Bldg. 5A, LB9A - Secondary Containment Test (7.19.23).pdf
PDF 224 KB Posted
- Solicitation number
- 36C26225Q0989
About this file
This document is an Underground Storage Tank Secondary Containment Testing Report Form for the Veteran Affairs Long Beach Health Care System. The testing was performed by Tait Environmental Services, Inc. on 07/19/2023 for Tank #9A in Building 5B, located at 5901 E 7th St, Long Beach, CA 90822.
The report details comprehensive testing of the underground storage tank's secondary containment, including tank, piping, and sump/UDC (Under-Dispenser Containment) components. All tests were conducted using vacuum and pressure methods with test equipment including a 0-30 inHg Vacuum Gauge and 0-15 PSI Pressure Gauge. The testing covered multiple pipe runs (Supply, Return, Siphon, and Remote Fill) and sump areas, with all components passing the tightness tests. The service technician, Danny Lemos, used PEI/RP-1200 industry standard procedures and held a valid ICC (International Code Council) license expiring 04/24/2025.
View the file
Other files
Show all 43
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .