ATTACHMENT 1H - Drawings-Electrical.pdf
PDF 3 MB Posted
- Solicitation number
- 36C26224B0007
About this file
This document package includes construction drawings and specifications for an electrical system upgrade project at a Department of Veterans Affairs medical center. The project scope involves repairing the Sterile Processing Service department and upgrading the equipment area. Drawings depict the existing site and building plans, demolition plans, new work plans including lighting and power plans, schedules, details, a one-line diagram, and panel schedules. Specifications include general notes, codes and standards to be followed, equipment schedules and details. The project entails upgrading electrical infrastructure to support new medical equipment in the Sterile Processing area including installation of new switchboards, panels, transformers and feeders.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UE
OE
M/G 400A/3P
M/G 400A/3P
C
PC
R
TS
T
100/3
100/3/70
100/3/70/1
100/3/CB
PP
J
GF
OR
OR
OR
EPO
AM
VM
DM
ST
KK
GFR
M
SPD
R
LP1
1,3,5
A1
LIGHT FIXTURE, CEILING MOUNTED
A1 = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
NL = NIGHT LIGHT
= ARROW INDICATES AIMING DIRECTION
a
LIGHTING TRACK WITH TRACK LIGHT FIXTURES
A1E = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
LIGHT FIXTURE, POLE MOUNTED
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
LIGHT FIXTURE, WALL MOUNTED
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
EMERGENCY BATTERY PACK LIGHT FIXTURE,
WALL MOUNTED
Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT
FIXTURE SCHEDULe
EMERGENCY BATTERY PACK LIGHT FIXTURE,
CEILING MOUNTED
Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT
FIXTURE SCHEDULE
EXIT SIGN, WALL MOUNTED, FACE/ARROWS AS INDICATED
X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT
FIXTURE SCHEDULE
EXIT SIGN, CEILING MOUNTED, FACE/ARROWS AS INDICATED
X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT
FIXTURE SCHEDULE
EMERGENCY LIGHT FIXTURE, CEILING MOUNTED
A1E = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
NL = NIGHT LIGHT
A1E a
A1 a
A1
A1
X1E
X1E
Y1E
Y1E
HOMERUN TO PANELBOARD
TICK MARKS INDICATE NUMBER OF CONDUCTORS.
DESIGNATIONS ARE PANELBOARD AND
CIRCUIT NUMBERS.
UNSWITCHED HOT CONDUCTORS SHOWN LEADING
NEUTRAL CONDUCTOR
NEUTRAL CONDUCTOR
SWITCHED HOT CONDUCTORS SHOWN TRAILING
GROUND CONDUCTOR
EQUIPMENT GROUNDING CONDUCTOR IN RACEWAY
ISOLATED GROUNDING CONDUCTOR IN RACEWAY
CONCEALED RACEWAY
EXPOSED RACEWAY
RACEWAY TURNING DOWN
RACEWAY TURNING UP
EQUIPMENT TERMINATION
LOW VOLTAGE CABLE (NOT ROUTED IN CONDUIT)
LIGHT FIXTURE, BOLLARD
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
A1
RECEPTACLE, SIMPLEX, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, NEMA 5-20R, UNO
RECEPTACLE, DOUBLE-DUPLEX, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, CEILING MOUNTED, NEMA 5-20R, UNO
RECEPTACLE, SPECIAL PURPOSE
RECEPTACLE, TWIST-LOCK
RECEPTACLE, DUPLEX, FLOOR MOUNTED, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, DROP CORD, NEMA 5-20R, UNO
RECEPTACLE, MOUNTED 6" ABOVE COUNTER,
TYPE AS INDICATED ABOVE
RECEPTACLE DESIGNATIONS AS FOLLOWS:
C = CLOCK HANGER
E = EMERGENCY POWER
GF = GROUND FAULT CIRCUIT INTERRUPTER
IG = ISOLATED GROUND
S = SWITCHED
TR = TAMPER RESITANT
WP = WEATHER PROOF COVER
WR = WEATHER RESISTANT
XP = EXPLOSION PROOF
SWITCH, SINGLE POLE
SWITCH DESIGNATIONS AS FOLLOWS:
2 = TWO-POLE WALL SWITCH
3 = THREE-WAY WALL SWITCH
4 = FOUR-WAY WALL SWITCH
D = DIMMER SWITCH
OS# = OCCUPANCY SENSOR WALL SWITCH, REFER
TO OCCUPANCY SENSOR AND SWITCH SCHEDULE
P = SINGLE-POLE, SINGLE-THROW PILOT LIGHT
WALL SWITCH
K = KEYED WALL SWITCH
M = MOTOR RATED SWITCH
WP = WEATHER PROOF SWITCH AND COVER
OCCUPANCY SENSOR, CEILING MOUNTED
OS# = CEILING MOUNTED OCCUPANCY SENSOR, REFER
TO OCCUPANCY SENSOR AND SWITCH SCHEDULE
POWER PACK FOR LIGHTING CONTROL
JUNCTION BOX
RECEPTACLE ON EMERGENCY POWER
RECEPTACLE, ISOLATED GROUND TYPE
MULTI-OUTLET, SURFACE RACEWAY, 24" ON CENTER,
NEMA 5-20R, UNO
SWITCHBOARD, MOTOR CONTROL CENTER OR DISTRIBUTION
PANELBOARD ON HOUSEKEEPING PAD
PANELBOARD, RECESS MOUNTED
PANELBOARD, SURFACE MOUNTED
TRANSFORMER
DISCONNECT SWITCH, NON-FUSED, 100/3 INDICATES
AMPERES/POLES, CB = CIRCUIT BREAKER TYPE
DISCONNECT SWITCH, FUSED, 100/3/70 INDICATES
AMPERES/POLES/FUSE, CB = CIRCUIT BREAKER TYPE
COMBINATION DISCONNECT SWITCH WITH MOTOR STARTER
100/3/70/1 INDICATES AMPERES/POLES/FUSE/ NEMA STARTER
SIZE, NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE
MAGNETIC MOTOR STARTER, NEMA SIZE AS NOTED,
3-POLE, UNO
CONTACTOR
PHOTOCELL
RELAY
TIME SWITCH
LOW-VOLTAGE TRANSFORMER
PUSH BUTTON, TYPE AS NOTED
VARIABLE FREQUENCY DRIVE WITH DISCONNECT SWITCH
100/3/70 INDICATES AMPERES/POLES/FUSE SIZE,
NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE
UNDERGROUND ELECTRIC LINE
MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
CABINET, RECESS MOUNTED
CABINET, SURFACE MOUNTED
RECEPTACLE, DUPLEX, GROUND-FAULT CIRCUIT
INTERRUPTER, NEMA 5-20R, UNO
MULTI-SERVICE POWER POLE WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
OVERHEAD ELECTRIC LINE
MUSHROOM TYPE PUSH BUTTON, TYPE AS NOTED
TRANSFER SWITCH, RATINGS AS INDICATED
ATS = AUTOMATIC TRANSFER SWITCH
MTS = MANUAL TRANSFER SWITCH
TX#
600AF
500AT
3P
400AS
3P
225AF
LPS-R
275KW STANDBY
480Y/277V, 3PH, 4W
GENERATOR, SEPARATELY DERIVED
SOURCE, TYPE AND RATINGS AS INDICATED
275KW STANDBY
480Y/277V, 3PH, 4W
GENERATOR, NON-SEPARATELY DERIVED
SOURCE, TYPE AND RATINGS AS INDICATED
DRAWOUT CIRCUIT
BREAKER, RATINGS
AS INDICATED
600AF
500AT
3P
CIRCUIT BREAKER,
RATINGS AS
INDICATED
FUSED DISCONNECT
SWITCH, RATINGS
AS INDICATED
400AS
3P
225AF
LPS-R
NEMA 1
COMBINATION FUSED
SWITCH AND STARTER,
RATINGS AS
INDICATED
PANELBOARD,
SINGLE-SECTION,
RATINGS PER
SCHEDULES
PANELBOARD,
MULTI-SECTION,
RATINGS PER
SCHEDULES
AMMETER
VOLTMETER
COMBINATION DIGITAL
AMMETER/VOLTMETER
SHUNT-TRIP RELAY
KIRK-KEY INTERLOCK
GROUND-FAULT RELAY
UTILITY METER
RELAY
SURGE PROTECTION
DEVICE
AUTOMATIC TRANSFER SWITCH WITH BYPASS
TYPE AND RATINGS AS INDICATED
VARIABLE FREQUENCY
DRIVE WITH
DISCONNECT, RATINGS
AS INDICATED
GROUND CONNECTION
POTENTIAL TRANSFORMER
CURRENT TRANSFORMER
GROUND CONNECTION
