7-4-DA26052-26189700 Approved Structural Calculations.pdf

PDF 23 MB Posted

Attached to
DFCM Construction - VBS Construction Stage II - Invitation to Bid - Snow College - Washburn Entrance and Landscaping - 26189700
Solicitation number
DA26052-Stage II
Issued by
Utah

About this file

This is an approved structural calculations document for the Snow College Washburn Building Entrance Addition project located in Richfield, Utah, prepared by Reaveley Engineers and reviewed by the Utah Division of Facilities Construction and Management. The project involves a new entrance addition on the south side of the Washburn building with an associated landscaping renovation on the south and west sides, with a total construction cost estimate of $5,400,000. The structural calculations are based on the 2021 International Building Code with Risk Category III classification and include comprehensive design criteria for gravity loads, lateral forces, wind, seismic activity (Seismic Design Category D), snow loads (28 psf ground snow load), and foundations. The document provides detailed analysis of floor and roof framing systems utilizing steel beams (W-series and other sections), columns (HSS sections), and concrete slabs, along with masonry wall and pier designs using 8-inch concrete masonry units with specified reinforcement patterns.

The calculations incorporate site-specific hazard data including a basic wind speed of 108 mph, seismic spectral response values (SDS = 0.65g, SD1 = 0.35g), soil bearing pressure of 2,000 psf on compacted fill, and a 30-inch frost depth requirement. Foundation design specifies minimum 2 feet of compacted fill down to suitable undisturbed natural soils with provisions for seismic and wind load increases of 50 percent. The structural system employs special reinforced masonry shear walls with an R-value of 5.0 as the primary seismic force-resisting system. Detailed beam summary tables identify member sizes and capacities for both roof and low roof framing levels, while wall and pier summary worksheets document reinforcing requirements, bearing pressures, and demand-to-capacity ratios for all masonry elements. All structural elements demonstrated adequate capacity under the prescribed load combinations and design criteria.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Structural Calculations

PREPARED FOR PREPARED BY

250 E 200 S, SUITE 1000 · SALT LAKE CITY, UT 84111

reaveley.com

Structural Calculations

2024.0434 Snow College

CRSA

175 S Main Street, Ste 300 Salt Lake City, UT 84111

Justin Nadauld, SE Emily Williamson

Snow College - Washburn Building Entrance Addition

JUSTIN D.

NADAULD

No.

4859789-2203

P R

O F

E S

S

IO

NAL

STRUCTURAL

E N

G

IN

E E

R

STATE OF UTAH

07/10/2026

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

07/13/2026

REVIEWED FOR CODE

COMPLIANCE

Calculations Index

01 Design Criteria

02 Gravity Loads

03 Gravity Framing

04 Lateral Loads, Drift & Irregularities

05 Lateral Force Resisting System

06 Diaphragms, Chords & Collectors

07 Footings, Piers & Foundation Walls

08 Architectural Elements

09 Cladding Support

DC

GL

GF

LAT

LFRS

DCC

FTG

AE

CLAD

1 - 09

1 - 15

1 - 65

1 - 27

1 - 28

1 - 99

1 - 51

1 - 16

1 - 18

10 Supplemental Calculations S 1-17

DESIGN CRITERIA

1. Design Criteria

1.1. Governing Building Code .................................. 2021 International Building Code (IBC)

A. Risk Category.............................................. III

1.2. Floor Live Loading

A. Office ........................................................... 50 psf Live Load + 15 psf Partition Load B. Lobbies, Exit Facilities & Corridors ............. 100 psf Live Load C. Mechanical Rooms ..................................... 125 psf Live Load or actual weights, if larger

1.3. Roof Loading

A. Roof Live Load ............................................ 20 psf B. Roof Snow Load ......................................... 22 psf + Drift per IBC

1. Ground Snow Load, Pg .......................... 28 psf

2. Snow Exposure Factor, Ce .................... 1.0

3. Importance Factor, Is ............................. 1.1

4. Thermal Factor, Ct ................................. 1.0 Roof

5. Slope Factor, Cs ..................................... 1.0

C. Roof Rain Load Intensity:

1. 15-min duration/100-year return period, i15 3.6 inches per hour

2. 60-min duration/100-year return period, i60 1.5 inches per hour

1.4. Earthquake

A. Seismic Design Category ............................ D B. Spectral Response Accelerations:

SS = 0.83 g SDS = 0.65 g S1 = 0.25 g SD1 = 0.35 g

C. Site Class .................................................... D (Default) D. Basic Seismic-Force-Resisting System ...... Special Reinforced Masonry Shear Walls

R = 5.0 Ω0 = 2.5 Cd = 3.5 E. Importance Factor, Ie................................... 1.25 F. Redundancy Factor, ρ ................................. 1.0 G. Analysis Procedure ..................................... Equivalent Lateral Force (Static) H. Seismic Design Coefficient, Cs ................... 0.166 I. Design Base Shear ..................................... 68 kips J. Building Seismic Movement:

Level Total Displacement Story Drift

Elastic – δe Inelastic - δ Elastic - Δe Inelastic - Δ

High Roof 0.18 0.72” 0.18 0.72”

Roof 0.01 0.04” 0.01” 0.04”

Base - - - -

1.5. Wind

A. Basic Design Wind Speed, V ...................... 108 mph B. Wind Directionality Factor, Kd ..................... 0.85 C. Ground elevation factor, Ke ......................... 0.82 D. Exposure category ...................................... C E. Internal Pressure Coefficient, GCpi ............. 0.18 F. Topographic Factor, Kzt ............................... 1.0 G. Components and Cladding Design Pressure:

Design Wind Pressure - LRFD (psf)

Location Tributary Area (ft2)

< 10 50 100 > 500

Walls Within 13 ft of building corner 30 26 22 19

All other areas 25 22 21 19

Roof

Within 19ft of building exterior perimeter 70 60 49 33

Between 19 ft and 32 ft of building exterior perimeter

52 45 41 33

All other areas 23 23 23 16

DC 1 of 9

1.6. Foundations

A. The soils report and log of borings was obtained by the Owner for the Engineer's use in the design of the foundation and is not a part of the Contract Documents. This report and log of borings is available for the Contractor's information but is not a warranty of the subsurface conditions. The Contractor may use the report at their own risk.

B. Soils Report by AGEC Applied Geotech, dated October 3, 2025.

C. Soil Bearing Pressure: 2,000 psf on a minimum of 2 feet of compacted fill down to suitable, undisturbed, natural soils D. Increase for seismic or wind loading: 50% E. Frost Depth: 30 inches below grade F. Lateral Soil Pressure Fluid Equivalent Density:

Soil Type Active (increase for seismic)

At-Rest (increase for seismic)

Passive (decrease for seismic)

Sand & Gravel 40 pcf (27 pcf) 55 pcf (12 pcf) 300 pcf (27 pcf)

Clay & Silt 50 pcf (27 pcf) 65 pcf (12 pcf) 250 pcf (27 pcf)

G. Coefficient of Friction ................................. 0.35

1.7. Classification for Fire Rated Construction

A. For the purpose of determining fire-resistive assemblies, the following framing systems shall be considered unrestrained:

1. Single span and simply supported end spans of multiple bays that are supported by bearing walls:

a. Steel beams supporting metal decking.

b. Metal decking.

2. Interior spans of multiple bays supported by bearing walls:

a. Steel beams supporting metal decking.

B. All other steel floor and roof framing members shall be considered restrained.

C. Diagonal members in vertical braced frames shall be considered as secondary members for fireproofing protection.

2. Earthwork

2.1. Soil conditions shall be verified by the Geotechnical Engineer prior to placement of structural fill, floor slabs, and foundations. If soil conditions exist that are different than the soils report, the Structural Engineer shall be notified to re-evaluate the foundation design at additional expense to the owner.

2.2. Clearing: Prior to placing fill or base course, non-engineered fill, topsoil, organics, debris, and other deleterious material shall be removed at least 3 feet beyond the perimeter of the proposed building and flatwork. As a minimum the entire building area shall be scraped to remove the top 4 inches of soil.

2.3. Near surface Fill: The depth of this material is approximately five to ten feet. Do not place any footing on this material.

2.4. Proof Rolling: The natural undisturbed soil below all footings shall be proof rolled prior to placing concrete. Remove all soft spots and completely replace them with compacted structural fill.

2.5. Excavations that extend below ground water level shall be dewatered. The water level should be maintained below the base of the excavation during placement of fill or concrete. Free-draining gravel with less than 5% passing the Number 200 sieve should be used for fill or backfill below the original water level.

2.6. Vibratory Compaction: The natural undisturbed soil below all footings shall be compacted with vibratory compacting equipment in lifts not to exceed the equipment’s capacity prior to placing concrete. Remove all soft spots and replace with compacted structural fill.

