This document contains the electrical drawings related to the New Diesel Mechanic Program project at the Parnall Correctional Facility in Jackson, Michigan. The project involves the complete demolition of the existing electrical systems and equipment throughout the entire facility, and the installation of new electrical infrastructure, including a new 500 kVA medium voltage transformer, new panelboards, new receptacles, lighting, and a new fire alarm system. The electrical work is part of a larger construction project to build a new Heavy Diesel Program at the facility.
The electrical drawings provide details on the new site electrical layout, demolition plans, lighting plans, power plans, and riser diagrams. Key details include the installation of a new 500 kVA 12,470Y-480/277V transformer, new 480/277V and 208/120V panelboards and branch circuits, LED lighting fixtures, and a new addressable fire alarm system. The project is part of a state and local contract opportunity identified as 472/22091. SMD with the State of Michigan and Jackson County.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1P 1 POLE (2P, 3P, 4P, ETC.)
A AMPS
AC ABOVE COUNTER
AC- AIR CONDITIONER
ACU- AIR CONDITIONING UNIT
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
AF AMP FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT
INTERRUPTER
AHJ AUTHORITY HAVING
JURISDICTION
AHU- AIR HANDLING UNIT
AIC AMPS INTERUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
AMPL AMPLIFIER
ANNUN ANNUNCIATOR
APPROXAPPROXIMATELY
AQ-STAT AQUASTAT
ARCH ARCHITECT, ARCHITECTURAL
AS AMP SWITCH OR ABOVE SHELF
AT AMP TRIP
ATS AUTOMATIC TRANSFER
SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
B- BOILER
BATT BATTERY
BC BELOW COUNTER
BD BOARD
BLDG BUILDING
BMS BUILDING MANAGEMENT
SYSTEM
C CONDUIT
CAB CABINET
CAT CATALOG
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CHLR- CHILLER
CKT CIRCUIT
CKT BRKRCIRCUIT BREAKER
CLG CEILING
COMB COMBINATION
CMPR COMPRESSOR
CND(C) CONDUIT
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR
CONTINUOUS
CONTR CONTRACTOR
CONV CONVECTOR
CP CIRCULATING PUMP
CRT CATHODE-RAY TUBE
CT CURRENT TRANSFORMER
CT- COOLING TOWER
CTR CENTER
CU COPPER
CU- CONDENSING UNIT
CUH- CABINET UNIT HEATER
DCP DOMESTIC WATER
CIRCULATING PUMP
DEPT DEPARTMENT
DET DETAIL
DFU- DUCT FURNACE
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DPR DAMPER
DS SAFETY DISCONNECT
SWITCH
DT DOUBLE THROW
DWG DRAWING
DWH- DOMESTIC WATER HEATER
EBB- ELECTRIC BASEBOARD
EC ELECTRICAL CONTRACTOR
EF- EXHAUST FAN
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMS ENERGY MANAGEMENT
SYSTEM
EMT ELECTRICAL METALLIC
TUBING
EP ELECTRIC PNEUMATIC
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXH EXHAUST
EXIST (E) EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FABP FIRE ALARM BOOSTER
POWER SUPPLY PANEL
FACP FIRE ALARM CONTROL
PANEL
FCU FAN COIL UNIT
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE CONDUIT
FLR FLOOR
FLUOR FLUORESCENT
FSES FOOD SERVICE EQUIP.
SUPPLIER
F/S FIRE/SMOKE
FU FUSE
FU- FURNACE
FUDS FUSED SAFETY DISCONNECT
SWITCH
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT
INTERRUPTER
GFP GROUND FAULT PROTECTOR
GND GROUND
GRS GALVANIZED RIGID STEEL
(CONDUIT)
GYP BD GYPSUM BOARD
H- HUMIDIFIER
HID HIGH INTENSITY DISCHARGE
HOA HANDS-OFF-AUTOMATIC
SWITCH
HORIZ HORIZONTAL
HP HORSEPOWER
HPF HIGH POWER FACTOR
HR HOUR
HT HEIGHT
HTG HEATING
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND
AIR CONDITIONING
HWP HYDRONIC WATER PUMP
IC INTERRUPTING CAPACITY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL
CONDUIT
INCAND INCANDESCENT
IR INFRARED
I/W INTERLOCK WITH
JB JUNCTION BOX
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LC LIGHT CONTROL
LOC LOCATE OR LOCATION
LT LIGHT
LT FLEX LIQUID TIGHT FLEXIBLE
METAL CONDUIT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MAG.S MAGNETIC STARTER
M/C MOMENTARY CONTACT
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDC MAIN DISTRIBUTION CENTER
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT
SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MMS MANUAL MOTOR STARTER
MOA MULTIOUTLET ASSEMBLY
MSP MOTOR STARTER
PANELBOARD
MSBD MAIN SWITCHBOARD
MT MOUNT
MT.C EMPTY CONDUIT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MTR MOTOR, MOTORIZED
MUA- MAKE-UP AIR UNIT
N.C. NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY
DISCONNECT SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
N.O. NORMALLY OPEN
NPF NORMAL POWER FACTOR
NTS NOT TO SCALE
OH OVERHEAD
OL OVERLOADS
P POLE
P- PUMP
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PE PNEUMATIC ELECTRIC
PED PEDESTAL
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
PP POWER POLE
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV- POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE
(CONDUIT)
PWR POWER
QUAN QUANTITY
RCPT RECEPTACLE
RECEPT RECEPTACLE
REQD REQUIRED
RGC RIGID GALVANIZED STEEL
CONDUIT
RM ROOM
RSC RIGID STEEL CONDUIT
RTU- ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF- SUPPLY FAN
SHT SHEET
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
S/S STOP/START PUSHBUTTONS
STA STATION
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TCC TEMPERATURE CONTROL
CONTRACTOR
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TL TWIST LOCK
TR TAMPER RESISTANT
TS TAMPER PROOF SWITCH
T-STAT THERMOSTAT
TTC TELEPHONE TERMINAL
CABINET
TV TELEVISION
TVTC TELEVISION TERMINAL
CABINET
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UF UNDER FLOOR
UG UNDERGROUND
UH- UNIT HEATER
UL UNDERWRITERS'
LABORATORIES, INC.
