MECHANICAL ABBREVIATIONSSYMBOL DESCRIPTIONSYMBOL DESCRIPTIONDESCRIPTIONSYMBOL
HWR HEATING WATER RETURN
HEATING WATER SUPPLYHWS
CWR CHILLED WATER RETURN
CHILLED WATER SUPPLYCWS
SIZE (IN)
ROUND DUCT AND PIPE:
DIMENSIONS
(INxIN)
RECTANGULAR DUCT:
DEVICE AIRFLOW (CFM)
DIFFUSERS, REGISTERS, AND GRILLES:
DEVICE TYPE, REFER TO
SCHEDULE FOR FACE
AND INLET / OUTLET SIZE
MECHANICAL CALLOUTS:
90° ELBOW DOWN
45° RECTANGULAR BEND
END CAPS
90° ELBOW UP
DUCT SECTION, ROUND
ACCESS
DAMPER:
DUCT SECTION, EXHAUST
DUCT SECTION, RETURN
DUCT SECTION, SUPPLY
FLEXIBLE DUCT
EXPANSION JOINT
REDUCED PRESSURE
BACKFLOW PREVENTION
DEVICE
DIRECTION OF FLOW
PIPE GUIDE
FSD - FIRE AND SMOKE DAMPER
FD - FIRE DAMPER
SD - SMOKE DAMPER
BD - BACK DRAFT DAMPER
VD OR NO LABEL - MAN. VOL.
DAMPER
RD -
OPEN FUNNEL DRAIN /
FLOOR DRAIN
PIPE ANCHOR
PNEUMATIC VALVE
OPERATOR
ELECTRIC VALVE
OPERATOR
ANGLE VALVE
GLOBE VALVE
THREE-WAY VALVE
BUTTERFLY VALVE
GATE VALVE
BALL VALVE
RELIEF OR SAFETY VALVE
PLUG VALVE
CHECK VALVE
PRESSURE REDUCING
VALVE
STRAINER
UNION
REDUCER
PIPE CAP
TOP CONNECTION
SIDE CONNECTION
BOTTOM CONNECTION
TEE DOWN
TEE UP
RISE OR DROP
RISER UP (ELBOW)
RISER DOWN (ELBOW)
BLIND FLANGE
ROUND PRESSURE TAP
ROUND LOW-LOSS TEE
* LOCATE OPPOSED BLADE MANUALLY
OPERATED BALANCING DAMPER 3X
DUCT DEPTHS DOWNSTREAM FROM
ELBOWS
TEST PLUG
PRESSURE GAUGE
AUTOMATIC AIR VENT
THERMAL WELL
CALIBRATED MANUAL
BALANCING VALVE
TEMPERATURE
PRESSURE RELIEF VALVE
GENERAL PROJECT NOTES
FCV AUTOMATIC FLOW CONTROL
VALVE
VALVE WITH LOCK SHIELD
ON HANDLE
HWRR HEATING WATER REVERSE RETURN
CWRR CHILLED WATER REVERSE RETURN
ABV - ABOVE
AC - AIR CONDITIONING UNIT
ACCU - AIR COOLED
CONDENSING UNIT
ADJ - ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AFMD - AIRFLOW
MONITORING DEVICE
AHU - AIR HANDLING UNIT
AMP - AMPERE
ANSI - AMERICAN NATIONAL
STANDARDS INSTITUTE
APD - AIR PRESSURE DROP
APPROX - APPROXIMATE
ARCH - ARCHITECT,
ARCHITECTURAL
AS - AIR SEPARATOR
ASHRAE -AMERICAN SOCIETY OF
HEATING, REFRIGERATION,
AND AIR CONDITIONING
ENGINEERS
ASI - ARCHITECT'S
SUPPLEMENTAL
INSTRUCTION
ASME - AMERICAN SOCIETY OF
MECHANICAL ENGINEERS
ASTM - AMERICAN SOCIETY FOR
TESTING AND MATERIALS
AT/FP - ANTI TERRORISM /
FORCE PROTECTION
AUTO - AUTOMATIC
AUX - AUXILIARY
AVG - AVERAGE
BDD - BACKDRAFT DAMPER
BFP - BACKFLOW PREVENTER
BAL - BALANCE
BFF - BELOW FINISHED FLOOR
BHP - BRAKE HORSEPOWER
BLDG - BUILDING
BLR - BOILER
BOT - BOTTOM
BP - BOTTOM OF PIPE
BTU - BRITISH THERMAL UNIT
BTUH - BRITISH THERMAL
UNIT PER HOUR
BYP - BYPASS
CA COMPRESSED AIR
CAP - CAPACITY
CD - CONDENSATE DRAIN
CERT - CERTIFY
CFM - CUBIC FEET PER MINUTE
CF - CHEMICAL FEED
CHEM - CHEMICAL
CHL - CHILLER
CL - CENTER LINE
CLASS - CLASSIFICATION
CLG - CEILING
CO - CLEANOUT
COL - COLUMN
COMM - COMMUNICATION
COMP - COMPRESSOR
CONC - CONCRETE
CONT - CONTINUE,
CONTINUOUS
CONN - CONNECT
COORD -COORDINATE
CORR - CORRIDOR
CTR - CENTER
CTRL - CONTROL
CU - CUBIC
CW - COLD WATER PIPING
CWS - CHILLED WATER SUPPLY
CWR - CHILLED WATER RETURN
CWP - CHILLED WATER PUMP
D - DRAIN
dB - DECIBEL
DB - DRY BULB
DDC - DIRECT DIGITAL
CONTROL
DEG (°) -DEGREE
DEPT - DEPARTMENT
DET - DETAIL
DIA (Ø) - DIAMETER
DIAG - DIAGRAM,
DIAGRAMMATIC
DIM - DIMENSION
DIV - DIVISION
DN - DOWN
DP - DEW POINT
DPS - DIFFERENTIAL
PRESSURE SENSOR
DPT - DIFFERENTIAL PRES
TRANSMITTER
DWG - DRAWING
DWH - DOMESTIC WATER
HEATER
DWV - DRAIN, WASTE, AND
VENT
E - EAST
EA - EACH
EA - EXHAUST AIR
EAT - ENTERING AIR TEMP
EC - EVAPORATIVE COOLER
ECON -ECONOMIZER
EER - ENERGY EFFICIENCY
RATIO
EF - EXHAUST FAN
EFF - EFFICIENCY
EL - ELEVATION
ELL - ELBOW
ELEC - ELECTRIC, ELECTRICAL
EMER -EMERGENCY
ESP - EXTERNAL STATIC PRES
EST - ESTIMATE
ET - EXPANSION TANK
ETC - ET CETRA (AND SO
FORTH)
EVAP - EVAPORATE
EWT - ENTERING WATER
TEMPERATURE
EX - EXAMPLE
EXH - EXHAUST
EXT - EXTERIOR, EXTERNAL
F - FAHRENHEIT
FA - FIRE ALARM
FF - FINISHED FLOOR
FCU - FAN COIL UNIT
FCV - FLOW CONTROL VALVE
FD - FIRE DAMPER
FFA - FROM FLOOR ABOVE
FFB - FROM FLOOR BELOW
FIN - FINISH
FLA - FULL LOAD AMPS
FLEX - FLEXIBLE
FLR - FLOOR
FP - FIRE PROTECTION
FPM - FEET PER MINUTE
FPS - FEET PER SECOND
FREQ -FREQUENCY
FSS - FLOW SENSING SWITCH
FSTAT-FREEZESTAT
FT - FOOT, FEET
G - GAS , GAUGE
GA - GAGE
GAL - GALLON
GALV - GALVANIZED
GFS - GLYCOL FEED SYSTEM
GOVT -GOVERNMENT
GPH - GALLONS PER HOUR
GPM - GALLONS PER MINUTE
GRV - GRAVITY ROOF
VENTILATOR
HB - HOSE BIBB
HC - HEATING COIL
HCU - HEAT AND CURE UNIT
HORIZ -HORIZONTAL
HP - HORSEPOWER
HR - HOUR
HSKPG- HOUSEKEEPING
HT - HEIGHT
HVAC -HEATING, VENTILATION,
AND AIR CONDITIONING
HFD - HEATING, VENTILATING,
AND DEHUMIDIFYING UNIT
HVU - HEATING AND
VENTILATING UNIT
HWP - HEATING WATER PUMP
Hz - HERTZ
I/O - INPUT/OUTPUT
IAH - INTAKE AIR HOOD
ID - INSIDE DIAMETER
IFR - IN FLOOR RADIANT HEAT
IH - INTAKE HOOD
IN - INCHES
IN WC -INCHES WATER COLUMN
INFO - INFORMATION
IPLV - INTERVAL PART LOAD
VALUE
IPS - IRON PIPE SIZE
ISO - ISOMETRIC
k - KILO
K - KELVIN
K - THOUSAND
kg - KILOGRAM kPa - KILOPASCAL kW - KILOWATT kWh - KILOWATT HOUR
L - LITER
L/s - LITERS PER SECOND
LEL - LOWER EXPLOSIVE LIMIT
LPM - LITRES PER MINUTE
LAT - LEAVING AIR TEMP
LBS - POUNDS
LF - LINEAR FEET (FOOT)
LKR - LOCKER
LRA - LOCKED ROTOR AMPS
LV - LOUVER
LVR - LOUVER
m - METER
MAINT -MAINTENANCE
MAN - MANUAL
MATL - MATERIAL
MAU - MAKE UP AIR UNIT
MAX - MAXIMUM
MBH - THOUSAND BTU PER HOUR
MCA - MINIMUM CIRCUIT AMPS
MD - MANUAL DAMPER
MED - MEDIUM
MECH - MECHANICAL
MEZZ - MEZZANINE
MFG - MANUFACTURING
MFR - MANUFACTURER
MIN - MINIMUM
MISC - MISCELLANEOUS
mm - MILLIMETER
MOD - MODIFY
ms - MILLISECOND
MTD - MOUNTED
MULT - MULTIPLE
mW - MILLIWATT
N - NORTH
NA - NOT APPLICABLE
NAT - NATURAL
NC - NORMALLY CLOSED
NC - NOISE CRITERIA
NCS - NATIONAL CAD STANDARD
NEG - NEGATIVE
NIC - NOT IN CONTRACT
NO - NORMALLY OPEN
NO - NUMBER
NOM - NOMINAL
NTS - NOT TO SCALE
O - OXYGEN
OA - OUTSIDE AIR
OAU - OUTDOOR AIR UNIT
OBD - OPPOSED BLADE DAMPER
OC - ON CENTER
OD - OUTSIDE DIAMETER
OPP - OPPOSITE
OPT - OPTIONAL
ORIG - ORIGINAL
OUT - OUTLET
OZ - OUNCE
P - PUMP
PBU - PAINT BOOTH UNIT
PCT - PERCENT