WITH TEST WELL
CONTACT, OPEN
CONTACT, CLOSED
MOTOR
FEEDER TAGCAPACITOR
SURGE ARRESTER
HEATER
225A 3P
NEMA 1
COMBINATION CIRCUIT
BREAKER AND
STARTER, RATINGS AS
INDICATED
225A 3P
200A 3P
ATS#
200A 3P
ATS#
TRANSFORMER
TX#
TRANSFORMER,
SHIELDED
200A DEAD-FRONT ELBOW
600A DEAD-FRONT ELBOW
DEAD-FRONT SPLITTER
FAULT INDICATOR
LIGHTNING PROTECTION AIR TERMINAL
LIGHTNING PROTECTION CABLE CONNECTION
LIGHTNING PROTECTION GROUND ROD
LIGHTNING PROTECTION CONDUCTOR
LIGHTNING PROTECTION SYMBOLS
ELECTRICAL ONE-LINE DIAGRAM SYMBOLS
LIGHTING SYMBOLS
POWER EQUIPMENT SYMBOLS
WIRING DEVICE SYMBOLS
CIRCUITING SYMBOLS
ES EMERGENCY SHUNT RELAY
MECHANICAL OR FIRE SPRINKLER PLAN NOTE CALL OUT
PLUMBING PLAN NOTE CALL OUT
ELECTRICAL, TECHNOLOGY, OR FIRE ALARM
PLAN NOTE CALL OUT
PLUMBING EQUIPMENT DESIGNATION
EQUIPMENT DESIGNATION TAG
OWNER FURNISHED, CONTRACTOR INSTALLED
EQUIPMENT DESIGNATION
NEW WORK TO EXISTING WORK CONNECTION POINT
DETAIL REFERENCE
SECTION CUT DESIGNATION
ELECTRICAL: (AFF, AFG UNLESS NOTED OTHERWISE)
EP-101
EP-101
AUDIBLE APPLIANCES (CENTERLINE)
ALARMS (TOP)
ANNUNCIATOR PANELS (TOP)
CLOCK OUTLETS (CENTERLINE)
CONTROLS (TOP)
EXIT SIGNS (WALL-MOUNTED, BOTTOM)
FIRE ALARM ANNUNCIATOR PANEL (DISPLAY)
FIRE ALARM BELL (EXTERIOR)
FIRE ALARM CONTROL PANEL/UNIT (DISPLAY)
GROUND BAR
INTERCOM (AFEA ONLY)
INTERCOMS (TOP)
PANELS & PANELBOARDS (TOP)
PULL STATIONS (TOP)
PHOTOCELLS
RECEPTACLES (BOTTOM)
RECEPTACLES, EXTERIOR (BOTTOM)
RECEPTACLES, GARAGES (BOTTOM)
RECEPTACLES IN EQUIPMENT ROOMS (TOP)
RECEPTACLES ABOVE COUNTERTOPS (TOP)
REMOTE INDICATING LIGHT, EQUIPMENT ROOMS (TOP)
REMOTE INDICATING LIGHT, FINISHED AREAS (TOP)
SAFETY SWITCHES & STARTERS
SWITCHES (TOP)
TELEPHONE/DATA/TV OUTLETS (BOTTOM)
VISIBLE APPLIANCES (CENTERLINE)
ANNOTATION STANDARD MOUNTING HEIGHTS
ABBREVIATIONS
1P SINGLE-POLE
1PH SINGLE-PHASE
3P THREE-POLE
3PH THREE-PHASE
3W THREE-WIRE
4W FOUR-WIRE
A OR AMP AMPERE
A/C AIR CONDITIONING
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED
CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, OR
AUTOMATIC FREQUENCY CONTROL,
OR AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
AIP ABANDONED IN PLACE
ALT ALTERNATE
AMB AMBIENT
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BLK BLOCK
BPIP BOILER PLANT INSTRUMENTATION PANEL
BRKR BREAKER
BYP BY-PASS
C CONDUIT
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
CD CONSTRUCTION DOCUMENTS OR
CANDELA
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED /
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED /
OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAXIAL CABLE
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUED
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMER. MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ESMT EASEMENT
ETD EXISTING TO BE DEMOLISHED
ETR EXISTING TO REMAIN
ETL EXISTING TO BE RELOCATED
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FI FILM ILLUMINATOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLUOR FLUORESCENT
FO FIBER-OPTIC
FP FIRE PROTECTION
FT FEET OR FOOT
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G GROUND OR GENERATOR
GND GROUND
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
HCM HORIZONTAL CABLE MANAGER
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IC INSULATION CONTACT
IESNA ILLUMINATION ENGINEERING SOCIETY
OF NORTH AMERICA
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
JB OR J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAH KILOVOLT-AMPERE-HOUR
KVAR KILOVOLT-AMPERE-REACTIVE
KW KILOWATT
KWH KILOWATT-HOUR
KWHM KILOWATT-HOUR METER
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LT LIGHT
LTCP LOCAL TEMPERATURE CONTROL PANEL
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MT MOUNT
MTD MOUNTED
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
N NEUTRAL
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NC NORMALLY CLOSED
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, OR PULL BOX, OR
PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
PNLBD PANELBOARD
POD POWER OPERATED DAMPER
POE POWER OVER ETHERNET
PP PATCH PANEL
PT POTENTIAL TRANSFORMER
PTRV POWER TYPE ROOF VENTILATION
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REC RECESSED
RELO RELOCATED
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RU RACK UNIT
SCC SHORT CIRCUIT CAPACITY
SD SMOKE DETECTOR
SES SERVICE ENTRANCE SECTION
SF SQUARE FEET (FOOT)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TC TIME CLOCK
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT-AMPERE
VAR VOLT-AMPERE-REACTIVE
VCM VERTICAL CABLE MANAGER
VFD VARIABLE FREQUENCY DRIVE
W WATT
WH WATER HEATER
WP WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
XP EXPLOSION PROOF
84" 48" 48" 84" 48" 80" 60"
120" 60" 72" 36" 48" 72" 48"
144" 18" 24" 26" 48" 44" 48"
CEILING
48" 48" 18" 84"
A
# E (CONTINUED) M (CONTINUED)
B
C
D
E
F
N
G
H
I
J
K
L
M
O
P
R
S
T
U
V
W
X
A. ELECTRICAL PLANS AND SECTIONS ARE INTENDED TO
ACCURATELY ILLUSTRATE THE SCOPE OF WORK, BUT ARE STILL
DIAGRAMMATIC IN NATURE.
B. ELECTRICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE
INSTALLED. THE CONTRACTOR IS RESPONSIBLE FOR ENSURING
THAT ALL SYSTEMS ARE FULLY FUNCTIONAL AND COMPLIANT
WITH APPLICABLE CODES.
C. ELECTRICAL DRAWINGS REFLECT COORDINATION EFFORTS
WITH BUILDING DISCIPLINES. HOWEVER, COORDINATION WITH
OTHER TRADES IS REQUIRED.
D. REFERENCE ARCHITECTURAL DRAWINGS FOR ADDITIONAL
INFORMATION REGARDING SCHEDULE AND PHASING
REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF
SERVICES.
E. COORDINATE WITH SCHEDULE WITH THE CONTRACTING
OFFICER'S REPRESENTATIVE BEFORE THE START OF WORK.
F. PANELBOARDS AND OTHER ELECTRICAL EQUIPMENT REQUIRE
SHUTDOWN. COORDINATE SERVICE SHUTDOWN FOR ALL
EQUIPMENT WITH THE CONTRACTING OFFICER'S
REPRESENTATIVE.
G. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND
TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES
SHALL HAVE DIVIDERS BETWEEN DEVICES.
H. UPDATE ALL PANELBOARD SCHEDULES AFFECTED AT THE
COMPLETION OF THE PROJECT.
I. IF FIELD CONDITIONS VARY FROM THE DRAWINGS, THE
CONTRACTOR SHALL DOCUMENT THE VARIATION AND REPORT
IT TO THE GENERAL CONTRACTOR FOR RESOLUTION WITH THE
ENGINEER OF RECORD.
