A04_44045721_GRTE_Fire_Alarm_Points_List.xlsx
XLSX spreadsheet 38 KB Posted
- Attached to
- GRTE FIRE SUPPRESSION/PANEL INSPECTIONS Federal contract opportunity
- Solicitation number
- 140P1426Q0099
About this file
This file is a fire alarm points list in spreadsheet format for Grand Teton National Park (GRTE) fire suppression and panel inspection work. The document appears to be an appendix or technical reference that catalogs fire alarm system points and locations throughout the park facilities, serving as a detailed inventory for the annual fire suppression system inspections, annual fire panel inspections, and 2026 repairs outlined in Solicitation Number 140P1426Q0099. The list functions as a technical specification document that contractors would use to understand the scope and extent of fire alarm systems requiring inspection and maintenance across GRTE facilities. This reference material would be essential for bidders to accurately assess labor requirements, scheduling needs, and pricing for the inspection and repair services requested by the Department of the Interior National Park Service Intermountain Region.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment_1_Questions_and_Answers_0001.docx | DOCX document | |
| Sol_140P1426Q0099_Amd_0001.pdf | ||
| Amendment_1_GRTE_Fire_Alarm_Points_List_Rev_09222026_0001.xlsx | XLSX spreadsheet | |
| Amendment_1_GRTE_Fire_Suppression_and_Fire_Panel_Inspection_STATEMENT_OF_WORK_Rev_09222026_0001.docx | DOCX document | |
| Amendment_1_GRTE_Fire_Inspections_Location_Schedule_2026_Rev_09222026_0001.xlsx | XLSX spreadsheet | |
| B03_Teton_County_2015-5409_Rev_30_08222026.pdf | ||
| A04_44045721_GRTE_Fire_Inspections_Location_Schedule_2026.xlsx | XLSX spreadsheet | |
| Sol_140P1426Q0099.pdf | ||
| A04_44045721_GRTE_Fire_Suppression_and_Fire_Panel_Inspection_STATEMENT_OF_WORK.docx | DOCX document | |
| A04_2026_Repairs_Needed_2025_Deficiency_List.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| Panel location | Brinkerhoff |
| 10 | Master Bedroom Smoke Detector |
| 11 | Kitchen Smoke Detector |
| 12 | Bedroom #1 Smoke Detector |
| 13 | Bedroom #2 Smoke Detector |
| 14 | Bedroom #3 Smoke Detector |
| 15 | Living Room North Smoke Detector |
| 16 | Living Room South Smoke Detector |
| 17 | Pull Station |
| 18 | Reception Motion Detector |
| 19 | Kitchen Motion Detector |
| 20 | North Motion Detector |
| 21 | NW Motion Detector |
| 22 | South Motion Detector |
| 23 | SW Motion Detector |
| 24 | Master Bedroom Motion Detector |
| 25 | Basement Motion Detector |
| 26 | Caretakers Cottage Motion Detector |
| Panel location | Burt Dr 101, 103, 105, 107 |
| 1 | HEAT DETECTORS |
| 2 | PULL STATION |
| 3 | SUPERVISORY GENERAL |
| 4 | SUPERVISORY GENERAL |
| 5 | WATER FLOW- GENERAL |
| 6 | 105 LIVING ROOM SMOKE |
| 7 | 150 KITCHEN SMOKE |
| 8 | 101 KITCHEN SMOKE |
| 9 | 101 LIVING ROOM SMOKE |
| 10 | HEAT DETECTOR 101 / 103 GARAGE |
| 12 | 101 BEDROOM SMOKE |
| 13 | 101 HALLWAY SMOKE |
| 14 | 101 CO DETECTOR |
| 15 | 101 BEDROOM SMOKE |
| 16 | 105 BEDROOM SMOKE |
| 17 | 105 CO DETECTOR |
| 18 | 105 HALLWAY SMOKE |
| 19 | 105 BEDROOM SMOKE |
| 20 | 107 BEDROOM SMOKE |
| 21 | 107 HALLWAY SMOKE |
| 22 | 107 CO DETECTOR |
| 23 | 107 BEDROOM SMOKE |
| 24 | 103 BEDROOM SMOKE |
| 25 | 103 CO DETECTOR |
| 26 | 103 HALLWAY SMOKE |
| 27 | 103 BEDROOM SMOKE |
| 28 | 103 LIVING ROOM SMOKE |
| 29 | 103 KITCHEN SMOKE |
| 30 | 107 KITCHEN SMOKE |
| 31 | 107 LIVING ROOM SMOKE |
| 33 | BASEMENT HEAT DETECTOR |
| 34 | BASEMENT HEAT DETECTOR |
| 201 | TAMPER 101 / 103 BASEMENT |
| 202 | WATERFLOW 101/ 103 BASEMENT |
| 203 | PULLSTATION BEWTEEN 105 / 107 FRONT DOOR |
| 211 | PULLSTATION BETWEEN 101 / 103 FRONT DOOR |
| 232 | 24V MONITOR PANEL |