UNO UNLESS NOTED OTHERWISE
UT UNDERGROUND TELEPHONE
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VDT VIDEO DISPLAY TERMINAL
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VL VERIFY LOCATION WITH
OWNER
VOL VOLUME
W WATT
W/ WITH
WG WIRE GUARD
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR RANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Ø PHASE
C CENTER LINE
P PLATEL
L
ELECTRICAL ABBREVIATIONS LIST
1.ALL WALL AND FLOOR PENETRATIONS ARE TO BE SEALED TO MAINTAIN ORIGINAL
RATING.
2.ALL CONDUITS SHALL BE FIELD ROUTED ALONG EXISTING PIPING AND STRUCTURAL
STEEL.
3.CONTRACTORS SHALL VISIT THE PROJECT SITE AND DETERMINE THE EXACT EXTENT
OF THE DEMOLITION WORK REQUIRED BEFORE BIDDING THE PROJECT.
4.REMOVE ALL EXISTING OBSOLETE EXPOSED CONDUIT, WIRE AND UNUSED EQUIPMENT
WHERE WORK IS BEING DONE EXCEPT ITEMS NOTED OTHERWISE.
5.WHERE BUILDING SURFACES ARE DAMAGED BY THE REMOVAL OF OLD WORK,
SURFACES SHALL BE PATCHED TO MATCH ADJACENT.
6.EXISTING WORK WHICH IS PRESENTLY CONCEALED AND WHICH WILL REMAIN
CONCEALED AND DOES NOT INTERFERE WITH ANY NEW WORK OF ANY TRADE NEED
NOT BE REMOVED. HOWEVER, ALL CONDUIT SHALL BE CAPPED BELOW FINISH SURFACE
AND THEN PATCHED TO MATCH, OR AS NOTED.
7.EXISTING OPENINGS, WHICH ARE TO BE REUSED, SHALL BE MODIFIED OR ENLARGED
TO SUIT THE NEW SYSTEMS AS REQUIRED. PROVIDE ALL REQUIRED CUTTING AND
PATCHING.
8.CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING THE EXISTING WALLS TO
MATCH THE ADJACENT SURFACES BEHIND ALL SURFACE MOUNTED EQUIPMENT.
9.CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT AND LOADS PRIOR TO INSTALLING
SERVICE TO EQUIPMENT.
10.DRAWINGS ARE BASED ON EXISTING RECORD DOCUMENT AND CASUAL FIELD
OBSERVATION. REPORT ANY DISCREPANCIES TO ENGINEER FOR CLARIFICATION.
11.CONDUITS AND BOXES:
11.1. 3/4" MINIMUM TRADE SIZE.
11.2. EMT TYPE CONDUIT IS APPROVED.
11.3. NO PVC ALLOWED INSIDE OF BUILDINGS.
11.4. CONDUITS SHALL BE ATTACHED WITH TWO-HOLE STRAPS. SINGLE HOLE STRAPS
ARE NOT PERMITTED.
11.5. NO SET SCREWS ARE ALLOWED.
11.6. TAMPER-PROOF SCREWS REQUIRED FOR EXPOSED CONDUIT AND BOXES
MOUNTED BELOW TEN FEET.
11.7. DRIVE PIN ANCHORS USED ON MASONRY OR CONCRETE WALLS/ CEILINGS.
12.ALL CONDUIT ABOVE 10 FOOT SHALL MEET THE FOLLOWING REQUIRMENTS:
12.1. STRAP DISTANCE: 5 FEET.
12.2. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED- GRC.
12.3. FITTINGS: COMPRESSION.
12.4. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES.
13.ALL CONDUIT BELOW 10 FOOT SHALL MEET THE FOLLOWING REQUIREMENTS:
13.1. STRAP DISTANCE: 3 FEET.
13.2. FASTENERS: 2 HOLE WITH SECURITY SCREWS.
13.3. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED - GRC.
13.4. FITTINGS: COMPRESSION.
13.5. BELL BOXES: FS TYPE.
13.6. NO KNOCKOUTS.
13.7. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES
14.ALL EXPOSED WIRING SHALL BE IN CONDUIT. OPEN LOW VOLTAGE WIRING ABOVE
CEILINGS IS ACCEPTABLE. REFER TO TC DRAWINGS FOR SUPPORT DETAILS.
15.CONDUITS SHALL BE INSTALLED STRAIGHT AND LEVEL AND SHALL BE PARALLEL OR
PERPENDICULAR TO THE BUILDING LINES.
16.CONTRACTOR SHALL VERIFY ALL VOLTAGES BEFORE CONNECTING ANY EQUIPMENT.
17.ALL LOCATIONS WHERE THE WALLS CAN'T BE FISHED SHALL BE SURFACE MOUNTED
CONDUIT FOLLOWING NOTES 11 AND 12 ABOVE.
18.ALL WALLS THAT ARE ACCESSIBLE SHALL BE FISHED AND DEVICE CUT INTO WALL.
19.ALL EXTERIOR CONCEALED CONDUIT UNDERGROUND SHALL BE RNC, TYPE EPC-40-
PVC
20.ANY ELECTRICAL OUTAGE SHALL NOT LAST OVER 2-HOURS. FOR OUTAGES OVER
PORTABLE GENERATORS SHALL BE USED TO REPLACE ANY ELECTRICAL SERVICE
EXCEEDING THIS TIME PERIOD.
