11. 95 pct Structural Dwgs.pdf
PDF 11 MB Posted
- Attached to
- 127EAW26Q0053 - Kern River Ranger District HVAC
- Solicitation number
- 127EAW26Q0053
- Issued by
-
Department of Agriculture Forest Service
About this file
These are structural design drawings and specifications for a federal construction project, specifically 95% submittal plans prepared by CYS Structural Engineers Inc. for a facility located at 111 Scripps Drive, Sacramento, California (Project No. S2030).
The documents contain comprehensive structural engineering details for both an Administration Building and a Warehouse Building, including general notes, design criteria, and detailed construction specifications. Design criteria comply with the 2012 International Building Code, with Occupancy Risk Category II classifications. For the Administration Building, design loads include roof live load of 20 PSF (reducible), floor live load of 50 PSF (reducible), partition load of 15 PSF, corridors at 100 PSF, and storage at 250 PSF. Wind exposure is Category C with 110 MPH ultimate design speed. Seismic design is based on 2012 IBC Chapter 16 and ASCE 7-10, with Site Class D and Seismic Design Category D. The Warehouse Building uses similar standards with storage loads reduced to 100 PSF. Structural systems include steel ordinary moment frames and concentric braced frames for lateral resistance, with foundation designs based on allowable soil bearing pressure of 2,500 PSF (DL+LL) and 3,333 PSF (DL+LL+Seismic/Wind). The specifications detail reinforcing steel requirements (ASTM A615 Grade 60), structural steel specifications (ASTM A992 Grade 50 for wide flanges), concrete specifications (3,000-4,000 PSI strength), and wood framing requirements including glued laminated beams and engineered lumber products. Plans include foundation plans, framing plans, wall elevations, building sections, and numerous construction details addressing connections, footings, shearwalls, nailing schedules, and specialized conditions such as I-joist support systems and mechanical platform framing.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
number:
reference
Sheet
A
B
C
1 2 3 4
S C
R
IP
P S
D R
IV
E
S A
C R
A M
E N
TO
, C
A
C YS
S T R U C T U R A L E N G I N E E R S I N C .
A R
T
HUR ER NEST
RO
S
S
ST RUCT URA L
No. S2030
STA TE OF CA LIFORNIA
RE
G
IS
TE
RED PROFESS IONAL ENG
INEER
95% SUBMITTAL
S
TR
U C
TU
R
A L
G E
N E
R A
L N
O
TE
S
A B
B R
E V
IA
TI
O N
S
1. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COMPLY WITH THE PERTINENT SECTIONS OF THE "CONSTRUCTION SAFETY ORDERS" ISSUED BY THE STATE OF CALIFORNIA LATEST EDITION, AND ALL
OSHA REQUIREMENTS AS THEY APPLY TO THIS PROJECT.
2. THE STRUCTURAL ENGINEER DOES NOT ACCEPT ANY RESPONSIBILITY FOR THE CONTRACTOR'S
FAILURE TO COMPLY WITH THESE REQUIREMENTS.
3. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE
DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO, BRACING FOR
VERTICAL AND/OR LATERAL LOADS, SHORING AND LOADS DUE TO CONSTRUCTION EQUIPMENT,
ETC. OBSERVATION VISITS TO THE SITE BY THE STRUCTURAL ENGINEER WILL NOT INCLUDE
INSPECTION OF THE ABOVE ITEMS.
GENERAL BUILDING STRUCTURAL NOTES:
1. ALL DRAWINGS ARE CONSIDERED TO BE A PART OF THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL
BE RESPONSIBLE FOR THE REVIEW AND COORDINATION OF ALL DRAWINGS AND SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES THAT OCCUR SHALL BE BROUGHT TO THE ATTENTION OF THE USACE PRIOR TO THE START OF CONSTRUCTION SO THAT A CLARIFICATION CAN BE ISSUED. ANY WORK PERFORMED IN CONFLICT WITH THE CONTRACT DOCUMENTS OR ANY CODE REQUIREMENTS SHALL BE
CORRECTED BY THE CONTRACTOR AT THEIR OWN EXPENSE AND AT NO EXPENSE TO THE USACE.
2. TYPICAL NOTES AND DETAILS SHALL APPLY UNLESS OTHERWISE SHOWN OR NOTED ON DRAWINGS.
3. DETAILS OF CONSTRUCTION NOT FULLY SHOWN SHALL BE OF THE SAME NATURE AS SHOWN FOR SIMILAR
CONDITION.
4. ALL WORK SHALL CONFORM TO THE MINIMUM STANDARDS OF THE 2012 INTERNATIONAL BUILDING CODE WITH
LATEST REVISIONS REFERRED TO HEREIN AS "THE CODE", AND OTHER REGULATING AGENCIES WHICH HAVE AUTHORITY OVER ANY PORTION OF THE WORK, INCLUDING THE STATE OF CALIFORNIA DIVISION OF INDUSTRIAL SAFETY, AND THOSE CODES AND STANDARDS LISTED IN THESE NOTES AND SPECIFICATIONS.
5. NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS.
WHERE NO DETAILS ARE GIVEN, CONSTRUCTION SHALL BE AS SHOWN FOR SIMILAR WORK. IF CONFLICTS OCCUR BETWEEN DRAWINGS AND SPECIFICATIONS, THE MOST EXPENSIVE MATERIALS OR METHODS SHALL PREVAIL (FOR BIDDING). CONTRACTING OFFICER SHALL BE NOTIFIED OF CONFLICTS AND THAT PORTION OF
WORK SHOULD NOT PROCEED UNTIL CONFLICT IS RESOLVED.
6. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE. THEY
DO NOT INDICATE THE METHOD OF CONSTRUCTION.
7. NO STRUCTURAL MEMBERS SHALL BE CUT, NOTCHED OR OTHERWISE PENETRATED UNLESS SPECIFICALLY
APPROVED BY THE CONTRACTING OFFICER IN ADVANCE OR SHOWN ON THESE DRAWINGS.
8. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO STARTING CONSTRUCTION. DIMENSIONS AND ELEVATIONS MUST BE VERIFIED WITH ARCHITECTURAL DRAWINGS. IN THE EVENT OF A CONFLICT, THE CONTRACTING OFFICER IS TO BE NOTIFIED IMMEDIATELY. DRAWING SCALES GIVEN ARE APPROXIMATE- DO
NOT SCALE PLANS OR DETAILS.
9. SEE ARCHITECTURAL DRAWINGS FOR THE FOLLOWING:
SIZE AND LOCATION OF ALL DOOR AND WINDOW OPENINGS.
SIZE AND LOCATION OF ALL INTERIOR AND EXTERIOR NON-BEARING PARTITIONS.
SIZE AND LOCATION OF ALL CONCRETE CURBS, EQUIPMENT PADS, PITS, FLOOR DRAINS, SLOPES AND
DEPRESSED AREAS, CHANGE IN LEVEL, CHAMFERS, GROOVES, INSERTS, ETC.
BUILDING SIZE AND LOCATION OF ALL FLOOR AND ROOF OPENINGS EXCEPT AS SHOWN.
BUILDING FLOOR AND ROOF FINISHES.
BUILDING DIMENSIONS NOT SHOWN ON STRUCTURAL DRAWINGS.
10. SEE BUILDING MECHANICAL, BUILDING PLUMBING AND BUILDING ELECTRICAL DRAWINGS AND
SPECIFICATIONS FOR THE FOLLOWING:
PIPE RUNS, SLEEVES, HANGERS, TRENCHES, WALL AND SLAB OPENINGS, ETC. EXCEPT AS SHOWN OR
NOTED.
ELECTRICAL CONDUIT RUNS, BOXES, OUTLETS IN WALL OR SLABS.
CONCRETE INSERTS FOR ELECTRICAL, MECHANICAL OR PLUMBING FIXTURES.
SIZE AND LOCATION OF MACHINE OR EQUIPMENT BASES AND ANCHOR BOLTS FOR MOTOR MOUNTS.
STRUCTURAL ABBREVIATIONS
@ AT
∠ ANGLE
ABV ABOVE
AB ANCHOR BOLT
AC ASPHALTIC CONCRETE
ACI AMERICAN CONCRETE INSTITUTE
ADDNL ADDITIONAL
ADJ ADJACENT
AFF ABOVE FINISH FLOOR
AGG AGGREGATE
AISC AMERICAN INSTITUTE FOR STEEL CONSTRUCTION
ALT ALTERNATE
ALUM ALUMINUM
APA THE ENGINEERED WOOD ASSOCIATION
APPROX APPROXIMATE
ARCH ARCHITECT/ARCHITECTURAL
ASTM AMERICAN SOCIETY FOR TESTING & MATERIALS
AWS AMERICAN WELDING SOCIETY
BEV BEVELED
BLW BELOW
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM
BN BOUNDARY NAILING/BOUNDARY FASTENING
BOC BOTTOM OF CONCRETE
BOF BOTTOM OF FOOTING
BOS BOTTOM OF STEEL
BOTT BOTTOM
BRBF BUCKLING-RESTRAINED BRACED FRAME
BRCG BRACING
BRG BEARING
BTW BETWEEN
BYD BEYOND
C CAMBER
CCR CALIFORNIA CODE OF REGULATIONS
CC CENTER TO CENTER
CE CIVIL ENGINEER
CG CENTER OF GRAVITY
CIP CAST-IN-PLACE
CJ CONSTRUCTION JOINT
CJP COMPLETE JOINT PENETRATION
CLG CEILING
CL CENTERLINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONSTR CONSTRUCTION
CONT CONTINUOUS
COORD COORDINATE/COORDINATION
CP COMPLETE PENETRATION
CRC COLD-ROLLED CHANNEL
CTR CENTER
CTRD CENTERED
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION
DEPR DEPRESSED
DF DOUGLAS FIR
DIA (Ø) DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DL DEAD LOAD
DLT DEEP LEG TRACK
DN DOWN
DO DUPLICATE ORDER
DSA DIVISION OF THE STATE ARCHITECT
DTL DETAIL
DWG DRAWING
(E) EXISTING CONDITION
EA EACH
EE EACH END
EJ EXPANSION JOINT
ELEV ELEVATION
EN EDGE NAILING/EDGE FASTENING
EOS EDGE OF SLAB
EOR ENGINEER OF RECORD
