-C-1Air CompressorIn ServicePM,system6/15/2022 3:12:32 PMPLUMBINGNON RPIECompletedClosed6/15/2022 11:12:00 AM6/21/2022 12:00 AM6/21/2022 7:48 AM0d 7h 48m7.806/27/2022 7:48:26 AM
MonthlyJun 27 2022 7:47AM by SJONES: 14,476
EQCOMPRESR016No5d 12h 48m5d 20h 36m101.251.25
2022-1986*2022-1986*Monthly Checks of Ingersol Rand Compressors1660-C-1Air CompressorIn ServicePM,system6/15/2022 3:12:32 PMPLUMBINGNON RPIECompletedClosed6/15/2022 11:12:00 AM6/21/2022 12:00 AM6/21/2022 7:48 AM0d 7h 48m7.806/27/2022 7:48:26 AM
MonthlyJun 27 2022 7:46AM by SJONES: 10,777
EQCOMPRESR016No5d 12h 48m5d 20h 36m101.501.5
2022-2030*2022-2030*Room 110 Door closer on East wall door slamming.456-DOORSDoors, Closers and HardwareIn ServiceROUTINESteffensen, ScottSCOTT6/22/2022 6:48:02 PMDoors_HardwareNON RPIECompletedClosed6/22/2022 2:46:00 PM6/22/2022 12:00 AM6/22/2022 12:00 AM0d 0h 0m0.006/28/2022 1:01:52 PM
870Jun 28 2022 1:01PM by SJONES: Adjusted door closer, complete.
EQDOORS000Yes0d -14h -46m0d -14h -46m000.600.6
2022-2061*2022-2061*1681--Bay 12 Air hose is leaking air1681In ServiceROUTINEKBR, KBRKBR-FacilitiesLead6/23/2022 12:27:30 PMNON RPIECompletedClosed6/23/2022 8:25:00 AM6/23/2022 12:00 AM6/23/2022 12:00 AM0d 0h 0m0.006/28/2022 11:48:49 AM
892Jun 28 2022 11:48AM by SJONES: Removed and replaced air hose, checked good.
LO000Yes0d -8h -25m0d -8h -25m004.004
2022-2069*2022-2069*LAM 2--REPAIR BROKEN LIGHT SWITCH ( 2ND ROW EAST END)LAM-Electric-LowInterior Voltage Circuits on Fabric StructuresIn ServiceROUTINEJONES, SONYASYELTON6/27/2022 2:22:45 PMELECTRICALNON RPIECompletedClosed6/27/2022 10:20:00 AM7/20/2022 12:00 AM7/20/2022 12:00 AM0d 0h 0m0.007/20/2022 3:16:18 PM
NON-RIPEJul 20 2022 3:16PM by SJONES: Replaced faulty switch with new one.
EQELEC-PWR000No22d 13h 40m22d 13h 40m000.500.5
2022-2158*2022-2158*328--REPAIR INOP COMPRESSOR328-C-1Air Compressor ControlsIn ServiceROUTINEJONES, SONYASYELTON7/6/2022 1:30:47 PMPLUMBINGNON RPIECompletedClosed7/6/2022 9:29:00 AM7/6/2022 12:00 AM7/6/2022 12:00 AM0d 0h 0m0.007/6/2022 4:27:38 PM
955Jul 6 2022 4:27PM by SJONES: Reset compressor motor, checked good.
EQCOMPRESR000No0d -9h -29m0d -9h -29m000.500.5
2022-2180*2022-2180*PM BATTERY CHARGER320-BC-3Battery ChargerIn ServicePM,system7/7/2022 10:53:02 AMSpecial-EquipNON RPIECompletedClosed7/7/2022 6:53:02 AM7/11/2022 12:00 AM7/11/2022 12:00 AM0d 0h 0m0.007/12/2022 6:42:14 AM

Semi-annual Jul 12 2022 6:42AM by SJONES: PM complete.

Jul 12 2022 6:42AM by SJONES: PM complete.

