Steam Supply and Condensate Hangers & Supports for HVAC Piping and Equipment Return Piping Replacement 230529-1 PGRU, Geneva, NY
SECTION 230529
HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
PART 1 - GENERAL
1.1 SUMMARY
A. This Section includes the following hangers and supports for HVAC system piping and equipment:
1. Steel pipe hangers and supports.
2. Clevis Hangers.
3. Thermal-hanger shield inserts.
4. Tunnel Floor Supports.
5. Fastener systems.
6. Alignment guides
B. Related Sections include the following:
1. Division 23 Section " Expansion Fittings and Loops for HVAC Piping" for pipe guides and anchors.
1.2 DEFINITIONS
A. MSS: Manufacturers Standardization Society for The Valve and Fittings Industry Inc.
B. Terminology: As defined in MSS SP-90, "Guidelines on Terminology for Pipe Hangers and Supports."
1.3 PERFORMANCE REQUIREMENTS
A. Design supports for multiple pipes, including pipe stands, capable of supporting combined weight of supported systems, system contents, and test water.
1.4 SUBMITTALS
A. Product Data: Catalog sheets, specifications and installation instructions for the following:
1. Steel pipe hangers and supports.
2. Thermal-hanger shield inserts.
3. Powder-actuated fastener systems.
4. Alignment guides.
Return Piping Replacement 230529-2 PGRU, Geneva, NY
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection:
1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, manufacturers specified.
2.2 STEEL PIPE HANGERS AND SUPPORTS
A. Description: MSS SP-58, Types 1 through 58, factory-fabricated components. Refer to Part 3 "Hanger and Support Applications" Article for where to use specific hanger and support types.
B. Manufacturers:
1. B-Line Systems, Inc.; a division of Cooper Industries.
2. Carpenter & Paterson, Inc.
3. Empire Industries, Inc.
4. ERICO/Michigan Hanger Co.
5. Globe Pipe Hanger Products, Inc.
6. Grinnell Corp.
C. Galvanized, Metallic Coatings: Pregalvanized or hot dipped.
D. Hanger Inserts: Hanger with pipe insulation insert for support of bearing surface of piping.
2.3 THERMAL-HANGER SHIELD INSERTS
A. Description: 100-psig- minimum, compressive-strength insulation insert encased in sheet metal shield.
B. Manufacturers:
1. Carpenter & Paterson, Inc.
2. ERICO/Michigan Hanger Co.
3. PHS Industries, Inc.
4. Pipe Shields, Inc.
5. Rilco Manufacturing Company, Inc.
6. Value Engineered Products, Inc.
C. Insulation-Insert Material for Hot Piping: Water-repellent treated, ASTM C 533, Type I calcium silicate.
Return Piping Replacement 230529-3 PGRU, Geneva, NY
2.4 TUNNEL FLOOR SUPPORTS
A. Hot piping:
1. (Adjustable) Roller stand with base plate, B-Line B3117SL.
2. Size roller to include insulation requirements.
2.5 FASTENER SYSTEMS
A. Mechanical-Expansion Anchors: Insert-wedge-type zinc-coated steel, for use in hardened portland cement concrete with pull-out, tension, and shear capacities appropriate for supported loads and building materials where used.
1. Manufacturers:
a. B-Line Systems, Inc.; a division of Cooper Industries.
b. Empire Industries, Inc.
c. Hilti, Inc.
d. ITW Ramset/Red Head.
e. MKT Fastening, LLC.
f. Powers Fasteners.
2.6 MISCELLANEOUS MATERIALS
A. Structural Steel: ASTM A 36/A 36M, steel plates, shapes, and bars; galvanized.
PART 3 - EXECUTION
3.1 HANGER AND SUPPORT APPLICATIONS
A. Specific hanger and support requirements are specified in Sections specifying piping systems and equipment.
B. Comply with MSS SP-69 for pipe hanger selections and applications that are not specified in piping system Sections.
C. Use hangers and supports with galvanized, metallic coatings for piping in tunnels and concealed crawl spaces.
D. Horizontal-Piping Hangers and Supports: Unless otherwise indicated and except as specified in piping system Sections, install the following types:
1. Adjustable, Steel Clevis Hangers (MSS Type 1): For suspension of insulated stationary pipes, NPS 1/2 to NPS 30.
2. Single Pipe Rolls (MSS Type 41): For suspension of pipes, NPS 1 to NPS 30, from 2 rods if longitudinal movement caused by expansion and contraction might occur. Provide vertical adjustment for different pipe elevations if required.
