ATTACHMENT 13-ASBESTOS REPORTS.pdf

PDF 25 MB Posted

Attached to
CONSTRUCTION: Multi-Purpose Building Renovation, FAA, MMAC, Oklahoma City, OK
Solicitation number
6973GH-18-R-00009
Issued by

About this file

ATTACHMENT 13-ASBESTOS REPORTS (pdf)

View the file

Other files

File Type Posted
ATTACHMENT 13-ASBESTOS REPORTS.pdf PDF
ATTACHMENT 10- .html file.htm HTM file
ATTACHMENT 5-SF25.pdf PDF
ATTACHMENT 2-DRAWINGS VOLUME 1 ARCHITECTURAL.pdf PDF
ATTACHMENT 10R-BUSINESS RELATIONSHIP AFFIDAVIT.pdf PDF
ATTACHMENT 7-CONTRACTOR'S RELEASE.pdf PDF
ATTACHMENT 4-WAGE DETERMINATION OK49.pdf PDF
ATTACHMENT 15-ADDENDUM 2.pdf PDF
ATTACHMENT 2-DRAWINGS VOLUME 2 MECHANICAL.pdf PDF
ATTACHMENT 3-CHAPTER 33 CONSTRUCTION SAFETY.pdf PDF
ATTACHMENT 2-DRAWINGS VOLUME 1 CIVIL.pdf PDF
ATTACHMENT 8-OPERATIONAL CONTROL DOCUMENTS.pdf PDF
20180116 SITE VISIT ATTENDEES SIGN IN SHEET.pdf PDF
ATTACHMENT 2-DRAWINGS VOLUME 3 TELECOM AND SECURITY.pdf PDF
AMENDMENT 0001.pdf PDF
AMENDMENT 0003.pdf PDF
ATTACHMENT 5R-SF25 PERFORMANCE BOND 8/2016.pdf PDF
ATTACHMENT 12-CLIENT AUTHORIZATION LETTER.docx DOCX document
ATTACHMENT 2-DRAWINGS VOLUME 2 INTERIORS AND FIRE PROTECTION.pdf PDF
24-ATTEND Sign In Second Site Visit.pdf PDF
ATTACHMENT 6R-SF25A PAYMENT BOND 8/2016.pdf PDF
SIR 6973GH-18-R-00009.pdf PDF
ATTACHMENT 2-DRAWINGS VOLUME 2 PLUMBING.pdf PDF
ATTACHMENT 6-SF25A.pdf PDF
AMENDMENT 0002.pdf PDF
ATTACHMENT 1-SPECIFICATIONS VOLUME 2.pdf PDF
ATTACHMENT 9- .html file.htm HTM file
ATTACHMENT 9R-ANTI/NON-COLLUSION AFFIDAVIT.pdf PDF
ATTACHMENT 11-PAST PERFORMANCE SURVEY.pdf PDF
ATTACHMENT 9-OCAT 00310 ANTI/NON-COLLUSION AFFIDAVIT.pdf PDF
ATTACHMENT 1-SPECIFICATIONS VOLUME 1.pdf PDF
ATTACHMENT 2-DRAWINGS VOLUME 1 STRUCTURAL.pdf PDF
ATTACHMENT 2-DRAWINGS VOLUME 3 ELECTRICAL.pdf PDF
ATTACHMENT 14-ADDENDUM 1.pdf PDF
ATTACHMENT 10-OCAT 00320 BUSINESS RELATIONSHIP AFFIDAVIT.pdf PDF
ATTACHMENT 6-SF25A.pdf PDF
ATTACHMENT 9-OCAT 00310 ANTI/NON-COLLUSION AFFIDAVIT.pdf PDF
SIR 6973GH-18-R-00009.pdf PDF
ATTACHMENT 14-ADDENDUM 1.pdf PDF
ATTACHMENT 1-SPECIFICATIONS VOLUME 2.pdf PDF
ATTACHMENT 10-OCAT 00320 BUSINESS RELATIONSHIP AFFIDAVIT.pdf PDF
ATTACHMENT 2-DRAWINGS VOLUME 3 TELECOM AND SECURITY.pdf PDF
AMENDMENT 0001.pdf PDF
ATTACHMENT 2-DRAWINGS VOLUME 1 ARCHITECTURAL.pdf PDF
20180116 SITE VISIT ATTENDEES SIGN IN SHEET.pdf PDF
ATTACHMENT 2-DRAWINGS VOLUME 2 PLUMBING.pdf PDF
ATTACHMENT 5R-SF25 PERFORMANCE BOND 8/2016.pdf PDF
ATTACHMENT 2-DRAWINGS VOLUME 1 STRUCTURAL.pdf PDF
AMENDMENT 0003.pdf PDF
ATTACHMENT 2-DRAWINGS VOLUME 2 INTERIORS AND FIRE PROTECTION.pdf PDF
Show 40 more

Latest 50 of 251 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

For the best experience, open this PDF portfolio in

Acrobat X or Adobe Reader X, or later.

Get Adobe Reader Now!

http://www.adobe.com/go/reader

2016 DRAFT ASBESTOS SURVEY REPORT

Building 24 - Multipurpose Building (024-MPB)

FEDERAL AVIATION ADMINISTRATION

MIKE MONRONEY AERONAUTICAL CENTER

OKLAHOMA CITY, OKLAHOMA

Prepared for:

FEDERAL AVIATION ADMINISTRATION

MIKE MONRONEY AERONAUTICAL CENTER

6500 South MacArthur Oklahoma City, Oklahoma 73169

Prepared by:

WESTON SOLUTIONS, INC.