EQBATTCHGR017No3d 17h 6m3d 17h 6m101.001
2022-2181*2022-2181*PM BATTERY CHARGER320-BC-4Battery ChargerIn ServicePM,system7/7/2022 10:53:02 AMSpecial-EquipNON RPIECompletedClosed7/7/2022 6:53:02 AM7/11/2022 12:00 AM7/11/2022 12:00 AM0d 0h 0m0.007/12/2022 6:43:06 AM
Semi-annualJul 12 2022 6:43AM by SJONES: PM complete.
EQBATTCHGR017No3d 17h 6m3d 17h 6m100.500.5
2022-2182*2022-2182*PM BATTERY CHARGER320-BC-5Battery ChargerIn ServicePM,system7/7/2022 10:53:02 AMSpecial-EquipNON RPIECompletedClosed7/7/2022 6:53:02 AM7/11/2022 12:00 AM7/11/2022 12:00 AM0d 0h 0m0.007/12/2022 6:44:00 AM
Semi-annualJul 12 2022 6:44AM by SJONES: PM complete.
EQBATTCHGR017No3d 17h 6m3d 17h 6m100.500.5
2022-2183*2022-2183*PM BATTERY CHARGER320-BC-2Battery ChargerIn ServicePM,system7/7/2022 10:53:02 AMSpecial-EquipNON RPIECompletedClosed7/7/2022 6:53:02 AM7/11/2022 12:00 AM7/11/2022 12:00 AM0d 0h 0m0.007/12/2022 6:41:25 AM
Semi-annualJul 12 2022 6:41AM by SJONES: PM complete.
EQBATTCHGR017No3d 17h 6m3d 17h 6m100.500.5
2022-2231*2022-2231*Monthly Checks of Ingersol Rand Compressors1659-C-1Air CompressorIn ServicePM,system7/13/2022 11:03:50 AMPLUMBINGNON RPIECompletedClosed7/13/2022 7:03:50 AM7/18/2022 12:00 AM7/18/2022 8:36 AM0d 8h 36m8.607/19/2022 8:36:45 AM
MonthlyJul 19 2022 8:36AM by SJONES: 14,932
EQCOMPRESR016No4d 16h 56m5d 1h 32m100.500.5
2022-2232*2022-2232*Monthly Checks of Ingersol Rand Compressors1660-C-1Air CompressorIn ServicePM,system7/13/2022 11:03:50 AMPLUMBINGNON RPIECompletedClosed7/13/2022 7:03:50 AM7/18/2022 12:00 AM7/18/2022 8:36 AM0d 8h 36m8.607/19/2022 8:36:45 AM
MonthlyJul 19 2022 8:35AM by SJONES: 10,814
EQCOMPRESR016No4d 16h 56m5d 1h 32m100.500.5
2022-2284*2022-2284*Lam 3 A.C. UNIT # 11 IS MAKING A WEIRD SOUNDLAM3In ServiceROUTINEKBR, KBRKBR-FacilitiesLead7/20/2022 11:20:55 AMNON RPIECompletedClosed7/20/2022 7:19:00 AM7/20/2022 12:00 AM7/20/2022 12:00 AM0d 0h 0m0.007/20/2022 3:13:50 PMNON-RIPEJul 20 2022 3:13PM by SJONES: Unit is currently not under contract.
LO000Yes0d -7h -19m0d -7h -19m002.002
2022-2288*2022-2288*LAM 2--REPLACE MISSING ELECTRICAL OUTLETLAM-Electric-LowInterior Voltage Circuits on Fabric StructuresIn ServiceROUTINEJONES, SONYASYELTON7/21/2022 11:25:26 AMELECTRICALNON RPIECompletedClosed7/21/2022 7:24:00 AM7/21/2022 12:00 AM7/21/2022 12:00 AM0d 0h 0m0.007/21/2022 3:16:56 PM
NON-RIPEJul 21 2022 3:16PM by SJONES: Replaced outlet.
EQELEC-PWR000No0d -7h -24m0d -7h -24m001.001
2022-2297*2022-2297*Lam 3 multiple pedestrian doors won't lock and the ones that do you can just pull hard and they come open POC Alfred ChubbLAM3In ServiceROUTINEKBR, KBRKBR-FacilitiesLead7/25/2022 12:14:50 PMNON RPIECompletedClosed7/25/2022 8:13:00 AM8/2/2022 12:00 AM8/2/2022 12:00 AM0d 0h 0m0.008/2/2022 12:42:14 PMNon-RPIE Request
For door locations, contact Keilon Campbell @ x794-8932Aug 2 2022 12:42PM by SJONES: Adjusted and replaced door latches, complete.
LO000Yes7d 15h 47m7d 15h 47m002.002
2022-2320*2022-2320*ANNUAL PM AIR COMPRESSORS346-C-OAir Compressor for Waste Oil TankIn ServicePM,system7/27/2022 10:45:25 AMPLUMBINGNON RPIECompletedClosed7/27/2022 6:45:25 AM8/2/2022 12:00 AM8/2/2022 12:00 AM0d 0h 0m0.008/2/2022 1:29:50 PMAnnualAug 2 2022 1:29PM by SJONES: Compressor is no longer on contract.
EQCOMPRESR0112No5d 17h 14m5d 17h 14m100.100.1
2022-2486*2022-2486*Lam 3 roll up door on west end stuck at about 3/4 way upLAM3In ServiceROUTINEKBR, KBRKBR-FacilitiesLead8/4/2022 11:44:04 AMNON RPIECompletedClosed8/4/2022 7:43:00 AM8/4/2022 12:00 AM8/4/2022 12:00 AM0d 0h 0m0.008/4/2022 2:17:19 PMNON-RIPEAug 4 2022 2:17PM by SJONES: Used lift and man basket to get door unstuck and moving freely.
LO000Yes0d -7h -43m0d -7h -43m002.002
2022-2535*2022-2535*Monthly Checks of Ingersol Rand Compressors1660-C-1Air CompressorIn ServicePM,system8/10/2022 1:18:50 PMPLUMBINGNON RPIECompletedClosed8/10/2022 9:18:50 AM8/17/2022 12:00 AM8/17/2022 3:17 PM0d 15h 17m15.288/17/2022 3:17:46 PM
MonthlyAug 17 2022 3:16PM by SJONES: 10,840
EQCOMPRESR016No6d 14h 41m7d 5h 58m101.001
2022-2536*2022-2536*Monthly Checks of Ingersol Rand Compressors1659-C-1Air CompressorIn ServicePM,system8/10/2022 1:18:50 PMPLUMBINGNON RPIECompletedClosed8/10/2022 9:18:50 AM8/17/2022 12:00 AM8/17/2022 3:17 PM0d 15h 17m15.288/17/2022 3:17:46 PM
MonthlyAug 17 2022 3:15PM by SJONES: 15,521
EQCOMPRESR016No6d 14h 41m7d 5h 58m101.001
2022-2728*2022-2728*1662 - Wash Rack #4 Hose Reel has a busted hose1662In ServiceROUTINEKBR, KBRKBR-FacilitiesLead9/6/2022 5:21:47 PMNON RPIECompletedClosed9/6/2022 1:20:00 PM9/8/2022 12:00 AM9/8/2022 12:00 AM0d 0h 0m0.009/12/2022 8:30:11 AM
1447Sep 12 2022 8:30AM by SJONES: Complete.
LO000Yes1d 10h 40m1d 10h 40m001.001
2022-2730*2022-2730*Bldg 1681, Bay 3 and 15 Air hose is leaking air.1681In ServiceROUTINEKBR, KBRKBR-FacilitiesLead9/7/2022 1:03:35 PMNON RPIECompletedClosed9/7/2022 8:57:00 AM9/12/2022 12:00 AM9/12/2022 12:00 AM0d 0h 0m0.009/12/2022 2:49:19 PM
1462Sep 12 2022 2:49PM by SJONES: Removed and replaced the shut off valve at station 15 and it leak checked good, no leak found at station 3.
LO000Yes4d 15h 3m4d 15h 3m002.002
2022-2794*2022-2794*Monthly Checks of Ingersol Rand Compressors1660-C-1Air CompressorIn ServicePM,system9/14/2022 12:41:46 PMPLUMBINGNON RPIECompletedClosed9/14/2022 8:41:46 AM9/19/2022 12:00 AM9/20/2022 7:15 AM1d 7h 15m31.259/20/2022 7:15:59 AM

Monthly Sep 20 2022 7:14AM by SJONES: 10,899 Sep 20 2022 7:14AM by SJONES: 10,899

EQCOMPRESR016No4d 15h 18m5d 22h 33m101.001
2022-2795*2022-2795*Monthly Checks of Ingersol Rand Compressors1659-C-1Air CompressorIn ServicePM,system9/14/2022 12:41:46 PMPLUMBINGNON RPIECompletedClosed9/14/2022 8:41:46 AM9/19/2022 12:00 AM9/20/2022 7:15 AM1d 7h 15m31.259/20/2022 7:15:59 AM
MonthlySep 20 2022 7:15AM by SJONES: 16,068
EQCOMPRESR016No4d 15h 18m5d 22h 33m101.001
2022-2801*2022-2801*346--Warehouse Bay 103, two fixtures in the overhead and not illuminated. Possible circuit breaker open or all eight lamps are out346-Room-103In ServiceROUTINEKBR, KBRKBR-FacilitiesLead9/14/2022 7:47:56 PMNON RPIECompletedClosed9/14/2022 3:46:00 PM10/19/2022 12:00 AM10/20/2022 12:00 AM1d 0h 0m24.0010/31/2022 9:32:53 AM

1479 Oct 31 2022 9:32AM by SJONES: Found switch bad, replaced switch, found traveller wires for 3 way switches to be bad. Removed wire from conduit and ran all new wire. Found (2) 4 bulb and (2) 2 bulb t-5 ballasts to have failed, ordered ballasts and replaced. replaced (12) 4ft t-5 bulbs, used scissor lift & forklift to complete task.

Oct 31 2022 9:32AM by SJONES: Found switch bad, replaced switch, found traveller wires for 3 way switches to be bad. Removed wire from conduit and ran all new wire. Found (2) 4 bulb and (2) 2 bulb t-5 ballasts to have failed, ordered ballasts and replaced. replaced (12) 4ft t-5 bulbs, used scissor lift & forklift to complete task.

LO000Yes34d 8h 14m35d 8h 14m0056.0056
2022-2802*2022-2802*346--Front entrance lamp dooes not illuminate from dusk til dawn346-Bldg-ExteriorIn ServiceROUTINEKBR, KBRKBR-FacilitiesLead9/14/2022 7:52:37 PMNON RPIECompletedClosed9/14/2022 3:48:00 PM9/15/2022 12:00 AM9/15/2022 12:00 AM0d 0h 0m0.009/19/2022 7:49:19 AM1480Sep 19 2022 7:49AM by SJONES: Removed and replaced photocell and bulb, checked good.
LO000Yes0d 8h 12m0d 8h 12m000.500.5
2023-0015*2023-0015*ANNUAL PM AIR COMPRESSORS328-C-1Air Compressor ControlsIn ServicePM,SYELTON9/28/2022 10:39:25 AMPLUMBINGNON RPIECompletedClosed9/28/2022 6:39:25 AM10/3/2022 12:00 AM10/3/2022 12:00 AM0d 0h 0m0.0010/5/2022 10:46:21 AM
AnnualOct 5 2022 10:46AM by SJONES: Annual PM complete.
EQCOMPRESR0112No4d 17h 20m4d 17h 20m103.003
2023-0102*2023-0102*Building 850 Forklift Battery Charger is not working please check that it is receiving power.850In ServiceROUTINEKBR, KBRKBR-FacilitiesLead10/4/2022 11:01:16 AMNON RPIECompletedClosed10/4/2022 6:57:00 AM10/4/2022 12:00 AM10/4/2022 12:00 AM0d 0h 0m0.0010/5/2022 10:44:13 AM
1607Oct 5 2022 10:44AM by SJONES: Found two fuses to be bad in disconnect, replaced fuses, charger functioning properly.
LO000Yes0d -6h -57m0d -6h -57m001.001
2023-0125*2023-0125*PM BATTERY CHARGER850-BAT-1Battery ChargerIn ServicePM,SYELTON10/5/2022 1:46:04 PMSpecial-EquipNON RPIECompletedClosed10/5/2022 9:46:04 AM10/12/2022 12:00 AM10/12/2022 12:00 AM0d 0h 0m0.0010/13/2022 6:47:02 AM

Semi-annual Oct 13 2022 6:47AM by SJONES: PM complete.

