DESIGN CRITERIA:
GOVERNING BUILDING CODE: IBC 2015 WITH OKLAHOMA CITY SUPPLEMENT
BUILDING RISK CATEGORY: III
DESIGN LOADS:
DEAD LOADS:
ROOF SYSTEM .................................................... 20 PSF SUPERIMPOSED FRAMING................................................................ ACTUAL WEIGHT OF MATERIALS, UNLESS NOTED OTHERWISE
INSULATION......................................................... 1 PSF
CEILING COLLATERAL.......................................... 3 PSF
MISC/MECH COLLATERAL.................................... 5 PSF
LIVE LOADS:
ROOF (NON-REDUCIBLE)..................................... 20 PSF
MECH PLATFORMS............................................... 150 PSF
MECHANICAL FLOOR ........................................... 250 PSF
ALL OTHER FLOORS ............................................ 80 PSF
CONCENTRATED POINT LOADS
SLAB ON GRADE (6"X6") ........................... 20,000 LBS
SNOW LOAD: (ASCE 7-10)
BASIC GROUND SNOW LOAD, (Pg)..................... 10 PSF
TERRAIN CATEGORY........................................... C
ROOF EXPOSURE................................................ PARTIAL
EXPOSURE FACTOR, (Ce)................................... 1.0
THERMAL FACTOR, (Ct)....................................... 1.0 SLOPE FACTOR, (Cs)........................................... 1.0
IMPORTANCE FACTOR, (Is).................................. 1.10 SLOPED ROOF SNOW, (Ps)................................. 11 PSF
WIND LOAD: (ASCE 7-10)
BUILDING DESIGN:
BASIC WIND SPEED............................................. 120 MPH
EXPOSURE CATEGORY....................................... C
TOPOGRAPHIC FACTOR, (Kzt)............................. 1.0 IMPORTANCE FACTOR, (Iw) ................................ 1.0
BUILDING ENCLOSURE CA................................... ENCLOSED BUILDING
SEISMIC DESIGN DATA: (ASCE 7-10)
SHORT PERIOD ACCELERATION, Ss .................. 0.279 g LONG PERIOD ACCELERATION, S1.................... 0.079 g
SOIL SITE CLASS ................................................ C
SITE COEFFICIENT, Fa ....................................... 1.2 SITE COEFFICIENT, Fv ....................................... 1.7 DESIGN SPECTRAL ACCELERATION, SDs ........ 0.159 g DESIGN SPECTRAL ACCELERATION, SD1 ........ 0.072 g
SEISMIC DESIGN CATEGORY ............................ B
IMPORTANCE FACTOR, (Ie) ................................. 1.25 ANALYSIS METHOD............................................... EQUIVALENT LATERAL FORCE
SEISMIC FORCE RESISTING SYSTEM.................. STEEL SYSTEMS NOT SPECIFICALLY
DETAILED FOR SEISMIC RESISTANCE
DESIGN BASE SHEAR........................................... 2528 kips R=3.0, =3.0, Cd=3.0, I=1.25, Cs=0.093
TEMPERATURE:
STRUCTURE SHALL BE ANALYZED FOR T = +30,-30 °F (60 °F TOTAL T )
MATERIAL DESIGN VALUES:
CONCRETE (MINIMUM ULTIMATE COMPRESSIVE STRENGTH AT 28 DAYS,
NORMAL WEIGHT, UNLESS NOTED OTHERWISE)
SLABS ON GRADE AND FOUNDATIONS.................... 4,000 PSI
ALL OTHER STRUCTURAL CONCRETE, U.N.O.......... 4,000 PSI
CONCRETE REINFORCEMENT(MINIMUM YIELD STRENGTH)
ALL DEFORMED BARS, UNLESS NOTED OTHERWISE.
(ASTM A615, GRADE 60).............................................. FY = 60,000 PSI
WELDED WIRE FABRIC (ASTM A185).......................... FY = 60,000 PSI
SMOOTH BARS (ASTM A82).......................................... FY = 70,000 PSI
DEFORMED BAR ANCHORS (ASTM A706)................... FY = 60,000 PSI
STRUCTURAL STEEL (MINIMUM YIELD STRENGTH)
WIDE FLANGES (ASTM A992 OR A572, GR. 50)......... FY = 50,000 PSI
PIPES (ASTM A500, GRADE B)...................................... FY = 42,000 PSI
TUBES (ASTM A500, GRADE B).................................... FY = 46,000 PSI
ALL OTHER SHAPES, PLATES AND ANCHOR BOLTS
UNLESS NOTED OTHERWISE (ASTM A36)................. FY = 36,000 PSI
BASE PLATE (ASTM A572, GR. 50).............................. FY = 50,000 PSI
ANCHOR RODS (DIAMETER LESS THAN 1 1/2")
(ASTM F 1554, WELDABLE GRADE 55).................. FY = 55,000 PSI
ANCHOR RODS (DIAMETER EQUAL TO AND GREATER THAN 1 1/2")
(ASTM F 1554, GRADE 105) ................................... FY = 105,000 PSI
COLD FORMED STRUCTURAL SHAPES..................... FY = 33,000 PSI (MIN)
SOILS/FOUNDATION NOTES:
1. FOUNDATION RECOMMENDATIONS ARE BASED ON THE
GEOTECHNICAL REPORT DATED MARCH 25, 2014 FOR EXISTING
MULTI-PURPOSE BUILDING AT MIKE MONRONEY AERONAUTICAL
CENTER, OKLAHOMA CITY, OKLAHOMA, PROJECT NO.: 731-13165
PREPARED BY BURGESS ENGINEERING AND TESTING INC, 809
NW 34TH STREET, MOORE OK 73160, PHONE NO.: (405) 790-0488
2. AT BASEMENT FLOOR LEVEL, ALLOWABLE SOIL BEARING
PRESSURE OF 22,000 PSF FOR NEW AND EXISTING SHALLOW
FOOTINGS SHALL BE USED. SHALLOW FOOTINGS SHALL BEAR
AT APPROXIMATELY 18'-9" BELOW GROUND/FIRST FLOOR LEVEL.
3. ALLOWABLE PIER FOUNDATION CAPACITY (WITH MIN. 2 FT
SOCKET INTO SHALE):
END BEARING ………………………………. 17,500 PSF
SKIN FRICTION ……………………………… 1,750 PSF
ALL DRILLED PIERS SHALL BE CASED AND ODOT PROTOCOL FOR
CONSTRUCTION OF DRILLED PIER MUST BE FOLLOWED.
4. AT BASEMENT FLOOR LEVEL, FLOOR SLABS SHALL BE
CONSTRUCTED ON COMPACTED MINIMUM 6 INCH THICK
DRAINABLE GRANULAR FILL PLACED ON TOP OF PROPERLY
PREPARED BEDROCK OR STRUCTURAL FILL, AS APPLICABLE.
5. AT GROUND / FIRST FLOOR LEVEL, GRADE BEAMS WITH VOID
FORMS SHALL BE CONSTRUCTED BY FORMING SIDES AND
SUPPLIED WITH SOIL RETAINERS. STRUCTURAL FLOOR SLAB ON
GRADE SHALL BE CONSTRUCTED WITH VOID FORMS AND
REINFORCING BAR SUPPORTED ON CHAIRS.
6. AFTER EXCAVATING, FOOTINGS SHOULD BE INSPECTED AND
CONCRETE PLACED AS QUICKLY AS POSSIBLE TO AVOID
EXPOSURE TO WETTING AND DRYING.
7. WATER SHOULD NOT BE ALLOWED TO COLLECT IN THE
EXCAVATIONS OR NEAR THE FOUNDATIONS AND FLOOR SLAB
AREAS OF THE BUILDINGS DURING CONSTRUCTION.
8. ALL VEGETATION, TOPSOIL, SOFT OR LOOSE SOIL, CONCRETE,
ASPHALT, OLD FOUNDATIONS AND DELETERIOUS MATERIALS
SHALL BE STRIPPED FROM THE BUILDING SITE. STRIPPING AND
UNDERCUTTING SHALL EXTEND A MINIMUM OF 5 FEET BEYOND
THE BUILDING PERIMETER AND THE DEPTH SHALL BE AS
DETERMINED BY THE GEOTECHNICAL ENGINEER.
9. AFTER STRIPPING THE SITE BUT PRIOR TO PLACING FILL THE
SITE SHALL BE PROOF ROLLED WITH A TANDEM AXLE DUMP
TRUCK (9 TONS/AXLE) OR SIMILAR RUBBER TIRED VEHICLE.
SOILS THAT RUT OR DEFLECT EXCESSIVELY (GREATER THAN 1
INCH) SHALL BE UNDERCUT AND RECOMPACTED IN PLACE OR
REPLACED WITH PROPERLY COMPACTED STRUCTURAL FILL.
THE RECOMPACTED SOIL OR ENGINEERED FILL SHALL BE
MOISTURE CONDITIONED DURING PLACEMENT.
10. AFTER PROOF ROLLING, THE SUBGRADE SOILS SHALL BE
SCARIFIED TO A DEPTH OF 8 INCHES, MOISTURE CONTENT
ADJUSTED TO WITHIN 2 PERCENT ABOVE THE OPTIMUM
MOISTURE CONTENT, AND COMPACTED TO 95 PERCENT OF THE
STANDARD PROCTOR MAXIMUM DRY DENSITY AS DEFINED BY
ASTM D698.
11. STRUCTURAL FILL MATERIAL SHALL BE PLACED IN LIFTS NOT
EXCEEDING 8 INCHES. EACH LIFT OF STRUCTURAL FILL
MATERIAL SHALL HAVE THE MOISTURE CONTENT ADJUSTED TO
WITHIN 3 PERCENT ABOVE THE OPTIMUM MOISTURE CONTENT,
AND COMPACTED TO 98 PERCENT OF THE STANDARD PROCTOR
MAXIMUM DRY DENSITY AS DETERMINED BY ASTM DESIGNATION
D698.
12. BACKFILL ALL TRENCHES AND EXCAVATIONS THAT UNDERMINE
OR ENCROACH ON FOUNDATIONS BEARING ON / IN SHALE PER
NOTE 11.
STEEL CONSTRUCTION NOTES:
1. ALL STRUCTURAL STEEL SHALL BE DETAILED,
FABRICATED, AND ERECTED IN ACCORDANCE WITH THE
APPLICABLE EDITIONS OF THE AISC "CODE OF STANDARD
PRACTICE FOR STEEL BUILDINGS AND BRIDGES" AND THE
AISC "SPECIFICATION FOR STRUCTURAL STEEL
BUILDINGS", AND AS SUPPLEMENTED BY THESE GENERAL
NOTES IN ADDITION TO THE PROJECT SPECIFICATIONS.