GENERAL NOTES
PROJECT CODES AND STANDARDS
A. ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS 2015
B. VA PG-18-13 VA BARRIER FREE DESIGN STANDARD 2018
(SUPPLEMENT TO ABA STANDARDS)
C. ASHRAE STANDARD 90.1-2019 – ENERGY STANDARD FOR
BUILDINGS EXCEPT LOW RISE RESIDENTIAL BUILDINGS
D. IBC 2021 – INTERNATIONAL BUILDING CODE
E. IEBC 2021 – INTERNATIONAL EXISTING BUILDING CODE
F. IECC 2018 – INTERNATIONAL ENERGY CONSERVATION CODE
G. JCAHO EC 7.40 – EMERGENCY ELECTRICAL POWER SYSTEM
INSPECTION, MAINTENANCE, AND TESTING
H. NFPA 70-2023 - NATIONAL ELECTRICAL CODE (NEC)
I. NFPA 99-2021 – HEALTH CARE FACILITIES CODE
J. NFPA 101-2021 – LIFE SAFETY CODE
K. NFPA 110-2022 – STANDARD FOR EMERGENCY AND STANDBY
POWER SYSTEMS
L. VA PG-18-10 ELECTRICAL DESIGN MANUAL, DECEMBER 2019
M. VA PG-18-10 LIGHTING DESIGN MANUAL, JANUARY 1, 2022
N. VA H-18-8 SEISMIC DESIGN REQUIREMENTS
O. VA PHYSICAL SECURITY & RESILIENCY DESIGN MANUAL 2020
(JULY 22 REVISION)
IG
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR SBBL COLLABORATIVE JN, INC.
100 N. STONE AVE STE 1102
TUCSON, AZ 85701-1524
(520) 620-0255
NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023
NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024
NM ELEC - EVANS SORDIASHIE #22817 EXP. 12/31/2023
CIVIL / STRUCTURAL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
HEALTHCARE PLANNER
THE INNOVA GROUP
3196 NORTH SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
SPUR #: 1993.10
/9
/2
:3
:5
P
M
ELECTRICAL LEGEND AND
ABBREVIATIONS
SH Drawing # 65 OF 79ES
BID DOCUMENTS
REPAIR SPS SEWER AND
UPGRADE EQUIPMENT AREA
08/11/2023
501-21-101
RAYMOND G. MURPHY VAMC
1501 SAN PEDRO DRIVE SE
ALBUQUERQUE, NM 87108
E-000
No. REVISION DESCRIPTION DATE
PARKING
PARKING
PARKING
SU
PP
OR
T
DR
M
ED
IC
AL
G
RO
UP
D R
S O U T H
V E T E R A N S
L O O P
R O A D
N O R T H
V E T E R A N S
L O O P
R O A D
PA
TR
IO
T W
AY
SU
PP
OR
T
DR
BUS STOP
T-60
SMOKING SHELTER
J
S A
N
P
ED
R O
DR
I V E
DR
IV
E
R
I DG
EC RE
ST
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
BUILDING 45
BUILDING 41
SPS DEPARTMENT
BUILDING 41
BASEMENT LEVEL, QUAD C
TEMPORARY SPS FACILITY
SE LOT NEAR BUILDING 45BUILDING 77
BUILDING 47
NEW AUTOMATIC GATE.
SEE NOTE 46.
GATE
RAYMOND G. MURPHY VA
MEDICAL CENTER CAMPUS
N
B45
B41 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR SBBL COLLABORATIVE JN, INC.
100 N. STONE AVE STE 1102
TUCSON, AZ 85701-1524
(520) 620-0255
NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023
NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024
NM ELEC - EVANS SORDIASHIE #22817 EXP. 12/31/2023
CIVIL / STRUCTURAL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
HEALTHCARE PLANNER
THE INNOVA GROUP
3196 NORTH SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
SPUR #: 1993.10
/9
/2
:3
:0
P
M
ELECTRICAL SITE PLAN
SH Drawing # 66 OF 79ES
BID DOCUMENTS
REPAIR SPS SEWER AND
UPGRADE EQUIPMENT AREA
08/11/2023
501-21-101
RAYMOND G. MURPHY VAMC
1501 SAN PEDRO DRIVE SE
ALBUQUERQUE, NM 87108
ES100
N
NTS1" = 40'-0"
ELECTRICAL SITE PLAN1
ELECTRICAL KEYNOTES
46 NEW 120V EMERGENCY POWER TO ELECTRONIC GATE. COORDINATE EXACT LOCATION AND
POWER REQUIREMENTS WITH CIVIL DRAWINGS.
J
J
J
UE UEUE UE UE
U E
U E
U E
U E
U E
U E
U E
UE UEUE UE
U E
U E
U E
U E
UE
UE
'SWBD-SPS' (ETR)
MOBILE SPS TRAILER 1(SPS-T1)
M O
B
IL
E S
P S
T R
A
IL
E R
S P
S -T
TEMPORARY 1000KW
DIESEL ENGINE
GENERATOR W/
INTEGRAL ABOVE GRADE
SUB-BASE FUEL TANK
(NEW)
F2 F2E F2 F2E
F2
F2E
XFMR (NEW) TR-T77
ATS-SW-SPS 2 (NEW)
PANEL 'SPS-2' (NEW)
100/2/80/3R
PANEL 'SPS-1' (NEW)
XFMR 'TX-SPS-L' (NEW)
F2E
PX1
PX1
'SPS-L' (NEW)
100/2/80/3R
SPS-L
SPS-2
TEMP-AH-2
TEMP-AH-1 SPS-2
2,4,6
FACTORY MOUNTED
DISCONNECT SWITCH
BY DIV 23
FACTORY MOUNTED
DISCONNECT SWITCH
SPS-1
2,4,6
WR/
WP
WP/
WR
SPS-L
SPS-L
MECHANICAL
EQUIP.
HAND
HOLE
TO
EXISTING
BUILDING 77
LIFT
SPS-L
CONCRETE
ENCASED
NEMA 3R ATS-SW-SPS 1 (NEW)
CONCRETE
ENCASED
ETR
ETR
F2E
34 36
SPS-L
E-501
E-501
E-501
E-501
E-501
GATE
SPS-L
SPS-L
F2E F2E
F2EF2E
NEMA 3R
NEMA 3R
NEMA 3R
NEMA 3R
NEMA 3R NEMA 3R
NEMA 3R
NEMA 3R
NEMA 3R
DHWCP-1
W1E (ETR)
X
X
X
X
WS-1
DHW-1
SPS-L
F2 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR SBBL COLLABORATIVE JN, INC.
100 N. STONE AVE STE 1102
TUCSON, AZ 85701-1524
(520) 620-0255
NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023
NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024
NM ELEC - EVANS SORDIASHIE #22817 EXP. 12/31/2023
CIVIL / STRUCTURAL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
HEALTHCARE PLANNER
THE INNOVA GROUP
3196 NORTH SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
SPUR #: 1993.10
/9
/2
:3
:1
P
M
TEMPORARY SPS TRAILER ENLARGED
POWER PLAN
SH Drawing # 67 OF 79ES
BID DOCUMENTS
REPAIR SPS SEWER AND
UPGRADE EQUIPMENT AREA
08/11/2023
501-21-101
RAYMOND G. MURPHY VAMC
1501 SAN PEDRO DRIVE SE
ALBUQUERQUE, NM 87108
ES401
N
3/16" = 1'-0"
ENLARGED ELECTRICAL SITE PLAN1
ELECTRICAL KEYNOTES
5 PROVIDE 20' LIGHT POLE. SEE DETAIL 5/E-501 FOR LIGHT POLE BASE INFORMATION. TYPICAL.
10 MELTRIC ELECTRIC CABLE CONNECTORS PROVIDED BY STERIS FOR FINAL CONNECTION TO TRAILER.
21 REMOVE EXISTING 750KVA TRANSFORMER AND REPLACE WITH A NEW 12470V-480Y/277V, 3-PHASE, 4W TRANSFORMER.
FIELD VERIFY EXISTING TRANSFORMER FEEDER PRIOR TO REMOVAL AND COORDINATE TRANSFORMER REPLACEMENT WITH THE VA MAINTENANCE DEPARTMENT TO LIMIT POWER DISRUPTIONS. REFER TO E-601 FOR MORE INFORMATION.
22 REFER TO DETAIL 6/E-501 FOR EQUIPMENT MOUNTING INFORMATION. TYPICAL.
23 POWER FOR CART LIFT. COORDINATE EXACT LOCATION WITH ARCHITECTURAL. COORDINATE FINAL POWER CONNECTIONS REQUIREMENTS WITH LIFT MANUFACTURER PRIOR TO ROUGH IN ONCE LIFT MODEL IS APPROVED BY VA
COR.
32 PROVIDE 100A, NEMA 3R DISCONNECT SWITCH WITH A 80A FUSE TO BE USED WITH THE MOBILE SPS COLD WEATHER PACKAGE. COORDINATE ADDITIONAL REQUIREMENTS WITH EQUIPMENT MANUFACTURER. SEE ONE-LINE DIAGRAM FOR
MORE INFORMATION.
33 FIXTURES CONTROLLED VIA PHOTO CELL AND TIME CLOCK. REFER TO 1/E-502 FOR TIME CLOCK AND PHOTOCELL DETAILS AND CONTROLS. FIXTURES SURFACE MOUNTED TO UNDERSIDE OF CANOPY. COORDINATE MOUNTING DETAILS
WITH ARCHITECTURAL.