Oct 13 2022 6:47AM by SJONES: PM complete.

EQBATTCHGR017No6d 14h 13m6d 14h 13m101.001
2023-0167*2023-0167*Monthly Checks of Ingersol Rand Compressors1660-C-1Air CompressorIn ServicePM,SYELTON10/12/2022 10:46:59 AMPLUMBINGNON RPIECompletedClosed10/12/2022 6:46:59 AM10/17/2022 12:00 AM10/17/2022 1:56 PM0d 13h 56m13.9310/17/2022 1:57:07 PM
MonthlyOct 17 2022 1:55PM by SJONES: 10,899
EQCOMPRESR016No4d 17h 13m5d 7h 9m100.500.5
2023-0168*2023-0168*Monthly Checks of Ingersol Rand Compressors1659-C-1Air CompressorIn ServicePM,SYELTON10/12/2022 10:47:00 AMPLUMBINGNON RPIECompletedClosed10/12/2022 6:47:00 AM10/17/2022 12:00 AM10/17/2022 1:56 PM0d 13h 56m13.9310/17/2022 1:57:07 PM
MonthlyOct 17 2022 1:56PM by SJONES: 16,621
EQCOMPRESR016No4d 17h 13m5d 7h 9m100.500.5
2023-0234*2023-0234*1681--ACCESS DOOR BY OVERHEAD DOOR #21 NEEDS DOOR CLOSER ADJUSTED OR REPLACED TO KEEP FROM SLAMMING1681-DOORSNon-Motorized DoorsIn ServiceROUTINEJONES, SONYASYELTON10/25/2022 7:16:37 PMDoors_HardwareNON RPIECompletedClosed10/25/2022 3:15:00 PM11/3/2022 12:00 AM11/3/2022 12:00 AM0d 0h 0m0.0011/7/2022 6:51:33 AM
1754Nov 7 2022 6:51AM by SJONES: Adjusted door closer on access door, complete.
EQDOORS000No8d 8h 45m8d 8h 45m000.250.25
2023-0238*2023-0238*366--The air compressor on the outside of 366, is constantly running.366BUILDING 366In ServiceROUTINEKBR, KBRKBR-FacilitiesLead10/26/2022 12:44:24 PMNON RPIECompletedClosed10/26/2022 8:39:00 AM10/26/2022 12:00 AM10/26/2022 12:00 AM0d 0h 0m0.0010/27/2022 8:35:26 AM
1758Oct 27 2022 8:35AM by SJONES: Reset breaker, complete.
LO000Yes0d -8h -39m0d -8h -39m001.001
2023-0255*2023-0255*ANNUAL AIR COMPRESSOR PM455-C-2AIR COMPRESSORIn ServicePM,SYELTON10/26/2022 12:59:23 PMComp.-Air-SysNON RPIECompletedClosed10/26/2022 8:59:23 AM11/1/2022 12:00 AM11/1/2022 12:00 AM0d 0h 0m0.0011/2/2022 1:54:55 PMANNUALNov 2 2022 1:54PM by SJONES: Changed oil, changed two filters, checked belts, annual PM complete.

Nov 2 2022 1:54PM by SJONES: Changed oil, changed two filters, checked belts, annual PM complete.

