Attachment 13 - Drawings Technology.pdf
PDF 8 MB Posted
- Attached to
- Y1DA--580-324 | Replace/Construct Bldg 121 | Houston, TX Federal contract opportunity
- Solicitation number
- 36C77625R0030_1
About this file
This document is a set of technology-related architectural drawings for a VA Medical Center building replacement project, specifically focusing on technology systems installation details. The drawings provide comprehensive technical specifications for various technology systems, including telecommunications, security surveillance, nurse call, fire alarm, and physical access control systems. The plans include detailed installation guidelines, symbol legends, mounting heights, cable and connector color codes, grounding requirements, and compliance standards for each system type.
Key technical specifications cover requirements such as installing technology devices according to national electrical codes, BICSI standards, VA OIT standards, and Americans with Disabilities Act guidelines. The drawings specify conduit sizes, cable types (including plenum-rated cabling), outlet configurations, equipment mounting details, and system interconnection requirements. Specific systems detailed include wireless access points, data outlets, security cameras, nurse call stations, fire alarm devices, and communication infrastructure, with meticulous attention to placement, height, and technical compliance across multiple technology domains.
View the file
Other files for this federal contract opportunity
Show all 36
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TECHNOLOGY GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
PROVIDE TECHNOLOGY DEVICES AND EQUIPMENT IN ACCORDANCE WITH THE CONTRACT DOCUMENTS, MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT, LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, BICSI STANDARDS, AND VA OIT
STANDARDS.
PROVIDE ADDITIONAL SUPPORT FOR DEVICES AND EQUIPMENT WHERE BUILDING CONSTRUCTION IS NOT
SUITABLE FOR DIRECT MOUNTING.
FIRESTOP, DRAFTSTOP, SMOKESTOP OR PROTECT ANNULAR SPACE AROUND PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILINGS, AND ROOF IN ACCORDANCE WITH REQUIREMENTS OF NFPA 70, UL LISTING
REQUIREMENT AND APPLICABLE BUILDING CODES.
PROVIDE CABLING THAT COMPLIES WITH THE LATEST EDITION OF TELECOMMUNICATIONS DISTRIBUTION
METHOD MANUAL AND ANSI/TIA/EIA PUBLICATIONS.
COMPLY WITH THE LATEST ANSI/TIA/EIA 758 AND 607 - BONDING AND GROUNDING TELECOMMUNICATIONS.
COMPLY WITH THE LATEST ANSI/TIA/EIA 568 - COMMERCIAL BUILDING TELECOMMUNICATIONS WIRING STANDARD.
COMPLY WITH THE LATEST ANSI/TIA/EIA 569 - TELECOMMUNICATIONS PATHWAYS AND SPACES.
COMPLY WITH ANSI/TIA-1069 STANDARD FOR HOSPITAL SIGNALING & NURSE CALL EQUIPMENT.
COMPLY WITH ANSI/TIA-1179 HEALTHCARE FACILITY TELECOMMUNICATION INFRASTRUCTURE STANDARD.
COMPLY WITH THE LATEST NFPA 70 NATIONAL ELECTRICAL CODE.
COMPLY WITH THE LATEST NFPA 99 HEALTHCARE FACILITIES CODE.
COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE.
CONTRACTOR RESPONSIBLE FOR THE COORDINATION OF ALL WORK WITH ALL OTHER TRADES PRIOR TO
INSTALLATION.
MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES TO INDICATE A QUALITY STANDARD AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL IN ACCORDANCE WITH SPECIFIED PROCESSES FOR APPROVAL AND APPROVED BY THE COR
WILL BE ACCEPTABLE. COMPLY WITH "BUY AMERICAN ACT".
MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, BOXES, OUTLET, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
PROVIDE RGS OR EMT CONDUIT UNLESS OTHERWISE NOTED.
PROVIDE MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT LABEL LISTED BY APPROVED THIRD PARTY
TESTING AGENCY.
NOTIFY COR REGARDING DISCREPANCY BETWEEN PLANS AND SPECIFICATIONS FOR CLARIFICATION. THE MORE
STRINGENT SHALL TAKE PRECEDENCE.
PROVIDE TIA/EIA 4 PR UTP COPPER CABLE, JACKS, AND CONNECTORS.
ALL WORK AREA OUTLETS SHALL BE 8 PIN, 8P8C KEYSTONE JACK WIRED PER T568B.
LABEL DEVICES IN ACCORDANCE WITH LATEST ANSI/TIA 606 AS WELL AS THE STANDARDS SET FORTH BY THE
VAMC OIT.
PROVIDE A MINIMUM OF 12" CLEARANCE ABOVE THE CABLE TRAY PER TIA/EIA 569.
VA SHALL CONDUCT A WAP SURVEY AND PROVIDE THE SURVEY TO THE CONTRACTOR. CONTRACTOR SHALL INSTALL CABLING AND EQUIPMENT IN ACCORDANCE WITH THE SURVEY. COORDINATE WITH COR/OIT.
ALL CABLING INSTALLED ABOVE CEILING SHALL BE PLENUM RATED.
MINIMUM CONDUIT SIZE TO BE USED IS 1 1/4" CONDUIT.
WALL MOUNTED DEVICES PLACED IN TELECOMMUNICATIONS ROOM TO BE MOUNTED ON FIRE RETARDANT
PLYWOOD.
ALL CAMERAS SHALL BE IN COMPLIANCE WITH THE NATIONAL DEFENSE AUTHORIZATION ACT.
ADO AUTOMATIC DOOR OPERATOR
AFF ABOVE FINISH FLOOR
BOD BASIS OF DESIGN
CCTV CLOSED CIRCUIT TELEVISION
COAX COAXIAL CABLE
COMM COMMUNICATION
COR CONTRACTING OFFICER REPRESENTATIVE
DC DOOR CONTACT SWITCH
DN DOWN
DO DOOR OPERATOR
DVC DIGITAL VOICE COMMAND
DVR DIGITAL VIDEO RECORDER
E EXISTING DEVICES
EEB EMERGENCY EXIT BUTTON
EL ELECTRICAL STRIKE
EMT ELECTRICAL METALLIC CONDUIT
ETR EXISTING TO REMAIN
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FAAP FIRE ALARM ANNUNCIATOR PANEL
FO FIBER OPTIC
FAGAP FIRE ALARM GRAPHIC ANNUNCIATOR PANEL
IT INTERCOMMUNICATION ROOM
MATV MASTER ANTENNA TELEVISION
MM MULTI MODE FIBER
NAC NOTIFICATION APPLIANCE CONTROL PANEL
N NEW DEVICES
NCA NETWORK CONTROL ANNUNCIATOR
NS NO SCALE
NTS NOT TO SCALE
NVR NETWORK VIDEO RECORDER
TECHNOLOGY ABBREVIATIONS LIST
OC ON CENTER
OIT OFFICE OF INFORMATION TECHNOLOGY
PACS PHYSICAL ACCESS CONTROL SYSTEM
PAMN PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEM
PB PUSH BUTTON
PBB PRIMARY BONDING BUSBAR
PDU RACK POWER DISTRIBUTION UNITS
POE POWER OVER ETHERNET
PR PAIR
RBB RACK BONDING BUSBAR
RGS RIGID GALVANIZED STEEL CONDUIT
RX REQUEST TO EXIT
SBB SECONDARY BONDING BUSBAR
SEP SERVICE ENTRANCE PROTECTION
SLC SIGNALING LINE CIRCUIT
SM SINGLE MODE FIBER
SSTV SECURITY SURVAILLANCE TELEVISION SYSTEM
TBB TELECOM BONDING CONDUCTOR
TELTELEPHONE
TM TELEMONITORING
TP TWISTED PAIR
TR TELECOM ROOM
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
WMWIRE MANAGEMENT
WAP WIRELESS ACCESS POINT
UL UNDERWRITERS LABORATORY
UPS UNINTERRUPTIBLE POWER SUPPLY
UTP UNSHIELDED TWISTED PAIR
CABLES AND CONNECTORS COLOR LEGEND
NOTES
4 PAIR CABLE
4 PAIR CABLE
SSTV
4 PAIR CABLE
6/12/24/36
6/12/24
MULTI COLOR
CONDUCTORS
4 PAIR UTP
COAX RG6
MULTI COLOR
CONDUCTORS
TELEPHONE
DESCRIPTION
ITEM JACK CABLE PATCH CABLES I.D.
DATA/COMPUTER
IVORY
BLUE
IVORY
GREEN
IVORY
BLUE
T
C
WIRELESS
ACCESS POINT
FIBER - MULTI-MODE
FIBER - SINGLE-MODE
SOUND SYSTEM
NURSE CALL
MATV
SSTV - IP
GREEN
BLACK
IVORY
N/A
WHITE
N/A
N/A
ORANGE
AQUA
YELLOW3
BLACK
PURPLE
BLUE
BLACK
GREEN
AQUA
YELLOW
WHITE
N/A
N/A
N/A
WAP
FO
FO
SS
SSTV
NC
MATV
PACS N/A GRAY N/A PACS
CONDUIT COLOR
BLUE1
YELLOW2
YELLOW2
YELLOW2
YELLOW2
YELLOW2
1.
2.
3.
