Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANTS
321 4 5 6 7 8 9 10
ARCHITECT:
RENOVATE MAIN KITCHEN
SYRACUSE VA MEDICAL CENTER
800 IRVING AVE, SYRACUSE, NY 13210
PROJECT NO: 528A7-18-716
PROJECT DATA PROJECT DESCRIPTIONDRAWING INDEX
SITE LOCATION KEY PLAN
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827 (607)223-4334
C&S Companies 499 Col Eileen Collins Blvd Syracuse, New York, 13212
(315) 455-2000
RENOVATE MAIN KITCHEN
SYRACUSE VA MEDICAL CENTER
528A7-18-716
BUILDING 1
11/23/2022 JWE SRB
KITCHEN CONSULTANT:
Commercial Kitchen Consulting 21 Powers Rd Binghamton, New York, 13903
(607) 242-5571
BI
M
8A 7-
-7
R en ov at e
M ai n Ki tc he n/ R en ov at e
M ai n Ki tc he n_ R
.rv t
/2 1/
:5
0:
P M
T-100R
TITLE SHEET
Sheet Number Sheet Name
T-100R TITLE SHEET
G-100R GENERAL NOTES & SYMBOLS
G-101 CODE CONFORMANCE
G-102R1 CONSTRUCTION SEQUENCING AND INFECTION CONTROL PLAN
H-101R HAZARDOUS MATERIALS PLAN
AD-101 ARCHITECTURAL DEMOLITION PLAN
A-101 ARCHITECTURAL PLAN
A-102 ARCHITECTURAL REFLECTED CEILING PLAN
A-301 ENLARGED BATHROOM PLANS
A-501 TYPICAL DETAILS
A-502 WINDOW DETAILS & PARTITION TYPES
A-701 SIGNAGE PLAN AND DETAILS
FX-001 FIRE PROTECTION SYMBOLS, NOTES AND DETAILS
FX-101 FIRE PROTECTION PLAN
M-001 MECHANICAL NOTES AND ABBREVIATIONS
MD101 MECHANICAL DEMOLITION PLAN
M-101 MECHANICAL PLAN
M-102 MECHANICAL EQUIPMENT PLAN
M-103 MECHANICAL CEILING PLANS
M-501 MECHANICAL SCHEDULES AND DETAILS
M-701 MECHANICAL CONTROLS SCHEMATICS
M-702 AHU-16 CONTROLS MODIFICATIONS
E-001 ELECTRICAL ABBREVIATIONS
ED101 ELECTRICAL DEMOLITION PLAN
E-101 ELECTRICAL PLAN
E-501R ELECTRICAL SCHEDULES AND PARTIAL RISER DIAGRAMS
E-502 LIGHTING DETAILS AND SCHEDULES
P-001 PLUMBING SYMBOLS, NOTES, AND ABBREVIATIONS
P-101 PLUMBING PLAN
P-301 PLUMBING PLANS - ENLARGED
QC101R EXISTING FOODSERVICE EQUIPMENT LAYOUT
QC102R FOODSERVICE EQUIPMENT LAYOUT
QC103 FOODSERVICE EQUIPMENT LAYOUT
QC104 UTILITY DISTRIBUTION SYSTEM DRAWING
QC105 UTILITY DISTRIBUTION SYSTEM DRAWING
QC106 WALK-IN FREEZER DRAWING
QC107 WALK-IN COMBINATION COOLER DRAWING
QC108 WALK-IN COMBINATION COOLER DRAWING
SEISMIC ANALYSIS
STATE: NEW YORK
COUNTY: ONONDAGA
GOVERNMENT PROPERTY: DEPARTMENT OF VETERANS AFFAIRS
LOCAL JURISDICTION: SYRACUSE VAMC
YEAR AND CODE IN EFFECT BY DISCIPLINE:
• VA HVAC DESIGN MANUAL, NOVEMBER 1, 2017
• VA ELECTRICAL DESIGN MANUAL, DECEMBER 2015
• H-18-8 VA SEISMIC DESIGN REQUIREMENTS, OCTOBER 1 2016
• INTERNATIONAL BUILDING CODE (IBC), 2015
• INTERNATIONAL MECHANICAL CODE, 2015
• NFPA 70, NATIONAL ELECTRICAL CODE, 2017
• ASCE-7, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES, 2016
SITE ZONING: NA
SEISMIC ANALYSIS PER IBC:
• RISK CATEGORY IV, (ESSENTIAL FACILITY PER CHAP 7, TABLE 5 OF VA SEISMIC DESIGN MANUAL
• SITE CLASS D PER IBC 1613.3.2 (ASSUMED)
• SS = 0.141 (MAPPED SPECTRAL ACCELERATION FOR SHORT PERIOD PER IBC SECTION 1613.3.1)
• S1 = 0.051 (MAPPED SPECTRAL ACCELERATION FOR 1-SECOND PERIOD PER IBC SECTION 1613.3.1)
• FA = 1.6 (SITE COEFFICIENT PER IBC TABLE 1613.3.3(1))
• FV = 2.4 (SITE COEFFICIENT PER IBC TABLE 1613.3.3(2))
• SMS = FA SS = 0.225 (MAX CONSIDERED EARTHQUAKE SPECTRAL RESPONSE ACCELERATIONS FOR SHORT PERIOD PER IBC 1613.3.3)
• SM1 = FV S1 = 0.122 (MAX CONSIDERED EARTHQUAKE SPECTRAL RESPONSE ACCELERATIONS FOR 1-SECOND PERIOD PER IBC 1613.3.3)
• SDS = (2/3) SMS = 0.15
• SD1 = (2/3) SM1 = 0.081
• SEISMIC DESIGN CATEGORY: C
THE PROJECT WILL RENOVATE THE MAIN KITCHEN ON THE SECOND FLOOR AT THE SYRACUSE VA. THE PROJECT ENTAILS MECHANICAL UPGRADES TO FIX SOME SPACE COMFORT ISSUES, CONSOLIDATION AND REPLACEMENT OF EXISTING ELECTRICAL PANELS, AND REPLACEMENT OF ALL LIGHTING IN THE WORK AREA. THE KITCHEN WALK-IN COOLERS WILL BE REPLACED AND A NEW UTILITY DISTRIBUTION SYSTEM WILL BE PROVIDED. ARCHITECTURAL FEATURES WILL BE UPGRADED INCLUDING REPLACEMENT OF THE CEILINGS, PATCHING OF THE FLOOR TILES AND WALL, AND REMOVAL OF WALLS TO MAXIMIZE WORK AREA AND IMPROVE WORK FLOW. THE ENTIRE AREA OF RENOVATION IS APPROXIMATELY 6,600 SQUARE FEET.
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANTS
321 4 5 6 7 8 9 10
ARCHITECT:
Project Director
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827 (607)223-4334
C&S Companies 499 Col Eileen Collins Blvd Syracuse, New York, 13212
(315) 455-2000
SYRACUSE VA MEDICAL CENTER
528A7-18-716
BUILDING 1
06/23/2023 DW JD
KITCHEN CONSULTANT:
Commercial Kitchen Consulting 747 Conklin Road Binghamton, New York 13903
(607) 217-5389
100% CONSTRUCTION
DOCUMENTS
RENOVATE MAIN KITCHENGENERAL NOTES & SYMBOLS
G-100R
GENERAL NOTES
1. UNLESS SPECIFICALLY NOTED AS EXISTING, ALL ITEMS, EQUIPMENT, AND WORK SHOW IS NEW AND SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR.
2. DURING THE EXECUTION OF THIS CONTRACT, THE SITE AND BUILDINGS WILL BE OCCUPIED AND IN USE. WORK DONE UNDER THIS CONTRACT SHALL BE PERFORMED WITHOUT INCONVENIENCE TO THE OWNER INSOFAR
AS POSSIBLE. ALL WORK SHALL BE COORDINATED WITH THE CONTRACTING OFFICER ’ S REPRESENTATIVE AND IS SUBJECT TO HIS CONTINUOUS APPROVAL.
3. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT ALL EQUIPMENT INSTALLED MEETS THE INTENDED OPERATIONAL REQUIREMENTS OF THE VETERAN'S HEALTH ADMINISTRATION END-USER. SHOULD THERE
BE ANY DIFFERENCES IN PROVIDING UTILITY SERVICE TO THE EQUIPMENT OR CONFIGURATION/LOCATION OF THE EQUIPMENT SHOWN ON THE DESIGN DRAWINGS, THE CONTRACTOR MUST COORDINATE WITH THE CONTRACTING OFFICER AND CONTRACTING OFFICER REPRESENTATIVE AND PROPOSE MEANS AND METHODS TO MAKE ANY NECESSARY CHANGES AND ADJUSTMENTS TO ACCOMMODATE THE NEW EQUIPMENT INSTALLATION. THIS APPLIES TO ALL SUPPORT SERVICES AND FACILITIES REQUIRED TO PROPERLY INSTALL THE EQUIPMENT, ALLOWING IT TO FUNCTION ADEQUATELY AS PART OF THE SYSTEMS FOR WHICH IT WAS DESIGNED AND SELECTED. THESE CHARACTERISTICS INCLUDE, BUT ARE NOT LIMITED TO, WEIGHT, DIMENSIONS, ELECTRICAL, MECHANICAL, PLUMBING, AND UTILITY SERVICES. ACCOMMODATING SERVICES MAY ALSO BE REQUIRED, SUCH AS DIMENSIONS, LOCATIONS, AND SIZES OF SUPPORTING MEMBERS, CONNECTION SIZES FOR PIPES, ELECTRICAL SERVICE SIZE AND PROTECTION, ELECTRICAL CONNECTION LOCATION, UTILITY AND PLUMBING CONNECTION SIZES AND LOCATIONS. ALL REQUIRED CHANGES TO THE CONTRACT DRAWINGS AND SPECIFICATIONS MUST BE DESIGNED AND STAMPED BY REGISTERED ENGINEERS IN THE APPROPRIATE DISCIPLINE EMPLOYED BY THE CONTRACTOR AND INCLUDED AS PART OF THE EQUIPMENT SUBMITTALS. THESE CHANGES ARE SUBJECT TO THE APPROVAL OF THE PROJECT A/E AND THE CONTRACTING OFFICER'S REPRESENTATIVE. THE CONTRACTOR'S RESPONSIBILITY FOR FIELD VERIFICATION OF MEASUREMENTS, EQUIPMENT AND UTILITIES PRIOR TO CONSTRUCTION IS REFERENCED IN NUMEROUS SECTIONS OF THE CONTRACT SPECIFICATIONS. ANY NEW WORK CHANGE REQUESTS BY THE CONTRACTOR, AS A RESULT OF ANY DEVIATION, WILL BE CONSIDERED ON A CASE-BY-CASE BASIS BY THE CONTRACTING OFFICER WHO WILL MAKE THE DETERMINATION, BASED ON REVIEW OF THE DRAWINGS AND SPECIFICATIONS, AS TO WHAT IS FAIR AND REASONABLE TO BOTH THE GOVERNMENT AND THE CONTRACTOR.
