793-B685-04 MACHINERY SPACE HEATING AND COOLING LOAD CALCULATIONS.pdf
PDF 171 KB Posted
- Attached to
- Excavator Barge Federal contract opportunity
- Solicitation number
- W912BU-23-B-0024
About this file
This document contains machinery space heating and cooling load calculations for a 95-foot towboat. The calculations were performed according to ASHRAE standards using outdoor design conditions of 99°F DB and 76°F WB for cooling, and 15°F for heating. Indoor conditions were set at 120°F for cooling and 50°F for heating. Calculations were provided for the engine room, tank room, pump room, storage room, and other machinery spaces. Equipment loads and ventilation requirements were calculated for each space based on rated equipment capacities and specified air change rates. Heating and sensible and latent cooling loads were tabulated along with required supply and exhaust air flows.
View the file
Other files for this federal contract opportunity
Show all 50
Excavator Barge has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REV. DATE APRD.
□ Accepted
□ Accepted with Comments
□ Not Accepted Refer to Notations On:
□ Drawing
□ Return Document Resubmission: □ Required □ Not Required Approved Subj. to Approv. Reg. Agcy. Apprvl.
Reviewer:
Date Returned:
Return Document No.:
REVISIONS
DESCRIPTION
Original Issue
GENERAL NOTES:
Per ASHRAE, the following design conditions were used:
Outdoor Cooling - 99°F D.B. / 76°F W.B.
Outdoor Heating - 15°F
Indoor Cooling - 120°F Indoor Heating - 50°F
Rate of Change for Engine Room - 2 air changes per minute Rate of Change for Tank Room - 3 minutes per air change Rate of Change for Pump Room - 3 minutes per air change
Note - For storage room, assume that the ventilation and heating required will be half that of the tank room. No calculation sheet is included. The storage room will be outfitted with an exhaust fan only, no suppy fan will be provided.
Space heating sized to maintain 50°F while only running fans at 50% rating (not full rated CFM). It is unlikely that the fans will need to be operated at full rated CFM during winter conditions. Additionally, it is assumed that equipment and lighting is operational during the winter so the heat generated by that equipment is subtracted from the required heating load.
All glass windows and door windows are assumed to be single pane.
Insulation values are based on SNAME T&R 4-7.
MDC REVIEW
DR. BY DES. BY CHK'D BY
VCB JDC
APRD. FOR THE DIR. - CH. DES. BR. SIZE REV.
DATE
SHEET: 1 OF 8
DEPARTMENT OF THE ARMY
MARINE DESIGN CENTER
CORPS OF ENGINEERS
02/04/13 SCALE: AS SHOWN
LITTLE ROCK DISTRICT - TOWBOAT
95' x 39' x 10'
MACHINERY SPACE HEATING &
VENTILATION LOAD CALCULATIONS
RECOMMENDED
/S/ Tim Keyser, PE
PROJECT NO. DRAWING NO.