DC 2 of 9

BUILDING CODE FOR LIVE LOAD REDUCTION: IBC

Live Load Reduction Method: General

ROOF LOADS:

Consider Snow Loads, Ignore Roof Live Loads

DETERMINING NUMBER OF STORIES FOR LIVE LOAD REDUCTION:

Include Roof Levels: No

Include Unreducible Levels: Yes

Include Storage Levels: Yes

SELF-WEIGHT:

Slabs / Decks: Yes

Include half mass of walls above and below

Walls: Yes

Include half mass of columns above and below

Beams: Yes

Columns: Yes

Automatically calculate and include Self-Weight for Story Masses:

Slabs / Decks: Yes

Apply to top of wall

Beams: Yes

Columns: Yes

Walls: Yes

Automatically calculate and include Self-Weight for Member Dead Loads:

05/20/26 12:02:29

Page 1/1

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

RAM Structural System 25.00.02.42

General Criteria DC 3 of 9

ASCE Hazards Report Address:

No Address at This Location

Standard: ASCE/SEI 7-16 Latitude: 38.765586

Risk Category: III Longitude: -112.098102

Soil Class: D - Stiff Soil Elevation: 5379.3308647796575 ft

(NAVD 88)

Wind

Results:

Wind Speed 108 Vmph

10-year MRI 73 Vmph

25-year MRI 79 Vmph

50-year MRI 83 Vmph

100-year MRI 88 Vmph

Data Source: ASCE/SEI 7-16, Fig. 26.5-1C and Figs. CC.2-1–CC.2-4, and Section 26.5.2

Date Accessed: Tue Nov 25 2025

Value provided is 3-second gust wind speeds at 33 ft above ground for Exposure C Category, based on linear interpolation between contours. Wind speeds are interpolated in accordance with the 7-16 Standard. Wind speeds correspond to approximately a 3% probability of exceedance in 50 years (annual exceedance probability = 0.000588, MRI = 1,700 years).

Site is not in a hurricane-prone region as defined in ASCE/SEI 7-16 Section 26.2.

Page 1 of 5https://ascehazardtool.org/ Tue Nov 25 2025

DC 4 of 9 https://ascehazardtool.org/

SS : 0.833

S1 : 0.247

Fa : 1.167

Fv : N/A

SMS : 0.972

SM1 : N/A

SDS : 0.648

SD1 : N/A

TL : 6

PGA : 0.368

PGA M : 0.453

FPGA : 1.232

Ie : 1.25

Cv : 1.216

Seismic

Site Soil Class:

Results:

Data Accessed:

Date Source:

D - Stiff Soil

USGS Seismic Design Maps

Ground motion hazard analysis may be required. See ASCE/SEI 7-16 Section 11.4.8.

Tue Nov 25 2025

Page 2 of 5https://ascehazardtool.org/ Tue Nov 25 2025

DC 5 of 9 https://doi.org/10.5066/F7NK3C76

Ice

Results:

Data Source:

Date Accessed:

Ice Thickness: 0.25 in.

Concurrent Temperature: 15 F

Gust Speed 30 mph

Standard ASCE/SEI 7-16, Figs. 10-2 through 10-8

Tue Nov 25 2025

Ice thicknesses on structures in exposed locations at elevations higher than the surrounding terrain and in valleys and gorges may exceed the mapped values.

Values provided are equivalent radial ice thicknesses due to freezing rain with concurrent 3-second gust speeds, for a 500-year mean recurrence interval, and temperatures concurrent with ice thicknesses due to freezing rain.

Thicknesses for ice accretions caused by other sources shall be obtained from local meteorological studies. Ice thicknesses in exposed locations at elevations higher than the surrounding terrain and in valleys and gorges may exceed the mapped values.

Page 3 of 5https://ascehazardtool.org/ Tue Nov 25 2025

DC 6 of 9

Snow

Mapped Elevation: 5379.3 ft

Data Source: ASCE/SEI 7-16, Table 7.2-8

Date Accessed: Tue Nov 25 2025

In "Case Study" areas, site-specific case studies are required to establish ground snow loads. Extreme local variations in ground snow loads in these areas preclude mapping at this scale.

Ground snow load determination for such sites shall be based on an extreme value statistical analysis of data available in the vicinity of the site using a value with a 2 percent annual probability of being exceeded (50-year mean recurrence interval).

Values provided are ground snow loads. In areas designated "case study required," extreme local variations in ground snow loads preclude mapping at this scale. Site-specific case studies are required to establish ground snow loads at elevations not covered.

Snow load values are mapped to a 0.5 mile resolution. This resolution can create a mismatch between the mapped elevation and the site-specific elevation in topographically complex areas. Engineers should consult the local authority having jurisdiction in locations where the reported ‘elevation’ and ‘mapped elevation’ differ significantly from each other.

Page 4 of 5https://ascehazardtool.org/ Tue Nov 25 2025

DC 7 of 9

Rain

Data Source:

Date Accessed:

15-minute Precipitation Intensity: 3.6 in./h

60-minute Precipitation Intensity: 1.5 in./h

NOAA National Weather Service, Precipitation Frequency Data Server, Atlas 14 (https://www.nws.noaa.gov/oh/hdsc/)

Tue Nov 25 2025

The ASCE Hazard Tool is provided for your convenience, for informational purposes only, and is provided “as is” and without warranties of any kind. The location data included herein has been obtained from information developed, produced, and maintained by third party providers; or has been extrapolated from maps incorporated in the ASCE standard. While ASCE has made every effort to use data obtained from reliable sources or methodologies, ASCE does not make any representations or warranties as to the accuracy, completeness, reliability, currency, or quality of any data provided herein. Any third-party links provided by this Tool should not be construed as an endorsement, affiliation, relationship, or sponsorship of such third-party content by or from ASCE.

ASCE does not intend, nor should anyone interpret, the results provided by this Tool to replace the sound judgment of a competent professional, having knowledge and experience in the appropriate field(s) of practice, nor to substitute for the standard of care required of such professionals in interpreting and applying the contents of this Tool or the ASCE standard.

In using this Tool, you expressly assume all risks associated with your use. Under no circumstances shall ASCE or its officers, directors, employees, members, affiliates, or agents be liable to you or any other person for any direct, indirect, special, incidental, or consequential damages arising from or related to your use of, or reliance on, the Tool or any information obtained therein. To the fullest extent permitted by law, you agree to release and hold harmless ASCE from any and all liability of any nature arising out of or resulting from any use of data provided by the ASCE Hazard Tool.

Page 5 of 5https://ascehazardtool.org/ Tue Nov 25 2025

DC 8 of 9 https://www.nws.noaa.gov/oh/hdsc/

)*+,-./0123456.,-.506.748977:.;,5/,58<.*+4.2-4=.,-.2=84/.60.>4=,?:.8=025/.-50@.709/.>9724-.@,6+.6+4.70197.926+0=,6:.+9>,58.A2=,-/,16,05<

B

CDEF�GE(H�I#$�J

KLM$M�NOEPDH�$DEF�QE(H�R(QPM$�OM#OM$MD�����SM(O�NOEPDH�$DEF�QE(H�M$�TU(�MH�R(QPM�(��(��V�#OEW(WTQT�S�E��MXYMMH(DYM��EO��LM�QEY(�TED�NTRMD��KLM�NOTH�P$MH�TD��LM�U(#�T$� �����WS� �����

ZQMR(�TED$��EO��LM$M�NOTH�YMQQ$�FMOM�M$�TU(�MH�WS�(NNOMN(�TDN�H(�(��OEU�������WS�������[C\C�HTNT�(Q�MQMR(�TED�UEHMQ$�(DH�U(S�DE��YETDYTHM�FT�L��LM�(Y�P(Q�$T�M�MQMR(�TED��KLM$M�#OMHTY�TED$�(OM

Y(QYPQ(�MH�P$TDN��LM�#OEYM$$�EP�QTDMH�TD�KLM�[�(L�CDEF�GE(H�C�PHS�

]TD(Q�#OMHTY�TED$�NTRMD�(OM�WEPDHMH�(��(�QEFMO�QTUT���EO�(�UTDTUPU�NOEPDH�$DEF�QE(H�E�����#$���E�UMM��̂C_Z����Z$�TU(�MH�R(QPM$��EO�$DEF�QE(H$�(��MQMR(�TED$�$TNDT�TY(D�QS�LTNLMO��L(D�(QQ

DM(OWS�$�(�TED$�QM(H��E�PDOM($ED(WQS�LTNL�$DEF�QE(H�M$�TU(�M$���LMOM�EOM���LM�#OMHTY�TED$�TD��LM�U(#�(OM�DE��(QQEFMH��E�MX�MDH�WMSEDH��LM�LTNLM$�����SM(O�$�(�TED�NOEPDH�$DEF�QE(H�E�����

#$���ZQMR(�TED$�ERMO����������(OM�(Q$E�YED$THMOMH�QM$$�(YYPO(�M�HPM��E��LM�QTUT�MH�DPUWMO�E��$�(�TED$�(���LM$M�MQMR(�TED$��KLM�OM$PQ�$�$LEFD�TD��LT$�OM#EO��L(RM�TDYQPHMH�(�F(ODTDN�T���LM�OM$PQ�$

L(RM�OM(YLMH�EO�MXYMMHMH��LM�P##MO�QTUT��

`LTQM�NOM(��M��EO�$�L(RM�WMMD�U(HM��E�MD$POM��LM$M�#OMHTY�TED$�(OM�($�(YYPO(�M�($�#E$$TWQM��HM$TNDMO$�UP$��P$M�MX#MO��aPHNMUMD���E�MD$POM��L(��$PYL�#OMHTY�TED$�(OM�(##OE#OT(�M��EO��LMTO

#(O�TYPQ(O�#OEaMY���KLM�CẐ[�(DH��LM�(P�LEO$�Y(DDE��(YYM#��OM$#ED$TWTQT�S��EO�#OMHTY�TED�MOOEO$�EO�(DS�YED$MbPMDYM$�OM$PQ�TDN��LMOM�OEU� cdefghidejfhhghkdlgmnojfidlgjpkdghqdrnhidsghidtuvfdwxgvdrhyzd{ygqdrxnq|td}~�c���d�o�o�dghqd�h�ojyh�fhxg�d�hmohffjohmd�gpn�x|d�n��opgxoyh��d�g�fjd�����

DC 9 of 9 pf = 0.7*1.1*1.0*28 = 21.6psf

GRAVITY LOADS

Reaveley Engineers

Project Job Ref.

