This is a comprehensive set of electrical and Information Technology (IT) bid documents and design specifications for the Fort Sill Gravesite Expansion and Cemetery FCA Improvements project located in Elgin, Oklahoma, issued by the National Cemetery Administration under the U.S. Department of Veterans Affairs. The project number is 920CM3006, with an issue date of October 12, 2026 (or July 1, 2026 for certain sheets), and the Architect/Engineer of Record is JD Engineering, PC, located in Hamilton, Montana, with Sean Fitzpatrick as the key contact (720.491.7559). The Department of Veterans Affairs project manager and Contracting Officer's Representative (COR) is Homayoun Kazemipour.
The documents contain detailed electrical installation plans, fire alarm system installation plans for multiple buildings (Administration Building, Maintenance Building, and Public Information Building), panel schedules, security system specifications, and comprehensive IT infrastructure requirements. Key electrical work includes irrigation controller installations with conduit routing specifications (1-inch conduits with #8 AWG copper conductors), pull boxes, and underground/aboveground conduit systems complying with NEC, NFPA, and OSHA standards. Fire alarm systems include addressable fire alarm control panels, smoke alarms, pull stations, and audio-visual notification devices. IT infrastructure requires a new telecommunications room with cable trays, network racks, grounding systems, Cat6A cabling, fiber optic connections, access control systems, and various network equipment including UPS systems, patch panels, and PDUs. All work must be performed in coordination with other trades, use UL-approved/listed materials, follow manufacturer specifications, and comply with applicable codes and local utility company requirements. The contractor must provide all necessary materials for complete and operational systems at no additional cost, with specific attention to grounding per Specification 260526 and proper bonding of equipment.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
H
ELECTRICAL SITE PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
56 Louis Prima Drive, Suite B, Covington, LA 70433 720.491.7559; Sean Fitzpatrick
FORT SILL
GRAVESITE EXPANSION AND
CEMETERY FCA IMPROVEMENTS
Elgin, OK
920CM3006
N/A
10/12/2026Revisions: Date: ZTNT
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
Approved: Project Manager/COR Department of Veteran Affairs, NCA POC: Homayoun Kazemipour Email: homayoun.kazemipour@va.gov
GENERAL NOTES
1. ALL ELECTRICAL WORK IS NEW, AND SHALL BE INSTALLED IN ACCORDANCE WITH
THE LATEST EDITION OF THE NEC, NFPA, AND OSHA. THE CONTRACTOR SHALL
PROVIDE AND INSTALL ALL NECESSARY ELECTRICAL EQUIPMENT AND
CONNECTIONS INCLUDING CONTROL WIRING IN CONDUIT SYSTEM TO OTHER
DISCIPLINES' EQUIPMENT AS INDICATED/AS REQUIRED FOR A COMPLETE,
FUNCTIONAL ELECTRICAL SYSTEM.
2. CONDUCTORS SHALL BE COPPER MINIMUM #12 THW OR THWN, INSTALLED IN RIGID
STEEL CONDUITS FOR ABOVEGROUND AND PVC FOR UNDERGROUND RUNS.
PROVIDE 90° ELBOW AND CONDUIT TRANSITION FROM PVC TO RIGID STEEL
CONDUIT (RGS) FOR UNDERGROUND ROUTING BEFORE TURNING UP TO ABOVE
GROUND SURFACE.
3. ALL BRANCH CIRCUITS SHALL CONTAIN WIRING INCLUDING AN INSULATED (GREEN)
GROUNDING CONDUCTOR IN A CONDUIT, EACH SIZED PER NEC. ALL CONDUCTOR
SIZES ARE BASED ON THE USE OF "THW/THWN" INSULATION.
4. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,
ELBOWS, JB'S, WIRE TROUGHS, PULL BOXES, HANDHOLES OR OTHER REQUIRED
ELEMENTS FOR PROPER INSTALLATION OF THE WORK. ALL NECESSARY
MATERIALS NEEDED TO FULFILL THE PROJECT REQUIREMENTS SHALL BE
PROVIDED AT NO ADDITIONAL COST.
5. WORK SHALL BE CARRIED OUT IN COORDINATION WITH OTHER DISCIPLINES.
COORDINATE WITH CIVIL CONTRACT DOCUMENTS IN TERMS OF ROUTING PATHS,
EQUIPMENT COMPATIBILITY AND MOUNTING ARRANGEMENT PRIOR TO
INSTALLATION.
6. THE LOCATIONS OF ALL ELECTRICAL EQUIPMENT AND CONDUIT ROUTING ARE
APPROXIMATE. COORDINATE AND INSTALL THESE ITEMS SO AS TO ELIMINATE
INTERFERENCE WITH PIPING AND ALL OTHER EQUIPMENT. ADJUST THE LOCATION,
MHT's AND PROVIDE APPROPRIATE MOUNTING HARDWARE AS REQUIRED AT NO
ADDITIONAL COST.
7. COMPLY WITH NFPAs, UFAS, OTHER APPLICABLE CODES, AND AUTHORITY HAVING
JURISDICTION OR AS SHOWN ON DRAWINGS FOR MOUNTING HEIGHTS OF ALL
ELECTRICAL EQUIPMENT AND DEVICES. MAINTAIN MINIMUM WORKING
CLEARANCES REQUIRED BY NEC AND LOCAL UTILITY COMPANY.
8. FOLLOW MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLATIONS, UNLESS
INDICATED OR SPECIFIED OTHERWISE. INFORM VA AND OBTAIN WRITTEN
DIRECTION FROM THE CONTRACTING OFFICER REPRESENTATIVE IF CONFLICTS
EXIST BETWEEN MANUFACTURERS REQUIREMENTS AND CONTRACT DOCUMENTS
PRIOR TO THE START OF THE AFFECTED WORK.
9. ALL MATERIALS AND EQUIPMENT SHALL BE HEAVY DUTY, UL APPROVED/LISTED
AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS.
10. PROVIDE ALL GROUNDING AS PER SPECIFICATION 260526.
11. ITEMS OMITTED FROM EITHER THE SPECIFICATIONS OR THE DRAWINGS, BUT ARE
SHOWN OR DESCRIBED IN THE OTHER TRADES, AND ALL ITEMS NECESSARY TO
MAKE THE ELECTRICAL SYSTEM COMPLETE AND OPERATIONAL, SHALL FORM A
PART OF THE WORK.
12. UNDERGROUND FACILITIES AND CABLE LOCATIONS ARE ESTIMATED.
UNDERGROUND LOCATES OF EXISTING UNDERGROUND FACILITIES IS REQUIRED
TO CONFIRM ROUTE.
13. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS
AND A SEPARATE GREEN INSULATED EQUIPMENT GROUND CONDUCTOR TO
ENSURE SAFETY AND COMPLIANCE.
KEYED NOTES
1. EXISTING 208/120V ELECTRICAL PANEL LPP. USE EXISTING SINGLE PHASE 20A
CIRCUIT BREAKER #16 BREAKER POSITION TO PROVIDE 120V SOURCE TO
IRRIGATION CONTROLLER H.
2. INSTALL NEW (2) 1'' CONDUITS ((1) FOR POWER AND (1) SPARE) FROM ELECTRICAL
PANEL LPP TO PULLBOX #1. HORIZONTAL DIRECTIONAL BORE ROAD CROSSING TO
INSTALL CONDUITS. INSTALL SEPARATE (1) #8 AWG CU CONDUCTORS FOR PHASE,
NEUTRAL, AND GROUND CONDUCTORS WITHIN SAME CONDUIT FOR IRRIGATION
CONTROLLER H.
3. INSTALL PULLBOX #1 (PB1) TO FACILITATE ROAD CROSSING AND CONDUIT
DIRECTION CHANGE. INSTALL PULL STRING AND CAP ENDS OF SPARE 1" CONDUIT.
PULLBOX TO BE INSTALLED 6' FROM CURB EDGE TO AVOID FUTURE SIDEWALK.
4. INSTALL NEW (2) 1" CONDUITS ((1) FOR POWER AND (1) SPARE) FROM PULLBOX #1
TO PULLBOX #2. INSTALL SEPARATE (1) #8 AWG CU CONDUCTORS FOR PHASE,
NEUTRAL, AND GROUND CONDUCTORS WITHIN SAME CONDUIT FOR IRRIGATION
CONTROLLER H. PULLBOX TO BE INSTALLED 6' FROM CURB EDGE TO AVOID
FUTURE SIDEWALK.
5. INSTALL PULLBOX #2 (PB2) TO FACILITATE CONDUIT INSTALLATION. INSTALL PULL
STRING AND CAP ENDS OF SPARE 1" CONDUIT. SPARE CONDUIT ENDS HERE.
PULLBOX TO BE INSTALLED 6' FROM CURB EDGE TO AVOID FUTURE SIDEWALK.
6. INSTALL NEW (1) 1'' CONDUIT FROM PULLBOX #2 TO IRRIGATION CONTROLLER H.
INSTALL SEPARATE (1) #8 AWG CU CONDUCTORS FOR PHASE, NEUTRAL, AND
GROUND CONDUCTORS WITHIN CONDUIT. CONDUIT TO BE INSTALLED 6' FROM
CURB EDGE TO AVOID FUTURE SIDEWALK.
7. IRRIGATION CONTROLLER H APPROXIMATE LOCATION. REFER TO "L" SHEETS FOR
INSTALLATION REQUIREMENTS.
N
0 4 8
1 INCH = 4 FEET
SCALE: 1'' = 100'-0''
ELECTRICAL SITE PLANF3
EP103
AMENDMENT 001 10/12/20261
BACKFILL TRENCHES
TO SUB-GRADE
WARNING TAPE
POWER CONDUIT (REFER TO DETAIL
C6), SIZE INDICATED ON SITE PLAN
(TYP), CONDUIT SIZE VARIES.
