5-5-DA26052-26189700 Approved Energy COMcheck.pdf
PDF 753 KB Posted
- Solicitation number
- DA26052-Stage II
- Issued by
- Utah
About this file
This is an Energy Compliance Certificate for the Washburn Addition project located in Richfield, Utah, prepared by the Division of Facilities Construction and Management under the 2021 IECC standards. The project involves an entrance addition on the south side of the Washburn building at Snow College, with an associated construction cost estimate of $5,400,000. The energy compliance report, dated May 29, 2026, and reviewed for code compliance on July 13, 2026, documents the building's envelope design, interior and exterior lighting systems, and mechanical specifications across 5,073 square feet of nonresidential space in Climate Zone 5b. The building envelope achieves 11% better performance than code requirements, featuring metal frame and masonry exterior walls with continuous insulation, metal frame windows with thermal breaks, and roof insulation rated at R-30. The facility incorporates LED lighting throughout with proposed interior lighting consuming 1,690 watts against an allowable 3,653 watts, representing 54% better performance than code, and exterior lighting utilizing 2,972 proposed watts against 6,583.48 allowed watts, achieving 55% better performance than code standards.
The compliance certificate includes detailed fenestration specifications with performance certifications required in accordance with NFRC standards, interior and exterior lighting controls incorporating occupancy sensors, time switches, and daylight shutoff capabilities, and an inspection checklist addressing envelope compliance, lighting systems, electrical equipment efficiency, and insulation installation requirements. All proposed systems have been designed to meet 2021 IECC mandatory requirements and energy efficiency benchmarks, with architect Kathryn Anderson certifying compliance on June 26, 2026. The document confirms that the proposed design aligns with building plans and specifications submitted with the permit application, and addresses energy code compliance across envelope assemblies, fenestration products, lighting power allowances, and control systems for both interior and exterior applications.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Report Title: Washburn Addition Report Date: May 29, 2026, 09:54 AM (PDT) 1 of 17
Compliance Certificate
Project Information
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Project No:
All Electric:
Is Renewable:
Has Battery:
Has Charger:
Has Heat Pump
2021 IECC
Washburn Addition Richfield, Utah 5b Addition 117392 false false false false false
Construction Site: Owner/Agent: Designer/Contractor:
Notes:
Building Area
Description Floor Area
1-School-University (School/University) : Nonresidential 5073
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
07/13/2026
REVIEWED FOR CODE
COMPLIANCE
Report Title: Washburn Addition Report Date: May 29, 2026, 09:54 AM (PDT) 2 of 17
Envelope Compliance Certificate
Project Information
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Vertical Glazing / Wall Area:
2021 IECC
Washburn Addition Richfield, Utah 5b Addition 0.218
Construction Site: Owner/Agent: Designer/Contractor:
Envelope Assemblies
Assembly Gross Area or Perimeter
Cavity R- Value
Cont.
