NASA/KSC SOLICITATION 80KSC018R0016
SECTION C – DESCRIPTION/SPECIFICATION/WORK STATEMENT
14. Specification 79K40362 Section 40 29 99 Subpart 3.7.3: The second sentence of this subpart is revised to read, “The inner line shall be pressurized to design pressure with
100 percent helium, or a mixture of 10% helium and 90% nitrogen with adjusted detection criteria, and the field welds tested for leakage.”
15. Drawing 79K40361 Volume 1, Sheet C-101: Flag Note J is revised to read, “REMOVE 60’ x 40’ CONCRETE SLAB AND PADS. FOR SLAB, ASSUME 12”
THICK CONCRETE SLAB WITH 6” x 6” 8-GAUGE REINFORCING MESH. FOR
PADS, ASSUME 24” THICK CONCRETE WITH 3/8”-DIAMETER REBAR.”
16. Drawing 79K40361 Volume 2, Sheet E-608: For Cable ID GSP-01, the TO
TERMINATION REFERENCE DESIGNATOR is revised from “UPS Panel TBD CB
TBD” to “Panel LH2-PB Circuit 3.” For Cable ID GSP-02, the TO TERMINATION
REFERENCE DESIGNATOR is revised from “FAC Panel TBD CB TBD” to “Panel
LH2-PA Circuit 1.” For Cable ID GSP-29, the TO TERMINATION REFERENCE
DESIGNATOR is revised from “UPS Panel TBD CB TBD” to “Panel LH2-PB Circuit 2.”
For Cable ID GSP-30, the TO TERMINATION REFERENCE DESIGNATOR is revised from “FAC Panel TBD CB TBD” to “Panel LH2-PA Circuit 2.”
17. Specification 79K40362 Section 26 05 00.00 40 Subpart 3.2.1.8: The third sentence of this subpart is revised to read, “Maximum support spacing is 10 feet.”
18. Specification 79K40362 Section 27 05 28.36 40 Subpart 2.4.1: The first sentence of the second paragraph of this subpart is revised to read, “Support cable trays at not more than 10-foot intervals.”
19. Drawing 79K40361 Volume 2, Sheet T-002: General Note 23 is revised to add, “D. CABLES INSTALLED IN VERTICAL OR HORIZONTAL CABLE TRAY AT 10-
FOOT INTERVALS.”
20. 79K40361 Volume 2, Sheet T-102: Flag Note C is considered deleted from this sheet. The 14 conduits in Zone F4 referred to by Flag Note C are not required and are considered deleted from this sheet.
21. Specification 79K40362 Section 43 42 41.99 Subpart 2.1.2.1h): The first sentence is revised to read, “Cycles - The inner sphere shall be designed to withstand 7000-pressure and thermal cycles without damage to vessel structure.” The wording “or insulation package” is considered deleted from this sentence.
22. Specification 79K40362 Section 43 42 41.99 Subpart 2.1.3.1e): The first sentence is revised to read, “Cycles - The outer sphere shall be designed to withstand 7000-pressure thermal cycles without damage to vessel structure.” The wording “or insulation package” is considered deleted from this sentence.
NASA/KSC SOLICITATION 80KSC018R0016
SECTION C – DESCRIPTION/SPECIFICATION/WORK STATEMENT
23. Specification 79K40362 Section 43 42 41.99 Subpart 2.2.5: A sentence is added at the end of the subpart stating, “Identify the number of pressure and thermal cycles the perlite insulation can withstand without significant damage or performance degradation in the required submittal.”
24. Specification 79K40362 Section 43 42 41.99 Subpart 2.2.5.1: A sentence is added stating, “Identify the number of pressure and thermal cycles the hollow glass microsphere insulation can withstand without significant damage or performance degradation in the associated submittal.”
25. Specification 79K40362 Section 43 42 41.99 Subpart 1.3: In SD-02 Shop
Drawings, Materials and Equipment is considered as having a “; G” added after it. This submittal requires review and approval by the government.
26. Specification 79K40362 Section 43 42 41.99 Subpart 1.3: In SD-03 Product Data, Data Sheets for Materials and Equipment is considered as having a “; G” added after it.
This submittal requires review and approval by the government.
(c) "Or Equal" Items”
Throughout the technical specifications and drawings of this contract, where certain manufacturers’ trade names and model numbers are specified and followed by the term "or equal," the manufacturer's name and data as specified shall represent the minimum standard type, quality, and capacity acceptable for incorporation into the work covered by this contract.
The products of other manufacturers will be considered as being acceptable, provided that such products fully meet or exceed all minimum structural or use and operational features of the particular manufacturers’ items as specified, and provided that the other manufacturers’ items are easily interchangeable and can be adequately incorporated within the allocated space in the building or structure. In all cases, the acceptability of "or equal" items shall be at the
Contracting Officer's discretion, based upon data submitted by the Contractor in accordance with the requirements under the Shop Drawings Clause.
(d) Omissions from the drawings or specifications, or the omission or misdescription of details of work which are manifestly necessary to carry out the intent of the drawings and specifications, or which are customarily performed, shall not relieve the Contractor from performing such omitted or misdescribed details of the work but they shall be performed as if fully and correctly set forth and described in the drawings and specifications.
(e) The Contractor shall check all drawings furnished him immediately upon their receipt and shall promptly notify the Contracting Officer of any discrepancies. Figures marked on drawings shall in general be followed in preference to scale measurements. Large scale drawings shall in general govern small scale drawings. The Contractor shall compare all drawings and verify the figures before laying out the work and will be responsible for any errors which might have been avoided thereby.