AMENDMENT 0004 - ATTACHMENT C - ASBESTOS SURVEY REPORT.pdf

PDF 22 MB Posted

Attached to
Project# 501-21-101: Repair Sterile Processing Service (SPS) & Upgrade Equipment Area
Solicitation number
36C26224B0007
Issued by

About this file

This amendment provides an asbestos survey report related to federal contract opportunity number 36C26224B0007. The opportunity is for Project #501-21-101 to replace and repair Sterile Processing Service equipment items and upgrade flooring, walls and ceiling tile materials at an 11,000 square foot Sterile Processing Service space. The scope includes procuring and setting up two temporary Steris sterilizer trailers or equal along with supporting piping systems for utilities, waste, ventilation and fire protection, and an emergency generator. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22 is the contracting agency. The procurement is for pre-solicitation of offers to provide repair and upgrade services at a Veterans Affairs medical facility.

View the file

Other files

File Type Posted
C01 Award Notice of 36C26224C0167.pdf PDF
S06 36C26224B0007 0006.pdf PDF
S06 ATTACHMENT 4 - REVISED WAGE DETERMINATION NM20240044 01-06-2024.pdf PDF
S06 36C26224B0007 0005.pdf PDF
AMENDMENT 0004 - ATTACHMENT A - GEOTECHNICAL REPORT.pdf PDF
AMENDMENT 0004 - ATTACHMENT B - SECTION 26 12 19.pdf PDF
AMENDMENT 0004 - ATTACHMENT 4 - REVISED WAGE DETERMINATION NM20240001.pdf PDF
S06 36C26224B0007 0004.pdf PDF
S06 36C26224B0007 0003.pdf PDF
S06 36C26224B0007 0002 01-30-2024.pdf PDF
S06 36C26224B0007 0001 01162024.pdf PDF
ATTACHMENT 4 - WAGE DETERMINATION NM20230044 06-09-2023.pdf PDF
ATTACHMENT 1D - Drawings-Architectural.pdf PDF
ATTACHMENT 1H - Drawings-Electrical.pdf PDF
ATTACHMENT 1A - Drawings-General.pdf PDF
ATTACHMENT 1E - Drawings-Fire Protection.pdf PDF
ATTACHMENT 1F - Drawings-Plumbing.pdf PDF
ATTACHMENT 1C- Drawings-Structural.pdf PDF
ATTACHMENT 1B - Drawings-Civil.pdf PDF
ATTACHMENT 2 - 501-21-101 Bid Spec Complete-Updated.pdf PDF
ATTACHMENT 1G - Drawings-Mechanical.pdf PDF
ATTACHMENT 3 - RFI FORM 501-21-101.docx DOCX document
ATTACHMENT 1I - Drawings-Telecommunications.pdf PDF
S02 36C26224B0007.docx DOCX document
S02. 36C26224B0007 Pre-Solicitation Notice.docx DOCX document
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MECX, Inc.

8864 Interchange Drive Houston, Texas 77054 www.mecx.net

ASBESTOS SURVEY REPORT

Raymond G. Murphy VA Health Care System (NMVAHCS) 1501 San Pedro SE.

Albuquerque, New Mexico 87108

Covering Buildings:

10, 10A, 41, 42, 43, 43A, 45, 46, 49, 49A, 50, 51, 52, 53, 54, 55, 56, 64, 66, 67, 67A, 94, T3, T15C, T15D, T51, T60, T71, T72, T73, and T74

MECX Project Number: 1244.019C.00

Prepared for:

New Mexico Veterans Affairs Health Care System

Albuquerque, New Mexico Order No. VA258‐Q‐0471

Prepared by:

