9. 95 pct Mech-Elec-Plumbing Dwgs.pdf

PDF 12 MB Posted

Attached to
127EAW26Q0053 - Kern River Ranger District HVAC
Solicitation number
127EAW26Q0053
Issued by

About this file

This document is a 95% submittal set of construction drawings and specifications for a federal facility project located at 111 Scripps Drive, Sacramento, California, with project number 15.089. The package includes comprehensive electrical, mechanical, plumbing, and fire alarm system designs for both an Administration Building and Warehouse Building, presented at the design development stage.

The electrical scope encompasses a complete power distribution system with utility service connection, main switchboards, distribution panels, and branch circuiting for general purpose and specialized loads including HVAC equipment, lighting, receptacles, and control systems. The design incorporates solar photovoltaic (PV) arrays on both buildings with inverters and combiner boxes, underground and aerial conduit routing with detailed schedules, emergency systems, and EV charging infrastructure. Fire alarm systems include addressable smoke detectors, manual pull stations, notification appliances (strobes and horns), and a central fire alarm control panel with battery backup and remote extender capabilities. Mechanical systems feature variable refrigerant flow (VRF) heat pump systems for both buildings with multiple indoor fan coil units, dedicated outside air units, exhaust fans with occupancy controls, propane gas heater units, and associated ductwork with registers and grilles. Plumbing systems include cold/hot water distribution, sanitary waste and vent piping, gas service for equipment, floor drains, eyewash/safety showers, fire sprinkler risers, and water heater equipment. The drawings contain detailed fixture schedules, equipment schedules, wiring diagrams, and installation details for all systems, with keyed notes and general specifications addressing code compliance, material standards, and construction sequencing requirements.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T

M a

DETAIL DESIGNATION, "A" SIGNIFIES DETAIL, "E1" SIGNIFIES SHEET NUMBER

MECHANICAL EQUIPMENT, CONNECTED BY ELECTRICAL CONTRACTOR

FLAG REFERRING TO NUMBERED NOTE ON SAME SHEET

CONDUIT RISER

INSULATED GREEN GROUND CONDUCTOR

CONDUIT RUN UNDERGROUND OR UNDER FLOOR

CONDUIT RUN CONCEALED IN CEILING OR WALL, SEE NOTE BELOW

HOMERUN TO PANELBOARD OR RESPECTIVE TERMINAL

MAIN SWITCHBOARD

PANELBOARD, SURFACE MOUNTED

PANELBOARD, RECESSED MOUNTED

FLEX CONNECTION TO FIXTURE

JUNCTION BOX, SIZE AS REQUIRED BY CODE

TRANSFORMER

FUSED DISCONNECT SWITCH

DIMMER SWITCH

SWITCH, MOTOR RATED

ALL SWITCHES+48" TO TOP OF BOX, U.O.N.

APPLIES TO "a" IDENT. OUTLETS CONTROLLEDSINGLE POLE SWITCH

INDICATES SIZE OF CONDUIT = ONE AND ONE HALF INCH CONDUIT(1)1-1/2"C

NUMBER WITHIN PARENTHESIS INDICATES QUANTITY OF CONDUITS

3.

NOTES:

A E1

J J

OS WALL MOUNTED OCCUPANCY AUTO-OFF LIGHT SWITCH

CEILING MOUNTED OCCUPANCY SWITCH.

INSTALL PER MANUFACTURER REQUIREMENTS.

CEILING MOUNTED DAY LIGHT SENSOR / OCCUPANCY SENSOR

INSTALL PER MANUFACTURER REQUIREMENTS.

@ 48" AFF TO TOP OF BOX, U.O.N. PLANS

WALL TELEPHONE/DATA OUTLET

WALL DATA OUTLET

WALL TELEPHONE OUTLET

DOUBLE DUPLEX OUTLET, +15" TO BOTTOM OF BOX, U.O.N.

EXISTING WORK SHOWN THE SAME AS NEW EXCEPT LIGHT

& DASHED, UNLESS OTHERWISE NOTED

SYMBOLS LISTABBREVIATION LIST

A AMPERE

AC ALTERNATING CURRENT

AF AMP FRAME

AFCI ARC FAULT CIRCUIT INTERRUPT

AFF ABOVE FINISHED FLOOR

AIC AMPERES INTERRUPTING

CAPACITY

AHJ AUTHORITY HAVING JURISDICTION

AT AMP TRIP SETTING

AS AMP SENSOR

AWG AMERICAN WIRE GAUGE

BC BARE COPPER

BRKR BREAKER

C CONDUIT

CKT CIRCUIT

CLG CEILING

CO CONDUIT ONLY, WITH PULL LINE

CR CONTROLLED RECEPTACLE

CU COPPER

CWP METALLIC COLD WATER PIPE

DC DIRECT CURRENT

DISC DISCONNECT

DP DISTRIBUTION PANEL

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

EOL END OF LINE DEVICE

EQUIP EQUIPMENT

EXIST EXISTING

F FUTURE

FACP FIRE ALARM CONTROL PANEL

FAEP FIRE ALARM EXTENDER PANEL

FTC FIRE ALARM TERMINAL CABINET

GA GAUGE

GFI GROUND FAULT CIRCUIT

INTERRUPT

GND GROUND

GP METALLIC GAS PIPE

HP HORSE POWER

HT HEIGHT

HZ HERTZ

IN INCH

ISC SHORT CIRCUIT CURRENT

(RMS SYMMETRICAL)

J-BOX JUNCTION BOX

KCMIL THOUSAND CIRCULAR MILLS

KVA KILO VOLT AMP

KW KILOWATT

LV LOW VOLTAGE

MCM THOUSAND CIRCULAR MILLS

MECH MECHANICAL

MDP MAIN DISTRIBUTION PANEL

MISC MISCELLANEOUS

MSB MAIN SWITCHBOARD

NIES NOT IN ELECTRICAL SECTION OF

THESE PLANS & SPECS.

P POLE

PB PULL BOX

PFB PROVISION FOR FUTURE BREAKER

W/ MOUNTING HARDWARE

PH, Ø PHASE

PLYWD PLYWOOD

PNL PANEL

PR PAIR

PV PHOTOVOLTAIC

RM ROOM

SW SWITCH

TEL TELEPHONE

TR TELEPHONE ROOM

TTB TELEPHONE TERMINAL BOARD

UCR UNCONTROLLED RECEPTACLE

UG UNDERGROUND

UON UNLESS OTHERWISE NOTED

V VOLTS

WP WEATHERPROOF

W WATT

XFMR TRANSFORMER

1. ADEQUATELY STRAP AND SUPPORT ALL CONDUIT WORK PER NEC. IN

GENERAL, SUPPORT ALL CONDUIT WITHIN THREE FEET (3') OF OUTLET

BOX, CABINET OR PANEL AND MAXIMUM TEN FEET (10') ON CENTER

THEREAFTER.

2. ALL CONDUCTORS INSTALLED IN PANELBOARDS SHALL BE TRAINED,

LACED, AND INSTALLED WITH PHASE TAPE ON ALL CONDUCTORS.

3. LABEL DEVICES ON EACH COVER PLATE IDENTIFYING CIRCUIT AND

PANEL DEVICE IS CONNECTED TO, PER UFC

4. CLEAN ALL EXTERIOR AND INTERIOR SURFACES OF PANELS AND ALL

MATERIAL AND METAL SHAVINGS FROM PANEL AND CABINET INTERIORS.

ALL OPENINGS SHALL BE SEALED AND APPLY TOUCH-UP SPRAY PAINT

WHERE NEEDED.

5. FIELD COORDINATE ALL DEVICE LOCATIONS PRIOR TO ROUGH-IN.

6. CONTRACTOR SHALL PROVIDE ARC FLASH LABELS FOR ELECTRICAL

POWER PANELS INCLUDED IN THE PROJECT SCOPE IN ACCORDANCE

WITH NFPA 70E . REFER TO UFC 3-560-01 FOR ARC FLASH LABEL

REQUIREMENTS.

7. INSTALLATION SHALL COMPLY WITH 2013 NEC 210.4(B) - EACH

MULTIWIRE BRANCH CIRCUIT SHALL BE PROVIDED WITH A MEANS THAT

WILL SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED CONDUCTORS

AT THE POINT WHERE THE BRANCH CIRCUIT ORIGINATES. THEREFORE

ANY CIRCUIT SHARING A COMMON NEUTRAL SHALL BE CAPABLE OF

SIMULTANEOUS DISCONNECT OR DEDICATED NEUTRALS SHALL BE

INSTALLED.

8. SUPPORT ENCLOSURES, BOXES AND CONDUIT INSTALLATIONS PER NEC

314.23 (A) THROUGH (H).

9. SEAL CONDUIT OPENINGS THROUGH WALLS AND CEILINGS. INSTALL

ESCUTCHEON PLATES AT BUILDING INTERIOR. WHERE EQUIPMENT IS

INSTALLED ON THE EXTERIOR WALL, STUB CONDUITS THROUGH WALL

AND SEAL CONDUIT OPENINGS, THEN INSTALL EXTERIOR EQUIPMENT.

ALSO, SEAL AROUND THE PERIMETER EDGE OF THE EQUIPMENT

ENCLOSURE BETWEEN THE ENCLOSURE AND BUILDING.

10. CONDUITS INSTALLED ON ROOF AND BUILDING EXTERIOR SHALL BE

RIGID GALV. STEEL (HEAVY WALL) WITH THREADED FITTINGS. CONDUIT

AND WALL TO BE PAINTED OUT TO MATCH EXTERIOR FINISH.

11. INSTALL 'MECHANICALLY FASTENED' NAMEPLATE ON ALL EQUIPMENT,

WITH DESCRIPTION INDICATED ON DRAWINGS. NAMEPLATES SHALL

READ EXACTLY AS DESCRIBED ON THE DRAWINGS. IN GENERAL

NAMEPLATE LETTERING SIZE SHALL BE 3/16" HIGH FOR ALL NAMEPLATES

SERVING FEEDER AND BRANCH CIRCUIT BREAKERS. ON MAIN SERVICE

PANEL, DISTRIBUTION PANELS AND ALL OTHER NAMEPLATES LETTERING

SHALL BE 1/4" HIGH.

12. COORDINATE EQUIPMENT LOCATIONS, CONTROL AND POWER WIRING

REQUIREMENTS AND CONNECTION POINTS WITH ALL APPLICABLE

DISCIPLINES.

13. FUSES SHALL BE PROVIDED AND INSTALLED AS PER UNIT NAMEPLATE

DATA ON THE EQUIPMENT PROVIDED. PROVIDE (3) SPARE FUSES OF

EACH TYPE PROVIDED FOR EQUIPMENT.

14. VERIFY CEILING TYPES PRIOR TO ORDERING LUMINAIRES. CONFIRM

THAT FEATURES DESCRIBED IN THE SPECIFICATION OF THE LUMINAIRE

ARE INCLUDED AS WELL AS PART NUMBERS LISTED ON SCHEDULE IN

THE SUBMITTAL PACKAGE. NOTED DISCREPANCIES SHALL BE CLARIFIED

WITH CONTRACTING OFFICER PRIOR TO BID.

15. A LAMINATED COPY OF THE FINAL RECORD ONE LINE DIAGRAM SHALL BE

PLACED IN ELECTRICAL ROOM.

16. WIRING DEVICES AND COVER PLATES SHALL BE PROVIDED IN COLOR

SELECTED BY ARCHITECT. THE COLOR OF THE WIRING DEVICE AND

COVER PLATE SHALL BE THE SAME. U.O.N.

17. FOR ROOF PENETRATIONS, REFER TO ARCHITECTURAL PLANS FOR

INSTALLATION REQUIREMENTS.

18. FOR WALL PENETRATION INSTALLATIONS, REFER TO ARCHITECTURAL

PLANS FOR REQUIREMENTS.