2. A REGISTERED PROFESSIONAL ENGINEER SHALL BE
RETAINED TO PROVIDE SIGNED AND SEALED CONNECTION
DESIGN DATA FOR BRACING CONNECTIONS AND ANY NON-
STANDARD CONNECTIONS NOT SHOWN IN THESE
CONSTRUCTION DOCUMENTS. DESIGN DATA FOR SIMPLE
SHEAR CONNECTIONS MAY BE SUBMITTED WITHOUT SEAL
AND SIGNATURE OF A PROFESSIONAL ENGINEER. ALL
CONNECTIONS SHALL BE DESIGNED FOR THE LOADINGS
GIVEN ON THESE CONSTRUCTION DOCUMENTS. ALL
DESIGN DATA SHALL BE SUBMITTED PRIOR TO OR WITH
THE STRUCTURAL STEEL SUBMITTALS.
3. CONNECTIONS SHALL BE DESIGNED FOR THE FACTORED
END REACTIONS, AXIAL LOADS AND END MOMENTS
SHOWN ON THE DRAWINGS. WHERE END REACTIONS ARE
NOT SHOWN, CONNECTIONS SHALL BE DESIGNED TO
SUPPORT ONE-HALF THE TOTAL UNIFORM LOAD CAPACITY
SHOWN IN THE " MAXIMUM TOTAL UNIFORM LOAD TABLES"
IN PART 3 OF THE AISC STEEL CONSTRUCTION MANUAL,
14TH EDITION, FOR THE GIVEN BEAM SIZE, SPAN AND
STEEL ASTM SPECIFICATION. THE MINIMUM DESIGN SHEAR
LOAD FOR ANY CONNECTION SHALL BE FOR 15 KIPS
(FACTORED), REGARDLESS OF THE BEAM END REACTIONS
SHOWN ON THE DRAWINGS.
4. ALL CONNECTION PLATES, STIFFENERS, AND BOLTS
SHOWN ON THE DRAWINGS ARE SCHEMATIC ONLY
UNLESS ACTUAL SIZES ARE SPECIFIED. CONTRACTOR
SHALL DESIGN ALL CONNECTIONS, SPLICES, PLATES,
GUSSET PLATES, STIFFENERS, BOLTS, AND WELDS FOR
FORCES INDICATED ON DRAWINGS IN ADDITION TO THE
REQUIREMENTS OF THE AISC DESIGN SPECIFICATION.
5. ALL STEEL CONNECTIONS, GUSSET AND WING PLATES
SHALL BE DESIGNED AND PROVIDED TO DEVELOP
FORCES INDICATED ON DRAWINGS. IN ALL CASES, A
MINIMUM 3/8" PLATE AND A MINIMUM OF (2) BOLTS SHALL
BE PROVIDED. PROVIDE STIFFENER PLATES FOR ALL
WELDED CONNECTIONS OR WING PLATES CONNECTED TO
WEB WHERE THE FORCE IS TRANSVERSE TO THE WEB OF
THE MEMBER WITH THE WING PLATES.
6. THE STEEL CONTRACTOR SHALL FURNISH ERECTION
BOLTS AS REQUIRED FOR FIELD CONNECTIONS.
7. ALL BEAMS THAT ARE REQUIRED TO HAVE CAMBER SHALL
BE FABRICATED WITH CAMBERS UPWARD. BEAMS
WITHOUT SPECIFIED CAMBER SHALL BE FABRICATED
SUCH THAT AFTER ERECTION ANY CAMBER DUE TO
ROLLING OR SHOP FABRICATION IS UPWARD.
8. ALL SHOP AND FIELD WELDS SHALL BE MADE IN
ACCORDANCE WITH THE ANSI/AWS "D1.1 STRUCTURAL
WELDING CODE - STEEL", APPLICABLE EDITION.
9. UNLESS NOTED OTHERWISE, ALL BOLTS SHALL BE ASTM
A325-N WITH SUITABLE WASHERS AND NUTS.
10. SUBSTITUTION OF EXPANSION ANCHORS FOR EMBEDDED
ANCHORS SHOWN ON THE DRAWING WILL NOT BE
PERMITTED.
11. CUTS, HOLES, COPING, ETC. REQUIRED FOR WORK OF
OTHER TRADES SHALL BE SHOWN ON THE SHOP
DRAWINGS AND MADE IN THE SHOP. CUTS OR BURNING
OF HOLES IN STRUCTURAL STEEL MEMBERS IN THE FIELD
WILL NOT BE PERMITTED.
12. ALL EXTENSION BARS, RUN-OFF PLATES, AND BACKING
BARS USED IN WELDED CONNECTIONS SHALL BE
REMOVED AND THE JOINTS SHALL BE GROUND SMOOTH
WHERE SUCH CONNECTION IS PERMANENTLY EXPOSED
TO VIEW OR IS DESIGNATED AS ARCHITECTURALLY
EXPOSED STRUCTURAL STEEL (AESS). REFER TO
ARHITECTURAL DRAWINGS FOR ALL LOCATIONS
REQUIRING AESS.
13. THE ERECTION CONTRACTOR SHALL SURVEY ANCHOR
RODS AND REPORT ANY DISCREPANCIES FROM THE
CONTRACT DOCUMENTS TO THE ARCHITECT-ENGINEER.
ALL CORRECTIONS TO WORK MUST BE APPROVED IN
WRITING BY THE ARCHITECT-ENGINEER PRIOR TO THE
START OF ERECTION.
14. ALL STRUCTURAL STEEL EMBEDDED IN CONCRETE AND
NOT INSIDE THE BUILDING CONDITIONED ENVELOPE,
SHALL BE HOT-DIPPED GALVANIZED, UNLESS NOTED
OTHERWISE.
15. ALL ADDITIONAL FRAMING REQUIRED TO SUPPORT OR
BRACE MECHANICAL OR ELECTRICAL EQUIPMENT OR
PIPING NOT SHOWN ON THE STRUCTURAL DRAWINGS
SHALL BE SUPPLIED BY THE MECHANICAL OR ELECTRICAL
CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.
CONCRETE CONSTRUCTION NOTES:
1. ALL DETAILING, FABRICATION AND PLACING OF REINFORCING BARS,
UNLESS NOTED OTHERWISE, SHALL FOLLOW THE LATEST EDITION ACI
DETAILING MANUAL, DETAILS AND DETAILING OF CONCRETE
REINFORCEMENT, ACI MANUAL OF ENGINEERING AND PLACING DRAWINGS
FOR REINFORCED CONCRETE STRUCTURES, ACI SPECIFICATIONS FOR
STRUCTURAL CONCRETE FOR BUILDINGS AND THE PROVISIONS OF ACI
"BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE" (ACI 318-
APPLICABLE EDITION).
2. UNLESS NOTED OTHERWISE, LAP SPLICES OR EMBEDMENT LENGTHS
SHALL CONFORM TO ACI REQUIREMENTS FOR CLASS B SPLICES. REFER
TO REINFORCEMENT LAP LENGTH SCHEDULE.
3. UNLESS NOTED OTHERWISE, CONCRETE COVER OVER STEEL
REINFORCEMENT SHALL CONFORM TO MINIMUM REQUIRED BY ACI 318-
APPLICABLE EDITION.
4. AT INTERSECTING FOUNDATIONS AND WALLS EXTEND ALL HORIZONTAL
REINFORCING OF THE INTERSECTING MEMBER BEYOND THE POINT OF
INTERSECTION TO THE OPPOSITE FACE AND BEND TO A STANDARD 90
DEGREE HOOK, OR PROVIDE BENT DOWELS OF EQUAL SIZE AND SPACING
AND LAP AS REQUIRED BY NOTE 2 (BUT NOT LESS THAN 24") IN EACH
DIRECTION. REFER TO TYPICAL CONCRETE PLAN DETAIL.
5. PROVIDE CORNER BARS IN BOTH FACES OF ALL EXTERIOR BEAMS AND
WALLS. NUMBER, SIZE AND SPACING OF CORNER BARS SHALL BE EQUAL
TO NUMBER, SIZE AND SPACING OF HORIZONTAL REINFORCING WITH
WHICH THEY LAP AND SHALL EXTEND 40 BAR DIAMETERS IN EACH
DIRECTION. IF REINFORCING MEETING AT THE CORNER IS OF DIFFERENT
SIZE, CORNER BAR SHALL MATCH THE LARGER OF THE BARS. BOTH LEGS
OF CORNER BARS SHALL BE EQUAL LENGTH. REFER TO CONCRETE PLAN
DETAIL.
6. TOP STEEL REINFORCING OF FOOTINGS SHALL PASS THROUGH THE
CONFINED CORE OF THE COLUMN FOOTING. BOTTOM STEEL
REINFORCING OF FOOTINGS SHALL PASS THROUGH THE CONFINED
CORE OF THE COLUMN FOOTING. FOOTING TIE/STIRRUPS SHALL START
WITHIN 3" OF FACE OF COLUMN FOOTING.
7. ALL OPENINGS IN CONCRETE WALLS AND ELEVATED SLABS LARGER THAN
1'-0" ON ANY SIDE OR DIAMETER SHALL HAVE A MINIMUM OF (2) #5 BARS (1
EACH FACE) PLACED AT ALL FOUR SIDES OF THE OPENING AND
EXTENDED 2'-6" BEYOND THE EDGE OF OPENING. CORNERS OF ANY SIZE
OPENING SHALL BE REINFORCED WITH (2) #5X5'-0" DIAGONAL BARS (1
EACH FACE).
8. ALL REINFORCING SHALL BE SUPPORTED FROM THE INTERIOR OF THE
CONCRETE ELEMENTS. PROVIDE ALL STANDS REQUIRED TO ADEQUATELY
HOLD REINFORCEMENT IN PLACE DURING CONCRETE PLACEMENT.
9. A SINGLE CONCRETE POUR, FOR GRADE BEAMS, CONTINUOUS FOOTINGS
AND WALLS SHALL NOT EXCEED 60 FEET NOR 45 FEET FOR TRENCHES.
CONSTRUCTION JOINTS SHALL BE LOCATED BETWEEN 1/4 POINT AND 1/3
POINT OF A SPAN, WHERE A SPAN IS ASSUMED TO BE THE COLUMN
SPACING. REFER BULKHEAD DETAIL.
10. PROVIDE SLEEVES IN BEAMS, SLABS AND WALLS FOR ALL PENETRATIONS
(DO NOT DRILL). LOCATIONS MUST BE APPROVED BY ARCHITECT-
ENGINEER. PIPE PENETRATIONS THROUGH GRADE BEAMS SHALL NOT
INTERRUPT THE LONGITUDINAL REINFORCEMENT OF THE GRADE BEAMS.
GRADE BEAM PENETRATIONS NEAR PIER SUPPORTS ARE NOT PERMITTED.
11. POST INSTALLED DOWELS AND ANCHORS INTO CONCRETE SHALL USE
HILTI HIT-HY200 OR APPROVED EQUAL, UNLESS NOTED OTHERWISE.