34 75' SHORELINE CABLE PROVIDED BY MOBILE SPS TRAILER PROVIDER. CONTRACTOR SHALL MAKE FINAL CONNECTIONS TO PANEL AND MOBILE SPS TRAILER. REFER TO MANUFACTURER'S CUTSHEET FOR ADDITIONAL INFORMATION.
35 PROVIDE (3) #4, (1)#8G IN 1" CONDUIT FROM DISCONNECT TO 70A PANELBOARD LOCATED INSIDE MOBILE SPS TRAILER.
REFER TO MANUFACTURER'S CUTSHEET FROM ADDITIONAL INFORMATION.
36 PROVIDE HEAVY DUTY, TRAFFIC-RATED CABLE COVER FOR USE WITH TEMPORARY CABLING.
37 REFER TO 8-WAY DUCT LINE DETAIL (7/E-501) AND ONE-LINE DIAGRAM FOR MORE INFORMATION.
38 REFER TO 3-WAY DUCT LINE DETAIL (7/E-501) AND ONE-LINE DIAGRAM FOR MORE INFORMATION.
39 REFER TO ONE-LINE DIAGRAM FOR TEMPORARY GENERATOR CONNECTIONS AND CABLE AND CONDUIT SIZES.
40 NEW 120V EMERGENCY POWER TO ELECTRONIC GATE. COORDINATE EXACT LOCATION AND POWER REQUIREMENTS WITH CIVIL DRAWINGS. PROVIDE 1#12, 1#12N , 1#12G IN 3/4"C IN DIRECT BURIED EARTH WITH MINIMUM COVER TO TOP
OF ENVELOPE TO BE 24 INCHES. CIRCUIT TO PANEL SPS-L #11.
42 COORDINATE ROUTING OF UNDERGROUND ELECTRICAL CONDUCTORS WITH EXISTING CONDITIONS AND CIVIL
DRAWINGS. SURVEY DATA PRIOR TO CONSTRUCTIONS.
45 PROVIDE 120V POWER FOR CAMERA INTERFACE ADAPTER. COORDINATE EXACT LOCATION AND REQUIREMENTS WITH
DIVISON 27 PRIOR TO INSTALL.
48 CONNECT EXISTING WATER SOFTENER TO NEAREST 120V CRITICAL POWER CIRCUIT CURRRENTLY SERVING THE AREA.
49 COORDINATE FINAL POWER CONNECTIONS AND REQUIREMENTS WITH DIVISION 22.
GENERAL NOTES:
A. ON WALLS THAT TILE OR WALL PROTECTION HAS BEEN REMOVED AND REPLACED AND WALL
THICKNESS HAS BEEN CHANGED, ELECTRICAL JUNCTION BOXES OR ELECTRICAL DEVICES
SHALL BE ADJUSTED SO THAT THE ELECTRICAL DEVICE IS FLUSH / RECESSED WITH THE
SURFACE OF THE WALL.
J J
J
J
J
SPS
DEPARTMENT
BUILDING 41
BASEMENT
LEVEL, QUAD
C
N
BUILDING 41 -
BASEMENT LEVEL
KEY PLAN
1 2 3 4 5 6
G
H
I
SOILED RECV &
DECONTAMINATION
BC-110
STOR
BC-127
STERILIZATION
PREPARATION
BC-111
RECEPTION AND
PGM ASST
BC-125
OFFICE OF CHIEF
BIOMED
BC-125A
VESTIBULE
BC-113
EQUIP TEST &
STORAGE
BC-115D
WORK AREA &
STOR
BC-115C
BIOMED WORK
SPACE
BC-125D
OFFICE
BC-115E
BREAKDOWN
BC-115B
HALL
BC-103A
BREAK ROOM
BC-103B
TLT (F)
BC-115G
TLT
BC-104
TLT
BC-105
STOR
BC-118
STAFF WORK AREA
BC-115
RECEPTION
BC-121A
MED SUPPLY TECH
BC-121B
OFFICE
BC-123
HAC
BC-115A
TECHNICAL WORK
SPACE
BC-126
PARTS RM
BC-126A
MECH RM
BC-126B
CORRIDOR
CB-17
STOR
BC-119
MECH
BC-115F
LOCKERS
BC-102
MED GAS
BC-121
CORRIDOR
CB-15
CART WASH
BC-114
CORRIDOR
CB-16
SPS CHANGE AREA
BC-103
HLD DECON
BC-110B
VEST
BC-111A
DUMBWAITER
X1
FACILTY ACCESS
STAIRWELL
S11
TLT
BC-102A
CORRIDOR
MED GAS STOR
BC-107
DOCK
CORRIDOR
CORRIDOR
OFFICE
BC-103C
1 2 3 4 5 6
G
H
I
XFMR 'TX-CTCBB-2'
(ETR)
PNL 'CTCBB-2' (ETR)
ETD
SOILED RECV &
DECONTAMINATION
BC-110
STOR
BC-127
STERILIZATION
PREPARATION
BC-111
RECEPTION AND
PGM ASST
BC-125
OFFICE OF CHIEF
BIOMED
BC-125A
EQUIP TEST &
STORAGE
BC-115D
WORK AREA &
STOR
BC-115C
BIOMED WORK
SPACE
BC-125D
OFFICE
BC-115E
BREAKDOWN
BC-115B
HALL
BC-103A
BREAK ROOM
BC-103B
TLT (F)
BC-115G
TLT
BC-104
TLT
BC-105
STOR
BC-118
STAFF WORK AREA
BC-115
RECEPTION
BC-121A
MED SUPPLY TECH
BC-121B
OFFICE
BC-123
HAC
BC-115A
TECHNICAL WORK
SPACE
BC-126
PARTS RM
BC-126A
MECH RM
BC-126B
CORRIDOR
CB-17
STOR
BC-119
MECH
BC-115F
LOCKERS
BC-102
MED GAS
BC-121
CORRIDOR
CB-15
CART WASH
BC-114
CORRIDOR
CB-16
SPS CHANGE AREA
BC-103
HLD DECON
BC-110B
VEST
BC-111A
DUMBWAITER
X1
FACILTY ACCESS
STAIRWELL
S11
TLT
BC-102A
CORRIDOR
MED GAS STOR
BC-107
DOCK
CORRIDOR
CORRIDOR
OFFICE
BC-103C
ETL
ETR ETR
ETR ETR ETR ETR ETR ETR
ETR
ETR ETR ETR ETR ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETRETRETR
ETR
ETR
ETR
ETR
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR SBBL COLLABORATIVE JN, INC.
100 N. STONE AVE STE 1102
TUCSON, AZ 85701-1524
(520) 620-0255
NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023
NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024
NM ELEC - EVANS SORDIASHIE #22817 EXP. 12/31/2023
CIVIL / STRUCTURAL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
HEALTHCARE PLANNER
THE INNOVA GROUP
3196 NORTH SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
SPUR #: 1993.10
/9
/2
:3
:0
P
M
ELECTRICAL DEMOLITION PLAN - BLDG
SH Drawing # 68 OF 79ES
BID DOCUMENTS
REPAIR SPS SEWER AND
UPGRADE EQUIPMENT AREA
08/11/2023
501-21-101
RAYMOND G. MURPHY VAMC
1501 SAN PEDRO DRIVE SE
ALBUQUERQUE, NM 87108
ED101
N
1/8" = 1'-0"
ELECTRICAL LIGHTING DEMOLITION FLOOR PLAN2
N
1/8" = 1'-0"
ELECTRICAL POWER DEMOLITION FLOOR PLAN1
ELECTRICAL KEYNOTES
1 DISCONNECT AND REMOVE EXISTING CART WASH DISCONNECT SWITCH. REMOVE ASSOCIATED
CONDUITS AND CONDUCTORS BACK TO BRANCH PANEL.
11 DASHED LINE INDICATES AREA OF WORK.
12 DISCONNECT AND REMOVE ALL LIGHT FIXTURES AND CONTROLS WITHIN THE AREA OF WORK
AND RETURN TO OWNER'S STOCK. REMOVE CONDUIT AND FEEDERS BACK TO NEAREST
JUNCTION BOX AND VERIFY CIRCUIT LABELING OR LABEL WITH FEEDER CIRCUITS.
50 REFER TO ARCHITECTURAL DRAWINGS FOR ADDITIONAL NOTES ON DEMOLITION OF UTILITY
COLUMN.
GENERAL NOTES:
A. ALL LOCATIONS ARE APPROXIMATE. FIELD VERIFY EXACT COUNTS AND LOCATIONS PRIOR TO
DEMOLITION.