EQCOMP-AIR0112No5d 15h 0m5d 15h 0m003.003
2023-0288*2023-0288*ANNUAL PM AIR COMPRESSORS455-C-1Air CompressorIn ServicePM,SYELTON10/26/2022 6:31:19 PMPLUMBINGNON RPIECompletedClosed10/26/2022 2:31:19 PM11/1/2022 12:00 AM11/1/2022 12:00 AM0d 0h 0m0.0011/2/2022 1:33:49 PM
AnnualNov 2 2022 1:33PM by SJONES: Annual PM complete, changed oil and air filter, checked belts.
EQCOMPRESR0112No5d 9h 28m5d 9h 28m101.501.5
2023-0294*2023-0294*865--ADJUST BOTH DOOR CLOSERS, SLAMMING VERY HARD865-DOORSDoors, Closers and HardwareIn ServiceROUTINEJONES, SONYASYELTON10/31/2022 7:27:49 PMDoors_HardwareNON RPIECompletedClosed10/31/2022 3:27:00 PM11/2/2022 12:00 AM11/2/2022 12:00 AM0d 0h 0m0.0011/3/2022 6:41:49 AM
1776Nov 3 2022 6:41AM by SJONES: Removed and replaced both door closers, checked good.
EQDOORS000No1d 8h 33m1d 8h 33m004.004
2023-0401*2023-0401*1660--Hose reel#1 has a large hole in it. Hose reel #2 leaking where the water inlet connects. Hose reel #5 and #7 leaking where water inlet connects.1660-Bldg-ExteriorIn ServiceROUTINEKBR, KBRKBR-FacilitiesLead11/8/2022 2:16:22 PMNON RPIECompletedClosed11/8/2022 9:08:00 AM11/17/2022 12:00 AM11/17/2022 12:00 AM0d 0h 0m0.0011/21/2022 9:48:49 AMHoses are old and might have to be replaced.Nov 21 2022 9:48AM by SJONES: Replaced busted hose station ststion#1, replaced o-rings on swivel to hose reels #1,2,5, and 7.
LO000Yes8d 14h 52m8d 14h 52m002.002
2023-0419*2023-0419*PM BATTERY CHARGER869-BC-1Battery ChargerIn ServicePM,SYELTON11/8/2022 4:34:33 PMSpecial-EquipNON RPIECompletedClosed11/8/2022 11:34:33 AM11/15/2022 12:00 AM11/15/2022 12:00 AM0d 0h 0m0.0011/21/2022 7:36:41 AM
Semi-annualNov 21 2022 7:36AM by SJONES: PM complete.
EQBATTCHGR017No6d 12h 25m6d 12h 25m100.500.5
2023-0420*2023-0420*PM BATTERY CHARGER869-BC-2Battery ChargerIn ServicePM,SYELTON11/8/2022 4:34:33 PMSpecial-EquipNON RPIECompletedClosed11/8/2022 11:34:33 AM11/15/2022 12:00 AM11/15/2022 12:00 AM0d 0h 0m0.0011/21/2022 7:35:07 AM
Semi-annualNov 21 2022 7:35AM by SJONES: PM complete.
EQBATTCHGR017No6d 12h 25m6d 12h 25m100.500.5
2023-0421*2023-0421*PM BATTERY CHARGER869-BC-5Battery ChargerIn ServicePM,SYELTON11/8/2022 4:34:33 PMSpecial-EquipNON RPIECompletedClosed11/8/2022 11:34:33 AM11/15/2022 12:00 AM11/15/2022 12:00 AM0d 0h 0m0.0011/21/2022 7:33:57 AM
Semi-annualNov 21 2022 7:33AM by SJONES: PM complete.
EQBATTCHGR017No6d 12h 25m6d 12h 25m100.500.5
2023-0422*2023-0422*PM BATTERY CHARGER869-BC-6Battery ChargerIn ServicePM,SYELTON11/8/2022 4:34:33 PMSpecial-EquipNON RPIECompletedClosed11/8/2022 11:34:33 AM11/15/2022 12:00 AM11/15/2022 12:00 AM0d 0h 0m0.0011/21/2022 7:31:18 AM
Semi-annualNov 21 2022 7:31AM by SJONES: Unit is tagged out.
EQBATTCHGR017No6d 12h 25m6d 12h 25m100.200.2
2023-0423*2023-0423*PM BATTERY CHARGER869-BC-7Battery ChargerIn ServicePM,SYELTON11/8/2022 4:34:33 PMSpecial-EquipNON RPIECompletedClosed11/8/2022 11:34:33 AM11/15/2022 12:00 AM11/15/2022 12:00 AM0d 0h 0m0.0011/21/2022 7:32:18 AM
Semi-annualNov 21 2022 7:32AM by SJONES: Unit is tagged out.
EQBATTCHGR017No6d 12h 25m6d 12h 25m100.200.2
2023-0441*2023-0441*GEN - ANNUAL PM EMERGENCY GENERATORS (DIESEL)456-GEN-SETSTAN BY GENTERATOR SET 60DGCBIn ServicePM,SYELTON11/8/2022 4:34:33 PMEmgncy-PowerNON RPIECompletedClosed11/8/2022 11:34:00 AM4/5/2023 12:00 AM4/5/2023 12:00 AM0d 0h 0m0.004/10/2023 2:31:46 PMApr 6 2023 9:28AM by SS2740: Annual maintenance was performed by Cummins Technician. Analysis reports for Oil, Antifreeze and fuel samples will be submitted when they arrive.
EQGENERATO0120No147d 12h 26m147d 12h 26m104.004
2023-0487*2023-0487*Monthly Checks of Ingersol Rand Compressors1660-C-1Air CompressorIn ServicePM,SYELTON11/16/2022 3:52:53 PMPLUMBINGNON RPIECompletedClosed11/16/2022 10:52:53 AM11/21/2022 12:00 AM11/21/2022 7:32 AM0d 7h 32m7.5311/22/2022 7:32:58 AM
MonthlyNov 22 2022 7:32AM by SJONES: LED display screen broken unable to get run hours.
EQCOMPRESR016No4d 13h 7m4d 20h 39m100.250.25
2023-0488*2023-0488*Monthly Checks of Ingersol Rand Compressors1659-C-1Air CompressorIn ServicePM,SYELTON11/16/2022 3:52:53 PMPLUMBINGNON RPIECompletedClosed11/16/2022 10:52:53 AM11/21/2022 12:00 AM11/21/2022 7:32 AM0d 7h 32m7.5311/22/2022 7:32:58 AM
MonthlyNov 22 2022 6:57AM by SJONES: 16,629
EQCOMPRESR016No4d 13h 7m4d 20h 39m100.500.5
2023-0528*2023-0528*LAM 2--WEST END ROLL UP DOOR IS HAVING PROBLEMSLAM-2In ServiceROUTINEJONES, SONYASYELTON11/21/2022 6:04:12 PMNON RPIECompletedClosed11/21/2022 1:03:00 PM12/15/2022 12:00 AM12/15/2022 12:00 AM0d 0h 0m0.0012/19/2022 7:16:30 AM1870Dec 19 2022 7:16AM by SJONES: Used scissor lift and forklift to complete task. Lubed up door track to allow smooth operations, door rolling up and down properly.
EQ000No23d 10h 57m23d 10h 57m002.002
2023-0580*2023-0580*ANNUAL PM AIR COMPRESSORSLAM-Air-Compressor-1Air compressorIn ServicePM,SYELTON11/30/2022 11:57:34 AMSpecial-EquipNON RPIECompletedClosed11/30/2022 6:57:34 AM12/7/2022 12:00 AM12/7/2022 12:00 AM0d 0h 0m0.0012/8/2022 9:36:02 AMAnnualDec 8 2022 9:36AM by SJONES: Completed by BACS on 10/7/22.
EQCOMPRESS0112No6d 17h 2m6d 17h 2m100.100.1
2023-0581*2023-0581*ANNUAL PM AIR COMPRESSORSLAM-Compressed-AirComnpressed Air Equipment_Service in Fabric StructIn ServicePM,SYELTON11/30/2022 11:57:34 AMSpecial-EquipNON RPIECompletedClosed11/30/2022 6:57:34 AM12/7/2022 12:00 AM12/7/2022 12:00 AM0d 0h 0m0.0012/8/2022 7:18:07 AM
AnnualDec 8 2022 7:18AM by SJONES: Completed by BACS on 10/7/22
EQCOMPRESR0112No6d 17h 2m6d 17h 2m100.100.1
2023-0667*2023-0667*1660--Air hose leaking. Several spots by bay doors.1660In ServiceKBR, KBRKBR-FacilitiesLead12/7/2022 1:34:38 PMNON RPIECompletedClosed12/7/2022 8:32:00 AM12/20/2022 12:00 AM12/20/2022 12:00 AM0d 0h 0m0.0012/21/2022 3:17:01 PM
1954Dec 21 2022 3:17PM by SS2740: Replaced 2 hoses. Replaced 12 hose disconnects couplers.
LO000Yes12d 15h 28m12d 15h 28m008.008
2023-0693*2023-0693*PM BATTERY CHARGER819-BCBattery ChargerIn ServicePM,SYELTON12/8/2022 11:31:38 AMSpecial-EquipNON RPIECompletedClosed12/8/2022 6:31:38 AM12/12/2022 12:00 AM12/12/2022 12:00 AM0d 0h 0m0.0012/14/2022 8:06:08 AM
Semi-annualDec 14 2022 8:06AM by SJONES: Charger on disconnect 9 coming on w/ no forklift plugged into charger.
EQBATTCHGR017No3d 17h 28m3d 17h 28m102.002
2023-0711*2023-0711*PM BATTERY CHARGER864-BC-1Battery ChargerIn ServicePM,SYELTON12/8/2022 11:31:38 AMSpecial-EquipNON RPIECompletedClosed12/8/2022 6:31:38 AM12/12/2022 12:00 AM12/12/2022 12:00 AM0d 0h 0m0.0012/14/2022 7:42:42 AM
Semi-annualDec 14 2022 7:42AM by SJONES: PM complete, checks sat.
EQBATTCHGR017No3d 17h 28m3d 17h 28m100.500.5
2023-0747*2023-0747*Monthly Checks of Ingersol Rand Compressors1660-C-1Air CompressorIn ServicePM,SYELTON12/14/2022 11:48:25 AMPLUMBINGNON RPIECompletedClosed12/14/2022 6:48:25 AM12/20/2022 12:00 AM12/20/2022 8:40 AM0d 8h 40m8.671/4/2023 8:41:13 AM
MonthlyJan 4 2023 8:39AM by SJONES: Could not get hours because of inop display screen, complete.
EQCOMPRESR016No5d 17h 11m6d 1h 51m100.500.5
2023-0748*2023-0748*Monthly Checks of Ingersol Rand Compressors1659-C-1Air CompressorIn ServicePM,SYELTON12/14/2022 11:48:25 AMPLUMBINGNON RPIECompletedClosed12/14/2022 6:48:25 AM12/20/2022 12:00 AM12/20/2022 8:40 AM0d 8h 40m8.671/4/2023 8:41:13 AM