19. DRAWINGS ARE TO BE CONSIDERED DIAGRAMMATIC. CONTRACTOR

SHALL ACCEPT RESPONSIBILITY IN FAMILIARIZING THEMSELVES WITH

ARCHITECTURAL AND STRUCTURAL CONDITIONS ALONG WITH INHERENT

SPACE LIMITATIONS. WITH THAT UNDERSTANDING. ALL ELECTRICAL

WORK AND MATERIAL IS NEW AND SHALL BE PROVIDED BY THE

CONTRACTOR UNLESS OTHERWISE INDICATED.

20. ALL GENERAL PURPOSE AND CONVENIENCE OUTLETS SHALL BE

SPECIFICATION GRADE 120V 20A DUPLEX. PROVIDE GFI AND AFCI

PROTECTION IN ACCORDANCE WITH NFPA 70.

1. ELECTRICAL & MECHANICAL EQUIPMENT SHALL

BE ANCHORED OR BRACED TO MEET

HORIZONTAL AND DISPLACEMENT

REQUIREMENTS PRESCRIBED IN THE CURRENT

IBC.

2. ALL PERMANENTLY MOUNTED EQUIPMENT AND

COMPONENTS.

3. TEMPORARY OR MOVEABLE EQUIPMENT THAT

IS PERMANENTLY ATTACHED TO THE BUILDING

UTILITY SERVICES SUCH AS ELECTRICITY, GAS

OR WATER.

4. MOVEABLE EQUIPMENT WHICH IS STATIONED IN

ONE PLACE FOR MORE THAN 8 HOURS AND

HEAVIER THAN 400lbs. ARE REQUIRED TO BE

ANCHORED WITH TEMPORARY ATTACHMENTS.

THE ATTACHMENT OF THE FOLLOWING ELECTRICAL

AND MECHANICAL COMPONENTS SHALL BE POSITIVELY

ATTACHED TO THE STRUCTURE, BUT NEED NOT BE

DETAILED ON THE PLANS. THESE COMPONENTS SHALL

HAVE FLEXIBLE CONNECTIONS PROVIDED BETWEEN

THE COMPONENT AND ASSOCIATED DUCTWORK,

PIPING, AND CONDUIT:

A. COMPONENTS WEIGHTING LESS THAN 400

POUNDS AND HAVEING A CENTER OF MASS

LOCATED 4 FEET OR LESS ABOVE THE

ADJACENT FLOOR OR ROOF LEVEL THAT

DIRECTLY SUPPORTS THE COMPONENT.

B. COMPONENTS WEIGHTING LESS THAN 20

POUNDS OR IN THE CASE OF DISTRIBUTED

SYSTEMS, LESS THAN 5 POUNDS PER FOOT,

WHICH ARE SUSPENDED FROM A ROOF OR

FLOOR OR HUNG FROM A WALL.

FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS

ON THE APPROVED DRAWINGS, THE INSTALLATION

SHALL BE SUBJECT TO THE APPROVAL OF THE

CONTRACTING OFFICER. THE PROJECT INSPECTOR

WILL VERIFY THAT ALL COMPONENTS AND EQUIPMENT

HAVE BEEN ANCHORED IN ACCORDANCE WITH ABOVE

REQUIREMENTS.

1. PIPING, DUCTWORK, AND ELECTRICAL

DISTRIBUTION SYSTEMS SHALL COMPLY WITH THE

FORCES AND DISPLACEMENT PRESCRIBED IN

ASCE 7-10 SECTION 13.6 AND IBC, SECTIONS

1616A.1.23 AND 1616A.1.26.

2. THE BRACING AND ATTACHMENTS TO THE

STRUCTURE SHALL BE DETAILED ON THE

APPROVED PLANS TO SATISFY ANCHORAGE

REQUIREMENTS OF ACI 318, APPENDIX D.

3. COPIES OF THE MANUAL SHALL BE AVAILABLE ON

THE JOB SITE PRIOR TO THE START OF HANGING

AND BRACING OF THE PIPE, DUCTWORK, AND

ELECTRICAL DISTRIBUTION SYSTEMS.

4. THE CONTRACTING OFFICER SHALL BE

CONSULTED AS TO THE ADEQUACY OF THE

STRUCTURE TO SUPPORT HANGER AND BRACE

LOADS.

MINIMUM 20A BRANCH CIRCUIT CU CONDUCTOR SIZES SHALL BE ACCORDING TO

BRANCH CIRCUIT VOLT DROP CONDUCTOR LENGTH CHART, BASED UPON

MEASURED FIELD ROUTING LENGTHS. MINIMUM CONDUIT SIZE SHALL BE

INCREASED TO ACCOMMODATE MAXIMUM 40% CONDUIT FILL INCLUDING ALL

CONDUCTORS. WHERE NECESSARY, PROVIDE A JUNCTION BOX AT ACCESSIBLE

CEILING SPACE TO CONVERT THE LAST 15 FEET MAX OF CONDUCTORS TO #10 AWG

TO ACCOMMODATE TERMINATION OF WIRING DEVICES, LIGHTING FIXTURES,

CIRCUIT BREAKER, ETC.

NO CROSSBARS ON CONDUIT RUN INDICATES MINIMUM 3/4" CONDUIT, TWO

#12 CU CONDUCTORS. CROSSBARS INDICATE NUMBER OF #12 CU

CONDUCTORS IN CONDUIT. CONDUCTOR SIZES OTHER THAN #12 NOTED

ON DRAWINGS. INCREASE CONDUIT SIZE AS REQUIRED TO ACCOMMODATE

N.E.C. WIRE FILL REQUIREMENTS. INCLUDE ADDITIONAL BOND WIRE IN ALL

PVC AND FLEXIBLE CONDUIT. LONG CROSSBAR INDICATES NEUTRAL

CONDUCTOR, SHORT CROSSBARS INDICATE PHASE CONDUCTORS.

BRANCH CIRCUIT VOLT DROP CONDUCTOR LENGTH CHART

LOAD IN

VOLT AMPERES

LENGTH OF CONDUCTOR

WIRE SIZE IN (GAUGE)

12 10 8 6 4 1200 109 180 271 417 632 1560 84 138 208 321 486 1800 73 120 180 278 421 1920 68 112 169 261 395 2340 x 92 138 214 324 2880 x 75 112 174 263 3000 x 72 108 167 253 3900 x x 83 128 194 4800 x x 67 104 158

NOTES:

1. THIS CHART FOR COPPER CONDUCTORS ONLY.

2. THIS CHART ASSUMES AN 80% POWER FACTOR AND STEEL

RACEWAYS.

3. MAXIMUM LENGTH OF CONDUCTOR FOR LESS THAN 3%

VOLTAGE DROP AT GIVEN VA LOAD.

4. USE WIRE SIZE FROM THIS CHART UNLESS OTHERWISE

NOTED ON THE DRAWINGS.

5. FOR VA VALUES NOT SHOWN USE NEXT HIGHEST VALUE

FROM THE CHART

DEDICATED EQUIPMENT OUTLET. COORDINATE WITH EQUIPMENT

MANUFACTURER FOR REQUIREMENTS PRIOR TO ROUGH-IN.

DUPLEX CONVENIENCE OUTLET, +15" TO BOTTOM OF COVER PLATE, U.O.N., OR

AS NOTED. "A" ADJACENT TO OUTLET INDICATES MOUNTED ABOVE COUNTER.

APPLIES TO ALL PLUG IN RECEPTACLES.

INSTALL CU GROUND CONDUCTOR IN ALL BRANCH CIRCUIT CONDUIT CONDUCTOR

PATHWAYS.

FEEDER TAG / CALLOUTXX-XX

21. VERIFY ROOF DETAILS FOR MOUNTING, ATTACHMENT AND LOADING ON

STANDING BEAM METAL ROOF WITH CONTRACTING OFFICER.

22. ALL WORK SHALL BE DONE IN COMPLIANCE WITH THE ELECTRICAL

SAFETY REQUIREMENTS CONTAINED IN UFC-3-560-01 FOR GOVERNMENT

WORKERS AND EM385-1 FOR CONTRACT WORK.

r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E E

LE

C T R

IC

A L S Y M B O

LS

A N D

N O T E S .d w g 1/

:5 :1 P M jm o b e rl y, 1:

number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

95% SUBMITTAL

.0

E

LE

C

TR

IC

A

L S

Y M

B O

LS

A

N D

N O

TE

S number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

B U

IL

D

IN

G

LI

G

H

TI

N G

F

IX

TU

R

E S

C H

ED

U

LE

r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E

LI

G H T

IN

G

F

IX

T U R E

S C H E D U

LE

.d w g 1/

:5 :1

P M jm o b e rl y, 1:

WAREHOUSE

SWITCHBOARD

PATIO

ADDITIVE

BID ITEM #1

ADMINISTRATION

BUILDING

WAREHOUSE

PATIO

XFMR 'T-A'

CATV U.G. P.B.

TELEPHONE U.G. P.B.

XFMR 'T-W'

TELEPHONE

U.G. P.B.

CATV U.G. P.B.

SEE E130 FOR

ELECTRICAL

EQUIPMENT LAYOUT

NOT IN BASE BID

EV1

EV2

UGD-W

UGP-W

UGT-W

UGTV-W

UGEV1

UG-XW

TO WP-14

UG-G

WP

GFI

(E) UTILITY POLE

MS

SLA

WM-11,13

UGEV2

SLG

UGLC

UG-M

UGS-W

r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E E

LE

C T R

IC

A L S

IT

E

P

LA

N

P O W E R .d w g 1/

:5 :2

P M jm o b e rl y, 1:

0 2' 4' 8' A1 E101

ELECTRICAL SITE PLAN

SCALE: 1" = 30'

number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

E

LE

C

TR

IC

A

L S

IT

E

P

LA

N

PO

W

ER

KEYED NOTES:

SEE E103 & E401 FOR ELECTRICAL ROOM AND TR DETAILS.

PEDESTAL E.V. CHARGING STATION FOR (2) STATIONS. SEE DETAILS

B1/E502.

SEE DRAWING ES-101 FOR EXACT LOCATION OF ELECTRICAL PULL BOX AND

TRANSFORMER.

SEE DRAWING ES-101 FOR EXACT LOCATION OF TELEPHONE PULL BOX.

SEE DRAWING ES-101 FOR EXACT LOCATION OF CATV.

NEW UNDERGROUND TELEPHONE AND CABLE TV SERVICE FEEDERS IN

COMMON TRENCH. WORK TO BE INSTALLED PER DETAIL C2/E503.

NEW ROADWAY RATED N-36 PULLBOX WITH ROADWAY RATED LID WITH

"TELEPHONE" LABEL IN THE CENTER OF LID. CONTRACTOR TO SUPPLY AND

INSTALL PER DETAIL C2/E503.

NEW ROADWAY RATED N-24 PULLBOX WITH ROADWAY RATED LID WITH

"CABLE T.V." LABEL IN THE CENTER OF LID. CONTRACTOR TO SUPPLY AND

INSTALL PER DETAIL C2/E503.

NEW ROADWAY RATED N-24 PULLBOX WITH ROADWAY RATED LID WITH

"ELECTRICAL" LABEL IN THE CENTER OF LID. CONTRACTOR TO SUPPLY AND

INSTALL TRANSFORMER CONCRETE PAD PER DETAIL C2/E503.

MONUMENT SIGN. SEE DETAIL A1/E202.

LIGHTING TO BE INSTALLED WITHIN LOCKABLE DISPLAY CABINETS ON

KIOSK. SEE LUMINAIRE SCHEDULE FOR TYPE. INSTALL PER

MANUFACTURER'S RECOMMENDATIONS. COORDINATE WITH LANDSCAPE

DRAWINGS.

PROVIDE U.G. POWER CONNECTION FOR ACCESS CONTROL, GATE

OPERATOR, GATE MOTOR, AND SERVICE RECEPTACLE WITH IN USE COVER

IF MOUNTED EXTERNAL TO THE GATE MOTOR PROTECTIVE HOUSING.

COORDINATE EXACT LOCATION, WIRING AND MOTOR SIZING PRIOR TO

ROUGH-IN.

SEE E106 FOR CIRCUITING.

SHEET NOTES:

1. SEE SHEET E102 FOR PARKING AND AREA LIGHTING SITE PLAN.

2. FOR CONDUIT AND CONDUCTOR DETAILS, SEE SCHEDULE ON

SHEET E6.05.