4. PRELIMINARY AIR BALANCE REPORT. AT THE BEGINNING OF THE WORK IMMEDIATELY AFTER RECEIVING NOTICE TO PROCEED, THE CONTRACTOR SHALL MEASURE AND SUBMIT A PRELIMINARY BALANCE REPORT IN COMPLIANCE WITH THE SPECIFICATIONS FOR ALL TERMINAL UNITS IN THE AREA OF WORK OF THIS PROJECT. MEASURE ALL SUPPLY, RETURN, AND EXHAUST AIR QUANTITIES. IF AN AHU SERVES THE ENTIRE SPACE, MEASURE AHU IN FULL COOLING, MAX AIR FLOW, AT THE AHU, AND MAX AIR FLOW AT ALL ZONES AND ALL DIFFUSERS; MEASURE THE DISCHARGE STATIC PRESSURE AT THE AHU AND THE SUCTION STATIC PRESSURE AT THE AHU. THEN EACH ZONE SHALL BE SET TO FULL REHEAT AND THE AIR QUANTITY MEASURED AT EACH OUTLET AND THE WATER FLOWS AND TEMPERATURES MEASURED AT EACH REHEAT BOX. OTHER TERMINAL UNITS TO INCLUDE BUT NOT LIMITED TO: FAN COIL UNITS, RADIANT PANELS, AND CHILLED BEAM SHALL HAVE BOTH HYDRONIC AND AIRFLOW MEASURED AT FULL CAPACITY. THE EXISTING MECHANICAL DRAWINGS WILL BE PROVIDED BY THE FACILITY ENGINEERING DEPARTMENT AT THE VA. SUBMIT A BLANK AIR BALANCE REPORT FOR APPROVAL PRIOR TO BEGINNING THE PRELIMINARY AIR BALANCE.
5. BEFORE ANY DEMOLITION OR CONSTRUCTION WORK IS BEGUN, THE CONTRACTOR AND THE CONTRACTING OFFICER ’ S REPRESENTATIVE SHALL SURVEY THE EXISTING CEILINGS TO BE REMOVED AND REPLACED FOR THEIR EXISTING CONDITION. THIS SURVEY WILL BE USED BY THE CONTRACTING OFFICER ’ S REPRESENTATIVE AT JOB COMPLETION TO DETERMINE WHICH RE-INSTALLED CEILING COMPONENTS MUST BE REPLACED
WITH NEW.
6. REQUEST APPROVAL FROM THE CONTRACTING OFFICER ’ S REPRESENTATIVE SEVEN DAYS IN ADVANCE FOR THE SHUTDOWN OF ANY EXISTING SYSTEM.
7. FINAL ADVANCE NOTICE OF 48 HOURS SHALL BE GIVEN TO THE CONTRACTING OFFICER ’ S REPRESENTATIVE PRIOR TO THE PROPOSED SHUTDOWN OF ANY SYSTEM.
8. THE CLOSING AND OPENING OF VALVES SHALL BE WITNESSED BY THE CONTRACTING OFFICER ’ S REPRESENTATIVE; NOTIFY LOCAL AUTHORITIES AS REQUIRED.
9. PROVIDE ADEQUATE FIRE PROTECTION IN THE ENTIRE CONSTRUCTION AREA FOR THE DURATION OF THE CONSTRUCTION PERIOD. REFER TO SPECIFICATION DIVISION 1, “ GENERAL REQUIREMENTS ” , “ FIRE SAFETY
REQUIREMENTS ”.
10. THE ENTIRE EXISTING FIRE PROTECTION SYSTEM SHALL BE RESTORED TO FULL OPERATION AT THE END OF EACH WORKING DAY.
11. ALL EXISTING FIRE ALARMS AND FIRE EXITS AND ANY OTHER ASPECT OF THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN IN FULL OPERATION. THE COST OF RESPONSE TO ANY FALSE ALARM AS CHARGED BY ANY
LOCAL FIRE DEPARTMENT SHALL BE PAID BY THE CONTRACTOR.
12. THE GENERAL NOTES ON THIS SHEET APPLY TO ALL THE DRAWING DISCIPLINES.
13. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE, ALTHOUGH NO ATTEMPT WAS MADE TO SHOW EVERY OFFSET, FITTING, BEAM, PIPE SUPPORT. ANY CHANGES REQUIRED TO FIT EQUIPMENT, PIPING AND
DUCTWORK, THAT IS NOT CLEAR FROM THE DESIGN DRAWINGS, SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER AND CONTRACTING OFFICER REPRESENTATIVE. THESE CHANGES ARE SUBJECT TO THE APPROVAL OF THE PROJECT A/E AND THE CONTRACTING OFFICER'S REPRESENTATIVE. THE CONTRACTOR'S RESPONSIBILITY FOR FIELD VERIFICATION OF MEASUREMENTS, EQUIPMENT AND UTILITIES PRIOR TO CONSTRUCTION IS REFERENCED IN NUMEROUS SECTIONS OF THE CONTRACT SPECIFICATIONS. ANY NEW WORK CHANGE REQUESTS BY THE CONTRACTOR, AS A RESULT OF ANY DEVIATION, WILL BE CONSIDERED ON A CASE-BY-CASE BASIS BY THE CONTRACTING OFFICER, WHO WILL MAKE THE DETERMINATION, BASED ON REVIEW OF THE DRAWINGS AND SPECIFICATIONS, AS TO WHAT IS FAIR AND REASONABLE TO BOTH THE
GOVERNMENT AND THE CONTRACTOR.
14. THE WORK INCLUDES ALL ITEMS OF THE SPECIFICATIONS.
15. VISIT THE SITE AND BE FULLY COGNIZANT OF ALL CONDITIONS PRIOR TO SUBMITTING BID. REPORT ANY DISCREPANCIES TO THE ENGINEER PRIOR TO SUBMITTAL OF BID.
16. DO NOT BEGIN FABRICATION, CUT ANY MEMBERS, OR BEGIN INSTALLATION UNTIL THE SUBMITTALS AND SHOP DRAWINGS HAVE BEEN APPROVED. ANY WORK CONSTRUCTED OR INSTALLED PRIOR TO THE APPROVAL OF
SUBMITTALS AND SHOP DRAWINGS SHALL BE AT THE CONTRACTOR ’ S RISK AND SHALL BE REMOVED AND REINSTALLED OR RECONSTRUCTED AT THE CONTRACTOR ’ S EXPENSE AT THE REQUEST OF THE CONTRACTING OFFICER ’ S REPRESENTATIVE TO THE COMPLETE SATISFACTION OF THE CONTRACTING OFFICER ’ S REPRESENTATIVE.
17. DO NOT PENETRATE OR CUT ANY STRUCTURAL MEMBERS NOT SPECIFICALLY SHOWN ON THE DRAWINGS (E.G., JOISTS, BEAMS, ETC.). IF STRUCTURAL MEMBERS CONFLICT WITH ROUTING, CONTACT THE CONTRACTING OFFICER ’ S REPRESENTATIVE FOR DIRECTION BEFORE PROCEEDING. EXERCISE CAUTION IN CUTTING CONCRETE FLOORS AND WALLS TO AVOID EXISTING UTILITIES WHICH MAY BE LOCATED IN AND UNDER CONCRETE
SURFACES.
18. THE CONTRACTOR SHALL PROVIDE NEW OPENINGS IN WALLS, FLOOR, AND ROOF, AND PATCH EXISTING OPENINGS IN CONJUNCTION WITH THE DEMOLITION AND INSTALLATION OF THE NEW BUILDING COMPONENTS, INCLUDING MECHANICAL, PLUMBING, ELECTRICAL, AND GENERAL CONTRACTOR ’ S ITEMS. ALL NECESSARY FRAMING, COUNTER-FLASHING, ETC. SHALL BE INCLUDED.
19. FOR ALL FLOOR, WALL, AND ROOF PENETRATION, VERIFY THE LOCATION OF THE (E) STRUCTURAL MEMBERS PRIOR TO DRILLING AND CUTTING, RELOCATE OPENINGS AS REQUIRED AND OFFSET DUCTS, PIPES, CONDUIT, ETC. AS APPROPRIATE. REVIEW THE STRUCTURAL DRAWINGS IN THE ENGINEERING OFFICE.
