Attachment_8a_Seed_Project_Bldg_4_Vivarium_Generator_final_Drawings.pdf
PDF 9 MB Posted
- Solicitation number
- 75N99019R00001
About this file
This notice solicits proposals for a Multiple Award Construction Contract to provide general construction services for the National Institutes of Health. Up to 16 indefinite-delivery, indefinite-quantity contracts will be awarded, with up to 12 set aside for small businesses in various socioeconomic categories. The total value of all contracts is not to exceed $2 billion over eight years.
Small business opportunities include up to three awards each for small businesses, HUBZone small businesses, 8(a) small businesses, and service-disabled veteran-owned small businesses. Work will involve construction projects of varying size, scope and complexity across NIH facilities, including maintenance, repair, alterations, and new construction. The solicitation release date is February 11, 2019, with proposals due March 14, 2019. A pre-proposal site visit is scheduled for a seed project. The Department of Health and Human Services National Institutes of Health Office of Research Facilities will administer the contracts.
Attachment 8a-Seed Project Bldg 4 Drawings
View the file
Other files
Show 40 more
Latest 50 of 51 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(E) PANEL E1LP1
POLES 42 VOLTS 277/480 VOLTS MOUNTING SURFACE NOTES: CB TYPE EDB
SECT 1 PH/WIRE 3 PHASE/4 WIRE (A, B, C, N, EG) LOCATION ELEC. RM 127
AIC 14,000 MAIN 100 AMPS MLO FED FROM PANEL EH1
NEUTRAL 100 % MANUFACTURER SQAURE D, SERIES NF
LOAD CKT PHASE KVA CKT LOAD
LOAD DESCRIPTION KVA FEEDER TRIP # A B C # TRIP FEEDER KVA LOAD DESCRIPTION
(E) SPARE - - 20 1 0.70 2 20 EXISTING 0.70 LTG LAB 211 VIA E1LP1 2 (E)
(E) LTG LAB 109 VIA E1LP1 3 0.80 EXISTING 20 3 0.80 4 20 - - SPARE (E)
(E) SPARE - - 20 5 0.50 6 20 EXISTING 0.50 LTG LAB 228 VIA E1LP1 3 (E)
(E) LTG LAB 128 VIA E1LP1 1 0.50 EXISTING 20 7 0.50 8 20 - - SPARE (E)
(E) LTG - 1ST FL TOILET RM 0.40 EXISTING 20 9 0.80 10 20 EXISTING 0.40 LTG - 2ND FL TOILET RMS (E)
(E) LTG - 1ST FL EXIT SIGNS 0.10 EXISTING 20 11 0.20 12 20 EXISTING 0.10 LTG - 2ND FL EXIT SIGNS (E)
(E) LTG - 1ST FL CORRIDORS 0.80 EXISTING 20 13 1.60 14 20 EXISTING 0.80 LTG - 2ND FL CORRIDORS (E)
(E) RELAY PANEL - ELEC RM 127 1.20 EXISTING 20 15 2.40 16 20 EXISTING 1.20 RELAY PANEL ELEC 227 (E)
(E) SPARE - - 20 17 0.17 18 20* 2#12, 1#12 G, 3/4" C 0.17 GENRATOR AREA LTG (N)
(E) SPARE - - 20 19 20 20 - - SPARE (E)
(E) SPARE - - 20 21 22 20 - - SPARE (E)
(E) SPARE - - 20 23 24 20 - - SPARE (E)
(E) SPARE - - 20 25 26 20 - - SPARE (E)
(E) SPARE - - 20 27 28 20 - - SPARE (E)
(E) SPARE - - 20 29 30 20 - - SPARE (E)
(E) SPARE - - 20 31 32 20 - - SPARE (E)
(E) SPARE - - 20 33 34 20 - - SPARE (E)
(E) SPARE - - 20 35 36 20 - - SPARE (E)
(E) SPARE - - 20 37 38 20 - - SPARE (E)
(E) SPARE - - 20 39 40 20 - - SPARE (E)
(E) SPARE - - 20 41 42 20 - - SPARE (E)
TOTAL CONNECTED KVA PER PHASE 2.8 4.0 0.9
LOAD COMPUTATIONS AND MINIMUM FEEDER AMPACITY
CATEGORY CONNECTED KVA DMD FACTOR DMD KVA DEMAND AMPS MULTIPLIER MIN AMPACITY
LIGHTING 5.1 1.00 5.1 14 1.00 14
RECEPTACLES - NEC TABLE 220-13 - - 1.00 -
KITCHEN EQUIPMENT - 0.65 - - 1.00 -
LARGEST MOTOR 1.25 - - 1.00 -
OTHER LOADS 2.6 1.00 2.6 7 1.00 7
DEMAND AMPS 21
NOTES * USE EXISTING SPARE CIRCUIT BREAKER.