SAND BED
TRENCH
FINAL GRADE ±3''
12''
GENERAL BACKFILL
12''MINIMUM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
56 Louis Prima Drive, Suite B, Covington, LA 70433 720.491.7559; Sean Fitzpatrick
FORT SILL
GRAVESITE EXPANSION AND
CEMETERY FCA IMPROVEMENTS
Elgin, OK
920CM3006
N/A
10/12/2026Revisions: Date: ZTNT
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
Approved: Project Manager/COR Department of Veteran Affairs, NCA POC: Homayoun Kazemipour Email: homayoun.kazemipour@va.gov
SCALE: NTS
UNDERGROUND CONCRETE PULLBOX-TURF AREA DETAILC1
SCALE: NTS
2-WAY DUCT LINEC6
SCALE: NTS
IRRIGATION CONTROLLER TRENCH AND CONDUIT DETAILSE5
KEYED NOTES
1. DUCT BANK SITS 24'' BELOW THE SURFACE.
2.
GENERAL NOTES
1. ALL ELECTRICAL WORK IS NEW, AND SHALL BE INSTALLED IN ACCORDANCE WITH
THE LATEST EDITION OF THE NEC, NFPA, LOCAL CODES, AND OSHA. THE
CONTRACTOR SHALL PROVIDE AND INSTALL ALL NECESSARY ELECTRICAL
EQUIPMENT AND CONNECTIONS INCLUDING CONTROL WIRING IN CONDUIT SYSTEM
TO OTHER DISCIPLINES' EQUIPMENT AS INDICATED/AS REQUIRED FOR A
COMPLETE, FUNCTIONAL ELECTRICAL SYSTEM.
2. CONDUCTORS SHALL BE COPPER MINIMUM #12 THW OR THWN, INSTALLED IN RIGID
STEEL CONDUITS FOR ABOVEGROUND AND PVC FOR UNDERGROUND RUNS.
PROVIDE 90° ELBOW AND CONDUIT TRANSITION FROM PVC TO RIGID STEEL
CONDUIT (RGS) FOR UNDERGROUND ROUTING BEFORE TURNING UP TO ABOVE
GROUND SURFACE.
3. ALL BRANCH CIRCUITS SHALL CONTAIN WIRING INCLUDING AN INSULATED (GREEN)
GROUNDING CONDUCTOR IN A CONDUIT, EACH SIZED PER NEC. ALL CONDUCTOR
SIZES ARE BASED ON THE USE OF "THW/THWN" INSULATION.
4. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,
ELBOWS, JB'S, WIRE TROUGHS, PULL BOXES, HANDHOLES OR OTHER REQUIRED
ELEMENTS FOR PROPER INSTALLATION OF THE WORK. ALL NECESSARY
MATERIALS NEEDED TO FULFILL THE PROJECT REQUIREMENTS SHALL BE
PROVIDED AT NO ADDITIONAL COST.
5. WORK SHALL BE CARRIED OUT IN COORDINATION WITH OTHER DISCIPLINES.
COORDINATE WITH CIVIL CONTRACT DOCUMENTS IN TERMS OF ROUTING PATHS,
EQUIPMENT COMPATIBILITY AND MOUNTING ARRANGEMENT PRIOR TO
INSTALLATION.
6. THE LOCATIONS OF ALL ELECTRICAL EQUIPMENT AND CONDUIT ROUTING ARE
APPROXIMATE. COORDINATE AND INSTALL THESE ITEMS SO AS TO ELIMINATE
INTERFERENCE WITH PIPING AND ALL OTHER EQUIPMENT. ADJUST THE LOCATION,
MHT's AND PROVIDE APPROPRIATE MOUNTING HARDWARE AS REQUIRED AT NO
ADDITIONAL COST.
7. COMPLY WITH NFPAs, UFAS, OTHER APPLICABLE CODES, AND AUTHORITY HAVING
JURISDICTION OR AS SHOWN ON DRAWINGS FOR MOUNTING HEIGHTS OF ALL
ELECTRICAL EQUIPMENT AND DEVICES. MAINTAIN MINIMUM WORKING
CLEARANCES REQUIRED BY NEC AND LOCAL UTILITY COMPANY.
8. FOLLOW MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLATIONS, UNLESS
INDICATED OR SPECIFIED OTHERWISE. INFORM VA AND OBTAIN WRITTEN
DIRECTION FROM THE CONTRACTING OFFICER REPRESENTATIVE IF CONFLICTS
EXIST BETWEEN MANUFACTURERS REQUIREMENTS AND CONTRACT DOCUMENTS
PRIOR TO THE START OF THE AFFECTED WORK.
9. ALL MATERIALS AND EQUIPMENT SHALL BE HEAVY DUTY, UL APPROVED/LISTED
AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS.
10. PROVIDE ALL GROUNDING AS PER SPECIFICATION 260526.
11. ITEMS OMITTED FROM EITHER THE SPECIFICATIONS OR THE DRAWINGS, BUT ARE
SHOWN OR DESCRIBED IN THE OTHER TRADES, AND ALL ITEMS NECESSARY TO
MAKE THE ELECTRICAL SYSTEM COMPLETE AND OPERATIONAL, SHALL FORM A
PART OF THE WORK.
12. MAINTAIN 10' SEPARATION FROM EACH DRIVER GROUND ROD.
13. 20A CIRCUITS ARE TO CONSIST OF (1) #12 AWG CU CONDUCTOR AND (1) #12 AWG
CU NEUTRAL AND (1) #12 CU GROUND PER CONDUIT. NO MORE THAN THREE
CIRCUITS IN A SINGLE CONDUIT.
14. 30A CIRCUITS ARE TO CONSIST OF (1) #10 AWG CU CONDUCTOR AND (1) #10
AWG CU NEUTRAL AND (1) #12 CU GROUND PER CONDUIT. NO MORE THAN
THREE CIRCUITS IN A SINGLE CONDUIT.
EP601
IRRIGATION CONTROLLER
ELECTRICAL INSTALLATION PLAN
AMENDMENT 001 10/12/20261
225A RATED MAINLUG PANELBOARD
SQUARD D, NQOD, 42 POSITION
208/120V, 3 PHASE
4 WIRE, SURFACE MOUNTED
A
PANEL LPA
FUSEBOX 1
RECPT. HONOR GUARD
RECPT. FOREMAN OFFICERECPT. HONOR GUARD
CU-01
NEW TOTAL
RECPT. VESTIBULE RECPT. FOREMAN OFFICE
GFCI T-SIDEEWC
ICE MACHINE HEATER
HEATERHEATER
HEATER UNDERCOUNTER
RECPT. COPIEROUTSIDE RECPT.
EMERGENCY LIGHTS/ MECH. ROOM
CARETAKER OFFICE
WATER HEATER
WATER HEATER
WATER HEATER
IT RACK (PSU)
SPARE
HW HEATER
LOAD SERVED
TOTAL NEW CONNECTED AMPS PER PHASE
LOAD SERVEDB C A B C
7.1
7.1
12.0
31.1 31.1 24.0
A: 31.1 B: 32.6 C: 24.0
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
PHASE
0.0
A
41 42
PANEL LPA
FUSEBOX 2
HONOR GUARD LIGHTS
BATH LIGHTS
NEW TOTAL
LOAD SERVED
TOTAL NEW CONNECTED AMPS PER PHASE
20 20
LOAD SERVEDB C A B C
A: 0.0 B: 16.0 C: 0.0
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
PHASE
RECPT MULTI PURPOSE ROOM
100A RATED EXTERIOR PANEL
100A MAIN BREAKER, 36 POSITION
208/120V, 3 PHASE
4 WIRE, SURFACE MOUNTED
A
PANEL LPP
COMMITTAL SHELTER NO LABEL
NEW TOTAL
UNIT HEATER
RECPT. ELECTRIC ROOM
IRR CENTRAL NORTH PANEL
SPARELIGHTS BATHROOM
TIME CLOCK OUTDOOR LIGHTS
SECURITY CAMERALIGHTING ELECTRIC ROOM
WATER COOLER
WATER HEATER
IRR CENTRAL, SOUTH PANEL, PIC
RECPT. MEN BATH, STORAGE
IRR, SEC 2 & 3
LIGHTS OFFICE IRRIGATION CONTROLLER H
MAIN
LOAD SERVED
TOTAL NEW CONNECTED AMPS PER PHASE
20 20
LOAD SERVEDB C A B C
3.0
A: 0.0 B: 0.0 C: 3.0
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
PHASE
0.0 0.0
RECPT. OFFICE
EXHAUST FAN
GFI BATHROOMS
QUAD RECPT. ELECTRIC RM
0.00.0 0.0
225A RATED MAINLUG PANELBOARD
SQUARD D, NQOD, 42 POSITION
208/120V, 3 PHASE
4 WIRE, SURFACE MOUNTED
RECPT MULTI PURPOSE ROOM
RECPT DIRECTORS OFFICE
RECPT DIRECTORS OFFICE
RECPT
RECPT
RECPT FRONT OFFICE
RECPT FRONT OFFICE
RECPT FRONT OFFICE
RECPT FRONT OFFICE
RECPT FRONT OFFICE
RECPT FRONT OFFICE
RECPT
RECPT
RECPT
RECPT
RECPT
RECPT
RECPT MAIN OFFICE
TIME CLOCK
BREAK ROOM LIGHTS
OPERATIONAL LIGHTS
LOBBY LIGHTS
CONFERENCE ROOM LIGHTS
DIRECTOR OFFICE LIGHTS
REFRIGERATOR
RECPT BREAKROOM GFCI
RECPT BREAKROOM GFCI
RECPT BREAKROOM
RECPT BREAKROOM
RECPT BREAKROOM
HALL LIGHTS
RECPT MENS ROOM GFCI
RECPT BREAKROOM
FIRE ALARM PANEL
SECURITY PANEL
RECPT ELECTRICAL ROOM
RECPT MAINT. OFFICE
RECPT TR ROOM16.0
EXTERIOR RECEPTACLE
BLANK
SPARE
12.0
SPARE
1.5 0.0
OUTSIDE GFI
60 35
60 35
60 35
3.0
RECEPTACLE OUTDOORE
1.5
12.0
12.0
12.0
12.0
IT RACK (PSU)
PANEL SCHEDULE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
56 Louis Prima Drive, Suite B, Covington, LA 70433 720.491.7559; Sean Fitzpatrick
FORT SILL
GRAVESITE EXPANSION AND
CEMETERY FCA IMPROVEMENTS
Elgin, OK
920CM3006
N/A
07/01/2026Revisions: Date: ZTNT
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
Approved: Project Manager/COR Department of Veteran Affairs, NCA POC: Homayoun Kazemipour Email: homayoun.kazemipour@va.gov
GENERAL NOTES
1. ALL ELECTRICAL WORK IS NEW, AND SHALL BE INSTALLED IN ACCORDANCE WITH
THE LATEST EDITION OF THE NEC, NFPA, AND OSHA. THE CONTRACTOR SHALL
PROVIDE AND INSTALL ALL NECESSARY ELECTRICAL EQUIPMENT AND
CONNECTIONS INCLUDING CONTROL WIRING IN CONDUIT SYSTEM TO OTHER
DISCIPLINES' EQUIPMENT AS INDICATED/AS REQUIRED FOR A COMPLETE,
FUNCTIONAL ELECTRICAL SYSTEM.
2. CONDUCTORS SHALL BE COPPER MINIMUM #12 THW OR THWN, INSTALLED IN RIGID
STEEL CONDUITS FOR ABOVEGROUND AND PVC FOR UNDERGROUND RUNS.
PROVIDE 90° ELBOW AND CONDUIT TRANSITION FROM PVC TO RIGID STEEL
CONDUIT (RGS) FOR UNDERGROUND ROUTING BEFORE TURNING UP TO ABOVE
GROUND SURFACE.
3. ALL BRANCH CIRCUITS SHALL CONTAIN WIRING INCLUDING AN INSULATED (GREEN)
GROUNDING CONDUCTOR IN A CONDUIT, EACH SIZED PER NEC. ALL CONDUCTOR
SIZES ARE BASED ON THE USE OF "THW/THWN" INSULATION.
4. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,
ELBOWS, JB'S, WIRE TROUGHS, PULL BOXES, HANDHOLES OR OTHER REQUIRED
ELEMENTS FOR PROPER INSTALLATION OF THE WORK. ALL NECESSARY
MATERIALS NEEDED TO FULFILL THE PROJECT REQUIREMENTS SHALL BE
PROVIDED AT NO ADDITIONAL COST.
5. WORK SHALL BE CARRIED OUT IN COORDINATION WITH OTHER DISCIPLINES.
COORDINATE WITH CIVIL CONTRACT DOCUMENTS IN TERMS OF ROUTING PATHS,
EQUIPMENT COMPATIBILITY AND MOUNTING ARRANGEMENT PRIOR TO
INSTALLATION.
6. THE LOCATIONS OF ALL ELECTRICAL EQUIPMENT AND CONDUIT ROUTING ARE
APPROXIMATE. COORDINATE AND INSTALL THESE ITEMS SO AS TO ELIMINATE
INTERFERENCE WITH PIPING AND ALL OTHER EQUIPMENT. ADJUST THE LOCATION,
MHT's AND PROVIDE APPROPRIATE MOUNTING HARDWARE AS REQUIRED AT NO
ADDITIONAL COST.
7. COMPLY WITH NFPAs, UFAS, OTHER APPLICABLE CODES, AND AUTHORITY HAVING
JURISDICTION OR AS SHOWN ON DRAWINGS FOR MOUNTING HEIGHTS OF ALL
ELECTRICAL EQUIPMENT AND DEVICES. MAINTAIN MINIMUM WORKING
CLEARANCES REQUIRED BY NEC AND LOCAL UTILITY COMPANY.
8. FOLLOW MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLATIONS, UNLESS
INDICATED OR SPECIFIED OTHERWISE. INFORM VA AND OBTAIN WRITTEN
DIRECTION FROM THE CONTRACTING OFFICER REPRESENTATIVE IF CONFLICTS
EXIST BETWEEN MANUFACTURERS REQUIREMENTS AND CONTRACT DOCUMENTS
PRIOR TO THE START OF THE AFFECTED WORK.
9. ALL MATERIALS AND EQUIPMENT SHALL BE HEAVY DUTY, UL APPROVED/LISTED
AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS.
10. PROVIDE ALL GROUNDING AS PER SPECIFICATION 260526.
11. ITEMS OMITTED FROM EITHER THE SPECIFICATIONS OR THE DRAWINGS, BUT ARE
SHOWN OR DESCRIBED IN THE OTHER TRADES, AND ALL ITEMS NECESSARY TO
MAKE THE ELECTRICAL SYSTEM COMPLETE AND OPERATIONAL, SHALL FORM A
PART OF THE WORK.
12. UNDERGROUND FACILITIES AND CABLE LOCATIONS ARE ESTIMATED.
UNDERGROUND LOCATES OF EXISTING UNDERGROUND FACILITIES IS REQUIRED
TO CONFIRM ROUTE.
SCALE: NTS
ADMIN BLDG PANEL LPA - FUSEBOX 1 SCHEDULEC1
EP60
SCALE: NTS
ADMIN BLDG PANEL LPA - FUSEBOX 2 SCHEDULEC5
SCALE: NTS
P.I.C. BUILDING PANEL LPP SCHEDULEF1
KEYED NOTES
1. NO NEW CIRCUITS ARE BEING ADDED, FACP CIRCUIT NUMBER COULD NOT BE
DETERMINED BASED OF PANEL SCHEDULE. CONTRACTOR TO CONFIRM CIRCUIT
NUMBER FOR FACP AND REWIRE TO NEW FACP.
MULTI-PURPOSE RM
O
PER
ATIO
N
AL C
EN
TER
OFF. STOR.
H.A.C.
LOBBY
VESTIBU
LE
VESTIBULE
M
EN
'S LO
C
KER
R
O O
M
W O
M
EN
'S LO
C
KER
R
O O
M
BOOT WASH
VESTIBULE
MAINT. OFF.
MECHANICAL
CORRIDOR
FOREMAN
HONOR GUARD
ELEC. RM.
RESTROOM
LUNCHROOM
DIRECTOR
RESTROOM
GENERAL OFFICE
ADMINISTRATION BLDG
FIRE ALARM INSTALLATION PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
56 Louis Prima Drive, Suite B, Covington, LA 70433 720.491.7559; Sean Fitzpatrick
FORT SILL
GRAVESITE EXPANSION AND
CEMETERY FCA IMPROVEMENTS
Elgin, OK
920CM3006
N/A
07/01/2026Revisions: Date: ZTNT
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
Approved: Project Manager/COR Department of Veteran Affairs, NCA POC: Homayoun Kazemipour Email: homayoun.kazemipour@va.gov
GENERAL NOTES
1. ALL ELECTRICAL WORK IS NEW, AND SHALL BE INSTALLED IN ACCORDANCE WITH
THE LATEST EDITION OF THE NEC, NFPA, AND OSHA. THE CONTRACTOR SHALL
PROVIDE AND INSTALL ALL NECESSARY ELECTRICAL EQUIPMENT AND
CONNECTIONS INCLUDING CONTROL WIRING IN CONDUIT SYSTEM TO OTHER
DISCIPLINES' EQUIPMENT AS INDICATED/AS REQUIRED FOR A COMPLETE,
FUNCTIONAL ELECTRICAL SYSTEM.
2. CONDUCTORS SHALL BE COPPER MINIMUM #12 THW OR THWN, INSTALLED IN RIGID
STEEL CONDUITS FOR ABOVEGROUND AND PVC FOR UNDERGROUND RUNS.
PROVIDE 90° ELBOW AND CONDUIT TRANSITION FROM PVC TO RIGID STEEL
CONDUIT (RGS) FOR UNDERGROUND ROUTING BEFORE TURNING UP TO ABOVE
GROUND SURFACE.
3. ALL BRANCH CIRCUITS SHALL CONTAIN WIRING INCLUDING AN INSULATED (GREEN)
GROUNDING CONDUCTOR IN A CONDUIT, EACH SIZED PER NEC. ALL CONDUCTOR
SIZES ARE BASED ON THE USE OF "THW/THWN" INSULATION.
4. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,
ELBOWS, JB'S, WIRE TROUGHS, PULL BOXES, HANDHOLES OR OTHER REQUIRED
ELEMENTS FOR PROPER INSTALLATION OF THE WORK. ALL NECESSARY
MATERIALS NEEDED TO FULFILL THE PROJECT REQUIREMENTS SHALL BE
PROVIDED AT NO ADDITIONAL COST.
5. WORK SHALL BE CARRIED OUT IN COORDINATION WITH OTHER DISCIPLINES.
COORDINATE WITH CIVIL CONTRACT DOCUMENTS IN TERMS OF ROUTING PATHS,
EQUIPMENT COMPATIBILITY AND MOUNTING ARRANGEMENT PRIOR TO
INSTALLATION.
