NOTES:
1.
2.
3.
4.
SIX INCH [150mm] PLENUM AS SHOWN SHALL BE SUPPLIED BY MANUFACTURER OF
FAN COIL UNIT.
SEE DETAIL FOR SUPPLY & RETURN PIPING CONNECTIONS.
PROVIDE ACCESS FOR FILTER REMOVAL.
SEE FAN COIL UNIT SCHEDULE FOR PIPE SIZES.
SUPPLY & RETURN GRILLES SHALL BE SIZED TO SUIT CONNECTIONS ON FAN COIL
UNIT. DUCTWORK SHALL SUIT GRILLES AND FAN COIL UNIT FURNISHED.
6" PLENUM
FINISHED CEILING
4-WAY DEFLECTION
SUPPLY AIR GRILLE
HANGER ROD
SUPPORTS SECURE TO
STRUCTURE ABOVE
WITH SPRING
ISOLATORS (TYP)DUCT SIZE TO SUIT
SUPPLY AIR GRILLE
304 SS DRAIN PAN &
PIPE CONNECTION
FOR SOFFIT SEE
ARCH. DRAWINGS RETURN AIR GRILLEACCESS DOOR SIZED TO
ALLOW ACCESS TO
ELECTRICAL AND COIL
CONNECTIONS AND
ALLOW FOR MOTOR/FAN
ASSEMBLY REMOVAL
COIL
FAN
FILTER
TERMINATE OVERFLOW
DRAIN ABOVE
LAVATORY, SINK, OR
FLOOR DRAIN
INSULATE FULL
LENGTH OF THE
CONDENSATE DRAIN
PIPING
ACCESS DOOR
HEATING ONLY PANELS
HWS
HWR
RUNOUT & INTERCONNECTING PIPING.
PROVIDE DIELECTRIC FITTINGS AS
REQUIRED. CIRCUIT TO COMPLY WITH
SPECIFIED CAPACITY & PRESSURE DROP.
(TYP.)
NOTE:
1. MINIMUM FLOW SHALL BE NO
LESS THAN 0.5 GPM
TEST PLUG
1.
2.
3.
4.
5.
6.
RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A
MINIMUM OF 3 TIMES THE DIAMETER OF INLET
A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR
INLET TO THIS BOX, BUT ALLOWED TO ACCOMMODATE MINOR
OFFSETS. MAXIMUM LENGTH 3'-0" [900mm].
A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE
SAME SIZE AS THE BOX INLET, PROVIDED THE EQUIVALENT
LENGTH OF THE BRANCH DUCT, AS SHOWN, DOES NOT EXCEED
10 FEET (3 METERS). FOR LONGER LENGTHS, INCREASE THE
DUCT SIZE AND PROVIDE A DUCT TRANSITION TO MAINTAIN THE
DUCT STATIC PRESSURE DROP AT OR BELOW 0.2"/100' [1.64Pa/m].
FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL
UNIT SUPPLY AIR DUCT TO DIFFUSER, SHALL NOT EXCEED 5'-0"
[1500mm]. USE RIGID ELBOWS FOR CHANGE OF DIRECTION
GREATER THAN 45°.
COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER.
PROVIDE INSULATION W/VAPOR BARRIER FOR CONNECTING
DUCT SECTIONS.
USE OF THE FLEXIBLE AIR DUCT CONNECTORS ARE NOT
PERMITTED FOR THE DEDICATED AHU SERVING THE SURGICAL
SUITE.
SEE NOTE 3
SEE NOTE 1
SEE NOTE 2
DIFFUSER (TYP)
FLEX DUCT CONNECTOR
SOUND ATTENUATOR
REHEAT COIL
VAV
SE
E
N O
TE
RADIANT CEILING PANEL SCHEDULE (HYDRONIC )
MARK
CIRCUIT
NUMBER
BASIS OF DESIGN
NUMBER
OF
PANELS
PANEL SIZE
HEATING
REMARKS
MANUFACTURER MODEL
HEATING
CAPACITY EWT LWT
HOT
WATER
FLOW RATE
WPD
IN BTUH °F °F GPM FT
HRP-1 40 48 X 24ARMSTRONG AR-M 2616 140 120 0.26 1.696
VANE VANE
NOTE:
1.