(E) PANEL E2RP1
POLES 42 VOLTS 120/208 VOLTS MOUNTING SURFACE NOTES: CB TYPE EDB
SECT 1 PH/WIRE 3 PHASE/4 WIRE (A, B, C, N, EG) LOCATION ELEC. RM 127
AIC 10,000 MAIN 100 AMPS MLO FED FROM PANEL EL1
NEUTRAL 100 % MANUFACTURER SQAURE D, SERIES NF
LOAD CKT PHASE KVA CKT LOAD
LOAD DESCRIPTION KVA FEEDER TRIP # A B C # TRIP FEEDER KVA LOAD DESCRIPTION
2.00 1 2.20 2 20 EXISTING 0.20 REC - FIRE DEPT (E)
(E) MOA EQUIP RM 114 2.00 EXISTING 60 3 2.20 4 20 EXISTING 0.20 REC - NIH FIRE REC (E)
2.00 5 2.50 6 20 EXISTING 0.50 REC - LAN 115 FA EQUIP (E)
(E) ROOM 116 FREEZER 0.80 EXISTING 20 7 0.90 8 20 EXISTING 0.10 PLUMB. SENSORS TIOLET 113 (E)
0.80 9 0.90 10 20 EXISTING 0.10 PLUMB. SENSORS TIOLET 119 (E)
(E) SPARE - - 20 11 0.10 12 20 EXISTING 0.10 KEYWATCH (E)
(E) REC - RM 166 FREEZER OFF EXISTING 20 13 14 20 - - SPARE (E)
(E) SPARE - - 20 15 0.18 16 20* 2#12, 1#12 G, 3/4" C 0.18 GENERATOR REC AND LIGHTING (N)
(E) SPARE - - 20 17 0.50 18 20 EXISTING 0.50 NAC PANEL (E)
(E) SPARE - - 20 19 0.50 20 20 EXISTING 0.50 MAIN FA PANEL (E)
(E) SPARE - - 20 21 22 20 - - SPARE (E)
(E) REC - RM 128A FREEZER 0.80 EXISTING 20 23 0.80 24 20 - - SPARE (E)
0.80 - 25 0.80 26 - - - SPACE AND PROVISIONS (E)
(E) REC - RM 128B FREEZER 0.80 EXISTING 20 27 0.80 28 - - - SPACE AND PROVISIONS (E)
0.80 29 0.80 30 - - - SPACE AND PROVISIONS (E)
TOTAL CONNECTED KVA PER PHASE 4.4 4.1 4.7
LOAD COMPUTATIONS AND MINIMUM FEEDER AMPACITY
CATEGORY CONNECTED KVA DMD FACTOR DMD KVA DEMAND AMPS MULTIPLIER MIN AMPACITY
LIGHTING - 1.00 - - 1.00 -
RECEPTACLES 6.9 NEC TABLE 220-13 6.9 19 1.00 19
KITCHEN EQUIPMENT - 0.65 - - 1.00 -
LARGEST MOTOR 1.25 - - 1.00 -
OTHER LOADS 6.3 1.00 6.3 17 1.00 17
DEMAND AMPS 37
NOTES * USE EXISTING SPARE CIRCUIT BREAKER.