6. THE LOCATIONS OF ALL ELECTRICAL EQUIPMENT AND CONDUIT ROUTING ARE
APPROXIMATE. COORDINATE AND INSTALL THESE ITEMS SO AS TO ELIMINATE
INTERFERENCE WITH PIPING AND ALL OTHER EQUIPMENT. ADJUST THE LOCATION,
MHT's AND PROVIDE APPROPRIATE MOUNTING HARDWARE AS REQUIRED AT NO
ADDITIONAL COST.
7. COMPLY WITH NFPAs, UFAS, OTHER APPLICABLE CODES, AND AUTHORITY HAVING
JURISDICTION OR AS SHOWN ON DRAWINGS FOR MOUNTING HEIGHTS OF ALL
ELECTRICAL EQUIPMENT AND DEVICES. MAINTAIN MINIMUM WORKING
CLEARANCES REQUIRED BY NEC AND LOCAL UTILITY COMPANY.
8. FOLLOW MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLATIONS, UNLESS
INDICATED OR SPECIFIED OTHERWISE. INFORM VA AND OBTAIN WRITTEN
DIRECTION FROM THE CONTRACTING OFFICER REPRESENTATIVE IF CONFLICTS
EXIST BETWEEN MANUFACTURERS REQUIREMENTS AND CONTRACT DOCUMENTS
PRIOR TO THE START OF THE AFFECTED WORK.
9. ALL MATERIALS AND EQUIPMENT SHALL BE HEAVY DUTY, UL APPROVED/LISTED
AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS.
10. PROVIDE ALL GROUNDING AS PER SPECIFICATION 260526.
11. ITEMS OMITTED FROM EITHER THE SPECIFICATIONS OR THE DRAWINGS, BUT ARE
SHOWN OR DESCRIBED IN THE OTHER TRADES, AND ALL ITEMS NECESSARY TO
MAKE THE ELECTRICAL SYSTEM COMPLETE AND OPERATIONAL, SHALL FORM A
PART OF THE WORK.
12. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS.
EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED
EQUIPMENT GROUNDING CONDUCTOR.
13. UNDERGROUND FACILITIES AND CABLE LOCATIONS ARE ESTIMATED.
UNDERGROUND LOCATES OF EXISTING UNDERGROUND FACILITIES IS REQUIRED
TO CONFIRM ROUTE.
14. SMOKE ALARMS MUST BE INSTALLED IN LOCATIONS THAT DO NOT OBSTRUCT OR
INTERFERE WITH THE OPERATION OR PLACEMENT OF ANY EQUIPMENT.
15. REUSE EXISTING CONDUIT WITH FIRE ALARM WIRING FOR INTERCONNECTION OF
AUDIO VISUAL ALARMS TO ADDRESSABLE FIRE ALARM CONTROL PANEL.
16. REUSE EXISTING CONDUIT WITH FIRE ALARM WIRING FOR INTERCONNECTION OF
PULL STATION TO THE ADDRESSABLE FIRE ALARM CONTROL PANEL.
N
0 8 16
1 INCH = 8 FEET
SCALE: 1'' = 8'-0''
ADMIINISTRATION BUILDING FIRE ALARM INSTALLATION PLANE3
FIRE DETECTION AND ALARM SCHEDULE
SYMBOLS ITEM DESCRIPTION MANUFACTURER CATALOG
NUMBER
FIRE/SMOKE ALARM SIMPLEX 4098-9601
PULLSTATION SIMPLEX 2099-975
FIRE ALARM ADDRESSABLE SYSTEM SIMPLEX 4010-6401
AUDIO AND VISUAL NOTIFICATION
NODE SIMPLEX S59AV-0001
FIRE ALARM HEAT DETECTOR SIMPLEX 4098-9734
A
B
C
D
E
A
A A
E-101
A
A
A
A
A
A
A
A
A
E
D
B
E
E
D
D
B
D
D
D
E D
E
B
D
D
D D
D
E
D
B
D
B
D
E
D
B
D
D
E
D
D
D
A
A
OUTSIDE ROOM
STORAGE
FLAMMABLE
STORAGE
HEAVY & ROUTINE
MAINTENANCE BAYS
PARTS AND TOOLS
ROOM
MAINTENANCE BLDG
FIRE ALARM INSTALLATION PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
56 Louis Prima Drive, Suite B, Covington, LA 70433 720.491.7559; Sean Fitzpatrick
FORT SILL
GRAVESITE EXPANSION AND
CEMETERY FCA IMPROVEMENTS
Elgin, OK
920CM3006
N/A
07/01/2026Revisions: Date: ZTNT
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
Approved: Project Manager/COR Department of Veteran Affairs, NCA POC: Homayoun Kazemipour Email: homayoun.kazemipour@va.gov
0 4 8
1 INCH = 4 FEET
N
SCALE: 1'' = 4'0''
MAINTENANCE BUILDING FIRE ALARM INSTALLATION PLANE3
D
E-102
FIRE DETECTION AND ALARM SCHEDULE
SYMBOLS ITEM DESCRIPTION MANUFACTURER CATALOG
NUMBER
FIRE/SMOKE ALARM SIMPLEX 4098-9601
PULLSTATION SIMPLEX 2099-975
FIRE ALARM ADDRESSABLE SYSTEM SIMPLEX 4010-6401
AUDIO AND VISUAL NOTIFICATION
NODE SIMPLEX S59AV-0001
FIRE ALARM HEAT DETECTOR SIMPLEX 4098-9734
A
B
C
D
E
B
A
A
A
A A
A
B
B B
D
D D
D
D
D D
D
D
GENERAL NOTES
1. ALL ELECTRICAL WORK IS NEW, AND SHALL BE INSTALLED IN ACCORDANCE WITH
THE LATEST EDITION OF THE NEC, NFPA, AND OSHA. THE CONTRACTOR SHALL
PROVIDE AND INSTALL ALL NECESSARY ELECTRICAL EQUIPMENT AND
CONNECTIONS INCLUDING CONTROL WIRING IN CONDUIT SYSTEM TO OTHER
DISCIPLINES' EQUIPMENT AS INDICATED/AS REQUIRED FOR A COMPLETE,
FUNCTIONAL ELECTRICAL SYSTEM.
2. CONDUCTORS SHALL BE COPPER MINIMUM #12 THW OR THWN, INSTALLED IN RIGID
STEEL CONDUITS FOR ABOVEGROUND AND PVC FOR UNDERGROUND RUNS.
PROVIDE 90° ELBOW AND CONDUIT TRANSITION FROM PVC TO RIGID STEEL
CONDUIT (RGS) FOR UNDERGROUND ROUTING BEFORE TURNING UP TO ABOVE
GROUND SURFACE.
3. ALL BRANCH CIRCUITS SHALL CONTAIN WIRING INCLUDING AN INSULATED (GREEN)
GROUNDING CONDUCTOR IN A CONDUIT, EACH SIZED PER NEC. ALL CONDUCTOR
SIZES ARE BASED ON THE USE OF "THW/THWN" INSULATION.
4. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,
ELBOWS, JB'S, WIRE TROUGHS, PULL BOXES, HANDHOLES OR OTHER REQUIRED
ELEMENTS FOR PROPER INSTALLATION OF THE WORK. ALL NECESSARY
MATERIALS NEEDED TO FULFILL THE PROJECT REQUIREMENTS SHALL BE
PROVIDED AT NO ADDITIONAL COST.
5. WORK SHALL BE CARRIED OUT IN COORDINATION WITH OTHER DISCIPLINES.
COORDINATE WITH CIVIL CONTRACT DOCUMENTS IN TERMS OF ROUTING PATHS,
EQUIPMENT COMPATIBILITY AND MOUNTING ARRANGEMENT PRIOR TO
INSTALLATION.
6. THE LOCATIONS OF ALL ELECTRICAL EQUIPMENT AND CONDUIT ROUTING ARE
APPROXIMATE. COORDINATE AND INSTALL THESE ITEMS SO AS TO ELIMINATE
INTERFERENCE WITH PIPING AND ALL OTHER EQUIPMENT. ADJUST THE LOCATION,
MHT's AND PROVIDE APPROPRIATE MOUNTING HARDWARE AS REQUIRED AT NO
ADDITIONAL COST.
7. COMPLY WITH NFPAs, UFAS, OTHER APPLICABLE CODES, AND AUTHORITY HAVING
JURISDICTION OR AS SHOWN ON DRAWINGS FOR MOUNTING HEIGHTS OF ALL
ELECTRICAL EQUIPMENT AND DEVICES. MAINTAIN MINIMUM WORKING
CLEARANCES REQUIRED BY NEC AND LOCAL UTILITY COMPANY.
8. FOLLOW MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLATIONS, UNLESS
INDICATED OR SPECIFIED OTHERWISE. INFORM VA AND OBTAIN WRITTEN
DIRECTION FROM THE CONTRACTING OFFICER REPRESENTATIVE IF CONFLICTS
EXIST BETWEEN MANUFACTURERS REQUIREMENTS AND CONTRACT DOCUMENTS
PRIOR TO THE START OF THE AFFECTED WORK.
9. ALL MATERIALS AND EQUIPMENT SHALL BE HEAVY DUTY, UL APPROVED/LISTED
AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS.
10. PROVIDE ALL GROUNDING AS PER SPECIFICATION 260526.
11. ITEMS OMITTED FROM EITHER THE SPECIFICATIONS OR THE DRAWINGS, BUT ARE
SHOWN OR DESCRIBED IN THE OTHER TRADES, AND ALL ITEMS NECESSARY TO
MAKE THE ELECTRICAL SYSTEM COMPLETE AND OPERATIONAL, SHALL FORM A
PART OF THE WORK.
12. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS.
EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED
EQUIPMENT GROUNDING CONDUCTOR.
13. UNDERGROUND FACILITIES AND CABLE LOCATIONS ARE ESTIMATED.
UNDERGROUND LOCATES OF EXISTING UNDERGROUND FACILITIES IS REQUIRED
TO CONFIRM ROUTE.
14. SMOKE ALARMS MUST BE INSTALLED IN LOCATIONS THAT DO NOT OBSTRUCT OR
INTERFERE WITH THE OPERATION OR PLACEMENT OF ANY EQUIPMENT.
15. REUSE EXISTING CONDUIT WITH FIRE ALARM WIRING FOR INTERCONNECTION OF
AUDIO VISUAL ALARMS TO ADDRESSABLE FIRE ALARM CONTROL PANEL.
16. REUSE EXISTING CONDUIT WITH FIRE ALARM WIRING FOR INTERCONNECTION OF
PULL STATION TO THE ADDRESSABLE FIRE ALARM CONTROL PANEL.
PUBLIC INFORMATION BLDG (PIC)
FIRE ALARM INSTALLATION PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
56 Louis Prima Drive, Suite B, Covington, LA 70433 720.491.7559; Sean Fitzpatrick
FORT SILL
GRAVESITE EXPANSION AND
CEMETERY FCA IMPROVEMENTS
Elgin, OK
920CM3006
N/A
07/01/2026Revisions: Date: ZTNT
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
Approved: Project Manager/COR Department of Veteran Affairs, NCA POC: Homayoun Kazemipour Email: homayoun.kazemipour@va.gov
N
0 8 16
1 INCH = 8 FEET
SCALE: 1'' = 8'-0''
PUBLIC INFORMATION BUILDING (PIC) FIRE ALARM INSTALLATION PLANE3
B
E-103
FIRE DETECTION AND ALARM SCHEDULE
SYMBOLS ITEM DESCRIPTION MANUFACTURER CATALOG
NUMBER
FIRE/SMOKE ALARM SIMPLEX 4098-9601
PULLSTATION SIMPLEX 2099-975
FIRE ALARM ADDRESSABLE SYSTEM SIMPLEX 4010-6401
AUDIO AND VISUAL NOTIFICATION
NODE SIMPLEX S59AV-0001
FIRE ALARM HEAT DETECTOR SIMPLEX 4098-9734
A
B
C
D
E
D
D
D
D
D
D
B
B
BD
A
E
E
B
A
GENERAL NOTES
1. ALL ELECTRICAL WORK IS NEW, AND SHALL BE INSTALLED IN ACCORDANCE WITH
THE LATEST EDITION OF THE NEC, NFPA, AND OSHA. THE CONTRACTOR SHALL
PROVIDE AND INSTALL ALL NECESSARY ELECTRICAL EQUIPMENT AND
CONNECTIONS INCLUDING CONTROL WIRING IN CONDUIT SYSTEM TO OTHER
DISCIPLINES' EQUIPMENT AS INDICATED/AS REQUIRED FOR A COMPLETE,
FUNCTIONAL ELECTRICAL SYSTEM.
2. CONDUCTORS SHALL BE COPPER MINIMUM #12 THW OR THWN, INSTALLED IN RIGID
STEEL CONDUITS FOR ABOVEGROUND AND PVC FOR UNDERGROUND RUNS.
PROVIDE 90° ELBOW AND CONDUIT TRANSITION FROM PVC TO RIGID STEEL
CONDUIT (RGS) FOR UNDERGROUND ROUTING BEFORE TURNING UP TO ABOVE
GROUND SURFACE.
3. ALL BRANCH CIRCUITS SHALL CONTAIN WIRING INCLUDING AN INSULATED (GREEN)
GROUNDING CONDUCTOR IN A CONDUIT, EACH SIZED PER NEC. ALL CONDUCTOR
SIZES ARE BASED ON THE USE OF "THW/THWN" INSULATION.
4. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,
ELBOWS, JB'S, WIRE TROUGHS, PULL BOXES, HANDHOLES OR OTHER REQUIRED
ELEMENTS FOR PROPER INSTALLATION OF THE WORK. ALL NECESSARY
MATERIALS NEEDED TO FULFILL THE PROJECT REQUIREMENTS SHALL BE
PROVIDED AT NO ADDITIONAL COST.
5. WORK SHALL BE CARRIED OUT IN COORDINATION WITH OTHER DISCIPLINES.
COORDINATE WITH CIVIL CONTRACT DOCUMENTS IN TERMS OF ROUTING PATHS,
EQUIPMENT COMPATIBILITY AND MOUNTING ARRANGEMENT PRIOR TO
INSTALLATION.
6. THE LOCATIONS OF ALL ELECTRICAL EQUIPMENT AND CONDUIT ROUTING ARE
APPROXIMATE. COORDINATE AND INSTALL THESE ITEMS SO AS TO ELIMINATE
INTERFERENCE WITH PIPING AND ALL OTHER EQUIPMENT. ADJUST THE LOCATION,
MHT's AND PROVIDE APPROPRIATE MOUNTING HARDWARE AS REQUIRED AT NO
ADDITIONAL COST.
7. COMPLY WITH NFPAs, UFAS, OTHER APPLICABLE CODES, AND AUTHORITY HAVING
JURISDICTION OR AS SHOWN ON DRAWINGS FOR MOUNTING HEIGHTS OF ALL
ELECTRICAL EQUIPMENT AND DEVICES. MAINTAIN MINIMUM WORKING
CLEARANCES REQUIRED BY NEC AND LOCAL UTILITY COMPANY.
8. FOLLOW MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLATIONS, UNLESS
INDICATED OR SPECIFIED OTHERWISE. INFORM VA AND OBTAIN WRITTEN
DIRECTION FROM THE CONTRACTING OFFICER REPRESENTATIVE IF CONFLICTS
EXIST BETWEEN MANUFACTURERS REQUIREMENTS AND CONTRACT DOCUMENTS
PRIOR TO THE START OF THE AFFECTED WORK.
9. ALL MATERIALS AND EQUIPMENT SHALL BE HEAVY DUTY, UL APPROVED/LISTED
AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS.
10. PROVIDE ALL GROUNDING AS PER SPECIFICATION 260526.
11. ITEMS OMITTED FROM EITHER THE SPECIFICATIONS OR THE DRAWINGS, BUT ARE
SHOWN OR DESCRIBED IN THE OTHER TRADES, AND ALL ITEMS NECESSARY TO
MAKE THE ELECTRICAL SYSTEM COMPLETE AND OPERATIONAL, SHALL FORM A
PART OF THE WORK.
12. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS.
EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED
EQUIPMENT GROUNDING CONDUCTOR.
13. UNDERGROUND FACILITIES AND CABLE LOCATIONS ARE ESTIMATED.
UNDERGROUND LOCATES OF EXISTING UNDERGROUND FACILITIES IS REQUIRED
TO CONFIRM ROUTE.
14. SMOKE ALARMS MUST BE INSTALLED IN LOCATIONS THAT DO NOT OBSTRUCT OR
INTERFERE WITH THE OPERATION OR PLACEMENT OF ANY EQUIPMENT.
15. REUSE EXISTING CONDUIT WITH FIRE ALARM WIRING FOR INTERCONNECTION OF
AUDIO VISUAL ALARMS TO ADDRESSABLE FIRE ALARM CONTROL PANEL.
16. REUSE EXISTING CONDUIT WITH FIRE ALARM WIRING FOR INTERCONNECTION OF
PULL STATION TO THE ADDRESSABLE FIRE ALARM CONTROL PANEL.
1.
2.
3.
4.
5.
6.
KEYNOTES:
PROVIDE JUNCTION BOXES IN THE DOOR FRAME WHERE SHOWN ON THIS DETAIL. ROUGH-IN SHALL BE PROVIDED WHETHER THE CURRENT SECURITY SCHEME UTILIZES THEM OR NOT. ALL CONDUITS SHALL BE EMT CONDUIT UNLESS OTHERWISE NOTED. FLEXIBLE CONDUIT OF ANY TYPE WILL NOT BE ACCEPTED. COORDINATE INSTALLATION WITH ON-SITE DOOR FRAME INSTALLATION CONTRACTOR.
ALL DOOR POSITION SWITCHES ARE REQUIRED TO BE RECESSED UNLESS OTHERWISE NOTED. ELECTRIC HINGE MONITORS ARE NOT AN
ACCEPTABLE REPLACEMENT FOR THE RECESSED DOOR POSITION SWITCH.
4" SQUARE BACKBOX WITH SINGLE GANG PLASTER RING. PROVIDE 2 1/2" DEEP MASONRY BOX WHERE APPLICABLE. REFER TO FLOOR PLAN(S) FOR
ACTUAL CREDENTIAL READER TYPE AND ROUGH-IN LOCATIONS.
CONDUIT SHALL ROUTE FROM THE CREDENTIAL READER TO THE SECURED SIDE OF THE DOOR. CONDUIT SHALL ROUTE TO THE NEAREST SECURITY
PANEL.
MOUNT A MINIMUM 4" SQUARE 2-1/8" DEEP JUNCTION BOX WITH BLANK COVER PLATE ON THE SECURED SIDE OF THE DOOR ABOVE ACCESSIBLE CEILING. INSTALLING CONTRACTOR SHALL SIZE THE JUNCTION BOXES PER SYSTEM INSTALLATION REQUIREMENTS AND APPLICABLE CODES.
MAINTAIN ACCESS TO THE JUNCTION BOX.
CONDUIT SHALL ROUTE TO THE NEAREST ACCESSIBLE CEILING. PROVIDE A NYLON BUSHING ON CONDUIT END.
