703-B725-03 REV- EMERGENCY LIGHTING VOLTAGE DROP AND CABLE SCHEDULE.pdf

PDF 113 KB Posted

Attached to
Excavator Barge Federal contract opportunity
Solicitation number
W912BU-23-B-0024
Issued by
Department of the Army Corps of Engineers Engineering District Philadeplhia

About this file

This document provides an emergency lighting voltage drop and cable schedule for a floating crane project. It details the circuit layout and voltage drop calculations for various emergency lighting loads across the crane, including shops, engine control rooms, generator rooms, tank rooms, rigging rooms, store rooms, and deck areas. Cable sizes and lengths are specified for each circuit branch. Voltage drop percentages are calculated to confirm code compliance for each circuit.

View the file

Other files for this federal contract opportunity

Other files attached to Excavator Barge, newest first.
File Type Posted
W912BU-23-B-0024 Amendment 2.pdf PDF
W912BU-23-B-0024 Amendment 1.pdf PDF
W912BU-23-B-0024.pdf PDF
871-B690-01 Compressed Air.pdf PDF
871-B552-01 Spudwell Structure and Spud Handling Sys.pdf PDF
871-B637-01 Waste Oil System.pdf PDF
871-B427-01 Vertical and Inclined Ladders.pdf PDF
871-B415-01 Doors Windows Hatches and Manholes.pdf PDF
871-B309-01 Transverse Structure.pdf PDF
871-B305-01 Scantling Plan.pdf PDF
871-B307-01 Shell Plating.pdf PDF
871-B405-01 Cathodic Protection.pdf PDF
871-B115-01 WEIGHT ESTIMATES.pdf PDF
871-B205-01 PROFILE.pdf PDF
871-B000-02 Drawing Index.pdf PDF
731-E170-01 DRY DOCKING PLAN.pdf PDF
871-B670-01 Vents Sounds Overflows and Fills.pdf PDF
871-B672-01 Drainage System.pdf PDF
871-B720-02 DC One-Line Diagram.pdf PDF
871-B665-01 Potable Water System.pdf PDF
871-B630-01 Fuel Oil System.pdf PDF
871-B410-01 Fendering Details.pdf PDF
871-B399-01 ABS Structure Calculations.pdf PDF
871-B325-01 Seachest Details.pdf PDF
871-B215-01 General Arrangement.pdf PDF
871-B311-01 Longitudinal Structure.pdf PDF
871-B150-01 DAMAGE STABILITY.pdf PDF
871-B760-01 Shore Power and Off-Vessel Power Details.pdf PDF
871-B725-01 Voltage Drop and Cable Schedule.pdf PDF
871-B720-01 Rev A AC One-Line.pdf PDF
871-B710-02 Rev A AC Load Analysis.pdf PDF
871-B667-01 Sewage System.pdf PDF
871-B445-01 Rev A Lifesaving Safety Plan.pdf PDF
871-B635-01 Lube Oil System.pdf PDF
871-B550-01 Spud Contructon Details.pdf PDF
871-B601-01 Pipe Marking Guide.pdf PDF
871-B315-01 Deck House Structure.pdf PDF
871-B320-01 Independent Tanks Details.pdf PDF
871-B130-01 TANK CAPACITY.pdf PDF
871-B125-01 HYDROSTATICS.pdf PDF
871-B105-01 Lines Plan.pdf PDF
793-B685-04 MACHINERY SPACE HEATING AND COOLING LOAD CALCULATIONS.pdf PDF
793 SAMPLE PLACARD.pdf PDF
703-B685-03 REV- HOT WATER CIRCULATING SYSTEM.pdf PDF
871-B730-03 DC SYS AND E-Lighting.pdf PDF
871-B460-01 HULL MARKINGS.pdf PDF
871-B720-02 DC One Line Diagram.pdf PDF
T1716010 KEEN Stability Letter - signed with Load Charts_106379386.pdf PDF
871-B730-01 Lighting Plan.pdf PDF
871-B730-02 Receptacle Plan.pdf PDF
Show all 50

Excavator Barge has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REV. DATE APRD.