Matthew Haak

TDSHS MAC # 0218

November 11, 2015

NEW MEXICO VETERANS AFFAIRS HEALTH CARE SYSTEM

NOVEMBER 11, 2015

ii

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM Report Final.docx

TABLE OF CONTENTS

Section Page

1.0 INTRODUCTION

2.0 SCOPE OF WORK

2.1 METHODOLOGY

2.2 SURVEY DESCRIPTION

3.0 FINDINGS PER BUILDING

3.1 BUILDING 41

3.1.1 Building 41 ‐ Suspect Asbestos‐Containing Materials

3.1.2 Building 41 ‐ Samples Reported as Asbestos‐Containing

3.1.2.1 Building 41 ‐ Asbestos‐Containing Materials Inventory Summary

3.1.2.1.1 Quad A Mechanical Rooms

3.1.2.1.2 Quad B Mechanical Rooms

3.1.2.1.3 Quad C Mechanical Rooms

3.1.2.1.4 Quad D Mechanical Rooms

3.1.2.1.5 Quad D Mechanical Rooms ............. Error! Bookmark not defined.

3.1.2.1.6 Building 41 Interstitial Spaces

3.1.3 Inspection Notes:

3.1.4 Conclusions

3.2 BUILDING 10

3.2.1 Building 10 ‐ Suspect Asbestos‐Containing Materials

3.2.2 Building 10 ‐ Samples Reported as Asbestos‐Containing

3.2.3 Building 10 ‐ Asbestos‐Containing Materials Inventory Summary

3.2.4 Inspection Notes:

3.2.5 Conclusions

3.3 BUILDING 10A

3.3.1 Building 42 ‐ Suspect Asbestos‐Containing Materials

3.4 BUILDING 42

3.4.1 Building 42 ‐ Suspect Asbestos‐Containing Materials

3.4.2 Building 42 ‐ Samples Reported as Asbestos‐Containing

3.4.3 Building 42 ‐ Asbestos‐Containing Materials Inventory Summary

3.4.4 Conclusions

3.5 BUILDING 43

iii

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM Report

3.5.1 Building 43 ‐ Suspect Asbestos‐Containing Materials

3.5.2 Building 43 ‐ Samples Reported as Asbestos‐Containing

3.5.3 Building 43 ‐ Asbestos‐Containing Materials Inventory Summary

3.5.4 Conclusions

3.6 BUILDING 43A

3.6.1 Building 43A ‐ Suspect Asbestos‐Containing Materials

3.6.2 Building 43 ‐ Samples Reported as Asbestos‐Containing

3.6.3 Building 43A ‐ Asbestos‐Containing Materials Inventory Summary

3.7 BUILDING 45

3.7.1 Building 45 ‐ Suspect Asbestos‐Containing Materials

3.7.2 Building 45 ‐ Samples Reported as Asbestos‐Containing

3.7.3 Building 45 ‐ Asbestos‐Containing Materials Inventory Summary

3.8 BUILDING 46

3.8.1 Building 46 ‐ Suspect Asbestos‐Containing Materials

3.8.2 Building 46 ‐ Samples Reported as Asbestos‐Containing

3.8.3 Building 46 ‐ Asbestos‐Containing Materials Inventory Summary

3.8.2 Conclusions

3.9 BUILDING 49 & 49A

3.9.1 Building 49 & 49A ‐ Suspect Asbestos‐Containing Materials

3.9.2 Building 49 & 49A ‐ Samples Reported as Asbestos‐Containing

3.8.3 Building 49 & 49A ‐ Asbestos‐Containing Materials Inventory Summary

3.10 BUILDING 50

3.10.1 Building 50 ‐ Suspect Asbestos‐Containing Materials

3.10.2 Building 50 ‐ Samples Reported as Asbestos‐Containing

3.10.3 Building 50 ‐ Asbestos‐Containing Materials Inventory Summary

3.11 BUILDING 51

3.11.1 Building 51 ‐ Suspect Asbestos‐Containing Materials

3.12 BUILDING 52

3.12.1 Building 52 ‐ Suspect Asbestos‐Containing Materials

3.12.2 Building 52 ‐ Samples Reported as Asbestos‐Containing

3.12.3 Building 52 ‐ Asbestos‐Containing Materials Inventory Summary

3.13 BUILDING 53

3.13.1 Building 53 ‐ Suspect Asbestos‐Containing Materials

3.13.2 Building 53 ‐ Samples Reported as Asbestos‐Containing

3.13.3 Building 53 ‐ Asbestos‐Containing Materials Inventory Summary

3.14 BUILDING 54

3.14.1 Building 54 ‐ Suspect Asbestos‐Containing Materials

3.14.2 Building 54 ‐ Samples Reported as Asbestos‐Containing

3.14.3 Building 54 ‐ Asbestos‐Containing Materials Inventory Summary iv

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM Report

3.15 BUILDING 55

3.15.1 Building 55 ‐ Suspect Asbestos‐Containing Materials

3.15.2 Building 55 ‐ Samples Reported as Asbestos‐Containing

3.15.3 Building 55 ‐ Asbestos‐Containing Materials Inventory Summary

3.16 BUILDING 56

3.16.1 Building 56 ‐ Suspect Asbestos‐Containing Materials

3.16.2 Building 56 ‐ Samples Reported as Asbestos‐Containing

3.16.3 Building 56 ‐ Asbestos‐Containing Materials Inventory Summary

3.17 BUILDING 66

3.17.1 Building 66 ‐ Suspect Asbestos‐Containing Materials

3.17.2 Building 66 ‐ Samples Reported as Asbestos‐Containing

3.17.3 Building 66 ‐ Asbestos‐Containing Materials Inventory Summary

3.18 BUILDING 67

3.18.1 Building 67 ‐ Suspect Asbestos‐Containing Materials

3.18.2 Building 67 ‐ Samples Reported as Asbestos‐Containing

3.18.3 Building 67 ‐ Asbestos‐Containing Materials Inventory Summary

3.19 BUILDING 67A

3.19.1 Building 67A ‐ Suspect Asbestos‐Containing Materials

3.19.2 Building 67A ‐ Samples Reported as Asbestos‐Containing

3.19.3 Building 67A ‐ Asbestos‐Containing Materials Inventory Summary

3.20 BUILDING 94

3.20.1 Building 94 ‐ Suspect Asbestos‐Containing Materials

3.21 BUILDING T74

3.21.1 Building T74 ‐ Suspect Asbestos‐Containing Materials

3.21.2 Building T74 ‐ Samples Reported as Asbestos‐Containing

3.21.3 Building T74 ‐ Asbestos‐Containing Materials Inventory Summary

3.22 BUILDING T15C

3.22.1 Building T15C ‐ Suspect Asbestos‐Containing Materials

3.22.2 Building T15C ‐ Samples Reported as Asbestos‐Containing

3.22.3 Building T15C ‐ Asbestos‐Containing Materials Inventory Summary

3.22.3 Conclusions

3.23 BUILDING T15D

3.23.1 Building T15D ‐ Suspect Asbestos‐Containing Materials

3.23.2 Building T15D ‐ Samples Reported as Asbestos‐Containing

3.23.3 Building T15D ‐ Asbestos‐Containing Materials Inventory Summary

3.24 BUILDING T60

3.24.1 Building T60 ‐ Suspect Asbestos‐Containing Materials

3.24.2 Building T60 ‐ Samples Reported as Asbestos‐Containing

3.24.3 Building T60 ‐ Asbestos‐Containing Materials Inventory Summary v

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM Report

3.25 BUILDING T72

3.25.1 Building T72 ‐ Suspect Asbestos‐Containing Materials

3.25.2 Building T72 ‐ Samples Reported as Asbestos‐Containing

3.25.3 Building T72 ‐ Asbestos‐Containing Materials Inventory Summary

3.26 BUILDING T3

3.26.1 Building T3 ‐ Suspect Asbestos‐Containing Materials

3.27 BUILDING T51

3.27.1 Building T51 ‐ Suspect Asbestos‐Containing Materials

3.28 BUILDING T71

3.28.1 Building T71 ‐ Suspect Asbestos‐Containing Materials

3.29 BUILDING T73

3.29.1 Building T73 ‐ Suspect Asbestos‐Containing Materials

4.0 CONCLUSIONS AND RECOMMENDATIONS

5.0 LIMITATIONS

6.0 ASBESTOS SURVEY SAMPLING STRATEGY

NOVEMBER 11, 2015

vi

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM Report Final.docx

APPENDICES

A – Asbestos Summary Table B – Laboratory Results C – MECX’s Project Team Certifications D – Photo Log E – Figures ACRONYMS

Asbestos‐ Containing Building Materials (ACBM), 4 regulated asbestos‐containing material (RACM), 4 asbestos‐containing materials (ACMs), 1 EPA Asbestos Model Accreditation Plan (MAP), 1 Loflin Environmental Services, Inc. (Loflin), 4 National Emissions Standards for Hazardous Air Pollutants (NESHAP), 1 National Institute of Standards and Technology (NIST), 4 National Voluntary Laboratory Accreditation Program (NVLAP), 4 New Mexico Air Quality Bureau (AQB), 1 New Mexico Occupational Health and Safety Bureau (OHSB), 1 Occupational Safety and Health Administration (OSHA), 1 polarized light microscopy (PLM), 4 Texas Department of State Health Services (TDSHS), 1 Asbestos Hazard Emergency Response Act (AHERA), 1

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM Report Final.docx

1.0 INTRODUCTION

This report provides the results of a survey for asbestos‐containing materials (ACMs) completed for thirty‐ one (31) buildings within the Raymond G. Murphy New Mexico Veterans Affairs Health Care System (NMVAHCS) located at 1501 San Pedro SE in Albuquerque, New Mexico (Site).

MECX conducted the survey in order to meet requirements that are compliant with the EPA Asbestos Hazard Emergency Response Act (AHERA) regulations (40 CFR 763), National Emissions Standards for Hazardous Air Pollutants (NESHAP) regulations (40 CFR 61, Subpart M), the Occupational Safety and Health Administration (OSHA) Asbestos Standards (29 CFR 1910.1001 and 29 CFR 1926.1101) and the local New Mexico Environment Department Air Quality Bureau (AQB) and the New Mexico Occupational Health and Safety Bureau (OHSB) rules, regulations and guidelines for renovation/demolition

MECX’s representatives Mr. Matthew Haak (TDSHS License 10‐5791) and Mr. James Murray (TDSHS License 10‐5776), are Texas Department of State Health Services (TDSHS) licensed Asbestos Consultants.