DOOR FRAME ROUGH-IN DIAGRAM
(ALL SINGLE DOORS)
FINISHED ACCESSIBLE
CEILING
FINISHED FLOOR
1/2" EMT CONDUIT
MINIMUM (TYP.)
3/4" EMT CONDUIT
MINIMUM TO ABOVE THE
ACCESSIBLE CEILING
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
56 Louis Prima Drive, Suite B, Covington, LA 70433 720.491.7559; Sean Fitzpatrick
FORT SILL
GRAVESITE EXPANSION AND
CEMETERY FCA IMPROVEMENTS
Elgin, OK
920CM3006
N/A
07/01/2026Revisions: Date: ZTNT
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
Approved: Project Manager/COR Department of Veteran Affairs, NCA POC: Homayoun Kazemipour Email: homayoun.kazemipour@va.gov
GENERAL NOTES
1. ALL ELECTRICAL WORK IS NEW, AND SHALL BE INSTALLED IN ACCORDANCE WITH
THE LATEST EDITION OF THE NEC, NFPA, AND OSHA. THE CONTRACTOR SHALL
PROVIDE AND INSTALL ALL NECESSARY ELECTRICAL EQUIPMENT AND
CONNECTIONS INCLUDING CONTROL WIRING IN CONDUIT SYSTEM TO OTHER
DISCIPLINES' EQUIPMENT AS INDICATED/AS REQUIRED FOR A COMPLETE,
FUNCTIONAL ELECTRICAL SYSTEM.
2. CONDUCTORS SHALL BE COPPER MINIMUM #12 THW OR THWN, INSTALLED IN RIGID
STEEL CONDUITS FOR ABOVEGROUND AND PVC FOR UNDERGROUND RUNS.
PROVIDE 90° ELBOW AND CONDUIT TRANSITION FROM PVC TO RIGID STEEL
CONDUIT (RGS) FOR UNDERGROUND ROUTING BEFORE TURNING UP TO ABOVE
GROUND SURFACE.
3. ALL BRANCH CIRCUITS SHALL CONTAIN WIRING INCLUDING AN INSULATED (GREEN)
GROUNDING CONDUCTOR IN A CONDUIT, EACH SIZED PER NEC. ALL CONDUCTOR
SIZES ARE BASED ON THE USE OF "THW/THWN" INSULATION.
4. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,
ELBOWS, JB'S, WIRE TROUGHS, PULL BOXES, HANDHOLES OR OTHER REQUIRED
ELEMENTS FOR PROPER INSTALLATION OF THE WORK. ALL NECESSARY
MATERIALS NEEDED TO FULFILL THE PROJECT REQUIREMENTS SHALL BE
PROVIDED AT NO ADDITIONAL COST.
5. WORK SHALL BE CARRIED OUT IN COORDINATION WITH OTHER DISCIPLINES.
COORDINATE WITH CIVIL CONTRACT DOCUMENTS IN TERMS OF ROUTING PATHS,
EQUIPMENT COMPATIBILITY AND MOUNTING ARRANGEMENT PRIOR TO
INSTALLATION.
6. THE LOCATIONS OF ALL ELECTRICAL EQUIPMENT AND CONDUIT ROUTING ARE
APPROXIMATE. COORDINATE AND INSTALL THESE ITEMS SO AS TO ELIMINATE
INTERFERENCE WITH PIPING AND ALL OTHER EQUIPMENT. ADJUST THE LOCATION,
MHT's AND PROVIDE APPROPRIATE MOUNTING HARDWARE AS REQUIRED AT NO
ADDITIONAL COST.
7. COMPLY WITH NFPAs, UFAS, OTHER APPLICABLE CODES, AND AUTHORITY HAVING
JURISDICTION OR AS SHOWN ON DRAWINGS FOR MOUNTING HEIGHTS OF ALL
ELECTRICAL EQUIPMENT AND DEVICES. MAINTAIN MINIMUM WORKING
CLEARANCES REQUIRED BY NEC AND LOCAL UTILITY COMPANY.
8. FOLLOW MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLATIONS, UNLESS
INDICATED OR SPECIFIED OTHERWISE. INFORM VA AND OBTAIN WRITTEN
DIRECTION FROM THE CONTRACTING OFFICER REPRESENTATIVE IF CONFLICTS
EXIST BETWEEN MANUFACTURERS REQUIREMENTS AND CONTRACT DOCUMENTS
PRIOR TO THE START OF THE AFFECTED WORK.
9. ALL MATERIALS AND EQUIPMENT SHALL BE HEAVY DUTY, UL APPROVED/LISTED
AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS.
10. PROVIDE ALL GROUNDING AS PER SPECIFICATION 260526.
11. ITEMS OMITTED FROM EITHER THE SPECIFICATIONS OR THE DRAWINGS, BUT ARE
SHOWN OR DESCRIBED IN THE OTHER TRADES, AND ALL ITEMS NECESSARY TO
MAKE THE ELECTRICAL SYSTEM COMPLETE AND OPERATIONAL, SHALL FORM A
PART OF THE WORK.
12. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS.
EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED
EQUIPMENT GROUNDING CONDUCTOR.
13. UNDERGROUND FACILITIES AND CABLE LOCATIONS ARE ESTIMATED.
UNDERGROUND LOCATES OF EXISTING UNDERGROUND FACILITIES IS REQUIRED
TO CONFIRM ROUTE.
SCALE: NTS
MOUNTING HEIGHTS FOR WALL MOUNTED DEVICESC1
MOUNTING HEIGHT AND
IT ROOM DOOR FRAME
E-501
SCALE: NTS
TR DOOR FRAMEE2
KEYED NOTES
1. PROVIDE JUNCTION BOXES IN THE DOOR FRAME WHERE SHOWN ON THIS DETAIL.
ROUGH-IN SHALL BE PROVIDED WHETHER THE CURRENT SECURITY SCHEME
UTILIZES THEM OR NOT. ALL CONDUITS SHALL BE EMT CONDUIT UNLESS
OTHERWISE NOTED. FLEXIBLE CONDUIT OF ANY TYPE WILL NOT BE ACCEPTED.
COORDINATE WITH ON-SITE FRAME INSTALLATION CONTRACTOR.
2. ALL DOOR POSITION SWITCHES ARE REQUIRED TO BE RECESSED UNLESS
OTHERWISE NOTED. ELECTRIC HINGE MONITORS ARE NOT AN ACCEPTABLE
REPLACEMENT FOR THE RECESSED DOOR POSITION SWITCH.
3. 4'' SQUARE BACK BOX WITH SINGLE GANG PLASTER RING. PROVIDE 2 1/2'' DEEP
MASONRY BOX WHERE APPLICABLE. REFER TO FLOOR PLAN(S) FOR ACTUAL
CREDENTIAL READER TYPE AND ROUGH-IN LOCATIONS.
4. CONDUIT SHALL ROUTE FROM THE CREDENTIAL READER TO THE SECURED SIDE
OF THE DOOR. CONDUIT SHALL ROUTE A MINIMUM OF 12'' FROM THE JUNCTION
BOX, TO THE NEAREST SERVING SECURITY PANEL. PROVIDE A NYLON BUSHING ON
CONDUIT END.
5. MOUNT A MINIMUM 4'' SQUARE 2-1/8'' DEEP JUNCTION BOX WITH BLANK COVER
PLAT ON THE SECURED SIDE OF THE DOOR ABOVE ACCESSIBLE CEILING.
INSTALLING CONTRACTOR SHALL SIZE THE JUNCTION BOXES PER INSTALLATION
REQUIREMENTS AND APPLICABLE CODES, MAINTAIN ACCESS TO THE JUNCTION
BOX.
6. PROVIDE A HORIZONTALLY MOUNTED SINGLE GANG BACK BOX FOR THE REQUEST
TO EXIT SENSOR. REFER TO THE CONTROLLED SECURITY SCHEME SCHEDULE FOR
DOORS THAT REQUIRE THIS ROUGH-IN.
7. CONDUIT SHALL ROUTE A MINIMUM OF 12'' FROM THE JUNCTION BOX TO THE
NEAREST SECURITY PANEL. PROVIDE A NYLON BUSHING ON CONDUIT END.
TELECOMMUNICATION OUTLET, FLUSH MOUNTED, 4" SQUARE OUTLET BOX WITH PLASTER
RING. NUMBER WHERE SHOWN INDICATES THE NUMBER OF CATEGORY 6 JACKS IN THE
OUTLET BOX. WHERE NUMBER IS NOT SHOWN, PROVIDE TWO DATA JACKS, ONE VOICE
JACK, ALL CATEGORY 6, AND ONE BLANK IN THE OUTLET BOX WITH STAINLESS STEEL
COVER PLATE. ARRANGE SO THAT DATA JACKS ARE ON TOP.
SAME AS ABOVE EXCEPT OUTLET BOX MOUNTED AT 42" ABOVE FINISHED FLOOR OR 3"
ABOVE COUNTER. COORDINATE WITH ARCHITECTURAL DRAWINGS.
SAME AS ABOVE EXCEPT OUTLET BOX MOUNTED 60" ABOVE FINISHED FLOOR.
TELECOMMUNICATIONS BACKBOARD, 4'x8'x3/4", FIRE-RETARDANT PLYWOOD, PAINT
ALL SIDES AND EDGES WITH GRAY PAINT. ALIGN EIGHT FOOT SIDE VERTICALLY.
TELECOMMUNICATION FLOOR RACK, STEEL, 72"Hx19"W, WITH CABLING MANAGEMENT
SYSTEM.
1. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING DEVICES, CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN THE WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE DEVICE AND REMOVE WIRING
COMPLETELY FROM THE ABANDONED CONDUITS.
2. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED WIRING - IF ANY.
DEMOLITION
ELECTRICAL
GENERAL NOTES
INFORMATION TECHNOLOGY/DATA SYSTEM LEGEND ABBREVIATIONS
L21-20 RECEPTACLE
RACK PDU (rPDU)
DUAL-POWERED IT/NETWORKING
EQUIPMENT
SERVER CABINET WITH rPDUs
AND EQUIPMENT
UPS (RACK-MOUNTED)
DISTRIBUTION PANEL
1. LED LIGHTING PLACED IN AISLES DIRECTLY IN FRONT OF AND BEHIND CABINET ROWS.
2. LIGHTING OPERATED BY MOTION SENSOR PER CABINET ROW OR SECTION.
3. 500 LUMENS IN THE HORIZONTAL PLANE AND 200 LUMENS IN THE VERTICAL PLANE REQUIRED MEASURED AT 3FT AFF IN FRONT OF AND BEHIND EQUIPMENT CABINETS.
LIGHTING
1. MINIMUM QTY TWO 120V 20A CONVENIENCE POWER OUTLETS PER WALL; PLACEMENT DETERMINED BY OTHERS.
2. PRIMARY BONDING BUSBAR; PLACEMENT DETERMINED BY OTHERS.
3. SECONDARY BONDING BUSBAR; PLACEMENT DETERMINED BY OTHERS.
4. SERVICE PANEL FOR A-SIDE POWER, GENERATOR BACK IF THE FACILITY HAS GENERATION CAPABILITIES. SHALL BE EQUIPPED WITH POWER METER; PLACEMENT PER
OTHERS.
5. SERVICE PANEL B-SIDE POWER, GENERATOR BACKED IF POSSIBLE. SHALL BE EQUIPPED WITH POWER METER; PLACEMENT PER OTHERS.
6. 20A 208V THREE- PHASE TWIST LOCK RECEPTACLE (L21-20R); 8.5FT AFF {WYE(5-WIRE)} COORDINATE INSTALLATION LOCATION WITH TELECOMMUNICATIONS CONTRACTOR.
7. 30A 208V THREE-PHASE TWIST LOCK RECEPTACLE (L21-20R); 8.5FT AFF {WYE(5-WIRE)} COORDINATE INSTALLATION LOCATION WITH TELECOMMUNICATIONS CONTRACTOR.
8. POWER BUSWAY (VOLTAGE AND AMPERAGE TO SUPPORT ADEQUATE SINGLE & DOUBLE BREAKER 208V, 20A, L21-20R BUSWAY TAPS PER SERVER ROW) FED FROM A-SIDE
SOURCE.
9. POWER BUSWAY (VOLTAGE AND AMPERAGE TO SUPPORT ADEQUATE SINGLE & DOUBLE BREAKER 208V, 20A, L21-20R BUSWAY TAPS PER SERVER ROW) FED FROM B-SIDE
SOURCE.
10. POWER BUSWAY (VOLTAGE AND AMPERAGE TO SUPPORT ADEQUATE SINGLE BREAKER 208V, 20A, L21-20R BUSWAY TAPS PER SERVER ROW) FED FROM A-SIDE SOURCE.
11. POWER BUSWAY (VOLTAGE AND AMPERAGE TO SUPPORT ADEQUATE SINGLE BREAKER 208V, 20A, L21-20R BUSWAY TAPS PER SERVER ROW) FED FROM B-SIDE SOURCE.
12. BLUE CABLE PATCH FOR A-SIDE UPS.
13. YELLOW CABLE PATH FOR B-SIDE UPS.
DATA TELECOM OUTLET
TELECOM OUTLET FLOOR
MOUNTED
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
56 Louis Prima Drive, Suite B, Covington, LA 70433 720.491.7559; Sean Fitzpatrick
FORT SILL
GRAVESITE EXPANSION AND
CEMETERY FCA IMPROVEMENTS
Elgin, OK
920CM3006
N/A
07/01/2026Revisions: Date: ZTNT
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
Approved: Project Manager/COR Department of Veteran Affairs, NCA POC: Homayoun Kazemipour Email: homayoun.kazemipour@va.gov
INFORMATION TECHNOLOGY (IT)
SYMBOLS & NOTES
T-001
IT DEMOLITION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
56 Louis Prima Drive, Suite B, Covington, LA 70433 720.491.7559; Sean Fitzpatrick
FORT SILL
GRAVESITE EXPANSION AND
CEMETERY FCA IMPROVEMENTS
Elgin, OK
920CM3006
N/A
07/01/2026Revisions: Date: ZTNT
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
Approved: Project Manager/COR Department of Veteran Affairs, NCA POC: Homayoun Kazemipour Email: homayoun.kazemipour@va.gov
GENERAL NOTES
1. ALL ELECTRICAL WORK IS NEW, AND SHALL BE INSTALLED IN ACCORDANCE WITH
THE LATEST EDITION OF THE NEC, NFPA, AND OSHA. THE CONTRACTOR SHALL
PROVIDE AND INSTALL ALL NECESSARY ELECTRICAL EQUIPMENT AND
CONNECTIONS INCLUDING CONTROL WIRING IN CONDUIT SYSTEM TO OTHER
DISCIPLINES' EQUIPMENT AS INDICATED/AS REQUIRED FOR A COMPLETE,
FUNCTIONAL ELECTRICAL SYSTEM.
2. CONDUCTORS SHALL BE COPPER MINIMUM #12 THW OR THWN, INSTALLED IN RIGID
STEEL CONDUITS FOR ABOVEGROUND AND PVC FOR UNDERGROUND RUNS.
PROVIDE 90° ELBOW AND CONDUIT TRANSITION FROM PVC TO RIGID STEEL
CONDUIT (RGS) FOR UNDERGROUND ROUTING BEFORE TURNING UP TO ABOVE
GROUND SURFACE.
3. ALL BRANCH CIRCUITS SHALL CONTAIN WIRING INCLUDING AN INSULATED (GREEN)
GROUNDING CONDUCTOR IN A CONDUIT, EACH SIZED PER NEC. ALL CONDUCTOR
SIZES ARE BASED ON THE USE OF "THW/THWN" INSULATION.
4. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,
ELBOWS, JB'S, WIRE TROUGHS, PULL BOXES, HANDHOLES OR OTHER REQUIRED
ELEMENTS FOR PROPER INSTALLATION OF THE WORK. ALL NECESSARY
MATERIALS NEEDED TO FULFILL THE PROJECT REQUIREMENTS SHALL BE
PROVIDED AT NO ADDITIONAL COST.
5. WORK SHALL BE CARRIED OUT IN COORDINATION WITH OTHER DISCIPLINES.
COORDINATE WITH CIVIL CONTRACT DOCUMENTS IN TERMS OF ROUTING PATHS,
EQUIPMENT COMPATIBILITY AND MOUNTING ARRANGEMENT PRIOR TO
INSTALLATION.
6. THE LOCATIONS OF ALL ELECTRICAL EQUIPMENT AND CONDUIT ROUTING ARE
APPROXIMATE. COORDINATE AND INSTALL THESE ITEMS SO AS TO ELIMINATE
INTERFERENCE WITH PIPING AND ALL OTHER EQUIPMENT. ADJUST THE LOCATION,
MHT's AND PROVIDE APPROPRIATE MOUNTING HARDWARE AS REQUIRED AT NO
ADDITIONAL COST.
7. COMPLY WITH NFPAs, UFAS, OTHER APPLICABLE CODES, AND AUTHORITY HAVING
JURISDICTION OR AS SHOWN ON DRAWINGS FOR MOUNTING HEIGHTS OF ALL
ELECTRICAL EQUIPMENT AND DEVICES. MAINTAIN MINIMUM WORKING
CLEARANCES REQUIRED BY NEC AND LOCAL UTILITY COMPANY.
8. FOLLOW MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLATIONS, UNLESS
INDICATED OR SPECIFIED OTHERWISE. INFORM VA AND OBTAIN WRITTEN
DIRECTION FROM THE CONTRACTING OFFICER REPRESENTATIVE IF CONFLICTS
EXIST BETWEEN MANUFACTURERS REQUIREMENTS AND CONTRACT DOCUMENTS
PRIOR TO THE START OF THE AFFECTED WORK.
9. ALL MATERIALS AND EQUIPMENT SHALL BE HEAVY DUTY, UL APPROVED/LISTED
AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS.
10. PROVIDE ALL GROUNDING AS PER SPECIFICATION 260526.
11. ITEMS OMITTED FROM EITHER THE SPECIFICATIONS OR THE DRAWINGS, BUT ARE
SHOWN OR DESCRIBED IN THE OTHER TRADES, AND ALL ITEMS NECESSARY TO
MAKE THE ELECTRICAL SYSTEM COMPLETE AND OPERATIONAL, SHALL FORM A
PART OF THE WORK.
12. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS.
EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED
EQUIPMENT GROUNDING CONDUCTOR.
13. UNDERGROUND FACILITIES AND CABLE LOCATIONS ARE ESTIMATED.
UNDERGROUND LOCATES OF EXISTING UNDERGROUND FACILITIES IS REQUIRED
TO CONFIRM ROUTE.
14. COORDINATE WITH VA OIT AND INCORPORATE A PHASING PLAN FOR THE
RELOCATION OF THE EQUIPMENT IN THIS CABINET TO THE NEW TR RACK. ALL
SYSTEM MUST REMAIN OPERATIONAL UNTIL CUT OVER TO THE NEW TR RACK.
15. ALL EXISTING WAO MUST REMAIN OPERATIONAL UNTIL CUT OVER TO NEW PATCH
PANELS INSTALLED IN THE NEW TR RACK.