(E) PANEL FE2RP1
POLES 42 VOLTS 120/208 VOLTS MOUNTING SURFACE NOTES:
SECT 1 PH/WIRE 3 PHASE/4 WIRE (A, B, C, N, EG) LOCATION ELECT RM 127
AIC 10,000 MAIN 250 AMPS MCB FED FROM PANEL DP1 BY XFMR NTC1
NEUTRAL 100 % MANUFACTURER SQUARE D
LOAD CKT PHASE KVA CKT LOAD
LOAD DESCRIPTION KVA FEEDER TRIP # A B C # TRIP FEEDER KVA LOAD DESCRIPTION
REC - TIS CUL 112 (BSC) 1.00 20 1 1.90 2 20 0.90 REC EQUIP RM 128A
REC - TIS CUL 112 (GENERAL) 1.00 20 3 1.90 4 0.90
REC - TIS CUL 112 (INCUBAT) 1.00 20 5 2.00 6 20 1.00 REC - SCOPE RM 128C
REC - TIS CUL 112 (INCUBAT) 1.00 20 7 2.20 8 20* 2#12, 1#12 G, 3/4" C 1.20 GENERATOR BATTERY CHARGER
REC - TIS CUL 112 (BSC) 1.00 20 9 2.00 10 20 1.00 REC - TIS CUL 131 INCUBAT
REC - TIS CUL 112 (BSC) 1.00 20 11 2.00 12 20 1.00 REC - TIS CUL 131 BSC
REC - TIS CUL 112 INCUBAT) 0.40 20 13 1.40 14 20 1.00 REC - TIS CUL 131 GENERAL
SPARE - 20 15 0.50 16 20 0.50 REC - TIS CUL 131 BSC
REC - EQUIP RM 116 (CO2) 1.00 20 17 1.90 18 20 0.90 REC EQUIP RM 128B
REC - SCOPE RM 109C 0.40 20 19 1.30 20 0.90
REC - ELEC RM 127 1.00 20 21 2.00 22 20 1.00 REC - TIS CUL 133 BSC
GENERATOR JACKET HEATER 1.25 2#12, 1#12 G, 3/4" C 20* 23 2.25 24 20 1.00 REC - TIS CUL 133 GENERAL
1.25 25 2.25 26 20 1.00 REC - TIS CUL 133 BSC
SPARE - 20 27 1.00 28 20 1.00 REC - TIS CUL 133 INCUBAT
- 29 1.00 30 20 1.00 REC - TIS CUL 135 INCUBAT
2.00 31 3.00 32 20 1.00 REC - TIS CUL 135 BSC
MOA RM 138 2.00 60 33 3.00 34 20 1.00 REC - TIS CUL 135 GENERAL
2.00 35 3.00 36 20 1.00 REC - TIS CUL 135 BSC
3.30 37 5.30 38 2.00
PANEL CP1 (LAN 115) 2.80 100 39 4.80 40 60 2.00 MOA - EQUIP RM 114
3.00 41 5.00 42 2.00
TOTAL CONNECTED KVA PER PHASE 17.4 15.2 17.2
LOAD COMPUTATIONS AND MINIMUM FEEDER AMPACITY
CATEGORY CONNECTED KVA DMD FACTOR DMD KVA DEMAND AMPS MULTIPLIER MIN AMPACITY
LIGHTING - 1.00 - - 1.00 -
RECEPTACLES 36.9 NEC TABLE 220-13 23.5 65 1.00 65
KITCHEN EQUIPMENT - 0.65 - - 1.00 -
LARGEST MOTOR 1.25 - - 1.00 -
OTHER LOADS 12.8 1.00 12.8 36 1.00 36
DEMAND AMPS 101
NOTES *USE EXISTING SPARE CIRCUIT BREAKER.