GENERAL ELECTRICAL NOTES
OUTLETS
ELECTRICAL SYMBOLS LEGEND
SINGLE RECEPTACLE (120 VOLT)
DUPLEX RECEPTACLE
EMERGENCY RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
FLUSH FLOOR BOX
SURFACE FLOOR BOX
SPECIAL EQUIPMENT RECEPTACLE
TELEPHONE OUTLET
DATA OUTLET
TELEPHONE / DATA OUTLET
POWER POLE
JUNCTION BOX
WALL JUNCTION BOX
PULL (JUNCTION) BOX
UNDERFLOOR JUNCTION BOX
CEILING MOUNTED WIFI
SWITCHES
SINGLE-POLE SWITCH
THREE-WAY SWITCH
FOUR-WAY SWITCH
SWITCH WITH PILOT LIGHT
THERMAL OVERLOAD SWITCH
MANUAL MOTOR SWITCH
KEY SWITCH
TIME SWITCH
DIMMER SWITCH
MECHANICAL
SINGLE PHASE MOTOR
THREE PHASE MOTOR
RESISTANCE HEATER, KW SHOWN
PIPE TRACE HEATER
ELECTRIC UNIT HEATER
ELECTRIC WATER HEATER
NURSE CALL
NURSE CALL CONTROLLER
MASTER STATION
EMERGENCY PULL STATION
EMERGENCY PUSH STATION
CODE BLUE STATION
PENDENT INTERFACE
BED / LIGHT INTERFACE
SINGLE BED STATION
DUAL BED STATION
DOME LIGHT
STAFF REGISTER STATION
STAFF STATION
DUTY STATION
DESIGNATIONS
DEMOLITION NOTE
PLAN NOTE
ADDENDUM NOTE
FIXTURES
LIGHT FIXTURE
STRIP FIXTURE
EMERGENCY LIGHT FIXTURE
IN-GRADE LIGHT FIXTURE
SPOTLIGHT
(number of heads shown)
EXIT SIGN
(face & direction as shown)
WALL MOUNT LIGHT FIXTURE
CEILING LIGHT FIXTURE
TRACK & FIXTURE
STREET TYPE POLE FIXTURE
POLE MOUNTED LIGHT FIXTURE
EXTERIOR WALL MOUNT LIGHT FIXTURE
WALLPACK LIGHT FIXTURE
SPECIAL PURPOSE LIGHT FIXTURE
HIGH BAY LIGHT FIXTURE
EMERGENCY EGRESS LIGHT FIXTURE
(number of heads shown)
DOCK LIGHT FIXTURE
SERVICE AND EQUIPMENT
TRANSIENT VOLTAGE SURGE SUPPRESSION
VARIABLE FREQUENCY DRIVE
TRANSFORMER
DISCONNECT SWITCH (fuse size shown)
MAGNETIC STARTER (BY x/C U.O.N.)
COMB. STARTER (BY x/C U.O.N.)
PANELBOARD, SURFACE MOUNTED
PANELBOARD, FLUSH MOUNTED
WEATHERHEAD
UTILITY METER, AS REQUIRED
CURRENT TRANSFORMERS
GENERATOR, KW SHOWN
TELEPHONE TERMINAL BOARD
GROUND CONNECTION PER N.E.C.
WIREWAY
TRANSFER SWITCH
ENCLOSED CIRCUIT BREAKER
CAPACITOR
CIRCUITRY AND RACEWAYS
CONDUIT INSTALLED (by E.C.)
CONDUIT INSTALLED (by others)
CONDUIT STUB UP
CONDUIT STUB DOWN
HOME RUN (with circuit numbers)
END OF CONDUIT RUN
END OF CONDUIT RUN, CAP AND STAKE
"CONDUIT RUN CONTINUES" INDICATION
FLEXIBLE PIGTAILS/CONNECTIONS
WIREMOLD AS SPECIFIED
PLUGMOLD AS SPECIFIED
BUS DUCT
UNDERFLOOR DUCT
SOUND AND SIGNAL
SPEAKER
WALL MOUNTED SPEAKER
WALL MOUNTED SPEAKER / CLOCK COMBO
SINGLE FACE CLOCK
DUAL FACE CLOCK
VIDEO INPUT
AUDIO / VIDEO INPUT
BELL
VOLUME CONTROL
BUZZER
CHIME
TELEVISION OUTLET
MICROPHONE OUTLET
INTERCOM OUTLET
CAMERA
DOOR CONTACT
MOTION DETECTOR
BEAM DETECTOR
KEY PAD
SECURITY SYSTEM CONTROL PANEL
CCTV CONTROL PANEL
CARD READER
STUDENT STATION
ADMINISTRATION STATION
TEACHER STATION
GLASS BREAK
EXIT ONLY
ELECTRIC STRIKE
CONTROL
THERMOSTAT
HUMIDISTAT
PHOTOCELL (voltage as required)
TIME CLOCK (24 hour U.O.N.)
PUSHBUTTON STATION
(number of buttons indicated)
CONTROL TRANSFORMER
LIGHTING CONTACTOR
IRRIGATION CONTROLLER
(120 volt xxVA connection by x/C)
WALL MOUNT DUAL TECHNOLOGY SENSOR SENSOR
SWITCH WV-PDT-16 SERIES
OCCUPANCY SENSOR / PHOTOCELL SENSOR SWITCH CMR-
PC-ADC SERIES
ULTRASONIC SENSOR - 360° - 2 CIRCUIT SENSOR SWITCH
CMR-PDT-10-2P
ULTRASONIC SENSOR - 360° - 1000 SQ FT SENSOR SWITCH
CMR-PDT-10
ULTRASONIC SENSOR - 360° - 500 SQ FT SENSOR
SWITCH CMR-PDT SERIES
SWITCH STYLE OCCUPANCY SENSOR SENSOR SWITCH
WSD-PDT SERIES
POWER PACK SENSOR SWITCH MP20 SERIES
DIGITAL TIME SWITCH WATT STOPPER TS-400
FIRE ALARM
SMOKE DETECTOR
HEAT DETECTOR
DUCT SMOKE DETECTOR
HORN
HORN & LIGHT
SPEAKER
SPEAKER & LIGHT
PULL STATION
FIRE ALARM CONTROL PANEL
ANNUNCIATOR PANEL
END OF LINE DEVICE
REMOTE INDICATING LIGHT, WALL MTD.
REMOTE INDICATING LIGHT, CLG. MTD.