R- Value
Proposed U-Factor
Budget U- Factor
Roof:Roof, Insulation Entirely Above Deck, [Bldg. Use 1 - School- University]
5481 --- 30.00 0.032 0.032
Roof:Roof, Insulation Entirely Above Deck, [Bldg. Use 1 - School- University]
1710 --- 30.00 0.032 0.032
Floor:Floor, Unheated Slab-On-Grade, Vertical 2 ft., [Bldg. Use 1 - School-University] (c)
571 --- 15.00 0.520 0.520
NORTH
Ext Wall:Ext Wall 4, Masonry, Light Density, Furring: Metal, [Bldg. Use 1 - School-University]
1261 1.50 11.40 0.067 0.090
Window:Window 3, Metal Frame with Thermal Break, Perf. Specs.:
Product ID , SHGC 0.23, VT 0.51, [Bldg. Use 1 - School- University] (b)
78 --- --- 0.350 0.360
EAST
Ext Wall:Ext Wall 5, Masonry, Light Density, Furring: Metal, [Bldg. Use 1 - School-University]
1261 1.50 11.40 0.067 0.090
Ext Wall:Ext Wall 6, Masonry, Light Density, Furring: Metal, [Bldg. Use 1 - School-University]
653 1.50 11.40 0.067 0.090
Ext Wall:Ext Wall 7, Masonry, Light Density, Furring: Metal, [Bldg. Use 1 - School-University]
373 1.50 11.40 0.067 0.090
Ext Wall:Ext Wall 8, Masonry, Light Density, Furring: Metal, [Bldg. Use 1 - School-University]
653 1.50 11.40 0.067 0.090
Ext Wall:Ext Wall 9, Metal Frame, 16" o.c., [Bldg. Use 1 - School- University]
512 19.00 10.00 0.052 0.055
Window:Window 4, Metal Frame with Thermal Break, Perf. Specs.:
Product ID , SHGC 0.22, PF 2.60, VT 0.47, [Bldg. Use 1 - School- University] (b)
149 --- --- 0.350 0.360
SOUTH
Ext Wall:Ext Wall 2, Metal Frame, 16" o.c., [Bldg. Use 1 - School- University]
1712 19.00 10.00 0.052 0.055
Window:Window 5, Metal Frame with Thermal Break, Perf. Specs.:
Product ID , SHGC 0.21, PF 1.00, VT 0.47, [Bldg. Use 1 - School- University] (b)
1400 --- --- 0.340 0.360
Door:Door 3, Perf. Specs.: Product ID , SHGC 0.21, PF 1.00, VT 0.47, [Bldg. Use 1 - School-University] (b)
64 --- --- 0.340 0.630
Ext Wall:Ext Wall 3, Masonry, Light Density, Furring: Metal, [Bldg. Use 1 - School-University]
984 1.50 11.40 0.067 0.090
WEST
Report Title: Washburn Addition Report Date: May 29, 2026, 09:54 AM (PDT) 3 of 17
Assembly Gross Area or Perimeter
Cavity R- Value
Cont.
R- Value
Proposed U-Factor
Budget U- Factor
Ext Wall:Ext Wall, Metal Frame, 16" o.c., [Bldg. Use 1 - School- University]
1671 19.00 10.00 0.052 0.055
Window:Window 1, Metal Frame with Thermal Break, Perf. Specs.:
Product ID , SHGC 0.21, PF 0.26, VT 0.47, [Bldg. Use 1 - School- University] (b)
566 --- --- 0.340 0.360
Door:Door 2, Insulated Metal, Swinging, [Bldg. Use 1 - School- University]
54 --- --- 0.200 0.370
Ext Wall:Ext Wall 1, Masonry, Light Density, Furring: Metal, [Bldg. Use 1 - School-University]
1261 1.50 11.40 0.067 0.090
(a) Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.
(b) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
(c) Slab-On-Grade proposed and budget U-factors shown in table are F-factors.
Envelope PASSES: Design 11% better than code
Envelope Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed envelope systems have been designed to meet the 2021 IECC requirements in COMcheckWeb and to comply with any applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Kathryn Anderson, Architect 06/26/26
Report Title: Washburn Addition Report Date: May 29, 2026, 09:54 AM (PDT) 4 of 17
Interior Lighting Compliance Certificate
Project Information
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
2021 IECC
Washburn Addition Richfield, Utah 5b Addition
Construction Site: Owner/Agent: Designer/Contractor:
Allowed Interior Lighting Power
A B C D
Area Category Floor Area (ft2) Allowed Watts / ft2 Allowed Watts
1-STUDENT COMMONS (Common Space Types:Atrium) (Ceiling Height 20 ft.)
2905 0.48 1394
2-HALL (Common Space Types:Corridor/Transition >=8 ft wide) 769 0.41 315
3-STORAGE 107 (Common Space Types:Electrical/Mechanical) 476 0.43 205
4-KITCHENETTE (Common Space Types:Lounge/Breakroom) 97 0.59 57
5-STORAGE 104 (Common Space Types:Electrical/Mechanical) 102 0.43 44
6-MECHANICAL (Common Space Types:Electrical/Mechanical) 133 0.43 57
Total Allowed Watts: 3653
Proposed Interior Lighting Power
A B C D
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
# of Fixture Fixture Watt. (B X C)
1-STUDENT COMMONS (Common Space Types:Atrium) (Ceiling Height 20 ft.)
