472.22019.SMD Parnall CF VV - New Diesel Mechanic Program - 50% Design Development E Drawings.pdf

PDF 5 MB Posted

Attached to
472/22091. SMD; Parnall CF - New Heavy Diesel Program (CM)
Solicitation number
RFP - 171 - 230000000652
Issued by
Jackson County, Michigan

About this file

This document contains the electrical drawings related to the New Diesel Mechanic Program project at the Parnall Correctional Facility in Jackson, Michigan. The project involves the complete demolition of the existing electrical systems and equipment throughout the entire facility, and the installation of new electrical infrastructure, including a new 500 kVA medium voltage transformer, new panelboards, new receptacles, lighting, and a new fire alarm system. The electrical work is part of a larger construction project to build a new Heavy Diesel Program at the facility.

The electrical drawings provide details on the new site electrical layout, demolition plans, lighting plans, power plans, and riser diagrams. Key details include the installation of a new 500 kVA 12,470Y-480/277V transformer, new 480/277V and 208/120V panelboards and branch circuits, LED lighting fixtures, and a new addressable fire alarm system. The project is part of a state and local contract opportunity identified as 472/22091. SMD with the State of Michigan and Jackson County.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1P 1 POLE (2P, 3P, 4P, ETC.)

A AMPS

AC ABOVE COUNTER

AC- AIR CONDITIONER

ACU- AIR CONDITIONING UNIT

ACLG ABOVE CEILING

ADO AUTOMATIC DOOR OPENER

AF AMP FRAME

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT

INTERRUPTER

AHJ AUTHORITY HAVING

JURISDICTION

AHU- AIR HANDLING UNIT

AIC AMPS INTERUPTING CAPACITY

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

AMPL AMPLIFIER

ANNUN ANNUNCIATOR

APPROXAPPROXIMATELY

AQ-STAT AQUASTAT

ARCH ARCHITECT, ARCHITECTURAL

AS AMP SWITCH OR ABOVE SHELF

AT AMP TRIP

ATS AUTOMATIC TRANSFER

SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

B- BOILER

BATT BATTERY

BC BELOW COUNTER

BD BOARD

BLDG BUILDING

BMS BUILDING MANAGEMENT

SYSTEM

C CONDUIT

CAB CABINET

CAT CATALOG

CATV CABLE TELEVISION

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CHLR- CHILLER

CKT CIRCUIT

CKT BRKRCIRCUIT BREAKER

CLG CEILING

COMB COMBINATION

CMPR COMPRESSOR

CND(C) CONDUIT

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR

CONTINUOUS

CONTR CONTRACTOR

CONV CONVECTOR

CP CIRCULATING PUMP

CRT CATHODE-RAY TUBE

CT CURRENT TRANSFORMER

CT- COOLING TOWER

CTR CENTER

CU COPPER

CU- CONDENSING UNIT

CUH- CABINET UNIT HEATER

DCP DOMESTIC WATER

CIRCULATING PUMP

DEPT DEPARTMENT

DET DETAIL

DFU- DUCT FURNACE

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DPR DAMPER

DS SAFETY DISCONNECT

SWITCH

DT DOUBLE THROW

DWG DRAWING

DWH- DOMESTIC WATER HEATER

EBB- ELECTRIC BASEBOARD

EC ELECTRICAL CONTRACTOR

EF- EXHAUST FAN

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMS ENERGY MANAGEMENT

SYSTEM

EMT ELECTRICAL METALLIC

TUBING

EP ELECTRIC PNEUMATIC

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXIST EXISTING

EXH EXHAUST

EXIST (E) EXISTING

EXP EXPLOSION PROOF

FA FIRE ALARM

FABP FIRE ALARM BOOSTER

POWER SUPPLY PANEL

FACP FIRE ALARM CONTROL

PANEL

FCU FAN COIL UNIT

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE CONDUIT

FLR FLOOR

FLUOR FLUORESCENT

FSES FOOD SERVICE EQUIP.

SUPPLIER

F/S FIRE/SMOKE

FU FUSE

FU- FURNACE

FUDS FUSED SAFETY DISCONNECT

SWITCH

GA GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT

INTERRUPTER

GFP GROUND FAULT PROTECTOR

GND GROUND

GRS GALVANIZED RIGID STEEL

(CONDUIT)

GYP BD GYPSUM BOARD

H- HUMIDIFIER

HID HIGH INTENSITY DISCHARGE

HOA HANDS-OFF-AUTOMATIC

SWITCH

HORIZ HORIZONTAL

HP HORSEPOWER

HPF HIGH POWER FACTOR

HR HOUR

HT HEIGHT

HTG HEATING

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND

AIR CONDITIONING

HWP HYDRONIC WATER PUMP

IC INTERRUPTING CAPACITY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL

CONDUIT

INCAND INCANDESCENT

IR INFRARED

I/W INTERLOCK WITH

JB JUNCTION BOX

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LC LIGHT CONTROL

LOC LOCATE OR LOCATION

LT LIGHT

LT FLEX LIQUID TIGHT FLEXIBLE

METAL CONDUIT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MAX MAXIMUM

MAG.S MAGNETIC STARTER

M/C MOMENTARY CONTACT

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDC MAIN DISTRIBUTION CENTER

MDP MAIN DISTRIBUTION PANEL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT

SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MMS MANUAL MOTOR STARTER

MOA MULTIOUTLET ASSEMBLY

MSP MOTOR STARTER

PANELBOARD

MSBD MAIN SWITCHBOARD

MT MOUNT

MT.C EMPTY CONDUIT

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MTR MOTOR, MOTORIZED

MUA- MAKE-UP AIR UNIT

N.C. NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NFDS NON-FUSED SAFETY

DISCONNECT SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

N.O. NORMALLY OPEN

NPF NORMAL POWER FACTOR

NTS NOT TO SCALE

OH OVERHEAD

OL OVERLOADS

P POLE

P- PUMP

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PE PNEUMATIC ELECTRIC

PED PEDESTAL

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

PP POWER POLE

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV- POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE

(CONDUIT)

PWR POWER

QUAN QUANTITY

RCPT RECEPTACLE

RECEPT RECEPTACLE

REQD REQUIRED

RGC RIGID GALVANIZED STEEL

CONDUIT

RM ROOM

RSC RIGID STEEL CONDUIT

RTU- ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SF- SUPPLY FAN

SHT SHEET

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

SPKR SPEAKER

SP SPARE

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

S/S STOP/START PUSHBUTTONS

STA STATION

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TCC TEMPERATURE CONTROL

CONTRACTOR

TEL TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM TERMINAL

TL TWIST LOCK

TR TAMPER RESISTANT

TS TAMPER PROOF SWITCH

T-STAT THERMOSTAT

TTC TELEPHONE TERMINAL

CABINET

TV TELEVISION

TVTC TELEVISION TERMINAL

CABINET

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UF UNDER FLOOR

UG UNDERGROUND

UH- UNIT HEATER

UL UNDERWRITERS'

LABORATORIES, INC.