TDSHS licensing and training meet the EPA Asbestos Model Accreditation Plan (MAP) requirements. Training for asbestos professionals is required under the EPA Asbestos MAP which EPA issued under the Asbestos Hazard Emergency Response Act of 1986 (AHERA). The MAP requires the use of trained and accredited asbestos professionals when conducting asbestos inspections or designing or conducting response actions at schools and public and commercial buildings. It provides guidance to states on the minimum training requirements for accrediting asbestos professionals. State training programs must be at least as stringent as the MAP. The MAP established five required training disciplines:

Worker

Contractor/supervisor

Inspector

Management planner, and

Project designer

As licensed Asbestos Consultants, MECX’s representatives are accredited to perform the functions of all five disciplines.

MECX completed the survey between the dates of August 16 – 20 and October 5 ‐ 7, 2015.

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

The following buildings as specified by representatives of the NMVAHCS were included in this survey:

Building No.

Building Use Year Built

Number of

Floors

Approximate

Square Feet

10 Research‐ Administration 2014 3 10,000

10A Electric Room 2014 1 336

41 Clinical‐Administrative‐ Hospital‐

Interstitial

1986 13 577,353

42 Electrical Vault and Emergency

Generator Room

1986 1 2,884

43 Energy Plant 2006 3 14,280

43A Energy Plant Pump House 2012 1 486

45 Spinal Cord Injury 1991 1 53,721

46 Warehouse 1986 1 21,688

49 MRI 1990 2 7,500

49A MRI 1993 2 2,218

50 GU Clinic 1992 1 3,290

51 Warehouse 1982 1 1,200

52 Mental Health Administration 2012 1 7,343

53 Behavioral Health Care 2013 2 17,607

54 Hospital ‐ Patient Overnight Housing 2010 1 3,626

55 Hospital – Patient Overnight Housing 2008 1 3,496

56 Projects and Contracts Office 2008 1 8,848

64 Well House 1996 1 576

66 Research‐ Administration 2011 1 4,620

67 Research‐ Administration 2011 1 4,180

67A Research‐Electrical 2012 1 400

94 Pump House 2013 1 190

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

Building No.

Building Use Year Built

Number of

Floors

Approximate

Square Feet

T3 Warehouse 1984 1 5000

T15C Employee Fitness‐Police 1980 1 2320

T73 Linen Storage Warehouse 2011 1 1,650

T74 Research Storage Warehouse 2011 1 1,500

None of the roofs were accessed or inspected during this survey as directed by NMVAHCS personnel at the time of the inspection. Therefore none of the roofing materials were sampled. In addition to the roofing materials there may be suspect materials located on the roof such as but not limited to HVAC duct seam, patching & penetration tar and thermal system insulation (TSI) on pipes. All suspect materials located on the roofs must be assumed to be asbestos containing until such time they have been tested and shown otherwise.

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

2.0 SCOPE OF WORK

The objective of this survey, as defined by the client, was to collect representative samples of suspect friable and non‐friable asbestos‐containing materials (ACMs) located in the interior building spaces and exterior suspect Asbestos‐ Containing Building Materials (ACBM), excluding Roofs and Roofing Material. In addition to collection ACM samples, the assessment of the condition of the suspect materials and quantified materials containing asbestos was to be noted. The assessment, sampling and subsequent analysis was conducted in order to identify ACMs within the NMVAHCS facility.

In addition to the collection and analysis of bulk samples, MECX will review, update, and incorporate new findings into the existing NMVAHCS Asbestos Management and Operations Plan.

2.1 METHODOLOGY

The survey consisted of inspections of reasonably accessible building components to identify suspect ACM.

MECX’s representatives, TDSHS licensed Asbestos Inspector/Consultant, collected samples of suspect ACM in accordance with the EPA Model Accreditation Plan specified in the AHERA.

The collected samples were placed in polyethylene bags, given unique sample numbers, and transported for analysis (following chain‐of‐custody protocol) to Loflin Environmental Services, Inc. (Loflin), in Houston, Texas, which is a TDSHS licensed asbestos laboratory. Loflin is a participating member in the National Institute of Standards and Technology (NIST) administered by the National Voluntary Laboratory Accreditation Program (NVLAP). Bulk samples submitted for testing were analyzed for asbestos content by polarized light microscopy (PLM).

The laboratory analyzed the bulk samples using PLM, according to protocol of the U.S. Environmental Protection Agency (USEPA) Analytical Method EPA/600/R‐93/116. The USEPA defines an ACM as any material that contains greater than one (1) percent asbestos by PLM analysis (NESHAP 40 CFR Part 61, Subpart M). When the bulk samples contained more than one layer, the laboratory analyzed all layers of the sample.

Suspect samples containing less than or equal to one percent asbestos are not to be considered ACM by regulatory definition. If lab analysis found that any of the material samples were asbestos‐containing, then the material has to potential to be considered a regulated asbestos‐containing material (RACM), according the EPA’s NESHAP regulation for renovations and demolitions (reference 40 CFR Part 61).

Suspect ACMs were classified as either friable or non‐friable during the inspection. ACMs also were classified as either friable or non‐friable.

Friable ACMs are those that contain more than one percent asbestos and, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure. All friable ACMs are considered RACM and, therefore, subject to EPA regulations.

Non‐friable ACMs cannot be crushed with hand pressure. All non‐friable ACMs are categorized as either Category I or Category II materials.

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM o Category I ‐ non‐friable asbestos‐containing packings, gaskets, resilient floor covering, and asphalt roofing products.

o Category II ‐ non‐friable ACMs, excluding Category I non‐friable ACMs.

2.2 SURVEY DESCRIPTION

MECX collected approximately 710 representative bulk samples of all accessible interior suspect asbestos‐ containing materials. Suspect ACMs may exist in inaccessible or hidden areas of the structure that were not observed or inspected during this investigation. This inspection was conducted as a comprehensive survey but due to the inaccessibility of some areas hidden materials may exist that would only be accessible through destructive measures.

A limited survey was conducted on the buildings exteriors. None of the roofs were accessed or inspected during this survey as directed by NMVAHCS personnel at the time of the inspection. Therefore, none of the roofing materials were sampled. In addition to the roofing materials there may be suspect materials located on the roof such as but not limited to HVAC duct seam, patching & penetration tar and TSI on pipes. All suspect materials located on the roofs must be assumed to be asbestos containing until such time they have been tested and shown otherwise.

The quantification of the asbestos‐containing materials is an estimate made at the time of sampling. The quantities are estimates only and should be verified by all parties, including any contractors bidding the removal to determine exact square footage’s and the accessibility of the specific materials.

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

3.0 FINDINGS PER BUILDING

3.1 BUILDING 41

Building 41 ‐ Suspect Asbestos‐Containing Materials

The following table lists the homogeneous areas (HA) of suspect asbestos‐containing materials identified and sampled within Building 41.

