This document provides an emergency lighting voltage drop and cable schedule for a floating crane project. It details the circuit layout and voltage drop calculations for various emergency lighting loads across the crane, including shops, engine control rooms, generator rooms, tank rooms, rigging rooms, store rooms, and deck areas. Cable sizes and lengths are specified for each circuit branch. Voltage drop percentages are calculated to confirm code compliance for each circuit.
View the file
Other files for this federal contract opportunity
Show all 50
Excavator Barge has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REV. DATE APRD.
□ Accepted
□ Accepted with Comments
□ Not Accepted Refer to Notations On:
□ Drawing
□ Return Document Resubmission: □ Required □ Not Required Approved Subj. to Approv. Reg. Agcy. Apprvl.
Reviewer:
Date Returned:
Return Document No.:
General Notes:
DR. BY DES. BY CHK'D BY
IGS IGS SNT
APRD. FOR THE DIR. - CH. DES. BR. SIZE REV.
DATE
SHEET: COVERJuly 12, 2016 SCALE: NTS
CEMVR, FLOATING CRANE
300' x 68' x 12'
EMERGENCY LIGHTING VOLTAGE
DROP & CABLE SCHEDULE
RECOMMENDED - SECT. CH.
/ / J.COATSWORTH
PROJECT NO. DRAWING NO.
/ / G. LEE A 2685 703-B725-03 -
REVISIONS
DESCRIPTION
Original Issue
MDC REVIEW
MARINE DESIGN CENTER
100 PENN SQUARE EAST
PHILADELPHIA, PA 19107
DEPARTMENT OF THE ARMY
MARINE DESIGN CENTER
CORPS OF ENGINEERS
CIRCUIT CABLE Cm L A V VD VD% VD%
LOAD GROUP NUBMER SIZE TOTAL
FROM BATTERY BANK TO PANEL E1 E1 D-66 66370 15 26.4 24 0.154 0.64 0.64
SHOP (PORT) EM LIGHTS E1-1 T-10 10380 60 4.2 24 0.626 2.61 3.25
SHOP (PORT) EM LIGHTS E1-1A T-6 6530 70 1.0 24 0.288 1.20 4.45
SHOP (PORT) EM LIGHTS E1-1B T-6 6530 65 1.0 24 0.267 1.11 4.36
SHOP (PORT) EM LIGHTS E1-1C T-6 6530 40 1.0 24 0.164 0.68 3.94
SHOP (PORT) EM LIGHTS E1-1D T-6 6530 50 1.0 24 0.205 0.86 4.11
CIRCUIT CABLE Cm L A V VD VD% VD%
LOAD GROUP NUBMER SIZE TOTAL
SHOP (STBD) EM LIGHTS E1-2 T-6 6530 30 4.2 24 0.498 2.07 2.72
SHOP (STBD) EM LIGHTS E1-2A T-6 6530 50 1.0 24 0.205 0.86 3.57
SHOP (STBD) EM LIGHTS E1-2B T-6 6530 35 1.0 24 0.144 0.60 3.31
SHOP (STBD) EM LIGHTS E1-2C T-6 6530 40 1.0 24 0.164 0.68 3.40
SHOP (STBD) EM LIGHTS E1-2D T-6 6530 50 1.0 24 0.205 0.86 3.57
E1 - EMERGENCY LIGHTING VOLTAGE DROP CALCULATIONS
2685 - CEMVR FLOATING CRANE
VOLTAGE DROP EQUATIONS
SINGLE PHASE VD=(2KxLxI)/Cm K=12.9 FOR Cu
FROM PANEL E1 TO SHOP (PORT) EM LIGHTS
FROM PANEL E1 TO SHOP (STBD) EM LIGHTS