Section Sheet no./rev.

Calc. by

J

Date

12/11/2025

Chk'd by Date App'd by Date

SNOW LOADING

In accordance with ASCE7-16

Tedds calculation version 1.0.12

Building details

Roof type; Flat

Width of roof; b = 176.00 ft

Ground snow load

Ground snow load (Figure 7.2-1); pg = 28.00 lb/ft2

Density of snow; γ = min(0.13 × pg / 1ft + 14lb/ft3, 30lb/ft3) = 17.64 lb/ft3

Surface roughness category (Sect. 26.7); C

Exposure condition (Table 7.3-1); Partially exposed

Exposure factor (Table 7.3-1); Ce = 1.00

Thermal condition (Table 7.3-2); All

Thermal factor (Table 7.3-2); Ct = 1.00

Importance category (Table 1.5-1); III

Importance factor (Table 1.5-2); Is = 1.10

Min snow load for low slope roofs (Sect 7.3.4); pf_min = Is × 20 lb/ft2 = 22.00 lb/ft2

Flat roof snow load (Sect 7.3); pf = 0.7 × Ce × Ct × Is × pg = 21.56 lb/ft2

Roof projection drifts

Max height of obstruction; hobs = max(h1_obs, h2_obs) = 10.00 ft

Width of obstruction; bobs = 50.00 ft

Distance from LHS eaves; b1_obs = 5.00 ft

Distance from RHS eaves; b2_obs = 121.00 ft

Balanced snow load height; hb = pf / γ = 1.22 ft

Height from balance load to top of projection; hc_obs = hobs - hb = 8.78 ft

Length of lower roof; ll_obs = max(b1_obs, b2_obs) = 121.00 ft

Drift height windward drift; hd_l_obs = √(Is) × 0.75 × (0.43 × (max(20 ft, ll_obs) × 1ft2)1/3 × (pg / 1lb/ft2 +

10)1/4 - 1.5ft) = 2.97 ft

Drift height; hd_obs = min(hd_l_obs, hobs - hb) = 2.97 ft

Drift width; Wd_obs = min(4 × hd_l_obs, 8 × (hobs - hb)) = 11.90 ft

Drift surcharge load; pd_obs = hd_obs × γ = 52.46 lb/ft2

GL 1 of 15

Section Sheet no./rev.

Calc. by

J

Date

12/11/2025

Chk'd by Date App'd by Date

176'

Roof elevation

Balanced load 22.0 psf

5'

74.5 psf

52.4 psf

11' 10.7"

74.5 psf

22.0 psf

Obstruction

Drift calculations

Balanced snow load height; hb = pf / γ = 1.22 ft

Length of upper roof; lu = 50.00 ft

Length of lower roof; ll = 121.00 ft

Height diff between uppper and lower roofs; hdiff = 10.00 ft

Height from balance load to top of upper roof; hc = hdiff - hb = 8.78 ft

Drift height leeward drift; hd_l = min(√(Is) × (0.43 × (max(20 ft, lu) × 1ft2)1/3 × (pg / 1lb/ft2 + 10)1/4 -

1.5ft),0.6 × ll) = 2.55 ft

Drift height windward drift; hd_w = 0.75 × √(Is) × (0.43 × (max(20 ft, ll) × 1ft2)1/3 × (pg / 1lb/ft2 + 10)1/4 -

1.5ft) = 2.97 ft

Maximum lw/ww drift height; hd_max = max(hd_w, hd_l) = 2.97 ft

Drift height; hd = min(hd_max, hc) = 2.97 ft

Drift width; Wd = min(4 × hd_max, 8 × hc) = 11.90 ft

Drift surcharge load; pd = hd × γ = 52.46 lb/ft2

GL 2 of 15

Section Sheet no./rev.

Calc. by

J

Date

12/11/2025

Chk'd by Date App'd by Date

11' 10.7"

74.0 psf

21.6 psf

Elevation on snow drift

GL 3 of 15

Floor Type: LOW ROOF

Steel Code: AISC360-16 LRFD

05/04/26 17:17:38

Page 1/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

RAM Steel 25.00.02.42

Floor Map GL 4 of 15

1 1.5 2 3 3.9 4 5 0

D

C

B

A

L1L1

Steel Code: AISC360-16 LRFD

05/04/26 17:17:38

Page 2/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GL 5 of 15

Surface Loads

Label DL CDL LL Reduction PLL CLL Mass DL psf psf psf Type psf psf psf

01 TYP ROOF 15.0 5.0 20.0 Roof 0.0 0.0 12.0

Line Loads

Label DL CDL LL Reduction PLL CLL Mass DL k/ft k/ft k/ft Type k/ft k/ft k/ft

L1 01 - TYP 6' MAS PAR 0.000 0.000 0.360 Unreducible 0.000 0.000 0.360

Steel Code: AISC360-16 LRFD

05/04/26 17:17:38

Page 3/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GL 6 of 15

05/04/26 17:17:38

Page 1/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GL 7 of 15

M1 M2

M3

M1

M2

M3

1 1.5 2 3 3.9 4 5 0

D

C

B

A

Steel Code: AISC360-16 LRFD

05/04/26 17:17:38

Page 2/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GL 8 of 15

Snow Loads

Label Type Magnitude 1 Magnitude 2 Magnitude 3 psf psf psf

01 TYP SNOW Constant 22.000 --- ---

02 SND-01 Drift 75.000 75.000 22.000

02 SND-01 Drift 75.000 75.000 22.000

Steel Code: AISC360-16 LRFD

05/04/26 17:17:38

Page 3/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GL 9 of 15

Floor Type: ROOF

05/04/26 17:17:38

Page 1/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GL 10 of 15

C

B

A

L

L1 L1 L1 L1 L1

L

L

L1L1L1L1L1

Steel Code: AISC360-16 LRFD

05/04/26 17:17:38

Page 2/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GL 11 of 15

Surface Loads

Label DL CDL LL Reduction PLL CLL Mass DL psf psf psf Type psf psf psf

01 TYP ROOF 15.0 5.0 20.0 Roof 0.0 0.0 12.0

Line Loads

Label DL CDL LL Reduction PLL CLL Mass DL k/ft k/ft k/ft Type k/ft k/ft k/ft

L1 01 - TYP 6' MAS PAR 0.000 0.000 0.360 Unreducible 0.000 0.000 0.360

Steel Code: AISC360-16 LRFD

05/04/26 17:17:38

Page 3/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GL 12 of 15

05/04/26 17:17:38

Page 1/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GL 13 of 15

C

B

A

Steel Code: AISC360-16 LRFD

05/04/26 17:17:38

Page 2/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GL 14 of 15

Snow Loads

Label Type Magnitude 1 Magnitude 2 Magnitude 3 psf psf psf

01 TYP SNOW Constant 22.000 --- ---

Steel Code: AISC360-16 LRFD

05/04/26 17:17:38

Page 3/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GL 15 of 15

GRAVITY FRAMING

DataBase: Snow College Washburn Addition v03 05/11/2026 22:09:20

GF 1 of 64

TABLES SELECTED:

Master Steel Table: ramaisc

Default Steel Table: ramaisc

Alternate Steel Table: reacomp

UNBRACED LENGTH:

Use Cb=1 for all Cantilevers

Calculate Cb for all Simple Span Beams

Deck Perpendicular to Beam Braces flange

Deck Parallel to Beam does not Brace flange

Noncomposite/Precomposite Beam Design:

Do Not Consider Point of Inflection as Brace Point

Check Unbraced Length

SPAN/DEPTH CRITERIA:

Maximum Span/Depth Ratio (ft/ft): 28.00

COMPOSITE IEFF:

Do Not Reduce Ieff per AISC 360 Commentary

DEMAND/CAPACITY LIMITS:

Strength Deflection

Steel Beam: 1.000 1.000

C-Beams: 1.000 1.000

DEFLECTION CRITERIA:

Dead Load: 0.0 0.0

Live Load: 360.0 0.0

Noncomposite

Dead Load: 0.0 0.0

Live Load: 360.0 0.0

Total Load: 240.0 0.0

Shored

Total (Init+Superimp-Camber): 240.0 0.0

Live Load: 360.0 0.0

Total Superimposed: 240.0 0.0

Initial (Construction Load): 280.0 0.0

Post Composite

Unshored

Default Criteria L/d Δ (in)

Steel Code: AISC360-16 LRFD

05/11/26 21:49:39

Page 1/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Beam Design Criteria GF 2 of 64

