80KSC018R016
Amendment 6
SF30 Continuation
Summary of Changes:
80KSC018R016 is amended as follows:
Reference: 80KSC018R016 C.2 CONTRACT DRAWINGS, MAPS, SPECIFICATIONS, AND/OR STATEMENTS OF WORK (JAN 2018)
(b) Addenda to Drawings, Maps, Specifications, and/or Statements of Work:
ADD:
20. 79K40361 Volume 2, Sheet T-102: Flag Note C is considered deleted from this sheet. The 14 conduits in Zone F4 referred to by Flag Note C are not required and are considered deleted from this sheet.
21. Specification 79K40362 Section 43 42 41.99 Subpart 2.1.2.1h): The first sentence is revised to read, “Cycles - The inner sphere shall be designed to withstand 7000-pressure and thermal cycles without damage to vessel structure.” The wording “or insulation package” is considered deleted from this sentence.
22. Specification 79K40362 Section 43 42 41.99 Subpart 2.1.3.1e): The first sentence is revised to read, “Cycles - The outer sphere shall be designed to withstand 7000-pressure thermal cycles without damage to vessel structure.” The wording “or insulation package” is considered deleted from this sentence.
23. Specification 79K40362 Section 43 42 41.99 Subpart 2.2.5: A sentence is added at the end of the subpart stating, “Identify the number of pressure and thermal cycles the perlite insulation can withstand without significant damage or performance degradation in the required submittal.”
24. Specification 79K40362 Section 43 42 41.99 Subpart 2.2.5.1: A sentence is added stating, “Identify the number of pressure and thermal cycles the hollow glass microsphere insulation can withstand without significant damage or performance degradation in the associated submittal.”
25. Specification 79K40362 Section 43 42 41.99 Subpart 1.3: In SD-02 Shop Drawings, Materials and Equipment is considered as having a “; G” added after it. This submittal requires review and approval by the government.
26. Specification 79K40362 Section 43 42 41.99 Subpart 1.3: In SD-03 Product Data, Data Sheets for Materials and Equipment is considered as having a “; G” added after it. This submittal requires review and approval by the government.
Reference: 80KSC018R016 J-B-26 GOVERNMENT PROPERTY TO BE INSTALLED BY THE CONTRACTOR
INSERT:
| Communications Rack, Ref Des 34634 |
| 1 ea. |
| TBD |
| New |