RD-04: RD-04: LED: 18 58 1044
RD-02: RD-02: LED: 4 20 80
2-HALL (Common Space Types:Corridor/Transition >=8 ft wide)
RD-01: RD-01: LED: 20 15 300
3-STORAGE 107 (Common Space Types:Electrical/Mechanical)
TP-22: TP-22: LED: 8 21 168
4-KITCHENETTE (Common Space Types:Lounge/Breakroom)
TP-22: TP-22: LED: 2 21 42
5-STORAGE 104 (Common Space Types:Electrical/Mechanical)
TP-22: TP-22: LED: 2 21 42
6-MECHANICAL (Common Space Types:Electrical/Mechanical)
SL-41: SL-41: LED: 2 7 14
Total Proposed Watts: 1690
Report Title: Washburn Addition Report Date: May 29, 2026, 09:54 AM (PDT) 5 of 17
Proposed Interior Lighting Controls
Fixture Lighting Control
1-STUDENT COMMONS (Common Space Types:Atrium) (Ceiling Height 20 ft.)
RD-04: RD-04: LED: Interior Timeswitch, Manual Control
RD-02: RD-02: LED: Interior Timeswitch, Manual Control
2-HALL (Common Space Types:Corridor/Transition >=8 ft wide)
RD-01: RD-01: LED: Interior Timeswitch, Manual Control
3-STORAGE 107 (Common Space Types:Electrical/Mechanical)
TP-22: TP-22: LED: Manual Control
4-KITCHENETTE (Common Space Types:Lounge/Breakroom)
TP-22: TP-22: LED: Occupancy Sensor, Manual Control
5-STORAGE 104 (Common Space Types:Electrical/Mechanical)
TP-22: TP-22: LED: Manual Control
6-MECHANICAL (Common Space Types:Electrical/Mechanical)
SL-41: SL-41: LED: Manual Control
Interior Lighting PASSES: Design 54% better than code
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been designed to meet the 2021 IECC requirements in COMcheckWeb and to comply with any applicable mandatory requirements listed in the Inspection Checklist.
Report Title: Washburn Addition Report Date: May 29, 2026, 09:54 AM (PDT) 6 of 17
Exterior Lighting Compliance Certificate
Project Information
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Exterior Lighting Zone:
2021 IECC
Washburn Addition Richfield, Utah 5b Addition Other (LZ3)
Construction Site: Owner/Agent: Designer/Contractor:
Allowed Exterior Lighting Power
A B C D E
Area/Surface Category Quantity Allowed Watts / ft2 Tradable Wattage Allowed Watts (B X C)
Entry Canopy (Entry canopy) 1602 ft2 0.40 No 640.8000000000001
Ext Area (Landscaping) 136067 ft2 0.04 No 5442.68
Total Tradable Watts (a): 6083.48
Base Site Allowance (b): 500
Total Allowed Watts: 6583.48
(a) Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b) A base site allowance equal to 400 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
A B C D E
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
Lamps/Fixture # of Fixture Fixture Watt. (C X D)
Entry Canopy (Entry canopy, 1602 ft2): Tradeable Wattage
RD-03: RD-03: LED: 0 6 15 90
HR-01: HR-01: LED: 0 4 3 12
Ext Area (Landscaping, 136067 ft2): Tradeable Wattage
PL-01: PL-01: LED: 0 13 70 910
NG-01: NG-01: LED: 0 8 35 280
LS-01: LS-01: LED: 0 60 28 1680
Total Tradable Proposed Watts: 2972
Proposed Exterior Lighting Controls
Fixture Lighting Control
Entry Canopy (Entry canopy, 1602 ft2)
RD-03: RD-03: LED: Daylight Shutoff, Exterior Timeswitch
HR-01: HR-01: LED: Daylight Shutoff, Exterior Timeswitch
Ext Area (Landscaping, 136067 ft2)
PL-01: PL-01: LED: Daylight Shutoff, Facade or Landscape
Report Title: Washburn Addition Report Date: May 29, 2026, 09:54 AM (PDT) 7 of 17
Fixture Lighting Control
NG-01: NG-01: LED: Daylight Shutoff, Facade or Landscape
LS-01: LS-01: LED: Daylight Shutoff, Facade or Landscape
Exterior Lighting PASSES: Design 55% better than code
Exterior Lighting Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been designed to meet the 2021 IECC requirements in COMcheckWeb and to comply with any applicable mandatory requirements listed in the Inspection Checklist.
