528A7-18-716 RENOVATE MAIN KITCHEN –PLAN REVISIONS BY SHEET NUMBER – REVIEW FIRST General Note:
Please refer to QC-102R for revised furniture plan, updated equipment plan, updated room functions, and updated floor plans. Note that wall shown to be demolished between C-203 and B-266 is now to remain which results in slightly smaller floor plan for new C-205H. No architectural work will be required in C-203 electrical closet. Any work shown on plans for C-201 is no longer required.
| T-100: | G-102, H-101, QC-101 and QC-102 have been superseded/changed to G-102R, H-101R, QC-101R and QC-102R in the plans set. |
| G-101: | * Please refer to QC-102R for revised furniture plan, updated equipment plan, updated room functions, and updated floor plans. |
AD101
Note minor architectural demo eliminations.
A101
1) Eliminate new walls and doors associated with C201, C203A and C205H
2) Eliminate Refrigerator and Fixed Countertop from Existing C261/New C205C
* Please refer to QC-102R for revised furniture plan, updated equipment plan, updated room functions, and updated floor plans.
A-102: * Please refer to QC-102R for revised furniture plan, updated equipment plan, updated room functions, and updated floor plans.
A701 Signage schedule:
Training Room C205C/Existing Call Center C261 will be retitled “Call Center C205C”
1) What is labeled (C205H Call Center and C205N)/(Existing B266 Super Offices/B264 STOR) will be the new “C205H Supervisor Workstations”
2) Existing salad prep area/supv office C202E/C265A will become “C205F Employee Area”
* Please refer to QC-102R for revised furniture plan, updated equipment plan, updated room functions, and updated floor plans.
FX-101
1) Delete general note #4, i.e., FLEXIBLE SPRINKER DROPS ARE PERMITTED.
* Please refer to QC-102R for revised furniture plan, updated equipment plan, updated room functions, and updated floor plans.
M-101: * Please refer to QC-102R for revised furniture plan, updated equipment plan, updated room functions, and updated floor plans.
M-102: * Please refer to QC-102R for revised furniture plan, updated equipment plan, updated room functions, and updated floor plans.
M-103: * Please refer to QC-102R for revised furniture plan, updated equipment plan, updated room functions, and updated floor plans.
ED-101
1) Delete keyed notes 11 and 16 E-101
1) EEQ2C-B relocate to C203
2) ELS2A-A remains as is
3) Replace keyed note 2 with the following: Replace existing 2 Section panel E2BA with single section surface mount panelboard and relocate to small closet on opposite side of where E2BA-1 breaker was located. E2BA-1 circuits to be relocated to E2BA. Existing panelboard boxes to remain and be used as junction boxes. Provide new screw covers over existing panelboard boxes and E2BA-1 enclosed breaker box.
4) No work in C201
5) Add (4) data lines coiled in ceiling with 10’ extra length opposite C205H and above existing tray line.
* Please refer to QC-102R for revised furniture plan, updated equipment plan, updated room functions, and updated floor plans.
E-501
1) “Kitchen conveyor” circuit currently shown in 2CE to be re-fed out of new EEQ2C-B.
P-101: * Please refer to QC-102R for revised furniture plan, updated equipment plan, updated room functions, and updated floor plans.
P-301: * Please refer to QC-102R for revised furniture plan, updated equipment plan, updated room functions, and updated floor plans.
QC-101: QC-101 is superseded by QC-101R QC-102: QC-102 is superseded by QC-102R QC103: * Please refer to QC-102R for revised furniture plan, updated equipment plan, updated room functions, and updated floor plans.
QC104: * Please refer to QC-102R for revised furniture plan, updated equipment plan, updated room functions, and updated floor plans.
QC105: * Please refer to QC-102R for revised furniture plan, updated equipment plan, updated room functions, and updated floor plans.