HORIZONTAL DATA RUNS SHALL BE INSTALLED IN BLUE CONDUIT WHERE USED FOR HORIZONTAL DATA CABLING. OTHER THAN HORIZONTAL CABLING CONDITIONS SHALL BE
IDENTIFIED BY THE FOLLOWING COLORS:
DEMARCATION POINT - ORANGE
NETWORK CONNECTION - GREEN
FIRST LEVEL, TERMINATING BUILDING BACKBONE, MC(CD) TO IC(BD) - WHITE
SECOND LEVEL, IC(BD) TO TR(HD/FD) - GRAY
CAMPUS BACKBONE - BROWN
YELLOW CONDUIT SHALL HAVE A SECONDARY IDENTIFIER COLOR ADDED AS A STRIPE IN ORDER TO INDICATE SPECIFIC SYSTEM SERVED. COORDINATE SECONDARY
INDICATING COLOR WITH COR.
WHERE MULTIPLE SYSTEMS UTILIZE THE SAME CABLE COLOR, SYSTEM SPECIFIC CABLING SHALL HAVE A STRIPE IN ORDER TO INDICATE SPECIFIC SYSTEM SERVED.
COORDINATE STRIPE COLOR FOR SPECIFIC SUBSYSTEMS WITH COR.
GENERAL TECHNOLOGY SYMBOL LEGEND
DATA OUTLET - N-4 PR UTP
SYMBOL HEIGHT DESCRIPTION
18"N (N - QUANTITY)
WIRELESS ACCESS POINT - N-4 PR UTP
WALL PHONE JACKW 48"
N
CEILING (N - QUANTITY)
TV OUTLET WALL MOUNTEDAS NOTED
CHANNEL TR EQUIPMENT RACKFLOOR
VERTICAL WIRE MANAGEMENT
MATV EQUIPMENT CABINETMATV 6' TO TOP
FLOOR
WIRE MESH CABLE TRAY (4" - SEE PLANS FOR OTHER DIMENSIONS)
HIGH CAPACITY FLOOR BOX FOR DATA (2-4P) & POWER (4-RECEPTACLE)FLOOR
J JUNCTION BOX - AS NOTED ON PLANSAS NOTED
GROUND BUS
ABOVE
CEILING
18"
4'x8'x3/4" FIRE RETARDED TTB8"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
SEE DRAWINGS FOR MORE INFORMATION.
NOTE: NOT ALL SYMBOLS ARE USED.
OR
NURSE CALL SYMBOL LEGEND
SYMBOL HEIGHT DESCRIPTION
M NURSE CALL MASTER STATION/CONSOLE
NURSE CALL EQUIPMENT CABINETNCE
18"
6' TO TOP
E NURSE CALL EMERGENCY STATION WITH PULL CORD AND AUDIO +40" AFF IN
RESTROOM, +72" AFF IN SHOWER (V - VANDAL RESISTANT, PB - PUSH BUTTON)40", 72"
N NURSE CALL DOME LIGHT
(Z - ZONE LIGHT, V - VANDAL RESISTANT)CEILING
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
SEE DRAWINGS FOR MORE INFORMATION.
NOTE: NOT ALL SYMBOLS ARE USED.
PUBLIC ADDRESS SYMBOL LEGEND
SYMBOL HEIGHT DESCRIPTION
CEILING MOUNTED SPEAKERSCEILING
WALL MOUNTED SPEAKERS96"
S
S
VOLUME CONTROL48"VC
PAGING CONSOLE48"PA
PAGING CABINETFLOORPA
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
SEE DRAWINGS FOR MORE INFORMATION.
NOTE: NOT ALL SYMBOLS ARE USED.
SECURITY SYMBOL LEGEND
SYMBOL HEIGHT DESCRIPTION
ELECTRONIC LOCKING MECHANISM
CARD READER
(K - KEYPAD)48"CR
ES DOOR
PHYSICAL ACCESS CONTROL SYSTEMPACS 6' TO TOP
DOOR CONTACT
REQUEST FOR EXIT SENSOR
DC
RX
DOOR
ABOVE
DOOR
ADO DOOR OPERATORDOOR
88" MOTION DETECTORMD
SSTV DOME CAMERA FIXED
SSTV (90/180/270/360) PANORAMIC MULTISENSOR CAMERA
CEILING
CEILING
SSTV CAMERA EQUIPMENT CABINETSSTV FLOOR
DP
DPP
DURESS PANIC ALARM PUSH BUTTON48"
DURESS PANIC ALARM PANEL6' TO TOP
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
SEE DRAWINGS FOR MORE INFORMATION.
NOTE: NOT ALL SYMBOLS ARE USED.
TECHNOLOGY DEVICE WORK IS INDICATED BY AN UPPER CASE LETTER.
E: EXISTING DEVICE TO REMAIN
D: EXISTING DEVICE TO BE DEMOLISHED
R: EXISTING DEVICE TO BE REPLACED
N: NEW DEVICE
TECHNOLOGY DEVICES THAT DO NOT HAVE AN UPPERCASE LETTER SHALL BE
ASSUMED TO BE NEW.
DEVICES THAT ARE INDICATED HALFTONE ON THE PLAN ARE EXISTING TO REMAIN.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
EXAMPLE 1: DATA OUTLET TO BE DEMOLISHED.
EXAMPLE 2: DATA OUTLET TO BE REPLACED.
EXAMPLE 3: NEW DATA OUTLET.
EXAMPLE 4: EXISTING DATA OUTLET TO REMAIN.
DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
D
R
NONE OF THE NEW SECURITY SURVEILLANCE CAMERAS
SUPPLIED BY CONTRACTOR WILL BE SOURCED FROM
CHINESE MANUFACTURERS IN ACCORDANCE WITH THE
NATIONAL DEFENSE AUTHORIZATION ACT. CONTRACTOR
TO ENSURE NO NEW CAMERAS ARE REFURBISHED
CAMERAS FROM CHINA.
CONCERNING NEW SECURITY
SURVEILLANCE CAMERAS:
Engineers Architects Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: ARCHITECT/ENGINEER OF RECORD
Date Checked Drawn
FULLY SPRINKLERED
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
ACG Project Number
1/
/2
1:
:0
PM
C :\U se rs
\n ju si \D oc um en ts
\E _2
2-
1-
BC
LC
V
A-
BL
D G
_n ju si .rv t
T-001
TECHNOLOGY GENERAL NOTES,
SYMBOL LEGEND, AND
ABBREVIATIONS
1 6LAS
REPLACE BUILDING 121
MICHAEL E. DEBAKEY VAMC
2002 HOLCOMBE BOULEVARD
HOUSTON, TX 77030 JANUARY 24, 2025
100% CONSTRUCTION DOCUMENTS
580-324
ADR
22-021
TECHNOLOGY SYMBOL NOTES
SEAL
057626
P
ROFESSIONAL
A N
D
RE W D. RICHA
R D
S
N O
RT H C A R OLIN
A
E N G IN E E R
Docusign Envelope ID: 126CBD56-F5D8-40C2-9764-866FC75E4BC9
1/27/2025 1/27/2025
2 2 2 2
E
2 2
DC
RX
ES
CR
CR RX ES
DC
CR
RX ES DC
CR
DC RX
ES
CR
RX ES DC
CR
RX ES DC
S S S S S S S
S
S
S
S
S
S
S
S S S S S
S
SN
N
RX
RX
ES
ES
DC
DC
CR
CR
CR
ES
RX
DC
E
2 2
2 2
2 2
2 2
2 2
E
M
N
E
N
72"
72"
DC ES RX
CR
CR
DC ES RX
CR
DC DCRX
J
J
JJ JJ
J
J
J
J
ADO
AD
O
AD
O
S
J
J
J
J
RX
KP
DC ES
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
TR
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
GROUP
ROOM 2
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
14 TLT
OFFICE/CONSULT
HAC
STAFF TLT
TOILET
OFFICE
OFFICE
OFFICE
ELEC
SOILED
FAMILY
CONSULT
TOILET
STAFF
CONFERENCE
ROOM
OCCUPATIONAL
THERAPY
COMMUNITY
ROOM
RESOURCE/
COMPUTERS
OFFICE
FAMILY
CONSULT
EXAM
OFFICE
OFFICE
STAFF
LOUNGE
VEST
MECHANICAL
MEDS
OPEN
OFFICE
GROUP
ROOM 1
RECEPTION/CHECK-IN
VEST
WAITING
CORRIDOR
C06
CORRIDOR
C04
CORRIDOR
C05
CORRIDOR
C03
CORRIDOR
C02
CORRIDOR
C01
LOBBY
FIRE
RISER
ROOM
STORAGE
22 T-101
CLEAN
SUPPLY
07A
TRAINING
TLT
53BSTOR
53C
1 1.7 2 3 4 5 B.11 B.10 6
A
A.5
B
C
D
E
4.1
4 4
4 4
4 4
4 4
4 4
4 4
180 180
90 5
54"
48"
K
2 2
2 2 6
2 2 6
1 48"
18"
48"
18" 18"
48"
18" 48" 18" 48"
1415 1415
K
K
K
P P
P
P
P
TR
A.5
PBB
PACS
NCE
DPP
PA
SSTV
48" 7 8
K
TR
CORRIDOR
C04
A.5
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: ARCHITECT/ENGINEER OF RECORD
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
ACG Project Number
1/
/2
1:
:1
PM
C :\U se rs
\n ju si \D oc um en ts
\E _2
2-
1-
BC
LC
V
A-
BL
D G
_n ju si .rv t
T-101
FIRST FLOOR TECHNOLOGY PLAN
2 6LAS
REPLACE BUILDING 121
MICHAEL E. DEBAKEY VAMC
2002 HOLCOMBE BOULEVARD
HOUSTON, TX 77030 JANUARY 24, 2025
100% CONSTRUCTION DOCUMENTS
580-324
ADR
22-021
N O
R
TH
0 4 8 16
Scale: 1/8" = 1'-0"1 FIRST FLOOR TECHNOLOGY PLAN
1 COORDINATE LOCATION OF CODE SIZE WALL
MOUNTED JUNCTION BOX FOR CONNECTION TO
SYSTEM FURNITURE WITH VA. PROVIDE FLEXIBLE
CONDUIT FROM BOX TO FURNITURE. MAKE ALL
CONNECTIONS AND WIRE AS REQUIRED.