ECR EM LIGHTING E1-3 T-10 10380 50 6.3 24 0.783 3.26 3.90
ECR EM LIGHTING E1-3A T-6 6530 15 1.0 24 0.062 0.26 4.16
ECR EM LIGHTING E1-3B T-6 6530 15 1.0 24 0.062 0.26 4.16
ECR EM LIGHTING E1-3C T-6 6530 15 2.1 24 0.123 0.51 4.42
ECR EM LIGHTING E1-3D T-6 6530 10 2.1 24 0.082 0.34 4.25
ECR EM LIGHTING E1-3C-1 T-6 6530 10 1.0 24 0.041 0.17 4.59
ECR EM LIGHTING E1-3D-1 T-6 6530 10 1.0 24 0.041 0.17 4.42
CIRCUIT CABLE Cm L A V VD VD% VD%
LOAD GROUP NUBMER SIZE TOTAL
GENERATOR RM EM LIGHTING E1-4 T-16 16510 70 6.3 24 0.689 2.87 3.51
GENERATOR RM EM LIGHTING E1-4A T-6 6530 20 2.1 24 0.164 0.68 4.20
GENERATOR RM EM LIGHTING E1-4B T-6 6530 15 2.1 24 0.123 0.51 4.03
GENERATOR RM EM LIGHTING E1-4C T-6 6530 20 2.1 24 0.164 0.68 4.20
GENERATOR RM EM LIGHTING E1-4A-1 T-6 6530 10 1.0 24 0.041 0.17 4.37
GENERATOR RM EM LIGHTING E1-4B-1 T-6 6530 10 1.0 24 0.041 0.17 4.20
GENERATOR RM EM LIGHTING E1-4C-1 T-6 6530 25 1.0 24 0.103 0.43 4.63
GENERATOR RM EM LIGHTING E1-4C-2 T-6 6530 20 1.0 24 0.082 0.34 4.54
FROM PANEL E1 TO ENGINEER CONTROL RM EM LIGHTING
FROM PANEL E1 TO GENERATOR RM EM LIGHTING
MAIN DECK HEAD & GALLEY EM LIGHTING E1-5 T-6 6530 40 1.3 24 0.205 0.86 1.50
MAIN DECK HEAD & GALLEY EM LIGHTING E1-5A T-6 6530 15 0.7 24 0.039 0.16 1.66
MAIN DECK HEAD & GALLEY EM LIGHTING E1-5B T-6 6530 20 0.3 24 0.026 0.11 1.61
MAIN DECK HEAD & GALLEY EM LIGHTING E1-5C T-6 6530 25 0.3 24 0.033 0.14 1.63
MAIN DECK HEAD & GALLEY EM LIGHTING E1-5A-1 T-6 6530 15 0.3 24 0.020 0.08 1.74
CIRCUIT CABLE Cm L A V VD VD% VD%
LOAD GROUP NUBMER SIZE TOTAL
UPPER DECK EM LIGHTING E1-6 T-10 10380 50 4.1 24 0.510 2.12 2.76
UPPER DECK EM LIGHTING E1-6A T-6 6530 20 1.7 24 0.131 0.55 3.31
UPPER DECK EM LIGHTING E1-6B T-6 6530 10 0.3 24 0.013 0.05 2.82
UPPER DECK EM LIGHTING E1-6C T-6 6530 10 2.1 24 0.082 0.34 3.11
UPPER DECK EM LIGHTING E1-6A-1 T-6 6530 10 0.3 24 0.013 0.05 3.37
UPPER DECK EM LIGHTING E1-6A-2 T-6 6530 10 0.3 24 0.013 0.05 3.37
UPPER DECK EM LIGHTING E1-6A-3 T-6 6530 10 1.0 24 0.041 0.17 3.48
UPPER DECK EM LIGHTING E1-6C-1 T-6 6530 50 1.0 24 0.205 0.86 3.96
FROM PANEL E1 TO MAIN DECK HEAD & GALLEY EM LIGHTING
FROM PANEL E1 TO UPPER DECK EM LIGHTING
FROM BATTERY BANK TO PANEL E2 E2 D-66 66370 15 26.1 24 0.152 0.63 0.63
RIGGING RM EM LIGHTS E2-1 T-16 16510 100 4.2 24 0.656 2.73 3.37
RIGGING RM EM LIGHTS E2-1A T-6 6530 10 2.1 24 0.082 0.34 3.71
RIGGING RM EM LIGHTS E2-1B T-6 6530 30 1.0 24 0.123 0.51 3.88