UNO UNLESS NOTED OTHERWISE

UT UNDERGROUND TELEPHONE

UTIL UTILITY

UV UNIT VENTILATOR OR

ULTRAVIOLET

V VOLT

VA VOLT-AMPERES

VDT VIDEO DISPLAY TERMINAL

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VL VERIFY LOCATION WITH

OWNER

VOL VOLUME

W WATT

W/ WITH

WG WIRE GUARD

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR RANSFER

ANGLE

@ AT

DELTA

' FEET

" INCHES

# NUMBER

Ø PHASE

C CENTER LINE

P PLATEL

L

ELECTRICAL ABBREVIATIONS LIST

1.ALL WALL AND FLOOR PENETRATIONS ARE TO BE SEALED TO MAINTAIN ORIGINAL

RATING.

2.ALL CONDUITS SHALL BE FIELD ROUTED ALONG EXISTING PIPING AND STRUCTURAL

STEEL.

3.CONTRACTORS SHALL VISIT THE PROJECT SITE AND DETERMINE THE EXACT EXTENT

OF THE DEMOLITION WORK REQUIRED BEFORE BIDDING THE PROJECT.

4.REMOVE ALL EXISTING OBSOLETE EXPOSED CONDUIT, WIRE AND UNUSED EQUIPMENT

WHERE WORK IS BEING DONE EXCEPT ITEMS NOTED OTHERWISE.

5.WHERE BUILDING SURFACES ARE DAMAGED BY THE REMOVAL OF OLD WORK,

SURFACES SHALL BE PATCHED TO MATCH ADJACENT.

6.EXISTING WORK WHICH IS PRESENTLY CONCEALED AND WHICH WILL REMAIN

CONCEALED AND DOES NOT INTERFERE WITH ANY NEW WORK OF ANY TRADE NEED

NOT BE REMOVED. HOWEVER, ALL CONDUIT SHALL BE CAPPED BELOW FINISH SURFACE

AND THEN PATCHED TO MATCH, OR AS NOTED.

7.EXISTING OPENINGS, WHICH ARE TO BE REUSED, SHALL BE MODIFIED OR ENLARGED

TO SUIT THE NEW SYSTEMS AS REQUIRED. PROVIDE ALL REQUIRED CUTTING AND

PATCHING.

8.CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING THE EXISTING WALLS TO

MATCH THE ADJACENT SURFACES BEHIND ALL SURFACE MOUNTED EQUIPMENT.

9.CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT AND LOADS PRIOR TO INSTALLING

SERVICE TO EQUIPMENT.

10.DRAWINGS ARE BASED ON EXISTING RECORD DOCUMENT AND CASUAL FIELD

OBSERVATION. REPORT ANY DISCREPANCIES TO ENGINEER FOR CLARIFICATION.

11.CONDUITS AND BOXES:

11.1. 3/4" MINIMUM TRADE SIZE.

11.2. EMT TYPE CONDUIT IS APPROVED.

11.3. NO PVC ALLOWED INSIDE OF BUILDINGS.

11.4. CONDUITS SHALL BE ATTACHED WITH TWO-HOLE STRAPS. SINGLE HOLE STRAPS

ARE NOT PERMITTED.

11.5. NO SET SCREWS ARE ALLOWED.

11.6. TAMPER-PROOF SCREWS REQUIRED FOR EXPOSED CONDUIT AND BOXES

MOUNTED BELOW TEN FEET.

11.7. DRIVE PIN ANCHORS USED ON MASONRY OR CONCRETE WALLS/ CEILINGS.

12.ALL CONDUIT ABOVE 10 FOOT SHALL MEET THE FOLLOWING REQUIRMENTS:

12.1. STRAP DISTANCE: 5 FEET.

12.2. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED- GRC.

12.3. FITTINGS: COMPRESSION.

12.4. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES.

13.ALL CONDUIT BELOW 10 FOOT SHALL MEET THE FOLLOWING REQUIREMENTS:

13.1. STRAP DISTANCE: 3 FEET.

13.2. FASTENERS: 2 HOLE WITH SECURITY SCREWS.

13.3. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED - GRC.

13.4. FITTINGS: COMPRESSION.

13.5. BELL BOXES: FS TYPE.

13.6. NO KNOCKOUTS.

13.7. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES

14.ALL EXPOSED WIRING SHALL BE IN CONDUIT. OPEN LOW VOLTAGE WIRING ABOVE

CEILINGS IS ACCEPTABLE. REFER TO TC DRAWINGS FOR SUPPORT DETAILS.

15.CONDUITS SHALL BE INSTALLED STRAIGHT AND LEVEL AND SHALL BE PARALLEL OR

PERPENDICULAR TO THE BUILDING LINES.

16.CONTRACTOR SHALL VERIFY ALL VOLTAGES BEFORE CONNECTING ANY EQUIPMENT.

17.ALL LOCATIONS WHERE THE WALLS CAN'T BE FISHED SHALL BE SURFACE MOUNTED

CONDUIT FOLLOWING NOTES 11 AND 12 ABOVE.

18.ALL WALLS THAT ARE ACCESSIBLE SHALL BE FISHED AND DEVICE CUT INTO WALL.

19.ALL EXTERIOR CONCEALED CONDUIT UNDERGROUND SHALL BE RNC, TYPE EPC-40-

PVC

20.ANY ELECTRICAL OUTAGE SHALL NOT LAST OVER 2-HOURS. FOR OUTAGES OVER

PORTABLE GENERATORS SHALL BE USED TO REPLACE ANY ELECTRICAL SERVICE

EXCEEDING THIS TIME PERIOD.