Report Title: Washburn Addition Report Date: May 29, 2026, 09:54 AM (PDT) 8 of 17
Inspection Checklist
Energy Code: 2021 IECC
Requirements: 0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Plan Review
Section
& Req.ID Plan Review Complies? Comments/Assumptions
C103.2
[PR1]1
Plans and/or specifications provide all information with which compliance can be determined for the building envelope and document where exceptions to the standard are claimed.
Complies
Does Not Comply
Not Observable
Not Applicable
C402.4.2
[PR14]1
In enclosed spaces > 2,500 ft2 directly under a roof with ceiling heights >15 ft. and used as an office, lobby, atrium, concourse, corridor, storage, gymnasium/exercise center, convention center, automotive service, manufacturing, non-refrigerated warehouse, retail store, distribution/sorting area, transportation, or workshop, the following requirements apply: (a) the daylight zone under skylights is >= half the floor area; (b) the skylight area to daylight zone is >= 3 percent with a skylight VT >= 0.40; or a minimum skylight effective aperture >= 1 percent.
Complies
Does Not Comply
Not Observable
Not Applicable
C406
[PR9]1
Plans, specifications, and/or calculations provide all information with which compliance can be determined for the additional energy efficiency package options.
Complies
Does Not Comply
Not Observable
Not Applicable
C103.2
[PR4]1
Plans, specifications, and/or calculations provide all information with which compliance can be determined for the interior lighting and electrical systems and equipment and document where exceptions to the standard are claimed. Information provided should include interior lighting power calculations, wattage of bulbs and ballasts, transformers and control devices.
Complies
Does Not Comply
Not Observable
Not Applicable
C103.2
[PR8]1
Plans, specifications, and/or calculations provide all information with which compliance can be determined for the exterior lighting and electrical systems and equipment and document where exceptions to the standard are claimed. Information provided should include exterior lighting power calculations, wattage of bulbs and ballasts, transformers and control devices.
Complies
Does Not Comply
Not Observable
Not Applicable
C402.4.1
[PR10]1
The vertical fenestration area <= 30 percent of the gross above-grade wall area.
Complies
Does Not Comply
Not Observable
Not Applicable
C402.4.1
[PR11]1
The skylight area <= 3 percent of the gross roof area.
Complies
Does Not Comply
Not Observable
Not Applicable
Additional Comments/Assumptions:
Report Title: Washburn Addition Report Date: May 29, 2026, 09:54 AM (PDT) 9 of 17
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Report Title: Washburn Addition Report Date: May 29, 2026, 09:54 AM (PDT) 10 of 17
Footing / Foundation Inspection
Section
& Req.ID Footing / Foundation Inspection Complies? Comments/Assumptions
C303.2
[FO4]2
Slab edge insulation installed per manufacturer’s instructions.
Complies
Does Not Comply
Not Observable
Not Applicable
C303.2.1
[FO6]1
Exterior insulation protected against damage, sunlight, moisture, wind, landscaping and equipment maintenance activities.
Complies
Does Not Comply
Not Observable
Not Applicable
C105
[FO3]2
Installed slab-on-grade insulation type and R-value consistent with insulation specifications reported in plans and COMcheck reports.
Complies
Does Not Comply
Not Observable
Not Applicable
See the Envelope Assemblies table for values
C402.2.4
[FO7]2
Slab edge insulation depth/length. Slab insulation extending away from building is covered by pavement or >= 10 inches of soil.