| Panel location | Burt Dr 102, 104, 106, 108 |
| 1 | HEAT DETECTORS |
| 2 | PULL STATION |
| 3 | SUPERVISORY -GENERAL |
| 4 | SUPERVISORY -GENERAL |
| 5 | WATER FLOW -GENERAL |
| 6 | Smoke Detector 106 Living Room |
| 7 | Smoke Detector 106 Kitchen |
| 8 | Smoke Detector 106 Hallway |
| 9 | Smoke Detector 102 Living Room |
| 10 | Heat Detector 102, 104 Garage |
| 12 | Smoke Detector 102 Bedroom |
| 13 | Smoke Detector 102 Hallway |
| 14 | 102 CO Detector |
| 15 | Smoke Detector 102 Bedroom |
| 16 | Smoke Detector 106 Bedroom |
| 17 | 106 CO Detector |
| 18 | Smoke Detector 102 Kitchen |
| 19 | Smoke Detector 106 Bedroom |
| 20 | Smoke Detector 108 Bedroom |
| 21 | Smoke Detector 108 Hallway |
| 22 | 108 CO Detector |
| 23 | Smoke Detector 108 Bedroom |
| 24 | Smoke Detector 104 Bedroom |
| 25 | 104 CO Detector |
| 26 | Smoke Detector 104 Hallway |
| 27 | Smoke Detector 104 Bedroom |
| 28 | Smoke Detector 104 Living Room |
| 29 | Smoke Detector 104 Kitchen |
| 30 | Smoke Detector 108 Kitchen |
| 31 | Smoke Detector 108 Living Room |
| 33 | Heat Detector Basement |
| 34 | Heat Detector Basement |
| 201 | Tamper 102, 104 Basement |
| 202 | Waterflow 102, 104 Basement |
| 203 | Pull Station 106, 108 Front Door |
| 211 | Pull Station 102, 104 Front Door |
| 232 | 24v Monitor in Panel |
| Panel location | Carncross 102, 104, 106, 108 |
| 1 | HEAT DETECTORS |
| 2 | PULL STATION |
| 3 | SUPERVISORY GENERAL |
| 4 | SUPERVISORY GENERAL |
| 5 | WATER FLOW |
| 6 | 106 LIVING ROOM SMOKE |
| 7 | 106 KITCHEN SMOKE |
| 8 | 102 KITCHEN SMOKE |
| 9 | 102 LIVING ROOM SMOKE |
| 10 | HEAT DETECTOR IN 102/104 GARAGE |
| 12 | 102 BEDROOM SMOKE DETECTOR |
| 13 | 102 HALLWAY SMOKE DETECTOR |
| 14 | 102 CO DETECTOR |
| 15 | 1O2 BEDROOM SMOKE |
| 16 | 106 BEDROOM SMOKE |
| 17 | 106 CO DETECTOR |
| 18 | 106 HALLWAY SMOKE |
| 19 | 106 BEDROOM HALL SMOKE |
| 20 | 108 BEDROOM SMOKE |
| 21 | 108 HALLWAY SMOKE |
| 22 | 108 CO DETECTOR |
| 23 | 108 BEDROM SMOKE |
| 24 | 104 BEDROOM SMOKE |
| 25 | 104 CO DETECTOR |
| 26 | 104 HALLWAY SMOKE |
| 27 | 104 BEDROOM SMOKE |
| 28 | 104 LIVING ROOM SMOKE |
| 29 | 104 KITCHEN SMOKE |
| 30 | 108 KITCHEN SMOKE |
| 31 | 108 LIVING ROOM SMOKE |
| 33 | HEAT DETECTOR IN 102/104 GARAGE |
| 34 | HEAT DETECTOR IN 106/108 GARAGE |
| 201 | TAMPER 102 BASEMENT |
| 202 | 102 BASEMENT WATERFLOW |
| 203 | PULLSTATION BETWEEN 106 / 108 FRONT DOOR |
| 211 | PULLSTATION BETWEEN 102 / 104 FRONT DOOR |
| 233 | 24V POWER SUPPLY PANEL |
| Panel location | Carncross 110, 112, 114, 116 |
| 1 | HEAT DETECTORS |
| 2 | PULL STATIONS |
| 3 | SUPERVISORY GENERAL |
| 4 | SUPERVISORY GENERAL |
| 5 | WATER FLOW- GENERAL |
| 6 | 114 LIVING ROOM SMOKE |
| 7 | 114 KITCHEN SMOKE |
| 8 | 110 KITCHEN SMOKE |
| 9 | 110 LIVING ROOM |
| 10 | HEAT DETECTOR 110 / 112 GARAGE |
| 12 | 110 BEDROOM SMOKE |
| 13 | 110 HALLWAY SMOKE |
| 14 | 110 CO DETECTOR |
| 15 | 110 BEDROOM SMOKE |
| 16 | 114 BEDROOM SMOKE |
| 17 | 114 CO DETECTOR |
| 18 | 114 HALLWAY SMOKE |
| 19 | 114 BEDROOM SMOKE |
| 20 | 116 BEDROOM SMOKE |
| 21 | 116 HALLWAY SMOKE |
| 22 | 116 CO DETECTOR |
| 23 | 116 BEDROOM SMOKE |
| 24 | 112 BEDROOM SMOKE |
| 25 | 112 CO DETECTOR |
| 26 | 112 HALLWAY SMOKE |
| 27 | 112 BEDROOM SMOKE |
| 28 | 112 LIVING ROOM |
| 29 | 112 KITCHEN SMOKE |
| 30 | 116 KITCHEN SMOKE |
| 31 | 116 LIVING ROOM SMOKE |
| 33 | HEAT DETECTOR BASEMENT 110 |
| 34 | HEAT DETECTOR BASEMENT 114 |
| 201 | TAMPER 110 BASEMENT |
| 202 | WATERFLOW 110 BASEMENT |
| 203 | PULLSTATION BETWEEN 114 / 116 FRONT DOOR |
| 211 | PULLSTATION BETWEEN 110 / 112 FRONT DOOR |
| 232 | 24V SUPPLY IN PANEL |
| Panel location | Carncross 118, 120, 122, 124 |
| 1 | Fire Alarm- Heat Detector |
| 2 | Pull Station |
| 3 | Supervisory General |
