793-B685-04 MACHINERY SPACE HEATING AND COOLING LOAD CALCULATIONS.pdf

PDF 171 KB Posted

Attached to
Excavator Barge Federal contract opportunity
Solicitation number
W912BU-23-B-0024
Issued by
Department of the Army Corps of Engineers Engineering District Philadeplhia

About this file

This document contains machinery space heating and cooling load calculations for a 95-foot towboat. The calculations were performed according to ASHRAE standards using outdoor design conditions of 99°F DB and 76°F WB for cooling, and 15°F for heating. Indoor conditions were set at 120°F for cooling and 50°F for heating. Calculations were provided for the engine room, tank room, pump room, storage room, and other machinery spaces. Equipment loads and ventilation requirements were calculated for each space based on rated equipment capacities and specified air change rates. Heating and sensible and latent cooling loads were tabulated along with required supply and exhaust air flows.

View the file

Other files for this federal contract opportunity

Other files attached to Excavator Barge, newest first.
File Type Posted
W912BU-23-B-0024 Amendment 2.pdf PDF
W912BU-23-B-0024 Amendment 1.pdf PDF
W912BU-23-B-0024.pdf PDF
871-B690-01 Compressed Air.pdf PDF
871-B552-01 Spudwell Structure and Spud Handling Sys.pdf PDF
871-B637-01 Waste Oil System.pdf PDF
871-B427-01 Vertical and Inclined Ladders.pdf PDF
871-B415-01 Doors Windows Hatches and Manholes.pdf PDF
871-B309-01 Transverse Structure.pdf PDF
871-B305-01 Scantling Plan.pdf PDF
871-B307-01 Shell Plating.pdf PDF
871-B405-01 Cathodic Protection.pdf PDF
871-B115-01 WEIGHT ESTIMATES.pdf PDF
871-B205-01 PROFILE.pdf PDF
871-B000-02 Drawing Index.pdf PDF
731-E170-01 DRY DOCKING PLAN.pdf PDF
871-B670-01 Vents Sounds Overflows and Fills.pdf PDF
871-B672-01 Drainage System.pdf PDF
871-B720-02 DC One-Line Diagram.pdf PDF
871-B665-01 Potable Water System.pdf PDF
871-B630-01 Fuel Oil System.pdf PDF
871-B410-01 Fendering Details.pdf PDF
871-B399-01 ABS Structure Calculations.pdf PDF
871-B325-01 Seachest Details.pdf PDF
871-B215-01 General Arrangement.pdf PDF
871-B311-01 Longitudinal Structure.pdf PDF
871-B150-01 DAMAGE STABILITY.pdf PDF
703-B725-03 REV- EMERGENCY LIGHTING VOLTAGE DROP AND CABLE SCHEDULE.pdf PDF
871-B760-01 Shore Power and Off-Vessel Power Details.pdf PDF
871-B725-01 Voltage Drop and Cable Schedule.pdf PDF
871-B720-01 Rev A AC One-Line.pdf PDF
871-B710-02 Rev A AC Load Analysis.pdf PDF
871-B667-01 Sewage System.pdf PDF
871-B445-01 Rev A Lifesaving Safety Plan.pdf PDF
871-B635-01 Lube Oil System.pdf PDF
871-B550-01 Spud Contructon Details.pdf PDF
871-B601-01 Pipe Marking Guide.pdf PDF
871-B315-01 Deck House Structure.pdf PDF
871-B320-01 Independent Tanks Details.pdf PDF
871-B130-01 TANK CAPACITY.pdf PDF
871-B125-01 HYDROSTATICS.pdf PDF
871-B105-01 Lines Plan.pdf PDF
793 SAMPLE PLACARD.pdf PDF
703-B685-03 REV- HOT WATER CIRCULATING SYSTEM.pdf PDF
871-B730-03 DC SYS AND E-Lighting.pdf PDF
871-B460-01 HULL MARKINGS.pdf PDF
871-B720-02 DC One Line Diagram.pdf PDF
T1716010 KEEN Stability Letter - signed with Load Charts_106379386.pdf PDF
871-B730-01 Lighting Plan.pdf PDF
871-B730-02 Receptacle Plan.pdf PDF
Show all 50

Excavator Barge has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REV. DATE APRD.