SUBSTITUTION REQUESTS SHALL PROVIDE CALCULATIONS
DEMONSTRATING THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING
THE PERFORMANCE VALUES OF THE SPECIFIED PRODUCT UNDER THE
CONDITIONS OF THE PROJECT. SUBSTITUTION REQUESTS SHALL
FURTHER DEMONSTRATE PRODUCT APPLICABILITY BY ICC ESR SHOWING
COMPLIANCE WITH THE RELEVANT BUILDING CODE FOR SEISMIC USE,
LOAD RESISTANCE, INSTALLATION CATEGORY, AND ANY OTHER RELEVANT
PROJECT CONDITIONS.
12. UNLESS NOTED OTHERWISE ON ARCHITECTURAL DRAWINGS, PROVIDE
3/4" CHAMFER ON ALL EXPOSED CONCRETE EDGES.
13. PROVIDE CONCRETE EQUIPMENT PADS OF SIZE REQUIRED FOR
EQUIPMENT FURNISHED. SEE MECHANICAL AND ELECTRICAL DRAWINGS
FOR NUMBER, SIZE AND LOCATION OF SUCH PADS ON THE FLOOR SLAB
UNLESS OTHERWISE SHOWN. MINIMUM THICKNESS SHALL BE 4". MINIMUM
REINFORCING SHALL BE #4 BARS AT 12" ON CENTER EACH WAY. TOOL OR
CHAMFER ALL PAD EDGES.
14. THE SIZE AND LOCATION OF ALL EQUIPMENT PADS, FLOOR PITS, TRENCH
DRAINS AND OPENINGS FOR ALL DUCTS AND PIPES THROUGH FLOOR
SLABS AND FOOTINGS SHALL BE VERIFIED WITH THE MECHANICAL AND
ELECTRICAL CONTRACTORS REQUIREMENTS PRIOR TO PLACEMENT.
15. ALL JOINTS IN PITS AND TRENCHES SHALL BE KEYED. WATERSTOPS
SHALL BE INSTALLED IN ALL CONSTRUCTION JOINTS. ALL PITS AND
TRENCHES SHALL BE WATER-PROOFED.
16. ALL CONCRETE SLAB ACCESSORIES (TRENCHES, GRATING, EMBEDDED
ITEMS, ETC.) SHALL BE DESIGNED FOR THE UNIFORM AND
CONCENTRATED LIVE LOADS ON THIS SHEET.
17. LOCALLY SLOPE THE SLAB TO FLOOR DRAINS WITH AN 18" RADIUS
AROUND THE DRAIN BODY. REFER PLUMBING FOR ADDITIONAL FLOOR
DRAIN INFORMATION.
18. REFER TO THE PLUMBING SPECIFICATIONS FOR THE USE OF SLEEVES
AND SEALANTS AT PLUMBING PENETRATIONS THROUGH THE SLAB ON
GRADE.
19. PROVIDE BOLLARDS AS REQUIRED BY ARCHITECTURAL SHEETS.
STEEL DECK NOTES:
1. NORMAL WEIGHT CONCRETE SLABS ON COMPOSITE STEEL
DECK SHALL UTILIZE REINFORCEMENT AT MID-DEPTH OF
THE SLAB, AS INDICATED ON THE PLANS UNLESS NOTED
OTHERWISE.
2. AT ROOF LEVELS, THE DECK SHALL BE ATTACHED TO
SUPPORTS WITH #12 TEKS AT 6 INCHES ON CENTER WITH #
10 TEKS SIDELAP SCREWS AT 12 INCHES ON CENTER. AT
FLOOR LEVELS, THE COMPOSITE DECK SHALL BE
ATTACHED TO SUPPORTS WITH INCH PUDDLE WELDS AT
12 INCHES ON CENTER WITH #10 TEKS SIDELAP FASTENERS
AT 24 INCHES ON CENTER.
3. ALL STEEL DECK SHALL SPAN A MINIMUM OF (3) SPANS IN
THE DIRECTION SHOWN ON THE FRAMING PLANS.
4. ROOF STEEL DECK SHALL CONSIST OF 20 GAGE, 1 1/2 INCH
WIDE RIB GALVANIZED DECKING (TYPE B) WITH RIB
SPACING AT 6 INCHES ON CENTER. PROPERTIES SHALL
MEET OR EXCEED THE SDI SPECIFIED MINIMUM.
5. COMPOSITE STEEL DECK SHALL CONSIST OF 20 GAUGE,
1 1/2 INCH GALVANIZED COMPOSITE DECKING (VL) WITH RIB
SPACING AT 6 INCHES ON CENTER. PROPERTIES SHALL
MEET OR EXCEED THE SDI SPECIFIED MINIMUM.
6. DECK FOR FLOOR OPENINGS LARGER THAN 6" IN ANY
DIRECTION (INCLUDING AT SLAB BLOCKOUT AND PIPE
SLEEVE LOCATIONS), SHALL NOT BE CUT UNTIL THE
CONCRETE THAT IS SUPPORTED BY THE DECK HAS CURED
FOR A MINIMUM OF 7 DAYS.
7. IN ADDITION TO THE ATTACHMENT AT SUPPORTING BEAMS
AND JOIST, THE SPECIFIED DECK ATTACHMENT APPLIES AT
BENT PLATES AND ANGLES IN CONTACT WITH THE DECK.
CONSTRUCTION NOTES:
1. ALL DIMENSIONS TO EXISTING STRUCTURES MUST BE
VERIFIED IN THE FIELD BY THE CONTRACTOR AS REQUIRED
FOR NEW CONSTRUCTION.
2. ALL INTERFERING PIPES, UTILITIES, AND FIXTURES WILL BE
RELOCATED BY CONTRACTOR AS REQUIRED.
3. THE CONTRACTOR SHALL PROVIDE AND INSTALL ALL
SHORING, PROPS, AND GUYS REQUIRED FOR THE
TEMPORARY SUPPORT OF THE EXISTING STRUCTURE AND
REMOVE SAME AFTER COMPLETION.
4. THE CONTRACTOR IS HELD RESPONSIBLE FOR
PROTECTION OF PERSONNEL AND EQUIPMENT DURING THE
COURSE OF OPERATIONS ACCORDING TO CURRENT
SAFETY REGULATIONS.
5. THE CONTRACTOR SHALL SUBMIT TO THE ENGINEER
COPIES OF ALL SHOP DRAWINGS OF NEW WORK FOR
APPROVAL.
6. THE CONTRACTOR SHALL REPAIR ALL EXISTING WORK
WHICH HAS BEEN DAMAGED BY HIS CONSTRUCTION
OPERATIONS AND REMOVE ALL DEBRIS FROM THE SITE
AFTER COMPLETION OF THE PROJECT.
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
TIENG
AI LING
21544 O K L A H O M A
RE
G
IS
T E
RE
D PROFESSIONAL ENG
INEER
/1
9/
6:
:2
PM
C :\U se rs
\ta l\D oc um en ts
\M y
Re vi t\6
_S tru c_ ta l.r vt
GENERAL NOTES
TAL
BJW
TAL 37
S-001
S-001
SOIL RETENTION SYSTEM NOTES:
1. THE CONTRACTOR SHALL DESIGN, UTILIZING A PROFESSIONAL
ENGINEER REGISTERED IN THE STATE WHERE THE PROJECT
IS LOCATED, A SOIL RETENTION SYSTEM ACCORDING TO THE
SCHEMATIC DIMENSIONS, DETAILS AND LOCATIONS SHOWN ON
THE PLANS. THE SOIL RETENTION SYSTEM SHALL BE
INSTALLED IN STRICT CONFORMANCE WITH THE DESIGN. THE
SIGNED AND SEALED RETENTION SYSTEM DESIGN SHALL BE
SUBMITTED FOR RECORD PURPOSES ONLY.
2. THE BASIS OF DESIGN SHALL AT A MINIMUM UTILIZE THE
INFORMATION CONTAINED IN THE PROJECT GEOTECHNICAL
ENGINEER'S LETTER OF ADDITIONAL INFORMATION (PROJECT
NO. 731-13165) DATED AUGUST 16, 2016 PREPARED FOR THIS
PROJECT BY BURGESS ENGINEERING AND TESTING INC, 809
NW 34TH STREET, MOORE OK 73160, PHONE NO.: (405) 790-
0488.
3. THE CONTRACTOR SHALL VERIFY LOCATIONS OF ALL
UNDERGROUND UTILITIES BEFORE INSTALLING ANY OF THE
SOIL RETENTION SYSTEM COMPONENTS OR COMMENCING
ANY EXCAVATION. ANY DISTURBANCE OR DAMAGE TO
EXISTING STRUCTURES, UTILITIES OR OTHER PROPERTY,
CAUSED BY THE CONTRACTOR’S OPERATION, SHALL BE
REPAIRED BY THE CONTRACTOR IN A MANNER SATISFACTORY
TO THE ARCHITECT / ENGINEER AT NO ADDITIONAL COST TO
THE OWNER.
4. THE SOIL RETENTION SYSTEM SHALL BE INSTALLED IN STRICT
CONFORMANCE WITH THE CONTRACTOR’S DESIGN PRIOR TO
COMMENCING ANY RELATED EXCAVATION. IF UNABLE TO
INSTALL THE SOIL RETENTION SYSTEM AS DESIGNED AND
SUBMITTED, THE CONTRACTOR SHALL HAVE THE ADEQUACY
OF THE DESIGN RE-EVALUATED. ANY RE-EVALUATION AND
MODIFICATION TO THE SUBMITTED DESIGN SHALL BE
RESUBMITTED FOR RECORD PURPOSES.
5. WHEN ALLOWED, THE CONTRACTOR MAY ELECT TO CUT OFF A
PORTION OF THE SOIL RETENTION SYSTEM LEAVING THE
REMAINDER IN PLACE. THE REMAINING SOIL RETENTION
SYSTEM SHALL NOT INTERFERE WITH THE NEW
CONSTRUCTION. REMOVED SYSTEM COMPONENTS SHALL
BECOME THE PROPERTY OF THE CONTRACTOR.
6. IF AN OBSTRUCTION IS ENCOUNTERED, THE CONTRACTOR
SHALL NOTIFY THE A/E. THE CONTRACTOR SHALL BREAK UP,
PUSH ASIDE, OR REMOVE THE OBSTRUCTION. AN
OBSTRUCTION SHALL BE DEFINED AS ANY OBJECT (SUCH AS
BUT NOT LIMITED TO, BOULDERS, LOGS, OLD FOUNDATIONS
ETC.) WHERE ITS PRESENCE WAS NOT OBVIOUS OR
SPECIFICALLY NOTED ON THE PLANS PRIOR TO BIDDING. THIS
CONDITION SHALL BE TREATED AS AN “UNKNOWN” CONDITION
AND SHALL BE DEALT WITH ACCORDING TO THE CONTRACT
FOR UNKNOWN CONDITIONS.