| 4 | Supervisory General |
| 5 | Fire Alarm- Water Flow |
| 6 | Smoke Detectors General |
| 7 | Smoke Detector 122 Kitchen |
| 8 | Smoke Detector 118 Kitchen |
| 9 | Smoke Detector 118 Living Room |
| 10 | Heat Detector 118,120 Garage |
| 12 | Smoke Detector 118 Bedroom |
| 13 | Smoke Detector 118 Hallway |
| 14 | Tamper 118 CO Detector |
| 15 | Smoke Detector 118 Bedroom |
| 16 | Smoke Detector 122 Bedroom |
| 17 | 124 CO Detector |
| 18 | Smoke Detector 122 Hallway |
| 19 | Smoke Detector 122 Bedroom |
| 20 | Smoke Detector 124 Bedroom |
| 21 | Smoke Detector 124 Hallway |
| 22 | 124 CO Detector |
| 23 | Smoke Detector 124 Bedroom |
| 24 | Smoke Detector 120 Bedroom |
| 25 | 120 CO Detector |
| 26 | Smoke Detector 120 Halllway |
| 27 | Smoke Detector 120 Bedroom |
| 28 | Smoke Detector 120 Living Room |
| 29 | Smoke Detector 120 Kitchen |
| 30 | Smoke Detector 124 Kitchen |
| 31 | Smoke Detector 124 Living Room |
| 33 | Heat Detector Basement |
| 34 | Heat Detector Basement |
| 201 | Tamper 118, 120 Basement |
| 202 | Waterflow 118, 120 Basement |
| 203 | Pull Station 112,124 Front Door |
| 211 | Pull Station 118, 120 Front Door |
| 232 | 24v Monitor in Panel |
| Panel location | Colter Bay Maintenance |
| 1 | WATERFLOW |
| 2 | SPRINKLER TAMPERS 2 |
| 3 | FACP SMOKE DETECTOR |
| 4 | SOUTH PULLSTATION |
| 5 | NORTH PULLSTATION |
| 6 | POWER NACS |
| Panel location | Colter Bay Visitor |
| 2 | SE lecture room door |
| 3 | SW Lecture room door |
| 10 | NW upper smoke |
| 13 | Sales area smoke |
| 14 | Sales hold up BTN |
| 16 | Perm BTN motion |
| 24 | Sale hall motion |
| 28 | Sale area motion |
| 32 | Sale area motion |
| 39 | Lecture room smoke |
| 40 | Proj btn smoke |
| 42 | Lecture room motion |
| 43 | Cash room hold up |
| 45 | W sales door |
| 46 | Store room smoke |
| 47 | E sales door |
| 48 | SE sales door |
| 63 | Sales hold up |
| 9 | SE upper smoke |
| 11 | NE upper smoke |
| 12 | SE upper smoke |
| 17 | SW upper motion |
| 18 | NW upper motion |
| 19 | NE upper motion |
| 20 | SE upper motion |
| 21 | Mid upper motion |
| 22 | Cruciform motion |
| 23 | SW upper door |
| 25 | Arts prj bath smoke |
| 26 | NW lower smoke |
| 27 | E lower smoke |
| 29 | Bskt display door |
| 30 | E lower door |
| 31 | NW lower door |
| 33 | NW lower motion |
| 34 | N lower motion |
| 35 | NW lower motion |
| 36 | SE lower motion |
| 37 | S lower motion |
| Panel location | Craig Thomas Discovery Center |
| 9 | NPS 118 MOTION |
| 10 | BOOKSTORE MOTION |
| 11 | NPS 119 MOTION |
| 12 | INFO DESK MOTION |
| 13 | NPS WORK MOTION |
| 14 | EXHIBIT MOTION |
| 15 | NPS HALL MOTION |
| 16 | MECH 124 MOTION |
| 17 | PERMIT 113 MOTION |
| 18 | ORIENTATION MOTION |
| 19 | COPY/MAIL MOTION |
| 20 | EMPLOYEE ENTRANCE MOTION |
| 21 | GENERATOR MOTION |
| 22 | NHA 133 MOTION |
| 26 | SPRINKLER FLOW |
| 27 | SPRINKLER TAMPER |
| 28 | FIRE PUMP FAIL |
| 29 | FIRE PUMP PHASE REV. |
| 31 | FIRE PUMP RUN |
| 32 | NPS FIRE PULL |
| 33 | BOOKSTORE PULL |
| 34 | EMPLOYEE ENTRANCE FIRE PULL |
| 35 | DOOR 131 PULL |
| 36 | DOOR 109 PULL |
| 37 | LOCKER HALL PULL |
| 38 | INFO DESK PANIC |
| 39 | DOOR 110 PULL |
| 40 | DOOR 108 PULL |
| 43 | BOOKSTORE PANIC |
| 44 | NHA 133 PANIC |
| 45 | ROOM 113 PANIC |
| 46 | DOOR 108 DS |
| 48 | NPS DUCT DET. |
| 51 | WEST MEZZ DUCT |
| 52 | DOOR 106 PULL |
| 53 | DOOR 101B PULL |
| 57 | WEST EX. MOTION |
| 58 | NIGHTDOOR MOTION |
| 59 | CLASS RM. MOTION |
| 60 | NHS MEZZ TAMPER |
| 61 | CLASSMEZZ TAMPER |
| 101 | SMOKE AUD ENTRY |
| 102 | MOTION AUD ENTRY |
| 103 | SMOKE AUD ROW 7E |
| 104 | SMOKE AUD ROW 7W |
| 105 | SMOKE AUD ROW 2E |
| 106 | SMOKE AUD ROW 2W |
| 107 | MOTOIN AUD NORTH |
| 108 | AUD DOOR NW |
| 109 | AUD NW DR PULL |