□ Accepted

□ Accepted with Comments

□ Not Accepted Refer to Notations On:

□ Drawing

□ Return Document Resubmission: □ Required □ Not Required Approved Subj. to Approv. Reg. Agcy. Apprvl.

Reviewer:

Date Returned:

Return Document No.:

REVISIONS

DESCRIPTION

Original Issue

GENERAL NOTES:

Per ASHRAE, the following design conditions were used:

Outdoor Cooling - 99°F D.B. / 76°F W.B.

Outdoor Heating - 15°F

Indoor Cooling - 120°F Indoor Heating - 50°F

Rate of Change for Engine Room - 2 air changes per minute Rate of Change for Tank Room - 3 minutes per air change Rate of Change for Pump Room - 3 minutes per air change

Note - For storage room, assume that the ventilation and heating required will be half that of the tank room. No calculation sheet is included. The storage room will be outfitted with an exhaust fan only, no suppy fan will be provided.

Space heating sized to maintain 50°F while only running fans at 50% rating (not full rated CFM). It is unlikely that the fans will need to be operated at full rated CFM during winter conditions. Additionally, it is assumed that equipment and lighting is operational during the winter so the heat generated by that equipment is subtracted from the required heating load.

All glass windows and door windows are assumed to be single pane.

Insulation values are based on SNAME T&R 4-7.

MDC REVIEW

DR. BY DES. BY CHK'D BY

VCB JDC

APRD. FOR THE DIR. - CH. DES. BR. SIZE REV.

DATE

SHEET: 1 OF 8

DEPARTMENT OF THE ARMY

MARINE DESIGN CENTER

CORPS OF ENGINEERS

02/04/13 SCALE: AS SHOWN

LITTLE ROCK DISTRICT - TOWBOAT

95' x 39' x 10'

MACHINERY SPACE HEATING &

VENTILATION LOAD CALCULATIONS

RECOMMENDED

/S/ Tim Keyser, PE

PROJECT NO. DRAWING NO.

/S/ Greg Lee, PE A 2885 793-B685-04 -

MARINE DESIGN CENTER

100 PENN SQUARE EAST

PHILADELPHIA, PA 19107

SPACE

NO. SENS LATENT TOTAL R/C PERS HEAT

Engine Rm 1 Main CL 548978 0 548978 1 18414 0 24205 30175 0.31 29340 4.85 Tank Rm 2 Hold CL 3843 0 3843 1 1653 0 169 1653 3 2004 3.07 Pump Rm 3 Hold CL -23788 -23788 1 1860 0 -1049 1860 3 2255 10.01 Storage Rm 4 Hold CL ----- ----- ----- 0 ----- ----- ----- ----- ----- 1002 1.54

DATE 2/4/2013 REV. -

MDC PROJECT NO. 2885

DWG. NO. 793-B685-04

SHEET 2 OF 8

Heating Load

(kw) REMARKS

Towboat - Machinery Space Heating & Ventilation Load Calculations SPACE DECK SIDE BTU/HR SHF Outside Air Based On CFM R/C TOTAL