Monthly Jan 4 2023 8:40AM by SJONES: 16629 1057/7098

EQCOMPRESR016No5d 17h 11m6d 1h 51m100.500.5
2023-0795*2023-0795*Battery charger not coming on. Might be a fuse problem.850In ServiceROUTINEKBR, KBRKBR-FacilitiesLead12/20/2022 1:53:31 PMNON RPIECompletedClosed12/20/2022 8:52:00 AM12/20/2022 12:00 AM12/20/2022 12:00 AM0d 0h 0m0.0012/21/2022 7:31:37 AM
EIM 1995Dec 21 2022 7:27AM by SS2740: Verified voltage is good at the disconnect to charger and at the charger
LO000Yes0d -8h -52m0d -8h -52m003.203.2
2023-0856*2023-0856*ANNUAL PM AIR COMPRESSORS389-C-1Air Compressor (For Sprinkler System)In ServicePM,SYELTON12/28/2022 1:37:37 PMPLUMBINGNON RPIECompletedClosed12/28/2022 8:37:37 AM1/4/2023 12:00 AM1/4/2023 12:00 AM0d 0h 0m0.001/4/2023 7:03:28 AM
AnnualJan 4 2023 7:03AM by SJONES: Removed from PM system.
EQCOMPRESR0112No6d 15h 22m6d 15h 22m100.00
2023-0943*2023-0943*PM BATTERY CHARGER320-BC-2Battery ChargerIn ServicePM,SYELTON1/4/2023 11:44:40 AMSpecial-EquipNON RPIECompletedClosed1/4/2023 6:44:40 AM1/9/2023 12:00 AM1/9/2023 12:00 AM0d 0h 0m0.001/10/2023 6:52:29 AM
Semi-annualJan 10 2023 6:52AM by SS2740: PM Complete, Unit operating properly, all checks sat.
EQBATTCHGR017No4d 17h 15m4d 17h 15m100.500.5
2023-0944*2023-0944*PM BATTERY CHARGER320-BC-3Battery ChargerIn ServicePM,SYELTON1/4/2023 11:44:40 AMSpecial-EquipNON RPIECompletedClosed1/4/2023 6:44:40 AM1/9/2023 12:00 AM1/9/2023 12:00 AM0d 0h 0m0.001/10/2023 6:51:09 AM
Semi-annualJan 10 2023 6:51AM by SS2740: PM Complete, Unit operating properly, all checks sat.
EQBATTCHGR017No4d 17h 15m4d 17h 15m100.500.5
2023-0945*2023-0945*PM BATTERY CHARGER320-BC-4Battery ChargerIn ServicePM,SYELTON1/4/2023 11:44:40 AMSpecial-EquipNON RPIECompletedClosed1/4/2023 6:44:40 AM1/9/2023 12:00 AM1/9/2023 12:00 AM0d 0h 0m0.001/10/2023 6:49:33 AM
Semi-annualJan 10 2023 6:49AM by SS2740: PM Complete, Unit operating properly, all checks sat.
EQBATTCHGR017No4d 17h 15m4d 17h 15m100.500.5
2023-0946*2023-0946*PM BATTERY CHARGER320-BC-5Battery ChargerIn ServicePM,SYELTON1/4/2023 11:44:40 AMSpecial-EquipNON RPIECompletedClosed1/4/2023 6:44:40 AM1/10/2023 8:59 AM0.001/19/2023 9:00:04 AM
Semi-annualJan 10 2023 6:44AM by SS2740: PM Complete, Unit operating properly, all checks sat.
EQBATTCHGR017No6d 2h 14m100.500.5
2023-0981*2023-0981*458--Exhaust removal reels (x4) on west side of building are inoperative . The reels function and has power, but fans won't come on to remove exhaust.458-AHU-1DXCCDX Cooling Coil (ACCU-1)In ServiceROUTINEKBR, KBRKBR-FacilitiesLead1/9/2023 8:41:30 PMHVACNON RPIECompletedClosed1/9/2023 3:35:00 PM1/9/2023 12:00 AM1/9/2023 12:00 AM0d 0h 0m0.001/11/2023 7:21:44 AM
2094Jan 11 2023 7:21AM by SJONES: Reset motor controls to hand, fans work correctly.
EQDX-SPLIT000Yes0d -15h -35m0d -15h -35m002.002
2023-0982*2023-0982*1659--Inside of paint Booth- bottom of regulator is leaking massive amounts of air.1659In ServiceROUTINEKBR, KBRKBR-FacilitiesLead1/10/2023 12:14:31 PMNON RPIECompletedClosed1/10/2023 7:11:00 AM1/10/2023 12:00 AM1/10/2023 12:00 AM0d 0h 0m0.001/11/2023 8:29:39 AM
2097Jan 11 2023 8:29AM by SJONES: Removed leaking regulator and replaced with new one, complete.
LO000Yes0d -7h -11m0d -7h -11m002.002
2023-1006*2023-1006*Monthly Checks of Ingersol Rand Compressors1660-C-1Air CompressorIn ServicePM,SCOTT1/10/2023 6:04:02 PMPLUMBINGNON RPIECompletedClosed1/10/2023 1:04:02 PM1/17/2023 12:00 AM1/17/2023 12:00 AM0d 0h 0m0.001/19/2023 8:09:59 AM
MonthlyJan 19 2023 8:09AM by SJONES: 11,908 total run hours.
EQCOMPRESR016No6d 10h 55m6d 10h 55m100.500.5
2023-1007*2023-1007*Monthly Checks of Ingersol Rand Compressors1659-C-1Air CompressorIn ServicePM,SCOTT1/10/2023 6:04:02 PMPLUMBINGNON RPIECompletedClosed1/10/2023 1:04:02 PM1/17/2023 12:00 AM1/17/2023 12:00 AM0d 0h 0m0.001/19/2023 8:11:35 AM
MonthlyJan 19 2023 8:11AM by SJONES: 16,629 total run hours.
EQCOMPRESR016No6d 10h 55m6d 10h 55m100.500.5
2023-1011*2023-1011*1662--Hose reel #1 leaking at Wash rack1662In ServiceROUTINEKBR, KBRKBR-FacilitiesLead1/12/2023 1:40:42 PMNON RPIECompletedClosed1/12/2023 8:38:00 AM1/17/2023 12:00 AM1/17/2023 12:00 AM0d 0h 0m0.001/17/2023 4:06:02 PM
2112Jan 17 2023 4:06PM by SJONES: Found brass swivel to have failed at hose reel, removed hoses from swivel and put new seals in swivel, reinstalled everything, hose reel functioning properly.
LO000Yes4d 15h 22m4d 15h 22m001.001
2023-1015*2023-1015*461--Bldg air will not go above 110PSI. Regulators will not adjust higher.461-C-1Air CompressorOut Of ServiceROUTINEKBR, KBRKBR-FacilitiesLead1/17/2023 7:15:09 PMPLUMBINGNON RPIECompletedClosed1/17/2023 2:09:00 PM1/18/2023 12:00 AM1/18/2023 12:00 AM0d 0h 0m0.001/19/2023 7:32:38 AM
2131Jan 19 2023 7:32AM by SJONES: Adjusted air pressure on regulator, complete.
EQCOMPRESR100Yes0d 9h 51m0d 9h 51m000.500.5
2023-1077*2023-1077*Bldg 1681, bay 14, POC Joseph Simon 307-277-3049 - Hose reel mounted to the floor damaged and leaking.1681-DOORSNon-Motorized DoorsIn ServiceKBR, KBRKBR-FacilitiesLead1/23/2023 3:33:39 PMDoors_HardwareNON RPIECompletedClosed1/23/2023 10:30:00 AM1/25/2023 12:00 AM1/25/2023 12:00 AM0d 0h 0m0.001/31/2023 2:21:04 PM
2241Jan 30 2023 11:55AM by SS2740: Removed cut section of hose and crimped on new end. Leak checks good.
EQDOORS000Yes1d 13h 30m1d 13h 30m002.002
2023-1081*2023-1081*Bldg. LAM1 Repair West side personal door closer.LAM1In ServiceROUTINESteffensen, ScottSCOTT1/23/2023 9:56:05 PMNON RPIECompletedClosed1/23/2023 4:54:00 PM1/31/2023 12:00 AM1/31/2023 12:00 AM0d 0h 0m0.001/31/2023 4:44:30 PM2243 Found during PM 2023-1002Jan 31 2023 4:44PM by SS2740: Repaired broken door closer. Door closer functioning correctly. Complete
LOLAMS000No7d 7h 6m7d 7h 6m001.001
2023-1082*2023-1082*Bldg. LAM1 Make repairs to South end roll up door.LAM1In ServiceROUTINESteffensen, ScottSCOTT1/24/2023 11:30:24 AMNON RPIECompletedClosed1/24/2023 6:28:00 AM1/31/2023 12:00 AM2/21/2023 12:00 AM21d 0h 0m504.002/22/2023 6:42:38 AM2244 Found during PM 2023-1002. Getting quote from Southeastern Dock & Door.Feb 22 2023 6:42AM by SS2740: Waiting on overhead door company to repair.
LOLAMS000No6d 17h 32m27d 17h 32m001.001
2023-1083*2023-1083*Bldg. LAM2 Repair small tear in fabric on West end of structure.LAM2In ServiceROUTINESteffensen, ScottSCOTT1/24/2023 11:34:06 AMNON RPIECompletedClosed1/24/2023 6:32:00 AM1/31/2023 12:00 AM1/31/2023 12:00 AM0d 0h 0m0.001/31/2023 3:50:51 PM2187 found during PM 2023-1043Jan 31 2023 3:50PM by SS2740: Installed patch over tear. Complete.
LO000No6d 17h 28m6d 17h 28m001.001
2023-1123*2023-1123*Bldg. LAM2 Replace bad GFCL outlet found during PM. 2023-1042.LAM2In ServiceROUTINESteffensen, ScottSCOTT1/30/2023 12:16:47 PMNON RPIECompletedClosed1/30/2023 7:14:00 AM2/14/2023 12:00 AM2/14/2023 12:00 AM0d 0h 0m0.002/15/2023 6:34:16 AM2224Feb 15 2023 6:34AM by SS2740: Replaced 3 damaged and faulty GFCI and cover with new ones.
LO000No14d 16h 46m14d 16h 46m001.001
2023-1124*2023-1124*Bldg. 1662 Repair leaking hose reel at station # 2. Found during PM 2023-10421662In ServiceROUTINESteffensen, ScottSCOTT1/30/2023 12:20:46 PMNON RPIECompletedClosed1/30/2023 7:19:00 AM1/30/2023 12:00 AM1/30/2023 12:00 AM0d 0h 0m0.001/31/2023 7:34:38 AM
