RESPONSE_TO_BIDDER_QUESTIONS_6-5-18.docx

DOCX document 21 KB Posted

Attached to
Upgrade Liquid Hydrogen (LH2) System, Launch Complex 39B Federal contract opportunity
Solicitation number
80KSC018R0016
Issued by
National Aeronautics and Space Administration Kennedy Space Center

About this file

Response to Bidder Questions 6/5/18

View the file

Other files for this federal contract opportunity

Other files attached to Upgrade Liquid Hydrogen (LH2) System, Launch Complex 39B, newest first.
File Type Posted
Sphere_Source_Selection_Statement_Final_Signed.pdf PDF
80KSC018R016_Amendment_9.pdf PDF
80KSC018R016_Amendment_8_SF30.pdf PDF
80KSC018R016_Amendment_7.pdf PDF
RESPONSE_TO_BIDDER_QUESTIONS_6-15-18.docx DOCX document
RESPONSE_TO_BIDDER_QUESTIONS_6-14-18.docx DOCX document
80KSC018R016_Amendment_6_SF30.pdf PDF
Solicitation_KSC018R0016_SF1442_J-B-26_Change_Page.pdf PDF
80KSC018R016_Amendment_6_Continuation.docx DOCX document
Solicitation_KSC018R0016_SF1442_C.2__Change_Page.pdf PDF
RESPONSE_TO_BIDDER_QUESTIONS_6-11-18.docx DOCX document
80KSC018R016_Amendment_5_SF30.pdf PDF
RESPONSE_TO_BIDDER_QUESTIONS_6-4-18.docx DOCX document
80KSC018R016_Amendment_4.pdf PDF
RESPONSE_TO_BIDDER_QUESTIONS_5-31-18.docx DOCX document
80KSC018R016_Amendment_3.pdf PDF
RESPONSE_TO_BIDDER_QUESTIONS_5-30-18.docx DOCX document
RESPONSE_TO_BIDDER_QUESTIONS_5-23-18.docx DOCX document
PCN_98985_Geotechnical_Report.pdf PDF
PCN_98985_Environmental_Report.pdf PDF
RESPONSE_TO_BIDDER_QUESTIONS_5-9-18.docx DOCX document
RESPONSE_TO_BIDDER_QUESTIONS_5-8-18.docx DOCX document
80KSC018R016_Amendment_2.pdf PDF
Pre-Bid_Attendee_List.docx DOCX document
80KSC018R016_Amendment_1.pdf PDF
Brand_Name_Justification_PLC.pdf PDF
80KSC018R0016__Attachment_J1C_DOL_Area_Wage_Determination.pdf PDF
80KSC018R0016_SF1442.pdf PDF
Solicitation_80KSC018R0016_SF1442_Continuation.pdf PDF
Show all 29

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

80KSC018R0016

QUESTION & ANSWERS 6/5/18

RESPONSE TO BIDDER QUESTIONS:

1. REFERENCE: Drawing T-002 QUESTION: General note 42 states “Contractor shall provide surge protection devices(s) for all OSP copper cabling for controls, systems and communications. Coordinate exact requirements with the government.” Please provide part numbers and cables affected by this note.

ANSWER: The note is a general note, typically used in T Sheets with communication cabling to be installed by a contractor where copper cabling is possibly included. There are only two copper cables identified in the T Sheets for the contractor to provide, KGCS-20 and KGCS-21. Because these are armored cables where the shield cabling is required to be bonded to the grounding system at both ends of the cable termination, they do not require surge protection devices. This response is specific to the question and does not remove requirements for surge protection devices wherever else identified as required within the drawings or specification for electrical circuits or equipment.

1. REFERENCE: 40 29 99, Vacuum Jacketed Piping, Subpart 3.5 & Amendment 4, C2 Contract Drawings, (b), 10 QUESTION: Amendment 4, C2 Contract Drawings, (b), 10 deleted all coating for Non-VJ piping which are stainless steel construction. Are coatings required for the VJ Piping per 40 29 99, Sub Part 3.5 of the same stainless steel construction required?

ANSWER: For clarification, Item (b) 10. was in the original version of Solicitation 80KSC018R0016 SF1442 Continuation Clause C.2 and was not new content in Amendment 4. In reference to Specification 79K40362 Section 40 29 99 Subpart 3.5, yes, the exposed surface would be the outer jacket of the vacuum-jacketed (VJ) piping and the coating requirement remains as specified.

1. REFERENCE: Answer to Q&A’s 5-30-18, Number 3, Specification 43 42 41.99, subpart 3.3.4, 2nd paragraph QUESTION: Answer to Q&A’s 5-30-18, Number 3 and Specification 43 42 41.99, subpart 3.3.4, 2nd paragraph reference Demineralized Water for final rinsing. Is 50,000 Ohm demineralized water per KSC-C-123J acceptable? If not, what grade is?

ANSWER: Yes, reagent water as specified in KSC-C-123J Section 3.7.4 is acceptable for this purpose.