AIR Exhaust CFM

DECK

Main

ADJOINING SPACE LOAD

KEY

INSUL

TYPE

U

KEY AREA TO TD U QS QL QT TO TD U QW

Weather 1 5" 112/145 33 x 31 1023 145 25 0.079 2008 2008 15 35 0.056 2005 Void 2 none n/a 33 x 31 1023 100 -20 1.198 -24511 -24511 40 10 1.295 13248 Weather (Port Side) 3 5" 112/145 33 x 9 297 125 5 0.076 113 113 15 35 0.056 582 Weather (Stbd Side) 3 5" 112/145 31 x 9 279 99 -21 0.071 -416 -416 15 35 0.056 547 Weather 5 5" 112/145 31 x 9 279 125 5 0.071 99 99 15 35 0.056 547 Mess/Control Rm 4 5" 112/145 33 x 9 297 75 -45 0.069 -916 -916 70 -20 0.060 -353 Lights 7 33 x 31 1023 7 7161 7161 Equipment, sensible 8 565440 565440 Equipment, latent 8 0 0 TO TER CFM Personnel 9 0 0 0 0 15 35 15088 570315 Total 548978 0 548978 *see note

Total Qw w/ equipment running (i.e. Total above minus equipment and lighting loads) = 14289

Total Qw w/o engines running (fans shutdown, no infiltration) = 16575

L = 33 W = 31 H = 9 * Note - assume that fan(s) is run at 50% in winter time

0.5 Minutes per Air Change

5970.00

24205 18414 30175 29340 4.85

Sq. Ft. 1023 ΣQL 0

3 = Outboard Bhd or Shell Height 9 ΣQT 548978

Volume 9207 ΣQW 570315

R of C 0.3051163 CFM 30175

ΣQS 548978 KW 4.9

SHF 1.00 DATE 2/4/2013 REV. -DWG. NO. 793-B685-04

MDC PROJECT NO. 2885

SPACE TEMP COOLING 120ºF SPACE TEMP HEATING 50ºF

Space Temp Underway

Number of pers. =

SHEET 3 OF 8

SUMMARY

Load Constant = cfm *from inside of space

Total Supply Air Required = cfm *includes combustion air

Room Dimensions (ft.)

8 = Equipment 9 = Personnel 7 = Lights cfm Tr Air Flow Requirement = cfm

5 = After Bulkhead

TO = Temperature of Adjoining Space or Outside

QS = Heat Load, BTU/Hr, Sensible

SYMBOLS

TD = Temperature Difference

U = Transmittance, BTU/Sq. Ft./Hr/ºF

4 = Forward Bulkhead

2 = Deck Under QL = Heat Load, BTU/Hr, Latent

1 = Deck Over

KEY

QW = Heat Load, BTU/Hr, Winter

QT = Heat Load, BTU/Hr, Total

6 = Inboard Bulkhead

SPACE SPACE NO. FRAMES

DIMENSIONS

Engine Rm 29-46

Exhaust Air Quantity = cfm

Heating Load =

Temperature Difference =

Rate of Change = Combustion Air Reqmt = kW

Outside Air Temperature =

R of C Air Quantity =

Main qsd qld

STBD Main Engine 246720 0 1.00 Port Main Engine 246720 0 1.00

Generator 1 60000 0 0.50 Generator 2 60000 0 0.50 Transformer 12000 0 1.00

Total

DATE 2/4/2013 REV. -

565440 2827200565440

246720 246720 30000 30000 12000

123360 123360 15000 15000

DWG. NO. 793-B685-04

MDC PROJECT NO. 2885

EQUIP. LOADS USE

FACTOR

MAX PROB.

TOTAL BTU/HR

BTU/HR WITHOUT HOOD

SENSIBLE LATENT

246720 246720 30000

BTU/HR WITH HOOD

SENSIBLE LATENT

SHEET 4 OF 8

Use of hood reduces Max. Prob. Total BTU/HR by 50 %.