Note: 0.0 indicates No Limit

Dead Load: 0.0 0.0

Live Load: 600.0 0.0

Total Load: 240.0 0.0

Noncomposite

Dead Load: 0.0 0.0

Live Load: 600.0 0.0

Total Load: 240.0 0.0

Shored

Total (Init+Superimp-Camber): 240.0 0.0

Live Load: 360.0 0.0

Total Superimposed: 600.0 0.0

Initial (Construction Load): 280.0 0.0

Post Composite

Unshored

L/600 Criteria L/d Δ (in)

Total Load: 240.0 0.0

CAMBER CRITERIA FOR COMPOSITE BEAMS:

Maximum Camber (in): 4.000

Minimum Camber (in): 0.750

Camber Increment (in): 0.250

(For Unshored Composite the specified % of

Construction DL is used)

Percent of Dead Load used for Camber: 85.00

Do not Camber Beams with Cantilevers

Do not Camber Beams with Depth > 100.0 in

Do not Camber Beams with Depth < 14.0 in

Do not Camber Beams with Weight > 1000.0 lbs/ft

Do not Camber Beams with Weight < 24.0 lbs/ft

Do not Camber Beams with Span < 20.0 ft

CAMBER CRITERIA FOR NONCOMPOSITE BEAMS:

Do not Camber

STUD CRITERIA:

Minimum % of Full Composite Allowed - Short Span: 25.00

Maximum % of Full Composite Allowed: 95.00

Stud Distribution: Use Optimum

Steel Code: AISC360-16 LRFD

05/11/26 21:49:39

Page 2/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Beam Design Criteria GF 3 of 64

Enforce AISC 360-16 Commentary I3.2d(1) for Spans greater than 30'

Ductility of Shear Connection:

Maximum Stud Spacing - Deck Not Parallel: Per Code

Maximum Stud Spacing - Deck Parallel: Per Code

Minimum Flange Width for 3 Rows of Studs (in): 8.500

Minimum Flange Width for 2 Rows of Studs (in): 5.500

Maximum Rows of Studs Allowed: 3

Long Span Defined as Span Greater Than: 30.00 ft

Minimum % of Full Composite Allowed - Long Span: 50.00

WEB OPENING CRITERIA:

Allow Stiffeners on Two Sides of web

Allow Stiffeners on One Side of web

Increment of Length (in): 1.000

Increment of Thickness (in): 0.125

Increment of Width (in): 0.250

Minimum Thickness (in): 0.250

Minimum Width (in): 1.000

Stiffener Dimensions

Stiffener Fy (ksi): 36.000

Steel Code: AISC360-16 LRFD

05/11/26 21:49:39

Page 3/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Beam Design Criteria GF 4 of 64

Floor Type: LOW ROOF Beam Numbers

05/11/26 21:49:39

Page 1/2

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GF 5 of 64

C

B

A

8 9

Steel Code: AISC360-16 LRFD

05/11/26 21:49:39

Page 2/2

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GF 6 of 64

Floor Type: LOW ROOF Beam Designs

05/11/26 21:49:39

Page 1/2

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GF 7 of 64

C

B

A

W8x10

W12x14

W x

W x

W x

W12x14

W x

W x

W x

W14x22

W10x12

W x

W x

W16x31

W12x16

W x

W x

W x

W14x22

W10x12

W8x10

W8x10

W8x10

W x

W8x10

W8x10

W8x10

W14x22

W x

W x

W x

Steel Code: AISC360-16 LRFD

05/11/26 21:49:39

Page 2/2

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GF 8 of 64

05/11/26 21:49:39

Page 1/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GF 9 of 64

C

B

A

Steel Code: AISC360-16 LRFD

05/11/26 21:49:39

Page 2/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GF 10 of 64

Decks: Deck Label Deck Type Slab Action Orientation

N DECK Noncomposite One-Way 0.00 degrees

N DECK Noncomposite One-Way 90.00 degrees

Steel Code: AISC360-16 LRFD

05/11/26 21:49:39

Page 3/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GF 11 of 64

Floor Type: ROOF Beam Numbers

05/11/26 21:49:39

Page 1/2

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GF 12 of 64

C

B

A

4 18

Steel Code: AISC360-16 LRFD

05/11/26 21:49:39

Page 2/2

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GF 13 of 64

Floor Type: ROOF Beam Designs

05/11/26 21:49:39

Page 1/2

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GF 14 of 64

C

B

A

W8x10

W8x10

W x

W8x10

W8x10

W8x10

W x

W12x14

W12x14

W12x14

W12x14

W14x22

W12x14

W8x10

W16x26

W12x14

W x

W12x14

W12x14

W12x14

W12x14

W14x22

W8x10

W8x10

W8x10

W8x10

W8x10

W8x10

W24x76

W12x14

W27x84

W12x16

W12x16

W12x16

W30x99

W8x10

W x

W8x10

W8x10

W8x10

W x

W x

Steel Code: AISC360-16 LRFD

05/11/26 21:49:39

Page 2/2

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GF 15 of 64

05/11/26 21:49:39

Page 1/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GF 16 of 64

C

B

A

Steel Code: AISC360-16 LRFD

05/11/26 21:49:39

Page 2/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GF 17 of 64

Decks: Deck Label Deck Type Slab Action Orientation

N DECK Noncomposite One-Way 90.00 degrees

Steel Code: AISC360-16 LRFD

05/11/26 21:49:39

Page 3/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Floor Map GF 18 of 64

STEEL BEAM DESIGN SUMMARY:

Demand/Capacity Limits for: Strength: 1.000 Deflection: 1.000

Floor Type: ROOF

Beam # Length +Mu -Mu ΦMn Fy Beam Size Studs ft kip-ft kip-ft kip-ft ksi

2 39.33 155.8 0.0 246.9 50.0 W18X40 u

3 13.33 0.0 -311.8

39.33 254.9 -311.8 1170.0 50.0 W30X99 u

4 5.08 2.9 0.0 32.9 50.0 W8X10 u

5 11.50 14.8 0.0 32.9 50.0 W8X10 u

6 23.88 32.8 -427.7 1017.0 50.0 W30X99 u

15.50 0.0 -427.7

9 13.33 0.0 -581.5

39.33 187.4 -581.5 1927.5 50.0 W33X141 u

10 23.88 3.5 -468.4 772.8 50.0 W27X84 u

15.50 0.0 -468.4

11 23.88 45.4 -199.1 597.5 50.0 W24X76

15.50 0.0 -199.1

12 39.33 216.7 0.0 420.8 50.0 W24X55 u

13 13.33 25.0 0.0 502.5 50.0 W24X55 u

14 11.50 13.6 0.0 124.5 50.0 W14X22 u

15 23.70 58.0 0.0 165.8 50.0 W16X26 u

16 20.58 43.4 0.0 124.5 50.0 W14X22 u

18 23.25 32.8 0.0 65.2 50.0 W12X14 u

19 23.70 34.1 0.0 65.2 50.0 W12X14 u

20 11.50 7.9 0.0 32.9 50.0 W8X10 u

21 15.50 17.1 0.0 32.9 50.0 W8X10 u

22 15.50 17.1 0.0 32.9 50.0 W8X10 u

23 15.50 17.1 0.0 32.9 50.0 W8X10 u

24 15.50 11.7 0.0 32.9 50.0 W8X10 u

25 23.88 28.2 0.0 65.2 50.0 W12X14 u

26 11.50 6.5 0.0 32.9 50.0 W8X10 u

27 23.70 27.8 0.0 65.2 50.0 W12X14 u

28 20.58 20.9 0.0 65.2 50.0 W12X14 u

29 5.34 1.4 0.0 32.9 50.0 W8X10 u

30 2.67 0.4 0.0 32.9 50.0 W8X10 u

31 23.88 41.2 0.0 75.4 50.0 W12X16 u

Steel Code: AISC360-16 LRFD

05/11/26 21:49:39

Page 1/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Beam Summary GF 19 of 64

