ATTACHMENT 1G - Drawings-Mechanical.pdf
PDF 2 MB Posted
- Solicitation number
- 36C26224B0007
About this file
This document package includes drawings and specifications for mechanical HVAC system repairs and upgrades at the Raymond G. Murphy VA Medical Center in Albuquerque, New Mexico. The scope of work involves repairing the Sterile Processing Service sewer system and upgrading equipment areas in Building 41. Drawings show the existing basement layout, proposed demolition plans, new work plans including mechanical, piping, and control details. Specifications include schedules for ductwork, fans, air handling units, controls points, and sequence of operations. The solicitation number is 36C26224B0007 with an estimated value over $250,000. The contracting agency is the Department of Veterans Affairs.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ABBREVIATIONS
HVAC PIPING TYPES
GENERAL DUCT SYMBOLS
A/E ARCHITECT / ENGINEER
AAHX AIR TO AIR HEAT EXCHANGER
AB AIR BLENDER
AAV AUTOMATIC AIR VENT
ACC AIR COOLED CONDENSER
ACU AIR CONDITIONING UNIT
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFW AIR FOIL WHEEL (FAN)
AHU AIR-HANDLING UNIT
AMP AMPERAGE
AP ACCESS PANEL
APD AIR PRESSURE DROP
ARI AIR CONDITIONING AND REFRIGERATION
INSTITUTE
AS AIR SEPARATOR
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AW AIR WASHER
AXF AXIAL FLOW
B
B BOILER
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BFP BACKFLOW PREVENTER
BHP BRAKE HORSEPOWER
BHX BOILER BLOWDOWN HEAT EXCHANGER
BIW BACKWARD INCLINED WHEEL (FAN)
BSC BIOLOGICAL SAFETY CABINETS
BT BLOWOFF TANK
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C
C CENTIGRADE (CELSIUS)
CC COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CENT CENTRIFUGAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFT CUBIC FEET
CFP CHEMICAL FEED PUMP
CH CHILLER
CHP CHILLED WATER PUMP
CHW CHILLER WATER
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CI CAST IRON
CM CUBIC METER
CM/S CUBIC METER PER SECOND
CO CARBON MONOXIDE
CO2 CARBON DIOXIDE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
CP CONDENSATE PUMP
CS CONDENSATE STORAGE TANK
CSG CLEAN STEAM GENERATOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONSTANT VOLUME
CW COLD WATER (POTABLE)
CC CHILLED WATER COOLING COIL
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
A
F
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
FA FREE AREA
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT
FCUC FAN COIL UNIT COOLING ONLY
FCUH FAN COIL UNIT HEATING ONLY
FCW FORWARD CURVED WHEEL (FAN)
E
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC EVAPORATIVE COOLER
ECC ENGINEERING CONTROL CENTER
ECU EVAPORATIVE CONDENSER UNIT
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EGS EMERGENCY GAS SHUTOFF
EGT ENTERING GLYCOL TEMPERATURE
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ERC ELECTRIC REHEAT COIL
ERP ELECTRIC RADIANT PANEL
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETO ETHYLENE OXIDE
ETR EXISTING TO REMAIN
EUH ELECTRIC UNIT HEATER
EWC EVAPORATIVE WATER COOLER
EWT ENTERING WATER TEMPERATURE
EX. EXISTING
D
DB DECIBELS
Db DRY-BULB TEMPERATURE
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DIA DIAMETER
DIW DEIONIZED WATER
DP DEW POINT TEMPERATURE
DPA DIFFERENTIAL PRESSURE ASSEMBLY
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
FD FIRE DAMPER
FF FINAL FILTER
FHX FLUE GAS/FEEDWATER HEAT EXCHANGER
FM FLOW METER
FOP FUEL OIL PUMP
FOT FUEL OIL TANK
FOHX FUEL OIL HEAT EXCHANGER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FPTU FAN POWERED TERMINAL UNIT
FRP FIBER REINFORCED POLYESTER
FS FLOW SWITCH
FSTAT FREEZESTAT
FT FEET
FT-LB FOOT-POUND
FTR FIN TUBE RADIATION
FV FACE VELOCITY
FSD COMBINATION FIRE / SMOKE DAMPER
G
GA GAUGE
GAL GALLONS
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GS GALVANIZED STEEL
K kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR
J
J INTENTIONALLY LEFT BLANK
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICF IN-LINE CENTRIFUGAL FAN
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCH WATER COLUMN
IN WG INCH WATER GAUGE
IN-LB INCH-POUND
IPLV INTEGRATED PART LOAD VALUE
IRH INFRARED HEATER
IS INSECT SCREEN
IU INDUCTION UNIT
IV INLET VANES
H
HU HUMIDIFIER
H&CW HOT & COLD WATER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HEAD
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPC HIGH PRESSURE STEAM CONDENSATE RETURN
HPS HIGH PRESSURE STEAM (61-300 PSIG)
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRP HYDRONIC RADIANT (CEILING) PANEL
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HTM HUMIDIFIER TERMINAL
HUM HUMIDIFIER UNIT MOUNTED
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HC HOT WATER HEATING COIL
HHP HEATING HOT WATER PUMP
HHR HEATING HOT WATER RETURN
HHS HEATING HOT WATER SUPPLY
HHUH HOT WATER UNIT HEATER
HX HEAT EXCHANGER
HZ HERTZ
I
L
L LITER
L/h LITERS PER HOUR (OR LITERS/HOUR) L/m LITERS PER MINUTE (OR LITERS/MINUTE) L/s LITERS PER SECOND (OR LITERS/SECOND)
LAT LEAVING AIR TEMPERATURE
LBS/HR POUNDS PER HOUR
LF LINEAR FOOT (FEET)
LGT LEAVING GLYCOL TEMPERATURE
LH LATENT HEAT
LPG LIQUID PROPANE GAS
LPC LOW PRESSURE STEAM CONDENSATE RETURN
CLPC LOW PRESSURE STEAM CONDENSATE (CLEAN)
LLHX LIQUID TO LIQUID HEAT EXCHANGER
LPS LOW PRESSURE STEAM (0-15 PSIG)
CLPS LOW PRESSURE STEAM (CLEAN)
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
N
NA NOT APPLICABLE
NC NOISE CRITERIA
NG NATURAL GAS
NGFM NATURAL GAS FLOWMETER
NOAA NATIONAL OCEANIC & ATMOSPHERIC
ADMINISTRATION
M
M METER, SI UNIT
M/s METERS PER SECOND
(OR METERS/SECOND)
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKE-UP AIR UNIT
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
MERV MINIMUM EFFICIENCY REPORTING VALUE
MH MANHOLE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MM MILLIMETER
MOV MOTOR OPERATED VALVE
MPC MEDIUM PRESSURE STEAM CONDENSATE
RETURN
MPS MEDIUM PRESSURE STEAM (16-60 PSIG)
MTD MEAN TEMPERATURE DIFFERENCE
MVD MANUAL VOLUME DAMPER
MZ MULTI-ZONE
P
P PUMP
PA PASCAL
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT (FEET)
PD PRESSURE DROP
PF PRE-FILTER
PG PRESSURE GAGE
PGW PROPYLENE GLYCOL-WATER (SOLUTION)
PHC PREHEAT COIL
PPM PARTS PER MILLION
PRS PRESSURE REGULATING (VALVE) STATION
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH – ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
PTAC PACKAGED TERMINAL AIR CONDITIONER
O
OA OUTSIDE AIR
OAI OUTSIDE AIR INTAKE
OD OUTSIDE DIAMETER
OFM OIL FLOWMETER
OSD ORGANIC SOIL FILTER
Q
Q INTENTIONALLY LEFT BLANK
T&PCV TEMPERATURE AND PRESSURE
CONTROL VALVE
TAB TESTING, ADJUSTING, BALANCE
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TG TRANSFER GRILLE
TP TRAP
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
TWU THRU-WALL UNIT
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SC SHADING COEFFICIENT
SCFM STANDARD CUBIC FEET PER MINUTE
SCR SILICON CONTROLLED RECTIFIER
DSD DUCT SMOKE DETECTOR
SD SMOKE DAMPER
SEN SENSIBLE HEAT
SF SUPPLY FAN
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SI SQUARE INCHES
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT (FEET)
SS STAINLESS STEEL
SSHX STEAM TO STEAM HEAT EXCHANGER
SSR SOLID SEPARATOR
ST STEAM TRAP
SUH STEAM UNIT HEATER
SVS STEAM VENT SILENCER
SWHX STEAM TO WATER HEAT EXCHANGER
R
R/E RETURN OR EXHAUST
RA RETURN AIR
RAD REFRIGERANT AIR DRYER
RAF RADIO FREQUENCY
RAHX ROTARY AIR HEAT EXCHANGER
RAT RETURN AIR TEMPERATURE
RCCH REMOTE CONDENSER CHILLER
RCU RECIPROCATING CHILLER UNIT
RD REFRIGERANT DISCHARGE
REA RELIEF AIR
RF RETURN FAN
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
RO REVERSE OSMOSIS
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
RTU ROOF TOP UNIT
RV RELIEF VALVE
T
UC UNDER CUT
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
URV UPBLAST UNIT VENTILATOR
U
X INTENTIONALLY LEFT BLANK
W
W WATTS
WAG WASTE ANESTHESIA GAS
Wb WET-BULB (TEMPERATURE)
WC WATER COOLED
WCCH WATER COOLED CHILLER
WCCU WATER COOLED CONDENSING UNIT
WCHP WATER COOLED HEAT PUMPS
WCPU WATER COOLED PACKAGED UNIT
WF WATER FILTER
WFM WATER FLOWMETER
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
V VALVE
VAF VANE-AXIAL FAN
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL OPPOSED BLADE)
VFD VARIABLE FREQUENCY DRIVE
VI VIBRATION ISOLATOR
VIV VARIABLE INLET VANES
VP VACUUM PUMP
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE) RETURN
VSD VARIABLE SPEED DRIVE
VUH VERTICAL UNIT HEATER
X
V
GENERAL NOTES:
A. MECHANICAL PLANS AND SECTIONS ARE INTENDED TO ACCURATELY ILLUSTRATE THE
SCOPE OF WORK BUT ARE STILL DIAGRAMMATIC IN NATURE.
B. MECHANICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE
CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY
FUNCTIONAL AND COMPLIANT WITH APPLICABLE CODES.
C. THE EXISTING CONDITIONS DEPICTED IN THESE PLANS ARE BASED ON AS-BUILT
DOCUMENTATION AND INFORMATION OBTAINED FROM FIELD SURVEYS AND ARE AS
ACCURATE AS POSSIBLE. DUE TO OBSTRUCTIONS, CEILINGS, ETC., NOT ALL CONDITIONS
COULD BE VERIFIED. THE CONTRACTOR SHALL SURVEY THE SITE PRIOR TO BID AND
NOTIFY THE ARCHITECT/ENGINEER OF ANY CONFLICTS, OBSTRUCTIONS, OR
INCONSISTENCIES PREVENTING INSTALLATION OF THE MECHANICAL SYSTEM.
D. ALL EXPOSED UNINSULATED PIPING SHALL BE PAINTED PER THE SPECIFICATION SECTION
"PAINTING".
E. PROVIDE VIBRATION ISOLATION FOR ALL MECHANICAL EQUIPMENT TO PREVENT
TRANSMISSION OF VIBRATION TO BUILDING STRUCTURE.
F. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH ARCHITECTURAL,
STRUCTURAL, CIVIL, ELECTRICAL WORK, ETC., SHOWN ON OTHER CONTRACT DOCUMENT
DRAWINGS.
G. MAINTAIN A MINIMUM OF 6′-8″ CLEARANCE TO UNDERSIDE OF PIPES, DUCTS, CONDUITS,
SUSPENDED EQUIPMENT, ETC., THROUGHOUT ACCESS ROUTES IN MECHANICAL ROOMS.
H. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT OR PIPING
INSULATION IS APPLIED.
I. LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN ACCESSIBLE
LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP AND DOWNSTREAM AS
RECOMMENDED BY THE MANUFACTURER FOR GOOD ACCURACY.
J. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS CERTIFIED
DRAWINGS. COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS REQUIRED
FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND
COORDINATE ALL DUCT AND PIPING DIMENSIONS BEFORE FABRICATION.
CWR
CWS
CD
LPC
LPS
MPC
MPS
HPC
HPS
CONDENSATE DRAIN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
HIGH PRESSURE STEAM CONDENSATE
HIGH PRESSURE STEAM SUPPLY
MEDIUM PRESSURE STEAM CONDENSATE
MEDIUM PRESSURE STEAM SUPPLY
LOW PRESSURE STEAM CONDENSATE
LOW PRESSURE STEAM SUPPLY
VACUUM RETURN
FEEDWATER PUMP DISCHARGE
FEEDWATER PUMP SUCTION
VR
CONTINUOUS BLOWDOWN
CHEMICAL FEED
BOILER BLOWOFF BO
CF
CBD
FWPD
FWPS
A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO
INSTALL COMPLETE AND OPERABLE PIPING SYSTEMS AS INDICATED ON THE DRAWINGS, AS
SPECIFIED AND AS REQUIRED BY CODE.
B. UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD, TIGHT TO UNDERSIDE OF
STRUCTURE OR SLAB, WITH SPACE FOR INSULATION IF REQUIRED.
C. INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS, TRAPS, FLANGES, AND OTHER
APPURTENANCES REQUIRING ACCESS ARE ACCESSIBLE.
D. ALL VALVES SHALL BE INSTALLED SO THAT VALVE REMAINS IN SERVICE WHEN EQUIPMENT
OR PIPING ON EQUIPMENT SIDE OF VALVE IS REMOVED.
E. UNIONS AND/OR FLANGES SHALL BE INSTALLED AT EACH PIECE OF EQUIPMENT, IN
BYPASSES, AND IN LONG PIPING RUNS (100' OR MORE) TO PERMIT DISASSEMBLY FOR
ALTERATION AND REPAIRS.
F. PITCH STEAM PIPING DOWNWARD IN THE DIRECTION OF FLOW 1/4" IN 10' (1" IN 40') MINIMUM.
PITCH ALL STEAM RETURN LINES DOWNWARD IN THE DIRECTION OF CONDENSATE FLOW
1/2" PER 10' (1" IN 20') MINIMUM. WHERE LENGTH OF BRANCH LINES ARE LESS THAN 8', PITCH
BRANCH LINES TOWARD MAINS 1/2" PER FOOT MINIMUM.
G. PITCH UP ALL STEAM AND CONDENSATE RUNOUTS TO RISERS AND EQUIPMENT 1/2" PER
FOOT. WHERE THIS PITCH CANNOT BE OBTAINED, RUNOUTS OVER 8' IN LENGTH SHALL BE
ONE SIZE LARGER THAN NOTED.
H. TAP ALL BRANCH LINES FROM TOP OF STEAM MAINS (45° PREFERRED, 90° ACCEPTABLE).
I. PROVIDE AN END OF MAIN DRIP AT EACH RISE IN THE STEAM MAIN. PROVIDE CONDENSATE
DRIPS AT THE BOTTOM OF ALL STEAM RISERS, DOWNFED RUNOUTS TO EQUIPMENT,
RADIATORS, ETC., AT END OF MAINS AND LOW POINTS, AND AHEAD OF ALL PRESSURE
REGULATORS, CONTROL VALVES, ISOLATION VALVES, AND EXPANSION JOINTS.
J. ON STRAIGHT STEAM PIPING RUNS WITH NO NATURAL DRAINAGE POINTS, INSTALL DRIP
LEGS AT INTERVALS NOT EXCEEDING 200' WHERE PIPE IS PITCHED DOWNWARD IN THE
DIRECTION OF STEAM FLOW AND A MAXIMUM OF 100' WHERE THE PIPE IS PITCHED UP SO
THAT CONDENSATE FLOW IS OPPOSITE OF STEAM FLOW.
K. STEAM TRAPS SHALL BE MINIMUM 3/4″ IN SIZE.
L. ALL PIPING WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN
PIPING AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE
OWNER.
A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO
INSTALL COMPLETE AND OPERABLE HVAC SYSTEMS AS INDICATED ON THE DRAWINGS, AS
SPECIFIED AND AS REQUIRED BY CODE.
B. CERTAIN ITEMS SUCH AS RISES AND DROPS IN DUCTWORK, ACCESS DOORS, VOLUME
DAMPERS, ETC., ARE INDICATED ON THE CONTRACT DOCUMENT DRAWINGS FOR CLARITY
FOR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED AS THE
EXTENT OF THE REQUIREMENTS FOR THESE ITEMS.
C. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS, ARE INTERNAL CLEAR
DIMENSIONS AND DUCT SIZE SHALL BE INCREASED TO COMPENSATE FOR DUCT LINING
THICKNESS.
D. PROVIDE ALL 90° SQUARE ELBOWS WITH DOUBLE RADIUS TURNING VANES UNLESS
OTHERWISE INDICATED. ELBOWS IN DISHWASHER, KITCHEN, AND LAUNDRY EXHAUST
SHALL BE UNVANED SMOOTH RADIUS CONSTRUCTION WITH A RADIUS EQUAL TO 1.5 TIMES
THE WIDTH OF THE DUCT. PROVIDE ACCESS DOORS UPSTREAM OF ALL ELBOWS WITH
TURNING VANES.