SCALE: NTS
ADMIN BLDG SERVER RACKD2 SCALE: NTS
ADMIN BLDG PATCH PANELD6
TD101
ROUTER
SWITCH
DELL STORAGE
DELL VOICE GATEWAY
(ANALOG TELEPHONE TO VOIP)
TELECOMMUNICATION
SINGLE LINE DIAGRAM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
56 Louis Prima Drive, Suite B, Covington, LA 70433 720.491.7559; Sean Fitzpatrick
FORT SILL
GRAVESITE EXPANSION AND
CEMETERY FCA IMPROVEMENTS
Elgin, OK
920CM3006
N/A
07/01/2026Revisions: Date: ZTNT
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
Approved: Project Manager/COR Department of Veteran Affairs, NCA POC: Homayoun Kazemipour Email: homayoun.kazemipour@va.gov
GENERAL NOTES
1. ALL ELECTRICAL WORK IS NEW, AND SHALL BE INSTALLED IN ACCORDANCE WITH
THE LATEST EDITION OF THE NEC, NFPA, LOCAL CODES, AND OSHA. THE
CONTRACTOR SHALL PROVIDE AND INSTALL ALL NECESSARY ELECTRICAL
EQUIPMENT AND CONNECTIONS INCLUDING CONTROL WIRING IN CONDUIT SYSTEM
TO OTHER DISCIPLINES' EQUIPMENT AS INDICATED/AS REQUIRED FOR A
COMPLETE, FUNCTIONAL ELECTRICAL SYSTEM.
2. CONDUCTORS SHALL BE COPPER MINIMUM #12 THW OR THWN, INSTALLED IN RIGID
STEEL CONDUITS FOR ABOVEGROUND AND PVC FOR UNDERGROUND RUNS.
PROVIDE 90° ELBOW AND CONDUIT TRANSITION FROM PVC TO RIGID STEEL
CONDUIT (RGS) FOR UNDERGROUND ROUTING BEFORE TURNING UP TO ABOVE
GROUND SURFACE.
3. ALL BRANCH CIRCUITS SHALL CONTAIN WIRING INCLUDING AN INSULATED (GREEN)
GROUNDING CONDUCTOR IN A CONDUIT, EACH SIZED PER NEC. ALL CONDUCTOR
SIZES ARE BASED ON THE USE OF "THW/THWN" INSULATION.
4. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,
ELBOWS, JB'S, WIRE TROUGHS, PULL BOXES, HANDHOLES OR OTHER REQUIRED
ELEMENTS FOR PROPER INSTALLATION OF THE WORK. ALL NECESSARY
MATERIALS NEEDED TO FULFILL THE PROJECT REQUIREMENTS SHALL BE
PROVIDED AT NO ADDITIONAL COST.
5. WORK SHALL BE CARRIED OUT IN COORDINATION WITH OTHER DISCIPLINES.
COORDINATE WITH CIVIL CONTRACT DOCUMENTS IN TERMS OF ROUTING PATHS,
EQUIPMENT COMPATIBILITY AND MOUNTING ARRANGEMENT PRIOR TO
INSTALLATION.
6. THE LOCATIONS OF ALL ELECTRICAL EQUIPMENT AND CONDUIT ROUTING ARE
APPROXIMATE. COORDINATE AND INSTALL THESE ITEMS SO AS TO ELIMINATE
INTERFERENCE WITH PIPING AND ALL OTHER EQUIPMENT. ADJUST THE LOCATION,
MHT's AND PROVIDE APPROPRIATE MOUNTING HARDWARE AS REQUIRED AT NO
ADDITIONAL COST.
7. COMPLY WITH NFPAs, UFAS, OTHER APPLICABLE CODES, AND AUTHORITY HAVING
JURISDICTION OR AS SHOWN ON DRAWINGS FOR MOUNTING HEIGHTS OF ALL
ELECTRICAL EQUIPMENT AND DEVICES. MAINTAIN MINIMUM WORKING
CLEARANCES REQUIRED BY NEC AND LOCAL UTILITY COMPANY.
8. FOLLOW MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLATIONS, UNLESS
INDICATED OR SPECIFIED OTHERWISE. INFORM VA AND OBTAIN WRITTEN
DIRECTION FROM THE CONTRACTING OFFICER REPRESENTATIVE IF CONFLICTS
EXIST BETWEEN MANUFACTURERS REQUIREMENTS AND CONTRACT DOCUMENTS
PRIOR TO THE START OF THE AFFECTED WORK.
9. ALL MATERIALS AND EQUIPMENT SHALL BE HEAVY DUTY, UL APPROVED/LISTED
AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS.
10. PROVIDE ALL GROUNDING AS PER SPECIFICATION 260526.
11. ITEMS OMITTED FROM EITHER THE SPECIFICATIONS OR THE DRAWINGS, BUT ARE
SHOWN OR DESCRIBED IN THE OTHER TRADES, AND ALL ITEMS NECESSARY TO
MAKE THE ELECTRICAL SYSTEM COMPLETE AND OPERATIONAL, SHALL FORM A
PART OF THE WORK.
12. MAINTAIN 10' SEPARATION FROM EACH DRIVEN GROUND ROD
UTILITY DISTRIBUTION
SYSTEM
ADMINISTRATION
BUILDING
TR ROOM
UTILITY
SCALE: NTS
TELECOMMUNICATION SINGLE LINE DIAGRAMF4
UTILITY
TRANSFORMER
UTILITY
METER
SUBSTATION
T-101
SEPARATELY ENCLOSED
CIRCUIT BREAKER
1000A
MDP-1000A BUS,
208Y/120V
3-PHASE, 4-WIRE
225A
PANEL LPA FUSEBOX 2
225A MAINLUG
PANELBOARD, 208/120V
3-PHASE, 4-WIRE
PANEL LPA FUSEBOX 1
225A MAINLUG
PANELBOARD, 208/120V
3-PHASE, 4-WIRE
20A 20A
L21-20
RECEPTACLE
L21-20
RECEPTACLE
MULTI-PURPOSE RM
O
PER
ATIO
N
AL C
EN
TER
OFF. STOR.
H.A.C.
LOBBY
VESTIBU
LE
VESTIBULE
M
EN
'S LO
C
KER
R
O O
M
W O
M
EN
'S LO
C
KER
R
O O
M
BOOT WASH
VESTIBULE
MAINT. OFF.
MECHANICAL
CORRIDOR
FOREMAN
HONOR GUARD
ELEC. RM.
RESTROOM
LUNCHROOM
DIRECTOR
RESTROOM
GENERAL OFFICE
TR
TR
INFORMATION TECHNOLOGY PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
56 Louis Prima Drive, Suite B, Covington, LA 70433 720.491.7559; Sean Fitzpatrick
FORT SILL
GRAVESITE EXPANSION AND
CEMETERY FCA IMPROVEMENTS
Elgin, OK
920CM3006
N/A
07/01/2026Revisions: Date: ZTNT
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
Approved: Project Manager/COR Department of Veteran Affairs, NCA POC: Homayoun Kazemipour Email: homayoun.kazemipour@va.gov
N
0 4 8
1 INCH = 4 FEET
GENERAL NOTES
1. ALL ELECTRICAL WORK IS NEW, AND SHALL BE INSTALLED IN ACCORDANCE WITH
THE LATEST EDITION OF THE NEC, NFPA, AND OSHA. THE CONTRACTOR SHALL
PROVIDE AND INSTALL ALL NECESSARY ELECTRICAL EQUIPMENT AND
CONNECTIONS INCLUDING CONTROL WIRING IN CONDUIT SYSTEM TO OTHER
DISCIPLINES' EQUIPMENT AS INDICATED/AS REQUIRED FOR A COMPLETE,
FUNCTIONAL ELECTRICAL SYSTEM.
2. CONDUCTORS SHALL BE COPPER MINIMUM #12 THW OR THWN, INSTALLED IN RIGID
STEEL CONDUITS FOR ABOVEGROUND AND PVC FOR UNDERGROUND RUNS.
PROVIDE 90° ELBOW AND CONDUIT TRANSITION FROM PVC TO RIGID STEEL
CONDUIT (RGS) FOR UNDERGROUND ROUTING BEFORE TURNING UP TO ABOVE
GROUND SURFACE.
3. ALL BRANCH CIRCUITS SHALL CONTAIN WIRING INCLUDING AN INSULATED (GREEN)
GROUNDING CONDUCTOR IN A CONDUIT, EACH SIZED PER NEC. ALL CONDUCTOR
SIZES ARE BASED ON THE USE OF "THW/THWN" INSULATION.
4. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,
ELBOWS, JB'S, WIRE TROUGHS, PULL BOXES, HANDHOLES OR OTHER REQUIRED
ELEMENTS FOR PROPER INSTALLATION OF THE WORK. ALL NECESSARY
MATERIALS NEEDED TO FULFILL THE PROJECT REQUIREMENTS SHALL BE
PROVIDED AT NO ADDITIONAL COST.
5. WORK SHALL BE CARRIED OUT IN COORDINATION WITH OTHER DISCIPLINES
COORDINATE WITH CIVIL CONTRACT DOCUMENTS IN TERMS OF ROUTING PATHS,
EQUIPMENT COMPATIBILITY AND MOUNTING ARRANGEMENT PRIOR TO
INSTALLATION.
6. THE LOCATIONS OF ALL ELECTRICAL EQUIPMENT AND CONDUIT ROUTING ARE
APPROXIMATE. COORDINATE AND INSTALL THESE ITEMS SO AS TO ELIMINATE
INTERFERENCE WITH PIPING AND ALL OTHER EQUIPMENT. ADJUST THE LOCATION,
MHT's AND PROVIDE APPROPRIATE…