20. WHERE THERE IS A CONFLICT ON THE PLANS, SPECIFICATIONS, NOTES, GENERAL NOTES, REFERENCES, PUBLICATIONS, CODES, ETC. WITH RESPECT TO MATERIALS, PRODUCTS, METHODS, WORKMANSHIP, PROCEDURE, EXECUTION, ETC. THE MOST STRINGENT OR BENEFICIAL TO THE OWNER AS DETERMINED BY THE CONTRACTING OFFICER ’ S REPRESENTATIVE SHALL BE UTILIZED OR INSTALLED. NO RELIEF OR EXTRA PAYMENT SHALL BE MADE TO THE CONTRACTOR BECAUSE OF THE INTERPRETATION OF THE CONTRACTING OFFICER ’S REPRESENTATIVE.
21. ALL WORK SHALL BE DONE WITH COMPLETE COMPLIANCE WITH THE PUBLISHED EDITIONS OF THE APPLICABLE CODES AND STANDARDS WHETHER STATUTORY OR NOT. ALL WORK SHALL BE INSTALLED TO COMPLY WITH THE UNIFORM BUILDING MECHANICAL, PLUMBING, ELECTRICAL, AND FIRE CODES, NATIONAL ELECTRICAL CODE, UNDERWRITER ’ S LABORATORY, INC., AMERICAN NATIONAL STANDARD INSTITUTE, INC., NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION, BASIC ELECTRICAL REGULATIONS, AND CODES AND STANDARDS OF THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA). IF ANY PART OF THE INSTALLATION DOES NOT MEET CODE, NOTIFY THE CONTRACTING OFFICER ’ S REPRESENTATIVE PRIOR TO BEGINNING THE INSTALLATION. IF ANY PART OF THE PROJECT CANNOT BE INSTALLED TO CONFORM WITH THE PLANS AND/OR SPECIFICATIONS, NOTIFY THE CONTRACTING OFFICER ’ S REPRESENTATIVE PRIOR TO BEGINNING THE INSTALLATION.
22. ALL EXISTING DUCTWORK, PIPING, CONDUIT, AND MECHANICAL, PLUMBING, AND ELECTRICAL EQUIPMENT NOT TO BE REUSED OR REMAIN IN SERVICE SHALL BE REMOVED FROM THE FACILITY. THE CONTRACTING OFFICER ’ S REPRESENTATIVE HAS THE OPTION TO RECLAIM ANY DEMOLISHED MATERIALS OR EQUIPMENT FOR THE GOVERNMENT, IN WHICH CASE IT SHALL BE DELIVERED TO THE LOCATION DESIGNATED BY THE
CONTRACTING OFFICER ’ S REPRESENTATIVE.
23. FOR EACH PHASE AND BEFORE INTERRUPTING EACH (E) UTILITY, DETERMINE, IN ADVANCE, IF ANY DOWNSTREAM SERVICE BEYOND THE CONSTRUCTION AREA OF THE PHASE WILL BE INTERRUPTED, AND PROPOSE MEANS AND METHODS TO PROVIDE A TEMPORARY SERVICE BYPASSING THE CONSTRUCTION AREA. THE CONTRACTOR'S RESPONSIBILITY FOR FIELD VERIFICATION OF MEASUREMENTS, EQUIPMENT AND UTILITIES PRIOR TO CONSTRUCTION IS REFERENCED IN NUMEROUS SECTIONS OF THE CONTRACT SPECIFICATIONS. ANY NEW WORK CHANGE REQUESTS BY THE CONTRACTOR, AS A RESULT OF ANY DEVIATION, WILL BE CONSIDERED ON A CASE-BY-CASE BASIS BY THE CONTRACTING OFFICER, WHO WILL MAKE THE DETERMINATION, BASED ON REVIEW OF THE DRAWINGS AND SPECIFICATIONS, AS TO WHAT IS FAIR AND REASONABLE TO BOTH THE
GOVERNMENT AND THE CONTRACTOR.
24. THE FLOOR AREAS BELOW OVERHEAD WORK, WHERE WELDING “ HOT WORK ” IS TO BE PERFORMED, SHALL BE CLEARED TO A MINIMUM DISTANCE OF 36 FEET (OR MORE BASED ON MOST STRINGENT BETWEEN FACILITY POLICY, MANUFACTURER'S RECOMMENDATIONS, OR NFPA 241) BEYOND THE POINT DIRECTLY BELOW THE OVERHEAD “ HOT WORK ” . ALL FLAMMABLE MATERIALS SHALL BE CLEARED TO A DISTANCE 50 FEET (OR MORE BASED ON MOST STRINGENT BETWEEN FACILITY POLICY, MANUFACTURER'S RECOMMENDATIONS, OR NFPA 241) BEYOND THE POINT DIRECTLY BELOW THE OVERHEAD “ HOT WORK ” .
25. EXISTING DUCTWORK, DOMESTIC COLD-WATER PIPING, DOMESTIC HOT WATER PIPING, CHILLED AND HEATING HOT WATER PIPING, WASTE, VENT, FIRE SPRINKLER LINES, FIRE ALARM EQUIPMENT, ELECTRICAL CONDUIT, TELEPHONE CONDUIT, COMMUNICATION CONDUIT, PNEUMATIC TUBING MAY HAVE TO BE RELOCATED TO FACILITATE THE INSTALLATION OF THE WORK. THE CONTRACTOR MUST COORDINATE WITH THE CONTRACTING OFFICER AND CONTRACTING OFFICER REPRESENTATIVE AND PROPOSE MEANS AND METHODS TO MAKE ANY NECESSARY CHANGES AND ADJUSTMENTS TO ACCOMPLISH THE WORK. THE CONTRACTOR'S RESPONSIBILITY FOR FIELD VERIFICATION OF MEASUREMENTS, EQUIPMENT AND UTILITIES PRIOR TO CONSTRUCTION IS REFERENCED IN NUMEROUS SECTIONS OF THE CONTRACT SPECIFICATIONS. ANY NEW WORK CHANGE REQUESTS BY THE CONTRACTOR, AS A RESULT OF ANY DEVIATION, WILL BE CONSIDERED ON A CASE-BY-CASE BASIS BY THE CONTRACTING OFFICER, WHO WILL MAKE THE DETERMINATION, BASED ON REVIEW OF THE DRAWINGS AND SPECIFICATIONS, AS TO WHAT IS FAIR AND REASONABLE TO BOTH THE GOVERNMENT AND THE CONTRACTOR.
26. THE CONTRACTOR IS HEREBY NOTIFIED THAT SOME WORK MAY BE REQUIRED OUTSIDE OF THE AREAS SHOWN ON THESE DRAWINGS. THIS COULD INCLUDE CONTROL MODIFICATIONS OR CONNECTIONS AT REMOTE
LOCATIONS, CONTROL PANELS, CPU ’ S, ETC.
27. BECAUSE OF THE SMALL SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO INDICATE ALL OFFSETS, TRANSITIONS, FITTINGS, AND ACCESSORIES THAT MAY BE REQUIRED. COORDINATE ALL THE WORK OF ALL THE TRADES TO INSURE ALL DUCTS, PIPES, CONDUITS, ETC. DO NOT CONFLICT AND CLEAR STRUCTURAL AND ARCHITECTURAL MEMBERS.
28. THE CONTRACTOR SHALL PAY FOR ALL DAMAGE, INCLUDING WATER DAMAGE, TO PROPERTY AND EQUIPMENT CAUSED BY HIS WORK THROUGHOUT THE CONSTRUCTION AND WARRANTEE PERIOD.
29. ALL CEILING DEMOLITION WORK SHALL BE DONE AFTER NORMAL WORKING HOURS. THE INSTALLATION OF THE NEW CEILING SHALL BE DONE AFTER NORMAL WORKING HOURS. THE WORK AREA SHALL BE CLEANED
BEFORE THE START OF EACH WORKING DAY.
30. REMOVE T-BARS AND 2X4 CEILING PANELS AS REQUIRED FOR THE DEMOLITION AND THE INSTALLATION OF THE NEW WORK. REINSTALL EXISTING OR REPLACE WITH NEW AS REQUIRED TO THE SATISFACTION OF THE
CONTRACTING OFFICER ’ S REPRESENTATIVE. FOR ANY HARD CEILING AREA, CUT AND DEMOLISH ENOUGH OF THE HARD CEILING TO DO THE WORK REQUIRED. REBUILD AND PATCH THE DEMOLISHED. FINISH AND PAINT TO MATCH EXISTING TO THE SATISFACTION OF THE CONTRACTING OFFICER ’ S REPRESENTATIVE.
31. ALL VALVES, VOLUME DAMPERS, CONTROL DEVICES, VAR, ETC. SHALL BE INSTALLED IN AN ACCESSIBLE LOCATION.
32. ALL UL LISTED EQUIPMENT SHALL BE INSTALLED AS PER LISTING OR LABELING. MAXIMUM FUSE SIZES MEANS FUSE PROTECTION REQUIRED.
33. PATCH AND PAINT TO MATCH EXISTING, ALL SURFACES DAMAGED BY THE DEMOLITION AND ALL OPENINGS NOT TO BE REUSED.
34. REPAIR DAMAGE TO CEILING, WALLS, ETC. TO THE SATISFACTION OF THE CONTRACTING OFFICER ’ S REPRESENTATIVE.
35. WHEN A DETAIL OR NOTE IS IDENTIFIED AS TYPICAL, THE CONTRACTOR IS TO APPLY THE DETAIL OR NOTE TO EVERY SIMILAR CONDITION, WHETHER OR NOT THE REFERENCED DETAIL OR NOTE IS REPEATED OR
REFERENCED.
