This document details specifications for a Liebert CW Precision Cooling System, Model CW076DC1CT03DJ, with a nominal cooling capacity of 76 kW. The system includes two units with specific configuration options such as downflow orientation, 208/3/60 voltage, 65,000 amps short circuit current rating, and a locking disconnect. Key technical features include EC motorized impeller fans operating at 12,400 CFM, two 4.15 HP motors, a 3-way high-pressure valve, infrared auto-flush humidification, hot water reheat, and 4" MERV 8 filters.

The cooling system offers advanced controls and monitoring capabilities through a Liebert iCOM control with high-definition display, supporting multiple communication protocols including BACnet IP, Modbus RTU, and SNMP. Additional features include a network switch with fourteen interconnection ports, zone leak detection sensors, smoke sensors, and a low voltage terminal package with extra shutdown and alarm contacts. The system comes with a 1st-year parts and labor warranty and includes accessories such as a standard floorstand, fan lowering jack, and plenum with top duct collar.

View the file

Other files for this federal contract opportunity

Other files attached to Hurlburt Field HVAC MACC, newest first.
File Type Posted
Solicitation Amendment - FA441725R00170003.pdf PDF
Rev. 7_30_25_Attachment 7 - Section L Instructions to Offerors - HVAC MACC.pdf PDF
Solicitation Amendment FA441725R00170003 SF 30.pdf PDF
Attachment 12 - B90131 Updates to Building Drawings (2015).pdf PDF
Attachment 13 - B90131 Controls Drawings Specific to CRAC Units.pdf PDF
Amendment - FA441725R00170002.pdf PDF
Rev. 7_23_25_Attachment 7 - Section L Instructions to Offerors - HVAC MACC.pdf PDF
Attachment 15 - Bldg 90131 Asbestos Sampling 22-Jun-22.pdf PDF
Rev. 7_23_25_Attachment 8 - Section M Evaluation Factors for Award.pdf PDF
Attachment 10 - 7.29_RFI Final - FA441725R0017 - Hurlburt HVAC MACC.pdf PDF
Attachment 14 - ACM_LBP Survey Bldg 90131_1 Mar 2024_FTEV201009_Repair_Renovation.pdf PDF
Amendment FA441725R00170002 SF 30.pdf PDF
Solicitation Amendment FA441725R00170001 SF 30.pdf PDF
B90131 Site Visit Sign -In _Redacted.pdf PDF
Site Visit Brief.pdf PDF
Attachment 2 - HF HVAC-MACC Ordering Guide.pdf PDF
Attachment 7 - Section L Instructions to Offerors - HVAC MACC.pdf PDF
Attachment 8 - Section M Evaluation Factors for Award.pdf PDF
Attachment 9 - Section H Special Contract Requirements.pdf PDF
4e Air Unit Schedules B90131.pdf PDF
Attachment 5 - PPQ.docx DOCX document
Attachment 6 - Financial Worksheet.docx DOCX document
4b WTA _SEED project.pdf PDF
Attach 4g - 50 Division Construction Cost Estimate Worksheet.xlsx XLSX spreadsheet
Solicitation - FA441725R0017.pdf PDF
Attachment 1- Hurlburt HVAC MACC SOW.pdf PDF
Attachment 3 - Wage Determination FL20250217.pdf PDF
4a SOW Replace - Upgrade CRAC Units B90131 - 03-March-2025.pdf PDF
4c Existing Equipment.pdf PDF
4d Mechanical Drawing Seed Project.pdf PDF
Show all 30

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Liebert CW, Model CW076DC1CT03DJ, Precision Cooling System: Nominal LBRT- CW-076 kW Chilled Water System

Quantity (2)

Main Unit Options:

• Downflow Orientation

• 208/3/60 Voltage with 65,000 amps rms Short Circuit Current Rating

• Locking Disconnect Included and Dual Float Condensate Pump Included

• EC motorized impeller with fans operating below floor

• Operating at 12400 CFM and 0.2 inches ESP at 0 - 1000 feet

• 2 Motors, 4.15 Hp each motor

• Qty of (1) per Unit - 3-Way Valve High Pressure (400 psig / 2,758 kPa) with insulated chilled water piping

• 400 psig / 2,758 kPa Flow Switch, ships loose

• Infrared with Auto-Flush Humidification

• Hot Water Reheat

• 4" MERV 8 Filters

• 24 (610mm)" Standard Floorstand

• Includes 1 EC Fan Lowering Jack Per Order

• 24" Plenum with Top Duct Collar

Controls, Sensors, and Monitoring:

• Liebert iCOM Control with High-Definition Display

• iCOM based communication o BACnet IP (Ethernet Port) o Modbus RTU (RS-485 Port) o SNMP (Ethernet Port) o IP Protocols over one network

• Low Voltage Terminal Package o (2) Two Extra Terminals for Remote Shutdown o (2) Two Extra Common Alarm Contacts o Main Fan Auxiliary Switch o Liqui-tect Shutdown

• Qty of (1) vNSA14-iCOM-H per Order - Ships Loose

• Network switch is designed for connecting multiple Ethernet-ready devices. The vNSA14-iCOM-H has built in iCOM 9 inch touch color screen and an additional fourteen ports to interconnect any combination of fourteen iCOM controllers and displays. The vNSA has a power input range of 100-240 VAC single phase, 47- 63 Hz. Power wiring is required.

• Qty of (1) per Unit 4 Side Zone Leak Detection Sensor Included

• Smoke Sensor Included

Warranties:

• 1st Year Parts and Labor Warranty Included