2705 Bee Cave Road, Suite 100

Austin, TX 78746

(512) 651-7100

Contract DTFAAC-15-D-00033 Delivery Order 005

October 2016

Weston Solutions, Inc. – 2016 Asbestos Survey Report – 024-MPB i

TABLE OF CONTENTS

Section Page

1 INTRODUCTION

2 BUILDING DESCRIPTION

3 2014 ASBESTOS SURVEY

4 2016 SURVEY METHODOLOGY

4.1 ASBESTOS IDENTIFICATION AND SAMPLING METHODOLOGY

4.2 SAMPLE IDENTIFICATION AND CUSTODY

4.3 LABORATORY METHODS

5 024-MPB INSPECTION AND SAMPLING RESULTS

6 ASBESTOS ARCHIBUS DATABASE

APPENDIX A ASBESTOS INSPECTION REPORT

APPENDIX B ASBESTOS ACCESS DATABASE

LIST OF TABLES

Section Page Table 3-1 2014 Survey – Positive Asbestos Sampling Results – 024-MPB

Table 4-1 2016 Survey – Building Prioritization List

Table 5-1 2016 Survey – Positive Asbestos Sampling Results – 024-MPB

Weston Solutions, Inc. – 2016 Asbestos Survey Report – 024-MPB ii

ACRONYMS / ABBREVIATIONS

024-MPB Building 24, or Multipurpose Building

ACM Asbestos-Containing Material AHERA Asbestos Hazard Emergency Response Act

CFR Code of Federal Regulations

DOL Department of Labor

EPA United States Environmental Protection Agency

FAA Federal Aviation Administration FLTL floor tile ft2 square feet

HA Homogeneous Area HASP Health and Safety Plan

MMAC Mike Monroney Aeronautical Center

OSHA Occupational Safety and Health Administration

PIRN Pipe Insulation Runs PJTV Pipe Insulation Joints, Tees, and Valves PLM Polarized Light Microscopy

WESTON® Weston Solutions, Inc.

Weston Solutions Inc. – 2016 Asbestos Survey Report – 024-MPB

1 INTRODUCTION

The Federal Aviation Administration (FAA) contracted Weston Solutions, Inc. (WESTON®) to complete asbestos surveys, perform asbestos testing, and submit field data provided in a format that can be incorporated into the FAA facility management software ARCHIBUS for 13 FAA-leased facilities located at the Mike Monroney Aeronautical Center (MMAC) in Oklahoma City, Oklahoma.

Asbestos is a known carcinogen that was used in a large variety of building materials since the early twentieth century. The risk hazard associated with asbestos is from inhalation of fibers contained within the material. As a result of its known adverse health effects, asbestos and the disturbance of fibrous components has been federally regulated by the United States

Environmental Protection Agency (EPA), the Occupational Safety and Health Administration

(OSHA), and the State of Oklahoma Department of Labor (DOL). These regulations require assessment and identification of the presence of Asbestos Containing Material (ACM) through surveys performed by licensed inspectors.

2 BUILDING DESCRIPTION

Building 24, or Multipurpose Building (024-MPB), is utilized as office space for several entities stationed on the FAA campus. The building was constructed in 1972 and is of masonry and aggregate concrete construction. 024-MPB consists of three stories with a basement and has approximately 211,203 square feet (ft2) of total floor space. The building was confirmed to have

ACM during the 2014 asbestos survey performed by WESTON, as detailed in Section 3.

Each of the three above-ground floors has four mechanical rooms containing HVAC units to direct the heating and cooling for the building, and each mechanical room includes a pipe chase that houses restroom plumbing. The boiler room is found within the basement of the building.

The boiler room consists of a boiler and chiller which supply heating and cooling for the building.

Weston Solutions, Inc. – 2016 Asbestos Survey Reports

3 2014 ASBESTOS SURVEY

In 2014, WESTON and its subcontractor Argus Environmental, LLC collected asbestos samples over a five-month period using field rotations consisting of two weeks onsite and a varied amount of time off-site dependent upon schedules of MMAC, WESTON, and Argus

Environmental. Survey efforts were considered complete once 5,000 samples were collected per the MMAC Statement of Work. The first field rotation was conducted the Week of 17 April

2014, and the last rotation was conducted the Week of 28 July 2014. Details of the 2014 asbestos survey can be found in the 2014 Final Asbestos Survey Report1 previously submitted to

FAA.

Prior to conducting the 2014 asbestos surveys, WESTON performed a preliminary assessment in

January 2014 of 26 buildings identified by MMAC. The purpose of the preliminary assessment was to create a prioritized list of buildings to be surveyed from the highest to lowest priority up to a 5,000-sample limit. The final prioritized building list that was used as a guide for field sampling contained 26 buildings. A total of 23 buildings were sampled for ACM in 2014, and

11 of those buildings were confirmed to have ACM. Buildings identified as containing ACM were: 001-HQB, 002-WSE, 009-H08, 010-H09, 015-BMB, 016-LMN, 022-ARB, 024-MPB, 025-RTF, 026A-STB, and 030-B30.

An individual survey report was prepared for each building that was surveyed in 2014, and these reports can be found in the 2014 Final Asbestos Survey Report previously submitted to FAA.

The 2014 reports include the asbestos results as applicable, sketches of the floor plans depicting sample locations, and photos of materials containing ACM.

The 2014 asbestos survey of interior building materials for 024-MPB was performed on 14–16

April 2014. Three hundred twenty-six samples were collected from inside Building 024-MPB.

Within the 326 collected bulk samples, 366 separate interior building material layers were subjected to Polarized Light Microscopy (PLM) laboratory analysis. As listed in Table 3-1 below, regulated ACM was found in the following material:

1 Source: Weston Solutions, Inc. 2014.

Table 3-1

2014 Survey – Positive Asbestos Sampling Results – 024-MPB

Homogeneous Area Description/Location Sample ID

Percent

Asbestos Quantity Condition Friable/

Nonfriable

Black/Yellow Mastic below non-ACM 12x12" Cream w/ Heavy Blue Streak Floor Tile; Room B22

24-H41B 3% Chrysotile ~ 370 ft2 Good condition Nonfriable

12x12" non- ACM Black Floor Tile;

Room 137

24-H59A 2% Chrysotile ~ 310 ft2 Good

2x4' Hole Ceiling Tile;

100C

24-H63C 2% Chrysotile ~ 1,191 ft2 Good non-ACM 12x12” Peach/Gray

Room 204A

24-H76A 4% Chrysotile ~ 153 ft2 Good

12x12" Gray w/ Black/White Streak Floor Tile & Black Mastic;

Corridors 200A, 200B, 200C & 200D

24-H81A

2% Chrysotile 5%

~ 8,210 ft2 Good non-ACM 12x12" Peach Marbled

Room 230

24-H84A 4% Chrysotile ~ 105 ft2 Good

Area Description/Location Sample ID

Percent

Nonfriable

Brown/Gray Square Pattern Carpet;

Rooms 258 & 262

24-H90A 4% Chrysotile ~ 1,500 ft2 Good

12x12" Gray

Black/White Streak Floor Tile & Black Mastic;

Corridors 300A, 300B, 300C & 300D

24-H94A

2%

4%

~ 8,210 ft2 Good

Based on the appropriate laboratory analysis, asbestos was not identified in any other sample layer during the 2014 survey for 024-MPB. Due to the limited nature of the 2014 survey, Argus

Environmental Consultants, LLC does not warrant the existence or non-existence of ACM in areas not sampled.