B. SHADED AREAS ARE OUT OF PROJECT SCOPE.
J
J
UE UEUE UE UE
U E
U E
U E
U E
U E
U E
U E
UE UEUE UE UE
U E
U E
U E
U E
UE
UE
MOBILE SPS TRAILER 1(SPS-T1)
M O
B
IL
E S
P S
T R
A
IL
E R
S P
S -T
TEMPORARY 1000KW
DIESEL ENGINE
GENERATOR W/ SUB-
BASE FUEL TANK (NEW)
F2 F2E F2 F2E
F2
F2E
XFMR (NEW)
TR-T77
ATS-SW-SPS 2 (NEW)
PANEL 'SPS-2' (NEW)
100/2/80/3R
PANEL 'SPS-1' (NEW)
XFMR 'TX-SPS-L' (NEW)
F2E
PX1
PX1
'SPS-L' (NEW)
100/2/80/3R
TEMP-AH-2
TEMP-AH-1
WR/
WP
MECHANICAL
EQUIP.
HAND
HOLE
TO
EXISTING
BUILDING 77
LIFT
ATS-SW-SPS 1 (NEW)
ETR
ETR
F2E
'SWBD-SPS' (ETR)
W1E (ETR)
F2E
F2E
F2E
F2E th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR SBBL COLLABORATIVE JN, INC.
100 N. STONE AVE STE 1102
TUCSON, AZ 85701-1524
(520) 620-0255
NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023
NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024
NM ELEC - EVANS SORDIASHIE #22817 EXP. 12/31/2023
CIVIL / STRUCTURAL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
HEALTHCARE PLANNER
THE INNOVA GROUP
3196 NORTH SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
SPUR #: 1993.10
/9
/2
:3
:0
P
M
TEMPORARY SPS TRAILER ENLARGED
POWER PLAN POST DEMOLITION
SH Drawing # 69 OF 79ES
BID DOCUMENTS
REPAIR SPS SEWER AND
UPGRADE EQUIPMENT AREA
08/11/2023
501-21-101
RAYMOND G. MURPHY VAMC
1501 SAN PEDRO DRIVE SE
ALBUQUERQUE, NM 87108
ED401
N
3/16" = 1'-0"
ENLARGED ELECTRICAL SITE PLAN POST CONSTRUCTION DEMOLITION1
ELECTRICAL KEYNOTES
41 THE ELECTRICAL CONTRACTOR SHALL REMOVE TEMPORARY DEVICES AS REQUIRED FROM
THE AREA INDICATED BY DASHED LINE. THE ELECTRICAL DEMOLITION WORK OUTSIDE
BUILDING 41 WILL BE INCLUDED (BUT NOT LIMITED TO) TO THE REMOVAL AND DISCONNECTION
OF ANY TEMPORARY SPS MOBILE TRAILERS, GENERATORS, LIGHTING AND AUTOMATIC GATES
THAT WERE REQUIRED DURING THE SPS RENOVATION. REFER TO ARCHITECTURAL DRAWINGS
FOR PHASING INFORMATION.
47 TRANSFORMER TR-177 AND ALL ASSOCIATED CONDUCTORS, CONDUITS AND HAND HOLES TO
REMAIN INDEFINATELY. DO NOT DEMOLISH DURING RESTORATION PHASE.
49 COORDINATE FINAL POWER CONNECTIONS AND REQUIREMENTS WITH DIVISION 22.
GENERAL NOTES:
A. ON WALLS THAT TILE OR WALL PROTECTION HAS BEEN REMOVED AND REPLACED AND WALL
THICKNESS HAS BEEN CHANGED, ELECTRICAL JUNCTION BOXES OR ELECTRICAL DEVICES
SHALL BE ADJUSTED SO THAT THE ELECTRICAL DEVICE IS FLUSH / RECESSED WITH THE
SURFACE OF THE WALL.
ESES
ES
ES
ES
ES
PP
PP
PP
PP
J
J
J J
J
J
J
J
J
J
J
J
1 2 3 4 5 6
G
H
A1
B1
A1A1A1EA1A1
A2E A2
A2
A1
A1E
A1
A1E
B1A1E
A1E
A1
A1E
A1A1A1
A1E A1 A1 A1E A1 A1 A1
A1E
A1
A1
A1
A1E
A2E
A2
A1
A1A1
A2
A1
A1E B1
B1
A1E
A1A1
A1
A1
A1E
A1A1
A1
A1
A1E
A1
A1A1
A1E
X
X
X
X
X
X
PNL 'CTCBB-2' (ETR)
SOILED RECV &
DECONTAMINATION
BC-110
HLD ALCOVE
BC-110C
STOR
BC-127
STERILIZATION
PREPARATION
BC-111
EQUIP TEST &
STORAGE
BC-115D
WORK AREA &
STOR
BC-115C
BIOMED WORK
SPACE
BC-125D
OFFICE
BC-115E
BREAKDOWN
BC-115B
HALL
BC-103A
BREAK ROOM
BC-103B
TLT (F)
BC-115G
TLT
BC-104
TLT
BC-105
STOR
BC-118
STAFF WORK AREA
BC-115
RECEPTION
BC-121A
MED SUPPLY TECH
BC-121B OFFICE
BC-123
HAC
BC-115A
STOR
BC-119
MECH
BC-115F
LOCKERS
BC-102
MED GAS
BC-121
CORRIDOR
CB-15
CART WASH
BC-114
CORRIDOR
CB-16
SPS CHANGE AREA
BC-103
HLD DECON
BC-110B
DUMBWAITER
X1
FACILTY ACCESS
STAIRWELL
S11
TLT
BC-102A
CORRIDOR
DOCK
OFFICE
BC-103C
X
A1E
A1
A2
X
LIGHTING
PROVIDED BY
CART WASH
VENDOR
RC1
LVD
LVD
RC1
LVD
LVD
RC1
A1 A1E
LVD
LVD
LVD
RC1
HAC
BC-110D
OS1
OS1
OS1
LVD
1 2 3 4 5
G
H
I
PNL 'CTCBB-2' (ETR)
XFMR 'TX-CTCBB-2'
(ETR)
SOILED RECV &
DECONTAMINATION
BC-110
STOR
BC-127
STERILIZATION
PREPARATION
BC-111
RECEPTION AND
PGM ASST
BC-125
OFFICE OF CHIEF
BIOMED
BC-125A
EQUIP TEST &
STORAGE
BC-115D
WORK AREA &
STOR
BC-115C
BIOMED WORK
SPACE
BC-125D
OFFICE
BC-115E
BREAKDOWN
BC-115B
HALL
BC-103A
BREAK ROOM
BC-103B
TLT (F)
BC-115G
TLT
BC-104
TLT
BC-105
STAFF WORK AREA
BC-115
RECEPTION
BC-121A
MED SUPPLY TECH
BC-121B
HAC
BC-115A
MECH RM
BC-126B
STOR
BC-119
MECH
BC-115F
LOCKERS
BC-102
MED GAS
BC-121
CORRIDOR
CB-15
CART WASH
BC-114
CORRIDOR
CB-16
SPS CHANGE AREA
BC-103
HLD DECON
BC-110B
VEST
BC-111A
DUMBWAITER
X1
FACILTY ACCESS
STAIRWELL
S11
TLT
BC-102A
CORRIDOR
OFFICE
BC-103C
MECH
BD-141
ELECTRICAL
CLOSET
BC-110E
MECH EQUIP
BC-112
VESTIBULE
BC-113
CTCBB-2
19,21,23
CTCBB-2
41-EF15A
CTPB
14,16,18
DIV. 23
VESTIBULE
BC-100
HAC
BC-110D
HLD ALCOVE
BC-110C
HLD ANTEROOM
BC-110A
E-101
60/3/35/1
ETR
ETR
CTCBB-2
WP
WP
WP
WP
WP WP
WP
ETR
ETR
AUTO DOOR
AUTO DOOR
AUTO DOOR 30
AUTO DOOR
ETL43
AUTO DOOR
(ETR) (ETR) (ETR) (ETR) (ETR) (ETR)
(ETR)
(ETR)
(ETR) (ETR) (ETR)
(ETR) (ETR) (ETR)
(ETR)
(ETR)
(ETR)
(ETR)
(ETR)
(ETR)
(ETR)
(ETR)
(ETR)
(ETR)
(ETR)
(ETR)
(ETR)
(ETR) (ETR)
(ETR)
(ETR)
(ETR) (ETR)
(ETR) (ETR)
(ETR) (ETR)
CTCBB-2
G
ELECTRICAL
CLOSET
BC-110E
PNL 'CTLB' (ETR)
PNL 'CTPB' (ETR)
XFMR 'CTLB' (ETR)
CTCBB (ETR)
PNL 'CLPB' (ETR)
PNL 'CLLB' (ETR)
PNL 'CCLB' (ETR)
PNL 'CCPB' (ETR)
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR SBBL COLLABORATIVE JN, INC.