EQ (=) EQUAL
ES EACH SIDE
EW EACH WAY
EB EXPANSION BOLT
EQUIP EQUIPMENT
EXTR EXTERIOR
FAB FABRICATE
f'c MINIMUM ULTIMATE COMPRESSIVE STRENGTH
OF CONCRETE
FBC FLAT BAR COLLECTOR
FD FLOOR DRAIN
FF FINISH FLOOR
FFE FINISH FLOOR ELEVATION
FG FINISH GRADE
FHWS FLAT HEAD WOOD SCREW
FJ FLOOR JOIST
FIN FINISH
FLG FLANGE
FLR FLOOR
f'm MINIMUM ULTIMATE COMPRESSIVE STRENGTH
OF MASONRY
FN FIELD NAILING/FIELD FASTENING
FND FOUNDATION
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FOS FACE OF STUD
FRMG FRAMING
FRP FIBER REINFORCED POLYMER
FT (') FOOT/FEET
FTG FOOTING
Fy SPECIFIED YIELD STRENGTH OF REINFORCING, PSI OR SPECIFIED MINIMUM YIELD STRESS OF
STEEL, KSI
GA GAUGE
GALV GALVANIZED
GL GLUE LAMINATED LUMBER
GRD GRADE
GT GROUT
GWB GYPSUM WALLBOARD
HAS HEADED ANCHOR STUD
HC HANDICAP
HD HOLDOWN
HDG HOT-DIPPED GALVANIZED
HDR HEADER
HK HOOK
HORIZ HORIZONTAL
HT HEIGHT
HSB HIGH STRENGTH BOLT
HSS HOLLOW STRUCTURAL SECTION
ICBO INTERNATIONAL CONFERENCE OF BUILDING OFFICIALS
IBC INTERNATIONAL BUILDING CODE
ICC INTERNATIONAL CODE COUNCIL
ID INSIDE DIAMETER
IN (") INCH
INTR INTERIOR
INFO INFORMATION
JST JOIST
JT JOINT
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LG LONG
LGTH LENGTH
LONG LONGITUDINAL
LS LAG SCREW
LSL LAMINATED STRAND LUMBER
LT WT LIGHT WEIGHT
LVL LAMINATED VENEER LUMBER
LWC LIGHT WEIGHT CONCRETE
MAX MAXIMUM
MB MACHINE BOLT
MCJ MASONRY CONTROL JOINT
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL, PLUMBING
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MRD METAL ROOF DECK
MTL METAL
(N) NEW
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NO. (#) NUMBER OR POUNDS
NOM NOMINAL
NS&FS NEARSIDE & FARSIDE
NSG NON SHRINK GROUT
NTS NOT TO SCALE
NWC NORMAL WEIGHT CONCRETE
OC ON CENTER
OD OUTSIDE DIAMETER
OSB ORIENTED STRAND BOARD
OSHA OCCUPATIONAL SAFETY & HEALTH ADMINISTRATION
OSHPD OFFICE OF STATEWIDE HEALTH PLANNING &
DEVELOPMENT
OWSJ OPEN WEB STEEL JOIST
OPG OPENING
OPP OPPOSITE
OH OPPOSITE HAND
OVS OVERSIZED HOLE
PAF POWDER/POWER ACTUATED FASTENER
PCC PRECAST CONCRETE
PC PIPE COLUMN
PCF POUNDS PER CUBIC FOOT
PERP PERPENDICULAR
PEMB PRE-ENGINEERED METAL BUILDING
PJP PARTIAL JOINT PENETRATION
PL PLATE
PLF PER LINEAR FOOT
PLWD PLYWOOD
PN PERIMETER NAILING
PP PARTIAL PENETRATION
PSI POUNDS PER SQUARE INCH
PSF POUNDS PER SQUARE FOOT
PSL PARALLEL STRAND LUMBER
PTDF PRESSURE TREATED DOUG FIR
PT POINT
PV PHOTOVOLTAIC
PVC POLYVINYL CHLORIDE
R RADIUS
REINF REINFORCING/REINFORCEMENT
REQ REQUIRED
RJ ROOF JOIST
RR ROOF RAFTER
RSB RECESSED STUD BOLT
SAD SEE ARCHITECTURAL DRAWINGS
SC SLIP CRITICAL
SCBF SPECIAL CONCENTRIC BRACED FRAME
SCHED SCHEDULE
SDST SELF-DRILLING SELF-TAPPING
SE STRUCTURAL ENGINEER
SEIS JT SEISMIC JOINT
SEOR STRUCTURAL ENGINEER OF RECORD
SHT SHEET
SHTHG SHEATHING
SHRWL SHEARWALL
SIM SIMILAR
SJ SHRINKAGE JOINT
SLH SHORT LEG HORIZONTAL
SLRS SEISMIC LOAD RESISTING SYSTEM
SLV SHORT LEG VERTICAL
SM SHEET METAL
SMRF SPECIAL MOMENT RESISTING FRAME
SMS SHEET METAL SCREWS
SOG SLAB ON GRADE
SP STRUCTURAL PANELING
SPCG SPACING
SPEC SPECIFICATION
SQ SQUARE
SS STAINLESS STEEL
STAG STAGGER
STD STANDARD
STIFF STIFFENER
STL STEEL
STRUC STRUCTURAL
SYM SYMMETRICAL
T24 TITLE 24 CALIFORNIA CODE
tf FLANGE THICKNESS
THRD THREAD OR THREADED
THK THICK/THICKNESS
TN TOE NAIL
T.A. TOP OF
TOC TOP OF CONCRETE
TOF TOP OF FOOTING/TOP OF FRAMING
TOS TOP OF STEEL
TOW TOP OF WALL
TRAN TRANSVERSE
TS (SEE HSS)
TYP TYPICAL
T&B TOP & BOTTOM
T&G TONGUE & GROOVE
UBC UNIFORM BUILDING CODE
UNO UNLESS NOTED OTHERWISE
URM UNREINFORCED MASONRY
VERT VERTICAL
VIF VERIFY IN FIELD
W/ WITH
W/O WITHOUT
WDW WINDOW
WF WIDE FLANGE
WP WORK POINT
WRT WITH RESPECT TO
WS WOOD SCREW
WT WEIGHT/STRUCTURAL TEE
WWF WELDED WIRE FABRIC
S-001
S -0
Sheet
A
B
C
1 2 3 4
S C
R
IP
P S
D R
IV
E
S A
C R
A M
E N
TO
, C
A
A R
T
HUR ER NEST
RO
S
S
ST RUCT URA L
No. S2030
STA TE OF CA LIFORNIA
RE
G
IS
TE
RED PROFESS IONAL ENG
INEER
95% SUBMITTAL
S
TR
U C
TU
R
A L
G E
N E
R A
L N
O
TE
S
GENERAL:
IN ADDITION TO THE INSPECTIONS REQUIRED BY SECTION 110 OF THE 2012 IBC,
THE USACE SHALL EMPLOY A SPECIAL INSPECTOR TO PERFORM SPECIAL
INSPECTIONS & TESTS AS INDICATED ON THE STATEMENT OF SPECIAL
INSPECTIONS.
1. INSPECTORS: ALL TESTS AND INSPECTIONS SHALL BE PERFORMED BY AN
INDEPENDENT INSPECTION AGENCY WHICH IS IN THE EMPLOYMENT OF THE
USACE.
2. ALL SPECIAL INSPECTION & TESTING AGENCIES SHALL BE QUALIFIED PER
ASTM E329 AND APPROVED BY THE CONTRACTING OFFICER.
3. PROVIDE INSPECTION REPORTS TO CONTRACTING OFFICER WITHIN TWO
WEEKS OF PERFORMANCE INSPECTION OR TEST.
4. REFER TO CHAPTER 17 OF THE CODE FOR OTHER REQUIRED SPECIAL
INSPECTIONS AND TESTS NOT LISTED.
5. IT IS THE CONTRACTOR'S RESPONSIBILITY TO SEE THAT THE TESTS AND
INSPECTIONS ARE PERFORMED. JOB SITE VISITS BY THE CONTRACTING
OFFICER DO NOT CONSTITUTE AND ARE NOT A SUBSTITUTE FOR
INSPECTIONS.
6. WHERE THE CONTRACTOR CHOOSES TO USE AN APPROVED ALTERNATIVE
MEANS FOR FASTENING OR ANCHORING MATERIALS THAT REQUIRE
SPECIAL FIELD INSPECTION, SUCH AS FIELD WELDING, ADHESIVE OR
EXPANSION ANCHORS, ETC. ALL ADDITIONAL SPECIAL INSPECTION AND
TESTING COSTS SHALL BE PAID BY THE USACE AND DEDUCTED FROM THE
CONTRACT AMOUNT.
INSPECTION NOTES:DESIGN CRITERIA (2012 IBC):
OCCUPANCY
RISK CATEGORY .............................. II
LIVE LOADS
ROOF ..................................... 20.0 PSF (REDUCIBLE) TYP
FLOOR ................................... 50.0 PSF (REDUCIBLE) TYP UNO
PARTITION ................... 15.0 PSF TYP
CORRIDORS ........................... 100.0 PSF TYP
STORAGE ............................... 250 PSF TYP
SNOW LOADS
Pg = 0 PSF
LATERAL LOADS
WIND
EXPOSURE ............................................ C
WIND SPEED (ULTIMATE DESIGN) ......... 110 MPH (3 SEC GUST)
COMPONENTS & CLADDING (DEFERRED SUBMITTALS - CONTRACTOR
RESPONSIBLE FOR DESIGN)
WINDOW SYSTEMS ................................... 37.5 PSF
ROOF .......................................................... 71.0 PSF
CLADDING .................................................. 37.5 PSF
SEISMIC
DESIGN BASED ON THE 2012 IBC CHAPTER 16 & ASCE 7-10
SITE CLASS = D
SEISMIC DESIGN CATEGORY = D
MAPPED SEISMIC HAZARD PARAMETERS
Ss = 0.972 Fa = 1.1 SDS = 0.720 S1 = 0.328 Fv = 1.7 SD1 = 0.381
STEEL ORDINARY MOMENT FRAMES
I = 1.00 V = EQUIVALENT LATERAL FORCE PROCEDURE BASE
R = 3.50 SHEAR (STRENGTH DESIGN)
Ωo = 3.00 Cd = 3.00 V = CsW = 0.206W ρ = 1.30
STEEL ORDINARY CONCENTRIC BRACED FRAMES
I = 1.00 V = EQUIVALENT LATERAL FORCE PROCEDURE BASE
R = 3.25 SHEAR (STRENGTH DESIGN)
Ωo = 2.00 Cd = 3.25 V = CsW = 0.222W ρ = 1.00
WAREHOUSE BUILDING
SEISMIC DEMANDS ON NON-STRUCTURAL COMPONENTS
Fp = SEISMIC DESIGN FORCE (STRENGTH DESIGN) Fp = 0.4apSDSWp (1 + 2z
h) Wp (R / Ie) ap = 1.0 Rp = 2.5 Ip = 1.0
HORIZONTAL STRUCTURAL IRREGULARITIES: NONE
VERTICAL STRUCTURAL IRREGULARITIES: NONE
SEISMIC BASE LEVEL: GRADE LEVEL
STORY DRIFT
DEFORMATION COMPATIBILITY AS REQUIRED BY ASCE 7-10 SECTION 12.12.5
FOR USE IN CLADDING, STAIRS & OTHER NON-STRUCTURAL ELEMENTS
Δ = 3"
FLOOD DESIGN DATA
NONE APPLICABLE
SPECIAL LOADS
NONE APPLICABLE
WAREHOUSE BUILDING NOTES:
1. THE WAREHOUSE BUILDING NOTED ON THE DRAWINGS REQUIRES
ADDITIONAL DESIGN & DETAILING BY A FIRM SPECIALIZING IN THIS TYPE
OF WORK. SUBMITTALS, INCLUDING SHOP DRAWINGS AND
CALCULATIONS, SHALL BE PER THE SPECIFICATIONS.
2. THE WAREHOUSE BUILDING FOUNDATIONS & ANCHORAGE NOTED ON
THE DRAWINGS ARE FOR BIDDING PURPOSES ONLY. THE FOUNDATIONS
& ANCHORAGES SHALL BE REVIEWED & MODIFIED AS REQUIRED FOR
THE FINAL BUILDING REACTIONS BY A LICENSED CIVIL / STRUCTURAL
ENGINEER.
3. SPACE FRAMES SHALL BE DESIGNED AS "PIN" BASE.
4. SEE ARCH & MEP DWGS FOR THE LOCATION, MAGNITUDE & NATURE OF
ALL LOADS TO BE SUPPORTED & BRACED.