E. COORDINATE DIFFUSER, REGISTER, AND GRILLE LOCATIONS WITH ARCHITECTURAL
REFLECTED CEILING PLANS, LIGHTING, AND OTHER CEILING ITEMS AND MAKE MINOR DUCT
MODIFICATIONS TO SUIT.
F. PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS (SUPPLY, RETURN, AND
EXHAUST) CONNECTED TO AIR HANDLING UNITS, FANS, AND OTHER EQUIPMENT WHICH
REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT THE
POINT OF CONNECTION TO THE EQUIPMENT UNLESS OTHERWISE INDICATED.
G. RUNS OF FLEXIBLE DUCT SHALL NOT EXCEED 5' MAXIMUM LENGTH.
H. ALL DUCTWORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN
DUCTS, INCLUDING DIVIDED DUCTS AND TRANSITIONS AROUND OBSTRUCTIONS, SHALL BE
PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
I. PROVIDE ACCESS DOORS IN DUCTWORK FOR OPERATION, ADJUSTMENT, AND
MAINTENANCE OF ALL FANS, VALVES, AND MECHANICAL EQUIPMENT.
J. SEE SPECIFICATIONS FOR DUCTWORK GAUGES, BRACING, HANGERS, AND OTHER
REQUIREMENTS.
PIPING GENERAL NOTES: HVAC/SHEET METAL GENERAL NOTES:
EXISTING TO BE DEMOLISHED
LIMIT OF DEMOLITION
CONNECT NEW TO EXISTINGEXISTING TO REMAIN
NEW DUCT (INSIDE DIMENSIONS: W" X D")
RS
RL
REFRIGERANT SUCTION
REFRIGERANT LIQUID
SUPPLY AIR DUCT UP
SUPPLY AIR DUCT DOWN
H
T
H
T
26-P-3
MH-100
PUMP NO. 3 IN BUILDING NO. 26
EQUIPMENT ABBREVIATION (PUMP)
DETAIL NUMBER
SHEET NUMBER
SHEET NUMBER
SECTION NUMBER
THERMOSTAT
HUMIDISTAT
TEMPERATURE SENSOR
HUMIDITY SENSOR
BUILDING NUMBER WHERE EQUIPMENT IS LOCATED
26-TU-1-1
ITEM NUMBER (TERMINAL UNIT NO. 1)
ITEM (TERMINAL UNIT)
BUILDING NUMBER WHERE EQUIPMENT IS LOCATED
SERVED BY AIR HANDLER UNIT NO. 1
TERMINAL UNIT TAG
MECHANICAL EQUIPMENT TAG
1 OWNER FURNISHED, CONTRACTOR
INSTALLED EQUIPMENT DESIGNATION
EXISTING TO BE DEMOLISHED
EXISTING TO REMAIN
NEW PIPE
CONNECT NEW TO EXISTING
LIMIT OF DEMOLITION
GENERAL PIPING SYMBOLS
GENERAL ANNOTATIONS
AV
STRAINERFLOAT & THERMOSTATIC
STEAM TRAP
INVERTED BUCKET
STEAM TRAP
FLANGE CONNECTION PIPE DROP
PIPE RISER TEE DOWN
TEE UP
UNION
PRESSURE REDUCING
VALVE
BALL VALVE
ANGLE GLOBE VALVE
SAFETY RELIEF VALVE
GLOBE VALVE
MANUAL OR
AUTOMATIC AIR VENT
EXPANSION JOINT
EJ
PRESSURE AND
TEMPERATURE TEST PLUG
QUICK-COUPLE HOSE
CONNECTOR
FLOW METER
HVAC PIPING SYMBOLS
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CHR
CHS
HEATING HOT WATER RETURN
HEATING HOT WATER SUPPLY
HHR
HHS QV CRYOGEN VENT
DR DRIP RETURN
CAP
REDUCER (ECCENTRIC)
TYPE
AIRFLOW (CFM)
SD-1
TYPE
AIRFLOW (CFM)
RG-1
TYPE
AIRFLOW (CFM)
EG-1
SQUARE TO ROUND TRANSITION
ELBOW WITH TURNING
VANES
ROUND ELBOW
EXHAUST, RELIEF, MAKE UP, OR
OUTSIDE AIR DUCT DOWN
EXHAUST, RELIEF, MAKE UP, OR
OUTSIDE AIR DUCT UP
RETURN DUCT DOWN
RETURN DUCT UP
BRANCH DUCT WITH HIGH EFFICIENCY
TAKE-OFF (HETO) BRANCH FITTING &
MANUAL VOLUME DAMPER
BRANCH DUCT WITH CONICAL
FITTING & MANUAL VOLUME
DAMPER
DAMPERS: (BD, FD, FSD, MD, SD, VD)
BD
XX-XX
ANCHOR
TEEDIRECTION OF FLOW
S
K. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR CALLED FOR IN THE
SPECIFICATIONS THAT ARE NOT DEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE
ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE BEST CONDITIONS AND
RESULTS MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS AND SHALL HAVE THE
APPROVAL OF THE ENGINEER BEFORE BEING INSTALLED. DO NOT SCALE DRAWINGS.
L. PROVIDE ACCESS PANELS FOR INSTALLATION IN WALLS AND CEILINGS WHERE REQUIRED
TO SERVICE DAMPERS, VALVES, SMOKE DETECTORS, AND OTHER CONCEALED
MECHANICAL EQUIPMENT.
M. LOCATIONS AND SIZES OF ALL FLOOR, WALL, AND ROOF OPENINGS SHALL BE
COORDINATED WITH ALL OTHER TRADES INVOLVED.
N. ALL OPENINGS IN FIRE WALLS DUE TO DUCTWORK, PIPING, CONDUIT, ETC., SHALL BE FIRE
STOPPED WITH AN APPROVED FIRE STOPPING MATERIAL.
O. REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING, AND EQUIPMENT INSTALLATION.
DIRECTION OF PIPE
PITCH (DOWN)
FM
MV
HVAC VALVE SYMBOLS
PC PUMPED CONDENSATE
SPACE TAG
FLEXIBLE CONNECTOR
PUMP
REDUCER (CONCENTRIC)
GATE VALVE
BUTTERFLY VALVE
CHECK VALVE
THERMOMETER
PRESSURE GAUGE
STRAINER WITH BLOWOFF
AND HOSE CONNECTION
YR YEAR
Y
Z INTENTIONALLY LEFT BLANK
Z
M
CONTROL VALVE
CONTROL VALVE, THREE WAY
MOTOR CONTROLLED
VALVE
M
M
NOTE: NOT ALL ABBREVIATIONS OR SYMBOLS WILL BE UTILIZED FOR THIS PROJECT.
A. MECHANICAL TRADES BIDDING DEMOLITION WORK SHALL ALLOW FOR A FULL DAY ON SITE TO REVIEW EXISTING MECHANICAL SERVICES AND EQUIPMENT IN DEMOLITION AND REMOVED AREAS. ACCESS WILL BE GIVEN TO ROOF AND EXISTING MECHANICAL AND ELECTRICAL ROOMS AS REQUIRED. VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK. BRING ANY DISCREPANCIES FROM THE DRAWINGS AND NOTES TO THE ENGINEER OF RECORD IMMEDIATELY. MINOR CHANGES IN THE SCOPE OF THE
DEMOLITION WORK SHALL NOT JUSTIFY AN ADDITIONAL COST.
B. DEMOLISHED WORK SHALL INCLUDE FOR TEMPORARY AND PERMANENT WORK REQUIRED TO KEEP
NON-SCOPE AREAS IN OPERATION. COORDINATE UTILITY SHUT-OFFS AND TEMPORARY POWER,
STORAGE, AND ACCESS NEEDED TO COMPLETE WORK WITH GENERAL CONTRACTOR AND COR.
C. REMOVAL OF EXISTING FIXTURES AND EQUIPMENT WILL REQUIRE ISOLATION OF EXISTING PIPING BRANCHES AND/OR MAINS USING SHUTOFF VALVES. INSTALL NEW ISOLATION VALVES AS REQUIRED TO
COMPLETION DEMOLITION WORK.
D. REMOVAL OF EXISTING PLUMBING FIXTURES AND EQUIPMENT WILL REQUIRE CAPPING AND SEALING EXISTING MAINS OR BRANCHES, WITHOUT LEAVING DEAD LEGS, TO KEEP REMAINING SYSTEMS IN OPERATION. THE CONTRACTOR SHALL PROVIDE PROTECTIVE MEASURES TO PROTECT THE EXISTING
OCCUPIED AREAS AND EQUIPMENT DURING THE CONSTRUCTION WORK. THE CONTRACTOR SHALL
CLEAN THE AREAS OF ALL CONSTRUCTION DIRT DAILY, AND UPON COMPLETION OF THE WORK.