32 11.50 9.4 0.0 32.9 50.0 W8X10 u

33 23.70 40.4 0.0 65.2 50.0 W12X14 u

34 23.25 38.9 0.0 65.2 50.0 W12X14 u

35 2.67 0.5 0.0 32.9 50.0 W8X10 u

36 23.88 41.2 0.0 75.4 50.0 W12X16 u

37 11.50 9.4 0.0 32.9 50.0 W8X10 u

38 23.70 40.4 0.0 65.2 50.0 W12X14 u

39 23.25 38.9 0.0 65.2 50.0 W12X14 u

40 2.67 0.5 0.0 32.9 50.0 W8X10 u

41 23.88 41.2 0.0 75.4 50.0 W12X16 u

42 11.50 9.4 0.0 32.9 50.0 W8X10 u

43 23.70 40.4 0.0 65.2 50.0 W12X14 u

44 23.25 38.9 0.0 65.2 50.0 W12X14 u

45 2.67 0.5 0.0 32.9 50.0 W8X10 u

46 29.00 76.9 0.0 233.2 50.0 W18X40 u

Floor Type: LOW ROOF

Beam # Length +Mu -Mu ΦMn Fy Beam Size Studs ft kip-ft kip-ft kip-ft ksi

1 20.58 27.8 0.0 42.0 50.0 W12X14 u

2 23.70 35.2 0.0 37.6 50.0 W12X14 u

3 11.50 9.2 0.0 46.9 50.0 W10X12 u

4 23.88 35.9 0.0 45.4 50.0 W12X16 u

5 15.88 16.9 0.0 46.9 50.0 W10X12 u

7 11.17 16.6 0.0 124.5 50.0 W14X22 u

8 4.71 1.7 0.0 124.5 50.0 W14X22 u

9 23.88 88.8 0.0 164.7 50.0 W16X31

10 11.50 21.7 0.0 124.5 50.0 W14X22 u

17 11.84 13.8 0.0 32.9 50.0 W8X10 u

18 11.84 14.0 0.0 32.9 50.0 W8X10 u

19 11.84 14.0 0.0 32.9 50.0 W8X10 u

20 11.84 10.3 0.0 32.9 50.0 W8X10 u

21 11.84 14.1 0.0 32.9 50.0 W8X10 u

22 11.84 14.1 0.0 32.9 50.0 W8X10 u

24 11.84 11.4 0.0 32.9 50.0 W8X10 u

25 11.84 13.9 0.0 32.9 50.0 W8X10 u

26 11.84 12.1 0.0 32.9 50.0 W8X10 u

27 11.84 12.2 0.0 32.9 50.0 W8X10 u

28 11.84 14.1 0.0 32.9 50.0 W8X10 u

Steel Code: AISC360-16 LRFD

05/11/26 21:49:39

Page 2/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Beam Summary GF 20 of 64 u after Size denotes this size has been assigned by the User.

# after Size denotes beam failed deflection criteria.

* after Size denotes beam failed stress/capacity criteria.

29 5.08 2.0 0.0 32.3 50.0 W8X10 u

30 11.00 9.2 0.0 32.9 50.0 W8X10

31 11.84 5.9 0.0 32.9 50.0 W8X10

32 11.84 13.3 0.0 32.9 50.0 W8X10

52 11.17 11.9 0.0 32.9 50.0 W8X10

53 11.16 11.9 0.0 32.9 50.0 W8X10

54 11.16 11.9 0.0 32.9 50.0 W8X10

55 11.16 11.9 0.0 32.9 50.0 W8X10

56 11.16 11.9 0.0 32.9 50.0 W8X10

57 11.16 11.9 0.0 32.9 50.0 W8X10

58 17.75 27.8 0.0 32.4 50.0 W10X12

Steel Code: AISC360-16 LRFD

05/11/26 21:49:39

Page 3/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Beam Summary GF 21 of 64

Size Capacity Comments

MC8X8.5 20.94

MC8 33.79

MC9 33.79

MC10X6.5 17.78

MC10X8.4 19.89

MC10 33.79

MC12X10.6 33.34

MC12X14.3 43.87

MC12 58.72

MC13 58.72

MC18 97.87

C8X11.5 25.74

C8 33.79

C9X13.4 27.26

C9X15 33.34

C9 33.79

C10X15.3 28.08

C10 33.79

C12X20.7 49.49

C12 58.72

C15 78.30

W8X10 19.89

W8X13 26.91

User Defined Allowable Connection Values - Factored (kips):

on.

Engineer must verify that the standard number of bolts will fit in the connecti

First bolt is located 2.1/2" from top of steel. Top coped shall be limited to 1 a = 3" Max (see AISC figure 10-11)

Shear tabs: A36 (3/8" thick)

Designed per 15th ed. AISC pgs 10-87 to 10-91 ot excluded (A325N) in Std or SSLT holes.

Single shear tab connection FACTORED capacities using 7/8" dia bolts, threads n

Connection Table File Name: C:\ProgramData\Bentley\Engineering\RAM Structural

System\Tables\\AISC15th LRFD SS875 2020‑08‑28.con

Steel Code: AISC360-16 LRFD

05/11/26 21:49:39

Page 1/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Beam Connection Check GF 22 of 64

W8X15 28.66

W8X18 26.91

W8X21 29.25

W8X24 28.66

W8X28 33.34

W8X31 33.34

W8 33.79

W10X12 22.23

W10X15 26.91

W10X17 28.08

W10X19 29.25

W10X22 28.08

W10X26 30.42

W10 33.79

W12X14 35.10

W12X16 38.61

W12X19 41.24

W12X22 45.63

W12X26 40.36

W12X30 45.63

W12X35 52.65

W12X40 51.77

W12 58.72

W14X22 40.36

W14X26 44.75

W14X30 47.38

W14X34 50.02

W14X38 54.40

W14X43 53.53

W14 58.72

W16X26 58.50

W16X31 64.35

W16X36 69.03

W16X40 71.37

W16 78.30

W18X35 87.75

W18X40 92.14

W18 97.87

W21 97.87

Steel Code: AISC360-16 LRFD

05/11/26 21:49:39

Page 2/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Beam Connection Check GF 23 of 64

W24 117.45

W27 137.02

W30 156.60

W33 175.30

W36 193.53

W40 211.75

W44 229.98

0.00

Load Combinations:

1 1.4DL

2 1.2DL+1.6LL

Floor Type: ROOF

Number of Warnings = 0

Floor Type: LOW ROOF

Frame beams are not checked.

Beams with cantilevers are not checked at supports under cantilevers.

Notes:

Number of Warnings = 0

Steel Code: AISC360-16 LRFD

05/11/26 21:49:39

Page 3/3

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Beam Connection Check GF 24 of 64

DEFAULT SPLICE LEVELS:

Level Splice

ROOF Y

LOW ROOF N

DEMAND/CAPACITY LIMIT FOR STRENGTH:

Baseplates: 1.000

Columns: 1.000

DESIGN DEFAULTS:

Skip-load the Live Load around Column between column sides for calculating unbalanced moments: 30.0 deg.

Maximum Angle from column axis at which beam reaction is not split

STANDARD COLUMN TRIAL GROUPS:

Trial Group 1 Trial Group 2 Trial Group 3

I Section W14 W12 W10

Rect. HSS HSS6X6 HSS5X5 HSS4X4

Round HSS HSS6 HSS5 HSS4

HANGING COLUMN TRIAL GROUPS:

Trial Group 1 Trial Group 2 Trial Group 3

I Section W14 W12 W10

Rect. HSS HSS22X22 HSS20X20 HSS18X18

Round HSS HSS20 HSS18 HSS16

Channel C15 C12 C10

Tee WT22 WT20X16 WT20X12

Flat Bar FlatBar FlatBar FlatBar

Round Bar RoundBar RoundBar RoundBar

Single Angle L12X12 L10X10 L8X8

Double Angle 2L12X12 2L10X10 2L8X8

COLUMN BRACING:

Maximum Angle from column axis for which beam braces column: 60.0 deg.

Deck Does Not Brace Column

BASE PLATES:

Plate Fy (ksi) ..................................................................................................................... 36.000

Minimum Dimension From Face of Column to Edge of Plate (in) .................................. 3.000

Minimum Dimension From Side of Column to Edge of Plate (in) .................................. 1.000

Increment of Plate Dimensions (in) ................................................................................ 1.000

Increment of Plate Thickness (in) ................................................................................... 0.125

Design Code: AISC360-16 LRFD

Steel Code: AISC360-16 LRFD

05/11/26 22:01:58

Page 1/2

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Gravity Column Design Criteria GF 25 of 64

Minimum Footing Dimension Parallel to Web (;) .......................................................... 3.00

Minimum Footing Dimension Perpendicular to Web (;) ............................................... 3.00

Keep Base Plate Square:.................................................................................................. N

Steel Code: AISC360-16 LRFD

05/11/26 22:01:58

Page 2/2

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Gravity Column Design Criteria GF 26 of 64

DataBase: Snow College Washburn Addition v03 05/11/2026 22:04:15

GF 27 of 64

DEMAND/CAPACITY LIMIT FOR STRENGTH : 1.000

Column Line 1-C

Level Pu Mux Muy LC Interaction Eq. Angle Fy Size

ROOF 18.6 2.3 -5.6 1 0.46 Eq H1-1a 0.0 50 HSS6X6X1/4

LOW ROOF 19.0 1.5 -3.6 1 0.40 Eq H1-1a 0.0 50 HSS6X6X1/4

Column Line 1-B

Level Pu Mux Muy LC Interaction Eq. Angle Fy Size

ROOF 12.3 0.0 5.1 1 0.50 Eq H1-1a 0.0 50 HSS5X5X1/4

LOW ROOF 12.6 0.0 3.2 1 0.45 Eq H1-1a 0.0 50 HSS5X5X1/4

Column Line 7.42ft-36.33ft

Level Pu Mux Muy LC Interaction Eq. Angle Fy Size

ROOF 2.1 -0.7 0.0 1 0.07 Eq H1-1b 0.0 50 HSS4X4X1/4

LOW ROOF 6.6 -0.1 -1.6 1 0.18 Eq H1-1b 0.0 50 HSS4X4X1/4

Column Line 1.5-C

Level Pu Mux Muy LC Interaction Eq. Angle Fy Size

ROOF 58.9 0.0 0.0 1 0.92 Eq Axial 0.0 50 HSS6X6X1/4

LOW ROOF 59.3 0.0 0.0 1 0.93 Eq Axial 0.0 50 HSS6X6X1/4

Column Line 1.5-B

Level Pu Mux Muy LC Interaction Eq. Angle Fy Size

ROOF 21.0 0.0 8.7 1 0.38 Eq H1-1b 0.0 50 HSS5X5X1/4

LOW ROOF 26.7 0.0 -0.8 1 0.34 Eq H1-1a 0.0 50 HSS5X5X1/4

Column Line 1.5-A

Level Pu Mux Muy LC Interaction Eq. Angle Fy Size

LOW ROOF 12.6 0.3 1.5 1 0.39 Eq H1-1a 0.0 50 HSS4X4X1/4

Column Line 2-A

Level Pu Mux Muy LC Interaction Eq. Angle Fy Size

LOW ROOF 10.1 -1.1 1.3 1 0.36 Eq H1-1a 0.0 50 HSS4X4X1/4

Column Line 3-A

Level Pu Mux Muy LC Interaction Eq. Angle Fy Size

LOW ROOF 10.1 1.1 1.3 1 0.36 Eq H1-1a 0.0 50 HSS4X4X1/4

Column Line 3.9-C

Level Pu Mux Muy LC Interaction Eq. Angle Fy Size

Steel Code: AISC360-16 LRFD

05/11/26 22:05:42

Page 1/2

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Gravity Column Design Summary GF 28 of 64