HA Materials

1. 2'x2' White Recessed Grid, No Cuts

2. Gray Duct Sealant/Mastic On Metal Ducts

3. 12"x12" Pink & Blue Floor Tile & Yellow Mastic

4. Sheet Vinyl Flooring, New, Blue, Tan & Faux Wood

5. 12"x12" Multi‐Colored Floor Tile, Mottled With Yellow Mastic

6. 12"x12" Sand White Floor Tile & Yellow Mastic

7. White Joint Compound 8. 12"x12" Floor Tile, Black Smudges & Yellow Mastic

9. Gray Pebbly

10. Heating Water Insulation Sealant/Mastic

11. Faux Wood Sheet Vinyl, Narrow Strips

12. Tan Mottled Sheet Vinyl

13. 12"x12" Olive Floor Tile & Yellow Mastic

14. 2'X4' White Ceiling Tile, Small Cuts & Dots, New

15. 12"x12" Taupe Floor Tile & Yellow Mastic

16. Yellow Carpet Mastic 17. 2'X4' White Ceiling Tile, Cuts & Dots, Old

18. White Duct Insulation Sealant/Mastic On Air Handler Unit

19. 12"x12" Gray Mottled Floor Tile & Yellow Mastic (Replacement Tile For FT1)

20. Steam Sealant/Mastic 21. Tan Exterior Stucco & Plaster

22. Chilled Water Supply Insulation Sealant/Mastic

23. Red Fire Stop 24. 2'x4' Smooth Ceiling Tile

25. Hot Water Return Insulation Sealant/Mastic

26. Gray Fire Stop Plaster 27. 12"x12" Cranberry Mottled Floor Tile & Yellow Mastic

28. 12"x12" Taupe Floor Tile, Heavy Mottled & Yellow Mastic

29. Chilled Water Return Insulation Sealant/Mastic

30. 12"x12" Peach Floor Tile & Yellow Mastic

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

31. 12"x12" Beige Floor Tile With Mottling & Yellow Mastic

32. Hot Water Supply Insulation Sealant/Mastic

33. Stair Tread Black Mastic

34. Tan Sheet Vinyl 35. Red Metal Duct Sealant/Mastic On Metal Duct Seams

36. 2'x2' White Ceiling Tile Dots

37. Spray Applied Fire Proofing 38. Faux Wood Sheet Vinyl, Wider Strips

39. 12"x12" White Floor Tile With Gray Spots

40. Troweled Applied Fire Proofing

41. 12"x12" Green Floor Tile & Yellow Mastic

42. 2'x4' Ceiling Tile Squiggle Cuts

43. Domestic Water Insulation Sealant/Mastic At Hangar At Wall

44. Metal Duct Seam Sealant/Mastic

45. 4" Yellow Cove Base Mastic

46. Roof Drain Insulation Sealant/Mastic

47. Sewer Drain Insulation Sealant/Mastic

48. Domestic Hot Water Pipe Insulation Sealant/Mastic

49. Gray Sheet Vinyl Textured 50. 2’x2’ Recessed Grid 51. AHU Insulation Sealant/Mastic

52. Chilled Water Supply Insulation Sealant/Mastic

53. White Hot Water Supply Insulation Sealant/Mastic

54. White Duct Insulation Sealant/Mastic

Building 41 ‐ Samples Reported as Asbestos‐Containing

Sample No. Material Description Sample Location Friability Condition % Asbestos

B41‐CHWS‐01 Chilled Water Supply Insulation

Sealant/Mastic

Building 41, 6th Floor Mechanical Room

Non‐Friable Damaged 3‐5% Chrysotile

B41‐CHWS‐02 Chilled Water Supply Insulation

Sealant/Mastic

Building 41, 4th Floor Mechanical Room

Non‐Friable Damaged 3‐5% Chrysotile

B41‐CHWS‐03 Chilled Water Supply Insulation

Sealant/Mastic

Building 41, Basement Mechanical Room

Non‐Friable Damaged 3‐5% Chrysotile

B41‐CHWR‐01 Chilled Water Return Insulation

Sealant/Mastic

Building 41, 6th Floor Mechanical Room

Non‐Friable Damaged 3‐5% Chrysotile

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

Sample No. Material Description Sample Location Friability Condition % Asbestos

B41‐CHWR‐02 Chilled Water Return Insulation

Sealant/Mastic

Building 41, 4th Floor Mechanical Room

Non‐Friable Damaged 3‐5% Chrysotile

B41‐CHWR‐03 Chilled Water Return Insulation

Sealant/Mastic

Building 41, Basement Mechanical Room

Non‐Friable Damaged 3‐5% Chrysotile

B41‐CHWX‐01 Chilled Water Insulation

Sealant/Mastic

Building 41, Floor 5 Non‐Friable No Damage

3‐5% Chrysotile

B41‐CHWX‐02 Chilled Water Insulation

Sealant/Mastic

Building 41, Floor 5 Non‐Friable No Damage

3‐5% Chrysotile

B41‐CHWX‐03 Chilled Water Insulation

Sealant/Mastic

Building 41, Floor 5 Non‐Friable No Damage

3‐5% Chrysotile

B41‐HWS‐01

Hot Water Supply

Insulation Sealant/Mastic

Building 41, 6th Floor Mechanical Room

Non‐Friable Damaged 3‐5%

Chrysotile

B41‐HWS‐03

Hot Water Supply

Insulation Sealant/Mastic

Building 41, Basement Mechanical Room

Non‐Friable Damaged 3‐5%

Chrysotile

B41‐HWR‐03

Hot Water Return

Insulation Sealant/Mastic

Building 41, Basement Mechanical Room City

Water Non‐Friable Damaged

3‐5% Chrysotile

B41‐HWR‐04A

Hot Water Return

Insulation Sealant/Mastic

Building 41, Floor 3 Mechanical Room 3A‐

Non‐Friable

No Damage

3‐5% Chrysotile

B41‐HWX‐01

Heating Water Insulation

Sealant/Mastic Building 41, Floor 5 Non‐Friable

No Damage

3‐5% Chrysotile

B41‐HWX‐02

Heating Water Insulation

Sealant/Mastic Building 41, Floor 5 Non‐Friable

No Damage

3‐5% Chrysotile

B41‐HWX‐03

Heating Water Insulation

Sealant/Mastic Building 41, Floor 5 Non‐Friable

No Damage

3‐5%

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

B41‐DWS‐02

Domestic Water Insulation

Sealant/Mastic At Hangar At Wall

Building 41, Basement Mechanical Room

Non‐Friable Damaged 3‐5%

Chrysotile

B41‐RFS‐03

Sewer Drain Insulation

Sealant/Mastic

Building 41, Floor 5 Interstitial

Non‐Friable No

Damage 3‐5%

Chrysotile

B41‐RFS‐04

Sewer Drain Insulation

Sealant/Mastic

Building 41, Floor 5 Interstitial

Non‐Friable No

Damage 2‐4%

Chrysotile

B41‐DS1‐01

White Duct Insulation

Sealant/Mastic

Building 41, 6‐7 Interstitial Space

Non‐Friable Damaged 3‐5%

Chrysotile

B41‐DS1‐04

White Duct Insulation

Sealant/Mastic

Building 41, Interstitial Spaces

Non‐Friable No

Damage 3‐5%

Chrysotile

B41‐DS1‐05

White Duct Insulation

Sealant/Mastic

Building 41, Interstitial Spaces

Non‐Friable No

Damage 3‐5%

Chrysotile

B41‐DS1‐06

White Duct Insulation

Sealant/Mastic

Building 41, Interstitial Spaces

Non‐Friable No

Damage 3‐5%

Chrysotile

B41‐DS1‐07

White Duct Insulation

Sealant/Mastic

Building 41, Interstitial Spaces

Non‐Friable No

Damage 3‐5%

Chrysotile

B41‐DS2‐02 White Duct Insulation