Complies
Does Not Comply
Not Observable
Not Applicable
See the Envelope Assemblies table for values
Report Title: Washburn Addition Report Date: May 29, 2026, 09:54 AM (PDT) 11 of 17
Framing / Rough-In Inspection
Section # & Req.ID Framing / Rough-In Inspection Complies? Comments/Assumptions
C303.1.3
[FR12]2
Fenestration products rated in accordance with NFRC certified and as to performance labels or certificates provided.
Complies
Does Not Comply
Not Observable
Not Applicable
C402.5.4
[FR18]3
Factory-built fenestration and doors are labeled as meeting air leakage requirements.
Complies
Does Not Comply
Not Observable
Not Applicable
C402.5.9
[FR17]3
Vestibules are installed on all building entrances. Doors have self-closing devices.
Complies
Does Not Comply
Not Observable
Not Applicable
C402.4.3
[FR10]1
Vertical fenestration SHGC value. Complies
Does Not Comply
Not Observable
Not Applicable
See the Envelope Assemblies table for values
C402.4.3, C402.4.3.4
[FR8]1
Installed vertical fenestration U-factor and SHGC consistent with label specifications and as reported in plans and COMcheck reports.
Complies
Does Not Comply
Not Observable
Not Applicable
See the Envelope Assemblies table for values
C402.4.5
[FR14]2
U-factor of opaque swinging and nonswinging doors associated with the building thermal envelope meets requirements.
Complies
Does Not Comply
Not Observable
Not Applicable
See the Envelope Assemblies table for values
C402.5.1
[FR16]1
The building envelope contains a continuous air barrier that is sealed in an approved manner and either constructed or tested in an approved manner. Air barrier penetrations are sealed in an approved manner.
Complies
Does Not Comply
Not Observable
Not Applicable
Report Title: Washburn Addition Report Date: May 29, 2026, 09:54 AM (PDT) 12 of 17
Mechanical Rough-In Inspection
Section # & Req.ID Mechanical Rough-In Inspection Complies? Comments/Assumptions
C402.5.7, C403.7.7
[ME3]3
Stair and elevator shaft vents have motorized dampers that automatically close. Reference section C403.7.7 for operational details.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.7.7
[ME58]3
Outdoor air and exhaust systems have motorized dampers that automatically shut when not in use and meet maximum leakage rates. Check gravity dampers where allowed.
Reference section language for operational details.
Complies
Does Not Comply
Not Observable
Not Applicable
Report Title: Washburn Addition Report Date: May 29, 2026, 09:54 AM (PDT) 13 of 17
Rough-In Electrical Inspection
Section
& Req.ID Rough-In Electrical Inspection Complies? Comments/Assumptions
C405.2.3.1
[EL22]1
Spaces required to have light-reduction controls have a manual control that allows the occupant to reduce the connected lighting load in a reasonably uniform illumination pattern >= 50 percent.
Complies
Does Not Comply
Not Observable
Not Applicable
C405.2.7
[EL28]1
Automatic lighting controls for exterior lighting installed. Controls will be daylight controlled, set based on business operation time-of-day, or reduce connected lighting > 30%.
Complies
Does Not Comply
Not Observable
Not Applicable
C405.7
[EL26]2
Low-voltage dry-type distribution electric transformers meet the minimum efficiency requirements of Table C405.6.
Complies
Does Not Comply
Not Observable
Not Applicable
C405.8
[EL27]2
Electric motors meet the minimum efficiency requirements of Tables C405.7(1) through C405.7(4). Efficiency verified through certification under an approved certification program or the equipment efficiency ratings shall be provided by motor manufacturer (where certification programs do not exist).
Complies
Does Not Comply
Not Observable
Not Applicable
C405.9.1, C405.9.2
[EL28]2
Escalators and moving walks comply with ASME A17.1/CSA B44 and have automatic controls configured to reduce speed to the minimum permitted speed in accordance with ASME A17.1/CSA B44 or applicable local code when not conveying passengers.