5. COORD DIMS OF PEMB COL BASES TO MATCH ARCH FINISH DTLS.
CONTRACTOR SHALL NOTIFY CONTRACTING OFFICER AT FOLLOWING STAGES OF
CONSTRUCTION AND PROVIDE ALL NECESSARY ACCESS AND ASSISTANCE TO
ALLOW THE CONTRACTING OFFICER TO PERFORM SITE OBSERVATION VISITS.
THESE VISITS DO NOT CONSTITUTE INSPECTION OF THE WORK. PROVIDE A
MINIMUM OF 2 BUSINESS DAYS NOTICE PRIOR TO REQUIRED TIME OF VISIT.
[ ] PRIOR TO FOUNDATION CONCRETE POUR(S)
[ ] PRIOR TO CONCRETE SLAB ON GRADE CONCRETE POUR(S)
[ ] STRUCTURAL FRAME 50% COMPLETE
[ ] STRUCTURAL FRAME 100% COMPLETE
[ ] PRIOR TO COVERING PLYWOOD SHEATHING AT WALLS
[ ] PRIOR TO COVERING PLYWOOD SHEATHING AT ROOF/FLOORS
PERIODIC STRUCTURAL OBSERVATION:
DESIGN CRITERIA (2012 IBC):
OCCUPANCY
RISK CATEGORY .............................. II
LIVE LOADS
ROOF ..................................... 20.0 PSF (REDUCIBLE) TYP
FLOOR ................................... 50.0 PSF (REDUCIBLE) TYP UNO
PARTITION ................... 15.0 PSF TYP
CORRIDORS ........................... 100.0 PSF TYP
STORAGE ............................... 100 PSF TYP
SNOW LOADS
Pg = 0 PSF
LATERAL LOADS
WIND
EXPOSURE ............................................ C
WIND SPEED (ULTIMATE DESIGN) ......... 110 MPH (3 SEC GUST)
SEISMIC
V = EQUIVALENT LATERAL FORCE PROCEDURE BASE SHEAR
(STRENGTH DESIGN)
V = CsW = 0.111W
Cs = SDS = 0.111 (R/Ie)
BASIC SEISMIC-FORCE-RESISTING SYSTEM:
LIGHT FRAME WOOD WALLS SHEATHED W/
WOOD STRUCT PANELS.
R = 6.5 SITE CLASS = D
Ie = 1.0 Ss = 0.972 Fa = 1.1 SDS = 0.720
Ωo = 3.0 S1 = 0.328 Fv = 1.7 SD1 = 0.381 ρ = 1.3
Cd = 4.0 SEISMIC DESIGN CATEGORY = D
ADMINISTRATION BUILDING
S-002
S
Sheet
A
B
C
1 2 3 4
S C
R
IP
P S
D R
IV
E
S A
C R
A M
E N
TO
, C
A
A R
T
HUR ER NEST
RO
S
S
ST RUCT URA L
No. S2030
STA TE OF CA LIFORNIA
RE
G
IS
TE
RED PROFESS IONAL ENG
INEER
95% SUBMITTAL
S
TR
U C
TU
R
A L
G E
N E
R A
L N
O
TE
S
FOUNDATIONS:
1. REFER TO RECOMMENDATIONS IN SOILS REPORT, PROJECT NO.
363-KAS-COE-TO3 BY GENTERRA CONSULTANTS, INC., DATED JUNE 15, 2015.
ALLOWABLE SOIL BEARING PRESSURE FOR FOUNDATION IS 2500 PSF (DL +
LL) AND 3333 PSF (DL + LL + SEISMIC OR WIND).
2. ALL SITEWORK AND GRADING SHALL BE DONE IN COMPLIANCE WITH THE
SOILS REPORT AND THE SPECIFICATIONS.
3. SOILS ENGINEER SHALL VERIFY CONDITION AND/OR ADEQUACY OF ALL
FOUNDATION EXCAVATIONS PRIOR TO PLACEMENT OF CONCRETE.
4. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO SHORE AND
BRACE AS REQUIRED. SEE SAFETY NOTES FOR ADDITIONAL INFORMATION.
5. ALL FOUNDATIONS ARE SHOWN AND DIMENSIONED AS BEING FORMED.
FOUNDATIONS MAY BE PLACED IN NEAT EXCAVATIONS PROVIDED
FOOTINGS ARE INCREASED 2" IN WIDTH, SEE TYPICAL UNFORM FOOTING
DETAIL.
6. EXCAVATIONS SHALL BE CLEANED OF ALL DEBRIS AND LOOSE SOIL.
STANDING WATER SHALL BE REMOVED PRIOR TO CONCRETE PLACEMENT.
7. FOUNDATION DEPTHS INDICATED ON PLANS ARE MINIMUMS BASED OFF OF
THE SOILS REPORT MENTIONED ABOVE, AND ARE FOR ESTIMATING
PURPOSES. FINAL DEPTHS OF FOOTINGS MAY CHANGE AT THE TIME OF
EXCAVATION BY THE SOILS ENGINEER.
8. BOTTOMS OF ALL FOUNDATIONS SHALL BE LEVEL. CHANGES IN BOTTOM OF
FOUNDATION ELEVATION SHALL BE MADE ACCORDING TO STEPPED
FOOTING DETAILS.
9. FOOTINGS SHALL BE CENTERED UNDER WALLS AND/OR COLUMNS UNLESS
OTHERWISE INDICATED ON DRAWINGS.
10. CONTRACTOR SHALL CHECK FOOTING FORMS TO VERIFY THAT THEY ARE
SQUARE & PLUMB. THE CONTRACTOR SHALL ALSO VERIFY THAT ALL
INSERTS & EMBEDS ARE IN THEIR CORRECT LOCATION & ORIENTATION
PRIOR TO PLACING CONCRETE.
11. NOTIFY THE STRUCTURAL ENGINEER 48 HOURS IN ADVANCE OF PLACING
CONCRETE.
1. CONCRETE CONSTRUCTION SHALL CONFORM TO THE CODE PER GENERAL NOTES.
2. CONCRETE SHALL BE PLACED IN ACCORDANCE WITH ASTM C94 AND ACI STANDARD 304. IN
ADDITION, MAXIMUM FREE FALL OF CONCRETE SHALL BE 4'-0".
3. ALL CONCRETE SHALL BE THOROUGHLY CONSOLIDATED BY SUITABLE MEANS DURING
PLACEMENT AND SHALL BE THOROUGHLY WORKED AROUND REINFORCEMENT AND
EMBEDDED FIXTURES AND INTO CORNERS OF FORMS.
4. THE MINIMUM 28 DAY STRENGTH SHALL BE PER MIX DESIGN SCHEDULE.
5. CEMENT SHALL CONFORM TO ASTM C150, TYPE I OR II.
6. CONCRETE AGGREGATES:
A. NATURAL SAND AND ROCK AGGREGATES SHALL CONFORM TO ASTM C33.
B. LIGHTWEIGHT AGGREGATES SHALL CONFORM TO ASTM C330.
7. MINERAL ADMIXTURES SHALL COMPLY WITH ASTM C618 CLASS F.
8. LIQUID ADMIXTURES SHALL COMPLY WITH THE FOLLOWING:
A. WATER REDUCERS . . . . . . . . . . . . . . . . . . . ASTM C494 TYPE A
B. MID-RANGE WATER REDUCERS . . . . . . . . ASTM C494 TYPE A & F
C. NON-CHLORIDE ACCELERATORS . . . . . . . ASTM C494 TYPE C OR C & E
D. RETARDING ADMIXTURES . . . . . . . . . . . . . ASTM C494 TYPE B OR B & D
9. GENERAL:
A. NO PIPES OR DUCT SHALL BE PLACED IN CONCRETE SLABS OR WALLS UNLESS
SPECIFICALLY DETAILED.
B. REFER TO ARCHITECTURAL, STRUCTURAL AND MECHANICAL DRAWINGS FOR ALL
MOULDS, GROOVES, ORNAMENTS, CLIPS, ETC. TO BE CAST IN CONCRETE.
10. ALL CONSTRUCTION JOINTS SHALL BE CONSTRUCTED IN ACCORDANCE WITH ACI 318
SECTION 6.4 AND THE TYPICAL CONSTRUCTION JOINT DETAILS SHOWN ON THE
STRUCTURAL DRAWINGS. ALL SURFACES OF CONSTRUCTION JOINTS SHALL BE CLEANED TO
REMOVE DUST, CHIPS, OR OTHER FOREIGN MATTER PRIOR TO PLACING THE ADJACENT
CONCRETE. THE CONTRACTOR SHALL SUBMIT THE PROPOSED LOCATIONS OF
CONSTRUCTION JOINTS TO THE ENGINEER FOR REVIEW BY THE STRUCTURAL ENGINEER
BEFORE STARTING CONSTRUCTION.
11. MAXIMUM SPACING OF CONSTRUCTION OR CONTROL JOINTS FOR A REINFORCED SLAB ON
GRADE OR ELEVATED SLAB OVER METAL DECK SHALL BE 20'-0" OC.
12. REMOVE ALL DEBRIS AND EXCESS WATER FROM THE FORMS BEFORE PLACING ANY
CONCRETE.
13. REINFORCING, DOWELS, BOLTS, ANCHORS, SLEEVES, ETC. TO BE EMBEDDED IN CONCRETE
SHALL BE SECURELY POSITIONED AND FREE OF EXCESSIVE SCALE, RUST, DIRT, GREASE,
OIL OR ANY OTHER SUBSTANCES THAT WILL IMPAIR BOND WITH CONCRETE. OBTAIN
APPROVAL OF ALL AFFECTED TRADES PRIOR TO PLACING CONCRETE.
14. WALLS SHALL BE PLACED IN HORIZONTAL LAYERS OF 2'-0" MAXIMUM DEPTH.
15. CONCRETE IN WALLS, PIERS OR COLUMNS SHALL SET AT LEAST 2 HOURS BEFORE PLACING
CONCRETE IN BEAMS, SPANDRELS OR SLABS SUPPORTED THEREON.
16. NO WOOD SPREADERS ALLOWED. NO WOOD STAKES ALLOWED IN AREAS TO BE
CONCRETED.
17. CONTRACTOR SHALL PREPARE AND SUBMIT CONCRETE MIX DESIGNS PER THE
SPECIFICATIONS FOR REVIEW PRIOR TO PLACEMENT OF ANY CONCRETE. CONCRETE MIX
DESIGNS SHALL BE PER ACI 318 CHAPTER 5. CALCIUM CHLORIDE OR ADMIXTURES WHICH
ADD CHLORIDES ARE NOT PERMITTED.
18. CAST-IN-PLACE CONCRETE (NON-PRESTRESSED). THE FOLLOWING MINIMUM CONCRETE
COVER SHALL BE PROVIDED FOR REINFORCEMENT:
A. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH . . . . . . 3"
B. CONCRETE EXPOSED TO EARTH OR WEATHER:
NO. 6 THROUGH NO. 11 BAR . . . . . . . . . . . . . . . . . . . . . . . . . . 2"
NO. 5 BAR, W31 OR D31 WIRE, AND SMALLER
2"
FOOTNOTES:
1. ADD WATER REDUCING ADMIXTURES PER SPECIFICATIONS FOR PLACING.
2. FOR HOT WEATHER CONCRETING REFER TO ACI 305R.
3. FOR COLD WEATHER CONCRETING REFER TO ACI 306R.
4. OTHER ADMIXTURES SHALL BE REVIEWED BY THE ENGINEER OF RECORD AND TESTING
LABORATORY UPON CONCRETE MIX DESIGN SUBMITTAL.