(N) PANEL EDP1
POLES 42 VOLTS 277/480 VOLTS MOUNTING SURFACE NOTES:
SECT 1 PH/WIRE 3 PHASE/4 WIRE LOCATION MECH RM 434
AIC 35,000 MAIN 400 AMPS MCB FED FROM PANEL "EDMP"
NEUTRAL 100%
LOAD CKT PHASE KVA CKT LOAD
LOAD DESCRIPTION KVA FEEDER TRIP # A B C # TRIP FEEDER KVA LOAD DESCRIPTION
BUSSED FOR 100A - - BUSSED FOR 100A
FUTURE PROVISIONS - - - 1 2 - - - FUTURE PROVISIONS
BUSSED FOR 100A - - BUSSED FOR 100A
FUTURE PROVISIONS - - - 3 4 - - - FUTURE PROVISIONS
1.0 1.0 - BUSSED FOR 100A
EXHAUST FAN EF-1 1.0 3#12, #12G, 3/4"C 15 5 1.0 6 - - - FUTURE PROVISIONS
2HP 1.0 1.0 -
1.0 1.0 - BUSSED FOR 225A
EXHAUST FAN EF-2 1.0 3#12, #12G, 3/4"C 15 7 1.0 8 - - - FUTURE PROVISIONS
2HP 1.0 1.0 -
- - BUSSED FOR 225A
SPARE - - 20 9 10 - - - FUTURE PROVISIONS
- - BUSSED FOR 225A
SPARE - - 20 11 12 - - - FUTURE PROVISIONS
- BUSSED FOR 225A
MAIN 400 13 14 - - - FUTURE PROVISIONS
TOTAL CONNECTED KVA PER PHASE 2.0 2.0 2.0
LOAD COMPUTATIONS AND MINIMUM FEEDER AMPACITY
CATEGORY CONNECTED KVA DMD FACTOR DMD KVA DEMAND AMPS MULTIPLIER MIN AMPACITY
LIGHTING - 1.00 - - 1 -
RECEPTACLES - NEC TABLE 220-13 - - 1 -
KITCHEN EQUIPMENT - 0.65 - - 1 -
LARGEST MOTOR 3.0 1.25 3.8 4.5 1 4.5
OTHER LOADS 3.0 1 3.0 3.6 1 3.6
DEMAND AMPS 8
NOTES
(E) PANEL ELB2A
POLES 42 VOLTS 120/208 VOLTS MOUNTING RECESSED NOTES:
SECT 1 PH/WIRE 3 PHASE/4 WIRE LOCATION CORRIDOR B2-08 TYPE THQB BREAKERS
AIC 10,000 MAIN 100 AMPS MCB FED FROM L.V. RISER
NEUTRAL 100 % MANUFACTURER GE A SERIES II
LOAD CKT PHASE KVA CKT LOAD
LOAD DESCRIPTION KVA FEEDER TRIP # A B C # TRIP FEEDER KVA LOAD DESCRIPTION
(E) REC 0.60 EXISTING 20 1 1.60 2 20 EXISTING 1.00 REC (E)
(E) REC 1.20 EXISTING 20 3 2.20 4 20 EXISTING 1.00 REC (E)
(E) REC 0.30 EXISTING 20 5 0.80 6 20 EXISTING 0.50 REC (E)
(E) REC 0.30 EXISTING 20 7 0.50 8 20 EXISTING 0.20 REC (E)
(E) CARD READER 0.18 EXISTING 20 9 0.38 10 20 EXISTING 0.20 REC (E)
(E) ELECT STRIKE 0.18 EXISTING 20 11 0.48 12 20 EXISTING 0.30 REC (E)
(E) FA SYSTEM 0.50 EXISTING 20 13 0.50 14 20 - - SPARE (E)
(E) SPARE (ON) - - 20 15 0.18 16 20 EXISTING 0.18 REC PROCEDURE RM (E)
(E) SPARE (ON) - - 20 17 0.97 18 20** 2#12, #12G, 3/4"C 0.97 REC SPOT COOLER RM B2-34 (N)
(E) SEIMENS CONTROLS 0.50 EXISTING 20 19 1.47 20 20* 2#12, #12G, 3/4"C 0.97 REC SPOT COOLER RM B2-36 (N)
SPACE - - - 21 0.97 22 20** 2#12, #12G, 3/4"C 0.97 REC SPOT COOLER RM B2-38 (N)
SPACE - - - 23 24 - - - SPACE
SPACE - - - 25 26 - - - SPACE