ROOF 116.3 0.0 0.0 1 0.94 Eq Axial 0.0 50 HSS6X6X5/8

LOW ROOF 117.1 0.0 0.0 1 0.95 Eq Axial 0.0 50 HSS6X6X5/8

Column Line 3.9-B

Level Pu Mux Muy LC Interaction Eq. Angle Fy Size

ROOF 66.0 -2.6 -0.7 4 0.54 Eq H1-1a 0.0 50 HSS5X5X1/4

LOW ROOF 80.2 -2.8 -0.8 1 1.05 Eq H1-1a 0.0 50 HSS5X5X1/4

Column Line 3.9-A

Level Pu Mux Muy LC Interaction Eq. Angle Fy Size

LOW ROOF 11.3 -0.9 1.5 1 0.39 Eq H1-1a 0.0 50 HSS4X4X1/4

Column Line 5-B

Level Pu Mux Muy LC Interaction Eq. Angle Fy Size

LOW ROOF 6.8 -1.3 -0.2 1 0.38 Eq H1-1a 0.0 50 HSS4X4X1/8

Column Line 5-A

Level Pu Mux Muy LC Interaction Eq. Angle Fy Size

LOW ROOF 4.4 -0.9 0.7 1 0.14 Eq H1-1b 0.0 50 HSS4X4X1/4

Steel Code: AISC360-16 LRFD

05/11/26 22:05:42

Page 2/2

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Gravity Column Design Summary GF 29 of 64

BASE PLATES:

(ksi) (in) (in) (in)

1-C HSS6X6X1/4 36 12.00 8.00 0.375

1-B HSS5X5X1/4 36 11.00 7.00 0.375

7.42ft-36.33ft HSS4X4X1/4 36 10.00 6.00 0.375

1.5-C HSS6X6X1/4 36 12.00 8.00 0.625

1.5-B HSS5X5X1/4 36 11.00 7.00 0.500

1.5-A HSS4X4X1/4 36 10.00 6.00 0.375

2-A HSS4X4X1/4 36 10.00 6.00 0.375

3-A HSS4X4X1/4 36 10.00 6.00 0.375

3.9-C HSS6X6X5/8 36 12.00 8.00 0.875

3.9-B HSS5X5X1/4 36 11.00 7.00 0.875

3.9-A HSS4X4X1/4 36 10.00 6.00 0.375

5-B HSS4X4X1/8 36 10.00 6.00 0.375

5-A HSS4X4X1/4 36 10.00 6.00 0.250

Column Line Column Size Fy N B tp

Plate Fy (ksi) ..................................................................................................................... 36.000

Minimum Dimension From Face of Column to Edge of Plate (in) .................................. 3.000

Minimum Dimension From Side of Column to Edge of Plate (in) .................................. 1.000

Increment of Plate Dimensions (in) ................................................................................ 1.000

Increment of Plate Thickness (in) ................................................................................... 0.125

Minimum Footing Dimension Parallel to Web (2) .......................................................... 3.00

Minimum Footing Dimension Perpendicular to Web (2) ............................................... 3.00

Keep Base Plate Square:.................................................................................................. N

Design Code: AISC360-16 LRFD

Steel Code: AISC360-16 LRFD

05/11/26 22:07:13

Page 1/1

Building Code: IBC

DataBase: Snow College Washburn Addition v03

Reaveley Engineers

Base Plate Design Summary GF 30 of 64

WASHBURN ADDITION

A A

CC

BB

5' - 6" 48' - 0" 11' - 0" 27' - 2" 12' - 6"

104' - 2"

4" THICK CONCRETE SLAB

ON GRADE OVER 4" GRAVEL

W/CONSTRUCTION/

CONTROL JOINTS @ 10'-0"

O.C.E.W., TYPICAL

EXISTING WALLS AND

FOOTINGS NORTH OF

GRIDLINE A UNLESS

OTHERWISE NOTED

EXISTING WALLS AND

FOOTINGS EAST OF

GRIDLINE 5 UNLESS

OTHERWISE NOTED

S S

S S

TOF = 96' - 0"

TOF = 98' - 0"

S S

TOF = 96' - 0"

TOF = 98' - 0"

STEP FOOTING TO

MATCH EXISTING

FOOTING ELEVATION

STEP FOOTING TO

MATCH EXISTING

FOOTING ELEVATOIN

(E)TOF = 93' - 4"

TYP, UNO

TOF = 93' - 4"

TOF = 93' - 4"

S

NEW FOOTING TO

MATCH EXISTING

FOOTING ELEVATION

TOF = 98' - 0"

TYP AT

EXTERIOR

S

FC3.0

F C

3.

F C

3.

CP-1

CP-1

CP-1

CP-1 CP-1

CP-1

CP-1 F

S

5.

F S

5.

F S

5.

FS7.0

F S

3.

FS3.0FS3.0FS3.0FS3.0FS3.0

FS5.0

FS5.0 FS6.0FS5.0

D D

C J

CJ

C J

CJ

FS5.0

MW-1 ABV

M W

-1

M W

-1 A

B V

MW-1

M W

-1

MW-1

MW-1

M W

-1

MW-1

M W

-1

M W

-1 M W

-1

M W

-1CFW-1

C F

W -2

CFW-2

C

F W

-1

CFW-2

C F

W -2

CFW-2

C F

W -2

C F

W -1

C F

W -1

CFW-1

CFW-2

C F

W -2

C F

W -1

C F

W -2

CFW-1

C F

W -1

C F

W -1

MW-1

M W

-1 A

B V

F C

2.

FC2.0

FC1.5

CFW-1

FC1.5

CFW-1

FC1.5

F C

1.

FC2.0

F C

2.

F C

2.

FC2.0

F C

1.

FC1.5

C F

W -1

F C

1.

C F

W -1

F C

1.

C F

W -1

F C

1.

C F

W -1

F C

1.

C F

W -1

C F

W -1

C F

W -1

C F

W -1

F C

1.

F C

1.

F C

2.

FC2.0

F C

2.

F C

2.

CFW-1

FC2.0FC2.0

FC2.0

MW-1

FC2.0

F C

1.

F C

1.

C2

SB502

C1

SB502

C1

SB503B2

SF514

B1

SB514

C1

SB514

1. SEE ARCHITECTURAL, CIVIL AND LANDSCAPE

DRAWINGS FOR EXTERIOR CONCRETE RETAINING

AND / OR SITE WALLS NOT SHOWN ON THE

STRUCTURAL DRAWINGS.

2. SEE TYPICAL STEP DETAIL AT CONTINUOUS

FOOTING FOR REINFORCING REQUIREMENTS

. SEE FOR TYPICAL EXTERIOR

TO INTERIOR FOOTING STEP DETAIL.

3. PROVIDE REINFORCEMENT AT WALL ENDS,

INTERSECTIONS AND OPENINGS PER TYPICAL

DETAILS AND .

4. DOWEL ALL CONCRETE WALLS TO FOOTING PER

TYPICAL DETAIL .

5. PROVIDE COMPACTED STRUCTURAL FILL UNDER

ALL CONCRETE FOOTINGS PER TYPICAL DETAIL

FOOTING & FOUNDATION PLAN NOTES

/SB501C1 /SB514B2

/SB601C1 /SB601B1

/SB501C2

/SB502B1

SLAB ON GRADE PLAN NOTES

1. ALL SLABS ON GRADE SHALL BE 4 INCHES THICK,

UNLESS NOTED OTHERWISE. SEE TYPICAL

CONCRETE SLAB ON GRADE PROFILE DETAIL

FOR SUBGRADE REQUIREMENTS.

2. SEE ARCHITECTURAL, CIVIL AND LANDSCAPE

DRAWINGS FOR EXTERIOR CONCRETE WORK AT

DOORS, SIDEWALKS, ETC.

3. SEE ARCHITECTURAL DRAWINGS AND FINISH

SCHEDULE FOR SLAB DEPRESSIONS, SLOPES TO

DRAINS AND SLAB AREAS TO RECEIVE FLOOR TILE.