5. SLUMPS SHALL NOT EXCEED 8"±11
2" WHEN USING MID-RANGE WATER REDUCERS.
6. ADDITIONAL WATER SHALL NOT BE ADDED TO THE CONCRETE ONCE THE TRUCK LEAVES THE
BATCH PLANT.
7. MIX DESIGN SHALL NOT BE PROPORTIONED WITHOUT FIELD EXPERIENCE OR TRIAL MIXTURES
PER ACI 318, SECTION 5.3 WHEN USING MORE THAN 15% FLY ASH REPLACEMENT BY WEIGHT.
CONCRETE:
MIX DESIGN SCHEDULE
TYPE USE CLASS
STRENGTH
"f'c" MIN AT
28 DAYS
(PSI)
CONCRETE
UNIT
WEIGHT
(PCF)
MAX
AGGREGATE
SIZE (IN)
MAX
SLUMP
(IN)
MAX (5)
WATER TO
CEMENT
RATIO (%)
FLY ASH (7)
REPLACEMENT
A SLAB ON
GRADE 4000 150 1" ±1
4" 4" ±1" 0.40 15% MIN
25% MAX
B FOUNDATIONS /
WALLS 3000 150 1" ±1
4" 4" ±1" 0.50 15% MIN
25% MAX
19. A. ALL BARS SHALL HAVE A CLASS B MINIMUM SPLICE LAP UNLESS OTHERWISE NOTED.
SEE REINFORCEMENT LAP SPLICES TABLE.
B. SPLICES IN ADJACENT BARS SHALL BE NOT LESS THAN 5'-0" APART. UNO.
C. DOWEL ALL VERTICAL REINFORCING IN WALLS AND COLUMNS FROM FOUNDATION WITH
THE SAME SIZE REINFORCING. UNO.
D. SPLICE CONTINUOUS BARS IN SPANDRELS, GRADE BEAMS, WALL BEAMS, ETC. AS
FOLLOWS: TOP BARS AT MID-SPAN, BOTTOM BARS AT CENTERLINE SUPPORT UNO.
20. HORIZONTAL WALL REINFORCING IN DOUBLE LAYER WALLS SHALL BE STAGGERED. USE #2
SPREADERS APPROXIMATELY EVERY THIRD INTERSECTION EACH DIRECTION FOR ALL
DOUBLE LAYER WALLS.
21. MINIMUM WALL REINFORCING SHALL BE:
WALL THICKNESS SINGLE LAYER DOUBLE LAYER
7" OR LESS . . . . . . . . . . . . . #4 @ 12" OC EA WAY
8" . . . . . . . . . . . . . . . . . . . . . #4 @ 10" OC EA WAY
9" & 10" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . #4 @ 16" OC EA WAY 11" & 12" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . #4 @ 12" OC EA WAY
22. REINFORCING STEEL SHALL BE DETAILED, FABRICATED AND INSTALLED IN ACCORDANCE
WITH ACI 315. SEE REINFORCING STEEL NOTES FOR ADDITIONAL REQUIREMENTS.
23. FINAL PRODUCT AS INDICATED ON DRAWINGS SHALL COMPLY WITH THE FOLLOWING:
A. ALL CONCRETE SHALL HAVE A "CLASS B" FINISH PER ACI 347 WITH GRADUAL
IRREGULARITIES LIMITED TO 14" IN 5'-0" AS MEASURED WITH A STRAIGHT EDGE.
B. SURFACE IRREGULARITIES ATTRIBUTABLE TO PLACEMENT AND CONSOLIDATION
DEFICIENCIES AS DEFINED IN ACI 309.2R (E.G., BUG HOLES, HONEYCOMB, ETC.)
WILL BE REVIEWED BY THE ARCHITECT AND ENGINEER. UNSATISFACTORY WORK SHALL BE
REPAIRED AT THE CONTRACTOR'S EXPENSE.
C. GRADUAL SURFACE IRREGULARITIES SHALL NOT BE CUMULATIVE.
REINFORCING STEEL
1. REINFORCING SHALL CONFORM TO ASTM A615 - GRADE 60 UNLESS NOTED
OTHERWISE.
2. NO REINFORCING BARS ARE TO BE WELDED UNLESS SPECIFICALLY
DETAILED IN CONTRACT DOCUMENTS. ALL BARS SO DETAILED TO BE
WELDED SHALL BE ASTM A706 BARS.
3. WIRE FABRIC SHALL CONFORM TO ASTM A185. WELDED WIRE FABRIC SHALL
BE LAP SPLICED TWO SQUARES MINIMUM EACH DIRECTION.
4. REINFORCING, DOWELS, BOLTS, ANCHORS, SLEEVES, ETC. TO BE
EMBEDDED SHALL BE SECURELY POSITIONED BEFORE PLACING CONCRETE
OR GROUTING MASONRY. OBTAIN APPROVAL OF ALL AFFECTED TRADES
PRIOR TO PLACING CONCRETE.
5. SEE DTL B2 / S-501 FOR TYPICAL REBAR BENDS.
FOOTNOTES:
1. TABLE ABOVE BASED ON UNCOATED REINFORCING.
2. TOP REINFORCING IS HORIZONTAL REINFORCEMENT THAT HAS MORE
THAN TWELVE INCHES OF FRESH CONCRETE CAST BELOW IT.
3. FOR BARS WITH COVER LESS THAN 1 BAR DIAMETER OR WITH CLEAR
SPACING LESS THAN 2 BAR DIAMETERS, INCREASE LAP SPLICE BY 50%.
4. FOR LIGHTWEIGHT AGGREGATE CONCRETE, (WT = 110 PCF) INCREASE
LAP SPLICE BY 30%.
5. ALL LAP SPLICES SHALL BE CLASS B, UNO.
B
A
B
A
REINFORCEMENT SIZE (GR60, UNO)
TOP
TOP
OTHER
#3
#5
#4
#6
TOP
OTHER
TOP
OTHER 16
#3
37 56
#5
#4
#6
#10
#7
#8
#9
#11
#10
#7
#8
#9
#11
LAP SPLICE LENGTHS
REINFORCEMENT
REINFORCEMENT
LOCATION
SPLICE
CLASS
REINFORCEMENT
LOCATION
SPLICE
CLASS
REINFORCEMENT SIZE (GR60, UNO)
OTHER
f'c = 4000 PSI AT 28 DAYS f'c = 3000 PSI AT 28 DAYS
(IN INCHES)
S-003
S
Sheet
A
B
C
1 2 3 4
S C
R
IP
P S
D R
IV
E
S A
C R
A M
E N
TO
, C
A
A R
T
HUR ER NEST
RO
S
S
ST RUCT URA L
No. S2030
STA TE OF CA LIFORNIA
RE
G
IS
TE
RED PROFESS IONAL ENG
INEER
95% SUBMITTAL
S
TR
U C
TU
R
A L
G E
N E
R A
L N
O
TE
S
STRUCTURAL STEEL:
1. FABRICATION, ERECTION AND MATERIALS SHALL CONFORM WITH;
A. AISC 360-10 "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS"
B. AISC 341-10 "SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS"
C. 2012 IBC
2. STRUCTURAL STEEL SHAPES AND CONNECTORS SHALL CONFORM TO THE FOLLOWING:
A. WIDE FLANGE . . . . . . . . . . . . . . . . . . ASTM A992, GRADE 50 (Fy = 50 KSI)
B. HOLLOW STRUCTURAL SECTION
ASTM A500, GRADE C
RECTANGULAR: (Fy = 50 KSI) ROUND: (Fy = 46 KSI)
C. PIPE COLUMNS . . . . . . . . . . . . . . . . . ASTM A53, TYPES E OR S, GRADE B (Fy = 35 KSI)
D. PLATES, ANGLES, CHANNELS, BARS & MISCELLANEOUS SHAPES
. . . . . . . . . . . . . . ASTM A36
E. MOMENT FRAME CONTINUITY PLATES, STIFFENER PLATES, SHEAR PLATES AT
BEAM/COLUMN CONNECTIONS AND BASE PLATES
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASTM A572, GRADE 50
F. MACHINE BOLTS . . . . . . . . . . . . . . . . ASTM A307
G. HIGH STRENGTH BOLTS (HSB) . . . . ASTM A325-N (UNO)
H. WELDED HEADED STUDS . . . . . . . . . ASTM A108, GRADE 1010 THRU 1020
I. HARDENED STEEL WASHERS . . . . . ASTM F436
J. ANCHOR BOLTS . . . . . . . . . . . . . . . . ASTM F1554 GRADE 36 UNO (HEADED OR LOCKNUT)
3. SPLICING STRUCTURAL MEMBERS WHERE NOT DETAILED ON THE DRAWING IS PROHIBITED
WITHOUT PRIOR APPROVAL OF THE STRUCTURAL ENGINEER.
4. EXCEPT AS OTHERWISE NOTED, ALL BOLTS SHALL BE MACHINE BOLTS.
5. FOR ALL HIGH STRENGTH BOLTS, HARDENED WASHERS SHALL BE PROVIDED UNDER THE
TURNING ELEMENT OF BOLT FOR TORQUING AS REQUIRED.
6. HOLES FOR MACHINE BOLTS SHALL BE DRILLED AND OF THE SAME NOMINAL DIAMETER AS
THE BOLT PLUS 116".
7. COLUMN BASE PLATE ANCHOR BOLT HOLES MAY BE OVERSIZED IN ACCORDANCE WITH AISC
360-10 SECTION J9 AND TABLE 14-2 OF THE 14TH EDITION OF THE STEEL CONSTRUCTION
MANUAL, WITH HEAVY HEX NUTS OR PLATE WASHERS UNDER BASE PLATE.
8. USE STANDARD AISC GAGE AND PITCH FOR BOLTS EXCEPT AS OTHERWISE NOTED.
9. "SLIP CRITICAL" BOLTED CONNECTIONS:
A. "SLIP CRITICAL" CONNECTIONS (A325SC DESIGN VALUES WITH SPECIAL INSPECTION)
ARE REQUIRED AT ALL LATERAL FRAME LINES, SEISMIC LOAD RESISTING SYSTEM
COMPONENTS, AND ALL BOLTS IN OVERSIZED OR SLOTTED HOLES.
B. THE SPECIAL INSPECTOR MUST BE PRESENT DURING THE ENTIRE INSTALLATION AND
TIGHTENING OPERATION OF "SLIP CRITICAL" CONNECTIONS.
10. ALL WELDING IS TO BE DONE BY CERTIFIED WELDERS USING E70XX ELECTRODES (UNO). THE USE OF E70-T4 WELDING WIRE IS NOT ALLOWED FOR ANY APPLICATION. ALL WELDS SHALL BE
IN CONFORMITY WITH THE PROJECT SPECIFICATIONS AND STRUCTURAL WELDING CODE-
STEEL OF THE AMERICAN WELDING SOCIETY (AWS D1.1 LATEST REVISION).
11. WELD LENGTHS CALLED FOR ON PLANS ARE THE NET EFFECTIVE LENGTH REQUIRED. WHERE FILLET WELD SYMBOL IS GIVEN WITHOUT INDICATION OF SIZE, USE MINIMUM SIZE WELDS AS SPECIFIED IN AISC 360-10, SECTION J2.2b.
12. ALL STRUCTURAL STEEL SURFACES THAT ARE ENCASED IN CONCRETE, OR SPRAY-ON
FIREPROOFING, SHALL BE LEFT UNPAINTED. DO NOT PAINT THE TOP OF BEAMS & GIRDERS
TO RECEIVE STEEL DECK OR OTHER WELDED ATTACHMENTS.