100 N. STONE AVE STE 1102
TUCSON, AZ 85701-1524
(520) 620-0255
NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023
NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024
NM ELEC - EVANS SORDIASHIE #22817 EXP. 12/31/2023
CIVIL / STRUCTURAL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
HEALTHCARE PLANNER
THE INNOVA GROUP
3196 NORTH SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
SPUR #: 1993.10
/9
/2
:3
:0
P
M
ELECTRICAL NEW WORK PLAN - BLDG
SH Drawing # 70 OF 79ES
BID DOCUMENTS
REPAIR SPS SEWER AND
UPGRADE EQUIPMENT AREA
08/11/2023
501-21-101
RAYMOND G. MURPHY VAMC
1501 SAN PEDRO DRIVE SE
ALBUQUERQUE, NM 87108
E-101
N
1/8" = 1'-0"
ELECTRICAL LIGHTING FLOOR PLAN2
N
1/8" = 1'-0"
ELECTRICAL POWER FLOOR PLAN1
GENERAL NOTES:
A. CONTRACTOR IS RESPONSIBLE FOR VERIFYING AND CONNECTING ALL NEW AND
EXISTING RECONNECTED LOADS IN A BALANCED MANNER.
B. SHADED AREAS INDICATE OUT OF PROJECT SCOPE.
1/4" = 1'-0"
ELECTRICAL CLOSET BC-110E - ENLARGED FLOOR PLAN3
ELECTRICAL KEYNOTES
24 COORDINATE MOUNTING OF GFCI OUTLETS AROUND MOVABLE SINK. COORDINATE LENGTH OF WHIP SO THAT THE SINK CAN RAISE AND LOWER FOR ITS FULL RANGE OF MOTION. MOUNT CONVENIENCE OUTLETS SO THAT
THEY ARE NOT IMPEDED BY THE SINKS MOVEMENT.
26 CONNECT TO NEXT AVAILABLE CIRCUIT IN EXISTING LIFE SAFETY PANEL (CLPB) SERVING THIS AREA.
CONTRACTOR TO FIELD VERIFY LIFE SAFETY PANEL LOCATION PRIOR TO ROUGH IN.
27 CONNECT TO NEXT AVAILABLE CIRCUIT IN EXISTING CRITICAL PANEL (CCPB) SERVING THIS AREA. CONTRACTOR
TO FIELD VERIFY CRITICAL PANEL LOCATION PRIOR TO ROUGH IN.
29 NEW AUTODOOR - CONNECT 120V POWER CONNECTION TO EXISTING CIRCUIT CURRENTLY SERVING THE
EXISTING AUTOMATIC DOOR CONNECTION.
30 PROVIDE 120V POWER CONNECTION TO NEW AUTOMATIC DOOR. CONNECT TO EXISTING CIRCUIT CURRENTLY
SERVING EXISTING AUTOMATIC DOOR IN THIS AREA.
31 RELOCATE TO COORDINATE WITH COMPUTER MOUNTING BRACKET SO PERIPHERALS CAN UTILIZE THIS OUTLET.
43 REUSE EXISTING AUTO DOOR IN DOOR FRAME DEMOLISHED IN VESTIBULE BC-111A. CONNECT TO EXISTING
CIRCUIT CURRENTLY SERVING EXISTING AUTOMATIC DOOR IN THIS AREA.
44 PROVIDE NEW TWO COMPARTMENT POWER POLE FOR POWER AND COMMUNICATIONS CABLING. PROVIDE SIMILAR TO BASIS OF DESIGN LEGRAND 2 COMPARTMENT TELE-POWER POLE: 30TP-4WH. CHOOSE FINISH COLOR THAT MATCHES EXISTING TELE-POWER POLE COLOR. COORDINATE LENGTH OF POWER POLE WITH FINISH CEILING HEIGHT. PROVIDE QUANTITY OF RECEPTACLES REQUIRED TO COORDINATE WITH
WORKSTATION POWER. RESUSE EXISTING CONDUCTORS.
(M A
T C
H E
X
IS
T
IN
G
FINISHED GRADE
CONCRETE BASE &
REINFORCING STEEL,
SEE NOTE BELOW.
25mm (1") EMPTY
CONDUIT WITH CAP
(WHERE SHOWN ON
PLANS)
#4 BARE COPPER
GROUND 6069mm
(20'-0") COILED
BELOW BASE
GENERAL NOTES:
1. BACKFILL, CONCRETE, REINFORCING STEEL, AND ANCHOR BOLTS ARE
SHOWN FOR REFERENCE ONLY. STRUCTURAL DESIGN IS SHOWN ON
STRUCTURAL DRAWINGS.
2. REFER TO SPECIFICATION SECTION 26 56 00 FOR MOUNTING AND
LEVELING REQUIREMENTS.
(2
UNDISTURBED SOIL
OR SELECT BACKFILL
COMPACTED, SEE
NOTE BELOW.
PVC CONDUIT ADAPTER
COUPLING
RIGID STEEL CONDUIT
PVC CONDUIT
ANCHOR BOLTS PER POLE
MANUFACTURER'S REQUIREMENTS
WITH LEVELING NUTS ABOVE &
BELOW BASE PLATE
LIGHT POLE PER LIGHT
FIXTURE SCHEDULE
2-PIECE BOLT COVER PLATE.
POLE GROUNDING STUD
76x127mm (3"x5") REINFORCED
HAND HOLE WITH TAMPER
RESISTANT SCREWS. PROVIDE
IN-LINE SCREW-TYPE FUSE
HOLDER(S) WITH FUSE(S).
m m M
IN
CONDUIT CLAMP. SIZE
AS REQUIRED
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
REFER TO PLANS FOR
QUANTITY & SIZE OF
CONDUITS
GENERAL NOTES:
1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL
LONGER THAN 915mm (36") SHALL BE INSTALLED WITH A
CENTER SUPPORT ROD.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED
METHOD PER SPECIFICATION 26 05 33, RACEWAY AND BOXES
FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT CONDITIONS.
3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER TO
SPECIFICATION SECTION 13 05 41, SEISMIC RESTRAINT
REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.
LENGTH AS REQUIRED
LOCKING SQUARE
WASHER & LOCKNUT
9.52mm (3/8") MIN
GALVANIZED THREADED
ROD, TYP.
WASHER &
LOCKNUT
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS
AND USING THE RECOMMENDED MOUNTING HARDWARE.
DRYWALL BORDER
LUMINAIRE.
REFER TO
SCHEDULE
CEILING CROSS BEAM
GYPSUM BOARD
CEILING CROSS BEAM
LUMINAIRE MANUFACTURER'S
MOUNTING HARDWARE
REFER TO SPECIFICATION SECTION
26 51 00
LUMINAIRE.
REFER TO
SCHEDULE
GYPSUM BOARD (TYP)
CEILING MAIN BEAM
FIXTURE WHIP FROM
JUNCTION BOX
(1829mm (6') LONG
MAX.)
3 TWIST MINIMUM
(TYP)
LUMINAIRE SUSPENSION
WIRES REFER TO
SPECIFICATION
SECTION 26 51 00
DRYWALL CEILING
CROSS TEE, TYP.
HANGER WIRE AND MOUNTING
CHANNEL ATTACHED TO STRUCTURE
REFER TO SPECIFICATION SECTION
26 51 00
CEILING MAIN
BEAM.
DRYWALL CEILING
CROSS TEE, TYP.
GYPSUM
BOARD
WIRE TIE THROUGH
MOUNTING CHANNEL &
CROSS BEAM, TYP.
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS
AND USING THE RECOMMENDED MOUNTING HARDWARE.
LOCKING SQUARE
WASHER & NUT
6.35mm (1/4") SCREW
JUNCTION BOX
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
FIXTURE WHIP FROM JUNCTION BOX
(1829mm (6') LONG MAX)
CEILING HANGER WIRE
EXISTING SUBSTRATE
ABOVE GRADE
(2) 3" CONDUITS FOR
POWER FEEDERS
(24" MIN.)
(3")
DIRECT-BURIED DUCT LINE
GENERAL NOTES:
1. MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm (24").
(3")
1" CONDUIT FOR ATS
CONTROLS
TOP OF HANDLE
6'-6" AFF MAXIMUM
4'-0" +/- AFF
FRONT VIEWSIDE VIEW
DISCONNECT SWITCH, CIRCUIT
BREAKER ENCLOSURE, OR
MOTOR CONTROLLER
CHANNEL STRUT POST BASE W
(4) 1/4" EXPANSION ANCHORS.
(TYPICAL)
FLOOR
CHANNEL STRUT SUPPORT
FRAME.
1'-7" (MIN.)
CHANNEL STRUT
ANGLE BRACKET SUPPORT
FOR EACH SUPPORT LEG WITH
1/2" FLOOR EXPANSION
ANCHOR.