7. FLUTES OF THE EXPOSED RETENTION SYSTEM SHALL BE
FILLED WITH LAYERS OF STYROFOAM LAMINATED TO THE
CONTOUR OF THE FLUTE. THIS STYROFOAM LAYER IS TO
PROVIDE A FLAT SURFACE FOR THE INSTALLATION OF
WATERPROOFING MATERIAL BETWEEN THE CONCRETE WALL
AND THE RETENTION SYSTEM.
STRUCTURAL METAL STUD NOTES
1. STRUCTURAL METAL STUDS ARE DEFINED AS STEEL STUDS
USED IN EXTERIOR WALL FRAMING, ROOF FRAMING, INTERIOR
LOAD BEARING AND SHEAR WALLS, AND FASCIA/SOFFIT
FRAMING.
2. STRUCTURAL METAL STUDS SHALL CONFORM TO SSMA (STEEL
STUD MANUFACTURERS ASSOCIATION) CRITERIA.
3. STRUCTURAL METAL STUD MATERIAL SHALL HAVE THE
FOLLOWING MINIMUM PROPERTIES FOR EXTERIOR WALLS:
600S162-54 (16 GA)
A = 0.556 IN^2, Ixx = 2.86 IN^4 Sx = 0.953 IN^3, Fy = 50 KSI (MIN)
4. BRIDGING SHALL BE INSTALLED AS REQUIRED BY THE
MANUFACTURER, BUT NOT SPACED MORE THAN 4'-0" ON
CENTER.
5. ALL WELDING SHALL CONFORM TO THE PROVISIONS OF AWS
D1.1 AND ANSI/AWS D1.3. WHERE THE WELD THROAT IS NOT
SHOWN ON THE DRAWINGS, THE WELD SHALL BE AT LEAST AS
LARGE AS THE THICKNESS OF THE THINNEST SHEET JOINED.
ALL WELDS SHALL PROVIDE COMPLETE FUSION OF THE
SHEETS WITHOUT "BLOWOUTS."
6. AT TRACK BUTT JOINTS, ABUTTING PIECES OF TRACK SHALL BE
SECURELY ANCHORED TO A COMMON STRUCTURAL ELEMENT
OR THEY SHALL BE SPLICE WELDED TOGETHER.
ACI AMERICAN CONCRETE INSTITUTE
ADD'L ADDITIONAL
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
ANCH ANCHOR
AR ANCHOR ROD
ARCH ARCHITECTURAL
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASD ALLOWABLE STRESS DESIGN
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
AT/FP ANTI-TERRORISM FORCE PROTECTION
AWS AMERICAN WELDING SOCIETY
BM BEAM
BO BOTTOM OF
BOS BOTTOM OF STEEL
BOT BOTTOM
BP BASE PLATE
BR BRACING
BRG BEARING
BTWN BETWEEN
CJ CONSTRUCTION JOINT
CENTER LINE
CL CENTER LINE
CL COLLATERAL LOAD
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONNX CONNECTION
CONT CONTINUOUS
COORD COORDINATE
CR CENTER OF RADIUS
DBA DEFORMED BAR ANCHOR
DBE DECK BEARING ELEVATION
DEG DEGREE
DEMO DEMOLISH, DEMOLITION
db DIAMETER BAR
DIA DIAMETER
DIM DIMENSION
DL DEAD LOAD
DN DOWN
DTL DETAIL
DWLS DOWELS
EA EACH
EE EACH END
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
ELEV ELEVATION
EQ EQUAL
EQUIV EQUIVALENT
EW EACH WAY
EXP EXPANSION
EXST EXISTING
EXIST EXISTING
ºF/C DEGREES FAHRENHEIT/CELSIUS
FF FINISH FLOOR
FFE FINISHED FLOOR ELEVATION
FIN FINISH
FLR FLOOR
FLG FLANGE
FND FOUNDATION
FT FOOT/FEET
FTG FOOTING
FS FAR SIDE
GA GAGE
GALV GALVANIZED
GB GRADE BEAM
HORIZ HORIZONTAL
IBC INTERNATIONAL BUILDING CODE
IN INCH/INCHES
JB JOIST BEARING
JST JOIST
JT JOINT
LBS POUNDS
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG LONGITUDINAL
LRFD LOAD AND RESISTANCE FACTOR DESIGN
LSH LONG SIDE HORIZONTAL
LSSH LONG SLOTTED HOLES
MBM METAL BUILDING MANUFACTURER
MFR MANUFACTURER
MAT'L MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFG MANUFACTURER
MIN MINIMUM
MPH MILES PER HOUR
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTER
OH OPPOSITE HAND
OPNG OPENING
OVS OVERSIZED
PERIM PERIMETER
PL PLATE
± , +/- PLUS/MINUS
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POINT
REF REFER
REINF REINFORCE/REINFORCING
ABBREVIATIONSREINFORCED MASONRY NOTES:
1. ALL CMU SHALL BE 1 OR 2-CELL BLOCK.
2. MASONRY DESIGN STRENGTH, F’m = 2,000 PSI. MINIMUM NET
AREA COMPRESSIVE STRENGTH OF CONCRETE MASONRY UNIT
SHALL BE 2,800 PSI.
3. MINIMUM MORTAR COMPRESSIVE STRENGTH SHALL BE 1,800 PSI
AT 28 DAYS.
4. VERTICAL CELLS TO BE FILLED SHALL HAVE VERTICAL
ALIGNMENT SUFFICIENT TO MAINTAIN A CLEAR UNOBSTRUCTED
CONTINUOUS VERTICAL CELL NOT LESS THAN 2 INCHES BY 3
INCHES IN PLAN DIMENSION.
5. SLAB DOWELS SHALL BE INSTALLED PER THE CMU DETAILS.
6. LOCATION OF CONTROL JOINTS SHALL BE AS SHOWN ON CMU
ELEVATION SHEETS AND DETAILS OF CONTROL JOINTS SHALL BE
AS SHOWN, REFER TO TYPICAL MASONRY DETAILS.
7. REFER TO ARCHITECTURAL DRAWINGS FOR ALL CMU WALL
INFORMATION NOT SHOWN IN STRUCTURAL.
8. VERTICAL WALL REINFORCING SHALL USE THE BARS AS
REQUIRED IN THE MASONRY WALL SCHEDULE. VERTICAL
REINFORCING SHALL EXTEND CONTINUOUSLY FROM THE TOP OF
THE SLAB TO EMBED AT LEAST 6 INCHES INTO FLOOR OR ROOF
DIAPHRAGM BOND BEAM. LAP SPLICES OF 60 BAR DIAMETERS
ARE PERMITTED. DIAPHRAGM BOND BEAMS SHALL BE DEFINED
AS THE BOND BEAM AT THE FLOOR/ROOF LEVEL OR WHERE
ANGLE KICKERS ARE PROVIDED.
9. BOND BEAM REINFORCING SHALL USE THE BARS AS REQUIRED
IN THE MASONRY WALL SCHEDULE AND SHALL RUN
CONTINUOUS THROUGHOUT. CORNER BARS SHALL BE
PROVIDED AND LAP SPLICES OF 40 BAR DIAMETERS ARE
PERMITTED. BOND BEAMS SHALL EXIST AT THE BOTTOM, TOP,
AND INTERMEDIATE (EVERY 6TH COURSE OR CLOSER PER
DETAILS). COORDINATE WITH ARCHITECTURAL REQUIREMENTS.
10. AN ADDITIONAL VERTICAL BAR OF THE SAME SIZE AND LENGTH
AS THE NORMAL REINFORCING BAR SHALL BE PLACED:
A. ON EACH SIDE OF CONTROL JOINTS
B. AT ALL WALL INTERSECTIONS OF EXTERIOR WALLS
C. AT ALL DISCONTINUOUS EDGES
D. AT ALL DOOR AND WINDOW JAMS
E. AS SHOWN ON STRUCTURAL DRAWINGS
11. CMU LINTELS SHALL USE THE BARS AS REQUIRED PER TYPICAL
CMU WALL OPENING DETAIL AND CMU LINTEL TYPES, UNLESS
NOTED OTHERWISE. ALL OPENINGS GREATER THAN 2 FEET
SHALL HAVE A LINTEL.
12. CELLS WHICH CONTAIN REINFORCING STEEL SHALL BE FILLED
SOLIDLY WITH 3,000 PSI COARSE GROUT MEETING THE
REQUIREMENTS OF ASTM C476.
13. POST-INSTALLED DOWEL OR ANCHOR APPLICATIONS INTO
GROUTED MASONRY SHALL USE HILTI HY-70 OR APPROVED
EQUAL, UNLESS NOTED OTHERWISE. SUBSTITUTION REQUESTS
SHALL PROVIDE CALCULATIONS DEMONSTRATING THE
SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING THE
PERFORMANCE VALUES OF THE SPECIFIED PRODUCT UNDER
THE CONDITIONS OF THE PROJECT. SUBSTITUTION REQUESTS
SHALL FURTHER DEMONSTRATE PRODUCT APPLICABILITY BY
ICC ESR SHOWING COMPLIANCE WITH THE RELEVANT BUILDING
CODE FOR SEISMIC USE, LOAD RESISTANCE, INSTALLATION
CATEGORY, AND ANY OTHER RELEVANT PROJECT CONDITIONS.
MISCELLANEOUS NOTES:
1. REFERENCE DATUM ELEVATION 100'-0" IS EQUAL TO THE
ACTUAL FINISH FLOOR ELEVATION PROVIDED BY CIVIL.
REFERENCED ELEVATIONS ARE BASED ON THIS DATUM
ELEVATION.
2. GENERAL NOTES AND TYPICAL DETAILS APPLY TO THE ENTIRE
PROJECT AND CONVEY ENGINEERING INTENT. SPECIFIC
DETAILS ARE NOT DRAWN FOR EVERY CONDITION OF
CONSTRUCTION OR ASSEMBLY. MANY CONDITIONS SIMILAR TO
THOSE DEPICTED EXIST AND THOSE SIMILAR CONDITIONS ARE
INCLUDED IN THE CONTRACT SCOPE OF WORK. THE
CONTRACTOR SHALL INCLUDE COST OF THE WORK FOR THESE
SIMILAR CONDITIONS. FUTURE CLARIFICATION OF DETAILS
SHALL NOT BE THE BASIS OF ADDITIONAL COMPENSATION FOR
THE CONTRACTOR.
REQ'D REQUIRED
SCHED SCHEDULE
SDI STEEL DECK INSTITUTE
SF SQUARE FEET
SIM SIMILAR
SJ SAWCUT JOINT
SJI STEEL JOIST INSTITUTE
SL SNOW LOAD
SPEC SPECIFICATION
SSLT SHORT SLOTTED HOLES
SSMA STEEL STUD MANUFACTURERS
ASSOCIATION
STD STANDARD
STIFF STIFFENER
STL STEEL
SW SHEAR WALL
TO TOP OF
TOF TOP OF FOUNDATION/FOOTING
TOS TOP OF STEEL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
W/ WITH
W/O WITHOUT
WL WIND LOAD
WP WORKING POINT
WWF WELDED WIRE FABRIC
WWR WELDED WIRE REINFORCEMENT
ABBREVIATIONS (CONT.)