2 EXTERIOR, MULTI-SENSOR CAMERA. PROVIDE
INTERNAL HEATER. PROVIDE CORNER BRACKET
AND GOOSE NECK MOUNTING HARDWARE.
MOUNT APPROXIMATELY 12'-0" ABOVE FINISHED
GRADE.
3 INSTALL NURSE CALL PULL DEVICE WITHIN 1'-0"
MEASURED FROM THE OUTSIDE FRONT EDGE OF
THE TOILET BOWL. COORDINATE HEIGHT AFF
WITH LIGHT SWITCH AND OTHER WALL MOUNTED
FIXTURES
4 EXTERIOR, MULTI-SENSOR CAMERA. PROVIDE
INTERNAL HEATER. PROVIDE FLAT BRACKET AND
MOUNTING HARDWARE. MOUNT APPROXIMATELY
12'-0" ABOVE FINISHED GRADE.
5 EXTERIOR, MULTI-SENSOR CAMERA. PROVIDE
INTERNAL HEATER. PROVIDE FLAT BRACKET AND
MOUNTING HARDWARE. MOUNT BELOW
EXTERIOR CANOPY.
6 PROVIDE GUEST WIFI WIRELESS ACCESS POINT.
7 PROVIDE DATA RECEPTACLE FOR WALL
MOUNTED PHONE WITH PHONE MOUNT
FACEPLATE.
8 PROVIDE FOUR (4) 4" CONDUIT STUB UPS WITH
NYLON BUSHINGS. STUB UP CONDUIT A MINIMUM
OF 3" AFF.
9 PROVIDE 30"D x 84"H X 23"W 4 POST CHANNEL
RACK (BOD LEGRAND MM2072438-W)
10 PROVIDE THREE (3) VERTICAL WIRE MANAGERS
WITH FRONT DOOR (BOD MM20VMD706-W).
11 PROVIDE PRIMARY BONDING BUSBAR. BOND
BUSBAR TO INTERSYSTEMS BONDING BAR IN
ELECTRICAL ROOM 24.
12 PROVIDE 4"H x 12"W WIRE BASKET CABLE TRAY.
13 PROVIDE TWO (2) 4" CONDUIT PATHWAY WITH
NYLON BUSHING.
14 PROVIDE 2 GANG WALL BOX WITH KNOCKOUTS
RANGING FROM 3/4" TO 2" (BOD LEGRAND EFSB2).
RUN TWO (2), CAT 6A RATED, UTP CABLES FROM
THE TR AND TERMINATE BOTH CABLES ON TWO
(2) RJ45, KEYSTONE JACKS INSIDE THE WALL BOX.
RUN ONE (1) HDMI CABLE AND TWO (2) SPARE
PULL CORDS IN CONDUIT FROM THE DESIGNATED
WORK STATION TO THE WALL BOX.
15 RUN ONE (1) HDMI CABLE FROM THE SMART
BOARD WALL BOX TO THIS WORK STATION IN ONE
CONTINUOUS RUN OF CONDUIT. PROVIDE WALL
BOX AND FACEPLATE AT THE WORKSTATION.
16 PROVIDE WALL MOUNTED DOME LIGHT ABOVE
DOOR.
17 INTERIOR, DOME CAMERA. PROVIDE CORNER
BRACKET MOUNTING HARDWARE. MOUNT
APPROXIMATELY 10'-0" ABOVE FINISHED FLOOR.
A.
B.
C.
D.
UPON COMPLETION CONTRACTOR SHALL TEST
AND INSPECT ALL SYSTEMS FOR REQUIRED
FUNCTIONS AND DEMONSTRATE TO THE COR AND
VA SPECIFICATIONS.
COORDINATE WITH ARCHITECTURAL AND
INTERIOR ELEVATIONS FOR EXACT LOCATION AND
ELEVATION OF DEVICES.
PROVIDE TWO (2) MPTL PER WIRELESS ACCESS
POINT (VA OIT NETWORK AND GUEST WIFI) ABOVE
CEILING.
WIRE BASKET CABLE TRAY IS SHOWN AS A SINGLE
LINE IN THE FIRST FLOOR TECHNOLOGY PLAN FOR
VISIBILITY PURPOSES. PROVIDE 4"D x 12"W CABLE
TRAY IN THE AREAS SHOWN.
Scale: 1/4" = 1'-0"2 TELECOM ROOM ENLARGEMENT PLAN
Scale: 1/4" = 1'-0"
TELECOM ROOM CEILING
ENLARGEMENT PLAN3
N O
R
TH
0 2 4 8
N O
R
TH
0 2 4 8
SEAL
057626
P
ROFESSIONAL
A N
D
RE W D. RICHA
R D
S
N O
RT H C A R OLIN
A
E N G IN E E R
1/27/20251/27/2025
4" SQUARE BOX WITH LOCKING
RECEPTACLE, NEMA TYPE AS
INDICATED ON SHEET ET501.
4X4 BOX WITH COVER
15' CORD AND PLUG SUPPLIED
WITH Z-PDU
TELECOM
DATA
RACK
CABLE TRAY
SUPPORT THE BOX FROM THE
CABLE TRAY OR CHANNEL
STEEL SUPPORTS AND LOCATE
ABOVE THE RACK.
PACS
CONTROLLER
PACS
POWER
SUPPLY
PACS 8"x8"x6' HINGED TROUGH
8'x8'x3/4" FIRE
RATED PLYWOOD
PACS 6"x6"x6'
HINGED
VERTICAL
TROUGH
FIRE ALARM
ADDRESSABLE
RELAY OUTPUT
MODULE
1" CONDUIT FROM
EACH PACS DOOR
1" CONDUIT FROM
EACH PACS DOOR
20A, 110V, (1) 4S-JBOX
16" AFF IN CENTER OF
PLYWOOD
PACS
CONTROLLER
PACS
POWER
SUPPLY
J
1" NIPPLE (TYP)
SEE ELECTRICAL PLANS
FOR CIRCUITING
INFORMATION
FINISHED FLOOR
MOUNT AT HEIGHT EQUIVALENT TO
ADJACENT POWER, NOMINALLY 18" AFF
SURFACE MOUNT BOX
FOR DATA
RECEPTACLES
COMMUNICATIONS SYSTEMS'
SURFACE RACEWAY
WALL
CORRIDORROOM
SUSPENDED LAY-IN
CEILING
CABLE TRAY
GROUND CONDUIT TO
CABLE TRAY
GROUND SURFACE MOUNT
RACEWAY TO CONDUIT
1 1/4" CONDUIT A.
B.
C.
D.
NOTES:
BASIS OF DESIGN FOR SURFACE RACEWAY IS HUBBELL
P/N HBL2000A OR WIREMOLD 2400 SERIES.
CONTRACTOR SHALL PROVIDE A COMPLETE SURFACE
RACEWAY. PRIOR TO PROCUREMENT, CONTRACTOR
SHALL SUBMIT SAMPLES AND ATTAIN SOLUTIONS'
APPROVAL FROM VA COR.
ONE AND A QUARTER INCH CONDUIT NOTED SHALL BE
EXTENDED TO THE CABLE TRAY FROM THE ROOM AND
TERMINATE ON BOTH ENDS WITH A NYLON BUSHING.
COORDINATE LOCATION WITH ALL TRADES.
THIS TYPICAL IS DIAGRAMMATIC IN NATURE. COORDINATE
THE LOCATION OF EACH OUTLET ACCORDING TO THESE
SPECIFICATIONS AND DRAWING REQUIREMENTS IN FULL.
PROVIDE 5% GRADE
MIN 36" ON ALL SIDES LID LABLED 'SIGNAL'
POLYMER CONCRETE
UNDERGROUND ENCLOSURE,
MINIMUM SIZE 30"LX42"WX48"D
RIGID PVC CONDUIT ELBOW (MIN
RADIUS PER NEC OR MINIMUM
CABLE INSTALLATION BEND
RADIUS, WHICHEVER IS GREATER)
INCLUDE BELL ENDS AT THE END
OF THE CONDUIT ELBOW WITHIN
THE HANDHOLE WHEN REQUIRED.
STUB UP MIN 2" ABOVE GRAVEL. SEAL WITH
NON-HARDENING DUCT SEAL TO PREVENT
GRAVEL FROM ENTERING CONDUIT
COMPACTED BACKFILL
#57 STONE
CONNECTOR
PVC OR HDPE
CONDUIT
4" MIN
6" MIN
6" MINA.
B.
DETAIL NOTES:
DO NOT INSTALL IN VEHICULAR
TRAFFIC AREAS.
SEE TECHNOLOGY SITE PLANS
FOR AMOUNT OF CONDUITS
4" CONDUIT
CONCRETE FILL
BASE AND SPACERS
PLACED EVERY 5' ON
CENTER
FINISHED GRADE
CONCRETE TOP
(REFERENCE CIVIL
PAVING DETAILS)
75MM (3")
MINIMUM
75MM (3") MINIMUM
75MM (3")
MINIMUM
FINISHED FLOOR
MOUNT AT HEIGHT
EQUIVALENT TO ADJACENT
POWER, NOMINALLY 18" AFF
4-11/16" SQ. BY 2-1/2"
DEEP BOX WITH SINGLE
GANG 5/8" TILE RING.