3. SIGNAL, DATA, CONTROL WIRING REQUIRED BETWEEN ADMIN

AND WAREHOUSE SHALL BE ROUTED THROUGH "TELEPHONE"

U.G. PULL BOXES THROUGH DEDICATED RACEWAYS.

4. SEE SITE LIGHTING E102 FOR FIXTURE TYPE AND CIRCUITING.

5. CAP AND SEAL ALL UNUSED CONDUIT.

6. POWER FOR BREAK ROOM PATIO LIGHTING FROM BUILDING

DIRECTLY.

7. MINIMIZE THE USE OF PULL BOXES FOR SITE LIGHTING. UTILIZE

FIXTURE HOUSING AND POLE HAND HOLES FOR SPLICES. FOR

WIRES THAT PASS THROUGH, PULL A CONTINUOUS RUN, NO

SPLICES.

SITE SYMBOLS LIST

LIGHTING POLE BASE WITH CONDUIT IN/OUT POURED

IN PLACE. SPLICE POINT INSIDE POLE HAND HOLE.

BOLLARD LIGHT BASE PAD WITH CONDUIT IN/OUT

POURED IN PLACE. SPLICE POINT INSIDE FIXTURE

HOUSING.

SEE SHADE STRUCTURE LIGHT DETAIL _/E202.

MONUMENT SIGN. PROVIDE CONCRETE PAD FOR

FIXTURE MOUNTING.MS

EV

ELECTRIC VEHICLE LEVEL 2 CHARGING STATION DOUBLE

PEDESTAL, 208V, 1PH, 30A, 2 CONNECTORS. RFID

INTEGRAL 6KV SURGE PROTECTION, CAT6 ETHERNET

CONNECTION FOR TCP/IP COMMUNICATIONS.

PATIO

ADDITIVE

BID ITEM #1

ADMINISTRATION

BUILDING

WAREHOUSE

PATIO

12 12

121212

10 10

SL-2,4,6,8,10,12

+ 6 CONTROL

SL-1,3,5,7

+ 4 CONTROL

KIOSK

LIGHTING

P.O.C.

r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E

E

LE

C T R

IC

A L S

IT

E

P

LA

LI

G H T

IN

G .d w g 1/

:5 :2

P M jm o b e rl y, 1:

number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

E

LE

C

TR

IC

A

L S

IT

E

P

LA

N

LI

G

H

TI

N G

0 2' 4' 8' A1 E102

ELECTRICAL SITE PLAN - LIGHTING

SCALE: 1" = 30'

SITE SYMBOLS LIST

POLE MOUNT AREA LIGHT FIXTURE.

BOLLARD TYPE LIGHT FIXTURE.

COLUMN MOUNTED SPOT/FILL LIGHTING FIXTURE.

MONUMENT SIGN LIGHT FIXTURE.MS

G

N

P

N

P

C

C

G- GROUND

N- NEUTRAL

P- PHASE

C- CONTROL

A

2345678

C

E

F

H

G

B

D

G

H

EVIDENCE

STORAGE

201 SF

DEPUTY

DISTRICT

RANGER

136 SF

ELEC

110 SF

TELECOM

101 SF

LAW

ENFORCEMENT

361 SF

MAP / COPY / SUPPLY

399 SF

BREAKROOM

295 SF

PUBLIC

AFFAIRS

356 SF

MAIL

92 SF

RECEPTION

182 SF

LOBBY

329 SF

M

239 SF

W

253 SF

JAN

33 SF

SMALL

CONF

166 SF

W

56 SF

M

56 SF

HALL

88 SF

FIRE MANAGEMENT

1,022 SFDFMO

125 SF

FSR

12 SF

D W

R E

F.

C O

U N

TE

R

D

IS

P

LA

Y

RETAIL

P

LO

TT

E

R

HALL

347 SF

HALL

103 SF

STORAGE

123A

40 SF

POC

POC

POC

POC

T-A P.B.

WP

GFI

+108" POC

WP

GFI

A

GFI

A

GFI

GFI

AA

A

A

A

A

A

GFI

A

GFI

AA

A

A A

A

A

GFI

A

GFI

WP

GFI

TO UTILITY SERVICE

TRANSFORMER

WP

GFI

WP

GFI

WP

GFI

WP

GFI

WP

GFI

AP1-11

AP2-13,15,17

PC2-17

AP2-1,3,5

PC2-5

AP2-7,9,11

PC2-9

WP

GFI

WP

GFI

10 10

AP1-10,12,14

19 19

23 AP1-19,21,23

T.V.

AP1-2,16,18 AP1-20,22,24

PC1-20,22

9 9 7

9 A 7 9

A 7

AP1-7,9

AP1-15

A

5 3

AP1-3,5

PC1-1

AP1-1

AP2-2,4,6

PC2-2,4

PC2-8

AP2-8,10

A A

AP2-19,21,23

PC2-23

WP

GFI

U.G. P.B.

TEL

U.G. P.B.

CATV

WP

GFIWP

GFI

AP1-17

UGLC

AP1-6

A A

+44"

GWH

AP2-22

AP2-

20,21,23

AP1-13

GFI

AP1-25

6 6

A

A

A

A

A

A

2 A

AP1-4

WP

GFI

AP1-8

WP

GFI

number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

A D

M

IN

IS

TR

A

TI

O N

B U

IL

D

IN

G

FL

O

O R

P

LA

N

P O

W

ER

B A

S E

B

ID

0 4' 8' 16' A1 E103

FLOOR PLAN - ADMINISTRATION - POWER - BASE BID

SCALE: 1/8" = 1'-0"

SHEET NOTES:

1. PROVIDE EXTERIOR MOUNTED RECEPTACLES WITH IN-USE,

ALL WEATHER DEVICE COVERS.

2. PROVIDE MINIMUM OF 12 INCH SEPARATION FOR

RECEPTACLES THAT ARE BACK TO BACK ON A COMMON WALL.

3. CONTROLLED RECEPTACLES (CR) AND UNCONTROLLED

RECEPTACLES (UCR), ARE REQUIRED TO BE PROVIDED IN

PRIVATE OFFICE AND OPEN OFFICE SPACE.

-MINIMUM (1) CR WITHIN 6 FEET OF EACH UCR OR AS SPLIT

RECEPTACLES.

-CR SHALL HAVE PERMANENT MARKING.

C2 E103

WITH CONTROLLED RECEPTS.

SCALE: NONE

X-1,3,5

PCI-1,3

PANEL X, CKT 1,3,5 WITH PLUG

CONTROL RELAY PCI-1,3.

SEE TYPICAL DETAILS FOR SPACE

TYPE FOR CIRCUITING DETAILS.

TYP. HOMERUN EXAMPLE

C3 E103

LOW VOLTAGE INSTALLATION DETAIL

SCALE: NONE

RECESSED MONITOR POWER/

PROVIDE RECESSED POWER/

LOW VOLTAGE CONNECTION

BOX AT +60" A.F.F. ON CENTER.

DEDICATED HOMERUN

POWERED FROM CIRCUIT FOR

GENERAL RECEPTACLES.

2" IN WALL PATHWAY ONLY FOR

CABLING. PROVIDE WITH DOUBLE

GANG MUD RING AND BLANK

COVER PLATE. MATCH

RECEPTACLE HEIGHT ON CENTER

KEYED NOTES:

JUNCTION BOX UNDER SINK WITH MOTOR RATED

DISCONNECT SWITCH FOR HARDWIRED GARBAGE

DISPOSAL WITH TOGGLE SWITCH LOCATED ABOVE

COUNTER.

JUNCTION BOX FOR HARD WIRED DISHWASHER.

SEE BREAK ROOM COUNTER ELEVATION B3/E201.

VERIFY POWER AND SIGNAL REQUIREMENTS FOR

PLOTTER PRIOR TO ROUGH-IN.

SEE ENLARGED FLOOR PLAN E401

U.G. PULL BOX FOR BRANCH DISTRIBUTION FROM TR 104

TO U.G. PULL BOX AT WAREHOUSE FOR WAREHOUSE

P.O.C.

STEP UP TRANSFORMER PRIMARY 208/120V AC FROM

MSB SECONDARY 480V CU WINDINGS 12.5KVA, 60HZ,

150°C, ENERGY STAR, NEMA 3 WITH SCREENED

VENTILATION. REVERSE FEED CAPABLE WITH

WEATHERSHIELD.

U.G. TO WAREHOUSE BUILDING, SEE SHEET E101.

PROVIDE WP, GFI CONVENIENCE RECEPTACLE WITH IN

USE COVER FOR MECHANICAL EQUIPMENT.

P.O.C. FOR POWER AND SIGNAL TO CUSTOM CABINET

AND COUNTER. COORDINATE WITH ARCHITECT PRIOR

TO PUTTING OUT TO BID.

P.O.C. FOR FURNITURE SYSTEMS. SEE DETAIL A1/E608.

PROVIDE EXTENSION RINGS FOR RECEPTACLES FOR

MIN. 1 LAYER OF GWB OVER PLYWOOD. SEE

ARCHITECTURAL PLANS FOR DETAILS. INSTALL

RECEPTACLES IN ACCESSIBLE LOCATION, IE, BETWEEN

SET SHELF HEIGHTS OR ABOVE FILE CABINETS.

PROVIDE ONE ACCESSIBLE RECEPTACLE AT +15" TO

BOTTOM OF RECEPTACLE.

SEE ELECTRICAL ROOM LAYOUT B3/E401.

PROVIDE COMPUTER MONITOR POWER AND DATA BOX

PER DETAIL C3/E104.

B3 E401

B3 E201

B3 E401 r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E

F

LO

O R

P

LA

N

A D M

IN

W E R

B A S E

B

ID

.d w g 1/

:5 :2

P M jm o b e rl y, 23456789101112

C

E

F

H

G

RECREATION

/ LAND

USE /

ARCHAEOLOGY

781SF

EVIDENCE

STORAGE

201 SFREC / LAND/

MIN

OFFICER

122 SF

DEPUTY

DISTRICT

RANGER

136 SF

ELEC

110 SF

TELECOM

101 SF

LAW

ENFORCEMENT

361 SF

MAP / COPY / SUPPLY

399 SF

BREAKROOM

295 SF

PUBLIC

AFFAIRS

356 SF

MAIL

92 SF

RECEPTION

182 SF

LOBBY

329 SF

M

239 SF

W

253 SF

JAN

33 SF

SMALL

CONF

127 SF

W

56 SF

M

56 SF

HALL

88 SF

PUBLIC

MEETING

792 SF

NAT.

RESOURCES

711 SF

FIRE MANAGEMENT

1,022 SF

ECOSYSTEM

734SF

ECO STAFF

OFFICER

126 SF

DISTRICT

RANGER

215 SF

DFMO

125 SF

ADMIN

SUPPORT

519 SF

ECOSYSTEM

/ PLANNING

STORAGE

122 SF

D W

R E

F.

C O

U N

TE

R

D

IS

P

LA

Y

RETAIL

P

LO

TT

E

R

HALL

392 SF

HALL

103 SF

FSR

12 SF

POC

POC

POC

POC

T-A P.B.

WP

GFI

POC POCPOC POC

+108" POC

WP

GFI

A

GFI

A

GFI

GFI

AAA

A

A

A

A

GFI

A

GFI

AA

A

A A

A

A

GFI

A

GFI

POC

POC

POC

WP

GFI

TO UTILITY SERVICE

TRANSFORMER

WP

GFI

WP

GFI

WP

GFI

WP

GFI

WP

GFI

AP1-11

AP2-13,15,17

PC2-17

AP2-1,3,5

PC2-5

AP2-7,9,11

PC2-9

AP3-7,9,11

PC3-9

AP3-1,3,5

WP

GFI

WP

GFI

POC

AP3-19,21,23

PC3-19

AP3-20,22,24

PC3-22

AP3-8,10,12

AP3-16,18

PC3-16,18

WP

GFI

8 8

WP

GFI

WP

GFI

30 28

30 AP3-28,30

10 10

AP1-10,12,14

19 19

AP1-25,27

PC1-25,27

25 21

23 AP1-19,21,23

T.V.