4. SEE TYPICAL CONCRETE SLAB ON GRADE DETAILS

FOR CONSTRUCTION JOINTS, CONTROL JOINTS AND

ADDITIONAL SLAB REINFORCING .

5. SUBMIT SLAB ON GRADE CONTROL JOINT PLAN

FOR REVIEW.

6. PROVIDE HOUSEKEEPING PADS AND CURBS PER

DETAIL . VERIFY DIMENSIONS AND

LOCATIONS OF CURBS AND PADS WITH MECHANICAL

AND EQUIPMENT SUPPLIER.

/SB501A1

/SB501A3

MASONRY WALL NOTES

1. TERMINATE HORIZONTAL REINFORCEMENT AT

CONTROL JOINTS IN MASONRY WALLS PER DETAIL

2. PROVIDE ADDITIONAL HORIZONTAL AND

VERTICAL REINFORCING AT WALL CORNERS, EDGES

OF OPENINGS, WALL ENDS, AND WALL

INTERSECTIONS PER

3. SEE FOR TYPICAL REINFORCING

AROUND MISCELLANEOUS OR RECESSED MASONRY

WALL OPENINGS.

4. SEE FOR REQUIRED ADDITIONAL

DUCTILITY REINFORCING IN LOAD BEARING

MASONRY WALLS.

/SB612B2

/SB611C1

/SB612A2

/SB611A1

EXISTING BUILDING NOTES

1. THE CONTRACTOR SHALL FIELD VERIFY ALL

EXISTING CONDITIONS PRIOR TO DETAILING,

FABRICATING, ERECTING OR INSTALLING ANY

STRUCTURAL ELEMENT. ALL DISCREPANCIES SHALL

BE BROUGHT TO THE ATTENTION OF THE DESIGN

TEAM IN A TIMELY MANNER SUCH THAT WORK WILL

NOT BE DELAYED.

2. THE CONTRACTOR SHALL PROVIDE ADEQUATE

SHORING OF EXISTING STRUCTURE DURING

CONSTRUCTION.

(801) 355-5915

PROJECT

REVISIONS

54321

D

C

B

A

NOT F

OR C

ONSTRUCTIO

N***

54321

/1

/2

:5 :5

P

M SB101

FOOTING &

FOUNDATION

PLAN

25-026

NOT FOR

CONSTRUCTION

2025-01-01

W A

S H

B U

R N

B U

IL

D

IN

G

E N

T R

A N

C E

A D

D

IT

IO

N

W

S

R

IC

H F

IE

L D

U

T A

H

SCALE:SB101 1/8" = 1'-0"

A1 FOOTING AND FOUNDATION PLAN

N

NO. DATE DESCRIPTION

GF 31 of 64

GRID B 2-3

(SC-1)

G R

ID

C (S

C -2

G R

ID

C (S

C -3

G R

ID

C -D

(S C

-4

GRID D 5-6

SC-11

G R

ID

D -C

.5 (S

C -5

G R

ID

C -D

(S C

-7

G R

ID

C -D

(S C

-8

GRID D 1-2

(SC-10)

G R

ID

B -A

(S C

-6

DOOR

JAMB 1

DOOR

JAMB 2

COLUMN 1

DOOR

JAMB 3

COLUMN 3

COLUMN 2

COLUMN 4

DOOR

JAMB 4

COLUMN 5

COLUMN 1

G R

ID

B (S

C -9

4'-10"

6'-1 1/2"

3' -1

/2

3'

-1

/2

'-9

/4

2' -3

/2

3'-7"

0'-11 3/4"

Wall/Pier Summary Worksheet

Project: Engineer:

Fp: 0.75 xWeight Material Strength, f'm: Load Combination Factors Seismic

CMU 2000 psi f1: 0.5 SDS 0.65

Brick 2000 psi f2: 0.2 Ie 1.25 ka 2.00

Masonry Desnity: Medium Weight (125pcf)

Input un-factored loads

Ref. Total Unbraced Wall Wind

Area Location Calc. Height Height Width H1 H2 Weight Load Trib. DL SL Trib. DL LL Type Wt. Type Wythes Solid Width e DL SL LL

Sheet (ft) (ft) (ft) (ft) (ft) (psf) (psf) (ft) (psf) (psf) (ft) (psf) (psf) (psf) Grout (in.) #L Size Spcg./# Cells (in.) (lbs) (lbs) (lbs)

WALL GRID 2 B-A (SC-6) 1 9 9 78 30 2.5 15 49 Wall 78 8" CMU 1 N 30 2 #4 8 in. O.C. 4 94 304 0

WALL GRID B 2-3 (SC-1) 2 24 9 55 5 11 15 37 Wall 55 8" CMU 1 N 48 1 #5 32 in. O.C. 4 660 1640 0

WALL GRID 1 C-D (SC-8) 3 24 24 55 30 2.65 15 22 Wall 58 8" CMU 1 N 12 2 #5 24 in. O.C. 4 40 59 0

WALL GRID 2 C-D (SC-8) 4 24 24 55 5 12.7 15 22 Wall 58 8" CMU 1 N 12 2 #5 24 in. O.C. 4 190 279 0

WALL GRID D 1-2 (SC-10) 5 24 24 55 30 3.5 15 22 Wall 58 8" CMU 1 N 12 2 #5 24 in. O.C. 4 53 77 0

WALL GRID 3C (SC-2) 6 24 24 55 5 17.6 15 22 Wall 58 8" CMU 1 N 12 2 #5 24 in. O.C. 4 264 388 0

WALL GRID 4C (SC-3) 7 24 24 55 5 17.6 15 22 Wall 58 8" CMU 1 N 12 2 #5 24 in. O.C. 4 264 388 0

WALL GRID 5 C-D (SC-4) 8 9 9 55 30 5.63 15 48.5 Wall 55 8" CMU 1 N 12 1 #5 32 in. O.C. 4 85 273 0

WALL GRID 6 D-C.5 (SC-5) 9 9 9 55 30 5.63 15 48.5 Wall 55 8" CMU 1 N 12 1 #5 32 in. O.C. 4 85 273 0

WALL GRID D 5-6 (SC-11) 10 9 9 55 30 3.75 15 48.5 Wall 55 8" CMU 1 N 12 1 #5 32 in. O.C. 4 57 182 0

WALL GRID 1B (SC-9) 11 24 24 55 30 1.35 15 22 Wall 58 8" CMU 1 N 12 2 #5 24 in. O.C. 4 21 30 0

DOOR JAMB 1 12 24 9 5 0 10 78 5 11 15 37.273 Pier 78 8" CMU 1 N 16 1 #5 1 Cell 0 633 1572 0

DOOR JAMB 2 13 9 9 6 0 7 78 30 2.5 15 48.5 Pier 78 8" CMU 1 N 16 1 #5 1 Cell 0 163 526 0

DOOR JAMB 3 14 9 9 3 0 7 78 30 5.63 15 48.5 Pier 78 8" CMU 1 N 16 1 #5 1 Cell 0 240 773 0

DOOR JAMB 4 15 9 9 3 0 7 78 30 5.63 15 48.5 Pier 78 8" CMU 1 N 16 1 #5 1 Cell 0 240 773 0

COLUMN COL 1 16 24 24 30 1 1140 5880 Pier 78 8" CMU 1 Y 40 2 #5 3 Cells 0 3800 5972 0

COLUMN COL 2 17 9 9 5 1 1100 2800 Pier 78 8" CMU 1 Y 16 2 #5 2 Cells 0 1467 3156 0

COLUMN COL 3 18 9 9 3 0 7 78 5 1 1100 2800 Pier 78 8" CMU 1 N 12 2 #5 1 Cell 0 2750 3467 0

COLUMN COL 4 19 9 9 5 1 660 1200 Pier 78 8" CMU 1 Y 16 2 #5 2 Cells 0 880 1556 0

COLUMN COL 5 20 24 24 30 1 940 4570 Pier 78 8" CMU 1 Y 24 2 #5 2 Cells 0 1880 4746 0

MISC MISC OPENING 21 24 24 6 0 10 58 30 5 15 49 Pier 78 8" CMU 1 Y 32 2 #5 4 Cells 0 425 1389 0

SC Washburn Addition

Reinforcing

Eccentric LoadsRoof LoadsOpening Floor Loads Wall/Pier

Width

U n b ra c e d

H t.

T o ta l H e ig h t.