36. WHERE NO CONSTRUCTION DETAIL IS INDICATED, SUCH WORK SHALL BE SIMILAR TO COMPARABLE WORK DETAILED OR NOTED ELSEWHERE OR TO MATCH EXISTING CONDITIONS, SUBJECT TO THE APPROVAL OF THE
CONTRACTING OFFICER ’ S REPRESENTATIVE.
37. ALL HOLES, VOIDS, AND DAMAGED OR UNEVEN SURFACES WHICH ARE CAUSED BY THE CONTRACTOR’S WORK AND WHICH REMAIN EXPOSED IN THE WALL, FLOOR, CEILING, OR OTHER SURFACES SHALL BE PATCHED, REPAIRED, AND BROUGHT FLUSH WITH THE ADJACENT CONSTRUCTION. SUCH SURFACES, NOT CONCEALED BY THE NEW CONSTRUCTION, SHALL MATCH IN EVERY RESPECT THE EXISTING NON-DAMAGED CONSTRUCTION. REMOVE EXISTING UTILITIES BACK BEHIND EXISTING SURFACES AND CAP SO AS NOT TO INTERFERE WITH NEW PATCHES.
38. WHEREVER NEW WALL, FLOOR, OR CEILING FINISHES ARE INDICATED, THE CONTRACTOR SHALL BRING EXISTING ELECTRICAL, MECHANICAL, PLUMBING, AND OTHER BUILDING COMPONENTS FLUSH WITH THE NEW
FINISHED SURFACES IF APPROPRIATE.
39. THE DEMOLITION SHALL INCLUDE ALL ASSOCIATED ANCHORAGES, HANGERS, SUPPORTS, BRACES, FASTENERS, MASTIC, MORTAR, LATH, AND RELATED ITEMS. THE EXISTING SUBSTRATE, INCLUDING CONCRETE, MASONRY, METAL FRAMING AND FURRING SHALL BE REPAIRED WHERE DAMAGE BY THE CONTRACTOR’S WORK.
40. PROVIDE ALL VALVES, INSTRUMENTS, FITTINGS, ETC. AS SHOWN ON THE PIPING DIAGRAMS, SCHEMATICS, ETC. IT IS NOT POSSIBLE TO SHOW ALL VALVES, INSTRUMENTS, ETC. ON THE PLANS, HOWEVER, SELECTED VALVES HAVE BEEN SHOWN FOR REFERENCE. ALL VALVES SHALL BE ACCESSIBLE FROM THE FLOOR OR FROM FIXED PLATFORMS.
41. ALL NEW FIRE ALARM DEVICES INSTALLED IN HVAC EQUIPMENT SUCH AS SMOKE DETECTORS, SMOKE DAMPERS, FIRE/SMOKE DAMPERS, ETC. SHALL BE CONNECTED TO THE MAIN FIRE ALARM PANEL.
42. ALL EQUIPMENT AND MATERIALS SUBJECT TO THE WEATHER THAT ARE NOT FACTORY PAINTED SHALL BE FIELD PAINTED AND WEATHER PROOFED WITH PRIMER, AND TWO COATS OF EXTERIOR PAINT. SEE THE
SPECIFICATIONS. MATCH THE COLOR OF THE EXISTING BUILDING EXTERIOR. THE COLOR AND QUANTITY OF THE PAINT IS SUBJECT TO THE APPROVAL OF THE CONTRACTING OFFICER ’ S REPRESENTATIVE. SUBMITTAL
REQUIRED.
43. THE CONTROLS CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR MAKING THE CONTROL SYSTEM COMPLETE AND FULLY OPERABLE. THE CONNECTION TO THE EXISTING CONTROL SYSTEM SHALL BE COMPLETE SUCH THAT ALL NEW MONITORING AND CONTROL POINTS ARE RECOGNIZED BY THE EXISTING CONTROL SYSTEM AND THAT ALL NEW POINTS CAN BE READ, ACTUATED, AND RESET FROM THE EXISTING FRONT END, AND VICE-VERSA. THE ENGINEER SHALL BE NOTIFIED WHEN EACH PHASE OF THE SYSTEM HAS BEEN COMPLETELY CHECKED OUT, ADJUSTED, CALIBRATED, AND PUT INTO FINAL WORKING CONDITION WITH ALL THE TROUBLESHOOTING COMPLETED. A SUBSEQUENT JOBSITE MEETING WILL BE SCHEDULED WITH TWO WEEKS NOTICE AT WHICH TIME THE CONTROLS CONTRACTOR WILL DEMONSTRATE THE OPERATION OF THE CONTROL SYSTEMS TO ALL CONCERNED. IF ANY ITEMS OF THE CONTROL SEQUENCE CANNOT BE SUCCESSFULLY DEMONSTRATED OR REQUIRE FURTHER TROUBLESHOOTING, A SUBSEQUENT CONTROLS INSPECTION WILL BE REQUIRED AND WILL BE AT THE CONTRACTOR ’ S EXPENSE. THIS PROVISION SHALL BE A CONDITION OF FINAL ACCEPTANCE. THE CONTRACTOR SHALL BE PREPARED TO DEMONSTRATE ALL ITEMS IN THE SEQUENCE OF OPERATION. SUBSEQUENT CONTROLS DEMONSTRATIONS AND VERIFICATIONS WILL BE REQUIRED AT THE COMPLETION OF THE PROJECT.
FD
WOMEN'S TOILET
C209
MEN'S TOILET
C207
DIETICIANS
C258
OI&T
C264
INGREDIENT
STORAGE
C205D
KITCHEN
FACILITY
C205
NOURISHMENT/
SNACK PREP
C205I
DISH ROOM
C205J
ELEV. LOBBY
B200
SHAFT
203A
TOILET
B204
SECTION CHIEF
C205G
MANAGER
C260
SALAD PREP
C205F
CALL CENTER
C205H
CART WASH
C205K
TRAINING ROOM
C205C
CHIEF N&FS
C262
COOLER
C205B
FREEZER
C205E
TRAVEL DISTANCE
151'
TRAVEL DISTANCE
172'
EXIST
STAIR
EXIST
STAIR
EXIST
STAIR
MECH
C205A
ZONE 28 FLOW AND
TAMPER SWITCHES
NOTE: ZONE 29 FLOW AND
DAMPER SWITCHES ARE IN
THE BACK STAIRCASE.
OFFICE
C205N
LIFE SAFETY LEGEND
2 HOUR FIRE RATED
SMOKE BARRIER
TRAVEL DISTANCE
EXIT
AREA NOT IN CONTRACT
Infection Control Risk Assessment
Matrix of Precautions for Construction & Renovation
Step One:
Using the following table, identify the Type of Construction Project Activity (Type A-D)
TYPE A Inspection and Non-Invasive Activities.
Includes, but is not limited to:
removal of ceiling tiles for visual inspection only, e.g., limited to 1 tile per 50 square feet painting (but not sanding) wallcovering, electrical trim work, minor plumbing, and activities which do not generate dust or require cutting of walls or access to ceilings other than for visual inspection.
TYPE B Small scale, short duration activities which create minimal dust Includes, but is not limited to:
installation of telephone and computer cabling access to chase spacescutting of walls or ceiling where dust migration can be controlled.
TYPE C Work that generates a moderate to high level of dust or requires demolition or removal of any fixed building components or assemblies Includes, but is not limited to:
sanding of walls for painting or wall covering removal of floorcoverings, ceiling tiles and casework new wall construction minor duct work or electrical work above ceilings major cabling activities any activity which cannot be completed within a single workshift.
TYPE D Major demolition and construction projects Includes, but is not limited to:
activities which require consecutive work shifts requires heavy demolition or removal of a complete cabling system new construction.
Step Two:
Using the following table, identify the Patient Risk Groups that will be affected.
If more than one risk group will be affected, select the higher risk group:
Low Risk Medium Risk High Risk Highest Risk
• Office areas • Cardiology
• Echocardiography
• Endoscopy
• Nuclear Medicine
• Physical Therapy
• Radiology/MRI
• Respiratory Therapy
• CCU
• Emergency Room
• Labor & Delivery
• Laboratories (specimen)
• Medical Units
• Newborn Nursery
• Outpatient Surgery
• Pediatrics
• Pharmacy
• Post Anesthesia Care Unit
• Surgical Units
• Any area caring for immunocompromised patients
• Burn Unit
• Cardiac Cath Lab
• Central Sterile Supply
• Intensive Care Units
• Negative pressure isolation rooms
• Oncology
• Operating rooms including C-section rooms
Step Three: Match the
Patient Risk Group (Low, Medium, High, Highest) with the planned …
Construction Project Type (A, B, C, D) on the following matrix, to find the … Class of Precautions (I, II, III or IV) or level of infection control activities required.
IC Matrix - Class of Precautions: Construction Project by Patient Risk
Construction Project Type
Note: Infection Control approval will be required when the Construction Activity and Risk Level indicate that Class III or Class IV control procedures are necessary.
Patient Risk Group TYPE A TYPE B TYPE C TYPE D
LOW Risk Group I II II III/IV
MEDIUM Risk Group I II III IV
HIGH Risk Group I II III/IV IV HIGHEST Risk Group II III/IV III/IV IV
Description of Required Infection Control Precautions by Class
During Construction Project Upon Completion of Project
1. Remove or Isolate HVAC system in area where work is being done to prevent contamination of duct system.
2. Complete all critical barriers i.e. sheetrock, plywood, plastic, to seal area from non work area or implement control cube method (cart with plastic covering and sealed connection to work site with HEPA vacuum for vacuuming prior to exit) before construction begins.