Sealant/Mastic On Air Handler Unit

Building 41, 5th Floor Mechanical Room

Non‐Friable No Damage

3‐5% Chrysotile

B41‐DS2‐04 AHU Insulation Sealant/Mastic

Building 41, Floor 6 Non‐Friable No Damage

3‐5% Chrysotile

B41‐DS2‐05 AHU Insulation Sealant/Mastic

Building 41, Floor 5 Non‐Friable No Damage

3‐5% Chrysotile

B41‐DS2X‐01 AHU Insulation Sealant/Mastic

Building 41, Floor 5 Non‐Friable No Damage

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

B41‐DS2X‐03 AHU Insulation Sealant/Mastic

Building 41, Floor 5 Non‐Friable No Damage

3‐5% Chrysotile

B41‐STMX‐01 Steam Insulation Sealant/Mastic

Building 41, Floor 5 Non‐Friable No Damage

3‐5% Chrysotile

B41‐STMX‐02 Steam Insulation Sealant/Mastic

Building 41, Floor 5 Non‐Friable No Damage

3‐5% Chrysotile

B41‐STMX‐03 Steam Insulation Sealant/Mastic

Building 41, Floor 5 Non‐Friable No Damage

3‐5% Chrysotile

B41‐HWS‐04 Hot Water Supply Insulation

Sealant/Mastic

Building 41, Floor 7 Penthouse

Non‐Friable No Damage

3‐5% Chrysotile

Building 41 ‐ Asbestos‐Containing Materials Inventory Summary

Quad A Mechanical Rooms

Room Number

Estimated Quantity Mechanical Room Pipe

Insulation Sealant/Mastics/Mastics at Air Handler Unit

(AHU)

Estimated Quantity Air Handler Unit (AHU)

Sealant/Mastic/Mastic on AHU Duct Insulation

Other Category Material

BA‐114 40 lin. ft. None ID Category II Non‐ Friable

1A‐127 20 lin. ft. 200 sq. ft. Category II Non‐ Friable

2A‐112 20 lin. ft. 150 sq. ft. Category II Non‐ Friable

3A‐130 20 lin. ft. 150 sq. ft. Category II Non‐ Friable

4A‐112 20 lin. ft. 150 sq. ft. Category II Non‐ Friable

5A‐136 20 lin. ft. Non suspect Category II Non‐ Friable

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

Room Number

Estimated Quantity Mechanical Room Pipe

Insulation Sealant/Mastics/Mastics at Air Handler Unit

(AHU)

Estimated Quantity Air Handler Unit (AHU)

Sealant/Mastic/Mastic on AHU Duct Insulation

Other Category Material

6A‐113 20 lin. ft. 150 sq. ft. Category II Non‐

Quad B Mechanical Rooms

Number

Estimated Quantity Mechanical Room Pipe

Insulation Sealant/Mastics/Mastics at Air Handler Unit

(AHU)

Estimated Quantity Air Handler Unit (AHU)

Sealant/Mastic/Mastic on AHU Duct Insulation

Other Category Material

BB‐111 36 lin. ft. 200 sq. ft. 200 sq. ft. tank insulation

Sealant/Mastic

Category II Non‐ Friable

1B‐117 40 lin. ft. 400 sq. ft. Category II Non‐ Friable

2B‐117 Non suspect Non suspect Category II Non‐ Friable

3B‐127 15 lin. ft. 200 sq. ft. Category II Non‐ Friable

4B‐117 30 lin. ft. 200 sq. ft. Category II Non‐ Friable

5B‐161 25 lin. ft. 200 sq. ft. Category II Non‐ Friable

B-141A HW 150 lin. ft.

CHW 150 lin. ft.

Dom W 3 lin. ft.

Category II Non‐

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

Estimated Quantity Mechanical Room Pipe

Insulation Sealant/Mastics/Mastics at Air Handler Unit

(AHU)

Estimated Quantity Air Handler Unit (AHU)

Sealant/Mastic/Mastic on AHU Duct Insulation

Other Category Material

B-141 HW 100 lin. ft.

CHW 100 lin. ft.

Category II Non‐

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

Quad C Mechanical Rooms

Number

Estimated Quantity Mechanical Room Pipe

Insulation Sealant/Mastics/Mastics at Air Handler Unit

(AHU)

Estimated Quantity Air Handler Unit (AHU)

Sealant/Mastic/Mastic on AHU Duct Insulation

Other Category Material

BB‐111 36 lin. ft. 200 sq. ft. 200 sq. ft. tank insulation

Sealant/Mastic

Category II Non‐Friable

BC-112 70 lin. ft. None ID Category II Non‐Friable

1C-111 30 lin. ft. 350 sq. ft. Category II Non‐Friable

2C-167 8 lin. ft. 350 sq. ft. Category II Non‐Friable

3C-119A 90 lin. ft. 400 sq. ft. Category II Non‐Friable

4C-136 15 lin. ft. 200 sq. ft. Category II Non‐Friable

5C-157 140 lin. ft. 450 sq. ft. CHW 50’, HW 60’, STM 30’

Category II Non‐Friable

Quad D Mechanical Rooms

Room

Number

Estimated Quantity Mechanical Room Pipe

Insulation Sealant/Mastics/Mastics at Air Handler Unit

(AHU)

Estimated Quantity Air Handler Unit (AHU)

Sealant/Mastic/Mastic on AHU Duct Insulation

Other Category Material

BD-121 70 lin. ft. 500 sq. ft. Category II Non‐ Friable

1D-112 12 lin. ft. 250 sq. ft. Category II Non‐

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

Estimated Quantity Mechanical Room Pipe

Insulation Sealant/Mastics/Mastics at Air Handler Unit

(AHU)

Estimated Quantity Air Handler Unit (AHU)

Sealant/Mastic/Mastic on AHU Duct Insulation

Other Category Material

2D-126 15 lin. ft. 300 sq. ft. Category II Non‐ Friable

3D-127 20 lin. ft. 150 sq. ft. Category II Non‐ Friable

4D-140 20 lin. ft. 150 sq. ft. Category II Non‐ Friable

5D-122 20 lin. ft. 150 sq. ft. Category II Non‐ Friable

6D-127 12 lin. ft. 200 sq. ft. Category II Non‐

Building 41 Interstitial Spaces

Interstitial Space Estimated Quantity Sealant/Mastics/Mastics HVAC

Duct Insulation

Estimated Quantity Sealant/Mastic/Mastic on Drain Pipe Insulation

Category Material

Basement ‐ First 15,500 sq ft 750 lin ft Category II Non‐ Friable

First – Second 15,500 sq ft 750 lin ft Category II Non‐ Friable

Second – Third 15,500 sq ft 750 lin ft Category II Non‐ Friable

Third – Fourth 15,500 sq ft 750 lin ft Category II Non‐ Friable

Fourth – Fifth 15,500 sq ft 750 lin ft Category II Non‐ Friable

Fifth‐Sixth 7,500 sq ft 500 lin ft Category II Non‐

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

Sixth – Seventh 1,500 sq ft 150 lin ft Category II Non‐

Inspection Notes:

MECX sampled and determined the pipe risers relating to the mechanical systems located within the mechanical rooms were not found to contain asbestos.

Asbestos containing thermal system pipe insulation was determined to be associated with the Sealant/Mastic applied to the mechanical system piping at the location where the piping systems connect directly to the air handling units.