| 110 | SMOKE STORAGE |
| 111 | SMOKE MECH PLFM |
| 23 | BOOKSTORE DOOR |
| 24 | EMPLOYEE 126 DOOR |
| 25 | MECH 124 DOOR |
| 30 | FIRE PUMP |
| 41 | DOOR 110 DS |
| 42 | DOOR 110 DS |
| 47 | NHS DUCT DETECTOR |
| 49 | DOOR 131 DS |
| 50 | DOOR 135 DS |
| 54 | DOOR 108 DS |
| 55 | DOOR 106 DS |
| 56 | DOOR 101 B DS |
| 70 | EMPLOYEE ENTRANCE #70 |
| 71 | LOCKER D 71 |
| 72 | INFO DESK #72 |
| 73 | GEN RM #73 |
| 74 | MECH ROOM #74 |
| Panel location | Grand Teton Elevator Phone |
| Elevator phone 1 | |
| Elevator phone 2 | |
| Panel location | GTA warehouse |
| 1 | 100-Fire alarm ABOVE FACP- PHOTO DETECTOR |
| 2 | 100-Fire alarm GYM |
| 3 | 100-Fire alarm IT ROOM |
| 4 | 100-Fire alarm MECHANICAL ROOM- PHOTO DETECTOR |
| 5 | 100-Fire alarm MECHANICAL ROOM- THERMAL DETECTOR |
| 6 | 100-Fire alarm GTA WAREHOUSE |
| 7 | 100-Fire alarm OFFICE 011 |
| 8 | 100-Fire alarm OFFICE AREA ENTRANCE |
| 9 | 100-Fire alarm BREAK ROOM |
| 10 | 100-Fire alarm OFFICE AREA ENTRANCE |
| 11 | 100-Fire alarm OFFICE 002 |
| 12 | 100-Fire alarm OFFICE 003 |
| 13 | 100-Fire alarm OFFICE HALL |
| 14 | 100-Fire alarm COPY/FAX ROOM 009 |
| 15 | 100-Fire alarm GTA WAREHOUSE- THERMAL |
| 16 | 100-Fire alarm MEETING ROOM 008 |
| 17 | 100-Fire alarm OFFICE 004 |
| 18 | 100-Fire alarm OFFICE 005 |
| 19 | 100-Fire alarm OFFICE 006 |
| 20 | 100-Fire alarm OFFICE 007 |
| 21 | 100-Fire alarm GTA WAREHOUSE - THERMAL |
| 22 | 100-Fire alarm BOYS BATHROOM |
| 23 | 100-Fire alarm JANITOR BETWEEN BATHROOMS |
| 24 | 100-Fire alarm GIRLS BATHROOM |
| 25 | 100-Fire alarm GTA WAREHOUSE- THERMAL |
| 26 | 100-Fire alarm GTA WAREHOUSE- THERMAL |
| 27 | 100-Fire alarm GYM |
| 28 | 100-Fire alarm GYM |
| 29 | 100-Fire alarm DFM STORAGE- THERMAL |
| 30 | 100-Fire alarm DFM STORAGE- THERMAL |
| 31 | 100-Fire alarm INTERP STORAGE- THERMAL |
| 32 | 100-Fire alarm DOCUMENT PROCESSING |
| 33 | 100-Fire alarm DOCUMENT STORAGE |
| 34 | 100-Fire alarm DOCUMENT STORAGE |
| 35 | 100-Fire alarm DOCUMENT PROCESSING |
| 36 | 100-Fire alarm GYM |
| 37 | 100-Fire alarm PULL STATION- BY FACP |
| 38 | 593-Tamper on fire system TAMPER MAIN RISER |
| 39 | 100-Fire alarm WATERFLOW MAIN RISER |
| 40 | 100-Fire alarm PULL STATION- NE WAREHOUSE EXIT |
| 41 | 100-Fire alarm PULL STATION- NE OFFICE EXIT |
| 42 | 100-Fire alarm WEST WAREHOUSE EXIT |
| 43 | 100-Fire alarm PULL STATION- SW STORAGE EXIT |
| 44 | 100-Fire alarm PULL STATION- WEST STORAGE EXIT |
| Panel location | Headquarters Building |
| 1 | SPRINKLER TAMPER |
| 2 | SPRINKLER WATERFLOW/ PIV TAMPER - Fire or Spvs |
| 3 | WATERFLOW BELL |
| 4 | FACP PULL STATION |
| 5 | VESTIBULE 129A |
| 6 | CORRIDOR 133 EXIT |
| 7 | MECHANICAL 136 |
| 8 | MECH 136 PULLSTATION |
| 9 | VEHICLE BAY 142 |
| 10 | VEHICLE BAY 142 |
| 11 | VEHICLE BAY 142 |
| 12 | DRIVE THRU BAY 143 |
| 13 | ELEC BAY 139 PULLSTATION |
| 14 | HAZMAT 141 |
| 15 | VEHICLE BAY 142 |
| 16 | PLUMBING SHOP 140 |
| 17 | PLUMBING SHOP 140 PULLSTATION |
| 18 | ELECTRICAL BAY 139 |
| 19 | WAREHOUSE 128 N. |
| 20 | WAREHOUSE 128 S, |
| 21 | ELEVATOR 1 EQUIPMENT RM |
| 22 | ELEVATOR PRIMARY RECALL/ SHUNT |
| 23 | ELEVATOR SECONDARY RECALL/ HAT FLASH |
| 24 | SECURE STORAGE 134 PULLSTATION |
| 25 | STAIR #1 2ND FLOOR |
| 26 | CONFERENCE ROOM 201 |
| 27 | 2ND FLOOR ELEVATOR LOBBY |
| 28 | FACP PULL STATION |
| 29 | OPEN OFFICE 205 E. |
| 30 | OPEN OFFICE 205 W. |
| 31 | OFFICE 204 |
| 32 | OFFICE 211 |
| 33 | OPEN OFFIE 212 S. |
| 34 | OFFICE 215 |
| 35 | TELE/ MED 210 |
| 36 | TELE/ MED 209 |
| 37 | OFFICE 216 |
| 38 | OFFICE 217 |
| 39 | OFFICE 214 BLACKSHEEP |
| 40 | OPEN OFFICE 212 N. |
| 41 | OFFICE 213 |
| 42 | OFFICE 218 |
| 43 | COPY/FAX 224 |
| 44 | LOUNGE 225 |
| 45 | BREAKROOM 226 |
| 46 | OPEN OFFICE 227 S. |
| 47 | OFFICE 228 |