1-1/4" CONDUIT WITH
COMMUNICATIONS WIRING
WALL
CORRIDORROOM
6" MIN NYLON BUSHING
COORDINATE WITH DUCTWORK
EXTEND CONDUIT TO ABOVE
FINISHED ACCESSABLE
CEILING IN CORRIDOR TO
CABLE TRAY UNLESS NOTED
OTHERWISE.
SUSPENDED LAY-IN CEILING
CABLE TRAY
GROUND CONDUIT TO
CABLE TRAY
WALL TERMINATION BRACKET
BOD: CABLOFIL HB2
WALL BRACKET
BOD: CABLOFIL
FASUCB300PG
1.
2.
3.
4.
5.
DETAIL NOTES:
REFERENCE PLANS FOR WIRE MESH CABLE TRAY DIMENSIONS.
BOLT TO FLOOR & WALL PER MANUFACTURERS' INSTRUCTIONS.
BOND ALL CONDUIT CONNECTED TO WIRE MESH CABLE TRAY PER MANUFACTURER'S INSTRUCTIONS.
CONDUIT SLEEVES WITH NYLON BUSHINGS FOR NON-RATED WALL ASSEMBLIES. STI EZ-PATH SERIES
33 OR APPROVED EQUIVALENT FOR FIRE/SMOKE RATED WALLS.
WATERFALL LOCATIONS SHOWN ARE TYPICAL LOCATIONS. COORDINATE THE BEST LOCATION TO
DIRECT CABLING DOWN TO THE CHANNEL RACKS BELOW.
CONDUIT SLEEVES
WITH NYLON BUSHING
BOD: CABLOFIL WPS
TELECOM ROOM CORRIDOR
BOND CABLE TRAYS
WATERFALL BOD:
BDOPG OR SDO300PG
FOR OVER THE SIDE
AND LARGE QUANTITIES.
SPLICE WASHER KIT
BOD: CABLOFIL
SWKIN316
CORNER BRACKET
BOD: CABLOFIL EZT90EZ
WALL BRACKET
BOD: CABLOFIL
FASUCB300PG
WALL BRACKET
BOD: CABLOFIL
FASUCB300PG
WALL BRACKET
BOD: CABLOFIL
FASUCB300PG
TRAPEZE SUPPORT
BOD: CABLOFIL
FASP400PG @ 4'-0" O.C.
CHANNEL
RACK
CHANNEL
RACK
CHANNEL
RACK
CORNER BRACKET
BOD: CABLOFIL
EZT90EZ
TRAPEZE SUPPORT
BOD: CABLOFIL
FASP400PG @ 4'-0" O.C.
CORNER BRACKET
BOD: CABLOFIL
EZT90EZ
CORNER BRACKET
BOD: CABLOFIL
EZT90EZ
Engineers Architects Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: ARCHITECT/ENGINEER OF RECORD
Date Checked Drawn
FULLY SPRINKLERED
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
ACG Project Number
1/
/2
1:
:1
PM
C :\U se rs
\n ju si \D oc um en ts
\E _2
2-
1-
BC
LC
V
A-
BL
D G
_n ju si .rv t
T-501
TECHNOLOGY DETAILS
3 6LAS
REPLACE BUILDING 121
MICHAEL E. DEBAKEY VAMC
2002 HOLCOMBE BOULEVARD
HOUSTON, TX 77030 JANUARY 24, 2025
100% CONSTRUCTION DOCUMENTS
580-324
ADR
22-021
Scale: No Scale4 DATA CABINET PLUG CONNECTION
Scale: No Scale5 DOOR CONTROLLER ELEVATION
Scale: No Scale2 TELECOMMUNICATIONS SURFACE MOUNT OUTLET INSTALLATION
Scale: No Scale3 TELECOMMUNICATIONS HANDHOLE
Scale: No Scale1 TELECOMMUNICATIONS DUCT BANK DETAIL
Scale: No Scale6 TELECOMMUNICATIONS OUTLET INSTALLATION IN NEW WALLS
Scale: No Scale7 TELECOM ROOM WIRE MESH CABLE TRAY DETAIL
SEAL
057626
P
ROFESSIONAL
A N
D
RE W D. RICHA
R D
S
N O
RT H C A R OLIN
A
E N G IN E E R
A
B
B
A.
B.
C.
4 - 5 FEET
LESS THAN 1 FOOT
GREATER THAN 3
INCHES
CEILING
C
TYPICAL J-HOOK
0'-4"
1'-8"
ANSI/EIA/TIA COMPLIANT BUSBAR
1.
2.
3.
4.
5.
DETAIL NOTES:
0.25" THICK
MOUNT WITH 2" CLEARANCE BETWEEN REAR OF THE
BUSBAR AND THE WALL.
MOUNTED ON LISTED INSULATORS
PBB (20"W x 4"H)
SBB (12"W x 4"H)
1.
2.
3.
4.
5.
6.
7.
NOTES:
ALL CONNECTIONS TO THE PBB AND SBB SHALL BE MADE WITH
COMPRESSION STYLE LONG BARREL CONNECTORS ON THE
CONDUCTOR AND 2-LUG BOLTED CONNECTIONS TO THE
GROUNDING BUS BARS. CONNECTIONS TO STEEL SHALL BE
WITH SILICON BRONZE HARDWARE. CONNECTION TO SLEEVES
OR CONDUITS SHALL BE BY AN APPROVED GROUNDING
BUSHING.
LOCATE PBB AND SBB ON THE LEFT AND 12" AFF.
ALL CONDUCTORS USED FOR GROUNDING SHALL BE MARKED
AT CONNECTION POINT AND EVERY TWENTY FEET (20')
THEREAFTER WITH A LABEL IDENTIFYING IT AS THE
TELECOMMUNICATIONS BONDING BACKBONE (TBB)
CONDUCTOR. USE PANDUIT #LTYK OR APPROVED EQUIVALENT.
REFERENCE SPECIFICATIONS REGARDING PBB.
REFERENCE SPECIFICATIONS REGARDING SBB.
CONTRACTOR SHALL CLEAN THE GROUNDING BUS BAR AND
APPLY ANTI-OXIDANT PRIOR TO FASTENING THE CONNECTORS
TO THE GROUNDING BUS BAR.
ALL COPPER BACKBONE CABLING SHALL MEET THE
REQUIREMENTS OF TIA/EIA 568-C FOR RISER CABLE.
C O
M M
. E Q
U
IP
M
EN
T/ R
AC
KS
M
ET
AL
S
LE
EV
ES
(W
IT
H
IN
C
O M
M . R
M
ST
R
U C
TU
R
AL
S
TE
EL
W
IR
E M
ES
H
C
AB
LE
T
R
AY
MAIN
PBB (PRIMARY BONDING BUSBAR)
PROVIDE 6 AWG
CONDUCTOR, EACH
RUN
PROVIDE 4/0 AWG
CONDUCTOR TO GROUND
RING FOR ELECTRICAL
SYSTEM
EL
EC
TR
IC
AL
P
AN
EL
FINISHED FLOOR
CR
ES DC
RX
ELECTRONIC
LOCKING
MECHANISM
3/4" C 3/4" C
3/4" C
FINISHED CEILING
1" C
TO ACCESS CONTROL
SYSTEM PANEL (PACS),
VERIFY LOCATION
ESDC
3/4" C
3/4" C
3/4" C
CARD READER IN SINGLE
GANG BACK BOX, FACING
TOWARDS UNSECURED
SIDE OF DOOR
H
EI
G H
T
PE
R L
EG
EN
D
DOOR CONTACT
REQUEST FOR EXIT
SENSOR(S), FACING TOWARDS
SECURED SIDE OF DOOR
1.
2.
3.
DETAIL NOTES:
ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT, BOXES, AND SUPPORTS. COORDINATE AND VERIFY LOCATIONS WITH
OWNER.
PROVIDE CABLING PER MANUFACTURER'S RECOMMENDATION.
COORDINATE PER ARCHITECTURAL PLANS & DOOR HARDWARE SCHEDULE. INDICATED AS GENERAL. PROVIDE AS INDICATED ON
PLANS
8"x8"x4" HINGED
CONTROLLER BOX
MOUNTED ABOVE CEILING
REFERENCE ELECTRICAL PLANS.
TO 120V POWER.
REFERENCE
ELECTRICAL PLANS.
FINISHED FLOOR
CR
DC
RX
1.
2.
3.
DETAIL NOTES:
ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT, BOXES, AND SUPPORTS. COORDINATE AND VERIFY LOCATIONS WITH
COR/VA.
PROVIDE CABLING PER MANUFACTURER'S RECOMMENDATION.
COORDINATE PER ARCHITECTURAL PLANS & DOOR HARDWARE SCHEDULE. INDICATED AS GENERAL. PROVIDE AS INDICATED
ON PLANS
3/4" C
3/4" C
3/4" C
8"x8"x4" HINGED
CONTROLLER BOX
MOUNTED ABOVE DOOR
1" C
TO ACCESS CONTROL
SYSTEM PANEL (PACS),
VERIFY LOCATION
CARD READER IN SINGLE GANG BOX,
OR AS REQUIRED BY
MANUFACTURER, FACING TOWARDS
UNSECURED SIDE OF DOOR
REQUEST FOR EXIT
SENSOR(S), FACING
TOWARDS SECURED
SIDE OF DOOR
ES
3/4" C
ELECTRIC STRIKE
DOOR CONTACT
TO 120V POWER.
TO PBB/SBB
TELECOMMUNICATIONS
EQUIPMENT BONDING
CONDUCTOR (TEBC)
#6 AWG, MINIMUM
IRREVERSIBLE CRIMP
CONNECTOR(TYP. ALL)
WIRE MESH CABLE TRAY
BONDING CONDUCTOR.