MAGNETIC DOOR HOLDER
FIREFIGHTER COMMUNICATION JACK
FLOW SWITCH (furnished by FP/C)
TAMPER SWITCH (furnished by FP/C)
VISUAL ONLY UNIT
FIRE CONTROL POWER SUPPLY
MONITOR MODULE
CONTROL MODULE
CARBON DIOXIDE DETECTOR
CARBON MONOXIDE DETECTOR
SMOKE AND CARBON DIOXIDE DETECTOR
J
J
J
J
PP
F
S
P
TO
M
K
T
WH
M
P
E
CB
A
L
B1
B2
SRS
S
DS
NCC
X
X
X
D
S
S
VI
AV
B
V
B
C
M
I
C
DC
M
B
KP
SSCP
CCTV
CR
SS
AS
TS
GB
C
M
FCPS
V
FS
FC
DH
FACP
ANN
F
H
EOL
OS5
OS4
OS3
OS2
OS1
1,3
OR
WM
PM
BD
UFD
T
H
PC
TC
IC
OC
PP
T
TVSS
VFD
T
CT
G
TS
W W
T T
CD
M
2CO
ES
LIGHTING FIXTURE SCHEDULE
TYPE MANUFACTURER CATALOG NO. DESCRIPTION AND COMMENTS BALLAST INFO.
FIXTURE
MOUNTING
HEIGHT
LAMPS
KENALL LIGHTING
LED - 2X4
LA - GRID -
LAEM - GRID -
LED - 1X4 INDUSTRIAL STRIP FIXTURE.
LB
LBEM
KENALL LIGHTING
KENALL LIGHTING
KENALL LIGHTING
LED - 1X4 RECESSED CORRECTIONAL FIXTURE.
LD
LED - 1X1 RECESSED LIGHT FIXTURE.
LDEM
KENALL LIGHTING
KENALL LIGHTING
LE
LED - 1X4 HIGH BAY LIGHT FIXTURE.
LEEM
KENALL LIGHTING
KENALL LIGHTING
LF
LED - ROUND DOWNLIGHT FIXTURE.
LFEM
KENALL LIGHTING
KENALL LIGHTING
LG
LED - EXTERIOR WALL PACK.
LGEM
KENALL LIGHTING
KENALL LIGHTING
LC
LCEM
KENALL LIGHTING
KENALL LIGHTING
LED - EXTERIOR WALL PACK.
LED - ROUND DOWNLIGHT FIXTURE.
LED - 1X4 HIGH BAY LIGHT FIXTURE.
LED - 1X1 RECESSED LIGHT FIXTURE.
LED - 2X4
LED - 1X4 INDUSTRIAL STRIP FIXTURE.
LED - 1X4 RECESSED CORRECTIONAL FIXTURE.
KENALL LIGHTING
LED - 2X2
- GRID -
- GRID -KENALL LIGHTING
LED - 2X2
LH
LHEM
M at ri x
SHEET NUMBER
file no.
funding code contractor order no.
consultant job no.
472/22019.SMD
472/MaintProj sheet description consultant drawn by checked by issue date
JFS
MMG
E-100
22139.00
ELECTRICAL
LEGENDS
PHASE 300 09-09-2022
PHASE 400 12-14-2022
E
SB-3
SB-2
SB-1
HYD. 24
NEW VEHICLE
GATE
NEW PEDESTRIAN
GATE
DEMO EXISTING
SALLY PORT
NEW TRUCK /
CAR ENTRANCE
TO BUILDING 30
NEW PEDESTRIAN
ENTRANCE TO
BUILDING 30
EXISTING
INTERIOR FENCE
ENTRANCE
NEW B FENCE EXISTING A
FENCE
NEW B FENCE
NEW A FENCE
NEW INTERIOR
FENCE ENTRANCE
DE
SIG
N
AN
D
CO
NS
TR
UC
TIO
N
DI
VIS
IO
N
DE
PA
RT
M
EN
T
OF
T
EC
HN
OL
OG
Y, M
AN
AG
EM
EN
T, A
ND
B
UD
GE
T
ST
AT
E
OF
M
IC
HI
GA
N
AD
AM
P . L
AC
H, R A, D
IR
EC
TO
R
ST
AT
E
FA
CI
LI
TI
ES
A
DM
IN
IS
TR
AT
IO
N
REVIEW
DRAWING
NOT FOR
CONSTRUCTION
PLOT DATE: 12/13/2022
M at ri x
CO
NS
UL
TIN
G
EN
GI
NE
ER
S, IN
C
FA
X:
(5
) 4
-2
PH
ON
E:
(5
) 4
-2
LA
NS
IN
G, M
I 4
E
. C
ES
AR
E
. C
HA
VE
Z
AV
E.
W
EB
: w ww
.m at rix ce in c.
co m
SHEET NUMBER
file no.
funding code contractor order no.
consultant job no.
472/22019.SMD
472/MaintProj sheet description consultant drawn by checked by issue date
M
AT
RI
X
PR
OJ
EC
T:
/16
/20
7:
:52 A
M Au tod es k D oc s:/ /D
TM
B
PA
RN
AL
L D
IE
SE
L B
LD
G/
9_
BL
DG
_M
EP
.rv t
JFS
MMG
PA
RN
AL
L
CO
RR
EC
TI
O N
AL
F
AC
IL
IT
Y
N
EW
D
IE
SE
L
M
EC
H
AN
IC
AL
P
RO
GR
AM
E P
AR
N
AL
L
RD
JA
CK
SO
N , M
IC
H
IG
AN
E-200
22139.00
9.
ELECTRICAL - NEW
SITE PLAN -
REVISED FENCING
LAYOUT
PHASE 300 09-09-2022
PHASE 400 12-14-2022
N 0 1 124 8
SCALE: 1" = 40'-0"
NEW ELECTRICAL SITE PLAN
EXISTING ELECTRICAL SYSTEMS & EQUIPMENT TO BE DEMOLISHED
COMPLETELY THROUGHOUT ENTIRETY OF BUILDING. REMOVE ALL
EXISTING ASSOCIATED CONDUIT AND WIRE BACK TO SOURCE.
ELECTRICAL DEMOLITION KEYNOTES
7654321
B
C
7654321
B
C
B
C
B
C
M at ri x
SHEET NUMBER
file no.
funding code contractor order no.
consultant job no.