□ Accepted

□ Accepted with Comments

□ Not Accepted Refer to Notations On:

□ Drawing

□ Return Document Resubmission: □ Required □ Not Required Approved Subj. to Approv. Reg. Agcy. Apprvl.

Reviewer:

Date Returned:

Return Document No.:

General Notes:

DR. BY DES. BY CHK'D BY

IGS IGS SNT

APRD. FOR THE DIR. - CH. DES. BR. SIZE REV.

DATE

SHEET: COVERJuly 12, 2016 SCALE: NTS

CEMVR, FLOATING CRANE

300' x 68' x 12'

EMERGENCY LIGHTING VOLTAGE

DROP & CABLE SCHEDULE

RECOMMENDED - SECT. CH.

/ / J.COATSWORTH

PROJECT NO. DRAWING NO.

/ / G. LEE A 2685 703-B725-03 -

REVISIONS

DESCRIPTION

Original Issue

MDC REVIEW

MARINE DESIGN CENTER

100 PENN SQUARE EAST

PHILADELPHIA, PA 19107

DEPARTMENT OF THE ARMY

MARINE DESIGN CENTER

CORPS OF ENGINEERS

CIRCUIT CABLE Cm L A V VD VD% VD%

LOAD GROUP NUBMER SIZE TOTAL

FROM BATTERY BANK TO PANEL E1 E1 D-66 66370 15 26.4 24 0.154 0.64 0.64

SHOP (PORT) EM LIGHTS E1-1 T-10 10380 60 4.2 24 0.626 2.61 3.25

SHOP (PORT) EM LIGHTS E1-1A T-6 6530 70 1.0 24 0.288 1.20 4.45

SHOP (PORT) EM LIGHTS E1-1B T-6 6530 65 1.0 24 0.267 1.11 4.36

SHOP (PORT) EM LIGHTS E1-1C T-6 6530 40 1.0 24 0.164 0.68 3.94

SHOP (PORT) EM LIGHTS E1-1D T-6 6530 50 1.0 24 0.205 0.86 4.11

CIRCUIT CABLE Cm L A V VD VD% VD%

LOAD GROUP NUBMER SIZE TOTAL

SHOP (STBD) EM LIGHTS E1-2 T-6 6530 30 4.2 24 0.498 2.07 2.72

SHOP (STBD) EM LIGHTS E1-2A T-6 6530 50 1.0 24 0.205 0.86 3.57

SHOP (STBD) EM LIGHTS E1-2B T-6 6530 35 1.0 24 0.144 0.60 3.31

SHOP (STBD) EM LIGHTS E1-2C T-6 6530 40 1.0 24 0.164 0.68 3.40

SHOP (STBD) EM LIGHTS E1-2D T-6 6530 50 1.0 24 0.205 0.86 3.57

E1 - EMERGENCY LIGHTING VOLTAGE DROP CALCULATIONS

2685 - CEMVR FLOATING CRANE

VOLTAGE DROP EQUATIONS

SINGLE PHASE VD=(2KxLxI)/Cm K=12.9 FOR Cu

FROM PANEL E1 TO SHOP (PORT) EM LIGHTS

FROM PANEL E1 TO SHOP (STBD) EM LIGHTS

ECR EM LIGHTING E1-3 T-10 10380 50 6.3 24 0.783 3.26 3.90

ECR EM LIGHTING E1-3A T-6 6530 15 1.0 24 0.062 0.26 4.16

ECR EM LIGHTING E1-3B T-6 6530 15 1.0 24 0.062 0.26 4.16

ECR EM LIGHTING E1-3C T-6 6530 15 2.1 24 0.123 0.51 4.42

ECR EM LIGHTING E1-3D T-6 6530 10 2.1 24 0.082 0.34 4.25

ECR EM LIGHTING E1-3C-1 T-6 6530 10 1.0 24 0.041 0.17 4.59

ECR EM LIGHTING E1-3D-1 T-6 6530 10 1.0 24 0.041 0.17 4.42

CIRCUIT CABLE Cm L A V VD VD% VD%

LOAD GROUP NUBMER SIZE TOTAL