TYPICAL AT EACH SECTION
CONNECTION POINT
TELECOMMUNICATIONS
EQUIPMENT BONDING
CONDUCTOR (TEBC)
#6 AWG, MINIMUM
1.
DETAIL NOTES:
TEBC SHALL BE MOUNTED TO THE WIRE MESH CABLE TRAY IN SUCH A WAY, THAT THERE IS A MINIMUM OF 2" OF SEPARATION BETWEEN THE
NETWORK CABLING AND THE BONDING CONDUCTOR.
BOTTOM OF TRAY
2" MIN.
TO PBB/SBB
TELECOMMUNICATIONS EQUIPMENT BONDING
CONDUCTOR (TEBC) - #6 AWG MINIMUM
IRREVERSIBLE CRIMP
CONNECTOR(TYP. ALL)
BONDING TERMINAL
(TYPICAL AT EACH PIECE
OF EQUIPMENT)
SERVER
CABINET
FLOOR LEVEL
TWO-HOLE COMPRESSION
LUGS (RACKS NOT TO BE
MODIFIED IF ONLY ONE-
HOLE IS PROVIDED; USE
ONE-HOLE COMPRESSION
LUGS IN THIS CASE)
RACK BONDING
CONDUCTOR (RBC) #6 AWG
MINIMUM
TOP-MOUNTED RACK
BONDING BUSBAR (RBB),
ANGLED MOUNTING HOLES,
MOUNTED AT RU45
UNIT BONDING CONDUCTOR
(UBC) - #6 AWG
INDIVIDUAL EQUIPMENT
BONDING CONDUCTORS FROM
EACH PIECE OF EQUIPMENT
AND RACK TO THE RACK
BONDING CONDUCTOR
RACK BONDING CONDUCTOR
(RBC) EXTENDED TO BOTTOM
OF RACK TO ACCOMODATE
FUTURE GROWTH
RACK ISOLATION PADS
(IF APPLICABLE)
NETWORK
RACK
IRREVERSIBLE CRIMP
CONNECTOR (TYP. ALL)
Engineers Architects Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: ARCHITECT/ENGINEER OF RECORD
Date Checked Drawn
FULLY SPRINKLERED
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
ACG Project Number
1/
/2
1:
:1
PM
C :\U se rs
\n ju si \D oc um en ts
\E _2
2-
1-
BC
LC
V
A-
BL
D G
_n ju si .rv t
T-502
TECHNOLOGY DETAILS
4 6LAS
REPLACE BUILDING 121
MICHAEL E. DEBAKEY VAMC
2002 HOLCOMBE BOULEVARD
HOUSTON, TX 77030 JANUARY 24, 2025
100% CONSTRUCTION DOCUMENTS
580-324
ADR
22-021
Scale: No Scale7 "J-HOOK" SPACING REQUIREMENTS DETAIL
Scale: No Scale5 BONDING BUSBAR DETAIL
Scale: No Scale6 TELECOMMUNICATIONS GROUNDING
Scale: No Scale3 DOUBLE DOOR CARD ACCESS
Scale: No Scale4 SINGLE DOOR CARD ACCESS
Scale: No Scale1 TYPICAL WIRE MESH CABLE TRAY BONDING DETAIL
Scale: No Scale2 TYPICAL BONDING REQUIREMENTS FOR IT EQUIPMENT ENCLOSURES
SEAL
057626
P
ROFESSIONAL
A N
D
RE W D. RICHA
R D
S
N O
RT H C A R OLIN
A
E N G IN E E R
MINIMUM OF FOUR
CATEGORY 6A 8P8C
OUTLETS FOR DATA
OR TELEPHONY.
ONE CATEGORY 6A
8P8C OUTLET
ACTIVE FOR
TELEPHONY
SINGLE GANG WORKBOX
WITH TWO CONNECTOR
CHASSIS
FOUR CATEGORY 6A 8P8C
OUTLETS ACTIVE FOR
TELEPHONY / DATA.
FOUR POSITION FACEPLATE MOUNTED
ON SINGLE GANG WORKBOX. FACEPLATE
COLOR SPECIFIED BY OTHERS.
SINGLE GANG WORKBOX
WITH ONE CONNECTOR
CHASSIS
TWO CATEGORY 6A 8P8C
OUTLETS ACTIVE FOR
TELEPHONY / DATA.
FOUR POSITION FACEPLATE MOUNTED
ON SINGLE GANG WORKBOX. FACEPLATE
COLOR SPECIFIED BY OTHERS.
CLAMPS
RUNWAY
STRINGER
EXTENSION
CLAMPS
FLOOR SLEEVES (REFERENCE PLANS
FOR NUMBER OF FLOOR SLEEVES)
3" MIN
1.
2.
DETAIL NOTES:
REFERENCE PLANS FOR LADDER/TRAY DIMENSIONS.
BOLT TO FLOOR & WALL PER MANUFACTURERS' INSTRUCTIONS.
BONDING CONDUCTOR TO S.B.B.
CABLE LADDER
BOD:CABLOFIL
09-8104-0010-12BK
4"
3.94"
A 1.97" 118.2"
1.
DETAIL NOTE:
PROPOSED WIRE MESH CABLE TRAY: B.O.D. - LEGRAND CABLOFIL BDOPG OR
SDO300PG FOR OVER THE SIDE AND LARGE QUANTITIES. 4" DEEP X 12" WIDE
MINIMUM (SIZE COMMENSURATE WITH DISTRIBUTION REQUIREMENT)
CARBON STEEL, ELECTROPLATED ZINC FINISH ASTM A510 MATERIAL.
PROVIDE TRAY INSERT
WIRE MESH
CABLE TRAY
WATERFALL
RADIUS NO LESS THAN 8"
ANGLE NO LESS THAN 90 DEGREES
1'
0"
1' - 0"1' - 0"
0'
LAY-IN CEILING
1.
2.
3.
4.
NOTES:
BUILDING STRUCTURE.
TRAPEZE SUPPORT.
THREADED SUPPORT ROD WITH BUSHING AND NUTS.
WIRE MESH CABLE TRAY.
1/2" THREADED
SUPPORT RODS
@ 4'-0" O.C.
C-CLAMP TO
BLOCKING
CABLE RUNWAY. SEE
PLAN FOR LOCATION.
1/2' THREADED
SUPPORT RODS
@ 4'-0" O.C.
C-CLAMP TO
BLOCKING
WIRE MESH CABLE
TRAY RUNWAY. SEE
PLAN FOR LOCATION.
TRAPEZE SUPPORT
@ 4'-0" O.C.
BOD: CABLOFIL
FASP 400PG
NUT
ANCHOR TO STRUCTURE
4'-0" MAX. CABLE TRAY WIDTH
1.
2.
DETAIL NOTES:
DETAIL BASED ON 75 LBS RATED CAPACITY.
PROVIDE A MINIMUM OF 12" ABOVE THE CABLE TRAY PER TIA/EIA 569-B PARAGRAPH 4.5.6.2. CONTRACTOR TO NOTIFY COR WHEN
CLEARANCE DIMENSIONS CANNOT BE MET.
MINIMUM CLEARANCE
PER TIA/EIA 569-B
Example: 2 C A101 04
JACK #
ROOM #
UNIT # (IF APPLICABLE)
FLOOR #
Example: B01 F2 IT102 B A 02
BLDG # (IF APPLICABLE)
FLOOR # (IF APPLICABLE)
TELECOM CLOSET #
IT CLOSET LOCATION (UNIT B)
PATCH PANEL #
PORT #
FINISHED FLOOR
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
TYPICAL DATA RACK DETAIL NOTES:
TR CHANNEL RACK. 30" DEEP. PROVIDE TWO.
PROVIDE 6" WIRE MANAGER ON EACH END OF RACK ROWS
AND 6" WIRE MANAGER BETWEEN RACKS. PROVIDE THREE.
PROVIDE FIBER PATCH PANEL (1U) AND MPO CASSETTES
FOR CONNECTION TO FIBER BACKBONE AS SHOWN IN
RISER DIAGRAMS. PROVIDE FIBER PATCH PANEL IN RACK 1.
48 PORT COPPER ANGLED PATCH PANEL (1 RU), DATA.
PROVIDE A TOTAL OF 12.
OIT PROVIDED SWITCHES AS REQUIRED (5 STANDARD -
MAXIMUM OF 6).
RACK BONDING BUS MOUNTED AT RU45 (NOT SHOWN). SEE
RACK BONDING DETAIL. PROVIDE TWO.
UNINTERRUPTIBLE POWER SUPPLY (UPS). PROVIDE TWO.
PROVIDE BLANKING PANELS FOR ALL EMPTY SPACES.
HORIZONTAL WIRE MANAGEMENT 1RU. PROVIDE 4.
HORIZONTAL WIRE MANAGEMENT 2RU. PROVIDE 4.