4 2016 SURVEY METHODOLOGY

Pre-field work included consulting with MMAC personnel to properly identify any building material that should not be damaged by sample collection. WESTON and its subcontractor Tec-

An, Inc. collected asbestos samples over a four-month period using field rotations dependent upon schedules of MMAC, WESTON, and Tec-An, Inc. The first field rotation was conducted the week of 25 April 2016, and the last rotation was conducted the week of 8 August 2016.

Surveys were conducted in the general sequence according to the prioritization building list by asbestos inspectors licensed through the DOL.

024-MPB was inspected as part of the 2016 inspection update that included a total of 13 buildings. Table 4-1 provides a list of all buildings included in the 2016 inspection update, the final prioritization list, and the date(s) that the sampling was conducted.

Table 4-1

2016 Survey – Building Prioritization List

Priority # Building # Building Name Date Built Date of Rehabilitation Date Sampled

1 015-BMB Base Maintenance Building 1963 - 4/25/2016

2 024-MPB Multi-Purpose Building 1972 - 5/17/2016

3 174-AD3 ASDE-3 1989 - 5/24/2016

4 009-H08 Hangar 8 1958 1988 5/27/2016

5 022-ARB Aviation Records Building 1964 1990 8/8/2016

6 185-ATC Enroute Radar Maintenance

(ERM) 1990 - 6/30/2016

7 010-H09 Hangar 9 1959 1993 6/28/2016

8 001-HQB Headquarters Building 1958 1987 6/22/2016

9 002-WSE Warehouse 1958 2006 7/29/2016

10 013-CAI Civil Aeromedical Inst.

(High Bay Only) 1962 2011 8/2/2016

11 109-ILS ILS Training Facility 1957 - 8/4/2016

12 175-CLC Childcare Center 1990 - 6/27/2016

13 204-VTD VOR/DME/TACAN 1996 - 8/9/2016

An individual survey report was prepared by the subcontractor for each building that was surveyed in 2016; the report for 024-MPB can be found in Appendix A. The report includes the asbestos results as applicable, maps depicting sample locations, photos of all sampling locations, chains of custody, laboratory reports, and copies of asbestos inspector licenses.

Prior to conducting the surveys, a site-specific Health and Safety Plan (HASP) was developed and submitted to FAA detailing the procedures and protocols to be followed during all field activities associated with the surveys. The HASP complied with FAA, OSHA, EPA, and state and local health and safety regulations regarding the work effort.

4.1 ASBESTOS IDENTIFICATION AND SAMPLING METHODOLOGY

The Statement of Work for the limited asbestos surveys included the identification of suspect

ACM into homogenous areas based on the guidelines in the EPA Asbestos Hazard Emergency

Response Act (AHERA) 40 Code of Federal Regulations (CFR) Part 763 Subpart E.

A homogeneous area is defined as an area exhibiting consistent construction materials and techniques with the same date of installation. Sampling areas were adequately wetted with an amended water solution prior to disturbance. Materials were then directly placed into labeled sealable plastic bags and catalogued.

Suspect ACM samples were collected following AHERA rules in the following manner:

Surfacing material: A licensed/accredited inspector collected, in a random manner that was representative of the homogeneous area, bulk samples from each homogeneous area of friable surfacing material as follows:

‒ At least three bulk samples were collected from each homogeneous area that was 1,000 square feet (ft2) or less.

‒ At least five bulk samples were collected from each homogeneous area that was greater than 1,000 ft2 but less than or equal to 5,000 ft2.

‒ At least seven bulk samples were collected from each homogeneous area that was greater than 5,000 ft2.

Thermal system insulation: A licensed/accredited inspector collected, in a randomly distributed manner, at least three bulk samples from each homogeneous area of thermal system insulation as follows:

‒ At least one bulk sample was collected from each homogeneous area of patched thermal system insulation that was not assumed to be ACM if the patched section was less than 6 linear feet or 6 ft2.

‒ Bulk samples were collected from each insulated mechanical system where wraps, mastics, or cement and/or plaster had been used on fittings such as tees, elbows, valves, and seams.

‒ Bulk samples were not collected from any homogeneous area where the accredited inspector had determined that the thermal system insulation was fiberglass, foam glass, rubber, or other non-ACM.

Friable miscellaneous material: Samples were collected in a manner sufficient to determine whether the material was ACM or not ACM. At least two bulk samples were collected from each homogeneous area.

Non-friable suspected ACM: Samples were collected in a manner sufficient to determine whether the material was ACM or not ACM. At least two bulk samples were collected from each homogeneous area of non-friable suspect ACM.

Bulk samples for laboratory analysis were not collected from any roofing or exterior building materials as per the Statement of Work. Blank samples were not collected for quality control purposes as the process from sample collection point, to bagging, to arrival at the lab was streamlined and not conducive for introduction of potential asbestos contaminants. All sample locations for friable materials and dry wall joint compound/surface texture were patched.

Destructive sampling and evaluation under flooring, in any other inaccessible areas, or in any areas of the building outside the proposed evaluation area were not performed. Therefore, any suspect materials hidden in or behind walls, under flooring, or in other inaccessible areas were assumed to be ACM; the area(s) of suspect materials are annotated in the individual building report and figures.

4.2 SAMPLE IDENTIFICATION AND CUSTODY

Asbestos samples were identified using a unique identification. The identification system used is as follows:

Homogeneous Area: Double-alpha and double-digit sequence designating each homogeneous area (HA) in a singular building.

Building Number: Specific FAA-designated building number.

Month and Year of Sample Collection: Double-digit month and double-digit year sequence designating when sampling took place.