472/22019.SMD
472/MaintProj sheet description consultant drawn by checked by issue date
JFS
MMG
E-300
22139.00
ELECTRICAL
DEMOLITION PLAN
N 0 1 124 8
SCALE: 1/8" = 1'-0"
ELECTRICAL DEMOLITION PLAN - MAIN LEVELN
0 1 124 8
SCALE: 1/8" = 1'-0"
ELECTRICAL DEMOLITION PLAN - MEZZANINE
OS
3 3
3 3 3 3
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS OS
OSOS
OS
OS
OS
OS OS OS OS
OS OS OS OS
OS OS OS OS
OS OS
OS OS
OS OS
OS OS
OS OS
OS OS
OS
OS
OS
OSOSOSOSOSOSOS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS OS
OS OS
OS OS
OS OS
OS OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
PPPP
PP
PP PP
PP
PP PP
PP
PP
PC
B
C
B
C
LCLC
LC
LCLC
7654321
B
C
TOOL CRIB
105 TRUCK BAYS
COMPRESSOR RM
HEAVY DIESEL LAB
HEAVY DIESEL CLASSROOM
MEZZ ACCESS
CDL CLASSROOM
110MULTIPURPOSE
ELECTRICAL CLOSET
AUTO CLASSROOM
AUTO TOOL CRIB
FURN. CLOS.
WATER SERV. RM.
AUTO SHOP
STAFF OFFICES
CORRIDOR
MAIN ENTRY
CORRIDOR
INMATE TOILETS
STAFF TOILETS
CORRIDOR
7654321
B
C
VEST. / COAT ROOM
211 SF
UNASSIGNED
511 SF
TECH CLOS.
151 SF
LD LD
LE
LE
LE
LA LA
LA LA
LALA
LA
LA LA
LA
LB
LALA
LA LA
LA LA
LALA
LB
LA
LHEM
LH
LH LH LH
LHEM
LHEM
LHEM
LGEM
LGEM
LC
LC
LD LD LD
LA LA
LALA
LA
LA
LA
LA
LA
LC LC
LDLDLDLDLDLDLDLDLD
LD
LC LC
LC LC
LD
LD
LD
LD
LD
LD
LD
LD
LD
LD
LD
LD
LA LA
LA LA
LALA
LALA
LC
LC
LC
LA
LA
LA
LB
LB
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LA
LD
LC
LC
LC
LD
LDLD
LD LD
LDLD
LD LD
LB
LCLC LC
TO LIGHTS IN
MEZZANINE
LD
LD
LF
LF LF
LF LF LF
LFLF
LF LF
LFLFLF
LFLF
LF
XA
XA
XA
XA
XA
XA
XA XA
XA
XA
XA
XA
LHEM
XA
XA XA XA XA XA
XA
XA
XA
XA XA
XA
XA
XA
LHEM
LH
1. PROVIDE AND INSTALL NEW LIGHTING CONTROL DEVICES IN ALL
RENNOVATED SPACES.
GENERAL ELECTRICAL NOTES
M at ri x
SHEET NUMBER
file no.
funding code contractor order no.
consultant job no.
472/22019.SMD
472/MaintProj sheet description consultant drawn by checked by issue date
JFS
MMG
E-400
22139.00
ELECTRICAL
LIGHTING PLAN
N 0 1 124 8
SCALE: 1/8" = 1'-0"
ELECTRICAL LIGHTING PLAN - MEZZANINE N
0 1 124 8
SCALE: 1/8" = 1'-0"
MAIN LEVEL ELECTRICAL LIGHTING PLAN
GFI
WP
48"
48"
48" 48"
GFI
WP
48" 48" 48"
48"
48"
48" 48" 48" 48"
GFI
WP
J 72"
48" 48"
48"
CLNG
J
CLNG
J
CLNG
J
CLNG
J
CLNG
J
GFI
WP
GFI
WP
GFI
WP
TO
7654321
B
C
TOOL CRIB
TRUCK BAYS
COMPRESSOR RM
HEAVY DIESEL LAB
HEAVY DIESEL CLASSROOM
MEZZ ACCESS
CDL CLASSROOM
MULTIPURPOSE
TECH CLOS.
AUTO CLASSROOM
AUTO TOOL CRIB
WATER SERV. RM.
AUTO SHOP
AUTO SHOP
STAFF OFFICES
CORRIDOR
MAIN ENTRY
CORRIDOR
UNASSIGNED
INMATE TOILETS
J.C.
STAFF TOILETS
CORRIDOR
CORRIDOR
F-1
UH-1
SEE MEZZANINE PLAN
FOR CONTINUATION.
FRIDGE
FOOD WARMER
7654321
B
C
ELECTRICAL CLOSET
146 SF
CORRIDOR
231 SF
F-2
F-3
UH-2
VEST. / COAT ROOM
211 SF
SIMULATOR
SIMULATOR
COMMUNICATIONS RACEWAY
FOR TV TO TEACHER
COMPUTER CONNECTION
WALL FAN
COMMUNICATIONS RACEWAY
FOR TV TO TEACHER
COMPUTER CONNECTION
WALL FAN
COMMUNICATIONS RACEWAY
FOR TV TO TEACHER
COMPUTER CONNECTION
WALL FAN
CONCRETE PAD
NEW 500KVA MEDIUM VOLTAGE TRANSFORMER TN-30C
PRIMARY: 12,470V
SECONDARY: 480/277V
NEW UNDERGROUND
ELECTRICAL CONDUIT
AND WIRE
UH-3
F-5
UH-4
MDP
480/277V-3PH, 4W 600A
RP-1
208/120V-3PH, 4W 125A
TN-1
45KVA
LP-2
480/277V-3PH, 4W 200A
RP-4
208/120V-3PH, 4W 200A
TN-4
75KVA
LP-1
480/277V-3PH, 4W 200A
RP-3
208/120V-3PH, 4W 125A
TN-3
45KVA
HOIST
208V-1PH, 2HP
HOIST
208V-1PH, 2HP
HOIST
208V-1PH, 2HP
FURN. CLOS.
20 SF
AC-2
AC-3A
AC-3B
CU-3
WP
DWH-1
COMP-1
CU-4
CU-1
WP
WP
B
C
F-4
B
C
RP-2
208/120V-3PH, 4W 200A
TN-2
75KVA
1. PROVIDE AND INSTALL NEW CONDUIT, WIRE AND OVER CURRENT
PROTECTION FOR FURNACE IN LOCATION SHOWN.
2. PROVIDE AND INSTALL NEW CONDUIT, WIRE AND OVER CURRENT
PROTECTION FOR NEW UNIT HEATER IN LOCATION SHOWN.