GENERAL ELECTRICAL NOTES

OUTLETS

ELECTRICAL SYMBOLS LEGEND

SINGLE RECEPTACLE (120 VOLT)

DUPLEX RECEPTACLE

EMERGENCY RECEPTACLE

DOUBLE DUPLEX RECEPTACLE

FLUSH FLOOR BOX

SURFACE FLOOR BOX

SPECIAL EQUIPMENT RECEPTACLE

TELEPHONE OUTLET

DATA OUTLET

TELEPHONE / DATA OUTLET

POWER POLE

JUNCTION BOX

WALL JUNCTION BOX

PULL (JUNCTION) BOX

UNDERFLOOR JUNCTION BOX

CEILING MOUNTED WIFI

SWITCHES

SINGLE-POLE SWITCH

THREE-WAY SWITCH

FOUR-WAY SWITCH

SWITCH WITH PILOT LIGHT

THERMAL OVERLOAD SWITCH

MANUAL MOTOR SWITCH

KEY SWITCH

TIME SWITCH

DIMMER SWITCH

MECHANICAL

SINGLE PHASE MOTOR

THREE PHASE MOTOR

RESISTANCE HEATER, KW SHOWN

PIPE TRACE HEATER

ELECTRIC UNIT HEATER

ELECTRIC WATER HEATER

NURSE CALL

NURSE CALL CONTROLLER

MASTER STATION

EMERGENCY PULL STATION

EMERGENCY PUSH STATION

CODE BLUE STATION

PENDENT INTERFACE

BED / LIGHT INTERFACE

SINGLE BED STATION

DUAL BED STATION

DOME LIGHT

STAFF REGISTER STATION

STAFF STATION

DUTY STATION

DESIGNATIONS

DEMOLITION NOTE

PLAN NOTE

ADDENDUM NOTE

FIXTURES

LIGHT FIXTURE

STRIP FIXTURE

EMERGENCY LIGHT FIXTURE

IN-GRADE LIGHT FIXTURE

SPOTLIGHT

(number of heads shown)

EXIT SIGN

(face & direction as shown)

WALL MOUNT LIGHT FIXTURE

CEILING LIGHT FIXTURE

TRACK & FIXTURE

STREET TYPE POLE FIXTURE

POLE MOUNTED LIGHT FIXTURE

EXTERIOR WALL MOUNT LIGHT FIXTURE

WALLPACK LIGHT FIXTURE

SPECIAL PURPOSE LIGHT FIXTURE

HIGH BAY LIGHT FIXTURE

EMERGENCY EGRESS LIGHT FIXTURE

(number of heads shown)

DOCK LIGHT FIXTURE

SERVICE AND EQUIPMENT

TRANSIENT VOLTAGE SURGE SUPPRESSION

VARIABLE FREQUENCY DRIVE

TRANSFORMER

DISCONNECT SWITCH (fuse size shown)

MAGNETIC STARTER (BY x/C U.O.N.)

COMB. STARTER (BY x/C U.O.N.)

PANELBOARD, SURFACE MOUNTED

PANELBOARD, FLUSH MOUNTED

WEATHERHEAD

UTILITY METER, AS REQUIRED

CURRENT TRANSFORMERS

GENERATOR, KW SHOWN

TELEPHONE TERMINAL BOARD

GROUND CONNECTION PER N.E.C.

WIREWAY

TRANSFER SWITCH

ENCLOSED CIRCUIT BREAKER

CAPACITOR

CIRCUITRY AND RACEWAYS

CONDUIT INSTALLED (by E.C.)

CONDUIT INSTALLED (by others)

CONDUIT STUB UP

CONDUIT STUB DOWN

HOME RUN (with circuit numbers)

END OF CONDUIT RUN

END OF CONDUIT RUN, CAP AND STAKE

"CONDUIT RUN CONTINUES" INDICATION

FLEXIBLE PIGTAILS/CONNECTIONS

WIREMOLD AS SPECIFIED

PLUGMOLD AS SPECIFIED

BUS DUCT

UNDERFLOOR DUCT

SOUND AND SIGNAL

SPEAKER

WALL MOUNTED SPEAKER

WALL MOUNTED SPEAKER / CLOCK COMBO

SINGLE FACE CLOCK

DUAL FACE CLOCK

VIDEO INPUT

AUDIO / VIDEO INPUT

BELL

VOLUME CONTROL

BUZZER

CHIME

TELEVISION OUTLET

MICROPHONE OUTLET

INTERCOM OUTLET

CAMERA

DOOR CONTACT

MOTION DETECTOR

BEAM DETECTOR

KEY PAD

SECURITY SYSTEM CONTROL PANEL

CCTV CONTROL PANEL

CARD READER

STUDENT STATION

ADMINISTRATION STATION

TEACHER STATION

GLASS BREAK

EXIT ONLY

ELECTRIC STRIKE

CONTROL

THERMOSTAT

HUMIDISTAT

PHOTOCELL (voltage as required)

TIME CLOCK (24 hour U.O.N.)

PUSHBUTTON STATION

(number of buttons indicated)

CONTROL TRANSFORMER

LIGHTING CONTACTOR

IRRIGATION CONTROLLER

(120 volt xxVA connection by x/C)

WALL MOUNT DUAL TECHNOLOGY SENSOR SENSOR

SWITCH WV-PDT-16 SERIES

OCCUPANCY SENSOR / PHOTOCELL SENSOR SWITCH CMR-

PC-ADC SERIES

ULTRASONIC SENSOR - 360° - 2 CIRCUIT SENSOR SWITCH

CMR-PDT-10-2P

ULTRASONIC SENSOR - 360° - 1000 SQ FT SENSOR SWITCH

CMR-PDT-10

ULTRASONIC SENSOR - 360° - 500 SQ FT SENSOR

SWITCH CMR-PDT SERIES

SWITCH STYLE OCCUPANCY SENSOR SENSOR SWITCH

WSD-PDT SERIES

POWER PACK SENSOR SWITCH MP20 SERIES

DIGITAL TIME SWITCH WATT STOPPER TS-400

FIRE ALARM

SMOKE DETECTOR

HEAT DETECTOR

DUCT SMOKE DETECTOR

HORN

HORN & LIGHT

SPEAKER

SPEAKER & LIGHT

PULL STATION

FIRE ALARM CONTROL PANEL

ANNUNCIATOR PANEL

END OF LINE DEVICE

REMOTE INDICATING LIGHT, WALL MTD.