| 48 | OFFICE 229 |
| 49 | MENS RESTROOM 230 |
| 50 | WOMENS RESTROOM 231 |
| 51 | CHASE 230A |
| 52 | OPEN OFFICE 227 N. |
| 53 | CONFERENCE ROOM 237 |
| 54 | STAIR #2 2ND FLOOR |
| 55 | STAIR #2 2ND fLOOR |
| 56 | VESTIBULE 236 |
| 57 | DUCT DETECTOR 233 |
| 58 | DUCT DETECTOR 233 |
| 59 | OFFICE 233 |
| 60 | ELECTRIC ROOM 238 |
| 61 | IT ROOM 239A |
| 62 | MECH ROOM 239 |
| 63 | CORRIDOR DRIDLINE 8 |
| 64 | ATTIC 240 W. |
| 65 | MECH ROOM 239 S |
| 66 | AH1 DUCT DETECTOR |
| 67 | AH1 SHUTDOWN |
| 68 | AH2 DUCT DETECTOR |
| 69 | MECH ROOM 239 N. |
| 70 | NAC 1 TROUBLE |
| 71 | ATTIC 240 W |
| 72 | ATTIC 240 W. |
| 73 | ATTIC 240 MIDDLE |
| 74 | CORRIDOR 241 |
| 75 | ATTIC 240 E. |
| 76 | ATTIC 240 E. |
| 77 | CORRIDOR 241 |
| 78 | ATTIC 240 E. |
| 79 | CORRIDOR 241 |
| 80 | CORRIDOR 234 N |
| 81 | OPEN OFFICE 232 N. |
| 82 | CORRIDOR 234 S. |
| 83 | FOCUS BOOTH 232B |
| 84 | OPEN OFFICE 232 S. |
| 85 | CORRIDOR 222 N |
| 86 | TELE/MED 221 |
| 87 | CONFERENCE ROOM 220 |
| 88 | OPEN OFFICE 219 |
| 89 | CORRIDOR 222 S |
| 90 | LIBRARY 208 |
| 91 | LOUNGE 207 |
| 92 | KITCHENNETTE 206 |
| 93 | STAIR #1B 2ND FLOOR |
| 94 | STAIR #1 2ND FLOOR |
| 95 | NAC 3/ NAC 4 TROUBLE |
| 100 | VESTIBULE 310 |
| 101 | VESTIBULE 310 |
| 102 | OPEN OFFICE 309 N |
| 103 | OPEN OFFICE 309 MID |
| 104 | OPEN OFFICE 309 S |
| 105 | COPY/ FAX 305A |
| 106 | COPY/FAX 305 B |
| 107 | COP/ FAX 305 |
| 108 | OPEN OFFICE 303 N |
| 109 | OPEN OFFICE 303 MID |
| 110 | 3RD FLOOR ELEVATOR LOBBY |
| 112 | ELEVATOR #1 SHAFT |
| 113 | ELEVATOR #1 SHAFT |
| 114 | OPEN OFFICE 303 S. |
| 115 | OFFICE 302 |
| 116 | OPEN MEET/ DISP 304 |
| 117 | OFFICE 306 |
| 118 | OFFICE 307 |
| 119 | OFFICE 308 |
| 120 | DUCT DETECTOR 308 |
| 121 | DUCT DETECTOR 308 |
| 122 | STAIR #2 3RD FLOOR |
| 128 | MECH ROOM 105 FACP |
| 129 | RECEPTION 106 |
| 130 | CONFERENCE ROOM 109 |
| 131 | CHIEF FAC, MANGMENT 107 |
| 132 | OPEN OFFICE S. 108 |
| 133 | OPEN OFFICE N. 108 |
| 134 | OFFICE 115 |
| 135 | CORRIDOR 114 |
| 136 | MAIL 118 |
| 137 | OFFICE 117 |
| 138 | OFFICE 116 |
| 139 | OPEN OFFICE 121 |
| 140 | OFFICE 122 |
| 141 | OFFICE 123 |
| 142 | OFFICE 124 |
| 143 | CORRIDOR 131 S. |
| 144 | BREAK ROOM 129 |
| 145 | B+U STORAGE 130 |
| 146 | CORRIDOR 133 W |
| 147 | SECURE STORAGE 134 |
| 148 | SRM LAB 145 |
| 149 | CORRIDOR 133 W. HALL |
| 150 | STAIR 2 1ST FLOOR |
| 151 | CORRIDOR 131 N. |
| 152 | OFFICE 132A |
| 153 | CORRIDOR 133 E |
| 154 | SRM LAB 135 |
| 155 | ELECTRICAL 136 A |
| 156 | IT/ MDF 137 |
| 157 | CORRIDOR 138 |
| 158 | VESTIBULE 138 A |
| 159 | OFFICE 132 |
| 160 | CORRIDOR 132C |
| 161 | VESTIBULE 127A |
| 162 | FOCUS 132B |
| 163 | MES RESTROOM 127 |
| 164 | CAHSE 126A |
| 165 | WOMENS RESETROOM 125 |
| 166 | VESTIBULE 125A |
| 167 | JANITOR 126 |
| 168 | OFFIE 120 |
| 169 | CONFERENCE ROOM 119 |
| 170 | OFFICE 113 |
| 171 | TEL MED 111 |
| 172 | TEL MED 112 |
| 173 | OPEN OFFICE 102 N. |
| 174 | OPEN OFFICE 102 S. |
| 175 | ENROLLMENT ROOM 103A |
| 176 | STAIR #1 1ST FLOOR |
| 177 | ACTIVATION ROOM 103 |
| 178 | LOBBY 104 |
| 179 | COPY/ SUPPLY 110 |
| 180 | 1ST FLOOR ELEVATOR LOBBY |
| 181 | VESTIBULE 100 |
| 182 | ELEVATOR #1 MECH ROOM |
| 190 | OPEN OFFICE 303 |
| 191 | OPEN OFFICE 303 |
| 192 | OPEN OFFICE 309 |
| 193 | OPEN OFFICE 309 |
| 194 | OPEN OFFICE 309 |
| 1 | VEHICLE MAINTENANCE PARTS 155 |
| 2 | VEHICLE MAINT. PARTS 145 |
| 3 | WELDING SHOP 146 |
| 4 | WELDING SHOP 146 |
| 5 | WARM STORAGE 147 |
| 6 | WARM STORAGE 147 |
| 7 | WARM STORAGE 147 |
| 8 | WARM STORAGE 147 |
| 9 | ROAD BAYS 152 |
| 10 | ROAD BAYS 152 |
| 11 | DAMPER 152 |
| 12 | DAMPER 152 |
| 13 | ROAD BAYS 152 |
| 14 | ELEVATOR 2 RECALL/ 2ND RECALL/ HAT FLASH |
| 15 | LOBBY 159 PULLSTATION |
| 16 | ROAD BAYS 152 |