1 2
TOP THIRD
(RUs 31-45)
DESIGNATED FOR
PASSIVE
DISTRIBUTION
(PATCH PANELS)
MIDDLE THIRD
(RUs 16-30)
DESIGNATED FOR
ACTIVE
DISTRIBUTION
(SWITCHES) AND
OTHER ACTIVE
EQUIPMENT
BOTTOM THIRD
(RUs 1-15)
DESIGNATED FOR
POWER
DISTRIBUTION
EQUIPMENT (AND IN
SMALLER TRs, ACTIVE
FMS/BIOMED
EQUIPMENT)
A-SIDE FIBER
ROUTED THIS SIDE
B-SIDE FIBER
ROUTED THIS SIDE
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Engineers Architects Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: ARCHITECT/ENGINEER OF RECORD
Date Checked Drawn
FULLY SPRINKLERED
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
ACG Project Number
1/
/2
1:
:1
PM
C :\U se rs
\n ju si \D oc um en ts
\E _2
2-
1-
BC
LC
V
A-
BL
D G
_n ju si .rv t
T-503
TECHNOLOGY DETAILS
5 6LAS
REPLACE BUILDING 121
MICHAEL E. DEBAKEY VAMC
2002 HOLCOMBE BOULEVARD
HOUSTON, TX 77030 JANUARY 24, 2025
100% CONSTRUCTION DOCUMENTS
580-324
ADR
22-021
Scale: No Scale1 TYPICAL WORK FLOOR MOUNT OUTLET
Scale: No Scale2 TYPICAL WALL MOUNT PHONE VOIP OUTLET
Scale: No Scale3
TYPICAL HIGH DENSITY WALL MOUNTED WORK AREA
OUTLET CONFIGURATION
Scale: No Scale4
STANDARD DENSITY WALL MOUNTED WORK AREA OUTLET
CONFIGURATION
Scale: No Scale5 CABLE DETAILS
Scale: No Scale6 BONDING CONDUCTOR BEND RADIUS
Scale: No Scale7 CABLE TRAY SUPPORTS
Scale: No Scale8 IT CLOSET LABELING SCHEME Scale: No Scale9 JACK LABELING SCHEME
Scale: No Scale10 TYPICAL DATA RACK ELEVATION
SEAL
057626
P
ROFESSIONAL
A N
D
RE W D. RICHA
R D
S
N O
RT H C A R OLIN
A
E N G IN E E R
TO TELECOM
GROUNDING BUS
SSTV EQUIPMENT
CABINET (WALL
MOUNTED
1.
2.
3.
4.
DETAIL NOTES:
4 PR UTP (<295')
FIBER (>295')
PROVIDE CONDUIT/RACEWAY SYSTEM FROM CAMERA TO
SSTV EQUIPMENT CABINET.
ALL CAMERAS SHALL BE MULTI SENSOR AND SHALL MEET
NDAA REQUIREMENT.
TO OIT ROOM, 12 STRAND MM
FIBER (OM4) 4-4 PR UTP
TO PHYSICAL ACCESS CONTROL
SYSTEM (PACS) EQUIPMENT
20A, 120V
MS
TO GROUNDING BUS
TO DATA NETWORK/TELECOM
ROOM
PHYSICAL
ACCESS
CONTROL
PANEL(S) SEE
PACS WALL
ELEVATION FOR
MORE INFO
4 PR UTP
1" C
120V, 20A CIRCUIT, SEE
ELECTRICAL PLANS FOR
DETAILS
TO SECURITY CAMERA/
CCTV SYSTEM
TO FIRE ALARM
CONTROL PANEL
8"x8"x4" HINGED
CONTROLLER BOX
(TYPICAL FOR
EACH PACS
DOOR)
TO PACS DOORS
SEE DOOR CARD
ACCESS DETAILS FOR
MORE INFORMATION
TO GROUNDING BUS
S S S S SS
TO EXISTING PAMNS HEAD
END EQUIPMENT
TO TELEPHONE
SYSTEM INTERFACE
PAMNS (PUBLIC
ADDRESS MASS
NOTIFICATION
SYSTEM) CABINET
WITH AMPLIFIERS,
POWER SUPPLY,
AND RELATED
EQUIPMENT
C
PUBLIC
ANNOUNCEMENT
CONSOLE
MAXIMUM OF TEN
(10) SPEAKERS
PER ZONE
1.
DETAIL NOTES:
SPEAKERS SHALL HAVE DUAL COIL AND TRANSFORMER.
120V
JJ J J
V
VOLUME CONTROL
TO FIRE ALARM
SYSTEM INTERFACE
1.
2.
3.
4.
5.
6.
TYPICAL NURSE CALL SYSTEM RISER NOTES:
NURSE CALL AUSTCO EQUIPMENT CABINET
NURSE CALL CABLE, 4 PR CAT 6 OR PER MANUFACTURER'S
RECOMMENDATIONS.
NURSE CALL POWER CABLE, 2-14 AWG IN 3/4" CONDUIT OR PER
MANUFACTURER'S RECOMMENDATIONS. REQUIRED ON FIRST DOME
LIGHT OR DOMELESS CONTROLLER OF EVERY SIX CONSECUTIVE
DOME LIGHTS OR DOMELESS CONTROLLERS ON CHAIN.
NURSE CALL MULTI-COLOR DOME LIGHT.
NURSE CALL EMERGENCY STATION PULL CORD STATION (WITH
AUDIO).
NURSE CALL MASTER CONSOLE STATION (TOUCH SCREEN).
TO TELECOM
ROOM
NURSE CALL
EQUIPMENT
CABINET
TO GROUNDING
BUS
1.
2.
3.
GENERAL NURSE CALL SYSTEM RISER NOTES:
PROVIDE 1" CONDUIT FROM EACH DEVICE STUBBED UP ABOVE CEILING.
PROVIDE A COMPLETE RACEWAY SYSTEM FOR THE NURSE CALL
SYSTEM IF CABLE TRAY IS NOT AVAILABLE.
CONTRACTOR SHALL VERIFY RACEWAY REQUIREMENT WITH THE
NURSE CALL SYSTEM MANUFACTURERS.
E
M
TO NEXT
DOME LIGHT
N4
GRADE
NEW TR 42
NEW HHEXISTING MH
NEW
FACP
ROOM 24
EXISTING BUILDING 121
GRADE
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
RISER NOTES:
EXISTING CONDUIT AND CABLING CONTINUES THROUGH THE EXISTING CONDUIT DUCTBANK BACK TO B100.
NEAREST EXISTING MANHOLE.
FUSION SPLICE NEW FIBER CABLE TO EXISTING FIBER CABLING RETAINED DURING DEMOLITION. PROVIDE WATER
PROOF SPLICE ENCLOSURE.
PROVIDE NEW FIBER CABLE FROM THE NEAREST EXISTING MANHOLE TO THE NEW BUILDING 121. ROUTE CABLING THROUGH THE NEW HANDHOLE. PROVIDE 20'-0" CABLE SLACK IN HANDHOLE. LOOP, BUNDLE, AND LABEL CABLING.
INTERCEPT EXISTING CONDUIT RETAINED DURING DEMOLITON AND EXTEND CONDUIT TO NEW HANDHOLE LOCATION. NEW CONDUIT SHALL BE ENCASED IN CONCRETE. SEE TELECOMMUNICATIONS DUCT BANK DETAIL ON
SHEET T-501.
PROVIDE NEW HANDHOLE. BOD OLD CASTLE 3030-LA.
CONCRETE ENCASE CONDUIT UP TO THE BUILDING ENVELOPE.
PROVIDE NEW FIBER CABLING TO TR 42 AND THE NEW FACP IN ELECTRICAL ROOM 24. MATCH EXISTING CABLING.
ASSUME ONE (1) 24 STRAND, OS2, INTERLOCKING ARMOR, INDOOR-OUTDOOR RATED, TIGHT BUFFERED FIBER OPTIC CABLE FOR THE TR AND ONE (1) 12 STRAND, OS2, INTERLOCKING ARMOR, INDOOR-OUTDOOR RATED, TIGHT
BUFFERED FIBER CABLE FOR THE FACP.
NEW TR WITH CONDUIT STUB UPS.
NEW FIRE ALARM CONTROL PANEL IN ELECTRICAL ROOM 24.
NEW BUILDING 121.
3 4
10 11
6 7
GRADE
EXISTING
BUILDING
OIT ROOM
EXISTING
HH-OCEXISTING MH
EXISTING
FACP
EXISTING BUILDING 121
GRADE
1.
2.
3.
4.
5.
6.
7.
8.
9.
RISER NOTES:
EXISTING CONDUIT AND CABLING CONTINUES THROUGH THE EXISTING CONDUIT DUCTBANK BACK TO B100.
NEAREST EXISTING MANHOLE.
CAP, LABEL, AND RETAIN CABLING IN EXISTING MANHOLE FOR RE-USE. REFERENCE PARTIAL OSP RISER DIAGRAM
FOR MORE INFORMATION.
DEMOLISH EXISTING FIBER CABLING SERVING EXISTING BUILDING 121 BACK TO THE NEAREST MANHOLE. CONDUIT
TO REMAIN FOR RE-USE. REFERENCE PARTIAL OSP RISER DIAGRAM FOR MORE INFORMATION.
DEMOLISH EXISTING HANDHOLES AND CONDUIT BACK FROM EXISTING PERIMETER APPROXIMATELY 10'-0" FROM THE EXISTING BUILDING ENVELOPE. CAP CONDUIT AND PRESERVE FOR RE-USE. REFERENCE PARTIAL OSP RISER
DIAGRAM FOR MORE INFORMATION.
EXISTING FIBER CABLING SERVING OIT ROOM AND FACP TO BE DEMOLISHED BACK TO THE NEAREST EXISTING
MANHOLE.
EXISTING OIT ROOM TO BE DEMOLISHED.
EXISTING FIRE ALARM CONTROL PANEL TO BE DEMOLISHED.
EXISTING BUILDING 121 TO BE DEMOLISHED.
3 4
8 9
Engineers Architects Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: ARCHITECT/ENGINEER OF RECORD
Date Checked Drawn
FULLY SPRINKLERED
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
ACG Project Number
1/
/2
1:
:1
PM
C :\U se rs
\n ju si \D oc um en ts
\E _2
2-
1-
BC
LC
V
A-
BL
D G
_n ju si .rv t
T-601
TECHNOLOGY RISERS
6 6LAS
REPLACE BUILDING 121
MICHAEL E. DEBAKEY VAMC
2002 HOLCOMBE BOULEVARD
HOUSTON, TX 77030 JANUARY 24, 2025
100% CONSTRUCTION DOCUMENTS
580-324
ADR
22-021
Scale: No Scale1 SSTV SYSTEM RISER DIAGRAM
Scale: No Scale2 PHYSICAL ACCESS CONTROL SYSTEM (PACS) RISER DIAGRAM
Scale: No Scale3 PAMS RISER DIAGRAM
Scale: No Scale5 NURSE CALL RISER DIAGRAM
Scale: N.T.S.4 PARTIAL OSP RISER DIAGRAM
Scale: N.T.S.6 PARTIAL OSP RISER DEMOLITION DIAGRAM
SEAL
057626
P
ROFESSIONAL
A N
D
RE W D. RICHA
R D
S
N O
RT H C A R OLIN
A
E N G IN E E R
FIRE ALARM PULL STATION
SYMBOL HEIGHT DESCRIPTION
F 42"-48"
F FIRE ALARM STROBE
FIRE ALARM SPEAKER AND STROBE
90"
90"
XX - CANDELA
XX - CANDELA
XX - WATTAGEF
S
FIRE ALARM PHOTOELECTRIC SMOKE DETECTOR
FIRE ALARM HEAT DETECTORHD
SD CEILING
CEILING
DD FIRE ALARM DUCT SMOKE DETECTOR
FIRE ALARM CONTROL PANEL
FIRE ALARM NAC PANEL
FIRE ALARM ANNUNCIATOR PANEL
FLOW SWITCH
FACP
NAC
FAAP
TAMPER SWITCH
6'
6'
6'
FIRE ALARM GRAPHIC ANNUNCIATOR PANELFAGAP 6'
REMOTE LIGHT/TEST SWITCH FOR DUCT DETECTORS6'
RELAYSR 60"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
1.
A.
B.
C.
D.
E.
F.
G.
H.
I.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
PROVIDE FIRE ALARM SYSTEM AND COMPONENTS COMPLYING WITH THE LATEST:
NFPA 13- STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS.
NFPA 14- STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEM.
NFPA 20- STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION.
NFPA 70 NATIONAL ELECTRICAL CODE.
NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE.
NFPA 90A STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS.
NFPA 101 LIFE SAFETY CODE.
VA FIRE PROTECTION DESIGN MANUAL.
ANSI S3.41 AUDIBLE EMERGENCY EVACUATION SIGNAL.
FIRE ALARM SYSTEM SHALL COMPLY WITH FACTORY MUTUAL RESEARCH CORPORATION (FM).
PROVIDE FIRE ALARM WIRING IN CONDUIT, FACTORY PAINTED RED.
BEFORE STARTING WORK, TEST EXISTING FIRE ALARM SYSTEM IN WORK AREA AND ADJACENT AREAS.
NOTIFY COR REGARDING DEFICIENCIES AND NON-OPERATING COMPONENTS. VA WILL MAKE REPAIRS.
CONTRACTOR TO ENSURE THAT ALL NEW FIRE ALARM SPEAKERS, TONES, AND STROBES ARE IN-SYNC WITH ALL ADJACENT AREAS BEYOND THE AREA OF WORK. WHEN WORK IS COMPLETE, TEST EXISTING FIRE ALARM SYSTEM IN WORK
AREA AND ADJACENT AREAS.
MAKE REPAIRS TO RESOLVE INCORRECT SYSTEM OPERATIONS AT NO ADDITIONAL COST.
THE FIRE ALARM SYSTEM VENDOR/CONTRACTOR SHALL TERMINATE, TEST AND PROGRAM ALL NEW FIRE ALARM DEVICES.
COORDINATE WITH COR.
CONNECT SPRINKLER SYSTEM SUPERVISORY DEVICES TO THE FIRE ALARM SYSTEM. COORDINATE LOCATION WITH THE
SPRINKLER CONTRACTOR.
CONNECT ALL ELECTROMAGNETIC DOOR HOLD OPEN DEVICES TO THE FIRE ALARM SYSTEM. COORDINATE WITH THE
DOOR HARDWARE CONTRACTOR.
PROVIDE RELAY CONTROL MODULES FOR PACS, COORDINATE WITH PHYSICAL ACCESS CONTROL SYSTEM (PACS), CONTRACTOR AND COR.
PROVIDE RELAY CONTROL MODULES FOR COOKING POWER SUPPLY SHUT OFF.
PROVIDE RELAY CONTROL MODULES FOR KITCHEN HOOD FIRE SUPPRESSION SYSTEM.
THE OPERABLE PART OF A MANUAL ACTUATED ALARM INITIATING DEVICE SHALL BE NOT LESS THAN 42" (1.07M) AND NOT
MORE THAN 48" (1.22M) FROM FINISH FLOOR.
FOR LOCATION (CORRIDOR, ROOM OR ADJACENT SPACE) WITH TWO OR MORE VISIBLE FIRE ALARM NOTIFICATION APPLIANCES WITHIN THE FIELD OF VIEW, PROGRAM VISIBLE TO FLASH IN SYNCHRONIZATION.
ACC ACCESSIBLE
ACLG ABOVE CEILING
A/E ARCHITECT/ENGINEER
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AL ALUMINUM
ALTALTERNATE
AMP AMPERE
APPRX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
BOD BASIS OF DESIGN
C CONDUIT
CAB CABINET
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
CO CONTRACTING OFFICE
COR CONTRACTING OFFICER
REPRESENTATIVE
dB DECIBEL
DN DOWN
DVC DIGITAL VOICE COMMAND
E EXISTING DEVICES
ELEV ELEVATOR
ETR EXISTING TO REMAIN
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FAAP FIRE ALARM ANNUNCIATOR PANEL
FAGAP FIRE ALARM GRAPHIC
ANNUNCIATOR PANEL
FO FIBER OPTIC
J-BOX JUNCTION BOX
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MECH MECHANICAL
MFR MANUFACTURER
MINMINIMUM
MISC MISCELLANEOUS
MT MOUNT
N NEW DEVICES
NAC NETWORK APPLIANCE CIRCUIT
PANEL
NCA NETWORK CONTROL ANNUNCIATOR
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PIV POST INDICATING VALVE
PVC POLYVINYL CHLORIDE (CONDUIT)
QTY QUANTITY
R REMOVE AND REPLACE IN NEW
LOCATION
RCP REFLECTED CEILING PLAN
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
SC SURFACE CONDUIT
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIMSIMILAR
SPEC SPECIFICATION
SPKR SPEAKER
SR SURFACE RACEWAY
SS STAINLESS STEEL
STD STANDARD
SURF SURFACE MOUNTED
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TELTELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
TYP TYPICAL
UL UNDERWRITER'S LABORATORY
UTP UNSHIELDED TWISTED PAIR
1.
2.
3.
4.
5.
6.
7.
8.
FIRE ALARM RISER NOTES:
FIRE ALARM SYSTEM SHALL BE INTERCONNECTED WITH ACCESS CONTROL
SYSTEM TO ALLOW EGRESS DURING ALARM CONDITIONS. COORDINATE
BETWEEN ACCESS CONTROL SYSTEM AND FIRE ALARM SYSTEM
MANUFACTURERS.
ALL FIRE ALARM WIRING SHALL BE INSTALLED IN FACTORY PAINTED "RED"
EMT CONDUIT.
ALL WIRING SHALL BE AS RECOMMENDED BY THE FIRE ALARM
MANUFACTURER.
PROVIDE SEPERATE OUTPUT SIGNALS TO AIR HANDLER UNIT VFD FOR
INDIVIDUAL UNIT SHUT-DOWN.
PROVIDE ZONE ADAPTER MODULES TO CONNECT NON-ADDRESSABLE
DEVICES SUCH AS FLOW AND TAMPER SWITCHES, DOOR HOLD-OPEN
DEVICES, AND CONTROL SIGNALS.
PROVIDE POWER SUPPLY AND/OR NAC (NOTIFICATION APPLIANCE CIRCUIT)
PANEL AS REQUIRED FOR ADDITIONAL DEVICES.
PROVIDE POWER AMPLIFIERS FOR ALL SPEAKERS.
NEW FIRE ALARM EQUIPMENT SHALL MATCH THE EXISTING NOTIFIER ONYX
SERIES SYSTEM.
FS TS
TO ADDITIONAL
INDICATING
APPLIANCES
TO ADDITIONAL FLOW AND
TAMPER SWITCHES
TO ADDITIONAL
INITIATING DEVICES
NEW FIRE
ALARM
CONTROL
PANEL (FACP)
SPRINKLER SYSTEM DEVICES
F
F DD
RFOR PACS
SECURITY
SYSTEM
INTERCONNECT
FIRE ALARM
PANEL
ANNUNCIATOR
F S
F S
SD HD
DUCT SMOKE DETECTOR *
AREA SMOKE DETECTOR *
FIRE ALARM SYSTEM INPUT/OUTPUT MATRIX
OUTPUT
INPUT DEVICE
1.
S
O U
N D
G
EN
ER
AL
BU
IL
D
IN
G
A
LA
R M
F O
R
TH
ER
H
IG
H
R
IS
E (N
O N
-H
EA
LT
H
C
AR
E)
SE
E
SE
C
TI
O
N
.2 .1
2.