Return Piping Replacement 230529-4 PGRU, Geneva, NY
E. Hanger-Rod Attachments: Unless otherwise indicated and except as specified in piping system Sections, install the following types:
1. Steel Turnbuckles (MSS Type 13): For adjustment up to 6 inches for heavy loads.
2. Steel Clevises (MSS Type 14): For 120 to 450 deg F piping installations.
3. Malleable-Iron Sockets (MSS Type 16): For attaching hanger rods to various types of building attachments.
4. Steel Weldless Eye Nuts (MSS Type 17): For 120 to 450 deg F piping installations.
F. Saddles and Shields: Unless otherwise indicated and except as specified in piping system Sections, install the following types:
1. Steel Pipe-Covering Protection Saddles (MSS Type 39): To fill interior voids with insulation that matches adjoining insulation.
2. Protection Shields (MSS Type 40): Of length recommended in writing by manufacturer to prevent crushing insulation.
3. Thermal-Hanger Shield Inserts: For supporting insulated pipe.
G. Use mechanical-expansion anchors instead of building attachments where required in concrete construction.
3.2 HANGER AND SUPPORT INSTALLATION
A. Steel Pipe Hanger Installation: Comply with MSS SP-69 and MSS SP-89. Install hangers, supports, clamps, and attachments as required to properly support piping from building structure.
B. Thermal-Hanger Shield Installation: Install in pipe hanger or shield for insulated piping.
C. Fastener System Installation:
1. Install mechanical-expansion anchors in concrete after concrete is placed and completely cured. Install fasteners according to manufacturer's written instructions.
D. Install hangers and supports complete with necessary inserts, bolts, rods, nuts, washers, and other accessories.
E. Install hangers and supports to allow controlled thermal movement of piping systems, to permit freedom of movement between pipe anchors, and to facilitate action of expansion joints, expansion loops, expansion bends, and similar units.
F. Install lateral bracing with pipe hangers and supports to prevent swaying.
G. Install attachments at concentrated loads, including valves, flanges, and strainers, NPS 2 and larger and at changes in direction of piping.
H. Pipe Slopes: Install hangers and supports to provide indicated pipe slopes and so maximum pipe deflections allowed by ASME B31.9 (for building services piping) are not exceeded.
I. Insulated Piping: Comply with the following:
Return Piping Replacement 230529-5 PGRU, Geneva, NY
1. Attach clamps and spacers to piping.
a. Piping Operating above Ambient Air Temperature: Pipe hanger to be sized so insulation is continuous through pipe hanger.
b. Do not exceed pipe stress limits according to ASME B31.9 for building services piping.
2. Install MSS SP-58, Type 39, protection saddles if insulation without vapor barrier is indicated. Fill interior voids with insulation that matches adjoining insulation.
a. Option: Thermal-hanger shield inserts may be used. Include steel weight-distribution plate for pipe NPS 4 and larger if pipe is installed on rollers.
3. Shield Dimensions for Pipe: Not less than the following:
a. NPS 1/4 to NPS 3-1/2: 12 inches long and 0.048 inch thick.
4. Insert Material: Length at least as long as protective shield.
5. Thermal-Hanger Shields: Install with insulation same thickness as piping insulation.
3.3 ADJUSTING
A. Hanger Adjustments: Adjust hangers to distribute loads equally on attachments and to achieve indicated slope of pipe.
B. Trim excess length of continuous-thread hanger and support rods to 1-1/2 inches.
3.4 SCHEDULES
A. PIPE HANGER SPACING
PIPE SIZE MAX. HANGER SPACING HANGER
ROD DIAMETER
Inches Feet Inches 1 7 3/8 2 10 3/8 2-1/2 10 1/2 3 10 1/2
END OF SECTION 230529