REMOTE INDICATING LIGHT, CLG. MTD.

MAGNETIC DOOR HOLDER

FIREFIGHTER COMMUNICATION JACK

FLOW SWITCH (furnished by FP/C)

TAMPER SWITCH (furnished by FP/C)

VISUAL ONLY UNIT

FIRE CONTROL POWER SUPPLY

MONITOR MODULE

CONTROL MODULE

CARBON DIOXIDE DETECTOR

CARBON MONOXIDE DETECTOR

SMOKE AND CARBON DIOXIDE DETECTOR

J

J

J

J

PP

F

S

P

TO

M

K

T

WH

M

P

E

CB

A

L

B1

B2

SRS

S

DS

NCC

X

X

X

D

S

S

VI

AV

B

V

B

C

M

I

C

DC

M

B

KP

SSCP

CCTV

CR

SS

AS

TS

GB

C

M

FCPS

V

FS

FC

DH

FACP

ANN

F

H

EOL

OS5

OS4

OS3

OS2

OS1

1,3

OR

WM

PM

BD

UFD

T

H

PC

TC

IC

OC

PP

T

TVSS

VFD

T

CT

G

TS

W W

T T

CD

M

2CO

ES

LIGHTING FIXTURE SCHEDULE

TYPE MANUFACTURER CATALOG NO. DESCRIPTION AND COMMENTS BALLAST INFO.

FIXTURE

MOUNTING

HEIGHT

LAMPS

KENALL LIGHTING

LED - 2X4

LA - GRID -

LAEM - GRID -

LED - 1X4 INDUSTRIAL STRIP FIXTURE.

LB

LBEM

KENALL LIGHTING

KENALL LIGHTING

KENALL LIGHTING

LED - 1X4 RECESSED CORRECTIONAL FIXTURE.

LD

LED - 1X1 RECESSED LIGHT FIXTURE.

LDEM

KENALL LIGHTING

KENALL LIGHTING

LE

LED - 1X4 HIGH BAY LIGHT FIXTURE.

LEEM

KENALL LIGHTING

KENALL LIGHTING

LF

LED - ROUND DOWNLIGHT FIXTURE.

LFEM

KENALL LIGHTING

KENALL LIGHTING

LG

LED - EXTERIOR WALL PACK.

LGEM

KENALL LIGHTING

KENALL LIGHTING

LC

LCEM

KENALL LIGHTING

KENALL LIGHTING

LED - EXTERIOR WALL PACK.

LED - ROUND DOWNLIGHT FIXTURE.

LED - 1X4 HIGH BAY LIGHT FIXTURE.

LED - 1X1 RECESSED LIGHT FIXTURE.

LED - 2X4

LED - 1X4 INDUSTRIAL STRIP FIXTURE.

LED - 1X4 RECESSED CORRECTIONAL FIXTURE.

KENALL LIGHTING

LED - 2X2

- GRID -

- GRID -KENALL LIGHTING

LED - 2X2

LH

LHEM

M at ri x

SHEET NUMBER

file no.

funding code contractor order no.

consultant job no.

472/22019.SMD

472/MaintProj sheet description consultant drawn by checked by issue date

JFS

MMG

E-100

22139.00

ELECTRICAL

LEGENDS

PHASE 300 09-09-2022

PHASE 400 12-14-2022

E

SB-3

SB-2

SB-1

HYD. 24

NEW VEHICLE

GATE

NEW PEDESTRIAN

GATE

DEMO EXISTING

SALLY PORT

NEW TRUCK /

CAR ENTRANCE

TO BUILDING 30

NEW PEDESTRIAN

ENTRANCE TO

BUILDING 30

EXISTING

INTERIOR FENCE

ENTRANCE

NEW B FENCE EXISTING A

FENCE

NEW B FENCE

NEW A FENCE

NEW INTERIOR

FENCE ENTRANCE

DE

SIG

N

AN

D

CO

NS

TR

UC

TIO

N

DI

VIS

IO

N

DE

PA

RT

M

EN

T

OF

T

EC

HN

OL

OG

Y, M

AN

AG

EM

EN

T, A

ND

B

UD

GE

T

ST

AT

E

OF

M

IC

HI

GA

N

AD

AM

P . L

AC

H, R A, D

IR

EC

TO

R

ST

AT

E

FA

CI

LI

TI

ES

A

DM

IN

IS

TR

AT

IO

N

REVIEW

DRAWING

NOT FOR

CONSTRUCTION

PLOT DATE: 12/13/2022

M at ri x

CO

NS

UL

TIN

G

EN

GI

NE

ER

S, IN

C

FA

X:

(5

) 4

-2

PH

ON

E:

(5

) 4

-2

LA

NS

IN

G, M

I 4

E

. C

ES

AR

E

. C

HA

VE

Z

AV

E.

W

EB

: w ww

.m at rix ce in c.

co m

SHEET NUMBER

file no.

funding code contractor order no.

consultant job no.

472/22019.SMD

472/MaintProj sheet description consultant drawn by checked by issue date

M

AT

RI

X

PR

OJ

EC

T:

/16

/20

7:

:52 A

M Au tod es k D oc s:/ /D

TM

B

PA

RN

AL

L D

IE

SE

L B

LD

G/

9_

BL

DG

_M

EP

.rv t

JFS

MMG

PA

RN

AL

L

CO

RR

EC

TI

O N

AL

F

AC

IL

IT

Y

N

EW

D

IE

SE

L

M

EC

H

AN

IC

AL

P

RO

GR

AM

E P

AR

N

AL

L

RD

JA

CK

SO

N , M

IC

H

IG

AN

E-200

22139.00

9.

ELECTRICAL - NEW

SITE PLAN -

REVISED FENCING

LAYOUT

PHASE 300 09-09-2022

PHASE 400 12-14-2022

N 0 1 124 8

SCALE: 1" = 40'-0"

NEW ELECTRICAL SITE PLAN

EXISTING ELECTRICAL SYSTEMS & EQUIPMENT TO BE DEMOLISHED

COMPLETELY THROUGHOUT ENTIRETY OF BUILDING. REMOVE ALL

EXISTING ASSOCIATED CONDUIT AND WIRE BACK TO SOURCE.

ELECTRICAL DEMOLITION KEYNOTES

7654321

B

C

7654321

B

C

B

C

B

C

M at ri x

SHEET NUMBER

file no.

funding code contractor order no.

consultant job no.