2225Jan 31 2023 7:34AM by SS2740: Removed swivel on hose reel. Installed new O-ring kit in swivel and reinstalled. Station #2 Satisfactory.
LO000No0d -7h -19m0d -7h -19m000.500.5
2023-1201*2023-1201*Bldg. LAM1 LED lights on South End are out 2 ea.LAM1In ServiceROUTINESteffensen, ScottSCOTT2/1/2023 3:47:40 PMNON RPIECompletedClosed2/1/2023 10:46:00 AM2/8/2023 12:00 AM2/8/2023 12:00 AM0d 0h 0m0.002/8/2023 4:43:07 PM2256Feb 8 2023 4:43PM by SS2740: Used scissor lift & forklift to complete task. found incoming power supply to lights to be corroded at plug. Cleaned all connections. Lights operating properly.
LOLAMS000No6d 13h 14m6d 13h 14m001.601.6
2023-1264*2023-1264*Bldg. 1662 Repair washer hose on hose reel # 51662In ServiceROUTINESteffensen, ScottSCOTT2/13/2023 11:52:43 AMNON RPIECompletedClosed2/13/2023 6:51:00 AM2/16/2023 12:00 AM2/16/2023 12:00 AM0d 0h 0m0.002/21/2023 8:23:41 AM
2296Feb 21 2023 8:23AM by SS2740: Replaced broken spring on hose reel with new one. Reel functioning properly.
LO000No2d 17h 9m2d 17h 9m000.500.5
2023-1299*2023-1299*Monthly Checks of Ingersol Rand Compressors1660-C-1Air CompressorIn ServicePM,SCOTT2/16/2023 11:51:56 AMPLUMBINGNON RPIECompletedClosed2/16/2023 6:51:56 AM2/21/2023 12:00 AM2/21/2023 12:00 AM0d 0h 0m0.002/22/2023 6:51:16 AM
MonthlyFeb 22 2023 6:51AM by SS2740: Monthly compressor checks complete. All steps complete.
EQCOMPRESR016No4d 17h 8m4d 17h 8m101.001
2023-1300*2023-1300*Monthly Checks of Ingersol Rand Compressors1659-C-1Air CompressorIn ServicePM,SCOTT2/16/2023 11:51:56 AMPLUMBINGNON RPIECompletedClosed2/16/2023 6:51:56 AM2/21/2023 12:00 AM2/21/2023 12:00 AM0d 0h 0m0.002/22/2023 6:48:51 AM
MonthlyFeb 22 2023 6:48AM by SS2740: Monthly compressors check complete. All steps complete.
EQCOMPRESR016No4d 17h 8m4d 17h 8m101.001
2023-1315*2023-1315*Bldg. LAM 3 request Work Order to replace 2 GFCI receptacles that failed. Found during PM 2023-1178.LAM3In ServiceROUTINESteffensen, ScottSCOTT2/21/2023 1:55:07 PMNON RPIECompletedClosed2/21/2023 8:53:00 AM2/23/2023 12:00 AM2/23/2023 12:00 AM0d 0h 0m0.002/28/2023 8:24:03 AM2351Feb 28 2023 8:24AM by SS2740: Unwired and removed faulty GFCI. Wired in and installed 2 new GFCI's.
LO000No1d 15h 7m1d 15h 7m001.001
2023-1316*2023-1316*Bldg. LAM3 Request Work Order to repair 5 failed LED lights in overhead. Found during PM 2023-1178.LAM3In ServiceROUTINESteffensen, ScottSCOTT2/21/2023 1:57:38 PMNON RPIECompletedClosed2/21/2023 8:56:00 AM3/7/2023 12:00 AM3/7/2023 12:00 AM0d 0h 0m0.003/8/2023 6:51:09 AM2352Mar 8 2023 6:51AM by SS2740: Removed and unwired 6 LED lights. Wired in and installed 6 new LED lights. Used scissor lift and forklift to complete task.
LO000No13d 15h 4m13d 15h 4m003.003
2023-1318*2023-1318*Bldg. LAM4 Request Work Order to re-fasten J-Box to wall. Found during PM 2023-1242LAM4In ServiceROUTINESteffensen, ScottSCOTT2/21/2023 2:03:58 PMNON RPIECompletedClosed2/21/2023 9:02:00 AM2/21/2023 12:00 AM2/21/2023 12:00 AM0d 0h 0m0.002/21/2023 4:30:58 PM2354Feb 21 2023 4:30PM by SS2740: Found a bracket for the missing one in the shop supply. Installed bracket and attached J-Box.
LO000No0d -9h -2m0d -9h -2m000.500.5
2023-1319*2023-1319*Bldg. LAM4 Request Work Order to replace 1 faulty GFCI. Found during PM 2023-1242LAM4In ServiceROUTINESteffensen, ScottSCOTT2/21/2023 2:16:09 PMNON RPIECompletedClosed2/21/2023 9:09:00 AM2/21/2023 12:00 AM2/21/2023 12:00 AM0d 0h 0m0.002/21/2023 4:32:22 PM2355Feb 21 2023 4:32PM by SS2740: Unwired and removed the faulty GFCI. Wired in and installed new GFCI into LAM
LO000No0d -9h -9m0d -9h -9m000.500.5
2023-1437*2023-1437*Bldg LAM1, POC Haley Hill 794-8778 - The back door in LAM1 won't close. Is stuck or broke.LAM-1In ServiceROUTINEKBR, KBRKBR-FacilitiesLead3/2/2023 8:32:01 PMNON RPIECompletedClosed3/2/2023 3:31:00 PM3/13/2023 12:00 AM3/13/2023 12:00 AM0d 0h 0m0.003/13/2023 4:45:14 PM2449 Quote are submitted. Waiting on notice to proceed.Mar 13 2023 4:45PM by SS2740: Adjusted door latch so door would function properly. Complete
EQSTRUCTUR000Yes10d 8h 29m10d 8h 29m000.500.5
2023-1447*2023-1447*Bldg. LAM1 Personal door on West side of Bldg. Door closer arm is broken.LAM1In ServiceROUTINESteffensen, ScottSCOTT3/6/2023 9:01:10 PMNON RPIECompletedClosed3/6/2023 3:59:00 PM3/14/2023 12:00 AM3/14/2023 12:00 AM0d 0h 0m0.003/15/2023 6:43:17 AM2434Mar 15 2023 6:43AM by SS2740: Removed broken door closer and replaced with new one. Complete.
LOLAMS000No7d 8h 1m7d 8h 1m001.001
2023-1474*2023-1474*LAM3, POC Kyle Dixon - Lost power to about 1/3 of our overhead lighting and outlets, 1 of which is our QC computer is plugged into.LAM-3In ServiceURGENTKBR, KBRKBR-FacilitiesLead3/7/2023 2:51:48 PMNON RPIECompletedClosed3/7/2023 9:49:00 AM3/7/2023 12:00 AM3/7/2023 12:00 AM0d 0h 0m0.003/7/2023 3:52:37 PM2439Mar 7 2023 12:55PM by SS2740: Found tripped breaker. Reset breaker. Complete.
EQ000Yes0d -9h -49m0d -9h -49m000.750.75
2023-1480*2023-1480*Bldg 458, POC Cheryl Gaudette 794-8927 - Men's restroom door is slamming shut. Needs to be adjust to prevent an injury.458-DOORSDoors, Closers and HardwareIn ServiceROUTINEKBR, KBRKBR-FacilitiesLead3/9/2023 5:34:35 PMDoors_HardwareNON RPIECompletedClosed3/9/2023 12:34:00 PM3/15/2023 12:00 AM3/15/2023 12:00 AM0d 0h 0m0.003/15/2023 10:50:19 AM
2468Mar 15 2023 10:50AM by SS2740: Removed old door closer and replaced with new one. Complete.
EQDOORS000Yes5d 11h 26m5d 11h 26m001.001
2023-1481*2023-1481*LAM3, POC Kyle Dixon - Lost power.LAM-3In ServiceURGENTKBR, KBRKBR-FacilitiesLead3/9/2023 5:43:22 PMNON RPIECompletedClosed3/9/2023 12:42:00 PM3/9/2023 12:00 AM3/9/2023 12:00 AM0d 0h 0m0.003/14/2023 7:20:43 AM2467Mar 14 2023 7:20AM by SS2740: After checking power at panel L3 and L4, both panels indicated a phase loss. Went outside to main panel and checked incoming power from transformer and found with load i only have 100 volts and when you put a load on incoming power it drops to zero volts. This was turned over to public works/joint base.
EQ000Yes0d -12h -42m0d -12h -42m004.004
2023-1518*2023-1518*Monthly Checks of Ingersol Rand Compressors1660-C-1Air CompressorIn ServicePM,SCOTT3/14/2023 1:59:52 PMPLUMBINGNON RPIECompletedClosed3/14/2023 9:59:52 AM3/20/2023 12:00 AM3/20/2023 12:00 AM0d 0h 0m0.003/20/2023 1:54:00 PM
MonthlyMar 20 2023 1:54PM by SS2740: Monthly compressors check complete. All steps complete.
EQCOMPRESR016No5d 14h 0m5d 14h 0m100.500.5
2023-1519*2023-1519*Monthly Checks of Ingersol Rand Compressors1659-C-1Air CompressorIn ServicePM,SCOTT3/14/2023 1:59:52 PMPLUMBINGNON RPIECompletedClosed3/14/2023 9:59:52 AM3/20/2023 12:00 AM3/20/2023 12:00 AM0d 0h 0m0.003/20/2023 1:55:25 PM
MonthlyMar 20 2023 1:55PM by SS2740: Monthly compressors check complete. All steps complete.
EQCOMPRESR016No5d 14h 0m5d 14h 0m100.500.5
2023-1593*2023-1593*Bldg. 1659 Work with BACS tech Manny to replace thermal switch in air compressor. #2.1659-Bldg-Ext-Outside-Room-3In ServiceROUTINESteffensen, ScottSCOTT3/21/2023 1:33:08 PMNON RPIECompletedClosed3/21/2023 9:31:00 AM3/21/2023 12:00 AM3/21/2023 12:00 AM0d 0h 0m0.003/22/2023 6:34:18 AM