8" Ø STD WEIGHT PIPE
(CONCRETE FILLED) 4'-0"
PROJECTION ABOVE SLAB
CONCRETE SLIGHTLY
ROUNDED
NOTES:
1. POST TO BE PRIMED PRIOR TO SETTING IN CONCRETE.
2. TOP OF BLOCKOUT.
3. SURFACE SHALL MATCH SURROUNDING SURFACE
IN COLOR, TEXTURE, AND TREATMENT.
4. COORDINATE LOCATIONS WITH ARCHITECTURAL.
FINISH BLOCKOUT TO MATCH SLAB
4" C
LR
2'-0"
BOLLARD
BLOCKOUT 2'-0"
TOP OF
EXISTING SLAB
CENTER POST
IN CONCRETE
CONCRETE
ENCASEMENT
TOP OF EXISTING SLAB
VARIES
SUPPORTING MEMBER
OPENING
SUPPORTING MEMBER
L4x3x1/4 LLV FOR SPANS TO 4'-0" L5x3x1/4 LLV FOR SPANS > 4'-0" < 6'-0"
L6x4x3/8 LLV FOR SPANS > 5'-0" < 8'-0" L5x3x1/4 LLV FOR SPANS TO 5'-0"
NOTES:
1. DECK TO BE FASTENED TO ALL ANGLES.
2. PROVIDE ANGLE FRAME FOR ALL OPENINGS
LARGER THAN 6" IN ANY DIRECTION.
L3x3x1/4x0'-4"
(WELD TO SUPPORTING MEMBER)
WELD ALL EXPOSED SURFACES
TYPICAL FOR ROOF OPENING
FRAMES INSTALLED AFTER
STEEL DECK IS IN PLACE
TYP FOR ROOF OPENING
FRAMES INSTALLED BEFORE
STEEL DECK IS IN PLACE 3/16
3/16
TYP
3/16 3/16
TYP
1/4
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
TIENG
AI LING
21544 O K L A H O M A
RE
G
IS
T E
RE
D PROFESSIONAL ENG
INEER
/1
9/
6:
:5
PM
C :\U se rs
\ta l\D oc um en ts
\M y
Re vi t\6
_S tru c_ ta l.r vt
GENERAL NOTES
TAL
BJW
TAL 38
S-002
S-002
SCALE: NTS
2 TYPICAL BOLLARD DETAIL
SCALE: NTS
1 ROOF FRAMED OPENING
DECK BELOW REFER
TO SCHEDULE
EDGE
EDGE
REFER TO PLAN NOTE
FOR FASTENER TYPE
AND SPACING AT SUPPORT
CENTERLINE OF
SUPPORT MEMBER
BELOW REFER TO
FRAMING PLAN
NOTE: 5/8" PUDDLE WELD 6" OC AT EDGE
SIDELAP FASTENER
TYPE AND SPACING
REFER PLAN NOTES
36" COVERAGE
36/7
PATTERN
TYPE "1"
TYPE "2"
FLOOR DECK
5/8" PUDDLE
WELD AT 12" OC
AT SUPPORTS
#12 TEK SCREWS
AT 6" OC AT
SUPPORTS
ROOF DECK
1.5B
36" COVERAGE
36/4
PATTERN
1.5VL
TRANSVERSE SLAB STEEL
VAPOR RETARDER
REFER SPECIFICATIONS
CUT 3" OUT OF
EVERY OTHER BAR
AT SAW JOINT
LONGITUDINAL
SLAB STEEL
REFER SLAB
PLAN
SEALANTNOTE:
SAW JOINT WITHIN 8 HOURS
AFTER CONCRETE IS PLACED
1/8"
3/ 4"
A T
3" S
LA
B
1/
4" A
T 5"
S
LA
B
MAXIMUM
1 1/2" CLEAR
1" A
T 3"
S
LA
B 2"
A T
5" S
LA
B
R
EF
ER
PL
AN
AT SLABS WITH
FLOOR DRAINS
USE ASTM D1
190 SEALANT
1/8" RADIUS TOOLED
JOINT AT EXPOSED
FLOOR SLABS WITHOUT
FLOOR DRAINS
REF SLAB PLAN
1/4" RADIUS
TOOLED JOINT
GROOVE MAY
BE FORMED
OR SAWED
FORMED JOINT
WITH ZIP STRIPS
3/
4"
7/8"
"T "R
E F
PL
AN
5/8"
7/ 8"
T/
C
LR
EQ
2"
EQ
NOTE:
CONSTRUCTION JOINTS
REQUIRED AT SLAB
COLD JOINTS.
SEALANT
FORMED JOINT
VAPOR RETARDER
REFER SPECS
DIAMOND
PLATE DOWELS
3/8" THICK BY
4 1/2" SQUARE
AT 12" OC
1/4" SAW CUT
1/
4" A
T 5"
S
LA
B
2" A
T 8"
S
LA
B
REF SLAB PLAN
3" A
T 8"
S
LA
B 2"
A T
5" S
LA
B
R
EF
ER
PL
AN
MAXIMUM
3" CLEAR
REFER FOUNDATION
SECTIONS FOR
REINFORCING
INFORMATION
LAPPED TOP BAR
FROM ADJACENT SPAN
LOCATE POUR JOINTS
BETWEEN QUARTER
AND THIRD POINTS OF
CONTINUOUS FOOTING
SPAN
D /3
D /3
D /3
1"
2" 2"
1/
4"
(R
EF
ER
PL
A N
"D
NOTE:
BARS MAY BE CONTINUOUS
ACROSS MORE THAN ONE SPAN.
REFER SCHEDULE FOR GREATER TOP
REINFORCEMENT OF SPANS L1 AND L2
FIRST STIRRUP 3" FROM
FACE OF SUPPORT, UNO
PROVIDE STD
HOOK, TYP
DRILLED PIER
TYPICAL
REFER SCHEDULE
FOR BOTTOM
REINFORCING
FACE OF SUPPORT
FOR ROUND PIER
TYPICAL
FIRST STIRRUP 3" FROM
FACE OF SUPPORT
END OF CLEAR SPAN
TYPICAL
INTERIOR CLEAR SPAN
TYPICAL
INTERIOR CLEAR SPAN
TYPICAL
STIRRUPS SPACED AS SCHEDULED
TYPICAL U.N.O.
WIDTH
D
EP
TH
3" CLR
2" C
LR
3" CLR
A - BARS
B - BARS
STIRRUPS
ELEVATION
SECTION
L1 L2 L3
EQ. EQ.
SPLICE
CLASS B
SPLICE
CLASS B
SPLICE
CLASS B
SPLICE
CLASS B
FACE OF PIER CAP
FACE OF SUPPORT =
0.45 X PIER Ø OR TO
PIER CAP
0.89 X PIER Ø
OR WIDTH OF
TY
P
IC
AL
3" C
LE
AR
TY
P, U N
O 2"
C
LR
LINTEL TYPE 1
40db BEYOND
OPENING, TYP
MINIMUM OF (1) #5
BAR OR LARGER (TYP)
CASE 1
MINIMUM OF (1) #6
OR LARGER (TYP)
AT EACH CELL
LINTEL TYPE 2
CASE 2
LINTEL TYPE 3
CASE 3
LINTEL TYPE 3
MINIMUM OF (1) #7
BAR OR LARGER
AT EACH CELL
CASE 4
NOTES:
CASE 1 APPLIES TO: ALL OPENINGS 2 FEET OR LESS
EITHER DIRECTION.
CASE 2 APPLIES TO: ALL OPENINGS EXCEEDING 2 FEET
BUT NOT MORE THAN 4 FEET EITHER
DIRECTION.
CASE 3 APPLIES TO: ALL OPENINGS EXCEEDING 4 FEET
BUT NOT MORE THAN 5 FEET EITHER
DIRECTION.
CASE 4 APPLIES TO: ALL DOOR OPENINGS EXCEEDING 5 FEET
BUT NOT MORE THAN 6 FEET IN WIDTH
AND NOT EXCEEDING 8 FEET IN HEIGHT.
1. WHERE VERTICAL REINFORCING CONSISTS OF (2) BARS
OR MORE, EACH BAR SHALL BE PLACED IN A SEPARATE CELL.
2. REFER TO DETAIL 6 ON THIS SHEET FOR LINTEL TYPES.
EXTEND REINFORCING 40 db BEYOND OPENING, TYPICAL.
3. PROVIDE DOWELS (REF 5/SB501) AT VERTICAL REINFORCING
AT DOOR OPENINGS. VERTICAL REINFORCING SHALL SPAN
THE FULL HEIGHT OF THE WALL.