Material Type: Four-letter acronym designating material type for each homogeneous area. Examples include Pipe Insulation Runs (PIRN) and Pipe Insulation Joints, Tees, and Valves (PJTV).

Asbestos Sample Number: Quadruple-digit sequential sample within a singular building on a singular day.

For example, a sample for Homogeneous Area 1 (floor tile) in Building 24 collected on 25 May

2016 as the second sample collected in the building on that day would be designated as sample:

“HA01/024-0516-FLTL-0002.”

Upon completion of the sampling of each separate building, bulk material samples were then shipped under chain-of-custody to the Tec-An, Inc. laboratory. The laboratory is certified in

Oklahoma to perform analysis for asbestos content. Samples were shipped to the designated laboratory on a standard two-week turnaround time to the following:

Tec-An, Inc.

2517 S. Purdue Oklahoma City, OK 73128

(405) 681-7076

4.3 LABORATORY METHODS

Analysis of building material samples for asbestos was conducted by Tec-An, Inc. Tec-An, Inc.’s laboratory certifications are provided on Page 57 in Appendix A.

The asbestos bulk samples were analyzed by polarized light microscopy coupled with dispersion staining methods in accordance with EPA-approved analytical Method 600/R-93/116. Results are provided in percent (%) and type of asbestos identified. Positive stop procedures were used for bulk samples where greater than 1% asbestos were detected in building materials and no further analyses were performed. Point counting was conducted on samples that were reported as <1% for verification of asbestos-containing content.

5 024-MPB INSPECTION AND SAMPLING RESULTS

The asbestos inspection and sampling of 024-MPB was performed on 25 May 2016. A total of

132 samples from 54 homogeneous areas were collected from 024-MPB during the 2016 asbestos inspection. Descriptions, photographs, and mapped locations of all homogeneous area sampled are included beginning on Page 46 in Appendix A. Chains of custody and laboratory analytical reports are included beginning on Page 13 in Appendix A.

The homogeneous areas of 024-MPB that tested positive for asbestos are presented in Table 5-1 below.

Table 5-1

2016 Survey – Positive Asbestos Sampling Results – 024-MPB

Homogeneous Area/ Sample Numbers Description Material Type Friable Quantity

HA01

024-0516-FLTL-0001

024-0516-FLTL-0002

12x12 Floor Tile, White with Black and Grey Streaks

Floor Tile No 50,550 ft2

HA02

024-0516-CMST-0003

024-0516-CMST-0004

Mastic Under 12x12 Floor Tile, White with Black and Grey Streaks

Construction Mastic No 50,550 ft2

HA04

024-0516-FLTL-0007

024-0516-FLTL-0009

12x12 Floor Tile, Light Grey with White Steaks Floor Tile No 11,150 ft2

HA05

024-0516-CMST-0008

024-0516-CMST-0010

Tile, Light Grey with White Streaks

Mastic No 11,150 ft2

HA07

024-0516-LINM-0012

024-0516-LINM-0013

024-0516-LINM-0014

Mosaic Pattern Linoleum Flooring Linoleum Yes 21,250 ft2

HA08

024-0516-SEAL-0015

Expansion Joint for Linoleum Floor Transition Caulking No 200 Linear

Feet

HA09

024-0516-FLTL-0016

024-0516-FLTL-0018

9x9 Floor Tile, Tan Floor Tile No 3,000 ft2

HA15

024-0516-FLTL-0027

024-0516-FLTL-0064

12x12 Floor Tile, Off White with Streaks Floor Tile No 50,550 ft2

HA16

024-0516-CMST-0028

024-0516-CMST-0065

Tile, Off White With

HA17

024-0516-FLTL-0029

024-0516-FLTL-0031

White with Streaks Floor Tile No 50,550 ft2

HA18

024-0516-CMST-0030

024-0516-CMST-0032

Tile, Off White with

HA30

024-0516-PJTV-0072

024-0516-PJTV-0073

024-0516-PJTV-0074

Hot Water Pipe Hanger Insulation TSI Yes 275 Pipe

Hangers

HA32

024-0516-SEAL-0081

024-0516-SEAL-0082

Black HVAC Sealant Tape Sealant No 50 ft2

HA53

024-0516-CMST-0129

024-0516-CMST-0130

Tile, White with Light Brown Streaks

Mastic No 300 ft2

HA54

024-0516-CMST-0131

024-0516-CMST-0132

Tile, Light Brown with Brown Streaks

Mastic No 25 ft2

6 ASBESTOS ARCHIBUS DATABASE

To facilitate ARCHIBUS data entry by FAA-MMAC Facility Managers, WESTON developed a

Microsoft Access® database and desktop interface to capture and consolidate the asbestos survey data. This Access database was also created for the purposes of completing Chains of Custody electronically for use during field surveys, exporting corresponding analytical results, and as a mechanism for field and laboratory quality control.

The Access database includes functionality to import and export laboratory analytical data per building. It also provides the option to view sample counts by file for analytical data imported, and it produces an exception report for imported analytical data that does not match Chain of

Custody data. Information included in the data reports includes the following:

The number of asbestos samples per building.

Asbestos sample IDs, media type, and ACM status.

Sample attributes such as floor number, room number, and quadrant as applicable.

The Access database is provided as Appendix B (Compact Disc).

APPENDIX A

ASBESTOS INSPECTION REPORT

Building #024 (MPB) Asbestos Inspection Report Page 1 of 89

1 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 / info@tec-an.com / www.tec-an.com

Asbestos Inspection Report

Building 024 (Multipurpose Building) Mike Monroney Aeronautical Center

May 2016 mailto:info@tec-an.com http://www.tec-an.com/

Building #024 (MPB) Asbestos Inspection Report Page 2 of 89

2 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /

Table of Contents

a. Introduction Page 3

b. Sampling Results Page 4

c. Homogeneous Area Descriptions Page 5

d. Recommendations for Response Page 11

e. Regulatory Statements Page 12

f. Chain of Custody Page 13

g. Laboratory Analytical Sheets Page 26

h. Sample Location Maps Page 46

i. Asbestos Containing Material Maps Page 52

j. Asbestos Containing Pictures Page 57

k. Certifications Page 87

Asbestos Inspection Report

Introduction

The following is an asbestos inspection report for the asbestos inspection performed for Weston Solutions, Inc. for the “Inspection & Testing Services” contract. The inspection was performed at Building #024 (Multipurpose Building) of the Mike Monroney Aeronautical Center on May 25, 2016. The purpose of this inspection was to determine if any building materials within Building #024 (Multipurpose Building) contain asbestos. The sampling was performed by licensed inspector Grayson Cook, Oklahoma License #-159935. The sampling methods used were based on the guidelines of OSHA 29 CFR 1926.1101.