SPACE SPACE NO. FRAMES

Engine Rm 1

EQUIPMENT

29-46

REMARKS

30000 12000

Hold

ADJOINING SPACE LOAD

KEY

INSUL

TYPE

U

KEY AREA TO TD U QS QL QT TO TD U QW

Mixed Conditioned 1 4" 112 16 x 31 496 75 -45 0.078 -1741 -1741 70 -20 0.069 -684 Water 2 none n/a 16 x 31 496 85 -35 1.198 -20797 -20797 40 10 1.295 6423 Grey Water 3 4" 110 16 x 10 160 110 -10 0.301 -482 -482 40 10 0.190 304 FO Tank 4 4" 110 31 x 10 310 120 0 0.301 0 0 40 10 0.190 589 Pump Rm 5 4" 110 31 x 10 310 110 -10 0.301 -933 -933 40 10 0.190 589 Grey Water 3 4" 110 16 x 10 160 110 -10 0.301 -482 -482 40 10 0.190 304 Lights 7 16 x 31 496 7 3472 3472 Equipment, sensible 8 24806 24806 Equipment, latent 8 0 0 TO TSP CFM Personnel 9 0 0 0 0 15 35 827 31248 Total 3843 0 3843 *see note 38773

Total Qw w/ equipment running (i.e. Total above minus equipment and lighting loads) = 10495

* Note - assume that fan(s) is run at 50% in winter time L = 16 W = 31 H = 10 3 Minutes per Air Change

0.00 3.07

Sq. Ft. 496 ΣQL 0

3 = Outboard Bhd or Shell Height 10 ΣQT 3843

Volume 4960 ΣQW 31248

R of C 3 CFM 1653

ΣQS 3843 KW 3.1

SHF 1.00 DATE 2/4/2013 REV. -

DIMENSIONS

Load Constant = Space Temp w/ Ventilation

Number of pers. =

SPACE SPACE NO. FRAMES SPACE TEMP COOLING 120ºF SPACE TEMP HEATING 50ºFTank Rm 2 12-20

Room Dimensions (ft.)

Rate of Change =

Combustion Air Reqmt = cfm Outside Air Temperature = Temperature Difference = Tr Air Flow Requirement = cfm

R of C Air Quantity = cfm Exhaust Air Quantity = cfm

Heating Load = kW

KEY SYMBOLS SUMMARY

1 = Deck Over QS = Heat Load, BTU/Hr, Sensible

7 = Lights TO = Temperature of Adjoining Space or Outside DWG. NO. 793-B685-04

2 = Deck Under QL = Heat Load, BTU/Hr, Latent

QT = Heat Load, BTU/Hr, Total

4 = Forward Bulkhead QW = Heat Load, BTU/Hr, Winter

5 = After Bulkhead U = Transmittance, BTU/Sq. Ft./Hr/ºF

6 = Inboard Bulkhead TD = Temperature Difference

8 = Equipment 9 = Personnel MDC PROJECT NO. 2885 SHEET 5 OF 8 qsd qld

FO Purifier 15500 0 0.50 MSD Unit 15500 0 0.30

Blower Motor 2120 0 1.00 Blower Motor 2120 0 1.00

Potable Water Pump 3390 0 0.30 Grey Water Pump 9430 0 0.30 Oily Bilge Pump 580 0 0.30 Lube Oil Pump 580 0 0.30 Gear Oil Pump 580 0 0.30

Hydraulic Oil Pump 580 0 0.30 FLOCS Pump 2650 0 0.30

Black Water Pump 9430 0 0.30

Total

DATE 2/4/2013 REV. -

SPACE SPACE NO. FRAMES

Tank Rm 2 12-20

EQUIPMENT EQUIP. LOADS USE

FACTOR

MAX PROB.

TOTAL BTU/HR

BTU/HR WITHOUT HOOD BTU/HR WITH HOOD REMARKS

SENSIBLE LATENT SENSIBLE LATENT

7750 7750 0 3875 0 4650 4650 0 2325 0 2120 2120 0 1060 0 2120 2120 0 1060 0 1017 1017 0 509 0 2829 2829 0 1415 0 174 174 0 87 0 174 174 0 87 0 174 174 0 87 0 174 174 0 87 0 795 795 0 398 0 2829 2829 0 1415 0

24806 24806 0 12403 0

Use of hood reduces Max. Prob. Total BTU/HR by 50 %.