Asbestos containing air handler insulation Sealant/Mastic was determined through sampling to be associated with the return air side of the air handling units. It appears coil and supply side of the air handler units are a different homogeneous area and do not contain asbestos.

Conclusions

Based upon the results of this inspection, the materials identified above should be considered as asbestos containing. MECX recommends that damaged asbestos containing materials be removed. MECX recommends that the condition of the remaining asbestos‐containing materials be monitored. If the asbestos containing materials in the unaffected areas become damaged, or if they will be disturbed during renovations, then the materials should be abated in accordance with applicable federal and state laws.

According to NESHAPS 40 CFR 61 Subpart M, 61.145, friable or potentially friable ACM which will be disturbed, or has the potential to be disturbed during renovation, must be removed. A licensed asbestos consultant should be consulted prior to any renovation operations in a building or other structure containing ACM. The AQB requires that Asbestos Contractors must comply with the remediation and 40‐hour contractor supervisor training requirements of the Asbestos NESHAP, 40 CFR 61 Subpart M. Asbestos contractors are required to have a GB‐98 general contractor’s license and a GS‐29 special contractor’s license from the Construction Industries Division.

The quantities of asbestos‐containing materials are estimates made at the time of sampling and should be used by the NMVAHCS for limited budgeting purposes only. These quantities are estimates only and should be verified by all parties, including any contractors bidding the removal to determine exact square footage’s and the accessibility of the specific materials. No mechanical as–build drawings were provided to formulate the estimate of TSI. The TSI quantities noted in the tables are total linear feet regardless of the outside diameter (OD) or systems to which it is supporting.

The specific locations of all TSI was not determined due to significant restrictions, which are as follows:

Piping enclosed inside walls, Ceiling panel support/tie wires, Firewall extensions between floors throughout the plenums, and

The need to avoid creating/releasing dust inside the hospital.

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

Material descriptions and locations are presented in Appendix A. Recommendations concerning the ACMs identified, if any, are based on condition, friability, and potential for disturbance.

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

3.2 BUILDING 10

Building 10 ‐ Suspect Asbestos‐Containing Materials

The following table lists the HA suspect asbestos‐containing materials identified and sampled within Building 10.

1. 12"x12" Beige Floor Tile, Mottled & Yellow Mastic

2. 2'x4' Ceiling Tile With 2'x2' Recess Pattern

3. Steam Hard Fittings & Elbows, White Powder

4. Low Pressure Steam Hard Elbows & Fittings, White Powder

5. Gray Pebbly Sheet Vinyl 6. Red Fire Stop

7. Medium Pressure Steam, New

8. Chilled Water Sealant/Mastic, New

9. Window Caulk

10. Stucco & Plaster 11. Blue Sheet Vinyl 12. Lab Counter Top

13. White 2'x4' Ceiling Tile 14. Brown Cove Base Mastic 15. White Joint Compound

16. Multi‐Layered Floor Tile Elevator Floor

17. Heating (Hot) Water Insulation Mastic

18. Domestic Water Insulation Sealant/Mastic

19. Gray Metal Duct Seam Sealant/Mastic

20. White Chilled Water Supply Sealant/Mastic

21. White Chilled Water Return Sealant/Mastic

22. White Medium Pressure Steam Sealant/Mastic

23. 12"x12" Beige Floor Tile, Mottled & Yellow Mastic Residual Black Mastic

24. Domestic Water Insulation Mastic

Building 10 ‐ Samples Reported as Asbestos‐Containing

Sample No. Material Description Sample Location Friability Condition % Asbestos

B10‐STM‐01 Steam Hard Fittings & Elbows, White

Powder

Building 10, Basement, Mechanical Room &

Crawl Space

Friable No Damage

1‐2% Amosite

B10‐STM‐02 Steam Hard Fittings & Elbows, White

Powder

Building 10, Basement, Mechanical Room &

Crawl Space

Friable No Damage

1‐2% Amosite 1‐2%

Chrysotile

B10‐STM‐03 Steam Hard Fittings & Elbows, White

Powder

Building 10, Basement, Mechanical Room &

Crawl Space

Friable No Damage

1‐2% Amosite

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

B10‐STM‐04 Steam Hard Fittings & Elbows, White

Powder

Building 10, Basement, Mechanical Room &

Crawl Space

Friable No Damage

1‐2% Amosite

B10‐WC‐01 White Window Caulk Exterior Window Friable No Damage

<1% Chrysotile

B10‐HW‐03 Heating (Hot) Water Insulation

Sealant/Mastic

Building 10, Basement B2

Non‐Friable No Damage

3‐5% Chrysotile

B10‐CHWR‐03 White Chilled Water Return

Sealant/Mastic

Old Building 10, Penthouse

Non‐Friable No Damage

3‐5% Chrysotile

Building 10 ‐ Asbestos‐Containing Materials Inventory Summary

Material Category Estimated Quantity

Crawl Space Pipe Insulation Hard Fittings & Elbows

RACM 45 fittings/elbows

Basement Mechanical Room Heating (Hot) Water Insulation Sealant/Mastic

Cat II Non‐Friable 50 lin ft

Penthouse Mechanical Room CWR Sealant/Mastic

Cat II Non‐Friable 2 fittings/elbows

Inspection Notes:

Asbestos containing chilled water return line Sealant/Mastic located in the Penthouse of Old Building 10 is presumed to be limited to on return line with soft elbows.

Conclusions

Based upon the results of this inspection, the materials identified above should be considered as asbestos containing. MECX recommends that damaged asbestos containing materials be removed. MECX recommends that the condition of the remaining asbestos‐containing materials be monitored. If the asbestos containing materials in the unaffected areas become damaged, or if they will be disturbed during renovations, then the materials should be abated in accordance with applicable federal and state laws.

According to NESHAPS 40 CFR 61 Subpart M, 61.145, friable or potentially friable ACM which will be disturbed, or has the potential to be disturbed during renovation, must be removed. A licensed asbestos consultant should be consulted prior to any renovation operations in a building or other structure containing ACM. The AQB requires that Asbestos Contractors must comply with the remediation and 40‐hour

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM contractor supervisor training requirements of the Asbestos NESHAP, 40 CFR 61 Subpart M. Asbestos contractors are required to have a GB‐98 general contractor’s license and a GS‐29 special contractor’s license from the Construction Industries Division.

The quantities of asbestos‐containing materials are estimates made at the time of sampling and should be used by the NMVAHCS for limited budgeting purposes only. These quantities are estimates only and should be verified by all parties, including any contractors bidding the removal to determine exact square footage’s and the accessibility of the specific materials. No mechanical as–build drawings were provided to formulate the estimate of TSI. The TSI quantities noted in the tables are total linear feet regardless of the OD or systems to which it is supporting.

The specific locations of all TSI was not determined due to significant restrictions, which are as follows:

Piping enclosed inside walls, Ceiling panel support/tie wires, Firewall extensions between floors throughout the plenums, and

The need to avoid creating/releasing dust inside the hospital.

identified, if any, are based on condition, friability, and potential for disturbance

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

3.3 BUILDING 10A

Building 10A ‐ Suspect Asbestos‐Containing Materials

The following lists the HA suspect asbestos‐containing materials identified within Building 10A.

None

MECX inspected the above mentioned building for the presences of suspected asbestos containing building materials. No suspect materials were identified; therefore, no samples were collected for Building 10A.