This report consists of four sections. The first is a section defining key terms pertinent to this report, the

Building #024 (MPB) Asbestos Inspection Report Page 3 of 89

3 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 / second is a summary of the asbestos containing samples, the third is a brief description of the homogeneous areas, and the fourth outlines general recommendations for response.

Definitions

1. Asbestos Containing Building Material (ACBM) - Defined as any building material that contains more than 1% asbestos fibers.

2. Homogeneous Area - An area of thermal systems insulation (TSI), surfacing material or miscellaneous material that is uniform in color, texture and date of application. If a building material tests positive for asbestos fibers, then the entire quantity of the homogeneous area is considered positive.

3. Miscellaneous Material - Any interior building material on structural components, structural members of fixtures, such as floor and ceiling tiles, and does not include surfacing material or thermal system insulation.

4. Surfacing Material - Any material in a building that is sprayed-on, troweled-on or otherwise applied to surfaces for acoustical, fireproofing or other purposes.

5. Thermal System Insulation (TSI) - Any building material applied to pipes, fittings, boilers, breeching, tanks, ducts, or other interior structural components to prevent heat loss/gain, or water condensation or for other purposes.

Building Description

Building #024, or Multipurpose Building, of the Mike Monroney Aeronautical Center is used as offices for multiple entities stationed on the FAA campus. The building is of masonry and aggregate concrete construction. The building is a three story building with basement and is approximately 211,203 square feet of total floor space. The boiler room is located within the basement of the building. The boiler room consists of BOILER and CHILLER which supply all of the buildings heating and cooling. Each of the top three floors has four mechanical rooms that contain an HVAC unit to direct the heating and cooling of the building. Within each mechanical room there is a pipe chase that houses all the plumbing for the restrooms on each floor.

Sampling Results

The following homogeneous areas tested positive for asbestos.

Homogeneous Area/ Sample Numbers

Description Material Type Friable Quantity

HA01

024-0516-FLTL-0001

024-0516-FLTL-0002

12x12 Floor Tile, White with Black and Grey

Floor Tile No 50,550 Square Feet

HA02 Mastic Under 12x12 Construction No 50,550

Building #024 (MPB) Asbestos Inspection Report Page 4 of 89

4 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /

024-0516-CMST-0003

024-0516-CMST-0004

Floor Tile, White with Black and Grey Streaks

Mastic Square Feet

HA04

024-0516-FLTL-0007

024-0516-FLTL-0009

12x12 Floor Tile, Light Grey with White Steaks

Floor Tile No 11,150

HA05

024-0516-CMST-0008

024-0516-CMST-0010

Mastic Under 12x12 Floor Tile, Light Grey with White Streaks

Mastic

No 11,150

HA07

024-0516-LINM-0012

024-0516-LINM-0013

024-0516-LINM-0014

Mosaic Pattern Linoleum Flooring

Linoleum Yes 21,250

HA08

024-0516-SEAL-0015

Expansion Joint for Linoleum Floor Transition

Caulking No 200 Linear

HA09

024-0516-FLTL-0016

024-0516-FLTL-0018

9x9 Floor Tile, Tan Floor Tile No 3,000 Square

HA15

024-0516-FLTL-0027

024-0516-FLTL-0064

White with Streaks

HA16

024-0516-CMST-0028

024-0516-CMST-0065

Floor Tile, Off White With Streaks

No 50,550

HA17

024-0516-FLTL-0029

024-0516-FLTL-0031

White with Streaks

HA18

024-0516-CMST-0030

024-0516-CMST-0032

Floor Tile, Off White with Streaks

No 50,550

HA30

024-0516-PJTV-0072

024-0516-PJTV-0073

024-0516-PJTV-0074

Hot Water Pipe Hanger Insulation

TSI Yes 275 Pipe Hangers

HA32

024-0516-SEAL-0081

024-0516-SEAL-0082

Black HVAC Sealant Tape

Sealant No 50 Square

HA53

024-0516-CMST-0129

024-0516-CMST-0130

Floor Tile, White with Light Brown Streaks

No 300 Square

HA54

024-0516-CMST-0131

024-0516-CMST-0132

Floor Tile, Light Brown with Brown Streaks

No 25 Square

Homogeneous Area/Sample Description

Building #024 (MPB) Asbestos Inspection Report Page 5 of 89

5 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /

A total of 132 samples from 54 homogeneous areas were collected from Building #024 during this asbestos inspection.

HA01/ Sample #’s 024-0516-FLTL-0001, 024-0516-FLTL-0002 - This Homogeneous Area represents the 12x12 white floor tile with black and grey streaks taken from the 1st floor. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The floor tile tested positive for asbestos with 3% chrysotile fibers.

HA02/ Sample #’s 024-0516-CMST-0003, 024-0516-CMST-0004 - This Homogeneous Area represents the mastic under the 12x12 floor tile with black and grey streaks from the 1st floor. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The mastic tested positive for asbestos with 4% chrysotile fibers.

HA03/ Sample #’s 024-0516-SEAL-0005, 024-0516-SEAL-0006 - This Homogeneous Area represents the caulking from the expansion joint of the plaster walls. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The caulking tested negative for asbestos fibers.

HA04/ Sample #’s 024-0516-FLTL-0007, 024-0516-FLTL-0009 - This Homogeneous Area represents the 12x12 light grey floor tile with white streaks from the 2nd floor. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The floor tile tested positive for asbestos with 2% chrysotile fibers.

HA05/ Sample #’s 024-0516-CMST-0008, 024-0516-CMST-0010 - This Homogeneous Area represents the mastic under the 12x12 light grey floor tile with grey streaks from the 2nd floor. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The mastic tested positive for asbestos with 5% chrysotile fibers.