3. Maintain negative air pressure within work site utilizing HEPA equipped air filtration units.
4. Contain construction waste before transport in tightly covered containers.
5. Cover transport receptacles or carts. Tape covering unless solid lid.
1. Do not remove barriers from work area until completed project is inspected by the owner’s Safety Department and Infection Prevention & Control Department and thoroughly cleaned by the owner’s Environmental Services Department.
2. Remove barrier materials carefully to minimize spreading of dirt and debris associated with construction.
3. Vacuum work area with HEPA filtered vacuums.
4. Wet mop area with cleaner/disinfectant.
5. Upon completion, restore HVAC system where work was performed.
C
LA
S S
II
I
APPLICABLE CODES
THE VA HAS ADOPTED THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS AS A MINIMUM FOR ALL PROJECTS PERFORMED IN THE MODERNIZATION, ALTERATION, ADDITION, OR IMPROVEMENT OF ITS REAL PROPERTY AND THE CONSTRUCTION OF NEW STRUCTURES. VA DESIGN MANUALS AND MASTER SPECIFICATIONS SPECIFY OTHER CODES AND STANDARDS THAT THE VA FOLLOWS ON ITS PROJECTS:
• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE
ON THE TECHNICAL INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).
• INTERNATIONAL BUILDING CODE (IBC)
• NFPA 101 LIFE SAFETY CODE
• NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900
• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.
• VA SEISMIC DESIGN REQUIREMENTS, H-18-8
• NATIONAL ELECTRIC CODE (NEC)
• INTERNATIONAL PLUMBING CODE
• SAFETY CODE FOR ELEVATORS AND ESCALATORS, AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) A 17.1
• ASME BOILER AND PRESSURE VESSEL CODE
• ASME CODE FOR PRESSURE PIPING
• ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS) INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN GUIDE
(PG-18-13)
• BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, AMERICAN CONCRETE INSTITUTE AND COMMENTARY (ACI 318)
• MANUAL OF STEEL CONSTRUCTION, LOAD AND RESISTANCE FACTOR DESIGN SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS, AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
• ENERGY POLICY ACT (EPACT)
• DOE INTERIM FINAL RULE: ENERGY CONSERVATIONS STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULIT-FAMILY HIGH-RISE
RESIDENTIAL BUILDINGS AND NEW LOW-RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434 AND 435.
• FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING (MOU)
• EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENTAL, ENERGY, AND TRANSPORTATION MANAGEMENT.
• THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL REQUIREMENTS SECTION 01010 OF THE VA MASTER
CONSTRUCTION SPECIFICATION.
• VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD 62.1.
• SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15.
KITCHEN
FACILITY
C205
STAIRS
STAIRS
SPRINKLER ZONE 28
SPRINKLER ZONE 29
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANTS
321 4 5 6 7 8 9 10
ARCHITECT:
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827 (607)223-4334
C&S Architects, Engineers & Landscape Architect, PLLC 499 Col. Elieen Collins Blvd Syracuse, New York 13212
(315) 455-2000 www.cscos.com
RENOVATE MAIN KITCHEN
SYRACUSE VA MEDICAL CENTER
528A7-18-716
BUILDING 1
11/23/2022
KITCHEN CONSULTANT:
Commercial Kitchen Consulting 21 Powers Rd Binghamton, New York, 13903
(607) 242-5571 c s c o s .c o m
\c s fi le
\e n g \P ro je c t\
V
W a ts o n
E n g in e e ri n g \V
V A
S y ra c u s e
K it c h e n \D e s ig n \C
A D
D \R e v it \0
-C E
N T
R A
L
A R
C H
IT
E
C T
U R
A L \V
A R
C H
IT
E
C T
U R
A L .r v t
/2
/2
:1
:0
P
M
G-101
CODE CONFORMANCE
KBPMWL
1/8" = 1'-0"
CODE CONFORMANCE PLAN
AREA OF WORK 9,037 SQUARE FEET
APPLICABLE CODE 2018 NFPA 101
OCCUPANCY CLASSIFICATION CHAPTER 19 EXISTING HEALTH CARE OCCUPANCIES
CHAPTER 18 NEW HEALTH CARE OCCUPANCIES
FIRE PROTECTION FULLY SPRINKLERED
COOKING FACILITIES PROTECT IN ACCORDANCE WITH NFPA 96
OCCUPANT LOAD KITCHEN 100 SF/PERSON 6,470 /100 = 65 OCCUPANTS
TRAVEL DISTANCE 200 FT
COMMON PATH OF TRAVEL 100 FT
DEAD END CORRIDORS 30 FT
INTERIOR FINISHES NEW FINISHES SHALL BE CLASS A
SMOKE COMPARTMENT 40,000 SQ FT WHERE NO PATIENT SLEEPING AREAS
FIRE RESISTANCE REQUIREMENTS:
EXISTING RATED FIRE BARRIERS AND NON-RATED SMOKE BARRIERS ARE SHOWN AS PER VAMC SYRACUSE BUILDING NO. 1 LIFE SAFETY DRAWING REVISED APRIL 2019. EXISTING BARRIERS ARE MAINTAINED BY THE
WORK OF THIS PROJECT.
CODE DESIGN CRITERIA
SPRINKLER ZONE KEY PLAN:
SYMBOL LEGEND:
KEY PLAN: SECOND FLOOR
PLAN
NORTH
PROJECT
AREA
BACK STAIRWELL
MECH
C205A
ELEV. LOBBY
B200
NIC
NIC
NIC
SM
SM
SM
SM
SM SM SM
SM
SM
SM
SM
DB
DB
DB
DB
2-HR CONSTRUCTION WALL
B261A
DIRTYB261
RETHERM
B202H
WASH
ROOM
C265I
C202G
REFRIG
C265A
SUPER
OFFICE
B202B
REFRIG
B266 C203
ELEC
B264
STOR
C201
HR CL
C203A
SHAFT
B202C
REFRIG
B202D
REFRIG
C261
OFFICES
C202E
SALAD
PREP
C202F
C206C204
C260
DIETICIANS
C260A
MANAGER
C262
CHIEF N&FS
B202
KITCHEN
B202A
N
N
N
N
N
MENS
TOILET
WOMENS
TOILET
INGREDIENT
STORAGE
BREAK
ROOM
NOURISHMENT/
SNACK PREP
SUPER
OFFICES
2-HR
CONSTRUCTION
WALL
2-HR
CONSTRUCTION
WALL
3 3 3
1 1
SM
PHASE 1 CONSTRUCTION AREA (PRE UDS TASKS)
PHASE 2 CONSTRUCTION AREA (UDS INSTALL PHASE)
PHASE 3 CONSTRUCTION AREA (ANCILLARY TASKS NOT UDS DEPENDENT)
NEGATIVE AIR
STICKY MAT
DUST BARRIER
N
SM
DB
MECH
C205A
ELEV. LOBBY
B200
NIC
NIC
NIC
SM
SM
SM
SM SM SM
SM
SM
SM
SM
DB
DB
DB
DB
2-HR CONSTRUCTION WALL
CART WASH
C205K
DISH ROOM
C205J
NOURISHMENT/
SNACK PREP
C205I
KITCHEN
FACILITY
C205
SUPERVISORS
C205H
SHAFT
203A
COOLER
C205B
EMPLOYEE AREA
C205F
SECTION CHIEF
C205G
INGREDIENT
STORAGE
C205D
FREEZER
C205E
CALL CENTER
C205C
WOMEN'S TOILET
C209
MEN'S TOILET
C207
DIETICIANS
C258
MANAGER
C260
CHIEF N&FS
C262
N
N
N
N
N
2-HR
CONSTRUCTION
WALL
2-HR
CONSTRUCTION
WALL
3 1
2 1
SM
3 3 3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANTS
321 4 5 6 7 8 9 10
ARCHITECT:
Project Director
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827 (607)223-4334
C&S Companies 499 Col Eileen Collins Blvd Syracuse, New York, 13212
(315) 455-2000
SYRACUSE VA MEDICAL CENTER
528A7-18-716
BUILDING 1
06/06/2023 DW JD
KITCHEN CONSULTANT:
Commercial Kitchen Consulting 747 Conklin Road Binghamton, New York 13903
(607) 217-5389
GENERAL NOTES:
KEYED NOTES:
KEY PLAN:
DRAWING LEGEND:
/1
7/
:2 9:
P
M
G-102R1
CONSTRUCTION SEQUENCING AND
INFECTION CONTROL PLAN
1/8" = 1'-0"1 1/8" = 1'-0"2 CONSTRUCTION SEQUENCING AND ICRA PLAN - NEW
N
SEQUENCING NARRATIVE:
ALL TASKS NOT INCLUDED - NARRATIVE DESIGNED TO GIVE CONTRACTOR A GENERAL IDEA OF WORK
FLOW. NOTE THAT MANY ROOM NUMBERS ARE BEING CHANGED ON THIS PROJECT AS WELL AS
FUNCTIONAL USES OF THE SPACES.
THE CONTRACTOR SHALL SUBMIT A CONSTRUCTION PHASING PLAN WHICH HAS BEEN COORDINATED WITH
CURRENT VA SITE CONDITIONS FOR REVIEW.
KITCHEN WILL REMAIN OCCUPIED THROUGHOUT THE DURATION OF THE PROJECT. KITCHEN OPERATION OCCURS EVERY DAY. ALL WORK INSIDE KITCHEN MUST BE CONDUCTED BETWEEN THE HOURS OF 8:00 PM
AND 5:00AM.
