ATT_013b_Space_Requirements_-_Temperature_and_Humdiity_02272015a.pdf

PDF 51 KB Posted

Attached to
Facility Operations and Maintenance Services for the National Center for Agricultural Utilization Research in Peoria, IL
Solicitation number
AG-32SC-S-14-0010
Issued by

About this file

ATT 013

View the file

Other files

File Type Posted
Amend_011_Sf_30.pdf PDF
Schedule_B_052115.xls XLS spreadsheet
Amend__010_SF_30.pdf PDF
Questions-wkm-5-15-2015.docx DOCX document
Amend009.pdf PDF
NCAUR_Contract_Body_051815_Mod_008.docx DOCX document
Schedule_B_051815.xls XLS spreadsheet
NCAUR_Statement_of_Work_5-12_15.docx DOCX document
Amend_008.pdf PDF
051215_Questions.docx DOCX document
Amend_007.pdf PDF
Amend_006_SF_30_NCAUR.pdf PDF
05-2174.txt TXT text file
IL3_04032015.txt TXT text file
Amend_005_sf30.pdf PDF
NCAUR_Statement_of_Work_4_9_15.docx DOCX document
Revised_Schedule_B_040215.xls XLS spreadsheet
NCAUR_041015_Requests_for_Clarifications_and_Questions.pdf PDF
Amend004.pdf PDF
IL3_04022015.txt TXT text file
Attendee_Roster.pdf PDF
05-2174_0315.txt TXT text file
032305_NCAUR_SF_30.pdf PDF
Prebid_Meeting_Agenda_March_2015.doc DOC document
NCAUR_Contract_Body_03052015_Mod_002_(3)JJ.docx DOCX document
Revised_bid_Form_MOD_002.pdf PDF
NCAUR_Requests_for_Clarifications_and_Questions_-_J.docx DOCX document
Mod_002.pdf PDF
05-2173_12222014.txt TXT text file
IL3_03022015.txt TXT text file
E.5_SCA_WD_05-2174.txt TXT text file
ATT_026a_AW_Summary.xlsx XLSX spreadsheet
ATT_009a_Task_Report.pdf PDF
ATT_028b.pdf PDF
ATT_030b_Seimens_Points.pdf PDF
ATT_017a_-_Pest_Treatment_Matrix_(Floorplans).pdf PDF
ATT_001b_Craft_Codes.pdf PDF
ATT_012a_INVENTORY_REPORT_FOR_O_ _M.pdf PDF
ATT_014b-Contractor_Space_02272015.pdf PDF
ATT_004_Documents_Incorporated_By_Reference.docx DOCX document
ATT_025_-_Historical_Pricing_data.docx DOCX document
ATT_005_Gov_Services_Furnished.xlsx XLSX spreadsheet
E.4_DBA_WD_IL3.txt TXT text file
ATT_002a_Work_Order_Types.pdf PDF
E.7_Exhibit-NCAUR_Bldg_Standards_02_09_2105.pdf PDF
NCAUR_Statement_of_Work_3-7-14.docx DOCX document
E.2_Quality_Assurance_Plan.pdf PDF
ATT_027b_-_Annual_Simplex_Inspection_and_Testing_Report_(2).pdf PDF
ATT_015_DESCRIPTION_OF_FLOORING_SURFACES.xlsx XLSX spreadsheet
ATT_008a_Task_Instruction_List.pdf PDF
Show 40 more

Latest 50 of 96 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sub-Location Requirement

Corn Growth Room Maintain temperature set point ± 2.0°F and lighting schedule for space. Temperature set points and lighting schedule shall be as required by research.

CW Cooler / Freezer – Room 0102 For cooler; maintain temperature set point ± 1.0°C . For freezer;

maintain temperature set point ± 1.0°C .Temperature set points shall be as required by research (typically nominal 3°C for cooler and nominal -18°C for freezer).

CW Cooler – Room 0115A Maintain temperature set point ± 1.0°C . Temperature set point shall be as required by research (typically nominal 3°C for cooler).