13. ALL EXPOSED STRUCTURAL STEEL AND MISCELLANEOUS METAL SHALL BE HOT-DIP
GALVANIZED AFTER FABRICATION.
14. ALL ENDS OF EXTERIOR TUBE STEEL AND PIPE SHALL BE CAPPED WITH A 14" PLATE AND
WELDED CONTINUOUSLY TO SEAL.
15. PROVIDE 3" MINIMUM CONCRETE COVERAGE ON ALL STEEL BELOW GRADE.
16. ALL STRUCTURAL STEEL SHALL BE ERECTED PLUMB AND TRUE TO LINE. TEMPORARY
BRACING SHALL BE INSTALLED AND SHALL BE LEFT IN PLACE UNTIL OTHER MEANS ARE
PROVIDED TO ADEQUATELY BRACE THE STRUCTURE.
17. NON-SHRINK GROUT: A PRE-MIXED NON-METALLIC FORMULA WITH NO CHLORIDES HAVING
THE FOLLOWING CHARACTERISTICS:
A. FLOWABLE MIX AT TIME OF PLACEMENT
B. NO SHRINKAGE AFTER PLACEMENT
C. COMPRESSIBLE STRENGTH OF 5000 PSI (MINIMUM) AT 7 DAYS
D. CONFORMS TO ASTM C1107 (GRADE C)
S-004
S
Sheet
A
B
C
1 2 3 4
S C
R
IP
P S
D R
IV
E
S A
C R
A M
E N
TO
, C
A
A R
T
HUR ER NEST
RO
S
S
ST RUCT URA L
No. S2030
STA TE OF CA LIFORNIA
RE
G
IS
TE
RED PROFESS IONAL ENG
INEER
95% SUBMITTAL
S
TR
U C
TU
R
A L
G E
N E
R A
L N
O
TE
S
1. ALL STRUCTURAL WOOD SHALL CONFORM WITH THE FOLLOWING SPECIFICATIONS:
DOUGLAS FIR-COAST REGION . . . . . WEST COAST LUMBER INSPECTION BUREAU
GRADING RULES #17.
REDWOOD . . . . . . . . . . . . . . . . STANDARD SPECIFICATIONS FOR GRADES OF
CALIFORNIA REDWOOD LUMBER.
GLUED LAMINATED BEAMS . . . . . . . . STANDARD SPECIFICATION FOR STRUCTURAL
GLUED LAMINATED TIMBER, AITC 117.
PLYWOOD . . . . . . . . . . . . . . . . APA VOLUNTARY PRODUCT STANDARD PS 1-07
& PS 2-04 FOR SOFTWOOD PLYWOOD.
ORIENTED STRAND BOARD (OSB) . . . . APA STANDARD PRP-108 & PS 2-04
ENGINEERED LUMBER . . . . . . . . . . WEYERHAEUSER SPECIFICATIONS
LAMINATED VENEER LUMBER (LVL) PER ICC EVALUATION SERVICE INC.,
PARALLEL STRAND LUMBER (PSL) EVALUATION REPORT ESR 1387 OR APPROVED
& LAMINATED STRAND LUMBER (LSL) EQUAL
2. MINIMUM GRADES SHALL BE:
STRUCTURAL FRAMING (SF) . . . . . . . DF #1 TYPICAL EXCEPT:
CEILING JOISTS DF #2
ALL MEMBERS TO BE FREE OF HEART
CENTER. TYPICAL UNO.
GLUED LAMINATED MEMBERS (GL) . . . COMBINATION 24F-V4 SPECIES DF/DF
FOR SIMPLE SPANS
AND COMBINATION 24F-V8 SPECIES DF/DF
FOR CANTILEVERS
AND CONTINUOUS CONDITIONS.
STRUCTURAL PLYWOOD (SP) . . . . . . WALL PLYWOOD: 12" APA RATED SHEATHING,
5 PLY, 32
16 SPAN RATING,
STRUCTURAL 1, UNO.
ROOF PLYWOOD: 5 8" APA RATED SHEATHING,
5 PLY, 32
16 SPAN RATING,
STRUCTURAL 1, UNO.
ORIENTED STRAND BOARD (OSB) . . . . WALLS: 12" APA RATED SHEATHING,
16 SPAN RATING, STRUCTURAL 1, UNO
ROOF: 5 8" APA RATED SHEATHING,
16 SPAN RATING, STRUCTURAL 1, UNO.
PARALLEL STRAND LUMBER (PSL) . . . SHALL MEET THE FOLLOWING STRUCTURAL
PROPERTIES:
Fb = 2900 PSI Fv = 290 PSI
E = 2.0E6 PSI
LAMINATED VENEER LUMBER (LVL) . . . SHALL MEET THE FOLLOWING STRUCTURAL
PROPERTIES:
Fb = 2600 PSI Fv = 285 PSI
E = 1.9E6 PSI
LAMINATED STRAND LUMBER (LSL) . . . SHALL MEET THE FOLLOWING STRUCTURAL
PROPERTIES:
Fb = 2900 PSI Fv = 400 PSI
E = 1.7E6 PSI
3. WALLS SHALL HAVE DOUBLE TOP PLATES, LAPPED AT WALL AND PARTITION INTERSECTION WITH 3- 16d NAILS. SPLICE UPPER AND LOWER PLATES AS SHOWN IN TYPICAL WALL FRAMING DETAIL.
4. PROVIDE SOLID BLOCKING BETWEEN JOISTS OR RAFTERS AT ALL SUPPORTS (8'-0" OC MAX, SEE
BRIDGING DETAIL).
5. WHEN TOP PLATES ARE NOTCHED OR BORED, SEE TYPICAL DETAIL.
6. ALL BOLTS AND LAG SCREWS SHALL COMPLY WITH THE 2012 NATIONAL DESIGN SPECIFICATION FOR
WOOD CONSTRUCTION (ANSI/NFoPA NDS-2012).
7. HOLES FOR BOLTS IN WOOD SHALL BE BORED WITH A BIT OF THE SAME NOMINAL DIAMETER AS THE
BOLT + 116".
8. HOLES FOR LAG SCREWS SHALL BE FIRST BORED TO THE SAME NOMINAL DIAMETER AND DEPTH AS
THE SHANK. THE REMAINDER OF THE HOLE SHALL BE NO LARGER THAN THE ROOT OF THE THREAD.
9. LAG SCREWS AND WOOD SCREWS SHALL BE SCREWED AND NOT DRIVEN INTO PLACE.
10. ALL BOLTS AND LAG SCREWS SHALL BE PROVIDED WITH METAL WASHERS UNDER HEADS AND NUTS
WHICH BEAR ON WOOD. APPLIES ALSO TO POST-INSTALLED ANCHORS.
11. ALL BOLTS AND LAG SCREWS SHALL BE TIGHTENED AT TIME OF INSTALLATION AND RE-TIGHTENED
BEFORE CLOSING IN OR AT COMPLETION OF JOB.
12. INSTALL ALL STRUCTURAL PLYWOOD ON ROOF AND FLOORS WITH FACE GRAIN PERPENDICULAR TO
SUPPORTS.
13. CROSS BRIDGING BETWEEN JOISTS OR RAFTERS, SEE FRAMING PLANS AND TYPICAL DETAIL.
14. JOISTS UNDER AND PARALLEL TO NON-BEARING PARTITIONS SHALL BE DOUBLED AND NAILED
TOGETHER.
4"Ø 5"Øx5
8" 5"x5"x1 2"
2"Ø 21
2"Øx1 4" 2"x2"x1
4" 1 2"Ø 3
4" (2" OD)
8"Ø 23 4"Øx5
16" 21 2"x21
2"x1 4" 5
8"Ø 7 8" (21
4" OD)
4"Ø 3"Øx7 16" 3"x3"x5
16" 3 4"Ø 1" (21
2" OD)
8"Ø 31 2"Øx7
16" 31 2"x31
2"x3 8" 7
8"Ø 13
8" (3" OD)
1"Ø 4"Øx1 2" 33
4"x33 4"x3
8" 1"Ø 11 2" (31
4" OD)
MALLEABLE
IRON WASHERBOLT-DIA STEEL WASHER
CARRIAGE
BOLT-DIA
WROUGHT
IRON WASHER
CONTINUOUS BLOCKING
15. WHERE FRAMING HANGERS ARE REQUIRED AND ARE NOT SHOWN ON SECTIONS, DETAILS OR
PLANS THE FOLLOWING SIMPSON HANGERS SHALL BE USED. SLOPE, SKEW, TURN IN FLANGES AND
PROVIDE TOP FLANGE HANGERS AS REQUIRED.
2x & 3x MEMBERS . . . . . . . . U HANGERS 4x MEMBERS . . . . . . . . . . . . HU HANGERS 6x MEMBERS . . . . . . . . . . . . HUTF HANGERS
I-JOIST MEMBERS . . . . . . . . MIT HANGERS
GLU LAM MEMBERS . . . . . . . LEG HANGERS
16. ALL METAL HARDWARE SHALL BE MANUFACTURED BY SIMPSON STRONG-TIE COMPANY, OR
APPROVED EQUAL. ALL ITEMS SHALL BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS TO
THE MAXIMUM CAPACITY.
17. WOOD SYMBOLS:
18. PROVIDE PLYWOOD/OSB EDGE NAILING AROUND ALL OPENINGS AND BLOCK ALL UNSUPPORTED
PLYWOOD/OSB EDGES.
19. UPSET THREADS ON SILL BOLTS ARE NOT ALLOWED.
20. ALL FRAMING LUMBER SHALL HAVE A MAXIMUM MOISTURE CONTENT OF 19% AT THE TIME OF
INSTALLATION AND SHALL BE AT 19% MAXIMUM MOISTURE CONTENT (VERIFIED BY CONTRACTOR)
BEFORE BEING ENCLOSED BY INSULATION, GYPSUM BOARD, OR OTHER SURROUNDING
ARCHITECTURAL MATERIALS. THE CONTRACTOR SHALL TAKE ALL MEASURES NECESSARY TO
PROVIDE LUMBER MEETING THESE CRITERIA.
21. BOLTS ARE NOT TO BE INSTALLED IN LUMBER OVER 19% MOISTURE CONTENT.
22. EDGE NAILING OF STRUCTURAL WALL SHEATHING TO THE SILL PLATE SHALL NOT OCCUR UNTIL
ROOF FRAMING AND SHEATHING IS COMPLETE.
23. ALL FASTENERS INTO PRESSURE TREATED WOOD SHALL BE HOT-DIPPED GALVANIZED.
24. ALL WOOD MEMBERS IN DIRECT CONTACT WITH CONCRETE OR MASONRY SHALL BE
PRESSURE-PRESERVATIVE TREATED.
25. GLUED LAMINATED MEMBERS:
A. ALL SIMPLE SPAN FLOOR BEAMS AND WALL HEADERS SHALL HAVE 3500 FT RADIUS CAMBER
UNO. ALL SIMPLE SPAN ROOF BEAMS SHALL HAVE 1600 FT RADIUS CAMBER UNO.