/S/ Greg Lee, PE A 2885 793-B685-04 -
MARINE DESIGN CENTER
100 PENN SQUARE EAST
PHILADELPHIA, PA 19107
SPACE
NO. SENS LATENT TOTAL R/C PERS HEAT
Engine Rm 1 Main CL 548978 0 548978 1 18414 0 24205 30175 0.31 29340 4.85 Tank Rm 2 Hold CL 3843 0 3843 1 1653 0 169 1653 3 2004 3.07 Pump Rm 3 Hold CL -23788 -23788 1 1860 0 -1049 1860 3 2255 10.01 Storage Rm 4 Hold CL ----- ----- ----- 0 ----- ----- ----- ----- ----- 1002 1.54
DATE 2/4/2013 REV. -
MDC PROJECT NO. 2885
DWG. NO. 793-B685-04
SHEET 2 OF 8
Heating Load
(kw) REMARKS
Towboat - Machinery Space Heating & Ventilation Load Calculations SPACE DECK SIDE BTU/HR SHF Outside Air Based On CFM R/C TOTAL
AIR Exhaust CFM
DECK
Main
ADJOINING SPACE LOAD
KEY
INSUL
TYPE
U
KEY AREA TO TD U QS QL QT TO TD U QW
Weather 1 5" 112/145 33 x 31 1023 145 25 0.079 2008 2008 15 35 0.056 2005 Void 2 none n/a 33 x 31 1023 100 -20 1.198 -24511 -24511 40 10 1.295 13248 Weather (Port Side) 3 5" 112/145 33 x 9 297 125 5 0.076 113 113 15 35 0.056 582 Weather (Stbd Side) 3 5" 112/145 31 x 9 279 99 -21 0.071 -416 -416 15 35 0.056 547 Weather 5 5" 112/145 31 x 9 279 125 5 0.071 99 99 15 35 0.056 547 Mess/Control Rm 4 5" 112/145 33 x 9 297 75 -45 0.069 -916 -916 70 -20 0.060 -353 Lights 7 33 x 31 1023 7 7161 7161 Equipment, sensible 8 565440 565440 Equipment, latent 8 0 0 TO TER CFM Personnel 9 0 0 0 0 15 35 15088 570315 Total 548978 0 548978 *see note
Total Qw w/ equipment running (i.e. Total above minus equipment and lighting loads) = 14289
Total Qw w/o engines running (fans shutdown, no infiltration) = 16575
L = 33 W = 31 H = 9 * Note - assume that fan(s) is run at 50% in winter time
0.5 Minutes per Air Change
5970.00
24205 18414 30175 29340 4.85
Sq. Ft. 1023 ΣQL 0
3 = Outboard Bhd or Shell Height 9 ΣQT 548978
Volume 9207 ΣQW 570315
R of C 0.3051163 CFM 30175
ΣQS 548978 KW 4.9
SHF 1.00 DATE 2/4/2013 REV. -DWG. NO. 793-B685-04
MDC PROJECT NO. 2885
SPACE TEMP COOLING 120ºF SPACE TEMP HEATING 50ºF
Space Temp Underway
Number of pers. =
SHEET 3 OF 8
SUMMARY
Load Constant = cfm *from inside of space
Total Supply Air Required = cfm *includes combustion air
Room Dimensions (ft.)
8 = Equipment 9 = Personnel 7 = Lights cfm Tr Air Flow Requirement = cfm
5 = After Bulkhead
TO = Temperature of Adjoining Space or Outside
QS = Heat Load, BTU/Hr, Sensible
SYMBOLS
TD = Temperature Difference
U = Transmittance, BTU/Sq. Ft./Hr/ºF
4 = Forward Bulkhead
2 = Deck Under QL = Heat Load, BTU/Hr, Latent
1 = Deck Over
KEY
QW = Heat Load, BTU/Hr, Winter
QT = Heat Load, BTU/Hr, Total
6 = Inboard Bulkhead
SPACE SPACE NO. FRAMES
DIMENSIONS
Engine Rm 29-46
Exhaust Air Quantity = cfm
Heating Load =
Temperature Difference =
Rate of Change = Combustion Air Reqmt = kW
Outside Air Temperature =
R of C Air Quantity =
Main qsd qld
STBD Main Engine 246720 0 1.00 Port Main Engine 246720 0 1.00
Generator 1 60000 0 0.50 Generator 2 60000 0 0.50 Transformer 12000 0 1.00
Total
DATE 2/4/2013 REV. -
565440 2827200565440
246720 246720 30000 30000 12000
123360 123360 15000 15000
DWG. NO. 793-B685-04
MDC PROJECT NO. 2885
EQUIP. LOADS USE
FACTOR
MAX PROB.
TOTAL BTU/HR
BTU/HR WITHOUT HOOD
SENSIBLE LATENT
246720 246720 30000
BTU/HR WITH HOOD
SENSIBLE LATENT
SHEET 4 OF 8
Use of hood reduces Max. Prob. Total BTU/HR by 50 %.