THE VA WILL VACATE C260A AND C262 FOR THE DURATION OF THE PROJECT.
ABATEMENT MUST BE COORDINATED WITH SEQUENCING TASKS BELOW.
SOME AREAS OUTSIDE OF MAIN KITCHEN AREA THAT CAN BE ISOLATED FROM KITCHEN ACTIVITY (E.G.
BATHROOMS, EXTERNAL OFFICES, STORAGE AND COOLERS) CAN BE WORKED DURING REGULAR WORK
HOURS WITH APPROVAL OF COR.
DURING UDS INSTALL, COOKING STAFF WILL VACATE HOOD AND TRAY LINE AREA FOR 4 WEEKS-DURING WHICH UDS INSTALLATION MUST OCCUR. ALL WORK RELATED TO UDS INSTALL MUST OCCUR WITHIN THIS 4 WEEK WINDOW AND MUST BE DONE BETWEEN 8PM AND 5AM. TRAY LINE WILL UTILIZE EXISTING B261 (OR
NEW C205K) AS SWING SPACE DURING THIS TIME.
PRE UDS TASKS (RED)
INITIAL TASKS REQUIRED TO BE IN PLACE PRIOR TO UDS INSTALLATION IN NO PARTICULAR ORDER.
1. FOR ROOMS B261 AND B261A REFER TO FINAL NOTE IN SEQUENCING NARRATIVE ABOVE.
2. SELECTIVE DEMO IN C260A AND C262 FOR USE AS SWING SPACE FOR SUBSEQUENT TASKS.
3. RENOVATE EXISTING C204/C206 RESTROOMS.
4. CREATE NEW MECHANICAL ROOM C205A AND INSTALL NEW REFRIGERATION EQUIPMENT FOR
COOLER/FREEZERS.
5. INSTALL NEW WALK-IN COOLER C205B. NOTE THAT C205B COOLER MUST BE FULLY INSTALLED AND
OPERATIONAL BEFORE EXISTING C202G UNIT IS REPLACED.
6. RENOVATE EXISTING C265I.
7. RENOVATE EXISTING B202A NOURISHMENT/SNACK PREP.
8. RENOVATE EXISTING C202E/C265A SALAD PREP. (NOTE: B202A RENOVATION MUST BE COMPLETE
BEFORE C202E/C265A COMMENCES).
9. MEP ROUGH-IN AND PREP FOR UDS.
10. ELECTRICAL PANEL REPLACEMENTS.
11. REPLACE EXISTING C202G COOLER AND RENOVATE EXISTING C202F INGREDIENT STORAGE (USING
C260A/C262/ AS SWING SPACE).
12. RENOVATE EXISTING B264/B266 (USING C260A/C262/ AS SWING SPACE).
UDS INSTALL PHASE (YELLOW)
1. TEMPORARILY DISCONNECT AND MOVE COOKING EQUIPMENT UNDER HOOD TO SWING SPACE
C260A/C262.
2. INSTALL CONTRACTOR PROVIDED UDS.
3. COMPLETE ALL ABOVE CEILING AND NEW CEILING WORK THROUGHOUT KITCHEN.
4. EXTEND AND TERMINATE ALL HYDRONIC PIPING WORK.
5. COMPLETE ALL REMAINING WORK IN MAIN KITCHEN AREA (E.G. FLOOR AND WALL TILE REPAIRS, ETC…).
6. MOVE BACK AND RECONNECT ALL COOKING EQUIPMENT BACK UNDER HOOD.
7. COMPLETE ANY ANCILLARY TASKS AS APPLICABLE.
ANCILLARY TASKS NOT UDS DEPENDENT (GREEN)
THESE TASKS CAN BE DONE PRIOR TO, DURING OR AFTER UDS INSTALLATION EXCEPT AS NOTED BELOW
1. DEMOLISH RETHERM DOCKING STATIONS IN MAIN KITCHEN AREA (ONLY AFTER UDS INSTALL IS
COMPLETE AND AFTER APPROVAL FROM THE COR).
2. RENOVATE C260 (STAFF WILL USE C260A/C262 SWING SPACE).
3. RENOVATE C261 (STAFF WILL USE C260A/C262 SWING SPACE, CANNOT DO AT SAME TIME AS C260)
4. REPLACE WINDOWS IN EXISTING B202H.
5. COMPLETE ALL MEP CONNECTIONS AND ARCHITECTURAL PREP FOR CART WASHER (NOTE TRAY LINE
SWING SPACE REQUIREMENT DURING UDS INSTALLATION).
6. RENOVATE B200 ELEVATOR LOBBY AREA (NOTE TRAY LINE SWING SPACE REQUIREMENT DURING UDS
INSTALLATION).
7. RENOVATE C260A AND C262 OFFICES ONCE THEY ARE NO LONGER NEEDED FOR SWING SPACE.
CONSTRUCTION SEQUENCING AND ICRA PLAN -EXISTING
100% CONSTRUCTION
DOCUMENTS
RENOVATE MAIN KITCHEN
B202D
REFRIG.
B202C
B202B
SALAD PREP
C202E
OFFICE
C265A
C202F
COOLER
C202G
B202A
B202
OFFICES
B266
CLOSET
C201
RETHERM
B261
ELEV. LOBBY
B200
TOILET
C206
TOILET
C204
DIETARY
C261
N&FS
C262
MANAGER
C260A
DIETICIANS
C260
SHAFT
203A
C265I
B202H
WASH
ROOM
NOURISHMENT/
SNACK PREP
KITCHEN
FACILITY
INGREDIENT
STORAGE
BREAK
ROOM
N.I.C.N.I.C.
N.I.C.
REFRIG.
REFRIG.
N
AREA OF SUSPECTED HAZARDOUS MATERIALS
N NEGATIVE AIR
ACM TILE/MASTIC1
H-101R
HAZARDOUS MATERIALS PLAN
1/8" = 1'-0"1 HAZARDOUS MATERIALS PLAN
APPROXIMATE ASBESTOS AMOUNTS:
C202F: 125 SF TILE/MASTIC
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANTS
321 4 5 6 7 8 9 10
ARCHITECT:
Project Director
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827 (607)223-4334
C&S Companies 499 Col Eileen Collins Blvd Syracuse, New York, 13212
(315) 455-2000
SYRACUSE VA MEDICAL CENTER
528A7-18-716
BUILDING 1
04/04/2023 DW JD
KITCHEN CONSULTANT:
Commercial Kitchen Consulting 747 Conklin Road Binghamton, New York 13903
(607) 217-5389
KEYED NOTES:
KEY PLAN:
SYMBOL LEGEND:
100% CONSTRUCTION
DOCUMENTS
RENOVATE MAIN KITCHEN
N
GENERAL NOTES:
1. ASBESTOS/PCB ABATEMENT SHALL BE PERFORMED IN ACCORDANCE WITH THE SPECIFICATIONS AND APPLICABLE REGULATIONS. PERSONNEL HOLDING CURRENT NEW YORK STATE DEPARTMENT OF LABOR (NYSDOL) ASBESTOS HANDLER'S CERTIFICATES SHALL PERFORM THE WORK. ADDITIONALLY, THE CONTRACTOR MUST EMPLOY NYSDOL CERTIFIED SUPERVISORS TO BE ON THE WORK SITE FOR ALL ABATEMENT ACTIVITIES. THE CONTRACTOR MUST BE
CURRENTLY LICENSED BY THE NYSDOL.
2. CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND DISPOSAL OF ALL ASBESTOS-CONTAINING MATERIALS AND
ASBESTOS-CONTAMINATED MATERIALS WITHIN THE SPECIFIED AREAS.
3. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF ALL QUANTITIES OF ASBESTOS-CONTAINING AND
PCB-CONTAINING MATERIALS.
4. CONTRACTOR IS RESPONSIBLE FOR PRECLEANING ANY AND ALL EXISTING ASBESTOS CONTAMINATION, DUST AND
DEBRIS WITHIN THE REMOVAL AREAS.
5. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING THE INTEGRITY OF BUILDING FINISHES. THE CONTRACTOR SHALL REPAIR ANY AND ALL DAMAGES CAUSED BY ABATEMENT ACTIVITIES OR HIS PERSONNEL.
6. THE CONTRACTOR IS TO REMOVE THE ASBESTOS-CONTAINING MATERIALS (ACM'S) AND PCB-CONTAINING MATERIALS IN ACCORDANCE WITH NEW YORK STATE INDUSTRIAL CODE RULE 56 (12 NYCRR PART 56), THE VA SPECIFICATION AND APPLICABLE FEDERAL OSHA AND EPA REGULATIONS. WHERE THERE IS A DISCREPANCY, THE
MOST STRINGENT REGULATION SHALL APPLY.
7. THE CONTRACTOR SHALL COORDINATE THE LOCATION OF HIS REMOTE PERSONNEL AND WASTE
DECONTAMINATION UNIT(S), AND WASTE DUMPSTER WITH THE COR.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY AND ALL DAMAGES RESULTING FROM ASBESTOS
ABATEMENT ACTIVITIES.
9. ALL UTILITIES, ELECTRICAL AND MECHANICAL SYSTEMS AND PIPING SHALL BE LOCKED OUT AND TAGGED OUT BEFORE THE CONTRACTOR IS ALLOWED TO BEGIN ABATEMENT ACTIVITIES. MECHANICAL AND ELECTRICAL SYSTEMS, WHICH CANNOT BE LOCKED OUT AND TAGGED OUT, SHALL BE PROTECTED AND SUPPORTED
THROUGHOUT ABATEMENT ACTIVITIES.