Although this was a comprehensive asbestos survey do to the inaccessibility of some areas hidden suspect materials may exist within the building in areas such as above ceilings and in wall cavities.

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

3.4 BUILDING 42

Building 42 ‐ Suspect Asbestos‐Containing Materials

Building 42.

1. White Joint Compound 2. Generator Exhaust Insulation & Mastic

3. Heating Water, Insulation & Mastic

4. Domestic Water, Insulation & Mastic

5. Exterior Tan Stucco & Gray Plaster

6. Exterior Louver Caulk

Building 42 ‐ Samples Reported as Asbestos‐Containing

Sample No. Material Description Sample Location Friability Condition % Asbestos

B42‐GEX‐01 Generator Exhaust Insulation

Sealant/Mastic

Building 42, Generator Room

Non‐Friable No Damage

3‐5% Chrysotile

B42‐GEX‐02 Generator Exhaust Insulation

Sealant/Mastic

Building 42, Generator Room

Non‐Friable No Damage

3‐5% Chrysotile

B42‐GEX‐03 Generator Exhaust Insulation

Sealant/Mastic

Building 42, Generator Room

Non‐Friable No Damage

3‐5% Chrysotile

B42‐DW‐01 Domestic Water, Insulation

Sealant/Mastic

Building 42, Generator Room

Non‐Friable No Damage

3‐5% Chrysotile

B42‐DW‐02 Domestic Water, Insulation

Sealant/Mastic

Building 42, Generator Room

Non‐Friable No Damage

3‐5% Chrysotile

B42‐DW‐03 Domestic Water, Insulation

Sealant/Mastic

Building 42, Generator Room

Non‐Friable No Damage

3‐5% Chrysotile

3.4.3 Building 42 ‐ Asbestos‐Containing Materials Inventory Summary

Material Category Estimated Quantity

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

Generator Exhaust Insulation Sealant/Mastic

Cat II Non‐Friable 75 lin ft

Domestic Water, Insulation

Cat II Non‐Friable 10 lin ft

3.4.4 Conclusions

Based upon the results of this inspection, the materials identified above should be considered as asbestos containing. MECX recommends that damaged asbestos containing materials be removed. MECX recommends that the condition of the remaining asbestos‐containing materials be monitored. If the asbestos containing materials in the unaffected areas become damaged, or if they will be disturbed during renovations, then the materials should be abated in accordance with applicable federal and state laws.

According to NESHAPS 40 CFR 61 Subpart M, 61.145, friable or potentially friable ACM which will be disturbed, or has the potential to be disturbed during renovation, must be removed. A licensed asbestos consultant should be consulted prior to any renovation operations in a building or other structure containing ACM. The AQB requires that Asbestos Contractors must comply with the remediation and 40‐hour contractor supervisor training requirements of the Asbestos NESHAP, 40 CFR 61 Subpart M. Asbestos contractors are required to have a GB‐98 general contractor’s license and a GS‐29 special contractor’s license from the Construction Industries Division.

The quantities of asbestos‐containing materials are estimates made at the time of sampling and should be used by the NMVAHCS for limited budgeting purposes only. These quantities are estimates only and should be verified by all parties, including any contractors bidding the removal to determine exact square footage’s and the accessibility of the specific materials. No mechanical as–build drawings were provided to formulate the estimate of TSI. The TSI quantities noted in the tables are total linear feet regardless of the OD or systems to which it is supporting.

The specific locations of all TSI was not determined due to significant restrictions, which are as follows:

• Piping enclosed inside walls,

• Ceiling panel support/tie wires, and,

• Firewall extensions between floors throughout the plenums

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

3.5 BUILDING 43

Building 43 ‐ Suspect Asbestos‐Containing Materials

Building 43.