RIGGING RM EM LIGHTS E2-1C T-6 6530 20 1.0 24 0.082 0.34 3.71
RIGGING RM EM LIGHTS E2-1A-1 T-6 6530 15 1.0 24 0.062 0.26 3.97
CIRCUIT CABLE Cm L A V VD VD% VD%
LOAD GROUP NUBMER SIZE TOTAL
TANK RM EM LIGHTS E2-2 T-10 10380 60 4.2 24 0.626 2.61 3.24
TANK RM EM LIGHTS E2-2A T-6 6530 30 1.0 24 0.123 0.51 3.76
TANK RM EM LIGHTS E2-2B T-6 6530 25 2.1 24 0.205 0.86 4.10
TANK RM EM LIGHTS E2-2C T-6 6530 30 1.0 24 0.123 0.51 3.76
TANK RM EM LIGHTS E2-2B-1 T-6 6530 30 1.0 24 0.123 0.51 4.61
TANK RM EM LIGHTS E2-2B-2 T-6 6530 30 1.0 24 0.123 0.51 4.61
FROM PANEL E2 TO TANK RM EM LIGHTS
FROM PANEL E2 TO RIGGING RM EM LIGHTS
SINGLE PHASE VD=(2KxLxI)/Cm K=12.9 FOR Cu
E2 - EMERGENCY LIGHTING VOLTAGE DROP CALCULATIONS
2685 - CEMVR FLOATING CRANE
VOLTAGE DROP EQUATIONS
STORE RM, 4-P, & 5-P EM LIGHTING E2-3 T-6 6530 30 5.2 24 0.616 2.57 3.20
STORE RM, 4-P, & 5-P EM LIGHTING E2-3A T-6 6530 25 1.0 24 0.103 0.43 3.63
STORE RM, 4-P, & 5-P EM LIGHTING E2-3B T-6 6530 55 1.0 24 0.226 0.94 4.14
STORE RM, 4-P, & 5-P EM LIGHTING E2-3C T-6 6530 10 2.1 24 0.082 0.34 3.54
STORE RM, 4-P, & 5-P EM LIGHTING E2-3D T-6 6530 25 1.0 24 0.103 0.43 3.63
STORE RM, 4-P, & 5-P EM LIGHTING E2-3C-1 T-6 6530 10 1.0 24 0.041 0.17 3.80
CIRCUIT CABLE Cm L A V VD VD% VD%
LOAD GROUP NUBMER SIZE TOTAL
STORE RM, 4-S, & 5-S EM LIGHTING E2-4 T-10 10380 60 5.2 24 0.775 3.23 3.87
STORE RM, 4-S, & 5-S EM LIGHTING E2-4A T-6 6530 25 1.0 24 0.103 0.43 4.29
STORE RM, 4-S, & 5-S EM LIGHTING E2-4B T-6 6530 55 1.0 24 0.226 0.94 4.81
STORE RM, 4-S, & 5-S EM LIGHTING E2-4C T-6 6530 10 2.1 24 0.082 0.34 4.21
STORE RM, 4-S, & 5-S EM LIGHTING E2-4D T-6 6530 25 1.0 24 0.103 0.43 4.29
STORE RM, 4-S, & 5-S EM LIGHTING E2-4C-1 T-6 6530 10 1.0 24 0.041 0.17 4.46
FROM PANEL E2 TO STORE RM, 4-P, & 5-P EM LIGHTING
FROM PANEL E2 TO STORE RM, 4-S, & 5-S EM LIGHTING
6-P & 7-C EM LIGHTING E2-5 T-16 16510 100 3.1 24 0.484 2.02 2.65
6-P & 7-C EM LIGHTING E2-5A T-6 6530 20 1.0 24 0.082 0.34 3.00
6-P & 7-C EM LIGHTING E2-5B T-6 6530 35 2.1 24 0.288 1.20 3.85
6-P & 7-C EM LIGHTING E2-5B-1 T-6 6530 10 1.0 24 0.041 0.17 4.02
CIRCUIT CABLE Cm L A V VD VD% VD%
LOAD GROUP NUBMER SIZE TOTAL
6-S EM LIGHTING E2-6 T-16 16510 130 4.2 24 0.853 3.56 4.19
6-S EM LIGHTING E2-6A T-6 6530 15 1.0 24 0.062 0.26 4.45
6-S EM LIGHTING E2-6B T-6 6530 20 1.0 24 0.082 0.34 4.53
6-S EM LIGHTING E2-6C T-6 6530 15 2.1 24 0.123 0.51 4.70
6-S EM LIGHTING E2-6C-1 T-6 6530 10 1.0 24 0.041 0.17 4.87