2567Mar 22 2023 6:34AM by SS2740: Worked with BACS to replace thermal valve in compressor 1659-2 and replace check valve in 1659-1. Both units are functioning properly.
LO000No0d -9h -31m0d -9h -31m009.009
2023-1607*2023-1607*Bldg 455, POC Robert Pinckney - Northern Bay, S Wall the pipe that supplies the lubrication hoses is dripping on the floor. Please secure for the weekend.455-FURNISHINGS-AND-FIXTURESFurnishings and fixturesIn ServiceKBR, KBRKBR-FacilitiesLead3/23/2023 8:25:07 PMNON RPIECompletedClosed3/23/2023 4:22:00 PM3/23/2023 12:00 AM3/23/2023 12:00 AM0d 0h 0m0.003/28/2023 7:37:30 AM
Mar 27 2023 12:28PM by CPARKER: All valves are secured form tank. Entire system has been leaking in multiple areas since system was installed. AFSBn-CHS is aware and currently trying to resolve issue.
EQFURNITUR000Yes0d -16h -22m0d -16h -22m000.500.5
2023-1609*2023-1609*Bldg 1681, POC Joe Simon 307-277-3049 - Air hoses damaged and leaking bay 20, 24, 10, 26, 27, and 14.1681-INTERIORIn ServiceKBR, KBRKBR-FacilitiesLead3/27/2023 11:55:13 AMInt-FinishesNON RPIECompletedClosed3/27/2023 7:54:00 AM4/5/2023 12:00 AM4/6/2023 12:00 AM1d 0h 0m24.004/10/2023 6:33:33 AM
2618Apr 10 2023 6:33AM by SS2740: Replaced several hose connectors and tightened disconnects, Complete.
EQINTERIOR000Yes8d 16h 6m9d 16h 6m006.006
2023-1757*2023-1757*PM BATTERY CHARGER850-BAT-1Battery ChargerIn ServicePM,SCOTT4/5/2023 11:57:36 AMSpecial-EquipNON RPIECompletedClosed4/5/2023 7:57:36 AM4/13/2023 12:00 AM4/13/2023 12:00 AM0d 0h 0m0.004/13/2023 4:00:43 PM
Semi-annualApr 13 2023 4:00PM by CPARKER: PM complete.
EQBATTCHGR017No7d 16h 2m7d 16h 2m100.500.5
2023-1764*2023-1764*Bldg. LAM3 Mr. Mark Fuchs needs assistance with checking power to an access point (AP) at LAMS 3.
POC: Mark Fuchs, mark.e.fuchs.ctr@army.mil, 843-794-8759LAM3In ServiceROUTINEDoherty, JamesJamesD4/5/2023 3:52:40 PMNON RPIECompletedClosed4/5/2023 11:48:00 AM4/20/2023 12:00 AM4/20/2023 12:00 AM0d 0h 0m0.004/20/2023 4:42:24 PM2653Apr 20 2023 4:42PM by CPARKER: Used forklift and scissor lift to complete tasks. Assisted Mr. Fuchs person with the things they needed to complete their job. Everything working properly.
LO000Yes14d 12h 12m14d 12h 12m001.501.5
2023-1772*2023-1772*Bldg. 455, Hose reel for Vehicle Exhaust System is inoperable in northern most bay (Rm 108). The electrical reel will not coil the hose (cannot maneuver up or down). 480 Volt System.455-Room-108In ServiceROUTINEDoherty, JamesJamesD4/10/2023 8:31:50 PMNON RPIECompletedClosed4/10/2023 4:24:00 PM4/12/2023 12:00 AM4/12/2023 12:00 AM0d 0h 0m0.004/12/2023 3:24:25 PM2678Apr 12 2023 3:24PM by SS2740: Reset the up and down limits on 2 reels. Desired hose reels plus one in southern most bay. Functioning properly.
LO000Yes1d 7h 36m1d 7h 36m001.001
2023-1794*2023-1794*Monthly Checks of Ingersol Rand Compressors1660-C-1Air CompressorIn ServicePM,SCOTT4/11/2023 7:07:00 PMPLUMBINGNON RPIECompletedClosed4/11/2023 3:07:00 PM4/17/2023 12:00 AM4/17/2023 12:00 AM0d 0h 0m0.004/18/2023 6:39:47 AM
MonthlyApr 18 2023 6:39AM by SS2740: Monthly checks complete.
EQCOMPRESR016No5d 8h 53m5d 8h 53m100.500.5
2023-1795*2023-1795*Monthly Checks of Ingersol Rand Compressors1659-C-1Air CompressorIn ServicePM,SCOTT4/11/2023 7:07:00 PMPLUMBINGNON RPIECompletedClosed4/11/2023 3:07:00 PM4/17/2023 12:00 AM4/17/2023 12:00 AM0d 0h 0m0.004/18/2023 6:38:55 AM
MonthlyApr 18 2023 6:38AM by SS2740: Monthly checks complete.
EQCOMPRESR016No5d 8h 53m5d 8h 53m100.500.5
2023-1798*2023-1798*Bldg. LAM4 Remove the studs in the concrete that are causing a tripping hazard.LAM4In ServiceROUTINESteffensen, ScottSCOTT4/12/2023 2:12:30 PMNON RPIECompletedClosed4/12/2023 10:10:00 AM4/12/2023 12:00 AM4/12/2023 12:00 AM0d 0h 0m0.004/13/2023 9:54:57 AM2685Apr 13 2023 6:45AM by SS2740: Removed studs from concrete pad. Complete.
LO000No0d -10h -10m0d -10h -10m001.001
2023-2018*2023-2018*PM BATTERY CHARGER869-BC-1Battery ChargerIn ServicePM,SCOTT5/3/2023 2:40:47 PMSpecial-EquipNON RPIECompletedClosed5/3/2023 10:40:47 AM5/11/2023 12:00 AM5/11/2023 12:00 AM0d 0h 0m0.005/15/2023 10:51:20 AM
Semi-annualMay 15 2023 10:51AM by CPARKER: PM complete. Checks sat.
EQBATTCHGR017No7d 13h 19m7d 13h 19m100.300.3
2023-2019*2023-2019*PM BATTERY CHARGER869-BC-2Battery ChargerIn ServicePM,SCOTT5/3/2023 2:40:47 PMSpecial-EquipNON RPIECompletedClosed5/3/2023 10:40:47 AM5/11/2023 12:00 AM5/11/2023 12:00 AM0d 0h 0m0.005/15/2023 10:50:35 AM
Semi-annualMay 15 2023 10:50AM by CPARKER: PM complete. Checks sat.
EQBATTCHGR017No7d 13h 19m7d 13h 19m100.300.3
2023-2020*2023-2020*PM BATTERY CHARGER869-BC-5Battery ChargerIn ServicePM,SCOTT5/3/2023 2:40:47 PMSpecial-EquipNON RPIECompletedClosed5/3/2023 10:40:47 AM5/11/2023 12:00 AM5/11/2023 12:00 AM0d 0h 0m0.005/15/2023 10:50:00 AM
Semi-annualMay 15 2023 10:50AM by CPARKER: PM complete. Checks sat.
EQBATTCHGR017No7d 13h 19m7d 13h 19m100.300.3
2023-2021*2023-2021*PM BATTERY CHARGER869-BC-6Battery ChargerIn ServicePM,SCOTT5/3/2023 2:40:47 PMSpecial-EquipNON RPIECompletedClosed5/3/2023 10:40:47 AM5/11/2023 12:00 AM5/11/2023 12:00 AM0d 0h 0m0.005/15/2023 10:49:14 AM
Semi-annualMay 15 2023 10:49AM by CPARKER: Unit is tagged out at disconnect.
EQBATTCHGR017No7d 13h 19m7d 13h 19m100.100.1
2023-2022*2023-2022*PM BATTERY CHARGER869-BC-7Battery ChargerIn ServicePM,SCOTT5/3/2023 2:40:47 PMSpecial-EquipNON RPIECompletedClosed5/3/2023 10:40:47 AM5/11/2023 12:00 AM5/11/2023 12:00 AM0d 0h 0m0.005/15/2023 10:48:23 AM
Semi-annualMay 15 2023 10:48AM by CPARKER: Unit is tagged out at disconnect.
EQBATTCHGR017No7d 13h 19m7d 13h 19m100.100.1
2023-2092*2023-2092*Monthly Checks of Ingersol Rand Compressors1660-C-1Air CompressorIn ServicePM,SCOTT5/10/2023 12:01:42 PMPLUMBINGNON RPIECompletedClosed5/10/2023 8:01:42 AM5/15/2023 12:00 AM5/15/2023 12:00 AM0d 0h 0m0.005/16/2023 7:30:15 AM
MonthlyMay 16 2023 7:30AM by CPARKER: Monthly compressor check complete.
EQCOMPRESR016No4d 15h 58m4d 15h 58m100.500.5
2023-2093*2023-2093*Monthly Checks of Ingersol Rand Compressors1659-C-1Air CompressorIn ServicePM,SCOTT5/10/2023 12:01:42 PMPLUMBINGNON RPIECompletedClosed5/10/2023 8:01:42 AM5/15/2023 12:00 AM5/15/2023 12:00 AM0d 0h 0m0.005/16/2023 7:31:59 AM
MonthlyMay 16 2023 7:31AM by CPARKER: Monthly compressor check complete.
EQCOMPRESR016No4d 15h 58m4d 15h 58m100.500.5
2023-2213*2023-2213*Bldg. LAM3 Power loss to air compressor on West end. Trouble shoot and make repairs.LAM3In ServiceROUTINESteffensen, ScottSCOTT5/30/2023 12:15:07 PMNON RPIEInProcessOpen5/30/2023 8:13:00 AM0.002973
Parts on Order BACS 5/30/23LONo00.00
2023-2215*2023-2215*Bldg LAM3, office, POC Kyle Dixon - Lost power @ 1130am.LAM-3In ServiceROUTINEKBR, KBRKBR-FacilitiesLead5/30/2023 3:47:03 PMNON RPIECompletedClosed5/30/2023 11:46:00 AM5/30/2023 12:00 AM5/30/2023 12:00 AM0d 0h 0m0.005/30/2023 2:58:47 PMEIM RequestedMay 30 2023 2:58PM by SS2740: Found power on East side of LAM3 to have only 100 Volts. incoming on Phase B with no load being applied to the disconnect. Possibly bad connection on the incoming power supply. Notified James to inform Public Works.
EQ000Yes0d -11h -46m0d -11h -46m001.001