N
O
TI
FY
N
EC
ES
SA
R
Y
ST
AF
F
FO
R
R
ES
PO
N
SE
FO
H
EA
LT
H
C
AR
E
AN
D
H
IG
H R
IS
E
BU
IL
D
IN
G S
O N
LY
(A
LA
R
M S
IG
M
AY
B E
D
IF
FE
R
EN
T
IF
FE
R
EN
T
FL
O O
R S)
3.
N
O
TI
FY
F
IR
E
D
EP
AR
TM
EN
T
4.
IN
IT
IA
TE
SU
PE
R
VI
SO
R
Y
SI
G
TO
4-
H O
U R
M
AN
ED
PO
IN
T
FO
R
IM
M
ED
ES
PO
N
SE
5.
C
LO
SE
A
SS
O C
SM
KE
B
AR
R
IE
R D
O O
R S
O N
T H
E
FL
O O
R
6.
C
LO
SE
D
AM
PE
R
S
FA
P R
O
XI
M
AT
E
TO
ET
EC
TO
R
7.
S
H U
T D
O W
N
IR
H
AN
D
LE
R S
ER
VE
D B
Y
TH
E D
ET
EC
TO
R
8.
R
EC
AL
L
EL
EV
AT
O R
X X X
X X Xa
MANUAL PULL STATION
SPRINKLER WATERFLOW/PRESSURE SWITCH
WATER CONTROL VALVE TAMPER
* WHILE NFPA 101 DOES NOT REQUIRE SOME DETECTORS TO NOTIFY BUILDING OCCUPANTS, VA REQUIRES ALL SMOKE DETECTORS, OTHER THAN DUCT SMOKE DETECTORS, TO NOTIFY BUILDING OCCUPANTS AS REQUIRED BY THE LIFE SAFETY CODE OR ITS REFERENCES.
** THOSE DOORS THAT ARE REQUIRED TO BE TIED TO THE FIRE ALARM SYSTEM SUCH AS DELAYED EGRESS AND ACCESS CONTROLLED DOORS.
a - DO NOT PROVIDE DUCT DETECTORS IN DEDICATED (100%) EXHAUST FANS, THEY SHOULD CONTINUE TO RUN.
X
X X
X X
X
X
X
X
CONDUIT
INSTALL PER
NATIONAL
ELECTRIC CODE
AIR SUPPLY
DIFFUSER OR
RETURN AIR
OPENING
SMOKE/HEAT
DETECTOR
CEILING
FINISHED
FLOOR
NOTIFICATION DEVICE
(SPEAKER/STROBE )
STROBE
SMOKE/HEAT
DETECTOR
CONTROL PANEL
GRAPHIC
ANNUNCIATOR
MANUAL PULL
STATION
15'-0" MAX 3'-0" MIN
6" MIN 4" MIN 1'-0" MAX
96" MAX
TOP OF
LENS
80" MIN
BOTTOM OF
DEVICE
5'-6"
3'-8"
(3'-6" MIN)
(4'-0" MAX)
5'-0" MAX
EXIT
JUNCTION BOX
(SEAL TIGHT
FLEX MAX 6')
CONDUIT
JUNCTION BOX
(SEAL TIGHT
FLEX MAX 6')
5"
DOOR
WIDTH
(LESS 3")
MAGNETIC
DOOR
HOLDER
15'-0" MAX
A.
B.
DETAIL NOTES:
MOUNT ALL AUDIBLE & VISUAL DEVICES IN APPROVED FIRE ALARM BOXES.
ALL ABOVE CEILING DEVICES SHALL BE MOUNTED IN ACCESSIBLE LOCATION.
60"
KB
A.
B.
VISUAL APPLIANCES:
VISUAL APPLIANCES MIN DISTANCE IN
SLEEPING ROOMS S 24” FROM CEILING
TO TOP OF LENS FOR 110 CD STROBES
WITHIN 16’ OF THE PILLOW.
VISUAL APPLIANCES 177 CD USED IN
SLEEPING ROOMS CAN BE WITHIN 24”
MIN FROM CEILING.
Engineers Architects Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: ARCHITECT/ENGINEER OF RECORD
Date Checked Drawn
FULLY SPRINKLERED
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
ACG Project Number
1/
/2
1:
:5
PM
C :\U se rs
\n ju si \D oc um en ts
\E _2
2-
1-
BC
LC
V
A-
BL
D G
_n ju si .rv t
FA001
FIRE ALARM GENERAL NOTES,
SYMBOL LEGEND, AND RISER
1 2LAS
REPLACE BUILDING 121
MICHAEL E. DEBAKEY VAMC
2002 HOLCOMBE BOULEVARD
HOUSTON, TX 77030 JANUARY 24, 2025
100% CONSTRUCTION DOCUMENTS
580-324
ADR
22-021
FIRE ALARM SYMBOL LEGEND FIRE ALARM GENERAL NOTESFIRE ALARM ABBREVIATIONS LIST
Scale: No Scale
FIRE ALARM RISER1
Scale: No Scale3 FIRE ALARM DEVICE MOUNTING HEIGHTS
SEAL
057626
P
ROFESSIONAL
A N
D
RE W D. RICHA
R D
S
N O
RT H C A R OLIN
A
E N G IN E E R
DD
SD
F F S
F S
F F S
F
F
F
F S
F
F
FACP
FAAP
F
F S
FSFS
FS
F S
FS
F
F S
FS
F S
F S
FS
F S
F
F S
F S
F
F S
FSF S
F S
F
F
F F
FS
SD
F
SD
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
TR
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
GROUP
ROOM 2
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
OFFICE/CONSULT
TLT
OFFICE/CONSULT
HAC
STAFF TLT
TOILET
OFFICE
OFFICE
OFFICE
ELEC
SOILED
FAMILY
CONSULT
TOILET
STAFF
CONFERENCE
ROOM
OCCUPATIONAL
THERAPY
COMMUNITY
ROOM
RESOURCE/
COMPUTERS
OFFICE
FAMILY
CONSULT
EXAM
OFFICE
OFFICE
STAFF
LOUNGE
VEST
MECHANICAL
MEDS
OPEN
OFFICE
GROUP
ROOM 1
RECEPTION/CHECK-IN
VEST
WAITING
CORRIDOR
C06
CORRIDOR
C04
CORRIDOR
C05
CORRIDOR
C03 CORRIDOR
C02
CORRIDOR
C01
LOBBY
FIRE
RISER
ROOM
STORAGE
TRAINING
TLT
53B
STOR
53C
CLEAN
SUPPLY
07A
1 1.7 2 3 4 5 B.11 B.10 6
A
A.5
B
C
D
E
4.1
15cd
75cd
75cd
15cd
15cd
15cd
30cd
15cd
75cd
15cd 15cd
75cd
75cd
15cd
15cd
75cd
15cd
75cd75cd
15cd
75cd
15cd
15cd
15cd
30cd
30cd
30cd
75cd
15cd
15cd
30cd 30cd
15cd
1/2 W 1/2 W 1/2 W
1/2 W
1/2 W
1/2 W
1/2 W
1/2 W 1/2 W
1/2 W
1/2 W
1/2 W 1/2 W
1/2 W
1/2 W
1/2 W
1/2 W 1/2 W 1/2 W
1/2 W
15cd
1/2 W
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: ARCHITECT/ENGINEER OF RECORD
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
ACG Project Number
1/
/2
1:
:0
PM
C :\U se rs
\n ju si \D oc um en ts
\E _2
2-
1-
BC
LC
V
A-
BL
D G
_n ju si .rv t
FA101
FIRST FLOOR FIRE ALARM PLAN
2 2LAS
REPLACE BUILDING 121
MICHAEL E. DEBAKEY VAMC
2002 HOLCOMBE BOULEVARD
HOUSTON, TX 77030 JANUARY 24, 2025
100% CONSTRUCTION DOCUMENTS
580-324
ADR
22-021
N O
R
TH
0 4 8 16
Scale: 1/8" = 1'-0"1 FIRST FLOOR FIRE ALARM PLAN
1 PROVIDE DUCT MOUNTED SMOKE DETECTOR AND
REMOTE INDICATOR. COORDINATE LOCATION OF
REMOTE INDICATOR WITH THE COR.
2 PROVIDE TAMPER AND FLOW SWITCH.
COORDINATE EXACT LOCATION IN FIELD AND
WITH FIRE PROTECTION DRAWINGS
3 PROVIDE WALL MOUNTED SMOKE DETECTOR
WITHIN 5'-0" OF THE FAAP.
4 PROVIDE TAMPER SWITCH, TRANSIENT
ARRESTOR, AND MONITORING MODULE FOR NEW
PIV. COORDINATE EXACT LOCATION WITH CIVIL
AND FIRE PROTECTION DRAWINGS. COORDINATE
CONDUIT ROUTING WITH OTHER UNDERGROUND
UTILITIES. FIRE ALARM EQUIPMENT CABLING
CANNOT SHARE RACEWAY WITH OTHER CABLING.
5 WALL MOUNTED SPEAKER STROBE ABOVE PULL
STATION.
A.
B.
UPON COMPLETION CONTRACTOR SHALL TEST
AND INSPECT ALL SYSTEMS FOR REQUIRED
FUNCTIONS AND DEMONSTRATE TO THE COR AND
VA SPECIFICATIONS.
COORDINATE WITH ARCHITECTURAL ELEVATIONS
FOR EXACT LOCATION AND ELEVATION OF
DEVICES.
SEAL
057626
P
ROFESSIONAL
A N
D
RE W D. RICHA
R D
S
N O
RT H C A R OLIN
A
E N G IN E E R
| 11 TECH HOUSTON VA-BLDG 121 - 2.6.25 100% |