PD - PRESSURE DROP
OR DIFFERENCE
PH ( ) -PHASE
PKG - PACKAGE
PLBG - PLUMBING
PN - PART NUMBER
PNEU - PNEUMATIC
PPM - PARTS PER MILLION
PRI - PRIMARY
PRV - PRES REDUCING
VALVE
PS - PRESSURE SWITCH
PSI - POUNDS PER SQUARE
INCH
PSIA - POUNDS PER SQUARE
INCH ABSOLUTE
PSIG - POUNDS PER SQUARE
INCH GAUGE
PT - POINT
PWR - POWER
PVC - POLYVINYL CHLORIDE
QA - QUALITY ASSURANCE
QTY - QUANTITY
R - THERMAL RESISTANCE
RA - RETURN AIR
RAF - RETURN AIR FAN
REF - REFERENCE
REQ'D - REQUIRED
RET - RETURN
REV - REVISE, REVISION
RF - RETURN FAN
RFI - REQUEST FOR
INFORMATION
RFP - REQUEST FOR
PROPOSAL
RH - RELATIVE HUMIDITY
RM - ROOM
RPBP - REDUCED PRESSURE
BACKFLOW PREVENTER
RPM - REVOLUTIONS PER
MINUTE
RPS - REVOLUTIONS
PER SECOND
RV - RELIEF VALVE
S - SOUTH
S - SWITCH
SA - SUPPLY AIR
SCHED- SCHEDULE
SCHEM- SCHEMATIC
SD - SMOKE DAMPER
SECT - SECTION
SF - SQUARE FEET (FOOT)
SF - SUPPLY FAN
SG - STEAM GENERATOR
SH - STEAM HUMIDIFIER
SPEC - SPECIFICATION
SQ - SQUARE
STD - STANDARD
STOR - STORAGE
STRUCT-STRUCTURAL
SW - SWITCH
SYS - SYSTEM
T&P - TEMPERATURE AND
PRESSURE
TD - TEMPERATURE
DIFFERENCE
TDH - TOTAL DYNAMIC HEAD
TECH - TECHNICAL
TEMP - TEMPERATURE
THRU - THROUGH
TK - TANK
TP - TOTAL PRESSURE
TSTAT - THERMOSTAT
TYP - TYPICAL
UH - UNIT HEATER
UL - UNDERWRITERS
LABORATORIES
UNO - UNLESS NOTED
OTHERWISE
V - VOLT
VAR - VARIES
VAV - VARIABLE AIR VOLUME
VD - VOLUME DAMPER
VEL - VELOCITY
VENT - VENTILATION,
VENTILATOR
VERT - VERTICAL
VF - VENTILATION FAN
VFD - VARIABLE
FREQUENCY DRIVE
VOL - VOLUME
VP - VELOCITY PRESSURE
VS - VENT STACK
W - WATT
W - WEST
W/ - WITH
W/O - WITHOUT
WB - WET BULB
WC - WATER COLUMN
WG - WATER GAGE
WH - WATER HEATER
WT - WEIGHT
YD - YARD
YH - YARD HYDRANT
YR - YEAR
T - SPACE TEMPERATURE-
SENSOR/TRANSMITTER
PB - PUSH BUTTON
C - A -
TEMPERATURE GAUGE
OR THERMOMETER
COMBINATION VALVE
INCLUDING ISOLATION VALVE,
STRAINER, DIELECTRIC UNION,
P/T PORTS AND DRAIN VALVE
COMBINATION VALVE
INCLUDING DIELECTRIC UNION,
AIR VENT AND P/T PORT
COMBINATION VALVE
INCLUDING ISOLATION VALVE,
UNION P/T PORT, AND
AUTOMATIC FLOW CONTROL
VALVE
SIDE WALL SUPPLY GRILLE OR
REGISTER, REVERSE ARROW
INDICATES EXHAUST OR RETURN
CEILING DIFFUSER SQUARE
PATTERN. NO ARROWS INDICATE
4-WAY AIR PATTERN
90° RECTANGULAR ELBOW UP
WITH TURNING VANES
90° RECTANGULAR ELBOW
DOWN WITH TURNING VANES
90° RECTANGULAR ELBOW
HORIZ. PROVIDE TURNING
VANES IN ALL RECTANGULAR
90 ° ELBOWS
90° ROUND ELBOW,
HORIZONTAL
45° RECTANGULAR BEND, 1-
1/2 RADIUS
45 ° ROUND BEND, 1-1/2
RADIUS
RECTANGULAR TEE,
DIVERGING, MAIN AND TAP
(45° ENTRY) TYPICAL FOR
ALL SUPPLY
RECTANGULAR TAPS
STRAIGHT SIDED BRANCH
SPLIT. TRANSITION TO
FULL SIZE BEFORE
ELBOW.
* WITH TURNING VANES
BRANCH SPLIT. TRANSITION
TO FULL SIZE BEFORE
ELBOW. * WITH TURNING
VANES
WYE SPLIT. TRANSITION TO
FULL SIZE BEFORE ELBOW.
* WITH TURNING VANES
THREE WAY SPLIT.
TRANSITION TO FULL SIZE
BEFORE ELBOW.* WITH
TURNING VANES
FS - FLOW SWITCH
T - TEMP. SENSOR /
TRANSMITTER
P - PRESS. SENSOR/TRANS.
PS - PRESSURE SWITCH
OA -
DPS -
ESS -
CP -
MANUAL AIR VENT
RETURN/TRANSFER/EXHAUST
GRILLE
12Ø
12x12
3" MIN.
VD
VD
VD
VD
VD
VD
VD
VD
VD
TW
AV
P
T
MAV
A-1
NOTE:
1. NOT ALL SYMBOLS AND ABBREVIATIONS SHOWN IN THIS SHEET ARE USED ON
THIS PROJECT.
DUCT PRESSURE
CLASSIFICATION
CONDENSATE DRAINCD
FCV
CARBON DIOXIDE SENSOR
AIR QUALITY SENSOR
OUTDOOR AIR
TEMPERATURE SENSOR /
TRANSMITTER
DIFFERENTIAL PRESSURE
SWITCH
EMERGENCY SHUTDOWN
SWITCH
CONTROL PANEL
BAROMETRIC RELIEF
DAMPER
PRES - PRESSURE
A. MECHANICAL PLANS AND SECTIONS ARE INTENDED
TO ILLUSTRATE THE SCOPE OF WORK
ACCURATELY, HOWEVER THEY ARE STILL
DIAGRAMMATIC IN NATURE. REPRESENTATIONS OF
EQUIPMENT, VALVES, FITTINGS, ETC. SHOWN ON
THESE DRAWINGS MAY NOT REFLECT THE LOOK
OR SIZE OF THE ACTUAL MATERIALS SPECIFIED.
B. MECHANICAL DRAWINGS DO NOT SHOW ALL MINOR
ITEMS THAT MUST BE INSTALLED. THE
CONTRACTOR SHALL PROVIDE ALL LABOR AND
MATERIALS REQUIRED FOR A FULLY FUNCTIONING
SYSTEM COMPLIANT WITH ALL APPLICABLE CODES
AND LAWS.
C. PLAN AND SECTION DRAWINGS DO NOT SHOW ALL
REQUIRED BRANCH PIPING OR VALVES AND
GAUGES. REFER TO FLOW DIAGRAMS, DETAILS
AND PROJECT SPECIFICATIONS FOR REQUIRED
PIPING, VALVES AND GAUGES.
D. SECTION DRAWINGS DO NOT SHOW ALL REQUIRED
WORK IN THE AREA THEY ARE CUT. SECTION
DRAWINGS ARE PROVIDED TO ILLUSTRATE ONLY
CERTAIN CONDITIONS THAT MAY BE TOO
CONGESTED TO ILLUSTRATE IN A PLAN VIEW.
E. MECHANICAL DRAWINGS DO NOT SHOW ALL
REQUIRED OFFSETS IN PIPING AND DUCTWORK
REQUIRED FOR INSTALLATION COORDINATED WITH
ALL OTHER DISCIPLINES SUCH AS STRUCTURAL
STEEL. THE CONTRACTOR SHALL PROVIDE
ELBOWS IN PIPING AND DUCTWORK, ONLY WHEN
ABSOLUTELY REQUIRED, TO AVOID CONFLICT WITH
OTHER MECHANICAL COMPONENTS OR WORK OF
OTHER TRADES. OFFSETS SHALL USE ELBOWS OF
LEAST DEGREE TURN AS POSSIBLE.
F. ALL DUCT SIZES INDICATED REPRESENT INSIDE
CLEAR DIMENSIONS. CONTRACTOR SHALL ADJUST
SHEET METAL SIZE TO ACCOUNT FOR LINER
THICKNESS WHEN LINER IS REQUIRED PER THE
CONTRACT DOCUMENTS.
G. ALL EXPOSED PIPING NOT REQUIRED BY THE
SPECIFICATIONS TO BE INSULATED SHALL BE
PAINTED PER THE SPECIFICATION SECTION
"PAINTING".
H. MODIFY ROUTING OF PIPING AT EQUIPMENT
CONNECTION POINTS FROM THAT SHOWN TO
MATCH ACTUAL LOCATION OF CONNECTION POINTS
FOR SPECIFIC EQUIPMENT PURCHASED. CONNECT
ALL EQUIPMENT IN ACCORDANCE WITH EQUIPMENT
MANUFACTURER’S INSTRUCTIONS.
I. PIPING, DUCTWORK AND EQUIPMENT HANGERS
AND SUPPORTS SHALL NOT INTERFERE WITH
OPERATION AND MAINTENANCE OF EQUIPMENT.
J. EVERY PIECE OF FLOOR OR GRADE MOUNTED
HVAC OR PLUMBING EQUIPMENT SHALL HAVE A 6
INCH TALL CONCRETE HOUSEKEEPING PAD. THIS
APPLIES AS WELL TO EQUIPMENT SUPPORTED BY
STEEL STRUCTURE OR LEGS. ALL HOUSEKEEPING
PADS SHALL EXTEND BEYOND THE OUTER
PERIMETER OF THE EQUIPMENT, SUPPORT
STRUCTURE OR LEGS BY AT LEAST 3 INCHES.
K. ALL PIPE CAPS INDICATED ON CONDENSATE DRAIN
LINES SHALL BE THREADED PIPE CAPS OR PLUGS
TO SERVE AS PIPE CLEANOUTS.
CONNECT TO EXISTING
REMOVE BEYOND /
BETWEEN POINTS
MD - MOTORIZED DAMPER
PIPE FLEXIBLE CONNECTION
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
GARY W.