3. PROVIDE AND INSTALL NEW CONDUIT, WIRE AND OVER CURRENT
PROTECTION FOR NEW INFRARED HEATER IN LOCATION SHOWN.
4. PROVIDE AND INSTALL NEW POWER DEVICES AND EQUIPMENT BASED
ON PROGRAM REQUIREMNTS.
5. PROVIDE AND INSTALL VANDAL AND TAMPER RESISTANT DEVICE(S) IN
NOTED ROOM.
ELECTRICAL GENERAL NOTES
M at ri x
SHEET NUMBER
file no.
funding code contractor order no.
consultant job no.
472/22019.SMD
472/MaintProj sheet description consultant drawn by checked by issue date
JFS
MMG
E-500
22139.00
ELECTRICAL
POWER PLAN
N 0 1 124 8
SCALE: 1/8" = 1'-0"
MAIN LEVEL ELECTRICAL POWER PLANN
0 1 124 8
SCALE: 1/8" = 1'-0"
ELECTRICAL POWER PLAN - MEZZANINE
GFI
WP
7654321
B
C
7654321
B
C
EF-1
EF-2
EF-3
EF-4
EF-5
M at ri x
SHEET NUMBER
file no.
funding code contractor order no.
consultant job no.
472/22019.SMD
472/MaintProj sheet description consultant drawn by checked by issue date
JFS
MMG
E-501
22139.00
ELECTRICAL
POWER PLAN -
ROOF
N 0 1 124 8
SCALE: 1/8" = 1'-0"
ELECTRICAL POWER PLAN - ROOF
F
F
F
F
F
F
F
F
F
F F
F
F
F F
F F
F
F F
FF F
F
F
F
F F
F
7654321
B
C
7654321
B
C
TOOL CRIB
COMPRESSOR RM
HEAVY DIESEL LAB
HEAVY DIESEL CLASSROOM
MEZZ ACCESS
CDL CLASSROOM
110MULTIPURPOSE
TECH CLOS.
AUTO CLASSROOM
AUTO TOOL CRIB
WATER SERV. RM.
AUTO SHOP
AUTO SHOP
STAFF OFFICES
CORRIDOR
MAIN ENTRY
CORRIDOR
UNASSIGNED
INMATE TOILETS
J.C.
STAFF TOILETS
CORRIDOR
CORRIDOR
SEE MEZZANINE PLAN
FOR CONTINUATION.
ELECTRICAL CLOSET
146 SF
CORRIDOR
231 SF
VEST. / COAT ROOM
211 SF
CONCRETE PAD
NEW 500KVA MEDIUM VOLTAGE TRANSFORMER TN-30C
PRIMARY: 12,470V
SECONDARY: 480/277V
NEW UNDERGROUND
ELECTRICAL CONDUIT
AND WIRE
MDP
480/277V-3PH, 4W 600A
RP-1
208/120V-3PH, 4W 125A
TN-1
45KVA
LP-2
480/277V-3PH, 4W 200A
RP-4
208/120V-3PH, 4W 200A
TN-4
75KVA
LP-1
480/277V-3PH, 4W 200A
RP-3
208/120V-3PH, 4W 125A
TN-3
45KVA
FURN. CLOS.
20 SF
TRUCK BAYS
4096 SF
FACP
B
C
B
C
RP-2
208/120V-3PH, 4W 200A
TN-2
75KVA
1.FIRE ALARM CABLE CAN BE INSTALLED FREE AIR ABOVE CEILINGS.
2.PROVIDE RACEWAY WHERE SURFACE MOUNT DEVICES ARE REQUIRED.
CONDUIT SHALL BE 3/4" MINIMUM PAINTED RED.
3.ALL CABLE SHALL BE INSTALLED PER FIRE ALARM MANUFACTURER'S
SPECIFICATIONS.
4.FIRE ALARM REMOTE POWER SUPPLY SHALL BE MONITORED.
5.PROVIDE SMOKE DETECTOR ABOVE ALL FIRE ALARM PANELS AND
REMOTE POWER SUPPLIES.
6.REFER TO DRAWINGS FOR DEVICE QUANTITIES AND LOCATIONS. BRING
TO THE ENGINEER'S ATTENTION DISCREPANCIES PRIOR TO BIDDING
PROJECT.
7.UPON ALARM OF SMOKE DETECTORS, FIRE ALARM SYSTEM TO
RELEASE DOOR HOLDERS.
8.POWER SUPPLIES IN BOTH FACP AND FCPS SHALL HAVE 25% SPARE
CAPACITY.
9.TRUE PEER TO PEER NETWORK FOR FIRE ALARM SYSTEM.
10. FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR ALL CANDELA
RATINGS OF VISUAL UNITS TO COMPLY WITH NFPA 72. STROBE CANDELA
SETTINGS SHALL BE SET DURING INSTALLATION OF THE DEVICE.
11. REPLACE ALL EXISTING DUCT DETECTORS AS SHOWN ON PRINTS.
ANY DUCT DETECTORS THAT ARE DISCOVERED AND NOT SHOWN SHALL
BE BROUGHT TO THE ENGINEER'S ATTENTION.
12. PROVIDE REMOTE TEST STATIONS FOR EACH DUCT DETECTOR.
13. INSTALLATION METHODS SHALL BE IN ACCORDANCE WITH THE
NATIONAL ELECTRICAL CODE, ARTICLE 760.
14. 120V AC POWER FOR FIRE ALARM SYSTEM ENCLOSURES SHALL NOT
SHARE CONDUIT RACEWAY WITH FIRE ALARM SYSTEM CIRCUITS.
15. FIRE ALARM SYSTEM DEVICES SHALL BE MOUNTED TO ELECTRICAL
BOXES AS REQUIRED AND REFLECTED ON DEVICE INSTALLATION SHEET.
16. STROBE CANDELA SETTINGS SHALL BE SET DURING INSTALLATION OF
THE DEVICE.
17. AREA SMOKE DETECTORS SHALL NOT BE PLACED WITHIN 36-INCHES
OF AIR DISTRIBUTION DIFFUSERS OR RETURN GRILLS.
FIRE ALARM GENERAL NOTES
M at ri x
SHEET NUMBER
file no.
funding code contractor order no.
consultant job no.