E. COORDINATE REMOVAL, REPLACEMENT, AND/OR REPAIRS OF ANY EXISTING WALLS, CEILING, ETC.
REQUIRED FOR MECHANICAL DEMOLITION WORK WITH GENERAL CONTRACTOR.
F. PROVIDE TIGHTLY SEALED AND INSULATED TERMINATIONS FOR ALL PIPING, DUCTWORK, AND EQUIPMENT REMOVED FROM THE PROJECT. THERE SHALL BE NO "DEAD LEG" SECTIONS OF PIPING
WHERE WATER CAN SIT AND BECOME STAGNANT.
G. REFER TO THE CONTRACTING OFFICER'S REPRESENTATIVE (COR) FOR INSTRUCTIONS REGARDING THE
REMOVAL AND RETURN OR DEMOLITION OF EXISTING EQUIPMENT AND FIXTURES.
H. PORTIONS OF EXISTING SYSTEMS ARE SHOWN FOR CLARITY AND MAY NOT BE NECESSARY TO MODIFY OR REVISE THEM. ALL EXISTING SYSTEMS ARE SHOWN BASED ON AVAILABLE AS-BUILT DRAWINGS AND SITE SURVEYS OF ACCESSIBLE AREAS. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS.
I. ALL WORK MUST BE COORDINATED AND SCHEDULED WITH THE CONTRACTING OFFICER'S
REPRESENTATIVE TO ENSURE THE LEAST AMOUNT OF DISRUPTION OF BUILDING ACTIVITIES AS
POSSIBLE.
J. ALL ACCESSIBLE ABANDONED PIPING AND DUCTWORK SHALL BE REMOVED AND PROPERLY DISPOSED
OF.
K. SUPPLY AIR DUCTWORK AND PIPING NOT SHOWN HATCHED IS TO BE RETAINED, ANY DAMAGE TO
EXISTING INSULATION AND DUCTS TO BE REPAIRED TO MATCH EXISTING.
GENERAL DEMOLITION NOTES:
B-100
SPACE NAME
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR SBBL COLLABORATIVE JN, INC.
100 N. STONE AVE STE 1102
TUCSON, AZ 85701-1524
(520) 620-0255
NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023
NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024
NM ELEC - EVANS SORDIASHIE #22917 EXP. 12/31/2023
CIVIL / STRUCTURAL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
HEALTHCARE PLANNER
THE INNOVA GROUP
3196 NORTH SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:2 :0
A
M
LEGEND AND ABBREVIATIONS
RAC 57JRM
BID DOCUMENTS
REPAIR SPS SEWER AND
UPGRADE EQUIPMENT AREA
08/11/2023
501-21-101
RAYMOND G. MURPHY VAMC
1501 SAN PEDRO DRIVE SE
ALBUQUERQUE, NM 87108
M-000
SPUR #: 1993.10
No. REVISION DESCRIPTION DATE
S A
N
P
ED
R O
DR
I V E
DR
IV
E
R
I DG
EC RE
ST
5 350
5 350
3 5
5 340
5348.7
5348.5
5347.2
5337.2
5345.6
5348.6
5347.8
5346.9
5328.7
5347.0
5347.2
5347.4
5346.8
5348.6
5348.4
5348.4
5348.3
5348.1
5348.2
5348.2
5348.2
5347.3
5346.8
5349.0
5348.75348.2
5347.2
5347.2
5346.6
5345.2
5346.5
5346.6 5347.0
5345.2
5340.7
5337.1
5340.4
5342.7
5338.4 5335.6
5339.4
5339.1
5340.1
5336.3
5342.9
5345.6
5340.8
5327.1
5322.8
5324.4
5328.4
5323.2
5322.7
5320.8
5320.5
5340.5
5339.6 5340.7 5342.8
5348.8 5350.1
5348.2
5349.4
5349.8
5351.2
5350.2
5340.8
5348.5
5348.3
5344.5
5346.6
5346.7
5344.6
5340.3
5342.4
5342.7
5347.2
5346.4
5348.6
5346.5
5345.4
5345.2
5344.4 5346.5
5344.2
5342.8
5345.2
5340.2
5340.9
5338.6
5337.8
5342.85340.9
5340.9 5342.7
5344.4
5344.4
5344.8
5345.2
5345.2
5346.7
5346.7
5348.4
5346.5
5346.5 5346.6 5347.1
5348.8
5348.3
5348.2
5347.7
5349.0
5350.6
5349.0
5326.8
5326.5
5355.0
5350.8
5348.7
5344.8
5346.4
5348.4
5332.4
5342.8
5344.7
5349.6
5340.6
5340.1
5348.5
5336.5
5339.0
5352.4
5330.4
5326.3
5328.2
5350.9
5348.4
5346.6
5341.15344.9
5345.3
5347.3
5343.5
5346.2
5346.7
5344.9
5349.1
5338.8
5340.6
5341.2
5338.6
5336.6
5337.1
5334.6
5334.6
5328.7
5328.2
5327.0
5326.7
5325.2
5324.5
W
ALL
C O U
RT
C OU RT
C OU RT
W A
LL
WALK
EN CLOSED
WALK
EN CLOSED
W
ALL
E N
CL
OS ED
W
ALK
W
ALL
W
ALL
W A
LL
W A
LL
W A
LL
W
ALL
W
ALL
W A
LL
W
AL LS
W A
LL
W A
LL
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
TEMPORARY SPS FACILITY
SE LOT NEAR BUILDING 45
RAYMOND G. MURPHY VA MEDICAL CENTER CAMPUS
N
B45
B41
STERIS TRAILER
#1
STERIS TRAILER
#2
MECHANICAL EQUIP.
TEMP-AH-1
TEMP-AH-210
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR SBBL COLLABORATIVE JN, INC.
100 N. STONE AVE STE 1102
TUCSON, AZ 85701-1524
(520) 620-0255
NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023
NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024
NM ELEC - EVANS SORDIASHIE #22917 EXP. 12/31/2023
CIVIL / STRUCTURAL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
HEALTHCARE PLANNER
THE INNOVA GROUP
3196 NORTH SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:2 :0
A
M
MECHANICAL SITE PLAN
RAC 58 79JRM
BID DOCUMENTS
REPAIR SPS SEWER AND
UPGRADE EQUIPMENT AREA
08/11/2023
501-21-101
RAYMOND G. MURPHY VAMC
1501 SAN PEDRO DRIVE SE
ALBUQUERQUE, NM 87108
MS100
SPUR #: 1993.10
N
1/4" = 1'-0"
SITE PLAN - MECHANICAL1
KEYNOTES
10 ROUTE CONDENSATE TO NEAREST PLUMBING DRAIN.
12"x12" RA
12"ø SP. EA
14"ø SA-H
16"ø SA-C
12"ø SA-H
12"ø SP. EA
16"ø SA-C
12"x8" RA
9"ø SA-H
12"ø SA-C
12"ø SP. EA
12"x8" RA
11"ø SA-C
"x
8" R
A
8" ø
S A
-C 8" ø S
A -H
7" ø
S A
-C 7" ø S
A -H
6" ø
S A
-C
"x
6" S
A
"x
6" S
A
6" x8
S
A
8" x6
R
A
8" ø
S A
-C 8" ø S
A -H
9" ø
S A
-C 9" ø S
A -H
9" ø
S A
-C
9" ø
S A
-H
"ø
S A
-C
"ø S
A -H
7" ø
S A
-C 7" ø S
A -H
"x
S A
"x
6" S
A
"x
8" S
A
"x 8"
S A
12"x6" SA
12"x8" SA
10"x6" 10"x6" SA
14"x6" SA 14"x6" SA
20"ø SA-C
18"ø SA-H
18"x12" RA 16"x12" RA
14"ø SA-H
16"ø SA-C18"ø SA-C
16"ø SA-H
14"x14" EA
12"ø SP. EA
16"ø SP. EA
14"x11" EA
12"ø SA-H
14"ø SA-C
8"x9" EA
11"ø SA-H
12"ø SA-C 10"ø SA-C
10"ø SA-H
8"x9" EA
8"x4" SA
8"x4" SA
"x
5" S
A
"x
6" S
A
6" x6
E
A
"x
6" R
A12 "x
8" S
A
"x 8"
S A
"x
7" S
A
"x
E A
8" x8
E
A
"x
6" S
A
"x
6" R
A
"x
9" S
A
"x 8"
S A
"x
4" S
A
"x
7" E
A
"x
7" E
A
9" ø
S A
-C 9" ø S
A -H
"x
9" E
A18 "x
S A
"x
7" S
A
"x
7" S
A
"x
S
A
"ø S
A -C
"ø
S A
-H
"x
E
A
"x
S A
"ø
S P
. E A
"x
8" R
A
"x
8" S
A
"ø
S P
. E A
"x
E A
"ø
S P
. E A
"ø
S P
. E A
"x
E A
"x
R A
"ø
S A
-H
"ø
S A
-C
"ø S
A -C
"ø
S A
-H
"x
R A
"x
E A
"ø
S P
. E A
"ø
S P
. E A
"x
E A
"ø
S P
. E A
8" x4
E
A
6" x6
R
A
14"x7" SA 18"x7"
18"x7"14"x7" SA
6"x6" EA
10"x4" SA
6"x6" EA
8"x4" SA
10"x4" SA
8"x4" SA
14"x6" SA
16"ø SP. EA
6"ø SP. EA
12"x6" SA
"x
8" E
A
8" x4
E
A
9" ø
S A
-C 9" ø S
A -H
9"ø SA-C
14"x7" SA
22"x18" EA24"x20" EA
16"ø SP. EA
12"ø SP. EA
14"x14" EA
20"x16" EA
12"ø SP. EA
9"ø SA-H
11"ø SA-C
9"ø SA-H
16"ø SP. EA 13"ø SP. EA 13"ø SP. EA
1 2 3 4 5 6 7
G
H
I
11" Ø SP.