HA06/ Sample #’s 024-0516-CMST-0011 - This Homogeneous Area represents the mastic found under the mosaic pattern linoleum flooring from the basement level of the building. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The mastic tested negative for asbestos fibers.

HA07/ Sample #’s 024-0516-LINM-0012, 024-0516-LINM-0013, 024-0516-LINM-0014 - This Homogeneous Area represents the mosaic pattern linoleum flooring from the basement of the building.

This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The linoleum tested positive for asbestos with 20% chrysotile fibers.

HA08/ Sample #’s 024-0516-SEAL-0015- This Homogeneous Area represents the caulking from the expansion joint at the transition of the mosaic pattern linoleum flooring. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The caulking tested negative for asbestos fibers.

HA09/ Sample #’s 024-0516-FLTL-0016, 024-0516-FLTL-0018 - This Homogeneous Area represents the 9x9 tan floor tile found in the stairwells of the building. This material is classified as a non-friable

Building #024 (MPB) Asbestos Inspection Report Page 6 of 89

6 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 / miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The floor tile tested positive for asbestos with 6% chrysotile fibers.

HA10/ Sample #’s 024-0516-CMST-0017, 024-0516-CMST-0019 - This Homogeneous Area represents the mastic found under 9x9 tan floor tile in the stairwells of the building. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The mastic tested negative for asbestos fibers.

HA11/ Sample #’s 024-0516-FLTL-0020, 024-0516-FLTL-0022 - This Homogeneous Area represents the grey stair tread covers from the stairwells of the building. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The stair tread covers tested negative for asbestos fibers.

HA12/ Sample #’s 024-0516-CMST-0021, 024-0516-CMST-0023 - This Homogeneous Area represents the mastic under the grey stair tread covers in the stairwells of the building. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The mastic tested negative for asbestos fibers.

HA13/ Sample #’s 024-0516-FLTL-0024, 024-0516-FLTL-0025 - This Homogeneous Area represents the tan stair tread covers found in the stairwells of the building. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The stair tread covers tested negative for asbestos fibers.

HA14/ Sample #’s 024-0516-CMST-0026- This Homogeneous Area represents the mastic found under the tan stair tread covers found in the stairwells. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The mastic tested negative for asbestos fibers.

HA15/ Sample #’s 024-0516-FLTL-0027, 024-0516-FLTL-0064 - This Homogeneous Area represents the 12x12 floor white floor tile with streaks found on the under the carpet in the rooms and offices of the 2nd floor. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The floor tile tested positive for asbestos with 2% chrysotile fibers.

HA16/ Sample #’s 024-0516-CMST-0028, 024-0516-CMST-0065 - This Homogeneous Area represents the mastic under the 12x12 white floor tile with streaks found under the carpet in the rooms and offices of the 2nd floor. This material is classified as a friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The mastic tested positive for asbestos with 8% chrysotile fibers.

HA17/ Sample #’s 024-0516-FLTL-0029, 024-0516-FLTL-0031 - This Homogeneous Area represents 12x12 white floor tile with streaks found under the carpet in the rooms and offices of the 3rd floor. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The floor tile tested positive for asbestos with 3% chrysotile fibers.

Building #024 (MPB) Asbestos Inspection Report Page 7 of 89

7 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /

HA18/ Sample #’s 024-0516-CMST-0030, 024-0516-CMST-0032 - This Homogeneous Area represents the mastic associated with the 12x12 white floor tile with streaks found under the carpet in the rooms and offices of the 3rd floor. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The mastic tested positive for asbestos with 8% chrysotile fibers.

HA19/ Sample #’s 024-0516-WLTX-0033, 024-0516-WLTX-0034, 024-0516-WLTX-0035, 024-0516-WLTX- 0036, 024-0516-WLTX-0037, 024-0516-WLTX-0038, 024-0516-WLTX-0039- This Homogeneous Area represents the light wavy wall texture in the sheetrock walls of the visual arts center in the basement of the building. This material is classified as a friable surfacing material. Samples were collected and tested according to the Oklahoma asbestos regulations. The wall texture tested negative for asbestos fibers.

HA20/ Sample #’s 024-0516-WLJC-0040, 024-0516-WLJC-0041 - This Homogeneous Area represents the joint compound from the sheetrock walls of the visual arts center in the basement on the building. This material is classified as a friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The joint compound tested negative for asbestos fibers.

HA21/ Sample #’s 024-0516-WABD-0042, 024-0516-WABD-0043 - This Homogeneous Area represents the sheetrock from the walls of the visual arts center in the basement of the building. This material is classified as a friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The sheetrock tested negative for asbestos fibers.

HA22/ Sample #’s 024-0516-CLTX-0044, 024-0516-CLTX-0045, 024-0516-CLTX-0046 - This Homogeneous Area represents the flat texture on the plaster ceilings of the stairwells. This material is classified as a friable surfacing material. Samples were collected and tested according to the Oklahoma asbestos regulations. The texture tested negative for asbestos fibers.

HA23/ Sample #’s 024-0516-PLST-0047, 024-0516-PLST-0048, 024-0516-PLST-0049, 024-0516-PLST- 0050, 024-0516-PLST-0051, 024-0516-PLST-0052, 024-0516-PLST-0053 - This Homogeneous Area represents the plaster walls found throughout the building on each floor. This material is classified as a non-friable surfacing material. Samples were collected and tested according to the Oklahoma asbestos regulations. The plaster tested negative for asbestos fibers.

HA24/ Sample #’s 024-0516-CLJC-0054, 024-0516-CLJC-0055 - This Homogeneous Area represents the joint compound found in the flat textured sheetrock ceilings of the restrooms. This material is classified as a friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The joint compound tested negative for asbestos fibers.

HA25/ Sample #’s 024-0516-WABD-0056, 024-0516-WABD-0057 - This Homogeneous Area represents the sheetrock from the flat textured ceilings in the restrooms. This material is classified as a friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The sheetrock tested negative for asbestos fibers.

HA26/ Sample #’s 024-0516-CLTX-0058, 024-0516-CLTX-0059, 024-0516-CLTX-0060 - This Homogeneous Area represents the flat texture found on the sheetrock ceilings of the restrooms. This

Building #024 (MPB) Asbestos Inspection Report Page 8 of 89

8 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 / material is classified as a friable surfacing material. Samples were collected and tested according to the Oklahoma asbestos regulations. The texture tested negative for asbestos fibers.