AP1-2,16,18 AP1-20,22,24

PC1-20,22

9 9 7

9 A 7 9

A 7

AP1-7,9

AP1-15

A

5 3

AP1-3,5

PC1-1

AP1-1

AP2-2,4,6

PC2-2,4

PC2-8

AP2-8,10

A A

AP2-19,21,23

PC2-23

WP

GFI

U.G. P.B.

TEL

U.G. P.B.

CATV

WP

GFIWP

GFI

AP1-17

UGLC

AP1-6

A A

+44"

GWH

AP2-22

AP2-

20,21,23

AP1-13

GFI

AP1-25

6 6

A

A

A

A

A

A

2 A

AP1-4

AP2-25

AP3-2,4,6

PC3-1PC3-2

AP3-13,15,17

PC3-15

AP3-26

PC3-10

AP3-25,27,29

PC3-27

AP1-8

0 4' 8' 16' A1 E104

FLOOR PLAN - ADMINISTRATION - POWER - BASE BID & ALTERNATE

SCALE: 1/8" = 1'-0"

number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

A D

M

IN

IS

TR

A

TI

O N

B U

IL

D

IN

G

FL

O

O R

P

LA

N

PO

W

ER

B

A S

E B

ID

A

LT

E R

N

AT

E

B3 E401

B3 E201

B3 E401

KEYED NOTES:

JUNCTION BOX UNDER SINK WITH MOTOR RATED

DISCONNECT SWITCH FOR HARDWIRED GARBAGE

DISPOSAL WITH TOGGLE SWITCH LOCATED ABOVE

COUNTER.

JUNCTION BOX FOR HARD WIRED DISHWASHER.

SEE BREAK ROOM COUNTER ELEVATION B3/E201.

VERIFY POWER AND SIGNAL REQUIREMENTS FOR

PLOTTER PRIOR TO ROUGH-IN.

SEE ENLARGED FLOOR PLAN E401

U.G. PULL BOX FOR BRANCH DISTRIBUTION FROM TR 104

TO U.G. PULL BOX AT WAREHOUSE FOR WAREHOUSE

P.O.C.

STEP UP TRANSFORMER PRIMARY 208/120V AC FROM

MSB SECONDARY 480V CU WINDINGS 12.5KVA, 60HZ,

150°C, ENERGY STAR, NEMA 3 WITH SCREENED

VENTILATION. REVERSE FEED CAPABLE WITH

WEATHERSHIELD.

U.G. TO WAREHOUSE BUILDING, SEE SHEET E101.

PROVIDE WP, GFI CONVENIENCE RECEPTACLE WITH IN

USE COVER FOR MECHANICAL EQUIPMENT.

P.O.C. FOR POWER AND SIGNAL TO CUSTOM CABINET

AND COUNTER. COORDINATE WITH ARCHITECT PRIOR

TO PUTTING OUT TO BID.

P.O.C. FOR FURNITURE SYSTEMS. SEE DETAIL A1/E608.

PROVIDE EXTENSION RINGS FOR RECEPTACLES FOR

MIN. 1 LAYER OF GWB OVER PLYWOOD. SEE

ARCHITECTURAL PLANS FOR DETAILS. INSTALL

RECEPTACLES IN ACCESSIBLE LOCATION, IE, BETWEEN

SET SHELF HEIGHTS OR ABOVE FILE CABINETS.

PROVIDE ONE ACCESSIBLE RECEPTACLE AT +15" TO

BOTTOM OF RECEPTACLE.

SEE ELECTRICAL ROOM LAYOUT B3/E401.

PROVIDE COMPUTER MONITOR POWER AND DATA BOX

PER DETAIL C3/E104.

SHEET NOTES:

1. PROVIDE EXTERIOR MOUNTED RECEPTACLES WITH IN-USE,

ALL WEATHER DEVICE COVERS.

2. PROVIDE MINIMUM OF 12 INCH SEPARATION FOR

RECEPTACLES THAT ARE BACK TO BACK ON A COMMON WALL.

3. CONTROLLED RECEPTACLES (CR) AND UNCONTROLLED

RECEPTACLES (UCR), ARE REQUIRED TO BE PROVIDED IN

PRIVATE OFFICE AND OPEN OFFICE SPACE.

-MINIMUM (1) CR WITHIN 6 FEET OF EACH UCR OR AS SPLIT

RECEPTACLES.

-CR SHALL HAVE PERMANENT MARKING.

C2 E104

WITH CONTROLLED RECEPTS.

SCALE: NONE

X-1,3,5

PCI-1,3

PANEL X, CKT 1,3,5 WITH PLUG

CONTROL RELAY PCI-1,3.

SEE TYPICAL DETAILS FOR SPACE

TYPE FOR CIRCUITING DETAILS.

TYP. HOMERUN EXAMPLE

C3 E104

LOW VOLTAGE INSTALLATION DETAIL

SCALE: NONE

RECESSED MONITOR POWER/

PROVIDE RECESSED POWER/

LOW VOLTAGE CONNECTION

BOX AT +60" A.F.F. ON CENTER.

DEDICATED HOMERUN

POWERED FROM CIRCUIT FOR

GENERAL RECEPTACLES.

2" IN WALL PATHWAY ONLY FOR

CABLING. PROVIDE WITH DOUBLE

GANG MUD RING AND BLANK

COVER PLATE. MATCH

RECEPTACLE HEIGHT ON CENTER

r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E

F

LO

O R

P

LA

N

A D M

IN

P O W E R

B A S E

B

ID

A

LT

E R N A T E .d w g 1/

:5 :3

P M jm o b e rl y, 2345678

C

E

F

H

G

B

D

G

H

PROVIDE STACKED

OVER/UNDER MOUNTING.

20A, 208V, 1PH, 60HZ, NEMA

3R DISCONNECT SWITCHES,

WALL MOUNTED.

AM-19,21

AM-22,24

m m m m

AM-2,4

m

AM-18

m m m m

AM-5,7

m

AM-1,3

AM-16

m mm mm AM-10,12 m m m m

AM-14

m

AM-37,39,41

PROVIDE NEMA 3R 15A, 208V,

3PH, 60HZ, WALL MOUNTED

DISCONNECT SWITCH.

EVIDENCE

STORAGE

DEPUTY

DISTRICT

RANGER

ELEC

TELECOM

LAW

ENFORCEMENT

MAP / COPY /

SUPPLY

BREAKROOM

PUBLIC

AFFAIRS

MAIL

RECEPTION

LOBBY

M

W

JAN

FIRE

MANAGEMENT

DFMO

FSR

HALL

HALL

W

M

STORAGE

123A

HALL

A123

AM-16

AM-13,15,17

15A 70A

#4 number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

A D

M

IN

IS

TR

A

TI

O N

B U

IL

D

IN

G

FL

O

O R

P

LA

N

M E

C H

A N

IC

AL

P O

W

ER

B A

S E

B

ID

0 4' 8' 16' A1 E105

FLOOR PLAN - ADMINISTRATION - MECHANICAL POWER - BASE BID

SCALE: 1/8" = 1'-0"

SYMBOLS LIST:

m MOTOR RATED SWITCH MOUNTED IN ACCESSIBLE

SPACE, TO J-BOX ADJACENT TO THE UNIT IT SERVES

TO PROVIDE LOCAL SERVICE DISCONNECT.

r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E

F

LO

O R

P

LA

N

A D M

IN

M E C H A N

IC

A L P O W E R

B A S E

B

ID

.d w g 1/

:5 :3

P M jm o b e rl y, RECREATION

/ LAND

USE /

ARCHAEOLOGY

REC / LAND /

MIN OFFICER

SMALL

CONFERENCE

PUBLIC

MEETING

NAT.

RESOURCES

ECOSYSTEM

ECO STAFF

OFFICER

DISTRICT

RANGER

ADMIN

SUPPORT

ECOSYSTEM

/ PLANNING

STORAGE

EVIDENCE

STORAGE

DEPUTY

DISTRICT

RANGER

ELEC

TELECOM

LAW

ENFORCEMENT

MAP / COPY /

SUPPLY

BREAKROOM

PUBLIC

AFFAIRS

MAIL

RECEPTION

LOBBY

M

W

JAN

W

M

FIRE

MANAGEMENT

DFMO

FSR

HALL

HALL

HALL

A

23456789101112

C

E

F

H

G

PROVIDE STACKED

OVER/UNDER MOUNTING.

20A, 208V, 1PH, 60HZ, NEMA

3R DISCONNECT SWITCHES,

WALL MOUNTED.

AM-19,21

AM-22,24

m m m m

AM-2,4

m

AM-18

m m m m

AM-5,7

m

AM-1,3

AM-16

m mm mm AM-10,12 m m m m

AM-14

m mm m m

AM-9,11

AM-13,15,17

PROVIDE NEMA 3R 15A, 208V,

3PH, 60HZ, WALL MOUNTED

DISCONNECT SWITCH.

mmm m

AM-6,8

B A

WP

GFI

AP2-14

AM-38,40,42AM-38,40,42

#2

#2

AM-16

SEE CONDUIT AND FEEDER

SCHEDULE FOR SIZE AND

QUANTITIES.

KEYED NOTES:

PROVIDE 100A, 208V, 3PH, 60HZ, 5K AIC RATED, NEMA 3R

DISCONNECT SWITCHES AND SERVICE RECEPTACLE,

MOUNTED ON RACK SYSTEM PER DETAIL _/E___.

MAINTAIN ALL CLEARANCES FOR ELECTRICAL AND

MECHANICAL EQUIPMENT.

number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

A D

M

IN

IS

TR

A

TI

O N

B U

IL

D

IN

G

FL

O

O R

P

LA

N

M E

C H

A N

IC

AL

P O

W

ER

B A

S E

B

ID

A

LT

E

R N

AT

E

A1 E106

FLOOR PLAN - ADMINISTRATION - MECHANICAL POWER - BASE BID & ALTERNATE

SCALE: 1/8" = 1'-0" 0 4' 8' 16'

SYMBOLS LIST:

m MOTOR RATED SWITCH MOUNTED IN ACCESSIBLE

SPACE, TO J-BOX ADJACENT TO THE UNIT IT SERVES

TO PROVIDE LOCAL SERVICE DISCONNECT.

r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E

F

LO

O R

P

LA

N

A D M

IN

M E C H A N

IC

A L P O W E R

B A S E

B

ID

A

LT

.d w g 1/

:5 :3

P M jm o b e rl y, 2345678

C

E

F

H

G

B

D

G

H

EVIDENCE

STORAGE

201 SF

DEPUTY

DISTRICT

RANGER

136 SF

ELEC

110 SF

TELECOM

101 SF

LAW

ENFORCEMENT

361 SF

MAP / COPY / SUPPLY

399 SF

BREAKROOM

295 SF

PUBLIC

AFFAIRS

356 SF

MAIL

92 SF

RECEPTION

182 SF

LOBBY

329 SF

M

239 SF

W

253 SF

JAN

33 SF

SMALL

CONF

166 SF

W

56 SF

M

56 SF

HALL

88 SF

FIRE MANAGEMENT

1,022 SFDFMO

125 SF

FSR

12 SF

D W

R E

F.

C O

U N

TE

R

D

IS

P

LA

Y

RETAIL

P

LO

TT

E

R

HALL

347 SF

HALL

103 SF

STORAGE

123A

40 SF

POC,2

POC,2,3

TELCO POC

CATV POC

DVS

VM

DA

DA

BS

A S

TV

C

C

POSTAGE MACHINE

A

BS BS

HS

CC

DVS

VM

BS

K

BS

POC,2

POC,3

POC,3

M

C

C

LONG RANGE LENS TO SEE

TO SHADE STRUCTURE

ALONG PATH.

TYPE-2

TYPE-2

C

C

BS

MM

C

TYPE-1

M

M M C

M

A

M

MM

TYPE-2

M

H S

A S

H S

+60"

A S

H S

A S

H S

A S

H S number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

A D

M

IN

IS

TR

A

TI

O N

B U

IL

D

IN

G

FL

O

O R

P

LA

N

SI

G

N

AL

B A

S E

B

ID

0 4' 8' 16' A1 E107

FLOOR PLAN - ADMINISTRATION - SECURITY, ACCESS CONTROL, CCTV, CATV & SIGNAL - BASE BID

SCALE: 1/8" = 1'-0"

KEYED NOTES:

COORDINATE T.V. MOUNTING WITH FINAL SHOP DRAWINGS

FOR DISPLAY CASES BEFORE BID SET IS COMPLETE.