SPACE - - - 27 28 - - - SPACE
SPACE - - - 29 30 - - - SPACE
SPACE - - - 31 32 - - - SPACE
SPACE - - - 33 34 - - - SPACE
SPACE - - - 35 36 - - - SPACE
SPACE - - - 37 38 - - - SPACE
SPACE - - - 39 40 - - - SPACE
SPACE - - - 41 42 - - - SPACE
TOTAL CONNECTED KVA PER PHASE 4.1 3.7 2.3
LOAD COMPUTATIONS AND MINIMUM FEEDER AMPACITY
CATEGORY CONNECTED KVA DMD FACTOR DMD KVA DEMAND AMPS MULTIPLIER MIN AMPACITY
LIGHTING - 1.00 - - 1.00 -
RECEPTACLES 8.7 NEC TABLE 220-13 8.7 24 1.00 24
KITCHEN EQUIPMENT - 0.65 - - 1.00 -
LARGEST MOTOR - 1.25 - - 1.00 -
OTHER LOADS 1.4 1.00 1.4 4 1.00 4
DEMAND AMPS 28
NOTES * RE-USE EXISTING SPARE CIRCUIT BREAKER
** PROVIDE NEW CIRCUIT BREAKER TO MATCH EXISTING AIC RATING
(N) PANEL EMDP
POLES 54 VOLTS 277/480 VOLTS MOUNTING SURFACE
SECT 1 PH/WIRE 3 PHASE/4 WIRE (A, B, C, N, EG) LOCATION SWITCHGEAR RM B2-39
AIC 65,000 MAIN 800 AMPS MCB FED FROM ATS-EM
NEUTRAL 100%
LOAD CKT PHASE KVA CKT LOAD
LOAD DESCRIPTION KVA FEEDER TRIP # A B C # TRIP FEEDER KVA LOAD DESCRIPTION
1.3 1.3 *
AHU-4A 1.3 3#12, #12G, 3/4"C 15 1 1.3 2 60 SEE ONE LINE * H.V. RISER FEED
3HP 1.3 1.3 *
1.3 15.7 14.4
AHU-4B 1.3 3#12, #12G, 3/4"C 15 3 15.7 4 100 SEE ONE LINE 14.4 CHWS PUMP P-1**
3HP 1.3 15.7 14.4 40 HP
* 14.4 14.4
ELEVATOR RISER FEED * SEE ONE LINE 60 5 14.4 6 100 SEE ONE LINE 14.4 CHWS PUMP P-2**
* 14.4 14.4 40 HP
2.0 2.0 **
EDP1 2.0 SEE ONE LINE 400 7 2.0 8 100 SEE ONE LINE ** CHWS PUMP P-3**
2.0 2.0 ** 40 HP
BUSSED FOR 400A - *
FUTURE PROVISION - - - 9 10 110 SEE ONE LINE * L.V. RISER FEED
BUSSED FOR 400A - - BUSSED FOR 225A
FUTURE PROVISION - - - 11 12 - - - FUTURE PROVISION
* - BUSSED FOR 225A
MCC-2 * SEE ONE LINE 600 13 14 - - - FUTURE PROVISION
- - BUSSED FOR 225A
MAIN - SEE ONE LINE 800 15 16 - - - FUTURE PROVISION
BLANK - - - - - 30 - - SPD
TOTAL CONNECTED KVA PER PHASE 33.5 33.5 33.5
LOAD COMPUTATIONS AND MINIMUM FEEDER AMPACITY
CATEGORY CONNECTED KVA DMD FACTOR DMD KVA DEMAND AMPS MULTIPLIER MIN AMPACITY
LIGHTING - 1.00 - - 1 -
RECEPTACLES - NEC TABLE 220-13 - - 1 -
KITCHEN EQUIPMENT - 0.65 - - 1 -
LARGEST MOTOR 43.2 1.25 54.0 65 1 65.0
OTHER LOADS 51.18 1 51.2 61.6 1 61.6
H.V. RISER ADDED LOAD 0.17 1 0.17 0.20 1 0.20
FUTURE PROVISION - 1 - - 1 -
L.V. RISER ADDED LOAD 3.95 1 3.95 4.75 1 4.75
L.V. RISER XFMR FEED - 1 - - 1 -
PANEL "EDP1" 6.0 1 6.00 7.2 1 7.22
- - - - - 1 -
METERED LOAD* 230 1 229.8 277 1 277
DEMAND AMPS 415
NOTES * METERED DEMAND LOAD. REFERENCE ATS METERING MEMO.