472/22019.SMD

472/MaintProj sheet description consultant drawn by checked by issue date

JFS

MMG

E-300

22139.00

ELECTRICAL

DEMOLITION PLAN

N 0 1 124 8

SCALE: 1/8" = 1'-0"

ELECTRICAL DEMOLITION PLAN - MAIN LEVELN

0 1 124 8

SCALE: 1/8" = 1'-0"

ELECTRICAL DEMOLITION PLAN - MEZZANINE

OS

3 3

3 3 3 3

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS OS

OSOS

OS

OS

OS

OS OS OS OS

OS OS OS OS

OS OS OS OS

OS OS

OS OS

OS OS

OS OS

OS OS

OS OS

OS

OS

OS

OSOSOSOSOSOSOS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS OS

OS OS

OS OS

OS OS

OS OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

PPPP

PP

PP PP

PP

PP PP

PP

PP

PC

B

C

B

C

LCLC

LC

LCLC

7654321

B

C

TOOL CRIB

105 TRUCK BAYS

COMPRESSOR RM

HEAVY DIESEL LAB

HEAVY DIESEL CLASSROOM

MEZZ ACCESS

CDL CLASSROOM

110MULTIPURPOSE

ELECTRICAL CLOSET

AUTO CLASSROOM

AUTO TOOL CRIB

FURN. CLOS.

WATER SERV. RM.

AUTO SHOP

STAFF OFFICES

CORRIDOR

MAIN ENTRY

CORRIDOR

INMATE TOILETS

STAFF TOILETS

CORRIDOR

7654321

B

C

VEST. / COAT ROOM

211 SF

UNASSIGNED

511 SF

TECH CLOS.

151 SF

LD LD

LE

LE

LE

LA LA

LA LA

LALA

LA

LA LA

LA

LB

LALA

LA LA

LA LA

LALA

LB

LA

LHEM

LH

LH LH LH

LHEM

LHEM

LHEM

LGEM

LGEM

LC

LC

LD LD LD

LA LA

LALA

LA

LA

LA

LA

LA

LC LC

LDLDLDLDLDLDLDLDLD

LD

LC LC

LC LC

LD

LD

LD

LD

LD

LD

LD

LD

LD

LD

LD

LD

LA LA

LA LA

LALA

LALA

LC

LC

LC

LA

LA

LA

LB

LB

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LA

LD

LC

LC

LC

LD

LDLD

LD LD

LDLD

LD LD

LB

LCLC LC

TO LIGHTS IN

MEZZANINE

LD

LD

LF

LF LF

LF LF LF

LFLF

LF LF

LFLFLF

LFLF

LF

XA

XA

XA

XA

XA

XA

XA XA

XA

XA

XA

XA

LHEM

XA

XA XA XA XA XA

XA

XA

XA

XA XA

XA

XA

XA

LHEM

LH

1. PROVIDE AND INSTALL NEW LIGHTING CONTROL DEVICES IN ALL

RENNOVATED SPACES.

GENERAL ELECTRICAL NOTES

M at ri x

SHEET NUMBER

file no.

funding code contractor order no.

consultant job no.

472/22019.SMD

472/MaintProj sheet description consultant drawn by checked by issue date

JFS

MMG

E-400

22139.00

ELECTRICAL

LIGHTING PLAN

N 0 1 124 8

SCALE: 1/8" = 1'-0"

ELECTRICAL LIGHTING PLAN - MEZZANINE N

0 1 124 8

SCALE: 1/8" = 1'-0"

MAIN LEVEL ELECTRICAL LIGHTING PLAN

GFI

WP

48"

48"

48" 48"

GFI

WP

48" 48" 48"

48"

48"

48" 48" 48" 48"

GFI

WP

J 72"

48" 48"

48"

CLNG

J

CLNG

J

CLNG

J

CLNG

J

CLNG

J

GFI

WP

GFI

WP

GFI

WP

TO

7654321

B

C

TOOL CRIB

TRUCK BAYS

COMPRESSOR RM

HEAVY DIESEL LAB

HEAVY DIESEL CLASSROOM

MEZZ ACCESS

CDL CLASSROOM

MULTIPURPOSE

TECH CLOS.

AUTO CLASSROOM

AUTO TOOL CRIB

WATER SERV. RM.

AUTO SHOP

AUTO SHOP

STAFF OFFICES

CORRIDOR

MAIN ENTRY

CORRIDOR

UNASSIGNED

INMATE TOILETS

J.C.

STAFF TOILETS

CORRIDOR

CORRIDOR

F-1

UH-1

SEE MEZZANINE PLAN

FOR CONTINUATION.

FRIDGE

FOOD WARMER

7654321

B

C

ELECTRICAL CLOSET

146 SF

CORRIDOR

231 SF

F-2

F-3

UH-2

VEST. / COAT ROOM

211 SF

SIMULATOR

SIMULATOR

COMMUNICATIONS RACEWAY

FOR TV TO TEACHER

COMPUTER CONNECTION

WALL FAN

COMMUNICATIONS RACEWAY

FOR TV TO TEACHER

COMPUTER CONNECTION

WALL FAN

COMMUNICATIONS RACEWAY

FOR TV TO TEACHER

COMPUTER CONNECTION

WALL FAN

CONCRETE PAD

NEW 500KVA MEDIUM VOLTAGE TRANSFORMER TN-30C

PRIMARY: 12,470V

SECONDARY: 480/277V

NEW UNDERGROUND

ELECTRICAL CONDUIT

AND WIRE

UH-3

F-5

UH-4

MDP

480/277V-3PH, 4W 600A

RP-1

208/120V-3PH, 4W 125A

TN-1

45KVA

LP-2

480/277V-3PH, 4W 200A

RP-4

208/120V-3PH, 4W 200A

TN-4

75KVA

LP-1

480/277V-3PH, 4W 200A

RP-3

208/120V-3PH, 4W 125A

TN-3

45KVA

HOIST

208V-1PH, 2HP

HOIST

208V-1PH, 2HP

HOIST

208V-1PH, 2HP

FURN. CLOS.

20 SF

AC-2

AC-3A

AC-3B

CU-3

WP

DWH-1

COMP-1

CU-4

CU-1

WP

WP

B

C

F-4

B

C

RP-2

208/120V-3PH, 4W 200A

TN-2

75KVA

1. PROVIDE AND INSTALL NEW CONDUIT, WIRE AND OVER CURRENT

PROTECTION FOR FURNACE IN LOCATION SHOWN.

