Sub-Location Requirement
Corn Growth Room Maintain temperature set point ± 2.0°F and lighting schedule for space. Temperature set points and lighting schedule shall be as required by research.
CW Cooler / Freezer – Room 0102 For cooler; maintain temperature set point ± 1.0°C . For freezer;
maintain temperature set point ± 1.0°C .Temperature set points shall be as required by research (typically nominal 3°C for cooler and nominal -18°C for freezer).
CW Cooler – Room 0115A Maintain temperature set point ± 1.0°C . Temperature set point shall be as required by research (typically nominal 3°C for cooler).
CW Cooler - Room 0115B Maintain temperature set point ± 1.0°C . Temperature set point shall be as required by research (typically nominal 3°C for cooler).
NW Cooler (located north of Room
3232)
Maintain temperature set point ± 2.0°C . Temperature set point shall be as required by research (typically nominal 3°C for cooler).
Building 001 SW Cooler – Room 0306 Maintain temperature set point ± 2.0°C . Temperature set point shall be as required by research (typically nominal 3°C for cooler).
SW Freezer – Room 0306 Maintain temperature set point ± 5.0°C . Temperature set point shall be as required by research (typically nominal -18°C for freezer).
Physical Test Lab 0229 Maintain temperature between 72 and 74°F and relative humidity
(RH) between 47-53%.
Lab 0309 Maintain temperature between 71 and 75°F and relative humidity
(RH) between 45-55 %.
NMR Center 0019 Maintain temperature between 68-74°F and relative humidity (RH) between 30-60%.
IT Equipment Rooms 1314, 2051, 2100, 2228, 3020 &3135
Maintain temperature between 68°F and 72°F (24/7) and relative humidity (RH) between 30-60%.
Building 002 Boiler House (except for office) No cooling available. Temperature shall not drop below 50°F.
Temperature set point shall not exceed 60°F without Facility
Manager approval.
Building 002 Boiler House (office space only) Maintain temperature between 70-74°F.
Building 003 Semi-Works No cooling available. Temperature shall not drop below 50°F.
Temperature set point shall not exceed 60°F without Facility
Manager approval.
Building 004 Property Storage No Temperature Requirements
Building 005 Commodity Storage No Temperature Requirements
Building 007 Dry Milling Temperatures shall not drop below 50°F. Temperature set point shall not exceed 60°F without Facility Manager approval.
Building 008 Corn Growth Building Maintain temperature set point ± 2.0°F. Temperature set point shall be as required by research (24/7).
Building 009
Maintenance Building No cooling available. Temperatures shall not drop below 50°F.
Temperature set point shall not exceed 60°F without Facility
Manager approval.
Building 010 010A No cooling available. Temperatures shall not drop below 50°F
010B No greater than 70°F
010C No cooling available. Temperatures shall not drop below 50°F
Building 011 011A Temperature shall not exceed 70°F.
011B Temperature shall not exceed 70°F.
AG-32SC-S-14-0010 NCAUR Peoria ATT 013
MOD 001 1 02/25/2015
Building 012 012A Temperature shall not exceed 70°F.
012B Temperature shall not exceed 70°F.
Building 013 Garden Storage No Temperature Requirements
Miscellaneous Building System Requirements Include:
o Minimum of 50 psi steam pressure (24/7);
o Maximum 45°F chilled water temperature when cooling is required during occupancy;
General Space Requirements Include:
o Maintain space control set point temperatures ±2.0°F (North and Center Wings – i.e. occupied renovated areas);
o Maintain space control set point temperatures ±3.0°F (Administrative and South Wings – i.e. occupied non-renovated areas);
o During un-occupied periods, all labs and offices shall be greater than 65°F and less than 85°F;
o Unless noted otherwise, all other areas with heating capabilities shall not drop below 55°F; and o Unless noted otherwise, all other areas with cooling capabilities shall not rise above 85°F.
Research Related Requirements:
o Maintain increased steam pressure up to 120 psi when required by research, during normal work hours for the duration of the request;
o Maintain research related Controlled Temperature Environments at temperatures ±1.5°F;
o Maintain research related humidity control as required;
o All labs and offices shall be provided with their minimum air change requirement per ARS design standards manual 242.1;
o All areas with humidification control capabilities shall not fall below 30%
RH; and o Maintain Process Chilled Water control set point temperatures ± 2°F (24/7).