JAMES
16166
O K L A H O M A
LI
C
EN
S E
D
PRO FES S IO NA L
ENG
IN
EER
/2
0/
8:
:2
AM
C :\U se rs
\A
JA
\D oc um en ts \6
_M ec h_
AJ
A.
rv t
LEGEND & ABBREVIATIONS
AJA
BAS
MJA 351
M-001
M-001
DN
DN
DN
DN
DN
T
9.9
9.9
11.3
11.3
12.6
12.6
13.1
13.1
13.6
13.6
16.1
16.1
P.3 P.3
P.2 P.2
P.1 P.1
P P
N N
M M
L.6 L.6
L.1 L.1
L L
K.6 K.6
K K
J.3 J.3
J J
H H
G.9 G.9
01070104
MATCH LINE
SEE 1/M-102
M
AT
C H
LI
N
E S
EE
1/
M -1
ACB-01
ACB-02
A-1
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-1
18"x12" 10"x10"
8"x10"
12"x12"
14"x12"
VB1-12
A-2
A-2
A-2 160A-2
A-2
A-2
A-1
A-1
A-2
A-2
A-2
10"x12"14"x12" 20"x12"
VB1-11
A-1
A-1
A-1
A-1
A-1
A-1
A-1
A-1
A-1
VB1-10
16"x10" 10"x10"
20"x10"
8"x8" 8"x8"
8"x8"
6"x8"6"x8"6"x8"
6"x8" 6"x8"
6"x8"
VB1-13
20"x12" 14"x12" 12"x12" 8"x8"
12"x12" 12"x12"
10"x10"10"x10"
6"x10" 6"x10"A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-1
12"x10"14"x14"
18"x14"
A-2
A-2
A-2
A-2
A-2
A-2
VB1-14VB1-15
A-2
A-2
6"/12"
10"/12"
12"/12"
VB1-16
A-2
A-2
A-2
A-2
A-2
10"x10"
VB1-17
22"x14" 20"x12"
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
14"x10"
8"x10"
6"x10"
8"x10"8"x10"
8"x10"
6"x10"6"x10"
8"x10"
8"x10"
VB1-09
A-1
VVB-02
"x
"x
"x
"x
"x
"x
"x
"x
VB1-18
VB1-04
A-2
A-2
A-2
A-2
A-2
20"x12"
20"x12"
B-2
B-2 720 B-2
B-1
B-1
B-2
B-2
B-2
C
B-2
D
B
C
C
C
C
C
C
C
VB1-19 10"x10"
8"x10"
8"x10"8"x10"
10"x10" 10"x10"
6"x10" 8"x10"
6"x10"
D-1
D-1
VB1-20
A-2
A-2
"x
B-2
FCUB-1
0108E
B-1
C
C
C-1
B-1
8"x8" 21"x13"
12"ø
10"ø
14"ø
16"ø
16"ø
16"ø
16"ø
16"ø
16"ø
10"ø UP TO
EFB-01 IN
LANDSCAPE
AREA
A-2
2B-2
FD
A
FD
10"x10"
10"ø 10"ø
BURIED DUCT
0108B 0108C 0108D
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
GARY W.
JAMES
16166
O K L A H O M A
LI
C
EN
S E
D
PRO FES S IO NA L
ENG
IN
EER
/2
0/
8:
:1
AM
C :\U se rs
\A
JA
\D oc um en ts \6
_M ec h_
AJ
A.
rv t
BASEMENT MECHANICAL PLAN - AREA 1
RRS
BAS
MJA 352
M-101
M-101SCALE: 1/8" = 1'-0"
1 BASEMENT MECHANICAL PLAN - AREA 1
0 4' 8' 16'
1/8" = 1'-0"
N
KEYPLAN
GENERAL NOTES
SHEET KEYNOTES
BASEMENT AREA 1
Number Name
0101 RR WOMEN
0103 BREAK ROOM
0104 CONFERENCE ROOM
0105 CORRIDOR
0106 OPEN OFFICE
0107 CORRIDOR
0108 OPEN OFFICE
0108A PRIVATE OFFICE
0108B PHONE ROOM
0108C PHONE ROOM
0108D PHONE ROOM
0108E CONFERENCE ROOM
0112 ELEC.
0113 COMM.
0115 COMPUTER WORK ROOM
A. REFER TO M-001 FOR GENERAL NOTES FOR ALL
HVAC SHEETS.
B. PROVIDE MANUAL BALANCING DAMPERS IN ALL
SUPPLY AND EXHAUST DUCT RUNOUTS TO
DIFFUSERS AND REGISTERS.
C. DUCT RUNOUT SIZES TO AIR DISTRIBUTION DEVICES
SHALL BE THE SAME AS DEVICE NECK SIZE UNLESS
NOTED OTHERWISE.
D. DUCT RUNOUT SIZES TO THE VAV BOXES SHALL
BE THE SAME SIZE AS VAV BOX INLET SIZE UNLESS
NOTED OTHERWISE.
E. ALL DUCTWORK JOINTS AND SEAMS SHALL MEET
SEAL CLASS A.
F. THE PROJECT IS TO BE COMPLETED IN PHASES.
REFER TO ARCHITECTURAL FOR PHASING.
1. PROVIDE IN PHASE 2.
UP
DN
DN
9.9
9.9
11.3
11.3
12.6
12.6
13.1
13.1
13.6
13.6
16.1
16.1
G G
F F
E E
D D
C C
B B
A A
0301 0304
MATCH LINE
SEE 1/M-101
M
AT
C H
LI
N
E S
EE
1/
M -1
ACB-03
A-2
A-2
A-2
6"x10"6"x10"6"x10"
A-1
A-1
VB1-08
A-1
A-1
A-1
A-1
A-1
A-1
A-1
A-1
8"x8"12"x10"16"x10"18"x10"
20"x12"
"x
"x
"x
36"x26"
"x
36"x26"
VB1-05
A-2
A-1
A-1
A-1
A-1
A-1
14"x10" 12"x10"
8"x10"
"x
20"x14"
VB1-07
16"x12"
14"x12"
12"x12"
12"x10"
8"x10"
VB1-06
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2 175 A-1
50 A-1
A-2
VB1-03
12"x10"
8"x10" 6"x10"
VB1-02
10"x10"
8"x10"
A-1
A-1
A-2
A-2
A-1
A-1
A-1
A-1
VVB-01
VB1-01
12"x12"
10"x10"
B-2
B-1
B-1
B-2
B-2
B-2
C
A
0203D
0203C
B
B-1
B-1
B-1
B-1
"x
C
B-1
A
B-1
B-1
B-1
B-1
AA
VB1-22
VB1-21
10"x10"
"x
C
FCUB-2
A-2
C-1
C-1
16"ø16"ø
"ø
"ø
10"ø
"ø
"ø
A-1
EXISTING
CONDENSING
UNITS
EXISTING
A.C.FD
FD
"x
8"
0203A 0203B
0203E
8x1010x1012x1014x1218x12 20x12
16"
A-1
A-1
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
GARY W.
JAMES
16166
O K L A H O M A
LI
C
EN
S E
D
PRO FES S IO NA L
ENG
IN
EER
/2
0/
8:
:3
AM
C :\U se rs
\A
JA
\D oc um en ts \6
_M ec h_
AJ
A.
rv t
BASEMENT MECHANICAL PLAN - AREA 2
RRS
BAS
MJA 353
M-102
M-102
SCALE: 1/8" = 1'-0"
1 BASEMENT MECHANICAL PLAN - AREA 2
0 4' 8' 16'
1/8" = 1'-0"
N
KEYPLAN
GENERAL NOTES
SHEET KEYNOTES
BASEMENT AREA 2
Number Name
0201 CORRIDOR
0202 CORRIDOR
0203 OPEN OFFICE
0203A PHONE ROOM
0203B PHONE ROOM
0203C PRIVATE OFFICE
0203D PRIVATE OFFICE
0203E CONFERENCE ROOM
0204 ELEV. EQUIP
0205 SERVICE ELEV
0206 CORRIDOR
0207 CORRIDOR
0208 EXISTING LOADING DOCK
0209 EXISTING STAIR
0210 EXISTING LAB
0211 STORAGE
0212 RECORD STORAGE
0213 CORR.
0214 STORAGE
0215 STORAGE
0216 EXISTING STORAGE
A. REFER TO M-001 FOR GENERAL NOTES FOR ALL
HVAC SHEETS.
B. PROVIDE MANUAL BALANCING DAMPERS IN ALL
SUPPLY AND EXHAUST DUCT RUNOUTS TO
DIFFUSERS AND REGISTERS.
C. DUCT RUNOUT SIZES TO AIR DISTRIBUTION DEVICES
SHALL BE THE SAME AS DEVICE NECK SIZE UNLESS
NOTED OTHERWISE.
D. DUCT RUNOUT SIZES TO THE VAV BOXES SHALL
BE THE SAME SIZE AS VAV BOX INLET SIZE UNLESS
NOTED OTHERWISE.
E. ALL DUCTWORK JOINTS AND SEAMS SHALL MEET
SEAL CLASS A.
F. THE PROJECT IS TO BE COMPLETED IN PHASES.
REFER TO ARCHITECTURAL FOR PHASING.
NOT IN SCOPE OF WORK
EXCEPT FOR CLEANING
OF DUCTWORK AND
BALANCING CFM
G G
F F
E E
D D
C C
B B
A A
03220315
0303 0301
MATCH LINE
SEE 1/M-104
M
AT
C H
LI
N
E S
EE
1/
M -1
ACB-04
0212-2
ACB-05
70"x26"
A-2
A-2
A-2
A-1
A-1
A-1
6"x10"
8"x10"
10"x10"
14"x10" 12"x10"
8"x10"
VB1-02
10"x10"A-1
A-1
A-1
A-2
8"x10"
VVB-03
A-2
10"x10"
80"x20"
B-2
B-1
C
B-1
B-1
ACB-06
VVB2-08VVB2-07
VVB2-01
VVB2-06
VVB2-04VVB2-03
C-1
C-1
C-1
C-1
10"x10"
8"x8"
EFB-02
"ø
325 CFM 320 CFM
320 CFM
325 CFM
320 CFM
320 CFM315
CFM
CFM
CFM
CFM
CFM
C-1
SA
FD
M-403
325 CFM 320 CFM 320 CFM
A-1
14"x6" 14"x8" 16"x10"
A-2
18"x10" 14"x10" 12"x8"
10"x8"
A-1
6"x10"B-2
B-1
B-1
0407-1
FD
FD
FD
FD
FD
FD
O.A.
O.A.
"x
60"x34"
0" x3 4"
B-1
AHUB-02 AHUB-01
0322A
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
GARY W.