** ONLY (2) PUMPS WILL BE ON AT ONCE. THE CONTROLS LOGIC ALTERNATE'S ON/OFF BETWEEN TWO OF THE PUMPS.
THE THIRD PUMP IS REDUNDANT.
NOTES: PROVIDE SERVICE RATED ENTRANCE PANEL
AND LABEL AS SUCH.
(E) PANEL 1252A6
POLES 21 VOLTS 120/208 VOLTS MOUNTING SURFACE NOTES:
SECT 1 PH/WIRE 3 PHASE/4 WIRE LOCATION B2 SW W/C TYPE BQ CIRCUIT BREAKERS
AIC 10,000 MAIN 100 AMPS MCB FED FROM L.V. RISER
NEUTRAL 100 % MANUFACTURER SIEMENS
LOAD CKT PHASE KVA CKT LOAD
LOAD DESCRIPTION KVA FEEDER TRIP # A B C # TRIP FEEDER KVA LOAD DESCRIPTION
- 1 0.18 2 20 EXISTING 0.18 LAN CLOSET LIGHT (E)
(E) MAIN - EXISTING 100 3 0.75 4 20 EXISTING 0.75 LAN CLOSET FAN COIL (E)
- 5 2.40 6 2.40
(E) POWERS 3-SCU PANELS 0.54 EXISTING 20 7 2.94 8 50 EXISTING 2.40 UNKNOWN (E)
(E) SPC 12 0.50 EXISTING 20 9 2.90 10 2.40
1.90 11 2.40 12 20* 2#12, #12G, 3/4"C 0.50 COND. PUMPS AHU 4A/4B (N)
(E) INSECTARY #2 1.90 EXISTING 20 13 2.90 14 20 EXISTING 1.00 HOT WATER CIRC PUMP (E)
1.90 15 2.90 16 1.00 (E)
- 17 0.36 18 20* 2#12, #12G, 3/4"C 0.36 SIEMENS PNL B3 CHW PUMP (N)
(E) SPARE - - 60 19 - - - - -
- 21 - - - - -
(E) UNIT HEATER 1.00 EXISTING 20 23 1.00 - - - - -
TOTAL CONNECTED KVA PER PHASE 6.0 6.6 6.2
LOAD COMPUTATIONS AND MINIMUM FEEDER AMPACITY
CATEGORY CONNECTED KVA DMD FACTOR DMD KVA DEMAND AMPS MULTIPLIER MIN AMPACITY
LIGHTING - 1.00 - - 1.00 -
RECEPTACLES 7.1 NEC TABLE 220-13 7.1 20 1.00 20
KITCHEN EQUIPMENT - 0.65 - - 1.00 -
LARGEST MOTOR 2.0 1.25 2.5 7 1.00 7
OTHER LOADS 9.7 1.00 9.7 27 1.00 27
DEMAND AMPS 53
NOTES *RE-USE EXISTING SPARE CIRCUIT BREAKER.
| 14037 G001 |
| 14037 E001 E001 (1) |
| 14037 E101 |
| 14037 E102 |
| 14037 E103 |
| 14037 E104 |
| 14037 E105 |
| 14037 E106 |
| 14037 E107 |
| 14037 E108 |
| 14037 E201 |
| 14037 E601 E601 (1) |
| 14037 E601 E602 (1) |
| 14037 E601 E603 (1) |
| 14037 E601 E604 (1) |