MIN1 1/2
2"
(2)-#4X4'-0", TYP
BEND ENDS OF REBAR
AS REQ'D TO CLEAR
OBSTRUCTION
EDGE OF SLAB
AT RE-ENTRANT
CORNER
1/
2" 2"
(2)-#4X4'-0" CENTERED AT
CORNER OF JOINT , TYP
BLOCKOUT JOINTS
AT SLAB ON
GRADE
CJ CJ
SOLID BOTTOM LINTEL UNIT SOLID BOTTOM LINTEL UNIT
#3 AT 6" OC
STD 180° HOOK
TYPICAL AT TOP
SOLID BOTTOM LINTEL UNIT
NOM
8"
(2) #6 BARS(2) #6 BARS
NOM
8"
N O
M
8"
3"
N O
M
IN
AL
1' -4
3"
(2) #6 BARS
N O
M
IN
AL
2' -0
3" 3"
NOM
8"
(2) #6 BARS
LINTEL TYPE 1 LINTEL TYPE 2 LINTEL TYPE 3
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
TIENG
AI LING
21544 O K L A H O M A
RE
G
IS
T E
RE
D PROFESSIONAL ENG
INEER
/1
9/
6:
:5
PM
C :\U se rs
\ta l\D oc um en ts
\M y
Re vi t\6
_S tru c_ ta l.r vt
TYPICAL DETAILS
TAL
BJW
TAL 39
S-003
S-003
SCALE: NTS
1 DECK FASTENER LAYOUT DETAIL
SCALE: NTS
2 DECK TYPES DETAIL
SCALE: NTS
4 SAWED CONTROL JOINT (SJ)
SCALE: NTS
3 CONSTRUCTION JOINT (CJ)
SCALE: NTS
5 BULKHEAD
SCALE: NTS
10 GRADE BEAM REINFORCING
SCALE: NTS
7 CMU OPENING REINFORCING
SCALE: NTS
8 TYP RE-ENTRANT CORNER BAR
SCALE: NTS
9 REINFORCING AT SLAB JOINT
6 LINTEL TYPES
GRID
GRID
11"
1/
2"
4" 4"
1/
2"
1 1/2" 4" 4" 1 1/2"
BASE PLATE
3/4"x11"x0'-11"
W/ (4) 1 5/16" Ø HOLES
PLATE WASHER
1/4"x2"x0'-2" W/
13/16"Ø HOLE, TYP
TOP AND BOT,
(8) TOTAL
3/4" Ø ANCHOR ROD
(EMBED =1'-0") TYP
3/16
TYP
SIDES
HSS 4X4 COLUMN
1/4
BASE PLATE - 1 (BP-1)
GRID
GRID
1'-1"
1' -1
2"
1/ 2"
1/
2" 2"
2" 4 1/2" 4 1/2" 2"
BASE PLATE
1"x13"x1'-1"
W/ (4) 1 13/16" Ø HOLES
PLATE WASHER
3/8"x3"x0'-3" W/
1 1/16"Ø HOLE, TYP
TOP AND BOT,
(8) TOTAL
1" Ø ANCHOR ROD
(EMBED = 1'-2") TYP
3/16
TYP
SIDES
HSS 6X6 AND
HSS 5X5 COLUMN
1/4
BASE PLATE - 2 (BP-2)
GRID
1'-7"
1' -0
2" 8"
2"
2" 4 1/2" 4 1/2" 6" 2"
BASE PLATE
1 1/4"x13"X 1'-7" W/ (6) 1 15/16" Ø
HOLES
PLATE WASHER
3/8"x3"x0'-3" W/ 1 3/16"Ø
HOLE, TYP TOP AND
BOT, (12) TOTAL
1 1/8" Ø ANCHOR ROD
(EMBED = 1'-4") TYP
3/16
TYP, 3
SIDES
HSS 5X5
COLUMN
1/4
BASE PLATE - 5 (BP-5)
GUSSET PLATE
GRID
6" 6"
6 1/2" 1'-0 1/2"
GRID
1'-1"
1' -1
3" 2"
6" 2"
2" 4 1/2" 4 1/2" 2"
BASE PLATE
1"x13"X 1'-1"
W/ (4) 1 13/16" Ø HOLES
PLATE WASHER
3/8"x3"x0'-3" W/ 1 1/16"Ø
HOLE, TYP TOP AND
BOT, (8) TOTAL
1" Ø ANCHOR ROD
(EMBED = 1'-2") TYP
3/16
TYP, 3
SIDES
HSS 5X5 COLUMN
1/4
BASE PLATE - 3 (BP-3)
GRID
3"
6 1/2" 6 1/2"
GRID
1'-2"
1' -2
1/
2"
1/
2"7" 2"
2" 5" 5" 2"
PLATE WASHER
3/8"x3"x0'-3" W/ 1 1/16"Ø
HOLE, TYP TOP AND
BOT, (8) TOTAL
1" Ø ANCHOR ROD
(EMBED = 1'-2") TYP
3/16
TYP, 3
SIDESHSS 6X6
COLUMN
1/4
BASE PLATE - 4 (BP-4)
GRID
1/
2"
1/
2"
7" 7"
BASE PLATE
1 3/8"x14"X 1'-2"
W/ (4) 1 13/16" Ø HOLES
5" 7" 7" 7" 7" 7" 3"
1/
4"
3/ 4"
3"
1/ 4"
3/
4" 3"
1' -1
3'-7" 5" 3'-2"
BASE PLATE
2"x13"X 3'-7"
W/ (10) 2 5/16" Ø HLS
3/16
TYP, 3
SIDES
1 1/2" Ø ANCHOR ROD
(EMBED = 1'-4") TYP
PLATE WASHER
1/2"x3 1/2"x0'-3 1/2"
W/ 1 9/16"Ø HOLE,
TYP TOP AND BOT,
(20) TOTAL5/8" GUSSET
PLATE
HSS8X8
COLUMN
BASE PLATE - 6 (BP-6)
5/16
5 1/2" 8 1/2" 7" 7" 7" 3"
9" 9"
3" 6"
6" 3"
1' -6
3'-2"
5 1/2" 2'-8 1/2"
BASE PLATE 2"x18"X 3'-0"
W/ (8) 2 5/16" Ø HOLES
3/16
TYP, 3
SIDES 1 1/2" Ø ANCHOR ROD TYP,
REFER NOTE 1 BELOW
PLATE WASHER
1/2"x3 1/2"x0'-3 1/2" W/ 1
9/16"Ø HOLE, TYP TOP
AND BOT, (16) TOTAL
5/8" GUSSET
PLATE
HSS 8X8
COLUMN
BASE PLATE - 7 (BP-7)
5/16
5 1/2" 8 1/2" 7" 7" 7" 3"
9" 9"
3" 6"
6" 3"
1' -6
3'-2"
5 1/2" 2'-8 1/2"
BASE PLATE 2"x18"X 3'-0"
W/ (8) 2 5/16" Ø HOLES
3/16
TYP, 3
SIDES
1 1/2" Ø ANCHOR ROD TYP,
REFER NOTE 1 BELOW
PLATE WASHER
1/2"x3 1/2"x0'-3 1/2" W/ 1
9/16"Ø HOLE, TYP TOP
AND BOT, (16) TOTAL
5/8" GUSSET
PLATE
HSS10X4 COLUMN
BASE PLATE - 8 (BP-8)
5/16
NOTE:
1. AT BASE PLATE BP-7 AND 8, LENGTH OF
ANCHOR RODS SHALL BE BASED ON DEPTH
OF EXISTING CONCRETE BEAM OR JOIST WHICH
NEED TO BE FIELD VERIFIED. REFER SECTIONS
ON SHEET SF501 THROUGH SF504.
2. BELOW BASE PLATE BP-7 AND 8, PROVIDE
STEEL SHIM PLATES AS REQ'D FOR ERECTION
PRIOR TO GROUTING. NON SHRINK GROUT
THICKNESS REFER ANCH ROD DETAIL 1/S-005.
GRID
1'-4"
1' -4
2" 6"
6" 2"
2" 6" 6" 2"
PLATE WASHER
3/8"x3"x0'-3" W/ 1 1/16"Ø
HOLE, TYP TOP AND
BOT, (8) TOTAL
1" Ø HILTI HAS ANCHOR ROD
(EMBED = 1'-2" W/ HILTI HIT-HY
200 ADHESIVE), TYP.
PROJ REFER DETAIL 1/S-005
3/16
TYP, 3
SIDES
HSS 8X8
COLUMN
1/4
BASE PLATE - 9 (BP-9)
GRID
8" 8"
8" 8" BASE PLATE
1"x16"X 1'-4"
W/ (4) 1 13/16" Ø HOLES
GRID
1'-4"
1' -4
2" 6"
6" 2"
2" 8 1/2"
1"
4 1/2"
PLATE WASHER
3/8"x3"x0'-3" W/ 1 1/16"Ø
HOLE, TYP TOP AND
BOT, (8) TOTAL
1" Ø ANCHOR ROD
(EMBED = 1'-2") TYP
3/16
TYP, 3
SIDES
HSS 8X8
COLUMN
1/4
BASE PLATE - 10 (BP-10)
GRID
8" 8"
11 1/2" 4 1/2"
BASE PLATE
1"x16"X 1'-4"
W/ (4) 1 13/16" Ø HOLES
3" TY
P
MIN FOUR (4) DWLS UNO. DWL
SIZE MATCH PIER VERTICAL
REINF. PROVIDE STD HOOK AT
TOP AND CLASS "B" TENSION
EMBEDMENT INTO PIER
REFER TO DRILLED PIER
SCHEDULE FOR
REINFORCING SIZE AND
NUMBER UNLESS NOTED
OTHERWISE
3" CLEAR TO TIE
CAGE SPACERS
REQUIRED
TO MAINTAIN
CLEARANCE.
REFER TO DRILLED PIER
SCHEDULE FOR SIZE AND
SPACING OF TIES
PLASTIC SHOE REQUIRED TO
MAINTAIN CLEAR COVER
EQUAL SPACING BETWEEN
LONGITUDINAL REINFORCING
48 BAR Ø LAP
REFER PLAN
SHAFT
DIAMETER
3" TY
P
PILASTER, PIER CAP,
GRADE BEAM OR WALL
DRILLED PIER
(IN PLAN SECTION)
D
ET
AI
LS
R
EF
ER
3"
BOTTOM OF PIER
ELEVATION VARIES.
HIGHEST ELEVATION
REFER DRILLED PIER
SCHEDULE
TOP OF PIER
REFER SCHEDULE
TOP OF PILASTER, PIER
CAP, GRADE BEAM OR
WALL ELEV REFER PLANS
WEATHERED SHALE
ELEVATION VARIES
3' -0
P
1, 6'
-0
P
M
IN
.S O
C K
ET
D
EP
TH
3/4" CHAMFER
TYPICAL
#4 AT 12" OC EACH WAY
R
EF
M
EC
H O
R
PL
AN
NOTES:
1. DRILL AND GROUT #4 DOWELS AT 2'-0" OC
TYPICAL AT PERIMETER, (4) EACH PAD MINIMUM.
2. REFER TO PLANS OR MECHANICAL DRAWINGS FOR
PAD LOCATIONS.
R
EF
PL
AN
V A
R
IE
S (4
"M
IN
IM
U
M
8"
#4 DWLS REF NOTE 1
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
TIENG
AI LING
21544 O K L A H O M A
RE
G
IS
T E
RE
D PROFESSIONAL ENG
INEER
/1
9/
6:
:2
PM
C :\U se rs
\ta l\D oc um en ts
\M y
Re vi t\6
_S tru c_ ta l.r vt
TYPICAL DETAILS
TAL
BJW
TAL 40
S-004
S-004
SCALE: NTS
1 BASE PLATE TYPES
SCALE: NTS
2 DRILLED PIER
3 TYPICAL HOUSE KEEPING PAD DETAIL
D
IA
E
M
BE
D
PR
O
J
TH
R D
SEE SCHEDULE
3/16
TACK
COLUMN, SEE PLAN
1. ANCHOR RODS SHALL MEET THE REQUIREMENTS OF ASTM F1554
UNLESS NOTED OTHERWISE.
2. ALL ANCHOR RODS SHALL BE FURNISHED WITH HEAVY HEX NUTS AND
PLATE WASHERS OF SPECIFICATIONS COMPATIBLE WITH THOSE OF THE
THREADED SHANKS UNLESS NOTED OTHERWISE.
3. FOR CONVENTIONAL COLUMNS (W & HSS SHAPES) A NUT AND WASHER
SHALL BE PLACED UNDER THE BASE PLATE AND USED FOR LEVELING.