PROVIDE WITH RECESSED T.V./ LOW VOLTAGE COMBO BOX.

MOUNT BENEATH COUNTER, OUT OF PUBLIC SIGHT AND

OUT OF POSITION FOR ACCIDENTAL ACTIVATIONS.

REQUEST TO EXIT MOTION FOR AFTER HOURS EXITING/

EMERGENCY EGRESS. DURING REGULAR HOURS LOBBY

DOORS TO REMAIN UNLOCKED.

PROVIDE HANDSET WITH (4) TELEPHONE LINES AND

INTERCOM.

PROVIDE BALANCED MAGNETIC SWITCH FOR BOTH

ACCESS CONTROL AND SECURITY SYSTEM.

PROVIDE LAW ENFORCEMENT WITH (3) PHONE LINES WITH

(1) NOT ON NETWORK SWITCH. ENABLE DIRECT AUDITORY

CONNECTION TO RECEPTION COUNTER.

SEE DETAIL C3/E105 FOR WALL MOUNTED MONITOR

DIAGRAM.

SEE SHEET NOTE 1 FOR VOICE AND DATA CABLING.

PROVIDE WALL MOUNT HANDSET WITH MOUNTING TO

DEVICE COVER PLATE. PROVIDE COVER PLATE WITH

MOUNTING LUGS.

SEE SECURITY DOOR MOUNTING DETAILS, E504,

REFERENCED BY TYPE. COORDINATE WITH CONTRACTING

OFFICER FOR CABLING TYPE, QUANTITY, ETC..

SHEET NOTES:

1. RECEPTION AREA 118 COUNTER TO BE PROVIDED WITH;

· TWO (2) TELEPHONE HANDSETS WITH INTERCOM.

· THREE (3) TELEPHONE LINES (ONE) FOR TDD.

· TWO (2) DATA LINES.

· REQUEST TO EXIT MOTION PROVIDED ABOVE ENTRY DOORS FOR AFTER HOURS

EGRESS.

· HAND OPERATED PANIC DURESS BUTTON FOR AUDIBLE ALARM THROUGHOUT

BUILDING.

· SECURITY MONITOR WITH VIDEO INPUT SEQUENCING SWITCH.

· TWO (2) SAFES WITH ALARM ACTIVATION SWITCH.

· ENABLE DIRECT AUDITORY CONNECT TO LEO ROOM 107.

2. MOUNT CAMERAS ON EXTERIOR OF BUILDING, HIGH UNDER EAVE TO MAXIMIZE

PROTECTION FROM GLARE, ELEMENTS AND VANDALISM. DO NOT MOUNT WHERE VIEW IS

OBSTRUCTED. ALL CABLING AND CONDUCTORS TO BE HOME RUN TO TR104. DO NOT

DAISY CHAIN.

3. ROUTE ALL CABLING FOR SECURITY, ACCESS CONTROL, CATV, CCTV CAMERAS,

TELEPHONE, AND DATA TO T.R. 104.

4. PROVIDE (2) 2 INCH CONDUIT WITH PULL STRING FROM ELECTRIC ROOM 110 TO TR 104.

CAP AND SEAL. LABEL AS FUTURE.

5. FOR SYSTEMS FURNITURE (2) 8 PIN RJ45 MODULES IN EACH WORKSTATION ADJACENT TO

COMPUTER POWER RECEPTACLE. PROVIDE WITH COVERPLATE WITH (1) MODULE

LABELED VOICE AND (1) LABELED DATA.

6. COPPER DATA CABLE LENGTH LIMITED TO 295 FEED (90M) FROM PATCH PANEL IN TR TO

POINT OF USE AT MODULAR JACK.

7. CATV OR CCTV. SEE UFC 3-580 AND 2-4.3 FOR REQUIRED CABLE PER USE AND FIELD

MEASURED DISTANCES. COORDINATE WITH CONTRACTING OFFICER FOR SUPPLIER

SPECIFIC REQUIREMENTS.

8. JUNCTION AND OUTLET BOXES FOR PHONE/DATA SHALL BE DOUBLE GANG, 4-11/16" SQ.,

AT LEAST 2-1/8" DEEP, ELECTRICAL BOX.

9. ALL OUTLETS TO BE SUPPLIED BY MINIMUM 1 INCH EMT CONDUIT TO NEAREST CABLE

TRAY OR TR. INCREASE CONDUIT AND OUTLET BOXES AS NEEDED FOR WIRE COUNT

WHILE MAINTAINING LESS THAN 40% CONDUIT WIRE FILL.

10. SECURITY ALARM TO BE PARTITIONED 4 WAYS.

1. PUBLIC ACCESS; RM 119, 122, 121, 120

2. EMPLOYEE ACCESS; ALL BUT CAN TURN PART 1 ON/OFF SEPARATELY.

3. EVIDENCE STORAGE; RM 201 LAW ENFORCEMENT ACCESS ONLY VIA SEPARATE

KEYPAD.

4. 24 HR SAFE ALARM WITH LOCAL KEYPAD BYPASS;

a: ALARM SILENT DURING NORMAL BUSINESS HOURS b: ALARM AUDIBLE OTHERWISE.

11. ALL EXIT CCTV CAMERAS TO BE LOW LIGHT CAPABLE.

K

SIGNAL SYMBOLS LIST

KEYPAD

DS DOOR STRIKE

PI PASSIVE INFRARED DETECTOR

RM REQUEST TO EXIT - MOTION

R REQUEST TO EXIT - SWITCH

PUSH BUTTON - REMOTE OPEN/ BYPASS

AS ACTIVATION SWITCH FOR UNDER COUNTER SAFE

C SECURITY CAMERA

POC,x

POC,x,y

OR

POINT OF CONNECTION FOR

SYSTEM FURNITURE DATA/

TELEPHONE WHERE X= # OF EACH

CONDUCTOR, I.E. POC2= (2) CAT6

DATA AND (2) CAT6 TELEPHONE.

POC4,3= (4) CAT6 DATA AND (3)

CAT6 TELEPHONE.

DATA/TELEPHONE- MIN. (2) CAT6

DATA- MIN. (1) CAT6 BLUE, U.O.N.

TELEPHONE- MIN. (1) CAT6 WHITE, U.O.N.

TV TELEVISION

HS TELEPHONE HAND SET

VM VIDEO MONITOR

DVR DIGITAL VIDEO RECORDER

DVS DIGITAL VIDEO SEQUENCER/SELECTOR

M MAGNETIC DOOR HOLDER

BS BALANCED MAGNETIC SWITCH

CR CARD READER

CK CARD READER WITH KEYPAD

DA DURESS ALARM - AUDIBLE

(1) BLUE, (1) WHITE, U.O.N.

M WALL/CORNER MOUNT, DUAL TECHNOLOGY

PIR/MICRO MOTION DETECTOR

CEILING MOUNT, DUAL TECHNOLOGY

PIR/MICRO MOTION DETECTORM

r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E

F

LO

O R

P

LA

N

A D M

IG

N A L

B A S E

B

ID

.d w g 1/

:5 :4

P M jm o b e rl y, 23456789101112

C

E

F

H

G

RECREATION

/ LAND

USE /

ARCHAEOLOGY

781SF

EVIDENCE

STORAGE

201 SFREC / LAND/

MIN

OFFICER

122 SF

DEPUTY

DISTRICT

RANGER

136 SF

ELEC

110 SF

TELECOM

101 SF

LAW

ENFORCEMENT

361 SF

MAP / COPY / SUPPLY

399 SF

BREAKROOM

295 SF

PUBLIC

AFFAIRS

356 SF

MAIL

92 SF

RECEPTION

182 SF

LOBBY

329 SF

M

239 SF

W

253 SF

JAN

33 SF

SMALL

CONF

127 SF

W

56 SF

M

56 SF

HALL

88 SF

PUBLIC

MEETING

792 SF

NAT.

RESOURCES

711 SF

FIRE MANAGEMENT

1,022 SF

ECOSYSTEM

734SF

ECO STAFF

OFFICER

126 SF

DISTRICT

RANGER

215 SF

DFMO

125 SF

ADMIN

SUPPORT

519 SF

ECOSYSTEM

/ PLANNING

STORAGE

122 SF

D W

R E

F.

C O

U N

TE

R

D

IS

P

LA

Y

RETAIL

P

LO

TT

E

R

HALL

392 SF

HALL

103 SF

FSR

12 SF

POC,4 POC,3 POC,2 POC,2

POC,4

POC,4

POC,3

C

C

BS

POC,2

POC,2,3

TELCO POC

CATV POC

DVS

VM

DA

DA

BS

A S

TV

C

C

POSTAGE MACHINE

A

BS BS

HS

CC

DVS

VM

BS

K

BS

POC,2

POC,3

POC,3

M

C

C

LONG RANGE

LENS

TYPE-2

TYPE-2

CC BS

MM

C

TYPE-1

M

M M C

M

A

M

MM

TYPE-2

M

H S

A S

H S

+60"

A S

H S

A S

H S

A S

H S

M M

M M

TYPE-2

TYPE-2

M

M

M

MC

number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

A D

M

IN

IS

TR

A

TI

O N

B U

IL

D

IN

G

FL

O

O R

P

LA

N

SI

G

N

AL

B A

S E

B

ID

A

LT

E

R N

AT

E

0 4' 8' 16' A1 E108

FLOOR PLAN - ADMINISTRATION - SECURITY, ACCESS CONTROL, CCTV, CATV & SIGNAL - BASE BID

SCALE: 1/8" = 1'-0"

K

SIGNAL SYMBOLS LIST

KEYPAD

DS DOOR STRIKE

PI PASSIVE INFRARED DETECTOR

RM REQUEST TO EXIT - MOTION

R REQUEST TO EXIT - SWITCH

PUSH BUTTON - REMOTE OPEN/ BYPASS

AS ACTIVATION SWITCH FOR UNDER COUNTER SAFE

C SECURITY CAMERA

POC,x

POC,x,y

OR

POINT OF CONNECTION FOR

SYSTEM FURNITURE DATA/

TELEPHONE WHERE X= # OF EACH

CONDUCTOR, I.E. POC2= (2) CAT6

DATA AND (2) CAT6 TELEPHONE.

POC4,3= (4) CAT6 DATA AND (3)

CAT6 TELEPHONE.

DATA/TELEPHONE- MIN. (2) CAT6

DATA- MIN. (1) CAT6 BLUE, U.O.N.

TELEPHONE- MIN. (1) CAT6 WHITE, U.O.N.

TV TELEVISION

HS TELEPHONE HAND SET

VM VIDEO MONITOR

DVR DIGITAL VIDEO RECORDER

DVS DIGITAL VIDEO SEQUENCER/SELECTOR

M MAGNETIC DOOR HOLDER

BS BALANCED MAGNETIC SWITCH

CR CARD READER

CK CARD READER WITH KEYPAD

DA DURESS ALARM - AUDIBLE

(1) BLUE, (1) WHITE, U.O.N.

M WALL/CORNER MOUNT, DUAL TECHNOLOGY

PIR/MICRO MOTION DETECTOR

CEILING MOUNT, DUAL TECHNOLOGY

PIR/MICRO MOTION DETECTORM

KEYED NOTES:

COORDINATE T.V. MOUNTING WITH FINAL SHOP DRAWINGS

FOR DISPLAY CASES BEFORE BID SET IS COMPLETE.

PROVIDE WITH RECESSED T.V./ LOW VOLTAGE COMBO BOX.

MOUNT BENEATH COUNTER, OUT OF PUBLIC SIGHT AND

OUT OF POSITION FOR ACCIDENTAL ACTIVATIONS.

REQUEST TO EXIT MOTION FOR AFTER HOURS EXITING/

EMERGENCY EGRESS. DURING REGULAR HOURS LOBBY

DOORS TO REMAIN UNLOCKED.