472/22019.SMD
472/MaintProj sheet description consultant drawn by checked by issue date
JFS
MMG
E-502
22139.00
ELECTRICAL FIRE
ALARM
N 0 1 124 8
SCALE: 1/8" = 1'-0"
MAIN LEVEL ELECTRICAL POWER PLANN
0 1 124 8
SCALE: 1/8" = 1'-0"
ELECTRICAL POWER PLAN - MEZZANINE
FEED TO TE-13B/C
NOT CONFIRMED
PAD MOUNT SWITCH
SPLICE IN BASEMENT OF BLOCK 10
A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B
A B A B A B A B A B A B
A B A B A B A B A B A B A B A B A B A B
A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B
A B A B A B A B A B A B
A B
12.47kV
208/120V
30kV A
208/120V
150kVA
2.4k V
12.47kV
300kVA
208/120V 208/120V
150kVA
2.4k V
208/120V
150kVA
2.4k V
480V
500kVA 500kVA 500kVA 500kVA 500kVA
500kVA500kVA
500kVA 500kVA
500kVA
75kV A
75kV A
75kV A
75kV A
75kV A
75kVA
75kV A
75kV A
75kV A
75kV A
75kVA 75kVA 75kVA 75kV A
75kV A
75kV A
75kV A
75kV A
75kV A
75kV A
480V 480V 480V 480V 480V 480V480V480V
480V
480V 480V
480V480V480V 480V 480V 480V 480V
480V
480V480V480V480V480V480V
208/120V
208/120V 208/120V208/120V208/120V 208/120V
208/120V 208/120V 208/120V 208/120V 208/120V 208/120V 208/120V 208/120V
225kVA
208/120V208/120V 208/120V 208/120V 208/120V 208/120V 208/120V 208/120V 208/120V
12.47kV12.47kV12.47kV12.47kV12.47kV
12.47kV12.47kV12.47kV 12.47kV 12.47kV
12.47kV 12.47kV12.47kV12.47kV12.47kV12.47kV
12.47kV12.47kV12.47kV12.47kV12.47kV12.47kV12.47kV12.47kV 12.47kV 12.47kV 12.47kV
12.47kV 12.47kV 2.4kV 12.47kV
12.47kV
12.47kV
2.4k V
2.4k V
2.4k V
12.47kV 2.4k V
2.4k V
2.4k V
2.4k V
2.4k V
2.4k V
2.4k V
2.4k V
2.4k V
2.4k V
2.4k V
2.4k V
TN-6C TE-6C TN-19C TN-18C TN-60C TN-30C
TN-7D TE-7D TN-8D TE-8D TN-9D TE-9D TN-10D TE-10D TN-32D TN-31D
TN-16D TE-16DTN-80D-2TE-80DTN-80DTN-91DTE-92DTN-92DTE-79DTN-79DTE-126DTN-126DTN-219DTN-193D-1TN-197DTN-196D
TN-198ETN-57E TE-198E TN-218E TE-218E TN-71E
TN-138E
TE-4BTN-4B TN-5B TE-5B TE-5B2 TN-13B/C TE-13B/C TN-18B TE-18B/C TN-19B TE-19C TE-GH TN-27B TN-28 TN-29B
FAC "C" FAC "D"
BLDG 5BLDG 4
BLDG 13
& 17 BLDG 18 BLDG 19
GUARD
HOUSE BLDG 27 BLDG 28 BLDG 29
A B
A B A B A BA B
BLDG 6
BLDG 19 BLDG 18
BLDG 60 BLDG 30
BLDG 7 BLDG 8 BLDG 9 BLDG 10
BLDG 32 BLDG 31
300kVA 225kVA
112.5kV A
480V
BLDG 215 BLDG 197 BLDG 219
BLDG 126
BLDG 91
(53,200,201)
BLDG
80 & 49
BLDG 80
BLDG 16
BLDG 57
BLDG 198 BLDG 218
BLDG 71 BLDG 74
BLDG 138
225kVA225kVA 112.5kV A
225kVA
225kVA 225kVA 225kVA
225kVA300kVA300kVA150kVA150kVA 150kVA
750kVA 300kVA 300kVA
750kVA
TE-3A
FAC "B" FAC "B"
BLDG 79
BLDG 92
A B
480V
12.47kV
225kVA
TN-74E
2.4KV SWGR-B2
12.47KV SWGR-A1 12.47KV SWGR-B1
208V
A B
75kVA
208/120V
TE-13B/C
BLDG 196
12.47KV SWGR-A1 12.47KV SWGR-B1
12.47kV
E400-1
SCOPE OF WORK
C A T- 6 PA TC H
C A B LE -GREEN
C A T- 6 CA BLE
- GREEN
C O NTAC T
C LOSURE
C A BLES.
PU RPLE I N
C O LO R
DISCONNECT AND REMOVE EXISTING TRANSFORMER TN-30C.
EXISTING MEDIUM VOLTAGE CONDUIT AND WIRE TO REMAIN FOR
INSTALLATION OF NEW TRANSFORMER. DISCONNECT AND REMOVE
ALL CONDUIT AND WIRE FROM TRANSFORMER TN-30C TO BUILDING
30.
ELECTRICAL DEMOLITION KEYNOTES
M at ri x
SHEET NUMBER
file no.
funding code contractor order no.
consultant job no.