NOTE:
1. CONNECT THE SUPPORT FRAME WITH A MINIMUM OF (4) POINTS OF CONTACT TO THE BUILDING STRUCTURE TO PROVIDE A
RIGID ASSEMBLY.
1. CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS, OR AS SPECIFIED.
2. PROVIDE #4 REINFORCING RODS ON TOP AND BOTTOM OF DUCTS WHEN
CROSSING OR PLACED IN ROADWAYS.
3. MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm (24") OR AS
OTHERWISE SPECIFIED IN SECTION 26 05 41.
4. INNERDUCT QUANTITY AND SIZE AS INDICATED ON PLANS.
76mm
3"
76mm
3"
76mm
3" m m m m
GENERAL NOTES
3-WAY DUCT LINE
8-WAY DUCT LINE
76mm
76mm m m
3"
3"
76mm
3" m m m m
"th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR SBBL COLLABORATIVE JN, INC.
100 N. STONE AVE STE 1102
TUCSON, AZ 85701-1524
(520) 620-0255
NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023
NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024
NM ELEC - EVANS SORDIASHIE #22817 EXP. 12/31/2023
CIVIL / STRUCTURAL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
HEALTHCARE PLANNER
THE INNOVA GROUP
3196 NORTH SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
SPUR #: 1993.10
/9
/2
:3
:0
P
M
ELECTRICAL DETAILS
SH Drawing # 71 OF 79ES
BID DOCUMENTS
REPAIR SPS SEWER AND
UPGRADE EQUIPMENT AREA
08/11/2023
501-21-101
RAYMOND G. MURPHY VAMC
1501 SAN PEDRO DRIVE SE
ALBUQUERQUE, NM 87108
E-501
NTS
LIGHT POLE BASE DETAIL5
NTS
CONDUIT TRAPEZE MOUNTING DETAIL2 NTS
LUMINAIRE MOUNTING - GYPBOARD CEILING1NTS
EXIT SIGN MOUNTING - GYPBOARD CEILING3
NTS
DIRECT BURIAL CONDUIT DETAIL POWER4NTS
EQUIPMENT MOUNTING DETAIL6NTS
DUCT BANK DETAIL7
Emergency Line 120/277
Emergency Neutral
Push to
Test
ELCU-200
R e m o te
A c ti v a ti o n
N o rm a l
P o w e r
E m e rg e n c y
P o w e r
Emergency Power In
Emergency Neutral
Normal Power Sense
Normal Neutral
Emergency Power Out Normal Switch Sense
Cut jumper loop to use with Normally Closed Test Switch
Class 2 0-24 Volt Control Wiring
Push To Test Emergency
Lighting
Normal Neutral
Normal Neutral Control Device
Emergency Lighting
Normal Lighting
CONTACTOR C1
C
O
C O
PC CH1 CH2 CH3 CH4 COM COM 24V GND
REMOTE OVERRIDE
CH1 CH2 CH3 CH4
TIMESWITCH
CH1
CH2
CH3
CH4
H N
N
120 - 277V
NO
C
NO
NC
C
NO
NC
C
NO
NC
C
NC
(3) #12, (1)#12G, 3/4"C
TYPICAL
Switch
LMRC-211
Dimming Room Controller
Neutral Wht
Unswitched
Hot Blk 120/277 Grn
Earth Ground
NORMAL LTG
V io
G ry
Vio Gry
Class 2 0-10 Volt Control Wiring
Emergency Line 120/277
Emergency Neutral
Push to
Test
ELCU-200
R e m o te
A c ti v a ti o n
N o rm a l
P o w e r
E m e rg e n c y
P o w e r
Normal Switched Sense
Red Red
Emergency Power Out
White
Normal Neutral Emergency Neutral
Gray
Normal Power Sense
Black Black
Emergency Power In
Cut jumper loop to use with Normally Closed Test Switch
"Switching" Line
Class 2 0-24 Volt Control Wiring
Push To Test Emergency
Lighting
Leg #1
LIFE SAFETY LTG
LMDM-101
WATTSTOPPER
SPS-2, 8 EXTERIOR SITE POLE LIGHTING
SPS-L, 13 EXTERIOR CANOPY LIGHTING
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
VA Health Care System Approval:
ARCHITECT:
SPUR SBBL COLLABORATIVE JN, INC.
100 N. STONE AVE STE 1102
TUCSON, AZ 85701-1524
(520) 620-0255
NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023
NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024
NM ELEC - EVANS SORDIASHIE #22817 EXP. 12/31/2023
CIVIL / STRUCTURAL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
HEALTHCARE PLANNER
THE INNOVA GROUP
3196 NORTH SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
SPUR #: 1993.10
/9
/2
:3
:0
P
M
ELECTRICAL SCHEDULES & DETAILS
SH Drawing # 72 OF 79ES
BID DOCUMENTS
REPAIR SPS SEWER AND
UPGRADE EQUIPMENT AREA
08/11/2023
501-21-101
RAYMOND G. MURPHY VAMC
1501 SAN PEDRO DRIVE SE
ALBUQUERQUE, NM 87108
E-502
NOTES:
LIGHT FIXTURE SCHEDULE
TYPE
BASIS OF DESIGN:
MANUFACTURER AND MODEL
MOUNTING
LAMP BALLAST/DRIVER
DESCRIPTION
TYPE LUMENS
COLOR
TEMP
TYPE VOLTAGE
INPUT
WATTS
A1 LITHONIA: 2SRTL-L48-3000LM-AFL-MVOLT-EZ1-35K-80CRI-DWAM
GYP. BOARD CEILING.
PROVIDE FLANGE KITS
AS REQUIRED.
INTEGRAL WHITE LED 5000 lm 5000 K
0-10V LOW VOLTAGE DIMMABLE
ELECTRONIC LED DRIVER
277 V 80 W
2'X4' RECESSED CLEAN ROOM LED LIGHT FIXTURE
WITH ANTIMICROBIAL FINISH, GASKETED AND WET
LOCATION LISTED.
A1E LITHONIA: 2SRTL-L48-3000LM-AFL-MVOLT-EZ1-35K-80CRI-DWAM
GYP. BOARD CEILING.
PROVIDE FLANGE KITS
AS REQUIRED.
INTEGRAL WHITE LED 5000 lm 5000 K
0-10V LOW VOLTAGE DIMMABLE
ELECTRONIC LED DRIVER
277 V 80 W SAME AS 'A1' EXCEPT CONNECTED TO LIFE SAFETY BRANCH.
A2 LITHONIA: 2SRTL-L48-5000LM-AFL-MVOLT-EZ1-35K-90CRI-DWAM
GYP. BOARD CEILING.
PROVIDE FLANGE KITS
AS REQUIRED.
INTEGRAL WHITE LED 10000 lm 5000 K
0-10V LOW VOLTAGE DIMMABLE
ELECTRONIC LED DRIVER
277 V 80 W
2'X4' RECESSED CLEAN ROOM LED LIGHT FIXTURE
WITH ANTIMICROBIAL FINISH, GASKETED AND WET
LOCATION LISTED.
A2E LITHONIA: 2SRTL-L48-5000LM-AFL-MVOLT-EZ1-35K-90CRI-DWAM
GYP. BOARD CEILING.
PROVIDE FLANGE KITS
AS REQUIRED.
INTEGRAL WHITE LED 10000 lm 5000 K
0-10V LOW VOLTAGE DIMMABLE
ELECTRONIC LED DRIVER
277 V 80 W SAME AS 'A2' EXCEPT CONNECTED TO LIFE SAFETY BRANCH.
B1 LITHONIA: 2SRTL-L24-3000LM-AFL-MVOLT-EZ1-35K-80CRI-DWAM
GYP. BOARD CEILING.
PROVIDE FLANGE KITS
AS REQUIRED.
INTEGRAL WHITE LED 4665 lm 5000 K
0-10V LOW VOLTAGE DIMMABLE
ELECTRONIC LED DRIVER
277 V 42 W
2'X2' RECESSED CLEAN ROOM LED LIGHT FIXTURE
WITH ANTIMICROBIAL FINISH, GASKETED AND WET
LOCATION LISTED.
B1E LITHONIA: 2SRTL-L24-3000LM-AFL-MVOLT-EZ1-35K-80CRI-DWAM
GYP. BOARD CEILING.
PROVIDE FLANGE KITS
AS REQUIRED.