PROVIDE HANDSET WITH (4) TELEPHONE LINES AND

INTERCOM.

PROVIDE BALANCED MAGNETIC SWITCH FOR BOTH

ACCESS CONTROL AND SECURITY SYSTEM.

PROVIDE LAW ENFORCEMENT WITH (3) PHONE LINES WITH

(1) NOT ON NETWORK SWITCH. ENABLE DIRECT AUDITORY

CONNECTION TO RECEPTION COUNTER.

SEE DETAIL C3/E105 FOR WALL MOUNTED MONITOR

DIAGRAM.

SEE SHEET NOTE 1 FOR VOICE AND DATA CABLING.

PROVIDE WALL MOUNT HANDSET WITH MOUNTING TO

DEVICE COVER PLATE. PROVIDE COVER PLATE WITH

MOUNTING LUGS.

SEE SECURITY DOOR MOUNTING DETAILS, E504,

REFERENCED BY TYPE. COORDINATE WITH CONTRACTING

OFFICER FOR CABLING TYPE, QUANTITY, ETC..

SHEET NOTES:

1. RECEPTION AREA 118 COUNTER TO BE PROVIDED WITH;

· TWO (2) TELEPHONE HANDSETS WITH INTERCOM.

· THREE (3) TELEPHONE LINES (ONE) FOR TDD.

· TWO (2) DATA LINES.

· REQUEST TO EXIT MOTION PROVIDED ABOVE ENTRY DOORS FOR AFTER HOURS

EGRESS.

· HAND OPERATED PANIC DURESS BUTTON FOR AUDIBLE ALARM THROUGHOUT

BUILDING.

· SECURITY MONITOR WITH VIDEO INPUT SEQUENCING SWITCH.

· TWO (2) SAFES WITH ALARM ACTIVATION SWITCH.

· ENABLE DIRECT AUDITORY CONNECT TO LEO ROOM 107.

2. MOUNT CAMERAS ON EXTERIOR OF BUILDING, HIGH UNDER EAVE TO MAXIMIZE

PROTECTION FROM GLARE, ELEMENTS AND VANDALISM. DO NOT MOUNT WHERE VIEW IS

OBSTRUCTED. ALL CABLING AND CONDUCTORS TO BE HOME RUN TO TR104. DO NOT

DAISY CHAIN.

3. ROUTE ALL CABLING FOR SECURITY, ACCESS CONTROL, CATV, CCTV CAMERAS,

TELEPHONE, AND DATA TO T.R. 104.

4. PROVIDE (2) 2 INCH CONDUIT WITH PULL STRING FROM ELECTRIC ROOM 110 TO TR 104.

CAP AND SEAL. LABEL AS FUTURE.

5. FOR SYSTEMS FURNITURE (2) 8 PIN RJ45 MODULES IN EACH WORKSTATION ADJACENT TO

COMPUTER POWER RECEPTACLE. PROVIDE WITH COVERPLATE WITH (1) MODULE

LABELED VOICE AND (1) LABELED DATA.

6. COPPER DATA CABLE LENGTH LIMITED TO 295 FEED (90M) FROM PATCH PANEL IN TR TO

POINT OF USE AT MODULAR JACK.

7. CATV OR CCTV. SEE UFC 3-580 AND 2-4.3 FOR REQUIRED CABLE PER USE AND FIELD

MEASURED DISTANCES. COORDINATE WITH CONTRACTING OFFICER FOR SUPPLIER

SPECIFIC REQUIREMENTS.

8. JUNCTION AND OUTLET BOXES FOR PHONE/DATA SHALL BE DOUBLE GANG, 4-11/16" SQ.,

AT LEAST 2-1/8" DEEP, ELECTRICAL BOX.

9. ALL OUTLETS TO BE SUPPLIED BY MINIMUM 1 INCH EMT CONDUIT TO NEAREST CABLE

TRAY OR TR. INCREASE CONDUIT AND OUTLET BOXES AS NEEDED FOR WIRE COUNT

WHILE MAINTAINING LESS THAN 40% CONDUIT WIRE FILL.

10. SECURITY ALARM TO BE PARTITIONED 4 WAYS.

1. PUBLIC ACCESS; RM 119, 122, 121, 120

2. EMPLOYEE ACCESS; ALL BUT CAN TURN PART 1 ON/OFF SEPARATELY.

3. EVIDENCE STORAGE; RM 201 LAW ENFORCEMENT ACCESS ONLY VIA SEPARATE

KEYPAD.

4. 24 HR SAFE ALARM WITH LOCAL KEYPAD BYPASS;

a: ALARM SILENT DURING NORMAL BUSINESS HOURS b: ALARM AUDIBLE OTHERWISE.

11. ALL EXIT CCTV CAMERAS TO BE LOW LIGHT CAPABLE.

r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E

F

LO

O R

P

LA

N

A D M

IN

S

IG

N A L

B A S E

B

ID

A

LT

E R N A T E .d w g 1/

:5 :4

P M jm o b e rl y, 2345678

C

E

F

H

G

B

D

G

H

EVIDENCE

STORAGE

DEPUTY

DISTRICT

RANGER

ELEC

TELECOM

LAW

ENFORCEMENT

MAP / COPY /

SUPPLY

BREAKROOM

PUBLIC

AFFAIRS

MAIL

RECEPTION

LOBBY

M

W

JAN

FIRE

MANAGEMENT

DFMO

FSR

HALL

HALL

W

M

STORAGE

123A

HALL

A123

H

H

F os

D1

D1

D1D1D2

D2

D1 D1D1D2

D1D2

OS IRC

OS IRC D3

D3 A A d4 A A A A

K

K

K

K

K

K

4 4

F

A A

A

A

OS

OS

A

A

A AA A

os

B

AA

OSIRC

PC

d4 d4 d4 d4 d4

AAAA

AAAA

AAAA

PCOS

PCOS

OS

PC

B

AA

OSIRC

LCC

F

F os

BB

BB

BB

AA

AA

AA

AA

AA

AA

AA

AA

OSIRCOSIRC

4 4

PC

PC PC

OS

DLDL

DLDLDLDL POC

POC

POC

POC

DLDLDLDL

DLDLDLDL

DL DL

DL1

DL2

DL1

DL2

DLDLDLDL

OSPC

DL DL DL

TP

TP

4 C

H H osos

D1 D1 os

AA

IRC

A

C1

C1 C1

C1

OS

IRC

D3 D3 D3 D3 D3D3D3

D1 OS OS OS

L1

L2

L2

L1L1 number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

A D

M

IN

IS

TR

A

TI

O N

B U

IL

D

IN

G

FL

O

O R

P

LA

N

LI

G

H

TI

N G

B A

S E

B

ID

0 2' 8' 16' A1 E109

FLOOR PLAN - ADMINISTRATION - LIGHTING -BASE BID

SCALE: 1/8" = 1'-0"

ARCHITECTURAL ACCENT LIGHTS

FULL CUTOFF EXTERIOR WALL WASH.

SHEET NOTES:

1. MODULAR FURNITURE PROVIDED WITH LED TASK LIGHTING

WITH INTEGRATED OCCUPANCY CONTROL SENSORS.

2. MOUNT ALL IRC ENCLOSURES ABOVE ACCESSIBLE

CEILING WITHIN SPACE SERVED NEAREST TO PRIMARY

SWITCH U.O.N.

LOW VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR

OSC10-MOW.

OS

LOW VOLTAGE CEILING PHOTO SENSOR #ODCOP-OOW.PC

4 4 BUTTON IRC CONTROL SWITCH LEVITON #RLVSW-4LW

INTEGRATED ROOM CONTROLLER (IRC) LEVITON# MZD20-102.IRC

os WALLBOX OCCUPANCY SENSOR SINGLE RELAY LEVITON #ODS15-TDW d2 2 BUTTON OVERRIDE CONTROL SWITCH LEVITON #RDGSW-2DW

LOW VOLTAGE WALL MOUNTED PHOTO SENSOR #PCOUT-OSV.PC

W

LOW VOLTAGE WALL MOUNTED OCCUPANCY SENSOR

OSW12-MOW.

OS

W d4 4 BUTTON OVERRIDE CONTROL SWITCH LEVITON #RDGSW-4DW

LIGHTING SYMBOLS LIST:

KEYED NOTES:

IRC FOR LOBBY/RECEPTION AREA MOUNTED IN ADJACENT

ACCESSIBLE CEILING SPACE.

TP TIMED SWITCH WITH PILOT LIGHT, WALL BOX, LEVITON LTB30-1L

r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E

F

LO

O R

P

LA

N

A D M

IN

LI

G H T

IN

G

B A S E

B

ID

.d w g 1/

:5 :4

P M jm o b e rl y, 23456789101112

C

E

F

H

G

B

D

G

H

RECREATION

/ LAND

USE /

ARCHAEOLOGY

REC / LAND /

MIN OFFICER

SMALL

CONFERENCE

PUBLIC

MEETING

NAT.

RESOURCES

ECOSYSTEM

ECO STAFF

OFFICER

DISTRICT

RANGER

ADMIN

SUPPORT

ECOSYSTEM

/ PLANNING

STORAGE

EVIDENCE

STORAGE

DEPUTY

DISTRICT

RANGER

ELEC

TELECOM

LAW

ENFORCEMENT

MAP / COPY /

SUPPLY

BREAKROOM

PUBLIC

AFFAIRS

MAIL

RECEPTION

LOBBY

M

W

JAN

W

M

FIRE

MANAGEMENT

DFMO

FSR

HALL

HALL

HALL

H

H

H H

IRC

F os

D1

D1

D1D1D2

D2

D1 D1D1D2

D1D2

OS IRC

OS IRC D3

D3

D3 D3 D3 D3 D3D3D3D3D3

OS

OS OS OS

A A d4 A A A A

K

K

K

K

K

K

4 4

F

A A

A

A

OS

OS

A

A

A AA A

os

B

AA

OSIRC

PC

d4 d4 d4 d4 d4

AAAA

AAAA

AAAA

PCOS

PCOS

OS

PC

B

AA

OSIRC

LCC

F

F os

BB

BB

BB

AA

AA

AA

AA

AA

AA

AA

AA

OSIRCOSIRC

PC PC

osos

D1 D1 osos

AA

IRC

C1

A

C1

C1 C1

C1

OS

IRC

C1

C1

C2

AA

AA

AA

AA

PC

OS

C1

C1

C1

C1

AA

AA

AA

AA

C1

OS

IRC

B

B

AA

AA

IRC

OSPC

AAA

AAA

AAA

AAA

AAA

AAA

AAA

AAA

AAA

AAA

AAA

AAAAA

OS OS

OS OS OS

OS

PC

PC

PC

B B

4 4 A

A

PC

OS

A

A

PC

OS

IRC F

os

4 4

PC

OS

L1

L2

L2

L1L1

DLDL

DLDLDLDL

DLDLDLDL

DLDLDLDL

DL DL

DL1

DL2

DL1

DL2

DLDLDLDL

OSPC

DL DL DL

TP

TP

C

4d4 d4 d4 d4

DL

DLDL

DL DLDL

DLDL

DLDL

DLDL

DL

DL DL

DLDL

C2

DLDL

DLDL DLDL

DLDL

0 2' 8' 16' A1 E110

FLOOR PLAN - ADMINISTRATION - LIGHTING - BASE BID & ALTERNATE

SCALE: 1/8" = 1'-0"

number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

A D

M

IN

IS

TR

A

TI

O N

B U

IL

D

IN

G

FL

O

O R

P

LA

N

LI

G

H

TI

N G

B A

S E

B

ID

A

LT

E

R N

AT

E

ARCHITECTURAL ACCENT LIGHTS

FULL CUTOFF EXTERIOR WALL WASH.

LOW VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR

OSC10-MOW.