B. ALL GLUED LAMINATED MEMBERS SHALL HAVE A MAXIMUM MOISTURE CONTENT OF 16%.
C. SPECIAL INSPECTION OF GLUED LAMINATED BEAMS SHALL BE IN ACCORDANCE WITH IBC
SECTION 2303.1.3. SPECIAL INSPECTION IS NOT REQUIRED FOR NON-CUSTOM MEMBERS OF
8 INCH MAXIMUM WIDTH AND 18 INCH MAXIMUM DEPTH, AND WITH A MAXIMUM CLEAR SPAN
OF 32 FEET, MANUFACTURED AND MARKED IN ACCORDANCE WITH ANSI/AITC A190.1 SECTION
6.1.1 FOR NON-CUSTOM MEMBERS.
D. SUBMIT SHOP DRAWINGS PRIOR TO FABRICATION OF GLUED LAMINATED MEMBERS. SHOP
DRAWINGS SHALL INDICATE BEAMS AS SIMPLE OR CONTINUOUS.
E. APPEARANCE OF MEMBERS SHALL BE FRAMING OR INDUSTRIAL APPEARANCE EXCEPT
MEMBERS IN EXPOSED ARCHITECTURAL APPLICATIONS SHALL BE ARCHITECTURAL
APPEARANCE UNO.
F. COMPLY WITH AITC 111 FOR PROTECTION DURING SHIPPING AND FIELD HANDLING.
G. SHADED AREAS BELOW SHALL HAVE A 6" MINIMUM JOINT SPACING IN ADJACENT
LAMINATIONS.
TENSION ZONE
TENSION ZONE =
TOP & BOTTOM, FULL LENGTH
8 DEPTH + 1 LAM1
8 DEPTH + 1 LAM
NAILING NOTES & SCHEDULE:
1. ALL NAILS FOR STRUCTURAL WORK SHALL BE COMMON STEEL WIRE NAILS
COMPLYING WITH SECTION 2303.6. HOLES SHALL BE PRE-DRILLED WHERE
NECESSARY TO PREVENT SPLITTING. NAILING NOT NOTED IN SCHEDULE, ON
DRAWINGS, OR IBC TABLE 2304.9.1 SHALL BE A MINIMUM OF TWO NAILS AT
EACH CONTACT:
8d FOR 1x MATERIAL AND 16d FOR 2x MATERIAL.
2. FASTENERS USED IN WET OR EXTERIOR LOCATIONS, INCLUDING EXTERIOR
WALL COVERING ATTACHMENTS, SHALL COMPLY WITH SECTION 2304.9.1.1.
3. FASTENERS FOR PRESSURE-PRESERVATIVE TREATED AND FIRE
RETARDANT TREATED LUMBER SHALL COMPLY WITH SECTION 2304.9.5
4. PNEUMATIC FASTENERS INSTALLED IN SIMPSON HARDWARE SHALL BE
APPROVED BY SIMPSON AND THE BUILDING DEPARTMENT PRIOR TO
INSTALLATION.
5. PNEUMATIC FASTENERS TO BE INSTALLED INTO PLYWOOD SHEATHING
SHALL BE APPROVED BY THE BUILDING DEPARTMENT AND SHALL FALL
WITHIN THE 10% TOLERANCE LIMIT FOR HAND DRIVEN NAILS PER ASTM
F1667 FOR HEAD DIAMETER. ALL NAIL HEADS TO BE FULL ROUND HEADS.
6. MINIMUM NAIL DIMENSIONS:
(1) NAILS SPACED AT 6" OC AT EDGES, 12" AT INTERMEDIATE SUPPORTS EXCEPT 6" AT ALL SUPPORTS
WHERE SPANS ARE 48" OR MORE. FOR NAILING OF WOOD STRUCTURAL PANEL DIAPHRAGMS AND
SHEARWALLS, REFER TO SECTION 2305 AND THE TYPICAL STRUCTURAL PLYWOOD NAILING DETAIL.
NAILS FOR WALL SHEATHING SHALL BE COMMON.
COMMON OR DEFORMED SHANK.
DEFORMED SHANK
COMMON
WHEN POSSIBLE, NAILS DRIVEN PERPENDICULAR TO THE GRAIN SHALL BE USED INSTEAD OF
TOENAILS.
SEE DTL A4 / S-504 FOR NAILING EXAMPLES.
FOR WOOD MEMBER CONNECTIONS NOT IDENTIFIED IN THE DRAWINGS OR NAILING SCHEDULE,
CONNECT PER IBC TABLE 2304.9.1.
(3)
(4)
(2)
(5)
(6)
8d
NAIL SHANK DIAMETER LENGTH
.131" .281" 21 2"
HEAD DIAMETER
10d .148" .312" 3"
16d .162" .344" 31 2"
20d .192" .406" 4"
6d .113" .266" 2"
(7)
NAILING SCHEDULE (7)
CONNECTION NAILING
1. JOIST OR RAFTERS TO SIDES OF STUDS
8-INCH JOIST OR LESS
FOR EACH ADDITIONAL 4 INCHES IN DEPTH OF JOIST
2. BRIDGING TO JOIST, TOENAIL EACH END
A. BLOCKING BETWEEN JOISTS OR RAFTERS-TO JOIST
OR RAFTERS- TOENAILS EACH SIDE, EACH END
B. BLOCKING BETWEEN STUDS, EACH END
2- 8d
2- 10d 2- 10d TOENAILS OR 2- 16d
(5)
3- 16d 1- 16d
3. SOLE PLATE TO JOIST OR BLOCKING, TYPICAL FACE NAIL
SOLE PLATE TO JOIST OR BLOCKING, AT BRACED WALL PANELS
16d AT 16" OC 3- 16d PER 16"
4. TOP PLATE TO STUD, END NAIL 2x4: 2- 16d 2x6, 2x8: 3- 16d
5. STUD TO SOLE PLATE 4- 8d, TOENAIL OR 2- 16d, END NAIL
6. MULTIPLE STUDS, FACE NAIL STAGGERED 16d AT 24" OC
7. DOUBLED TOP PLATES, TYPICAL FACE NAIL
DOUBLED TOP PLATES, LAP SPLICE
16d AT 16" OC 8- 16d
8. BLOCKING BETWEEN JOISTS OR RAFTERS TO TOP PLATE, TOENAIL 3- 8d
9. RIM JOIST TO TOP PLATE, TOENAIL 8d AT 6" OC
10. TOP PLATES, LAPS & INTERSECTIONS, FACE NAIL 3- 16d
11. CONTINUOUS HEADER, TWO PIECES 16d AT 16" OC ALONG EACH EDGE
12. CEILING JOISTS TO PLATE, TOENAIL 3- 8d
13. CEILING JOISTS, LAPS OVER PARTITIONS, FACE NAIL 3- 16d
14. CEILING JOISTS TO PARALLEL RAFTERS, FACE NAIL 3- 16d
15. JOISTS OR RAFTERS AT ALL BEARINGS, TOENAIL 3- 8d
16. BUILT-UP CORNER STUDS 16d AT 24" OC
17. BUILT-UP GIRDER & BEAMS, FACE NAIL
(10" DEEP MAX)
20d AT 32" OC AT TOP & BOTTOM
STAGGERED ON OPPOSITE SIDES &
2- 20d AT ENDS & AT EACH SPLICE
18. WOOD STRUCTURAL PANELS & PARTICLEBOARD (1)
SUBFLOOR, ROOF & WALL SHEATHING (TO FRAMING):
2" OR LESS . . . . . . . . . . . . . . . . . 6d (2)
32" - 3 4" . . . . . . . . . . . . . . . . . . . . 8d (4) OR 6d (3)
8" - 1" . . . . . . . . . . . . . . . . . . . . . . 8d (2)
8" - 11
4" . . . . . . . . . . . . . . . . . . . . . 10d (4) OR 8d (3)
COMBINATION SUBFLOOR-UNDERLAYMENT (TO FRAMING):
4" & LESS . . . . . . . . . . . . . . . . . . . 6d (3)
8" - 1" . . . . . . . . . . . . . . . . . . . . . . . 8d (3)
8" - 11
4" . . . . . . . . . . . . . . . . . . . . . 10d (4) OR 8d (3)
S-005
S
A2 ADMINISTRATION FOUNDATION PLAN - BASE BID
SCALE: 1/8" = 1'-0"
number:
reference
Sheet
A
B
C
1 2 3 4
S C
R
IP
P S
D R
IV
E
S A
C R
A M
E N
TO
, C
A
A R
T
HUR ER NEST
RO
S
S
ST RUCT URA L
No. S2030
STA TE OF CA LIFORNIA
RE
G
IS
TE
RED PROFESS IONAL ENG
INEER
95% SUBMITTAL
123568
A
E
F
H
B
H
G
D
C
14'-5" 6'-6"
14'-1" 14'-7"
8'-4" 21'-5"
15'-6" 27'-6"
44'-7"
28'-3" 5'-0"
117'-4"
84'-1"
11'-9" 11'-9" 11'-9" 11'-9" 21'-0" 13'-0" 13'-0" 13'-0" 31 2"10'-01
2"
15'-11"
6" CONC CURB,
SHOWN SHADED, TYP
DEPR SLAB
-11
2" IN
SHOWERS
A3 S-302
B3 S-303
A3 S-303
B3 S-304
43'-0"
A (L= 28'-3")
F2
A (L= 15'-7")
A (L= 15'-11")
A (L= 6'-4")
A (L= 8'-3")
5" THK CONC SLAB W/ #4 @ 12" OC
EW AT MID-DEPTH, OVER 15 MIL
VAPOR BARRIER, 2" DRY SAND &
5" GRAVEL, TYP UNO
F3
F3
F3 F2 F2
F2
F3
F2
F2
F2
F2 F2F2
F2 F2
F2 1
F2F2F2
F2F2F2F2F2F2
A (L= 9'-2")
A2 S-501
B2 S-505
A2 S-501
A2 S-501
A D
M
IN
IS
TR
A
TI
O N
B U
IL
D
IN
G
FO
U
N D
A
TI
O N
P
LA
N
B A
S E
B
ID
0 4' 8' 16'
SHEARWALL SCHEDULE
SHEARWALL
MARK
STRUCT 1
SP
SP EDGE
NAILING (EN)
STUDS AT
PANEL EDGE (&
BLKG AT
UNSUPPORTED
PANEL EDGES)
SILL PL
SIZE
SILL AB
AT CONC
FLR
A 15 32" 10d @ 6" OC 2x 2x
8"Ø AB
@ 32" OC
SHEARWALL NOTES:
1. NAILS SHALL BE 10d COMMON WIRE NAILS W/ 0.148" SHANK DIA x 3" LONG. INSTALL
W/ 11
2" MIN PENETRATION & STAGGERED ES OF JT W/O CRUSHING OF FACE PLIES.
2. EN OCCURS AT EVERY PANEL EDGE. FN SHALL BE 10d @ 12" OC.
3. BLK ALL PANEL EDGES W/ FULL STUD DEPTH BLKG OF THK SPECIFIED.
4. PRE-DRILL HOLES FOR NAILS AS REQ TO PREVENT SPLITS AT SILL PL'S OR FRMG
TO WHICH SILL PL'S ARE NAILED.
5. ALL RIM BOARDS & RIM BLKG SHALL BE LSL "TIMBERSTRAND" MATERIAL, UNO.
6. WHERE SP OCCURS AT BOTH SIDES OF WALL, STAG JTS SO THAT NO TWO FALL
ON THE SAME STUD OR BLKG.
7. AB'S SHALL HAVE 9" MIN EMBEDMENT IN CONC, PLUS CURB HT WHERE OCCURS.
8. EXTR STRUC WALLS NOT IDENTIFIED AS SHEARWALLS SHALL BE SHEATHED W/
32" SP W/ 6" OC EN & 12" OC FN.