© Reaveley Engineers

GF 32 of 64

Project:

Fp: 0.75 xWeight

Ref. Total Unbraced

Area Location Calc. Height Height

Sheet (ft) (ft)

WALL GRID 2 B-A (SC-6) 1 9 9

WALL GRID B 2-3 (SC-1) 2 24 9

WALL GRID 1 C-D (SC-8) 3 24 24

WALL GRID 2 C-D (SC-8) 4 24 24

WALL GRID D 1-2 (SC-10) 5 24 24

WALL GRID 3C (SC-2) 6 24 24

WALL GRID 4C (SC-3) 7 24 24

WALL GRID 5 C-D (SC-4) 8 9 9

WALL GRID 6 D-C.5 (SC-5) 9 9 9

WALL GRID D 5-6 (SC-11) 10 9 9

WALL GRID 1B (SC-9) 11 24 24

DOOR JAMB 1 12 24 9

DOOR JAMB 2 13 9 9

DOOR JAMB 3 14 9 9

DOOR JAMB 4 15 9 9

COLUMN COL 1 16 24 24

COLUMN COL 2 17 9 9

COLUMN COL 3 18 9 9

COLUMN COL 4 19 9 9

COLUMN COL 5 20 24 24

MISC MISC OPENING 21 24 24

SC Washburn Addition

Wall/Pier Summary Worksheet

IBC - ACI 530/ASCE 5/TMS 402

EW

Concentric

DL WL EL MARK

(lbs) (plf) (plf)

878 75 147 MW-2

4290 20 165 MW-1

696 30 44 MW-3

696 5 44 MW-3

696 30 44 MW-3

696 5 44 MW-3

696 5 44 MW-3

248 30 42 MW-1

248 30 42 MW-1

248 30 42 MW-1

696 30 44 MW-3

4758 20 78 MC-1

936 130 106 MC-1

702 85 92 MC-1

702 85 92 MC-1

3120 100 195 MC-6

468 7 78 MC-3

585 13 73 MC-2

468 7 78 MC-3

1872 60 117 MC-4

4932 170 246 MC-5

H1

H2

Deck Brg.

GF 33 of 64

Project: SC Washburn Addition Engineer:

Ref. Total Unbraced Wall Wind

Area Location Calc. Height Height Width H1 H2 Weight Load Trib. DL SL Trib. DL LL Type Wt. Type Wythes Solid Width e DL SL LL

Sheet (ft) (ft) (ft) (ft) (ft) (psf) (psf) (ft) (psf) (psf) (ft) (psf) (psf) (psf) Grout (in.) #L Size Spcg. (in.) (lbs) (lbs) (lbs)

Eccentric Loads

Reinf.

Opening Roof Loads Floor Loads Wall/Pier

GF 34 of 64

Project: SC Washburn Addition

Ref. Total Unbraced

Area Location Calc. Height Height

Sheet (ft) (ft)

Wall/Pier Summary Worksheet

IBC - ACI 530/ASCE 5/TMS 402

EW

Concentric

DL WL EL MARK

(lbs) (plf) (plf)

GF 35 of 64

Ref. Total Unbraced Wall Wind

Area Location Calc. Height Height Width H1 H2 Weight Load Trib. DL SL Trib. DL LL Type Wt. Type Wythes Solid Width e DL SL LL

Sheet (ft) (ft) (ft) (ft) (ft) (psf) (psf) (ft) (psf) (psf) (ft) (psf) (psf) (psf) Grout (in.) #L Size Spcg. (in.) (lbs) (lbs) (lbs)

Opening Roof Loads Floor Loads Eccentric LoadsWall/Pier

Reinf.

GF 36 of 64

Area Location Calc. Height Height

Sheet (ft) (ft)

Wall/Pier Summary Worksheet

IBC - ACI 530/ASCE 5/TMS 402

EW

Concentric

DL WL EL MARK

(lbs) (plf) (plf)

GF 37 of 64

Ref. Total Unbraced Wall Wind

Area Location Calc. Height Height Width H1 H2 Weight Load Trib. DL SL Trib. DL LL Type Wt. Type Wythes Solid Width e DL SL LL

Sheet (ft) (ft) (ft) (ft) (ft) (psf) (psf) (ft) (psf) (psf) (ft) (psf) (psf) (psf) Grout (in.) #L Size Spcg. (in.) (lbs) (lbs) (lbs)

Reinf.

Opening Roof Loads Floor Loads Wall/Pier Eccentric Loads

GF 38 of 64

Area Location Calc. Height Height

Sheet (ft) (ft)

Wall/Pier Summary Worksheet

IBC - ACI 530/ASCE 5/TMS 402

EW

Concentric

DL WL EL MARK

(lbs) (plf) (plf)

GF 39 of 64

Project:

Fp: 0.75 xWeight

Ref. Total Unbraced

Area Location Calc. Height Height

Sheet (ft) (ft)

WALL GRID 2 B-A (SC-6) 1 9 9

WALL GRID B 2-3 (SC-1) 2 24 9

WALL GRID 1 C-D (SC-8) 3 24 24

WALL GRID 2 C-D (SC-8) 4 24 24

WALL GRID D 1-2 (SC-10) 5 24 24

WALL GRID 3C (SC-2) 6 24 24

WALL GRID 4C (SC-3) 7 24 24

WALL GRID 5 C-D (SC-4) 8 9 9

WALL GRID 6 D-C.5 (SC-5) 9 9 9

WALL GRID D 5-6 (SC-11) 10 9 9

WALL GRID 1B (SC-9) 11 24 24

DOOR JAMB 1 12 24 9

DOOR JAMB 2 13 9 9

DOOR JAMB 3 14 9 9

DOOR JAMB 4 15 9 9

COLUMN COL 1 16 24 24

COLUMN COL 2 17 9 9

COLUMN COL 3 18 9 9

COLUMN COL 4 19 9 9

COLUMN COL 5 20 24 24

MISC MISC OPENING 21 24 24

SC Washburn Addition

Wall/Pier Summary Worksheet

IBC - ACI 530/ASCE 5/TMS 402

Engineer: EW

Minimum Footing Size: 2 ft

Bearing Pressure 2000 psf

Max

DCR Axial DCR Deflection AsMax Footing Load Length Width Bearing

(kip) (ft) (ft) DCR

0.10 0.02 0.01 1.3 2.5 2.0 0.1

0.23 0.06 0.01 6.6 4.0 2.0 0.4

0.93 0.11 0.90 0.8 1.0 2.0 0.2

0.95 0.16 0.92 1.2 1.0 2.0 0.3

0.94 0.11 0.90 3.1 1.0 2.0 0.8

0.96 0.19 0.93 1.3 1.0 2.0 0.3

0.96 0.19 0.93 1.3 1.0 2.0 0.3

0.26 0.02 0.01 0.6 1.0 2.0 0.2

0.26 0.02 0.01 0.6 1.0 2.0 0.2

0.25 0.02 0.01 0.5 1.0 2.0 0.1

0.93 0.11 0.90 0.7 1.0 2.0 0.2

0.16 0.18 0.01 7.0 1.3 3.0 0.9

0.30 0.04 0.02 1.6 1.3 2.0 0.3

0.22 0.05 0.01 1.7 1.3 2.0 0.3

0.22 0.05 0.01 1.7 1.3 2.0 0.3

0.74 0.59 0.66 12.9 3.3 2.0 1.0

0.06 0.17 0.01 5.1 1.3 2.0 1.0

0.11 0.42 0.01 6.8 1.0 3.5 1.0

0.06 0.09 0.01 2.9 1.3 2.0 0.5

0.68 0.66 0.62 8.5 2.0 2.5 0.8

0.77 0.35 0.98 6.7 2.7 2.0 0.6

#VALUE!

#VALUE!

#VALUE!

#VALUE!

#VALUE!

Footing

GF 40 of 64

Area Location Calc. Height Height

Sheet (ft) (ft)

Wall/Pier Summary Worksheet

IBC - ACI 530/ASCE 5/TMS 402

Engineer: EW

Max

DCR Axial DCR Deflection AsMax Footing Load Length Width Bearing

(kip) (ft) (ft) DCR

#VALUE!

#VALUE!

#VALUE!

#VALUE!

#VALUE!

#VALUE!

#VALUE!

#VALUE!

Footing

GF 41 of 64

Area Location Calc. Height Height

Sheet (ft) (ft)

Wall/Pier Summary Worksheet

IBC - ACI 530/ASCE 5/TMS 402

Engineer: EW

Max

DCR Axial DCR Deflection AsMax Footing Load Length Width Bearing

(kip) (ft) (ft) DCR

Footing

GF 42 of 64

Area Location Calc. Height Height

Sheet (ft) (ft)

Wall/Pier Summary Worksheet

IBC - ACI 530/ASCE 5/TMS 402

Engineer: EW

Max

DCR Axial DCR Deflection AsMax Footing Load Length Width Bearing

(kip) (ft) (ft) DCR

Footing

GF 43 of 64

Masonry Wall/Pier - Strength Design

IBC - TMS 402/602

PROJECT NAME: ENGINEER:

LOCATION: 1 WALL GRID 2 B-A (SC-6) DATE:

WALL REINFORCING SEISMIC

Material: 8" CMU Material: ASTM A615 Gr. 60 SDS: 0.65 f'm: 2000 psi Layers: 2 I: 1.25

Wythes: One Thickness:7.625 in. Size: #4 ka: 2.00

Width: 30 in. Spacing: 8 in. o.c. Fp: 51 psf

Solid Grout: d: 5.125 in.

Self Weight: 78 psf Medium Weight (115pcf) Program Assumes Un-Reinforced Cells are Not Grouted

WALL/PIER GEOMETRY

Unbraced Height: 9 ft.

Height Above 0 ft.

UN-FACTORED LOADS 0.5 f1: 0.5 f2: 0.2

Eccentric Loads Concentric Loads Out-of-Plane Loads

Snow (S): 304 lbs Snow (S): 0 lbs Wind (Out): 75 plf

Live (L): 0 lbs Live (L): 0 lbs Wind (In): 75 plf

D…