Complies
Does Not Comply
Not Observable
Not Applicable
C405.10
[EL29]2
Total voltage drop across the combination of feeders and branch circuits <= 5%.
Complies
Does Not Comply
Not Observable
Not Applicable
C405.1.1
[EL30]2
At least 90% of dwelling unit permanently installed lighting shall have lamp efficacy >= 65 lm/W or luminaires with efficacy >= 45 lm/W or comply with C405.2.4 or C405.3.
Complies
Does Not Comply
Not Observable
Not Applicable
C405.11, C405.11.1
[EL31]2
50% of 15/20 amp receptacles installed in enclosed offices, conference rooms, copy rooms, break rooms, classrooms and workstations and > 25% of branch circuit feeders for modular furniture will have automatic receptacle control in accordance with C405.11.1.
Complies
Does Not Comply
Not Observable
Not Applicable
C405.2.1, C405.2.1.1
[EL18]1
Occupancy sensors installed in classrooms/lecture/training rooms, conference/meeting/multipurpose rooms, copy/print rooms, lounges/breakrooms, enclosed offices, open plan office areas, restrooms, storage rooms, locker rooms, corridors, warehouse storage areas, and other spaces <= 300 sqft that are enclosed by floor-to-ceiling height partitions. Reference section language C405.2.1.2 for control function in warehouses and section C405.2.1.3 for open plan office spaces.
Complies
Does Not Comply
Not Observable
Not Applicable
C405.2.1.2
[EL19]1
Occupancy sensors control function in warehouses: In warehouses, the lighting in aisleways and open areas is controlled with occupant sensors that automatically reduce lighting power by 50% or more within 20 minutes of when the areas are unoccupied.
The occupant sensors control lighting in each aisleway independently and do not control lighting beyond the aisleway being controlled by the sensor. Lights not turned off by occupant sensors is done so by time-switch.
Complies
Does Not Comply
Not Observable
Not Applicable
Report Title: Washburn Addition Report Date: May 29, 2026, 09:54 AM (PDT) 14 of 17
Section
& Req.ID Rough-In Electrical Inspection Complies? Comments/Assumptions
C405.2.1.3
[EL20]1
Occupant sensor control function in open plan office areas: Occupant sensor controls in open office spaces >= 300 sq.ft. have controls 1) configured so that general lighting can be controlled separately in control zones with floor areas <= 600 sq.ft. within the space, 2) general lighting in each zone permitted to turn on upon occupancy in control zone, 3) automatically turn off general lighting in all control zones within 20 minutes after all occupants have left the space, 4) are configured so that general lighting power in each control zone is reduced by >= 80% of the full zone general lighting power within 20 minutes of all occupants leaving that control zone.
Complies
Does Not Comply
Not Observable
Not Applicable
C405.2.2, C405.2.2.1
[EL21]2
Each area not served by occupancy sensors (per C405.2.1.1) have time-switch controls and functions detailed in sections C405.2.2.1.
Complies
Does Not Comply
Not Observable
Not Applicable
C405.2.4, C405.2.4.1, C405.2.4.2
[EL23]2
Daylight zones provided with individual controls that control the lights independent of general area lighting. See code section C405.2.3 Daylight-responsive controls for applicable spaces, C405.2.3.1 Daylight responsive control function and section C405.2.3.2 Sidelit zone.
Complies
Does Not Comply
Not Observable
Not Applicable
C405.2.5
[EL27]1
Additional interior lighting power allowed for special functions per the approved lighting plans and is automatically controlled and separated from general lighting.
Complies
Does Not Comply
Not Observable
Not Applicable
Report Title: Washburn Addition Report Date: May 29, 2026, 09:54 AM (PDT) 15 of 17
Insulation Inspection
Section
& Req.ID Insulation Inspection Complies? Comments/Assumptions
C303.1
[IN3]1
Roof insulation installed per manufacturer’s instructions and is labeled with R-value or insulation certificate providing R-value and other relevant data. Blown or poured loose-fill insulation is installed only where the roof slope is <=3 in 12.