10. SCHEDULING OF WORK SHALL BE COORDINATED WITH THE COR. ASBESTOS ABATEMENT ACTIVITIES SHALL BE COORDINATED TO AVOID INTERRUPTIONS TO THE NORMAL ACTIVITIES OF THE FACILITY. THE REMOVAL MAY BE
SCHEDULED AFTER NORMAL BUSINESS HOURS AT NO ADDITIONAL COST TO THE OWNER.
11. IN AREAS OF PUBLIC ACCESS, THE CONTRACTOR SHALL ERECT ISOLATION BARRIERS THAT SEPARATE THE WORK AREAS FROM THE REMAINDER OF THE BUILDING. THE BARRIERS SHALL BE CONSTRUCTED OF A FIRE RETARDANT SHEATHING MATERIAL OF AT LEAST 1/2" THICKNESS. THE ISOLATION BARRIER SHALL BE PLASTICIZED WITH TWO (2) LAYERS OF 6-MIL PLASTIC SHEETING. THE ISOLATION BARRIERS SHALL BE CAULKED AT THE SHEATHING SEAMS AND WHERE THE SHEATHING MEETS THE FLOOR, WALLS AND CEILING. THE ISOLATION BARRIER SHALL BE CONSTRUCTED USING 2"X4" FRAMING, 16 INCHES CENTER-TO-CENTER, AND CAULKED AT ALL SEAMS.
12. ALL ASBESTOS AND PCB-CONTAMINATED MATERIALS WITHIN THE CONTRACT LIMITS SHALL BE REMOVED AND DISPOSED OF AS CONTAMINATED WASTE UNLESS SPECIFICALLY EXCLUDED IN THE SPECIFICATIONS.
13. THE ABATEMENT CONTRACTOR SHALL PERFORM REMOVAL WITHIN HEPA-FILTERED NEGATIVE AIR PRESSURE TENT ENCLOSURES. ALL ABATEMENT AREAS SHALL HAVE AN AIRLOCK ENTRANCE OR ATTACHED DECON UNIT. THE TENT ENCLOSURE SHALL BE VENTED TO THE OUTDOOR AIR VIA HEPA-FILTERED NEGATIVE AIR MACHINES. TENTS SHALL BE CONSTRUCTED IN ACCORDANCE WITH 12 NYCRR PART 56. IN AREAS OF PUBLIC ACCESS THE TENT
ENCLOSURES SHALL BE SHEATHED FOR SAFETY.
14. COORDINATE ALL ABATEMENT ACTIVITIES WITH THE SEQUENCING AND ICRA PLAN.
REMOVE EXP
JT COVERS
REMOVE EXP
JT COVERS
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.
RETHERM
B261
DIRTY
B261A
ELEV LOBBY
B200
WASH ROOM
B202H
NOURISHMENT/
SNACK PREP
B202A
KITCHEN
FACILITY
B202
BREAK ROOM
C265ISUPER
OFFICE
C265A
SALAD PREP
C202E
INGREDIENT
STORAGE
C202F
REFRIG
C202G
REFRIG
B202D
REFRIG
B202C
REFRIG
B202B
SUPER
OFFICES
B266
STOR
B264
HR CL
C201
SHAFT
C203A
ELEC
C203
COMP
C205
STOR
C205I
MENS
TOILET
C204
WOMENS
TOILET
C206
OFFICES
C261
DIETICIANS
C260
MANAGER
260A
N&SF
C262
NUTRITION
SEC
C261A
REMOVE
EXIST CURB
EXISTING QUARRY
TILE FLOOR REMOVAL.
SEE CONSTRUCTION
PLAN FOR APPROX
LIMITS
EXISTING ST STL
COUNTER AND SINK
TO BE REMOVED
REMOVE EXIST WINDOWS
AND STOOLS. COORD W/
HVAC WORK.
EXIST ACM TILE AND QUARRY
TILE UNDERNEATH TO BE
REMOVED. SEE HAZARDOUS
MATERIAL PLAN.
REMOVE
MASONRY
PILASTER
EXIST
CONCRETE
CURB
REMOVAL
AFTER COOLER
REMOVAL,
TROWELL
SMOOTH
DEPRESSED
SLAB
FLOOR TILE
REMOVAL
EXISTING QUARRY TILE
FLOOR REMOVAL. COORD
WITH CONSTRUCTION PLAN
REMOVE
MASONRY
PILASTER
CUT EXIST HANDRAIL AND
WALL PROTECTION
WAINSCOT IN THIS AREA AND
PROVIDE NEW TO MATCH
5 5
1*
2 2
22 22
1*
5 5
7 7
8 8
1*
REMOVE
PILASTER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANTS
321 4 5 6 7 8 9 10
ARCHITECT:
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827 (607)223-4334
C&S Architects, Engineers & Landscape Architect, PLLC 499 Col. Elieen Collins Blvd Syracuse, New York 13212
(315) 455-2000 www.cscos.com
RENOVATE MAIN KITCHEN
SYRACUSE VA MEDICAL CENTER
528A7-18-716
BUILDING 1
KITCHEN CONSULTANT:
Commercial Kitchen Consulting 21 Powers Rd Binghamton, New York, 13903
(607) 242-5571 c s c o s .c o m
\c s fi le
\e n g \P ro je c t\
V
W a ts o n
E n g in e e ri n g \V
V A
S y ra c u s e
K it c h e n \D e s ig n \C
A D
D \R e v it \0
-C E
N T
R A
L
A R
C H
IT
E
C T
U R
A L \V
A R
C H
IT
E
C T
U R
A L .r v t
/2
/2
:1
:0
P
M
AD-101
ARCHITECTURAL DEMOLITION
PLAN
KBPMWL
1/8" = 1'-0"
ARCHITECTURAL DEMOLITION PLAN
PLAN
NORTH
KEY PLAN:
PROJECT
AREA
REMOVE DASHED WALLS IN THEIR ENTIRETY. * FOR NEW DOOR OPENING.
REMOVE DOOR, FRAME AND HARDWARE.
REMOVE WALK IN REFRIGERATORS IN THEIR ENTIRETY.
REMOVE TILE FLOORING IN IT'S ENTIRETY.
REMOVE CEILING AND SUPPORTS.
COMPLETELY REMOVE ALL TOILET ROOM ACCESSORIES INCLUDING BUT
NOT LIMITED TO TOILET PAPER DISPENSER, PAPER TOWEL DISPENSER,
SOAP DISPENSER, GRAB BARS, WASTE RECEPTACLES, MIRRORS, ETC.
REMOVE PARTITION SYSTEM AND FASCIA.
REMOVE VCT FLOORING.
DEMOLITION KEYED NOTES:
11/23/2022
WOMEN'S TOILET
C209
MEN'S TOILET
C207
283 SF
DIETICIANS
C258
677 SF
INGREDIENT
STORAGE
C205D
2907 SF
KITCHEN
FACILITY
C205
210 SF
NOURISHMENT/
SNACK PREP
C205I
686 SF
DISH ROOM
C205J
212 SF
ELEV. LOBBY
B200
36 SF
SHAFT
203A
113 SF
TOILET
B204
110 SF
SECTION CHIEF
C205G
NEW EXP JOINT COVER
PATCH ADJACENT
FLOORING, AND EXP
JOINT WALL COVERS
SEE 7/A-501
147 SF
MANAGER
C260
153 SF
SALAD PREP
C205F
123 SF
CALL CENTER
C205H
510 SF
CART WASH
C205K
48"X84" CASED
OPENING
273 SF
TRAINING ROOM
C205C
NEW QT
FLOORING
149 SF
CHIEF N&FS
C262
325 SF
COOLER
C205B
107 SF
FREEZER
C205E
A-301
INFILL
OPENING
INFILL
OPENING
S
SS
HW-8E
60" X 84"
CASED
OPENING
SS
HW-8B
T
S
HW-2
HW-2
S
V V
HW-3E
T
RR
HW-11B
4' - 0"3' - 0"
10' - 0 9/16" 3' - 2"
/1
14' - 0"
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.