DWG. NO. 793-B685-04

MDC PROJECT NO. 2885 SHEET 6 OF 8

ADJOINING SPACE LOAD

KEY

INSUL

TYPE

U

KEY AREA TO TD U QS QL QT TO TD U QW

Quarters 1 4" 112 18 x 31 558 75 -45 0.078 -1959 -1959 70 -20 0.069 -770 Water 2 none n/a 18 x 31 558 85 -35 1.198 -23397 -23397 40 10 1.295 7226 Seachest Void 3 4" 110 18 x 10 180 85 -35 0.377 -2375 -2375 40 10 0.210 378 Tank Rm 4 4" 110 31 x 10 310 110 -10 0.301 -933 -933 50 0 0.190 0 Storage Room 5 4" 110 31 x 10 310 110 -10 0.301 -933 -933 50 0 0.190 0 Seachest Void 3 4" 110 18 x 10 180 85 -35 0.377 -2375 -2375 40 10 0.21 378 Lights 7 18 x 31 558 7 3906 3906 Equipment, sensible 8 4278 4278 Equipment, latent 8 0 0 TO TSP CFM Personnel 9 0 0 0 0 15 35 930 35154 Total -23788 0 -23788 42366

Total Qw w/ equipment running (i.e. Total above minus equipment and lighting loads) = 34182

* Note - assume that fan(s) is run at 50% in winter time L = 18 W = 31 H = 10 3 Minutes per Air Change

0.00

-1049 10.01

Sq. Ft. 558 ΣQL 0

3 = Outboard Bhd or Shell Height 10 ΣQT -23788

Volume 5580 ΣQW 35154

R of C 3 CFM 1860

ΣQS -23788 KW 10.0

SHF 1.00 DATE 2/4/2013 REV. -

8 = Equipment 9 = Personnel MDC PROJECT NO. 2885 SHEET 7 OF 8

DWG. NO. 793-B685-04

2 = Deck Under QL = Heat Load, BTU/Hr, Latent

QT = Heat Load, BTU/Hr, Total

4 = Forward Bulkhead QW = Heat Load, BTU/Hr, Winter

5 = After Bulkhead U = Transmittance, BTU/Sq. Ft./Hr/ºF

6 = Inboard Bulkhead TD = Temperature Difference

SUMMARY

1 = Deck Over QS = Heat Load, BTU/Hr, Sensible

7 = Lights TO = Temperature of Adjoining Space or Outside

Heating Load = kW

KEY SYMBOLS

Tr Air Flow Requirement = cfm R of C Air Quantity = cfm

Exhaust Air Quantity = cfm

Temperature Difference =

DIMENSIONS

Load Constant = Space Temp w/ Ventilation

Number of pers. =

Room Dimensions (ft.)

Rate of Change =

Combustion Air Reqmt = cfm Outside Air Temperature =

SPACE SPACE NO. FRAMES SPACE TEMP COOLING 120ºF SPACE TEMP HEATING 50ºFPump Rm 3 20-29 qsd qld

Bilge Pump 2790 0.30 Ballast Pump 2790 0.30

Fire Pump 8680 0.30

Total

DATE 2/4/2013 REV. -

Use of hood reduces Max. Prob. Total BTU/HR by 50 %.

DWG. NO. 793-B685-04

MDC PROJECT NO. 2885 SHEET 8 OF 8

4278 4278 0 2139 0

2604 2604 0 1302 0

BTU/HR WITH HOOD

837 837 0 419 0 837 837 0 419 0

SPACE SPACE NO. FRAMES

Tank Rm 2 20-29

REMARKS

SENSIBLE LATENT SENSIBLE LATENTEQUIPMENT EQUIP. LOADS USE

FACTOR

MAX PROB.

TOTAL BTU/HR

BTU/HR WITHOUT HOOD