| 17 | DAMPER LAW ENFORCEMENT 155 |
| 18 | DAMPER LAW 155 |
| 19 | LAW ENFORCMENT 155 |
| 20 | LAW ENFORCEMNET 155 |
| 21 | FIRE EMERGENCY VEHICLE 156 |
| 22 | STAIR 4 LEVEL 1 PULL |
| 23 | LAW ENFORCEMENT 157 |
| 24 | LAW ENFOREMCNET 157 |
| 25 | FIRE CACHE 154 |
| 26 | ROADS BAYS FSD |
| 27 | ROAD BAYS 152 |
| 28 | ROAD BAYS 152 |
| 29 | ROAD BAYS 152 |
| 30 | ROAD BAYS 152 |
| 31 | WARM STORAGE 147 |
| 32 | WARM STORAGE 147 |
| 33 | WELDING SHOP 146 |
| 34 | VEHICLE BAY 144 |
| 35 | VEHICLE BAY 144 |
| 36 | VEHICLE BAY 144 |
| 37 | VEHICLE BAY 144 |
| 38 | ELEVATOR 2 RECALL/ PRIMARY RECALL/ SHUNT TRIP |
| 40 | STAIR 3 LEVEL 2 |
| 41 | CORRIDOR 257 |
| 42 | TELE/ MED 256 |
| 43 | JANITOR 258 |
| 44 | OPEN OFFICE 249 |
| 45 | OFFICE 251 |
| 46 | OFFIE 250 |
| 47 | OFFICE 247 |
| 48 | OFFICE 248 |
| 49 | OPEN OFFICE 249 |
| 50 | OFFICE 246 |
| 51 | OFFICE 245 |
| 52 | COPY/ FAX 243 |
| 53 | OPEN OFFICE 249 |
| 54 | OFFICE 242 |
| 55 | ATTIC 240 |
| 56 | CORRIDOR 241 |
| 57 | ATTIC 240 E |
| 58 | ATTIC 240 E |
| 59 | CORRIDOR 241 |
| 60 | ATTIC 240 |
| 61 | ATTIC 240 |
| 62 | ATTIC 240 W |
| 63 | CORRIDOR 241 |
| 64 | ATTIC 240 |
| 65 | ATTIC 240 |
| 66 | ATTIC 240 |
| 67 | WARM STORAGE 147 |
| 68 | ROADS BAY 152 PULLSTATION |
| 69 | EVIDENCE ENT PULL |
| 70 | VEHICLE BAY 144 PULL |
| 71 | WARM STRG 147 PULL |
| 72 | ROADS BAYS 152 PULL |
| 73 | ROADS BAYS 152 PULL |
| 74 | RESTROOM 278 |
| 75 | STAIR 4 LEVEL 2 PULLSTATION |
| 76 | STAIR 4 LEVEL 2 |
| 77 | CORRIDOR 273 |
| 78 | TRAINING ROOM 274 |
| 79 | SMALL CONFERENCE 276 |
| 81 | COY/FAX 270 |
| 82 | RADIO/ ELEC 272 |
| 83 | CORRIDOR 273 |
| 84 | TRAINING ROOM 265 |
| 85 | IT 271 |
| 86 | OFFICE 268 |
| 87 | ARCHIVE STRG 266 |
| 88 | OFFICE 267 |
| 89 | CORRIDOR 263 |
| 90 | CORRIDOR 273 |
| 91 | TRAINING ROOM 265 |
| 92 | CHASE 254 |
| 93 | MENS RESTROOM 253 |
| 94 | FOCUS ROOM 259 |
| 95 | CONFERENCE ROOM 260 |
| 96 | CORRIDOR 257 |
| 97 | CORRIDOR 234 |
| 98 | WOMENS RESTROOM 255 |
| 99 | CORRIDOR 257 |
| 100 | LAW ENFORCEMENT 157 PULLSTATION |
| 103 | ELEVATOR 2 LOBBY 2 |
| 104 | STAIR 3 LEVEL 2 PULLSTATION |
| 105 | NAC 2 TROUBLE NPT |
| 109 | STAIR 4 LEVEL 3 PULLSTATOIN |
| 110 | 315 FAN SHUTDOWN |
| 111 | MECH ROOM 315 PULLSTATION |
| 112 | LAW ENFORECMENT 155 PULLSTATION |
| 113 | ELEVATOR 2 EQUIPMENT RM |
| 114 | STAIR 3 LEVEL 3 PULLSTATION |
| 128 | OFFICE 145A |
| 130 | EVIDENCE 148 |
| 131 | EVIDENCE 148 |
| 132 | JANITOR 150 |
| 133 | RESTROOM 151 |
| 134 | ELEVATOR 2 MECH RM 160 |
| 135 | LOBBY 159 |
| 136 | CLOSET 158 |
| 137 | CORRIDOR 150 |
| 138 | CLOSET 149 |
| 139 | ELEVATOR 2 LOBBY 1 |
| 140 | STAIR 3 LEVEL 1 |
| 141 | STAIR 4 LEVEL 1 |
| 150 | STAIR 3 LEVEL 3 |
| 151 | SEASONAL OFFICE 314 |
| 152 | TELE/ MED 317 |
| 153 | TELE/ MED 318 |
| 154 | MECHANICAL 315 |
| 155 | MECHANICAL 315 |
| 156 | ELEC ROOM 315 |
| 157 | CORRIDOR 319 |
| 158 | STAIR 4 LEVEL 3 |
| 159 | CORRIDOR 319 |
| 160 | SEASONAL OFFICE 314 |
| 161 | VESTIBULE 316 |
| 162 | LOBBY 3RD FLOOR |
| 163 | ELEVATOR 2 TOP OF SHAFT |
| 164 | OPEN OFFICE 313 |
| 165 | OPEN OFFICE 313 |
| 166 | OPEN OFFICE 313 |
| 190 | OPEN OFFICE 244 |
| 191 | OPEN OFFICE 244 |
| 192 | OPEN OFFICE 244 |
| 193 | OPEN OFFICE 252 |
| 194 | OPEN OFFICE 269 |
| 195 | OPEN OFFICE 269 |
| 196 | OPEN OFFICE 269 |
| 197 | OPEN OFFICE 313 |
| 198 | OPEN OFFICE 313 |
| 199 | OPEN OFFICE 313 |
| 200 | LOBBY 3RD FLOOR |
| 201 | SEASONAL OFFICE 314 |
| 202 | CORRIDOR 319 |
| 203 | MECHANICAL 315 |
| 204 | ELEVATOR 2 LOBBY 3 |
| 1 | NAC 1 |
| 2 | NAC 2 |
| Panel location | Helitack Base |
| 1 | Front Entrance Smoke |
| 2 | Base Manager Office Smoke |
| 3 | Operations Room Smoke |
| 4 | Leads Office Smoke |
| 5 | Ready Room Smoke |
| 6 | Ready Room Smoke |
| 7 | Mens Restroom Smoke |
| 8 | Main Hall Smoke |
| 9 | Womens Restroom Smoke |
| 10 | Mech Room Smoke |
| 11 | Exercise Room Smoke |
| 12 | Laundry Room Smoke |
| 13 | Pilot Room Smoke |
| 14 | South Hall Smoke |
| 15 | Break Room Smoke |
| 167 | Front Entrance Pull Station |
| 168 | Ready Room Pull Station |
| 169 | Ready Room Pull Station |
| 170 | Mech Room Pull Station |
| 171 | Exercise Room Pull Station |
| 172 | South Hall Pull Station |
| 173 | Operations Room Pull Station |
| Panel location | Jenny Lake VC |
| 1 | smoke 1 |
| 2 | Smoke 2 |
| 3 | Smoke 3 |
| 4 | Smoke 4 |
| 5 | Pull station 1 |
| 6 | Pull station 2 |
| 7 | Horn strobe 1 |
| 8 | Horn strobe 2 |
| 9 | Horn strobe 3 |
| 10 | Horn strobe 4 |
| 11 | Wireless motion 1 |
| 12 | Wireless motion 2 |
| 13 | Wireless motion 3 |
| 14 | Wireless motion 4 |
| 15 | Wireless door contact 1 |
| 16 | Wireless door contact 2 |
| Panel location | Laurance S Rockefeller Center |
| 1 | FIRE ALARM |
| Smoke detector 1 | |
| Smoke detector 2 | |
| Smoke detector 3 | |
| Smoke detector 4 | |
| Smoke detector 5 | |
| Smoke detector 6 | |
| Smoke detector 7 | |
| Smoke detector 8 | |
| Smoke detector 9 | |
| Smoke detector 10 | |
| Smoke detector 11 | |
| Smoke detector 12 | |
| Smoke detector 13 | |
| Smoke detector 14 | |
| Smoke detector 15 | |
| Smoke detector 16 | |
| Smoke detector 17 | |
| Smoke detector 18 | |
| Smoke detector 19 | |
| Smoke detector 20 | |
| Smoke detector 21 | |
| Smoke detector 22 | |
| Smoke detector 23 | |
| Smoke detector 24 | |
| Smoke detector 25 | |
| Smoke detector 26 | |
| Smoke detector 27 | |
| Smoke detector 28 | |
| Smoke detector 29 | |
| Smoke detector 30 | |
| Smoke detector 31 | |
| Smoke detector 32 | |
| Smoke detector 33 | |
| Heat Detector | |
| Pull station 1 | |
| Pull station 2 | |
| Pull station 3 | |
| Pull staion 4 | |
| Strobe 1 | |
| Strobe 2 | |
| Strobe 3 | |
| Strobe 4 | |
| Strobe 5 | |
| Strobe 6 | |
| Strobe 7 | |
| Strobe 8 | |
| Strobe 9 | |
| 2 | PANIC |
| 3 | DELAY |
| 4 | MOTION |
| 5 | POINT 5 INSTANT ALARM |
| 6 | POINT 6 INSTANT ALARM |
| 7 | POINT 7 INSTANT ALARM |
| 8 | POINT 8 INSTANT ALARM |
| 9 | NOT USED |
| 10 | BASEMENT |
| 11 | ENTRY 101 |
| 12 | NOT USED |
| 13 | A/V ROOM |
| 14 | NOT USED |
| 15 | LOW TEMPERATURE |
| 19 | MOTION |
| Panel location | Noble Way 114, 116, 118, 120 |
| 5 | HEAT DETECTOR 118 / 120 GARAGE |
| 6 | 118 LIVING ROOM SMOKE |
| 7 | 118 KITCHEN SMOKE |
| 8 | 114 KITCHEN SMOKE |
| 9 | 114 LIVING ROOM SMOKE |
| 10 | HEAT DETECTOR 114 / 116 GARAGE |
| 12 | 114 BEDROOM SMOKE |
| 13 | 114 HALLWAY SMOKE |
| 14 | CO DETECTOR 114 |
| 15 | 114 BEDROOM SMOKE |
| 16 | 118 BEDROOM SMOKE |
| 17 | CO DETECTOR 118 |
| 18 | 118 HALLWAY SMOKE |
| 19 | 118 BEDROOM SMOKE |
| 20 | 120 BEDROOM SMOKE |
| 21 | 120 HALLWAY SMOKE |
| 22 | CO DETECTOR 120 |
| 23 | 120 BEDROOM SMOKE |
| 24 | 116 BEDROOM SMOKE |
| 25 | CI DETECTOR 116 |
| 26 | 116 HALLWAY SMOKE |
| 27 | 116 BEDROOM SMOKE |
| 28 | 116 LIVING ROOM |
| 29 | 116 KITCHEN SMOKE |
| 30 | 120 KITCHEN SMOKE |
| 31 | 120 LIVING ROOM SMOKE |
| 33 | HEAT DETECTOR 114 BASEMENT |
| 34 | HEAT DETECTOR 118 BASEMENT |
| 201 | PULLSTATION BETWEEN 118 / 120 FRONT DOOR |
| 202 | WATERFLOW 114 BASEMENT |
| 203 | PULLSTATION 118 / 120 FRONT DOOR |
| 211 | PULLSTATION BETWEEN 114 / 116 FRONT DOOR |
| 233 | 24V SUPPLY IN PANEL |
| Panel location | Noble Way 121, 123, 125, 127 |
| 5 | Heat Detector 125, 127 Garage |
| 6 | Smoke Detector 125 Living Room |
| 7 | Smoke Detector 125 Kitchen |
| 8 | Smoke Detector 121 Kitchen |
| 9 | Smoke Detector 121 Living Room |
| 10 | Heat Detector 121, 123 Garage |
| 12 | Smoke Detector 121 Bedroom |
| 13 | Smoke Detector 121 Hallway |
| 14 | 121 CO Detector |
| 15 | Smoke Detector 121 Bedroom |
| 16 | Smoke Detector 125 Bedroom |
| 17 | 125 CO Detector |
| 18 | Smoke Detector 125 Hallwy |
| 19 | Smoke Detector 125 Bedroom |
| 20 | Smoke Detector 127 Bedroom |
| 21 | Smoke Detector 127 Hallway |
| 22 | 127 CO Detector |
| 23 | Smoke Detector 127 Bedroom |
| 24 | Smoke Detector 123 Bedroom |
| 25 | 123 CO Detector |
| 26 | Smoke Detector 123 Hallway |
| 27 | Smoke Detector 123 Bedroom |
| 28 | Smoke Detector 123 Living Room |
| 29 | Smoke Detector 123 Kitchen |
| 30 | Smoke Detector 127 Kitchen |
| 31 | Smoke Detector 127 Living Room |
| 33 | Heat Detector 121 Basement |
| 34 | Heat Detector 125 Basement |
| 201 | 121 Tamper Basement |
| 202 | Waterflow 121 Basement |
| 203 | Pull Station 125, 127 Front Door |
| 211 | Pull Station 121, 123 Front Door |
| 232 | 24v Sup in Panel |
| Panel location | Porcupine Place 305, 307, 309, 311 |
| 2 | Smoke Detector Above Panel |
| 5 | Heat Detector N Basement Crawlspace |
| 6 | Heat Detector S Basement Crawlspace |
| 7 | Smoke Detector Basement Stairs |
| 8 | Smoke Detector 307 1455B Kitchen |
| 9 | Smoke Detector 305 1455A Kitchen |
| 10 | Smoke Detector 305 1455A Living Room |
| 11 | Smoke Detector 305 1455A Bedroom |
| 12 | CO Detector Apt 305 |
| 13 | Smoke Detector 305 1455A Hallway |
| 14 | Smoke Detector 305 1455A Bedroom |
| 15 | CO Detector Room 110 |
| 16 | Smoke Detector 307 1455B Laundry Room |
| 17 | Smoke Detector 307 1455B Bedroom |
| 18 | Smoke Detector 309 1455C Bedroom |
| 19 | Smoke Detector 309 1455C Laundry Room |
| 21 | Smoke Detector 311 1455D Bedroom |
| 22 | Smoke Detector 311 1455D Bedroom |
| 24 | Smoke Detector 311 1455D Hallway |
| 25 | Smoke Detector 311 1455C Living Room |
| 26 | Smoke Detector 311 1455D Kitchen |
| 27 | Smoke Detector 309 1455C Kitchen |
| 201 | Manual Pull Station Basement |
| 220 | Tamper 309 1455C Hallway |
| 223 | Tamper 311 1455D Hallway |
| 228 | Tamper 24V Sounder Base |
| 229 | Tamper 24v Sounder Base |
| 230 | Waterflow Basement Riser |
| 231 | Tamper Basement Riser |
| Panel location | Porcupine Place 302, 304, 306, 308 |
| 1 | Basement - Mech Room Pull Station |
| 2 | Basement - Mech Room Smoke |
| 3 | Basement - Mech Room Tamper/Water |
| 4 | Basement - Mech Room Tamper |
| 5 | Basement - Storage |
| 6 | Basement - Storage |
| 10 | Apt 306 - Living Smoke |
| 11 | Apt 308 - Kitchen Smoke |
| 13 | Apt 308 - Living Smoke |
| 14 | Apt 308 - CO Detector |
| 15 | Apt 308 - Bedroom Smoke |
| 16 | Apt 308 - Hall Smoke |
| 17 | Apt 308 - Bedroom Smoke |
| 18 | Apt 306 - CO Detector |
| 19 | Apt 306 - Hall Smoke |
| 20 | Apt 306 - Bedroom Smoke |
| 21 | Apt 304 - Bedroom Smoke |
| 22 | Apt 304 - Hall Smoke |
| 23 | Apt 304 - CO Detector |
| 24 | Apt 302 - Bedroom Smoke |
| 25 | Apt 302 - Hall Smoke |
| 26 | Apt 302 - Bedroom Smoke |
| 27 | Apt 302 - CO Detector |
| 28 | Apt 302 - Living Smoke |
| 29 | Apt 302 - Kitchen Smoke |
| 30 | Apt 304 - Living Smoke |
| Panel location | Water Treatment Plant |
| 1 | 100-Fire alarm MDF SMOKE |
| 2 | 100-Fire alarm OFFICE/LAB SMOKE |
| 3 | 100-Fire alarm OFFICE LAB ENT PULL STATION |
| 4 | 100-Fire alarm BATHROOM SMOKE |
| 5 | 100-Fire alarm PROCESS AREA NE SMOKE |
| 6 | 100-Fire alarm PROCESS AREA MID SMOKE |
| 7 | 100-Fire alarm PROCESS AREA NW SMOKE |
| 8 | 100-Fire alarm PROCESS AREA PULL STATION |
| 9 | 100-Fire alarm HEADWORDS PULL STATION ENT |
| 10 | 100-Fire alarm HEADWORKS SMOKES |
| 11 | 100-Fire alarm BLOWER ROOM N SMOKE |
| 12 | 100-Fire alarm BLOWER ROOM S SMOKE |
| 13 | 100-Fire alarm BASEMENT PULL STATION |
| 14 | 100-Fire alarm BASEMENT N SMOKE |
| 15 | 100-Fire alarm BASEMENT S SMOKE |
File details come from the government source that posted it. Updated .