INTEGRAL WHITE LED 4665 lm 5000 K
0-10V LOW VOLTAGE DIMMABLE
ELECTRONIC LED DRIVER
277 V 42 W SAME AS 'B2' EXCEPT CONNECT TO LIFE SAFETY BRANCH.
F2 HEW: AVX-4-L36/835-CPC-WET/CC-DRV-UNV SURFACE MOUNT INTEGRAL WHITE LED 3677 lm 5000 K
STANDARD ELECTRONIC LED
DRIVER
120 V 31 W 4' LONG OUTDOOR LED STRIP LIGHT
F2E HEW: AVX-4-L36/835-CPC-EM/10WRM-WET/CC-DRV-UNV SURFACE MOUNT INTEGRAL WHITE LED 3677 lm 5000 K
STANDARD ELECTRONIC LED
DRIVER
120 V 31 W SAME AS 'F2' EXCEPT WITH 90-MINUTE BATTERY BACKUP.
PX1
HEW: VA1-L160/740-T5-F-S-UNV-PCR-OCCWS
POLE: RSS4A20SYS12
20' POLE MOUNT LED 15793 lm 4000 K
STANDARD ELECTRONIC LED
DRIVER
277 V 161 W
POLE MOUNTED FIXTURE WITH 20' POLE WITH INTEGRAL PHOTOCELL. SELECT
FINISH COLOR TO MATCH EXISTING. CONFIRM SELECTION WITH ARCH PRIOR TO
PROCUREMENT.
W1E HEW: VWP H-L30/740-T3-SDGL-EM/10WC-UNV-PC WALL MOUNT INTEGRAL WHITE LED 3174 lm 4000 K
STANDARD ELECTRONIC LED
DRIVER
277 V 36 W
EXTERIOR WALLPACK FIXTURE WITH INTEGRAL PHOTOCELL. SELECT FINISH
COLOR TO MATCH EXISTING. CONFIRM SELECTION WITH ARCH PRIOR TO
PROCUREMENT.
X
WILLIAMS EXIT/CA SERIES:
EXIT/CA-R-AF-BA-EM-SDT
UNIVERSAL TOP/END
MOUNT
LED 0 lm 0 K STANDARD EXIT SIGN LED DRIVER 277 V 4 W
UNIVERSAL MOUNT, SINGLE/DOUBLE FACE EXIT SIGN WITH RED LETTERING
BRUSHED ALUMINUM HOUSING, SELF DIAGNOSTICS AND CONNECTED TO LIFE
SAFETY BRANCH CIRCUIT.
NTS
TYPICAL LINE-VOLTAGE CONTROL DIAGRAM2 NTS
EXTERIOR LIGHTING CONTROL DIAGRAM1
E. DO NOT INSTALL LINE VOLTAGE SENSORS ON GFCI PROTECTED CIRCUITS.
D. ALL SENSORS SHALL HAVE AN ADJUSTABLE TIME DELAY RANGE OF 30 SECONDS TO 30 MINUTES, UNLESS NOTED OTHERWISE.
C. VERIFY COLOR(S) FOR WALL SWITCHES WITH ARCHITECT.
B. PROVIDE ALL SENSORS FROM SAME MANUFACTURER.
A. SENSOR LAYOUT BASED ON COVERAGE PATTERNS OF MANUFACTURER INDICATED BELOW. ADJUST QUANTITIES AND LOCATIONS FOR ALTERNATE MANUFACTURERS.
GENERAL NOTES:
OCCUPANCY SENSOR AND SWITCH SCHEDULE
SYMBOL
TYPE
BASIS OF DESIGN: MANUFACTURER
AND MODEL
VOLTAGE COVERAGE ON MODE
TIME
DELAY
DESCRIPTION
WATTSTOPPER: DW-100-U 120/277V N/A MANUAL
MINUTES
LINE VOLTAGE, 1-BUTTON DUAL TECHNOLOGY OCCUPANCY LIGHT
SWITCH.
WATTSTOPPER: ELCU-200
120/277V, 24V DC
REMOTE
N/A N/A N/A
EMERGENCY LIGHTING CONTROL UNIT. PROVIDE WITH ENCLOSURE
AND MOUNT ABOVE CEILING. PROVIDE CONNECTION TO REMOTE
TEST SWITCH.
WATTSTOPPER: LMDC-100-U
24V DC
INPUT
MINIMUM 28', 360 DEGREE
RADIAL COVERAGE AT 9'
MOUNTING HEIGHT
MANUAL
MINUTES
CEILING MOUNTED, DUAL TECHNOLOGY DIGITAL VACANCY SENSOR
COMPATIBLE WITH DIGITAL ROOM CONTROLLER WITH CAT5E
NETWORKING.
WATTSTOPPER: LMDM-101-U
24V DC
INPUT
N/A MANUAL N/A
LOW VOLTAGE, 1-BUTTON DIMMING DIGITAL LIGHT SWITCH
COMPATIBLE WITH DIGITAL ROOM CONTROLLER WITH CAT5E
NETWORKING.
WATTSTOPPER: LMRC-211-U
120/277V, 24V DC,
0-10V DC
DIMMING
N/A N/A N/A
ONE RELAY/ZONE DIGITAL ROOM CONTROLLER WITH 0-10V DIMMING
OUTPUT AND CAT5E NETWORKING WITH CONTROL DEVICES.
NTS
TYPICAL LOW VOLTAGE EMERGENCY LIGHTING CONTROLS3
ATS-SPS 1 (NEW)
3P
600A
3000 AMPS 480Y/277V, 3PH, 4W
TRASH COURTYARD, NEMA 3R
SWBD-SPS (NEW)
3000AF
3000AT
3P
600AF
600AT
3P
600AF
600AT
3P
PAD-MOUNTED
XFMR 'TR-T77'
2500 KVA
12470V – 480Y/277V
3PH, 4W
ATS-SPS 2 (NEW)
3P
600A
600AF
600AT
3P
600 AMPS 480Y/277V, 3PH, 4W
EXTERIOR BY SPS-T1 (ON UNISTRUT)
PANEL SPS-1 (NEW)
600AF
600AT
3P
250AF
250AT
3P
70AF
70AT
3P
250AF
250AT
3P
T
G
TX-SPS-L
45 KVA
480V – 208V
3PH, 4W
20AF
20AT
3P
P N
L B
D S
P S
-L
100AS
2P
80AT
100AS
2P
80AT
600 AMPS 480Y/277V, 3PH, 4W
EXTERIOR BY SPS-T2 (ON UNISTRUT)
PANEL SPS-2 (NEW)
600AF
600AT
3P
250AF
250AT
3P
250AF
250AT
3P
20AF
20AT
3P
20AF
20AT
3P
20AF
20AT
1P
20AF
20AT
1P
20AF
20AT
1P
20AF
20AT
3P
800AF
800AT
3P
G F
R
ETR
30AF
30AT
3P
SPD
30AF
30AT
3P
SPD
1MVA STANDBY (ESSENTIAL)
480Y/277V, 3PH, 4W
600A/3P M/G
600A/3P
31656 FCA
1.8% CVD
29205 FCA
1.9% CVD
2095 FCA
2.9% CVD
2095 FCA
2.9% CVD
2325 FCA
2.6% CVD
25472 FCA
47217 FCA
1.3% CVD
45552 FCA
1.3% CVD
44752 FCA
1.3% CVD
24656 FCA 24656 FCA 2047 FCA
2056 FCA24656 FCA24656 FCA
NEMA 3R NEMA 3R
SOUTH
BUILDING 41
EXTERIOR
TO MOBILE
SPS-T1 PNL-
PP1
TO MOBILE
SPS-T1 PNL-
PP2
TO MOBILE SPS 1
COLD WEATHER
PACKAGE
TO MOBILE
SPS-T2 PNL-
PP1
TO MOBILE
SPS-T2 PNL-
PP2
SPS TRAILER 1 (SPS-T1)
SPARE SPARE
EXTERIOR LIGHTS
AROUND
TEMPORARY SPS
TRAILERS
TO EXISTING BLDG. 77
PANEL SES-HPDU-A
BEHIND BUILDING.
FROM
EXISTING
MV SWITCH
SPARE SPARE
TO MOBILE SPS 2
COLD WEATHER
PACKAGE
TO TEMP-
AH-1
TEMP-
AH-2
SPS TRAILER 2 (SPS-T2)
-2.5% PRI TAP
CRITICAL POWERCRITICAL POWER
CRITICAL POWER CRITICAL POWER
NORMAL POWER
CONCRETE
ENCASED
CONCRETE
ENCASED
SOUTH
BUILDING 41
EXTERIOR
(NEW)
SPARE
GENERAL NOTES:
A. PRELIMINARY FAULT CALCULATIONS ARE SHOWN. CONTRACTOR SHALL FIELD
VERIFY EXACT ROUTINGS AND REQUIRED LENGTHS. PROVIDE FINAL CALCULATIONS
FOR NEW EQUIPMENT IN ACCORDANCE WITH SPECIFICATION 26 05 73..
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked…
This is the start of the file's text. The full file is on GovTribe.