EA DN
RELOCATE SA
DIFFUSER
DEMOLISH
TO ROOM
BOUNDARY
AND CAP
D7
D7
D7
D7 D7
D7
D7 D7
D7
D7D7
D7 D7
D7
D7
D7
D9
M-501
SPS DEPARTMENT
BUILDING 41
BASEMENT LEVEL, QUAD C
N
BUILDING 41 - BASEMENT LEVEL KEY PLAN
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR SBBL COLLABORATIVE JN, INC.
100 N. STONE AVE STE 1102
TUCSON, AZ 85701-1524
(520) 620-0255
NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023
NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024
NM ELEC - EVANS SORDIASHIE #22917 EXP. 12/31/2023
CIVIL / STRUCTURAL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
HEALTHCARE PLANNER
THE INNOVA GROUP
3196 NORTH SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:2 :0
A
M
MECHANICAL DEMOLITION PLAN -
BASEMENT INTERSTITIAL
RAC 59JRM
BID DOCUMENTS
REPAIR SPS SEWER AND
UPGRADE EQUIPMENT AREA
08/11/2023
501-21-101
RAYMOND G. MURPHY VAMC
1501 SAN PEDRO DRIVE SE
ALBUQUERQUE, NM 87108
MD101
SPUR #: 1993.10
N
1/8" = 1'-0"
B41 BASEMENT INTERSTITIAL - HVAC DEMOLITON PLAN1
DEMOLITION KEYNOTES
D7 EXISTING AIR DEVICES IN THIS AREA TO BE REPLACED ALONG WITH CEILING REPLACEMENT. PREPARE DUCTWORK FOR CONNECTION TO NEW AIR
DEVICE. CONTRACTOR TO VERIFY LOCATION.
D9 TEMPORARY FAN SHALL BE INSTALLED ALONG WITH DEMOLITION OF EXISTING EXHAUST TO ENSURE SPACE HAS PROPER VENTILATION.
DN
MECH
BD-141
VESTIBULE
BC-125
STAIR
N0-3 VESTIBULE
BC-113
IRM SIGNAL CLOSET
BC-110D
CLOSET
BC-110C
SOILED RECV &
DECONTAMINATION
BC-110
STOR
BC-127
ELECTRICAL CLOSET
BC-110E
STERILIZATION PREPARATION
BC-111
MECH EQUIP
BC-112
RECEPTION AND PGM ASST
BC-125
OFFICE OF CHIEF BIOMED
BC-125A
EQUIP TEST & STORAGE
BC-115D
WORK AREA & STOR
BC-115C
BIOMED WORK SPACE
BC-125D
OFFICE
BC-115E
BREAKDOWN
BC-115B
HALL
BC-103A
BREAK ROOM
BC-103B
TLT (F)
BC-115G
TLT
BC-104
TLT
BC-105
STOR
BC-118
STAFF WORK AREA
BC-115
RECEPTION
BC-121A
MED SUPPLY TECH
BC-121B
OFFICE
BC-123
HAC
BC-115A
TECHNICAL WORK SPACE
BC-126
PARTS RM
BC-126A
MECH RM
BC-126B
CORRIDOR
CB-17
STOR
BC-119
MECH
BC-115F
LOCKERS
BC-102
MED GAS
BC-121
CORRIDOR
CB-15
CART WASH
BC-114
CORRIDOR
CB-16
SPS CHANGE AREA
BC-103
1 2 3 4 5 6 7
G
H
I
VESTIBULE
BC-100
HAC
BC-110D
HLD DECON
BC-110B
EG-1
HLD ALCOVE
BC-110C
HLD ANTEROOM
BC-110A
2'x2'
ACCESS
PANEL
EG-3
EG-3
EG-4
2'x2' ACCESS
PANEL
3'x3' ACCESS
PANEL
3'x3'
ACCESS
PANEL
3'x3' ACCESS
PANEL
3'x3' ACCESS
PANEL
3'x3' ACCESS
PANEL
3'x3' ACCESS
PANELS
SD-6
SD-6
SD-6 SD-6
SD-6
SD-6
SD-5SD-5
SD-5 SD-5
SD-5 SD-5
SD-4SD-4
SD-4
SD-5
RG-1
RG-1
RG-1
M-501
SPS DEPARTMENT
BUILDING 41
BASEMENT LEVEL, QUAD C
N
BUILDING 41 - BASEMENT LEVEL KEY PLAN
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR SBBL COLLABORATIVE JN, INC.
100 N. STONE AVE STE 1102
TUCSON, AZ 85701-1524
(520) 620-0255
NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023
NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024
NM ELEC - EVANS SORDIASHIE #22917 EXP. 12/31/2023
CIVIL / STRUCTURAL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
HEALTHCARE PLANNER
THE INNOVA GROUP
3196 NORTH SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:2 :0
A
M
MECHANICAL NEW WORK PLAN -
BASEMENT
RAC 60JRM
BID DOCUMENTS
REPAIR SPS SEWER AND
UPGRADE EQUIPMENT AREA
08/11/2023
501-21-101
RAYMOND G. MURPHY VAMC
1501 SAN PEDRO DRIVE SE
ALBUQUERQUE, NM 87108
MH100
SPUR #: 1993.10
N
1/8" = 1'-0"
B41 BASEMENT - HVAC NEW1
KEYNOTES
2 SPECIALTY EXHAUST UP FROM CART WASHER.
3 INSTALL NEW EXHAUST GRILL FOR HAC CLOSET AT THE APPROXIMATE LOCATION SHOWN. CONNECT TO EXISTING GENERAL EXHAUST SYSTEM.
4 INSTALL NEW TRANSFER AIR REGISTERS AND DUCT FOR VESTIBULE AT THE APPROXIMATE LOCATION SHOWN.
8 RELOCATE EXISTING AIR DEVICE AND DUCTWORK AS REQUIRED FOR FLOORPLAN MODIFICATIONS. CONNECT AT APPROXIMATE LOCATION SHOWN.
9 INSTALL NEW AIR DEVICES IN THIS AREA ALONGSIDE CEILING REPLACEMENT. NEW AIR DEVICES SHALL BE THE SAME AS EXISTING TYPES. REBALANCE AS NECESSARY, REFER TO ARCHITECTURAL DRAWINGS FOR SCOPE OF CEILING REPLACEMENT. CONTRACTOR TO VERIFY LOCATION OF EXISTING
EQUIPMENT AND NEW AIR DEVICES.
15 CONTRACTOR TO INSTALL NEW ACCESS PANEL IN THE LOCATION SHOWN. PRIOR TO INSTALLATION, CONFIRM LOCATION OF EXISTING EQUIPMENT TO
ENSURE PROPER CLEARANCE.
1 2 3 4 5 6 7
G
H
I
12x8" TRANSFER
DUCT AND GRILLES
6"x6" EA
EG-1
14"ø SP. EA
EG-3
EG-4
M-501
SPS DEPARTMENT
BUILDING 41
BASEMENT LEVEL, QUAD C
N
BUILDING 41 - BASEMENT LEVEL KEY PLAN
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR SBBL COLLABORATIVE JN, INC.
100 N. STONE AVE STE 1102
TUCSON, AZ 85701-1524
(520) 620-0255
NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023
NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024
NM ELEC - EVANS SORDIASHIE #22917 EXP. 12/31/2023
CIVIL / STRUCTURAL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
HEALTHCARE PLANNER
THE INNOVA GROUP
3196 NORTH SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:2 :1
A
M
MECHANICAL NEW WORK PLAN -
BASEMENT INTERSTITIAL
RAC 61JRM
BID DOCUMENTS
REPAIR SPS SEWER AND
UPGRADE EQUIPMENT AREA
08/11/2023
501-21-101
RAYMOND G. MURPHY VAMC
1501 SAN PEDRO DRIVE SE
ALBUQUERQUE, NM 87108
MH101
SPUR #: 1993.10
N
1/8" = 1'-0"
B41 BASEMENT INTERSTITIAL - HVAC NEW1
KEYNOTES
1 CONNECT NEW EXHAUST FROM CART WASHER TO EXISTING SPECIALTY EXHAUST AT THE APPROXIMATE LOCATION SHOWN.
2 SPECIALTY EXHAUST UP FROM CART WASHER.
3 INSTALL NEW EXHAUST GRILL FOR HAC CLOSET AT THE APPROXIMATE LOCATION SHOWN. CONNECT TO EXISTING GENERAL EXHAUST SYSTEM.