2. PROVIDE AND INSTALL NEW CONDUIT, WIRE AND OVER CURRENT

PROTECTION FOR NEW UNIT HEATER IN LOCATION SHOWN.

3. PROVIDE AND INSTALL NEW CONDUIT, WIRE AND OVER CURRENT

PROTECTION FOR NEW INFRARED HEATER IN LOCATION SHOWN.

4. PROVIDE AND INSTALL NEW POWER DEVICES AND EQUIPMENT BASED

ON PROGRAM REQUIREMNTS.

5. PROVIDE AND INSTALL VANDAL AND TAMPER RESISTANT DEVICE(S) IN

NOTED ROOM.

ELECTRICAL GENERAL NOTES

M at ri x

SHEET NUMBER

file no.

funding code contractor order no.

consultant job no.

472/22019.SMD

472/MaintProj sheet description consultant drawn by checked by issue date

JFS

MMG

E-500

22139.00

ELECTRICAL

POWER PLAN

N 0 1 124 8

SCALE: 1/8" = 1'-0"

MAIN LEVEL ELECTRICAL POWER PLANN

0 1 124 8

SCALE: 1/8" = 1'-0"

ELECTRICAL POWER PLAN - MEZZANINE

GFI

WP

7654321

B

C

7654321

B

C

EF-1

EF-2

EF-3

EF-4

EF-5

M at ri x

SHEET NUMBER

file no.

funding code contractor order no.

consultant job no.

472/22019.SMD

472/MaintProj sheet description consultant drawn by checked by issue date

JFS

MMG

E-501

22139.00

ELECTRICAL

POWER PLAN -

ROOF

N 0 1 124 8

SCALE: 1/8" = 1'-0"

ELECTRICAL POWER PLAN - ROOF

F

F

F

F

F

F

F

F

F

F F

F

F

F F

F F

F

F F

FF F

F

F

F

F F

F

7654321

B

C

7654321

B

C

TOOL CRIB

COMPRESSOR RM

HEAVY DIESEL LAB

HEAVY DIESEL CLASSROOM

MEZZ ACCESS

CDL CLASSROOM

110MULTIPURPOSE

TECH CLOS.

AUTO CLASSROOM

AUTO TOOL CRIB

WATER SERV. RM.

AUTO SHOP

AUTO SHOP

STAFF OFFICES

CORRIDOR

MAIN ENTRY

CORRIDOR

UNASSIGNED

INMATE TOILETS

J.C.

STAFF TOILETS

CORRIDOR

CORRIDOR

SEE MEZZANINE PLAN

FOR CONTINUATION.

ELECTRICAL CLOSET

146 SF

CORRIDOR

231 SF

VEST. / COAT ROOM

211 SF

CONCRETE PAD

NEW 500KVA MEDIUM VOLTAGE TRANSFORMER TN-30C

PRIMARY: 12,470V

SECONDARY: 480/277V

NEW UNDERGROUND

ELECTRICAL CONDUIT

AND WIRE

MDP

480/277V-3PH, 4W 600A

RP-1

208/120V-3PH, 4W 125A

TN-1

45KVA

LP-2

480/277V-3PH, 4W 200A

RP-4

208/120V-3PH, 4W 200A

TN-4

75KVA

LP-1

480/277V-3PH, 4W 200A

RP-3

208/120V-3PH, 4W 125A

TN-3

45KVA

FURN. CLOS.

20 SF

TRUCK BAYS

4096 SF

FACP

B

C

B

C

RP-2

208/120V-3PH, 4W 200A

TN-2

75KVA

1.FIRE ALARM CABLE CAN BE INSTALLED FREE AIR ABOVE CEILINGS.

2.PROVIDE RACEWAY WHERE SURFACE MOUNT DEVICES ARE REQUIRED.

CONDUIT SHALL BE 3/4" MINIMUM PAINTED RED.

3.ALL CABLE SHALL BE INSTALLED PER FIRE ALARM MANUFACTURER'S

SPECIFICATIONS.

4.FIRE ALARM REMOTE POWER SUPPLY SHALL BE MONITORED.

5.PROVIDE SMOKE DETECTOR ABOVE ALL FIRE ALARM PANELS AND

REMOTE POWER SUPPLIES.

6.REFER TO DRAWINGS FOR DEVICE QUANTITIES AND LOCATIONS. BRING

TO THE ENGINEER'S ATTENTION DISCREPANCIES PRIOR TO BIDDING

PROJECT.

7.UPON ALARM OF SMOKE DETECTORS, FIRE ALARM SYSTEM TO

RELEASE DOOR HOLDERS.

8.POWER SUPPLIES IN BOTH FACP AND FCPS SHALL HAVE 25% SPARE

CAPACITY.

9.TRUE PEER TO PEER NETWORK FOR FIRE ALARM SYSTEM.

10. FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR ALL CANDELA

RATINGS OF VISUAL UNITS TO COMPLY WITH NFPA 72. STROBE CANDELA

SETTINGS SHALL BE SET DURING INSTALLATION OF THE DEVICE.

11. REPLACE ALL EXISTING DUCT DETECTORS AS SHOWN ON PRINTS.

ANY DUCT DETECTORS THAT ARE DISCOVERED AND NOT SHOWN SHALL

BE BROUGHT TO THE ENGINEER'S ATTENTION.

12. PROVIDE REMOTE TEST STATIONS FOR EACH DUCT DETECTOR.

13. INSTALLATION METHODS SHALL BE IN ACCORDANCE WITH THE

NATIONAL ELECTRICAL CODE, ARTICLE 760.

14. 120V AC POWER FOR FIRE ALARM SYSTEM ENCLOSURES SHALL NOT

SHARE CONDUIT RACEWAY WITH FIRE ALARM SYSTEM CIRCUITS.

15. FIRE ALARM SYSTEM DEVICES SHALL BE MOUNTED TO ELECTRICAL

BOXES AS REQUIRED AND REFLECTED ON DEVICE INSTALLATION SHEET.

16. STROBE CANDELA SETTINGS SHALL BE SET DURING INSTALLATION OF

THE DEVICE.