OS

LOW VOLTAGE CEILING PHOTO SENSOR #ODCOP-OOW.PC

4 4 BUTTON IRC CONTROL SWITCH LEVITON #RLVSW-4LW

INTEGRATED ROOM CONTROLLER (IRC) LEVITON# MZD20-102.IRC

os WALLBOX OCCUPANCY SENSOR SINGLE RELAY LEVITON #ODS15-TDW d2 2 BUTTON OVERRIDE CONTROL SWITCH LEVITON #RDGSW-2DW

LOW VOLTAGE WALL MOUNTED PHOTO SENSOR #PCOUT-OSV.PC

W

LOW VOLTAGE WALL MOUNTED OCCUPANCY SENSOR

OSW12-MOW.

OS

W d4 4 BUTTON OVERRIDE CONTROL SWITCH LEVITON #RDGSW-4DW

LIGHTING SYMBOLS LIST: SHEET NOTES:

1. MODULAR FURNITURE PROVIDED WITH LED TASK LIGHTING

WITH INTEGRATED OCCUPANCY CONTROL SENSORS.

2. MOUNT ALL IRC ENCLOSURES ABOVE ACCESSIBLE

CEILING WITHIN SPACE SERVED NEAREST TO PRIMARY

SWITCH U.O.N.

KEYED NOTES:

IRC FOR LOBBY/RECEPTION AREA MOUNTED IN ADJACENT

ACCESSIBLE CEILING SPACE.

TP TIMED SWITCH WITH PILOT LIGHT, WALL BOX, LEVITON LTB30-1L

r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E

F

LO

O R

P

LA

N

A D M

IN

LI

G H T

IN

G

B A S E

B

ID

A

LT

.d w g 1/

:5 :4

P M jm o b e rl y, 2345678

C

E

F

H

F

SLOPE

4:12

SLOPE

4:12

SLOPE

4:12

SLOPE

3:12

SLOPE

4:12

SLOPE

3:12

SLOPE

3:12

SLOPE

6:12

SLOPE

6:12

SLOPE

6:12

30"

WP

GFI

PV

AP-

TO MSB PV TIE IN

TO TR FOR

NETWORK TIE IN

0 4' 8' 16' A1 E111

ROOF PLAN - P.V. ARRAY

SCALE: 1/8" = 1'-0"

number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

A D

M

IN

IS

TR

A

TI

O N

B U

IL

D

IN

G

R O

O F

P

LA

N

PO

W

ER

B

A S

E B

ID

SHEET NOTES:

1. SEE P.V. MOUNTING DETAILS E505

2. SEE P.V. GROUNDING DETAILS E505

3. SEE P.V. ELEVATION DETAILS E201.

4. SEE ARCHITECTURAL DRAWINGS FOR ROOF

PENETRATION DETAILS. SEE P.V. WIRING ONE LINE

E601 r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E R O O F

P

LA

N

A D M

W E R

B A S E

B

ID

.d w g 1/

:5 :5 P M jm o b e rl y, 23456789101112

C

E

F

H

F

B

D

G

H

SLOPE

4:12

SLOPE

4:12

SLOPE

4:12

SLOPE

3:12

SLOPE

4:12

SLOPE

3:12

SLOPE

4:12

SLOPE

4:12

SLOPE

2:12

SLOPE

3:12

SLOPE

6:12

SLOPE

6:12

SLOPE

6:12

SLOPE

6:12

30" 30"

WP

GFI

PV

AP-

TO MSB PV TIE IN

TO TR FOR

NETWORK TIE IN

WP

GFI

SHEET NOTES:

1. SEE P.V. MOUNTING DETAILS E505

2. SEE P.V. GROUNDING DETAILS E505

3. SEE P.V. ELEVATION DETAILS E201.

4. SEE ARCHITECTURAL DRAWINGS FOR ROOF

PENETRATION DETAILS. SEE P.V. WIRING ONE LINE

E601 number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

A D

M

IN

IS

TR

A

TI

O N

R O

O F

P

LA

N

PO

W

ER

B

A S

E B

ID

A

LT

E R

N

AT

E

0 4' 8' 16' A1 E112

ROOF PLAN - P.V. ARRAY

SCALE: 1/8" = 1'-0"

r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E

R O O F

P

LA

N

A D M

IN

P O W E R

B A S E

B

ID

A

LT

E R N A T E .d w g 1/

:5 :5

P M jm o b e rl y, 2-BAY

1,584SF

WORKOUT

469 SF

CACHE

398 SF

UNISEX

89 SF

SHOWER

ICE

LOCKERS

EYEWASH /

SHOWER

ENGINE 1

ENGINE 2

MIRRORED

WALL

AIR

COMPRESSOR,

OFOI

STAIR

MASTER

TREADMILL

CYCLE

1 2 3 4 5 6

7 8 9 10 11 12

TV

PANEL 'WP'

PANEL 'WL'

WP

GFI

GFI5

1WP-1,3,5

1+90"

TV

WP

GFI

13 13

WP-11,13

11WP

GFI

WM-6

WM-7

WM-8

ROLL UP DOOR

OPENER

AIR COMPRESSOR

ROLL UP DOOR

OPENER

WP

GFI

WP

GFI

WM- 4

WM-5

WP

GFI6

WP-6,8

WM-3

WM-1

WP-2,4

5 3

WM-9

WM-12

WM-2

m m m m m

+90"

PANEL 'WM'

WP-9

m

WM-10

m

WSB

T-W P.B.

WM-_

ELEC

CATV

TEL

P.B.

P.B.

+90"

TV

+90"

WP-16

WP-12

WP-17

WP-10

TELCO P.O.C.

CATV P.O.C.

SEE WAREHOUSE

TELCO/ CATV

ELEVATION, E20_

0 2' 4' 8' A1 E130

FLOOR PLAN - WAREHOUSE - POWER - BASE BID & ALTERNATE

SCALE: 1/4" = 1'-0"

KEYED NOTES:

COORDINATE LOCATION FOR POINT OF CONNECTION

PRIOR TO ROUGH-IN.

COORDINATE LOCATION AND CONNECTION TYPE WITH

DOOR CONTRACTOR PRIOR TO ROUGH-IN. MOUNT

EQUIPMENT POWER J-BOX WITHIN 30 INCHES OF P.O.C.

TO MOTOR OPERATOR. PROVIDE 3 POSITION CONTROL

SWITCH MOUNTED AT 46" AFF TO CENTER.

COORDINATE CONNECTION TYPE PRIOR TO ROUGH-IN.

RECESSED IN WALL JUNCTION BOX FOR CONNECTION

TO U.G. CONDUITS TO FLOOR RECEPTACLES FOR

EXERCISE EQUIPMENT. COORINATE LOCATION PRIOR

TO ROUGH IN.

PROVIDE FLUSH MOUNT WITH IN USE COVERS

COMPLETE WITH CORD PASS THROUGH OPENING

COVER TO BE CONSTRUCTED OF BRASS OR OTHER

MATERIAL OF EQUAL DURABILITY WITH HINGED SELF

CLOSING COVERS.

PROVIDE SPARE CONDUITS FROM U.G. PULL BOX TO

P.O.C. WITHIN BUILDING. SEE CONDUIT AND FEEDER

SCHEDULE FOR DETAILS.

PROVIDE 3/4" AC PLYWOOD 8 FEET HIGH. MUST BE FIRE

RATED 'NOT PAINTED'. PLYWOOD BACKING TO COVER

FULL LENGTH OF EAST WALL AND EXTEND 12 FEET

ALONG SOUTH WALL.

SHEET NOTES:

1. USFS FURNISHED EUIPMENT TO INCLUDE:

- ICE MACHINE, AIR COMPRESSOR, TREADMILL,

STAIR CLIMBER, T.V.

2. SEE CONDUIT AND FEEDER SCHEDULE, SHEET E602.

number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

W A

R E

H O

U S

E B

U

IL

D

IN

G

FL

O O

R P

LA

N

PO

W

ER

B A

S E

B

ID

A

LT

E

R N

AT

E

POWER SYMBOLS LIST:

3 POSITION SWITCH3

m MOTOR RATED DISCONNECT SWITCH

FOR SERVICE DISCONNECT

r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E

F

LO

O R

P

LA

N

W A R E H O U S E

P O W E R

B A S E

B

ID

A

LT

E R N A T E .d w g 1/

:5 :5

P M jm o b e rl y, C

B

2-BAY

1,584SF

WORKOUT

469 SF

CACHE

398 SF

UNISEX

89 SF

SHOWER

ICE

LOCKERS

EYEWASH /

SHOWER

ENGINE 1

ENGINE 2

MIRRORED

WALL

AIR

COMPRESSOR,

OFOI

STAIR

MASTER

TREADMILL

CYCLE

1 2 3 4 5 6

7 8 9 10 11 12

TV

PANEL 'WP'

PANEL 'WL'

PANEL 'WM'

+90"

TV

C

C C

SEE WAREHOUSE

TELCO/ CATV

ELEVATION, E20_

+44"

C C

BS

BS

C C

+90"

TV

BS

CR

BS

CR

R K +44"

KEYED NOTES:

PROVIDE MOUNTING LUGS FOR WALL MOUNTED HAND

SET. PROVIDE OUTLET WITH (2) 8 PIN RJ45 TYPE

OUTLET/CONNECTOR IN A DOUBLE GANG OUTLET,

STAINLESS STEEL FACEPLATE.

(1) CONNECTOR LABELED "VOICE"

(1) CONNECTOR LABELED "DATA"

T.V. DATA PORT CONNECTION, SEE DETAIL _/E___

SEE DETAIL _/E___ FOR ACCESS CONTROL DOOR

SECURITY EQUIPMENT LAYOUT.

SHEET NOTES:

1. SEE E130 FOR U.G. ENTRANCE CONDUCTOR ROUTING

DETAILS AND POWER PROVISIONS FOR TELEPHONE,

CATV, CCTV, SECURITY.

2. SECURITY ALARM REMOTE EXTENDER PANEL LOCATED

AT CATV BACKBOARD. ROUTE ALARM, CCTV, ACCESS

CONTROL CABLING IN CONDUIT TO BACKBOARD FOR

TERMINATION CONNECTIONS TO ADMINISTRATION

BUILDING.

number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

W A

R E

H O

U S

E B

U

IL

D

IN

G

FL

O O

R P

LA

N

SI

G N

AL

B

A S

E B

ID

A

LT

E R

N

AT

E

0 2' 4' 8' A1 E131

FLOOR PLAN - WAREHOUSE - SIGNAL - BASE BID & ALTERNATE

SCALE: 1/4" = 1'-0"

K

SIGNAL SYMBOLS LIST

KEYPAD

DS DOOR STRIKE

PI PASSIVE INFRARED DETECTOR

RM REQUEST TO EXIT - MOTION

R REQUEST TO EXIT - SWITCH

PUSH BUTTON - REMOTE OPEN

AS ACTIVATION SWITCH

C SECURITY CAMERA

POC,x

POC,x,y

OR

POINT OF CONNECTION FOR

SYSTEM FURNITURE DATA/

TELEPHONE WHERE X= # OF EACH

CONDUCTOR, I.E. POC2= (2)

CAT5e DATA AND (2) CAT5e TELEPHONE. POC4,3= (4) CAT5e DATA AND (3) CAT5e TELEPHONE.

DATA/TELEPHONE

DATA

TELEPHONE

TV TELEVISION

HS TELEPHONE HAND SET

VM VIDEO MONITOR

DVR DIGITAL VIDEO RECORDER

DVS DIGITAL VIDEO SEQUENCER/SELECTOR

M MAGNETIC DOOR HOLDER

BS BALANCED MAGNETIC SWITCH

CR CARD READER

CK CARD READER WITH KEYPAD

DA DURESS ALARM - AUDIBLE

r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E F

LO

O R

P

LA

N

W A R E H O U S E

S

IG

N A L

B A S E

B

ID

A

LT

E R N A T E .d w g 1/

:5 :5

P M jm o b e rl y, 3 12

1,584SF

WORKOUT

469 SF

CACHE

398 SF

UNISEX

89 SF

SHOWER

ICE

LOCKERS

EYEWASH /

SHOWER

ENGINE 1

ENGINE 2

MIRRORED

WALL

AIR

COMPRESSOR,

OFOI

STAIR

MASTER

TREADMILL

CYCLE

1 2 3 4 5 6

7 8 9 10 11 12

TV

WV

44" PADDLE FAN

+130" AFF

44" PADDLE FAN

+130" AFF

WS

OS

IRC

W

WS

DL

PC W

OS

W

WL-2

os

WR

WR

IR

C

IR

C WL-4

IR

C

P P

WL-1,3

OS W 4 4 PC W

PC W

PC W OS W

WL WL WL

WL WL

DL DL DL

WH

DL

WH

DL

WH

DL

WH

DL

WH WH

0 2' 4' 8' A1 E132

FLOOR PLAN - WAREHOUSE - LIGHTING - BASE BID & ALTERNATE

SCALE: 1/4" = 1'-0"

number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

W A

R E

H O

U S

E B

U

IL

D

IN

G

FL

O O

R P

LA

N

LI

G H

TI

N

G B

A S

E B

ID

A

LT

E R

N

AT

E

ARCHITECTURAL ACCENT LIGHTS

FULL CUTOFF EXTERIOR WALL WASH.

