Lab Results 2785 LB 6 10K UST DG700.pdf
PDF 68 KB Posted
- Solicitation number
- 36C26225Q0989
About this file
This document is a laboratory test results report from Oil Science Laboratory (OSL) for a gasoline sample from California Hazardous Services. The sample, identified as LB 6 10K UST with Purchase Order DG700, was taken on 12/19/24 and tested on 1/13/25. The comprehensive analysis includes multiple ASTM standard tests for gasoline quality, covering parameters such as Base, Sediment and Water percentage, Distillation characteristics, API Gravity, and Flash Point.
The test results indicate the gasoline sample meets ASTM specifications, with notable measurements including an API Gravity of 59.2, Distillation points ranging from 106°F to 352°F, and a Base, Sediment and Water percentage of <0.025. The report includes a disclaimer that the analysis is for informational purposes and does not guarantee against equipment failure, with the OSL's liability limited to the price of the analysis. The document is linked to a VA Healthcare System contract for underground fuel storage tank maintenance services in Long Beach, California.
View the file
Other files
Show all 43
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
California Hazardous Services Sample ID: LB 6 10K UST
1431 E St. Andrew Place Sample Type: Gasoline
Santa Ana, CA 92705 Purchase Order: DG700
Date Sample Taken: 12/19/24
Date Sample Tested: 1/13/25
Date Results Delivered: 1/13/25
Results Delivered: Dillon Bain
Results Delivered: N/A
OSL ID: 2785
Test Methods: Various ASTM
ASTM
1. Base, Sediment and Water % Volume (BS&W) D-2709
2. Distillation D-86
IBP ASTM D86 F
10% Point F
50% Point F
90% Point F
End Point F
% Residue
3. API Gravity 60F D-287
D-976
5. Sulfur (ppm) D-7039
6. Copper Strip D-130
7. Bacteria Sanicheck AB
8. Water D-7546
9. Flash Point D-93
Laboratory Results
<0.025
Based on test results sample meets ASTM specifications for gasoline.
This analysis is intended as an aid in a physical system/fluid review. No guarantee, expressed or implied, is made against the failure of components, engines, generators, or any othe system(s), or lack of their operation / start-up. Certain types of unusual catastrophic conditions leading to failure do not produce abnormal or severe readings. Catastrophic equipment failure can occur immediately after routine analysis. A different sample taken at the same/different time may produce different results; sample taken from different exit points, depths, or areas in the system can also produce significantly different results.
Data is provided for informational purposes only. This solely limits liability of Oil Science Laboratory for any mistakes, errors, or omissions in this analysis to the full price paid for this analysis only.
1.9
59.2
NA
NA
NA
NA
NA
C u st o m e r