Amendment_1_GRTE_Fire_Inspections_Location_Schedule_2026_Rev_09222026_0001.xlsx
XLSX spreadsheet 22 KB Posted
- Attached to
- GRTE FIRE SUPPRESSION/PANEL INSPECTIONS
- Solicitation number
- 140P1426Q0099
About this file
This is an Amendment 1 location schedule and fire inspection document for Grand Teton National Park (GRTE) that details the facilities requiring annual fire suppression system and fire alarm panel inspections during 2026. The schedule organizes inspections across four days at multiple locations throughout the park, with Day 1 covering Moran area facilities (Moran Entrance Station, Ranger Station, and housing quarters), Day 2 covering South District buildings including Laurance S. Rockefeller Preserve, Granite Entrance Station, White Grass Ranch, and various housing quarters, Day 3 covering Moose housing areas with multiple residential units, and Day 4 covering the Moose headquarters complex including the Craig Thomas Discovery and Visitor Center, Headquarters Building, shops, and warehouse facilities.
The document specifies 67 buildings and structures requiring inspection, with detailed information on square footage, fire suppression system types (primarily wet systems with various pipe diameters ranging from 1" to 6", some antifreeze systems, and dry systems), and sprinkler head counts for each location. Notable facilities include the Headquarters Building with 52,590 square feet and 396 heads, the Craig Thomas DVC with 19,700 square feet and 450 GPM capacity, and various residential quarters and ranger stations. Several locations are noted as having only alarm panels without sprinkler systems (Colter Bay VC, Moose Entrance Station, Helitack Base, Jenny Lake VC, and Water Treatment Plant), and some structures such as seasonal cabins are identified as unmonitored. The schedule also indicates that Brinkerhoff should be removed from scope for option year 1 and beyond, and notes that keys are required for certain facilities.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment_1_GRTE_Fire_Suppression_and_Fire_Panel_Inspection_STATEMENT_OF_WORK_Rev_09222026_0001.docx | DOCX document | |
| Amendment_1_GRTE_Fire_Alarm_Points_List_Rev_09222026_0001.xlsx | XLSX spreadsheet | |
| Amendment_1_Questions_and_Answers_0001.docx | DOCX document | |
| Sol_140P1426Q0099_Amd_0001.pdf | ||
| Sol_140P1426Q0099.pdf | ||
| A04_2026_Repairs_Needed_2025_Deficiency_List.docx | DOCX document | |
| A04_44045721_GRTE_Fire_Suppression_and_Fire_Panel_Inspection_STATEMENT_OF_WORK.docx | DOCX document | |
| A04_44045721_GRTE_Fire_Alarm_Points_List.xlsx | XLSX spreadsheet | |
| B03_Teton_County_2015-5409_Rev_30_08222026.pdf | ||
| A04_44045721_GRTE_Fire_Inspections_Location_Schedule_2026.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Location Details
| Suggested/Example Schedule | |||||
| BUILDINGS | Note | Square Footage | Type of System | HEADS | FIRE PUMP |
| Day 1 | |||||
| Moran | |||||
| Moran Entrance Station | 1017 | 1 1/4" Wet System | 24 | ||
| Moran Ranger Station-SRLC (Snake River Land Company) | 2500 | Dry System | 41 | ||
| Flagg Ranch Housing | |||||
| Quarters 1433 - Duplex | 3122 | 1" Wet System | 12 | ||
| Quarters 1434 - 4 Plex | 3105 | 1 1/4" Wet System | 22 | ||
| North District Buildings | |||||
| Colter Bay Roads Building (614) | 9200 | 6" Wet System | 100 | ||
| Colter Bay B&U Maintenance Shop (608) | 2808 | 6" Dry System | 60 | ||
| Colter Bay Ranger Station (600) | 2160 | Wet System | 25 | ||
| Colter Bay Housing | |||||
| Quarters 1439 - 6 Plex (636-640 White Bark) | 3960 | 2" Wet System | 42 | ||
| Quarters 1440 - 6 Plex (624-628 White Bark) | 3960 | 2" Wet System | 42 | ||
| Quarters 1441 - 4 Plex (616-622 White Bark) | 2988 | 2" Wet System | 22 | ||
| Quarters 1442 - 4 Plex (608-614 White Bark) | 2988 | 2" Wet System | 22 | ||
| Quarters 1443 - 4 Plex (600-606 White Bark) | 2988 | 2" Wet System | 22 | ||
| Quarters 1423 - Single Family House | 1680 | 2" Wet System | 8 | ||
| Quarters 1424 - Single Family House | 1680 | 2" Wet System | 8 | ||
| Quarters 1425 - Single Family House | 1680 | 2" Wet System | 8 | ||
| Quarters 1426 - Single Family House | 1680 | 2" Wet System | 8 | ||
| Quarters 1427 - Single Family House | 1680 | 2" Wet System | 8 | ||
| Quarters 1103 - Seasonal Cabin (not monitored) | 644 | 1" Wet System | 4 | ||
| Quarters 1104 - Seasonal Cabin (not monitored) | 644 | 1" Wet System | 4 | ||
| Colter Bay VC (closes 10/7/23) | NO SPRINKLERS, JUST ALARM PANEL | ||||
| Brinkerhoff (need Keys) | NO SPRINKLERS, JUST ALARM PANEL, Remove from Scope for Option year 1 and beyond | ||||
| Day 2 | |||||
| South District Buildings | |||||
| Laurance S. Rockefeller Preserve | 7573 | 3 " Antifreeze System | 94 | 200 GPM | |
| Granite Entrance Station | 1017 | 1" Wet System | 24 | ||
| White Grass Ranch | |||||
| Hammond Cabin | 1893 | 1 1/2" Antifreeze System | 14 | ||
| Main Cabin | 2941 | 2" Antifreeze System | 22 | ||
| Misc Locations around Moose | |||||
| Quarters 412 4 Lazy F Ranch | 1420 | Wet System | 4 | ||
| Quarters 500 Moulton ( Main house) | 1732 | Wet System | 5 | ||
| Quarters 282 Roy Chambers - Cabin | 224 | Wet System | 2 | ||
| Quarters 283 Roy Chambers - Main Residence | 829 | Wet System | 14 | ||
| Quarters 284 Roy Chambers - Kitchen | 520 | Wet System | 5 | ||
| Quarters 369- Rudd House | 3250 | Wet System | 8 | ||
| Beaver Creek Housing | |||||
| Quarters 1454 - 4 Plex (302-308 Porcupine) | 6492 | 1 1/2" Antifreeze System | 22 | ||
| Quarters 1455 - 4 Plex (305-311 Porcupine) | 6492 | 2 " Antifreeze System | 22 | ||
| Quarters 1446 - Fire Dorm (303 Porcupine) (not monitored) | 3024 | 1 1/2" Wet System | 87 | ||
| Quarters 1447 - Duplex (213 and 215 Pine Marten) | 2144 | 1 1/4" Wet System | 12 | ||
| Other | |||||
| Quarters 1093 - Nichol Springs | 1974 | 1" Wet System | 13 | ||
| Moose Entrance Station | NO SPRINKLERS, JUST ALARM PANEL | ||||
| Helitack Base/Ranger Station | NO SPRINKLERS, JUST ALARM PANEL | ||||
| Jenny Lake VC | NO SPRINKLERS, JUST ALARM PANEL | ||||
| Day 3 | |||||
| Moose Housing | |||||
| Quarters 188 - Duplex (188B has panel for both A and B) (not monitored) | 2144 | 1 1/4" Wet System | 12 | ||
| Quarters 187-D (120 4-Lazy-F Ranch Rd) | 1117 | 1" Wet System | 10 | ||
| Quarters 199 - 4 Plex (121-127 Noble Way) | 6492 | 4" Wet System & 1 1/4" Antifreeze System | 109 | ||
| Quarters 200 - 4 Plex (114-120 Noble Way) | 6492 | 4" Wet System & 1 1/4" Antifreeze System | 109 | ||
| Quarters 164-B (108 Noble Way) | 1296 | 1" Wet System | 13 | ||
| Quarters 194 - 4 Plex (102-108 Burt Dr) | 6492 | 4" Wet System & 1 1/4" Antifreeze System | 109 | ||
| Quarters 195 - 4 Plex (101-107 Burt Dr) | 6492 | 4" Wet System & 1 1/4" Antifreeze System | 109 | ||
| Quarters 196 - 4 Plex (118-124 Carncross) | 6492 | 4" Wet System & 1 1/4" Antifreeze System | 109 | ||
| Quarters 197 - 4 Plex (110-116 Carncross) | 6492 | 4" Wet System & 1 1/4" Antifreeze System | 109 | ||
| Quarters 198 - 4 Plex (102-108 Carncross) | 6492 | 4" Wet System & 1 1/4" Antifreeze System | 109 | ||
| Quarters 201 - (118 Mather Circle) | 1120 | Wet System | 5 | ||
| Quarters 202- (120 Mather Circle) | 1120 | Wet System | 5 | ||
| Quarters 203- (122 Mather Circle) | 535 | Wet System | 4 | ||
| Quarters 204- (124 Mather Circle) | 535 | Wet System | 4 | ||
| Quarters 205- (130 Mather Circle) | 1120 | Wet System | 5 | ||
| Quarters 206- (132 Mather Circle) | 1120 | Wet System | 5 | ||
| Quarters 1093 - Single Family House (GTA Nichol Springs) | Remove, duplicate. | ||||
| Day 4 | |||||
| Moose HQ area | |||||
| Craig Thomas DVC (open 9-5) | Start at 7:00 am | 19700 | 6" Wet System & 4" Antifreeze System | 120 | 450 GPM |
| Headquarters Building | 52590 | 6" Wet System | 396 | ||
| Moose Tornado Alley/IT Shop | 1192 | 4" Wet System | 46 | ||
| Grand Teton Elevator Phone | NO SPRINKLERS, JUST ALARM PANEL | ||||
| Moose Woodwork Shop (HPTC) | 5102 | 3" Antifreeze System | 54 | ||
| GTA Warehouse/Gym | 11331 | 4" Wet System | 100 | ||
| Water Treatment Plant (need keys) | NO SPRINKLERS, JUST ALARM PANEL |