Complies
Does Not Comply
Not Observable
Not Applicable
C402.2.1
[IN20]1
Roof assembly meets minimal thermal resistance installed between roof framing or in a continuous fashion on the roof assembly as stipulated in Table C402.1.3. Requirements for above deck insulation, minimum thickness, suspended ceilings, staggered joints and skylight curbs will be met.
Complies
Does Not Comply
Not Observable
Not Applicable
C402.2.3
[IN8]2
Installed floor insulation type and R-value consistent with insulation specifications reported in plans and COMcheck reports.
Complies
Does Not Comply
Not Observable
Not Applicable
See the Envelope Assemblies table for values
C402.2.6
[IN18]3
Radiant panels and associated components, designed for heat transfer from the panel surfaces to the occupants or indoor space are insulated with a minimum of R-3.5.
Complies
Does Not Comply
Not Observable
Not Applicable
C105 [IN2]1 Installed roof insulation type and R-value consistent with insulation specifications reported in plans and COMcheck reports. For some ceiling systems, verification may need to occur during Framing Inspection.
Complies
Does Not Comply
Not Observable
Not Applicable
See the Envelope Assemblies table for values
C402.5.1.1
[IN1]1
All sources of air leakage in the building thermal envelope are sealed, caulked, gasketed, weather stripped or wrapped with moisture vapor-permeable wrapping material to minimize air leakage.
Complies
Does Not Comply
Not Observable
Not Applicable
C303.2
[IN7]1
Above-grade wall insulation installed per manufacturer’s instructions.
Complies
Does Not Comply
Not Observable
Not Applicable
C105 [IN6]1 Installed above-grade wall insulation type and R-value consistent with insulation specifications reported in plans and COMcheck reports.
Complies
Does Not Comply
Not Observable
Not Applicable
See the Envelope Assemblies table for values
Report Title: Washburn Addition Report Date: May 29, 2026, 09:54 AM (PDT) 16 of 17
Final Inspection
Section # & Req.ID Final Inspection Complies? Comments/Assumptions
C303.3, C408.2.5.2
[FI17]3
Furnished O&M instructions for systems and equipment to the building owner or designated representative.
Complies
Does Not Comply
Not Observable
Not Applicable
C405.5.1
[FI19]1
Exterior lighting power is consistent with what is shown on the approved lighting plans, demonstrating proposed watts are less than or equal to allowed watts.
Complies
Does Not Comply
Not Observable
Not Applicable
See the Exterior Lighting fixture schedule for values
C401.3
[FI58]1
A thermal envelope certificate will be supplied and completed by an approved third party.
Complies
Does Not Comply
Not Observable
Not Applicable
C408.1.1
[FI57]1
Building operations and maintenance documents will be provided to the owner.
Documents will cover manufacturers' information, specifications, programming procedures and means of illustrating to owner how building, equipment and systems are intended to be installed, maintained, and operated.
Complies
Does Not Comply
Not Observable
Not Applicable
C408.2.5
[FI16]3
Furnished as-built drawings for electric power systems within 90 days of system acceptance.
Complies
Does Not Comply
Not Observable
Not Applicable
C408.3
[FI33]1
Lighting systems have been tested to ensure proper calibration, adjustment, programming, and operation.
Complies
Does Not Comply
Not Observable
Not Applicable
C402.5.10
[FI26]3
Recessed luminaires in thermal envelope to limit infiltration and be IC rated and labeled.
Seal between interior finish and luminaire housing.
Complies
Does Not Comply
Not Observable
Not Applicable
C402.5.11
[FI59]1
Operable openings > 40 ft2 will be interlocked with heating and cooling systems to setback setpoint temperatures within 10 minutes of opening.
Complies
Does Not Comply
Not Observable
Not Applicable
C402.5.8
[FI37]1
Weatherseals installed on all loading dock cargo door openings and provide direct contact along the top and sides of vehicles parked in the doorway.
Complies
Does Not Comply
Not Observable
Not Applicable
Report Title: Washburn Addition Report Date: May 29, 2026, 09:54 AM (PDT) 17 of 17