SPACE SPACE NO. FRAMES
Engine Rm 1
EQUIPMENT
29-46
REMARKS
30000 12000
Hold
ADJOINING SPACE LOAD
KEY
INSUL
TYPE
U
KEY AREA TO TD U QS QL QT TO TD U QW
Mixed Conditioned 1 4" 112 16 x 31 496 75 -45 0.078 -1741 -1741 70 -20 0.069 -684 Water 2 none n/a 16 x 31 496 85 -35 1.198 -20797 -20797 40 10 1.295 6423 Grey Water 3 4" 110 16 x 10 160 110 -10 0.301 -482 -482 40 10 0.190 304 FO Tank 4 4" 110 31 x 10 310 120 0 0.301 0 0 40 10 0.190 589 Pump Rm 5 4" 110 31 x 10 310 110 -10 0.301 -933 -933 40 10 0.190 589 Grey Water 3 4" 110 16 x 10 160 110 -10 0.301 -482 -482 40 10 0.190 304 Lights 7 16 x 31 496 7 3472 3472 Equipment, sensible 8 24806 24806 Equipment, latent 8 0 0 TO TSP CFM Personnel 9 0 0 0 0 15 35 827 31248 Total 3843 0 3843 *see note 38773
Total Qw w/ equipment running (i.e. Total above minus equipment and lighting loads) = 10495
* Note - assume that fan(s) is run at 50% in winter time L = 16 W = 31 H = 10 3 Minutes per Air Change
0.00 3.07
Sq. Ft. 496 ΣQL 0
3 = Outboard Bhd or Shell Height 10 ΣQT 3843
Volume 4960 ΣQW 31248
R of C 3 CFM 1653
ΣQS 3843 KW 3.1
SHF 1.00 DATE 2/4/2013 REV. -
DIMENSIONS
Load Constant = Space Temp w/ Ventilation
Number of pers. =
SPACE SPACE NO. FRAMES SPACE TEMP COOLING 120ºF SPACE TEMP HEATING 50ºFTank Rm 2 12-20
Room Dimensions (ft.)
Rate of Change =
Combustion Air Reqmt = cfm Outside Air Temperature = Temperature Difference = Tr Air Flow Requirement = cfm
R of C Air Quantity = cfm Exhaust Air Quantity = cfm
Heating Load = kW
KEY SYMBOLS SUMMARY
1 = Deck Over QS = Heat Load, BTU/Hr, Sensible
7 = Lights TO = Temperature of Adjoining Space or Outside DWG. NO. 793-B685-04
2 = Deck Under QL = Heat Load, BTU/Hr, Latent
QT = Heat Load, BTU/Hr, Total
4 = Forward Bulkhead QW = Heat Load, BTU/Hr, Winter
5 = After Bulkhead U = Transmittance, BTU/Sq. Ft./Hr/ºF
6 = Inboard Bulkhead TD = Temperature Difference
8 = Equipment 9 = Personnel MDC PROJECT NO. 2885 SHEET 5 OF 8 qsd qld
FO Purifier 15500 0 0.50 MSD Unit 15500 0 0.30
Blower Motor 2120 0 1.00 Blower Motor 2120 0 1.00
Potable Water Pump 3390 0 0.30 Grey Water Pump 9430 0 0.30 Oily Bilge Pump 580 0 0.30 Lube Oil Pump 580 0 0.30 Gear Oil Pump 580 0 0.30
Hydraulic Oil Pump 580 0 0.30 FLOCS Pump 2650 0 0.30
Black Water Pump 9430 0 0.30
Total
DATE 2/4/2013 REV. -
SPACE SPACE NO. FRAMES
Tank Rm 2 12-20
EQUIPMENT EQUIP. LOADS USE
FACTOR
MAX PROB.
TOTAL BTU/HR
BTU/HR WITHOUT HOOD BTU/HR WITH HOOD REMARKS
SENSIBLE LATENT SENSIBLE LATENT
7750 7750 0 3875 0 4650 4650 0 2325 0 2120 2120 0 1060 0 2120 2120 0 1060 0 1017 1017 0 509 0 2829 2829 0 1415 0 174 174 0 87 0 174 174 0 87 0 174 174 0 87 0 174 174 0 87 0 795 795 0 398 0 2829 2829 0 1415 0
24806 24806 0 12403 0
Use of hood reduces Max. Prob. Total BTU/HR by 50 %.