4. HEADED BOLTS MAY BE SUBSTITUTED FOR RODS AS SHOWN.
NOTES:
ANCHOR ROD
SCHEDULE
DIA NSG
< 1" 2" > 1" 3"
*PROJ = BASE PLATE THICKNESS + NSG + WASHER + DIA + 1 1/2"
**THRD = PROJ + 1"
NON SHRINK GROUT (NSG)
TOC
PLATE WASHERS
ADD (1) #4 BAR
MINIMUM CENTERED
ON COLUMN
CONTROL
JOINT
COLUMN & BASE
PLATE PER PLAN ALIGN CORNERS
OF CONTROL
JOINT WITH
CONTRACTION
JOINT
NON-SHRINK
CONCRETE
AROUND
COLUMN
6"
INTERIOR
ADD (1) #4 BAR
MINIMUM CENTERED
ON COLUMN
CONTROL
JOINT
CONTROL
JOINT
COLUMN & BASE
PLATE PER PLAN
CORNER EXTERIOR
ADD (1) #4 BAR
MINIMUM CENTERED
ON COLUMN
NON-SHRINK CONCRETE
AROUND COLUMN
COLUMN & BASE
PLATE PER PLAN
NON-SHRINK CONCRETE
AROUND COLUMN
ALIGN CORNERS OF
CONTROL JOINT WITH
CONTRACTION JOINT
6" 6"
CLASS B
CONCRETE REINFORCEMENT LAP LENGTH SCHEDULE
BAR SIZE TOP BARS* BOTTOM BARS
#4 #5 #6 #7 #8 #9 #10 #11
CLASS B EPOXY COATED
CONCRETE REINFORCEMENT LAP LENGTH SCHEDULE
BAR SIZE TOP BARS* BOTTOM BARS
#4 #5 #6 #7 #8 #9 #10 #11
* GREATER THAN 12" OF CONCRETE BELOW REINF.
1. EPOXY COATED BARS W/ CLEAR COVER > 3db AND CLEARS SPACING > 6db.
2. CONCRETE STRENGTH, F'C = 4,000 PSI.
3. REINFORCING STEEL STRENGTH, FY = 60,000 PSI.
2'-9" 2'-1" 3'-5" 2'-7" 4'-1" 3'-1" 5'-11" 4'-6" 6'-9" 5'-2" 7'-7" 5'-10" 8'-6" 6'-7" 9'-6" 7'-3"
3'-3" 2'-6" 4'-1" 3'-1" 4'-10" 3'-9" 7'-1" 5'-5" 8'-1" 6'-2" 9'-1" 7'-0" 10'-3" 7'-10" 11'-4" 8'-9"
CORNER BARS TO MATCH SIZE AND
SPACING OF REINFORCING. LAP
SPLICE REFER LAP LENGTH
SCHEDULE.
H O
O K
S
TD
HOOK
STD 90°
HOOK
STD 90°
HOOK
STD 90°
COMPONENT AND CLADDING WIND PRESSURES
(LRFD)
OUTWARD PRESSURES (PSF) INWARD PRESSURES (PSF)
1. WIND PRESSURES ARE PERPENDICULAR TO BUILDING SURFACES.
2. PRESSURES SHOWN POSITIVE SIGNIFY INWARD PRESSURE, NEGATIVE SIGNIFY OUTWARD (SUCTION) PRESSURES.
3. REFER TO 4/S-005 ON THIS SHEET FOR COMPONENT ZONE.
4. CORRESPONDING WIND PRESSURES ARE TABULATED BASED UPON TRIBUTARY AREA.
5. COMPONENT ZONE BOUNDARIES CAN BE DETERMINED USING a = 17'-0" (IN ACCORDANCE WITH ASCE 7-10).
6. WIND PRESSURES ARE GIVEN AT THE LRFD LOAD LEVEL (FOR ASD MULTIPLY PRESSURES BY 0.6 PER ASCE 7-10).
7. AT VESTIBULE CURTAIN WALL, USE COMPONENT ZONE 5.
ON WALL
ZONE 4 ZONE 5 ZONE 4 ZONE 5
-38.8 -37.2 -36.2 -35.6 -35.1 -34.0 -33.5 -31.9
-29.8
-31.0 -30.3
-47.7 -44.5 -42.7 -41.4 -40.3 -38.2 -37.2 -34.0
-29.8
-32.1 -30.8
35.8 34.2 33.3 32.6 32.1 31.0 30.5 28.9
26.8
28.0 27.3
COMPONENT AND CLADDING NOTES:
35.8 34.2 33.3 32.6 32.1 31.0 30.5 28.9
26.8
28.0 27.3
TRIBUTARY
AREA
(SF)
0 to 10
>500
ON ROOFON WALLON ROOF
ZONE 2
-65.6 -58.6 -54.5 -51.6 -49.4 -44.6 -42.4 -42.4
-42.4
-42.4 -42.4
ZONE 1
-39.1 -38.1 -37.5 -37.1 -36.8 -36.1 -35.8 -35.8
-35.8
-35.8 -35.8
ZONE 1, 2 AND 3
16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0
ZONE 3
-98.7 -81.7 -71.8 -64.8 -59.3 -47.9 -42.4 -42.4
-42.4
-42.4 -42.4
4 4
5 5
(T Y
P)a
(TYP)
a
3 33
3 2
2 3
2 2
REF NOTE 7
REF NOTE 7
SUPPORTING EXISTING
CONC MEMBER
OPENING
SUPPORTING EXISTING
CONC MEMBER
L3x3x1/4 FOR SPANS TO 2'-6" L4x3x1/4 LLV FOR SPANS > 2'-6" < 4'-0"
L4x3x3/8 LLV FOR SPANS > 2'-6" < 5'-0" L3x3x1/4 FOR SPANS TO 2'-6"
NOTES:
1. SHIM AND GROUT GAP BETWEEN TOP OF STEEL ANGLE AND
EXISTING CONCRETE SLAB.
2. PROVIDE ANGLE FRAME FOR ALL OPENINGS LARGER THAN
8" IN ANY DIRECTION.
3. LOCATE REBAR IN EXISTING CONCRETE MEMBER PRIOR TO
DRILLING FOR ANCHOR EMBEDMENT.
L3x3x1/4x0'-6" (ATTACH TO
EXISTING SUPPORTING MEMBER
W/ (2)-1/2" DIA x 3" EMBED HILTI
HAS ROD AND HIT-HY 200
ADHESIVE)
3/16
3/16
TYP
3/16 3/16
TYP
3"
BOTTOM OF
EXISTING SLAB
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
TIENG
AI LING
21544 O K L A H O M A
RE
G
IS
T E
RE
D PROFESSIONAL ENG
INEER
/1
9/
6:
:5
PM
C :\U se rs
\ta l\D oc um en ts
\M y
Re vi t\6
_S tru c_ ta l.r vt
WIND DIAGRAM AND TYPICAL DETAILS
TAL
BJW
TAL 41
S-005
S-005
SCALE: NTS
1 ANCHOR ROD
SCALE: NTS
2 SLAB BLOCKOUT - RECTANGULAR
SCALE: NTS
TYPICAL ADD'L REINF AT
CORNERS AND INTERSECTION
SCALE: NTS
4 COMPONENTS AND CLADDING WIND DIAGRAM
N
SCALE: NTS
TYPICAL FRAMED OPENING AT EXISTING
CONC ROOF AND FLOOR
0.7
G.9
2'-9"
1'-9" 1'-0"
1/
2" 5"
1' -0
2" C
LR
TYP
2" CLR
(10)-#8 VERT
#3 TIES AT
14" OC
WALL REINF
PILASTER - 1 (PI-1)
0.8
L.1
4" 6" 8"
1'-6"
9" 9"
1' -6
5/
8"
3/ 8"
5/
8"
PILASTER - 2 (PI-2)
TYP
2" CLR
WALL REINF
#3 TIES AT
12" OC
(8)-#6 VERT
ANCH RODANCH ROD
13.1
P.1 0.7
J
1'-6"
8" 4" 6"
8" 4"
6"
(10)-#7 VERT
#3 TIES AT
14" OC
WALL REINF
PILASTER - 3 (PI-3)ANCH ROD
1' -8
1'-8" 10"
2'-6"
1' -6
TYP
2" CLR
1'-6"
P.2
8" 4"
6"
(6)-#7 VERT
#3 TIES AT
14" OC
WALL REINF
PILASTER - 4 (PI-4)
ANCH ROD
10" 10"
1'-8"
1' -6
TYP
2" CLR
9" 3"
8"
4" 8" 4"
1'-0" 1'-6"
9"
1' -8
2'-6"
ANCH ROD
#3 TIES AT
14" OC
(10)-#7 VERTWALL REINF
P.3
13.1
PILASTER - 5 (PI-5)
0.6
L.1
P.3
13.6
PILASTER - 6 (PI-6)
0.6
L.6
9" 3"
8"
1 5/8"8 3/8"3 5/8"
10"10"
9"
1' -8
1'-8"
ANCH ROD
#3 TIES AT
14" OC (8)-#7 VERT
6" 4"
8"
1'-0" 5" 8 1/2"
#3 TIES AT
14" OC
P.2
9.9
PILASTER - 7 (PI-7)
2'-1 1/2"
1' -6
ANCH ROD
(8)-#7 VERT
WALL REINF
ADD'L BARS AT
CORNER REF
DTL 3/S-005
ADD'L BARS AT
CORNER REF
DTL 3/S-005
ADD'L BARS AT
CORNER REF
DTL 3/S-005
ADD'L BARS AT
CORNER REF
DTL 3/S-005
ADD'L BARS AT
CORNER REF
DTL 3/S-005
L.6
0.9
PILASTER - 8 (PI-8)
5/
8"
3/ 8"
8"
10"10"
1'-8"
ANCH ROD
#3 TIES AT
14" OC
(8)-#7 VERT
1' -8
WALL REINF
P.1
13.6
1" 1'-4" 1'-0"
GRID
1' -0
3/ 4"
1/
4" C
O N
C W
AL
L
1' -0
"E X
IS
T
COL
C O
L
2'-4" (PILASTER)
4'-9" (BEAM)
1' -6
PILASTER - 9 (PI-9)
#3 TIES AT
14" OC
(10)-#7 VERT, PROVIDE
STD HOOK AT TOP
#4 BENT DWL SPACED
VERTICALLY AT 12" OC. DRILL
AND EMBED INTO EXIST
CONC WALL W/ HILTI HIT HY
200 ADHESIVE
8"
2' -0
TYP
2" CLR
TY
P
2" C
LR TY
P
2" C
LR
TYP
2" CLR
TY
P
2" C
LR
ANCH ROD
7 1/2" AT GRID H-1
5 3/4" TYP
V
ER
IF
Y
4"
TY
P
2 1/2" AT GRID A-8
PILASTER - 10 (PI-10)
GRID
COL
#3 TIES AT
14" OC
(8)-#7 VERT, PROVIDE
STD HOOK AT TOP
6"1'-1"1'-3"
1' -0
3/ 4"
1/
4" C
O N
C W
AL
L
1' -0
"E X
IS
T
C O
L
2'-4" (PILASTER)
4'-9" (BEAM)
1' -6
E M
BE
D
8"
2' -0
TY
P
2" C
LR
6"
2 1/2"
ANCH ROD
#4 BENT DWL SPACED
VERTICALLY AT 12" OC. DRILL
AND EMBED 10" INTO EXIST
CONC WALL W/ HILTI HIT HY
200 ADHESIVE
4" CLRE
M
BE
D
1' -2
EMBED
10"
GRID
2'-4"
1'-2" 1'-2"
1/
2" 5"
1' -0
TY
P
2" C
LR
TYP
2" CLR
(10)-#8 VERT
#3 TIES AT
14" OC
WALL REINF
PILASTER - 11 (PI-11)
ANCH ROD
TY
P
2" C
LR
C
LR
1/
2"
NOTE:
1. TOP OF PILASTER ELEVATION FOR PI-1, 3, 4, 5,
6, 7, 8 AND 11 SHALL BE 99'-4".