2.
THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED, SUPPORTED AND FASTENED
AS RECOMMENDED BY SMACNA.
R SHALL
EQUAL OR
BE
GREATER
THAN W.
R SHALL
EQUAL OR
BE
GREATER
THAN
1/3W.
R SHALL
EQUAL OR
BE
GREATER
THAN
1/6W.
STANDARD RADIUS OR LONG
RADIUS ELBOW
SHORT RADIUS
ELBOW WITH
ONE VANE
SHORT RADIUS
ELBOW WITH
TWO VANES
W
R
R
2/3W 1/ 3W
W W
1/2W 1/ 3W
1/6W
R
NOTE:
1.
2.
3.
4.
ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.
WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE REGARDLESS OF W
DIMENSION.
ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.
WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE DOUBLE VANE TYPE.
W
W1
NOTE:
UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.
MAX.
M
AX.
EQ
U
IP
M
EN
T
AIR FLOW AIR FLOW
TYPICAL DUCTWORK TRANSITION
PLAN OR SIDE VIEWTYPICAL DUCTWORK TRANSITION WITH
EQUIPMENT MOUNTED IN DUCT
PLAN OR SIDE VIEW
MAX.
M
AX.
M
AX
M
AX
30°
15°
15°
5 FT
THRU [20]
6 8 10
[32][25] [40]
[65]
[50]
[75]
-1312 14 -16 -
[125][100]
[150]
[250]
[200]
[300]
[400]
[350]
[450]
[600]
[500]
20 241814 16128 1064 532 2 1/21 1/21 1 1/4
[9100] [9600][8500][7600] [8200][7000][5800] [6700][5200][4100] [4900][3700][3000] [3400][2700][2100]
--- --[4900] -[4100][3700] [4000] -[3000][2400][1800][1500]
THRU 3/4
[2100] [2100]
[2100]
[2700]
[2400]
SIDE VIEW TRAPEZE HANGER FOR UP TO 1000
LB. [453KG] UNIFORM LOAD
ADJUSTABLE CLEVIS HANGERTYPE 1
- SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER TYPE 43
- SEE SPECIFICATIONS
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
TUBING
IN.
[mm]
FT.
[mm]
FT.
[mm]
[2 5m m
1" M
AX
PROVIDE INSULATION SHIELD
& INSERT FOR ALL PIPING
(8" [200mm] MIN.)
BAND
1-5/8" [43mm] 12 GAUGE CHANNEL OR 2"x2"x1/4" [50x50x6.4mm] ANGLE
1/2" [15mm] DIA.
HANGER RODS WITH
36" [900mm] MAX.
SPACING ON EACH
CHANNEL
WELD
SADDLE
INSULATION SHIELD
AT HANGER
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9 PSF
MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
NOTES:
SEE SPECIFER FOR DETAILED
HANGER REQUIREMENTS
AIR SPLIT DUCT TAKE-OFF PLAN
VIEW
BRANCH DUCT TAKE-OFF PLAN VIEW
SUPPLY REGISTER TAKE-OFF PLAN
VIEW
AIR FLOW
AIR FLOW
AI
R
F
LO
W
SUPPLY REGISTER OR
BRANCH DUCT
TURNING VANES
MAIN
SUPPLY
DUCT
SEE FLOOR PLAN
FOR
SPLIT DIMENSION
PROVIDE VOLUME
DAMPER
PROVIDE VOLUME
DAMPER
ADJUSTABLE
METAL ROD OR
LINKAGE
TOP REGISTER
MAIN
SUPPLY
DUCT
VOLUME EXTRACTOR; ADJUSTABLE FROM
FULLY CLOSED POSITION TO CFM NOTED ON
FLOOR PLANS
AIR FLOW AIR FLOW
1/4 W OR 4"
[100mm]
MIN.
AIR FLOW
MAIN SUPPLY DUCT
AI
R
F
LO
W
W
COIL
TEST PLUG (TYP.)
REDUCER, IF REQUIRED
WATER RETURN
MANUAL AIR VENT
UNION
CONNECTIONS
(TYP.)