9. LENGTHS INDICATED ON SHEARWALL PLANS OR SHEARWALL ELEVS ARE MINS.
VERIFY SHEARWALL LENGTHS W/ ARCH DWGS & NOTIFY CONTRACTING OFFICER
PRIOR TO CONSTR IF MIN REQ SHEARWALL LENGTH CANNOT BE ACHIEVED.
10. PROVIDE STRAPPING ABV & BLW SHEARWALL OPGS WHERE NOTED ON PLANS OR
SHEARWALL ELEVS. ALSO SEE DTL A1 / S-503.
11. ALL SHEARWALLS SHALL HAVE SILL AB'S W/ STL PL WASHERS & STD CUT
WASHERS. THE STL PL WASHERS SHALL COMPLY & BE INSTALLED IN
ACCORDANCE W/ DTL A4 / S-503.
12. SEE DTL B4 / S-503 FOR SP NAILING.
PAD FOOTING SCHEDULE
MARK SIZE THK REINF
2'-0" SQ 2'-0" 3- #6 EW AT BOTT
3'-0" SQ 2'-0" 4- #6 EW AT BOTT
4'-0" SQ 2'-0" 5- #6 EW AT BOTT
F2
F3
F4
CONTINUOUS FOOTING SCHEDULE
MARK WIDTH DEPTH LONG REINF TRANS REINF
2'-0" 2'-0" 3- #6 CONT
BOTT
#6 @ 12" OC
3'-0" 2'-0" 4- #6 CONT
BOTT
#6 @ 12" OC
5'-0" 2'-0" 7- #6 CONT
BOTT
#6 @ 12" OC
CF2.0
CF3.0
CF5.0
NOTES:
1. PAD FTGS SHALL BE CTRD UNDER COLS / POSTS, TYP UNO.
2. FOR TYP DTL OF PAD FTG AT WOOD POST, SEE DTL A2 / S-501.
3. FOR TYP DTL OF PAD FTG AT STL COL, SEE DTL B2 / S-502.
NOTES:
1. CONT FTGS ARE TYP, UNO
2. CONT FTGS SHALL BE CTRD UNDER WALLS UNO.
3. LONG REINF TO BE CONT THRU PAD FTGS, TYP WHERE OCCURS,
UNO.
4. FOR TYP DTLS OF CONT FTGS AT EXTR WALLS, SEE DTLS B3 / S-511
5. FOR TYP DTLS OF CONT FTGS AT INTR WALLS, SEE DTLS B4 / S-511
6. SEE DTL B4 / S-501 FOR REINF DTLS AT FTG INTERSECTIONS.
7. SEE DTLS A1 / S-502 & A2 / S-502 FOR CONC FTG FORMING DTLS.
CF2.0
FOUNDATION LEGEND:
6x6 WOOD POST UNO ON PLAN
INDICATES STRUC WOOD STUD WALL, 2x6
@ 16" OC, TYP UNO. SEE DTL C4 / S-504
FOR BEV TOP PL WHERE OCCURS
INDICATES NON-STRUC WOOD STUD
WALL, SEE DTLS C2 / S-501, B4 / S-504
& A2 / S-507
SHADING INDICATES 6" HIGH CONC
CURB, TYP UNO, SEE DTL A4 / S-502
HATCH INDICATES DEPR SLAB,
TYP UNO. SEE DTL A3 / S-502
CF#
F#
CONT FTG MARK PER "CONTINUOUS
FOOTING SCHEDULE" THIS SHEET
SHRWL MARK PER "SHEARWALL SCHEDULE"
THIS SHEET. SEE WALL ELEVS FOR
EXTENTS OF DESIGNATED SHRWLS
HOLDOWN TYPE, SEE DTL A2 / S-503
PAD FTG MARK PER "PAD FOOTING
SCHEDULE" THIS SHEET
S S INDICATES STEPPED FTG PER DTL A4 / S-501.
FOUNDATION NOTES:
1. SEE SHEETS S-001 THRU S-005 FOR GENERAL NOTES
2. SEE SHEETS S-201 & S-202 FOR WALL ELEVATIONS
3. SEE SHEETS S-501 THRU S-510 FOR DETAILS
4. SEE CIVIL DWGS, GEOTECHNICAL REPORT & SPECS FOR SUB-GRADE
RECOMMENDATIONS.
5. DIMS ARE TO FACE OF STUD OR CENTERLINE OF COLS / POSTS, UNO.
6. SAD FOR DIMS, EXTEND & NATURE OF ALL WALLS.
7. SAD FOR DIMENSIONS & LOCATIONS OF ALL SLAB STEPS, SLOPES, FLR DRAINS,
CURBS & SLAB EDGES.
8. TOC SLAB ELEV = 0'-0" (EQUALS CIVIL DATUM 85.10')
9. TOP OF FTG ELEV (TOF) = -1'-0" UNO.
SAD & OTHER CONSULTANT DWGS FOR UTILITIES THAT WILL AFFECT FTGS &
COMPLY W/ DTL A1 / S-501.
10. SOG CJ LOCATIONS SHALL BE APPROVED BY THE ARCHITECT / ENGINEER PRIOR
TO PLACEMENT OF CONC PER DTL B4 / S-502.
11. EXTR CONC FLATWORK IS NOT SHOWN. SEE CIVIL & ARCH DWGS.
12. PROVIDE 3" MIN CONC COVER AT ALL COLS, AB'S & BASE PLATES BLW GRD, TYP.
13. SILL PLATES SHALL BE 2x PTDF W/ WIDTH TO MATCH STUDS, TYP UNO.
S-101
S -1
A2 COMBINED FOUNDATION PLAN - BASE BID + ALTERNATE
number:
reference
Sheet
A
B
C
1 2 3 4
S C
R
IP
P S
D R
IV
E
S A
C R
A M
E N
TO
, C
A
A R
T
HUR ER NEST
RO
S
S
ST RUCT URA L
No. S2030
STA TE OF CA LIFORNIA
RE
G
IS
TE
RED PROFESS IONAL ENG
INEER
95% SUBMITTAL
1235671012
A
E
F
G
H
B
H
D
C
11 489
6'-61 4" 14'-41
2" 6'-61 4"
14'-1" 14'-7" 15'-11" 21'-5"44'-7" 27'-5"
5'-0"
117'-4"
84'-1"
206'-4"
89'-0"
117'-3"
8'-4"60'-0"
8'-81 4"
8" 12'-4" 12'-4" 12'-4" 12'-4" 12'-4" 37'-11
8" 11'-9" 11'-9" 11'-9" 11'-9" 21'-0" 13'-0" 13'-0" 13'-0" 31 2"
B3 S-301
A3 S-301
B3 S-302
A3 S-302
B3 S-303
A3 S-303
6" CONC CURB,
SHOWN SHADED, TYP
DEPR SLAB -11
2"
IN SHOWERS
B3 S-304
32'-7" 27'-5" 14'-9" 14'-3" 15'-7"
A3 S-304
A1 S-304
A (L= 31'-4")
A (L= 20'-10")
A (L= 15'-11")
A (L= 6'-4")
A (L= 8'-3")
A (L= 13'-2")
A (L= 8'-0")
A (L= 11'-0")
A (L= 8'-10")
A (L= 10'-0")
33'-7" 26'-73 4"
5'-0" 5'-0"
CF5.0
8" CONC RETAINING
WALL BLW
S S
S S
S S
S S
10'-0"2'-0"
A (L= 6'-0")
8" CONC RETAINING
WALL BLW
5" THK CONC SLAB W/ #4 @ 12" OC
EW AT MID-DEPTH, OVER 15 MIL
VAPOR BARRIER, 2" DRY SAND &
5" GRAVEL, TYP UNO
F4 F3
F2
F2 F3
F2
F3
F3
F3
F3 F2 F2
F2
F3
F2
F2
F2 F2
F2F2F2
F2F2F2F2F2
F2F2
F2
F2
F2 F2
B2 S-505
B1 S-503
A2 S-501
F2
A2 S-501
F2
A2 S-501
A3 S-511
A1 S-511
A2 S-511
1 1
11 1 1
1 1
A (L= 9'-8")
A D
M
IN
IS
TR
A
TI
O N
B U
IL
D
IN
G
FO
U
N D
A
TI
O N
P
LA
N B
A S
E B
ID
A
LT
0 4' 8' 16'
FOUNDATION NOTES:
1. SEE S-101 FOR FOUNDATION NOTES
FOUNDATION LEGEND:
1. SEE S-101 FOR FOUNDATION LEGEND
S-102
S
G
8 7
HDR BLW,
TYP
INDICATES 23
32" T&G SP,
UNBLOCKED, W/ 10d @ 6" OC EN & BN, 10d @
12" OC FN
OPG FOR ACCESS
DBL 2x10
A2 S-508 number:
reference
Sheet
A
B
C
1 2 3 4
S C
R
IP
P S
D R
IV
E
S A
C R
A M
E N
TO
, C
A
A R
T
HUR ER NEST
RO
S
S
ST RUCT URA L
No. S2030
STA TE OF CA LIFORNIA
RE
G
IS
TE
RED PROFESS IONAL ENG
INEER
95% SUBMITTAL
A D
M
IN
IS
TR
A
TI
O N
B U
IL
D
IN
G
M E
C H
P
LA
TF
O
R M
F R
A M
IN
G
P
LA
N
PLATFORM FRAMING LEGEND:
INDICATES STRUC WOOD
STUD WALL BLW
INDICATES NON-STRUC
WOOD STUD WALL BLW
WOOD POST OR HSS COL BLW,
SEE FND PLAN FOR SIZE
PLATFORM FRAMING NOTES:
1. SEE SHEETS S-001 THRU S-005 FOR GENERAL
NOTES.
2. SEE SHEETS S-201 & S-202 FOR WALL
ELEVATIONS.
3. SEE SHEETS S-501 THRU S-510 FOR DETAILS.
4. DIMS ARE TO FOS OR CL OF COLS / POSTS, UNO.
5. BM CL'S SHALL ALIGN W/ WALL / COL CL'S, UNO.
6. SAD & OTHER CONSULTANT DWGS FOR
PLATFORM PENETRATIONS NOT SHOWN.
PROVIDE FRMG AROUND OPGS PER DTLS ON
SHEETS S-503 THRU S-510. SAWCUT OR CORE
DRILL CLEAN HOLES W/ NO OVERCUTTING,
COMPLY W/ DTLS.
7. HDRS NOT LABELED W/ SIZE SHALL USE HDR
SIZE PER DTL A1 / S-504.
8. SPLICE TOP PL'S PER DTL C2 / S-503.
9. SEE DTL B1 / S-504 FOR TYP PERMITTED
NOTCHES & HOLES IN WOOD FRMG.
10. SEE DTL A1 / S-504 TYP WALL FRMG.
11. SEE DTL A4 / S-505 FOR TYP WALL BACKING.
12. DEE DTL B4 / S-505 FOR TYP HARD CLG FRMG
SCHED.