GENERATOR RM EM LIGHTING E1-4 T-16 16510 70 6.3 24 0.689 2.87 3.51

GENERATOR RM EM LIGHTING E1-4A T-6 6530 20 2.1 24 0.164 0.68 4.20

GENERATOR RM EM LIGHTING E1-4B T-6 6530 15 2.1 24 0.123 0.51 4.03

GENERATOR RM EM LIGHTING E1-4C T-6 6530 20 2.1 24 0.164 0.68 4.20

GENERATOR RM EM LIGHTING E1-4A-1 T-6 6530 10 1.0 24 0.041 0.17 4.37

GENERATOR RM EM LIGHTING E1-4B-1 T-6 6530 10 1.0 24 0.041 0.17 4.20

GENERATOR RM EM LIGHTING E1-4C-1 T-6 6530 25 1.0 24 0.103 0.43 4.63

GENERATOR RM EM LIGHTING E1-4C-2 T-6 6530 20 1.0 24 0.082 0.34 4.54

FROM PANEL E1 TO ENGINEER CONTROL RM EM LIGHTING

FROM PANEL E1 TO GENERATOR RM EM LIGHTING

MAIN DECK HEAD & GALLEY EM LIGHTING E1-5 T-6 6530 40 1.3 24 0.205 0.86 1.50

MAIN DECK HEAD & GALLEY EM LIGHTING E1-5A T-6 6530 15 0.7 24 0.039 0.16 1.66

MAIN DECK HEAD & GALLEY EM LIGHTING E1-5B T-6 6530 20 0.3 24 0.026 0.11 1.61

MAIN DECK HEAD & GALLEY EM LIGHTING E1-5C T-6 6530 25 0.3 24 0.033 0.14 1.63

MAIN DECK HEAD & GALLEY EM LIGHTING E1-5A-1 T-6 6530 15 0.3 24 0.020 0.08 1.74

CIRCUIT CABLE Cm L A V VD VD% VD%

LOAD GROUP NUBMER SIZE TOTAL

UPPER DECK EM LIGHTING E1-6 T-10 10380 50 4.1 24 0.510 2.12 2.76

UPPER DECK EM LIGHTING E1-6A T-6 6530 20 1.7 24 0.131 0.55 3.31

UPPER DECK EM LIGHTING E1-6B T-6 6530 10 0.3 24 0.013 0.05 2.82

UPPER DECK EM LIGHTING E1-6C T-6 6530 10 2.1 24 0.082 0.34 3.11

UPPER DECK EM LIGHTING E1-6A-1 T-6 6530 10 0.3 24 0.013 0.05 3.37

UPPER DECK EM LIGHTING E1-6A-2 T-6 6530 10 0.3 24 0.013 0.05 3.37

UPPER DECK EM LIGHTING E1-6A-3 T-6 6530 10 1.0 24 0.041 0.17 3.48

UPPER DECK EM LIGHTING E1-6C-1 T-6 6530 50 1.0 24 0.205 0.86 3.96

FROM PANEL E1 TO MAIN DECK HEAD & GALLEY EM LIGHTING

FROM PANEL E1 TO UPPER DECK EM LIGHTING

FROM BATTERY BANK TO PANEL E2 E2 D-66 66370 15 26.1 24 0.152 0.63 0.63

RIGGING RM EM LIGHTS E2-1 T-16 16510 100 4.2 24 0.656 2.73 3.37

RIGGING RM EM LIGHTS E2-1A T-6 6530 10 2.1 24 0.082 0.34 3.71

RIGGING RM EM LIGHTS E2-1B T-6 6530 30 1.0 24 0.123 0.51 3.88

RIGGING RM EM LIGHTS E2-1C T-6 6530 20 1.0 24 0.082 0.34 3.71

RIGGING RM EM LIGHTS E2-1A-1 T-6 6530 15 1.0 24 0.062 0.26 3.97

CIRCUIT CABLE Cm L A V VD VD% VD%

LOAD GROUP NUBMER SIZE TOTAL

TANK RM EM LIGHTS E2-2 T-10 10380 60 4.2 24 0.626 2.61 3.24

TANK RM EM LIGHTS E2-2A T-6 6530 30 1.0 24 0.123 0.51 3.76