4 INSTALL NEW TRANSFER AIR REGISTERS AND DUCT FOR VESTIBULE AT THE APPROXIMATE LOCATION SHOWN.
7 CAP EXISTING DUCTWORK AT THE APPROXIMATE LOCATION SHOWN. CONTRACTOR TO VERIFY LOCATION OF EXISTING DUCTWORK AND
EQUIPMENT.
I
41-EF15
41-ERC3
"x
E A
24"x20" EA
"x
E A
"ø
S P
. E A
"ø
S P
. E A
"ø
S P
. E A
"x
E A
"x
R A
"ø
S A
-H
"ø
S A
-C
12"x12" RA
12"ø SP. EA
14"ø SA-H
16"ø SA-C
"ø
S P
. E A
"ø
S P
. E A
D3
41-EF13
41-EF16
41-EF12
D5
MECH ROOM
BC-112
D4
I
41-EF15A
"x
E A
"x
E A
"ø
S P
. E A
"ø
S P
. E A
"x
E A
"x
R A
"ø
S A
-H
"ø
S A
-C
"ø
S P
. E A
24"x20" EA
41-EF12
41-EF16 41-EF13
41-ERC3
12"x12" RA
12"ø SP. EA
14"ø SA-H
16"ø SA-C
"ø
S P
. E A
"ø
S P
. E A
D5
24"x20" EA
MECH ROOM
BC-112
EXISTING DDC
PANEL
2 3 4
2" HPC 2" HPS
1 1/2" HPC
1 1/2" HPS
1" HPS
1" HPC
1 1/2" HPC
1 1/2" HPS
EXISTING STEAM PIPE
ROUTED IN TRENCH
BELOWSOILED RECV &
DECONTAMINATION
BC-110
STERILIZATION PREPARATION
BC-111
MECH
BC-115F
STOR
BC-119
CORRIDOR
CB-16
SPS CHANGE AREA
BC-103
1 1/2" HPC
1 1/2" HPS
SPS DEPARTMENT
BUILDING 41
BASEMENT LEVEL, QUAD C
N
BUILDING 41 - BASEMENT LEVEL KEY PLAN
2 3 4
1 1/4" LPS
2" HPC 2" HPS
1 1/2" HPC
1 1/2" HPS
1" HPS
1" HPC
1 1/2" HPC
1 1/2" HPS
EXISTING STEAM PIPE
ROUTED IN TRENCH
BELOW
SOILED RECV &
DECONTAMINATION
BC-110
STERILIZATION PREPARATION
BC-111
MECH
BC-115F
STOR
BC-119
CORRIDOR
CB-16
SPS CHANGE AREA
BC-103
1 1/2" HPC
1 1/2" HPS
D8
1 1/2" HPC
1 1/2" HPS
CART WASH
BC-114
1 1/4" LPS
1 1/2" HPC
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR SBBL COLLABORATIVE JN, INC.
100 N. STONE AVE STE 1102
TUCSON, AZ 85701-1524
(520) 620-0255
NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023
NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024
NM ELEC - EVANS SORDIASHIE #22917 EXP. 12/31/2023
CIVIL / STRUCTURAL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
HEALTHCARE PLANNER
THE INNOVA GROUP
3196 NORTH SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:2 :1
A
M
ENLARGED HVAC PLANS
RAC 62JRM
BID DOCUMENTS
REPAIR SPS SEWER AND
UPGRADE EQUIPMENT AREA
08/11/2023
501-21-101
RAYMOND G. MURPHY VAMC
1501 SAN PEDRO DRIVE SE
ALBUQUERQUE, NM 87108
M-501
SPUR #: 1993.10
N
1/4" = 1'-0"
B41 BASEMENT MECHANICAL ROOM BC-112 - ENLARGED DEMOLITION PLAN1
N
1/4" = 1'-0"
B41 BASEMENT MECHANICAL ROOM BC-112 - ENLARGED HVAC PLAN2
N
1/4" = 1'-0"
B41 BASEMENT - PIPING ENLARGED PLAN4
N
1/4" = 1'-0"
B41 BASEMENT - PIPING ENLARGED DEMO PLAN3
KEYNOTES
5 INSTALL NEW EXHAUST FAN 41-EF15A.
11 EXISTING STEAM AND CONDENSATE PIPE FROM TRENCH BELOW.
12 ROUTE 1-1/2" LOW PRESSURE STEAM AND LOW-PRESSURE CONDENSATE TO CART WASH. CONTRACTOR TO
INSTALL PER MANUFACTURERS DETAILS.
13 CONTRACTOR TO DISCONNECT EXISTING EQUIPMENT TO ALLOW FOR DRAIN LINING. ANY SHUT DOWN NEEDS TO BE COORDINATED WITH THE COR OF THE VA BEFORE DISCONNECTING. ANY EQUIPMENT MOVED FOR DRAIN LINING WILL REQUIRE RECONNECTION ONCE THE LINING PROCESS IS COMPLETE. CONTRACTOR TO VERIFY ALL
PIPING CONNECTIONS ARE GOOD BEFORE START UP.
14 CONNECT NEW CONTROL DEVICES TO THE EXISTING DDC PANEL IN THIS APPROXIMATE LOCATION. CORRIDNATE
EXACT LOCATION WITH VA STAFF.
DEMOLITION KEYNOTES
D3 DEMOLISH EXISTING EXHAUST FAN (41-EF15). EXISTING ENERGY RECOVERY COIL ASSEMBLY IS TO REMAIN.
D4 EXISTING ENERGY RECOVERY ASSEMBLY AND ALL ASSOCIATED CONTROLS ARE TO REMAIN.
D5 EXTING CARTWASH FAN (41-EF13) IS EXISTING TO REMAIN. REBALANCE AIRFLOW TO 1,000 CFM TO MATCH NEW CARTWASH EXHAUST REQUIREMENTS. VERIFY REQUIRED EXHAUST AIRFLOW WITH ACTUAL PURCHASED
CARTWASH.
D8 DEMOLISH EXISTING PIPE FROM OLD CART WASH TO THIS LOCATION.
RETURN / EXHAUST AIR - TYPICAL
RETURN / EXHAUST
AIR MAIN DUCT
RETURN / EXHAUST GRILLE
RA/EA
RIGID DUCT
RIGID DUCT TRANSITION
BEVELED TAKE-OFF WITH
LOCKABLE VOLUME DAMPER
RETURN / EXHAUST AIR - SHALLOW PLENUM SPACE
RETURN / EXHAUST
GRILLE
RA/EA
RECTUAGULAR
RETURN PLENUM
(SAME SIZE AS GRILLE
CONNECTION SIZE)
RIGID DUCT
RETURN / EXHAUST
AIR MAIN DUCT
BEVELED TAKE-OFF
WITH LOCKABLE
VOLUME DAMPER
RECTANGULAR OR ROUND
ELBOW WITHOUT TURNING
VANES. REFER TO PLANS AND
SCHEDULE FOR DUCT SIZES
SUSPEND FROM
STRUCTURE ABOVE
PER SMACNA
GUIDELINES
ROUND FLEXIBLE CONNECTION
RECTANGULAR FLEXIBLE CONNECTION
FLANGED CONNECTION
ON FAN/MOTOR SIDE
WASHER
1-1/2" MIN. TO 3" MAX. INSTALLED.
6" NOMINAL WITH MATERIAL TAUT
FLEXIBLE MATERIAL
AS SPECIFIED
1"x1/8" DRAW
BAND (TYP)
1"x1/8" BAND IRON
BOLTS ON 4" CENTERS
5/16" FLANGE
DUCT
SHEET METAL
SCREWS ON 12"
CENTERS
RIVETS ON 4"
CENTERS
SHEET METAL AS
SPECIFIED FOR
DUCTWORK
1"x1/8" BAND IRON
BOLTS ON 4" CENTERS
1" FLANGE & HEM
ALTERNATE
POSITION OF BOLT
1-1/2" POCKET
SLIP
DUCT
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
1-1/2" MIN. TO 3" MAX. INSTALLED.