WATER SUPPLY
SHUT OFF VALVE
DRAIN WITH HOSE
CONNECTION
MV
MODULATION CONTROL VALVE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANTS
321 4 5 6 7 8 9 10
ARCHITECT:
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827 (607)223-4334
C&S Companies 499 Col Eileen Collins Blvd Syracuse, New York, 13212
(315) 455-2000
RENOVATE MAIN KITCHEN
SYRACUSE VA MEDICAL CENTER
528A7-18-716
BUILDING 1
09/08/2023 DW JD
KITCHEN CONSULTANT:
Commercial Kitchen Consulting 21 Powers Rd Binghamton, New York, 13903
(607) 242-5571
BI
M
8A 7-
-7
R en ov at e
M ai n Ki tc he n/ R en ov at e
M ai n Ki tc he n_ R
.rv t
/1 7/
:2
9:
P M
M-501R
MECHANICAL SCHEDULES AND
DETAILS
SPACE
INFORMATION
COOLING LOADS
HEAT LOAD
REQUIRED ROOM AIRFLOWS DESIGN AIRLFOWS FOR
FINAL BALANCING
SENSIBLE TOTAL TOT ACH CLG FLOW HTG FLOW SUPPLY (MAX) RETURN
ROOM ID/# BTU/HR BTU/HR BTU/HR QTY CFM CFM CFM CFM
C205D 18,567 30,882 2,896 15 1,352 1,352 1,360 1,360
C205J 9,876 14,555 2,097 15 450 418 450 450
ROOM AIR SCHEDULE
ID LOCATION
TERMINAL UNIT SCHEDULE
BASIS OF
DESIGN TYPE
INLET
SIZE
(IN)
AIRLFOW (CFM)
DESIGN UNIT MAX UNIT MIN
HW HEATING COIL
ENTERING
AIR TEMP
(F)
LEAVING
AIR TEMP
(F)
STATIC
PRESSURE
(IN. WC.)
ENTERING
WATER
TEMP (F)
LEAVING
WATER
TEMP (F)
FLOW
(GPM)
HEAD
(FT)
2-VAV-42S
1-VAV-42S
TITUS DESV
TITUS DESV
B202A
B202
REHEAT
BYPASS
24X16
ROOM
C205J
C205D
COOLING
SETPOINT
(F)
HEATING
SETPOINT
(F)
MIN
RELATIVE
HUMIDITY
MAX
RELATIVE
HUMIDITY
DESIGN CONDITIONS
ID LOCATION
FOUR PIPE FAN COIL UNIT SCHEDULE
BASIS OF
DESIGN
COOLING COIL
MIN. SENS.
(BTUH)
MIN TOTAL
(BTUH)
ENTERING
AIR (F)
HEATING COIL
GPM
MAX.
COIL
P.D.
1-FCU-42S CARRIER 42DH C205D
FAN
CFM
1,360
DB WB
87 71
MIN.
LOAD
(BTUH)
ENTERING
AIR (F) GPM
MAX.
COIL
P.D.
FAN MOTOR
NOM.
HP
VOLT/
PH/HZ
18,567 30,882 13.8 11400 1.14 1 208/1/60
0.5
1/2" = 1'-0"3 FAN COIL UNIT DETAIL
3/4" = 1'-0"1
HYDRONIC RADIANT CEILING PANELS - PIPING
CONNECTIONS
1/2" = 1'-0"2 DUCT CONNECTION - VAV
PIPE
SIZE
(IN)
PIPE
SIZE
(IN)
DIFFUSER SCHEDULE
TAG MANUFACTURER MODEL DESCRIPTION QTY
ED-1 TITUS PAR 24X24 PERFORATED STEEL EXHAUST DIFFUSER 6
ED-2 TITUS PAR 12X12 PERFORATED STEEL EXHAUST DIFFUSER 4
SD-1 TITUS OMNI 24X24 STEEL PLAQUE FACE SUPPLY DIFFUSER 33
NTS4 DUCTWORK RADIUS ELBOWS
NTS5 DUCTWORK SQUARE VANE ELBOWS
NTS6 DUCTWORK TRANSITIONS
NTS7 PIPE HANGERS
NTS8 SUPPLY DUCTWORK TAKE-OFFS
NTS9
TERMINAL UNIT WATER COILS - PIPING
CONNECTIONS