TANK RM EM LIGHTS E2-2B T-6 6530 25 2.1 24 0.205 0.86 4.10

TANK RM EM LIGHTS E2-2C T-6 6530 30 1.0 24 0.123 0.51 3.76

TANK RM EM LIGHTS E2-2B-1 T-6 6530 30 1.0 24 0.123 0.51 4.61

TANK RM EM LIGHTS E2-2B-2 T-6 6530 30 1.0 24 0.123 0.51 4.61

FROM PANEL E2 TO TANK RM EM LIGHTS

FROM PANEL E2 TO RIGGING RM EM LIGHTS

SINGLE PHASE VD=(2KxLxI)/Cm K=12.9 FOR Cu

E2 - EMERGENCY LIGHTING VOLTAGE DROP CALCULATIONS

2685 - CEMVR FLOATING CRANE

VOLTAGE DROP EQUATIONS

STORE RM, 4-P, & 5-P EM LIGHTING E2-3 T-6 6530 30 5.2 24 0.616 2.57 3.20

STORE RM, 4-P, & 5-P EM LIGHTING E2-3A T-6 6530 25 1.0 24 0.103 0.43 3.63

STORE RM, 4-P, & 5-P EM LIGHTING E2-3B T-6 6530 55 1.0 24 0.226 0.94 4.14

STORE RM, 4-P, & 5-P EM LIGHTING E2-3C T-6 6530 10 2.1 24 0.082 0.34 3.54

STORE RM, 4-P, & 5-P EM LIGHTING E2-3D T-6 6530 25 1.0 24 0.103 0.43 3.63

STORE RM, 4-P, & 5-P EM LIGHTING E2-3C-1 T-6 6530 10 1.0 24 0.041 0.17 3.80

CIRCUIT CABLE Cm L A V VD VD% VD%

LOAD GROUP NUBMER SIZE TOTAL

STORE RM, 4-S, & 5-S EM LIGHTING E2-4 T-10 10380 60 5.2 24 0.775 3.23 3.87

STORE RM, 4-S, & 5-S EM LIGHTING E2-4A T-6 6530 25 1.0 24 0.103 0.43 4.29

STORE RM, 4-S, & 5-S EM LIGHTING E2-4B T-6 6530 55 1.0 24 0.226 0.94 4.81

STORE RM, 4-S, & 5-S EM LIGHTING E2-4C T-6 6530 10 2.1 24 0.082 0.34 4.21

STORE RM, 4-S, & 5-S EM LIGHTING E2-4D T-6 6530 25 1.0 24 0.103 0.43 4.29

STORE RM, 4-S, & 5-S EM LIGHTING E2-4C-1 T-6 6530 10 1.0 24 0.041 0.17 4.46

FROM PANEL E2 TO STORE RM, 4-P, & 5-P EM LIGHTING

FROM PANEL E2 TO STORE RM, 4-S, & 5-S EM LIGHTING

6-P & 7-C EM LIGHTING E2-5 T-16 16510 100 3.1 24 0.484 2.02 2.65

6-P & 7-C EM LIGHTING E2-5A T-6 6530 20 1.0 24 0.082 0.34 3.00

6-P & 7-C EM LIGHTING E2-5B T-6 6530 35 2.1 24 0.288 1.20 3.85

6-P & 7-C EM LIGHTING E2-5B-1 T-6 6530 10 1.0 24 0.041 0.17 4.02

CIRCUIT CABLE Cm L A V VD VD% VD%

LOAD GROUP NUBMER SIZE TOTAL

6-S EM LIGHTING E2-6 T-16 16510 130 4.2 24 0.853 3.56 4.19

6-S EM LIGHTING E2-6A T-6 6530 15 1.0 24 0.062 0.26 4.45

6-S EM LIGHTING E2-6B T-6 6530 20 1.0 24 0.082 0.34 4.53

6-S EM LIGHTING E2-6C T-6 6530 15 2.1 24 0.123 0.51 4.70

6-S EM LIGHTING E2-6C-1 T-6 6530 10 1.0 24 0.041 0.17 4.87

FROM PANEL E2 TO 6-P & 7-C EM LIGHTING

FROM PANEL E2 TO 6-S EM LIGHTING

File details come from the government source that posted it. Updated .