JAMES
16166
O K L A H O M A
LI
C
EN
S E
D
PRO FES S IO NA L
ENG
IN
EER
/2
0/
8:
:4
AM
C :\U se rs
\A
JA
\D oc um en ts \6
_M ec h_
AJ
A.
rv t
BASEMENT MECHANICAL PLAN - AREA 3
RRS
BAS
MJA 354
M-103
M-103
SCALE: 1/8" = 1'-0"
1 BASEMENT MECHANICAL PLAN - AREA 3 0 4' 8' 16'
1/8" = 1'-0"
N
KEYPLAN
GENERAL NOTES
SHEET KEYNOTES
BASEMENT AREA 3
Number Name
0301 RR WOMEN
0303 RR MEN
0304 JAN.
0305 EXISTING TEL/COM
0306 CORR.
0308 EXISTING BATTERY BACK UP
0309 EXISTING ELEC
0310 BREAK ROOM
0311 EXISTING BOILER
0312 ELEC VAULT
0313 AREA-WAY
0314 EXISTING SPRAY ROOM
0315 EXISTING ELEC
0316 RR WOMEN
0318 SECURE STORAGE
0319 SECURE SHREDDER
0320 CORRIDOR
0321 FOLDER/ INSERTER
0322 STORAGE
0322A SYSTEMS
0322B JAN.
A. REFER TO M-001 FOR GENERAL NOTES FOR ALL
HVAC SHEETS.
B. PROVIDE MANUAL BALANCING DAMPERS IN ALL
SUPPLY AND EXHAUST DUCT RUNOUTS TO
DIFFUSERS AND REGISTERS.
C. DUCT RUNOUT SIZES TO AIR DISTRIBUTION DEVICES
SHALL BE THE SAME AS DEVICE NECK SIZE UNLESS
NOTED OTHERWISE.
D. DUCT RUNOUT SIZES TO THE VAV BOXES SHALL
BE THE SAME SIZE AS VAV BOX INLET SIZE UNLESS
NOTED OTHERWISE.
E. ALL DUCTWORK JOINTS AND SEAMS SHALL MEET
SEAL CLASS A.
F. THE PROJECT IS TO BE COMPLETED IN PHASES.
REFER TO ARCHITECTURAL FOR PHASING.
NOT IN SCOPE OF WORK
EXCEPT FOR CLEANING
OF DUCTWORK AND
BALANCING CFM
1. CONTRACTOR SHALL FIELD VERIFY THE QUANTITY
OF EXISTING SUPPLY AIR DISTRIBUTION DEVICES IN
THIS EXISTING ROOM. THE AIR QUANTITY INDICATED
IS THE TOTAL SUPPLY AIR FLOW FOR THIS ROOM AND
SHALL BE DIVIDED EQUALLY BETWEEN THE SUPPLY
AIR DISTRIBUTION DEVICES IN THIS ROOM. EACH
SUPPLY AIR DISTRUBUTION DEVICE SHALL BE
BALANCED TO THE REQUIRED SUPPLY AIR FLOW.
PROVIDE MANUAL VOLUME DAMPER FOR EACH
DEVICE IF REQUIRED.
2. DUCT CONNECTION FOR TEMPORARY AIR HANDLING
UNIT.
3. TEMPORARY AIR HANDLING UNIT DUCT ISOLATION
DAMPER.
4. BALANCE PRINT SHOP EXISTING DIFFUSERS SERVED
BY AHUB-02 TO THE AIR QUANTITIES INDICATED.
5. CONNECT TO EXISTING RELIEF AIR LOUVER.
T
T
T
T
T
T
P.1 P.1
P P
N N
M M
L.6 L.6
L.1 L.1
L L
K.6 K.6
K K
J.3 J.3
J J
H H
G.9 G.9
0.7
0.7
0.8
0.8
0.9
0.9
0425 0427
04220421
MATCH LINE
SEE 1/M-103
M
AT
C H
LI
N
E S
EE
1/
M -1
0407-4
0415-2
VB1-15
A-2
A-2
A-2
A-2
A-2
A-2
A-2
14"x12"12"x10"10"x10"
A-1
8"x8"
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
10"x10" 16"x12"
20"x12"
12"x12"
14"x12" 16"x12"
20"x12"
B-2
C-1
C-1
B-1
B-1
8"x8"
85 CFM
85 CFM 85 CFM
250 CFM
250 CFM
320 CFM320 CFM
325 CFM 320 CFM 320 CFM
325 CFM 320 CFM 320 CFM
325 CFM 320 CFM 320 CFM
325 CFM 320 CFM 320 CFM
325 CFM 320 CFM 320 CFM
325 CFM
180 CFM
175 CFM
175 CFM 135 CFM
135 CFM 135 CFM 135 CFM
135 CFM135 CFM
110 CFM200 CFM
90 CFM
90 CFM140 CFM
150 CFM
150 CFM
150 CFM 150 CFM
150 CFM
150 CFM
75 CFM
75 CFM
100 CFM100 CFM
100 CFM
140 CFM
100 CFM100 CFM
120 CFM
75 CFM
105 CFM
105 CFM
25 CFM
75 CFM
60 CFM 60 CFM
10"ø UP TO
EFB-03 IN
LANDSCAPE
AREA C-1
C-1
2 3
90 CFM
90 CFM140 CFM140 CFM
140 CFM
140 CFM
A-1
A-1
14"x6" 14"x8" 16"x10"
10"x8"
A-1
A-2
A-1
8"x10"
105 CFM
105 CFM
B-1
B-1
B-1
5 5
10"x10"
10"ø
10"ø 10"x10"
A-2
B-1
PHASE 2FCUB-3
PHASE 2
10"ø
BURIED DUCT
45 CFM40 CFM
0 CFM
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
GARY W.
JAMES
16166
O K L A H O M A
LI
C
EN
S E
D
PRO FES S IO NA L
ENG
IN
EER
/2
0/
8:
:0
AM
C :\U se rs
\A
JA
\D oc um en ts \6
_M ec h_
AJ
A.
rv t
BASEMENT MECHANICAL PLAN - AREA 4
RRS
BAS
MJA 355
M-104
M-104
SCALE: 1/8" = 1'-0"
1 BASEMENT MECHANICAL PLAN - AREA 4
0 4' 8' 16'
1/8" = 1'-0"
N
KEYPLAN
GENERAL NOTES
SHEET KEYNOTES
BASEMENT AREA 4
Number Name
0401 RR MEN
0402 CORRIDOR
0403 WORK ROOM
0404 EXISTING OFFICE
0405 EXISTING STUDIO
0406 EXISTING OFFICE
0407 PRINT SHOP
0408 EXISTING OFFICE
0409 EXISTING CORRIDOR
0411 EXISTING STUDIO
0412 EXISTING OPEN OFFICE
0413 EXISTING OFFICE
0414 EXISTING WORK AREA
0415 EXISTING OPEN OFFICE
0416 EXISTING OFFICE
0417 EXISTING OFFICE
0418 EXISTING CORRIDOR
0419 EXISTING OFFICE
0421 EXISTING OFFICE
0422 EXISTING CONFERENCE ROOM
0423 EXISTING CIRCULATION
0425 EXISTING OFFICE
0426 EXISTING. TEL/COM
0427 EXISTING STORAGE
0428 RR MEN
A. REFER TO M-001 FOR GENERAL NOTES FOR ALL
HVAC SHEETS.
B. PROVIDE MANUAL BALANCING DAMPERS IN ALL
SUPPLY AND EXHAUST DUCT RUNOUTS TO
DIFFUSERS AND REGISTERS.
C. DUCT RUNOUT SIZES TO AIR DISTRIBUTION DEVICES
SHALL BE THE SAME AS DEVICE NECK SIZE UNLESS
NOTED OTHERWISE.
D. DUCT RUNOUT SIZES TO THE VAV BOXES SHALL
BE THE SAME SIZE AS VAV BOX INLET SIZE UNLESS
NOTED OTHERWISE.
E. ALL DUCTWORK JOINTS AND SEAMS SHALL MEET
SEAL CLASS A.
F. THE PROJECT IS TO BE COMPLETED IN PHASES.
REFER TO ARCHITECTURAL FOR PHASING.
G. PROVIDE TEMPROARY AIR HANDLING UNIT THAT
PROVIDES HEATING AND COOLING. BOTH COOLING
AND HEATING SHALL BE PROVIDED FROM THE
CONTRACTORS CHOICE OF UTILITIES. THE EXISTING
BUILDING CHILLED AND HEATING WATER SYSTEMS
SHALL NOT BE USED. CONTRACTOR SHALL LOCATE
TEMPORARY AIR HANDLING UNIT. CONTRACTOR
SHALL ROUTE AND CONNECT TEMPORARY DUCT
WORK FROM TEMPORARY AIR HANDLING UNIT TO
EXISTING DUCTWORK WHERE INDICATED.
NOT IN SCOPE OF WORK
EXCEPT FOR CLEANING
OF DUCTWORK AND
BALANCING CFM
1. CLEAN EXISTING DUCT WORK TO REMAIN WITHIN
CROSS HATCHED AREA AND IN PRINT SHOP. CLEANING
SHALL BE ACCOMPLISHED OUTSIDE OF NORMAL
BUSINESS HOURS AS DIRECTED BY THE OWNER AND
SHALL BE PERFORMED BY AN AIR SYSTEMS CLEANING
SPECIALIST.
2. DUCT CONNECTION FOR TEMPORARY AIR HANDLING
UNIT.
3. TEMPORARY AIR HANDLING UNIT DUCT ISOLATION
DAMPERS.
4. AREAS WITHIN CROSS HATCHED AREAS SHALL BE
PROVIDED WITH TEMPORARY COOLING AND HEATING
DURING CONSTRUCTION. ALL INTERRUPTIONS SHALL
OCCUR OUTSIDE OF NORMAL BUSINESS HOURS AS
DIRECTED BY THE OWNER.
5. CONTRACTOR SHALL FIELD VERIFY THE QUANTITY
OF EXISTING SUPPLY AIR DISTRIBUTION DEVICES IN
THIS EXISTING ROOM. THE AIR QUANTITIES INDICATED
IS THE TOTAL SUPPLY AIR FLOW FOR THIS ROOM AND
SHALL BE DIVIDED EQUALLY BETWEEN THE SUPPLY
AIR DISTRIBUTION DEVICES IN THIS ROOM. EACH
SUPPLY AIR DISTRUBUTION DEVICE SHALL BE
BALANCED TO THE REQUIRED SUPPLY AIR FLOW.
PROVIDE MANUAL VOLUME DAMPER FOR EACH
DEVICE IF REQUIRED.
6. NEW THERMOSTATS TO REPLACE EXISTING
THERMOSTATS IN PHASE 1.
7. BALANCE PRINT SHOP EXISTING DIFFUSERS SERVED
BY AHUB-02 TO THE AIR QUANTITIES INDICATED.