6" NOMINAL WITH MATERIAL TAUTFLANGED CONNECTION
ON FAN/MOTOR SIDE
WASHER
FLEXIBLE MATERIAL
AS SPECIFIED
1 1/2"1/2"1/2"
CONICAL TAP WITH
LOCKABLE VOLUME
DAMPER (NOTE 3)
1-1/2" WIDE DUCT
STRAP
SUPPORT FROM
STRUCTURE INSULATED
SHEETMETAL
SUPPLY DUCT
CEILING
NOTES:
1. SEAL CONNECTIONS WITH SEALANT AND TAPE.
2. FLEXIBLE DUCT ALLOWED ONLY IN VERTICAL DROP TO AIR DEVICE. MAXIMUM RUN-OUT LENGTH IS 5'-0".
IF INSTALLED IN AN INTERSTITIAL SPACE, 8'-0" LENGTH ALLOWED.
3. PROVIDE VOLUME DAMPER IN NECK OF DIFFUSER IF INSTALLED IN AN INACCESSIBLE CEILING.
AIR DEVICE MOUNTING
FRAME. COORDINATE
WITH CEILING TYPE
SUPPLY DIFFUSER
(NOTE 3)
1.5 X DUCT DIAMETER
SHEETMETAL ELBOW
W/EXTERIOR INSULATION
PRE-INSULATED
FLEXIBLE DUCT
(NOTE 2)
DUCT COLLAR AT
DIFFUSER NECK.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR SBBL COLLABORATIVE JN, INC.
100 N. STONE AVE STE 1102
TUCSON, AZ 85701-1524
(520) 620-0255
NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023
NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024
NM ELEC - EVANS SORDIASHIE #22917 EXP. 12/31/2023
CIVIL / STRUCTURAL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
HEALTHCARE PLANNER
THE INNOVA GROUP
3196 NORTH SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:2 :1
A
M
MECHANICAL DETAILS & SCHEDULES
RAC 63JRM
BID DOCUMENTS
REPAIR SPS SEWER AND
UPGRADE EQUIPMENT AREA
08/11/2023
501-21-101
RAYMOND G. MURPHY VAMC
1501 SAN PEDRO DRIVE SE
ALBUQUERQUE, NM 87108
M-601
SPUR #: 1993.10
SMACNA HVAC Duct Construction Standards w/ith VA overrides. Refer to Specification section 233100 HVAC Ducts and Casings for gage and joint requirements
DUCT CONSTRUCTION SCHEDULE
DUCTS CONNECTED TO DUCT MATERIAL PRESSURE
CLASS
SEAL
CLASS
LEAKAGE
CLASS (RECT)
LEAKAGE
CLASS (RND)
SUPPLY
FAN COIL UNITS, FURNACES, HEAT PUMPS, AND TERMINAL UNITS GALVANIZED SHEETMETAL 2 A 16 8
OPERATING ROOMS (DOWNSTREAM OF HEPA FILTERS) 304 STAINLESS STEEL 2 A 16 8
CONSTANT VOLUME AIR HANDLING UNITS GALVANIZED SHEETMETAL 2 A 8 4
VARIABLE AIR VOLUME AIR HANDLING UNITS - MED PRESSURE GALVANIZED SHEETMETAL 3 A 8 4
VARIABLE AIR VOLUME AIR HANDLING UNITS - HIGH PRESSURE GALVANIZED SHEETMETAL 4 A 4 2
EQUIPMENT NOT LISTED GALVANIZED SHEETMETAL 2 A 8 4
OUTSIDE AIR
EQUIPMENT NOT LISTED GALVANIZED SHEETMETAL 2 A 16 8
RETURN
FAN COIL UNITS, FURNACES, HEAT PUMPS, AND TERMINAL UNITS GALVANIZED SHEETMETAL 2 A 16 8
CONSTANT VOLUME AIR HANDLING UNITS GALVANIZED SHEETMETAL 2 A 16 8
VARIABLE AIR VOLUME AIR HANDLING UNITS GALVANIZED SHEETMETAL 2 A 8 4
EQUIPMENT NOT LISTED GALVANIZED SHEETMETAL 2 A 16 8
EXHAUST
GENERAL CLEAN EXHAUST (ASHRAE 62.1 CLASS 1 OR 2) GALVANIZED SHEETMETAL 2 A 16 8
AIR HANDLING UNITS GALVANIZED SHEETMETAL 2 A 8 4
KITCHEN HOODS 304 STAINLESS STEEL 2 A 4 2
DISHWASHER OR HIGH HUMIDITY LOCATIONS 304 STAINLESS STEEL 2 A 4 2
FUME HOOD, LABORATORY AND PROCESS AIR (ASHRAE 62.1 CLASS 3 OR 4) 304 STAINLESS STEEL 3 A 4 2
EQUIPMENT NOT LISTED GALVANIZED SHEETMETAL 2 A 16 8
FAN SCHEDULE (EF/RF/SF)
MARK
BASIS OF DESIGN
(MODEL/MANUFACTURER) LOCATION
FAN DATA MOTOR DATA
MOUNTING
CONFIGURATION
(ARR. / DISCH.)
ELECTRICAL
WEIGHT
(LBS) NOTES
MAX
(CFM)
DESIGN
(CFM)
ESP
("WC) HP DRIVE TYPE
FLA
(A) VOLTS/PH
41-EF15A USF-22-A1 / GREENHECK BC-112 MECH ROOM 6,500 4,950 3.5 5 DIRECT ECM DIRECT 4 / CW UB 7.6 460/3 400 ALL LISTED
TEMP UNIT SCHEDULE (TEMP-AH)
MARK BASIS OF DESIGN
COOLING COIL DATA HEATING COIL DATA OUTDOOR FAN DATA INDOOR BLOWER DATA COMPRESSOR DATA PHYSICAL DATA
NOTESTOTAL (BTUH) SENSIBLE (BTUH) CAPACITY (BTUH) HP RPM AMPS FLOW (CFM) HP AMPS V/PH RATED LOAD AMPS DIMENSIONS (") WEIGHT (lb)
TEMP-AH-1 BARD / WH-30HB-C 25,400 22,700 16,426 1/5 1075 1.2 950 1/2 1.1 460/3 3.4 17.125 x 33.3 x 74.563 159 1,2,3
TEMP-AH-2 BARD / WH-30HB-C 25,400 22,700 16,426 1/5 1075 1.2 950 1/2 1.1 460/3 3.4 17.125 x 33.3 x 74.563 159 1,2
1. UNITS TO WORK IN CONJUNCTION WITH ONE ANOTHER.
2. PROVIDE UNIT WITH FACTORY MOUNTED DISCONNECT SWITCH.
3. PROVIDE UNIT WITH ELECTRIC HEATER COIL (5KW /17,000 BTU/H) ACCESSORY
1. PROVIDE INLET AND OUTLET FLANGES, FLEXIBLE CONNECTOR, NEOPRENE VIBRATION ISOLATORS, AND DISCONNECT SWITCH.
2. MECHANICAL CONTRACTOR IS TO COORDINATE THE EQUIPMENT PAD SIZE AND CONSTRUCTION WITH THE GENERAL CONTRACTOR.
3. FAN MUST BE SEISMICALLY CERTIFIED.
4. MECHANICAL AND CONTROLS CONTRACTOR SHALL REVIEW EXISTING CONTROL DEVICES AND INTERLOCKS PRIOR TO DEMOLITION OF EXISTING EXHAUST FAN. PROVIDE AND INSTALL
ALL NEW EQUIPMENT AND CONTROLS DEVICES NECESSARY TO MAINTAIN EXISTING SEQUENCE OF OPERATIONS.