2. TOP OF PILASTER ELEVATION FOR PI-2 SHALL
BE 83'-7".
3. TOP OF PILASTER ELEVATION FOR PI-9 AND
10 SHALL BE 99'-0".
4. PROVIDE ADDITIONAL #3 CLOSED TIES AT TOP
OF EACH PILASTER, REFER SECTION 7/SB503.
5. CLEAN, ROUGHEN AND APPLY BONDING AGENT
TO EXISTING CONCRETE SURFACE AT
CONCRETE PILASTER.
GRID
8"
2'-0"
#4 BENT DWL SPACED
VERTICALLY AT 12" OC. DRILL
AND EMBED 10" INTO EXIST
CONC WALL W/ HILTI HIT HY
200 ADHESIVE
10"
EXIST CONC WALL
(4)-#7 AT TOP AND
BOT W/ 1'-0" HOOK
AT EA END
(4)-#7 AT TOP AND
BOT W/ 1'-0" HOOK
AT EA END
#3 CLOSED
STIRRUP AT
9" OC
#3 CLOSED
STIRRUP AT
9" OC
REF NOTE 5 BELOW
E M
BE
D
REF NOTE 5
BELOW
REF NOTE 5
BELOW
EXISTING
REINFORCING
BAR
CUT FACE OF EXISTING
CONC TO BE EXPOSED
REMOVE LOOSE CONC DEBRIS,
PRIME CONC SURFACE W/
BONDING AGENT WELD-CRETE
OR EQUAL AND FILL HOLE W/
REPAIR MORTAR
BACK-GOUGE REBAR AND
APPLY ANTI-CORROSIVE
METAL PRIMER AT EXPOSED
REBAR.EXISTING CONC
NOTE:
DETAIL ABOVE IS FOR EXISTING REINFORCED
CONCRETE WHICH SHALL BE CUT AND EXPOSED
TO VIEW.
1 1/2"
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
TIENG
AI LING
21544 O K L A H O M A
RE
G
IS
T E
RE
D PROFESSIONAL ENG
INEER
/1
9/
6:
:0
PM
C :\U se rs
\ta l\D oc um en ts
\M y
Re vi t\6
_S tru c_ ta l.r vt
TYPICAL DETAILS
TAL
BJW
TAL 42
S-006
S-006
SCALE: 1" = 1'-0"
1 PILASTER TYPES
0 6" 1' 2'
1" = 1'-0"
2 TYP CUT REBAR PATCHING DETAIL
8 9 10 11 12 13 14 15 16
G
H
J
K
L
M
N
P
16.1
P.2
SF202
'-9
3/ 4"
CMU SHEAR WALL CMU SHEAR WALL
C M
U S
H
EA
R W
AL
L
SF201
SF202
SF201
SF201
SF202
L.6
L.1
K.6
J.3
13.1 13.6
G.9
9.9
P.3
P.1
P.4
11.3 12.6
ELEV
PIT
C M
U S
H
EA
R W
AL
L
ELEV = 84'-3"
TO EXIST SLAB
P2
P2
P2
P2
P2P2
P1P1
25'-0" 23'-4" 1'-8" 25'-0"
5'-2 1/4"
9'-9 3/4" 6'-5 3/4" 3'-6 1/4" 1'-8"
7'-7 5/8" 5'-8 3/8" 10'-0" 25'-0" 12'-11"
9' -4
1/ 2"
1' -1
3/
4" 9'
-1 1/
4" 4'
-1
1/ 4"
'-0
'-0
5' -8
3/ 8"
7' -7
5/ 8"
1' -8
3'
-6 1/
4"
6' -5
3/ 4"
9' -9
3/ 4"
5' -2
1/ 4"
'-0
1'
-8
'-4
SB401
TYP
SB501 TYP
SB502
SB502
SB502
SB501
SB501
SB501
14'-6"
'-6
5' -0
14'-0"
'-0
14'-0"
'-0
5'-0"
83'-3"
T O FTG
EL =
2'-11 1/4" 19'-11" 8'-6 1/4" 6'-6 1/2"
2' -1
1/
2"
'-1
2' -1
1/
2" 1'
-6 1/
4" 7'
-7
2' -1
1/
4"
'-1 1"
2' -1
3/ 4"
'-3
1' -6
3/ 4"
SB501
4 44
EXIST FTG
EXIST FTG
EXIST FTG
EXIST FTG
5'-0"
EXIST FTG
'-6
EXIST FTG
EXIST FTG
5' -0
P.05
1/ 2"
PROVIDE SOIL RETENTION
AND SHORING OF EXISTING
CONCRETE FOOTING. REFER
SOIL RETENTION SYSTEM
NOTES ON SHEET S-002
5' -0
P1P1
3'-6" 18'-0" 3'-6" 23'-4"
MATCH LINE
SEE 1/SB102
M
AT
C H
LI
N
E S
EE
1/
SB
MATCH LINE
SEE 1/SB102
M
AT
C H
LI
N
E S
EE
1/
SB
FOUNDATION PLAN NOTES
1 5" CONC SLAB ON GRADE REINF W/ #4 AT
16" OC EA WAY OVER 10-MIL VAPOR
RETARDER OVER 6" GANULAR FILL. TOP OF
SLAB ELEVATION SHALL MATCH EXISTING
BASEMENT CONC SLAB
2 1'-0" THICK CONC BASEMENT WALL, VERTICAL
AND HORIZONTAL REINF REFER WALL SECTION.
3 5" CONC SLAB REINF W/ #4 AT 16" OC EA WAY
OVER EXISTING ELEVATOR PIT. BACKFILL
BELOW SLAB WITH CRUSHER RUN OR
CRUSHED STONE. TOP OF SLAB ELEVATION
SHALL MATCH EXISTING CONC SLAB.
BP-1 BASE PLATE MARK, REFER BASE PLATE
TYPES 1/S-004
PI-1 PILASTER MARK, REFER PILASTER
TYPES 1/S-006
4 NEW FOUNDATION OR EXTENSION TO EXISTING
FOUNDATION, REFER FOUNDATION SECTION
FOR DETAILS. TOP OF FOOTING ELEVATION =
84'-3", UNLESS NOTED OTHERWISE.
P1 DRILLED PIER MARK, SIZE AND REINF
REFER SCHEDULE ON SHEET SF101
F1 FOOTING MARK, SIZE AND REINF REFER
SCHEDULE ON SHEET SF101
5 8" CMU WALL W/ VERTICAL REINFORCING #5 AT
32" OC AND BOND BEAM REINFORCED W/ (2)-#5
CONT. AT 4'-0" OC, TOP AND BOTTOM OF WALL.
DESIGNED BY:
DRAWN BY:
WORK ORDER NO.
OFFICE OF
ISSUED BY
DRAWING NO.
DATE
PREPARED BYREVIEWED BY
REV DATE
APPROVED BY
DESCRIPTION
OF
SHEET NO.
APP'DCHECK
FACILITY MANAGEMENT
AMP-400
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
FEDERAL AVIATION ADMINISTRATION
DECEMBER 20, 2017
405/840-2931 www.fsb-ae.com
13-007860 AMP-400-E-
FRANKFURT SHORT BRUZA
DEPARTMENT OF TRANSPORTATION
5801 BROADWAY EXT., SUITE 500
OKLAHOMA CITY, OKLAHOMA
Work Request Construction No: 13-007860
MPB-24 (MULTI-PURPOSE BUILDING)
RENOVATION
M.OWENSBY
TIENG
AI LING
21544 O K L A H O M A
RE
G
IS
T E
RE
D PROFESSIONAL ENG
INEER
/1
9/
6:
:3
PM
C :\U se rs
\ta l\D oc um en ts
\M y
Re vi t\6
_S tru c_ ta l.r vt
BASEMENT FOUNDATION SLAB PLAN -
AREA 1
TAL
BJW
TAL 43
SB101
SB101
SCALE: 1/8" = 1'-0"
1 BASEMENT FOUNDATION SLAB PLAN - AREA 1
N
KEYPLAN
0 4' 8' 16'
1/8" = 1'-0"
8 9 10 11 12 13 14 15 16
A
B
C
D
E
F
G
H
16.1
25'-0" 23'-4" 1'-8" 25'-0" 5'-2 1/4" 9'-9 3/4" 6'-5 3/4" 3'-6 1/4" 1'-8"
7'-7 5/8" 5'-8 3/8" 10'-0" 25'-0" 12'-11"
1' -9
3/ 4"
CMU SHEAR WALL
C M
U S
H
EA
R W
AL
L
SF201
SF204
SF204
SF204
SF201
13.1 13.6
G.9
9.9 11.3 12.6
EXISTING ELEVATOR
PIT TO REMAIN.
REPLACE EXISTING
ELEVATOR
C M
U S
H
EA
R W
AL
L
STEEL BRACE COL
EXIST LIFT PIT
TO REMAIN
SF201
P2
P2
P2
P2
P2
TO EXIST SLAB
EL =
1' -8
'-4
'-0
'-0
'-0
'-0
'-0
'-0
SB501
SB502 SIM
SB501
SB502
SB502 SIM
14'-6"
'-6
2' -1
1/
2"
84'-3"
2' -1
3/ 4"
'-1
1" 2'
-1
1/ 4"
2' -1
1/
2"
'-1
2' -1
1/
2"
6' -4
1/ 2"
2'-11 1/2" 12'-6 1/2"
2'-3"
SB501
'-0
14'-0"
14'-0"
'-0
6'
-0 " 13'-0"
EXIST FTG
EXIST FTG
5'-0"
EXIST FTG
EXIST CONC FTG
BELOW TO REMAIN
EXIST FTG
EXIST FTG
EXIST RETAINING
WALL FND
EXIST RETAINING
WALL FND
1'-6 3/4"…