Addendum 2 YOS Bldg 7 HVAC Schendt 101116.pdf

PDF 112 KB Posted

Attached to
CTF YOS Building 7 HVAC CMS92454
Solicitation number
DQ1 CAAA 2017000355 2
Issued by
Ouray County, Colorado Springs City, Colorado

About this file

This is Addendum Number 2 to the YOS Building 7 HVAC Replacement project issued by Schendt Engineering Corporation on behalf of the Colorado Department of Corrections. The addendum modifies the original contract documents and specifications for HVAC replacement work at the facility. The bid submission deadline is Thursday, October 13, 2016 at 4:00 PM Mountain Daylight Time. Bidders are required to acknowledge receipt of this addendum and the previous addendum with their bid submission. All bidders, subcontractors, and material suppliers must review the addendum to understand how it affects their respective work scopes.

The addendum provides four key modifications to the project requirements. First, the Colorado Department of Corrections Life Safety Officer will conduct hazardous material testing and any required abatement work, with contractors assuming existing surfaces and insulation are free of asbestos-containing materials for bidding purposes. Second, baseboard radiators must be controlled through a local thermostat mounted 48 inches above finished floor on an interior wall within a thermostat lock-box, with initial setpoint at 70 degrees Fahrenheit and modulating control valve operation as specified. Third, a Building Automation System control panel with 120-volt service duplex receptacle must be installed in Security & Storage room 113 and coordinated with existing conditions and Owner approval. Fourth, bidding documents are available through Schendt Engineering's FTP site at ftp://96.81.48.17/CDOC_YOS_B7/ with all documents distributed electronically.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Schendt Engineering Corporation

2912 Beacon Street (719) 637-8850 Colorado Springs, CO 80907-9207 www.secengr.com

YOS_Bldg 7_ADDENDUM_No2 Page 1 of 1

ADDENDUM NUMBER 2

DATE: October 11, 2016

OWNER: Colorado Department of Corrections

PROJECT: YOS Bldg 7 HVAC Replacement

PROJ. NO: YOS1601 / SEC Project No. 14143

The Drawings, Specifications and Contract Documents on the subject project are modified, corrected, supplemented and/or superseded as hereinafter described. The following additions, deletions, changes and information shall become a part of and modify all work shown or described in the Drawings.

All bidders shall make necessary adjustments in their bid on account of this addendum. Each and every bidder, subcontractor, and material supplier shall be responsible for reading each item in this addendum to ascertain to what extent and in what manner it affects the work in which they are interested. Each Bidder shall indicate on the Bid Form their acknowledgment of receipt of this addendum document by addendum number and addendum date.

Addendum Items:

1. REMINDER: BID DATE is Thursday October 13, 2016 at 4:00 PM MDT. Refer to Documented Quote dated September 29, 2016 regarding email submission requirements. Please acknowledge receipt of both addenda with bid submission.

2. CDOC Life Safety Officer shall perform hazardous material testing assessment as required for this project, and if required, CDOC will perform required abatement to accomplish the work; for bidding purposes, contractors shall assume any existing surfaces or insulation to be disturbed in the course of the work is free of asbestos-containing materials.

3. Sheet M1.01, Mechanical Plan: Baseboard Radiator shall be controlled through a local thermostat mounted 48” AFF on an interior wall and enclosed in a thermostat lock-box. The space temperature setpoint shall be initially set at 70°F. Refer to Heating Mode Sequence of Operation below:

Heating Mode: When the space temperature drops below heating setpoint, the hot water control valve shall modulate open to maintain space temperature. When the space temperature rises above heating setpoint, the hot water control valve shall modulate closed. Control valve shall fail open.

4. Sheet E1.01, Control Panel: Provide BAS control panel with 120 volt service duplex receptacle located in Security & Storage room 113. Service receptacle shall be located within the control panel and shall be served from HD-10. Coordinate control panel location within space with existing conditions and Owner.

5. NOTE: Bidders may procure addenda and Bidding Documents from Schendt Engineering FTP site:

ftp://96.81.48.17/CDOC_YOS_B7/ . All bidding documents will be distributed electronically.

END OF ADDENDUM NUMBER 2