HA27/ Sample #’s 024-0516-WLTX-0061, 024-0516-WLTX-0062, 024-0516-WLTX-0063- This Homogeneous Area represents the heavy repair wall texture found a the south end of Room B10 . This material is classified as a friable surfacing material. Samples were collected and tested according to the Oklahoma asbestos regulations. The texture tested negative for asbestos fibers.

HA28/ Sample #’s 024-0516-PJTV-0066, 024-0516-PJTV-0067, 024-0516-PJTV-0068 - This Homogeneous Area represents the chiller water supply line fitting insulation found in the boiler room and the mechanical rooms. This material is classified as a friable TSI material. Samples were collected and tested according to the Oklahoma asbestos regulations. The pipe insulation tested negative for asbestos fibers.

HA29/ Sample #’s 024-0516-PJTV-0069, 024-0516-PJTV-0070, 024-0516-PJTV-0071 - This Homogeneous Area represents the heater hot water supply line fitting insulation found in the boiler room and the mechanical rooms. This material is classified as a friable TSI material. Samples were collected and tested according to the Oklahoma asbestos regulations. The insulation tested negative for asbestos fibers.

HA30/ Sample #’s 024-0516-PJTV-0072, 024-0516-PJTV-0073, 024-0516-PJTV-0074 - This Homogeneous Area represents the pipe hanger insulation on the heater hot water lines. This material is classified as a friable TSI material. Samples were collected and tested according to the Oklahoma asbestos regulations.

The insulation tested positive for asbestos with 10% Amosite and 35% chrysotile fibers.

HA31/ Sample #’s 024-0516-DTIN-0078, 024-0516-DTIN-0079, 024-0516-DTIN-0080 - This Homogeneous Area represents the insulation on the round air ducts within the boiler room and mechanical rooms. This material is classified as a friable TSI material. Samples were collected and tested according to the Oklahoma asbestos regulations. The insulation tested negative for asbestos fibers.

HA32/ Sample #’s 024-0516-SEAL-0081, 024-0516-SEAL-0082 - This Homogeneous Area represents the black rubber sealant tape found on the air handler units in the mechanical rooms. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The sealant tape tested positive for asbestos with 8% chrysotile fibers.

HA33/ Sample #’s 024-0516-SEAL-0083, 024-0516-SEAL-0084 - This Homogeneous Area represents the white caulking found on the plaster walls in the mechanical rooms. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The caulking tested negative for asbestos fibers.

HA34/ Sample #’s 024-0516-DCTP-0085, 024-0516-DCTP-0086 - This Homogeneous Area represents the white coated duct tape found on the air handler unit in mechanical room 317. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The duct tape tested negative for asbestos fibers.

HA35/ Sample #’s 024-0516-SEAL-0087, 024-0516-SEAL-0088 - This Homogeneous Area represents the white repair sealant on the duct insulation in mechanical room 324. This material is classified as a non-

Building #024 (MPB) Asbestos Inspection Report Page 9 of 89

9 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 / friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The sealant tested negative for asbestos fibers.

HA36/ Sample #’s 024-0516-SEAL-0089, 024-0516-SEAL-0090 - This Homogeneous Area represents the grey rubber caulking found in the bare metal duct work on the North wall of mechanical room 324. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The caulking tested negative for asbestos fibers.

HA37/ Sample #’s 024-0516-SEAL-0091, 024-0516-SEAL-0092 - This Homogeneous Area represents the green duct sealant found on the bare metal duct work within the first floor mechanical rooms. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The sealant tested negative for asbestos fibers.

HA38/ Sample #’s 024-0516-SEAL-0093, 024-0516-SEAL-0094 - This Homogeneous Area represents the joint compound found in the light orange peel textured sheetrock walls. This material is classified as a friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The joint compound tested negative for asbestos fibers.

HA39/ Sample #’s 024-0516-SEAL-0093, 024-0516-SEAL-0094 - This Homogeneous Area represents the grey caulking found on the air ducts of mechanical room 138. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The caulking tested negative for asbestos fibers.

HA40/ Sample #’s 024-0516-PJTV-0095, 024-0516-PJTV-0096, 024-0516-PJTV-0097 - This Homogeneous Area represents the L.P. steam pipe fitting insulation found in the mechanical rooms of the building. This material is classified as a friable TSI material. Samples were collected and tested according to the Oklahoma asbestos regulations. The insulation tested negative for asbestos fibers.

HA41/ Sample #’s 024-0516-PJTV-0098, 024-0516-PJTV-0099, 024-0516-PJTV-0100 - This Homogeneous Area represents the insulation on the condenser return line fittings in the mechanical rooms of the building. This material is classified as a friable TSI material. Samples were collected and tested according to the Oklahoma asbestos regulations. The insulation tested negative for asbestos fibers.

HA42/ Sample #’s 024-0516-PJTV-0101, 024-0516-PJTV-0102, 024-0516-PJTV-0103 - This Homogeneous Area represents insulation on the heater hot water return line fittings in the mechanical rooms of the building. This material is classified as a friable TSI material. Samples were collected and tested according to the Oklahoma asbestos regulations. The insulation tested negative for asbestos fibers.

HA43/ Sample #’s 024-0516-PJTV-0104, 024-0516-PJTV-0105, 024-0516-PJTV-0106 - This Homogeneous Area represents the insulation on the chilled water return line fittings in the mechanical rooms of the building. This material is classified as a friable TSI material. Samples were collected and tested according to the Oklahoma asbestos regulations. The insulation tested negative for asbestos fibers.

HA44/ Sample #’s 024-0516-FRPF-0107, 024-0516-FRPF-0108, 024-0516-FRPF-0109, 024-0516-FRPF- 0110, 024-0516-FRPF-0111 - This Homogeneous Area represents the spray-on fireproofing insulation found on the above the ceiling tile on the concrete walls and ceilings of the basement. This material is

Building #024 (MPB) Asbestos Inspection Report Page 10 of 89

10 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 / classified as a friable surfacing material. Samples were collected and tested according to the Oklahoma asbestos regulations. The fireproofing tested negative for asbestos fibers.