HW-3E
S
42 SF
MECH
C205A
NEW FLEXIBLE
TRAFFIC DOOR
AND FRAME
NEW UTILITY
DISTRIBUTION
SYSTEM BY
OTHERS
LIMITS OF NEW
QT FLOOR
HW-5D
F
HW-5
F
EXISTING
HANDRAIL
TO
REMAIN
L
APPROX
LIMITS OF
NEW QT
FLOOR
TILE
MA-3
MA-3
MA-3
CA-10
CA-10
MA-3
CC-6
C A
-6
CB-6
CB-6
MA-3
MA-3
MD-4
MD-4
MA-3
MA-3
HW-10C
68"x84"
DOUBLE
DOOR
NEW QT
FLOORING,
PATCH WALL
AND BASE
CUT EXIST HANDRAIL AND
WALL PROTECTION
WAINSCOT IN THIS AREA, AND
PROVIDE NEW TO MATCH
MD-4
MD-4
ALIGN
MA-3MA-3
MD-4
MD-4
MD-4
MD-4
MA-3 MA-3
FC FC
MD-4
MD-4
MD-4
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
CT-3
FEC
FEC
FD
FD
FIXED
COUNTERTOP
RR
HW-11B
C201
C205M
MA-4
NEW QT
FLOORING
NEW LVT-1
FLOORING
REFRIGERATOR SEE
KITCHEN DRAWINGS
A-502
APPLY DARK
TINTED FILM ON
WINDOW
APPLY DARK
TINTED FILM ON
WINDOW
NEW WINDOW
SHADES
NEW WINDOW
SHADES
NEW WINDOW
SHADES
NEW WINDOW AND SILLS
(OWNER FURNISHED,
CONTRACTOR
INSTALLED)
2' - 6"
CB-4
NEW QT FLOORING,
PATCH WALL
AND BASE
NEW QT FLOORING,
PATCH WALL AND
BASE
34 SF
OFFICE
C205N
NEW WALLS
AND DOOR
ALIGN
2' - 0"
10'-0" +/-
36" X 84" CASED
OPENING
2" MIN 1' - 10" +/-
2" MIN 2' - 10" +/-
M
IN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANTS
321 4 5 6 7 8 9 10
ARCHITECT:
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827 (607)223-4334
C&S Architects, Engineers & Landscape Architect, PLLC 499 Col. Elieen Collins Blvd Syracuse, New York 13212
(315) 455-2000 www.cscos.com
RENOVATE MAIN KITCHEN
SYRACUSE VA MEDICAL CENTER
528A7-18-716
BUILDING 1
KITCHEN CONSULTANT:
Commercial Kitchen Consulting 21 Powers Rd Binghamton, New York, 13903
(607) 242-5571 c s c o s .c o m
\c s fi le
\e n g \P ro je c t\
V
W a ts o n
E n g in e e ri n g \V
V A
S y ra c u s e
K it c h e n \D e s ig n \C
A D
D \R e v it \0
-C E
N T
R A
L
A R
C H
IT
E
C T
U R
A L \V
A R
C H
IT
E
C T
U R
A L .r v t
/2
/2
:1
:5
P
M
A-101
ARCHITECTURAL PLAN
KBPMWL
1/8" = 1'-0"
ARCHITECTURAL PLAN
KEY PLAN:
PLAN
NORTH
PROJECT
AREA
GENERAL CONSTRUCTION NOTES:
BROKEN CERAMIC WALL TILE ALLOWANCE:
CRACKED AND BROKEN GLAZED CERAMIC WALL TILES ARE TO BE REMOVED AND REPLACED THROUGHOUT THE PROJECT AREA. IN ADDITION TO WALLS AND TILES PATCHED DUE TO WALL DEMOLITION WORK, THE CONTRACTOR SHALL INCLUDE AN ALLOWANCE OF 100 SQ. FT. TOTAL OF ADDITIONAL WALL TILE
REPLACEMENT IN LOCATIONS DIRECTED BY THE OWNER.
BROKEN QUARRY TILE ALLOWANCE:
CRACKED AND BROKEN QUARRY FLOOR TILES ARE TO BE REMOVED AND REPLACED THROUGHOUT THE PROJECT AREA. IN ADDITION TO NEW AREAS OF QUARRY TILE INDICATED ON DRAWINGS OR SCHEDULED, AND FLOOR PATCHING DUE TO WALL DEMOLITION WORK, THE CONTRACTOR SHALL INCLUDE AN ALLOWANCE OF 100 SQ. FT. TOTAL OF ADDITIONAL QUARRY TILE REPLACEMENT IN LOCATIONS DIRECTED BY THE OWNER.
HOLES IN STRUCTURAL GLAZED TILES:
HOLES 1/2 INCH DIAMETER OR LESS IN EXISTING STRUCTURAL GLAZED TILE SHALL BE SEALED WITH MORTAR
MATCHING THE EXISTING MORTAR JOINTS.
KEYED NOTES:
CONTRACTOR TO PROVIDE AND INSTALL BOWMAN HP-010 (OR EQUAL) HAIRNET DISPENSER.1
KITCHEN
FACILITY
C205
NOURISHMENT/
SNACK PREP
C205I
DISH ROOM
C205J
CART WASH
C205K
ELEV. LOBBY
B200
SECTION CHIEF
C205G
INGREDIENT
STORAGE
C205D
SALAD PREP
C205F
WOMEN'S TOILET
C209
MEN'S TOILET
C207
TRAINING ROOM
C205C
DIETICIANS
C258
MANAGER
C260
COOLER
C205B
SHAFT
203A
FREEZER
C205E
CALL CENTER
C205H
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.
CHIEF N&FS
C262
MECH
C205A
A-102
A-102
EXISTING
HOOD
C201
A-1025
A-102
EXPOSED STRUCTURE
NO CEILING
6" METAL STUDS
AT 16" OC
UNDERSIDE OF DECK
ACOUSTIC TILE
CEILING EACH SIDE
5/8" GYP BD
KITCHEN HOOD
1' - 3"
UNDERSIDE OF DECK
6" METAL STUDS
AT 16" OC
ACOUSTIC TILE
CEILING
5/8" GYP BD
KITCHEN HOOD
6" METAL STUDS
AT 16" OC
ACOUSTIC TILE
CEILING5/8" GYP BD
+/-7'-10 3/4" AFF
UNDERSIDE OF DECK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANTS
321 4 5 6 7 8 9 10
ARCHITECT:
Watson Engineering, P.C.
1112 State Rte. 434 Owego, NY 13827 (607)223-4334
C&S Architects, Engineers & Landscape Architect, PLLC 499 Col. Elieen Collins Blvd Syracuse, New York 13212
(315) 455-2000 www.cscos.com
RENOVATE MAIN KITCHEN
SYRACUSE VA MEDICAL CENTER
528A7-18-716
BUILDING 1
KITCHEN CONSULTANT:
Commercial Kitchen Consulting 21 Powers Rd Binghamton, New York, 13903
(607) 242-5571 c s c o s .c o m
\c s fi le
\e n g \P ro je c t\
V
W a ts o n
E n g in e e ri n g \V
V A
S y ra c u s e
K it c h e n \D e s ig n \C
A D
D \R e v it \0
-C E
N T
R A
L
A R
C H
IT
E
C T
U R
A L \V
A R
C H
IT
E
C T
U R
A L .r v t
/2
/2
:1
:5
P
M
A-102
ARCHITECTURAL REFLECTED
CEILING PLAN
KBPMWL
1/8" = 1'-0"
REFLECTED CEILING PLAN
KEY PLAN:
PLAN
NORTH
PROJECT
AREA
1" = 1'-0"
BULKHEAD-1
1" = 1'-0"
BULKHEAD -2
1" = 1'-0"
BULKHEAD -3
ALIGN
A-301
A-301
1. SHELF IF IN EQUIPMENT LIST 7610; SEE DETAIL 10 28 00-4
2. LAVATORY, WITH WRIST OR SENSOR CONTROL FAUCET
3. FOR UPSWING GRAB BAR LOCATION AND ANCHORING, REFER TO DETAIL 11/A-301
4. INSULATE HOT SUPPLY AND WASTE.
5. KNEE CLEARANCE PER SECTION 306 ADA-ABA AG.
6. REMOVE EXISTING TILE FINISH. PATCH AND PREPARE WALLS FOR NEW TILE FINISH.
98 SF
WOMEN'S TOILET
C209
88 SF
MEN'S TOILET
C207
/8
1' - 9" +/- V.I.F.
/2
V .I
.F
/2
V .I
.F
ALIGN
ALIGN
/2
V
.I .F
2' - 9" 1' - 6" 1' - 6"1' - 6 1/2" 1' - 2 1/2"
15' - 4" V.I.F.
5'
T
Y P
T
Y P
MD-4
MD-4
MA-2
MA-3
FA
FC
A-501
NEW TILE FLOORING (CMT-1), TYP.
A-501
Sim
NEW TILE
FLOORING
(CMT-1) TYP
NEW WALL
TILE (CT-2)
T Y
P
M
IN
t o
M A
X
NEW WALL
TILE (CT-2)
WATER CLOSET,
REFER TO
PLUMBING
A-501
NEW WALL
TILE (CT-2)
WALL HUNG
LAVATORY,
REFER TO
PLUMBING
WATER CLOSET
REFER TO
PLUMBING
WALL HUNG
LAVATORY, REFER
TO PLUMBING
NEW WALL
TILE (CT-2)
/4
T Y
P
WALL HUNG
LAVATORY,
REFER TO
PLUMBING
NEW WALL TILE
(CT-2)
WALL HUNG
LAVATORY,
REFER TO
PLUMBING
URINAL, REFER
TO PLUMBING
WATER CLOSET,
REFER TO PLUMBING
A-501
WALL MOUNTED
LAVATORY,
REFER TO
PLUMBING
NEW WALL
TILE (CT-2)
WATER
CLOSET,
REFER TO
PLUMBING
NEW WALL
TILE (CT-2)
" WATER CLOSET,
REFER TO
PLUMBING
NEW WALL
TILE (CT-2)
M
IN
T
O
M A
X
ACCESSORIES SCHEDULE
ITEM
ROOM
NO.
PAPER TOWEL DISPENSER
UPSWING GRAB BAR
SOAP DISPENSER
TOILET PAPER DISPENSER
SANITARY NAPKIN WASTE RECEPTACLE
C204
1-
C206
MIRROR (CONTINUOUS, 3' H X 1'-10" W)
BABY CHANGING STATION 117
VV
VV
CC
VV
CC
VV
VV
GENERAL NOTES:
1. MOUNT ALL ACCESSORIES WITH FASTENERS AND ANCHORS
AS RECOMMENDED BY THE MANUFACTURER.
2. MOUNT ALL ACCESSORIES AT ADA ACCESSIBLE HEIGHTS AND
LOCATIONS AS RECOMMENDED BY THE MANUFACTURER.
3. ALL PIPING BELOW ALL SINKS TO BE COVERED WITH
ACCESSIBILITY APPROVED…