17. AREA SMOKE DETECTORS SHALL NOT BE PLACED WITHIN 36-INCHES

OF AIR DISTRIBUTION DIFFUSERS OR RETURN GRILLS.

FIRE ALARM GENERAL NOTES

M at ri x

SHEET NUMBER

file no.

funding code contractor order no.

consultant job no.

472/22019.SMD

472/MaintProj sheet description consultant drawn by checked by issue date

JFS

MMG

E-502

22139.00

ELECTRICAL FIRE

ALARM

N 0 1 124 8

SCALE: 1/8" = 1'-0"

MAIN LEVEL ELECTRICAL POWER PLANN

0 1 124 8

SCALE: 1/8" = 1'-0"

ELECTRICAL POWER PLAN - MEZZANINE

FEED TO TE-13B/C

NOT CONFIRMED

PAD MOUNT SWITCH

SPLICE IN BASEMENT OF BLOCK 10

A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B

A B A B A B A B A B A B

A B A B A B A B A B A B A B A B A B A B

A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B

A B A B A B A B A B A B

A B

12.47kV

208/120V

30kV A

208/120V

150kVA

2.4k V

12.47kV

300kVA

208/120V 208/120V

150kVA

2.4k V

208/120V

150kVA

2.4k V

480V

500kVA 500kVA 500kVA 500kVA 500kVA

500kVA500kVA

500kVA 500kVA

500kVA

75kV A

75kV A

75kV A

75kV A

75kV A

75kVA

75kV A

75kV A

75kV A

75kV A

75kVA 75kVA 75kVA 75kV A

75kV A

75kV A

75kV A

75kV A

75kV A

75kV A

480V 480V 480V 480V 480V 480V480V480V

480V

480V 480V

480V480V480V 480V 480V 480V 480V

480V

480V480V480V480V480V480V

208/120V

208/120V 208/120V208/120V208/120V 208/120V

208/120V 208/120V 208/120V 208/120V 208/120V 208/120V 208/120V 208/120V

225kVA

208/120V208/120V 208/120V 208/120V 208/120V 208/120V 208/120V 208/120V 208/120V

12.47kV12.47kV12.47kV12.47kV12.47kV

12.47kV12.47kV12.47kV 12.47kV 12.47kV

12.47kV 12.47kV12.47kV12.47kV12.47kV12.47kV

12.47kV12.47kV12.47kV12.47kV12.47kV12.47kV12.47kV12.47kV 12.47kV 12.47kV 12.47kV

12.47kV 12.47kV 2.4kV 12.47kV

12.47kV

12.47kV

2.4k V

2.4k V

2.4k V

12.47kV 2.4k V

2.4k V

2.4k V

2.4k V

2.4k V

2.4k V

2.4k V

2.4k V

2.4k V

2.4k V

2.4k V

2.4k V

TN-6C TE-6C TN-19C TN-18C TN-60C TN-30C

TN-7D TE-7D TN-8D TE-8D TN-9D TE-9D TN-10D TE-10D TN-32D TN-31D

TN-16D TE-16DTN-80D-2TE-80DTN-80DTN-91DTE-92DTN-92DTE-79DTN-79DTE-126DTN-126DTN-219DTN-193D-1TN-197DTN-196D

TN-198ETN-57E TE-198E TN-218E TE-218E TN-71E

TN-138E

TE-4BTN-4B TN-5B TE-5B TE-5B2 TN-13B/C TE-13B/C TN-18B TE-18B/C TN-19B TE-19C TE-GH TN-27B TN-28 TN-29B

FAC "C" FAC "D"

BLDG 5BLDG 4

BLDG 13

& 17 BLDG 18 BLDG 19

GUARD

HOUSE BLDG 27 BLDG 28 BLDG 29

A B

A B A B A BA B

BLDG 6

BLDG 19 BLDG 18

BLDG 60 BLDG 30

BLDG 7 BLDG 8 BLDG 9 BLDG 10

BLDG 32 BLDG 31

300kVA 225kVA

112.5kV A

480V

BLDG 215 BLDG 197 BLDG 219

BLDG 126

BLDG 91

(53,200,201)

BLDG

80 & 49

BLDG 80

BLDG 16

BLDG 57

BLDG 198 BLDG 218

BLDG 71 BLDG 74

BLDG 138

225kVA225kVA 112.5kV A

225kVA

225kVA 225kVA 225kVA

225kVA300kVA300kVA150kVA150kVA 150kVA

750kVA 300kVA 300kVA

750kVA

TE-3A

FAC "B" FAC "B"

BLDG 79

BLDG 92

A B

480V

12.47kV

225kVA

TN-74E

2.4KV SWGR-B2

12.47KV SWGR-A1 12.47KV SWGR-B1

208V

A B

75kVA

208/120V

TE-13B/C

BLDG 196

12.47KV SWGR-A1 12.47KV SWGR-B1

12.47kV

E400-1

SCOPE OF WORK

C A T- 6 PA TC H

C A B LE -GREEN

C A T- 6 CA BLE

- GREEN

C O NTAC T

C LOSURE

C A BLES.

PU RPLE I N

C O LO R

DISCONNECT AND REMOVE EXISTING TRANSFORMER TN-30C.

EXISTING MEDIUM VOLTAGE CONDUIT AND WIRE TO REMAIN FOR

INSTALLATION OF NEW TRANSFORMER. DISCONNECT AND REMOVE

ALL CONDUIT AND WIRE FROM TRANSFORMER TN-30C TO BUILDING

30.

ELECTRICAL DEMOLITION KEYNOTES

M at ri x

SHEET NUMBER

file no.

funding code contractor order no.

consultant job no.