https://aslac.mvpplant.com/v2/Plant/Work/WOHistory/Detail/35289https://aslac.mvpplant.com/v2/Plant/Asset/Equipment/Detail/7238https://aslac.mvpplant.com/v2/Plant/Asset/Location/Detail/504https://aslac.mvpplant.com/v2/Plant/Work/WOHistory/Detail/36871https://aslac.mvpplant.com/v2/Plant/Asset/Equipment/Detail/7626https://aslac.mvpplant.com/v2/Plant/Work/WOHistory/Detail/36889https://aslac.mvpplant.com/v2/Plant/Asset/Equipment/Detail/7802https://aslac.mvpplant.com/v2/Plant/Work/WOHistory/Detail/36925https://aslac.mvpplant.com/v2/Plant/Asset/Equipment/Detail/5546https://aslac.mvpplant.com/v2/Plant/Work/WOHistory/Detail/36926https://aslac.mvpplant.com/v2/Plant/Asset/Equipment/Detail/5482https://aslac.mvpplant.com/v2/Plant/Work/WOHistory/Detail/36973https://aslac.mvpplant.com/v2/Plant/Work/WOHistory/Detail/35402https://aslac.mvpplant.com/v2/Plant/Asset/Location/Detail/496https://aslac.mvpplant.com/v2/Plant/Work/WOHistory/Detail/37034https://aslac.mvpplant.com/v2/Plant/Asset/Equipment/Detail/7077https://aslac.mvpplant.com/v2/Plant/Work/WOHistory/Detail/37121https://aslac.mvpplant.com/v2/Plant/Asset/Equipment/Detail/6186https://aslac.mvpplant.com/v2/Plant/Work/WOHistory/Detail/37122https://aslac.mvpplant.com/v2/Plant/Asset/Equipment/Detail/6187https://aslac.mvpplant.com/v2/Plant/Work/WOHistory/Detail/37123https://aslac.mvpplant.com/v2/Plant/Asset/Equipment/Detail/6188https://aslac.mvpplant.com/v2/Plant/Work/WOHistory/Detail/37124https://aslac.mvpplant.com/v2/Plant/Asset/Location/Detail/508https://aslac.mvpplant.com/v2/Plant/Asset/Equipment/Detail/6189https://aslac.mvpp…