Lab Results 2785 LB 7 2K UST DG700.pdf
PDF 69 KB Posted
- Solicitation number
- 36C26225Q0989
About this file
This document is a diesel fuel laboratory test report from Oil Science Laboratory (OSL) for a sample taken from the VA Hospital in Long Beach, California. The laboratory analysis, identified with Sample ID VA Hosp LB 7 2K UST and Purchase Order DG700, was conducted on a diesel fuel sample collected on 12/20/24 and tested on 1/13/25. The comprehensive test results cover nine different ASTM standard measurements, including Base, Sediment and Water percentage, Distillation characteristics, API Gravity, Cetane Index, Sulfur content, Copper Strip rating, Bacteria presence, Water content, and Flash Point.
The test results indicate that the diesel sample meets ASTM specifications for #2 diesel. Key measurements include an API Gravity of 38.2, Cetane Index of 50.0, Sulfur content of 14.0 ppm, a Copper Strip rating of 1A, no bacterial presence, 30 ppm water content, and a Flash Point of 134.0°F. The report includes a disclaimer noting that the analysis is intended as an aid in a physical system/fluid review and does not guarantee against equipment failure. The sample was processed for California Hazardous Services, located in Santa Ana, CA, and the results were delivered to Dillon Bain.
View the file
Other files
Show all 43
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
California Hazardous Services Sample ID: VA Hosp LB 7 2K UST
1431 E St. Andrew Place Sample Type: Diesel
Santa Ana, CA 92705 Purchase Order: DG700
Date Sample Taken: 12/20/24
Date Sample Tested: 1/13/25
Date Results Delivered: 1/13/25
Results Delivered: Dillon Bain
Results Delivered: N/A
OSL ID: 2785
Test Methods: Various ASTM
ASTM
1. Base, Sediment and Water % Volume (BS&W) D-2709
2. Distillation D-86
IBP ASTM D86 F
10% Point F
50% Point F
90% Point F
End Point F
% Residue
3. API Gravity 60F D-287
4. Cetane Index D-976
5. Sulfur (ppm) D-7039
6. Copper Strip D-130
7. Bacteria Sanicheck AB
8. Water D-7546
9. Flash Point D-93
Laboratory Results
<0.025
Based on test results sample meets ASTM specifications for #2 diesel.
This analysis is intended as an aid in a physical system/fluid review. No guarantee, expressed or implied, is made against the failure of components, engines, generators, or any othe system(s), or lack of their operation / start-up. Certain types of unusual catastrophic conditions leading to failure do not produce abnormal or severe readings. Catastrophic equipment failure can occur immediately after routine analysis. A different sample taken at the same/different time may produce different results; sample taken from different exit points, depths, or areas in the system can also produce significantly different results.
Data is provided for informational purposes only. This solely limits liability of Oil Science Laboratory for any mistakes, errors, or omissions in this analysis to the full price paid for this analysis only.
1.8
38.2
50.0
14.0
1A
Negative 0
30ppm
134.0
C u st o m e r
S a m p le D a ta
File details come from the government source that posted it. Updated .