Lab Results 2785 LB 15 1500G UST DG700.pdf
PDF 69 KB Posted
- Solicitation number
- 36C26225Q0989
About this file
This document is a diesel fuel laboratory test report from Oil Science Laboratory for a sample taken from the VA Hospital in Long Beach, California. The lab analysis tested multiple characteristics of the diesel fuel using various ASTM standard methods, including Base, Sediment and Water percentage, Distillation parameters, API Gravity, Cetane Index, Sulfur content, Copper Strip rating, Bacteria presence, Water content, and Flash Point. The results indicate the diesel sample meets ASTM specifications for #2 diesel, with specific measurements provided for each tested parameter. The sample was taken on 12/23/24, tested on 1/13/25, and is associated with Purchase Order DG700 for California Hazardous Services located in Santa Ana, CA. The laboratory includes a disclaimer noting that the analysis is informational and does not guarantee against equipment failure.
View the file
Other files
Show all 43
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
California Hazardous Services Sample ID: VA Hosp LB 15 1500G UST
1431 E St. Andrew Place Sample Type: Diesel
Santa Ana, CA 92705 Purchase Order: DG700
Date Sample Taken: 12/23/24
Date Sample Tested: 1/13/25
Date Results Delivered: 1/13/25
Results Delivered: Dillon Bain
Results Delivered: N/A
OSL ID: 2785
Test Methods: Various ASTM
ASTM
1. Base, Sediment and Water % Volume (BS&W) D-2709
2. Distillation D-86
IBP ASTM D86 F
10% Point F
50% Point F
90% Point F
End Point F
% Residue
3. API Gravity 60F D-287
4. Cetane Index D-976
5. Sulfur (ppm) D-7039
6. Copper Strip D-130
7. Bacteria Sanicheck AB
8. Water D-7546
9. Flash Point D-93
Based on test results sample meets ASTM specifications for #2 diesel.
This analysis is intended as an aid in a physical system/fluid review. No guarantee, expressed or implied, is made against the failure of components, engines, generators, or any othe system(s), or lack of their operation / start-up. Certain types of unusual catastrophic conditions leading to failure do not produce abnormal or severe readings. Catastrophic equipment failure can occur immediately after routine analysis. A different sample taken at the same/different time may produce different results; sample taken from different exit points, depths, or areas in the system can also produce significantly different results.
Data is provided for informational purposes only. This solely limits liability of Oil Science Laboratory for any mistakes, errors, or omissions in this analysis to the full price paid for this analysis only.
1.8
38.3
49.0
15.0
1A
Negative 0
31ppm
133.0
Laboratory Results
<0.025
C u st o m e r
S a m p le D a ta
File details come from the government source that posted it. Updated .