DN
DN
DN
DN
(2) F-2
8"x10"
12"x10"
V1-02
(2) A-1
(8) A-2
(8) A-2
12"x10"14"x14"14"x14"
12"x10"
V1-06
12"x10"
14"x14"14"x14"
12"x10" V1-05
10"x6"
12"x10"
10"x6"
V1-07
6"x10"
8"x10"
12"x10"8"x10"6"x10"
V1-04
(3) A-2 190 (2) A-2
8"x10"
V1-03
10"x10"12"x10"V1-08
6"x8"
VV1-01
V1-12
V1-13
A-2
A-2
A-2
10"x6"
12"x8"
8"x10"
10"x10"
12"x10"
14"x10"
12"x10"
10"x10"
8"x10"
(7) A-2
(4) A-2
(4) A-2
A-1
A-1
C-1
C-1
C-1
1108 1109
B-2
B-1
B-2
B-2
B-2
B-2
B-1
B-2
B-2
B-1
B-1
MATCH LINE
SEE 1/M-112
M
AT
C H
LI
N
E S
EE
1/
M -1
V1-01
10"x8"
V1-09
52"x20"
"x
"x
"x
16"ø10"ø
"x
16"ø
"x
10"x12"
8"x12"
B
B-2
B-1
B
B
14"ø
9.9
9.9
11.3
11.3
12.6
12.6
13.1
13.1
13.6
13.6
P.4 P.4
P.3 P.3
P.2 P.2
P.1 P.1
P P
N N
M M
L.6 L.6
L.1 L.1
L L
K.6 K.6
K K
J.3 J.3
J J
H H
G.9 G.9
60"x18"
12"ø
8"ø
10"ø
20"x18"
14"x18"
FC1-01
FC1-09
D-1
D-1
D-1
D-1
B-2
FCU1-1
ACUB-02
ACUB-01
FC1-02
1119E
1119A
A
A
"x
14"ø
16"ø
14"ø
8"ø
14"ø
8"ø
E/A
EFB-01
D-1
B-1
B-1
M-401
28"x12" 10"x12"
10"x12"
E-1
LV1-01
A-2
B-1
8X12
(2) A-2
A-1
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
GARY W.
JAMES
16166
O K L A H O M A
LI
C
EN
S E
D
PRO FES S IO NA L
ENG
IN
EER
/2
0/
8:
:1
AM
C :\U se rs
\A
JA
\D oc um en ts \6
_M ec h_
AJ
A.
rv t
FIRST FLOOR MECHANICAL PLAN - AREA
RRS
BAS
MJA 356
M-111
M-111
SCALE: 1/8" = 1'-0"
1 FIRST FLOOR MECHANICAL PLAN - AREA 1 0 4' 8' 16'
1/8" = 1'-0"
N
KEYPLAN
GENERAL NOTES
SHEET KEYNOTES
GROUND FLOOR AREA 1
Number Name
1101 VESTIBULE
1102 STAIR 1
1103 ELEV 1
1104 STORAGE
1105 ENTRYWAY
1106 LOUNGE
1107 CORRIDOR
1108 WOMENS
1109 MENS
1110 CORRIDOR
1111 SYSTEMS
1112 ELEC.
1113 JAN.
1114 A/V
1115 EXISTING MECH
1116 CONFERENCE
1118 BREAK ROOM
1119 OPEN OFFICE
1119A PHONE ROOM
1119B PHONE ROOM
1119C PHONE ROOM
1119D PHONE ROOM
1119E COMM
1120 CIRCULATION
A. REFER TO M-001 FOR GENERAL NOTES FOR ALL
HVAC SHEETS.
B. PROVIDE MANUAL BALANCING DAMPERS IN ALL
SUPPLY AND EXHAUST DUCT RUNOUTS TO
DIFFUSERS AND REGISTERS.
C. DUCT RUNOUT SIZES TO AIR DISTRIBUTION DEVICES
SHALL BE THE SAME AS DEVICE NECK SIZE UNLESS
NOTED OTHERWISE.
D. DUCT RUNOUT SIZES TO THE VAV BOXES SHALL
BE THE SAME SIZE AS VAV BOX INLET SIZE UNLESS
NOTED OTHERWISE.
E. ALL DUCTWORK JOINTS AND SEAMS SHALL MEET
SEAL CLASS A.
F. THE PROJECT IS TO BE COMPLETED IN PHASES.
REFER TO ARCHITECTURAL FOR PHASING.
1. ROUTE RELIEF AIR DUCT ABOVE SOFFIT TO
LV1-01.
DN
DN
DN
DN
AB
C
V1-12 A-2
12"x8"
A-1
(4) A-2
(6) A-2
(4) A-2
6"x10"
12"x10"
6"x10"
V1-15
V1-18 10"x10"
12"x12"
8"x8"
A-1 65 A-1
C-1
C-1
8"x8"
1216 1215
B-1
B-2
B-2
B-2
B-1
B-2
B-2
MATCH LINE
SEE 1/M-111
M
AT
C H
LI
N
E S
EE
1/
M -1
20"x10"
(4) A-2
V1-17
14"x10"
12"x10"
10"x10" 6"x10" (3) A-2
8"x10"10"x10"8"x10" 10"x10"
10"x10"
18"x16"
14"x14"
14"x10"
A-1 958"x8"
A
9.9
9.9
11.3
11.3
12.6
12.6
13.1
13.1
13.6
13.6
16.1
16.1
G G
F F
E E
D D
C C
B B
A A
40"x20"
10"ø
FC1-03
FC1-04
(3) A-2 245B-2
1185FCU1-2
(6) A-2
V1-42V1-16
12"x10"16"x12"20"x12"20"x12"16"x12"12"x10"
16"ø 16"ø
A
A
14"ø
14"ø
24"x18"
"x
"x
12"x10"
28"x28"
52"x16"
"x
36"x20"
EA
12X12 EXH. UP
28X28 OA UP
B-1
B-1
M-401
FD
FD
FD
FD
LV1-02
VV1-02
"x
10"x8"
1232 1233
A-1
10"x8"
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
GARY W.
JAMES
16166
O K L A H O M A
LI
C
EN
S E
D
PRO FES S IO NA L
ENG
IN
EER
/2
0/
8:
:2
AM
C :\U se rs
\A
JA
\D oc um en ts \6
_M ec h_
AJ
A.
rv t
FIRST FLOOR MECHANICAL PLAN - AREA
RRS
BAS
MJA 357
M-112
M-112
SCALE: 1/8" = 1'-0"
1 FIRST FLOOR MECHANICAL PLAN - AREA 2
0 4' 8' 16'
1/8" = 1'-0"
N
KEYPLAN
GENERAL NOTES
SHEET KEYNOTES
GROUND FLOOR AREA 2
Number Name
1201 VEST.
1207 CORRIDOR
1209 STOR.
1211 EXISTING MECH
1212 VENDING
1213 ELEC.
1214 COMM.
1215 MENS
1216 WOMENS
1217 CIRCULATION
1218 OPEN OFFICE
1219 EXISTING STAIR
1221 SERVICE ELEV
1222 EXISTING ATO ROOM
1223 EXISTING SMF DATA ROOM
1224 ENTRY
1225 SMF STORAGE
1226 EXISTING TELECOM
1227 EXISTING DATA ROOM
1228 ELEC CL.
A. REFER TO M-001 FOR GENERAL NOTES FOR ALL
HVAC SHEETS.
B. PROVIDE MANUAL BALANCING DAMPERS IN ALL
SUPPLY AND EXHAUST DUCT RUNOUTS TO
DIFFUSERS AND REGISTERS.
C. DUCT RUNOUT SIZES TO AIR DISTRIBUTION DEVICES
SHALL BE THE SAME AS DEVICE NECK SIZE UNLESS
NOTED OTHERWISE.
D. DUCT RUNOUT SIZES TO THE VAV BOXES SHALL
BE THE SAME SIZE AS VAV BOX INLET SIZE UNLESS
NOTED OTHERWISE.
E. ALL DUCTWORK JOINTS AND SEAMS SHALL MEET
SEAL CLASS A.
F. THE PROJECT IS TO BE COMPLETED IN PHASES.
REFER TO ARCHITECTURAL FOR PHASING.
LV1-02.
DN DN
(8) A-2 225(8) A-2
(8) A-2
(8) A-2
(4) A-2
(6) A-2
A-2
A-1
A-1
A-1
A-1
A-1
A-1
A-1
A-1
A-1
12"x12"
18"x12"
12"x12"
V1-20
V1-19
10"x8"12"x10"
14"x10"
12"x10"8"x10"
V1-23
28"x12"
28"x10"
14"x10"8"x10" 14"x10"
8"x10"
V1-24
14"x10" 8"x10"12"x10"6"x10"
6"x8"
8"x8"
10"x10"
10"x10"
8"x8"
6"x8"
V1-21
10"x8"
14"x8"
14"x10"
V1-25
(2) A-2
6"x8"
VV1-03
A-1 65A-1
B-2
B-2
B-2
B-2
B-2
B-1
B-2
B-1
MATCH LINE
SEE 1/M-114
M
AT
C H
LI
N
E S
EE
1/
M -1
"x
V1-37
12"x12"
18"x12" 12"x12"
8"x10" 16"x18" 16"x18"
V1-36
8"x10"
12"x10"
12"ø
14"x8"
C-1 50 C-1
C-1
B-1
G G
F F
E E
D D
C C
B B
A A
0.9
0.9
64"x18" 60"x18"
"x
"x
"x
16"ø
16"ø
8"ø
"ø
"ø
8" ø
FC1-05
FC1-06
B-2
(2) A-1
16"ø
VV1-07
19"x18" 14"ø
C-3
B-1
B-1
M-401
LV1-03
A
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
GARY W.
JAMES
16166
O K L A H O M A
LI
C
EN
S E
D
PRO FES S IO NA L
ENG
IN
EER
/2
0/
8:
:4
AM
C :\U se rs
\A
JA
\D oc um en ts \6
_M ec h_
AJ
A.
rv t
FIRST FLOOR MECHANICAL PLAN - AREA
RRS
BAS
MJA 358
M-113
M-113
SCALE: 1/8" = 1'-0"
1 FIRST FLOOR MECHANICAL PLAN - AREA 3
0 4' 8' 16'
1/8" = 1'-0"
N
KEYPLAN
GENERAL NOTES
SHEET KEYNOTES
GROUND FLOOR AREA 3
Number Name
1301 VEST.
1302 CORRIDOR
1303 WOMENS
1304 MENS
1305 COMM.
1306 EXISTING MECH
1307 ELEC.
1308 JAN.
1309 BREAK ROOM
1311 CORRIDOR
1312 OPEN OFFICE
1313 CIRCULATION
1314 OPEN OFFICE
1315 EXISTING DATA ROOM CAGE
A. REFER TO M-001 FOR GENERAL NOTES FOR ALL
HVAC SHEETS.
B. PROVIDE MANUAL BALANCING DAMPERS IN ALL
SUPPLY AND EXHAUST DUCT RUNOUTS TO
DIFFUSERS AND REGISTERS.
C. DUCT RUNOUT SIZES TO AIR DISTRIBUTION DEVICES
SHALL BE THE SAME AS DEVICE NECK SIZE UNLESS
NOTED OTHERWISE.