CW Cooler - Room 0115B Maintain temperature set point ± 1.0°C . Temperature set point shall be as required by research (typically nominal 3°C for cooler).

NW Cooler (located north of Room

3232)

Maintain temperature set point ± 2.0°C . Temperature set point shall be as required by research (typically nominal 3°C for cooler).

Building 001 SW Cooler – Room 0306 Maintain temperature set point ± 2.0°C . Temperature set point shall be as required by research (typically nominal 3°C for cooler).

SW Freezer – Room 0306 Maintain temperature set point ± 5.0°C . Temperature set point shall be as required by research (typically nominal -18°C for freezer).

Physical Test Lab 0229 Maintain temperature between 72 and 74°F and relative humidity

(RH) between 47-53%.

Lab 0309 Maintain temperature between 71 and 75°F and relative humidity

(RH) between 45-55 %.

NMR Center 0019 Maintain temperature between 68-74°F and relative humidity (RH) between 30-60%.

IT Equipment Rooms 1314, 2051, 2100, 2228, 3020 &3135

Maintain temperature between 68°F and 72°F (24/7) and relative humidity (RH) between 30-60%.

Building 002 Boiler House (except for office) No cooling available. Temperature shall not drop below 50°F.

Temperature set point shall not exceed 60°F without Facility

Manager approval.

Building 002 Boiler House (office space only) Maintain temperature between 70-74°F.

Building 003 Semi-Works No cooling available. Temperature shall not drop below 50°F.

Temperature set point shall not exceed 60°F without Facility

Manager approval.

Building 004 Property Storage No Temperature Requirements

Building 005 Commodity Storage No Temperature Requirements

Building 007 Dry Milling Temperatures shall not drop below 50°F. Temperature set point shall not exceed 60°F without Facility Manager approval.

Building 008 Corn Growth Building Maintain temperature set point ± 2.0°F. Temperature set point shall be as required by research (24/7).

Building 009

Maintenance Building No cooling available. Temperatures shall not drop below 50°F.

Temperature set point shall not exceed 60°F without Facility

Manager approval.

Building 010 010A No cooling available. Temperatures shall not drop below 50°F

010B No greater than 70°F

010C No cooling available. Temperatures shall not drop below 50°F

Building 011 011A Temperature shall not exceed 70°F.

011B Temperature shall not exceed 70°F.

AG-32SC-S-14-0010 NCAUR Peoria ATT 013

MOD 001 1 02/25/2015

Building 012 012A Temperature shall not exceed 70°F.

012B Temperature shall not exceed 70°F.

Building 013 Garden Storage No Temperature Requirements

Miscellaneous Building System Requirements Include:

o Minimum of 50 psi steam pressure (24/7);

o Maximum 45°F chilled water temperature when cooling is required during occupancy;

General Space Requirements Include:

o Maintain space control set point temperatures ±2.0°F (North and Center Wings – i.e. occupied renovated areas);

o Maintain space control set point temperatures ±3.0°F (Administrative and South Wings – i.e. occupied non-renovated areas);

o During un-occupied periods, all labs and offices shall be greater than 65°F and less than 85°F;

o Unless noted otherwise, all other areas with heating capabilities shall not drop below 55°F; and o Unless noted otherwise, all other areas with cooling capabilities shall not rise above 85°F.

Research Related Requirements:

o Maintain increased steam pressure up to 120 psi when required by research, during normal work hours for the duration of the request;

o Maintain research related Controlled Temperature Environments at temperatures ±1.5°F;

o Maintain research related humidity control as required;

o All labs and offices shall be provided with their minimum air change requirement per ARS design standards manual 242.1;

o All areas with humidification control capabilities shall not fall below 30%

RH; and o Maintain Process Chilled Water control set point temperatures ± 2°F (24/7).

AG-32SC-S-14-0010 NCAUR Peoria ATT 013

MOD 001 2 02/25/2015