LOW VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR

OSC10-MOW.

OS

LOW VOLTAGE CEILING PHOTO SENSOR #ODCOP-OOW.PC

4 4 BUTTON IRC CONTROL SWITCH LEVITON #RLVSW-4LW

INTEGRATED ROOM CONTROLLER (IRC) LEVITON# MZD20-102.IRC

os WALLBOX OCCUPANCY SENSOR SINGLE RELAY LEVITON #ODS15-TDW d2 2 BUTTON OVERRIDE CONTROL SWITCH LEVITON #RDGSW-2DW

LOW VOLTAGE WALL MOUNTED PHOTO SENSOR #PCOUT-OSV.PC

W

LOW VOLTAGE WALL MOUNTED OCCUPANCY SENSOR

OSW12-MOW.

OS

W d4 4 BUTTON OVERRIDE CONTROL SWITCH LEVITON #RDGSW-4DW

LIGHTING SYMBOLS LIST:

r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E

F

LO

O R

P

LA

N

W A R E H O U S E

LI

G H T

IN

G

B A S E

B

ID

A

LT

E R N A T E .d w g 1/

:5 :5

P M jm o b e rl y, DS DS DS

DS

DS

DS

14" SOLATUBE

SKYLIGHTS

SLOPE

6:12

SLOPE

6:12

SLOPE

6:12

SLOPE

6:12

RIDGE

STANDING

SEAM METAL

ROOFING, TYP

A

C

B

1 2 3 4 5 6

7 8 9 10 11 12

WP

GFI

WP

GFI

WP-15

PV-WSB

TO WSB P.V.

TIE IN BREAKER

TO DATA BACKBOARD

JUNCTION BOX ROOF

PENETRATION

0 2' 4' 8' A1 E133

ROOF PLAN - POWER

SCALE: 1/4" = 1'-0"

KEYED NOTES:

SEE DETAILS FOR MOUNTING, SHEET E___

SEE P.V. GROUNDING DETAIL, _/E___

SEE P.V. ELEVATIONS, SHEET E2__

SHEET NOTES:

1. SEE ARCHITECTURAL SHEETS FOR ROOF PENETRATION

DETAILS.

number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

W A

R E

H O

U S

E B

U

IL

D

IN

G R

O O

F P

LA

N

PO

W

ER

B A

S E

B

ID

A

LT

E

R N

AT

E r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E

R O O F

P

LA

N

W A R E H O U S E

P O W E R

B A S E

B

ID

A

LT

E R N A T E .d w g 1/

:5 :0 P M jm o b e rl y, 14°

14.5" 4'-4.14"

14°

14.5" 4'-4.14"

14°

14.5"

4'-4.14"

5'

5'18°

27°

14'x12' OVERHEAD

AC B

3°

11.83" 4'-2.74"

3°

11.83" 4'-2.74"

0 2' 4' 8' A1 E201

WEST ADMIN ELEVATION P.V. ARRAY

SCALE: 1/4" = 1'-0"

number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

B U

IL

D

IN

G

E

LE

C

TR

IC

A

L E

LE

V

A

TI

O N

S

0 2' 4' 8' B1 E201

EAST WAREHOUSE ELEVATION P.V. ARRAY

SCALE: 1/4" = 1'-0"

r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E E

LE

C T R

IC

A L E

LE

V A T

IO

N S .d w g 1/

:5 :0

P M jm o b e rl y, PANEL 'APL'

PANEL 'AS'

FACP

LANDSCAPING

CONTROL PANEL.

NOT IN ELECTRICAL

CONTRACT.

PANEL 'AP3'

PANEL 'AP2'

ELEC

TELECOM

TELCO P.O.C.

AP-

AP-+44"

AP-12

AP-AP-

AP-__

AP-__

CATV P.O.C.

19" FLOOR

MOUNT

RACK, TYP.

number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

A D

M

IN

IS

TR

A

TI

O N

E N

LA

R

G E

D F

LO

O

R P

LA

N

S

0 2' 4' 8' B3 E401

ELECTRICAL & TELECOM ROOMS LAYOUT

SCALE: ############

KEYED NOTES:

PROVIDE 3/4" AC PLYWOOD 8 FEET HIGH. MUST BE FIRE

RATED 'NOT PAINTED'. PLYWOOD BACKING TO COVER

FULL LENGTH OF EAST, NORTH AND WEST WALLS AND

EXTEND 7 FEET ALONG SOUTH WALL.

PROVIDE SPARE CONDUITS FROM TR TO P.B. TEL AND

P.B. CATV PER CONDUIT AND FEEDER SCHEDULE.

r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E E N

LA

R G E D

F

LO

O R

P

LA

N S

A D M

IN

IS

T R A T

IO

N .d w g 1/

:5 :0

P M jm o b e rl y, 3'-2" 3'-2" 2'-10" 2'-6"

91.5"

3'-2" 2'-4"

UTILITY METER

MAIN SUBMAIN

TO WSB

U.G.P.S. TVSS MSB CONTROLS

CONDUIT

OPENING

11'-8"

RESERVED

FOR

ADVANCED

METERING

RESERVED

FOR

ADVANCED

MONITORING

TVSS

100/3 150/3 150/3 150/3

100/3 150/3 150/3 150/3

400/3

MS

MS

C.T.

METER

UGPS

WSB MAIN

number:

reference

Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

D E

TA

IL

S

METAL STUD WALL

SURFACE MOUNT

PANEL

FINISH FLOOR

6'-6"

B3 E501

PANEL MOUNTING DETAIL - METAL STUD

SCALE: NONE

METAL

BACKING

PLATE

#12 SHEET METAL SCREW

(4 TOTAL) IN HOLES

PROVIDED WITH

PANELBOARD OR CABINET.

B2 E501

MAIN GROUND BUS DETAIL

SCALE: NONE

INSTALL CENTER SUPPORT

WHEN PANEL HEIGHT

EXCEEDS 60"

WOOD FRAME WALL

B-LINE B22 CROSS

MEMBERS SECURED TO

WOOD STUD WALL WITH

3/8" x 3" LAG BOLTS WITH

FLAT WASHERS.

SECURE PANEL TO

B-LINE CHANNEL WITH (2)

3/8" DIA. MACH. BOLTS,

FLAT WASHER, NUT &

JAMB NUT PER SUPPORT.

SURFACE MOUNT

PANEL

FINISH FLOOR

A3 E501

PANEL MOUNTING DETAIL - WOOD STUD

SCALE: NONE

PREDRILLED

BOLT HOLES

2" 4"

1"

24" MIN.

2"

MIN.

5"

1/4"

1"

COPPER

GROUND BAR

INSULATED

SPACER

WALL MOUNTING

BRACKET

STEEL EXPANSION

ANCHOR

NOTES:

1. PROVIDE A MINIMUM OF 1 MOUNTING POINT PER 12"

OF BAR LENGTH.

2. PROVIDE QUANTITY OF PREDRILLED STANDARD

NEMA BOLT HOLES SIZED AND SPACED AS

REQUIRED FOR CONNECTIONS USED.

3. FOR ALL ADDITIONAL INSTALLATION

REQUIREMENTS REFER TO SPEC SECTIONS 26 05 26.

SECTION ELEVATION

ISOMETRIC

UFER

GROUND

BLDG. MAIN

METALLIC

COLD

WATER

PIPE

BLDG.

MAIN GAS

PIPE

TO MAIN

SERVICE

SWITCHBOARD

GROUND BAR WITH LUGS

1/4"x4"x20". MOUNT 24"

ABOVE FLOOR.

PANELS HP, HP1, HP1A,

HP2, HP3, M3, M1

NOTES:

1. TYPICAL AT EACH BUILDING.

2. SEE ONE-LINE DIAGRAM FOR GROUND CONDUCTOR

SIZES.

3. UFER GROUND, 25' BARE COPPER CONDUCTOR

ENCASED IN CONCRETE FOOTING 3" FROM BOTTOM.

BLDG.

STEEL

A2 E501

MAIN GROUND BUS DETAIL

SCALE: NONE

NOTE:

A1 E501

MAIN SWITCHBOARD ELEVATION

SCALE: NONE

LOCATE SWITCHBOARD PER PLANS - IN ADDITION TO ANY OTHER CONCRETE

PAD AT LOCATION MAIN SWITCHBOARD SHALL BE SECURED ON 2" CONCRETE

HOUSEKEEPING PAD & SHALL EXTEND OUT 8" FROM ALL SIDES OF MAIN

SWITCHBOARD - HOUSEKEEPING PAD SHALL BE REINFORCED WITH #4 REBAR

AT 12" O.C. - ATTACH MAIN SWITCHBOARD TO HOUSEKEEPING PAD WITH (6)

CONCRETE EXPANSION BOLTS "RED HEAD" 1/2" DIA. OR EQUAL WITH 3"

MINIMUM EMBEDMENT TO MEET DSA IR-26 PULL-OUT REQUIREMENTS

KEYED NOTES:

ISOLATED SECTION FOR ADVANCED METERING

EQUIPMENT. SEE DETAILS ____ AND COORDINATE WITH

CONTRACTING OFFICER FOR COMPLETE DETAILS.

r:

.0 u s a c e is a b e lla la k e d rw g s E le c tr ic a l\ E D E T A

IL

S .d w g 1/

:5 :0

P M jm o b e rl y, Sheet

A

B

C

1 2 3 4

SC

R

IP

PS

D R

IV

E

S

AC

R A

M

EN

TO

, C

A

.0

D E

TA

IL

S

TRANSFORMER TOTAL

WEIGHT: 600 LBS

B3 E502

TRANSFORMER MOUNTING DETAIL

SCALE: NONE

FLAT WASHER, LOCK

WASHER, AND NUT.

VIBRATION PAD

CONCRETE FLOOR

1/2" DIA. HILTI KWIKBOLT KB-TZ WITH

3-1/4" MINIMUM EMBEDMENT IN HOLES.

PROVIDE FOUR (4) TOTAL. TEST 100% OF

ANCHORS TO 3200 LBS. TENSION.

FLAT WASHER, LOCK WASHER,

AND NUT.

38"28"

114"

MAX

SWITCHBOARD

TOTAL WEIGHT:

2200 LBS. MAX.PER SECTION

1/2" DIA. HILTI KWIKBOLT KB-TZ

WITH 3-1/4" MINIMUM EMBEDMENT

IN HOLES PROVIDED AT EACH

CORNER OF EACH SECTION. TEST

50% OF ANCHORS TO 40 FT-LBS

TORQUE.

A3 E502

WAREHOUSE SWITCHBOARD DETAIL

SCALE: NONE

6''

POWER CONDUITS ON BOTTOM

(EA. SIDE)

2'' SAND BASE

3'' MIN.

18''

MIN.

12"

MIN.

6''

UNDISTURBED EARTH

WARNING TAPE

MIN. 6'' DEEP SAND W/

YELLOW CAUTION TAPE

BACKFILL WITH

SAND

PROVIDE MIN. 6'' SEPARATION

BETWEEN POWER AND ALL

OTHER CONDUITS AT ALL

HORIZONTAL AND CROSSING

LOCATIONS

COMMUNICATION AND…

This is the start of the file's text. The full file is on GovTribe.