D. DUCT RUNOUT SIZES TO THE VAV BOXES SHALL
BE THE SAME SIZE AS VAV BOX INLET SIZE UNLESS
NOTED OTHERWISE.
E. ALL DUCTWORK JOINTS AND SEAMS SHALL MEET
SEAL CLASS A.
F. THE PROJECT IS TO BE COMPLETED IN PHASES.
REFER TO ARCHITECTURAL FOR PHASING.
LV1-03.
DN
14"x10" 8"x10"12"x10"6"x10"
8"x10"
16"x10"
18"x12"
V1-31
8"x10"
16"x10"
18"x12"
V1-32
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
8"x10"14"x10" 16"x12"
V1-34 (6) A-2
V1-35
10"x6"10"x8"12"x8"12"x10"12"x10"12"x8"10"x8"
10"x6"
(8) A-2
A-2
10"x6"
(4) A-2
10"x10"
16"x10"
V1-26
12"x6"
(4) A-1
V1-28
14"x10"
12"x10"
10"x8"
10"x6"
(4) A-2
10"x10"
16"x10"
V1-29
(2) A-2
(2) A-2
6"x8"
A-1
A-1
C-1
C-1
8"x8"
10"x10"
B-2
B-2
B-2
B-2
B-1
B-2
B-2
14151402
1403 1404
1407 1414
1409 1408
MATCH LINE
SEE 1/M-113
M
AT
C H
LI
N
E S
EE
1/
M -1
(5) A-2
"x
"x
"x
40"x18"
"x
14"x18"
16"x18"
20"x18"
20"x18"
12"x6"
V1-33
B-2
B-1
B-1
B
A
B
P P
N N
M M
L.6 L.6
L.1 L.1
L L
K.6 K.6
K K
J.3 J.3
J J
H H
G.9 G.9
0.7
0.7
0.8
0.8
0.9
0.9
"x
"x
6" x8
"ø
14"ø 10"ø
14"ø
12"ø
"ø
"ø
"ø
FC1-07
FC1-08
V1-39
V1-38D-1
A-1
V1-40
D-1
V1-41
A-2
FCU1-3
(4) A-2
1417B
1417C
1417D
B-1
B-1
B-1
B-1
26"x18"
6"ø6"ø
"x1 8"
OA
E A
EFB-03
B-1
B-1
B-1
B-1
M-401
D-1
FD
FD
43"x13" 12"x12" 12"x12"
E-2 660 E-2
LV1-04
140110X8
V1-30 1417
(2) F-2
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
GARY W.
JAMES
16166
O K L A H O M A
LI
C
EN
S E
D
PRO FES S IO NA L
ENG
IN
EER
/2
0/
8:
:5
AM
C :\U se rs
\A
JA
\D oc um en ts \6
_M ec h_
AJ
A.
rv t
FIRST FLOOR MECHANICAL PLAN - AREA
RRS
BAS
MJA 359
M-114
M-114
SCALE: 1/8" = 1'-0"
1 FIRST FLOOR MECHANICAL PLAN - AREA 4
0 4' 8' 16'
1/8" = 1'-0"
N
KEYPLAN
GENERAL NOTES
SHEET KEYNOTES
GROUND FLOOR AREA 4
Number Name
1401 VESTIBULE
1402 STAIR 3
1403 ELEV 3
1404 STORAGE
1405 ENTRYWAY
1406 LOUNGE
1407 CORRIDOR
1408 WOMENS
1409 MENS
1411 NURSING
1412 ELEC.
1413 COMM.
1414 EXISTING MECH
1415 CONFERENCE
1416 A/V
1417 OPEN OFFICE
1417B PRIVATE OFFICE
1417C CONFERENCE ROOM
1417D PRIVATE OFFICE
1418 CIRCULATION
A. REFER TO M-001 FOR GENERAL NOTES FOR ALL
HVAC SHEETS.
B. PROVIDE MANUAL BALANCING DAMPERS IN ALL
SUPPLY AND EXHAUST DUCT RUNOUTS TO
DIFFUSERS AND REGISTERS.
C. DUCT RUNOUT SIZES TO AIR DISTRIBUTION DEVICES
SHALL BE THE SAME AS DEVICE NECK SIZE UNLESS
NOTED OTHERWISE.
D. DUCT RUNOUT SIZES TO THE VAV BOXES SHALL
BE THE SAME SIZE AS VAV BOX INLET SIZE UNLESS
NOTED OTHERWISE.
E. ALL DUCTWORK JOINTS AND SEAMS SHALL MEET
SEAL CLASS A.
F. THE PROJECT IS TO BE COMPLETED IN PHASES.
REFER TO ARCHITECTURAL FOR PHASING.
LV1-04.
DN
DN
DN
T
MATCH LINE
SEE 1/M-122
M
AT
C H
LI
N
E S
EE
1/
M -1
32"x18" 46"x20"
"x
"x
12"x18"
24"x18"
A-2 185(8)
10"x10"
12"x12"
12"x12"
10"x10"
V2-10
V2-35
10"x10"
12"x12"
12"x12"
10"x10"
A-2 185(8)24"x12"
EQUAL
SPLIT
24"x12"
EQUAL
SPLIT
16"øV2-11
16"ø
14"ø
12"ø
V2-06
V2-07
V2-08
14"x12"
10"x10"
A-2 200(4)
12"x10"
F-2 270(2)
A-2 130(4)
10"x10" 12"x10"
A-2 145(4)
V2-04
12"x10"
14"x12"
A-3 320(4)
12"x12"
16"x12" 18"x12" V2-05
V2-01
V2-02
V2-03 A-2 250(4)
12"x10" 14"x12"
14"ø
A-2 145(4)
A-2 185(4)
12"x10" 14"x10"
12"x10" 14"x10"
12"ø
14X14 EXH. UP
8" ø
VV2-01 8"x10"
A-2
A-1
C-1
C-1
21042117
B-1
B-1
B-2
B-2
A-2
B-1
B-2
B-1
B-1
B-2
B-2
B-2
B-2
V2-09
10"x6"
12"x6"
10"x6"
12"x6"
12"x8"
16"ø
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
B
B
D D
9.9
9.9
11.3
11.3
12.6
12.6
13.1
13.1
13.6
13.6
P.4 P.4
P.3 P.3
P.2 P.2
P.1 P.1
P P
N N
M M
L.6 L.6
L.1 L.1
L L
K.6 K.6
K K
J.3 J.3
J J
H H
G.9 G.9
D
38"x30"
"x
12"ø 16"ø
12"ø
38"x30" RETURN
UP TO THIRD FLR
28"X36" O/A UP
38"x30" SUPPLY
UP TO THIRD FLR
11"x10"
8X8
TYP.
FC2-02
FC2-01
D-1
D-1
D-1
D-1
A-2
A-2
B-1
A-1
A-2
V2-40
V2-3910"x10"
8"x8"
V2-4114"x12"12"x10"
A-2
A-2
FCU2-1
A-1 40A
B-1
FC2-09
B-1
B-1
10"ø
6"ø
10"ø 14"ø
B-1 130B-1
FSD
FSD
FSD
E-1
E-1
28"x12"
10"x12"
10"x12"
VD
MD
2113A
2113B
1116 1116
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
GARY W.
JAMES
16166
O K L A H O M A
LI
C
EN
S E
D
PRO FES S IO NA L
ENG
IN
EER
/2
0/
8:
:1
AM
C :\U se rs
\A
JA
\D oc um en ts \6
_M ec h_
AJ
A.
rv t
SECOND FLOOR MECHANICAL PLAN -
AREA 1
RRS
BAS
MJA 360
M-121
M-121
SCALE: 1/8" = 1'-0"
1 SECOND FLOOR MECHANICAL PLAN - AREA 1 0 4' 8' 16'
1/8" = 1'-0"
N
KEYPLAN
GENERAL NOTES
SHEET KEYNOTES
SECOND FLOOR AREA 1
Number Name 2118 Room 2119 Room
2101 ELEV 1
2102 ENTRYWAY
2103 STAIR 1
2104 LOUNGE
2105 OPEN OFFICE
2106 CORRIDOR
2107 WOMENS
2108 MENS
2109 COMM.
2111 ELEC.
2112 SYSTEMS
2113 OPEN OFFICE
2113A PHONE ROOM
2113B PHONE ROOM
2113C PHONE ROOM
2113D PHONE ROOM
2113F PRIVATE OFFICE
2113G PRIVATE OFFICE
2113H CONFERENCE ROOM
2114 STORAGE
2115 STORAGE
2116 BREAK ROOM
2117 CONFERENCE ROOM
A. REFER TO M-001 FOR GENERAL NOTES FOR ALL
HVAC SHEETS.
B. PROVIDE MANUAL BALANCING DAMPERS IN ALL
SUPPLY AND EXHAUST DUCT RUNOUTS TO
DIFFUSERS AND REGISTERS.
C. DUCT RUNOUT SIZES TO AIR DISTRIBUTION DEVICES
SHALL BE THE SAME AS DEVICE NECK SIZE UNLESS
NOTED OTHERWISE.
D. DUCT RUNOUT SIZES TO THE VAV BOXES SHALL
BE THE SAME SIZE AS VAV BOX INLET SIZE UNLESS
NOTED OTHERWISE.
E. ALL DUCTWORK JOINTS AND SEAMS SHALL MEET
SEAL CLASS A.
F. THE PROJECT IS TO BE COMPLETED IN PHASES.
1. OPPOSED BLADE BALANCING DAMPER.
DN
DN
DN
AB
C
MATCH LINE
SEE 1/M-121
M
AT
C H
LI
N
E S
EE
1/
M -1
A-2 165(6)
A-2 215(6)
A-2 155(8)
A-2 250(8)
A-2 150(8)
A-2 230(3)
A-2
10"x10" 24"x10"
14"x10"
8"x10"
V2-12 16"ø
10"x6"
12"x8" 8"x10"
14"x10"
V2-13 14"x10"
12"x8"
V2-14
10"x6"
8"x10"
"x
36"x20"38"x22"18"x22"
40"x32"
14"x16"
10"x6"
V2-18
16"x10"
10"x10"
V2-16
12"x10" 16"x12" 16"x12" 12"x10"
V2-15
16"x18"
8"x10"
V2-17
8"x10" 11"x10"
VV2-02
A-1
A-1
C-1
C-1
8"x8"
"x
C-1 506"x6"
22112212
B-2
B-2
B-2
B-2
B-2
B-2
B-2
B-1
B-1
12"x10"
12"x10"
8"x10"
V2-38
A-2 155(8)
12"x10"
12"x10"
8"x10"
14"ø
"ø
"ø
"ø
16"ø
16"ø
16"ø
9.9
9.9
11.3
11.3
12.6
12.6
13.1
13.1
13.6
13.6
16.1
16.1
G G
F F
E E
D D
C C
B B
A A
"x
8"x10"12"x10"
14"x10"
10"x10"10"x8"
8"ø
40X32 RETURN
UP TO THIRD FLR.