DWG. NO. 793-B685-04
MDC PROJECT NO. 2885 SHEET 6 OF 8
ADJOINING SPACE LOAD
KEY
INSUL
TYPE
U
KEY AREA TO TD U QS QL QT TO TD U QW
Quarters 1 4" 112 18 x 31 558 75 -45 0.078 -1959 -1959 70 -20 0.069 -770 Water 2 none n/a 18 x 31 558 85 -35 1.198 -23397 -23397 40 10 1.295 7226 Seachest Void 3 4" 110 18 x 10 180 85 -35 0.377 -2375 -2375 40 10 0.210 378 Tank Rm 4 4" 110 31 x 10 310 110 -10 0.301 -933 -933 50 0 0.190 0 Storage Room 5 4" 110 31 x 10 310 110 -10 0.301 -933 -933 50 0 0.190 0 Seachest Void 3 4" 110 18 x 10 180 85 -35 0.377 -2375 -2375 40 10 0.21 378 Lights 7 18 x 31 558 7 3906 3906 Equipment, sensible 8 4278 4278 Equipment, latent 8 0 0 TO TSP CFM Personnel 9 0 0 0 0 15 35 930 35154 Total -23788 0 -23788 42366
Total Qw w/ equipment running (i.e. Total above minus equipment and lighting loads) = 34182
* Note - assume that fan(s) is run at 50% in winter time L = 18 W = 31 H = 10 3 Minutes per Air Change
0.00
-1049 10.01
Sq. Ft. 558 ΣQL 0
3 = Outboard Bhd or Shell Height 10 ΣQT -23788
Volume 5580 ΣQW 35154
R of C 3 CFM 1860
ΣQS -23788 KW 10.0
SHF 1.00 DATE 2/4/2013 REV. -
8 = Equipment 9 = Personnel MDC PROJECT NO. 2885 SHEET 7 OF 8
DWG. NO. 793-B685-04
2 = Deck Under QL = Heat Load, BTU/Hr, Latent
QT = Heat Load, BTU/Hr, Total
4 = Forward Bulkhead QW = Heat Load, BTU/Hr, Winter
5 = After Bulkhead U = Transmittance, BTU/Sq. Ft./Hr/ºF
6 = Inboard Bulkhead TD = Temperature Difference
SUMMARY
1 = Deck Over QS = Heat Load, BTU/Hr, Sensible
7 = Lights TO = Temperature of Adjoining Space or Outside
Heating Load = kW
KEY SYMBOLS
Tr Air Flow Requirement = cfm R of C Air Quantity = cfm
Exhaust Air Quantity = cfm
Temperature Difference =
DIMENSIONS
Load Constant = Space Temp w/ Ventilation
Number of pers. =
Room Dimensions (ft.)
Rate of Change =
Combustion Air Reqmt = cfm Outside Air Temperature =
SPACE SPACE NO. FRAMES SPACE TEMP COOLING 120ºF SPACE TEMP HEATING 50ºFPump Rm 3 20-29 qsd qld
Bilge Pump 2790 0.30 Ballast Pump 2790 0.30
Fire Pump 8680 0.30
Total
DATE 2/4/2013 REV. -
Use of hood reduces Max. Prob. Total BTU/HR by 50 %.
DWG. NO. 793-B685-04
MDC PROJECT NO. 2885 SHEET 8 OF 8
4278 4278 0 2139 0
2604 2604 0 1302 0
BTU/HR WITH HOOD
837 837 0 419 0 837 837 0 419 0
SPACE SPACE NO. FRAMES
Tank Rm 2 20-29
REMARKS
SENSIBLE LATENT SENSIBLE LATENTEQUIPMENT EQUIP. LOADS USE
FACTOR
MAX PROB.
TOTAL BTU/HR
BTU/HR WITHOUT HOOD