1. Boiler Feed Water Insulation & Sealant/Mastic

2. Boiler Blow Down Line Insulation & Sealant/Mastic

3. Boiler Chemical Feed Line Insulation & Sealant/Mastic

4. Steam Header Metals Plate Coating

5. Steam Header Bleed Off 6. Steam Header Sealant/Mastic

7. Boiler Feed Water Insulation & Sealant/Mastic Upper

8. Boiler Economizer Panel Gasket

9. Condensate Elbow Insulation & Sealant/Mastic

10. Condensate Tank Insulation & Sealant/Mastic

11. Domestic Water Cold Fitting Insulation and Sealant/Mastic

12. Drain Line Insulation & Sealant/Mastic

13. Hot Water Line Insulation & Sealant/Mastic

14. Low Pressure Steam Insulation & Sealant/Mastic

15. Medium Pressure Steam Insulation & Sealant/Mastic

16. Chilled Water Piping Insulation & Sealant/Mastic

17. Chilled Water Piping Insulation & Sealant/Mastic

18. Chilled Water Chemical Supply Lines Insulation & Sealant/Mastic

19. White Joint Compound 20. 2'x4' White Ceiling Tile, Specs

21. 12"x12" Beige Mottled Floor Tile & Yellow Mastic

22. Stucco & Gray Plaster 23. White Vent Piping Insulation & Sealant/Mastic

24. White Bypass Piping Insulation & Sealant/Mastic

3.5.2 Building 43 ‐ Samples Reported as Asbestos‐Containing

B43‐BFW‐02 Boiler Feed Water Insulation

Sealant/Mastic

Boiler 3 Non‐Friable Damaged 3‐5%

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

B43‐BFW‐03 Boiler Feed Water Insulation

Sealant/Mastic

Boiler 2 Non‐Friable Damaged 3‐5% Chrysotile

B43‐BFW‐04 Boiler Feed Water Insulation

Sealant/Mastic

Boiler 2 Non‐Friable Damaged 3‐5% Chrysotile

B43‐BFW‐05 Boiler Feed Water Insulation

Sealant/Mastic

Boiler 1 Non‐Friable Damaged 3‐5% Chrysotile

B43‐BDW‐03 Boiler Blow Down Line Insulation Sealant/Mastic

Center Boiler 2 Non‐Friable Damaged 3‐5% Chrysotile

B43‐CF‐03 Boiler Chemical Feed Line Insulation Sealant/Mastic

Boiler 1 Non‐Friable Damaged 2‐4 % Chrysotile

B43‐PLC‐01 Steam Header Metals Plate Coating

Steam Header Non‐Friable Damaged 2‐3% Chrysotile

B43‐SHB‐01 Steam Header Bleed Off

Steam Header Non‐Friable Damaged 2‐4% Chrysotile

B43‐BFWT‐01 Boiler Feed Water Insulation

Sealant/Mastic

Boiler 1 Non‐Friable No Damage

3‐5% Chrysotile

B43‐EPG‐01 Boiler Economizer Panel Gasket

Boiler 1 Non‐Friable No Damage

95 % Chrysotile

B43‐CON‐01 White Condensate Elbow/Fitting Insulation

Sealant/Mastic

Condensate Line Adjacent To Stairs

Non‐Friable No Damage

3‐5% Chrysotile

B43‐CON‐04 White Condensate Elbow Insulation Sealant/Mastic

Condensate Line Adjacent To Stairs

Non‐Friable Damaged

3‐5% Chrysotile

B43‐CON‐05 White Condensate Elbow Insulation Sealant/Mastic

Condensate Line Adjacent To Stairs

Non‐Friable Damaged

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

B43‐CTNK‐02 Condensate Tank Insulation

Sealant/Mastic

Basement Condensate Tank

Non‐Friable No

Damage

3‐5% Chrysotile

B43‐LPS‐01 Low Pressure Steam Insulation

Sealant/Mastic

Mezzanine Low Pressure Steam Line

Non‐Friable No

Damage

3‐5% Chrysotile

B43‐MPS‐01 Medium Pressure Steam Insulation Sealant/Mastic

Mezzanine Medium Pressure Steam Line

Non‐Friable No

Damage

3‐5% Chrysotile

B43‐MPS‐02 Medium Pressure Steam Insulation Sealant/Mastic

Mezzanine Medium Pressure Steam Line

Non‐Friable No

Damage

3‐5% Chrysotile

B43‐VNT‐01 White Vent Piping Insulation

Sealant/Mastic

Vent Lines Non‐Friable No

Damage

3‐5% Chrysotile

B43‐VNT‐02 White Vent Piping Insulation

Sealant/Mastic

Vent Lines Non‐Friable No

Damage

3‐5% Chrysotile

B43‐VNT‐03 White Vent Piping Insulation

Sealant/Mastic

Vent Lines Non‐Friable No

Damage

3‐5% Chrysotile

B43‐VNT‐04 White Vent Piping Insulation

Sealant/Mastic

Vent Lines Non‐Friable No

Damage

3‐5% Chrysotile

B43‐LPS‐02 Low Pressure Steam Insulation

Sealant/Mastic

Mezzanine Low Pressure Steam Line

Non‐Friable No

Damage

3‐5% Chrysotile

B43‐LPS‐03 Low Pressure Steam Insulation

Sealant/Mastic

Mezzanine Low Pressure Steam Line

Non‐Friable No

Damage

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

3.5.3 Building 43 ‐ Asbestos‐Containing Materials Inventory Summary

Material Category Estimated Quantity

Boiler Feed Water Sealant/Mastic Cat II Non‐Friable 60 lin ft

Boiler Blow Down Line Sealant/Mastic Cat II Non‐Friable Boiler 2

10 lin ft

Boiler Chemical Feed Line Sealant/Mastic

Cat II Non‐Friable Boiler 1

10 lin ft

Condensate Elbow/Fitting Sealant/Mastic

Cat II Non‐Friable 150 lin ft

Condensate Tank Sealant/Mastic Cat II Non‐Friable Basement

100 sq ft

Low Pressure Steam Sealant/Mastic Cat II Non‐Friable Mezzanine

75 lin ft

Medium Pressure Steam Sealant/Mastic Cat II Non‐Friable Mezzanine

75 lin ft

White Vent Piping Sealant/Mastic Cat II Non‐Friable 10 lin ft

Steam Header Metals Plate Coating Cat II Non‐Friable 2 sq ft

Steam Header Bleed Off Cat II Non‐Friable 1 fitting/elbow

Boiler Economizer Panel Gasket Cat I Boiler Gaskets/Seals

3.5.4 Conclusions

Based upon the results of this inspection, the materials identified above should be considered as asbestos containing. MECX recommends that damaged asbestos containing materials be removed. MECX recommends that the condition of the remaining asbestos‐containing materials be monitored. If the asbestos containing materials in the unaffected areas become damaged, or if they will be disturbed during renovations, then the materials should be abated in accordance with applicable federal and state laws.

According to NESHAPS 40 CFR 61 Subpart M, 61.145, friable or potentially friable ACM which will be disturbed, or has the potential to be disturbed during renovation, must be removed. A licensed asbestos consultant should be consulted prior to any renovation operations in a building or other structure containing ACM. The AQB requires that Asbestos Contractors must comply with the remediation and 40‐hour contractor supervisor training requirements of the Asbestos NESHAP, 40 CFR 61 Subpart M. Asbestos

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM contractors are required to have a GB‐98 general contractor’s license and a GS‐29 special contractor’s license from the Construction Industries Division.

The quantities of asbestos‐containing materials are estimates made at the time of sampling and should be used by the NMVAHCS for limited budgeting purposes only. These quantities are estimates only and should be verified by all parties, including any contractors bidding the removal to determine exact square footage’s and the accessibility of the specific materials. No mechanical as–build drawings were provided to formulate the estimate of TSI. The TSI quantities noted in the tables are total linear feet regardless of the OD or systems to which it is supporting.

The specific locations of all TSI was not determined due to significant restrictions, which are as follows:

• Piping enclosed inside walls,

• Ceiling panel support/tie wires, and,

• Firewall extensions between floors throughout the plenums

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

3.6 BUILDING 43A

Building 43A ‐ Suspect Asbestos‐Containing Materials

Building 43A.

1. White Pipe Sealant/Mastic Mastic

2. Stucco & Gray Plaster

Building 43A ‐ Samples Reported as Asbestos‐Containing

Using PLM, the laboratory analyzed samples in the above list. Samples of the following materials were found to contain greater than one percent (1%) asbestos as follows:

None

3.6.3 Building 43A ‐ Asbestos‐Containing Materials Inventory Summary

None

None of the samples of the above referenced suspect materials analyzed by Polarized Light Microscopy (PLM) using the Environmental Protection Agency EPA 600 method by a fully qualified third‐party laboratory were reported to contain asbestos above 1.0 %. Although this was a comprehensive asbestos survey do to the inaccessibility of some areas hidden suspect materials may exist within the building in areas such as above ceilings and in wall cavities.

Z:\Projects\1200s ‐ Projects\1244‐VA Hospitals\019‐VISN 18 Albuqurqe, NM\NM VA ACM\Final Working Folder\NM VA ACM

3.7 BUILDING 45

Building 45 ‐ Suspect Asbestos‐Containing Materials

Building 45.

Specks & Yellow Mastic

2. 12"x12" Light Green, Mottled Floor Tile & Yellow Mastic

3. White Joint Compound

4. 12"x12" Gray, Mottled Floor Tile & Yellow Mastic

5. Green Cove Base & Yellow Mastic

6. White 2'x4' Ceiling Tile

7. Medium Pressure Steam Insulation & Sealant/Mastic

8. Condensate Lines Insulation & Sealant/Mastic

9. Red Metal Duct Seam Sealant/Mastic

10. White Duct Insulation Sealant/Mastic

11. White Metal Duct Seam Sealant/Mastic

12. Red Fire Stop

13. Gray Metal Duct Seam Sealant/Mastic

14. Hot Water Insulation & Sealant/Mastic

15. Chilled Water System Insulation & Sealant/Mastic

16. White Metal Duct Seam Sealant/Mastic

17. Tan Stucco & Gray Plaster 18. 12"x12" Beige Floor Tile, Inclusions & Yellow Mastic

3.7.2 Building 45 ‐ Samples Reported as Asbestos‐Containing

Using PLM, the laboratory analyzed samples in the above list. Samples of the following materials were found to contain greater than one percent (1%) asbestos as follows:

None

3.7.3 Building 45 ‐ Asbestos‐Containing Materials Inventory Summary

None

None of the samples of the above referenced suspect materials analyzed by Polarized Light Microscopy (PLM) using the Environmental Protection Agency EPA 600 method by a fully qualified third‐party laboratory were reported to contain asbestos above 1.0 %.