14X14 EXH. UP
TO THIRD FLR.
28X28 O/A
UP TO ROOF
44X30 SUPPLY
AIR UP TO THIRD
FLOOR
FC2-04
FC2-03
"x
D-1
D-1
V2-4114"x12"12"x10"
A-2
A-2
B-2
"x
2304E2304D A-1
A-1
A-2
A-2
V2-44
A-2 150(2)
B-1
B-1
14"ø
14"ø
B-1
B-1
FSD
FSD
FSD
VD
MD
2304G
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
GARY W.
JAMES
16166
O K L A H O M A
LI
C
EN
S E
D
PRO FES S IO NA L
ENG
IN
EER
/2
0/
8:
:2
AM
C :\U se rs
\A
JA
\D oc um en ts \6
_M ec h_
AJ
A.
rv t
SECOND FLOOR MECHANICAL PLAN -
AREA 2
RRS
BAS
MJA 361
M-122
M-122
SCALE: 1/8" = 1'-0"
1 SECOND FLOOR MECHANICAL PLAN - AREA 2
0 4' 8' 16'
1/8" = 1'-0"
N
KEYPLAN
GENERAL NOTES
SHEET KEYNOTES
SECOND FLOOR AREA 2
Number Name
2207 JAN.
2208 ELEC.
2209 COMM.
2211 MENS
2212 WOMENS
2213 STORAGE
2214 SERVICE ELEV
2215 OPEN OFFICE
2216 EXISTING STAIR
A. REFER TO M-001 FOR GENERAL NOTES FOR ALL
HVAC SHEETS.
B. PROVIDE MANUAL BALANCING DAMPERS IN ALL
SUPPLY AND EXHAUST DUCT RUNOUTS TO
DIFFUSERS AND REGISTERS.
C. DUCT RUNOUT SIZES TO AIR DISTRIBUTION DEVICES
SHALL BE THE SAME AS DEVICE NECK SIZE UNLESS
NOTED OTHERWISE.
D. DUCT RUNOUT SIZES TO THE VAV BOXES SHALL
BE THE SAME SIZE AS VAV BOX INLET SIZE UNLESS
NOTED OTHERWISE.
E. ALL DUCTWORK JOINTS AND SEAMS SHALL MEET
SEAL CLASS A.
F. THE PROJECT IS TO BE COMPLETED IN PHASES.
MATCH LINE
SEE 1/M-124
M
AT
C H
LI
N
E S
EE
1/
M -1
A-2 200(8)
A-2 200(8)
A-2 200(6)
A-2 230(8)
A-2 230(8)
A-2 185(6)
A-2 135(2)
A-1
A-1
50"x24"
"x
"x
"x
40"x22" 34"x20" 28"x20"
"x
22"x20"
A-2 150(6)8"x10"
14"x10" 8"x10"
V2-19
10"x10"14"x12"
22"x12"
V2-20
12"x8"10"x6"
10"x10"
12"x12"12"x12"10"x10"
V2-21V2-36
8"x12"
12"x12"10"x10"
8"x10"
11"x10"
VV2-03
10"x10"
14"x12"
V2-37
14"x12"
10"x10" 10"x6"
12"x8"
14"x10"
10"x6"
V2-24
V2-2214"x12"
10"x10"
14"x12"
10"x10"
V2-23
14"x10"
12"x8"
10"x6"
V2-25
16"ø 10"x10"
12"x10"
16"x10"
A-2
C-1
6"x6"
10"x10"
10"x10"
10"x10"8"x8"
C-1
C-1
2303 2302
B-2
B-2
B-2
B-2
B-2
B-2
B-2
B-2
B-1
B-1
B-1
B
G G
F F
E E
D D
C C
B B
A A
0.9
0.9
16"ø16"ø
50X24 RETURN UP
TO THIRD FLR.
50X20 O/A UP
TO ROOF
14X14 EXH. UP
TO THIRD FLR.
50 X24 SUPPLY UP
TO THIRD FLR.
FC2-05
FC2-06
"x
2304B2304A
A-2
A-2
A-2
V2-42 A-1
A-1
14"x10"10"x10"8"x10"
8"x8"
V2-45 6"ø
FC2-10
V2-43
B-2
B-1
B-1
D-1
16"ø
12"ø8"ø
16"ø
16"ø
16"ø
16"ø
10"ø B-1
B-1
FSD FSD
FSD
VD1
MD
2304C
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
GARY W.
JAMES
16166
O K L A H O M A
LI
C
EN
S E
D
PRO FES S IO NA L
ENG
IN
EER
/2
0/
8:
:4
AM
C :\U se rs
\A
JA
\D oc um en ts \6
_M ec h_
AJ
A.
rv t
SECOND FLOOR MECHANICAL PLAN -
AREA 3
RRS
BAS
MJA 362
M-123
M-123
SCALE: 1/8" = 1'-0"
1 SECOND FLOOR MECHANICAL PLAN- AREA 3
N 0 4' 8' 16'
1/8" = 1'-0"
KEYPLAN
GENERAL NOTES
SHEET KEYNOTES
SECOND FLOOR AREA 3
Number Name
2301 LOBBY
2302 WOMENS
2303 MENS
2304 OPEN OFFICE
2304A PRIVATE OFFICE
2304B PRIVATE OFFICE
2304C CONFERENCE ROOM
2304D PRIVATE OFFICE
2304E PRIVATE OFFICE
2304F PHONE ROOM
2304G PHONE ROOM
2305 COMM.
2306 ELEC.
2307 SYSTEMS
2308 OPEN OFFICE
2308A PHONE ROOM
2308B PHONE ROOM
2308C PHONE ROOM
2309 NURSING
2309D PHONE ROOM
2311 STORAGE
A. REFER TO M-001 FOR GENERAL NOTES FOR ALL
HVAC SHEETS.
B. PROVIDE MANUAL BALANCING DAMPERS IN ALL
SUPPLY AND EXHAUST DUCT RUNOUTS TO
DIFFUSERS AND REGISTERS.
C. DUCT RUNOUT SIZES TO AIR DISTRIBUTION DEVICES
SHALL BE THE SAME AS DEVICE NECK SIZE UNLESS
NOTED OTHERWISE.
D. DUCT RUNOUT SIZES TO THE VAV BOXES SHALL
BE THE SAME SIZE AS VAV BOX INLET SIZE UNLESS
NOTED OTHERWISE.
E. ALL DUCTWORK JOINTS AND SEAMS SHALL MEET
SEAL CLASS A.
F. THE PROJECT IS TO BE COMPLETED IN PHASES.
DN
DN
DN
M
AT
C H
LI
N
E S
EE
1/
M -1
MATCH LINE
SEE 1/M-123
A-2 150(4)
A-1
A-1
34"x20" 26"x20"
"x
20"x18"
16"x18"
14"x18"
10"x16"
16"x18" 12"x18"16"ø
16"ø
8"x10"14"x10"
14"x10"
10"x10"
A-2 180(8)
A-2 215(8)
A-2 165(12)
A-2 160(2)
A-2 265(4)A-2
160(4)
A-3 345(2)
A-1 130(4)
A-2 190(8)
8"x10"14"x10"14"x14"14"x14"14"x10"8"x10"
V2-32
16"ø
8"x10"14"x10"14"x10"
10"x8"10"x6"
V2-33
V2-34
V2-31
16"ø
10"x10"
14"x12"
14"x12"
12"x10"
V2-27
V2-26
10"x10"
14"x12"14"ø
12"ø
10"x10"
14"x10"
10"x8"
V2-30 10"ø10"x10"
14"x10"
V2-28V2-29
12"ø
16"ø
20"x12" 12"x12"
A-1
VV2-04
14X14 EXH
UP
C-1
8"x8"
C-1
10"x10"
C-1
6"x6"
6"x6"
24072405
2409 2408
B-2
B-1
B-2
B-2
B-2
B-2
B-2
A-1
B-1
B-2
B-2
B-2
B-1
B-1
B-1
B-2
A
P.1 P.1
P P
N N
M M
L.6 L.6
L.1 L.1
L L
K.6 K.6
K K
J.3 J.3
J J
H H
G.9 G.9
0.7
0.7
0.8
0.8
0.9
0.9
B B
C
DD
50X22 RETURN UP
TO THIRD FLOOR
50X22 SUPPLY UP
TO THIRD FLR.
18X60 O/A
UP TO ROOF
FC2-08
FC2-07
11"x10" 8"x10" 50 "x
50"x22"
2309D2308C2308B2308A D-1
D-1
D-1
V2-45
6"x8" 6"ø
D-1
D-1
D-1
FCU2-2
B-1
B-1
FSD
FSD
FSD
12"x12"12"x12"
"x
E-2
E-2
VD
MD
2414A 2414C
2414B
F-3 345(2)
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
GARY W.
JAMES
16166
O K L A H O M A
LI
C
EN
S E
D
PRO FES S IO NA L
ENG
IN
EER
/2
0/
8:
:5
AM
C :\U se rs
\A
JA
\D oc um en ts \6
_M ec h_
AJ
A.
rv t
SECOND FLOOR MECHANICAL PLAN -
AREA 4
RRS
BAS
MJA 363
M-124
M-124
SCALE: 1/8" = 1'-0"
1 SECOND FLOOR MECHANICAL PLAN - AREA 4
0 4' 8' 16'
1/8" = 1'-0"
N
KEYPLAN
GENERAL NOTES
SHEET KEYNOTES
SECOND FLOOR AREA 4
Number Name
2401 ELEV 3
2402 ENTRYWAY
2403 STAIR 3
2404 LOUNGE
2405 CONFERENCE ROOM
2407 BREAK ROOM
2408 WOMENS
2409 MENS
2411 JAN.
2412 ELEC.
2413 COMM.
2414 OPEN OFFICE
2414A PHONE ROOM
2414B PHONE ROOM
2414C PHONE ROOM
2415 STORAGE
A. REFER TO M-001 FOR GENERAL NOTES FOR ALL
HVAC SHEETS.
B. PROVIDE MANUAL BALANCING DAMPERS IN ALL
SUPPLY AND EXHAUST DUCT RUNOUTS TO
DIFFUSERS AND REGISTERS.
C. DUCT RUNOUT SIZES TO AIR DISTRIBUTION DEVICES
SHALL BE THE SAME AS DEVICE NECK SIZE UNLESS
NOTED OTHERWISE.
D. DUCT RUNOUT SIZES TO THE VAV BOXES SHALL
BE THE SAME SIZE AS VAV BOX INLET SIZE UNLESS
NOTED OTHERWISE.