0 4' 8' 16'
B3 SCALE: 1/8" = 1'-0"
ADMINISTRATION MECH PLATFORM
FRAMING PLAN - BASE BID + ALTERNATE
0 4' 8' 16'
C3 SCALE: 1/8" = 1'-0"
ADMINISTRATION MECH
PLATFORM FRAMING PLAN - BASE BID
G
HDR BLW,
TYP
INDICATES 23
32" T&G SP,
UNBLOCKED, W/ 10d @ 6" OC EN & BN, 10d @
12" OC FN
A2 S-508
PSL ABV
I-JST ABV
S-103
S
A2 ADMINISTRATION ROOF FRAMING PLAN - BASE BID
number:
reference
Sheet
A
B
C
1 2 3 4
S C
R
IP
P S
D R
IV
E
S A
C R
A M
E N
TO
, C
A
A R
T
HUR ER NEST
RO
S
S
ST RUCT URA L
No. S2030
STA TE OF CA LIFORNIA
RE
G
IS
TE
RED PROFESS IONAL ENG
INEER
95% SUBMITTAL
A D
M
IN
IS
TR
A
TI
O N
B U
IL
D
IN
G
R O
O F
FR
A
M
IN
G P
LA
N
B
A S
E B
ID
123568
A
E
F
H
B
H
G
D
C
A3 S-302
B3 S-303
A3 S-303
B3 S-304
2x8 OUTRIGGER
@ 24" OC, TYP
2x8 OUTRIGGER
@ 24" OC
2x WALL
BLW
6x6 POST-UP
FROM BM BLW
JST HGR, TYP
SLOPE DN
SLOPE DN
PV PANELS, SAD
6x6 POST-UP
FROM BM BLW
2x8 OUTRIGGER @
24" OC, TYP AT RAKE
2x8 OUTRIGGER @ 24" OC, SISTER W/ JST, TYP AT EAVE
STRAP
STRAP W/ BLKG BLW
32" SP, UNBLOCKED UNO,
W/ 10d @ 6" OC EN & BN, 10d @ 12" OC FN
STRAP W/ BLKG BLW
6x6 POST-UP
FROM BM BLW
4x117
8 2.0E PSL
C1 S-508
C1 S-510
A3 S-510
B4 S-508
B3 S-510
0 4' 8' 16'
FRAMING LEGEND:
WOOD POST OR HSS
COL PER PLAN
INDICATES STRUC WOOD
STUD WALL BLW
INDICATES NON-STRUC
WOOD STUD WALL BLW
WOOD POST OR HSS COL BLW,
SEE FND PLAN FOR SIZE
INDICATES STEP IN ROOF
INDICATES BLOCKED
DIAPHRAGM
FRAMING NOTES:
1. SEE SHEETS S-001 THRU S-005 FOR GENERAL
NOTES.
2. SEE SHEETS S-201 & S-202 FOR WALL
ELEVATIONS.
3. SEE SHEETS S-501 THRU S-510 FOR DETAILS.
4. DIMS ARE TO FOS OR CL OF COLS / POSTS, UNO.
5. BM CL'S SHALL ALIGN W/ WALL / COL CL'S, UNO.
6. SAD & OTHER CONSULTANT DWGS FOR ROOF
PENETRATIONS NOT SHOWN. PROVIDE FRMG
AROUND OPGS PER DTLS ON S-5 SHEETS.
SAWCUT OR CORE DRILL CLEAN HOLES W/ NO
OVERCUTTING, COMPLY W/ DTLS.
7. HDRS NOT LABELED W/ SIZE SHALL USE HDR
SIZE PER DTL A1 / S-504.
8. SPLICE TOP PL'S PER DTL C2 / S-504.
9. PROVIDE BRIDGING, BLKG, ERECTION BRCG,
WEB STIFFENERS, FILLERS & NAILING FOR ROOF
I-JSTS PER I-JST MFR & AS SHOWN ON PLANS.
SEE SHEET S-506 FOR I-JST DESIGN CRITERIA.
10. ROOF JSTS SHALL HAVE BRIDGING OR BLKG @
6' - 0" OC MAX PER DTL A4 / S-508. TYP ALL ROOF
JSTS GREATER THAN 12' - 0" LG. NOT ALL
BRIDGING / BLKG SHOWN FOR CLARITY.
11. ALL RIDGE BOARDS SHALL BE 13
4x14 2.0E LVL, TYP UNO.
12. SEE DTL B1 / S-504 FOR TYP PERMITTED
NOTCHES & HOLES IN WOOD FRMG.
13. SEE DTL A1 / S-504 TYP WALL FRMG.
14. SEE DTL A4 / S-505 FOR TYP WALL BACKING.
15. DEE DTL B4 / S-505 FOR TYP HARD CLG FRMG
SCHED.
S-104
S
A2 COMBINED ROOF FRAMING PLAN - BASE BID + ALTERNATE
number:
reference
Sheet
A
B
C
1 2 3 4
S C
R
IP
P S
D R
IV
E
S A
C R
A M
E N
TO
, C
A
A R
T
HUR ER NEST
RO
S
S
ST RUCT URA L
No. S2030
STA TE OF CA LIFORNIA
RE
G
IS
TE
RED PROFESS IONAL ENG
INEER
95% SUBMITTAL
1235671012
A
E
F
G
H
B
H
D
C
11 489
2x8 OUTRIGGER
@ 24" OC
2x8 OUTRIGGER
@ 24" OC
2x8 OUTRIGGER @ 24" OC, TYP AT RAKE
2x WALL
BLW
B3 S-301
A3 S-301
B3 S-302
A3 S-302
B3 S-303
A3 S-303
6x6 POST-UP
FROM HDR
BLW
2x LEDGER2x8 OUTRIGGER @ 24" OC, SISTER W/ JST, TYP AT EAVE
2x8 OUTRIGGER @ 24" OC, SISTER W/ JST
6x6 POST-UP
FROM BM BLW JST HGR, TYP
8x88x88x88x8
2x @ 24" OC
OVERFRAMING, TYP
SLOPE DN
SLOPE DN
SLOPE DN
SLOPE DN
PV PANELS,
SAD
A3 S-304
A1 S-304
B1 S-304
BRIDGING / BLKG
@ 6'-0" OC MAX,
SEE PLAN NOTES
12'-0"
2x117
8 2.0E PSL
OPG BLW
OVERFRMG
2x117
2.0E PSL
4x117
8 2.0E PSL
6x6 POST-UP
FROM BM BLW
2x117
2.0E PSL
RIDGE BOARD
STRAP
STRAP W/ BLKG BLW
STRAP STRAP
STRAP
STRAP W/ BLKGSTRAP W/
BLKG
6x6 POST-UP
FROM BM BLW
6x6 POST-UP
FROM BM BLW
8x8 8x8 8x8 8x8
8x8 8x8 8x8
6x6 POST-UP
FROM BM BLW
4x117
2.0E PSL
C1 S-508
C1 S-510
B3 S-510
A3 S-509
B3 S-509
A3 S-509
A3 S-510
C2 S-509
4x117
8 2.0E PSL
C2 S-509
C3 S-509
B4 S-508
A D
M
IN
IS
TR
A
TI
O N
B U
IL
D
IN
G
R O
O F
FR
A
M
IN
G P
LA
N
B A
S E
B
ID
A
LT
0 4' 8' 16'
FRAMING NOTES:
1. SEE S-104 FOR FRAMING NOTES
FRAMING LEGEND:
1. SEE S-104 FOR FRAMING LEGEND
S-105
S
A2 WAREHOUSE FOUNDATION PLAN
SCALE: 1/4" = 1'-0" 0 2' 4' 8'
number:
reference
Sheet
A
B
C
1 2 3 4
S C
R
IP
P S
D R
IV
E
S A
C R
A M
E N
TO
, C
A
A R
T
HUR ER NEST
RO
S
S
ST RUCT URA L
No. S2030
STA TE OF CA LIFORNIA
RE
G
IS
TE
RED PROFESS IONAL ENG
INEER
95% SUBMITTAL
C
B
A
B
B3 S-321
COLS BY PEMB MFR, TYP
ROD CROSS BRCG
ROD CROSS BRCG
60'-0"
23'-6" 36'-6"
2x6 STUDS
@ 16" OC
2x6 STUDS
@ 16" OC
8" THK CONC SLAB W/
#4 @ 12" OC EW T&B, TYP
COORD W/
PEMB MFR
6"
2x4 STUDS @ 16" OC, TYP
A2 S-321
DEPR SLAB -11
2"
IN SHOWER
B4
S-521
F1F1
F2
F3 F3
F3
F2 F2
F2
F3 F3
F3
COORD W/
PEMB MFR
A (L= 8'-11")
A (L= 6'-11")
2- #4 HAIRPINS
5'-0" LG, TYP
B2 S-521
B1 S-521
A4
S-521TYP
FOUNDATION NOTES:
1. FOR GENERAL FOUNDATION NOTES SEE SHEET S-001
& S-002.
2. VERIFY PEMB COL & FRMG SIZES & LOCATIONS W/
PEMB MFR DWGS. PEMB FRAME COLS SHOWN ARE
NOT TO SCALE.
3. SOG CONSTR & CONTROL JTS LOCATIONS SHALL BE
APPROVED BY THE SEOR PRIOR TO THE PLACEMENT
OF CONC. SEE DTL B4/S-502.
4. REFER TO THE SPECS & SOILS REPORT FOR
SUB-GRADE RECOMMENDATIONS.
5. TOP OF SOG ELEV = +0'-0" (WRT 93.00'), TYP UNO.
6. TOP OF FTG ELEV = -1'-2" TYP UNO.
7. SAD FOR DIMS, LOCATIONS & LIMITS OF ALL RAISED
SLABS, CURBS, TRENCHES, FD'S & FLR SLOPES.
MAINTAIN CONC SOG THK AT ALL FLR SLOPES.
8. SAD FOR DIMS, EXTENT, & NATURE OF ALL WALLS.
9. DO NOT ROUTE UTILITIES UNDERNEATH OR THRU
SPREAD FTGS.
10. PROVIDE CERTIFICATION LETTER FROM SOILS
ENGINEER AT TIME OF FND INSPECTION TO THE
CONTRACTING OFFICER, LETTER SHALL BE DATED
AFTER ISSUANCE OF PERMIT & CERTIFY THAT THE
PAD & FTG EXCAVATIONS ARE READY TO RECEIVE
IMPROVEMENTS.
11. FOR TYP DTLS OF CONT FTGS AT INTR WOOD WALLS,
SEE DTLS B4 / S-511 FOR BRG WALLS & C2 / S-501
FOR NON-BRG WALLS.
COL DESIGNED & INSTALLED BY
PEMB MFR (SYMBOL NTS)
INDICATES DIAG BRACE DESIGNED
& INSTALLED PER PEMB MFR
INDICATES CONC CURB, SAD
& DTLS B1 / S-521 & B2 / S-521
F#
PAD FTG MARK PER
"PAD FOOTING SCHEDULE" THIS SHEET
FOUNDATION LEGEND:
HATCH INDICATES DEPR SLAB
(ELEV = 84.975'), TYP UNO
W A
R E
H O
U S
E B
U
IL
D
IN
G
FO
U N
D A
TI
O
N P
LA
N
PAD FOOTING SCHEDULE
MARK SIZE THK REINF
2'-0" SQ 2'-0" 2-#5 EW T&B
2'-6" SQ 2'-0" 3-#5 EW T&B
4'-0" SQ 2'-0" 4-#5 EW T&B
F1
F2
F3
NOTES:
1. PAD FTGS SHALL BE CTRD UNDER
COLS / POSTS, TYP UNO.
2. LONG REINF TO BE CONT THRU PAD
FTGS, TYP WHERE OCCURS, UNO.
SHEARWALL SCHEDULE
SHEARWALL
MARK
STRUCT 1
SP
SP EDGE
NAILING (EN)
STUDS AT
PANEL EDGE (&
BLKG AT
UNSUPPORTED
PANEL EDGES)
SILL…
This is the start of the file's text. The full file is on GovTribe.