472/22019.SMD

472/MaintProj sheet description consultant drawn by checked by issue date

JFS

MMG

E-600

22139.00

ELECTRICAL RISER

DIAGRAM - DEMO

NOT TO SCALEE-600

1 RISER DIAGRAM DEMO

FEED TO TE-13B/C

NOT CONFIRMED

PAD MOUNT SWITCH

SPLICE IN BASEMENT OF BLOCK 10

A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B

A B A B A B A B A B A B

A B A B A B A B A B A B A B A B A B A B

A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B

A B A B A B A B A B A B

A B

12.47kV

208/120V

30kV A

208/120V

150kVA

2.4k V

12.47kV

300kVA

208/120V 208/120V

150kVA

2.4k V

208/120V

150kVA

2.4k V

480V

500kVA 500kVA 500kVA 500kVA 500kVA

500kVA500kVA

500kVA 500kVA

500kVA

75kV A

75kV A

75kV A

75kV A

75kV A

75kVA

75kV A

75kV A

75kV A

75kV A

75kVA 75kVA 75kVA 75kV A

75kV A

75kV A

75kV A

75kV A

75kV A

75kV A

480V 480V 480V 480V 480V 480V480V480V

480V

480V 480V

480V480V480V 480V 480V 480V 480V

480V

480V480V480V480V480V480V

208/120V

208/120V 480/277V208/120V208/120V 208/120V

208/120V 208/120V 208/120V 208/120V 208/120V 208/120V 208/120V 208/120V

225kVA

208/120V208/120V 208/120V 208/120V 208/120V 208/120V 208/120V 208/120V 208/120V

12.47kV12.47kV12.47kV12.47kV12.47kV

12.47kV12.47kV12.47kV 12.47kV 12.47kV

12.47kV 12.47kV12.47kV12.47kV12.47kV12.47kV

12.47kV12.47kV12.47kV12.47kV12.47kV12.47kV12.47kV12.47kV 12.47kV 12.47kV 12.47kV

12.47kV 12.47kV 2.4kV 12.47kV

12.47kV

12.47kV

2.4k V

2.4k V

2.4k V

12.47kV 2.4k V

2.4k V

2.4k V

2.4k V

2.4k V

2.4k V

2.4k V

2.4k V

2.4k V

2.4k V

2.4k V

2.4k V

TN-6C TE-6C TN-19C TN-18C TN-60C TN-30C

TN-7D TE-7D TN-8D TE-8D TN-9D TE-9D TN-10D TE-10D TN-32D TN-31D

TN-16D TE-16DTN-80D-2TE-80DTN-80DTN-91DTE-92DTN-92DTE-79DTN-79DTE-126DTN-126DTN-219DTN-193D-1TN-197DTN-196D

TN-198ETN-57E TE-198E TN-218E TE-218E TN-71E

TN-138E

TE-4BTN-4B TN-5B TE-5B TE-5B2 TN-13B/C TE-13B/C TN-18B TE-18B/C TN-19B TE-19C TE-GH TN-27B TN-28 TN-29B

FAC "C" FAC "D"

BLDG 5BLDG 4

BLDG 13

& 17 BLDG 18 BLDG 19

GUARD

HOUSE BLDG 27 BLDG 28 BLDG 29

A B

A B A B A BA B

BLDG 6

BLDG 19 BLDG 18

BLDG 60 BLDG 30

BLDG 7 BLDG 8 BLDG 9 BLDG 10

BLDG 32 BLDG 31

300kVA 225kVA

112.5kV A

480V

BLDG 215 BLDG 197 BLDG 219

BLDG 126

BLDG 91

(53,200,201)

BLDG

80 & 49

BLDG 80

BLDG 16

BLDG 57

BLDG 198 BLDG 218

BLDG 71 BLDG 74

BLDG 138

500kVA225kVA 112.5kV A

225kVA

225kVA 225kVA 225kVA

225kVA300kVA300kVA150kVA150kVA 150kVA

750kVA 300kVA 300kVA

750kVA

TE-3A

FAC "B" FAC "B"

BLDG 79

BLDG 92

A B

480V

12.47kV

225kVA

TN-74E

2.4KV SWGR-B2

12.47KV SWGR-A1 12.47KV SWGR-B1

208V

A B

75kVA

208/120V

TE-13B/C

BLDG 196

12.47KV SWGR-A1 12.47KV SWGR-B1

12.47kV

E400-1

SCOPE OF WORK

C A T- 6 PA TC H

C A B LE -GREEN

C A T- 6 CA BLE

- GREEN

C O NTAC T

C LOSURE

C A BLES.

PU RPLE I N

C O LO R

CONTRACTOR SHALL PROVIDE AND INSTALL NEW 30E FUSE FOR NEW

TRANSFORMER FEEDING NEW SERVICE AT BUILDING 30. CONTRACTOR

SHALL PROVIDE AND INSTALL NEW 500KVA 12,470Y-480/277V

TRANSFORMER. REFER TO SHEET E-500 FOR MORE DETAIL.

ELECTRICAL KEYNOTES

M at ri x

SHEET NUMBER

file no.

funding code contractor order no.

consultant job no.

472/22019.SMD

472/MaintProj sheet description consultant drawn by checked by issue date

JFS

MMG

E-601

22139.00

ELECTRICAL RISER

DIAGRAM - NEW

NOT TO SCALEE-601

1 RISER DIAGRAM NEW

PHASE 300 09-09-2022

PANEL

PANEL PANEL

KVA

T

KVA

T

PANEL PANEL

KVA

T

KVA

T

PANEL PANEL

NEW

MDP

480/277V

3PH, 4W

600A / MCB

NEW

LP-1

480/277V

3PH, 4W

200A / MLO

NEW

LP-2

480/277V

3PH, 4W

200A / MLO

#6

TN1

#6

TN2

NEW

RP-1

208/120V

3PH, 4W

125A / MCB

NEW

RP-2

208/120V

3PH, 4W

200A / MCB

#6

TN3

#6

TN4

NEW

RP-3

208/120V

3PH, 4W

125A / MCB

NEW

RP-4

208/120V

3PH, 4W

200A / MCB

A B A B

75kVA

480/277V208/120V

12.47kV12.47kV

TN-60C TN-30C

FAC "C" FAC "D"

A B A B A BA B

BLDG 60

500kVA

12.47KV SWGR-A1 12.47KV SWGR-B1

TN-9D / TN-10D

TN-9D / TN-10D

TE-10D / TN-32D

TE-10D / TN-32D

TN-18CTN-18C

BUILDING 30

C A T- 6 PA TC H

C A B LE -GREEN

C A T- 6 CA BLE

- GREEN

C O NTAC T

C LOSURE

C A BLES.

PU RPLE I N

C O LO R

M at ri x

SHEET NUMBER

file no.

funding code contractor order no.

consultant job no.

472/22019.SMD

472/MaintProj sheet description consultant drawn by checked by issue date

JFS

MMG

E-602

22139.00

ELECTRICAL RISER

DIAGRAM -

BUILDING 30

NOT TO SCALEE-602

1 RISER DIAGRAM NEW BUILDING 30

File details come from the government source that posted it. Updated .