E. ALL DUCTWORK JOINTS AND SEAMS SHALL MEET
SEAL CLASS A.
F. THE PROJECT IS TO BE COMPLETED IN PHASES.
DN
DN
MATCH LINE
SEE 1/M-132
M
AT
C H
LI
N
E S
EE
1/
M -1
(6) A-2
(6) A-2
(6) A-2
(6) A-2
(4) A-2
(2) F-2
(4) A-2
(3) A-2
(8) A-2
(8) A-2
(8) A-2
V3-11
8"x12"
12"x12"
12"x12"
8"x12"
V3-35
34"x18"34"x16"20"x16"
14"x16"
10"x16"
10"x10"
12"x10"
12"x10" V3-06
12"ø
V3-08
10"x10" 14"x10"
V3-07 12"x10"
10"x10"
8"x12"
12"x12"
12"x12"
8"x12"
V3-10
V3-09
10"x6"
10"x8"
10"x10"
12"x10"
12"x10" 10"x10"
10"x8"
10"x6"
V3-01
V3-02
V3-03
V3-05
V3-04
VV3-01
8"x10"
12"x12"
"x
12"ø
8"ø
12"ø
14"ø
12"ø
12"ø
14"ø
14"x12"
12"x10"
8"x10"
12"x10"
10"x10"
8"x10"
8"x10"
10"x10"
12"x10"
10"x10"
12"x10"
12"ø
A-1 70A-2
10"x8"
10"x8"8"x8" C-1
C-1
16X16 EXH. UP
TO EF3-01 ON
ROOF
B-1
B-1
B-2
B-2
B-1
B-2
B-1
B-2
B-2
B-2
9.9
9.9
11.3
11.3
12.6
12.6
13.1
13.1
13.6
13.6
P.3 P.3
P.2 P.2
P.1 P.1
P P
N N
M M
L.6 L.6
L.1 L.1
L L
K.6 K.6
K K
J.3 J.3
J J
H H
G.9 G.9
B
B
D D
D
82X30 RA UP TO
AHU3-1 ON ROOF
"x
50"x24"
36X28 O/A UP
TO IH3-01 ON
ROOF
82X30 SUPPLY
UP TO AHU3-1
ON ROOF
"x
"x
10"x16"
FC3-02
FC3-01
"x
"x
D-1
D-1
D-1
D-1
8"x10"
10"x10"
A-2
A-2
V3-38
V3-44
A-1
A-2
B-1
B-1
B-1
V3-39 18"x10"
10"x10"
A-2
A-2
B-2
FCU3-1
FC3-09
3113E
3113F
3113G
8"ø 16"ø
16"ø
10"ø
6"ø
14"ø
B-1 10 B-1
FSD FSD
FSD
FSD
FSD
28"x12"
E-1
E-1
10"x12"
10"x12"
VD
FC3-11
1MD
3113D
3113C
3113B
3113A
(2) A-2
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
GARY W.
JAMES
16166
O K L A H O M A
LI
C
EN
S E
D
PRO FES S IO NA L
ENG
IN
EER
/2
0/
8:
:1
AM
C :\U se rs
\A
JA
\D oc um en ts \6
_M ec h_
AJ
A.
rv t
THIRD FLOOR MECHANICAL PLAN - AREA
RRS
BAS
MJA 364
M-131
M-131SCALE: 1/8" = 1'-0"
1 THIRD FLOOR MECHANICAL PLAN - AREA 1
0 4' 8' 16'
1/8" = 1'-0"
N
KEYPLAN
GENERAL NOTES
SHEET KEYNOTES
THIRD FLOOR AREA 1
Number Name
3101 ELEV 1
3102 ENTRYWAY
3103 STAIR 1
3104 LOUNGE
3105 OPEN OFFICE
3106 ELEVATOR CONTROL
3107 WOMENS
3108 MENS
3109 COMM.
3111 ELEC.
3112 SYSTEMS
3113 OPEN OFFICE
3113A PHONE ROOM
3113B PHONE ROOM
3113C PHONE ROOM
3113D PHONE ROOM
3113E PRIVATE OFFICE
3113F PRIVATE OFFICE
3113G CONFERENCE ROOM
3116 BREAK ROOM
3117 CONFERENCE ROOM
A. REFER TO M-001 FOR GENERAL NOTES FOR ALL
HVAC SHEETS.
B. PROVIDE MANUAL BALANCING DAMPERS IN ALL
SUPPLY AND EXHAUST DUCT RUNOUTS TO
DIFFUSERS AND REGISTERS.
C. DUCT RUNOUT SIZES TO AIR DISTRIBUTION DEVICES
SHALL BE THE SAME AS DEVICE NECK SIZE UNLESS
NOTED OTHERWISE.
D. DUCT RUNOUT SIZES TO THE VAV BOXES SHALL
BE THE SAME SIZE AS VAV BOX INLET SIZE UNLESS
NOTED OTHERWISE.
E. ALL DUCTWORK JOINTS AND SEAMS SHALL MEET
SEAL CLASS A.
F. THE PROJECT IS TO BE COMPLETED IN PHASES.
DN UP
DN
DN
DN
DN
AB
C
MATCH LINE
SEE 1/M-131
M
AT
C H
LI
N
E S
EE
1/
M -1
(8) A-2
(4) A-2
(10) A-2
(7) A-2
(6) A-2
18"ø16"ø
10"x10"
14"x10" V3-18
10"ø
V3-17
V3-16
10"x10" 14"x10" 20"x10"
24"x10"
24"x12"
V3-15
10"x6"
12"x10" 16"x10"
14"x10"
10"x10"
V3-14
V3-13
12"x10"
10"x10"
8"x10"
6"x10"
12"x10"
10"x10"
8"x10"
14"ø V3-1212"x10"
12"x12"
10"x10"
10"x6"
VV3-02
10"x8"
A-1
A-1
C-1
8"x8" 10"x10" C-1
"x
6"x6" C-1
10"x10"
B-1
B-2
B-2
B-2
B-2
B-2
B-2
B-2
V3-37
(8) A-2
8"x10"
12"x10"
12"x10"
8"x10"
(8) A-2
8"x10"
12"x10"
12"x10"
8"x10"
"x
"x
"x
46"x18"50"x18"
"x
16"ø
14"ø
16"ø
14"ø
12"ø
40"x32"
A-3
9.9
9.9
11.3
11.3
12.6
12.6
13.1
13.1
13.6
13.6
16.1
16.1
G G
F F
E E
D D
C C
B B
A A
A
76X30 SUPPLY UP
TO AHU3-2 ON
ROOF
16"x16" 28"x28"
76X30 RETURN UP
TO AHU3-2 ON
ROOF
16X16 EXH. UP
TO EF3-02 ON ROOF
28X28 O/A UP
TO IH3-02
ON ROOF
FC3-03
FC3-04
D-1
D-1
12"x12"
V3-39 18"x10"
10"x10"
A-2
A-2
B-2
A-2 140 A-2
B-1
B-1 140 8" x1 0"
A-2
A-2
A-2
V3-40
14"x10"
14"ø
FCU3-3
3113G
32153304E
3304D
3304F
3304G
B-1
10"x16"
14"ø
10"ø
B-1
B-1
FSD
FSD
FSD
VD
MD
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
GARY W.
JAMES
16166
O K L A H O M A
LI
C
EN
S E
D
PRO FES S IO NA L
ENG
IN
EER
/2
0/
8:
:2
AM
C :\U se rs
\A
JA
\D oc um en ts \6
_M ec h_
AJ
A.
rv t
THIRD FLOOR MECHANICAL PLAN - AREA
RRS
BAS
MJA 365
M-132
M-132
SCALE: 1/8" = 1'-0"
1 THIRD FLOOR MECHANICAL PLAN - AREA 2
0 4' 8' 16'
1/8" = 1'-0"
N
KEYPLAN
GENERAL NOTES
SHEET KEYNOTES
THIRD FLOOR AREA 2
Number Name
3207 JAN.
3208 ELEC.
3209 COMM.
3211 MENS
3212 WOMENS
3213 STORAGE
3214 SERVICE ELEV
3215 OPEN OFFICE
3216 EXISTING STAIR
A. REFER TO M-001 FOR GENERAL NOTES FOR ALL
HVAC SHEETS.
B. PROVIDE MANUAL BALANCING DAMPERS IN ALL
SUPPLY AND EXHAUST DUCT RUNOUTS TO
DIFFUSERS AND REGISTERS.
C. DUCT RUNOUT SIZES TO AIR DISTRIBUTION DEVICES
SHALL BE THE SAME AS DEVICE NECK SIZE UNLESS
NOTED OTHERWISE.
D. DUCT RUNOUT SIZES TO THE VAV BOXES SHALL
BE THE SAME SIZE AS VAV BOX INLET SIZE UNLESS
NOTED OTHERWISE.
E. ALL DUCTWORK JOINTS AND SEAMS SHALL MEET
SEAL CLASS A.
F. THE PROJECT IS TO BE COMPLETED IN PHASES.
MATCH LINE
SEE 1/M-134
M
AT
C H
LI
N
E S
EE
1/
M -1
(10) A-2
(6) A-2
(8) A-2
(8) A-2
(6) A-2
(8) A-2
A-2
A-1
(2) A-2
8"x10"12"x10"
12"x10"
V3-19
16"ø
10"x10"
14"x10"
16"x10"
12"x18"
16"x10"
14"x10"10"x10"10"x10"
10"x12"16"x12"
20"x12"16"x12"
10"x12"
V3-20
V3-21
34"x20"
60"x20"
10"x10"
16"x10"
16"x10"
10"x10"
V3-22 V3-23
"x
"x
"x
"x
10"x10"
16"x10"
16"x10" V3-36
V3-25
16"x10"
12"x10"
10"x10"
10"x6"
10"x8"
VV3-03
V3-24 10"x6"
C-1
C-1
C-1
8"x8" 10"x10"
6"x6"
16X16 UP TO
EF3-03 ON ROOF
B-1
B-2
B-2
B-2
B-2
B-2
B-2
B-2
B-2
B-1
B-1
B-1
A-2
"x
"x
G G
F F
E E
D D
C C
B B
A A
A
50X20 O/A UP
TO IH3-03 ON ROOF
70X34 RETURN UP
TO AHU3-3 ON ROOF
70X34 SUPPLY UP
TO AHU3-3 ON ROOF
16"ø
"ø
10"ø
"ø
"ø
FC3-05
FC3-06
"x
"x
B-2
D-1
V3-42
V3-41
A-1
A-1
A-3
A-3
8" x8
" 12"x12"
10"x12"
V3-43
FC3-10
3304A
3304B 3304C
B-1
B-1
B-2
16"ø
18"ø
6"ø
12"ø
10"ø 8"ø
14"ø
"x3
0"
B-1 80B-1
FSD
FSD
FSD FSD
VD
1 MD
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
GARY W.
JA…