Lab Results 2785 LB 9C 30K UST DG700.pdf
PDF 69 KB Posted
- Solicitation number
- 36C26225Q0989
About this file
This document is a laboratory test report for a diesel fuel sample from California Hazardous Services, analyzed by Oil Science Laboratory with Sample ID VA Hosp LB-9C 30K. The lab conducted nine specific tests using ASTM standards, including Base, Sediment and Water percentage, Distillation characteristics, API Gravity, Cetane Index, Sulfur content, Copper Strip rating, Bacteria testing, Water content, and Flash Point. The results indicate the diesel sample meets ASTM specifications for #2 diesel, with key measurements including an API Gravity of 46.8, Cetane Index of 61.5, Sulfur content of 13.0 ppm, and a Flash Point of 133.0. The sample was taken on 12/31/24, tested on 1/13/25, and the results were delivered to Dillon Bain on the same date. The laboratory includes a disclaimer that the analysis is for informational purposes and does not guarantee against equipment failure.
View the file
Other files
Show all 43
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
California Hazardous Services Sample ID: VA Hosp LB-9C 30K
1431 E St. Andrew Place Sample Type: Diesel
Santa Ana, CA 92705 Purchase Order: DG700
Date Sample Taken: 12/31/24
Date Sample Tested: 1/13/25
Date Results Delivered: 1/13/25
Results Delivered: Dillon Bain
Results Delivered: N/A
OSL ID: 2785
Test Methods: Various ASTM
ASTM
1. Base, Sediment and Water % Volume (BS&W) D-2709
2. Distillation D-86
IBP ASTM D86 F
10% Point F
50% Point F
90% Point F
End Point F
% Residue
3. API Gravity 60F D-287
4. Cetane Index D-976
5. Sulfur (ppm) D-7039
6. Copper Strip D-130
7. Bacteria Sanicheck AB
8. Water D-7546
9. Flash Point D-93
Laboratory Results
<0.025
Based on test results sample meets ASTM specifications for #2 diesel.
This analysis is intended as an aid in a physical system/fluid review. No guarantee, expressed or implied, is made against the failure of components, engines, generators, or any othe system(s), or lack of their operation / start-up. Certain types of unusual catastrophic conditions leading to failure do not produce abnormal or severe readings. Catastrophic equipment failure can occur immediately after routine analysis. A different sample taken at the same/different time may produce different results; sample taken from different exit points, depths, or areas in the system can also produce significantly different results.
Data is provided for informational purposes only. This solely limits liability of Oil Science Laboratory for any mistakes, errors, or omissions in this analysis to the full price paid for this analysis only.
1.8
46.8
61.5
13.0
1A
Negative 0
35ppm
133.0
C u st o m e r
S a m p le D a ta
File details come from the government source that posted it. Updated .