472/22019.SMD
472/MaintProj sheet description consultant drawn by checked by issue date
JFS
MMG
E-600
22139.00
ELECTRICAL RISER
DIAGRAM - DEMO
NOT TO SCALEE-600
1 RISER DIAGRAM DEMO
FEED TO TE-13B/C
NOT CONFIRMED
PAD MOUNT SWITCH
SPLICE IN BASEMENT OF BLOCK 10
A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B
A B A B A B A B A B A B
A B A B A B A B A B A B A B A B A B A B
A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B A B
A B A B A B A B A B A B
A B
12.47kV
208/120V
30kV A
208/120V
150kVA
2.4k V
12.47kV
300kVA
208/120V 208/120V
150kVA
2.4k V
208/120V
150kVA
2.4k V
480V
500kVA 500kVA 500kVA 500kVA 500kVA
500kVA500kVA
500kVA 500kVA
500kVA
75kV A
75kV A
75kV A
75kV A
75kV A
75kVA
75kV A
75kV A
75kV A
75kV A
75kVA 75kVA 75kVA 75kV A
75kV A
75kV A
75kV A
75kV A
75kV A
75kV A
480V 480V 480V 480V 480V 480V480V480V
480V
480V 480V
480V480V480V 480V 480V 480V 480V
480V
480V480V480V480V480V480V
208/120V
208/120V 480/277V208/120V208/120V 208/120V
208/120V 208/120V 208/120V 208/120V 208/120V 208/120V 208/120V 208/120V
225kVA
208/120V208/120V 208/120V 208/120V 208/120V 208/120V 208/120V 208/120V 208/120V
12.47kV12.47kV12.47kV12.47kV12.47kV
12.47kV12.47kV12.47kV 12.47kV 12.47kV
12.47kV 12.47kV12.47kV12.47kV12.47kV12.47kV
12.47kV12.47kV12.47kV12.47kV12.47kV12.47kV12.47kV12.47kV 12.47kV 12.47kV 12.47kV
12.47kV 12.47kV 2.4kV 12.47kV
12.47kV
12.47kV
2.4k V
2.4k V
2.4k V
12.47kV 2.4k V
2.4k V
2.4k V
2.4k V
2.4k V
2.4k V
2.4k V
2.4k V
2.4k V
2.4k V
2.4k V
2.4k V
TN-6C TE-6C TN-19C TN-18C TN-60C TN-30C
TN-7D TE-7D TN-8D TE-8D TN-9D TE-9D TN-10D TE-10D TN-32D TN-31D
TN-16D TE-16DTN-80D-2TE-80DTN-80DTN-91DTE-92DTN-92DTE-79DTN-79DTE-126DTN-126DTN-219DTN-193D-1TN-197DTN-196D
TN-198ETN-57E TE-198E TN-218E TE-218E TN-71E
TN-138E
TE-4BTN-4B TN-5B TE-5B TE-5B2 TN-13B/C TE-13B/C TN-18B TE-18B/C TN-19B TE-19C TE-GH TN-27B TN-28 TN-29B
FAC "C" FAC "D"
BLDG 5BLDG 4
BLDG 13
& 17 BLDG 18 BLDG 19
GUARD
HOUSE BLDG 27 BLDG 28 BLDG 29
A B
A B A B A BA B
BLDG 6
BLDG 19 BLDG 18
BLDG 60 BLDG 30
BLDG 7 BLDG 8 BLDG 9 BLDG 10
BLDG 32 BLDG 31
300kVA 225kVA
112.5kV A
480V
BLDG 215 BLDG 197 BLDG 219
BLDG 126
BLDG 91
(53,200,201)
BLDG
80 & 49
BLDG 80
BLDG 16
BLDG 57
BLDG 198 BLDG 218
BLDG 71 BLDG 74
BLDG 138
500kVA225kVA 112.5kV A
225kVA
225kVA 225kVA 225kVA
225kVA300kVA300kVA150kVA150kVA 150kVA
750kVA 300kVA 300kVA
750kVA
TE-3A
FAC "B" FAC "B"
BLDG 79
BLDG 92
A B
480V
12.47kV
225kVA
TN-74E
2.4KV SWGR-B2
12.47KV SWGR-A1 12.47KV SWGR-B1
208V
A B
75kVA
208/120V
TE-13B/C
BLDG 196
12.47KV SWGR-A1 12.47KV SWGR-B1
12.47kV
E400-1
SCOPE OF WORK
C A T- 6 PA TC H
C A B LE -GREEN
C A T- 6 CA BLE
- GREEN
C O NTAC T
C LOSURE
C A BLES.
PU RPLE I N
C O LO R
CONTRACTOR SHALL PROVIDE AND INSTALL NEW 30E FUSE FOR NEW
TRANSFORMER FEEDING NEW SERVICE AT BUILDING 30. CONTRACTOR
SHALL PROVIDE AND INSTALL NEW 500KVA 12,470Y-480/277V
TRANSFORMER. REFER TO SHEET E-500 FOR MORE DETAIL.
ELECTRICAL KEYNOTES
M at ri x
SHEET NUMBER
file no.
funding code contractor order no.
consultant job no.
472/22019.SMD
472/MaintProj sheet description consultant drawn by checked by issue date
JFS
MMG
E-601
22139.00
ELECTRICAL RISER
DIAGRAM - NEW
NOT TO SCALEE-601
1 RISER DIAGRAM NEW
PHASE 300 09-09-2022
PANEL
PANEL PANEL
KVA
T
KVA
T
PANEL PANEL
KVA
T
KVA
T
PANEL PANEL
NEW
MDP
480/277V
3PH, 4W
600A / MCB
NEW
LP-1
480/277V
3PH, 4W
200A / MLO
NEW
LP-2
480/277V
3PH, 4W
200A / MLO
#6
TN1
#6
TN2
NEW
RP-1
208/120V
3PH, 4W
125A / MCB
NEW
RP-2
208/120V
3PH, 4W
200A / MCB
#6
TN3
#6
TN4
NEW
RP-3
208/120V
3PH, 4W
125A / MCB
NEW
RP-4
208/120V
3PH, 4W
200A / MCB
A B A B
75kVA
480/277V208/120V
12.47kV12.47kV
TN-60C TN-30C
FAC "C" FAC "D"
A B A B A BA B
BLDG 60
500kVA
12.47KV SWGR-A1 12.47KV SWGR-B1
TN-9D / TN-10D
TN-9D / TN-10D
TE-10D / TN-32D
TE-10D / TN-32D
TN-18CTN-18C
BUILDING 30
C A T- 6 PA TC H
C A B LE -GREEN
C A T- 6 CA BLE
- GREEN
C O NTAC T
C LOSURE
C A BLES.
PU RPLE I N
C O LO R
M at ri x
SHEET NUMBER
file no.
funding code contractor order no.
consultant job no.
472/22019.SMD
472/MaintProj sheet description consultant drawn by checked by issue date
JFS
MMG
E-602
22139.00
ELECTRICAL RISER
DIAGRAM -
BUILDING 30
NOT TO SCALEE-602
1 RISER DIAGRAM NEW BUILDING 30
File details come from the government source that posted it. Updated .