HA45/ Sample #’s 024-0516-SEAL-0112, 024-0516-SEAL-0113 - This Homogeneous Area represents the black caulking on the window frames found within the courtyard. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The caulking tested negative for asbestos fibers.

HA46/ Sample #’s 024-0516-SEAL-0114, 024-0516-SEAL-0115 - This Homogeneous Area represents the expansion joint caulking in the concrete floor of the courtyard. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The caulking tested negative for asbestos fibers.

HA47/ Sample #’s 024-0516-SEAL-0116, 024-0516-SEAL-0117 - This Homogeneous Area represents the black caulking found around the entry doors of the courtyard. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The caulking tested negative for asbestos fibers.

HA48/ Sample #’s 024-0516-SEAL-0118, 024-0516-SEAL-0119 - This Homogeneous Area represents the tan expansion joint caulking in the brick/concrete walls of the courtyard. This material is classified as a friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The caulking tested negative for asbestos fibers.

HA49/ Sample #’s 024-0516-DTIN-0120, 024-0516-DTIN-0121, 024-0516-DTIN-0122 - This Homogeneous Area represents the interior duct insulation found in the metal duct insulation. This material is classified as a friable TSI material. Samples were collected and tested according to the Oklahoma asbestos regulations. The insulation tested negative for asbestos fibers.

HA50/ Sample #’s 024-0516-INBD-0123, 024-0516-INBD-0124 - This Homogeneous Area represents the joint compound found in the insulation board found around the concrete foundation of the mechanical rooms of the building. This material is classified as a friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The insulation board tested negative for asbestos fibers.

HA51/ Sample #’s 024-0516-FLTL-0125, 024-0516-FLTL-0126 - This Homogeneous Area represents the 12x12 white floor tile with light brown streaks in the storage room of the Data Center. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The floor tile tested negative for asbestos fibers.

HA52/ Sample #’s 024-0516-FLTL-0127, 024-0516-FLTL-0128 - This Homogeneous Area represents the 12x12 light brown floor tile with brown streaks found on the south wall of the Data Center. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The floor tile tested negative for asbestos fibers.

HA53/ Sample #’s 024-0516-CMST-0129, 024-0516-CMST-0130 - This Homogeneous Area represents the mastic under the 12x12 white floor tile with light brown streaks in the storage room of the Data Center. This material is classified as a non-friable miscellaneous material. Samples were collected and

Building #024 (MPB) Asbestos Inspection Report Page 11 of 89

11 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 / tested according to the Oklahoma asbestos regulations. The mastic tested positive for asbestos with 3% chrysotile fibers.

HA54/ Sample #’s 024-0516-CMST-0131, 024-0516-CMST-0132 - This Homogeneous Area represents the mastic under the 12x12 light brown floor tile with brown streaks. This material is classified as a non-friable miscellaneous material. Samples were collected and tested according to the Oklahoma asbestos regulations. The mastic tested positive for asbestos with 3% chrysotile fibers.

Additional Information Asbestos containing floor tile and black mastic was found under multiple types of carpet in multiple areas of the building. At this time it is assumed that the positive floor tile and black mastic is found under all carpeted areas within the 1st, 2nd and 3rd floors of the building.

All pipe hangers excluding the Heater Hot Water Return/Supply pipes were found to be either fiberglass or foam glass. According to OSHA/EPA regulations materials including but not limited to fiberglass and foam glass are not required to be sampled, and can be determined to be asbestos free by an accredited inspector. It was also observed that all pipe run insulation within the building was fiberglass.

Recommendations for Response If any of the building materials found to be friable asbestos containing building materials are to be disturbed by renovation/demolition activities, or are found to be significantly damaged (more than 10% distributed damage or 25% localized damage), then the material must be removed or encapsulated by a licensed asbestos contractor.

If any of the building materials found to be non-friable asbestos containing building material are to be disturbed by renovation activities, then the material must be removed following the OSHA Class II Non-friable Asbestos Removal Requirements. If the non-friable materials are to be disturbed by demolition activities, then the materials must be removed following the OSHA Class II Non-friable Asbestos Removal Requirements. However, according to Department of Environmental Quality regulations, some non-friable asbestos containing building materials may remain in the building during demolition.

Regulatory Statement

All Federal rules and regulations (OSHA and /or EPA) are written as minimum regulatory standard.

States have the right to enact regulatory rules and regulations, and have the latitude to enact more stringent rules and regulations. Before beginning any demolition or renovation activity, contact the appropriate state regulatory agencies for clarification of asbestos abatement rules and regulations.

Destructive Bulk Sampling

No destructive bulk sampling was conducted during this asbestos inspection. There is a possibility asbestos containing materials could be located in vertical pipe chases in the form of pipe insulation on domestic, boiler and chiller piping (Thermal System Insulation). There is also a possibility that asbestos containing building materials could be located behind walls and above inaccessible ceiling areas.

Building #024 (MPB) Asbestos Inspection Report Page 12 of 89

12 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /

Before beginning demolition or renovation conduct a limited destructive inspection to determine the material composition of materials in pipe chases and behind walls.

Respectfully, Grayson Cook Tec-An, Inc.

Oklahoma License # 159935 Report Date – 06/14/2016

Chain of Custody and Laboratory Analytical Report

Building #024 (MPB) Asbestos Inspection Report Page 13 of 89

13 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /

Building #024 (MPB) Asbestos Inspection Report Page 14 of 89

14 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /

Building #024 (MPB) Asbestos Inspection Report Page 15 of 89

15 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /

Building #024 (MPB) Asbestos Inspection Report Page 16 of 89

16 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /

Building #024 (MPB) Asbestos Inspection Report Page 17 of 89

17 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /

Building #024 (MPB) Asbestos Inspection Report Page 18 of 89

18 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /

Building #024 (MPB) Asbestos Inspection Report Page 19 of 89

19 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /

Building #024 (MPB) Asbestos Inspection Report Page 20 of 89

20 Tec-An, Inc / 2517 S. Purdue, OKC, OK 73128 / Ph) 405-681-7076 / Fx) 405-681-7256 /

Building #024 (MPB) Asbestos Inspection Report Page 21 of 89

21 Tec-An, Inc / 2517 S.