5. PROVIDE BACNET MSTP CONTROLS SYSTEM COMPATIBLE WITH SIEMENS, APOGEE. COORDINATE CONTROLS WITH DIAGRAM ON M-701.
NOT TO SCALE
TYPICAL EXHAUST / RETURN AIR DEVICE DETAIL1NOT TO SCALE
FLEXIBLE EQUIPMENT CONNECTION3 NOT TO SCALE
TYPICAL SUPPLY DIFFUSER DETAIL2
M
CT
M
M
M
M
CHW
HW
DX
M
HW
IFB
ELEC
M
SD
M
SD
AFS
T
H
H
L
H
L
FRZ
T
P
T
H
H
L
H
L
O
H L
ABBREVIATIONS
AI ANALOG INPUT
A
AO ANALOG OUTPUT
AFS AIRFLOW STATION
BI BINARY INPUT
B
BO BINARY OUTPUT
BP BUILDING PRESSURE
AF AFTER FILTER
CC COOLING COIL
C
CHW CHILLED WATER
CP CIRCULATING PUMP
DX DIRECT EXPANSION
D
DP DIFFERENTIAL PRESSURE
EA EXHAUST AIR
E
EF EXHAUST FAN
CT CURRENT TRANSMITTER
FF FINAL FILTER
F
GF GAS FURNACE
G
HC HEATING COIL
H
ER ENERGY RECOVERY
BPC BUILDING PRESSURE CONTROL
HW HOT WATER
HGB HOT GAS BYPASS
IFB INTEGRAL FACE AND BYPASS
I
LAT LEAVING AIR TEMPERATURE
L
LWT LEAVING WATER TEMPERATURE
HGB HOT GAS BYPASS
AFCV AIRFLOW CONTROL VALVE
AHU AIR HANDLING UNIT
EAT ENTERING AIR TEMPERATURE
EWT ENTERING WATER TEMPERATURE
MAT MIXED AIR TEMPERATURE
M
MOA MINIMUM OUTSIDE AIR
ECM ELECTRONICALLY COMMUTATED MOTOR
NG NATURAL GAS
N
DD DIRECT DRIVE
OA OUTSIDE AIR
O
OCC OCCUPANCY
OX OXYGEN
OXS OXYGEN SENSOR
PCC PRECOOLING COIL
P
PHC PREHEAT COIL
PF PREFILTER
BAC BUILDING AUTOMATION CONTROL
RA RETURN AIR
R
R/E RETURN/EXHAUST
R/R RETURN/RELIEF
SA SUPPLY AIR
S
SF SUPPLY FAN
SD SMOKE DAMPER
RF RETURN FAN
FSD FIRE SMOKE DAMPER
TCP TEMPERATURE CONTROL PANEL
T
TA TRANSFER AIR
TMV THERMOSTATIC MIXING VALVE
TCV TEMPERATURE CONTROL VALVE
UV ULTRAVIOLET
U
VFD VARIABLE FREQUENCY DRIVE
V
SYMBOLS
EQUIPMENT
CHILLED WATER COIL
DIRECT EXPANSION COIL
HOT WATER COIL
HOT WATER INTEGRAL FACE AND
BYPASS COIL
ELECTRIC HEATING COIL
GAS FURNACE
HUMIDIFIER DISPERSION GRID
MODULATING OPPOSED BLADE
DAMPER
MODULATING PARALLEL BLADE
DAMPER
SMOKE DAMPER
BACKDRAFT DAMPER
VAV ATU MODULATING DAMPER
2-POSITION OPPOSED BLADE
DAMPER
2-POSITION PARALLEL BLADE
DAMPER
FILTER
BLOWER FAN
PLENUM FAN
PUMP
CURRENT TRANSMITTER
2-WAY MODULATING
CONTROL VALVE
THERMOSTATIC MIXING VALVE
3-WAY MODULATING
CONTROL VALVE
SENSORS & DEVICES
DUCTWORK
PIPING
ZONE
NEGATIVE SPACE DIFFERENTIAL
PRESSURE SENSOR
POSITIVE SPACE DIFFERENTIAL
PRESSURE SENSOR
ZONE OCCUPANCY SENSOR
ZONE HUMIDITY SENSOR
ZONE TEMPERATURE SENSOR
AQUASTAT
FLOW METER
PRESSURE SENSOR
TEMPERATURE SENSOR
SUPPLY AIR DUCT STATIC PRESSURE
SENSOR
RETURN/EXHAUST AIR DUCT STATIC
PRESSURE SENSOR
DIFFERENTIAL PRESSURE SENSOR
DAMPER POSITION INDICATOR
HUMIDITY SENSOR
FREEZESTAT
TEMPERATURE SENSOR
SMOKE DETECTOR
AIRFLOW STATION
VOC VOLATILE ORGANIC COMPOUND
AIRFLOW SENSOR
RHC REHEAT COIL
XX XXXX
POINT TYPE
POINT NAME
AV ANALOG VIRTUAL
BV BINARY VIRTUAL
MECHANICAL CONTROLS LEGEND
SEQUENCE OF OPERATIONS
EXHAUST FAN (41-EF15A)
GENERAL DESCRIPTION
The exhaust fan provides general exhaust ventilation to the conditioned space(s) as shown on the drawings.
OPERATING MODES
OCCUPIED MODE
The exhaust fan shall be in occupied mode per the project design conditions schedule shown on sheet M-701.
UNOCCUPIED MODE
The exhaust fan shall be in unoccupied mode for all periods not included in the occupied hours of operation.
SAFETIES, OVERRIDES, AND INTERLOCKS
LOW EXHAUST AIR STATIC PRESSURE
The unit shall be disabled via hard wired interlock at the fan start circuit upon activation of the EA duct static pressure controller.
COMPONENT CONTROL LOOPS
EXHAUST FAN CONTROL – DUCT STATIC PRESSURE
• When the HOA switch is in hand position, the variable speed exhaust fan shall operate at a speed set manually by the operator at the user interface of the drive.
• When the HOA switch is in off position, the fan shall be off.
• When the HOA switch is in auto position, the variable speed supply fan shall operate subject to the unit enable signal, and unit operating modes.
OCCUPIED MODE:
• The exhaust fan shall be enabled after the EA damper has proven operable.
• The controller shall measure the EA static pressure and modulate the exhaust fan VFD to maintain the EA static pressure setpoint. The minimum fan speed shall be determined during test and balancing.
UNOCCUPIED MODE:
The exhaust fan shall be off.
MOTORIZED DAMPER
OCCUPIED MODE:
The motorized damper shall be open. The motorized damper shall open 30 sec (adj.)
prior to activation of the exhaust fan.
UNOCCUPIED MODE:
The motorized damper shall be closed. The motorized damper shall close 30 sec (adj.) after the fan is OFF.
H
LEA OUT
M
CT
ECM
N.C.
M
AO
BI
BI
BO EF START/STOP
BI
BOEA DAMPER
EA DAMPER STATUS
EF SPEED
EF STATUS
EF FAULT
BIEA LOW STATIC SHUTDOWN BIEA STATIC PRESSURE REPLACE EXISTING
WITH NEW BACNET
MSTP DEVICE
HL
EA IN
NOTE:
DAMPER(S) , ACTUATOR(S), AND STATIC PRESSURE DEVICES ARE EXISTING. PROVIDE NEW ELECTRONIC ACTUATOR(S) AND CONTROL DEVICES NECESSARY TO INTEGRATE NEW FAN AND CONTROLS INTO THE EXISTING ECC TERMINAL.
ASSOCIATED ENERGY RECOVERY RUN-AROUND LOOP IS EXISTING TO REMAIN.
B-ASC
EXISTING ENGINEERING
CONTROL CENTER
EXISTING
NETWORK
B-ASC
B-ASC
B-AAC
BACNET
BUILDING
CONTROLLER
(B-BC)
EXISTING ETHERNET
COMMUNICATION
NOTES:
1. REUSE EXISTING COMMUNICATION NETWORK.
2. INSTALL NEW CONTROLLERS (B-AAC, B-ASC) AS REQUIRED.
MSTP COMMUNICATION
(TYPICAL)
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR SBBL COLLABORATIVE JN, INC.
100 N. STONE AVE STE 1102
TUCSON, AZ 85701-1524
(520) 620-0255
NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023
NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024
NM ELEC - EVANS SORDIASHIE #22917 EXP. 12/31/2023
CIVIL / STRUCTURAL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
2519 MADISON AVE
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
HEALTHCARE PLANNER
THE INNOVA GROUP
3196 NORTH SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:2 :1
A
M
MECHANICAL CONTROLS
RAC 64JRM
BID DOCUMENTS
REPAIR SPS SEWER AND
UPGRADE EQUIPMENT AREA
08/11/2023
501-21-101
RAYMOND G. MURPHY VAMC
1501 SAN PEDRO DRIVE SE
ALBUQUERQUE, NM 87108
M-701
SPUR #: 1993.10
4. DIVISION 23 CONTRACTOR TO PROVIDE ROOM AIR BALANCE WHERE POSSIBLE. AIR BALANCE SHALL BE NEUTRAL FOR NON-CRITICAL SPACES NOT SHOWN IN SCHEDULE.
3. ZONE LEVEL SET POINT CONDITIONS SHALL RESET TO UNOCCUPIED UNTIL PATIENT ROOM SETPOINTS ARE SATISFIED.
2. ZONE LEVEL SET POINT CONDITIONS SHALL BE AS SCHEDULED UNLESS OTHERWISE SCHEDULED OR NOTED FOR ROOM SPECIFIC SPACE CONDITIONS.
1. ZONE LEVEL OCCUPANCY HOUR SCHEDULE SHALL BE PER BUILDING OPERATING HOURS UNLESS OTHERWISE SCHEDULED.
NOTES:
SUNDAY 7:30 a.m. - 6:00 p.m.
SATURDAY 7:30 a.m. - 6:00 p.m.
MONDAY - FRIDAY 7:30 a.m. - 6:00 p.m.
BUILDING OPERATING HOURS (VERIFY WITH STATION)
MIN. AMBIENT DB TEMP (50…